Certificate of Compliance: Steel Pipe For Automatic Fire Sprinkler Systems

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Certificate of Compliance

This certificate is issued for the following:

Steel Pipe for Automatic Fire Sprinkler Systems


Listing Rated Working Rated Working Certification
Product Nominal Pipe Size, in.
Country Pressure, psi Pressure, kPa Type

Schedule 10a, d, m, q China 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 5, 6 300 2070 FM Approved

Schedule 10a, d, m, q China 8, 10, 12 225 1550 FM Approved

Notes: a - FM Approved for use with FM Approved pipe couplings on rolled grooves.
d - When hot dip galvanized by factory, the sprinkler pipe is FM Approved for dry pipe systems.
m - FM Approved for use in all steel sprinkler systems composed of uncoated steel pipe.
q - Manufactured out of ASTM A795 / A795M Grade B steel

Prepared for: Tianjin Youfa International Trade Co Ltd, RM 1502-1509, 15F, NO. 4 Anshun Building
Dafeng Road, Hongqiao District, Tianjin City, China 300120

FM Approvals Class: 1630 – “Steel Pipe for Automatic Fire Sprinkler Systems”

Approval Identification: 3064021 Approval Granted: March 9, 2018

To verify the availability of the Approved product, please refer to www.approvalguide.com

Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.

David B. Fuller
VP, Manager – Fire Protection

FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062
USA
Certificate of Compliance
This certificate is issued for the following:

Steel Pipe for Automatic Fire Sprinkler Systems


Listing Rated Working Rated Working Certification
Product Nominal Pipe Size, in.
Country Pressure, psi Pressure, kPa Type

Schedule 40a, b, d, e, m, q China 1, 1-1/4, 1-1/2, 2, 2-1/2, 3, 4, 5, 6 300 2070 FM Approved

Schedule 40a, b, d, e, m, q China 8, 10, 12 225 1550 FM Approved

Notes: a - FM Approved for use with FM Approved pipe couplings on rolled grooves.
b - FM Approved for use with FM Approved pipe fittings when threaded.
d - When hot dip galvanized by factory, the sprinkler pipe is FM Approved for dry pipe systems.
e - Any FM Approved pipe coupling or fitting suitable for use with Schedule 10 pipe may be used with this product at the
lower rated pressure of the pipe or the fitting.
m - FM Approved for use in all steel sprinkler systems composed of uncoated steel pipe.
q - Manufactured out of ASTM A53 / A53M Grade B steel

Prepared for: Tianjin Youfa International Trade Co Ltd, RM 1502-1509, 15F, NO. 4 Anshun Building
Dafeng Road, Hongqiao District, Tianjin City, China 300120

FM Approvals Class: 1630 – “Steel Pipe for Automatic Fire Sprinkler Systems”

Approval Identification: 3064021 Approval Granted: March 9, 2018

To verify the availability of the Approved product, please refer to www.approvalguide.com

Said Approval is subject to satisfactory field performance, continuing Surveillance Audits, and strict conformity to the
constructions as shown in the Approval Guide, an online resource of FM Approvals.

David B. Fuller
VP, Manager – Fire Protection

FM Approvals
1151 Boston-Providence Turnpike
Norwood, MA 02062
USA