DIGSI4 Process Data Analysis

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Sigra 4

© Siemens AG 2008
Energy Sector
SIGRA 4 - Process Data Analysis

 Representation of indications and measured values


 Retrieval of fault records with DIGSI 4
 The COMTRADE format
 Parameterization of fault record representation
 Definition of user profile
 Angle measuring
 Fourier analysis
 Impedance calculation
 Export of fault records

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Evaluation of Fault record

The following data are used for the evaluation:

 Measured values recorded in the device fault record

 Characteristics calculated by SIGRA 4, for ex. impedance

 Binary signals

 Data of other fault records for comparison

© Siemens AG 2008
Energy Automation Energy Sector
Generation of RIO-File in DIGSI 4 (Part 1)

Only relevant for distance


protection !

© Siemens AG 2008
Energy Automation Energy Sector
Generation of RIO-File in DIGSI 4 (Part 2)

Only relevant for distance


protection !

FALSE at I(nom) = 1A
TRUE at I(nom) = 5A

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Indication / Measured Value Indication

Evaluation of fault record data via the SIGRA 4 views:

 Time signal

 Vector diagrams

 Circle diagram

 Harmonic components

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Time Signal View

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Vector Diagram View

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Circle Diagram View

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Harmonic Component View

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Graphical Structure of a Fault Record

The graphical interface of a fault records consists of the


following:

 Views with as many diagrams as you like

 Diagrams with as many signals as you like

 Signals of any view and diagram


- analog signals
- binary signals
- status signals

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Diagrams / Signals

 Insert / Assign

 Copy

 Delete

 Define Properties

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Object Properties

Diagram properties

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Signal Assignment

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Structure of Fault Records

A fault record has the following components:

*.CFG - COMTRADE configuration file

*.DAT - COMTRADE file (measured values)

*.RIO - protection settings (optional)

*.DG4 - SIGRA 4 session connection memory

© Siemens AG 2008
Energy Automation Energy Sector
DIGSI 4 - Exporting of Fault Records

 Open Record Object

 Select Fault Record

 Open Export Dialog

 Define Export File

 Export Fault in the COMTRADE format

© Siemens AG 2008
Energy Automation Energy Sector
DIGSI 4 - Definition of Setting Values for
Fault Records

Open the Fault


Record dialog box
in the settings
mode

Set values

Transfer values
to device

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - The .dat Data File

0000000000,0000000000,-00118,000030,000084,000150,-00108,-00038,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 First set of data


0000000001,0000001666,-00126,000098,000024,000113,-00162,000052,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000002,0000003332,-00081,000114,-00035,000036,-00142,000110,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
0000000003,0000004998,-00024,000124,-00104,-00057,-00107,000168,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 The contents of the
0000000004,0000006664,000039,000080,-00120,-00115,-00030,000150,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 .DAT data files can be
0000000005,0000008330,000101,000026,-00129,-00168,000054,000117,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 viewed in the Text
Editor. The figures are
separated by commas.
The data file can be
0000000596,0000992936,000081,-00116,000029,-00039,000146,-00105,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0 edited in external
0000000597,0000994602,000022,-00125,000097,000054,000110,-00161,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0 programs like Excel.
0000000598,0000996268,-00037,-00086,000117,000113,000039,-00147,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000599,0000997934,-00101,-00030,000126,000166,-00050,-00116,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0
0000000600,0000999600,-00117,000027,000086,000149,-00104,-00043,0,0,0,0,0,0,0,0,0,0,0,0,1,0,0,0,0,0,0 Last set of data
Scanning value of the Value of the 19 binary
analog values (0 or 1)
Time scale in ms channels (analog
channel multiplied
by its factor)
Number of the scanning value

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Process Data Analysis

 Parameterization of fault records

 Definition of user profile

 Synchronization of fault records

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Measuring a Fault Record

Tools for fault record measuring:

 Zoom

 Table
- assignment of measured signals
- assignment of times

 Cursor behavior
- magnetic (on status signals) pointer
- snapping (on samples) pointer

 Status signals

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Parameterization of Fault Record

Parameterize
channels
(Network Nodes)

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Parameterization of Fault Record

Parameterize
Network Nodes

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - User Profiles

 Define and save

 Use

 Define assignment

 Delete

 Insert device type

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - User Profiles

Define
Save
Use
Delete

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - User Profiles

Assign

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Synchronization Procedure

 Insert comparison fault record B


 Insert empty diagram in the Time Signal view
 Insert signal of fault record A, for ex. phase voltage in
short circuit
 Insert comparison signal from fault record B
 Cursor position
- Cursor 1 on synchronous point signal fault record A
- Cursor 2 on synchronous point signal fault record B
 Select Synchronize Fault Records (menu command)
 Check synchronous points and displacement
 Trigger synchronization

© Siemens AG 2008
Energy Automation Energy Sector
SIGRA 4 - Dialog Box

© Siemens AG 2008
Energy Automation Energy Sector