Integrating IEC 61850 and DNP

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

Integrating IEC 61850 & IEEE 1815 (DNP3)

Andrew West
Regional Technical Director,
SUBNET Solutions, Inc.

SUMMARY

North America has a mature electric power grid. The majority of grid automation changes are
undertaken as evolutionary modifications or extensions of existing systems, rather than by wholesale
replacement. This can impact the approach taken when considering the adoption of new technologies or
methodologies.

When introducing an IEC 61850 substation automation system into a North American utility, it is often
necessary to interconnect it to a SCADA system that is using IEEE 1815 (DNP3). A new standard, IEEE
1815.1, provides guidance on mapping data and functionality between IEC 61850 and DNP3.

Some of the major benefits provided by IEC 61850 lie in its data models and integrated configuration
management processes. IEEE 1815.1 shows how to preserve the IEC 61850 model semantics through the
DNP3 SCADA system and how to automate the DNP3 configuration and integrate this with the IEC 61850
engineering processes. It also defines a process by which IEDs that support DNP3 can be integrated into
an IEC 61850 automation system.

This paper outlines the mapping processes defined in IEEE 1815.1 and describes how these can provide a
consistent and automated way of integrating IEC 61850 into an existing utility’s control system.

KEYWORDS

IEC 61850, IEEE 1815 (DNP3), SCADA, Substation Automation System, Gateway

Introduction

The integration of the various functions of the intelligent electric power grid brings together
technologies that evolved independently. Each function has requirements that have led to the use of
techniques and common practices that efficiently and economically address the challenges of
supporting that function. This differentiation extends into the architectures and procedures used for
management of information associated with the configuration, monitoring, control and fault recovery of
each function. As the diverse functions are integrated in order to improve the capabilities and resilience
of the grid, it can be necessary to interface, harmonize or adapt information management between
subsystems that have differing goals and requirements. Integration is simplified when standardized rules
for harmonizing systems are defined and adopted.

1
This paper discusses the integration of systems that use communication and data modelling that
conform to two different but widely-used power grid communication standards: IEC 61850 and IEEE
1815 (DNP3). This is of particular significance in the North American power system where DNP3 is widely
adopted and the common upgrade strategy is one of step-wise addition rather than wholesale
replacement. In such an environment, an effective strategy for integrating subsystems using these
different standards can simplify the adoption of the new IEC 61850 standard into parts of systems that
already use DNP3. The IEEE 1815.1 standard serves to define mechanisms and procedures that allow
consistent integration of these systems, and may engender tools that allow a high degree of automation
of this integration process.

IEC 61850

IEC 61850 was originally developed in order to provide information management for all functions of
Substation Automation Systems. The original edition, published in the early years of the new
millennium, introduced standardized mechanisms for:

• Data models representing all substation devices and functions


• A common configuration syntax with a single configuration repository for all devices in the
substation automation system using XML
• A standard set of services for reporting data, performing control operations and managing
diagnostic access to data
• Creation of specific protocols (GOOSE and SMV) to support high-speed coordination of the
data processes required to facilitate electric network protection functions and the
distribution of voltage and current waveform data between devices as a time-series of
analog measurement samples
• Mappings of the data models and services onto existing protocols (primarily MMS) and the
newly developed GOOSE and SMV protocols

While the original development of IEC 61850 had its roots in addressing the requirements of substation
control and protection systems, ongoing work and new editions of IEC 61850 and associated standards
extend the functionality beyond the substation into other power system domains. New data models and
functions already cover management of wind farms; hydro-electric power plants and distributed energy
resources. Over time, it is expected that additional models and functions will be added to cover all
aspects of data management for power system operation.

IEC 61850 is a complex and feature-rich standard that facilitates the creation of powerful automation
systems. It has already been deployed in thousands of new substation automation systems world-wide
and is gaining traction in other power system domains.

IEEE 1815 (DNP3)

DNP3 (now IEEE Standard 1815), on the other hand, evolved from traditional SCADA requirements for
remotely monitoring and controlling assets in a reliable manner over a wide area using low-bandwidth
and potentially unreliable communication systems. It focuses primarily on providing a light-weight
means of transporting relatively simple data values and control commands with a high degree of
integrity and resilient methods for recovery from communication system errors and failures. Being more

2
generic and not tied to specific power system data models, DNP3 has seen wide adoption outside of the
electric power system, particularly within water and wastewater utilities.

The DNP3 specification was originally published in 1993 and continues to evolve with extensions
providing new data types and functions, at the request of the industry through the DNP Users Group,
who manages the evolution of the protocol. One guiding principle of this ongoing evolution is to
maintain compatibility and interoperability between devices implementing the original specification and
devices implementing the most recently added features.

Approximately a decade ago, DNP3 was extended with the definition of an XML Device Profile syntax for
specifying and managing device capabilities and configuration. It is possible to use the DNP3-XML Device
Profile to specify the operation of a DNP3 device, including its protocol functionality, the naming of all
its data points, etc. The Device Profile also includes a section specifying the mapping between the DNP3
data object map and the corresponding IEC 61850 data model attributes. DNP3 devices can support the
capability to read the Device Profile of another device as a means of setting the configuration of the
communication with that other device, including information such as data object naming and
association with the corresponding IEC 61850 data model attributes. This functionality can enable the
automation of the configuration of the mapping between IEC 61850 and DNP3 in a gateway device and
the interaction between that gateway and other DNP3 devices.

The Device Profile capability to associate DNP3 data objects with corresponding IEC 61850 data
attributes permits the IEC 61850 semantics to be used on DNP3 systems even where IEC 61850 itself is
not used. This adoption of IEC 61850 semantics can be an early step when planning a future integration
of IEC 61850.

IEEE 1815.1

IEEE Standard 1815.1 [1], published in December 2016, defines a standardized mechanism for a gateway
(or protocol translator) to map data between the power system data object models of IEC 61850 and
the simpler data types of DNP3. It also defines the mechanisms for mapping functionality (data
reporting, control commands, protocol housekeeping, etc.) between these systems. Following its
publication by the IEEE, the IEC will consider adopting the document as a dual-logo standard, expected
to become IEC TS 61850-80-2.

The need for a mechanism to interface between IEC 61850 and DNP3 was identified by NIST and EPRI
during a review of smart grid requirements conducted in 2008. At that time DNP3 was a de-facto
industry consortium agreement and not a standard per-se. As it was considered necessary that DNP3
become a recognized standard in order to permit cooperation and coordination with the IEC, the DNP3
specification was reformatted and offered for adoption as an IEEE standard, which occurred in 2010. A
second edition was published in 2012 with enhanced security features and work on the next edition has
commenced.

Mapping Use Cases

IEEE 1815.1 addresses two basic use cases. Use Case A: Interfacing a DNP3 master with an IEC 61850
Server and Use Case B: Interfacing a DNP3 outstation with an IEC 61850 client.

3
The most common application is expected to be Use Case A, where a new substation automation system
based on IEC 61850 is to communicate with an existing utility control center using DNP3 as the wide-
area SCADA protocol. This is illustrated in Figure 1, below. The second use case is most likely to appear
where an existing substation that uses DNP3 for internal communication is extended with the
introduction of new devices supporting IEC 61850 which must communicate with the other substation
devices.

Figure 1

There are two subcases of Use Case A for interfacing the new IEC 61850 substation to a DNP3 master:
The first subcase (called A1) is for the introduction of a new (greenfield) substation where the allocation
of the DNP3 data mapping may be freely chosen. The second subcase (A2) is the replacement of an
existing DNP3 outstation with a new system based on IEC 61850, where the mapping of the new data is
to match the DNP3 mapping previously used, so as to prevent or minimize the need to reconfigure the
master station. A somewhat similar case can occur if the configuration of the IEC 61850 substation is
subsequently altered: It may be possible to alter the substation equipment and configuration while
maintaining the same data mapping to the SCADA master, thereby minimizing engineering effort and
isolating the control center from detail changes in the substation.

Mapping Details

The IEC 61850 data models include constructs called Logical Nodes that represent power system
equipment or power system functions (such as protection or control functions). The Logical Nodes are
built from sets of data, where each data element is itself a defined structure of values known as a

4
Common Data Class (CDC). The CDC is a set of data attributes (values) representing an object, such as a
Single Point Status (Boolean off/on). The Single Point Status CDC has the Boolean value and other
associated attributes, such as quality flags (indicating if the value is valid, etc.), a time of last change,
substitution data (if the value can be overridden), naming information, etc.

Each of these attributes may be a simple data type (such as a Boolean, or a floating point number) or
could itself be a structure composed of multiple attributes. If these structures are decomposed
completely, they are built from a set of simple data types (Booleans, analogs, etc.) which each have a
specific interpretation. Each of these “leaf nodes” of the CDC structure can be mapped to a DNP3 data
object of a suitable type, in the manner illustrated in Figure 2.

Figure 2 IEC 61850 Attribute Mapping

IEEE 1815.1 defines the rules that can be used to perform this mapping. In some cases, alternative
mappings may be specified that depend on the capabilities of the device: For example, an IEC 61850
Double Point Status CDC represents the four states of a “2 bit” value that is often used for devices that
may be fully closed, fully open, in transit between open and closed or in an undefined (failed) state. The
status, quality and event time of this object can be mapped either to one DNP3 double bit binary object
or to two DNP3 single bit binary objects, depending on which data types are supported by the gateway
and other DNP3 device with which it communicates. Where both types are supported, the double bit
binary mapping is identified as the preferred mapping rule choice.

A suite of mapping rules is defined for mapping between the component attributes of all IEC 61850 CDC
types and DNP3 data types. By defining these mapping rules for the CDCs from which the Logical Node is
constructed, the creation of new Logical Nodes for new domains does not require the creation of new
rules, unless some new CDC type must also be created that does not adopt the same characteristics as
the existing CDCs.

The mapping of the attributes of the CDC could be performed in several different ways, from a “light”
mapping that typically only transfers the value, quality and time (“stVal”, “q” and “t” of the CDC) to a
single DNP3 data object {value, quality and timestamp} tuple, or a more complete mapping that also
maps additional attributes from the CDC. For many applications, the lightweight mapping corresponds
closely to traditional SCADA data reporting and may be sufficient for normal operational purposes.

5
Another mapping strategy can be to use the data attributes selected for use in IEC 61850 data sets as
the basis for choosing the data to be mapped. Data sets are typically configured for reporting a selection
of operationally significant data.

The potential exists for a tool to automatically generate a DNP3 configuration that maps all selected IEC
61850 data. This could have templating rules to indicate which attributes of each CDC are to be mapped.
An early step for the process is to determine the common set of DNP3 capabilities supported by the
gateway and the DNP3 devices with which it communicates. This “merge” of the common capabilities
can be performed automatically from the two DNP3 XML Device Profiles, to form a single device profile
that specifies the common capabilities. This is then an input document to the configuration tool, from
which the tool can identify what mapping options are available. The collection of IEC 61850 SCL files (ICD
/ CID / SCD) must be processed in the usual manner to produce the SCD file for the system, which is then
processed by the mapping tool to add the DNP3 mapping data in the SCD file and configure the mapping
information in the DNP-XML file that can then be used to automatically configure the gateway.

Figure 3 Use Case A1 Mapping Steps

The steps and data flow for Use Case A1 are shown in Figure 3, above. This figure shows the input data
files for both IEC 61850 and DNP3. Step 1 covers the creation of the configuration of the IEC 61850
Substation Automation System, which is performed in the usual manner. Step 2 shows the merging of
the DNP capabilities to the common capability set. User input (or suitable template selection options) is
needed at step 3 to identify and select the data that is to be reported to the DNP3 master and possibly

6
to make choices from amongst the available mapping rules. From that point on, the mapping process
can be automatic to produce the SCD file with mapping data and DNP3-XML files that define the
gateway configuration. The DNP3-XML can then be used to automatically configure the gateway and the
DNP3 master (if it supports configuration by XML import).

For Use Case A2, more manual intervention is required because the aim is to produce a new DNP3
configuration that appears the same as a pre-defined (or pre-existing) configuration. For this case, the
existing DNP3 configuration dictates the required DNP3 capabilities. The gateway must have been
determined to provide these capabilities if the mapping is to be successful, so there is no need to find
the common set of capabilities as was done in Use Case A1: The existing configuration from the master’s
XML file and the point list it contains specifies the data and format that is required. The user is
responsible for identifying what data will be required from the IEC 61850 system and explicitly selecting
the data to be mapped. The user might also need to make appropriate choices from the mapping rules.
Once the data selection is complete (step 3 in Figure 4), the process continues as for Use Case A1.

Figure 4 Use Case A2 Mapping Steps

The mapping requirements for Use Case B are quite different and have more in common with the
process for configuring an IEC 61850 server that represents the data collected from the DNP3 IEDs. The
procedure is outlined in Figure 5. Here the gateway uses the IED’s XML files to configure its interaction
with each IED. Manual intervention will be required to identify what IEC 61850 data models are to be
assembled from the DNP3 data in the IEDs and to create the ICD file representing those models. The

7
gateway ICD or IID file can then be used in the remainder of the IEC 61850 configuration process to
introduce the data from the DNP3 IEDs as normal IEC 61850 models.

Figure 5 Use Case B Mapping Steps

Function Mapping

IEC 61850 is built on a framework inherited from factory automation principles. The functions and
services it uses are closely aligned with those provided by MMS. DNP3 has a somewhat simpler function
set, aimed at efficient collection of Report By Exception (event reporting) of changes to monitored data
and a two-pass (Select Before Operate or SBO) control strategy that provides exceptional resilience
against communication system data errors.

The IEC 61850 functionality that most closely resembles DNP3’s RBE process is the Buffered Report
system. For many applications it is likely that the only data that needs to be mapped through the
gateway will be data that comes from (or is to be placed in) buffered reports.

The control model supported by MMS is fundamentally based on the writing of values to a target device
that then causes that device to perform an action. This differs from the SCADA concept of commands
being requests with no inherent state and gives rise to quite different steps being performed through a
command sequence.

8
Figure 6 SBO With Enhanced Security (Use Case A)

Figure 7 SBO With Enhanced Security (Use Case B)

9
IEEE 1815.1 considers the characteristics of each mapping of control commands between MMS and
DNP3 and shows how both command success and command failure cases are to be handled. Each side
of the gateway is effectively insulated from the details of the operation of the other side. Examples
showing the command flow for a successful SBO with enhanced security command are shown for Use
Case A in Figure 6 and Use Case B in Figure 7.

Note that for Use Case A, Figure 6 (from IEEE 1815.1) shows that the status change could be reported by
GOOSE, a report or a poll. IEC 61850 GOOSE is not technically guaranteed to report all states of a rapid
series of changes on a single value and polling may not observe some changes of state. In normal SCADA
(and DNP3) RBE usage, all changes of state are expected to be reported. Hence, in this application,
buffered reporting is the preferred method for IEC 61850 to report changes to the gateway. For Use
Case B, the choice to use GOOSE, reporting or polling depends more on the purpose for which the value
change is used: For process coordination, the use of GOOSE is common.

Conclusion

IEEE 1815.1 provides guidelines for a consistent method to map between IEC 61850 data models and
DNP3. The guidelines can be used to form the basis of a gateway and configuration tool that can, to a
large degree, automate the process for implementing a gateway from a greenfield IEC 61850 substation
to a DNP3 SCADA control center.

Even where IEC 61850 is not yet in use, the mapping guidelines can be followed to produce native DNP3
configurations that have the same structure and semantics as data sourced from IEC 61850 through a
gateway that follows the mapping rules. Adopting these guidelines in the near term may be a prudent
step for utilities that plan to deploy IEC 61850 substations in the future.

A side-effect of the mapping process is an automatic association of IEC 61850 semantics with each DNP3
data object. This association is specified in the configuration specified in the DNP3-XML Device Profile
which is used to configure the devices. Thus the semantic information is known to the DNP3 outstation
and master, even though it is never transmitted over the channel at run time. This gains the efficiency of
DNP3 (which might still operate over a low-bandwidth channel) and the rich object model information
available from IEC 61850.

Utilities that use or plan to use both IEC 61850 and DNP3 should familiarize themselves with IEEE 1815.1
when it becomes available and adopt its guidelines

BIBLIOGRAPHY

[1] IEEE Standard 1815.1 “Standard for Exchanging Information between networks Implementing IEC 61850 and
IEEE Std 1815™ (Distributed Network Protocol - DNP3)”