013 Cat-6040AC CAMP-SIL-BCS4 Pressure Checking and Setting
013 Cat-6040AC CAMP-SIL-BCS4 Pressure Checking and Setting
013 Cat-6040AC CAMP-SIL-BCS4 Pressure Checking and Setting
Fig. 1 6422670
8.6.3 Tools
For pressure checking and setting the tools listed in table 2 are required.
Fig. 2 630640
1 2 Test kit with gauges and hoses (see chapter 3.2 „Tools“) 1 476 323
2 1 Test adapter for proportional valve 1 433 919
3 1 Multimeter 1 088 932
4 1 O/E-ring spanner, 10 mm 0 717 903
5 1 O/E-ring spanner, 13 mm 0 559 698
6 1 O/E-ring spanner, 17 mm 0 559 702
7 1 O/E-ring spanner, 19 mm 0 717 908
8 1 O/E-ring spanner, 24 mm 0 717 913
9 1 Allan Key, 3 mm 0 014 122
10 1 Allan Key, 4 mm 0 014 123
11 1 Allan Key, 5 mm 0 014 124
12 1 Allan Key, 6 mm 0 014 125
13 1 Accumulator test and charging device 1 438 546
---- 1 Adapter for nitrogen cylinder (see chapter 3.2 in THB)
Table 2
Fig. 3 642680
Primary relief valves for pilot pressure pumps Auxiliary pressure 1 of 50 bar
6A (90 bar) and 6B (60 bar) 10. With service switch S31 (Fig. 5) deactivated,
1. Connect pressure gauges to test points M1 check the pressure at test point M3,
(range up to 150 bar), M2, M3 and M4 (range required value: 50 bar. If necessary adjust
up to 60 bar, Fig. 4 & 5) for the pilot pressure valve 1.30 (Fig. 6).
system.
2. Open valves PRV-6A and PRV-6B (Fig.4)
completely, to prevent pressure peaks during
start up.
3. Start electric motor.
4. Check the pressure at test points M1 and M2.
Required value: ~ 0 bar.
5. Screw the adjuster of valves 1.10; 1.11; 1.20
and 1.30 (Fig. 6) completely in and then ¼
turn back.
This is to avoid any influence of these valves
while setting PRV-6A and PRV-6B.
6. Adjust a pressure of 90 bar at relief valve Fig. 5 642665
PRV-6A
Check the pressure at test points M1.
7. Adjust a pressure of 60 bar at relief valve
PRV-6B
Check the pressure at test points M2.
Fig. 6 642151
Gear pump 6B (Fig. 1) delivers the oil exclusively An electronic load limit system is installed to pre-
to the central greasing system. vent an overload of the motor.
The current from the electronic load limit system is
converted into hydraulic pressure by a proportional
valve (23, Fig. 8).
The pilot pressure of 35 bar is used for the follow-
ing functions: The proportional valve Y17 (23, Fig. 8), which is
linked to the load limit system of the electric
motor, delivers a pressure signal to port X1 on
- Supply of the proportional valves to control the the main pump regulators P1 to P4.
work functions. The pressure level is related to the load factor
- Displacement of the swing balance valve (Y1 / of the motor.
Y2). Pressure sensor B1 (Fig. 7 + 8) is installed to
monitor the control pressure.
The auxiliary pressure 1 of 50 bar is used for the
following functions:
- Servicelift
- Pressure increase of the main pumps for trav-
eling
- Travel motor speed control (2. travel speed)
- Releasing the swing parking brake.
3. Check pressure.
The gauge must indicate approx. 8 bar
(200 mA).
Fig. 8 642667
Fig. 9 630782
Note:
It is also possible to check and read the current
values via the BCS
Note:
Fig. 11 642668
Fig. 10 621211
Fig. 12 642144
3. Set primary relief valve (PRV 1) of pump P1: 4. Check primary relief settings for pumps P2, P3
& P4 in the same way.
When a new primary relief valve is installed
screw the adjuster 1 turn out, to avoid pressure
peaks.
Fig. 15 642078
Fig. 17 642668
2. Connect a gauge (range: 60 bar) to the test 6.2 If pressures are equal:
points (M5) in the supply line of swing balance
Replace the 400-bar gauges with 60-bar
valve (Fig. 20).
gauges (more accurate reading).
3. Switch on electric motor.
Do not operate the function 'swing'
4. Check pressure (rated: 35 bar). as this would destroy the gauges!
If required adjust pressure reducing valve
(112, Fig. 20) accordingly.
The charge pressure will be indicated. The
required value must be 25 bar.
Fig. 20 642681
Fig. 22 642674
Note:
Activate 'swing left or right' and move joy For cooling of the closed swing circuit a certain
stick slowly into the end position. volume of oil is flushed out by the flushing valve
Check pressure (rated; 22 bar). 106 (Fig. 24 & 25) and replaced by the charge
If necessary adjust pressure relief valve circuit.
109 (Fig. 23).
Adjustment: Space "S" of the adjuster screw of
8. To check the high pressure, connect two 400- flushing valve 106 (Fig. 25) has to be 15 mm.
bar gauges to test points MX5 & MX6 at the
swing balance valve 105 (Fig. 21).
Note:
Fig. 25 642110
7. Check pressures.
Rated:
At test point M-A2 = 60 bar
At test point M-B1 = 0 bar
Overview:
S31 M-A2 M-B1
OFF 60 bar 0 bar
ON 80 bar 80 bar
Table 5
Fig. 27 642665
Inlet pressure:
If the pressures will not appear as shown in table The track tensioning system is protected by two
5, the function and setting of the change over valve secondary relief valves, which are preset to 330
(SV, Fig. 28) has to be checked. bar.
To make the switch point of the change over valve
visible, the auxiliary pressure 2 has to be tempo- These valves are installed in the carbody (134, Fig.
rary increased to 70 bar (see chapter 8.6.4.1). 29).
Fig. 31 642679
Pressure relief
Checking and setting
Pressure relief valves (68) are works set to approx.
1. Connect a gauge (range: 400 bar) to the rele- 8 bar, to . To check, proceed as follows:
vant test point at the fan motor.
1. Connect pressure gauges (range: 25 bar) to
2. Ensure, that the hydraulic oil temperature is the relevant test points at the distributor block
above 70°C, so that the fan motors run with of the cooling circuit to be checked.
maximum rpm.
2. Ensure, that the hydraulic oil temperature is
above 50°C, so that the fan motors are run-
3. Check pressure.
ning with maximum speed.
With an oil temperature of approx. 50° C the 3. Check pressure:
pressure at the fan motor is approx. 200 bar. Circulating pressure should be approx. 5 bar.
Fig. 34 642061
Location of the accumulator below the cab module
Fig. 35 642672
Fig. 37 642064
Legend, Fig. 37
Checking and setting: S= Protective cap
All hydraulic accumulators installed in the machine O= O-Ring
have to be checked at regular intervals and re- SW6 = Allen key
charged if necessary (see Operation and mainte- H= Hexagon cap nut
nance manual). P= Internal hexagon screw
For this work, the recommended “charging and V= Valve
testing unit” should be used. (see chapter 3.2
THB).
A general procedure how to handle the “charging
and testing unit” is described on the following pag-
es:
Charging and testing unit for Charging and testing unit for
diaphragm accumulators bladder accumulators with
adaptor A3
Fig. 38 642065
Legend, Fig. 38
1 = Hydr. accumulator 5 = Charging hose
2 = Adaptor A 6 = Connector
3 = Charging and test- 7 = Pressure reducer
ing unit 8 = Adaptor
4 = Connector 9 = Nitrogen bottle
Fig. 36 642063
Legend, Fig. 36
DESCRIPTION (Charging and testing unit)
A = Spindle
B = Pressure release
FUNCTION
C = Check valve
The charging and testing unit is used to charge
D = Screw connector
accumulators with nitrogen or to check or to
A3 = Adaptor
change the existing pre-charge pressure in accu-
mulators. For this purpose the charging and testing
unit is screwed onto the gas valve of the hydraulic
TESTING
On bladder accumulators (Charging and testing
unit with adaptor A3) open valve by turning spindle
A clockwise.
On piston and diaphragm accumulators (Charg-
ing and testing unit) open valve V by turning the
internal hexagon screw anticlockwise with spindle
A. When the needle of the gauge begins to move,
give the spindle another complete turn. The gauge
now shows the charging pressure in the accumula-
tor. The check valve C prevents any escape of
nitrogen.
WARNING
REDUCING THE PRE-CHARGE PRESSURE
Carefully open release B. The nitrogen escapes Nitrogen and operating fluid can
into the atmosphere. escape when filling or testing
the accumulator due to a faulty,
INCREASING PRE-CHARGE PRESSURE i.e. leaking, bladder, diaphragm
Only use nitrogen for charging accumulators. or piston seals.
Caution!
Never use oxygen! Danger of ex- Risk to health in the case of
plosion! If the gas pressure in the aggressive fluids!
nitrogen bottle is higher than the The check valve C must not be
max. operating pressure of the removed. The valve has a safety
accumulator, a gas pressure re- function for the whole charging
ducer must be fitted. and testing unit.
Fig. 41 642089a
Fig. 39 642087
Fig. 42 642090