Electric DD321

Download as pdf or txt
Download as pdf or txt
You are on page 1of 114
At a glance
Powered by AI
The document provides instructions for the 380-690 V electric system for the NC7 series, DD531, and DT821 machines. It describes the main components, operation, and maintenance procedures of the MSE electric system.

The main components described include layouts, protector switches, switches, gauges, circuit breakers, transformers, contactors, relays, and the Multitimer unit.

The document describes that the Multitimer unit controls inputs and outputs like the water pump, compressor, water pump 2, pressure control functions, oil level control, shank lubrication, and oil temperature control.

Original instructions

BG00203315 A.1 2013-09-11

380-690 V electric system - NC7


series, DD531, DT821
380-690 V electric system - NC7 series, DD531, DT821

Table of Contents

1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1
1.2. General .................................................................................................. 1

2. Safety and Environmental Instructions ...................... 3


2.1. Safety ..................................................................................................... 3

3. MSE electric system main components ......................5


3.1. Main components ................................................................................. 5
3.1.1. Lay-outs .......................................................................................6
3.1.2. Protector switches ....................................................................... 14
3.1.3. Switches ...................................................................................... 15
3.1.4. Gauges ........................................................................................15
3.1.5. Circuit breakers ........................................................................... 16
3.1.6. Transformers ............................................................................... 17
3.1.7. Contactors and relays ................................................................. 18
3.1.8. Multitimer unit (MTU) ...................................................................20
3.1.9. External sensors ..........................................................................20

4. MSE electric system operation .................................... 21


4.1. Function of the Multitimer unit ............................................................ 21
4.1.1. Inputs and Outputs for MTU ........................................................ 22
4.2. Functionality description for the MSE system ...................................24
4.2.1. Water pump .................................................................................24
4.2.2. Compressor .................................................................................25
4.2.3. Water pump 2 (optional) ..............................................................26
4.2.4. Pressure control functions ...........................................................27
4.2.5. Oil level control ............................................................................28
4.2.6. Shank lubrication .........................................................................29
4.2.7. Oil temperature control ................................................................30

5. Operator's maintenance procedures ...........................31


5.1. Electric system ..................................................................................... 31
5.1.1. Electric system - Operator's safety instructions .......................... 31
5.1.2. Checking the operation of the emergency stop devices ..............33
5.1.3. Checking the electric cabinets and connection boxes .................33
5.1.4. Checking the electric cables and harnesses ............................... 33
5.1.5. Checking the sockets and plugs ..................................................34
5.1.6. Checking the operation of the drilling module movement
prevention switches (if equipped) ................................................35

Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

6. Periodic maintenance procedures .............................. 37


6.1. Electric system ..................................................................................... 37
6.1.1. Electric system maintenance - Safety instructions ...................... 37
6.1.2. Checking connections and contacts (110 VAC - 1000 VAC) ...... 39
6.1.3. Checking connections and contacts (24 VDC, battery system) .. 40
6.1.4. Checking control system ............................................................. 40
6.1.5. Checking the operation of the fault current protector switch ....... 40
6.1.6. Checking the condition of the power supply cable ...................... 40
6.1.7. Checking the water drainage holes ............................................. 40
6.1.8. Checking the seal bushings ........................................................ 41
6.1.9. Checking the motor terminals ......................................................41
6.1.10. Cleaning electric devices .............................................................42

7. Electric system repair ...................................................43


7.1. Procedures after a long period out of use ......................................... 43
7.2. In connection to repair ......................................................................... 43

8. MSE electric system troubleshooting ......................... 45


8.1. Troubleshooting ................................................................................... 45
8.1.1. Powerpack does not start or stops .............................................. 45
8.1.2. Powerpack starts, but stops after a while ....................................45
8.1.3. Powerpack main contactor clapping ............................................45
8.1.4. Working lights do not work .......................................................... 45
8.1.5. 220-240 V 1-phase socket outlet does not work ......................... 46
8.1.6. Oil filling pump does not work ..................................................... 46

Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals

This manual, and especially the safety information, is valid only if no


unauthorized changes to the product are made.
Continuing improvement and advancement of product design might have
caused changes to your product which are not included in this publication.
Note also that if a third party has made changes to the product after
delivery from the manufacturer, this publication does not include
information on these changes or their influences on the product.
Whenever a question arises regarding your product, or this manual, please
consult your local Sandvik representative for the latest available
information.

1.2. General
Electric system consists of the main switchgear (MP), and the devices,
sensors, and the control and the indicator light panel connected to it. The
electric control of the hydraulic system is dealt with in separate instruction
manuals.
In the electric circuits of the electric motors, the working lights, the cabin
heater, and the socket outlets the voltage is over 100 VAC. The sensors,
the switches, the indicator lights, and the electric control of hydraulics use
reduced voltage (24 VDC).
Sandvik manufactures the electric system of the rig to conform to the
standard EN 791.
The power supply must be dimensioned to guarantee trouble free operation
at full power and when electric motors are started. The power supply
transformer or the generator, and the power supply cable must be rated to
meet the rig’s power requirements.
The rig is designed to operate in a supply network that meets the
requirements in 4.3.1 of the standard EN 60204-1. The power requirement,
the frequency, and the operating voltage are given on the panel at themain
switch. The fluctuation of the rated voltage must not exceed ±10 % at the
main switchgear, whether idling or operating at full power.
Sandvik defines the maximum voltage drop in the power supply cable to
below 3 %.

Copyright © Sandvik Mining and Construction 1


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Electric system is made to the protection class IP55, which means


enclosures that are jets of water and dust tight.
Water must never be sprayed directly at the electric boxes or
cabinets of the rig!

2 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

2. SAFETY AND ENVIRONMENTAL INSTRUCTIONS


2.1. Safety
Electric devices will stay in safe working condition if they are
repaired and serviced by a qualified electrician.

Repairs on electric devices is only allowed to personswho are not


only qualified but also authorized to do the work.

Check the condition of all electric devices and wires regularly.

Remember to close all electric switchgear doors properly after


repairs or adjustments.

If you suspect a fault in any electric device, cut off the voltage at
themain switch, and call in an electricianwho is specialized in the
electric systems of the equipment you are using.

Make sure that the voltage cannot be accidentally switched on when


you are working on the equipment.

Even when you are working on dead equipment, use good insulated
tools. This is a simple method to improve your own safety.

Take the operation of the safety devices seriously. If a safety device


prevents the operation of a device, call in an electrician at once to
determine the fault.

Copyright © Sandvik Mining and Construction 3


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

This page is intentionally left blank

4 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3. MSE ELECTRIC SYSTEM MAIN COMPONENTS


3.1. Main components
The MSE electric system consists of the main switchgear (MP), and the
devices, sensors, and the control and the indicator light panel connected to
it.

• Main switchgear contains the main switch, the motor controls, and the
power supply system for the electric devices.

Copyright © Sandvik Mining and Construction 5


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.1. Lay-outs

2P101/
2P128

2P100
OPTION

OPTION
55172786

39053178
2

2
1P101/
1P128

1P100
OPTION
55172786

39053178
1

P400
39002818
3-PH EFS
OPTION
F291
F333

P410

PH OR CABIN
F253

OPTION
F252

F251
MAIN SWITCH
Hz

F313
Q100
kW

F312
V

F311

OPTION
S301

OPTION
S300

F452.5 F454.7 OPTION

F452.4 F454.6 OPTION

F452.3 F454.5 OPTION

F452.2 F454.4 OPTION

F452.1 F454.3 OPTION

F451.6 F454.2
F451.5 F454.1
F451.4 OPTION F453.5 OPTION

F451.3 OPTION F453.4 OPTION

F451.2 F453.3 OPTION

F451.1 F453.2 OPTION

F450 F453.1 OPTION

Figure: Front view of cabinet NC7 series

6 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

F333

PH OR CABIN
F253

OPTION
F252

F251
F312

F311

X28
3-PH EFS
OPTION
F291
Q100

P410

(2P128)
2P101

X41
(1P128)
1P101

X24

X63
F454.6
F454.5
F454.4
F454.3
F454.2
F454.1
F453.5 OPTION
P400

F453.4 OPTION

F453.3 OPTION

F453.2 OPTION

F453.1 OPTION
2P100

F452.5
F452.4
F452.3
1P100

F452.2
F452.1
F451.6
F451.5
F451.4
OPTION
S300

F451.3 OPTION

F451.2
F451.1
F450

Figure: Front view of cabinet DT821

Copyright © Sandvik Mining and Construction 7


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Figure: Front view of cabinet DD531

8 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

K901, K902, K903 Tele-op.


CONTACTOR

HPP DELTA
CONTACTOR
HPP STAR
1K105

1K104

POWERBACK START
POWERBACK STOP
RELAY (OPTION)

RELAY (OPTION)

RELAY (OPTION)
START / DELTA

DL-app. components
DL-app. components
1K103, K310, K311
K903

1F100

CONTACTOR
1K100

HPP MAIN
K902
K901

K310
K311
1K103
131
130
129
128

2-BOOM
OPTION
127
126

2K105/

2X110
1K105
125

2-BOOM
OPTION
K240
124
123
122
121
131
130
129
128

2-BOOM
OPTION

1X110
127

2F100
126
125
124
123
122
121
17
16
15

1K104

2K104
15

2-BOOM
OPTION
15
14
13
12
223 CDE (DS-OPTION)
222 CDE (DS-OPTION)
221 CDE (DS-OPTION)
189

20x42
188
1F100

187

X160(X182 DS-rigs)
186

1K100

2K100
185

2-BOOM
OPTION
184

X110
184
183
182
181
176
175
174
173
172
172
POS. 172
2-BOOM 172
OIL LASER LIGHTS 171
LEVEL DL DL LIGHTS LIGHTS 2-BOOM OPTION 171
LIGHTS LIGHTS LIGHTS OPTION
171
171
156
155

2K112

1K112
154
153

F454.7
F454.6
F454.5
F454.4
F454.3
F454.2
F454.1
F453.5
F453.4
F453.3
F453.2
F453.1
F452.5
F452.4
F452.3
F452.2
F452.1
F451.6
F451.6
F451.5
F451.4
F451.3
F451.2
F451.1

X63

X24
F450
F450

X28
152

164
163
162
161

451
451
451
T310

151
296

OPTION
X291
295

3PH.
294

X112
293

X450
292
K602 2K101 1K101
K327K405 K404 K403 K402 K401 K400
291

X101
V466

Q100
V548
V547
2V529 TPC OPTION
1V529 TPC OPTION
2V249 THC OPTION
1V249 THC OPTION
V400
592 TRS/UK OPTION

X62
X41
591 TRS/UK OPTION
590 TRS/UK OPTION
587 UK OPTION
586 TPC OPTION
585 TPC OPTION
584 TPC OPTION
583 BEMA OPTION
582 SOLO OPTION
581 SOLO OPTION
580
577 BEMA OPTION
576 BEMA OPTION
575 BEMA OPTION
573
573
572 SOLO OPTION
571 THC OPTION

K445 K465 K466 K471


570

TPC MOV.PREV. POWER


569

ON
CONTROL

565 SOLO OPTION


230VAC
F310

X36
564 SOLO OPTION
563
562
MULTI TIMER UNIT

561

OPTION
560 SOLO OPTION
559 SOLO OPTION
558
558
556
555
F320

24VDC

554
553

ALTERNATIVES
A100

OPTION

THC MOV.PREV.
550

THC

K465
546

TCH / TPC
A420

545

OPTION
544
544

OPTION CONTROL
K424

MAIN
543
WATER PUMP

542
541 CABIN OPTION
F230

540 CABIN OPTION


1K447 2K447
K77

E/S STOP E/S STOP


CONTROL CONTROL

539 CABIN OPTION


539 CABIN OPTION
A

THC
538
538
537
A
DL-app.

536
K79

535

X44
X43
534
533
532
K230

532
COMPRESSOR

K77.2 TPC OPTION 531


WP

X500
530
F240

530
K78 E/S STOP 529
529
K231 WP 528
COMPR.
K240

527 TPC OPTION


527 TPC OPTION
K241 COMPR. 526
526
K395 OA1 OPTION 525
524
523 TPC OPTION
K396 OA2 OPTION
K451

HEATER
OPTION

522 TPC OPTION


OPTION
F250

522
K480
1PH

521
PILOT OPTION
X50
X42
520
520
K461 TRR OPTION 520
3PH SOCKET 1PH SOCKET

519
518
OPTION
K430

K320 517
516
OPTION

515
3. PH
F290

515
515
514
F296

OPTION

514
K290
OA2

OPTION

513
512
511
T250

X120/X74

510
509
508
507
X23
K296

506
OPTION

505
OA2

504
504
504
503
OPTION
F295

502
OA1

502
K295

OPTION

501
OA1

501
501
501
501
501
501
OPTION
T290

501
EXT.
PUMP

501
501
501
501
501
501
501
K491 K492 K493

K659 WARNNG HORN


DL-app. components

DS-app. components

DUST EXTRACTOR
F220, K220 CEMENT

K659 DL-app.
CEMENT DUST
EXTRACTOR
DS-OPTION
EXTERNAL PUMP OPTION

K444

F220
K291

CEMENT DUST
EXTRACTOR
DS-OPTION
K220
T490

R490

Figure: Inside view of cabinet, NC7 series

Copyright © Sandvik Mining and Construction 9


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

1K105

2K105
131

OPTION
130
129
128

OPTION

2X110
2F100

OPTION
127
126
125
124
123
122
121
131
130
129
128

1X110
127

1K104

2K104
126

OPTION
125
124
123
122
121
189
188

1F100
187
186
185
184
184

1K100

2K100

OPTION
183
182
181
180
179

X110
178
177
176
175
174
173
172
172

Q100
172
172
171
171
171
171
156
155
154
153
152
151
17
16
15

LIGHT OPT.
15

REV CAM
2K101 K445 K471 K405
15
14
CONTROL
230VAC
F310

13
12

POWER
ON
OPTION
TCH
24VDC
F320

2-BOOM
OPTION

X101
2-BOOM
OPTION
2K112
T250

V446
F230

2V529
1V529
WP

1K101
V400
595
594
593
592
591
1K112 590
589
588
587
586
585
584
579
578
571
569
F240

568
COMPR.

567
OPTION
296
563
X291

295
562
294
293 558
292 558
291 557
556
451 555
554
451 553
451 V548
OPTION
F250

V547
1PH

F454.4 546
F454.3 545
F454.2 544
F454.2
A420

F454.1 544
F453.5 543
F453.4 542
F453.3 541
F453.2 540
F290

OPTION

F453.1 539
F452.5
X450
3PH

538
F452.4
THC MOV.PREV.

538
F452.3 537
F452.3 536
OPTION

F452.2 535
K465

F452.1 534
F451.6 533
F451.6 532
F451.5 532
F451.4 531
K320 F451.2 530
X500
ALTERNATIVES

F451.1 530
TCH / TPC

F450 529
K480 OPTION X112
162
161
529
528
HYDR.OIL 527
K77.2 OPTION K602 LEVEL 527
526
K50 OPTION
K404 LIGHT 525
K290

524
OPTION

523
K493 OPTION 2K447 THC.OPT. 522
K403 LIGHT 522
1K447 THC.OPT. 521
OPTION OPTION
K491 K492

520
520
K402 LIGHT 520
OPTION
TPC MOV.PREV.

K296
K466

519
OA2
T310

518
OPTION

517
K401 LIGHT 516
K465

515
515
K400 LIGHT 515
OPTION
K295

514
OA1

514
513
K230

512
K444

OPTION

511
WP

510
F295

OPTION

509
508
OA

507
506
COMPR.

505
K240
ALTERNATIVES

504
504
COMP.CONT.

EMG.STOP

504
WP.CONT.
K291

CONTROL

CONTROL
OPTION

EMG.STOP

503
CONTROL

503
MAIN

A100 502
1PH SOCKET HEATER

502
K451

OPT.

501
MULTI TIMER UNIT 501
OPTION
F296

501
501
OA

501
501
501
OPTION
K430

501
OPTION

501
T490

501
501
501
501
K395 OPT.
K231
K241

K424

501
T290
K78

K77

501
K396 OPT. OPTION 501

R490 OPTION 501

Figure: Inside view of cabinet, DT821

10 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Figure: Inside view of cabinet, DD531

Copyright © Sandvik Mining and Construction 11


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

501
501
501
501
501
501
X502
+ + - -

A410

N L PE
DC/DC CONVERTER FOR
TELEOPERATION

543
X510

542
OPTION
A450

172
171
K425
SUPPLY BOOSTER
DATA TRANSFER

OUT
C100

OPTION

IN

Figure: Inside view of doors, NC7 series

12 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

K425

K461 OPT.

451
X451 451
451

501
501
X501 544
544
544
171
172
X510
A410
+ + - -

N L PE

Figure: Inside view of doors, DT821, DD531

Copyright © Sandvik Mining and Construction 13


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.2. Protector switches

Motor protector switch of the powerpack


of boom 1, with thermal and magnetic
triggering. The set value (A) of the
triggering current for the thermal switch is A
1.2x the nominal current given on the
1F100
motor's type plate. The triggering current
of the magnetic switch is constant. The
protective switch must be reset by turning
its control handle first to position 0 and
then to position 1.
Motor protector switch of the powerpack
of boom 2, with thermal and magnetic
triggering. The set value (A) of the
triggering current for the thermal switch is A
1.2x the nominal current given on the
2F100
motor's type plate. The triggering current
of the magnetic switch is constant. The
protective switch must be reset by turning
its control handle first to position 0 and
then to position 1. (optional).
Motor protector switch of the powerpack
of boom 3, with thermal and magnetic
triggering. The set value (A) of the
triggering current for the thermal switch is
1.2x the nominal current given on the A
3F100
motor's type plate. The triggering current
of the magnetic switch is constant. The
protective switch must be reset by turning
its control handle first to position 0 and
then to position 1. (optional).

Water booster pump’s motor protector switch, with fixed


magnetic triggering and adjustable thermal triggering. The
F230
set value of the thermal triggering current is equal to the
nominal current given on the motor's type plate.
Compressor's motor protector switch, with fixed magnetic
triggering and adjustable thermal triggering. The set value
F240
of the thermal triggering current is equal to the nominal
current given on the motor's type plate.
Transformer protector switch of outlet socket and cabin
F250
heater transformer (optional)
Protector switch, with fixed magnetic triggering and
adjustable thermal triggering for power supply transformer
F290
of 3-phase service socket outlet or its transformer or the
circuit breaker for external pump supply (optional)

14 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Motor protector switch of the oil cooler fan, with fixed


magnetic triggering and adjustable thermal triggering for
F295, F296,
booms 1, 2 and 3. The set value of the thermal triggering
F297
current is equal to the nominal current given on the motor's
type plate (optional).
F310 Transformer protector switch of control transformer
Transformer protector switch of internal 24 V control
F320
voltage of main switchgear cabinet

3.1.3. Switches

Main switch; cuts off power supply.


The main switch can be locked in the ‘0’ position. The main
switch cuts off the control conductor that monitors the
Q100
supply cable and the protective conductor. The control
conductor is optional equipment. When the main switch is
set to position 1 (ON), the electrical cabinet door is closed.

WARNING! ELECTRICAL HAZARD!


Electric shock could cause death or severe injury.
The main switch does not switch off the voltage from the cable reel
or from the slip rings without a pilot system. The carrier’s
accumulator circuit remains on as well.
S301 Emergency stop button (optional)

3.1.4. Gauges

1P100 Rock drill percussion hour meter for boom 1


Rock drill percussion hour meter for boom 2 (rigs with two
2P100
booms)
Rock drill percussion hour meter for boom 3 (rigs with three
3P100
booms)
1P101 Hour meter for powerpack 1
2P101 Hour meter for powerpack 2 (rigs with two booms)
3P101 Hour meter for powerpack 3 (rigs with three booms)
P400 Compressor hour meter
P410 Supply voltage meter
1P128 Hour meter for boom 1 power extractor (optional)
Hour meter for boom 2 power extractor (optional) (rigs with
2P128
two booms)
Hour meter for boom 3 power extractor (optional) (rigs with
3P128
three booms)

Copyright © Sandvik Mining and Construction 15


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.5. Circuit breakers

F220 Protective switch for cement dust extractor (DS)


Fault current circuit breaker for cabin heater and sockets
F251
(optional)
F252 1-phase circuit breaker for socket X430 and X431 (optional)
F253 Circuit breaker for cabin heater (optional)
F291 Fault current circuit breaker for 3-phase socket (optional)
Fault current circuit breaker for internal 220 V control
F311
voltage in main switchgear
Circuit breaker for internal 220 V control voltage in main
F312
switchgear
F313 Not used in 380-690 V switchgear
F333 Circuit breaker for A100
Circuit breaker for internal 24 V control voltage in main
F450
switchgear
F451.1-
Circuit breakers for control system, instruments and carrier
F451.6
F452.1-
Circuit breakers for lights and jacks control
F452.5
F453.1-
Circuit breakers for cabin wiring harness (optional)
F453.5
Circuit breakers for A100, utility boom, hydraulic filling
F454.1-
pump control, cameras, optimine, swellex and fuel filter
F454.7
options
Protective switch for phase sequence monitoring relay and
F470
OA-cooler motors

Adjustments
Reset the protective switches to position I only when the main switch is in
the 0 position, if the drill rig is connected to the power supply network.

16 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.6. Transformers

Battery charger. Charges the carrier's batteries when the rig


is connected to the supply network and the main switch is
A410
on. The charger is equipped with charging automatics to
prevent overcharging.
Power transformer. The power source of the rig's 24 VDC
A420
circuit. Output 1000 VA.
A450 Remote control DC/DC converter (optional for DL)
C100 Supply booster for data transfer (optional for DL)
4500 VA power supply transformer for 1-phase 220-240 V
service socket outlet and cabin heater. The transformer is
T250 equipped with an overheating protector (150 °C) that cuts
off the socket outlet load. The protector resets automatically
when the transformer has cooled down sufficiently.
Transformer for external pump earth leakage relay
T290
(optional)
Control voltage transformer. Control voltage: 400 VA,
220-240 V or 110 V. The transformer is equipped with an
T310 overheating protector (150 °C) that cuts off load. The
protector resets automatically when the transformer has
cooled down sufficiently.
T490 Transformer for external pump control circuit (optional)

Copyright © Sandvik Mining and Construction 17


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.7. Contactors and relays

1K100 Starter contactor of powerpack motor for boom 1


1K101 Auxiliary starter relay for powerpack of boom 1
1K103 Auxiliary closing delay time relay for powerpack (DL)
1K104 Delta contactor of powerpack motor for boom 1
1K105 Star contactor of powerpack motor for boom 1
Thermistor relay for temperature control of powerpack
1K112
electric motor for boom 1
2K100 Starter contactor of powerpack motor for boom 2 (optional)
2K101 Auxiliary starter relay for powerpack of boom 2 (optional)
2K104 Delta contactor of powerpack motor for boom 2 (optional)
2K105 Star contactor of powerpack motor for boom 2 (optional)
Thermistor relay for temperature control of powerpack
2K112
electric motor for boom 2 (optional)
3K100 Starter contactor of powerpack motor for boom 3 (optional)
3K101 Auxiliary starter relay for powerpack of boom 3 (optional)
3K104 Delta contactor of powerpack motor for boom 3 (optional)
3K105 Star contactor of powerpack motor for boom 3 (optional)
Thermistor relay for temperature control of powerpack
3K112
electric motor for boom 3 (optional)
K50 Auxiliary relay for safety wire (optional)
K77 Emergency stop relay
K77.2 Emergency stop relay (utility boom, optional)
K78 Emergency stop auxiliary relay
K79 Emergency stop auxiliary relay (DL)
K220 Contactor for cement dust extractor (DS)
K230 Starter contactor of water booster pump
K231 Auxiliary relay for water booster pump
K240 Starter contactor of compressor
K241 Auxiliary relay for compressor
K290 Contactor for external pump (optional)
K291 Auxiliary relay for external pump (optional)
K295, K296, Starter contactor of oil cooler fan for booms 1, 2 and 3
K297 (optional)
K310 Auxiliary stop relay of powerpack (DL)

18 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

K311 Auxiliary start relay of powerpack (DL)


K312 Evaporation system auxiliary relay (optional for DT)
K320 Phase sequence control relay
K327 Time relay for positioning lasers (optional for DL, DS)
K395, K396,
Relay of oil cooler fan for booms 1, 2 and 3 (optional)
K397
K400-K405 Connecting contactor for lighting
K424 Auxiliary relay for monitoring functions
K425 Battery feed connector relay
Contactor for 1-phase socket outlet. Cuts off power supply
K430
to socket if transformer is overloaded (optional).
K444 Earth Continuity Relay (Australian models)
K445 Drilling stop auxiliary relay (power optional)
1K447, Time relays for return automatics electric supply (optional
2K447 for THC-rigs)
K451 Contactor for cabin heater (optional)
Jacks pressurizing TRR/TRS (optional for DD, hydraulic
K461
control)
Drilling module movement prevention relay (optional in
K465
THC- and TPC-rigs)
Drilling module movement prevention relay (optional in
K466
TPC-rigs)
K471 Auxiliary relay for supply net ON
K480 Pilot interlock relay (optional)
K481 External pump auxiliary relay (optional)
K491 Starting relay for External pump (optional)
K492 Earthing wire continuity control relay (Australian models)
K493 Blinking relay for earthing failure (Australian models)
K602 Hydraulic oil level low auxiliary relay
K659 Warning horn relay (DL)
K901 Remote control relay (optional for DL)
K902 Remote control relay (optional for DL)
K903 Remote control relay (optional for DL)
For producing fault current to earth fault relay when testing
R490
(optional)

Copyright © Sandvik Mining and Construction 19


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

3.1.8. Multitimer unit (MTU)

1 2

1 Adjustment of delay for water pressure monitoring


2 Adjustment of delay for air pressure monitoring
3.1.9. External sensors

Oil level switch. Two switching points are provided: lower


S420
level for oil level alarm and upper for oil filling pump.
S421 Pressure switch for shank lubrication and flushing air
S422 Pressure switch for flushing and cooling water
Oil temperature switch and gauge. The temperature
switches are incorporated in the temperature gauge. Two
S424 switching points are provided: upper for oil temperature
alarm and stopping (75 °C) and lower for bypassing oil filter
monitoring (30 °C).
S425 Pressure switch of hydraulic oil return filter
S441 Temperature switch for compressor’s output air
Pressure switch for hydraulic oil pressure filter of
1S180
powerpack for boom 1
Pressure switch for hydraulic oil pressure filter of
2S180
powerpack for boom 2 (optional)
Thermistors of powerpack motor for boom 1 (stator
1R112
temperature 155 °C)
Thermistors of powerpack motor for boom 2 (stator
2R112
temperature 155 °C) (optional)

20 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4. MSE ELECTRIC SYSTEM OPERATION


4.1. Function of the Multitimer unit
Water pump and drilling functions stop after set delay if water pressure
drops below 2.8 bar.
Drilling functions stop after set delay if output pressure from compressor
drops below 2.8 bar.
Under the cover of the timer unit (A100) you will find the two adjusting
screws that are used for setting the delays for the water pump and the
compressor.
By turning the adjusting screw clockwise you can increase the delay, and
by turning the screw anti-clockwise you decrease the delay.
The factory settings for the delays are: 4 seconds for water pressure and
10 seconds for air pressure.

Copyright © Sandvik Mining and Construction 21


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.1.1. Inputs and Outputs for MTU

IN 0 CH.
I/O Symbol Description Normal state*
0 S422 Water pressure control 0
1 S421 Air pressure control 0
2 S420 Hydraulic oil level control 1
Water pump auto/manual
3 S501 1
use
Water pump manual use
4 S501 0
(start)
Compressor control auto/
5 S502 1
manual use
Compressor manual use
6 S502 0
(start)
7 S505 Pressure switches reset 1
Double booster pump use
8 S507 0
(optional)
9 HP_RUN Hydraulic pump running 1
Water pump / compressor
10 Overload 1
overload
11 Oil_hot Hydraulic oil hot 0
COM 0 VDC -

OUT 100 CH.


I/O Symbol Description Normal state*
0 0
1 SLCU Shank lubrication unit supply 1
2 H601 Water pressure low 0
3 S609 Air pressure low 0
4 S602 Oil level low 0
5 Drill_stop Drilling stop 0
6 K424 Main control relay 1
7 Control 24 VDC control supply 1
COM +24 VDC 1
COM +24 VDC 1

22 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

I/O Symbol Description Normal state*


COM +24 VDC 1
COM +24 VDC 1

IN 1 CH.
I/O Symbol Description Normal state*
Pressure switch by pass
0 SH520 0
(power)
1 boom rotation and/or
1 1JB102 1
percussion on (only THC) **
2 SLCU SLU oil level low 0
DL-series identification (only
3 SOLO 1
DL)
2 boom rotation and/or
4 2JB102 percussion on (only 2 boom 1
THC) **
3 boom rotation and/or
5 3JB102 percussion on (only 3 boom 1
THC) **

OUT 101 CH.


I/O Symbol Description Normal state*
Water pump control aux.
0 K230 1
relay
Compressor control aux.
1 K240 1
relay
Double booster pump control
2 K281 0
aux. relay (optional)
SLCU booster control (only
3 SLCU 0 or 1
THC) **
COM +24 VDC 1

In the table, normal state means a state where the powerpack(s), drilling,
water pump and compressor are on and no faults are active. When the
input or output is 0, the voltage is 0 volts. When the input or output is 1, the
voltage is 24 VDC.
IN 1 CH 1, IN 1 CH 4 and IN 1 CH 5 are on only when percussion and/or
feed is on in the boom in question. OUT 101 CH 3 is on only 5 seconds at
the starting moment of any boom's percussion and/or rotation.
Note! The output leds of the multi-channel timer relay indicate the status of
the program, i.e. in order to ensure the state of the output, it must be
measured directly from the connector.

Copyright © Sandvik Mining and Construction 23


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2. Functionality description for the MSE system


4.2.1. Water pump

Three-position operating switch S501 is located on the SW panel in the


cabin or safety canopy.
Position 0:
The water pump is not on. When the first of the power packs starts (input
00.09 on), the pressure control functions are activated. This is used when
water at the required pressure is fed from the mine network without use of
the water booster pump.
Position 1:
The normal "on" position of the water pumps (input 00.03 on). When the
first of the power packs starts (input 00.09 on), the water pump starts after
two seconds, and the pressure control functions are activated. If the power
pack is already on and the switch is turned to position 1 (input 00.03 on),
the water pump starts. The water pump turns off when the power packs
stop.
Position S (momentary):
If all power packs are off and the switch is momentarily turned to position S
(input 00.04 momentarily on), only the water pump starts (manual operation
– e.g., for washing the rig). At the same time, water pressure control
becomes activated. Stop the water pump by turning the switch to position 0.
If the water pump is operated manually, the power pack cannot start. The
power pack can be started only after one switches off manual operation of
the water pump. A power failure or pressing the emergency stop button
(input 00.10 off) prevents the water pump from starting. Restarting is then
required.
The QN indicator panel contains the following indicators for the water
pump: green "water pump running" indicator light (H619) and red "water
pump overload" indicator light (H606). If the water pump overload condition
occurs, the power packs, water pump, and compressor are stopped (output
100.06 off; controlling relay K424).

24 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2.2. Compressor

Three-position operating switch S502 is located on the SW panel in the


cabin or safety canopy.
Position 0:
The compressor is not on. When the first of the power packs starts (input
00.09 on), the pressure control functions are activated. This is used when
air at the required pressure is fed from the mine network without use of the
compressor.
Position 1:
The normal "on" position of the compressor (input 00.05 on). When the first
of the power packs starts (input 00.09 on), the compressor starts after one
second, and the pressure control functions are activated. If the power pack
is already on and the switch is turned to position 1 (input 00.05 on), the
compressor starts. The compressor turns off when the power packs stop.
Position S (momentary):
If all power packs are off and the switch is momentarily turned to position S
(input 00.06 momentarily on), only the compressor starts (manual operation
– e.g., for producing compressed air). Note: Air pressure control is NOT
activated when only the compressor is used. Stop the compressor by
turning the switch to position 0. If the compressor is operated manually, the
power pack cannot start. The power pack can be started only after one
switches off manual operation of the compressor. A power failure or
pressing the emergency stop button (input 00.10 off) prevents the
compressor from starting. Restarting is then required.
The QN indicator panel contains the following indicators for the
compressor: green "compressor running" indicator light (H618), red
"compressor overload" indicator light (H605), and red "compressor air hot"
indicator light (H604). If the compressor overload or high temperature
condition occurs, the power packs, water pump, and compressor are
stopped (output 100.06 off; controlling relay K424).

Copyright © Sandvik Mining and Construction 25


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2.3. Water pump 2 (optional)

Two-position operating switch S507 is located on the SW panel in the cabin


or safety canopy.
Position 0:
Water pump 2 is not on and the system operates as if water pump 2 does
not exist; i.e., water pump 1 can be used normally.
Position 1:
The operation of water pump 2 depends on water pump 1’s status. Water
pump 2 does not start if water pump 1 is not running or water pump 1 is
already running. Water pump 2 may be started only when the operating
switches for both water pumps are in position 1 (the water pump 2 input is
00.08). In this case, water pump 2 starts immediately (output 101.02 on)
and water pump 1 starts with a delay of two seconds when the first of the
power packs is started. Water pump 2 does not stop until the power packs
are stopped. Then, water pump 1 stops immediately and water pump 2
stops with a delay of three seconds. If the operating switch for water pump
2 is turned to position 0 when water pump 1 is running, water pump 2 stops
only after a delay after water pump 1 has been stopped.
Hence, water pump 2 acts mainly as a slave to water pump 1. When
operated manually, water pump 2 starts immediately and water pump 1
starts with a delay of two seconds. When water pump 1 is turned off, water
pump 1 stops immediately andwater pump 2 stops with a delay of two
seconds.
The QN indicator panel contains the following indicators for water pump 2:
green "high-pressure water pump running" indicator light (H620) and red
"high-pressure water pump overload" indicator light (H615). If the water
pump 2 overload condition occurs, the power packs, water pump, and
compressor are stopped.

26 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2.4. Pressure control functions

For resetting the pressure sensors, button S505 is on the SW panel in the
cabin or safety canopy.
The rig is equipped with pressure switches for water pressure and air
pressure. The pressure control functions are activated when one or more
power packs are started (input 00.09 on). If the water pump is used
separately, water pressure control becomes activated (air pressure control
is not activated when only the compressor is used). The delays for water
pressure control and air pressure control are four and 10 seconds,
respectively. These time parameters can be adjusted with the power logic
adjustment screws without changes to software settings (for WP value, the
range is 4–24 seconds (recommendation: 4 s), and for the C value the
range is 10–30 seconds (recommendation: 10 s); i.e., the WP and C
pressure control delays are set to the factory values when the adjustment
screws are in their zero positions).
If the water pressure is below the limit set (for over 4 s), the water pump is
stopped (output 101.00 off), or, if the air pressure is below the set limit (for
over 10 s), automatic drilling is stopped (output 100.05 on). Stopping
automatic drilling means that the power packs remain on but on a
hydraulically controlled rig the drilling joysticks are centralized and on an
electrically controlled rig automatic drilling is disabled. Drilling functions can
be used temporarily by using manual operation (also before resetting of the
pressure sensors).
On the QN panel, the "low water pressure" indicator light (H601) (output
100.02 on) or "low air pressure" indicator light (H609) is lit and remains on
(output 100.03 on). The fault is stored in the memory and is reset with the
pressure control reset button (S505) (input 00.07 momentarily off). Both
faults are reset with the pressure sensor reset button (S505) (input 00.07)
on the SW panel.
If the fault is caused by low water pressure and fault duration exceeds one
minute, the water pump is also stopped and resetting the fault does not
start the water pump even if the power packs are on and the water pump
operation switch is in the "automatic" position. Pressing the reset button
enables restarting the water pump by setting the water pump operation
switch to the "start" position. After the water pump is started, also automatic
drilling is enabled.
From the moment the water pump is started, the control time for stopping
the water pump is one minute and its fault time is four seconds.
The water pressure fault indicator light is switched off after resetting if the
fault duration reaches four seconds. If the water pressure fault duration is
one minute, the indicator light turns off only after resetting and starting. The
air pressure fault indicator light always turns off after resetting.
If drilling is performed without using the water pump and the water pressure
is not sufficient, the fault indicator light is lit (output 100.02) and automatic
drilling is stopped (output 100.05 on). After resetting, automatic drilling can
be continued without starting of the water pump.

Copyright © Sandvik Mining and Construction 27


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

If drilling is performed without using the compressor and the air pressure is
not sufficient, the fault indicator light is lit (output 100.03) and automatic
drilling is stopped (output 100.05 on). After resetting, automatic drilling can
be continued without starting of the compressor.
If the water pump is used without the power pack(s) running and the water
pressure is not sufficient (for over one minute), the water pump restarts
only after resetting of the pressure sensors and momentarily setting the
water pump operation switch to the "start" position. If only the compressor
is used, air pressure control is not active and no actions are required.
If the pressure control reset button is pressed and held for more than 30
seconds, the software stops the drilling and power packs.
Note: Output 100.05 is activated if the water or air pressure is too low. On
hydraulically controlled rigs, output 100.05 controls relay K445, and for
other rigs it goes to the drilling control system. Also, any stabilizer pressure
control and SLU flow control are located on the same line after output
010.05 and relay K445 to control automatic drilling.

4.2.5. Oil level control

Oil level control (input 00.02) is always active when the power is on. After
the level control is activated, the level switch has a delay of three seconds
to prevent false alarms caused by small changes in the oil level (splashing).
If the oil level remains below the level switch point for over three seconds
(input 00.02 off), the power packs stop (output 100.07 off). The "low oil
level" indicator light (H602) on the QN panel is switched on and remains lit
(output 100.04 on). The fault is stored in the memory, and it is reset with
the pressure control reset button (S505) on the SW panel. Resetting the
fault does not start the motors.

28 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2.6. Shank lubrication

• Shank lubrication unit control


The shank lubrication unit gets its feed (output 100.01 on) when a power
pack is running and the air pressure is sufficient. The control has a 10-
second shutdown delay.
• Shank lubrication oil flow
- Hydraulically controlled rigs
When the power pack is running and the air pressure is sufficient but
the shank lubrication oil flow becomes insufficient, automatic drilling
for the boom in question is stopped (drilling joysticks are centralized)
and indicator light H72 is lit on the boom’s THC panel. Note: This
cannot be bypassed with the bypass button.
- Electrically controlled rigs
When the power pack is running and the air pressure is sufficient but
the shank lubrication oil flow becomes insufficient, automatic drilling
for the boom in question is stopped (with a delay of 30 seconds) and
indicator light H72 is lit on the boom’s TPC panel. The control is
activated already when the power pack is running and the air
pressure is sufficient; i.e., indicator light H72 indicates whether the
shank lubrication oil flow is sufficient.
• Shank lubrication oil level indicator light
The QN indicator panel features a separate indicator light for shank
lubrication oil level and hydraulic oil level. If the rig is equipped with oil
receiver over- and underpressure control, its indicator light replaces the
shank lubrication indicator light on the QN indicator panel.
The shank lubrication unit directly controls the shank lubrication oil level
indicator light (H608) on the QN panel. Moreover, the shank lubrication
oil level indicator light is lit on the drilling panel. In this case, the light is lit
only; automatic drilling is not stopped.
If the rig is equipped with oil receiver over- and underpressure control,
the shank lubrication unit’s shank lubrication oil level indicator light is
combined with the hydraulic oil level control indicator light (H602) on the
QN panel. In the event of a shank lubrication oil level fault (input 01.02
on), the light flashes (output 100.04 goes on and off), and if a hydraulic
oil level fault occurs, the light is lit continuously. Moreover, the shank
lubrication oil level indicator light is lit on the drilling panel. In this case,
the light is lit only; automatic drilling is not stopped.
Note: With Australian models, the "low shank lubrication oil level" signal
also stops all power packs and drilling. The power packs can be restarted
only after adding of shank lubrication oil.

Copyright © Sandvik Mining and Construction 29


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

4.2.7. Oil temperature control

If the oil temperature exceeds 75 °C (input 00.11 goes on), the power
packs stop (output 100.07 goes off) and the "high oil temperature" indicator
light (H610) on the QN panel turns on. The fault is cleared when the
temperature falls below 75 °C. On this display, the limits for stopping the rig
and bypassing the filter monitoring with cold oil are 75 °C and 30 °C,
respectively. The rig has a hydraulic oil temperature gauge in the cabin.

30 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

5. OPERATOR'S MAINTENANCE PROCEDURES


5.1. Electric system
5.1.1. Electric system - Operator's safety instructions

DANGER
ELECTRICAL HAZARD!
Failure to strictly follow instructions will lead to severe injury and/or
death and/or property damage.
Work on electrical equipment or devices is to be performed only by
persons with the expertise and qualifications required by the
authorities, or under the supervision of a person meeting these
requirements.

Operators are allowed to perform the following tasks on electrical


components:
• plug and unplug the trailing cable into/from the gate end panel
• switch on and off the product main switch on the electrical cabinet of the
drill rig
• plug and unplug the one and three phase outlets for external pumps and
devices
• replace the broken bulbs of the working and driving lights according to
given instructions
All other work on electrical components is allowed only for
professional electricians! See maintenance manual.
Do not open junctions or terminal boxes on electric motors, cable reel,
electrical cabinets, light fittings etc!

Copyright © Sandvik Mining and Construction 31


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Operator actions to perform

Operator actions to perform


Check visually the condition of the drill rig's electrical devices every day
before operation.
Check the operation of the earth leakage control system from the gate end
panel weekly. If the control does not switch the power off, the control
system must be repaired or replaced before any device connected to it is
started.
Always check the operation of the emergency stop switches before use of
the machine. Do not use the machine if an emergency switch does not stop
all functions on the machines. Note that lighting will stay on if an
emergency switch is pressed, and the machine is not isolated!
When the electrical cabinet product main switch is switched off, always be
aware that this does not normally isolate the electrical supply going into the
machine’s electrical cabinet. Hence, the trailing cable, cable reel and cable
going to the live side of the product main switch remain live! (This is the
case unless a separate Pilot core electrical system has been adopted at the
work site and the pilot core is wired through the machine’s product main
switch!)
WARNING! ELECTRIC SHOCK HAZARD!
Failure to follow these instructions could lead to death or serious
injury.
If any faults or defects on electrical components are observed, such
as loose connections, open covers or damaged insulation, stop and
isolate the machine immediately by turning off the product main
switch and removing the power plug from the electrical network.
Ensure that nobody connects the power on by accident! The fault
can only be investigated by a qualified and competent electrician.
Faults must be repaired and tested before operating the machine.

Fuses and the circuit breakers are protecting the wires and electrical
components against overheat and fire in case of overload and short circuit.
Breaker tripping or fuse burn is a sign of failure. Before resetting the
breaker or replacing the fuse the failure must be repaired. The original fuse
size and type must be used. Never replace the fuse with a fuse having
higher ampere value than the original.

32 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Replacing the light bulbs

Replacing the light bulbs


WARNING! ELECTRIC SHOCK HAZARD!
Failure to follow these procedures could result in serious injury!
Cut the supply voltage to the light using the product main switch and
the battery isolation switch before replacing the bulbs of the working
and driving lights. Exercise extreme caution when performing work
on HID gas discharge lamps. The light components include high
voltage parts.

Note that parts of the light may be hot after use, so allow it to cool before
commencing repair work.
The bulbs of gas-discharge lamps are gas-filled, so handle with care. Use
gloves and safety glasses.
Do not touch the lamp holder or the glass part of the bulb when carrying out
the replacement.
Use proper servicing stands when changing the light bulbs.
5.1.2. Checking the operation of the emergency stop devices

Check the operation of the emergency stop devices while the power pack
and/or diesel engine is running, by using each emergency stop device in
turn. When an emergency stop function is activated, the power pack and
diesel engine must stop. At the same time, the indicator light (H614) on the
QN panel must come on and remain on until the emergency stop device is
reset.
5.1.3. Checking the electric cabinets and connection boxes

Visually check that the doors and fuse hatches are closed and that the
cabinet with its protruding components is intact.
Check the electric boxes subjected to moisture, and dry them if necessary.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.
All damaged or broken components must be replaced.
5.1.4. Checking the electric cables and harnesses

Visually check that the cable sheaths and sheath connectors are intact.
Also check that the cable clamps are in proper condition.
All damaged or broken components must be replaced.

Copyright © Sandvik Mining and Construction 33


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

5.1.5. Checking the sockets and plugs

Visually check that sockets and plugs are in proper condition.


All damaged and broken components must be replaced.
WARNING! ELECTRICAL HAZARD!
Damaged socket or plug could cause death or severe injury.
Do not use damaged sockets or plugs.

34 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

5.1.6. Checking the operation of the drilling module movement prevention switches (if
equipped)

Operation of the drilling rig is prohibited if the drilling module movement


prevention system is not working or is not in proper condition.
1. Check the operations of the boom 1 (left boom) and the left side drilling
module movement prevention switch (SH292). Start the boom 1 (left
boom) power pack.
2. Activate all boom 1 (left boom) movements and make sure that they
function normally.
3. Lock rock drill rotation counterclockwise on and make sure that it
functions normally.
4. Turn the left side drilling module movement prevention switch (SH292) to
"Movement prevention ON" position.

5. Test drilling functions prevention, use rock drill rotation. Ensure that rock
drill rotation has stopped. Try to restart rock drill rotation
counterclockwise. Ensure that rock drill rotation does not start.
6. Ensure that all boom 1 (left boom) movements have been prevented by
activating the controls.
7. Turn the left drilling module movement prevention switch (SH292) to
"Movement prevention OFF" position.

8. Stop the boom 1 (left boom) power pack.


9. Repeat the steps 1-8 for the boom 2 (right boom), where applicable, and
for the right side drilling module movement prevention switch (SH293).

Copyright © Sandvik Mining and Construction 35


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

This page is intentionally left blank

36 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

6. PERIODIC MAINTENANCE PROCEDURES


6.1. Electric system
6.1.1. Electric system maintenance - Safety instructions

DANGER
ELECTRICAL HAZARD!
Failure to strictly follow instructions will lead to severe injury and/or
death and/or property damage.
Work on electrical equipment or devices is to be performed only by
persons with the expertise and qualifications required by the
authorities, or under the supervision of a person meeting these
requirements.
Make sure that the instructions set forth below are read and
understood before any electric system maintenance.

Copyright © Sandvik Mining and Construction 37


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Performing maintenance on electrical components

WARNING! ELECTRICAL HAZARD!


Failure to follow these instructions could lead to death or severe
injury.
Isolate the machine by turning off the main switch and removing the
power plug from the electrical network before any work on electrical
components.
Ensure that nobody connects the power on during the maintenance
or repair work!
Electrical safety tests and measurements must be done before
operating the machine.
• The work must be carried out according to local electric safety
regulations.
• Always use approved, correct and certified electrical testing equipment
and personal protective equipment.
• When performing electrical work, always ensure that the machine is
disconnected from the supply network before any service, repair or
maintenance. Ensure that the components in question are not live, and
then lock the main switch or arrange appropriate grounding.
• When the electrical cabinet main switch is switched off, always be aware
that this does not normally isolate the electrical supply going into the
machine’s electrical cabinet. Hence, the trailing cable, cable reel and
cable going to the live side of the main switch remain live!
(This is the case unless a separate Pilot core electrical system has been
adopted at the work site and the pilot core is wired through the machine’s
main switch!)
• Do not open live junctions or terminal boxes on electric motors, cable
reel, electrical cabinets, light fittings, HID gas discharge lamp fittings or
the like.
• Check the condition of the drill rig's electrical devices regularly.
• Check the operation of the earth leakage control system from the gate
end panel weekly. If the control does not switch the power off, the control
system must be repaired or replaced before any device connected to it is
started.
• Fuses and the circuit breakers are protecting the wires and electrical
components against overheat and fire in case of overload and short
circuit.
• Breaker tripping or fuse burn is a sign of failure. Before resetting the
breaker or replacing the fuse the failure must be repaired. The original
fuse size and type must be used. Never replace the fuse with a fuse
having higher ampere value than the original.

38 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

Modifications to electrical systems

Electrical modifications to the drill rig require written permission


from Sandvik Mining and Construction Oy's electrical design
department to ensure the correct operation of the modified device.

• When replacing any electrical components or wiring, always use original


parts of original equipment manufacturer and use the correct installation
and testing procedure before operating the machine. All changes or
corrections should be documented for future reference.
• Current settings of circuit devices such as overloads, circuit breakers and
other protective devices shall only be set to the specifications of original
equipment manufacturer.

Replacing the light bulbs

WARNING! ELECTRIC SHOCK HAZARD!


Failure to follow these procedures could result in severe injury!
Cut the supply voltage to the light using the main switches before
replacing the bulbs of the working and driving lights.
Exercise extreme caution when performing work on HID gas
discharge lamps. The light components include high voltage parts.
• Note that parts of the light may be hot after use, so allow it to cool before
commencing repair work.
• The bulbs of gas-discharge lamps are gas-filled, so handle with care.
Use gloves and safety glasses.
• Do not touch the lamp holder or the glass part of the bulb when carrying
out the replacement.
• Use proper servicing stands when changing the light bulbs.
6.1.2. Checking connections and contacts (110 VAC - 1000 VAC)

Components:
• slip ring unit
• main cabinet (main switch, motor contactors and breakers, transformers)
• electric motors
• sockets
• cabin heater
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.

Copyright © Sandvik Mining and Construction 39


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

6.1.3. Checking connections and contacts (24 VDC, battery system)

Components:
• battery
• battery isolation switch and breaker
• diesel engine starter motor and generator
• glow plugs
• driving panel.
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.
6.1.4. Checking control system

Components:
• solenoid valve connections.
Check:
1. Component wire connections for overheating and corrosion.
2. Tightness of component wire connections (bolts and nuts) using tools.
3. Sealing and insulations for signs of overheating/ageing.

6.1.5. Checking the operation of the fault current protector switch

Check the operation of the fault current protector switch in the main
switchgear door. Repair/replace the switch if necessary.
6.1.6. Checking the condition of the power supply cable

Pull the power supply cable out and check it for wear, cuts and overheating/
ageing.
The use of machine is prohibited if the cable is damaged. Replace
damaged cable immediately.
6.1.7. Checking the water drainage holes

Check that the water drainage holes are open. Open the drainage holes if
necessary.

40 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

6.1.8. Checking the seal bushings

Check the seal bushings condition and tightness. Replace/tighten the


bushings if necessary.
6.1.9. Checking the motor terminals

Check the tightness of the motor terminals and other screw-mounting


terminals in the main switchgear and in the control system. Tighten the
terminals if necessary.
Apply corrosion prevention grease (ID 86742989) to all connections to
ensure conductivity.

Copyright © Sandvik Mining and Construction 41


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

6.1.10. Cleaning electric devices

DANGER
ELECTRICAL HAZARD!
Electric shock will cause death or severe injury.
Ensure that all the devices are in proper condition before cleaning.
Do not clean damaged or broken devices.

1. Switch off the main power and unplug the machine from a power source
before cleaning.
2. Clean devices more frequently than at the specified interval, if required.
Devices cleaned using water:
• cables and harnesses
• solenoid valve connections
When cleaning using water, flush components with water. Do not use
high-pressure washer.
Devices cleaned using compressed air or anti-static (ESD) brush:
• slip ring unit
• main cabinet (main switch, motor contactors and breakers)
• electric motors
• sockets
• cabin heater
• battery
• battery isolation switch and breaker
• diesel engine starter motor and generator
• glow plugs
When cleaning using compressed air or anti-static (ESD) brush, blow or
brush dust and debris off the components carefully.
Devices cleaned using cleaning cloth (or compressed air).
WARNING! HAZARD OF UNEXPECTED MACHINE MOVEMENT!
Ensure that the main power is switched off when cleaning cabin/
canopy controls and panels to avoid unexpected movement of the
machine.
• cabin/canopy controls and panels
Wipe surfaces clean with a damp cloth.

42 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

7. ELECTRIC SYSTEM REPAIR


7.1. Procedures after a long period out of use
• Check the electric cabinets and boxes for condensate water. Wipe off
any moisture.
• Check the insulation resistance at the supply cable end with the main
switch in position I. Also check the insulation of the electric motors.
• Check the contactors of the plug connectors for oxidation. Clean and
protect with grease as necessary.

7.2. In connection to repair


If you have to replace components in the electric control system (24 V) or
remove protective agent, always apply protective agent to the connections
when you have finished the repairs: protective grease for plug-in
connections, such as multi-pole connectors and valve connectors, and
protective coating for screw connections.
• Protective grease ID - 867 429 89, multi-pole connectors

Copyright © Sandvik Mining and Construction 43


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

This page is intentionally left blank

44 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

8. MSE ELECTRIC SYSTEM TROUBLESHOOTING


8.1. Troubleshooting
8.1.1. Powerpack does not start or stops

• Make sure that the main switch is on.


• Check the indicator lights.
• Water pump or compressor is running.
• If the voltage meter does not show any reading, check the protector
switch F311.
• Check the circuit breaker F310 for the 220-240 V control voltage.
• If the indicator light H617 is not lit, check the protector switch F320 of the
24 VDC feed transformer, and the circuit breaker F450.
8.1.2. Powerpack starts, but stops after a while

• Compressor air temperature rise above 115 °C or compressor- or water


pump motors are overload. In this case all motors stops and indicator
light H604 goes on. Fault goes off when temperature is under 115 °C and
compressor- and water pump circuit breakers are on.
• Hydraulic oil tank temperature rise above 75 °C. After that power packs
stops and indicator light H610 goes on. Fault goes off when temperature
is again under 75 °C.
• The "shank lubrication oil level low" monitoring lights up indicator light
H608. In AUS rigs the "shank lubrication oil level low" signal also stops
all powerpacks (a 3-second delay). You can restart the powerpacks only
when you have added SLCU oil.
• Hydraulic oil level drops (over 3 seconds) below the minimum. Indicator
light H602 goes on. Press pressure switch reset buttonS505 (indicator
light H602 goes off), after that powerpacks can be restarted (if oil level is
above the minimum oil level).
8.1.3. Powerpack main contactor clapping

• Power supply network too weak. Check the supply voltage and the
dimensioning of the supply network, the cross-sectional area and length
of the supply cable.
• Check the control voltage.
8.1.4. Working lights do not work

• Working light bulb burnt.


• Lightning plug off.
• Check the working lights conductor protective switches F450, F452.1,
F452.2, F452.3 and F452.4.
• If the lighting transformer is overloaded (too hot), the thermal protector of
the transformer switches lighting off. The protector resets automatically
as the transformer cools down. Check the reason for overheating.
• Control circuit fault

Copyright © Sandvik Mining and Construction 45


ID: BG00203315 A.1 2013-09-11
380-690 V electric system - NC7 series, DD531, DT821

8.1.5. 220-240 V 1-phase socket outlet does not work

• Too great load


• Check the protective switch F250 of the socket outlet transformer.
• Check the circuit breaker F252 of the socket outlet terminal, and the fault
current protector switch F251.
• If the socket outlet transformer is overloaded (too hot), the thermal
protector of the transformer switches the socket load off. The protector
resets automatically as the transformer cools down. Check the reason for
overheating.
• Control circuit fault
8.1.6. Oil filling pump does not work

• Oil tank is full.


• Check conductor protective switch F454.2.
• Check the control circuits and the wiring.

46 Copyright © Sandvik Mining and Construction


ID: BG00203315 A.1 2013-09-11
www.sandvik.com
Original instructions
BG00245302 A.001.1 2014-06-24

Electrical drawings; reading and


symbols
Electrical drawings; reading and symbols

WARNING
IGNORING INSTRUCTIONS HAZARD!
To avoid death or injury you MUST read, understand and follow
operator's and maintenance manuals before installing, inspecting,
operating, servicing, testing, cleaning, transporting, storing,
dismantling or disposing of the product or a part or accessory of the
product.

Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

This page is intentionally left blank

Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

Table of Contents

1 Introduction ................................................................... 7
1.1 The Purpose of these instructions ......................................................7
1.1.1 Validity of the manuals ................................................................ 7

2 Instructions ....................................................................9
2.1 Symbols .................................................................................................9
2.2 Searching of spare part items using the schematics ........................15
2.3 Wire color abbreviations ......................................................................16
2.4 Identification marking of drawing sheets ...........................................17
2.5 Identification marking of components ................................................22
2.6 Cabling ...................................................................................................23
2.7 Can bus ..................................................................................................24

Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

This page is intentionally left blank

Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

1 INTRODUCTION
1.1 The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1 Validity of the manuals
This manual, and especially the safety information, is valid only if no
unauthorized changes to the product are made.
Continuing improvement and advancement of product design might have
caused changes to your product which are not included in this publication.
Note also that if a third party has made changes to the product after
delivery from the manufacturer, this publication does not include
information on these changes or their influences on the product.
Whenever a question arises regarding your product, or this manual, please
consult your local Sandvik representative for the latest available
information.

Copyright © Sandvik 7
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

This page is intentionally left blank

8 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2 INSTRUCTIONS
2.1 Symbols

voltmeter ammeter

+
h hour meter digital volt meter
-

control by flow manual operated control

emergency switch operated by turning

operated by pushing control by fluid level

operated by lever operated by key

control by temperature operated by pressure

operated by pressure
make contact
differential

change over break before


break contact
make contact

two-way contact with center- make change-over contact


off position delayed when reclosing

Copyright © Sandvik 9
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

make change-over contact


make change-over contact
delayed when closing and
delayed when closing
reclosing

position switch with positive


position switch, make
opening operation of the
contact, mechanically
break contact, mechanically
operated in both directions
operated in both directions

self operating thermal switch,


contact of a thermal relay
break contact

circuit breaker limit switch, make contact

multi-position switch, two multi-position switch, three


positions, locking positions positions, locking positions

multi-position switch,
automatic return to middle three phase circuit breaker
position

terminal plug

socket slip ring unit

crossing wires (no


junction of conductors
connection)

frame earth
chassis ground

operating device of relay relay coil of a slow-operating


(relay coil) relay

10 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

relay coil of a slow-releasing


step relay
relay

signal relay thermistor relay

phase sequence relay with


phase sequence relay
aux.power

actuating device of thermal


contactor
relay

solenoid valve proportional solenoid valve

valve with signal light and proportional valve with signal


protection unit light and protection unit

direction valve with signal


DC converter
light and protection unit

rectifier
battery charger current transformer
AC/DC converter

resolver led

signal lamp beacon

Copyright © Sandvik 11
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

working light positioning laser

P 250ba r I

I 4--20mA pressure transducer U linear sensor

proximity switch generator

dc motor three phase induction motor

battery (accumulator) or battery (accumulator) or


primary cell primary cells

resistor variable resistor

resistor with sliding contact


heating resistor
(potentiometer)

voltage depended resistor


U thermistor sensor
varistor

capacitor diode

inductor
coil fuse
winding choke

horn buzzer

12 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

cross-reference, position
from which the line
cable reel
continues / position to which
the line continues

fault current protection


rotary encoder
switch

three phase transformer with three


phase rectifier (example)

switch with start contact

Copyright © Sandvik 13
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

transformer (example)

Can module contact


Signal types:
DI = digital input
DO = digital output
AI = analog input
PWM = pulse width modulated
FB = feedback
GND = ground
REF = reference voltage

14 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2.2 Searching of spare part items using the schematics


1. Find the needed component using the schematics. (In this example the
relay K13 has to be replaced.)

2. Find the location of the component from the Position field.


The relay K13 is located in electrical cabinet MP.
3. Find the relay K13 from MP's layout picture.

4. Find the reference number(s) of the K13 relay. (The reference number is
the same for the other similar relays.)
K13's reference numbers are 64 and 65.

Copyright © Sandvik 15
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

5. Find the reference number(s) from the parts list.

K13 relay's part number is 888 152 09 and the relay socket's part number
is 888 153 29.

2.3 Wire color abbreviations


Color Abbreviation
Black BK
Brown BN
Red RD
Orange OG
Yellow YE
Green GN
Blue BU
Violet VT
Grey GY
White WH
Pink PK
Turquoise TQ

16 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2.4 Identification marking of drawing sheets


DescriptionsField descriptions

4 3 1 7 2 5 6

1 DPi Name of the equipment


Default position of a component
2 Position : MP
on page
Sandvik DPi Carrier Circuit
3 Drawing name
Diagram
SAFEMATIC CENTRAL
4 Page name
LUBRICATION
5 Sheet 25/35 Page/amount of pages
6 DWG NR 3-55078370-L Drawing number - Revision
ID-Code: refers to drawing
7 ID-Code
number

Copyright © Sandvik 17
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

Components in the main units

3 2

18 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

The default location (in the rig) of the components on


1 CARRIER
this sheet.
2 +MP The component is inside of the MP unit.
The component is inside of the PPC component
3 -PPC
(which is inside of the MP unit).

Forming the name of a connector pin

Copyright © Sandvik 19
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

Cross-references

20 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

Cross-References of a component

1 Relay coil
2 Relay contacts
• Relay contacts are shown at the bottom of the sheet below the relay coil.
• The cross reference at the side of the relay contacts (below the coil) tells
the location of the actual relay contacts.
• The cross reference at the side of the actual relay contacts tells the
location of the relay coil.

Copyright © Sandvik 21
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2.5 Identification marking of components

1 2 3

4
6
5 7

1 Connector pin number 2 Connector identification


3 Component identification 4 Wire number
5 Wire color 6 Cable identification
7 Component specifications 8 Terminal
9 Terminal block

22 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2.6 Cabling

1 Connection to subsystem 2 Cable type


3 Cable identification 4 Component identification
5 Dashed line = Option 6 Component identification

Copyright © Sandvik 23
ID: BG00245302 en-US A.001.1 2014-06-24
Electrical drawings; reading and symbols

2.7 Can bus

1 3 5

An example of can bus wiring


1 Vcc
2 Can low
3 Ground
4 Can high
5 Shield (ground)

24 Copyright © Sandvik
ID: BG00245302 en-US A.001.1 2014-06-24
www.sandvik.com
Original instructions
BG00210741 A.1 2013-09-10

Electric motor
Electric motor

Table of Contents

1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1

2. Electric motor operation ...............................................3


2.1. Check the coil insulation resistance ...................................................3
2.2. Performing the inspection ................................................................... 3
2.3. Drying the coil .......................................................................................3

3. Electric motor maintenance ......................................... 5


3.1. General maintenance instructions ......................................................5
3.2. Alternating-current motor maintenance ............................................. 6
3.2.1. Lubricating the bearings .............................................................. 7
3.3. VEM motors maintenance ....................................................................7
3.3.1. Bearings and lubrication ..............................................................8
3.3.2. Slide-contact system ................................................................... 10
3.3.3. Draining condensed water ...........................................................10
3.3.4. Cleaning ...................................................................................... 11
3.3.5. Motors with thermal-protected winding ........................................11

Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

This page is intentionally left blank

Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals

This manual, and especially the safety information, is valid only if no


unauthorized changes to the product are made.
Continuing improvement and advancement of product design might have
caused changes to your product which are not included in this publication.
Note also that if a third party has made changes to the product after
delivery from the manufacturer, this publication does not include
information on these changes or their influences on the product.
Whenever a question arises regarding your product, or this manual, please
consult your local Sandvik representative for the latest available
information.

Copyright © Sandvik Mining and Construction 1


ID: BG00210741 A.1 2013-09-10
Electric motor

This page is intentionally left blank

2 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

2. ELECTRIC MOTOR OPERATION


2.1. Check the coil insulation resistance
If the motor has been in storage for a long time, the coil insulation
resistance must be checked before installation.

2.2. Performing the inspection


The insulation resistance is checked using an insulation resistance meter
(megger). Before the inspection, all bridges and/or connections between
connectors must be removed from the terminals. The size of the insulation
resistance meter depends on the nominal voltage of the motor in question.
When the nominal voltage is max. 660 V, the insulation resistance must be
at minimum:
R = 1000*U (Ω), where R = insulation resistance, U = nominal voltage (V).
However, in order to protect the motor and equipment, the value must not
fall below the following minimum values:
R when warm = 2 MΩ
R when cold = 5 MΩ
If the measured value is below the above-mentioned minimum values, the
coil must be dried.
If the effects of moisture are externally visible on the motor, drying must be
started immediately. Never check the coils before the motor is dry, as this
can cause damage to the insulation.
A detected ground short circuit must be repaired by a qualified repair shop.

2.3. Drying the coil


The coil's drying method depends on the size of the motor and local
conditions. Fully-closed motors must be disassembled enough to allow
moisture to evaporate from the coils. Evaporation must be ensured with
sufficient ventilation of the premises.
The maximum drying temperature must not exceed 90 °C. The drying time
is thus 8 to 20 hours depending on the motor size and the amount of
moisture.
The following drying methods have proven effective:

Oven drying
Oven drying is suitable for motors of max. 75 kW depending on the oven
size and structure. The oven temperature must be adjustable, and the heat
must affect all parts of the motor evenly. This method is recommeded for
use whenever possible.

Copyright © Sandvik Mining and Construction 3


ID: BG00210741 A.1 2013-09-10
Electric motor

Drying in a heated closed space:


This method is suitable for all motors. The drying time is defined by the size
of the space. As the room temperature can generally not be raised higher
than 50 °C, even when using additional heating devices (electric heaters),
the drying process lasts longer than oven drying. Care must be taken when
placing heaters in the vicinity of motors, as local temperatures exceeding
90 °C can damage the coils.
The coil's insulation resistance must be measured again after drying. If the
minimum value is still not reached, the drying process must be repeated.

4 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

3. ELECTRIC MOTOR MAINTENANCE


3.1. General maintenance instructions
Motor maintenance also includes regular general cleaning and checking
every one to two years so that possible defects are detected before any
serious damages develop. The free flow of cooling air must be ensured in
all situations.
Because dirt and dust deposits in the motor frame and winding significantly
prevent the dissipation of waste heat, and corrosive dust and oil may cause
solution of the coil insulation, the cleaning intervals are defined according to
the motor's protection class and the local conditions of use.
Extra care must be taken when cleaning the coils. Never clean with sharp
or hard objects, or with compressed air containing water. Remove dry dust
by blowing with compressed air. Wipe away greasy deposits using a
volatile, incombustible solvent. Do not allow the solvent to remain in contact
with the insulation for long periods, as it can damage the insulation.
Check the fastening of the coil ends and their bindings after cleaning the
coils. Faulty or loose items must be repaired/replaced as necessary.
When cleaning the stator coil, clean also the entire motor frame and
especially the cooling ribs and the air channels.
The inner parts of the installation box and terminal boards must also be
cleaned. Dust deposits can cause surface leakage between the connectors
in the terminal boards, thus causing spark-overs. After cleaning the terminal
board is using a brush and compressed air, check the connector
fastenings. Repair if necessary.

Copyright © Sandvik Mining and Construction 5


ID: BG00210741 A.1 2013-09-10
Electric motor

Motors with TWS protection against overheating of windings


The connectors intended for the overheating protection of windings must be
joined to the tripping device according to the wiring diagram data in the
Technical bulletin TI W 111.13.6 and in the installation box, and the
manufacturer's instructions.
Note! The manufacturer of the electric motor has inspected the capacity
and maximum voltage of the temperature sensors installed in the
motor. However, if the user of the electric motor wishes to carry out
inspection measurements, the following must be taken into
consideration: Use of a monitor lamp, insulation resistance meter
(megger) or similar device to check the current flow of the
temperature sensor circuit is strictly forbidden – doing so will
damage the sensor!

The inspection can be carried out by measuring the cold resistance of the
temperature sensor circuit at room temperature (approx. 20 °C). The
voltage in the sensors cannot exceed 0.8 V. It is recommended that a
Wheatstone bridge be used in the measurement, and a supply voltage of
4.5 V. If the circuit has three functioning overheating protectors in a series,
the cold resistance of the circuit is 90 to 300 Ù. Measuring the warm
resistance is not necessary.
When measuring the maximum voltage of the temperature sensors and the
insulation resistance between temperature sensors and coils, the
inspection voltages specified in the DIN/VDE 0530 standard must be used,
and the wires leading away from the sensor circuit must be short-circuited.
Failure to do so will damage the sensors.

3.2. Alternating-current motor maintenance


Alternating-current motors have few wearing parts, so they need minimal
maintenance. However, the operation of the motors in normal use must be
checked regularly; if disturbances are detected early, more serious motor
damages can be avoided.
Generally, the only maintenance tasks include checking the operation of
roller bearings, and ensuring sufficient lubrication.
Motor equipment includes connection and adjustment devices which must
also be checked.

6 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

3.2.1. Lubricating the bearings

The condition of the roller bearings is checked by listening to their running


noise. This can be done using a stethoscope or an elongated metal object,
such as a screw driver. If the bearings are in good order, their running
noise is relatively strong and even.
The sound of insufficiently lubricated bearings resembles a high-pitched
squeak. Grinding and hacking noises are a sign of fatigue or that there is
dirt in the bearings. In these cases, the bearing must be replaced. When
replacing and greasing bearings, roller bearings must always be protected
from dust and moisture, as even small dirt particles can damage the
bearing surfaces.
After initial start-up, when the motor is running squeaze grease into the
lubrication nipple until excess grease exudes from it.

Lubrication VEM Strömberg


Lubricant amount (g) 100 25
Lubrication interval (operating hours) 2000 2500

Lubricants
The original lubricant is Klüber Quiet BQ 72--72.
The bearings must be lubricated with original lubricant. When using
lubricants of other known lubricant manufacturers, ensure that the new
product corresponds fully with the original lubricant. In favourable operating
conditions the lubrication intervals may be increased, but the grease quality
must be monitored regularly.
The lubricant used for servicing must be polycarbodiimide-based, as this
enables use of the lubricant in temperatures as high as 180 °C.
Note! Spare motors must be lubricated upon initial start-up, ensuring that
all grease channels are full.

3.3. VEM motors maintenance


When starting maintenance, the motor must be connected when dead, and
reconnection must be prevented in accordance with the safety instructions.
It must also be checked that there is no voltage in any of the parts
connected to the voltage source. If the motor is disconnected from the
mains for the duration of maintenance work, ensure that all possible
auxiliary circuits (e.g., anti-condensation heaters, external fans, brakes) are
also disconnected from the mains.
If the motor must be disassembled for maintenance work, remove the
sealing compound from the centering shoulders, and re-seal the motor with
a suitable sealing compound during assembly. Always remember to re-
install the copper seal rings.

Copyright © Sandvik Mining and Construction 7


ID: BG00210741 A.1 2013-09-10
Electric motor

3.3.1. Bearings and lubrication

The roller bearings of standard-type motors are pre-lubricated at the factory


(manufacturer-lubricated sealed bearings). The bearing grease meets the
requirements set by the DIN 51825 standard according to the following
table.

Lubricant grease Base substance of


Motor type
according to DIN 51825 : lubricant
All short-circuit asynchronous
Asonic GLY 32 or Multemp
motors IEC / DIN 56 - 132 T, Lithium
SRL
Transnorm 56 - 100
Short-circuit motors, motors
IEC/DIN 132 - 355, and
Transnorm 112 - 315 Short-
circuit motors IEC/DIN 132 - 355,
KE2R - 40 Polycarbodimide
and Transnorm 112 - 315 Motors
with external ventilation. Brake
motors, Motors with a slip-ring
rotor, IEC/DIN and Transnorm

With this grease type, the motor can be run at normal loads and in normal
operating conditions for approximately 10 000 operating hours (two-pole
design motors) or 20 000 operating hours (four or multipole design motors)
without having to change the roller-bearing grease (unless otherwise
specified). However, the condition of the grease must be checked
periodically prior to the specified service interval. The stated operating hour
interval only applies when the motor is run at nominal speed. If the nominal
speed of the motor used by the frequency converter is exceeded, the
regreasing interval decreases approximately in reverse ratio to the increase
in rpm.
The bearings must be thoroughly cleaned using a suitable solvent before
regreasing. Use the same single grease quality for the lubrication.
Alternatively, the alternative qualities specified by the manufacturer may be
used. Note that the bearings can only be filled to a capacity of 2/3 of their
free volume. If the bearings and bearing caps are filled fully, the bearing
temperature rises and wear increases. In bearings with regreasing devices,
grease is added at a suitable amount for the motor in question via the
lubrication nipple while the motor is running. Refer to the regreasing
intervals in the table below.

Four and multipole


Size Two-pole design motor
design motors
112 - 280 2000 h 4000 h
315 2000 h 4000 h
355 2000 h 3000 h

8 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

The required grease amounts for regreasing are presented in the table
below (note that a double amount of grease must be applied for the first
commissioning regreasing, because the lubrication pipes will still be
empty). The waste grease gathers in the grease chamber of the external
bearing cap. The waste grease must be removed after approximately five
regreasing cycles, e.g., during a condition inspection.

Series, Frame size Length, Pole


Grease amount, cm³
increasing by standard number
D side N side
112 all 10 10
132 all 17 17
160 all 23 20
180 2 23 23
180 ≥4 31 31
200 2 31 31
200 ≥4 35 31
225 2 35 35
225 ≥4 41 35
250 2 41 41
250 ≥4 52 41
280 2 52 52
280 ≥4 57 52
315 VL S2 57 52
315 VL M2 57 57
315 VL S4, 6, 8 64 52
315 VL M4, 6, 8 78 57
355 2 57 57
355 4 90 57
355 6, 8 90 57

Length, Pole
Series, IEC/DIN Grease amount, cm³
number
D side N side
160 LX2, M2 23 20
160 L4, 6, 8 23 20
180 M2 23 23
180 M4, L6, 8 23 20

Copyright © Sandvik Mining and Construction 9


ID: BG00210741 A.1 2013-09-10
Electric motor

Length, Pole
Series, IEC/DIN Grease amount, cm³
number
180 L4 23 23
200 L2 - -
200 LX2 31 31
200 L4, 6, 8LX 6 31 23
225 2 31 31
225 M4, 6, 8S4, 8 35 31
250 M2 35 35
250 M4, 6, 8 41 35
280 2 41 41
280 ≥4 52 41
315 2 52 52
315 ≥4 57 52
315 MX2 VL 57 52
315 MY2 VL 57 57
315 MX4, 6, 8 VL 64 52
315 MX4, 6, 8 VL 78 57

3.3.2. Slide-contact system

The slide-contact system must be inspected periodically. The slip rings


must be checked two to three times immediately after commissioning, at
approximately 50 operating hour intervals. After this, maintenance must be
carried out regularly, the maintenance intervals depending on the specific
operating conditions. A thin patina layer should form on the surface of the
slip rings. Normally, the patina forms during 100 to 150 operating hours. If
deep grooves or burn marks appear on the slip-ring surfaces, they must be
cleaned or, if necessary, machined even again.
Small grooves do not require machining. The pressure of the carbon
brushes must be checked. The pressure should be between 18.5 to 24
kPa. Always use the same brush brand when replacing the brushes. New
carbon brushes must be ground to shape. Take care with box-type brush
holders that the carbon brushes do not get jammed due to dirt. Carbon
brushes wear naturally with use. The rate of wear is between 3 to 5 mm per
1000 operating hours.
3.3.3. Draining condensed water

In favourable conditions for dew formation, condensed water accumulated


on the inner parts of the motor must be drained regularly through the
condensed-water draining opening at the lowest point of the bearing end-
shield. After draining, close the opening.

10 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
Electric motor

3.3.4. Cleaning

To ensure efficient cooling, all motor parts must be cleaned regularly.


Blowing the parts clean with compressed air without water and oil is usually
sufficient. In particular, the ventilation holes and gaps between fins must be
kept clean. Carbon dust resulting from natural wear collects in the inner
space of the motor, and must be removed periodically. It is also
recommended to check the electric motors when performing a periodic
check of the rig.
3.3.5. Motors with thermal-protected winding

It is strictly forbidden to check the penetrating power of sensor circuits


equipped with PTC resistors by using a testing lamp, an insulation meter or
a corresponding device, as this will cause immediate damage of the
sensors. If cold-resistance after-measurement (at approx. 20 °C) is needed,
the measuring voltage must never exceed 2.5 V (DC). It is recommended
that a Wheatstone bridge with a supply voltage of 4.5 V (DC) is used for the
measurement.
The cold resistance of the sensor circuit must never exceed 810 ohms.
Measuring the hot resistance is not necessary. With motors equipped with
thermo-protected winding, ensure that accidental automatic starting due to
the detection time of the winding's thermo protection and consequent
cooling of the motor does not cause any danger.

Copyright © Sandvik Mining and Construction 11


ID: BG00210741 A.1 2013-09-10
Electric motor

This page is intentionally left blank

12 Copyright © Sandvik Mining and Construction


ID: BG00210741 A.1 2013-09-10
www.sandvik.com
Original instructions
BG00245288 A.1 2013-07-11

Protecting electrical and electronic


components and connectors with
protective agents
Protecting electrical and electronic components and connectors with
protective agents

Table of Contents

1. Introduction ................................................................... 1
1.1. The Purpose of these instructions ......................................................1
1.1.1. Validity of the manuals ................................................................ 1
1.2. General notes ........................................................................................1

2. Instructions ....................................................................3
2.1. Connectors which are not to be protected .........................................3
2.2. Wax-like protective agent (Pentisol 710) ............................................ 5
2.3. Protective agent (CRC 2-26) ................................................................ 8
2.4. Protective grease (Ensto SR1) ............................................................ 10
2.5. Removing protective agents ................................................................11
2.6. Example housing corrosion protection ..............................................12

Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

This page is intentionally left blank

Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

1. INTRODUCTION
1.1. The Purpose of these instructions
This manual contains supplementary information for operation,
maintenance and repair of a component.
Before operating, or performing maintenance or repair procedures for the
component or system described in this manual, read and understand the
information in operator´s and maintenance manuals supplied with the
machine. Pay special attention to the safety information in chapter "2 Safety
and environmental instructions" of those manuals.
1.1.1. Validity of the manuals

This manual, and especially the safety information, is valid only if no


unauthorized changes to the product are made.
Continuing improvement and advancement of product design might have
caused changes to your product which are not included in this publication.
Note also that if a third party has made changes to the product after
delivery from the manufacturer, this publication does not include
information on these changes or their influences on the product.
Whenever a question arises regarding your product, or this manual, please
consult your local Sandvik representative for the latest available
information.

1.2. General notes


These instructions are applied to the electrical systems designed by the
Sandvik Mining and Constructions UG electrical design department.
Instructions specify the corrosion protection procedures performed for
electrical components and connectors with protective agents.

Protective agents
1. Wax-like protective agent (Pentisol 710)
• Protective agent for fixed connectors, metal components, and cable
components.
2. Protective spray (CRC 2-26)
• Light corrosion protection for less-demanding applications which do
not withstand protective grease.
3. Protective grease (Ensto SR1)
• For protecting plug connector contacts.

Copyright © Sandvik Mining and Construction 1


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

Definitions of items to be protected


A device containing electronic components, in which the
Module components and circuit board, with the exception of the
connector interface, are protected with, e.g., housing.
A device – normally rack-mounted – containing
electronic components, and in which the components
Card
and circuit board are in the open, protected only with
lacquer coating.
A device in which the electronic components and circuit
PLC
board are lightly protected (plastic casing).
Enclosed electrical assembly with user interface
Panel components (e.g., joystick or display) installed in the
cover.
Enclosed, distribution-box type assembly containing
Box
unprotected components.
Enclosed electrical assembly with unprotected
Switchgear
components which can cause sparking or heat up.
Assembly which includes a cable or protected wire set
Cable harness
connected at least to one plug connector.
A sensor or actuator (e.g., valve, electric motor) that has
Sensor or
internal electrical connection and possibly electronic
actuator
components which are protected with housing.

2 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

2. INSTRUCTIONS
2.1. Connectors which are not to be protected
• Connectors of card rack motherboards.

Figure: VME rack motherboard.

• Connectors of card motherboards.

Figure: Card motherboard connectors.

• Connectors on the card front.

Figure: VME card front plate (CPU and CAN).

Copyright © Sandvik Mining and Construction 3


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

• USB and RJ45 bus connectors.

• Any TCAD/TDATA main computer connertor

Figure: TCAD/TDATA PC.

4 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

2.2. Wax-like protective agent (Pentisol 710)


Preparations
• Set all jumper connectors, and program and and install all programmable
circuits in their sockets.
• Set any trimmers, DIL switches, and all other adjustable components to
the correct settings.
• Cover any sockets in which components may be later installed in
accordance with separate instructions.
• Attach the identification labels and protect them with tape.
• Protect the edges of the rack-installed cards as well as motherboard or
bus connectors with tape.

Copyright © Sandvik Mining and Construction 5


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

Items to be protected
• Terminal strips (NOT spring-clamp types) in boxes are to be protected
after connection. Typically, this is done during final assembly. If the box
contains components which can fail, e.g., relays, use CRC 2.
• After connecting the cable harnesses, protect the interior of the metal
plug connector housings (Harting).
Note! Protect mounting screw threads and screw joints with protective
grease.

Note! Pentisol is not to be used for Harting DD model.

Figure: Metal multi-pole connector.

• Battery connectors.
• Servo and R/D cards of TMS, TCAD, and TDAT jumbos.
Note! PC104 card pack of TCAD is not to be protected with Pentisol.

Figure: TCAD/TDAT card.

How protection is performed


• Spray a thin coating over the area to be protected.
• Prevent the protective agent from getting onto the contact surfaces of
connectors and sockets as instructed in the preparation instructions.

6 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

After protection
Allow the wax-like protective agent to dry at room temperature for at least 8
hours before packing in a VO package, or so that it does not drip before
installing electronic components. Ensure also that the protective agent is
not so wet that it sticks to the antistatic material of the package.
If necessary, wipe the edges of the rack-installed cards clean to make
installation and removal easier after protection.
Allow the metal multi-pole connectors to reach non-drip dryness.
Note! Terminal strips in switchgears are NOT to be protected with
protective agent since it contains solvents that require a drying time
of 24 hours at a temperature of 20 °C; the drying time is longer at
lower temperatures.

Solvent fumes are explosive in confined spaces! (e.g., in a


switchgear).

Copyright © Sandvik Mining and Construction 7


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

2.3. Protective agent (CRC 2-26)


Items to be protected
• PLC components (CPU, power supply, I/O units, EEPROM,
motherboard) without disassembling the housing. See exceptions for IO
connector protection.

Figure: PLC assembled.

• Power supplies, i.e., cards that generate a lot of heat.

Figure: Typical card power supply.

• Interior of Harting DD models (housing protected with Pentisol).

8 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

CRC

• Terminal strips in switchgears.


• Spring-clamp terminal strips.

How protection is performed


Spray a thin coating over the entire area to be protected, including the
connectors. Wipe off any excess agent.

Copyright © Sandvik Mining and Construction 9


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

2.4. Protective grease (Ensto SR1)


Items to be protected
All plug connectors and their metal screw threads that are not mentioned in
Sections 2.1, 2.2 and 3. Plug connectors whose contacts are to be
protected with SR1grease include, for example: Harting, DinA, M12, Junior
Timer, Deutch, Hummel, Omron IO, 230 V (or higher) power connectors,
Canon MIL connectors, and cable reel connectors.
• The threaded section of the Hummel connectors is to be lubricated with
grease before the connector is screwed on.

• PLC's I/O connector (screw terminal and underside) and the connectors
between units.

Figure: PLC's IO connector.

Note! Connectors of VME cards on Solo rigs are not to be protected with
SR1 grease.

10 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

How protection is performed


Squeeze a small amount of protective grease onto the male connector only
(remove excess grease, e.g., with a small brush). Insert the male connector
treated with grease a couple of times into the corresponding female
connector to apply the grease to its contacts. Next, connect the screw-on
connectors and ensure that they are properly connected. Remove any
excess grease.
Grease treatment example:
• The M12 connectors are protected with a special grease applicator
constructed from connector 55031363. Drill 3 holes of 1.5 mm through
the bottom of the connector to allow excess grease to escape from the
connector to be treated through the tool. Grind off the connector's thread.

Note! Do not over fill the connectors with grease since excess grease can
cause contact faults and/or mechanical damage to the connector!
Always remove excess grease from the connectors after protection.

2.5. Removing protective agents


Protective agents can be removed with a suitable solvent, e.g., electrical
cleaner. Avoid using highly alkaline cleaners.

Copyright © Sandvik Mining and Construction 11


ID: BG00245288 A.1 2013-07-11
Protecting electrical and electronic components and connectors with
protective agents

2.6. Example housing corrosion protection

Pentisol

Pentisol SR1 SS bolts:


NOTE: CRC 2 SR1 to
CRC 2 for threads
spring
clamp

Sealing Breather
surface

SR1
Water hole SR1

12 Copyright © Sandvik Mining and Construction


ID: BG00245288 A.1 2013-07-11
www.sandvik.com

You might also like