Application description 11/2014

SINAMICS G: Speed control


of a G110M, G120, G120C,
G120D or G120P using S7-
300/400 (STEP 7 V5) with
PROFNET, Safety Integrated
and HMI
SINAMICS G110M / G120 / G120C / G120D / G120P (with FW 4.6)
SIMATIC S7-300/400

http://support.automation.siemens.com/WW/view/en/58820849
Warranty and liability

Warranty and liability

Note The Application Examples are not binding and do not claim to be complete
regarding the circuits shown, equipping and any eventuality. The Application
Examples do not represent customer-specific solutions. They are only intended
to provide support for typical applications. You are responsible for ensuring that
the described products are used correctly. These application examples do not
relieve you of the responsibility to use safe practices in application, installation,
operation and maintenance. When using these Application Examples, you
recognize that we cannot be made liable for any damage/claims beyond the
liability clause described. We reserve the right to make changes to these
Application Examples at any time without prior notice.
If there are any deviations between the recommendations provided in these
application examples and other Siemens publications – e.g. Catalogs – the
contents of the other documents have priority.

We do not accept any liability for the information contained in this document.

Any claims against us – based on whatever legal reason – resulting from the use of
the examples, information, programs, engineering and performance data etc.,
described in this Application Example shall be excluded. Such an exclusion shall
not apply in the case of mandatory liability, e.g. under the German Product Liability
Siemens AG 2014 All rights reserved

Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life,


body or health, guarantee for the quality of a product, fraudulent concealment of a
deficiency or breach of a condition which goes to the root of the contract
(“wesentliche Vertragspflichten”). The damages for a breach of a substantial
contractual obligation are, however, limited to the foreseeable damage, typical for
the type of contract, except in the event of intent or gross negligence or injury to
life, body or health. The above provisions do not imply a change of the burden of
proof to your detriment.
Copyright

Any form of duplication or distribution of these Application Examples or excerpts


hereof is prohibited without the expressed consent of Siemens Industry Sector.

Security Siemens provides products and solutions with industrial security functions that
informa- support the secure operation of plants, solutions, machines, equipment and/or
tion networks. They are important components in a holistic industrial security
concept. With this in mind, Siemens’ products and solutions undergo continuous
development. Siemens recommends strongly that you regularly check for
product updates.
For the secure operation of Siemens products and solutions, it is necessary to
take suitable preventive action (e.g. cell protection concept) and integrate each
component into a holistic, state-of-the-art industrial security concept. Third-party
products that may be in use should also be considered. For more information
about industrial security, visit http://www.siemens.com/industrialsecurity.
To stay informed about product updates as they occur, sign up for a product-
specific newsletter. For more information, visit
http://support.automation.siemens.com.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 2
Table of Contents

Table of Contents
Warranty and liability................................................................................................... 2
Table of Contents ......................................................................................................... 3
1 Task ..................................................................................................................... 5
2 Solution............................................................................................................... 6
2.1 Overview of the general solution .......................................................... 6
2.2 Description of the core functionality ..................................................... 7
2.2.1 Configuring the communication ............................................................ 7
SIMATIC S7-300/400 ........................................................................... 7
SINAMICS G ........................................................................................ 7
2.2.2 Data exchange ..................................................................................... 7
Cyclic process data exchange ............................................................. 8
Acyclic data exchange (parameter access) ......................................... 8
2.3 Hardware and software components used........................................... 9
Sample files and projects ................................................................... 11
3 Setting up and Commissioning the Application .......................................... 12
3.1 Wiring ................................................................................................. 12
3.2 IP addresses and PN names ............................................................. 13
3.3 Settings on PG/PC ............................................................................. 13
3.4 Downloading the SIMATIC program .................................................. 14
Siemens AG 2014 All rights reserved

3.5 Downloading the SINAMICS configuration ........................................ 17


3.5.1 Preparation for using the network connection of the PG/PC ............. 17
3.5.2 Preparations for using the USB connection of the PG/PC ................. 20
3.5.3 Downloading the configuration into the SINAMICS G ........................ 22
4 Operation of the Application .......................................................................... 25
4.1 Prerequisites ...................................................................................... 25
4.2 Operation of the Application ............................................................... 25
4.3 Monitoring and parameter access via operator panel ........................ 27
Copyright

4.3.1 Screens and screen navigation .......................................................... 27


4.3.2 Process data exchange ...................................................................... 28
Control and status word ..................................................................... 28
Setpoint and actual values ................................................................. 29
4.3.3 Parameter access .............................................................................. 31
Reading/writing parameters ............................................................... 31
Fault buffer ......................................................................................... 33
5 Functional Mechanisms of the Application .................................................. 34
5.1 Functionality of process data exchange ............................................. 35
5.1.1 Accessing process data in the user program of the SIMATIC
S7-300/400 ......................................................................................... 36
5.1.2 Standardizing the setpoint and actual values .................................... 36
5.1.3 Control and status word ..................................................................... 37
5.1.4 FB 10 “PZD_G120_Tel_352” ............................................................. 39
5.2 Change-over to “Siemens Telegram 1” (with FB11) .......................... 42
5.3 Parameter access functionality .......................................................... 43
5.3.1 FB 20 “Parameter_Access” ................................................................ 44
5.3.2 The DBs “read/write_drive_parameters” and
“answer_from_drive” .......................................................................... 47
5.4 Function of the further blocks in the example projects ....................... 51
6 Configuration and Settings............................................................................. 52
6.1 Configuring the SIMATIC S7-300/400 controller ................................ 52
6.2 Configuring the SINAMICS G drive .................................................... 59

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 3
Table of Contents

7 Links & Literature ............................................................................................ 66


8 History............................................................................................................... 67
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 4
1 Task

1 Task
The SIMATIC S7 300/400 can be operated as a PROFINET controller. A
SINAMICS G110M, G120, G120C, G120D or G120P can be used here as
PROFINET device and be controlled by the SIMATIC S7-300/400.
This application example illustrates how to configure SINAMICS
G110M/G120/G120C/G120D/G120P and SIMATIC S7-300/400, start it up, and
access process data and parameters.

Overview of the automation task


The following figure gives an overview of the automation task:

Figure 1-1
Siemens AG 2014 All rights reserved

MPI, PROFIBUS
or Ethernet

PROFINET
Copyright

Requirements for the automation task


Table 1-1
Requirement Explanation
Access to process data The SINAMICS G shall be switched on and off via the control
word, and the speed value is to be specified
as fast as possible.
Access to parameters Read and write access from/to the parameters in the
SINAMICS G by the SIMATIC S7-300/400 (in this example:
ramp-up and ramp-down time) should be possible
and be performed using as few resources as possible, i.e.
small communication load.
Safety function of the The SINAMICS G converters have the option of performing a
SINAMICS G fail-safe shutdown (e.g. emergency-stop).

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 5
2 Solution
2.1 Overview of the general solution

2 Solution
This application example gives an example of how to connect a SINAMICS
G110M, G120, G120C, G120D or G120P to an SIMATIC S7-300. It uses blocks
which can be directly applied to your own application.

2.1 Overview of the general solution


Schematic layout
The following figure gives a schematic overview of the most important components
of the solution:

Figure 2-1

SINAMICS G120 S7-300/400 KTP 600


Siemens AG 2014 All rights reserved

PROFINET PC/PG

USB
(alternative for parameterization
Copyright

via the fieldbus)

Motor

The example shows you how ...


...the SIMATIC S7-300/400 controller is configured.
...the communication is programmed in the SIMATIC S7-300/400 controller.
...the SINAMICS G converter is configured using STARTER.

NOTICE This example is only valid for frequency converter SINAMICS G110M with
FW4.7 and SINAMICS G110M, G120, G120C, G120D and G120P as of FW4.6.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 6
2 Solution
2.2 Description of the core functionality

2.2 Description of the core functionality


2.2.1 Configuring the communication

TIA (Totally Integrated Automation)


The program for SIMATIC S7-300/400 and the configuration of the SINAMICS G
are centrally stored in a STEP 7. The respectively required editors are called up via
the STEP 7 Manager.

SIMATIC S7-300/400
SIMATIC S7-300/400 in this example is programmed with STEP 7 V5.
In HW Config, the SIMATIC S7 the stations connected via PROFINET, such as
SINAMICS G, are configured, and the communication is defined. One of several
message frame types can be selected here for the data exchange. It is important
that the same message frame type is selected here as for the SINAMICS G
configuration.
When inserting SINAMICS G into the SIMATIC project, the I/O addresses used by
the SIMATIC S7-300/400 for accessing the SINAMICS G are also specified.

SINAMICS G
Siemens AG 2014 All rights reserved

The configuration of SINAMICS G is performed using the STARTER


commissioning tool.
For SINAMICS G one of several message frame types can be selected for the data
exchange. This defines which data is transmitted or received in which order. It is
important that the same message frame type is selected when configuring the
SIMATIC S7-300/400.
Copyright

2.2.2 Data exchange

Data exchange between SINAMICS G and SIMATIC S7-300/400 occurs in two


areas:
Process data,
i.e. control word(s) and setpoint(s), or status word(s) and real value(s)
Parameter area,
i.e. reading/writing of parameter values

Note The two areas, process data and parameters, are independent from each other
and can also be used individually.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 7
2 Solution
2.2 Description of the core functionality

Cyclic process data exchange


Process data is transferred cyclically, which means in each bus cycle, in order for it
to be transferred as quickly as possible.
The SIMATIC S7-300/400 sends the control word and the setpoint value to
SINAMICS G and in return receives the status word and the actual value.
Depending on the message frame type, two further setpoint or real values, or
extended control or status words can be transferred respectively. The available
message frame types are listed in chapter 7.4.1 of the SINAMICS G120C operating
instructions (/7/), for example.
On the SIMATIC S7-300/400 side, the process data is supplied as I/O input or
output words.
In the SINAMICS G, the configuration specifies which bits of the control word
are used and which data is transmitted to the SIMATIC S7-300/400.

Acyclic data exchange (parameter access)

To be able to transfer parameters, message frame types were also defined where
additionally four words are provided for a parameter transfer. Since these four
words, like the process data, are always transmitted, a permanent communication
Siemens AG 2014 All rights reserved

load is produced even though the parameters themselves are generally only rarely
transferred.
PROFINET also provides the option of using an acyclic data exchange in addition
to the cyclic data exchange, which is only inserted on demand.
This makes it possible to transfer the parameter area acyclically on demand,
without creating a permanent communication load. The acyclic transfer takes
clearly longer than the cyclic transfer of the process data.
In this example an acyclic data exchange is used for parameter access.
Copyright

In the SIMATIC S7-300/400, parameter jobs are sent to the SINAMICS G by


writing data record 47, and the response of the SINAMICS G is read in by
reading data record 47.
No particular action is required on the SINAMICS G side.

Note When using a CP342-1, the parameters of the SINAMICS G cannot be accessed
with the acyclic data exchange.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 8
2 Solution
2.3 Hardware and software components used

2.3 Hardware and software components used


The application document was generated using the following components:

General hardware components


Table 2-1 Hardware components
Component Qty. Order number Note
or other S7-300/400
CPU with PFOFIBUS,
CPU 315-2 DP/PN 1 6ES7315-2EH14-0AB0
which supports data
record routing, see /9/
MMC 128kB 1 6ES7953-8LG30-0AA0 or larger MMC
or another module with
SM 323 1 6ES7323-1BH01-0AA0
DIs
SIMATIC Panel KTP600 This panel is optional.
1 6AV6647-0AD11-3AX0
Basic color PN
This SINAMICS
SINAMICS IOP oder 6SL3255-0AA00-4JA1
1 operator panel is
SINAMICS BOP-2 6SL3255-0AA00-4CA1
optional.
Includes STARTER on
Siemens AG 2014 All rights reserved

DVD and USB cable.


SINAMICS G120 As an alternative, the
PC converter 1 6SL3255-0AA00-2CA0 SW can be downloaded
connection kit -3.28yd (/6/) and a standard
micro USB cable be
used.
Two for the PG/PC
connection with the
PROFINET S7-CPU and two for the
4 6GK1901-1BB10-2AA0
Copyright

connector plug optional connection


between S7-CPU and
HMI.
PROFINET line 6XV1840-2AH10
Motor 1 1LA7083-4AA60

Hardware components when using a SINAMICS G110M


Table 2-2 Hardware components
Component Qty. Order number Note
6SL3517-1BE12-3AM0 oder any other G110M
1
(PM240M) power module
SINAMICS G110M
6SL3544-0TB02-1FA0 oder any other G110M
1
(CU240M PN) PROFINET control unit
6GK1901-0DB20-6AA0 straight
PROFINET
2 or or
connector plug M12
3RK1902-2DA00 angled
Connector and cable for
network and motor see /10/
connections

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 9
2 Solution
2.3 Hardware and software components used

Hardware components when using a SINAMICS G120


Table 2-3 Hardware components
Component Qty. Order number Note
1 6SL3244-0BB12-1FA0 or CU250S-2 PN
(CU 240E-2 PN) und (6SL3246-0BA22-1FA0)
SINAMICS G120
1 6SL3224-0BE22-2UA0
(PM240)
Two additional ones, to
PROFINET connect the SINAMICS
2 6GK1901-1BB10-2AA0
connector plug G120 with S7-300/400
and HMI

Hardware components when using a SINAMICS G120C


Table 2-4 Hardware components
Component Qty. Order number Note
or any other
SINAMICS G120C 1 6SL3210-1KE14-3UF1
SINAMICS G120C PN
Two additional ones, to
PROFINET connect the SINAMICS
2 6GK1901-1BB10-2AA0
Siemens AG 2014 All rights reserved

connector plug G120 with S7-300/400


and HMI

Hardware components when using a SINAMICS G120D


Table 2-5 Hardware components
Component Qty. Order number Note
1 6SL3544-0FB20-1FA0
Copyright

(CU 240D-2 PN) and


SINAMICS G120D
1 6SL3525-0PE21-5AA1 or any other PM250D
(PM250D) power unit
6GK1901-0DB20-6AA0 straight
PROFINET
2 or or
connector plug M12
3RK1902-2DA00 angled
Connector and cable for
network and motor see /10/.
connections

Hardware components when using a SINAMICS G120P


Table 2-6 Hardware components
Component Qty. Order number Note
1 6SL3243-0BB30-1FA0
(CU 230P-2 PN) and
SINAMICS G120P
1 6SL3223-0DE21-1BA0 or any other PM230
(PM230) power unit
Two additional ones, to
PROFINET connect the SINAMICS
2 6GK1901-1BB10-2AA0
connector plug G120 with S7-300/400
and HMI

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 10
2 Solution
2.3 Hardware and software components used

Software components
Table 2-7 Software components
Component Qty. Order number Note
SIMATIC STEP 7 Floating License
1
V5.5 SP4 6ES7810-4CC10-0YA5
STARTER
1 6SL3072-0AA00-0AG0 Free download: see /6/
V4.4
WinCC flexible 1 6AV6613-0AA51-3CA5
Version: 2008 SP3

Sample files and projects


The following list includes all files and projects used in this example /4/.
The project files only differ in the SINAMICS drives configured in it. The documentations apply
for all types of the SINAMICS drives projected.

Table 2-8 Sample files and projects


Component Note
STEP 7 project with
58820849_SINAMICS_G110M_at_S7-300400-PN_CODE_v23.zip
SINAMICS G110
Siemens AG 2014 All rights reserved

STEP 7 project with


1
58820849_SINAMICS_G120_E_at_S7-300400-PN_CODE_vnn.zip SINAMICS G120 and
CU240E-2 PN
STEP 7 project with
1
58820849_SINAMICS_G120_EF_at_S7-300400-PN_CODE_vnn.zip SINAMICS G120 and
CU240E-2 PN F
STEP 7 project with
1
58820849_SINAMICS_G120_S_at_S7-300400-PN_CODE_vnn.zip SINAMICS G120 and
CU250S-2 PN
Copyright

1 STEP 7 project with


58820849_SINAMICS_G120C_at_S7-300400-PN_CODE_vnn.zip
SINAMICS G120C
STEP 7 project with
1
58820849_SINAMICS_G120D_CU240D_at_S7-300400-PN_CODE_vnn.zip SINAMICS G120D and
CU240D-2 PN
STEP 7 project with
1
58820849_SINAMICS_G120D_CU240DF_at_S7-300400-PN_CODE_vnn.zip SINAMICS G120D and
CU240D-2 PN
1 STEP 7 project with
58820849_SINAMICS_G120P_at_S7-300400-PN_CODE_vnn.zip
SINAMICS G120P
Short documentation
58820849_SINAMICS_G120_at_S7-300400_SHORT-DOKU_v23_en.pdf
for experienced users
58820849_SINAMICS_G120_at_S7-300400-PN_DOKU_v23_en.pdf This document
1
nn = 22: for SINAMICS G120 with FW 4.6
nn = 23: for SINAMICS G120 with FW 4.7

CAUTION The example projects have been designed for usage with the example
components listed in Table 2-1. Converter and/or motor can be damaged or
destroyed if a SINAMICS G with a different output or a different motor is
connected, without adjusting the respective parameters.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 11
3 Setting up and Commissioning the Application
3.1 Wiring

3 Setting up and Commissioning the


Application
In the screenshots and graphics below, a general project name “G120_at_S7-300400”, or
Notes
“SINAMICS G120” respectively, is used. In example projects, the respectively used
SINAMICS type is specified.

3.1 Wiring
The figure below shows the hardware setup of the application.
Figure 3-1
L1
L2
L3
N
PE
24V
0V

on off2 off3 Ack Rev 0 n+ n-


L1 L2 L3 PE

+24 V OUT
Siemens AG 2014 All rights reserved

DI 4
F-DI1)
DI 5 L+ M E 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 M
SM323
DI COM 1
PB PN PN CPU 315-2 PN/DP
DI COM 2 2)
GND USB
USB line
is optional.
SINAMICS
G120
Copyright

U2 V2 W2 PE PN PN

L+ M PN PN USB
M
Y
SIMATIC Panel PG/PC
KTP600

1) F-DI not for CU230P-2 PN


2) For CU250S-2: DI5-

Notes The setup guidelines in the SINAMICS G manual (see /7/) and SIMATIC must
generally be followed.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 12
3 Setting up and Commissioning the Application
3.2 IP addresses and PN names

3.2 IP addresses and PN names


The following IP addresses and device names are used in the sample projects:

Table 3-1
IP Component Device Name
192.168.0.1 S7-CPU S7-CPU
G110M G110M
CU230P-2 PN G120xCU230Px2
CU240E-2 PN G120xCU240Ex2
CU240E-2 PN F G120xCU240Ex2xF
192.168.0.2
CU240S-2 PN G120xCU250Sx2xV
CU240D-2 PN G120xCU240Dx2
CU240D-2 PN F G120xCU240Dx2xF
G120C PN G120C
192.168.0.3 KTP600 KTP600
192.168.0.200 PG/PC

By default STEP 7 enters the device’s Short Designation for the device name. But
the user can modify it as needed. The device name is not case sensitive.
Siemens AG 2014 All rights reserved

The network mask is always 255.255.255.0 and no router is used.

3.3 Settings on PG/PC


Table 3-2
Action Screenshots / Remarks
Set the fixed TCP/IP address
Copyright

192.168.0.200 and the


network mask 255.255.255.0
in the Windows settings for
the network card to be used.
You may also enter any other
IP address (192.168.0.x).

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 13
3 Setting up and Commissioning the Application
3.4 Downloading the SIMATIC program

3.4 Downloading the SIMATIC program


This chapter describes the steps for the installation of the example code.

Table 3-3
No. Action Screenshots / Remarks
1. Connect the controller with the You can connect both devices directly or via a switch.
SIMATIC S7-300/400 using a
network cable.
2. Start STEP 7.
Siemens AG 2014 All rights reserved

3. Via “Extras > Set PG/PC


Interface...” you open the
settings of the online interface.
Copyright

Select the “TCP/IP network card”


with the network card used by
you.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 14
3 Setting up and Commissioning the Application
3.4 Downloading the SIMATIC program

No. Action Screenshots / Remarks


4. Call up the “Edit Ethernet
Node…” dialog.

5. Click on “Browse...”
– Select the CPU and click
OK.
Enter the IP address
192.168.0.1 and the subnet
mask 255.255.255.0, and
click on “Assign IP
Configuration”.
Enter the device name
“s7-cpu” and click on
“Assign Name”.
Exit the dialog by clicking
Siemens AG 2014 All rights reserved

“Close”.
Copyright

6. Click on “Accessible Nodes”.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 15
3 Setting up and Commissioning the Application
3.4 Downloading the SIMATIC program

No. Action Screenshots / Remarks


7. Mark all of the blocks in the
CPU with <STRG><A> and
delete them.
Acknowledge that system
blocks and system data
cannot be deleted.

8. If you have not yet dearchived


the project, select a project file in
“File > Retrieve...”, and
dearchive it.
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 16
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


9. Open the project, select the
“Blocks” folder and clock on
“Download” or “Blocks”
respectively.
Also download the system
data!

10. Restart the CPU after


downloading.
11. If you want to use the HMI,
assign the address 192.168.0.3
Siemens AG 2014 All rights reserved

and load it in the HMI


configuration.

3.5 Downloading the SINAMICS configuration


This chapter describes the steps for downloading the example configuration.
This can be performed via the network (LAN) connection, or directly via a USB
Copyright

connection of the PG/PC.

Notes Should you use a different SINAMICS G or motor you need to perform your own
configuration. Follow the instructions in chapter 6 “Configuration and Settings”,
especially steps 13 and 14.
In the screenshots below, a SINAMICS G is used. In the instruction texts deviating
names of the other SINAMICS G converter types might be mentioned.
The SIMATIC S7-300/400 CPU must support data record routing. (CPU 31x with
FW3.x or CPU 41x with FW5.1 or newer), see /9/

3.5.1 Preparation for using the network connection of the PG/PC

Table 3-4
No. Action Screenshots / Remarks
1. Connect the CU 240E-2 PN of You can connect both devices directly or via a switch.
the SINAMICS G120 to the
PG/PC.
2. Unless the SIMATIC program is
currently loaded, please perform
steps 1 to 3 from Table 3-3.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 17
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


3. Call up the “Edit Ethernet
Node…” dialog.

4. Click on “Browse...”
Select the SINAMICS G and
click on OK.
Enter the IP address
192.168.0.2 and the subnet
mask 255.255.255.0, and
click on “Assign IP
Configuration”.
Enter the device name of
your CU and click on
“Assign Name” (please
observe the note).
Siemens AG 2014 All rights reserved

– G110M
– G120xCU230Px2
– G120xCU240Ex2
– G120xCU240Ex2xF
– G120xCU250Sx2xV
– G120xCU240Dx2
– G120xCU240Dx2xF
– G120C
Exit the dialog by clicking
Copyright

“Close”.
Note:
The device name must match
the one given in the Properties of
SINAMICS G in HW Config.

5. Click on SINAMICS G.
Depending on the used
project, the SINAMICS G is
called…
– G110M_PN
– G120_CU230P_2_PN
– G120_CU240E_2_PN
– G120_CU240E_2_PN_F
– G120_CU250S_2_V_PN
– G120_CU240D_2_PN
– G120_CU240D_2_PN_F
– G120C_PN
Click 2x on
“Commissioning”.
This opens the STARTER
with the project.
The picture shows the example of a SINAMICS G120 with
CU 240E-2 PN.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 18
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


6. After the STARTER has opened,
select the SINAMICS G and
open its properties by clicking on
the right mouse button.
Siemens AG 2014 All rights reserved

7. Select
“S7ONLINE(TCP/IP->Network
card” and click on “OK”.
Copyright

8. Proceed with the instructions in


chapter 3.5.3.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 19
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

3.5.2 Preparations for using the USB connection of the PG/PC

Table 3-5
No. Action Screenshots / Remarks
1 Connect the SINAMICS G with the
PG/PC using a USB cable.
Wait until Windows has
recognized the SINAMICS G (USB
Mass Storage Device).

2 Click on SINAMICS G.
Siemens AG 2014 All rights reserved

Depending on the used


project, the SINAMICS G is
called…
– G110M_PN
– G120_CU230P_2_PN
– G120_CU240E_2_PN
– G120_CU240E_2_PN_F
– G120_CU250S_2_V_PN
– G120_CU240D_2_PN
Copyright

– G120_CU240D_2_PN_F
– G120C_PN

Click 2x on “Commissioning”.
This opens the STARTER
with the project.

The picture shows the example of a SINAMICS G120 with


CU 240E-2 PN.
3 Open “Set PG/PC interface”.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 20
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


3 Ensure that interface “S7USB” has
been programmed for the
“DEVICE (STARTER,SCOUT)”
access point and acknowledge
with OK.
Siemens AG 2014 All rights reserved

4 Mark the SINAMICS G and open


its Properties with the right mouse
button.
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 21
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


5 Select “DEVICE (S7USB)” and
click “OK”.

6 Proceed with the instructions in


chapter 3.5.3.

3.5.3 Downloading the configuration into the SINAMICS G


Siemens AG 2014 All rights reserved

Table 3-6
No. Action Screenshots / Remarks
1. Go online.
Copyright

2. If the “Target Device Selection”


window opens,
set the checkmark at
SINAMICS G,
select the desired access
point (S7Online for the
network and DEVICE for the
USB interface) and
click on “OK”.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 22
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


3. If the “Online/offline comparison”
window opens, click on “Load HW
Configuration to PG”

4. Start the download and tick “After


loading, copy RAM to ROM”.

Should you receive a note which


indicates different parameters for
Siemens AG 2014 All rights reserved

the power unit, you need to make


your own configuration. Follow the
instructions in chapter 6
“Configuration and Settings”,
especially steps 13 and 14.

If you have a CU without safety


functions (e.g. a CU240B-2PN),
continue with step 8.
5. Open “Functions>Safety
Copyright

Integrated” in the tree and click on


“Change settings” first, then on
“Copy Parameters” and then on
“Activate settings”.

6. Enter a password (e.g. “12345”)


and click on “OK”.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 23
3 Setting up and Commissioning the Application
3.5 Downloading the SINAMICS configuration

No. Action Screenshots / Remarks


7. Choose “Yes”, to save the
parameters in ROM.

8. Go offline.

9. Perform a power reset. Switch off all supply voltages of SINAMICS G, wait until all
LEDs are off, and then switch back on.
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 24
4 Operation of the Application
4.1 Prerequisites

4 Operation of the Application


4.1 Prerequisites
To be able to switch on the SINAMICS G via the SIMATIC S7-300/400 inputs, the
following points must be fulfilled:
If the safety functions of the SINAMICS G has been activated, then 24V must
be supplied at terminals 16 and 17 (DI 4 and 5) of the SINAMICS G; otherwise,
the STO safety function is active, the yellow “SAFE” LED at the SINAMICS G is
blinking and the SINAMICS G cannot be switched on.
For the SINAMICS G120D, these are terminals X9.2 and X9.4 .
24V must not be supplied at terminal 8 (DI 3) of the SINAMICS G120,
otherwise the command data record is switched over (at standard
configuration).
For SINAMICS G120D this is terminal X8.2.
When using an IOP, please check that the network icon ( ) is displayed on
the top right. If the hand icon ( ) is displayed there, press the Hand/Auto
button ( ).
When using a BOP-2, please check whether the hand icon ( ) is displayed. If
Siemens AG 2014 All rights reserved

yes, press the Hand/Auto button ( ).

4.2 Operation of the Application


SINAMICS G is exclusively moved via digital inputs. The HMI is then only used for
monitoring.
Copyright

Table 4-1
Terminal Name Function
E 0.0 ON Switching SINAMICS G on/off,
(Off2 and Off3 =1 must apply for the operation)
E 0.1 OFF2 0= Motor immediately switched off, drive spins out
E 0.2 OFF3 0= Fast stop, motor is decelerated with Off3 ramp down time (P1135) until it
stops
E 0.3 Ack Rising edge acknowledges a pending error in the SINAMICS G
E 0.4 Rev Reversed direction, the polarity of the setpoint value is negated
E 0.5 0 The setpoint value is set to 0.
E 0.6 n+ The setpoint value is increased
E 0.7 n- The setpoint value is decreased

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 25
4 Operation of the Application
4.2 Operation of the Application

To switch on SINAMICS G, please perform the steps below:

Table 4-2
Step Action Note / Result
1. Apply 24V to OFF2(E0.1) and The further required control bits for the
OFF3(E0.2). operation are permanently set to 1 by
the program.
2. Enter a pulse (switching on and This acknowledges a possibly pending
back off) to Ack (E0.3). error message.
3. Enter a pulse (switching on and The setpoint is set to 0.
back off) to 0 (E0.5).
4. Apply 24V to ON(E0.0). The drive switches on.
5. Change the setpoint value with The speed of the motor changes.
inputs n+ (E 0.6), n- (E0.7) and 0
(E0.5).
6. Detach the 24V from ON(E0.0). The drive switches back off.
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 26
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

4.3 Monitoring and parameter access via operator panel


4.3.1 Screens and screen navigation

Figure 4-1

Start screen
From all subordinate
screens

From all subordinate


screens Example project Support

Online Support - Promotion


Overview screen
Siemens AG 2014 All rights reserved

Process data exchange Parameter access


Status and control word

REad / write parameters


Copyright

Setpoint and actual values

Fault buffer

Terminate Runtime

Switch language (German/English)

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 27
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

4.3.2 Process data exchange

Both screens for the process data exchange access the idb_Process_Data data
block (DB11).

Control and status word

Figure 4-2
Siemens AG 2014 All rights reserved
Copyright

The bit commands, which you can partially specify via the digital input module, are
displayed in the 16 bit wide control word.
The current state of the SINAMICS G is given via the also 16 bit wide status word.

Manual mode
Using the “Manual mode” button enables activating the manual mode of the block.
Instead of switching to the control signals pending at the block, in this example to
the digital inputs, this mode switches to an internal control word specified via HMI,
for example. Also, an internal value is used instead of the pending setpoint value.
This enables a simple manual/automatic switch-over.

When (de-)activating the manual mode, the control word and the setpoint
value are not adjusted. It is therefore possible when switching over that
SINAMICS G automatically starts up or changes the speed.
DANGER

In this example, this enables switching from the digital inputs to manual operation
via HMI. The set control word bits are then displayed yellow.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 28
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

Setpoint and actual values

Figure 4-3
Siemens AG 2014 All rights reserved

Setpoint speed value:


Here, the setpoint speed value is displayed which in this example, is set via the
digital inputs E0.4 to E0.7 (see Table 4-1).
Copyright

In manual mode, the speed setpoint value is directly specified via HMI, the input
field is then shaded yellow.

When (de-)activating the manual mode, the control word and the setpoint
value are not adjusted. It is therefore possible when switching over that
SINAMICS G automatically starts up or changes the speed.
DANGER

Actual values:
The current actual values for speed, electrical current and torque are displayed
below the speed setpoint value input.

Control and status word:


To keep an eye on control word and status word, without switching to the
respective screen, they are also given here as a miniature display.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 29
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

Current messages:
Current faults and warnings are displayed with a respective number. A “0” means
that no fault or alarm exists. If a message is pending it is displayed according to
Figure 4-4.

Figure 4-4

Tap or click on the message number to display the respective message text.

Figure 4-5
Siemens AG 2014 All rights reserved
Copyright

The message text is displayed as long as the message number is pressed.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 30
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

4.3.3 Parameter access

Both screens for the process data exchange access the idb_Parameter_Access
data block (DB11).

Reading/writing parameters

Figure 4-6
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 31
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

Table 4-3
Action Comment
1. Select the access type with the “Read The selected access type is displayed
parameters” and “Write parameters” via a bright green button.
buttons.
2. Read parameters:
Proceed with point 3 in the table.
Write parameters:
When tapping or clicking the yellow
input field for the rampup/rampdown
time, a keyboard mask for the value
input opens. Close your input with the
Return key.
8,0
Siemens AG 2014 All rights reserved

3. Start the write or read job with the The job status specifies how the job
“Start” button. was completed:
done = completed without error
errori = job cancelled with error

The status refers to processing the


system function blocks SFB 52
“RDREC” and SFB 53 “WRREC” in
STEP7 code. For error diagnosis see
/3/.
Copyright

done and drive_errori means that the


job was transferred without error,
however, SINAMICS G could not or only
partially process the job.
The error codes are available in chapter
6.1.5.1 “Configuring the fieldbus,
PROFIdrive profile for PROFIBUS and
PROFINET, acyclic communication” in
the operating instruction (/7/).
4. Click “Start” again to terminate the The bits of the job status are deleted as
transmission requirement. soon as the transmission requirement is
no longer pending.

Note If you wish to check the parameters after a write job, you must trigger an
additional read job.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 32
4 Operation of the Application
4.3 Monitoring and parameter access via operator panel

Fault buffer
The screen displays the fault codes of eight current and eight acknowledged faults,
which are saved in the SINAMICS G.

Note The values are read by SINAMICS G via the “Read parameters” function in
Figure 4-6 and saved in the SIMATIC S7-300/400.
When the “Fault buffer” screen comes up, the data stored in SIMATIC S7-
300/400 is displayed and may therefore be out of date.

Figure 4-7
Siemens AG 2014 All rights reserved
Copyright

Tap or click on the message number to display the respective message text.

Figure 4-8

The message text is displayed as long as the message number is pressed.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 33
5 Functional Mechanisms of the Application

5 Functional Mechanisms of the Application


Program overview
Figure 5-1

OB 1 FC 5 “setpoint_
simulation“
“CYCL_EXC“

FB 10 “process data“

DB 10
“idb process data“
DB 100 “write drive
parameter“

FB 20 “parameter SFB 53 “WRREC“ DB 102 “answer


access“ from drive_write“

SFB 52 “RDREC“ DB 101 “read drive


parameter“

DB 103 “answer
DB 20 “idb parameter access“ from drive_read“
Siemens AG 2014 All rights reserved

The SIMATIC S7-300/400 program consists of three areas:


Setpoint value simulation
In this area a user program is simulated and a speed value generated with the
digital inputs.
Process data exchange
Copyright

In this area, the process data for the SINAMICS G is transmitted (e.g. one
command and setpoint) or received (status and actual values)
Parameter access
In this area, the parameters SINAMICS G are accessed.

Note The two communication areas, process data and parameter access, are
independent from each other and can each also be used individually.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 34
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

5.1 Functionality of process data exchange


Figure 5-2

OB 1 FC 5 “setpoint_
simulation“
“CYCL_EXC“

FB 10 “process data“

DB 10
“idb process data“
DB 100 “write drive
parameter“

FB 20 “parameter SFB 53 “WRREC“ DB 102 “answer


access“ from drive_write“

SFB 52 “RDREC“ DB 101 “read drive


parameter“

DB 103 “answer
DB 20 “idb parameter access“ from drive_read“
Siemens AG 2014 All rights reserved

The process data contains values which are regularly exchanged between
SIMATIC S7-300/400 and SINAMICS G. These values are at least the control and
status word as well as the setpoint and actual value. Selecting the message frame
type specifies the exact length and structure.
Copyright

The “Siemens Telegram 352, PZD 6/6” message frame type used in the example
exchanges 6 words in both directions, which are:
Table 5-1 Structure of Siemens “Telegram 352, PZD 6/6”
Send direction (viewed from SIMATIC) Receive direction (viewed from SIMATIC)
Control word Status word
Setpoint speed value Current speed (actual speed value)
(not used) Current electrical current
(not used) Current torque
(not used) Current warning
(not used) Current fault

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 35
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

5.1.1 Accessing process data in the user program of the SIMATIC S7-
300/400

At the start of the cycle, the operating system of SIMATIC S7-300/400 stores the
(user) data received by the SINAMICS G in the I/O input area of the SIMATIC CPU
and transmits the data stored in the I/O output area to the SINAMICS G at the end
of the cycle. In the user program, the data can be accessed by reading from or
writing to the I/O area. The address areas used are defined when specifying the
hardware configuration. See step 16 in Table 6-1.
If the I/O is accessed with the SFC 14/15 system functions, the consistency is
ensured across the entire data; hence, these functions are used in the example
program.

5.1.2 Standardizing the setpoint and actual values

The setpoint and actual values are transferred as standards. The reference values
are stored in parameters P2000 to P2006 of the SINAMICS G.
FB20 “Parameter_Access” takes on entirely the conversion of setpoint and actual
values. The reference values for speed current, torque stored in parameters
P2000, P2003 and P2004 of SINAMICS must also be entered at the block input.
Siemens AG 2014 All rights reserved

16384dec = 4000hex = 100% applies here, with 100% referring to the reference
value for the transferred variable.
Example:
If P2000 (reference speed or reference frequency) is 1500 1/min and if a speed
of 500 1/min shall be run, then 33% or 5461dec must be transferred.
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 36
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

5.1.3 Control and status word

The control and status word has already been defined. The subsequent figures
illustrate the control and status word when selecting the “Siemens Telegram 352,
PZD 6/6” message frame type.

Figure 5-3: Control word of the “Siemens Telegram 352, PZD 6/6” message frame type
Siemens AG 2014 All rights reserved
Copyright

Note A control word for which all bits are 0 is rejected as invalid by the SINAMICS G.
Therefore, at least bit 10 must always be set.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 37
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

Figure 5-4 Status word of the “Siemens Telegram 352, PZD 6/6” message frame type
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 38
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

5.1.4 FB 10 “PZD_G120_Tel_352”

This FB takes on the transmission of the process data from and to the SINAMICS
G. It copies the main control and status bits and converts the setpoint and actual
values. It can therefore be used as interface with SINAMICS G in own applications.

Figure 5-5 FB 10 “ PZD_G120_Tel_352“


Siemens AG 2014 All rights reserved
Copyright

Table 5-2 Interfaces of FB 10 “PZD_G120_Tel_352”


Data Initial
Parameter Description
type value
Input parameters
Address INT 0 IO address of SINAMICS G
Here, the IO address must be specified
which was assigned for message frame
352 of SINAMICS in HW Config.
Input and output address must be
identical to be able to use this block.
ON_OFF1 BOOL FALSE SINAMICS is switched on with a rising
edge at ON_OFF1.
Requirements:
OFF2 and OFF3 must already be
TRUE beforehand
No error must be pending
OFF2 BOOL TRUE Immediate STOP (motor coasts)
OFF3 BOOL TRUE Fast stop (with ramp down time in
P1153)

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 39
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

Data Initial
Parameter Description
type value
Acknowledge BOOL FALSE Pending errors are acknowledged with
rising edge.
Direction_reversal BOOL FALSE With this input, the polarity of the
setpoint value can be changed.
Activate_manual_mode BOOL FALSE Switches the block between manual
and automatic mode.
For FALSE, the control word and the
setpoint value are formed of the signals
pending at the block, for TRUE, control
word and setpoint value from tags in
the instance DB are used and can be
specified via HMI, for example.
Speed_setpoint REAL 0.0 Setpoint speed value in U/min
Negative values change the direction
Reference_speed_P2000 REAL 1500.0 Reference speed
Here, the same value must be specified
as in parameter P2000 of SINAMICS
G.
Reference_current_P2002 REAL 0.0 Reference current
Here, the same value must be specified
Siemens AG 2014 All rights reserved

as in parameter P2002 of SINAMICS


G.
Reference_torque_P2003 REAL 0.0 Reference torque
Here, the same value must be specified
as in parameter P2003 of SINAMICS
G.
Output parameters
Operation_enabled BOOL Drive is switched on, motor follows the
setpoint value.
Copyright

Closing_lockout_active BOOL On-inhibit active.


To cancel it, ON_OFF1 must be set to
FALSE and possibly pending errors be
acknowledged.
Alarm_active BOOL The SINAMICS G outputs a warning.
Fault_active BOOL The SINAMICS G outputs a fault.
Rotating_forward BOOL Rotational direction of the motor.
Output is TRUE, if the motor rotates
forward.
Actual_speed REAL Current speed in U/min.
Negative values mean that the motor
rotates backwards.
Actual_current REAL Current motor current in A
Actual_torque REAL Current motor torque in Nm
Negative values mean that the motor
decelerates.
Actual_alarm REAL Code of the currently pending error
Actual_fault REAL Code of the currently pending warning

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 40
5 Functional Mechanisms of the Application
5.1 Functionality of process data exchange

NOTICE To switch on SINAMICS G, OFF2 and OFF3 must initially be TRUE, then
SINAMICS G can be switched on with a positive edge (i.e. the signal
changes from FALSE to TRUE) at ON/OFF1.

Manual/automatic switchover (manual mode)


This function enables selecting whether SINAMICS G shall be controlled with the
values pending at the block inputs, or whether internal values shall be used and
the block inputs be ignored.
The internal values are located in the instance DB (“internal_Control_word” and
“internal_Status_word”) and can be specified by a visualization.
This enables realizing a switch-over between the values supplied by SIMATIC S7
(automatic) and the specification via a visualization (manual).
Independent of these settings, the bits of the status word and the actual values are
always output.

When switching over (activating or deactivating the manual mode), the


control word and the setpoint value are not adjusted. It is therefore
possible when switching over that SINAMICS G automatically starts up or
DANGER changes the speed.
Siemens AG 2014 All rights reserved

SCL language
FB 10 “PZD_G120_Tel_352” was created in SCL. During compilation in the block
folder, the SCL editor generates a function block created in STL. It can be copied
into your own projects and used without installed SCL.
SCL source “Process_Data(Tel_352)” is located in the “Sources” subfolder of the
S7 program.
The SCL source can be exported via the context menu and then be viewed with
any text editor.
Copyright

Figure 5-6

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 41
5 Functional Mechanisms of the Application
5.2 Change-over to “Siemens Telegram 1” (with FB11)

5.2 Change-over to “Siemens Telegram 1” (with FB11)


FB11 “PZD_G120_Tel_1” is, like FB10 “PZD_G120_Tel_352”, intended for
transmission of process data, however, it expects message frame “Siemens
Telegram 1” instead of “Siemens Telegram 352”.
The “Telegram 1” message frame only transfers two words in any direction: control
word and setpoint value or status word and actual value.

Figure 5-7
Siemens AG 2014 All rights reserved
Copyright

To switch over to message frame “Telegram 1”, you have to:


select message frame “Telegram 1” for SINAMICS G in HW Config,
call FB11“ PZD_G120_Tel_1” in OB1 instead of FB10 “PZD_G120_Tel_352”,
load the program folder into the CPU again (inc. system data, see Tab. 3.4
step 9),
change the interface configuration of SINAMICS G to message frame
“Telegram 1” in the Starter, see Tab. 6.2 step 15) and
adjust the HMI.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 42
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

5.3 Parameter access functionality


Figure 5-8

OB 1 FC 5 “setpoint_
simulation“
“CYCL_EXC“

FB 10 “process data“

DB 10
“idb process data“
DB 100 “write drive
parameter“

FB 20 “parameter SFB 53 “WRREC“ DB 102 “answer


access“ from drive_write“

SFB 52 “RDREC“ DB 101 “read drive


parameter“

DB 103 “answer
DB 20 “idb parameter access“ from drive_read“
Siemens AG 2014 All rights reserved

Acyclic parameter access occurs parallel to the cyclic process data exchange. This
saves resources, since this connection is only established on demand, i.e. when
accessing a parameter.
In SIMATIC S7-300/400, the “Write data record” and “Read data record” functions
must be used. Data record 47 must always be used.
Writing data record 47 sends a job to the SINAMICS G which performs the job and
provides a response. Reading data record 47 makes the response of SINAMICS G
available in SIMATIC S7-300/400 and can be evaluated.
Copyright

For reading and writing data records, the system function blocks SFB 53 “WRREC”
and SFB 52 “RDREC” are used in SIMATIC S7-300/400.
For the Data record 47 please refer to chap. 3.1.2 in the function manual Fieldbus
systems (Manuals).

Note Since SFB 53 “WRREC” and SFB 52 “RDREC” are not used with CP341-1, the
parameter access is not possible when using this CP.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 43
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

5.3.1 FB 20 “Parameter_Access”

The parameters are accessed in FB 20 “Parameter_Access”. It is called cyclically


in OB 1. The block was created so they can simply be used in own applications.

Figure 5-9

Table 5-3 Interfaces of FB 20 “Parameter_Access”


Data Initial
Parameter Description
type value
Siemens AG 2014 All rights reserved

Input parameters
Address INT 0 IO address of SINAMICS G.
Here, the IO address must be specified
which was assigned for message frame
Telegram 352 of SINAMICS in HW
Config.
Input and output address must be
identical to be able to use this block.
Copyright

DB_No_send INT 0 Number of the DB in which the data


record to be sent is stored.
DB_No_rev INT 0 Number of the DB in which the
response of SINAMICS G is to be
stored.
START BOOL FALSE The transmission is started with a rising
edge at START.
Output parameters
Busy BOOL Transmission active
Done BOOL Job successfully transferred.
Drive_Error BOOL Job successfully transferred, however,
the job could not or only partially be
completed by SINAMICS G.
The response contains the error
detection.
Error BOOL Access aborted with transmission error
ErrorID WORD Cause of the abort (see subsequent
error list)

Error list
The FB 20 “Parameter_Access” can output the following error codes:

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 44
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

Table 5-4
Error number Description Note
0 No error
8000 DB_No_send and DB_No_rev
are identical. Check the parameters of FB 20
8001 DB_No_rev or DB_No_send is “Parameter_Access”.
zero.
8002 SFC53 “WEREC” outputs In the instance DB, the error code of
errors the SFC is stored in
#WD_REC_STATUS.
8003 SFC53 “WEREC” outputs In the instance DB, the error code of
errors the SFC is stored in
#RD_REC_STATUS.
8004 Send DB is empty (length 0), In the instance DB, the error code of
non existent or faulty. the SFC24 “TEST_DB” is stored in
#TEST_DB_1_STATUS. If the code
is 0, the DB is empty or write
protected.
8005 Receive DB is empty (length In the instance DB, the error code of
0), non existent or faulty. the SFC24 “TEST_DB” is stored in
#TEST_DB_2_STATUS. If the code
is 0, the DB is empty or write
Siemens AG 2014 All rights reserved

protected.

Drive error
If during processing a job in SINAMICS G an error occurred, and the error
detection was set in the response, the response DB must be analyzed to find out
the cause of the error.
Copyright

Function
FB 20 “Parameter_Accesss” only transfers the selected DBs to or from SINAMICS
G and checks, whether the transmission was successful. It is also checked,
whether the error detection was set in the response of the SINAMICS G.
The structure of the error detection is available in chapter chapter 6.1.5.1
“Configuring the fieldbus, PROFIdrive profile for PROFIBUS and PROFINET,
acyclic communication” in the operating instruction (/7/)

Structure
The “Parameter” FB consists of three parts:
Checking the DB_No_xx input parameters
Network 1
A step chain which controls the sequence of the parameter access.
Networks 2 to 10
Call of the system functions “Read data record” or “Write data record”.
Network 11

Checking the DB_No_xx input parameters


It is checked, whether input parameters DB_No_send and DB_No_rev are equal or
if they were parameterized with “0”. One respective error message is output.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 45
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

Note Network 1 with checking the DB_No_xx input parameters can be deleted to save
computing time and storage space without affecting the other functions of the
block.

Step chain
The step chain of FB 20 “Parameter_access” is represented in the following
graphic. The possible transitions between the individual steps are also displayed
there.

Figure 5-10 Step chain


Siemens AG 2014 All rights reserved
Copyright

In the individual states of the step chain, the following functions are executed:

Table 5-5: Function of the states of FB 20 “Parameter_access”


State Function
0 Wait for start trigger Waiting for a rising edge of the “START” signal.
If it is detected, all output signals will be deleted, “BUSY” will
be set and step 1 will be activated.
1 Start WR_REC The “REQ” signal of SFB 53 “WRREC” is set and step 2 is
activated.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 46
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

State Function
2 Wait for end of Waiting until the “busy” signal of SFB 53 “WRREC” becomes
WR_REC 0 again. Then step 3 is activated.
3 Check result of It is checked whether the data record was written
WR_REC successfully.
If so, the “REQ” signal of SFB 53 “WRREC” will be deleted
again and step 4 will be activated.
If SFB 53 “WRREC” reports the error 16#DF80_B500 (peer
not ready), step 3 will be activated again and SFB 53
“WRREC” will repeat the job.
If a different error has occurred, the “REQ” signal of SFB 53
“WRREC” will be deleted, an internal error bit will be set and
step 7 will be activated.
4 Start RD_REC The “REQ” signal of FB “RDREC” is set and step 5 is
activated.
5 Wait for end of It is waited until the “busy” signal of FB “RDREC” becomes 0
RD_REC again. Then step 6 is activated.
6 Check result of Check whether the data record has been read successfully.
RD_REC If so, the “REQ” signal of SFB 52 “RDREC” will be deleted
again and step 7 will be activated.
If SFB 52 “RDREC” reports the error 16#DE80_B500 (peer
not ready), step 5 will be activated again and FB “RDREC”
Siemens AG 2014 All rights reserved

will repeat the job.


If a different error has occurred, the “REQ” signal of SFB 52
“RDREC” will be deleted, an internal error bit will be set and
step 7 will be activated.
7 Check for errors, It is checked whether one of the internal error bits has been
copy outputs set.
If an error bit has been set,
– the “ERROR” signal will be set,
– the “BUSY” signal deleted,
Copyright

– step 0 activated.
If no error bit has been set, the read times will be output, the
“BUSY” will be deleted, the “DONE” will be set and step 0
will be activated.

Call of the “Read data record” or “Write data record” system functions
After the currently required control bits were set in the sequence chart of FB 20
“Parameter_access”, the “Write data record” and “Read data record” system
functions (SFB 53 “WRREC” and SFB 52 “RDREC”) are called in network 10.
It is initially checked, whether the DB to be used exists in the SIMATIC S7-CPU
and how long it is. This creates an ANY pointer which references the data to be
send/received and calls the SFC.

5.3.2 The DBs “read/write_drive_parameters” and “answer_from_drive”

To access the parameters, a given job structure must be kept. The response of
SINAMICS G also contains a given response structure.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 47
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

Job and response structure


The structure of the jobs and responses are available in Chapter 7.3.2.1
“Configuring the fieldbus, PROFIdrive profile for PROFIBUS and PROFINET,
acyclic communication” in the operating instruction (/7/)

Note Since the structure of the data record to be sent or received depends on the
number of jobs and their number format, a generally valid structure cannot be
used.
FB 20 “Parameter_Access” is therefore limited to sending and receiving the data
record. The DBs for the data record to be send and received must be set by the
user.

The job to access a parameter consists of at least 10 words. Therefore, the job
should be assembled in a DB. The response by the SINAMICS G also consists of
several words.
A job may contain the access to several parameters. Since the length of the data to
be transferred per job depends on the number and data types of the SINAMICS G
parameters, no generally valid structure can be devised.
In this example, only the ramp up and ramp down times (P1120 and P1121) and a
part of the fault memory (P945.x) is accessed. The job of writing the parameters is
Siemens AG 2014 All rights reserved

stored in DB 100 “write_drive_parameters” and the job to read the parameters in


DB 101 “read_drive_parameters”.
The response of the SINAMICS G is copied to DB 102 “answer_from_drive_write”
or DB 103 “answer_from_drive_read”. The structure contained therein corresponds
to the structure for a successful writing/reading of the parameters.

Figure 5-11 DB 100 for writing the ramp up and ramp down time (in the picture: 10s and 15 s)
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 48
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

Figure 5-12 DB 102 for the response to the write job


Siemens AG 2014 All rights reserved

Figure 5-13 DB 101 for reading the ramp up and ramp down time and 16 values of the fault memory
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 49
5 Functional Mechanisms of the Application
5.3 Parameter access functionality

Figure 5-14: DB 103 for the response of the read job


Siemens AG 2014 All rights reserved
Copyright

Note Since the structure of the data record to be sent or received depends on the
number of jobs and their number format, a generally valid structure cannot be
used.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 50
5 Functional Mechanisms of the Application
5.4 Function of the further blocks in the example projects

5.4 Function of the further blocks in the example projects


Apart from FB10 and FB20 further blocks are contained in the example projects
which are necessary to make the examples runnable.
These tables are:

Table 5-6
Block Function
OB86 If the connection to a PROFIBUS station is interrupted or
restored, the SIMATIC S7-CPU calls these error organization
blocks. If this OB does not exist in the SIMATIC S7-CPU, it
goes to STOP instead.
In this OB, the user can program a reaction to a failed or
restored station, in this example it is empty.
FC5 Function for generating a speed setpoint value using the digital
inputs.
The setpoint value is stored in MD0.
This block is not intended for use in your own projects.
VAT_Process_Data Value tables for monitoring and control of FB10 and FB20.
Siemens AG 2014 All rights reserved

VAT_Parameter_Access
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 51
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

6 Configuration and Settings


Note If you only wish to download and commission the example program, please
follow the instructions in chapter 3 “Setting up and Commissioning the
Application”.

The step tables below describe what you have to do if you do not want to or cannot
use the sample code and you want to or have to configure SINAMICS G and
SIMATIC S7 CPU yourself.

6.1 Configuring the SIMATIC S7-300/400 controller


This chapter describes how the SIMATIC S7-300/400 must be configured for the
example program. This chapter does not discuss integrating the operator panel or
programming the SIMATIC S7-300/400.
The screenshots below use a general STEP 7 project name: “G120_at_S7”.
Note

Table 6-1
Siemens AG 2014 All rights reserved

No. Action Screenshots / Remarks


1. Start STEP 7 V5.5
Copyright

2. Start the “New project” wizard.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 52
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


3. Select CPU 315-2DP/PN, or
another CPU, which supports
data record routing, see /9/.

4. In this screen you click


“Continue >”.
Siemens AG 2014 All rights reserved
Copyright

5. Assign a name for the project


(e.g. “G120_at_S7-300”).

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 53
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


6. Click on the S7-300 station
Double-click the “Hardware”
icon to open the hardware
configuration.

7. Select the PROFINET interface


of the CPU and choose “Insert
PROFINET IO System“ from the
context menu (right mouse
button)
Siemens AG 2014 All rights reserved
Copyright

8. Ensure that address


192.168.0.1 and network
mask 255.255.225.000 have
been assigned.
Click on the “New” button
and create an Ethernet
network. The CPU will
automatically be connected
to it.
Click OK
Click on OK in the higher-
level mask

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 54
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


9. Double-click on the PN/IO
interface of the CPU.

10. Change the device name to


“S7-CPU” (or the respective
name assigned during node
initiation (step 4 in Table 3-3) ).
Siemens AG 2014 All rights reserved
Copyright

11. Ensure that the PROFINET


network is displayed.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 55
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


12. Search your SINAMICS G in the catalog. The path in the catalog is:
> PROFINET IO > Drives > SINAMICS > SINAMICS G110M
G120
G120C
G120D
Then select the used CU (Control Unit).
Note:
For CU 230P-2 PN look in the G120 folder.
Siemens AG 2014 All rights reserved
Copyright

The picture shows the example of a selected SINAMICS G120 with CU 240E-2 PN.

13. Drag the selected CU onto


the PROFINET line and
release the mouse button.

The window for selecting the


Ethernet interface opens
automatically:
Select address 192.168.0.2
for SINAMICS G.
Click the OK button.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 56
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


14. Confirm or select the firmware
you use..

15. Double-click slot 1.2 of


SINAMICS G, so its properties
are displayed.
Siemens AG 2014 All rights reserved
Copyright

16. Go to the “Message Frames”


tab.
Select “Siemens message
frame 352, PZD 6/6”
Ensure that the I-address
and the Q-address are both
256 respectively.
Click OK to close the dialog
box

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 57
6 Configuration and Settings
6.1 Configuring the SIMATIC S7-300/400 controller

No. Action Screenshots / Remarks


17. Enter a DI or DI/DO module (e.g.
6ES323-1BH01-0AA0) on slot 4
of the central rack.
Please ensure that the I-address
is 0.

18. Thus, the hardware configuration


is completed.
Click “Save and compile”
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 58
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

6.2 Configuring the SINAMICS G drive


The subsequent configuration instruction assumes that the SINAMIC G is to be
accessed via routing.
Table 6-2
No. Action Screenshots / Remarks
1. If still unsuccessful, install the
STARTER commissioning
software (see /6/).
2. Connect SINAMICS G and SINAMICS G120 S7-300/400
SIMATIC S7-300 via network
cables.
Siemens AG 2014 All rights reserved

Ethernet

3. Start the SIMATIC Manager and


open the project created in
chapter 6.1.
Copyright

4. Call up the “Edit Ethernet


Node…” dialog.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 59
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


5. Click on “Browse...”
Select the SINAMICS G and
click on OK.
Enter the IP address
192.168.0.2 and the subnet
mask 255.255.255.0, and
click on “Assign IP
Configuration”.
Enter the device name of
your CU and click on
“Assign Name” (please
observe the note).
– G110M
– G120xCU230Px2
– G120xCU240Ex2
– G120xCU240Ex2xF
– G120xCU250Sx2xV
– G120xCU240Dx2
– G120xCU240Dx2xF
– G120C
Exit the dialog by clicking
Siemens AG 2014 All rights reserved

“Close”.
Note:
The device name must match
the one given in the Properties of
SINAMICS G in HW Config.
6. Click on SINAMICS G.
Depending on the used
project, the SINAMICS G is
called…
Copyright

– G110M_PN
– G120_CU230P_2_PN
– G120_CU240E_2_PN
– G120_CU240E_2_PN_F
– G120_CU250S_2_V_PN
– G120_CU240D_2_PN
– G120_CU240D_2_PN_F
– G120C_PN

Click 2x on “Commissioning”.
This opens the STARTER with
the project.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 60
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


7. After the STARTER has opened,
select the SINAMICS G and
open its properties by clicking on
the right mouse button.
Siemens AG 2014 All rights reserved

8. Select
“S7ONLINE(TCP/IP->Network
card” and click on “OK”.
Copyright

9. Call up the “Target Device


Selection” dialog in the
STARTER via “Target system >
Select target device...”.
Select the CU and the
“S7ONLINE” access point and
then click on OK.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 61
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


10. Go online.

11. Select the SINAMICS G in the


tree and then press “Restore
factory settings”.

12. Remove the checkmark for


“Save factory settings to ROM”
and then click “OK”.
Siemens AG 2014 All rights reserved

13. Expand the tree and click on


“Configuration”.
Then call up the wizard.
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 62
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


14. Run the wizard and enter the
data you need.
If you have no specific
requirements, use the respective
default values, apart from the
following exceptions
Ensure that the field bus is
selected in the “Defaults of
the setpoint/command
sources” step.
In the “Motor” step you enter
the data of the connected
motor.

15. After the wizard has been run


through completely, double-click
on “Communication >
Siemens AG 2014 All rights reserved

PROFINET” in the tree, select


one of the “Receive” or “Send
direction” tabs, and select
if the PROFIsafe selection is
avaible, :“No PROFIsafe
telegram selected” and
“Siemens telegram 352,
PZD 6/6)”.
Note:
Copyright

The message frame type and the


address match the example.
It is decisive here that the same
message frame and the same
address are selected as for the
hardware configuration in
STEP 7.
16. If you do not wish to use any When using an F-CPU you can also call the safety
safety functions or have a CU functions via the field bus. However, this is not part of this
without safety functions (e.g. a example.
CU230P-2 PN), continue with More information on this subject can be found in the Safety
step 21. Integrated (/7/) function manual for the SINAMICS G, or in
the example with PROFIsafe (/8/).
17. Open “Safety Integrated” in the
tree and click on “Change
settings”.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 63
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


18. Select the “STO via terminal”,
click on “Copy parameters” and
then on “Activate settings”.

19. Enter a password and then click


on “Activate settings again”.

(The password used in this


example is “12345”)
Siemens AG 2014 All rights reserved

20. Choose “Yes”, to save the


parameters in ROM.

Proceed with step 22.


Copyright

21. Select the SINAMICS G in the


tree and then press “Copy RAM
to ROM”.

22. Load the configuration created


online into the PG.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 64
6 Configuration and Settings
6.2 Configuring the SINAMICS G drive

No. Action Screenshots / Remarks


23. Go offline.

24. Save the project on your hard


disc.
Siemens AG 2014 All rights reserved
Copyright

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 65
7 Links & Literature

7 Links & Literature


The following list is by no means complete and only provides a selection of
appropriate sources.
Table 7-1
Topic Title / link
/1/ Automating with STEP 7 in STL and SCL
Author: Hans Berger
Publisher: Publicis Publishing
ISBN: 978-3-89578-412-5
/2/ Automating with STEP 7 in LAD and FBD
STEP7
Author: Hans Berger
SIMATIC S7-
300/400 Publisher: Publicis Publishing
ISBN: 978-3-89578-410-1
/3/ Reference Manual
System and Standard Functions for S7-300 and S7400
Volume 1/2
http://support.automation.siemens.com/WW/view/en/44240604
/4/ Link to this http://support.automation.siemens.com/WW/view/en/58820849
document
http://support.automation.siemens.com
Siemens AG 2014 All rights reserved

/5/ Siemens Industry


Online Support
/6/ STARTER STARTER Software
http://support.automation.siemens.com/WW/view/en/26233208
/7/ SINAMICS Operating instructions (V4.7):
G110M http://support.automation.siemens.com/WW/view/de/102316337
Manuals List manual (V4.7) (parameters and error list):
http://support.automation.siemens.com/WW/view/de/99684082
Function manual Safety Integrated (V4.7):
Copyright

http://support.automation.siemens.com/WW/view/en/94003326
Function manual Fieldbus systems (V4.7):
http://support.automation.siemens.com/WW/view/en/99685159

SINAMICS Operating instructions (V4.7):


G120 http://support.automation.siemens.com/WW/view/en/94020562
Manuals List manual (V4.7) (parameters and error list):
http://support.automation.siemens.com/WW/view/en/99683523
Function manual Safety Integrated (V4.7):
http://support.automation.siemens.com/WW/view/en/94003326
Function manual Fieldbus systems (V4.7):
http://support.automation.siemens.com/WW/view/en/99685159

SINAMICS G120C Operating instructions (V4.7):


Manuals http://support.automation.siemens.com/WW/view/en/99710404
List manual (V4.7) (parameters and error list):
http://support.automation.siemens.com/WW/view/en/99683780
Function manual Safety Integrated (V4.7):
http://support.automation.siemens.com/WW/view/en/99683780
Function manual Fieldbus systems (V4.7):
http://support.automation.siemens.com/WW/view/en/99685159

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 66
8 History

Topic Title / link


SINAMICS G120D Operating instructions CU240D-2 (V4.7):
Manuals http://support.automation.siemens.com/WW/view/en/99711357
List manual (V4.7) (parameters and error list):
http://support.automation.siemens.com/WW/view/en/99684194
Function manual Safety Integrated (4.7):
http://support.automation.siemens.com/WW/view/en/94003326
Function manual Fieldbus systems (V4.7):
http://support.automation.siemens.com/WW/view/en/99685159

SINAMICS G120P Operating instructions (V4.7):


Manuals http://support.automation.siemens.com/WW/view/en/94020570
List manual (V4.7) (parameters and error list):
http://support.automation.siemens.com/WW/view/en/99683691
Function manual Fieldbus systems (V4.7):
http://support.automation.siemens.com/WW/view/en/99685159
/8/ Application SINAMICS G: Speed Control for G110M, G120, G120C or
example with G120D using S7-300/400F (in STEP 7 V5) via
PROFIsafe PROFINET/PROFIBUS with Safety Integrated and HMI
http://support.automation.siemens.com/WW/view/en/60441457
/9/ FAQ for data http://support.automation.siemens.com/WW/view/en/7000978
record routing http://support.automation.siemens.com/WW/view/en/50037141
/10/ FAQ for SINAMICS G110D/G110M/G120D, SIMATIC ET 200pro/ET
Siemens AG 2014 All rights reserved

supplementary 200pro FC, SIRIUS M200D: Listing of supplementary products


products (cables, connectors and accessories) for distributed frequency
converter and motor starters.
http://support.automation.siemens.com/WW/view/en/65355810

8 History
Copyright

Table 8-1
Version Date Revisions
V1.0 07/2012 First issue
V2.0 08/2012 Complete revision with focus on easy usability of the blocks
in own projects
Expansion by SINAMICS G120C, G120D and G120P
V2.1 04/2013 Extended by CU250S-2 PN
V2.1a 04/2013 Corrected used STARTER version in chap. 2.3
V2.2 04/2014 Update FB10 (initialize the input buffer with 0, when SFC14
shows error)
Use of STARTER V4.3.3
V2.3 11/2014 Extended by SINAMICS G120 with FW 4.7 and
STARTER V4.4.

SINAMICS G120C at S7-300/400


Beitrags-ID: 58820849, V2.3, 11/2014 67