Smoke Detector Installation
Smoke Detector Installation
Smoke Detector Installation
© 2014 UTC Fire & Security Americas Corporation, Inc. 1/6 P/N 13083-EN • REV J • ISS 10APR14
Installation Figure 1: Smoke detector placement
(1)
Notes
• Locate detectors in an operating environment as defined (5)
in “Specifications” on page 6.
(2)
• Mount detectors on a firm, permanent surface.
(1)
(2)
IDC_IN
(1) (5)
IDC_IN
(8) (9) (10)
2 2 2
1 3 1 3 1 3
(3)
702RU, 702RE,
701U 702U, 702E 702U, or 702E
6 4
5 5
6 4
NO C NC
(6) (7)
PWR_IN
(2)
PWR_IN
2 2
1 3 1 3
(3)
702U, 702E 702U, 702E
(4)
6 4 6 4
5 5 RD
BK
(1) IDC_IN BN
IDC_IN BN
(5)
(11)
(1) Initiating device circuit from a compatible listed control panel (7) Remote LED P/Ns 706U1A, 706U2A ,or 706U3A (for 721U or
(2) DC power circuit 721UT detector only)
(3) Continuity switch (8) Base for 711 series and 713-5U detectors
(4) Power supervision relay (P/N 204-12/24V) (9) Base for 721UT detector only
(5) End-of-line device (10) Base for 731U series detectors
(6) Remote test switch P/N 706U2A (for 721U and 721UT detectors (11) Remote LED P/Ns 706U1A, 706U2A, or 706U3A (for 741U or
only in this two-wire application) 741UT detectors only)
• Prior to testing, remove the red dust cover. The units do After all universal mounting bases are installed, including the
not work with the dust cover in place. end-of-line device, check the system wiring for continuity.
Verify that the manually operated continuity switch in each
• Follow the control panel’s recommended test procedure. base is in the shorting position — making contact with
To limit inconvenience to building occupants during testing terminals 1 and 2 (for use at initial installation only). See
it may be necessary to disable or disconnect the alarm Figure 8. Use a screwdriver to reset any unshorted continuity
notification appliances, HVAC shutdown, elevator control, switches (reset by prying the jumper wire out of the plastic
releasing service devices, and extinguishing systems prior stopper). This establishes continuity across the alarm initiating
to detector tests. If these or other functions controlled by circuit at initial installation. The wiring can now be tested for
the fire system are disconnected during testing, be sure to continuity using an ohmmeter or “megger.”
perform other tests to confirm that these functions will
operate during an actual event.
• Be sure to enable or reconnect all devices at the
conclusion of testing.
Regulatory information
Listings UL Listed (UL 268 and UL 521)
(1) Detector cap (2) Field-replaceable optical chamber FM Approved (except for TS7-4 and TS7-4T)
CSFM (California State Fire Marshal) Approved
Specifications UL two-wire S10A for all models except 731U/731L
compatibility
S11A for 731U/731L
Voltage 8.5 to 33 VDC, not polarity sensitive identifier
S00 for all bases
Maximum ripple 10% (Vp-p)
Typical average 711U, 713-5U: 70 μA
standby current (24 V) 721U, 721UT, 731L, 731U, 741U, 741UT: Contact information
100 µA
For contact information, see www.interlogix.com.