Electric DD321
Electric DD321
Electric DD321
Table of Contents
1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1
1.2. General .................................................................................................. 1
1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals
1.2. General
Electric system consists of the main switchgear (MP), and the devices,
sensors, and the control and the indicator light panel connected to it. The
electric control of the hydraulic system is dealt with in separate instruction
manuals.
In the electric circuits of the electric motors, the working lights, the cabin
heater, and the socket outlets the voltage is over 100 VAC. The sensors,
the switches, the indicator lights, and the electric control of hydraulics use
reduced voltage (24 VDC).
Sandvik manufactures the electric system of the rig to conform to the
standard EN 791.
The power supply must be dimensioned to guarantee trouble free operation
at full power and when electric motors are started. The power supply
transformer or the generator, and the power supply cable must be rated to
meet the rig’s power requirements.
The rig is designed to operate in a supply network that meets the
requirements in 4.3.1 of the standard EN 60204-1. The power requirement,
the frequency, and the operating voltage are given on the panel at themain
switch. The fluctuation of the rated voltage must not exceed ±10 % at the
main switchgear, whether idling or operating at full power.
Sandvik defines the maximum voltage drop in the power supply cable to
below 3 %.
If you suspect a fault in any electric device, cut off the voltage at
themain switch, and call in an electricianwho is specialized in the
electric systems of the equipment you are using.
Even when you are working on dead equipment, use good insulated
tools. This is a simple method to improve your own safety.
• Main switchgear contains the main switch, the motor controls, and the
power supply system for the electric devices.
3.1.1. Lay-outs
2P101/
2P128
2P100
OPTION
OPTION
55172786
39053178
2
2
1P101/
1P128
1P100
OPTION
55172786
39053178
1
P400
39002818
3-PH EFS
OPTION
F291
F333
P410
PH OR CABIN
F253
OPTION
F252
F251
MAIN SWITCH
Hz
F313
Q100
kW
F312
V
F311
OPTION
S301
OPTION
S300
F451.6 F454.2
F451.5 F454.1
F451.4 OPTION F453.5 OPTION
F333
PH OR CABIN
F253
OPTION
F252
F251
F312
F311
X28
3-PH EFS
OPTION
F291
Q100
P410
(2P128)
2P101
X41
(1P128)
1P101
X24
X63
F454.6
F454.5
F454.4
F454.3
F454.2
F454.1
F453.5 OPTION
P400
F453.4 OPTION
F453.3 OPTION
F453.2 OPTION
F453.1 OPTION
2P100
F452.5
F452.4
F452.3
1P100
F452.2
F452.1
F451.6
F451.5
F451.4
OPTION
S300
F451.3 OPTION
F451.2
F451.1
F450
HPP DELTA
CONTACTOR
HPP STAR
1K105
1K104
POWERBACK START
POWERBACK STOP
RELAY (OPTION)
RELAY (OPTION)
RELAY (OPTION)
START / DELTA
DL-app. components
DL-app. components
1K103, K310, K311
K903
1F100
CONTACTOR
1K100
HPP MAIN
K902
K901
K310
K311
1K103
131
130
129
128
2-BOOM
OPTION
127
126
2K105/
2X110
1K105
125
2-BOOM
OPTION
K240
124
123
122
121
131
130
129
128
2-BOOM
OPTION
1X110
127
2F100
126
125
124
123
122
121
17
16
15
1K104
2K104
15
2-BOOM
OPTION
15
14
13
12
223 CDE (DS-OPTION)
222 CDE (DS-OPTION)
221 CDE (DS-OPTION)
189
20x42
188
1F100
187
X160(X182 DS-rigs)
186
1K100
2K100
185
2-BOOM
OPTION
184
X110
184
183
182
181
176
175
174
173
172
172
POS. 172
2-BOOM 172
OIL LASER LIGHTS 171
LEVEL DL DL LIGHTS LIGHTS 2-BOOM OPTION 171
LIGHTS LIGHTS LIGHTS OPTION
171
171
156
155
2K112
1K112
154
153
F454.7
F454.6
F454.5
F454.4
F454.3
F454.2
F454.1
F453.5
F453.4
F453.3
F453.2
F453.1
F452.5
F452.4
F452.3
F452.2
F452.1
F451.6
F451.6
F451.5
F451.4
F451.3
F451.2
F451.1
X63
X24
F450
F450
X28
152
164
163
162
161
451
451
451
T310
151
296
OPTION
X291
295
3PH.
294
X112
293
X450
292
K602 2K101 1K101
K327K405 K404 K403 K402 K401 K400
291
X101
V466
Q100
V548
V547
2V529 TPC OPTION
1V529 TPC OPTION
2V249 THC OPTION
1V249 THC OPTION
V400
592 TRS/UK OPTION
X62
X41
591 TRS/UK OPTION
590 TRS/UK OPTION
587 UK OPTION
586 TPC OPTION
585 TPC OPTION
584 TPC OPTION
583 BEMA OPTION
582 SOLO OPTION
581 SOLO OPTION
580
577 BEMA OPTION
576 BEMA OPTION
575 BEMA OPTION
573
573
572 SOLO OPTION
571 THC OPTION
ON
CONTROL
X36
564 SOLO OPTION
563
562
MULTI TIMER UNIT
561
OPTION
560 SOLO OPTION
559 SOLO OPTION
558
558
556
555
F320
24VDC
554
553
ALTERNATIVES
A100
OPTION
THC MOV.PREV.
550
THC
K465
546
TCH / TPC
A420
545
OPTION
544
544
OPTION CONTROL
K424
MAIN
543
WATER PUMP
542
541 CABIN OPTION
F230
THC
538
538
537
A
DL-app.
536
K79
535
X44
X43
534
533
532
K230
532
COMPRESSOR
X500
530
F240
530
K78 E/S STOP 529
529
K231 WP 528
COMPR.
K240
HEATER
OPTION
522
K480
1PH
521
PILOT OPTION
X50
X42
520
520
K461 TRR OPTION 520
3PH SOCKET 1PH SOCKET
519
518
OPTION
K430
K320 517
516
OPTION
515
3. PH
F290
515
515
514
F296
OPTION
514
K290
OA2
OPTION
513
512
511
T250
X120/X74
510
509
508
507
X23
K296
506
OPTION
505
OA2
504
504
504
503
OPTION
F295
502
OA1
502
K295
OPTION
501
OA1
501
501
501
501
501
501
OPTION
T290
501
EXT.
PUMP
501
501
501
501
501
501
501
K491 K492 K493
DS-app. components
DUST EXTRACTOR
F220, K220 CEMENT
K659 DL-app.
CEMENT DUST
EXTRACTOR
DS-OPTION
EXTERNAL PUMP OPTION
K444
F220
K291
CEMENT DUST
EXTRACTOR
DS-OPTION
K220
T490
R490
1K105
2K105
131
OPTION
130
129
128
OPTION
2X110
2F100
OPTION
127
126
125
124
123
122
121
131
130
129
128
1X110
127
1K104
2K104
126
OPTION
125
124
123
122
121
189
188
1F100
187
186
185
184
184
1K100
2K100
OPTION
183
182
181
180
179
X110
178
177
176
175
174
173
172
172
Q100
172
172
171
171
171
171
156
155
154
153
152
151
17
16
15
LIGHT OPT.
15
REV CAM
2K101 K445 K471 K405
15
14
CONTROL
230VAC
F310
13
12
POWER
ON
OPTION
TCH
24VDC
F320
2-BOOM
OPTION
X101
2-BOOM
OPTION
2K112
T250
V446
F230
2V529
1V529
WP
1K101
V400
595
594
593
592
591
1K112 590
589
588
587
586
585
584
579
578
571
569
F240
568
COMPR.
567
OPTION
296
563
X291
295
562
294
293 558
292 558
291 557
556
451 555
554
451 553
451 V548
OPTION
F250
V547
1PH
F454.4 546
F454.3 545
F454.2 544
F454.2
A420
F454.1 544
F453.5 543
F453.4 542
F453.3 541
F453.2 540
F290
OPTION
F453.1 539
F452.5
X450
3PH
538
F452.4
THC MOV.PREV.
538
F452.3 537
F452.3 536
OPTION
F452.2 535
K465
F452.1 534
F451.6 533
F451.6 532
F451.5 532
F451.4 531
K320 F451.2 530
X500
ALTERNATIVES
F451.1 530
TCH / TPC
F450 529
K480 OPTION X112
162
161
529
528
HYDR.OIL 527
K77.2 OPTION K602 LEVEL 527
526
K50 OPTION
K404 LIGHT 525
K290
524
OPTION
523
K493 OPTION 2K447 THC.OPT. 522
K403 LIGHT 522
1K447 THC.OPT. 521
OPTION OPTION
K491 K492
520
520
K402 LIGHT 520
OPTION
TPC MOV.PREV.
K296
K466
519
OA2
T310
518
OPTION
517
K401 LIGHT 516
K465
515
515
K400 LIGHT 515
OPTION
K295
514
OA1
514
513
K230
512
K444
OPTION
511
WP
510
F295
OPTION
509
508
OA
507
506
COMPR.
505
K240
ALTERNATIVES
504
504
COMP.CONT.
EMG.STOP
504
WP.CONT.
K291
CONTROL
CONTROL
OPTION
EMG.STOP
503
CONTROL
503
MAIN
A100 502
1PH SOCKET HEATER
502
K451
OPT.
501
MULTI TIMER UNIT 501
OPTION
F296
501
501
OA
501
501
501
OPTION
K430
501
OPTION
501
T490
501
501
501
501
K395 OPT.
K231
K241
K424
501
T290
K78
K77
501
K396 OPT. OPTION 501
501
501
501
501
501
501
X502
+ + - -
A410
N L PE
DC/DC CONVERTER FOR
TELEOPERATION
543
X510
542
OPTION
A450
172
171
K425
SUPPLY BOOSTER
DATA TRANSFER
OUT
C100
OPTION
IN
K425
K461 OPT.
451
X451 451
451
501
501
X501 544
544
544
171
172
X510
A410
+ + - -
N L PE
3.1.3. Switches
3.1.4. Gauges
Adjustments
Reset the protective switches to position I only when the main switch is in
the 0 position, if the drill rig is connected to the power supply network.
3.1.6. Transformers
1 2
IN 0 CH.
I/O Symbol Description Normal state*
0 S422 Water pressure control 0
1 S421 Air pressure control 0
2 S420 Hydraulic oil level control 1
Water pump auto/manual
3 S501 1
use
Water pump manual use
4 S501 0
(start)
Compressor control auto/
5 S502 1
manual use
Compressor manual use
6 S502 0
(start)
7 S505 Pressure switches reset 1
Double booster pump use
8 S507 0
(optional)
9 HP_RUN Hydraulic pump running 1
Water pump / compressor
10 Overload 1
overload
11 Oil_hot Hydraulic oil hot 0
COM 0 VDC -
IN 1 CH.
I/O Symbol Description Normal state*
Pressure switch by pass
0 SH520 0
(power)
1 boom rotation and/or
1 1JB102 1
percussion on (only THC) **
2 SLCU SLU oil level low 0
DL-series identification (only
3 SOLO 1
DL)
2 boom rotation and/or
4 2JB102 percussion on (only 2 boom 1
THC) **
3 boom rotation and/or
5 3JB102 percussion on (only 3 boom 1
THC) **
In the table, normal state means a state where the powerpack(s), drilling,
water pump and compressor are on and no faults are active. When the
input or output is 0, the voltage is 0 volts. When the input or output is 1, the
voltage is 24 VDC.
IN 1 CH 1, IN 1 CH 4 and IN 1 CH 5 are on only when percussion and/or
feed is on in the boom in question. OUT 101 CH 3 is on only 5 seconds at
the starting moment of any boom's percussion and/or rotation.
Note! The output leds of the multi-channel timer relay indicate the status of
the program, i.e. in order to ensure the state of the output, it must be
measured directly from the connector.
4.2.2. Compressor
For resetting the pressure sensors, button S505 is on the SW panel in the
cabin or safety canopy.
The rig is equipped with pressure switches for water pressure and air
pressure. The pressure control functions are activated when one or more
power packs are started (input 00.09 on). If the water pump is used
separately, water pressure control becomes activated (air pressure control
is not activated when only the compressor is used). The delays for water
pressure control and air pressure control are four and 10 seconds,
respectively. These time parameters can be adjusted with the power logic
adjustment screws without changes to software settings (for WP value, the
range is 4–24 seconds (recommendation: 4 s), and for the C value the
range is 10–30 seconds (recommendation: 10 s); i.e., the WP and C
pressure control delays are set to the factory values when the adjustment
screws are in their zero positions).
If the water pressure is below the limit set (for over 4 s), the water pump is
stopped (output 101.00 off), or, if the air pressure is below the set limit (for
over 10 s), automatic drilling is stopped (output 100.05 on). Stopping
automatic drilling means that the power packs remain on but on a
hydraulically controlled rig the drilling joysticks are centralized and on an
electrically controlled rig automatic drilling is disabled. Drilling functions can
be used temporarily by using manual operation (also before resetting of the
pressure sensors).
On the QN panel, the "low water pressure" indicator light (H601) (output
100.02 on) or "low air pressure" indicator light (H609) is lit and remains on
(output 100.03 on). The fault is stored in the memory and is reset with the
pressure control reset button (S505) (input 00.07 momentarily off). Both
faults are reset with the pressure sensor reset button (S505) (input 00.07)
on the SW panel.
If the fault is caused by low water pressure and fault duration exceeds one
minute, the water pump is also stopped and resetting the fault does not
start the water pump even if the power packs are on and the water pump
operation switch is in the "automatic" position. Pressing the reset button
enables restarting the water pump by setting the water pump operation
switch to the "start" position. After the water pump is started, also automatic
drilling is enabled.
From the moment the water pump is started, the control time for stopping
the water pump is one minute and its fault time is four seconds.
The water pressure fault indicator light is switched off after resetting if the
fault duration reaches four seconds. If the water pressure fault duration is
one minute, the indicator light turns off only after resetting and starting. The
air pressure fault indicator light always turns off after resetting.
If drilling is performed without using the water pump and the water pressure
is not sufficient, the fault indicator light is lit (output 100.02) and automatic
drilling is stopped (output 100.05 on). After resetting, automatic drilling can
be continued without starting of the water pump.
If drilling is performed without using the compressor and the air pressure is
not sufficient, the fault indicator light is lit (output 100.03) and automatic
drilling is stopped (output 100.05 on). After resetting, automatic drilling can
be continued without starting of the compressor.
If the water pump is used without the power pack(s) running and the water
pressure is not sufficient (for over one minute), the water pump restarts
only after resetting of the pressure sensors and momentarily setting the
water pump operation switch to the "start" position. If only the compressor
is used, air pressure control is not active and no actions are required.
If the pressure control reset button is pressed and held for more than 30
seconds, the software stops the drilling and power packs.
Note: Output 100.05 is activated if the water or air pressure is too low. On
hydraulically controlled rigs, output 100.05 controls relay K445, and for
other rigs it goes to the drilling control system. Also, any stabilizer pressure
control and SLU flow control are located on the same line after output
010.05 and relay K445 to control automatic drilling.
Oil level control (input 00.02) is always active when the power is on. After
the level control is activated, the level switch has a delay of three seconds
to prevent false alarms caused by small changes in the oil level (splashing).
If the oil level remains below the level switch point for over three seconds
(input 00.02 off), the power packs stop (output 100.07 off). The "low oil
level" indicator light (H602) on the QN panel is switched on and remains lit
(output 100.04 on). The fault is stored in the memory, and it is reset with
the pressure control reset button (S505) on the SW panel. Resetting the
fault does not start the motors.
If the oil temperature exceeds 75 °C (input 00.11 goes on), the power
packs stop (output 100.07 goes off) and the "high oil temperature" indicator
light (H610) on the QN panel turns on. The fault is cleared when the
temperature falls below 75 °C. On this display, the limits for stopping the rig
and bypassing the filter monitoring with cold oil are 75 °C and 30 °C,
respectively. The rig has a hydraulic oil temperature gauge in the cabin.
DANGER
ELECTRICAL HAZARD!
Failure to strictly follow instructions will lead to severe injury and/or
death and/or property damage.
Work on electrical equipment or devices is to be performed only by
persons with the expertise and qualifications required by the
authorities, or under the supervision of a person meeting these
requirements.
Fuses and the circuit breakers are protecting the wires and electrical
components against overheat and fire in case of overload and short circuit.
Breaker tripping or fuse burn is a sign of failure. Before resetting the
breaker or replacing the fuse the failure must be repaired. The original fuse
size and type must be used. Never replace the fuse with a fuse having
higher ampere value than the original.
Note that parts of the light may be hot after use, so allow it to cool before
commencing repair work.
The bulbs of gas-discharge lamps are gas-filled, so handle with care. Use
gloves and safety glasses.
Do not touch the lamp holder or the glass part of the bulb when carrying out
the replacement.
Use proper servicing stands when changing the light bulbs.
5.1.2. Checking the operation of the emergency stop devices
Check the operation of the emergency stop devices while the power pack
and/or diesel engine is running, by using each emergency stop device in
turn. When an emergency stop function is activated, the power pack and
diesel engine must stop. At the same time, the indicator light (H614) on the
QN panel must come on and remain on until the emergency stop device is
reset.
5.1.3. Checking the electric cabinets and connection boxes
Visually check that the doors and fuse hatches are closed and that the
cabinet with its protruding components is intact.
Check the electric boxes subjected to moisture, and dry them if necessary.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.
All damaged or broken components must be replaced.
5.1.4. Checking the electric cables and harnesses
Visually check that the cable sheaths and sheath connectors are intact.
Also check that the cable clamps are in proper condition.
All damaged or broken components must be replaced.
5.1.6. Checking the operation of the drilling module movement prevention switches (if
equipped)
5. Test drilling functions prevention, use rock drill rotation. Ensure that rock
drill rotation has stopped. Try to restart rock drill rotation
counterclockwise. Ensure that rock drill rotation does not start.
6. Ensure that all boom 1 (left boom) movements have been prevented by
activating the controls.
7. Turn the left drilling module movement prevention switch (SH292) to
"Movement prevention OFF" position.
DANGER
ELECTRICAL HAZARD!
Failure to strictly follow instructions will lead to severe injury and/or
death and/or property damage.
Work on electrical equipment or devices is to be performed only by
persons with the expertise and qualifications required by the
authorities, or under the supervision of a person meeting these
requirements.
Make sure that the instructions set forth below are read and
understood before any electric system maintenance.
Components:
• slip ring unit
• main cabinet (main switch, motor contactors and breakers, transformers)
• electric motors
• sockets
• cabin heater
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.
Components:
• battery
• battery isolation switch and breaker
• diesel engine starter motor and generator
• glow plugs
• driving panel.
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.
6.1.4. Checking control system
Components:
• solenoid valve connections.
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.
Check the operation of the fault current protector switch in the main
switchgear door. Repair/replace the switch if necessary.
6.1.6. Checking the condition of the power supply cable
Pull the power supply cable out and check it for wear, cuts and overheating/
ageing.
The use of machine is prohibited if the cable is damaged. Replace
damaged cable immediately.
6.1.7. Checking the water drainage holes
Check that the water drainage holes are open. Open the drainage holes if
necessary.
DANGER
ELECTRICAL HAZARD!
Electric shock will cause death or severe injury.
Ensure that all the devices are in proper condition before cleaning.
Do not clean damaged or broken devices.
1. Switch off the main power and unplug the machine from a power source
before cleaning.
2. Clean devices more frequently than at the specified interval, if required.
Devices cleaned using water:
• cables and harnesses
• solenoid valve connections
When cleaning using water, flush components with water. Do not use
high-pressure washer.
Devices cleaned using compressed air or anti-static (ESD) brush:
• slip ring unit
• main cabinet (main switch, motor contactors and breakers)
• electric motors
• sockets
• cabin heater
• battery
• battery isolation switch and breaker
• diesel engine starter motor and generator
• glow plugs
When cleaning using compressed air or anti-static (ESD) brush, blow or
brush dust and debris off the components carefully.
Devices cleaned using cleaning cloth (or compressed air).
WARNING! HAZARD OF UNEXPECTED MACHINE MOVEMENT!
Ensure that the main power is switched off when cleaning cabin/
canopy controls and panels to avoid unexpected movement of the
machine.
• cabin/canopy controls and panels
Wipe surfaces clean with a damp cloth.
• Power supply network too weak. Check the supply voltage and the
dimensioning of the supply network, the cross-sectional area and length
of the supply cable.
• Check the control voltage.
8.1.4. Working lights do not work
WARNING
IGNORING INSTRUCTIONS HAZARD!
To avoid death or injury you MUST read, understand and follow
operator's and maintenance manuals before installing, inspecting,
operating, servicing, testing, cleaning, transporting, storing,
dismantling or disposing of the product or a part or accessory of the
product.
Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Table of Contents
1 Introduction ................................................................... 7
1.1 The Purpose of these instructions ......................................................7
1.1.1 Validity of the manuals ................................................................ 7
2 Instructions ....................................................................9
2.1 Symbols .................................................................................................9
2.2 Searching of spare part items using the schematics ........................15
2.3 Wire color abbreviations ......................................................................16
2.4 Identification marking of drawing sheets ...........................................17
2.5 Identification marking of components ................................................22
2.6 Cabling ...................................................................................................23
2.7 Can bus ..................................................................................................24
Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
1 INTRODUCTION
1.1 The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1 Validity of the manuals
This manual, and especially the safety information, is valid only if no
unauthorized changes to the product are made.
Continuing improvement and advancement of product design might have
caused changes to your product which are not included in this publication.
Note also that if a third party has made changes to the product after
delivery from the manufacturer, this publication does not include
information on these changes or their influences on the product.
Whenever a question arises regarding your product, or this manual, please
consult your local Sandvik representative for the latest available
information.
Copyright © Sandvik 7
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
8 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
2 INSTRUCTIONS
2.1 Symbols
voltmeter ammeter
+
h hour meter digital volt meter
-
operated by pressure
make contact
differential
Copyright © Sandvik 9
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
multi-position switch,
automatic return to middle three phase circuit breaker
position
terminal plug
frame earth
chassis ground
10 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
rectifier
battery charger current transformer
AC/DC converter
resolver led
Copyright © Sandvik 11
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
P 250ba r I
capacitor diode
inductor
coil fuse
winding choke
horn buzzer
12 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
cross-reference, position
from which the line
cable reel
continues / position to which
the line continues
Copyright © Sandvik 13
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
transformer (example)
14 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
4. Find the reference number(s) of the K13 relay. (The reference number is
the same for the other similar relays.)
K13's reference numbers are 64 and 65.
Copyright © Sandvik 15
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
K13 relay's part number is 888 152 09 and the relay socket's part number
is 888 153 29.
16 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
4 3 1 7 2 5 6
Copyright © Sandvik 17
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
3 2
18 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Copyright © Sandvik 19
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Cross-references
20 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
Cross-References of a component
1 Relay coil
2 Relay contacts
• Relay contacts are shown at the bottom of the sheet below the relay coil.
• The cross reference at the side of the relay contacts (below the coil) tells
the location of the actual relay contacts.
• The cross reference at the side of the actual relay contacts tells the
location of the relay coil.
Copyright © Sandvik 21
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
1 2 3
4
6
5 7
22 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
2.6 Cabling
Copyright © Sandvik 23
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols
1 3 5
24 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
www.sandvik.com
Original instructions
BG00210741 A.1 2013-09-10
Electric motor
Electric motor
Table of Contents
1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1
1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals
Oven drying
Oven drying is suitable for motors of max. 75 kW depending on the oven
size and structure. The oven temperature must be adjustable, and the heat
must affect all parts of the motor evenly. This method is recommeded for
use whenever possible.
The inspection can be carried out by measuring the cold resistance of the
temperature sensor circuit at room temperature (approx. 20 °C). The
voltage in the sensors cannot exceed 0.8 V. It is recommended that a
Wheatstone bridge be used in the measurement, and a supply voltage of
4.5 V. If the circuit has three functioning overheating protectors in a series,
the cold resistance of the circuit is 90 to 300 Ù. Measuring the warm
resistance is not necessary.
When measuring the maximum voltage of the temperature sensors and the
insulation resistance between temperature sensors and coils, the
inspection voltages specified in the DIN/VDE 0530 standard must be used,
and the wires leading away from the sensor circuit must be short-circuited.
Failure to do so will damage the sensors.
Lubricants
The original lubricant is Klüber Quiet BQ 72--72.
The bearings must be lubricated with original lubricant. When using
lubricants of other known lubricant manufacturers, ensure that the new
product corresponds fully with the original lubricant. In favourable operating
conditions the lubrication intervals may be increased, but the grease quality
must be monitored regularly.
The lubricant used for servicing must be polycarbodiimide-based, as this
enables use of the lubricant in temperatures as high as 180 °C.
Note! Spare motors must be lubricated upon initial start-up, ensuring that
all grease channels are full.
With this grease type, the motor can be run at normal loads and in normal
operating conditions for approximately 10 000 operating hours (two-pole
design motors) or 20 000 operating hours (four or multipole design motors)
without having to change the roller-bearing grease (unless otherwise
specified). However, the condition of the grease must be checked
periodically prior to the specified service interval. The stated operating hour
interval only applies when the motor is run at nominal speed. If the nominal
speed of the motor used by the frequency converter is exceeded, the
regreasing interval decreases approximately in reverse ratio to the increase
in rpm.
The bearings must be thoroughly cleaned using a suitable solvent before
regreasing. Use the same single grease quality for the lubrication.
Alternatively, the alternative qualities specified by the manufacturer may be
used. Note that the bearings can only be filled to a capacity of 2/3 of their
free volume. If the bearings and bearing caps are filled fully, the bearing
temperature rises and wear increases. In bearings with regreasing devices,
grease is added at a suitable amount for the motor in question via the
lubrication nipple while the motor is running. Refer to the regreasing
intervals in the table below.
The required grease amounts for regreasing are presented in the table
below (note that a double amount of grease must be applied for the first
commissioning regreasing, because the lubrication pipes will still be
empty). The waste grease gathers in the grease chamber of the external
bearing cap. The waste grease must be removed after approximately five
regreasing cycles, e.g., during a condition inspection.
Length, Pole
Series, IEC/DIN Grease amount, cm³
number
D side N side
160 LX2, M2 23 20
160 L4, 6, 8 23 20
180 M2 23 23
180 M4, L6, 8 23 20
Length, Pole
Series, IEC/DIN Grease amount, cm³
number
180 L4 23 23
200 L2 - -
200 LX2 31 31
200 L4, 6, 8LX 6 31 23
225 2 31 31
225 M4, 6, 8S4, 8 35 31
250 M2 35 35
250 M4, 6, 8 41 35
280 2 41 41
280 ≥4 52 41
315 2 52 52
315 ≥4 57 52
315 MX2 VL 57 52
315 MY2 VL 57 57
315 MX4, 6, 8 VL 64 52
315 MX4, 6, 8 VL 78 57
3.3.4. Cleaning
Table of Contents
1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1
1.2. General notes ........................................................................................1
2. Instructions ....................................................................3
2.1. Connectors which are not to be protected .........................................3
2.2. Wax-like protective agent (Pentisol 710) ............................................ 5
2.3. Protective agent (CRC 2-26) ................................................................ 8
2.4. Protective grease (Ensto SR1) ............................................................ 10
2.5. Removing protective agents ................................................................11
2.6. Example housing corrosion protection ..............................................12
1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals
Protective agents
1. Wax-like protective agent (Pentisol 710)
• Protective agent for fixed connectors, metal components, and cable
components.
2. Protective spray (CRC 2-26)
• Light corrosion protection for less-demanding applications which do
not withstand protective grease.
3. Protective grease (Ensto SR1)
• For protecting plug connector contacts.
2. INSTRUCTIONS
2.1. Connectors which are not to be protected
• Connectors of card rack motherboards.
Items to be protected
• Terminal strips (NOT spring-clamp types) in boxes are to be protected
after connection. Typically, this is done during final assembly. If the box
contains components which can fail, e.g., relays, use CRC 2.
• After connecting the cable harnesses, protect the interior of the metal
plug connector housings (Harting).
Note! Protect mounting screw threads and screw joints with protective
grease.
• Battery connectors.
• Servo and R/D cards of TMS, TCAD, and TDAT jumbos.
Note! PC104 card pack of TCAD is not to be protected with Pentisol.
After protection
Allow the wax-like protective agent to dry at room temperature for at least 8
hours before packing in a VO package, or so that it does not drip before
installing electronic components. Ensure also that the protective agent is
not so wet that it sticks to the antistatic material of the package.
If necessary, wipe the edges of the rack-installed cards clean to make
installation and removal easier after protection.
Allow the metal multi-pole connectors to reach non-drip dryness.
Note! Terminal strips in switchgears are NOT to be protected with
protective agent since it contains solvents that require a drying time
of 24 hours at a temperature of 20 °C; the drying time is longer at
lower temperatures.
CRC
• PLC's I/O connector (screw terminal and underside) and the connectors
between units.
Note! Connectors of VME cards on Solo rigs are not to be protected with
SR1 grease.
Note! Do not over fill the connectors with grease since excess grease can
cause contact faults and/or mechanical damage to the connector!
Always remove excess grease from the connectors after protection.
Pentisol
Sealing Breather
surface
SR1
Water hole SR1