Adbri Masonry Fire and Sound Brochure PDF
Adbri Masonry Fire and Sound Brochure PDF
Adbri Masonry Fire and Sound Brochure PDF
Preface 02 The wall systems shown in this brochure, are in accordance with the
Introduction 02 requirements of the National Construction Code - Building Code
NCC-BCA requirements 03 of Australia (NCC-BCA) Volumes 1 and 2, and meet Australian Stand-
ards AS 3700:2001.
1.0 Fire 03
1.1 Design of walls for fire resistance 03 Adbri Masonry acknowledges the Concrete Masonry Association of
1.2 General design/construction considerations 06 Australia’s (CMAA) ‘Design of Concrete Masonry Building’s Manual’
MA55 in the development of the wall systems.
1.3 FRL for integrity and insulation 07
1.4 FRL for structural adequacy for un-reinforced
and reinforced masonry 08
2.0 Sound 22
2.1 The NCC-BCA requirements 22 Introduction
2.2 Design of walls for sound insulation 22
2.3 General design/construction considerations 06
List of tables and charts
This brochure is intended as a guide for the design of walls requiring
Table A - NCC-BCA requirements for FRL 04
fire resistance using Adbri Masonry products in New South Wales.
Table B - Integrity and insulation values 07
Table C - Slenderness ratios for structural adequacy 08 THE PROPERTIES IN THIS BROCHURE ARE SPECIFIC TO ADBRI
MASONRY PRODUCTS AND DO NOT APPLY TO PRODUCTS OF
Table D - NCC-BCA Requirements 24
OTHER MANUFACTURERS.
Table E - Adbri Masonry wall systems for NSW 25
Table F - Acoustic Quickbrick 26 All definitions can be found in the Glossary, Section 2.0.
2 adbri masonry
1.0 Fire
1.1 Design of walls for fire resistance 2) For walls which are chased, the thickness must be reduced by the
depth of the chase to establish integrity and insulation. The effects
Structural adequacy - (ability to remain stable)
may only be ignored only if the following criteria are met:
To achieve the required FRL for structural adequacy the height of the
wall is limited. This limit varies according to the type of support given • The wall is grouted
to the wall and whether the wall is reinforced. • Depth of the chase is not greater than 30mm
The slenderness ratios given in the Masonry Code do not take into • The area of the chase is not greater than 1,000mm2
account any effect of applied finishes or the filling of cores with grout. • The total face of the chase is not greater than 100,000mm2 total
on both faces of the wall on any 5m2 area.
Integrity - (ability to resist the passage of flames and hot gases)
Design for integrity in this brochure is based on Clause 6.4 of AS3700 Step 3 - Design wall for FRL for structural adequacy
which deems that the FRL for integrity will be met if the wall meets
Check the following graphs that the proportions of the wall together
that value for insulation or from test results.
with the various support conditions and/or reinforcements are such
Insulation - (ability to limit the passage of heat) that the required FRL for structural adequacy is achieved.
To achieve the required FRL for insulation a minimum “material
If the actual wall height does not exceed the permissible heights,
thickness” must be provided by the wall.
then the chosen wall type will be satisfactory and no further steps
For units with less than or equal to 30% coring and where cores are filled
need to be taken. If the wall is still higher than permissible and no
with grout, the “material thickness” is taken as the actual thickness.
additional supports can be provided, then the wall will need to be
For units with over 30% coring the “material thickness” is the net
either reinforced or made thicker.
volume of the unit divided by the face area, commonly referred to as
the “equivalent thickness”. If the wall is cement rendered on both Notes:
sides, the thickness of the thinner coating up to a maximum value of 1) For walls with openings it is regarded as being divided into two
20mm may be added to the material thickness of the wall. sub-panels with a free edge at the centre of the opening.
Robustness 2) Where walls are chased they can be dealt with as follow:
The height limits of walls when determined by design for robustness are
in some cases less than those determined by design for fire resistance. For vertically spanning walls:
These cases are accounted for in the following design charts. • Where the chase is vertical - ignore
• Where the chase is horizontal and of length not greater than
Step 1 - Establish requirements
four times the wall thickness - ignore
Establish the required Fire Resistance Level (FRL) for the wall. • Where the chase is horizontal and of length greater than four times
Refer to Table A. the wall thickness - consider using the slenderness ratio of the
Where the required FRL does not include a value for structural wall based on the wall thickness at the bottom of the chase.
adequacy e.g., -/60/30, the wall must have a FRL for structural For walls spanning vertically and horizontally:
adequacy equal to that required for integrity i.e., to achieve • Where the length of chase is not greater than half the height for
a FRL of -/60/30, the wall must be designed for 60/60/30. a vertical chase or half the length for a horizontal chase - ignore
Step 2 - Check FRL for integrity and insulation • Where the length of chase is greater than half the height or half
the length take into account using the slenderness ratio of the
Establish the minimum wall type to satisfy the required FRL
wall based on the wall thickness at the bottom of the chase.
for integrity and insulation i.e., the last two values of the FRL.
As the required FRL for insulation is never required to be greater than Step 3a - The permissible height and length of a wall increases
the FRL for integrity, both insulation and integrity are checked for the when either reinforced vertically or with horizontally reinforced
integrity requirement e.g., for an FRL 180/120/90 both integrity and bond beams. For reinforced walls the permissible dimensions can
insulation would be checked for 120 minutes. be obtained from the following:
Table B provides values of integrity and insulation for single Section 1.5.4 - Vertical Reinforced Walls
leaf walls. Section 1.5.5 - Horizontal Reinforced Walls
1) All cavity walls achieve 240 minutes for integrity and insulation. Step 3b - If the permissible dimensions are still not sufficient, then
choose a thicker wall and return to Step 3a.
adbri masonry 3
Building Classes Class 3: a residential building, other than a building of Class 1 or 2
which is a common place of long term or transient living for a number
Class 1: one or more buildings which in association constitute:
of unrelated persons, including:
(a) Class 1a – single dwelling house
(a) A boarding house, guest house, hostel, lodging-house or
(i) a detached house; or backpackers accommodation; or
(ii) o ne or more attached dwellings, each being a building, (b) A residential part of a hotel or motel; or
separated by a fire-resisting wall, including a row house,
(c) A residential part of a school; or
terrace house, town house or villa unit; or
(d) Accommodation for the aged, disabled or children; or
(b) Class 1b - boarding house, guest house, hostel or the like with
a total floor area not exceeding 300m2 and in which not more than (e) A residential part of a health-care building which accommodates
12 persons would ordinarily be resident, which is not located above members of staff; or
or below another dwelling or another Class of building other than a
(f) A residential part of a Detention Centre for the accommodation of
private garage.
the inmates of the centre.
Class 2: a building containing two or more sole-occupancy units each
Class 4: a dwelling in a building that is Class 5, 6, 7, 8 or 9 if it is the
being a separate dwelling.
only dwelling in the building.
Table A - NCC-BCA requirements for FRL (Type of fire construction required is indicated in brackets)
Class 1 ANY
Classes 2, 3 & 4 Part 1 (C) 2 (B) 3 or more (A)
Class 5
Class 6
Class 7 (Except Car Parks) and 8
Class 7 Car Parks 1 or 2 (C)
Class 9
4 adbri masonry
Class 5: an office building used for professional or commercial Class 8: a laboratory, or a building in which a handicraft or process
purposes, excluding buildings of Class 6, 7, 8, or 9. for the production, assembling, altering, repairing, packing, finishing,
or cleaning of goods or produce is carried out for trade, sale or gain.
Class 6: a shop or other building for the sale of goods by retail or the
supply of services direct to the public, including: Class 9: a building of a public nature:
(a) An eating room, cafe, restaurant, milk or soft-drink bar; or (a) Class 9a – a health-care building; including those parts of the
building set aside as a laboratory; or
(b) A dining room, bar, shop or kiosk part of a hotel or motel; or
(b) Class 9b – an assembly building, including a trade workshop,
(c) A hairdresser’s or barber’s shop, public laundry, or undertaker’s
laboratory or the like in a primary or secondary school, but excluding
establishment; or
any other parts of the building that are of another Class; or
(d) Market or sale room, showroom, or service station.
(c) Class 9c – an aged care building.
Class 7: a building which is:
Class 10: a non-habitable building or structure:
(a) A public carpark*; or
(a) Class 10a – a non-habitable building being a private garage,
(b) For storage, or display of goods or produce for sale by wholesale. carport, shed, or the like; or
*for a list of conditions required to be met to use the nominated values for car (b) Class 10b – a structure being a fence, mast, antenna, retaining or
parks, please refer to table C1.1 in NCC-BCA Volume 1 to determine type of fire
construction required, then refer to clause 3.9a for Type A, 4.2a for Type B and free-standing wall, swimming pool, or the like.
5.2a for Type C
(c) Class 10c - a private bushfire shelter
B A C B A B A B A
adbri masonry 5
1.2 General design/construction considerations There are many companies producing a range of sealing products
suitable. Previously three have supplied detailed technical data which
To achieve the required fire performance of a wall, it is essential that
should be checked with companies if still available. They are:
installation is in accordance with the masonry manufacturer’s details
and relevant installation standards. This should include fire sealing 1) “Pyropanel 201SFR”, a two-part polyurethane fire rated sealant.
at the wall head and perimeters, and filling of mortar joints. All gaps “Intumex Mw” a fire prevention water based mastic and “Intumex
and penetrations should be effectively fire sealed. S”, a fire prevention silicone. These products have test reports
giving integrity and insulation in excess of 120 minutes for joints
Recesses for services
up to 54mm wide. They are being distributed through major
The effect of recesses for services on the fire-resistance periods plumbing outlets.
for structural adequacy, integrity and insulation of a wall, shall be
2) Fire Research Pty Ltd “Fyrejoint” is a one-part gunable acrylic
ignored provided that the thickness of wall remaining is not less than
compound. The product has been tested to give it up to four hours
half the wall thickness and the total area of recesses is not more
Fire Rating. The product is manufactured by Wormald.
than 10,000mm2 total on both faces within any 5m2 area.
Note: where the wall is constructed of cored or hollow units, the recess can 3) The Fire Stop System. The sealants 2000 and 790 are silicone
extend into the cores. based products. They are gunable and claim to have fire ratings for
If these limits are exceeded, the thickness of the wall shall be taken as the one to four hours with joints up to 30mm wide. The products are
overall thickness of the wall less than the depth of recess. manufactured by Dow Corning.
Control joints in fire resistant walls Design of cavity walls for fire resistance
Clause C3.16 of the NCC-BCA Volume One states: For the design of cavity walls some specific rules are given in
AS3700:
Construction joints, spaces and the like in and between building
elements required to be fire resisting with respect to integrity and For integrity and insulation the material thickness of both leaves
insulation must be protected in a manner identical with a prototype is added together and the cavity ignored to give the “material
tested in accordance with 1530.4 to achieve the required FRL. thickness”. However, for structural adequacy where only one leaf
is loadbearing, then the FRL for structural adequacy is based on the
loaded leaf alone and the non-loaded leaf is ignored. If both leaves
are equally loaded (to within 10% of one another) or both leaves are
non-load bearing, then the thickness for structural adequacy is based
on two-thirds of the sum of the thickness of the two leaves.
6 adbri masonry
1.3 FRL for Integrity and Insulation
230
90
190
90
190
140
190
140
(≤1800 kg/m3) 90
190
190
190
190
190
390
190
90
110
230
140
190
190
390
290
(≤1800 kg/m3)
90
140
Notes:
1) Non Load Bearing (NLB) - see definitions glossary 3) Results from Fire Tests
2) Load Bearing (LB) - see definitions glossary 4) Results from Deemed-to-Satisfy tables in AS3700.2001
adbri masonry 7
Table B - Integrity and Insulation cont.
190
190
190
190
190
110
230
110
140
Notes:
1) Non Load Bearing (NLB) - see definitions glossary 3) Results from Fire Tests
2) Load Bearing (LB) - see definitions glossary 4) Results from Deemed-to-Satisfy tables in AS3700.2001
Aggregate Type
FRL (minutes)
Litec2 Test4 29.6 (NLB) 29.6 (NLB) 29.6 (NLB) 29.6 (NLB) 29.6 (NLB)
Notes:
8 adbri masonry
Structural
1.4.1 How to use theAdequacy
Fire Resistance Level Charts (for Structural Adequacy) in the following charts
Laterally-supported
both ends
Litec 190
8.0 8.0
7.0 7.0
6.0 6.0
Litec 190
5.0 Litec 140 5.0
Height of Wall Between Supports (m)
2.0 2.0
1.0 1.0
0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m) Length of Wall Between Supports (m)
Height
Length Length
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and stiffness of supports, in
addition to normal considerations of loads and masonry properties
adbri masonry 9
Chart 2 < 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
90-mm leaf < 45% Basalt
Load Bearing, Deemed-to-Satisfy, Un-reinforced Masonry
9.0
avf = 0.75, ah = 1.0
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0
Fire-resistance level,
FRL (minutes), for
5.0
Structural Adequacy
Height of Wall Between Supports (m)
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)
9.0
avf = 0.75, ah = 2.5
8.0
Laterally - supported
Height
Length
6.0
Fire-resistance level,
FRL (minutes), for
5.0
Height of Wall Between Supports (m)
Structural Adequacy
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and stiffness of supports, in
addition to normal considerations of loads and masonry properties
10 adbri masonry
Chart 3 < 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
110-mm leaf < 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0 Fire-resistance level,
FRL (minutes), for
5.0 Structural Adequacy
Height of Wall Between Supports (m)
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
8.0
Laterally - supported
Height
Length
6.0
Fire-resistance level,
FRL (minutes), for
5.0 Structural Adequacy
Height of Wall Between Supports (m)
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
adbri masonry 11
Chart 4 < 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
140-mm leaf < 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
avf = 0.75, ah = 1.0
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0
Fire-resistance level,
1.0
FRL (minutes), for
Structural Adequacy
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
8.0
Laterally - supported
Height
Length
6.0
Supporting a concrete slab
5.0 Robustness governs in shaded areas
Height of Wall Between Supports (m)
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
12 adbri masonry
Chart 5 < 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
190-mm leaf < 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
7.0
6.0
Height
3.0 both ends and top
2.0
Length
9.0
6.0
90/4.31
120/4.05 avf = 0.75, ah = 2.5
4.0
180/3.93
240/3.80
Laterally - supported
Height
3.0
one end and top
2.0
Length
1.0 Fire-resistance level,
FRL (minutes), for
0 Structural Adequacy
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
adbri masonry 13
Chart 6 > 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
90-mm leaf ≥ 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
avf = 0.75, ah = 1.0
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0
Fire-resistance level,
FRL (minutes), for
5.0
Structural Adequacy
Height of Wall Between Supports (m)
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
9.0
avf = 0.75, ah = 2.5
8.0
Laterally - supported
Height
6.0 Length
5.0
Height of Wall Between Supports (m)
3.0 60/2.70
90/2.52
120/2.40
2.0 180/2.16
240/2.04
FRL/Height, (m)
1.0 Fire-resistance level,
FRL (minutes), for
Structural Adequacy
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
14 adbri masonry
Chart 7 > 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
110-mm leaf ≥ 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
avf = 0.75, ah = 1.0
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0
9.0
avf = 0.75, ah = 2.5
8.0
Laterally - supported
Height
Length
6.0
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
adbri masonry 15
Chart 8 > 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
140-mm leaf ≥ 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
avf = 0.75, ah = 1.0
8.0
Laterally - supported
Height
both ends and top
7.0
Length
6.0
Supporting a concrete slab
Robustness governs in shaded areas
5.0
Not supporting a concrete slab
Height of Wall Between Supports (m)
60/4.20
4.0 90/3.92
120/3.73
180/3.36
3.0 240/3.17
FRL/Height, (m)
2.0 Fire-resistance level,
FRL (minutes), for
1.0 Structural Adequacy
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
9.0
avf = 0.75, ah = 2.5
8.0
Laterally - supported
Height
Length
6.0
Supporting a concrete slab
Robustness governs in shaded areas
5.0
Not supporting a concrete slab
Height of Wall Between Supports (m)
60/4.20
4.0 90/3.92
120/3.73
180/3.36
3.0 240/3.17
FRL/Height, (m)
2.0
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
16 adbri masonry
Chart 9 > 45% Basalt
Supporting a Supporting
concrete slab a roof or floor
190-mm leaf ≥ 45% Basalt
Load Bearing, Deemed-to-Satisfy, Unreinforced Masonry
9.0
Robustness governs in shaded areas
8.0
7.0
180/4.56
4.0 240/4.31
Laterally - supported
Height
both ends and top
3.0
Length
2.0
Fire-resistance level,
1.0 FRL (minutes), for
Structural Adequacy
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
9.0
8.0
Supporting a concrete slab
Robustness governs in shaded areas
7.0
Not supporting a concrete slab
180/4.56
4.0 240/4.31 avf = 0.75, ah = 2.5
Length
1.0
Fire-resistance level,
FRL (minutes), for
0 Structural Adequacy
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Notes - It is the designer’s responsibility to allow for the effects of control joints, chases, openings, strength and stiffness of ties connectors, and strength and
stiffness of supports, in addition to normal considerations of loads and masonry properties
adbri masonry 17
1.4.3 Reinforced Masonry
The following charts cover mixed construction where partial reinforcement by bond beams and stiffeners have been incorporated into
the masonry wall. The charts have been calculated on:
The following mixed construction charts provide an FRL for Structural Adequacy of 240 minutes in accordance with AS3700 Clause 6.3.5 and 6.3.6.
For Intergrity and Insulation FRL’s refer to Section 1.4 Table B.
7.0
6.0
5.0
Height of Wall Between Supports (m)
Reinforced
Cores
4.0
Reinforcement N16
3.0
Height
2.0 N12
1.0
Horizontal
Spacing
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m)
190mm Column, 1 Bar, 1 Tensile, 1 Block, Centre 190mm Column, 2 Bars, 1 Tensile, Edge, 1 Block
9.0 N12 9.0
N12
N16 N16
8.0 8.0
N20 N20
7.0 7.0
6.0 6.0
Reinforcement N20
5.0 5.0
Height of Wall Between Supports (m)
Height of Wall Between Supports (m)
N12
Height
2.0 2.0
1.0 1.0
Horizontal Horizontal
Spacing Spacing
0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m) Length of Wall Between Supports (m)
Reinforcement* required to achieve a Fire Resistance Level (FRL) for Structural Adequacy of up to 240 minutes.
*(Minimum reinforcement to resist 0.5kPa lateral load in accordance with AS3700, Clause 6.3.5)
18 adbri masonry
1.4.5 Horizontally Reinforced Bond Beam
140mm Beam, 1 Bar, 1 Block 140mm Beam, 2 Bars, 1 Tensile, 2 Blocks, Centre
9.0 9.0 N12
N12
N16 N16
8.0 8.0
7.0 7.0
6.0 6.0
Reinforcement N12 & N16
5.0 5.0
Height of Wall Between Supports (m)
3.0 3.0
Spacing
Spacing
Vertical
Vertical
Reinforced Reinforced
2.0
Bond Beam 2.0
Bond Beam
1.0 1.0
Length Length
0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Length of Wall Between Supports (m) Length of Wall Between Supports (m)
190mm Beam, 1 Bar, 1 Block, Centre 190mm Beam, 2 Bars, 1 Tensile, 1 Block
9.0 9.0 N12
N12
N16 N16
8.0 8.0
N20 N20
Reinforcement N20 & N16
7.0 7.0
N12
4.0 4.0
3.0 3.0
Spacing
Spacing
Vertical
Vertical
Reinforced Reinforced
2.0
Bond Beam 2.0
Bond Beam
1.0 1.0
Length Length
0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Length of Wall Between Supports (m) Length of Wall Between Supports (m)
190mm Beam, 2 Bars, 1 Tensile, 2 Blocks, Centre 190mm Beam, 4 Bars, 2 Tensile, 2 Blocks, Edge
9.0 9.0
N12 N12
N16 N16
8.0 8.0
N20 Reinforcement N20 & N16 N20
7.0 7.0
N12
5.0 5.0
Height of Wall Between Supports (m)
4.0 4.0
3.0 3.0
Spacing
Spacing
Vertical
Vertical
Reinforced Reinforced
2.0
Bond Beam 2.0
Bond Beam
1.0 1.0
Length Length
0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0
Length of Wall Between Supports (m) Length of Wall Between Supports (m)
Reinforcement* required to achieve a Fire Resistance Level (FRL) for Structural Adequacy of up to 240 minutes.
*(Minimum reinforcement to resist 0.5kPa lateral load in accordance with AS3700, Clause 6.3.5)
adbri masonry 19
1.4.6 Wall Stiffeners using Steel Mullions
Lateral support can be provided to unreinforced masonry subject to lateral earthquake, wind or fire loads by building in galvanised steel mullions.
Steel mullions must be placed into open-ended masonry units, such as ‘H’ or ‘A’ shaped blocks, during construction of the masonry wall.
9.0
8.0
7.0
50 x 100mm Steel Mullion Stiffener Minimum Steel Clearance
as per AS3700 Table 6.2
6.0
1501 or
5.0
Height of Wall Between Supports (m)
2.0
1.0
Horizontal
Spacing
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 Reinforcement required to achieve an FRL for
Length of Wall Between Supports (m) Structural Adequacy of up to 120 minutes.
140mm Leaf
9.0
8.0
7.0
65 x 65mm Steel Mullion Stiffener Minimum Steel Clearance
as per AS3700 Table 6.2
6.0
1501 or
5.0
Height of Wall Between Supports (m)
2.0
1.0
Horizontal
Spacing
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Reinforcement required to achieve an FRL for
Length of Wall Between Supports (m) Structural Adequacy of up to 90 minutes.
20 adbri masonry
Chart 15 190mm Leaf
9.0
8.0
7.0
50 x 100mm Steel Mullion Stiffener Minimum Steel Clearance
as per AS3700 Table 6.2
6.0
2001 or
5.0
Height of Wall Between Supports (m)
Height
2.0
1.0
Horizontal
Spacing
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0
Reinforcement required to achieve an FRL for
Length of Wall Between Supports (m) Structural Adequacy of up to 240 minutes.
190mm Leaf
9.0
8.0
7.0
65 x 65mm Steel Mullion Stiffener Minimum Steel Clearance
as per AS3700 Table 6.2
6.0
2001 or
5.0
Height of Wall Between Supports (m)
2.0
1.0
Horizontal
Spacing
0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 9.0 Reinforcement required to achieve an FRL for
Length of Wall Between Supports (m) Structural Adequacy of up to 240 minutes.
adbri masonry 21
2.0 Sound
All wall systems in this brochure satisfy the performance Determine the building class and wall separating conditions between
requirement of the NCC-BCA and demonstrate compliance the sole occupancy units (SOU’s) using Table D
through one of the following means:
Step 2: Select your Adbri Masonry wall system
• Laboratory testing of an exact construction or
Use Table E, and the relevant NCC-BCA requirement as chosen
• The deemed-to-satisfy (DTS) provisions, these walls are considered in Step 1, to view the Adbri Wall systems available. Table E
to be acceptable forms of construction. The DTS walls consider categorises the requirements of the NCC-BCA and allocates
the overall Rw value of a particular wall type, which must meet the an available Adbri Masonry wall system to meet the requirement.
NCC-BCA requirement to comply. There may be several systems available to achieve NCC- BCA
compliance.
These provisions also take into account the building class and
state or territory. The NCC-BCA requirements for internal walls are Step 3: Details of your Adbri Masonry wall system
summarised in Table D.
Tables F, G, H, I and J provide a range of systems based around a
Note - Reference should be made to the NCC-BCA for detailed range of Adbri Masonry products. Each table is formatted to provide:
information and concessions.
1) Typical layout
Adbri Masonry has developed and tested a range of high
2) Wall schematic
performance wall systems to accomodate the requirements of the
NCC-BCA for Class 2 and 3 buildings. This information is included in 3) Adbri block type/series
Tables F, G, H, I and J. 4) Wall details
The systems in Tables G and H are best for load bearing measonry 5) Overall wall thickness
walls up to 3 storeys maximum.
6) Test report/Opinion number
2.2 Design of walls for sound insulation
7) Further information (if applicable).
These wall systems are usually used in internal applications in
commercial, industrial, institutional, domestic and high-rise domestic
construction, or in the renovation of older buildings. Wall systems
generally incorporate single leaf concrete masonry, CSR Bradford®
Insulation products, CSR Gyprock® and Tontine. All individual
masonry Rw values have been derived using Adbri, Renzo Tonin and
Associates, CMAA and CSIRO test reports, and opinions by Ron
Rumble Pty Ltd and Renzo Tonin and Associates, and Arup Pty Ltd.
Systems which require CSR product are based on the CSR ‘The Red
BookTM’ November 2009 Section ‘D’ Masonry Wall Systems.
The Rw and Rw + Ctr values shown in the wall systems are only
applicable when using Adbri Masonry, Tontine and CSR products
(or equivalent).
22 adbri masonry
Table D - NCC-BCA Requirements
Discontinuous
NCC-BCA Building Class Walls that separate Rw + Ctr Rw
Construction
Vol One
Notes
1 - Refer to glossary for Building Class definitions.
Rw + Ctr = 50
Rw + Ctr = 50 and
Discontinous Construction Lift
Rw = 50
Corridor
SOU 1
Living Room
SOU 1
Kitchen SOU 2
Living Room
SOU 2
Kitchen
adbri masonry 23
Table E - Adbri Masonry wall systems for New South Wales
I 150 series Litec block hollow with 13mm render both sides
J 200 series Litec block hollow with 13mm render both sides
Rw 45
Rw 50
I 150 series Litec block core filled with mininum 13mm render or minimum 10mm gyprock both sides
Rw + Ctr = 50 ALL Various units with Resilient Mount, Furring Channel and Insulation one side
Rw + Ctr = 50 + Various units (some walls corefilled) with Stud and Insulation one side,
ALL
Discontinuous Construction Discontinuous Construction for impact sound and insulation
•Gyprock® plasterboard may be directly applied to the masonry • Masonry units must be laid with all joints filled solid,
substrate, screw fixed to metal furring channels that are fixed to the except for adequately sound insulated articulation joints, including
masonry, or alternatively fixed to a separate stud frame. those between the masonry and any adjoining construction.
• Refer to manufacturer for all related load bearing and non-load • To achieve the specified sound performance, ties from masonry to
bearing stud design information. the stud framing must not be used.
• All block wall elements are to be designed in accordance with • For energy efficiency wall systems refer to ‘Adbri Block Energy
AS3700:2011 Masonry Structures. Efficiency Compliance Guide’.
24 adbri masonry
Table F - 110mm Acoustic Quickbrick
RR/05/39
N/A 41 No None None 110mm
43.Rpt6
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
adbri masonry 25
Table F - 110mm Acoustic Quickbrick (cont.)
9mm wet area fibre cement board 9mm wet area fibre cement
(14kg/m2) screw fixed to 16mm board (14kg/m2) screw fixed to 424j
56 67 Yes furring channels on resilient 64mm metal stud (10mm off 232mm
AO221834
acoustic mount with Tontine label masonry) with Tontine label TSB5
TSB3 insulation (20mm) insulation between studs
13mm render
54 58 Yes 13mm render 465b 296mm
50mm cavity between leaves
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
RR/05/39
NA 46 No None None 110mm
43.Rpt6
Schooner
RR/05/39
NA 45 No None None 110mm
43.Rpt6
Renderbrick
RR/05/39
NA 47 No None None 110mm
43.Rpt6
26 adbri masonry
Table G - 110mm Quickbrick, Schooner and Renderbrick (cont.)
13mm render
50 55 Yes 13mm render 433g 276mm
30mm cavity between leaves
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
adbri masonry 27
Table H - 140mm Ezibrick
RR/05/39
NA 50 No None None 140mm
43.Rpt6
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
28 adbri masonry
Table I - 150 Series
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
L1501.2 RR/05/3
NA 41 No None None 140mm
Hollow 943.Rpt6
L1501.4 RR/05/3
NA 44 No None None 14 0mm
Hollow 943.Rpt6
L15412 RR/05/3
NA 50 No None None 140mm
Corefilled 943.Rpt6
L1501.2 RR/05/3
NA 45 No 13mm render 13mm render 166mm
Hollow 943. Rpt6
L1501.4 RR/05/3
NA 47 No 13mm render 13mm render 166mm
Hollow 943.Rpt6
L15412 RR/05/3
NA 50 No 13mm render 13mm render 166mm
Corefilled 943.Rpt6
L1501.2 RR/05/3
NA 43 No 13mm plasterboard 13mm plasterboard 166mm
Hollow 943.Rpt6
L1501.4 RR/05/3
NA 45 No 13mm plasterboard 13mm plasterboard 166mm
Hollow 943.Rpt6
L15412 RR/05/3
NA 51 No 13mm plasterboard 13mm plasterboard 166mm
Corefilled 943.Rpt6
adbri masonry 29
Table I - 150 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
30 adbri masonry
Table I - 150 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
adbri masonry 31
Table J - 200 Series
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
L2001.2 RR/05/3
NA 42 No None None 190mm
Hollow 943.Rpt6
L2001.3 RR/05/3
NA 44 No None None 190mm
Hollow 943.Rpt6
L2001.4 RR/05/3
NA 47 No None None 190mm
Hollow 943.Rpt6
L20412 RR/05/3
NA 55 No None None 190mm
Corefilled 943.Rpt6
L2001.2 RR/05/3
NA 46 No 13mm render 13mm render 216mm
Hollow 943.Rpt6
L2001.3 RR/05/3
NA 47 No 13mm render 13mm render 216mm
Hollow 943.Rpt6
L2001.4 RR/05/3
NA 50 No 13mm render 13mm render 216mm
Hollow 943.Rpt6
L20412 RR/05/3
NA 57 No 13mm render 13mm render 216mm
Corefilled 943.Rpt6
L2001.2 RR/05/3
NA 44 No 13mm plasterboard 13mm plasterboard 216mm
Hollow 943.Rpt6
32 adbri masonry
Table J - 200 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
L2001.3 RR/05/3
NA 45 No 13mm plasterboard 13mm plasterboard 216mm
Hollow 943.Rpt6
L2001.4 RR/05/3
NA 48 No 13mm plasterboard 13mm plasterboard 216mm
Hollow 943.Rpt6
L20412 RR/05/3
NA 56 No 13mm plasterboard 13mm plasterboard 216mm
Corefilled 943.Rpt6
adbri masonry 33
Table J - 200 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
34 adbri masonry
Table J - 200 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
adbri masonry 35
Table J - 200 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
36 adbri masonry
Table J - 200 Series (cont.)
Test /
Discontinuous Block System
Rw + Ctr Rw Wall Lining System Detail Wall Lining Opinion
Construction Cores Width
Number
Notes
- Soundchek plasterboard or approved equivalent can be used
- Systems with furring channels on resilient mounts allow 14mm for width of resilient mount
adbri masonry 37
3.0 Glossary
Cavity wall a wall comprising two leafs of brick or block work tied Habitable room means a room used for normal domestic activities,
together, with an air gap/insulation between. and:
Common wall means a wall that is common to adjoining buildings. (a) Includes a bedroom, living room, lounge room, music room,
television room, kitchen, dining room, sewing room, study,
Deemed to satisfy provisions means provisions which are deemed
playroom, family room and sunroom; but
to satisfy the Performance Requirements of the NCC-BCA.
(b) Excludes a bathroom, laundry, water closet, pantry, walk-in
Discontinuous construction means a wall system having a
wardrobe, corridor, hallway, lobby, photographic darkroom,
minimum 20mm cavity between two separate leaves, with:
clothes-drying room, and other spaces of a specialised nature
(a) F or masonry, where wall ties are required to connect leaves, the occupied neither frequently nor for extended periods.
ties are of the resilient type; and
Insulation, in relation to an FRL, means the ability to maintain a
(b) F or other masonry, there is no mechanical linkage between leaves temperature on the surface not exposed to the furnace below the
except at the periphery. limits specified in AS 1530.4.
A staggered stud wall is not deemed to be discontinuous Integrity, in relation to an FRL, means the ability to resist the
construction. passage of flames and hot gases specified in AS 1530.4.
Envelope means the parts of a building’s fabric that separate a Internal wall excludes a common wall or party wall.
conditioned space or habitable room from:
Load bearing (LB) means intended to resist vertical forces
(a) The exterior of the building, or a non-conditioned space (other additional to those due to its own weight.
than a space through which conditioned air
Non load bearing (NLB) means a wall not designed to be subject to
(b) is being exhausted such as a cleaner’s room, chemical storage an external load, other then its own weight.
room or exhaust riser) including:
Sole occupancy unit means a room or part of a building for
(i) The floor of a rooftop plant room, lift machine room of the like; occupation by one or joint owner, lessee, tenant, or other occupier
and to the exclusion of any other owner, lessee, tenant, or other occupier
(ii) T he floor above a carpark or warehouse; and and includes:
(iii) The common wall with a carpark, warehouse or the like. (a) A dwelling; or
External wall means an outer wall of a building which is not a (b) A room or suite of rooms in a Class 3 building which includes
common wall. sleeping facilities; or
Fire-resistance level (FRL) means the grading periods in minutes (c) A room or suite of associated rooms in Class 5, 6, 7, 8 or 9
determined in accordance with NCC-BCA Specification A2.3, for the building; or
following criteria: (d) A room or suite of associated rooms in a Class 9c aged care
(a) Structural adequacy; and building, which includes sleeping facilities and any area for the
exclusive use of a resident.
(b) Integrity; and
Sound Transmission Class (STC) is no longer used, as the
(c) Insulation requirements of the NCC-BCA have changed to comply with
And expressed in that order a dash means that there is no international regulations. The STC was based on different criteria and
requirement for that criterion. For example, 90/--/-- means there is no do not include any correction factors.
requirement for an FRL for integrity and insulation, and --/--/-- means Total R-Value means the sum of the R-values of the individual
there is no requirement for FRL. component layers in a composite element including any air spaces
and associated surface resistances.
38 adbri masonry
RW-Value is the Weighted Sound Reduction Index (Rw) and is a
single number index used to describe the sound transmission loss
characteristics of a construction and is measured in decibels (dB).
adbri masonry 39
Other Adbri Masonry Solutions
Contact Us
adbrimasonry.com.au
[email protected]
Versaloc Walling System
®
NSW Product Range Energy Efficiency