Buffer Vessel Foundation - Latest

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 39
At a glance
Powered by AI
The document discusses the design calculation for the buffer vessel foundation of a nitrogen facility. It covers aspects like design of the foundation, reinforcement details, load considerations etc.

The design calculation report is about the design of the foundation for a 30m3 capacity gaseous nitrogen buffer vessel that will be installed at Durgapur Steel Plant. The report covers the foundation layout, load assumptions, reinforcement details, moment calculations etc.

The design considerations taken into account are - grade of concrete as M25, grade of steel as Fe500, soil bearing capacity, factors for serviceability and seismic loads etc.

STEEL AUTHORITY OF INDIA LTD.

DURGAPUR STEEL PLANT


CENTRE FOR ENGINEERING & TECHNOLOGY

OTTO PROJECTS PRIVATE LIMITED

NITROGEN FACILITIES FOR BELL LESS TOP CHARGING


SYSTEM IN BF-3 AT DSP

FOUNDATION FOR BUFFER VESSEL - DESIGN


CALCULATION

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
1 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
2 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DIA LTD.
T
& TECHNOLOGY

LIMITED

RGING

ESSEL - DESIGN

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
3 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
4 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
INTRODUCTION
GL of the site where the Buffer Vessel will be installed is at 82.500m level. The
foundation of 30 m3 capacity gaseous Nitrogen Buffer Vessels have been placed at 4.5m below
+82.500m level i.e. +78.000m level. The foundation comprise of a base slab with a hollow cylinder
placed on it. The base slab of the foundation is octagonal in plan having 4.8 m dia. inscribed circle.
The vessel sits directly on top of the cylinder at 300 mm above GL. One solid diaphragm has been
provided on top of cylinder. The cylinder is filled up with dry sand. But to take care of possible ingress
of ground water at a later date, the foundation has been checked considering the sand as saturated
with water. The vessel has been considered full of water in one case as there is statutory requirement
of hydrostatic testing of pressure vessels periodically.

The safe bearing capacity of soil at the under side of foundation has been taken as 12
t/sqm nett. Bottom of foundation is 4.5m below the GL, however allowance in gross base pressure has
been taken for a soil height of 2m.

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
5 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
2.500m level. The
aced at 4.5m below
b with a hollow cylinder
m dia. inscribed circle.
d diaphragm has been
ke care of possible ingress
g the sand as saturated
e is statutory requirement

on has been taken as 12


n gross base pressure has

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
6 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CONSIDERATION
Grade of concrete:M25
Grade of steel: Fe500
fck = 25 N/mm2
fy = 500 N/mm2

Properties of concrete :
Permissible Compressive Stress due to Bending, б cbc = 8.5 N/mm2
Permissible Direct Compressive Stress, бcc = 6 N/mm2
Permissible Tensile Stress due to Bending, б bt = 3 N/mm2
Permissible Direct Tensile Stress, бt = 3.2 N/mm2

Properties of steel :
Tensile stress of steel = 230 N/mm2

Mu,lim / bd2 = 3.33 N/sqmm


Factor of serviceability with out EQ or Wind =1.5
Factor of serviceability with EQ or Wind = 1.2
Net Safe Bearing Capacity of soil at 4.5m below GL = 12 t/sqm

Method of design : Limit State of Serviceability

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
7 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
8 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
BASE PRESSURE
LOAD DATA FOR NITROGEN BUFFER VESSEL:

DESCRIPTION EMPTY IN OPERATION WITH


(We) (Wo) WATER
Weight (in MT.) 12.5 13.4 42.5
Max. horizontal force - H (MT)
Due to seismic 6.55 -
Due to wind 3.6 -
Max. moment - M (T-M)
Due to seismic 36.637 -
Due to wind 11 -

Unit weight of pipe (DN 100) 17.1 kg/m


Length of pipe = 6.5 m (say)
Total weight of pipe = 17.1 x 6.5 = 111.15 kg

Unit weight of support (DN 80) = 8.32 kg/m


Length of pipe = 3 m (say)
Total weight of pipe = 8.32 x 3 = 24.96 kg

Total load due to pipe (DN 100) & its support = 136.11 kg
For design take this as = 150 kg = 0.15 t
Distance of centre of DN 100 from centre of vessel = 2m = 2000

Depth of u/s of foundation from GL = 4.5 m = 4500 mm


Height of cylinder from GL = 0.3 m = 300 mm
Height of soil over base slab = 4m = 4000 mm

Dia of inscribed circle of base slab, d b = 4.8 m = 4800 mm


Thickness of base slab = 0.5 m = 500 mm

PCD of bolts = 2.58 m = 2580 mm


Distance of outer face of cylinder from PCD of bolts = 0.1 m = 100
Distance of inner face of cylinder from PCD of bolts = 0.1 m = 100
Outer diameter of cylinder, do = 2.78 m = 2780 mm
Inner diameter of cylinder, di = 2.38 m = 2380 mm
Thickness of wall of cylinder, t = 0.2 m = 200 mm
Height of cylinder, h = 4.3 m = 4300 mm
At top thickness of cylinder = 0.3 m = 300 mm
Upto a depth from top = 1.5 m = 1500 mm
Outside dia of cylinder at top = 2.88 m = 2880 mm
Inside dia of cylinder at top = 2.28 m = 2280 mm

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
9 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Diameter of diaphragm on cylinder, dd = 2.28 m = 2280 mm
Thickness of diaphragm, td = 0.23 m = 230 mm
Depth of water inside cylinder (if any) = 4.07 m

Length of bracket = 0.75 m = 750 mm


Width of bracket = 0.3 m = 300 mm
Depth of bracket = 0.9 m = 900 mm

Factor used for calculation of area of octagon =0.828


X-sec Area of base slab, A = 0.828 x 4.8^2 = 19.077 sqm
X-sec Area of cylinder = 0.785 x 2.78^2 - 0.785 x 2.38 1.62 sqm
X-sec Area of diaphragm = 0.785 x 2.28^2 = 4.08 sqm
X-sec Area of water inside cylinder = 0.785 x 2.38^2 = 4.45 sqm

MOI of cylinder= 0.049x2.78^4 - 0.049x2.38^ 1.35 m4


Section modulus of cylinder = 1.35 / (2.78 / 2) 0.97 m3
Min. section modulus of base slab = 0.1016 x 4.8^3 = 11.24 m3

Unit weight of concrete = 2.5 t/cum


Unit weight of dry soil = 1.8 t/cum
Unit weight of submarge soil 2 t/cum
Unit weight of sand filling= 2 t/cum (Cosidering possible ingress of ground water inside cyli

Weight of cylinder = 20.45 t


Weight of diaphragm = 2.35 t
Weight of bracket = 0.51 t
Weight of sand = 36.22 t
Weight of base slab = 23.85 t
Weight of soil over base = 104.08 t
Total weight of foundation & soil = 151.24 t
Total weight of foundation, soil & sand = 187.46 t

Net base pressure permissible = 12 t/sqm


Gross base pressure permissible with out Wind/Seismic Load = 12 + (2 x 1.8) =
Gross base pressure permissible with Wind/Seismic Load = 1.25 x 12 + (2 x 1.8) =

DESIGN OF BRACKET :

Load on bracket due to pipe = 0.15 t


Distance of this load from support = 0.56 m
Load on bracket due to self weight = 0.51 t
Span of bracket = 0.75 m
Moment on bracket = 0.15x0.56 + 0.51x0.75/2 0.28 tm

Over all depth = 900 mm


Clear cover = 50 mm
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
10 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Diameter of r/f = 12 mm
Effective depth, d = 844 mm
Width, b = 300 mm

Factored moment, Mu = 1.5x0.28 = 0.42 tm


Mu/bd^2 0.02 tm
Pt,reqd = 0.06 %
Pt,min = 0.06 %
Ast,reqd = 151.92 sqmm
Provide 12 mm dia. Bars of 3 nos. on top of bracket.
Ast,provided = 339.12 sqmm (Hence OK)

Provided -
depth of bracket at end = 0.6
depth of bracket at support 0.9
reinforcement on top = 3 nos. 12mm dia bars.
reinforcement on bottom = 3 nos. 12mm dia bars.
side face reinforcement = 2 nos. 12mm dia bars on each side.

STRESS ON CYLINDER :

Case 1 : Dead Load + Water in Vessel

Vertical load on cylinder = 42.5 + 20.45 + 2.35 + 0.51 65.81 t


Moment due to bracket & pipe = 0.15x2 + 0.51x(2-0.75 1.13 tm
Maximum pressure at base = P/A + M/Z = 41.79 t/sqm = 0.4179 N/sqmm
Minimum pressure at base = P/A - M/Z = 39.46 t/sqm = 0.3946 N/sqmm

Case 2 : Dead Load + Wind Load

Vertical load on cylinder = 12.5 + 20.45 + 2.3 35.3 t


Horizontal force on cylinder = 3.6 t
Moment due to vessels = 11 tm
Moment due to horizontal Force = 3.6 x 4.3 = 15.48 tm
Moment due to bracket & pipe = 1.13 tm
Total moment on base, M = 11 + 15.48 + 1.13 27.61 tm
Maximum pressure at base = P/A + M/Z = 50.25 t/sqm = 0.5025 N/sqmm
Minimum pressure at base = P/A - M/Z = -6.67 t/sqm = -0.0667 N/sqmm
Developed tension is less than the permissible value. (Hence OK)

Case 3 : Dead Load + Water in Vessel + Seismic Load

Vertical load on cylinder = 65.81 t


Horizontal force on cylinder = 6.55 t
Moment due to vessels = 36.637 tm
Moment due to horizontal Force = 6.55 x 4.3 = 28.165 tm
Moment due to bracket & pipe = 1.13 tm

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
11 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Total moment on base, M = 65.93 tm
Maximum pressure at base = P/A + M/Z = 108.59 t/sqm = 1.0859 N/sqmm
Minimum pressure at base = P/A - M/Z = -27.35 t/sqm = -0.2735 N/sqmm
Developed tension is less than the permissible value. (Hence OK)

PRESSURE ON BASE SLAB :

Case 1 : Dead Load + Water in Vessel

Total vertical load on base slab, P = 42.5 + 187.46 = 229.96 t


Moment due to bracket & pipe = 1.13 tm
Maximum base pressure = P/A + M/Z 12.15 t/sqm
Minimum base pressure = P/A - M/Z = 11.95 t/sqm (Hence OK)

Case 2 : Dead Load + Wind Load

Vertical load on base slab, P = 12.5 + 187.46 199.96 t


Horizontal force on cylinder 3.6 t
Moment due to vessels = 11 tm
Moment due to horizontal Force = 3.6 x 4.8 = 17.28 tm
Moment due to bracket & pipe = 1.13 tm
Total moment on base slab, M = 11 + 17.28 + 1.13 = 29.41 tm
Maximum base pressure = P/A + M/Z 13.1 t/sqm
Minimum base pressure = P/A - M/Z = 7.87 t/sqm (Hence OK)

Case 3 : Dead Load + Water in Vessel + Seismic Load

Vertical load on base slab, P 229.96 t


Horizontal force on cylinder = 6.55 t
Moment due to vessels = 36.637 tm
Moment due to horizontal Force = 6.55 x 4.8 = 31.44 tm
Moment due to bracket & pipe = 1.13 tm
Total moment on base slab, M = 69.207 tm
Maximum base pressure = P/A + M/Z 18.21 t/sqm
Minimum base pressure = P/A - M/Z = 5.9 t/sqm (Hence OK)

Check for Sliding :

Maximum horizontal force on foundation = 6.55 t


Frictional coeffitient between soil & concrete = 0.5
Resisting force against sliding = 0.5 x 187.46 93.73 t
Factor of safety against sliding = 93.73 / 6.55 14.31 > 1.2, (Hence OK)

Check for Overturning :

Maximum moment on foundation = 69.207 t


Restoring moment = 187.46 x 4.8/2 = 449.9 t

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
12 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Factor of safety against sliding = 449.9 / 69.20 6.5 > 1.2, (Hence OK)

Check for Uplift Pressure :

Maximum height of ground water = 4.5 m


Total upward load = 1 x 4.5 x 19.077 85.85 t
Minimum downward load = 187.46 t
Factor of safety against uplift = 187.46 / 85.85 2.18 > 1.2, (Hence OK)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
13 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
mm

mm
mm

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
14 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
of ground water inside cylinder)

15.6 t/sqm
18.6 t/sqm

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
15 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
(Hence OK)

(Tension develops)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
16 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
(Tension develops)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
17 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
design of CYLINDER
REINFORCEMENT ON DIAPHRAGM -

Self weight of diaphragm = 0.575 t/sqm


LL during construction = 0.15 t/sqm
Total load on slab = 0.725 t/sqm
Span of diaphragm = 2.88 m
Moment on diaphragm = 0.376 tm
Factored moment, Mu = 0.564 tm
Thickness of diaphragm = 230 mm
Clear cover = 50 mm
Dia. of r/f bars = 12 mm
Effective depth, d = 162 mm
Width of diaphragm = 1000 mm
Mu / b d^2 = 0.21 N/sqmm
Pt,reqd = 0.06 %
Pt,min = 0.06 %
Ast,reqd 97.2 sqmm
Ast,min 97.2 sqmm
Required spacing of bars = 1162 mm
Provided spacing of bars = 200 mm
Provide 12mm dia. bars @ 200mm c/c both ways & both face of diaphragm.

VERTICAL REINFORCEMENT ON CYLINDER -

At top of cylinder (when vessel is empty & wind on vessel);


Vertical load = 12.5 t
Moment = 11 tm
Area of cylinder at top = 0.785 (2.88^2-2.28^2) = 2.43 m2
Section modulus at top of cylinder = (PI()/32) (2.88^3-2.28^3) 1.18 m3
Maximum pressure at top = 12.5/2.43 + 11/1.18 = 14.47 t/sqm = 0.1447 N/sqmm
Minimum pressure at top = 12.5/2.43 - 11/1.18 = -4.18 t/sqm = -0.0418 N/sqmm

At bottom of cylinder;
Maximum tension -0.2735 N/sqmm (Refer page 5 )
Hence, design should be done for pressure at bottom of cylinder.

For 1m width of cylinder on outer face,


area of cylinder for this portion = Π (1.39^2-1.19^2)/2Π1.39
= 0.186 sqm
= 186000 sqmm

Tension develops = 0.2735 x 186000 50871 N

Outer diameter of cylinder = 2.78 m 0.2735 0.2296

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
18 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Provided dia. of bars = 12 mm
Clear cover to reinforcement = 50 mm
PCD of outer face bars = 2.668 m
Peripheri of this PCD = Π 2.668 = 8.38 m 88
Maximum spacing of bars = 200 mm
Total nos. required of bars = 8380 / 200 = 42 548

Inner diameter of cylinder = 2.38 m 2724


Provided dia. of bars = 12 mm
PCD of inner face bars = 2.492 m Stress on cylinder

Proveded nos. of bars on each face = 46

Distance of centre of outer bars from neutral axis = 548 mm


Distance of centre of inner bars from neutral axis = 460 mm
Ratio of this two distances = 460/548 = 0.84
Tension force taken by outer face bars = 0.84x50871 = 42732 N
Tension force taken by inner face bars = (1-0.84)x5087 8139 N

Area of steel required on outer face = 42732 / 230 = 185.79 sqmm


Nos. of steel required on outer face per m length = 1.64
Area of steel required on outer face = 8139 / 230 = 35.39 sqmm
Nos. of steel required on outer face per m length = 0.31

VERTICAL REINFORCEMENT ON CYLINDER FOR LOCAL EFFECT DUE TO MOMENT FROM BRACKET -

Inner diameter of cylinder = 2.38 m


Load on bracket due to pipe = 0.15 t
Distance of this load from inner face bars = 0.81 m
Load on bracket due to self weight = 0.51 t
Distance of this load from inner face bars = 0.575 m
Moment on bracket = 0.15x0.81 + 0.51x0.575 0.41 tm
Factored moment, Mu = 0.615 tm

Thickness of cylinder = 200 mm


Clear cover = 50 mm
Dia. of r/f bars = 12 mm
Effective depth, d = 144 mm
Width of diaphragm = 300 mm
Mu / b d^2 = 0.99 N/sqmm
Pt,reqd = 0.242 %
Pt,min = 0.06 %
Ast,reqd 104.544 sqmm
Ast,min 25.92 sqmm
Provide 12 mm dia. Bars of 1 no(s).
Ast,provided = 113.04 sqmm (Hence OK)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
19 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Provided reinforcement is greater than the required one.
Provide 12mm dia. vertcal bars of 46nos. on each face of cylinder.

HORIZONTAL REINFORCEMENT ON CYLINDER -

max. thickness of cylinder = 300 mm


Clear cover = 50 mm
Dia. of r/f bars = 10 mm
Effective depth, d = 255 mm
Width of slab = 1000 mm
Pt,min = 0.06 %
Ast,min 153 sqmm
Required spacing of bars = 513 mm
Provided spacing of bars = 200 mm
Provide 10mm dia. horizontal bars @ 200mm c/c on each face of cylinder.

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
20 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
21 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
1.0859

ss on cylinder

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
22 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Rechecking the design according to Table139 of "Reinforced Concrete Designer's Handboo
Charles Reynolds :

Outer dia. of cylinder, do = 2.78 m


Clear cover = 50 mm
Dia. of horizontal bars = 10 mm
Dia. of vertical bars = 12 mm
PCD of outer face bars = 2.668 m = 2668 mm
Peripheri of this PCD = Π 2.668 = 8.38 m
Maximum spacing of bars = 200 mm
Total nos. required of bars = 8380 / 200 = 42
Provided nos. of bars = 46

Inner dia. of cylinder, di = 2.38 m


Provided dia. of inner bars 12 mm
PCD of inner face bars = 2.492 m
Peripheri of this PCD = Π 2.492 = 7.83 m
Provided nos. of bars = 46

Applied direct load on cylinder = 65.81 t


Applied moment on cylinder = 65.93 tm
Permissible stress on steel = 230 N/sqmm
Permissible stress on concrete, бcbc = 8.5 N/sqmm

Eccentricity, e = 65.93/65.81 = 1m = 1000 mm


θ= 7.83 °
Radius of outer face of cylinder, R = 1.39 m

Ckeck for outer face reinforcement -

e/do = 0.36
αe = modular ratio = 280/3бcbc = 11.0
Distance of extreme tension steel from compression edge, d1 = 2724 mm
Let, distance of neutral axis for compression edge, x1 = 0.38 d 1035.12 m
say, 0.6 m = 600

A=
B= x1 =
C=
0
1
2
DESIGN CALCULATION FOR BUFFER 3 VESSEL
OTTO PROJECT PVT. LTD.
23 DSP DOC. NO. 5 23 04 06
4 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
5
6
B= x1 =
C=
0
1
2
3
4
5
6
7
8
9
10
11
12 13
14

The protperties of the bars below the assumed nuetral axis are considered thus :
Bar As a a-x1 S = (a-x1) As Sa As a
marked mm2 mm mm mm3 / 103 mm4 / 106 mm3 / 103
0 226.08 697 97 21.93 15.29 157.58
1 226.08 859 259 58.55 50.29 194.2
2 226.08 1030 430 97.21 100.13 232.86
3 226.08 1208 608 137.46 166.05 273.1
4 226.08 1390 790 178.6 248.25 314.25
5 226.08 1572 972 219.75 345.45 355.4
6 226.08 1750 1150 259.99 454.98 395.64
7 226.08 1921 1321 298.65 573.71 434.3
8 226.08 2083 1483 335.28 698.39 470.92
9 226.08 2232 1632 368.96 823.52 504.61
10 226.08 2365 1765 399.03 943.71 534.68
11 226.08 2480 1880 425.03 1054.07 560.68
12 226.08 2574 1974 446.28 1148.72 581.93
13 226.08 2647 2047 462.79 1225.01 598.43
14 226.08 2696 2096 473.86 1277.53 609.51
15 226.08 2721 2121 479.52 1304.77 615.16
∑ 3391.2 4662.89 10429.87 6833.25

Depth to centre of tension, at = (10429.87x10^6) / (4662.89x10^3) 2237 mm

The compressive area above the assumed neutral axis is devided into a series of horizontal strips, the
properties of which are tabulated thus.

bs hs bs hs (αe-1)As' Atr
Strip
mm mm mm2 / 103 mm2/103 mm2 / 103

A 1035.4 200 207.08 7.91 214.99


B 770.2 200 154.04 3.39 157.43
C 555.6 200 111.12 4.52 115.64
∑ 488.06
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
24 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
bs = average width of cylinder in corresponding strip.
hs = width of strip.
Atr = equivalent area of strip = bs hs + (αe-1)As'

hc (x1-hc) Atr(x1-hc) Atr hc (x1-hc)


Strip Atr hc mm2/106
mm mm mm2/106 mm2/106

A 100 500 107.5 21.5 10750


B 300 300 47.23 47.23 14169
C 500 100 11.56 57.82 5782
∑ 166.29 126.55 30701
hc = distance of centre of width of strip from compression edge

Depth of centre of compression, ac =(30701x10^6) / (166.29x10^6) = 185 mm

x' = [(11x6833.25x10^3) + (126.55x10^6)] / [(11x3391.2) + (488.06x10^3) 384

Maximum stresses :

fcr = [658100x600 (1000+2237-384)] / [(2237-185) 166.29 x 10^6] 3.3


fst = [(2724-600) (3.3x166.29x10^6/600 - 658100) / (4662.89x10^3 116.84

Check trial position of neutral axis :

Actual x1 = 2668 / (1+116.84/11/3.3) = 632 mm


(The diference is not so much, Hence OK)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
25 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
esigner's Handbook" by

mm

0
1
2
3 DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
4 26 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
5
6
0
1
2
3
4
5
6
7
8
9
10
11
12 13
14 15

horizontal strips, the

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
27 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
mm

N/sqmm
N/sqmm

uch, Hence OK)

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
28 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
design of BASE SLAB
Reinforcement on Cantilever Portion :

Maximum projection of base slab = 1.202 m


Weight of soil & base slab 9.25 t/sqm

Maximum base pressure for Case 1 = 12.15 t/sqm


Net base pressure = 2.9 t/sqm
Moment on base slab = 2.09 tm
Factored moment = 3.135 tm
Maximum base pressure for Case 2 & Case 3 18.21 t/sqm
Net base pressure = 8.96 t/sqm
Moment on base slab = 6.47 tm
Factored moment = 7.764 tm

Maximum factored moment, Mu = 7.764 tm


Over all depth of base slab 500 mm
Clear cover = 50 mm
Dia. of r/f bars = 12 mm
Effective depth, d = 432 mm
Width of slab = 1000 mm
Mu / b d^2 = 0.42 N/sqmm
Pt,reqd = 0.106 %
Pt,min = 0.06 %
Ast,reqd 457.92 sqmm
Ast,min 259.2 sqmm
Required spacing of bars = 246 mm
Provided spacing of bars = 200 mm

Minimum base pressure = 5.9 t/sqm


Net downward pressure = 3.35 t/sqm
Moment on base slab = 2.42 tm
Factored moment = 2.90 tm
Over all depth of base slab 500 mm
Clear cover = 50 mm
Dia. of r/f bars = 12 mm
Effective depth, d = 432 mm
Width of slab = 1000 mm
Mu / b d^2 = 0.16 N/sqmm
Pt,reqd = 0.07 %
Pt,min = 0.06 %
Ast,reqd 302.4 sqmm
Ast,min 259.2 sqmm
Required spacing of bars = 373 mm
Provided spacing of bars = 200 mm

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
29 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Shear reinforcement on cantilever portion:
Distance of critical shear form edge of cylind 432 mm
Force on cantilever portion with out wind load 2.233 t
Critical shear stre 0.052 N/sqmm
Factored shear stress = 0.078 N/sqmm
Force on cantilever portion with wind load = 6.899 t
Critical shear stre 0.16 N/sqmm
Factored shear stress = 0.19 N/sqmm
Maximum shear stress = 0.19 N/sqmm
Permissible shear stress on concrete 3.1 N/sqmm (Hence OK)
Pt,provided = 0.131 %
Shear taken by concrete = 0.29 N/sqmm
Hence shear reinforcement is not required.

Reinforcement on Simply Supported Portion :

Maximum pressure on base slab inside cylinder ;


for case 1 = 12.15 t/sqm
for case 2 = 11.69 t/sqm
for case 3 = 14.88 t/sqm
Span of slab = 2.38 m

Maximum pressure for Case 1 = 12.15 t/sqm


Moment on base slab = 4.30 tm
Factored moment = 6.45 tm

Maximum pressure for Case 2 & Case 3 = 14.88 t/sqm


Moment on base slab = 5.27 tm
Factored moment = 6.32 tm

Maximum factored moment, Mu = 6.32 tm


Over all depth of base slab 500 mm
Clear cover = 50 mm
Dia. of r/f bars = 12 mm
Effective depth, d = 432 mm
Width of slab = 1000 mm
Mu / b d^2 = 0.34 N/sqmm
Pt,reqd = 0.082 %
Pt,min = 0.06 %
Ast,reqd 354.24 sqmm
Ast,min 259.2 sqmm
Required spacing of bars = 319 mm
Provided spacing of bars = 200 mm

Shear reinforcement on simply supported portion :

Pressure on base slab inside cylinder at a distance equat to the eff. depth of slab;
for case 1 = 12.15 t/sqm
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
30 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
for case 2 = 11.25 t/sqm
for case 3 = 13.85 t/sqm

Maximum upward pressure with out wind = 4.01 t/sqm


Weight of basse slab = 1.25 t/sqm
Area of simply supported portion = 4.447 sqm
Total force on slab = (4.01 - 1.25) x 4.447 = 12.270 t

This for will be distributed over a length = 7.480 m


Hence shear stress on slab = 12.27 / 7.48 / 0.432 = 3.797 t/sqm = 0.03797 N/sqmm
Factored shear stress = 0.06 N/sqmm

Maximum upward pressure with wind = 11.25 t/sqm


Total force on slab = (11.25 - 1.25) x 4.447 = 44.470 t
This force will be distributed over a length = 7.480 m
Hence shear stress on slab = 44.47 / 7.48 / 0.432 = 13.762 t/sqm = 0.13762 N/sqmm
Factored shear stress = 0.17 N/sqmm

Maximum shear stress = 0.17 N/sqmm


Permissible shear stress on concrete 3.1 N/sqmm (Hence OK)
Pt,provided = 0.131 %
Shear taken by concrete = 0.29 N/sqmm
Hence shear reinforcement is not required.

Provide 12mm dia. bars @ 200mm c/c on bottom face of base slab.
Provide 12mm dia. bars @ 200mm c/c on top face of base slab.

Check for Tangential Moment (Refer "Tall Chimneys Design & Construction" by S. N. Manoh

Maximum radius of foundation, a = 2.4 m


Central radius of cylinder, βa = 1.29 m
Therefore β = 0.5
Mr = Radial moment = Moment about Tangent
Mt = Tangential moment = Moment about Radius

For axial load, Mt = Coeff. x p a2 x 10-2


For moment, Mt = Coeff. x q a2 x 10-2

Coeffitient for Axial Load -


From Table 6.11,
Coff. For Mt
At f=0 At f=β At f=1
_ -10.48 -5.313

Coeffitient for Moment on foundation -


From Table 6.12,
Coff. For Mt
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
31 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
At f=0 At f=β At f=1
_ -5.242 -1.616

Moment on foundation -

Case 1 : Dead Load + Water Load + Water inside cylinder

p= 10.80 t

At f = 0 _
At f = β -6.52
At f = 1 -3.31

Case 2 : Dead Load + Wind Load

p= 9.23 t

At f = 0 _
At f = β -5.57
At f = 1 -2.83

q= 2.62 t/sqm

At f = 0 _
At f = β -0.79
At f = 1 -0.24

Total moment - at f = 0 _
Total moment - at f = β -6.36
Total moment - at f = 1 -3.07

Case 3 : Dead Load + Water in Vessel + Water inside cylinder + Seismic Load

p= 10.80 t

At f = 0 _
At f = β -6.52
At f = 1 -3.31

q= 6.16 t/sqm

At f = 0 _
At f = β -1.86
At f = 1 -0.57

Total moment - at f = 0 _
Total moment - at f = β -8.38

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
32 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
Total moment - at f = 1 -3.88

Reinforcement required for tangitial moment :

Maximum moment for Case 1 = 6.52 tm


Factored moment = 1.5 x 6.52 = 9.78 tm
Maximum moment for Case 2 & Case 3 = 8.38 tm
Factored moment = 1.2 x 8.38 = 10.06 tm

Maximum factored tangential moment, Mut = 10.06 tm


Over all depth of base slab 500 mm
Clear cover = 50 mm
Dia. of circumferential bars 12 mm
Dia. of radial bars = 12 mm
Effective depth, d = 432 mm
Width of slab = 1000 mm
Mu / b d^2 = 0.54 N/sqmm
Pt,reqd = 0.13 %
Pt,min = 0.06 %
Ast,reqd 561.6 sqmm

Ast,provided = Ast cos 45° + Ast cos(90-45)°


= 1.41 Ast
= 796.932 sqmm
Hence, provided reinforcement is heigher than the required reinforcement.

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
33 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
34 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
on" by S. N. Manohar):

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
35 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
36 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
SKETCH

DESIGN CALCULATION FOR BUFFER VESSEL


OTTO PROJECT PVT. LTD.
37 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
38 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048
DESIGN CALCULATION FOR BUFFER VESSEL
OTTO PROJECT PVT. LTD.
39 DSP DOC. NO. 5 23 04 06 A4 0048
DSP - NITROGEN FACILITIES FOR BLT IN BF-3
OPPL DOC. NO. 1081/DE/04/06/A4/0048

You might also like