GSA-M270 - M85001-0279 - Intelligent Manual Pull Stations PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Vigilant Catalog u Intelligent Initiating

Manual Pull
Patented

Stations
GSA-M270, GSA-M270P,
GSA-M278
GSA-M270 SERIES

GSA-M278

7150-1483:
0139 S2318

Overview • Break glass operation


An up-front visible glass rod on the GSA-M270 discourages
The GSA-M270 and GSA-M278 series Manual Pull Stations are tampering.
part of Vigilant’s Signature Series system. The GSA-M270 Fire
Alarm Manual Pull Stations feature our very familiar teardrop • Intelligent device with integral microprocessor
shape. They are made from die-cast zinc and finished with red All decisions are made at the station allowing lower com-
epoxy powder-coat paint complemented by aluminum colored munication speed while substantially improving control panel
stripes and markings. With positive pull-lever operation, one pull response time. Less sensitive to line noise and loop wiring
on the station handle breaks the glass rod and turns in a posi- properties; twisted or shielded wire is not required.
tive alarm, ensuring protection plus fool-proof operation. Presignal • ADA Compliant
models (GSA-M270P) are equipped with a general alarm (GA) Meets ADA requirements for manual pull stations.
keyswitch for applications where two stage operation is required.
The up-front highly visible glass rod discourages tampering, but is • Electronic Addressing with Non-volatile memory
not required for proper operation. Permanently stores programmable address, serial number,
type of device, and job number. Automatically updates historic
Vigilant’s double action single stage GSA-M278 station is a con- information including hours of operation, last maintenance
temporary style manual station made from durable red colored date, number of alarms and troubles, and time and date of last
lexan. To initiate an alarm, first lift the upper door marked “LIFT alarm.
THEN PULL HANDLE”, then pull the alarm handle.
• Automatic device mapping
Each station transmits wiring information to the loop control-
Standard Features ler regarding its location with respect to other devices on the
Note: Some features described here may not be supported by all control sys-
circuit.
tems. Check your control panel’s Installation and Operation Guide for details. • Stand-alone operation
The station inputs an alarm even if the loop controller’s polling
• Traditional familiar appearance
interrogation stops.
GSA-M270 models feature our familiar teardrop design with
simple positive pull action and sturdy die-cast metal body. • Diagnostic LEDs
Status LEDs; flashing GREEN shows normal polling; flashing
• One stage (GA), two stage (pre-signal), and double action
RED shows alarm state.
models
GSA-M270 models are available for one or two stage alarm • Designed for high ambient temperature operation
systems. The single stage double action GSA-M278 features a Install in ambient temperatures up to 120 °F (49 °C).
rugged Lexan housing with keyed reset mechanism.

Page 1 of 4 D ATA S H E E T M85001-0279


Not to be used for installation purposes. Issue 8
Application Typical Wiring
The operating characteristics of the fire alarm stations are deter- The fire alarm station’s terminal block accepts #18 AWG (0.75mm2)
mined by their sub-type code or “Personality Code”. NORMALLY- to #12 AWG (2.5mm2) wire sizes. See Signature Loop Controller
OPEN ALARM - LATCHING (Pesonality Code 1) is assigned by the catalog sheet for detailed wiring requirement specifications.
factory; no user configuration is required. The device is configured
for Class B IDC operation. An ALARM signal is sent to the loop Wiring Notes
controller when the station’s pull lever is operated. The alarm con-
1 Refer to Signature Loop Controller manual for maximum
dition is latched at the station.
wire distance.
2. All wiring is power limited and supervised.

Compatibility
Signature Series manual stations are compatible only with Vigi-
lant’s Signature Loop Controller.

Warnings & Cautions


This device will not operate without electrical power. As fires fre-
quently cause power interruption, we suggest you discuss further
safeguards with your local fire protection specialist.

Testing & Maintenance


To test (or reset) the station simply open the station and operate
the exposed switch. The GSA-M270 series are opened with a tool;
the GSA-M278 requires the key which is supplied with that station.
The station’s automatic self-diagnosis identifies when it is defec-
tive and causes a trouble message. The user-friendly maintenance Figure 4. Single Stage Systems
program shows the current state of each Signature series device
and other pertinent messages. Single devices may be deactivated
temporarily, from the control panel. Availability of maintenance
features is dependent on the fire alarm system used.
Scheduled maintenance (Regular or Selected) for proper system
operation should be planned to meet the requirements of the
Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ULC 536 standards.

Figure 5. Two Stage Systems

Page 2 of 4 D ATA S H E E T M85001-0279


Not to be used for installation purposes. Issue 8
Installation
Single-stage Signature Series fire alarm manual pull stations mount to North American 2½ inch (64 mm) deep 1-gang boxes.
Two stage presignal (270P) models require 1½ inch (38 mm) deep 4-inch square boxes with 1-gang, ½-inch raised covers. Openings
must be angular. Rounded openings are not acceptable. Recommended box: Steel City Model 52-C-13; in Canada, use Iberville Model CI-
52-C-49-1/2.
All models include terminals are suited for #12 to #18 AWG (2.5 mm2 to 0.75 mm2) wire size. Edwards recommends that these fire alarm
stations be installed according to latest recognized edition of national and local fire alarm codes.
Electronic Addressing: The loop controller electronically addresses each manual station, saving valuable time during system com-
missioning. Setting complicated switches or dials is not required. Each station has its own unique serial number stored in its on-board
memory. The loop controller identifies each device on the loop and assigns a “soft” address to each serial number. If desired, the stations
can be addressed using the SIGA-PRO Signature Program/Service Tool.

Figure 1. GSA-M278 installation Figure 2. GSA-M270, SIMGC-270F, SIMGC-270B installation

Cover Release
Screw

Comp atible
Electrical Box
with ½-inch
raised covers

Back
Plate

Toggle
Switch
MAL
NOR

LIFT Glass Rod


Release Lever
Do not use
boxes with
rounded
openings.

Figure 3. GSA-M270P, SIMGC-270PB installation

Page 3 of 4 D ATA S H E E T M85001-0279


Not to be used for installation purposes. Issue 8
Specifications
GSA-M270, SIMGC- GSA-M270P,
Catalog Number 270F, SIMGC-270B SIMGC-270PB GSA-M278
Single Action Single Action -Two Double Action
Description
- One Stage Stage (Presignal) - One Stage
Contact us... Uses 1 Module
Addressing Uses 1 Module Uses 2 Module
Email: [email protected] Requirements Address Addresses Address
Web: www.vigilant-fire.com
Standby = 250µA Standby = 396µA Standby = 250µA
Operating Current
Vigilant is an EDWARDS brand. Activated = 400µA Activated = 680µA Activated = 400µA
1016 Corporate Park Drive Diecast Zinc - Red Epoxy Lexan - Red with
Mebane, NC 27302 Construction & Finish
with aluminum markings white markings
© 2013 UTC Fire & Security Americas Type Code Factory Set
Corporation, Inc. All rights reserved. Operating Voltage 15.2 to 19.95 Vdc (19 Vdc nominal)
Specifications subject to change
without notice. Edwards is part of UTC
Operating Temperature: 32ºF to 120ºF (0ºC to 49ºC)
Storage and Operating
Climate, Controls & Security, a unit of Storage Temperature: -4ºF to 140ºF (-20ºC to 60ºC) Humidity: 0 to 93%
Environment
United Technologies Corporation. RH
On-board Green LED - Flashes when polled
LED Operation On-board Red LED - Flashes w hen in alarm
Both LEDs - Glow steady when in alarm (stand-alone)
Compatibility Use With: Signature Loop Controller
Agency Listings UL, ULC (note 1), MEA, CSFM
Note: SIMGC-270F, SIMGC-270B and SIMGC-270PB are ULC listed only. Suffix “F” indicates French markings.
Suffix “B” indicates English/French biling ual markings.

Ordering Information
Ship
Catalog Wt. lbs
Number Description (kg)
GSA-M270 One Stage Fire Alarm Station, English Markings - UL/ULC Listed
SIMGC-
One Stage Fire Alarm Station, French Markings - ULC Listed
270F
SIMGC-
One Stage Fire Alarm Station, French/English Markings - ULC Listed
270B
GSA- Two Stage (Presignal) Fire Alarm Station, English Markings - UL/ULC 1 (0.5)
M270P Listed
SIMGC- Two Stage (Presignal) Fire Alarm Station, French/English Markings
270PB - ULC Listed
Double Action (One Stage) Fire Alarm Station, English Markings
GSA-M278
- UL/ULC Listed

Accessories
32997 GA Key w/Tag - for pre-signal station (CANADA ONLY)
276-K2 GA Key - for pre-signal station (USA ONLY)
276-K1 Station Reset Key, Supplied with all Key Reset Stations
0.1 (.05)
27165 12 Glass Rods - for GSA-M270 series (CANADA ONLY)
270-GLR 20 Glass Rods - for GSA-M270 series (USA ONLY)
276-GLR 20 Glass Rods - for GSA-M278 series
276B-RSB Surface Mount Box, Red - for SIGA pull stations 1 (0.6)
06-27-13

Page 4 of 4 D ATA S H E E T M85001-0279


Not to be used for installation purposes. Issue 8

You might also like