J2-Super Series
Built-In Positioning Function
MODEL
J2-Super Series
MR-J2S- CP
SERVO AMPLIFIER
INSTRUCTION MANUAL
MR-J2S- CP
Servo Amplifier Instruction Manual
MODEL
G
MODEL
CODE
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read
through this Instruction Manual, Installation guide, Servo motor Instruction Manual and appended documents
carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until you have a
full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
: Indicates what must not be done. For example, "No Fire" is indicated by .
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
A- 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns
off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo amplifier, whether the
charge lamp is off or not.
Connect the servo amplifier and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you
may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric
shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area
are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the
power is off. The servo amplifier is charged and you may get an electric shock.
CAUTION
Install the servo amplifier, servo motor and regenerative resistor on incombustible material. Installing them
directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of
the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the
servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large
current may cause a fire when the servo amplifier malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal, Otherwise, a
burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the servo amplifier heat sink, regenerative resistor, servo motor, etc.since they may be hot while
power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a
parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A- 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric
shock, etc.
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts
missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Conditions
Environment
Servo amplifier Servo motor
In [ ] 0 to 55 (non-freezing) 0 to 40 (non-freezing)
Ambient operation [ ] 32 to 131 (non-freezing) 32 to 104 (non-freezing)
temperature [ ] 20 to 65 (non-freezing) 15 to 70 (non-freezing)
In storage
[ ] 4 to 149 (non-freezing) 5 to 158 (non-freezing)
Ambient In operation 90%RH or less (non-condensing) 80%RH or less (non-condensing)
humidity In storage 90%RH or less (non-condensing)
Ambience Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m (3280 ft) above sea level
HC-KFS Series
HC-MFS Series X Y : 49
HC-UFS13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153 X Y : 24.5
HC-RFS Series
[m/s2] 5.9 or less
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352 X : 24.5
HC-SFS203 353 Y : 49
HC-UFS202
X : 24.5
HC-SFS301
(Note) Y : 29.4
Vibration HC-KFS Series
HC-MFS Series X Y : 161
HC-UFS 13 to 73
HC-SFS81
HC-SFS52 to 152
HC-SFS53 to 153 X Y : 80
HC-RFS Series
[ft/s2] 19.4 or less
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352 X : 80
HC-SFS203 353 Y : 161
HC-UFS202
X : 80
HC-SFS301
Y : 96
Note. Except the servo motor with reduction gear.
A- 3
CAUTION
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo
motor and servo amplifier.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W)
directly. Do not let a magnetic contactor, etc. intervene.
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in
the specified direction. Otherwise, the emergency stop (EMG) and other protective circuits may not
operate.
Control Control
output output
RA RA
signal signal
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified
torque.
A- 4
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched
off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident.
A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by
electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ballscrew and the servo motor are
coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a
product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the
purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier signals but
also by an external forced stop (EMG).
Contacts must be open when Circuit must be
servo-off, when an trouble (ALM) opened during
and when an electromagnetic brake forced stop (EMG).
interlock (MBR).
Servo motor
RA EMG
24VDC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
A- 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident
due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general
environment.
Please consult our sales representative.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may
fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Home position setting in the absolute position detection system
Write to the EEP-ROM due to device changes
Write to the EEP-ROM due to point table changes
A- 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety
requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment
into which servo amplifiers have been installed.
(2) Configuration
Control box
Reinforced
insulating type
Reinforced 24VDC
insulating power
No-fuse Magnetic supply
transformer breaker Servo
contactor
motor
Servo
NFB MC amplifier M
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this
purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust,
dirt, etc. (IP54).
A- 7
(4) Power supply
(a) Operate the servo amplifier to meet the requirements of the overvoltage category II set forth in
IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC or EN
Standard should be used in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been
insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked ) of the
servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal (marked ). Always
connect the cables to the terminals one-to-one.
PE terminals PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
(marked ) of the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping
terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options. (Refer to section 14.1.4)
Relevant manuals
Manual name Manual No.
MELSERVO-J2-Super Series To Use the AC Servo Safely IB(NA)0300010
MELSERVO Servo Motor Instruction Manual SH(NA)3181
EMC Installation Guidelines IB(NA)67310
A- 9
MEMO
A - 10
CONTENTS
1.1 Introduction.............................................................................................................................................. 1- 1
1.1.1 Function block diagram ................................................................................................................... 1- 1
1.1.2 System configuration........................................................................................................................ 1- 4
1.1.3 I/O devices ......................................................................................................................................... 1- 9
1.2 Servo amplifier standard specifications ............................................................................................... 1-10
1.3 Function list ............................................................................................................................................ 1-12
1.4 Model code definition ............................................................................................................................. 1-13
1.5 Combination with servo motor.............................................................................................................. 1-14
1.6 Structure.................................................................................................................................................. 1-15
1.6.1 Part names ....................................................................................................................................... 1-15
1.6.2 Removal and reinstallation of the front cover .............................................................................. 1-19
1.7 Servo system with auxiliary equipment............................................................................................... 1-21
2. INSTALLATION 2- 1 to 2- 4
4. OPERATION 4- 1 to 4-46
5. PARAMETERS 5- 1 to 5-24
4
13. CHARACTERISTICS 13- 1 to 13- 8
5
15.11 Command and data No. list............................................................................................................. 15-11
15.11.1 Read commands ......................................................................................................................... 15-11
15.11.2 Write commands ........................................................................................................................ 15-14
15.12 Detailed explanations of commands............................................................................................... 15-17
15.12.1 Data processing.......................................................................................................................... 15-17
15.12.2 Status display ............................................................................................................................ 15-19
15.12.3 Parameter................................................................................................................................... 15-20
15.12.4 External I/O signal statuses..................................................................................................... 15-22
15.12.5 Input devices ON/OFF .............................................................................................................. 15-24
15.12.6 Disable/enable of I/O devices (DIO) ......................................................................................... 15-25
15.12.7 Input devices ON/OFF (test operation) ................................................................................... 15-26
15.12.8 Test operation mode .................................................................................................................. 15-27
15.12.9 Output signal pin ON/OFF output signal (DO) forced output.............................................. 15-30
15.12.10 Alarm history ........................................................................................................................... 15-31
15.12.11 Current alarm .......................................................................................................................... 15-32
15.12.12 Point table ................................................................................................................................ 15-33
15.12.13 Servo amplifier group designation......................................................................................... 15-39
15.12.14 Software version ...................................................................................................................... 15-40
6
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is introduced
here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in
the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7
MEMO
8
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The MR-J2S-CP AC servo amplifier with built-in positioning functions is the MR-J2S-A general-purpose
AC servo amplifier which incorporate single-axis positioning functions. These functions perform
positioning operation by merely setting the position data (target positions), servo motor speeds,
acceleration and deceleration time constants, etc. to point tables as if setting them in parameters. The
servo amplifier is the most appropriate to configure a program-free, simple positioning system or to
simplify a system, for example.
There are 3 points of point tables as standard, and they can be increased up to 31 points by using the MR
Configurator (servo configuration software).
You can choose a configuration suitable for your purpose, e.g. simple positioning system using external
I/O signals (DI/O), operation using DI/O and RS-422 serial communication, or multi drop operation using
RS-422 serial communication.
All servo motors are equipped with an absolute position encoder as standard. An absolute position
detection system can be configured by merely adding a battery to the servo amplifier. Once the home
position has been set, home position return is not required at power on, alarm occurrence, etc.
The MR-J2S-CP AC servo amplifier with positioning function is made easier to use and higher in function
by using it with the MR Configurator (servo configuration software).
1- 1
1. FUNCTIONS AND CONFIGURATION
CN2
amplifier detection protection detection
Encoder
Current
control
Point table
Model adaptive control
Acceleration Deceleration
No. Position Speed time time Dwell Auxiliary
data constant constant
1 1000 1000 80 80 0 0
Speed
control 2 2000 2000 100 100 0 0
3 4000 2000 70 60 500 1
4 500 2000 60 70 1000 1
5 1000 2000 80 80 0 0
Position 6 2000 1000 80 80 0 0
control
7 1000 1000 80 80 0
8 1000 1000 100 100 0 0
1000 100 100 0 0
31 2000 2000 80 80 0 0
Position MR-BAT
command
CON1
creation
Optional battery
RS-232C (for absolute position
A/D RS-422 D/A
detection system)
I/F
CN1A CN1B CN3
Analog monitor
(2 channels)
Controller
D I/O control
Analog Servo on RS-422/RS-232C
(2 channels) Start
Failure, etc.
To other servo
amplifier
Note 1. The built-in regenerative resistor is not provided for the MR-J2S-10CP (1).
2. For 1-phase 230VAC, connect the power supply to L1, L2 and leave L3 open. Refer to section 1.2 for the power supply
specification. L3 is not provided for a 1-phase 100 to120VAC power supply.
3. Servo amplifiers MR-J2S-200CP have a cooling fan.
1- 2
1. FUNCTIONS AND CONFIGURATION
CN2
amplifier detection protection detection
Encoder
Current
control
Point table
Model adaptive control
Acceleration Deceleration
No. Position Speed time time Dwell Auxiliary
data constant constant
1 1000 1000 80 80 0 0
Speed
control 2 2000 2000 100 100 0 0
3 4000 2000 70 60 500 1
4 500 2000 60 70 1000 1
5 1000 2000 80 80 0 0
Position 6 2000 1000 80 80 0 0
control
7 1000 1000 80 80 0
8 1000 1000 100 100 0 0
1000 100 100 0 0
31 2000 2000 80 80 0 0
Position MR-BAT
command
CON1
creation
Optional battery
RS-232C (for absolute position
A/D RS-422 D/A
detection system)
I/F
CN1A CN1B CN3
Analog monitor
(2 channels)
Controller
D I/O control
Analog Servo on RS-422/RS-232C
(2 channels) Start
Failure, etc.
To other servo
amplifier
1- 3
1. FUNCTIONS AND CONFIGURATION
(b) Configuration
The following configuration uses external I/O signals. The personal computer is used with MR
Configurator (servo configuration software) to set, change and monitor the parameters and point
tables.
Personal MR Configurator
External I/O computer (Servo configuration
signals Software)
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1- 4
1. FUNCTIONS AND CONFIGURATION
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
Personal MR Configurator
External I/O computer (Servo configuration
signals Software)
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1- 5
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
Personal MR Configurator
External I/O computer (Servo configuration
signals Software)
Servo amplifier (axis 1)
CN1A CN1B
RS–232C
RS–422
Servo motor
RS–422
External I/O
signals
Servo amplifier (axis 2)
CN1A CN1B
CN2 CN3
Power supply
Servo motor
1- 6
1. FUNCTIONS AND CONFIGURATION
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
Personal MR Configurator
External I/O computer (Servo configuration
signals Software)
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1- 7
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
Personal MR Configurator
External I/O computer (Servo configuration
signals Software)
Servo amplifier (axis 1)
CN1A CN1B
RS–232C
RS–422
Servo motor
RS–422
External I/O
signals
Servo amplifier (axis 2)
CN1A CN1B
CN2 CN3
Power supply
Servo motor
1- 8
1. FUNCTIONS AND CONFIGURATION
This servo amplifier allows devices to be allocated to the pins of connector CN1A/CN1B as desired. The
following devices can be allocated. For device details, refer to section 3.3.2.
Factory- Factory-
Input device Symbol Output device Symbol
allocated pin allocated pin
Proximity dog DOG CN1A-8 Home position return completion ZP CN1A-18
Servo-on SON CN1B-15 Rough match CPO CN1B-4
Forward rotation stroke end LSP CN1B-16 Movement finish MEND CN1B-6
Reverse rotation stroke end LSN CN1B-17 Trouble ALM CN1B-18
Forward rotation start ST1 CN1B-8 Ready RD CN1B-19
Reverse rotation start ST2 CN1B-9 Electromagnetic brake interlock MBR
Automatic/manual selection MD0 CN1B-7 Position range output POT
Point table No. selection 1 DI0 CN1B-5 Warning output WNG
Point table No. selection 2 DI1 CN1B-14 Battery warning output BWNG
Point table No. selection 3 DI2 Limiting torque TLC
Point table No. selection 4 DI3 Temporary stop PUS
Point table No. selection 5 DI4 In position INP
Forced stop EMG Point No. output 1 PT0
Reset RES Point No. output 2 PT1
Override selection OVR Point No. output 3 PT2
External torque limit selection TL Point No. output 4 PT3
Internal torque limit selection TL2 Point No. output 5 PT4
Proportion control PC
Temporary stop/restart STP
Manual pulse generator
TP0
multiplication 1
Manual pulse generator
TP1
multiplication 2
Gain switch CDP
Teach TCH
1- 9
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-J2S- 10CP 20CP 40CP 60CP 70CP 100CP 200CP 350CP 500CP 700CP 10CP1 20CP1 40CP1
Item
3-phase 200 to 230VAC, 50/60Hz 1-phase 100 to
Voltage/frequency 3-phase 200 to 230VAC, 50/60Hz
or 1-phase 230VAC, 50/60Hz 120VAC 50/60Hz
Power supply
Signed absolute value command system, incremental value command system, signed
System
absolute value command/incremental value command specifying system
Operational Positioning using RS-422 (232C) communication data
specifications
Position command Setting through RS-422 (232C) communication
input 1-point feed length setting range: 1[ m] to 999.999[mm]
Setting through RS-422 (232C) communication
Position Speed command
Acceleration/deceleration time is also set through RS-422 (232C) communication.
data input input
S-pattern acceleration/deceleration time constant is set in parameter No.14.
Signed absolute value command system, incremental value command system, signed
System
absolute value command/incremental value command specifying system
Point table number input, position data input system
Automatic Point table Positioning operation is performed once in accordance with the position and speed
operation commands.
mode Automatic continuous Varied speed operation (2 to 31 speeds), automatic continuous positioning operation (2 to
operation 31 points)
Jog operation is performed in accordance with the parameter-set speed command by
Manual Jog
contact input or through RS-422 (232C) communication.
operation
Manual pulse Manual feed is made by manual pulse generator.
mode
generator Command pulse multiplication: 1, 10 or 100 is selected using parameter.
Operation mode
Home position return is made starting with Z-phase pulse after passage of proximity dog.
Home position address may be set. Home position shift distance may be set. Home position
Dog type
return direction may be selected.
Automatic at-dog home position return return/automatic stroke return function
Manual Home position return is made by counting encoder pulses after contact with proximity dog.
home Home position address may be set. Home position shift value may be set. Home position
Count type
position return direction may be set.
return Automatic at-dog home position return return/automatic stroke return function
mode Home position return is made without dog.
Data setting type Home position may be set at any position by manual operation, etc. Home position address
may be set.
Home position return is made by pressing machine part against stroke end.
Stopper type
Home position address may be set. Home position return direction may be set.
1 - 10
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-J2S- 10CP 20CP 40CP 60CP 70CP 100CP 200CP 350CP 500CP 700CP 10CP1 20CP1 40CP1
Item
Home position Position where servo-on (SON) is switched on is defined as home position.
ignorance Home position address may be set.
(Servo-on position as
home position)
Home position return is made with respect to the rear end of a proximity dog.
Dog type rear end Home position address may be set. Home position shift value may be set. Home position
Manual return direction may be set.
reference
home
Operation mode
1 - 11
1. FUNCTIONS AND CONFIGURATION
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Function Description Reference
Select the required ones from among 31 preset point tables and
perform operation in accordance with the set values.
Positioning by automatic operation Section 4.2
Use the external input signal or communication function to choose
the point tables.
Servo motor speed can be varied continuously until the preset
Varied speed operation Section 4.2.6 (2)
moving distance is reached. (Max. set speeds: 31 speeds)
By merely choosing one point table and starting operation,
Automatic continuous positioning
positioning can be executed continuously in accordance with Section 4.2.6 (1)
operation
several point tables.
Dog type, count type, data setting type, stopper type, home
Manual home position return position ignorance, dog type rear end reference, count type front Section 4.4
end reference, dog cradle type
Up to 32 axes of MR-J2S-CP are controllable simultaneously by Section 4.6.3
Multidrop communication
RS-422 communication. Chapter 15
High-resolution encoder of 131072 pulses/rev is used as a servo
High-resolution encoder
motor encoder.
By merely setting the home position once, home position return
Absolute position detection system Section 4.5
need not be done at each power on.
You can switch between gains during rotation and gains during
Gain changing function Section 9.5
stop or use an external signal to change gains during operation.
Servo amplifier detects mechanical resonance and sets filter
Adaptive vibration suppression control Section 9.3
characteristics automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo
Low-pass filter Section 9.4
system response is increased.
Analyzes the frequency characteristic of the mechanical system by
Machine analyzer function simply connecting a MR Configurator (servo configuration
software)-installed personal computer and servo amplifier.
Can simulate machine motions on a personal computer screen on
Machine simulation
the basis of the machine analyzer results.
Personal computer changes gains automatically and searches for
Gain search function
overshoot-free gains in a short time.
Slight vibration suppression control Vibration of 1 pulse at servo motor stop is suppressed. Parameter No. 20
The electronic gear is used to make adjustment so that the servo
amplifier setting matches the machine moving distance. Also,
Electronic gear changing the electronic gear value allows the machine to be moved Section 5.2.1
at any multiplication ratio to the moving distance using the servo
amplifier.
Automatically adjusts the gain to optimum value if load applied to
Auto tuning the servo motor shaft varies. Higher in performance than MR-J2 Chapter 8
series servo amplifier.
S-pattern acceleration/deceleration time
Acceleration/deceleration can be made smoothly. Section 5.2.3
constant
Used when the built-in regenerative resistor of the servo amplifier
Regenerative option does not have sufficient regenerative capability for the Section 14.1.1
regenerative power generated.
Used when the regenerative option cannot provide enough
Brake unit regenerative power. Section 14.1.2
Can be used with the MR-J2S-500CP MR-J2S-700CP.
Used when the regenerative option cannot provide enough
Return converter regenerative power. Section 14.1.3
Can be used with the MR-J2S-500CP MR-J2S-700CP.
1 - 12
1. FUNCTIONS AND CONFIGURATION
MITSUBISHI AC SERVO
AC SERVO Model
MODEL MR-J2S-60CP
Capacity
POWER : 600W
POWER
INPUT : 3.2A 3PH 1PH200-230V 50Hz Applicable power supply
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
OUTPUT : 170V 0-360Hz 3.6A Rated output current
SERIAL : A5
TC3 AAAAG52 PASSED Serial number
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
1 - 13
1. FUNCTIONS AND CONFIGURATION
(2) Model
MR–J2S– CP MR–J2S–100CP or less MR–J2S–200CP 350CP
Series
Power Supply
Rated output
Rated Rated
Symbol Symbol
output [W] output [W]
10 100 100 1000
20 200 200 2000
40 400 350 3500
60 600 500 5000
70 750 700 7000
Rating plate
Rating plate
1.5 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply
to the models with electromagnetic brakes and the models with reduction gears.
Servo motors
Servo amplifier HC-SFS HC-UFS
HC-KFS HC-MFS HC-RFS
1000r/min 2000r/min 3000r/min 2000r/min 3000r/min
MR-J2S-10CP(1) 053 13 053 13 13
MR-J2S-20CP (1) 23 23 23
MR-J2S-40CP (1) 43 43 43
MR-J2S-60CP 52 53
MR-J2S-70CP 73 73 72 73
MR-J2S-100CP 81 102 103
MR-J2S-200CP 121 201 152 202 153 203 103 153 152
MR-J2S-350CP 301 352 353 203 202
MR-J2S-500CP 502 353 503 352 502
MR-J2S-700CP 702
Servo motors
Servo amplifier HA-LFS (Note 1)
1000r/min 1500r/min 2000r/min HC-LFS
MR-J2S-60CP 52
MR-J2S-100CP 102
MR-J2S-200CP 152
MR-J2S-350CP 202
MR-J2S-500CP 502 302
MR-J2S-700CP (Note 2)601 (Note 2)701M 702
Note 1. These servo motors may not be connected depending on the production time of the servo amplifier. Please refer to Appendix 3.
2. Consult us since the servo amplifier to be used with any of these servo motors is optional.
1 - 14
1. FUNCTIONS AND CONFIGURATION
1.6 Structure
Name/Application Reference
Battery holder
Section4.5
Contains the battery for absolute position data backup.
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
1 - 15
1. FUNCTIONS AND CONFIGURATION
POINT
This servo amplifier is shown without the front cover. For removal of the
front cover, refer to section 1.6.2.
Name/Application Reference
Battery holder
Section4.5
Contains the battery for absolute position data backup.
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
1 - 16
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CP
POINT
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to section 1.6.2.
Name/Application Reference
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
1 - 17
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CP
POINT
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to next page.
Name/Application Reference
Battery connector (CON1)
Used to connect the battery for absolute position data Section4.5
backup.
Battery holder
Section4.5
Contains the battery for absolute position data backup.
Display
The 5-digit, seven-segment LED shows the servo Chapter7
status and alarm number.
Operation section
MODE UP DOWN SET Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
1 - 18
1. FUNCTIONS AND CONFIGURATION
Before removing or installing the front cover, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
WARNING between P and N is safe with a voltage tester and others. Otherwise, an electric
shock may occur. In addition, always confirm from the front of the servo amplifier
whether the charge lamp is off or not.
2)
Front cover
1)
2)
1)
Front cover
Front cover socket
(2 places)
1) Hold down the removing knob. 1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Pull the front cover toward you. 2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 19
1. FUNCTIONS AND CONFIGURATION
Front cover
hook
(2 places)
B) A)
2)
2)
1) A)
1)
1) Push the removing knob A) or B), and put you 1) Insert the two front cover hooks at the bottom into the
finger into the front hole of the front cover. sockets of the servo amplifier.
2) Pull the front cover toward you. 2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 20
1. FUNCTIONS AND CONFIGURATION
To prevent an electric shock, always connect the protective earth (PE) terminal
WARNING (terminal marked ) of the servo amplifier to the protective earth (PE) of the control
box.
(1) MR-J2S-100CP or less
(a) For 3-phase 200V to 230VAC or 1-phase 230VAC
(Note 2)
Power supply Options and auxiliary equipment Reference Options and auxiliary equipment Reference
Circuit breaker Section 14.2.2 Cables Section 14.2.1
Magnetic contactor Section 14.2.2 Manual pulse generator Section 14.1.8
MR Configurator External digital display Section 14.1.7
Chapter 6
(Servo configuration software)
Power factor improving reactor Section 14.2.3
Circuit breaker Regenerative option Section 14.1.1
(NFB) or fuse
Servo amplifier Command device
Power
factor
To CN3 MR Configurator
improving CHARGE
Personal (Servo configuration
reactor
computer software
(FR-BAL)
To CN2 MRZJW3-SETUP151E)
L1
L2 U V W
L3
(Note 1)
Power supply lead
Control circuit terminal block D
L21
L11
P
Regenerative option Servo motor
C
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000r/min series have cannon connectors.
2. A 1-phase 230VAC power supply may be used with the servo amplifier of MR-J2S-70CP or less.
For 1-phase 230VAC, connect the power supply to L1 L2 and leave L3 open. Refer to section 1.2 for the power supply
specification.
1 - 21
1. FUNCTIONS AND CONFIGURATION
To CN3 MR Configurator
CHARGE
Personal (Servo configuration
Power computer software
factor To CN2 MRZJW3-SETUP151E)
improving
reactor L1
(FR-BAL) L2 U V W
(Note 1)
Power supply lead
Control circuit terminal block D
L21
L11
P
Regenerative option Servo motor
C
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000 r/min series have cannon connectors.
2. Refer to section 1.2 for the power supply specification.
1 - 22
1. FUNCTIONS AND CONFIGURATION
Junction terminal
block
To CN1A
Magnetic
contactor Manual pulse
(MC) generator
To CN1B
External digital display
Power MR Configurator
factor (Servo
improving To CN2 To CN3 configuration
reactor Personal software
L11 computer MRZJW3-
(FR-BAL)
SETUP151E)
L21
L1
U V W P C
L2
L3 Regenerative option
1 - 23
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CP
(Note 2)
Power supply
Options and auxiliary equipment Reference Options and auxiliary equipment Reference
Circuit breaker Section 14.2.2 Cables Section 14.2.1
Circuit
breaker Magnetic contactor Section 14.2.2 Manual pulse generator Section 14.1.8
(NFB) or
MR Configurator External digital display Section 14.1.7
fuse Chapter 6
(Servo configuration software)
Power factor improving reactor Section 14.2.3
Regenerative option Section 14.1.1
Magnetic
contactor
(MC)
Command device
Power
factor Servo amplifier
improving Junction terminal
block
reactor
(FR-BAL) To CN1A
Manual pulse
L1 generator
L2
L3 To CN1B
External digital display
(Note 1) C P U
Regenerative option
V To CN3
W MR Configurator
(Servo
configuration
Personal
software
To CN2 computer
MRZJW3-
L11 SETUP151E)
L21
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CP
Options and auxiliary equipment Reference Options and auxiliary equipment Reference
Circuit breaker Section 14.2.2 Cables Section 14.2.1
Magnetic contactor Section 14.2.2 Manual pulse generator Section 14.1.8
(Note 2)
Power supply MR Configurator External digital display Section 14.1.7
Chapter 6
(Servo configuration software)
Power factor improving reactor Section 14.2.3
Regenerative option Section 14.1.1
Command device
Circuit
breaker
(NFB) or Junction terminal
fuse block
Servo amplifier
L11
L21 To CN1A
Power
To CN3 MR Configurator
factor (Servo
improving configuration
reactor Personal
software
computer
(FR-BAL) To CN2 MRZJW3-
SETUP151E)
L3 U
L2 V
L1 W
(Note 1) C P
Regenerative option
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 25
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 26
2. INSTALLATION
2. INSTALLATION
Environment Conditions
In [ ] 0 to 55 (non-freezing)
Ambient operation [ ] 32 to 131 (non-freezing)
temperature [ ] 20 to 65 (non-freezing)
In storage
[ ] 4 to 149 (non-freezing)
Ambient In operation
90%RH or less (non-condensing)
humidity In storage
Indoors (no direct sunlight)
Ambience
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Altitude Max. 1000m (3280 ft) above sea level
[m/s ] 5.9 [m/s2] or less
2
Vibration
[ft/s2] 19.4 [ft/s2] or less
2- 1
2. INSTALLATION
Do not hold the front cover to transport the servo amplifier. The servo amplifier
may drop.
The equipment must be installed in the specified direction. Otherwise, a fault may
CAUTION occur.
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
40mm
(1.6 in.)
or more
Servo amplifier Wiring clearance
70mm
(2.8 in.) Up
10mm 10mm
(0.4 in.) (0.4 in.)
or more or more
Down
40mm
(1.6 in.)
or more
2- 2
2. INSTALLATION
10mm
100mm (0.4 in.)
(4.0 in.) or more
or more
30mm 30mm
(1.2 in.) (1.2 in.)
or more or more
40mm
(1.6 in.)
or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the
servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control
box or a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an
air purge (force clean air into the control box from outside to make the internal pressure higher than
the external pressure) to prevent such materials from entering the control box.
2- 3
2. INSTALLATION
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake
wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and
brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner
or stamped by workers or vehicles.
(4) The flexing lives of the cables are shown below. In actuality, provide a little allowance for these values.
For installation on a machine where the servo motor will move, the flexing radius should be made as
large as possible. Refer to section 13.4 for the flexing life.
2- 4
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P and N is safe with a
voltage tester and others. Otherwise, an electric shock may occur. In addition,
always confirm from the front of the servo amplifier whether the charge lamp is off
WARNING or not.
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the forced stop (EMG) and other protective circuits.
Servo amplifier Servo amplifier
COM COM
(24VDC) (24VDC)
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of
the connectors will lead to a failure. Connect them correctly.
3- 1
3. SIGNALS AND WIRING
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the servo amplifier to the protective earth
(PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the forced stop and other protective circuits.
3. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
4. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, supply interface power from
external.
5. When starting operation, always connect the forward/reverse rotation stroke end (LSN/LSP) with SG. (Normally closed
contacts)
6. Trouble (ALM) is connected with COM in normal alarm-free condition.
7. The pins with the same signal name are connected in the servo amplifier.
8. When using override (VC), make the override selection (OVR) device available.
9. When using analog torque limit (TLA), make the external torque limit selection (TL) devices available.
10. When connecting the personal computer together with monitor outputs 1, 2, use the maintenance junction card (MR-
J2CN3TM). (Refer to section 14.1.6).
11. Use MRZJW3-SETUP 151E.
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to section 3.6.2.
3- 2
3. SIGNALS AND WIRING
This section gives the internal connection diagram where the signal assignment is in the initial status.
Servo amplifier
CN1B 24VDC
VDD 3
COM 13
CN1A CN1A
COM 9 18 ZP
Approx. 4.7k
DOG 8
SG 10, 20 CN1B
CN1B 4 CPO
DI0 5 6 MEND
Approx. 4.7k
MD0 7 18 ALM
Approx. 4.7k
ST1 8 19 RD
Approx. 4.7k
ST2 9
Approx. 4.7k
DI1 14
Approx. 4.7k
SON 15
Approx. 4.7k
LSP 16 CN1A
Approx. 4.7k
LSN 17 6 LA
SG 10, 20 16 LAR
CN1A 7 LB
OPC 11 17 LBR
PG 13 Approx. 100 5 LZ
Approx. 1.2k
PP 3 15 LZR
NG 12 14 OP
Approx. 100 Approx. 1.2k
NP 2 1 LG
SD Casing CN3
CN1B 4 MO1
VC 2 14 MO2
TLA 12
2 RXD
15VDC
P15R 11
12 TXD
LG 1 9 SDP
SD Casing 19 SDN
CN1A 5 RDP
P15R 4 15 RDN
PE
3- 3
3. SIGNALS AND WIRING
POINT
The connector pin-outs shown above are viewed from the cable connector
wiring section side.
1 11 1 11
2 12 2 12
LG OPC LG P15R
NP VC TLA
3 13 3 13
4 14 4 14
PP VDD COM
P15R OP CPO DI1
5 15 5 15
6 16 6 16
LZ LZR Servo amplifier DI0 SON
LA LAR MEND LSP
7 17 7 17
8 18 8 18
LB LBR MD0 LSN
DOG ZP ST1 ALM
9 19 9 19
10 20 10 20
COM ST2 RD
SG SG SG SG
CN2 CN3
1 11 1 11
2 12 2 12
LG LG LG LG
LG LG RXD TXD
3 13 3 13
4 14 4 14
LG LG
MO1 MO2
5 15 5 15
6 16 6 16
RDP RDN
MD MDR
7 17 7 17
The connector frames are
8 18 connected with the PE (earth) 8 18
MR MRR
P5 terminal inside the servo amplifier.
9 19 9 19
10 20 10 20
BAT P5 SDP SDN
P5 TRE P5
3- 4
3. SIGNALS AND WIRING
Pin type Connector pin No. I/O division Device in initial status
CN1B-5 Point table No. selection 1 (DI0)
CN1B-14 Point table No. selection 2 (DI1)
CN1A-8 Proximity dog (DOG)
CN1B-15 Servo-on (SON)
Input-only pins CN1B-16 DI-1 Forward rotation stroke end (LSP)
CN1B-17 Reverse rotation stroke end (LSN)
CN1B-7 Automatic/manual selection (MD0)
CN1B-8 Forward rotation start (ST1)
CN1B-9 Reverse rotation start (ST2)
No device has been assigned in the initial
status. You can assign an I/O device using
I/O pin CN1A-19 DI-1 or DO-1
the MR Configurator (servo configuration
software).
CN1B-4 Rough match (CPO)
CN1B-6 Movement finish (MEND)
Output-only pins CN1B-18 DO-1 Trouble (ALM)
CN1B-19 Ready (RD)
CN1A-18 Home position return completion(ZP)
Devices Connector
Device name Functions/Applications
symbol pin No.
Forced stop EMG When EMG-SG are opened, the servo amplifier is placed in the forced stop status,
the servo switches off, and the dynamic brake is operated to bring the servo motor
to a sudden stop.
Short EMG-SG in the forced stop status to cancel the forced stop status.
Servo-on SON CN1B Connect SON-SG to switch on the base circuit and make the servo amplifier ready
15 to operate (servo-on).
Disconnect SON-SG to shut off the base circuit and coast the servo motor (servo-
off) .
Reset RES Disconnect RES-SG for more than 50ms to reset the alarm.
Some alarms cannot be deactivated by the reset signal. Refer to section 11.2.1
If RES-SG are shorted in no alarm status, the base circuit is not shut off.
Set " 1 " in parameter No. 55 to shut off the base circuit.
Since this device is not designed for stopping. Do not switch it on during operation.
3- 5
3. SIGNALS AND WIRING
Devices Connector
Device name Functions/Applications
symbol pin No.
Forward rotation LSP CN1B To start operation, short LSP-SG and/or LSN-SG. Open them to bring the motor to
stroke end 16 a sudden stop and make it servo-locked.
Set " 1" in parameter No. 22 to make a slow stop.
(Refer to section 5.2.5.)
(Note) Input signal Operation
CCW CW
LSP LSN
direction direction
1 1
Reverse rotation stroke LSN CN1B 0 1
end 17 1 0
0 0
Note. 0: LSP/LSN-SG off (open)
1: SP/LSN-SG on (short)
Forward rotation start ST1 CN1B 1. In the case of the absolute value command system.
8 When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
2. In the case of the incremental value command system.
When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
Forward rotation denotes the direction in which the address is incremented.
3. In absolute value command /incremental value command specifying system
When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
Reverse rotation start ST2 CN1B This device is used in the incremental value command system.
9 When ST2-SG are shorted in the automatic operation mode, positioning is executed
once in the reverse rotation direction on the basis of the position data set to the
point table.
In jog operation mode, the servo motor rotates in the reverse rotation direction
while ST2-SG are shorted.
Reverse rotation denotes the direction in which the address is decremented.
The reverse rotation start (ST2) is also used as the start signal of the function to
perform high-speed positioning to the home position. (Refer to section 4.4.11.)
Automatic/manual MD0 CN1B Short MD0-SG to choose the automatic operation mode, or open them to choose the
selection 7 manual operation mode.
Proximity dog DOG CN1A When terminals DOG-SG are shorted, the proximity dog signal is detected. The
8 polarity of dog detection input can be changed with the parameter.
Polarity of proximity dog
Parameter No.8
detection input
0 (initial value) DOG-SG are opened.
1 DOG-SG are shorted.
3- 6
3. SIGNALS AND WIRING
Devices Connector
Device name Functions/Applications
symbol pin No.
Point table No. DI0 CN1B The following table lists the point table numbers that may be chosen by the
selection 1 5 combinations of DI0, DI1, DI2, DI3 and DI4.
(Note)Input signal
Point table No.
Point table No. DI1 CN1B DI4 DI3 DI2 DI1 DI0
selection 2 14 0 (Manual home
0 0 0 0 0
position return)
Point table No. DI2 0 0 0 0 1 1
selection 3 0 0 0 1 0 2
Point table No. DI3 0 0 0 1 1 3
selection 4 0 0 1 0 0 4
Point table No. DI4 0 0 1 0 1 5
selection 5 0 0 1 1 0 6
0 0 1 1 1 7
0 1 0 0 0 8
0 1 0 0 1 9
0 1 0 1 0 10
0 1 0 1 1 11
0 1 1 0 0 12
0 1 1 0 1 13
0 1 1 1 0 14
0 1 1 1 1 15
1 0 0 0 0 16
1 0 0 0 1 17
1 0 0 1 0 18
1 0 0 1 1 19
1 0 1 0 0 20
1 0 1 0 1 21
1 0 1 1 0 22
1 0 1 1 1 23
1 1 0 0 0 24
1 1 0 0 1 25
1 1 0 1 0 26
1 1 0 1 1 27
1 1 1 0 0 28
1 1 1 0 1 29
1 1 1 1 0 30
1 1 1 1 1 31
Note. 0: DI0/DI1/DI2/DI3/DI4-SG off (open)
1: DI0/DI1/DI2/DI3/DI4-SG on (short)
Override selection OVR Short OVR-SG to make override (VC) valid.
External torque limit TL Short TL-SG to make external analog torque limit valid.
selection For more information, refer to section 3.4.4.
Internal torque limit TL2 Open TL2-SG to make the torque limit value set in parameter No.28 (TL1) valid, or
selection short them to make the value set in parameter No.29 (TL2) valid.
For more information, refer to section 3.4.4.
Proportion control PC Connect PC-SG to switch the speed amplifier from the proportional integral type to
the proportional type.
If the servo motor at a stop is rotated even one pulse due to any external factor, it
generates torque to compensate for a position shift. In such a case where the axis
will be locked mechanically after Movement finish (MEND) has turned off, turning
Proportion control (PC) on as soon as Movement finish (MEND) turns off can
suppress unnecessary torque that attempts to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the proportion control (PC)
and torque (TL) at the same time to make the torque less than the rated by the
analog torque limit (TLA).
3- 7
3. SIGNALS AND WIRING
Devices Connector
Device name Functions/Applications
symbol pin No.
Temporary STP Short STP-SG during automatic operation to make a temporary stop. Short STP-
stop/Restart SG again to make a restart.
Shorting the forward rotation start (ST1) or reverse rotation start (ST2) during a
temporary stop is ignored. Switching from automatic operation mode to manual
operation mode during a temporary stop clears the remaining moving distance.
During home position return and jog operation, the temporary stop/restart input is
ignored. Refer to section 4.2.6 (3).
Manual pulse TP0 Used to select the multiplication factor of the manual pulse generator.
generator When it is not selected, the parameter No.1 setting is made valid.
multiplication 1
Manual pulse TP1 (Note) Input signal Manual pulse generator
generator
TP1 TP0 multiplication factor
multiplication 2
0 0 Parameter No.1 setting
0 1 1 time
1 0 10 times
1 1 100 times
Note. 0: TP1/TP0-SG open
1: TP1/TP0-SG shorted
Gain switch CDP Connect CDP-SG to change the load inertia moment ratio into the parameter No.
64 setting and the gain values into the values multiplied by the parameter No. 65
to 67 settings.
Teach TCH Used when performing teaching. Shorting TCH-SG in the teaching setting mode
chooses this device and changes the position data of the point table No. to the
current position. (Refer to section 7.10.)
3- 8
3. SIGNALS AND WIRING
Devices Connector
Device name Functions/Applications
symbol pin No.
Trouble ALM CN1B ALM-SG are disconnected when power is switched off or the protective circuit is
18 activated to shut off the base circuit. Without alarm, ALM-SG are connected within
about 1s after power-on.
Ready RD CN1B RD-SG are connected when the servo is switched on and the servo amplifier is
19 ready to operate.
Movement finish MEND CN1B MEND-SG are connected when the in-position device (INP) turns on and the
6 command remaining distance is "0". (Refer to section 3.4.2.)
MEND-SG are connected at servo on.
Rough match CPO CN1B CPO-SG are connected when the remaining command distance falls within the
4 parameter-set rough match output range.
This signal is not output while the base circuit is off. Servo-on connects CPO-SG.
During home position return and manual operation, CPO-SG are kept connected.
Home position return ZP CN1A ZP-SG are connected on completion of home position return.
completion 18 In the absolute position system, ZP-SG are connected when the servo amplifier is
ready to operate but are disconnected if.
1) SON-SG are opened.
2) EMG-SG are opened.
3) RES-SG are shorted.
4) Alarm occurs.
5) Limit switch opens.
6) Home position return has not been made after the purchase of the product.
7) Home position return has not been made after the occurrence of absolute position
erasure (AL. 25) or absolute position counter warning (AL. E3).
8) Home position return has not been made after the changing of the electronic gear
value.
9) Home position return has not been made after the absolute position system was
made valid.
10) The ST1 coordinate system (000 in parameter No.1) has been changed.
11) Software limit is valid.
12) Home position return completion.
If the status is not any of 1) to 12) and the home position setting has already been
completed at least once, home position return completion (ZP) is placed in the same
output status as ready (RD).
Electromagnetic brake MBR In the servo-off or alarm status, MBR-SG are disconnected.
interlock When an alarm occurs, they are disconnected independently of the base circuit
status.
Position range POT Position range (POT) is on when the current position is within the range set in
parameters No. 50 to 53. If the current position is within the set range, the device
is off when a home position return is not yet complete or while the base circuit is off
(during servo off, alarm occurrence or alarm reset).
Warning WNG When warning has occurred, WNG-SG are connected.
When there is no warning, WNG-SG are disconnected within about 1s after power-
on.
Battery warning BWNG BWNG-SG are connected when battery cable breakage warning (AL.92) or battery
warning (AL.9F) has occurred.
When there is no battery warning, BWNG-SG are disconnected within about 1s
after power-on.
Limiting torque TLC TLC-SG are connected when the torque generated reaches the value set to the
internal torque limit 1 (parameter No. 28), internal torque limit 1 (parameter No.
29) or analog torque limit (TLA).
Temporary stop PUS PUS-SG are connected when deceleration to a stop is started by the temporary stop
signal. PUS-SG is disconnected when operation is resumed by making the
temporary stop signal valid again.
In position INP INP-SG are connected when the number of droop pulses is in the preset in-position
range. The in-position range can be changed using parameter No. 6.
When the in-position range is increased, INP-SG may be kept connected during
low-speed rotation. Servo-on connects INP-SG.
3- 9
3. SIGNALS AND WIRING
Devices Connector
Device name Functions/Applications
symbol pin No.
Point table No. output 1 PT0 As soon as Movement finish (MEND) turns on, the point table No. is output as a 5-
bit code.
3 - 10
3. SIGNALS AND WIRING
3 - 11
3. SIGNALS AND WIRING
(4) Communication
POINT
Refer to chapter 15 for the communication function.
Signal Connector
Signal Functions/Applications
symbol pin No.
RS-422 I/F SDP CN3 RS-422 and RS-232C functions cannot be used together.
9 Choose either one in parameter No. 16.
SDN CN3
19
RDP CN3
5
RDN CN3
15
RS-422 termination TRE CN3 Termination resistor connection terminal of RS-422 interface.
10 When the servo amplifier is the termination axis, connect this terminal to RDN
(CN3-15).
RS-232C I/F TXD CN3 RS-422 and RS-232C functions cannot be used together.
2 Choose either one in parameter No. 16.
RXD CN3
12
Signal Connector
Signal Functions/Applications
symbol pin No.
I/F internal power VDD CN1B Used to output 24V 10% to across VDD-SG.
supply 3 When using this power supply for digital interface, connect it with COM.
Permissible current : 80mA
Digital I/F power COM CN1A Used to input 24VDC (200mA or more) for input interface.
supply input 9 Connect the positive ( ) terminal of the 24VDC external power supply.
CN1B 24VDC 10%
13
Open collector power OPC CN1A When you use a manual pulse generator , supply this terminal with the positive ( )
input 11 power of 24VDC.
Digital I/F common SG CN1A Common terminal for input signals such as SON and EMG. Pins are connected
10 internally.
20 Separated from LG.
CN1B
10
20
15VDC power supply P15R CN1A Outputs 15VDC to across P15R-LG. Available as power for VC and VLA.
4 Permissible current: 30mA
CN1B
11
Control common LG CN1A Common terminal for TLA, VC, OP, MO1, MO2 and P15R.
1 Pins are connected internally.
CN1B
1
CN3
1, 11
3, 13
Shield SD Plate Connect the external conductor of the shield cable.
3 - 12
3. SIGNALS AND WIRING
(1) A forward rotation start (ST1) or a reverse rotation start (ST2) should make the sequence which can
be used after the main circuit has been established. These signals are invalid if it is switched on before
the main circuit is established.
Normally, it is interlocked with the ready signal (RD).
(2) A start in the servo amplifier is made when the external start signal changes from OFF to ON. The
delay time of the servo amplifier's internal processing is max. 3ms. The delay time of other signals is
max. 10ms.
(3) When a programmable controller is used, the ON time of the start/stop signal should be 5ms or longer
to prevent a malfunction.
(4) During operation, the forward rotation start (ST1) or reverse rotation start (ST2) is not accepted. The
next operation should always be started after the rough match (CPO) is output with the rough match
output range set to 0 or after the movement finish (MEND) is output.
3 - 13
3. SIGNALS AND WIRING
POINT
If an alarm cause, etc. are removed and servo-on occurs after a stop is
made by servo-off, alarm occurrence or Forced stop (EMG) ON during
automatic operation, Movement finish (MEND), Rough-match, (CPO) and
In position (INP) are turned on. To resume operation, confirm the current
position and the selected point table No. for preventing unexpected
operation.
ON
Movement finish (MEND)
OFF
When parameter No. 6 is small
ON
Movement finish (MEND)
OFF
When parameter No. 6 is large
ON ON
Rough match (CPO) Rough match (CPO)
OFF OFF
When "0" is set in parameter No. 12 When more than "0" is set in parameter No. 12
3 - 14
3. SIGNALS AND WIRING
(3) In position
The following timing chart shows the relationship between the signal and the feedback pulse of the
servo motor. This timing can be changed using parameter No. 6 (in-position range). INP-SG are
connected in the servo-on status.
Forward rotation start (ST1) ON
or reverse rotation start (ST2) OFF
In-position range
3ms or less
Servo motor speed
ON
In position (INP)
OFF
When positioning operation is performed once
Reverse
rotation
ON
In position (INP)
OFF
When servo motor reverses rotation direction during automatic continuous operation
3 - 15
3. SIGNALS AND WIRING
3.4.3 Override
POINT
When using the override (VC), make the override selection (OVR) device
available.
The override (VC) may be used to change the servo motor speed. The following table lists the signals and
parameter related to the override.
Item Name Remarks
Analog input signal Override (VC)
MR Configurator (servo configuration software)
Contact input signal Override selection (OVR)
setting required.
Parameter No.25 override offset 999 to 999mV
200
OVR
Override selection (OVR)
SG
preset speed
100
VC
Override (VC) LG
10 to 10V SD
0
10 0 10 [V]
Override (VC) application voltage
Motor
Override selection
(OVR)
Override (VC)
10 to 10V
(Note)
External input signal Speed change value
OVR
0 No change
1 Override (VC) setting is made valid.
Note. 0 : Off (open) across OVR-SG
1 : On (shorted) across OVR-SG
POINT
To use the torque limit, make the external torque limit selection (TL) and
internal torque limit selection (TL2) available.
The following table lists the signals and parameters related to the torque limit.
Item Name Remarks
Analog input signal Analog torque limit (TLA)
External torque limit selection (TL)
Contact input signals MR Configurator (servo configuration
Internal torque limit selection (TL2)
software) setting required.
Contact output signal Limiting torque (TLC)
No.28 (internal torque limit 1) 0 to 100%
No.29 (internal torque limit 2) 0 to 100%
Parameters No.26 (torque limit offset) 999 to 999mV
Selection of the rotation direction in which
No.59 (function selection 2)
torque limit is executed
The torque limit is available in two types: internal torque limit set in parameters and analog torque limit
(TLA) using analog input signal. This function limits torque on the assumption that the maximum torque
of the servo motor is 100%.
Max. torque
Torque
0
0 100
Torque limit value [%]
100
TL
SG
P15R
5% 2k
2k TLA
LG
0 Japan Resistor RRS10
0 0.05 10 SD
TLA application voltage [V] or equivalent
TLA Application Voltage vs. Connection Example
Torque Limit Value
3 - 17
3. SIGNALS AND WIRING
(3) External torque limit selection (TL), internal torque limit selection (TL2)
To use the external torque limit selection (TL) and internal torque limit selection (TL2), make them
available using the MR Configurator (servo configuration software) (refer to chapter 6).
These input signals may be used to choose the torque limit values made valid.
(Note) External input signals
Torque limit value made valid
TL2 TL
0 0 Internal torque limit value 1 (parameter No. 28)
TLA Parameter No. 28: Parameter No. 28
0 1
TLA Parameter No. 28: TLA
Parameter No. 29 Parameter No. 28: Parameter No. 28
1 0
Parameter No. 29 Parameter No. 28: Parameter No. 29
TLA Parameter No. 29: Parameter No. 29
1 1
TLA Parameter No. 29: TLA
Note. 0: TL/TL2-SG off (open)
1: TL/TL2-SG on (short)
(5) Selection of rotation direction for torque limit execution (parameter No.59)
Using parameter No.59, the rotation direction for torque limit execution can be selected.
Rotation direction for torque limit execution
Parameter No.59 setting
CCW direction CW direction
0 (initial value)
1
2
For example, when “ 1 ” is set in parameter No.59, torque limit is executed in the CCW direction
but not in CW direction.
3 - 18
3. SIGNALS AND WIRING
When an alarm has occurred, remove its cause, make sure that the operation
signal is not being input, ensure safety, and reset the alarm before restarting
CAUTION operation.
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a
stop. Switch off the main circuit power supply in the external sequence. To reset the alarm, switch the
control circuit power supply from off to on, press the "SET" button on the current alarm screen, or turn
the reset (RES) from off to on. However, the alarm cannot be reset unless its cause is removed.
(Note)
Main circuit
control circuit ON Power off Power on
power supply OFF
Base circuit ON
OFF
Dynamic brake Valid
Brake operation Brake operation
Invalid
Servo-on ON
(SON) OFF
Ready ON
(RD) OFF
Trouble ON
(ALM) OFF
1s
Reset ON
(RES) OFF 50ms or more 60ms or more
Alarm occurs.
Remove cause of trouble.
Note. Switch off the main circuit power as soon as an alarm occurs.
3 - 19
3. SIGNALS AND WIRING
3.6 Interfaces
The following diagram shows the power supply and its common line.
CN1A CN1A
CN1B 24VDC CN1B
RA
VDD
COM ALM,etc
DO-1
SON,etc.
Dl-1 SG
OPC
Manual pulse generator
MR-HDP01
5V
PP(NP)
A(B)
SG SG
0V
<Isolated>
OP
5V
15VDC 10% 30mA LG
P15R
LA,etc
LAR,etc Differential line driver
output
LG
TLA 35mA or less
SD
Analog input VC,
( 10V/max. current) etc.
MO1 CN3 Analog monitor
LG MO2
LG Single-phase
SD 100 to 200VAC
SDP
RXD L1
SDN
RXD L2
RDP
TXD
RDN
TXD E
LG
LG
SD
M
SD
Ground
3 - 20
3. SIGNALS AND WIRING
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in
sections 3.3.2. Refer to this section and connect the interfaces with the external equipment.
For use of internal power supply For use of external power supply
Servo amplifier
Do not connect
24VDC VDD-COM.
VDD Servo amplifier
TR SG
Switch
V CES 1.0V
SG
I CEO 100 A
Note. This also applies to the use of the external power supply.
COM COM
(Note)
Load 24VDC
Load
ALM, etc ALM, etc 10%
SG SG
3 - 21
3. SIGNALS AND WIRING
COM COM
R R (Note)
24VDC
ALM, etc ALM, etc 10%
SG SG
OP OP
Photocoupler
LG LG
SD SD
150
LAR LAR
(LBR, LZR) (LBR, LZR)
LG
SD SD
3 - 22
3. SIGNALS AND WIRING
2) Output pulse
Servo motor CCW rotation
LA
LBR
/2
LZ
LZR
400 s or more
OP
15VDC
P15R
Upper limit setting 2k VC‚ etc
2k
LG Approx.
10k
SD
MO1 10k
(MO2)
Reading in one or
both directions A
LG 1mA meter
SD
3 - 23
3. SIGNALS AND WIRING
For use of internal power supply For use of external power supply
Servo amplifier Servo amplifier
SG
SG
R: Approx. 4.7k
(Note) COM R: Approx. 4.7k
COM
For a transistor SON,
Approx. 5mA etc.
Switch
Switch SON,etc.
24VDC
VDD
TR
24VDC
VCES 1.0V 200mA or more
ICEO 100 A
Note. This also applies to the use of the external power supply.
For use of internal power supply For use of external power supply
Servo amplifier Servo amplifier
24VDC 24VDC Do not connect
VDD VDD VDD-COM.
COM COM
(Note)
Load Load 24VDC
ALM, etc ALM, etc 10%
SG SG
3 - 24
3. SIGNALS AND WIRING
Always connect a magnetic contactor (MC) between the main circuit power supply
and L1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut
down the power supply on the side of the servo amplifier’s power supply. If a
CAUTION magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
Use the trouble signal to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A circuit breaker (NFB) must be used with the input cables of the power supply.
NFB MC
Servo amplifier
L1
3-phase
200 to 230 VAC L2
L3
L11
L21
3 - 25
3. SIGNALS AND WIRING
MC
MC
SK
3 - 26
3. SIGNALS AND WIRING
3.7.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to section 12.1.
Connection Target
Symbol Description
(Application)
Supply L1, L2 and L3 with the following power.
For 1-phase 230VAC, connect the power supply to L1/L2 and leave L3 open.
1) MR-J2S-350CP or less
When using servo amplifier built-in regenerative resistor, connect between P-D
terminals. (Wired by default)
When using regenerative option, disconnect between P-D terminals and
connect regenerative option to P terminal and C terminal.
2) MR-J2S-500CP or 700CP
P, C, D Regenerative option
MR-J2S-500CP and 700CP do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal
and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and
connect regenerative option to P terminal and C terminal.
Refer to section 14.1.1 for details.
When using brake unit, connect to P terminal and N terminal.
Return converter
N Do not connect to servo amplifier MR-J2S-200CP or less.
Brake unit
For details, refer to section 14.1.2, 14.1.3.
Connect this terminal to the protective earth (PE) terminals of the servo motor
Protective earth (PE)
and control box for grounding.
3 - 27
3. SIGNALS AND WIRING
Power supply ON
OFF
Base circuit ON
OFF 10ms 10ms 60ms
Servo-on ON
(SON) OFF 60ms
Reset ON
(RES) OFF
20ms 10ms 20ms 10ms 20ms 10ms
Ready ON
(RD) OFF
Provide an external forced stop circuit to ensure that operation can be stopped and
CAUTION power switched off immediately.
Forced stop (EMG) can be used by making device setting on the MR Configurator (servo configuration
software).
Make up a circuit which shuts off main circuit power as soon as EMG-SG are opened at a forced stop.
To ensure safety, always install an external forced stop switch across EMG-SG. By disconnecting
EMG-SG, the dynamic brake is operated to bring the servo motor to a sudden stop. At this time, the
display shows the servo forced stop warning (AL.E6).
During ordinary operation, do not use the external forced stop (EMG) to alternate stop and run.
The servo amplifier life may be shortened.
Servo amplifier
VDD
COM
EMG
Forced stop
SG
3 - 28
3. SIGNALS AND WIRING
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier
and servo motor. Otherwise, the servo motor will operate improperly.
CAUTION
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the
connectors supplied with the servo motor. Doing so will deform the pins,
causing poor contact.
The connection method differs according to the series and capacity of the servo motor and whether or not
the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the
servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective
earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
PE terminal
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
During power-on, do not open or close the motor power line. Otherwise, a
CAUTION malfunction or faulty may occur.
The following table lists wiring methods according to the servo motor types. Use the connection diagram
which conforms to the servo motor used. For cables required for wiring, refer to section 14.2.1. For
encoder cable connection, refer to section 14.1.4. For the signal layouts of the connectors, refer to section
3.8.3.
For the servo motor connector, refer to chapter 3 of the Servo Motor Instruction Manual.
3 - 29
3. SIGNALS AND WIRING
(Note 1) 24VDC
B1
(Note 2)
HC-KFS053 (B) to 73 (B)
EMG B2 Electromagnetic
HC-MFS053 (B) to 73 (B) brake
To be shut off when servo-on (SON)
HC-UFS13 (B) to 73 (B) switches off or by Trouble (ALM)
CN2
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
U U
V V Motor
W W
(Note 1) 24VDC
HC-SFS121 (B) to 301 (B) B1
B2 (Note 2)
HC-SFS202 (B) to 702 (B)
HC-SFS203 (B) 353 (B) EMG Electromagnetic
To be shut off when servo-on (SON) brake
HC-UFS202 (B) to 502 (B) switches off or by Trouble (ALM)
HC-RFS353 (B) to 503 (B) CN2
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
(Note 1) 24VDC
HC-SFS81(B)
B1
HC-SFS52 (B) to 152 (B) B2
(Note 2)
HC-SFS53 (B) to 153 (B) EMG Electromagnetic
HC-RFS103 (B) to 203 (B) To be shut off when servo-on (SON) brake
switches off or by Trouble (ALM)
HC-UFS72 (B) 152 (B)
CN2
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
3 - 30
3. SIGNALS AND WIRING
3 - 31
3. SIGNALS AND WIRING
MS3102A20-29P MS3102A10SL-4P
Key Key
Pin Signal
Pin Signal Pin Signal
M A BC A (Note)B1
L N A MD K
K T P D B (Note)B2
J E
B MDR L A B
H
S R
F C MR M Note:For the motor with
G
D MRR N SD electromagnetic brake,
View a View b supply electromagnetic
E P
brake power (24VDC).
F BAT R LG There is no polarity.
G LG S P5
H T
J
3 - 32
3. SIGNALS AND WIRING
Configure the electromagnetic brake operation circuit so that it is activated not only
by the servo amplifier signals but also by an external forced stop (EMG).
Contacts must be open when Circuit must be
servo-on (SON) is off or when a trouble (ALM) opened during
is present when a electromagnetic brake forced stop (EMG).
interlock (MBR).
Servo motor
RA EMG
CAUTION 24VDC
Electromagnetic brake
The electromagnetic brake is provided for holding the motor shaft. Do not use it for
ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake
operates properly.
POINT
For the power supply capacity, operation delay time and other
specifications of the electromagnetic brake, refer to the Servo Motor
Instruction Manual.
Note the following when the servo motor equipped with electromagnetic brake is used.
1) In the device setting of the MR Configurator (servo configuration software), make the
electromagnetic brake interlock (MBR) available.
2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3) The brake will operate when the power (24VDC) switches off.
4) While the reset (RES) is on, the base circuit is shut off. When using the servo motor with a vertical
shaft, use the electromagnetic brake interlock (MBR).
5) Turn off the servo-on (SON) after the servo motor has stopped.
COM Z
MBR RA
24VDC B2
(2) Setting
1) In the device setting of the MR Configurator (servo configuration software), make the
electromagnetic brake interlock (MBR) available.
2) Using parameter No. 33 (electromagnetic brake sequence output), set a time delay (Tb) at servo-off
from electromagnetic brake operation to base circuit shut-off as in the timing chart shown in (3) of
this section.
3 - 33
3. SIGNALS AND WIRING
Coasting
Servo motor speed 0 r/min
(60ms) Tb
ON
Base circuit
OFF
(80ms) Electromagnetic
Electromagnetic (Note 1) ON brake operation
brake interlock delay time
(MBR) OFF
ON
Servo-on(RYn0)
OFF
(Note 3)
Forward rotation start ON
(ST1) or reverse rotation
start (ST2) OFF
Electromagnetic Release
brake Activate
Release delay time and external relay (Note 2)
Invalid (ON)
Forced stop (EMG)
Valid (OFF)
3 - 34
3. SIGNALS AND WIRING
No (ON)
Trouble (ALM)
Yes (OFF)
ON
Base circuit
OFF
Electromagnetic (Note 2) ON
brake interlock (MBR)
OFF
Electromagnetic brake
No (ON) operation delay time
Trouble (ALM)
Yes (OFF)
Main circuit ON
power
Control circuit OFF
3 - 35
3. SIGNALS AND WIRING
(e) Only main circuit power supply off (control circuit power supply remains on)
Dynamic brake
Dynamic brake
(10ms) Electromagnetic brake
Forward
Servo motor speed (Note 1)
rotation 15 or more Electromagnetic brake
0r/min
ON
Base circuit
OFF
(Note 3) ON
Electromagnetic
brake interlock (MBR) OFF
Electromagnetic brake
No (ON) operation delay time
Trouble (ALM) (Note 2)
Yes (OFF)
Main circuit ON
power supply OFF
Note 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status, the main circuit off warning (AL.E9) occurs and the trouble
(ALM) does not turn off.
3. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 36
3. SIGNALS AND WIRING
3.10 Grounding
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to
di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always
ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB (NA) 67310).
Control box
Servo motor
NFB MC Servo amplifier
CN2
L1
Encoder
Line filter
(Note)
Power supply L2
L3
L11
U U
L21
V V M
W W
CN1A CN1B
Programmable
controller
Ensure to connect it to PE
terminal of the servo amplifier.
Do not connect it directly to
the protective earth of
the control panel.
Outer
Protective earth(PE) box
Note. For 1-phase 230VAC, connect the power supply to L1 L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
3 - 37
3. SIGNALS AND WIRING
POINT
Refer to Table 14.1 in section 14.2.1 for the wire sizes used for wiring.
3.11.1 For the servo amplifier produced later than Jan. 2006
Approx. 10mm
Cut the wire running out of bar terminal to less than 0.5mm.
Less than 0.5mm
When using a bar terminal for two wires, insert the wires in the direction where the
insulation sleeve does not interfere with the next pole and pressure them.
Pressure
Pressure
3 - 38
3. SIGNALS AND WIRING
Button
(b) When the wires are put together using a bar terminal
Insert a bar terminal with the odd-shaped side of the pressured terminal on the button side.
3 - 39
3. SIGNALS AND WIRING
3.11.2 For the servo amplifier produced earlier than Dec. 2005
Approx. 10mm
(0.39inch)
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take
care to avoid a short caused by the loose wires of the core and the adjacent pole.
Do not solder the core as it may cause a contact fault. Alternatively, a bar
terminal may be used to put the wires together.
2) Connection
Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver
so that the cable does not come off. (Tightening torque: 0.3 to 0.4N m (2.7 to 3.5Ib in)) Before
inserting the cable into the opening, make sure that the screw of the terminal is fully loose.
When using a cable of 1.5mm2 or less, two cables may be inserted into one opening.
3 - 40
3. SIGNALS AND WIRING
Flat-blade screwdriver
Tip thickness 0.4 to 0.6mm (0.016 to 0.024in.)
Overall width 2.5 to 3.5mm (0.098 to 0.138in.)
To loosen. To tighten.
Cable
Opening
Use of a flat-blade torque screwdriver is recommended to manage the screw tightening torque. The
following table indicates the recommended products of the torque screwdriver for tightening torque
management and the flat-blade bit for torque screwdriver. When managing torque with a Phillips bit,
please consult us.
3 - 41
3. SIGNALS AND WIRING
When fabricating an encoder cable or the like, securely connect the shielded external conductor of the
cable to the ground plate as shown in this section and fix it to the connector shell.
Screw
Cable
Screw
Ground plate
3 - 42
4. OPERATION
4. OPERATION
(1) Wiring
(a) A correct power supply is connected to the power input terminals (L1, L2, L3, L11, L21) of the servo
amplifier.
(b) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the
power input terminals (U, V, W) of the servo motor.
(c) The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the
power input terminals (L1, L2, L3) of the servo motor.
(d) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
(e) Note the following when using the regenerative option, brake unit or power regeneration converter.
1) For the MR-J2S-350CP or less, the lead has been removed from across D-P of the control circuit
terminal block, and twisted cables are used for its wiring.
2) For the MR-J2S-500CP or more, the lead has been removed from across P-C of the servo
amplifier built-in regenerative resistor, and twisted cables are used for its wiring.
(f) When stroke end limit switches are used, the signals across LSP-SG and LSN-SG are on during
operation.
(g) 24VDC or higher voltages are not applied to the pins of connectors CN1A and CN1B.
(h) SD and SG of connectors CN1A and CN1B are not shorted.
(i) The wiring cables are free from excessive force.
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
(3) Machine
(a) The screws in the servo motor installation part and shaft-to-machine connection are tight.
(b) The servo motor and the machine connected with the servo motor can be operated.
4- 1
4. OPERATION
4.1.2 Startup
WARNING Do not operate the switches with wet hands. You may get an electric shock.
Before starting operation, check the parameters. Some machines may perform
unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands
and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor,
CAUTION servo motor, etc.since they may be hot while power is on or for some time after
power-off. Their temperatures may be high and you may get burnt or a parts may
damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can
cause injury.
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
For startup reference, a single machine structure will be described. Refer to this section and start up the
machine safely.
5) For the device command method, external input signals are used by the point table selection,
forward rotation start (ST1), servo-on (SON) and other commands.
6) Point table No.1 is used to execute automatic operation once.
4- 2
4. OPERATION
10
When forward rotation start (ST1) is
valid, address is incremented in CCW
No.1 Feeding function selection direction.
Since command resolution is 10 times,
feed length multiplication factor of 10
times is selected.
1
No.2 Function selection 1
Absolute position detection system.
No.4 Electronic gear numerator (CMX) 32768 From calculation result of formula (4.1)
No.5 Electronic gear denominator (CDV) 1250 From calculation result of formula (4.1)
After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
(d) Point table setting
Set the point table according to the operation pattern. Refer to section 4.2 for the point table
definitions and to sections 6.5 and 7.5 for the setting method.
Position data Servo motor Acceleration time Deceleration time Auxiliary
Dwell [ms]
[ 10STM m] speed [r/min] constant [ms] constant [ms] function
20000 2500 200 300 0 0
(e) Servo-on
Switch the servo-on in the following procedure.
1) Switch on main circuit/control circuit power.
2) Switch on the servo-on (SON).
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is
locked. By using the sequence in the diagnostic mode in section 7.3, the ready status can be shown
on the servo amplifier display. In the operation-ready status, the following screen appears.
4- 3
4. OPERATION
After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
home position return.
Device name Symbol ON/OFF Description
Automatic/manual selection MD0 ON
Point table No. selection 1 DI0 OFF Home position return mode is selected.
Point table No. selection 2 DI1 OFF
Forward rotation stroke end LSP ON CCW rotation side limit switch is turned on.
Reverse rotation stroke end LSN ON CW rotation side limit switch is turned on.
Servo-on SON ON Servo is switched on.
(h) Stop
In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo
motor.
When the servo motor used is equipped with an electromagnetic brake, refer to section 3.9 (3). Note
that forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off has the same
stopping pattern as described below.
1) Servo-on (SON) OFF
The base circuit is shut off and the servo motor coasts.
2) Alarm occurrence
When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the
servo motor to a sudden stop.
3) Forced stop (EMG) OFF
The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a
sudden stop. Servo forced warning (AL.E6) occurs.
4) Forward rotation stroke end (LSP), reverse rotation stroke end (LSN) OFF
The droop pulse value is erased and the servo motor is stopped and servo-locked. It can be run in
the opposite direction.
4- 4
4. OPERATION
4- 5
4. OPERATION
4- 6
4. OPERATION
4- 7
4. OPERATION
0
Absolute value command system
4- 8
4. OPERATION
CCW
CW
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to perform positioning to the position data
under the conditions of the preset speed, acceleration time constant and deceleration time constant. At
this time, reverse rotation start (ST2) is invalid.
Item Setting method Description
Automatic operation mode selection Automatic/manual selection (MD0) MD0 is turned on.
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table selection Point table No. selection 3 (DI2) Refer to section 4.2.1, (2).
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
Start Forward rotation start (ST1) Short ST1-SG (ON) to start.
4- 9
4. OPERATION
1
Incremental value command system
4 - 10
4. OPERATION
ST1:ON ST2:ON
CCW CCW
CW CW
ST2:ON ST1:ON
Parameter No. 1 0 Parameter No. 1 1
(c) Feed length multiplication selection (parameter No.1) Set the unit multiplication factor (STM) of
position data.
Parameter No.1 setting Position data input range [mm]
0 0 to 999.999
1 0 to 9999.99
2 0 to 99999.9
3 0 to 999999
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to make a motion in the forward rotation
direction over the distance of the position data under the conditions of the preset speed, acceleration
time constant and deceleration time constant. Short ST2-SG to make a motion in the reverse rotation
direction in accordance with the point table settings.
Item Setting method Description
Automatic operation mode selection Automatic/manual selection (MD0) MD0 is turned on.
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table selection Point table No. selection 3 (DI2) Refer to section 4.2.1, (2).
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
Short ST1-SG (ON) to start motion
Forward rotation start (ST1)
in forward rotation direction.
Start
Short ST2-SG (ON) to start motion
Reverse rotation start (ST2)
in reverse rotation direction.
4 - 11
4. OPERATION
This system is an auxiliary function for point tables to use them by specifying the absolute value
command and incremental value command.
(1) Point table
Set each value of point tables by using MR Configurator (Setup software) or operation section.
Set to point tables the following, "Position data", "Servo motor speed", "Acceleration time constant",
"Deceleration time constant", "Dwell time" and "Auxiliary function".
To specify the command system, set "Auxiliary function" as shown below.
For absolute value command system, set "0" or "1".
For incremental value command system, set "2" or "3".
Name Setting range Unit Description
(1) When this point table is used in an absolute value command system
Set the target address (absolute value).
This value can also be set using the teaching function. (Refer to section
7.10.)
Position data 999999 to 999999 10STM m
(2) When this point table is used in an incremental value command system
Set the moving distance. A " " sign indicates a reverse rotation
command.
The teaching function is unusable.
Set the command speed of the servo motor for execution of positioning.
Servo motor
0 to permissible speed r/min The setting should be equal to or less than the instantaneous permissible
speed
speed of the servo motor.
Acceleration Set the acceleration time constant.
0 to 20000 ms
time constant Set the time until the rated speed of the servo motor is reached.
Deceleration Set the deceleration time constant.
0 to 20000 ms
time constant Set the time until the servo motor running at rated speed comes to a stop.
Set the dwell.
Set "0" or "2" in the auxiliary function to make the dwell invalid.
Set "1" or "3" in the auxiliary function and 0 in the dwell to perform
Dwell 0 to 20000 ms continuous operation.
When the dwell is set, the position command of the selected point table is
completed, and after the set dwell has elapsed, the position command of the
next point table is started.
Set the auxiliary function.
(1) When this point table is used in an absolute value command system
0: Automatic operation is performed in accordance with a single point table
chosen.
1: Operation is performed in accordance with consecutive point tables
without a stop.
Auxiliary (2) When this point table is used in an incremental value command system
0 to 3 2: Automatic operation is performed in accordance with a single point table
function
chosen.
3: Operation is performed in accordance with consecutive point tables
without a stop.
When a different rotation direction is set, smoothing zero (command
output) is confirmed and the rotation direction is then reversed.
Setting "1" or "3" in point table No.31 results in an error.
For full information, refer to section 4.2.6.
4 - 12
4. OPERATION
CCW
CW
(c) Feed length multiplication selection (parameter No.1) Set the unit multiplication factor (STM) of
position data.
Parameter No.1 setting Position data input range [mm]
0 0 to 999.999
1 0 to 9999.99
2 0 to 99999.9
3 0 to 999999
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to perform positioning to the position data
under the conditions of the preset speed, acceleration time constant and deceleration time constant. At
this time, reverse rotation start (ST2) is invalid.
Item Setting method Description
Automatic operation mode selection Automatic/manual selection (MD0) MD0 is turned on.
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table selection Point table No. selection 3 (DI2) Refer to section 4.2.1, (2).
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
Start Forward rotation start (ST1) Short ST1-SG (ON) to start.
4 - 13
4. OPERATION
Forward
rotation Point table No. 1
Servo motor speed 0r/min
Reverse Point table No. 2
rotation
In position (INP) ON
OF
ON
Rough match (CPO)
OF
Movement finish ON
(MEND) OF
Ready (RD) ON
OF
ON
Trouble (ALM)
OF
Note 1: Reverse rotation start (ST2) is invalid in the absolute value command system and absolute value command/incremental
value command specifying system.
2: External input signal detection delays by the input filter setting time of parameter No. 2. Also, make up a sequence
that will change the point table selection earlier by the time that takes into account the output signal sequence from
the controller and the variation of a signal change due to the hardware.
4 - 14
4. OPERATION
4 - 15
4. OPERATION
Forward Speed
Servo motor speed rotation Speed
(3000)
(2000) Speed (1000)
0
Position address
0 5.00 10.00 15.00
4 - 16
4. OPERATION
Speed
Forward (3000)
rotation
Servo motor speed 0
Reverse Speed
rotation (2000)
Position address
0 5.00 10.00
4 - 17
4. OPERATION
Forward Speed
Servo motor speed Speed
rotation (3000)
(2000) Speed
0 (1000)
(Note) ON
Forward rotation start (ST1)
OFF
Note. Turning on Reverse rotation start (ST2) starts positioning in the reverse rotation direction.
4 - 18
4. OPERATION
3.00 6.00
Position address
0 5.00 8.00 10.00 16.00
4 - 19
4. OPERATION
Speed
Speed
Forward (3000)
(2000)
rotation
Servo motor speed 0
Reverse Speed (1000) Acceleration time constant
rotation
of point table No. 1 (100)
7.00
Position address
0 5.00 8.00 12.00
4 - 20
4. OPERATION
Dwell ta tb
ta tb
Servo motor speed
0
4 - 21
4. OPERATION
For machine adjustment, home position matching, etc., jog operation or a manual pulse generator may be
used to make a motion to any position.
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the point
table No. selection 1 to 5 (DI0 to DI4) are invalid.
Item Setting method Description
Manual operation mode selection Automatic/manual selection (MD0) Open MD0-SG (OFF).
Servo motor rotation direction Parameter No.1 Refer to (2) of this section.
Jog speed Parameter No.13 Set the speed of the servo motor.
Use the acceleration/deceleration
Acceleration/deceleration time constant Point table No.1
time constants in point table No.1.
ST1:ON ST2:ON
CCW CCW
CW CW
ST2:ON ST1:ON
Parameter No. 1 0 Parameter No. 1 1
(3) Operation
By shorting ST1-SG, operation is performed under the conditions of the jog speed set in the parameter
and the acceleration and deceleration time constants in set point table No.1. For the rotation direction,
refer to (2) of this section. By shorting ST2-SG, the servo motor rotates in the reverse direction to
forward rotation start (ST1).
4 - 22
4. OPERATION
Forward
rotation
Servo motor speed 0r/min
Reverse
rotation
ON
Forward rotation start Forward rotation jog
OFF
(ST1)
ON
Reverse rotation start Reverse rotation jog
OFF
(ST2)
4 - 23
4. OPERATION
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the point
table No. selection 1 to 5 (DI0 to DI4) are invalid.
Item Setting method Description
Manual operation mode selection Automatic/manual selection (MD0) Open MD0-SG (OFF).
Set the multiplication ratio of servo
motor rotation to the pulses generated by
Manual pulse generator
Parameter No.1 the manual pulse generator.
multiplication
For more information, refer to (3) of this
section.
Servo motor rotation direction Parameter No.1 Refer to (2) of this section.
CCW
Forward rotation CW
4 - 24
4. OPERATION
(4) Operation
Turn the manual pulse generator to rotate the servo motor. For the rotation direction of servo motor,
refer to (2) of this section.
4 - 25
4. OPERATION
Home position return is performed to match the command coordinates with the machine coordinates. In
the incremental system, home position return is required every time input power is switched on. In the
absolute position detection system, once home position return is done at the time of installation, the
current position is retained if power is switched off. Hence, home position return is not required when
power is switched on again.
This servo amplifier has the home position return methods given in this section. Choose the most
appropriate method for your machine structure and application.
This servo amplifier has the home position return automatic return function which executes home
position return by making an automatic return to a proper position if the machine has stopped beyond or
at the proximity dog. Manual motion by jog operation or the like is not required.
4 - 26
4. OPERATION
(3) Instructions
1) Before starting home position return, always make sure that the limit switch operates.
2) Confirm the home position return direction. Incorrect setting will cause the machine to run
reversely.
3) Confirm the proximity dog input polarity. Otherwise, misoperation can occur.
4 - 27
4. OPERATION
A home position return method using a proximity dog. With deceleration started at the front end of the
proximity dog, the position where the first Z-phase signal is given past the rear end of the dog or a motion
has been made over the home position shift distance starting from the Z-phase signal is defined as a home
position.
L2 2 S ................................................................................... (4.3)
L2 : Proximity dog length [mm]
S : Moving distance per servo motor revolution [mm]
4 - 28
4. OPERATION
ON
Z-phase
OFF
ON
Proximity dog (DOG)
OFF
ON 5ms or more
Forward rotation start (ST1)
OFF
ON
Reverse rotation start (ST2)
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
(4) Adjustment
In dog type home position return, adjust to ensure that the Z-phase signal is generated during dog
detection. Locate the rear end of the proximity dog (DOG) at approximately the center of two
consecutive Z-phase signals.
The position where the Z-phase signal is generated can be monitored in "Within one-revolution
position" of "Status display".
0 65536 0
Servo motor
Z-phase Proximity
dog
Proximity dog ON
(DOG) OF
4 - 29
4. OPERATION
In count type home position return, a motion is made over the distance set in parameter No.43 (moving
distance after proximity dog) after detection of the proximity dog front end. The position where the first Z-
phase signal is given after that is defined as a home position. Hence, if the proximity dog (DOG) is 10ms
or longer, there is no restriction on the dog length. This home position return method is used when the
required proximity dog length cannot be reserved to use dog type home position return or when the
proximity dog (DOG) is entered electrically from a controller or the like.
Z-phase ON
OFF
Proximity dog (DOG) ON
OFF
Forward rotation ON 5ms or more
start (ST1) OFF
Reverse rotation ON
start (ST2) OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 30
4. OPERATION
Data setting type home position return is used when it is desired to determine any position as a home
position. JOG operation, manual pulse generator operation or like can be used for movement.
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 31
4. OPERATION
In stopper type home position return, a machine part is pressed against a stopper or the like by jog
operation, manual pulse generator operation or the like to make a home position return and that position
is defined as a home position.
4 - 32
4. OPERATION
Movement finish ON
(MEND) OFF
Rough match ON
(CPO) OFF
Home position ON
return completion
(ZP) OFF
Stopper time
ON Parameter No. 44
Limiting torque (TLC)
OFF
(Note)
Torque limit to be
I/O devices Limit value status
enabled
TL1 TL
0 0 Parameter No.45
TLA Parameter No.45 Parameter No.45
0 1
TLA Parameter No.45 TLA
Parameter No.29 Parameter No.45 Parameter No.45
1 0
Parameter No.29 Parameter No.45 Parameter No.45
TLA Parameter No.45 Parameter No.45
1 1
TLA Parameter No.45 TLA
Note. 0: OFF
1: ON
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 33
4. OPERATION
The parameter No.42 (home position return position data) setting value is the positioning address after
the home position return is completed.
4 - 34
4. OPERATION
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the rear end of a proximity dog.
Hence, if a home position return is made at the creep speed of 100r/min, an
error of 200 pulses will occur in the home position. The error of the home
position is larger as the creep speed is higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and home position shift distance after it passed the rear
end is defined as a home position. A home position return that does not depend on the Z-phase signal can
be made.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item Device/Parameter used Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
Point table No. selection 1 (DI0) Open (turn off) DI0-SG.
selection
Point table No. selection 2 (DI1) Open (turn off) DI1-SG.
Dog type rear end reference home
Parameter No.8 5: Select the dog type rear end reference.
position return
Home position return direction Parameter No.8 Refer to section 4.4.1 (2) and select the home position return direction.
Dog input polarity Parameter No.8 Refer to section 4.4.1 (2) and select the dog input polarity.
Home position return speed Parameter No.9 Set the speed till the dog is detected.
Creep speed Parameter No.10 Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed
Home position shift distance Parameter No.11
the proximity dog rear end.
Set the moving distance after the axis has passed the proximity dog
Moving distance after proximity dog Parameter No.43
rear end.
Home position return acceleration/
Point table No.1 Use the acceleration/deceleration time constant of point table No. 1.
deceleration time constants
Home position return position data Parameter No.42 Use to set the current position on completion of home position return.
Creep speed
ON
Proximity dog (DOG)
OFF
ON
Forward rotation start (ST1)
OFF
5ms or more
ON
Reverse rotation start (ST2)
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 35
4. OPERATION
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the front end of a proximity dog.
Hence, if a home position return is made at the home position return speed
of 100r/min, an error of 200 pulses will occur in the home position. The
error of the home position is larger as the home position return speed is
higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and home position shift distance is defined as a home
position. A home position return that does not depend on the Z-phase signal can be made. The home
position may change if the home position return speed varies.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item Device/Parameter used Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
Point table No. selection 1 (DI0) Open (turn off) DI0-SG.
selection
Point table No. selection 2 (DI1) Open (turn off) DI1-SG.
Count type dog front end reference
Parameter No.8 6: Select the count type dog front end reference.
home position return
Refer to section 4.4.1 (2) and select the home position return
Home position return direction Parameter No.8
direction.
Dog input polarity Parameter No.8 Refer to section 4.4.1 (2) and select the dog input polarity.
Home position return speed Parameter No.9 Set the speed till the dog is detected.
Creep speed Parameter No.10 Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed
Home position shift distance Parameter No.11
the proximity dog rear end.
Set the moving distance after the axis has passed the proximity dog
Moving distance after proximity dog Parameter No.43
rear end.
Home position return acceleration/
Point table No.1 Use the acceleration/deceleration time constant of point table No. 1.
deceleration time constants
Home position return position data Parameter No.42 Use to set the current position on completion of home position return.
ON
Proximity dog (DOG)
OFF
Forward rotation ON
start (ST1) OFF
5ms or more
Reverse rotation ON
start (ST2) OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 36
4. OPERATION
The position where the first Z-phase signal is issued after detection of the proximity dog front end can be
defined as a home position.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item Device/Parameter used Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
Point table No. selection 1 (DI0) Open (turn off) DI0-SG.
selection
Point table No. selection 2 (DI1) Open (turn off) DI1-SG.
Dog cradle type home position return Parameter No.8 7: Select the dog cradle type.
Refer to section 4.4.1 (2) and select the home
Home position return direction Parameter No.8
position return direction.
Refer to section 4.4.1 (2) and select the dog input
Dog input polarity Parameter No.8
polarity.
Home position return speed Parameter No.9 Set the speed till the dog is detected.
Creep speed Parameter No.10 Set the speed after the dog is detected.
Set when the home position is moved from the Z-
Home position shift distance Parameter No.11
phase signal position.
Home position return
Use the acceleration/deceleration time constant of
acceleration/deceleration time Point table No.1
point table No. 1.
constants
Use to set the current position on completion of
Home position return position data Parameter No.42
home position return.
Creep speed
ON
Z-phase
OFF
ON
Proximity dog (DOG)
OFF
Forward rotation ON
start (ST1) OFF
5ms or more
Reverse rotation ON
start (ST2) OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 37
4. OPERATION
If the current position is at or beyond the proximity dog in the home position return using the proximity
dog, this function starts home position return after making a return to the position where the home
position return can be made.
Stroke end
(LSP or LSN)
Home position return direction Proximity dog
4 - 38
4. OPERATION
POINT
You cannot perform automatic positioning from outside the position data
setting range to the home position. In this case, make a home position
return again using a manual home position return.
If this function is used when returning to the home position again after performing a manual home
position return after a power-on and deciding the home position, automatic positioning can be carried out
to the home position at high speed. In an absolute position system, manual home position return is not
required after power-on.
Please perform a manual home position return beforehand after a power-on.
Set the input signals and parameter as follows.
Item Device/Parameter used Description
Automatic/manual selection (MD0) Short MD0-SG (ON).
Manual home position return mode
Point table No. selection 1 (DI0) Open DI0-SG (OFF).
selection
Point table No. selection 2 (DI1) Open DI1-SG (OFF).
Home position return speed Parameter No.9 Speed is set up.
Home position return acceleration Use the acceleration time constant of point table
Point table No.1
time constant No.1.
Set up the home position return speed of the automatic positioning function to the home position by
parameter No.9. Use the data of point table No.1 to set the acceleration time constant and deceleration
time constant. When reverse rotation start (ST2) is ON, it will position automatically at the home
position.
Home position return speed Deceleration time constant
Acceleration time constant
Parameter No. 9 of point table No. 1
of point table No. 1
Home position
4 - 39
4. OPERATION
POINT
When the following parameters are changed, the home position is lost
when turning on the power after the change. Execute the home position
return again when turning on the power.
First digit of parameter No.1 (ST1 coordinate system selection)
Parameter No. 4 (Electronic gear numerator)
Parameter No. 5 (Electronic gear denominator)
Parameter No. 42 (Home position return position data)
This servo amplifier contains a single-axis controller. Also, all servo motor encoders are compatible with
an absolute position system. Hence, an absolute position detection system can be configured up by merely
loading an absolute position data back-up battery and setting parameter values.
(1) Restrictions
An absolute position detection system cannot be built under the following conditions.
(2) Specifications
Item Description
System Electronic battery backup system
1 piece of lithium battery ( primary battery, nominal 3.6V)
Battery
Type: MR-BAT or A6BAT
Maximum revolution range Home position 32767 rev.
(Note 1) Maximum speed at power failure 500r/min
(Note 2) Battery backup time Approx. 10,000 hours (battery life with power off)
(Note 3) Data holding time during battery
2 hours at delivery, 1 hour in 5 years after delivery
replacement
Battery storage period 5 years from date of manufacture
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like.
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years independently of
whether power is kept on or off.
3. Period during which data can be held by the super capacitor in the encoder after power-off, with the battery voltage low or
the battery removed, or during which data can be held with the encoder cable disconnected.
Battery replacement should be finished within this period.
4 - 40
4. OPERATION
(3) Structure
Component Description
Servo amplifier
Use standard models.
Servo motor
Battery MR-BAT or A6BAT
Use a standard model.
Encoder cable
When fabricating, refer to (2), section 14.1.4.
Position control
data
Speed control
I/O circuit EEP-ROM memory
(DI0 to DI3), etc. LSO Current position
1XO
Position data, speed data Backup at
power off 1X
(current position read) LS
Detection of position
Speed detection
within one revolution
Battery MR-BAT
Servo motor
1 pulse/rev. Cumulative
revolution counter High-speed serial
Super capacitor communication
Before installing a battery, turn off the main circuit power while keeping the control
circuit power on. Wait for 15 minutes or more until the charge lamp turns off. Then,
WARNING confirm that the voltage between P and N is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, always confirm from the front
of the servo amplifier whether the charge lamp is off or not.
POINT
The internal circuits of the servo amplifier may be damaged by static
electricity.
Always take the following precautions.
Ground human body and work bench.
Do not touch the conductive areas, such as connector pins and electrical
parts, directly by hand.
4 - 41
4. OPERATION
1) Open the operation window. (When the model used is the MR-J2S-200CP MR-J2S-350CP or more,
also remove the front cover.)
2) Install the battery in the battery holder.
3) Install the battery connector into CON1 until it clicks.
Battery connector
Operation window Battery connector
CON1
CON1
Battery
Battery connector
CON1
4 - 42
4. OPERATION
The RS-422 or RS-232C communication function may be used to operate the servo amplifier from a
command device (controller) such as a personal computer. Positioning operation can be performed with
the positioning operation/position specified by selection of the point tables. Note that the RS-422 and RS-
232C communication functions cannot be used at the same time.
This section provides a data transfer procedure. Refer to chapter 15 for full information on the connection
and transferred data between the controller and servo amplifier.
By selecting the point table No. and switching on the forward rotation start (ST1) or reverse rotation start
(ST2) using the communication function, positioning operation in accordance with point tables can be
started.
Servo motor
speed 3ms
4 - 43
4. OPERATION
Positioning operation can be performed by changing the point table settings and making a start. For
example, positioning operation can be performed by writing the data of point table No.1, then specifying
point table No.1, and making a start.
For transmission data details, refer to chapter 15.
5ms or more
Transmission data 1) 2) 3) 4) 5) 6) 7) 8)
The RS-422 communication function can be used to operate several servo amplifiers on the same bus. In
this case, set the station numbers to the servo amplifiers to determine the destination servo amplifier of
the currently transmitted data. Use parameter No.15 to set the station numbers.
Always set one station number to one servo amplifier. Normal communication cannot be made if one
station number is set to two or more servo amplifiers. When using one command to operate several servo
amplifiers, use the group designation function described in section 4.6.4.
MITSUBISHI MITSUBISHI MITSUBISHI MITSUBISHI
4 - 44
4. OPERATION
When using several servo amplifiers, command-driven parameter settings, etc. can be made on a group
basis.
You can set up to six groups, a to f. Set the group to each station using the communication command.
Controller
RS-422
Group d Group c
4 - 45
4. OPERATION
Station 0
Servo motor
speed
Station 1
Servo motor
speed
Station 2
Group a Servo motor
speed
Station 3
Servo motor
speed
Station 4
Servo motor
speed
Group b
Station 5
Servo motor
speed
Station 6
Servo motor
speed
Group c Station 7
Servo motor
speed
Station 8
Servo motor
Group d speed
Station 9
Servo motor
speed
In addition, parameter values common to the stations of each group can be written and alarm reset
can be made, for example.
4 - 46
5. PARAMETERS
5. PARAMETERS
Never adjust or change the parameter values extremely as it will make operation
CAUTION instable.
POINT
Set "000E" when using the MR Configurator (servo configuration
software) to make device setting.
After setting the parameter No.19 value, switch power off, then on to
make that setting valid.
In the servo amplifier, its parameters are classified into the basic parameters (No.0 to 19), expansion
parameters 1 (No.20 to 53), expansion parameters 2 (No.54 to 77) and special parameters (No.78 to 90)
according to their safety aspects and frequencies of use. In the factory setting condition, the customer can
change the basic parameter values but cannot change the expansion parameter 1,2 values and special
parameter values. When fine adjustment, e.g. gain adjustment, is required, change the parameter No.19
setting to make the expansion parameters write-enabled.
The following table lists the parameters whose values are made valid for reference/write by setting
parameter No. 19. Operation can be performed for the parameters marked .
Expansion parameters 2
Parameter No.19 Basic parameters Expansion parameters 1
Operation No.54 to No.77
setting No.0 to No.19 No.20 to No.53
special parameters (No.78 to 90)
0000 Reference
(initial value) Write
Reference No.19 only
000A
Write No.19 only
Reference
000B
Write
Reference
000C
Write
Reference
000E
Write
5- 1
5. PARAMETERS
5.1.2 List
POINT
The parameters marked * before their symbols are made valid by
switching power off once and then switching it on again after parameter
setting.
5- 2
5. PARAMETERS
Customer
Class No. Symbol Name and Function Initial value Unit
setting
20 *OP2 Function selection 2 0000
21 For manufacturer setting 0002
22 *OP4 Function selection 4 0000
23 SIC Serial communications time-out selection 0
24 FFC Feed forward gain 0 %
25 VCO Override offset 0 mV
26 TLO Torque limit offset 0 mV
27 *ENR Encoder output pulses 4000 pulse/rev
28 TL1 Internal torque limit 1 100 %
29 TL2 Internal torque limit 2 100 %
30 *BKC Backlash compensation 0 pulse
31 MO1 Analog monitor 1 offset 0 mV
32 MO2 Analog monitor 2 offset 0 mV
33 MBR Electromagnetic brake sequence output 100 ms
Expansion parameters 1
34 GD2 Ratio of load inertia moment to Servo motor inertia moment 70 0.1 times
35 PG2 Position control gain 2 35 rad/s
36 VG1 Speed control gain 1 177 rad/s
37 VG2 Speed control gain 2 817 rad/s
38 VIC Speed integral compensation 48 ms
39 VDC Speed differential compensation 980
40 0
For manufacturer setting
41 0
42 *ZPS Home position return position data 0 10STM m
43 DCT Moving distance after proximity dog 1000 10STM m
44 ZTM Stopper type home position return stopper time 100 ms
45 ZTT Stopper type home position return torque limit value 15 %
46
*LMP Software limit 0 10STM m
47
48
*LMN Software limit 0 10STM m
49
50
*LPP Position range output address 0 10STM m
51
52
*LNP Position range output address 0 10STM m
53
5- 3
5. PARAMETERS
Customer
Class No. Symbol Name and Function Initial value Unit
setting
54 For manufacturer setting 0000
55 *OP6 Function selection 6 0000
56 For manufacturer setting 0000
57 *OP8 Function selection 8 0000
58 *OP9 Function selection 9 0000
59 *OPA Function selection A 0000
60 For manufacturer setting 0000
61 NH1 Machine resonance suppression filter 1 0000
62 NH2 Machine resonance suppression filter 2 0000
Expansion parameters 2
82 020B
83 0504
84 For manufacturer setting 0002
85 0000
86 0005
87 0D04
88 0102
89 0
90 0
Note. Depends on the parameter No. 68 setting.
5- 4
5. PARAMETERS
column.
ST1 coordinate system selection
(Refer to section 4.2.2 to 4.2.4)
0: Address is incremented in CCW direction
1: Address is incremented in CW direction
Feed length multiplication factor (STM)
(Refer to section 4.2.2 to 4.2.4)
0: 1 time
1: 10 times
2: 100 times
3: 1000 times
Manual pulse generator multiplication factor
(Refer to section 4.3.2)
0: 1 time
1: 10 times
2: 100 times
Servo-on (SON) -off, forced stop (EMG) -off
follow-up for absolute value command
in incremental system or absolute value command/
incremental value command specifying system
0: Invalid
1: Valid
Normally, when this servo amplifier is used
in the absolute value command method of the
incremental system, placing it in a servo off or
forced stop status will erase the home position.
When "1" is set in this parameter, the home
position will not be erased if the servo amplifier
is placed in a servo off or forced stop status.
Operation can be resumed when servo-on (SON)
is turned on again or forced stop (EMG) is canceled.
5- 5
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
2 *OP1 Function selection 1 0002 Refer to
Used to select the input filter and absolute position detection system. Name
and
0 0
function
Input filter column.
If external input signal causes chattering due
to noise, etc., input filter is used to suppress it.
0: None
1: 0.88[ms]
2: 1.77[ms]
3: 2.66[ms]
4: 3.55[ms]
5: 4.44[ms]
Selection of absolute position detection system
(Refer to section 4.5)
0: Incremental system
1: Absolute position detection system
1 Low 15Hz
2 response 20Hz
3 25Hz
4 30Hz
5 35Hz
6 45Hz
7 55Hz
Middle
8 70Hz
response
9 85Hz
A 105Hz
B 130Hz
C 160Hz
D 200Hz
E High 240Hz
F response 300Hz
If the machine hunts or generates large gear sound,
decrease the set value.
To improve performance, e.g. shorten the settling time,
increase the set value.
Gain adjustment mode selection
(For more information, refer to section 8.1.1.)
Set value Gain adjustment mode Description
0 Interpolation mode Fixes position control gain 1
(parameter No. 6).
1 Auto tuning mode 1 Ordinary auto tuning.
2 Auto tuning mode 2 Fixes the load inertia moment
ratio set in parameter No. 34.
Response level setting can be
changed.
3 Manual mode 1 Simple manual adjustment.
4 Manual mode 2 Manual adjustment of all gains.
5- 6
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
4 *CMX Electronic gear numerator 1 0 to
Set the value of electronic gear numerator. Setting "0" automatically sets the 65535
resolution of the servo motor connected. (Refer to section 5.2.1)
5 *CDV Electronic gear denominator 1 1 to
Set the value of electronic gear denominator. (Refer to section 5.2.1) 65535
6 INP In-position range 100 m 0 to
Used to set the droop pulse range when the in-position (INP) is output. 10000
7 PG1 Position control gain 1 36 rad/s 4 to 1000
Used to set the gain of position loop 1. (Refer to chapter 8)
Increase the gain to improve tracking performance in response to the position
command.
8 *ZTY Home position return type 0010 Refer to
Used to set the home position return system, home position return direction and Name
proximity dog input polarity. and
function
0 column.
Initial Setting
Class No. Symbol Name and Function Unit
value range
16 *BPS Serial communication function selection, alarm history clear 0000 Refer to
Used to select the serial communication baud rate, select various Name
communication conditions, and clear the alarm history. and
function
column.
Serial baud rate selection
(Refer to section 15.2.2)
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
4: 4800[bps] (For MR-DP60)
Alarm history clear (Refer to section 5.2.6)
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid (reset to 0).
Serial communication standard selection
(Refer to section 15.2.2)
0: RS-232C used
1: RS-422 used
Serial communication response delay time
(Refer to section 15.2.2)
0: Invalid
Basic parameters
5- 8
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
18 *DMD Status display selection 0000 Refer to
Used to select the status display shown at power-on. (Refer to section 7.2) Name
and
function
Status display on servo amplifier display column.
at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Servo motor speed
06: Droop pulses
07: Override voltage
08: Analog torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
Basic parameters
5- 9
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
19 *BLK Parameter write inhibit 0000 Refer to
Used to select the reference and write ranges of the parameters. Name
Operation can be performed for the parameters marked . and
Expansion parameters 2 function
Basic Expansion
Set No.54 to 77 column.
Operation parameters parameters 1
value special parameters
No.0 to 19 No.20 to 53
(No. 78 to 90)
0000 Reference
Basic parameters
(initial
value) Write
Reference No.19 only
000A
Write No.19 only
Reference
000B
Write
Reference
000C
Write
(Note) Reference
000E Write
Note. Set this parameter when making device setting using the MR Configurator
(servo configuration software).
20 *OP2 Function selection 2 0000 Refer to
Used to select slight vibration suppression control. Name
and
0 0 0 function
Slight vibration suppression control selection column.
0: Invalid
1: Valid
Used to select stop processing at forward rotation stroke end (LSP), reverse Name
rotation stroke end (LSN) off. and
function
0 0 0 column.
Stopping method used when forward rotation
stroke end (LSP), reverse rotation stroke
end (LSN) device or software limit is valid
(Refer to section 5.2.5)
0: Sudden stop
1: Slow stop
5 - 10
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
24 FFC Feed forward gain 0 % 0 to 100
Set the feed forward gain. When the setting is 100%, the droop pulses during
operation at constant speed are nearly zero. However, sudden
acceleration/deceleration will increase the overshoot. As a guideline, when the
feed forward gain setting is 100%, set 1s or more as the
acceleration/deceleration time constant up to the rated speed.
25 VCO Override offset 0 mV 999 to
Used to set the offset voltage to analog override. 999
26 TLO Torque limit offset 0 mV 999 to
Used to set the offset voltage to analog torque limit (TLA). 999
27 *ENR Encoder output pulses 4000 pulse/ 1
rev to
Used to set the encoder pulses (A-phase, B-phase) output by the servo
65535
amplifier.
Set the value 4 times greater than the A-phase or B-phase pulses.
You can use parameter No. 58 to choose the output pulse setting or output
division ratio setting.
The number of A/B-phase pulses actually output is 1/4 times greater than the
preset number of pulses.
The maximum output frequency is 1.3Mpps (after multiplication by 4). Use
this parameter within this range.
For output pulse designation
Set " 0 " (initial value) in parameter No. 58.
Set the number of pulses per servo motor revolution.
Output pulse set value [pulses/rev]
Expansion parameters 1
At the setting of 5600, for example, the actually output A/B-phase pulses are
as indicated below.
5600
A B-phase output pulses 1400[pulse]
4
For output division ratio setting
Set " 1 " in parameter No. 58.
The number of pulses per servo motor revolution is divided by the set value.
Resolution per servo motor revolution
Output pulse [pulses/rev]
Set value
At the setting of 8, for example, the actually output A/B-phase pulses are as
indicated below.
131072 1
A B-phase output pulses 4096[pulse]
8 4
28 TL1 Internal torque limit 1 100 % 0 to 100
Used to limit servo motor-torque on the assumption that the maximum torque
is 100%. When 0 is set, torque is not produced.
29 TL2 Internal torque limit 2 100 % 0 to 100
Used to limit servo motor-torque on the assumption that the maximum torque
is 100%. When 0 is set, torque is not produced.
Made valid by switching on the internal torque limit selection (TL2).
30 *BKC Backlash compensation 0 pulse (Note)
Used to set the backlash compensation made when the command direction is 0
reversed. to
This function compensates for the number of backlash pulses in the opposite 1600
direction to the home position return direction. In the absolute position
detection system, this function compensates for the backlash pulse count in
the direction opposite to the operating direction at power-on.
Note. The setting range differs depending on the software version of servo
amplifiers.
Version A4 or later: 0 to 1600
Version A3 or before: 0 to 1000
5 - 11
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
31 MO1 Analog monitor 1 (MO1) offset 0 mV 999 to
Used to set the offset voltage of the analog monitor 1 (MO1) output. 999
32 MO2 Analog monitor 2 (MO2) offset 0 mV 999 to
Used to set the offset voltage of the analog monitor 2 (MO2) output. 999
33 MBR Electromagnetic brake sequence output 100 ms 0 to 1000
Used to set the delay time (Tb) between when the electromagnetic brake
interlock (MBR) switches off and when the base circuit is shut off.
(Refer to section 3.9)
34 GD2 Ratio of load inertia moment to servo motor inertia moment 70 0.1 0 to 1000
Used to set the ratio of the load inertia moment to the servo motor shaft times
inertia moment. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
35 PG2 Position control gain 2 35 rad/s 1 to 1000
Used to set the gain of the position loop. (Refer to chapter 8)
Set this parameter to increase the position response level to load disturbance.
Higher setting increases the response level but is liable to generate vibration
and/or noise.
When auto tuning is selected, the result of auto tuning is automatically set.
36 VG1 Speed control gain 1 177 rad/s 20 to
Normally this parameter value need not be changed. 8000
Higher setting increases the response level but is liable to generate vibration
and/or noise. (Refer to chapter 8)
Expansion parameters 1
When auto tuning is selected, the result of auto tuning is automatically set.
37 VG2 Speed control gain 2 817 rad/s 20 to
Set this parameter when vibration occurs on machines of low rigidity or large 20000
backlash. Higher setting increases the response level but is liable to generate
vibration and/or noise. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
38 VIC Speed integral compensation 48 ms 1 to 1000
Used to set the integral time constant of the speed loop. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
39 VDC Speed differential compensation 980 0 to 1000
Used to set the differential compensation. (Refer to chapter 8)
Made valid when the proportion control (PC) is switched on.
40 For manufacturer setting 0
41 Do not change this value by any means. 0
42 *ZPS Home position return position data 0 10STM 32768
Used to set the current position on completion of home position return. m to
(Refer to section 4.4) 32767
43 DCT Moving distance after proximity dog 1000 10STM 0 to
Used to set the moving distance after proximity dog in count type home m 65535
position return. (Refer to section 4.4.3)
44 ZTM Stopper type home position return stopper time 100 ms 5 to 1000
In stopper type home position return, used to set the time from when the
machine part is pressed against the stopper and the torque limit set in
parameter No.45 is reached to when the home position is set.
(Refer to section 4.4.5)
45 ZTT Stopper type home position return torque limit 15 % 1 to 100
Used to set the torque limit value relative to the max. torque in [%] in stopper
type home position return. (Refer to section 4.4.5)
5 - 12
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
46 *LMP Software limit 0 10STM 999999
47 Used to set the address increment side software stroke limit. The software limit m to
is made invalid if this value is the same as in "software limit ". 999999
(Refer to section 5.2.8)
Set the same sign to parameters No.46 and 47. Setting of different signs will
result in a parameter error.
Set address:
Upper 3 Lower 3
digits digits
Parameter No. 47
Parameter No. 46
Set address:
Upper 3 Lower 3
digits digits
Parameter No. 49
Parameter No. 48
5 - 13
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
54 For manufacturer setting
0000
Do not change this value by any means.
55 *OP6 Function selection 6 0000 Refer to
Used to select how to process the base circuit when reset (RES) is valid. Name
and
0 0 0 function
column.
A-phase A-phase
1
B-phase B-phase
5 - 14
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
59 *OPA Function selection A 0000 Refer to
Used to select the alarm code. Name
and
0 0 function
column.
Rotation direction in which torque limit is made valid
Setting
CCW direction CW direction
0
1
2
88888 Watchdog
AL.12 Memory error 1
AL.13 Clock error
AL.15 Memory error 2
0 0 0 AL.17 Board error 2
AL.19 Memory error 3
AL.37 Parameter error
AL.8A Serial communication time-out error
AL.8E Serial communication error
AL.30 Regenerative error
0 0 1
AL.33 Overvoltage
0 1 0 AL.10 Undervoltage
AL.45 Main circuit device overheat
AL.46 Servo motor overheat
0 1 1
AL.50 Overload 1
AL.51 Overload 2
AL.24 Main circuit
1 0 0
AL.32 Overcurrent
AL.31 Overspeed
1 0 1 AL.35 Command pulse frequency error
AL.52 Error excessive
AL.61 Home operation alarm
AL.16 Encoder error 1
AL.1A Motor combination error
1 1 0
AL.20 Encoder error 2
AL.25 Absolute position erase
Note: 0:Pin-SG off (open)
1:Pin-SG on (short)
5 - 15
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
60 For manufacturer setting 0000
Do not change this value by any means.
61 NH1 Machine resonance suppression filter 1 0000 Refer to
Used to selection the machine resonance suppression filter. Name
(Refer to section 9.1.) and
function
0 column.
Notch frequency
Same setting as in parameter No. 61
However, you need not set "00" if you have
set adaptive vibration suppression control to
be "valid" or "held".
Notch depth
Same setting as in parameter No. 61
5 - 16
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
63 LPF Low-pass filter/adaptive vibration suppression control 0000 Refer to
Used to selection the low-pass filter and adaptive vibration suppression Name
control. (Refer to chapter 9) and
function
0 column.
64 GD2B Ratio of load inertia moment to servo motor inertia moment 2 70 0.1 0 to 3000
Used to set the ratio of load inertia moment to servo motor inertia moment times
when gain changing is valid.
65 PG2B Position control gain 2 changing ratio 100 % 10 to 200
Used to set the ratio of changing the position control gain 2 when gain
changing is valid.
Made valid when auto tuning is invalid.
66 VG2B Speed control gain 2 changing ratio 100 % 10 to 200
Used to set the ratio of changing the speed control gain 2 when gain changing
is valid.
Made valid when auto tuning is invalid.
67 VICB Speed integral compensation changing ratio 100 % 50 to
Used to set the ratio of changing the speed integral compensation when gain 1000
changing is valid. Made valid when auto tuning is invalid.
5 - 17
5. PARAMETERS
Initial Setting
Class No. Symbol Name and Function Unit
value range
68 *CDP Gain changing selection 0000 Refer to
Used to select the gain changing condition. (Refer to section 9.5) Name
and
0 0 0 function
column.
82 020B
83 0504
84 0002
85 0000
86 0005
87 0D04
88 0102
89 For manufacturer setting 0
90 Do not change this value by any means. 0
5 - 18
5. PARAMETERS
CAUTION False setting will result in unexpected fast rotation, causing injury.
POINT
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
1 CMX
The range of the electronic gear setting is 1000. If you set
10 CDV
any value outside this range, a parameter error (A37) occurs.
After setting the parameter No.4, 5 value, switch power off, then on to
make that setting valid.
CMX + Deviation
Moving
The following examples are used to explain how to calculate the electronic gear value.
POINT
The following specification symbols are needed for electronic gear
calculation.
Pb : Ballscrew lead [mm(in.)]
n : Reduction ratio
Pt : Servo motor resolution [pulse/rev]
S : Travel per servo motor revolution [mm/rev]
Machine specifications
The status display item of the servo amplifier display and the display item of the external digital display
(MR-DP60) shown at power-on can be changed by changing the parameter No.18 (status display
selection) settings. In the initial condition, the servo amplifier display shows the servo motor speed and
the MR-DP60 shows the current position.
For display details, refer to section 7.2.
Parameter No. 18
5 - 20
5. PARAMETERS
Preset
speed
Servo motor
speed
0 [r/min]
Ta Tb Ts
Ta Ts Tb
The servo status can be output to two channels in terms of voltage. The servo status can be monitored
using an ammeter.
(1) Setting
Change the following digits of parameter No.17.
Parameter No. 17
0 0
Parameters No.31 and 32 can be used to set the offset voltages to the analog output voltages. The
setting range is between 999 and 999mV.
Parameter Description Setting range [mV]
Parameter No.31 Used to set the offset voltage for the analog monitor 1 (MO1) output.
999 to 999
Parameter No.32 Used to set the offset voltage for the analog monitor 2 (MO2) output.
5 - 21
5. PARAMETERS
-8[V] -10[V]
CW direction CW direction
1 Torque (Note 2) 7 Droop pulses (Note 1) CCW direction
Driving in CCW direction 10[V]
8[V]
( 10V/2048pulse)
2048[pulse]
Max. torque
0 Max. torque 0 2048[pulse]
-8[V] -10[V]
CW direction CW direction
5 Speed command CCW direction B Bus voltage
8[V]
8[V]
Max. speed
0 Max. speed
0 400[V]
-8[V]
CW direction
Note 1. Encoder pulse unit.
2. 8V is outputted at the maximum torque. However, when parameter No. 28 29 are set to limit torque, 8V is outputted at the
torque highly limited.
5 - 22
5. PARAMETERS
Encoder
Current feedback
Differ-
ential
Position feedback
Servo Motor
speed Torque
5 - 23
5. PARAMETERS
The servo amplifier is factory-set to make a sudden stop when the limit switch or software limit is made
valid. When a sudden stop is not required, e.g. when there is an allowance from the limit switch
installation position to the permissible moving range of the machine, a slow stop may be selected by
changing the parameter No.22 setting.
Parameter No. 22 setting Description
0 (initial value) Droop pulses are reset to make a stop. (Sudden stop)
1 Droop pulses are drawn out to make a slow stop. (Slow stop)
The alarm history can be confirmed by using the MR Configurator (Set-up Software) or communication
function. The servo amplifier stores one current alarm and five past alarms from when its power is
switched on first. To control alarms which will occur during operation, clear the alarm history using
parameter No.16 (alarm history clear) before starting operation. Clearing the alarm history automatically
returns to “ 0 ”.
This parameter is made valid by switching power off, then on after setting.
Parameter No. 16
Rough match (CPO) is output when the command remaining distance reaches the value set in parameter
No. 12 (rough match output range). The set remaining distance is 0 to 65535 [ 10STM m].
Command remaining distance ( 10STM m)
set in parameter No. 12
Rough match ON
(CPO) OFF
ON
In position (INP)
OFF
A limit stop using a software limit is made as in stroke end operation. When a motion goes beyond the
setting range, the motor is stopped and servo-locked. This function is made valid at power-on but made
invalid during home position return. This function is made invalid when the software limit setting is
the same as the software limit setting. A parameter error (AL. 37) will occur if the software limit
setting is less than the software limit setting.
Inhibited area
Movable area
Unmovable Movable
Current position
Software limit
5 - 24
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
Some functions of the MR Configurator (servo configuration software)
may be unavailable for some versions. For details, please contact us.
6.1 Specifications
Item Description
Communication signal Conforms to RS-232C.
Baud rate[bps] 57600, 38400, 19200, 9600
System Station selection
Batch display, high-speed display, graph display
Monitor
Minimum resolution changes with the processing speed of the personal computer.
Alarm Alarm display, alarm history, data display at alarm occurrence
I/O display, function device display, no-rotation reason display, cumulative power-on time display,
Diagnostic software number display, motor information display, tuning data display, ABS data display, shaft
name setting.
Parameters Parameter setting, list display, change list display, detailed display, turning, device setting.
Test operation Jog operation, positioning operation, motor-less operation, DO forced output, single-step feed.
Advanced function Machine analyzer, gain search, machine simulation.
Position-Data Point Tables
File operation Data read, save, print
Others Station setting, help display
(1) Components
To use this software, the following components are required in addition to the servo amplifier and
servo motor.
Model (Note 1) Description
IBM PC-AT compatible where the English version of Windows® 95, Windows® 98, Windows® Me, Windows
NT® Workstation 4.0, Windows® 2000 Professional, Windows® XP Professional or Windows® XP Home
Edition operates
Processor: Pentium® 133MHz or more (Windows® 95, Windows® 98, Windows NT® Workstation 4.0,
Windows® 2000 Professional)
(Note 2)
Pentium® 150MHz or more (Windows® Me)
Personal
Pentium® 300MHz or more (Windows® XP Professional, Windows® XP Home Edition)
computer
Memory: 16MB or more (Windows® 95), 24MB or more (Windows® 98)
32MB or more (Windows® Me, Windows NT® Workstation 4.0, Windows® 2000 Professional)
128MB or more (Windows® XP Professional, Windows® XP Home Edition)
Free hard disk space: 60MB or more
Serial port used
Windows® 95, Windows® 98, Windows® Me, Windows NT® Workstation 4.0, Windows® 2000 Professional,
OS
Windows® XP Professional, Windows® XP Home Edition (English version)
One whose resolution is 800 600 or more and that can provide a high color (16 bit) display.
Display
Connectable with the above personal computer.
Keyboard Connectable with the above personal computer.
Mouse Connectable with the above personal computer. Note that a serial mouse is not used.
Printer Connectable with the above personal computer.
Communication MR-CPCATCBL3M
cable When this cannot be used, refer to section 14.1.4 (3) and fabricate.
Note 1. Windows and Windows NT are the registered trademarks of Microsoft Corporation in the United State and other countries.
Pentium is the registered trademarks of Intel Corporation.
2. On some personal computers, this software may not run properly.
6- 1
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
To RS-232C connector
RS-232C/RS-422
converter (Note 1)
Communication cable
To RS-232C (Axis 1)
connector
Servo amplifier
(Axis 2)
Servo amplifier
(Axis 32)
Note. Refer to Section 15.1.1 for cable connections.
6- 2
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
Click “System” on the menu bar and click “Station Selection” on the menu.
When the above choices are made, the following window appears.
POINT
This setting should be the same as the station number which has been set
in the parameter in the servo amplifier used for communication.
6- 3
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.4 Parameters
Click “Parameters” on the menu bar and click “Parameter List” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
d)
e)
f)
g)
i)
h)
6- 4
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6- 5
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
Click “Position-Data” on the menu bar and click “Point Tables” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
d)
h)
e) g) f)
6- 6
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6- 7
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
When using the device setting, preset “000E” in parameter No. 19.
Click “Yes” button reads and displays the function assigned to each pin from the interface unit and
extension IO unit.
Click “No” button displays the initial status of the interface unit and extension IO unit.
Click “Cancel” button terminates the processing.
Click “Yes” button or “No” button displays the following two windows.
6- 8
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
a)
b)
d)
c)
6- 9
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
a)
b)
Move the pointer to the place of the function to be assigned. Drag and drop it as-is to the pin you
want to assign in the DIDO device setting window.
2) Quitting
Click “Close” button to exit from the window. ( b) )
6 - 10
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
a)
b)
c)
d)
e)
6 - 11
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
When confirming the machine operation in the test operation mode, use the
machine after checking that the safety mechanism such as the forced stop (EMG)
CAUTION operates.
If any operational fault has occurred, stop operation using the forced stop (EMG).
POINT
For the program operation, refer to the manual of MR Configurator.
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
When an alarm occurs, the JOG operation is automatically canceled.
Hold down the “Forward” or “Reverse” button to rotate the servo motor. Release the “Forward” or
“Reverse” button to stop.
Click “Test” on the menu bar and choose “Jog” on the menu.
When the above choices are made, the following window appears.
a)
c)
b) d)
e)
f)
6 - 12
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6 - 13
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
When an alarm occurs, the positioning operation is automatically
canceled.
Click the “Forward” or “Reverse” button to start and rotate the servo motor by the preset moving distance
and then stop.
Click “Test” on the menu bar and click “Positioning” on the menu.
When the above choices are made, the following window appears.
a)
d)
b)
e)
c)
f)
g)
6 - 14
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6 - 15
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
When this operation is used in an absolute position detection system, the
home position cannot be restored properly.
Without a servo motor being connected, the output signals are provided and the servo amplifier display
shows the status as if a servo motor is actually running in response to the external I/O signals.
The sequence of the host programmable controller can be checked without connection of a servo motor.
Click “Test” on the menu bar and click “Operation w/o Motor” on the menu.
When the above choices are made, the following window appears.
a) b)
6 - 16
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
When an alarm occurs, the DO forced output is automatically canceled.
Each servo amplifier output signal is forcibly switched on/off independently of the output condition of the
output signal.
Click “Test” on the menu bar and click “Forced Output” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
6 - 17
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
In the jog operation mode, do not rewrite data from the point table list
screen or the servo amplifier's front panel. Otherwise, the set values are
made invalid.
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
When the above choices are made, the following window appears.
a)
b)
c)
d)
6 - 18
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
Click “Alarms” on the menu bar and click “History” on the menu.
When the above choices are made, the following window appears.
6 - 19
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
MEMO
6 - 20
7. DISPLAY AND OPERATION
Use the display (5-digit, 7-segment LED) on the front panel of the servo amplifier for status display,
parameter setting, etc. Set the parameters before operation, diagnose an alarm, confirm external
sequences, and/or confirm the operation status. Press the "MODE" "UP" or "DOWN" button once to move
to the next screen. Refer to section 7.2 and later for the description of the corresponding display mode.
To refer to or set the expansion parameters 1, expansion parameters 2 and special parameters, make
them valid with parameter No.19 (parameter write disable).
button
MODE Display and setting of basic parameters.
Basic parameter
Expansion parameter 2
Section 7.6
Display and setting of expansion parameters 2.
Special parameter
7- 1
7. DISPLAY AND OPERATION
The servo status during operation is shown on the 5-digit, 7-segment LED display. Press the "UP" or
"DOWN" button to change display data as desired. When the required data is selected, the corresponding
symbol appears. Press the "SET" button to display its data. At only power-on, however, data appears after
the symbol of the status display selected in parameter No. 18 has been shown for 2[s].
The servo amplifier display shows the lower five digits of 16 data items such as the motor speed.
After choosing the status display mode with the "MODE" button, pressing the "UP" or "DOWN" button
changes the display as shown below.
To Bus voltage
Command remaining
Peak load ratio
distance
DOWN
Within one-revolution
Servo motor speed position high
Analog torque
Bus voltage
limit voltage
To Current position
7- 2
7. DISPLAY AND OPERATION
Forward rotation
at 2500r/min
Servo motor
speed
Reverse rotation
at 3000r/min
Load inertia
15.5 times
moment
11252pulse
Multi-
revolution
counter
12566pulse Lit
7- 3
7. DISPLAY AND OPERATION
The following table lists the servo statuses that may be shown.
Display range
Status display Symbol Unit Description Servo amplifier
MR-DP60
display
Current 10STM The current position from the machine home position of 0 is 99999 to 999999 to
PoS
position mm displayed. 99999 999999
Command 10STM The command position is displayed. 99999 to 999999 to
CPoS
position mm 99999 999999
Command The command remaining distance of the currently selected
10STM 99999 to 999999 to
remaining rn point table is displayed.
mm 99999 999999
distance
Point table No. PT The point table No. being executed is displayed. 0 to 31 0 to 31
Feedback pulses from the servo motor encoder are counted
Cumulative
and displayed. 99999 to 999999 to
feedback C pulse
When the value exceeds 9999999, it returns to zero. 99999 999999
pulses
Press the "SET" button to reset the display value to zero.
The servo motor speed is displayed.
Servo motor 5400 to 5400 to
r r/min " " is added to the speed of the servo motor rotating in the
speed 5400 5400
CW rotation.
The number of droop pulses in the deviation counter is
displayed.
99999 to 999999 to
Droop pulses E pulse " " is added to the droop pulses in the CW rotation.
99999 999999
The displayed number of pulses is not yet multiplied by the
electronic gear value.
The override setting is displayed.
Override F % 0 to 200 0 to 200
100% is displayed when override is invalid.
Analog torque The voltage of the Analog torque limit (TLA) is displayed.
u V 0.00 to 10.00 0.00 to 10.00
limit voltage
Regenerative The ratio of regenerative power to permissible regenerative
L % 0 to 100 0 to 100
load ratio power is displayed in %.
The continuous effective load torque is displayed.
Effective load
J % The effective value in the past 15 seconds is displayed 0 to 300 0 to 300
ratio
relative to the rated torque of 100%.
The maximum torque generated during
acceleration/deceleration, etc.
Peak load ratio b % 0 to 300 0 to 300
The highest value in the past 15 seconds is displayed
relative to the rated torque of 100%.
Torque that occurred instantaneously is displayed.
Instantaneous
T % The value of the torque that occurred is displayed in real 0 to 400 0 to 400
torque
time relative to the rate torque of 100%.
Position within one revolution is displayed in encoder
Within one- pulses.
revolution Cy1 pulse The value returns to 0 when it exceeds the maximum 0 to 99999
position low number of pulses.
The value is incremented in the CCW direction of rotation. (Note)
The within one-revolution position is displayed in 100 pulse 0 to 131071
Within one- increments of the encoder.
100
revolution Cy2 The value returns to 0 when it exceeds the maximum 0 to 1310
pulse
position high number of pulses.
The value is incremented in the CCW direction of rotation.
Travel value from the home position in the absolute position
32768 to 32768 to
ABS counter LS rev detection systems is displayed in terms of the absolute
32767 32767
position detectors counter value.
Load inertia The estimated ratio of the load inertia moment to the servo
dC times 0.0 to 300.0 0.0 to 300.0
moment ratio motor shaft inertia moment is displayed.
The voltage (across P-N) of the main circuit converter is
Bus voltage Pn V 0 to 450 0 to 450
displayed.
Note. The MR-DP60 can display the status without dividing it into the high and low orders. The unit is [pulse].
7- 4
7. DISPLAY AND OPERATION
After choosing the diagnosis mode with the "MODE" button, pressing the "UP" or "DOWN" button changes
the display as shown below.
To Teaching
DOWN
Test operation mode
Motor type ID
Positioning operation
To Sequence
7- 5
7. DISPLAY AND OPERATION
7- 6
7. DISPLAY AND OPERATION
7- 7
7. DISPLAY AND OPERATION
The current alarm, past alarm history and parameter error are displayed. The lower 2 digits on the
display indicate the alarm number that has occurred or the parameter number in error. Display examples
are shown below.
After choosing the alarm mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the
display as shown below.
To Parameter error No.
Alarm history
Current alarm
(Fourth alarm in past)
UP
Alarm history
(Third alarm in past) Parameter error No.
To Current alarm
7- 8
7. DISPLAY AND OPERATION
Current alarm
Indicates the occurrence of overvoltage (AL.33).
Flickers at occurrence of the alarm.
Alarm history
Indicates that the fourth alarm in the past is overspeed (AL.31).
7- 9
7. DISPLAY AND OPERATION
7 - 10
7. DISPLAY AND OPERATION
You can set the target position, servo motor speed, acceleration time, deceleration time, dwell and auxiliary
function.
After choosing the point table mode with the "MODE" button, pressing the "UP" or "DOWN" button
changes the display as shown below.
UP
DOWN
7 - 11
7. DISPLAY AND OPERATION
Press "SET" in the point table mode. The following screen appears.
Press "UP" or "DOWN" to move to the next screen.
Target position
UP
Dwell
Auxiliary function
7 - 12
7. DISPLAY AND OPERATION
Press UP once.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
Press "UP" or "DOWN" after completion of the setting to return to the setting item screen. Further,
press "UP" and "DOWN" together to return to the point table No. display screen.
7 - 13
7. DISPLAY AND OPERATION
Press MODE three times. Press UP or DOWN to choose point table No. 1.
Press UP or DOWN to
change the setting.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
Press "UP" or "DOWN" after completion of the setting to return to the setting item screen. Further,
press "UP" and "DOWN" together to return to the point table No. display screen.
7 - 14
7. DISPLAY AND OPERATION
POINT
To use the expansion parameters, change the parameter No. 19 (parameter
write inhibit) value. (Refer to section 5.1.1)
After choosing the corresponding parameter mode with the "MODE" button, pressing the "UP" or "DOWN"
button changes the display as shown below.
To status display mode
MODE
UP
DOWN
The parameter whose abbreviation is marked * is made valid by switching power off, then on after
changing its setting. (Refer to section 5.1.2)
7 - 15
7. DISPLAY AND OPERATION
Press UP twice.
Use UP or DOWN .
( 2: Data setting type)
7 - 16
7. DISPLAY AND OPERATION
Press MODE three times. Press UP or DOWN to choose parameter No. 42.
Press UP or DOWN to
change the setting.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
When changing the parameter No. 42 setting, change its set value, then switch power off once and
switch it on again to make the new value valid.
7 - 17
7. DISPLAY AND OPERATION
The ON/OFF states of the digital I/O signals connected to the servo amplifier can be confirmed.
(1) Operation
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP once.
Input signals
Always lit
Output signals
Lit: ON
Extinguished: OFF
7 - 18
7. DISPLAY AND OPERATION
POINT
When the servo system is used in a vertical lift application, turning on the
electromagnetic brake interlock (MBR) after assigning it to pin CN1B-19
will release the electromagnetic brake, causing a drop. Take drop
preventive measures on the machine side.
The output signal can be forced on/off independently of the servo status. This function is used for output
signal wiring check, etc. This operation must be performed in the servo off state (SON off).
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP twice.
Press UP once.
7 - 19
7. DISPLAY AND OPERATION
The test operation mode is designed to confirm servo operation and not to confirm
machine operation. In this mode, do not use the servo motor with the machine.
CAUTION Always use the servo motor alone.
If any operational fault has occurred, stop operation using the forced stop (EMG) .
POINT
The test operation mode cannot be used in the absolute position detection
system. Use it after choosing "Incremental system" in parameter No. 1.
The MR Configurator (servo configuration software) is required to perform
positioning operation.
Test operation cannot be performed if the servo-on (SON) signal is not
turned OFF.
Call the display screen shown after power-on. Choose jog operation/motor-less operation in the following
procedure. Using the "MODE" button, show the diagnostic screen.
Press SET for more Press SET for more than 2s.
than 2s.
When this screen When this screen is displayed,
appears, jog feed can motor-less operation can be
be performed. performed.
Flickers in the test operation mode.
7 - 20
7. DISPLAY AND OPERATION
Jog operation can be performed when there is no command from the external command device.
(1) Operation
Connect EMG-SG to start jog operation and connect VDD-COM to use the internal power supply.
Hold down the "UP" or "DOWN" button to run the servo motor. Release it to stop. When using the MR
Configurator (servo configuration software), you can change the operation conditions. The initial
conditions and setting ranges for operation are listed below.
Item Initial setting Setting range
Speed [r/min] 200 0 to instantaneous permissible speed
Acceleration/deceleration time constant [ms] 1000 0 to 50000
If the communication cable is disconnected during jog operation performed by using the MR
Configurator (servo configuration software), the servo motor will be decelerated to a stop.
7 - 21
7. DISPLAY AND OPERATION
POINT
The MR Configurator (servo configuration software) is required to perform
positioning operation.
Positioning operation can be performed once when there is no command from the external command
device.
(1) Operation
Connect EMG-SG to start positioning operation and connect VDD-COM to use the internal power
supply.
Pressing the "Forward" or "Reverse" button on the MR Configurator (servo configuration software)
starts the servo motor, which will then stop after moving the preset travel distance. You can change
the operation conditions on the MR Configurator (servo configuration software). The initial conditions
and setting ranges for operation are listed below.
Item Initial setting Setting range
Travel distance [pulse] 10000 0 to 9999999
Speed [r/min] 200 0 to instantaneous permissible speed
Acceleration/deceleration time constant [ms] 1000 0 to 50000
If the communication cable is disconnected during positioning operation, the servo motor will come to
a sudden stop.
7 - 22
7. DISPLAY AND OPERATION
Without connecting the servo motor, you can provide output signals or monitor the status display as if the
servo motor is running in response to external input signals. This operation can be used to check the
sequence of a host programmable controller or the like.
(1) Operation
After turning off the signal across SON-SG, choose motor-less operation. After that, perform external
operation as in ordinary operation.
7 - 23
7. DISPLAY AND OPERATION
POINT
This function is available for the absolute value command system. It is not
available for the incremental value command system.
This function is enabled after a home position return.
After making sure that the servo motor has stopped, press the "SET"
button in the operation section or turn teach (TCH) ON and set the
position data.
Position data can be imported by pressing the "SET" button in the operation section or turning teach
(TCH) ON after moving the axis to the target position by JOG operation or manual pulse generator
operation.
Press UP or DOWN to call the point table No. where position data will be set.
7 - 24
7. DISPLAY AND OPERATION
When the preparations for teaching are over, set position data in the following procedure.
When the setting is completed correctly, the upper digits in the display section flicker as shown below.
Press the "MODE" button on the flickering screen to return to the teaching initial screen.
7 - 25
7. DISPLAY AND OPERATION
MEMO
7 - 26
8. GENERAL GAIN ADJUSTMENT
The gain adjustment in this section can be made on a single servo amplifier. For gain adjustment, first
execute auto tuning mode 1. If you are not satisfied with the results, execute auto tuning mode 2, manual
mode 1 and manual mode 2 in this order.
8- 1
8. GENERAL GAIN ADJUSTMENT
Yes
OK?
This mode permits
No adjustment easily with three
Manual mode 1 gains if you were not satisfied
with auto tuning results.
Operation
Yes
OK?
You can adjust all gains
No
manually when you want to
Manual mode 2 do fast settling or the like.
END
8- 2
8. GENERAL GAIN ADJUSTMENT
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load
inertia moment ratio) in real time and automatically sets the optimum gains according to that value. This
function permits ease of gain adjustment of the servo amplifier.
POINT
The auto tuning mode 1 may not be performed properly if the following
conditions are not satisfied.
Time to reach 2000r/min is the acceleration/deceleration time constant of
5s or less.
Speed is 150r/min or higher.
The ratio of load inertia moment to motor inertia moment is not more than
100 times.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque
during acceleration/deceleration or on a machine which is extremely loose,
auto tuning may not function properly, either. In such cases, use the auto
tuning mode 2 or manual mode 1,2 to make gain adjustment.
8- 3
8. GENERAL GAIN ADJUSTMENT
Load inertia
Automatic setting moment
Encoder
Command Control gains Current Servo
PG1,VG1 control motor
PG2,VG2,VIC
Current feedback
First digit
Third digit Response level setting
Auto tuning selection
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always
estimates the load inertia moment ratio from the current and speed of the servo motor. The results of
estimation are written to parameter No. 34 (load inertia moment ratio). These results can be confirmed on
the status display screen of the servo amplifier display section.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly,
chose the "auto tuning mode 2" (parameter No.3 : 2 ) to stop the estimation of the load inertia
moment ratio (Switch in above diagram turned off), and set the load inertia moment ratio (parameter No.
34) manually.
From the preset load inertia moment ratio (parameter No. 34) value and response level (The first digit of
parameter No. 3), the optimum control gains are automatically set on the basis of the internal gain tale.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since power-
on. At power-on, auto tuning is performed with the value of each control gain saved in the EEP-ROM
being used as an initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of
the inertia moment ratio may malfunction temporarily. In such a case,
choose the "auto tuning mode 2" (parameter No. 3: 2 ) and set the
correct load inertia moment ratio in parameter No. 34.
When any of the auto tuning mode 1, auto tuning mode 2 and manual mode
1 settings is changed to the manual mode 2 setting, the current control
gains and load inertia moment ratio estimation value are saved in the EEP-
ROM.
8- 4
8. GENERAL GAIN ADJUSTMENT
Since auto tuning is made valid before shipment from the factory, simply running the servo motor
automatically sets the optimum gains that match the machine. Merely changing the response level
setting value as required completes the adjustment. The adjustment procedure is as follows.
Acceleration/deceleration repeated
No
Auto tuning
conditions not satisfied. No
(Estimation of load inertia
moment ratio is difficult)
Yes
Choose the auto tuning mode 2
(parameter No.3 : 2 ) and set
the load inertia moment ratio
(parameter No.34) manually.
Acceleration/deceleration repeated
Requested No
performance satisfied?
Yes
END
To manual mode
8- 5
8. GENERAL GAIN ADJUSTMENT
Set the response (The first digit of parameter No.3) of the whole servo system. As the response level
setting is increased, the track ability and settling time for a command decreases, but a too high response
level will generate vibration. Hence, make setting until desired response is obtained within the vibration-
free range.
If the response level setting cannot be increased up to the desired response because of machine resonance
beyond 100Hz, adaptive vibration suppression control (parameter No. 63) or machine resonance
suppression filter (parameter No. 61 62) may be used to suppress machine resonance. Suppressing
machine resonance may allow the response level setting to increase. Refer to section 9.3 for adaptive
vibration suppression control and section 9.2 for machine resonance suppression filter.
Parameter No. 3
Machine characteristic
Response level setting Machine resonance
Machine rigidity Guideline of corresponding machine
frequency guideline
1 Low 15Hz
2 20Hz
3 25Hz
Large conveyor
4 30Hz
5 35Hz
6 45Hz Arm robot
7 55Hz
General machine
8 Middle 70Hz
tool conveyor
9 85Hz Precision
A 105Hz working
machine
B 130Hz
Inserter
C 160Hz
Mounter
D 200Hz Bonder
E 240Hz
F High 300Hz
8- 6
8. GENERAL GAIN ADJUSTMENT
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with
three parameters.
In this mode, setting the three gains of position control gain 1 (PG1), speed control gain 2 (VG2) and
speed integral compensation (VIC) automatically sets the other gains to the optimum values according to
these gains.
GD2
User setting
PG1
PG2
VG2
Automatic setting VG1
VIC
Therefore, you can adjust the model adaptive control system in the same image as the general PI control
system (position gain, speed gain, speed integral time constant). Here, the position gain corresponds to
PG1, the speed gain to VG2 and the speed integral time constant to VIC. When making gain adjustment
in this mode, set the load inertia moment ratio (parameter No. 34) correctly.
POINT
If machine resonance occurs, adaptive vibration suppression control
(parameter No. 63) or machine resonance suppression filter (parameter No.
61 62) may be used to suppress machine resonance. (Refer to section 9.2,
9.3.)
8- 7
8. GENERAL GAIN ADJUSTMENT
8- 8
8. GENERAL GAIN ADJUSTMENT
Position control
gain 1 guideline
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
( 13 to 15 )
2) Speed control gain 2 (VG2: parameter No. 37)
This parameter determines the response level of the speed control loop. Increasing this value
enhances response but a too high value will make the mechanical system liable to vibrate. The
actual response frequency of the speed loop is as indicated in the following expression.
Speed loop response Speed control gain 2 setting
frequency(Hz) (1 ratio of load inertia moment to servo motor inertia moment) 2
8- 9
8. GENERAL GAIN ADJUSTMENT
The interpolation mode is used to match the position control gains of the axes when performing the
interpolation operation of servo motors of two or more axes for an X-Y table or the like. In this mode, the
position control gain 2 and speed control gain 2 which determine command track ability are set manually
and the other parameter for gain adjustment are set automatically.
(1) Parameter
(a) Automatically adjusted parameters
The following parameters are automatically adjusted by auto tuning.
Parameter No. Abbreviation Name
34 GD2 Ratio of load inertia moment to servo motor inertia moment
35 PG2 Position control gain 2
37 VG2 Speed control gain 2
38 VIC Speed integral compensation
To meet higher response demands, the MELSERVO-J2-Super series has been changed in response level
setting range from the MELSERVO-J2 series. The following table lists comparison of the response level
setting.
Parameter No. 3
Note that because of a slight difference in gain adjustment pattern, response may not be the same if the
resonance frequency is set to the same value.
The MELSERVO-J2-Super series has an addition of the load inertia moment ratio fixing mode. It also has
the addition of the manual mode 1 which permits manual adjustment with three parameters.
Parameter No. 3
8 - 11
8. GENERAL GAIN ADJUSTMENT
MEMO
8 - 12
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used generally. Use them
if you are not satisfied with the machine status after making adjustment
in the methods in chapter 8.
If a mechanical system has a natural resonance point, increasing the servo system response may cause
the mechanical system to produce resonance (vibration or unusual noise) at that resonance frequency.
Using the machine resonance suppression filter and adaptive vibration suppression control functions can
suppress the resonance of the mechanical system.
Adaptive vibration
suppression control 1 or 2
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of
the specific frequency to suppress the resonance of the mechanical system. You can set the gain
decreasing frequency (notch frequency) and gain decreasing depth.
Notch
depth
Frequency
Notch frequency
9- 1
9. SPECIAL ADJUSTMENT FUNCTIONS
You can use the machine resonance suppression filter 1 (parameter No. 61) and machine resonance
suppression filter 2 (parameter No. 62) to suppress the vibration of two resonance frequencies. Note
that if adaptive vibration suppression control is made valid, the machine resonance suppression filter
1 (parameter No. 61) is made invalid.
Machine resonance point
Mechanical
system
response
Frequency
Notch
depth
Frequency
Parameter No. 61 Parameter No. 62
POINT
The machine resonance suppression filter is a delay factor for the servo
system. Hence, vibration may increase if you set a wrong resonance
frequency or a too deep notch.
(2) Parameters
(a) Machine resonance suppression filter 1 (parameter No. 61)
Set the notch frequency and notch depth of the machine resonance suppression filter 1 (parameter
No. 61)
When you have made adaptive vibration suppression control selection (parameter No. 63) "valid" or
"held", make the machine resonance suppression filter 1 invalid (parameter No. 61: 0000).
Parameter No. 61
0
Notch frequency
Setting Setting Setting Setting
Frequency Frequency Frequency Frequency
value value value value
00 Invalid 08 562.5 10 281.3 18 187.5
01 4500 09 500 11 264.7 19 180
02 2250 0A 450 12 250 1A 173.1
03 1500 0B 409.1 13 236.8 1B 166.7
04 1125 0C 375 14 225 1C 160.1
05 900 0D 346.2 15 214.3 1D 155.2
06 750 0E 321.4 16 204.5 1E 150
07 642.9 0F 300 17 195.7 1F 145.2
Notch depth
Setting
value Depth (Gain)
0 Deep ( 40dB)
1 ( 14dB)
2 ( 8dB)
3 Shallow( 4dB)
9- 2
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
If the frequency of machine resonance is unknown, decrease the notch
frequency from higher to lower ones in order. The optimum notch
frequency is set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine
analyzer on the MR Configurator (servo configuration software). This
allows the required notch frequency and depth to be determined.
Resonance may occur if parameter No. 61 62 is used to select a close
notch frequency and set a deep notch.
(1) Function
Adaptive vibration suppression control is a function in which the servo amplifier detects machine
resonance and sets the filter characteristics automatically to suppress mechanical system vibration.
Since the filter characteristics (frequency, depth) are set automatically, you need not be conscious of
the resonance frequency of a mechanical system. Also, while adaptive vibration suppression control is
valid, the servo amplifier always detects machine resonance, and if the resonance frequency changes,
it changes the filter characteristics in response to that frequency.
Machine resonance point Machine resonance point
Mechanical Mechanical
system system
response response
Frequency Frequency
Notch Notch
depth depth
Frequency Frequency
Notch frequency Notch frequency
When machine resonance is large and frequency is low When machine resonance is small and frequency is high
POINT
The machine resonance frequency which adaptive vibration suppression
control can respond to is about 150 to 500Hz. Adaptive vibration
suppression control has no effect on the resonance frequency outside this
range. Use the machine resonance suppression filter for the machine
resonance of such frequency.
Adaptive vibration suppression control may provide no effect on a
mechanical system which has complex resonance characteristics or which
has too large resonance.
Under operating conditions in which sudden disturbance torque is imposed
during operation, the detection of the resonance frequency may malfunction
temporarily, causing machine vibration. In such a case, set adaptive
vibration suppression control to be "held" (parameter No. 63: 2 ) to fix
the characteristics of the adaptive vibration suppression control filter.
9- 3
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
The operation of adaptive vibration suppression control selection (parameter No.63).
Parameter No. 63
POINT
Adaptive vibration suppression control is factory-set to be invalid
(parameter No. 63: 0000).
The filter characteristics generated are saved in the EEP-ROM every 60
minutes since power-on. At next power-on, vibration suppression control is
performed with this data saved in the EEP-ROM being used as an initial
value.
Setting the adaptive vibration suppression control sensitivity can change
the sensitivity of detecting machine resonance. Setting of "large sensitivity"
detects smaller machine resonance and generates a filter to suppress
machine vibration. However, since a phase delay will also increase, the
response of the servo system may not increase.
(1) Function
When a ballscrew or the like is used, resonance of high frequency may occur as the response of the
servo system is increased. To prevent this, the low-pass filter is factory-set to be valid for a torque
command. The filter frequency of this low-pass filter is automatically adjusted to the value in the
following expression.
Speed control gain 2 setting 10
Filter frequency(Hz)
2 (1 Ratio of load inertia moment to servo motor inertia moment setting 0.1)
(2) Parameter
Set the operation of the low-pass filter (parameter No. 63.)
Parameter No. 63
POINT
In a mechanical system where rigidity is extremely high and resonance is
difficult to occur, setting the low-pass filter to be "invalid" may increase
the servo system response to shorten the settling time.
9- 4
9. SPECIAL ADJUSTMENT FUNCTIONS
This function can change the gains. You can change between gains during rotation and gains during stop
or can use an external signal to change gains during operation.
9.5.1 Applications
The valid control gains PG2, VG2, VIC and GD2 of the actual loop are changed according to the conditions
selected by gain changing selection CDP (parameter No. 68) and gain changing condition CDS (parameter
No. 69).
CDP
Parameter No.68
External signal
CDP
Command pulse
frequency
Droop pulses
Changing
Model speed
Comparator
CDS
Parameter No.69
GD2
Parameter No.34
Valid
GD2 GD2 value
Parameter No.64
PG2
Parameter No.35
Valid
PG2 PG2B PG2 value
100
VG2
Parameter No.37
Valid
VG2 VG2B VG2 value
100
VIC
Parameter No.38
Valid
VIC VICB VIC value
100
9- 5
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.3 Parameters
When using the gain changing function, always set " 4 " in parameter No.3 (auto tuning) to choose
the manual mode of the gain adjustment modes. The gain changing function cannot be used in the auto
tuning mode.
Parameter Abbrev-
Name Unit Description
No. iation
7 PG1 Position control gain 1 rad/s Position and speed gains of a model used to set the response
36 VG1 Speed control gain 1 rad/s level to a command. Always valid.
Ratio of load inertia moment to 0.1 Control parameters before changing
34 GD2
servo motor inertia moment times
35 PG2 Position control gain 2 rad/s
37 VG2 Speed control gain 2 rad/s
38 VIC Speed integral compensation ms
Ratio of load inertia moment to 0.1 Used to set the ratio of load inertia moment to servo motor
64 GD2B
servo motor inertia moment 2 times inertia moment after changing.
Position control gain 2 changing Used to set the ratio (%) of the after-changing position
65 PG2B %
ratio control gain 2 to position control gain 2.
Speed control gain 2 changing Used to set the ratio (%) of the after-changing speed control
66 VG2B %
ratio gain 2 to speed control gain 2.
Speed integral compensation Used to set the ratio (%) of the after-changing speed integral
67 VICB %
changing ratio compensation to speed integral compensation.
68 CDP Gain changing selection Used to select the changing condition.
kpps Used to set the changing condition values.
69 CDS Gain changing condition pulse
r/min
You can set the filter time constant for a gain change at
70 CDT Gain changing time constant ms
changing.
9- 6
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) Ratio of load inertia moment to servo motor inertia moment 2 (GD2B: parameter No. 64)
Set the ratio of load inertia moment to servo motor inertia moment after changing. If the load inertia
moment ratio does not change, set it to the same value as ratio of load inertia moment to servo motor
inertia moment (parameter No. 34).
(3) Position control gain 2 changing ratio (parameter No. 65), speed control gain 2 changing ratio (parameter
No. 66), speed integral compensation changing ratio (parameter No. 67)
Set the values of after-changing position control gain 2, speed control gain 2 and speed integral
compensation in ratio (%). 100% setting means no gain change.
For example, at the setting of position control gain 2 100, speed control gain 2 2000, speed integral
compensation 20 and position control gain 2 changing ratio 180%, speed control gain 2 changing
ratio 150% and speed integral compensation changing ratio 80%, the after-changing values are as
follows.
Position control gain 2 Position control gain 2 Position control gain 2 changing ratio /100 180rad/s
Speed control gain 2 Speed control gain 2 Speed control gain 2 changing ratio /100 3000rad/s
Speed integral compensation Speed integral compensation Speed integral compensation changing
ratio /100 16ms
9- 8
9. SPECIAL ADJUSTMENT FUNCTIONS
CDS
Droop pulses [pulses] 0
CDS
After-changing gain
Before-changing gain
Change of each gain
CDT 100ms
9- 9
9. SPECIAL ADJUSTMENT FUNCTIONS
MEMO
9 - 10
10. INSPECTION
10. INSPECTION
Before starting maintenance and/or inspection, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between P and N is safe with a voltage tester and others. Otherwise, an electric
shock may occur. In addition, always confirm from the front of the servo amplifier
WARNING whether the charge lamp is off or not.
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement,
contact your safes representative.
POINT
Do not test the servo amplifier with a megger (measure insulation
resistance), or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
(1) Inspection
It is recommended to make the following checks periodically.
(a) Check for loose terminal block screws. Retighten any loose screws.
(b) Check the cables and the like for scratches and cracks. Perform periodic inspection according to
operating conditions.
(2) Life
The following parts must be changed periodically as listed below. If any part is found faulty, it must be
changed immediately even when it has not yet reached the end of its life, which depends on the
operating method and environmental conditions. For parts replacement, please contact your sales
representative.
(b) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of
their life when the cumulative number of power-on and forced stop times is 100,000, which depends
on the power supply capacity.
10 - 1
10. INSPECTION
MEMO
10 - 2
11. TROUBLESHOOTING
11. TROUBLESHOOTING
POINT
Using the MR Configurator (servo configuration software), you can refer to
unrotated servo motor reasons, etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No. Start-up sequence Fault Investigation Possible cause Reference
1 Power on LED is not lit. Not improved if connectors 1. Power supply voltage fault
LED flickers. CN1A, CN1B, CN2 and CN3 2. Servo amplifier is faulty.
are disconnected.
Improved when connectors Power supply of CN1 cabling is
CN1A and CN1B are shorted.
disconnected.
Improved when connector 1. Power supply of encoder
CN2 is disconnected. cabling is shorted.
2. Encoder is faulty.
Improved when connector Power supply of CN3 cabling is
CN3 is disconnected. shorted.
Alarm occurs. Refer to section 11.2 and remove cause. Section 11.2
2 Switch on servo-on Alarm occurs. Refer to section 11.2 and remove cause. Section 11.2
signal. Servo motor shaft is 1. Check the display to see if 1. Servo-on signal is not input. Section 7.3.2
not servo-locked the servo amplifier is (Wiring mistake)
(is free). ready to operate. 2. 24VDC power is not
2. Check the external I/O supplied to COM.
signal indication to see if
the servo-on (SON) signal
is ON.
3 Gain adjustment Rotation ripples Make gain adjustment in the Gain adjustment fault Chapter 7
(speed fluctuations) following procedure.
are large at low 1. Increase the auto tuning
speed. response level.
2. Repeat acceleration and
deceleration several times
to complete auto tuning.
Large load inertia If the servo motor may be Gain adjustment fault Chapter 7
moment causes the run with safety, repeat
servo motor shaft to acceleration and
oscillate side to side. deceleration several times to
complete auto tuning.
4 Cyclic operation Position shift occurs Confirm the cumulative Pulse counting error, etc.
command pulses, cumulative due to noise.
feedback pulses and actual
servo motor position.
11 - 1
11. TROUBLESHOOTING
POINT
Configure up a circuit which will detect the trouble (ALM) signal and turn
off the servo-on (SON) signal at occurrence of an alarm.
AL.31 1 0 1 Overspeed
AL.32 1 0 0 Overcurrent
AL.33 0 0 1 Overvoltage
AL.35 1 0 1 Command pulse frequency error
AL.37 0 0 0 Parameter error
AL.45 0 1 1 Main circuit device overheat (Note 1) (Note 1) (Note 1)
AL.46 0 1 1 Servo motor overheat (Note 1) (Note 1) (Note 1)
AL.50 0 1 1 Overload 1 (Note 1) (Note 1) (Note 1)
AL.51 0 1 1 Overload 2 (Note 1) (Note 1) (Note 1)
AL.52 1 0 1 Error excessive
AL.61 1 0 1 Home operation alarm
AL.8A 0 0 0 Serial communication time-out error
AL.8E 0 0 0 Serial communication error
88888 0 0 0 Watchdog
AL.90 Home position return incomplete
AL.92 Open battery cable warning
AL.96 Home position setting warning
AL.98 Software limit warning
Warnings
11 - 2
11. TROUBLESHOOTING
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
CAUTION If an absolute position erase alarm (AL.25) occurred, always make home position
setting again. Otherwise, misoperation may occur.
POINT
When any of the following alarms has occurred, always remove its cause
and allow about 30 minutes for cooling before resuming operation. If
operation is resumed by switching control circuit power off, then on to reset
the alarm, the servo amplifier and servo motor may become faulty.
Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)
The alarm can be deactivated by switching power off, then on press the
"SET" button on the current alarm screen or by turning on the reset (RES).
For details, refer to section 11.2.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic is operated to stop the servo
motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The
optional MR Configurator (servo configuration software) may be used to refer to the cause.
Display Name Definition Cause Action
AL.10 Undervoltage Power supply 1. Power supply voltage is low. Review the power supply.
voltage dropped. 2. There was an instantaneous
MR-J2S- CP: control power failure of 60ms or
160VAC or less longer.
MR-J2S- CP1: 3. Shortage of power supply capacity
83VAC or less caused the power supply voltage to
drop at start, etc.
4. The bus voltage dropped to the
folllowing value or less.
MR-J2S- CP: 200VDC
MR-J2S- CP1: 158VDC
5. Faulty parts in the servo amplifier Change the servo amplifier.
Checking method
Alarm (AL.10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
AL.12 Memory error 1 RAM, memory fault Faulty parts in the servo amplifier Change the servo amplifier.
Checking method
AL.13 Clock error Printed board fault
Alarm (any of AL.12 and 13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
AL.15 Memory error 2 EEP-ROM fault 1. Faulty parts in the servo amplifier Change the servo amplifier.
Checking method
Alarm (AL.15)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
2. The number of write times to EEP-
ROM exceeded 100,000.
AL.16 Encoder error 1 Communication 1. Encode connector (CN2) Connect correctly.
error occurred disconnected.
between encoder 2. Encoder fault Change the servo motor.
and servo amplifier. 3. Encoder cable faulty Repair or change the cable.
(wire breakage or short)
11 - 3
11. TROUBLESHOOTING
The output terminals 2. The wiring of U, V, W is Correctly connect the output terminals U,
U, V, W of the servo disconnected or not connected. V, W of the servo amplifier and the input
amplifier and the terminals U, V, W of the servo motor.
input terminals U, V,
W of the servo motor
are not connected.
AL.19 Memory error 3 ROM memory fault Faulty parts in the servo amplifier. Change the servo amplifier.
Checking method
Alarm (AL.19) occurs if power is
switched on after disconnection
of all cable but the control circuit
power supply cable.
AL.1A Motor Wrong combination Wrong combination of servo amplifier Use correct combination.
combination of servo amplifier and servo motor connected.
error and servo motor.
AL.20 Encoder error 2 Communication 1. Encoder connector (CN2) Connect correctly.
error occurred disconnected.
between encoder and 2. Encoder fault Change the servo motor.
servo amplifier. 3. Encoder cable faulty Repair or change the cable.
(wire breakage or shorted)
Encoder detected 4. Excessive acceleration is occurred 1. Decrease the speed control gain 2.
acceleration error. due to oscillation and others. 2. Decrease the auto tuning response level.
AL.24 Main circuit Ground fault 1. Power input wires and servo motor Connect correctly.
error occurred at the servo output wires are in contact at main
motor outputs (U,V circuit terminal block (TE1).
and W phases) of the 2. Sheathes of servo motor power Change the cable.
servo amplifier. cables deteriorated, resulting in
ground fault.
3. Main circuit of servo amplifier Change the servo amplifier.
failed.
Checking method
AL.24 occurs if the servo is
switched on after disconnecting
the U, V, W power cables from
the servo amplifier.
AL.25 Absolute Absolute position 1. Reduced voltage of super capacitor After leaving the alarm occurring for a few
position erase data in error in encoder minutes, switch power off, then on again.
Always make home position setting again.
2. Battery voltage low Change battery.
3. Battery cable or battery is faulty. Always make home position setting again.
Power was switched 4. Super capacitor of the absolute After leaving the alarm occurring for a few
on for the first time position encoder is not charged minutes, switch power off, then on again.
in the absolute Always make home position setting again.
position detection
system.
11 - 4
11. TROUBLESHOOTING
AL.31 Overspeed Speed has exceeded 1. Input command pulse frequency Set command pulses correctly.
the instantaneous exceeded the permissible
permissible speed. instantaneous speed frequency.
2. Small acceleration/deceleration Increase acceleration/deceleration time
time constant caused overshoot to constant.
be large.
3. Servo system is instable to cause 1. Re-set servo gain to proper value.
overshoot. 2. If servo gain cannot be set to proper
value.
1) Reduce load inertia moment ratio; or
2) Reexamine acceleration/
deceleration time constant.
4. Electronic gear ratio is large Set correctly.
(parameters No. 4, 5)
5. Encoder faulty. Change the servo motor.
11 - 5
11. TROUBLESHOOTING
11 - 6
11. TROUBLESHOOTING
11 - 7
11. TROUBLESHOOTING
AL.52 Error excessive The difference 1. Acceleration/deceleration time Increase the acceleration/deceleration
between the model constant is too small. time constant.
position and the 2. Internal torque limit 1 (parameter Increase the torque limit value.
actual servo motor No.28) is too small.
position exceeds 2.5 3. Motor cannot be started due to 1. Review the power supply capacity.
rotations. (Refer to torque shortage caused by power 2. Use servo motor which provides larger
the function block supply voltage drop. output.
diagram in section 4. Position control gain 1 (parameter Increase set value and adjust to ensure
1.1.1) No.7) value is small. proper operation.
5. Servo motor shaft was rotated by 1. When torque is limited, increase the
external force. limit value.
2. Reduce load.
3. Use servo motor that provides larger
output.
6. Machine struck something. 1. Review operation pattern.
2. Install limit switches.
7. Encoder faulty Change the servo motor.
8. Wrong connection of servo motor. Connect correctly.
Servo amplifier's output terminals
U, V, W do not match servo motor's
input terminals U, V, W.
AL.61 Operation "1" or more has been Setting mistake of auxiliary function Set "0" to auxiliary function of point table
alarm set to auxiliary of point table No. 31. No. 31.
function of point
table No. 31.
AL.8A Serial RS-232C or RS-422 1. Communication cable breakage. Repair or change communication cable
communication communication 2. Communication cycle longer than Set correct value in parameter.
time-out error stopped for longer parameter No. 23 setting.
than the time set in 3. Wrong protocol. Correct protocol.
parameter No.23.
AL.8E Serial Serial 1. Communication cable fault Repair or change the cable.
communication communication (Open cable or short circuit)
error error occurred
between servo 2. Communication device (e.g. Change the communication device (e.g.
amplifier and personal computer) faulty personal computer).
communication
device (e.g. personal
computer).
88888 Watchdog CPU, parts faulty Fault of parts in servo amplifier Change servo amplifier.
Checking method
Alarm (88888) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
11 - 8
11. TROUBLESHOOTING
POINT
When any of the following alarms has occurred, do not resume operation by
switching power of the servo amplifier OFF/ON repeatedly. The servo
amplifier and servo motor may become faulty. If the power of the servo
amplifier is switched OFF/ON during the alarms, allow more than 30
minutes for cooling before resuming operation.
Excessive regenerative warning (AL.E0)
Overload warning 1 (AL.E1)
If AL.E6 occurs, the servo off status is established. If any other warning occurs, operation can be
continued but an alarm may take place or proper operation may not be performed. Use the optional MR
Configurator (servo configuration software) to refer to the cause of warning.
Display Name Definition Cause Action
AL.90 Home position Positioning operation 1. Positioning operation was performed Perform home position return.
In incremental system
without home
position setting.
Home position setting 2. Home position setting speed could not be Review home position setting
ended abnormally. decreased to creep speed. speed/creep speed/moving
3. Limit switch was actuated during home
distance after proximity dog.
position setting starting at other than
position beyond dog.
Operation was 4. Voltage drop in encoder After leaving the alarm
performed without (Battery disconnected.) occurring for a few minutes,
making home position switch power off, then on again.
setting while an Always make home position
absolute position setting again.
erase (AL.25) is being 5. Battery voltage low Change battery. Always make
occurred. 6. Battery cable or battery is faulty. home position setting again.
AL.92 Open battery Absolute position 1. Battery cable is open. Repair cable or changed.
cable warning detection system battery 2. Battery voltage supplied from the servo Change battery.
voltage is low. amplifier to the encoder fell to about
3.2V or less.
(Detected with the encoder)
AL.96 Home position Home position setting 1. Droop pulses remaining are greater Remove the cause of droop pulse
setting warning could not be made. than the in-position range setting. occurrence
2. Command pulse entered after clearing Do not enter command pulse
of droop pulses. after clearing of droop pulses.
3. Creep speed high. Reduce creep speed.
11 - 9
11. TROUBLESHOOTING
AL.E3 Absolute position Absolute position encoder 1. Noise entered the encoder. Take noise suppression
counter warning pulses faulty. measures.
2. Encoder faulty. Change servo motor.
The multi-revolution counter 3. The movement amount from the home Make home position setting
value of the absolute position position exceeded a 32767 rotation or again.
encoder exceeded the 37268 rotation in succession.
maximum revolution range.
AL.E6 Servo forced stop EMG-SG are open. External forced stop was made valid. Ensure safety and deactivate
warning (EMG-SG opened.) forced stop.
AL.E9 Main circuit off Servo was switched on Switch on main circuit power.
warning with main circuit power
off.
When MR-DP60 external digital display detects an error, the following alarms are displayed. The alarms
are displayed only on the MR-DP60, but not on the servo amplifier display.
11 - 10
12. OUTLINE DIMENSION DRAWINGS
Approx.
(0.79)
(Terminal cover open)
(0.24)
6
20
MITSUBISHI MITSUBISHI
OPEN OPEN
C C C C
N N N N
1 1 1 1
168 (6.61)
156 (6.14)
A B A B
C C
Name plate C C
N N N N
2 3 2 3
TE1
(
E E
N
C N
C
)
L1 L2 L3
(Note)
6 (0.24)
U V W
Approx.7
TE2
(0.28)
6 PE terminal
(0.24)
4(0.16)
TE2 PE terminals
Front
D C P L21 L11
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 1
12. OUTLINE DIMENSION DRAWINGS
Approx.
(0.79)
(0.87)
(Terminal cover open)
6
20
MITSUBISHI MITSUBISHI
OPEN OPEN
C C C C
N N N N
1 1 1 1
A B
168(6.61)
156(6.14)
A B
C C
Name plate C C
N N N N
2 3 2 3
E E
N N
C C
L1 L2 L3
6(0.24)
U V W
PE terminal
Approx.7
22 42 6(0.24)
(0.87) (1.65)
6(0.24)
Mass
Servo amplifier
[kg]([lb])
MR-J2S-70CP 1.7
MR-J2S-100CP (3.75)
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
Front
D C P L21 L11 N
PE terminals
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 2
12. OUTLINE DIMENSION DRAWINGS
MITSUBISHI MITSUBISHI
168(6.61)
156(6.14)
TE2
TE1
PE terminal
Cooling fan wind direction
Mass
Servo amplifier
[kg]([lb])
MR-J2S-200CP 2.0
MR-J2S-350CP (4.41)
L11 L21 D P C N
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 3
12. OUTLINE DIMENSION DRAWINGS
(4) MR-J2S-500CP
2- 6( 0.24) [Unit: mm]
mounting hole ([Unit: in])
(0.24) 130(5.12) (0.24) Approx.70 200(7.87)
Approx.
6 118(4.65) 6 (2.76) (0.19) 5
(0.79)
(0.5)
7.5
Terminal layout
20
OPEN MITSUBISHI MITSUBISHI
OPEN OPEN
TE1
C C C C
N N N N
1 1 1 1
A B A B
C C C C
250(9.84)
235(9.25)
N N N N
2 3 2 3
TE2
N.P. N.P.
6(0.24)
(0.5)
Cooling fan
7.5
Mass
Servo amplifier
[kg]([lb])
MR-J2S-500CP 4.9(10.8)
TE2
12 - 4
12. OUTLINE DIMENSION DRAWINGS
(5) MR-J2S-700CP
2- 6( 0.24) [Unit: mm]
mounting hole ([Unit: in])
(0.39) 180(7.09) Approx.70 200(7.87)
10 160(6.23) 10 (2.76) 138(5.43) 62
Approx.
(0.5)
(2.44) 6(0.24)
7.5
(0.79)
(0.39)
Terminal layout
20
MITSUBISHI MITSUBISHI
OPEN OPEN
C C C C
N N N N
1 1 1 1
A B A B
C C C C
N N N N
2 3 2 3
TE2
350(13.8)
335(13.2)
OPEN
Cooling fan
TE1
6 (0.24)
(0.5)
7.5
Mass
Servo amplifier
[kg]([lb])
MR-J2S-700CP 7.2(15.9)
12 - 5
12. OUTLINE DIMENSION DRAWINGS
12.2 Connectors
10.0(0.39)
14.0
22.0 (0.87) (0.55)
33.3 (1.31)
12.7(0.50)
22.0 14.0
(0.87) (0.55) 27.4 (1.08)
39.0 (1.54)
(0.94)
23.8
33.3 12.7
5.2
(0.21)
(1.31) (0.50)
( 0.26)
29.7 (1.17)
12 - 6
12. OUTLINE DIMENSION DRAWINGS
C
D
A B C D F
Type E G
1 1 0.25 1 reference
DE-C1-J6-S6 34.5 (1.36) 19 (0.75) 24.99 (0.98) 33 (1.30) 6 (0.24) 18 (0.71) #4-40
12 - 7
12. OUTLINE DIMENSION DRAWINGS
MEMO
12 - 8
13. CHARACTERISTICS
13. CHARACTERISTICS
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier
from overloads. Overload 1 alarm (AL.50) occurs if overload operation performed is above the electronic
thermal relay protection curve shown in any of Figs 13.1. Overload 2 alarm (AL.51) occurs if the
maximum current flew continuously for several seconds due to machine collision, etc. Use the equipment
on the left-hand side area of the continuous or broken line in the graph.
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is
recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque.
1000 1000
During rotation
During rotation
100 100
Operation time [s]
Operation time[s]
During stop
10 10
During stop
1 1
0.1 0.1
0 50 100 150 200 250 300 0 50 100 150 200 250 300
1000
During rotation
Operation time[s]
10
c. MR-J2S-500CP MR-J2S-700CP
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor
stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the
electronic thermal relay protection is not activated.
13 - 1
13. CHARACTERISTICS
Table 13.1 Power supply capacity and generated heat per servo amplifier at rated output
(Note 1) (Note 2)
Area required for heat dissipation
Servo amplifier Servo motor Power supply Servo amplifier-generated heat[W]
capacity[kVA] At rated torque With servo off [m2] [ft2]
HC-KFS053 13 0.3 25 15 0.5 5.4
MR-J2S-10CP(1) HC-MFS053 13 0.3 25 15 0.5 5.4
HC-UFS13 0.3 25 15 0.5 5.4
HC-KFS23 0.5 25 15 0.5 5.4
MR-J2S-20CP(1) HC-MFS23 0.5 25 15 0.5 5.4
HC-UFS23 0.5 25 15 0.5 5.4
HC-KFS43 0.9 35 15 0.7 7.5
MR-J2S-40CP(1) HC-MFS43 0.9 35 15 0.7 7.5
HC-UFS43 0.9 35 15 0.7 7.5
HC-SFS52 1.0 40 15 0.8 8.6
MR-J2S-60CP HC-SFS53 1.0 40 15 0.8 8.6
HC-LFS52 1.0 40 15 0.8 8.6
HC-KFS73 1.3 50 15 1.0 10.8
MR-J2S-70CP HC-MFS73 1.3 50 15 1.0 10.8
HC-UFS72 73 1.3 50 15 1.0 10.8
HC-SFS81 1.5 50 15 1.0 10.8
MR-J2S-100CP HC-SFS102 103 1.7 50 15 1.0 10.8
HC-LFS102 1.7 50 15 1.0 10.8
HC-SFS121 2.1 90 20 1.8 19.4
HC-SFS201 3.5 90 20 1.8 19.4
HC-SFS152 153 2.5 90 20 1.8 19.4
HC-SFS202 203 3.5 90 20 1.8 19.4
MR-J2S-200CP
HC-RFS103 1.8 50 15 1.0 10.8
HC-RFS153 2.5 90 20 1.8 19.4
HC-UFS152 2.5 90 20 1.8 19.4
HC-LFS152 2.5 90 20 1.8 19.4
HC-SFS301 4.8 120 20 2.7 29.1
HC-SFS352 353 5.5 130 20 2.7 29.1
MR-J2S-350CP HC-RFS203 3.5 90 20 1.8 19.4
HC-UFS202 3.5 90 20 1.8 19.4
HC-LFS202 3.5 90 20 1.8 19.4
HC-SFS502 7.5 195 25 3.9 42.0
HC-RFS353 5.5 135 25 2.7 29.1
HC-RFS503 7.5 195 25 3.9 42.0
MR-J2S-500CP HC-UFS352 5.5 195 25 3.9 42.0
HC-UFS502 7.5 195 25 3.9 42.0
HC-LFS302 4.5 120 25 2.4 25.8
HA-LFS502 7.5 195 25 3.9 42.0
HC-SFS702 10.0 300 25 6.0 64.6
MR-J2S-700CP
HA-LFS702 10.6 300 25 6.0 64.6
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value assumes that the power
factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the
regenerative option, Refer to section 14.1.1.
13 - 2
13. CHARACTERISTICS
P
A ............................................................................................................................................. (13.1)
K T
where, A : Heat dissipation area [m2]
P : Loss generated in the control box [W]
T : Difference between internal and ambient temperatures [ ]
K : Heat dissipation coefficient [5 to 6]
When calculating the heat dissipation area with Equation 13.1, assume that P is the sum of all losses
generated in the enclosure. Refer to Table 13.1 for heat generated by the servo amplifier. "A" indicates
the effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall,
that extra amount must be added to the enclosure's surface area.
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the
enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore,
arrangement of the equipment in the enclosure and the use of a cooling fan should be considered.
Table 13.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is
operated at the ambient temperature of 40 (104 ) under rated load.
(Outside) (Inside)
Air flow
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because
the temperature slope inside and outside the enclosure will be steeper.
13 - 3
13. CHARACTERISTICS
Time constant
V0
Machine speed
te Time
V0 JL
Lmax te 1 ....................................................................................................................... (13.2)
60 JM
Lmax : Maximum coasting distance .................................................................................................[mm][in]
V0 : Machine rapid feed rate ........................................................................................ [mm/min][in/min]
JM : Servo motor inertial moment................................................................................. [kg cm2][oz in2]
JL : Load inertia moment converted into equivalent value on servo motor shaft..... [kg cm2][oz in2]
: Brake time constant ........................................................................................................................ [s]
te : Delay time of control section........................................................................................................... [s]
(There is internal relay delay time of about 30ms.)
0.016
Time constant [s]
12
0.014
10 73
Time constant
053 0.012 23
8
0.01 73
6
0.008
4
0.006
2 43 13 053
0.004
0 43
0 500 1000 1500 2000 2500 3000 0.002
0 13
Speed [r/min] 0 500 1000 1500 2000 2500 3000
Speed [r/min]
13 - 4
13. CHARACTERISTICS
0.04 0.045
0.035 0.04
121
0.035
Time constant [s]
702
0.08 53 0.012
0.01 103 503
0.06 0.008
153
0.006
0.04 353
0.004
0.02 103 0.002 353
203
153 0
0 0 500 1000 1500 2000 2500 3000
0 50 500 1000 1500 2000 2500 3000 Speed [r/min]
Speed [r/min]
e. HC-SFS3000r/min series f. HC-RFS series
0.07
73
0.06
0.05
0.1
Time constant [s]
0.09 0.04
72
0.08 502
Time constant [s]
30.0
25.0
302
20.0
15.0
10.0
5.0
0
0 500 1000 1500 2000
Speed [r/min]
i. HC-LFS series
13 - 5
13. CHARACTERISTICS
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load
inertia moment is higher than this value, the built-in dynamic brake may burn. If there is a possibility
that the load inertia moment may exceed the value, contact Mitsubishi.
The flexing life of the cables is shown below. This graph calculated values. Since they are not guaranteed
values, provide a little allowance for these values.
1 108 a
5 107
1 107
5 106 a : Long flexing-life encoder cable
MR-JCCBL M-H
MR-JHSCBL M-H
MR-ENCBL M-H
1 106
5 105 b : Standard encoder cable
MR-JCCBL M-L
MR-JHSCBL M-L
Flexing life [times]
1 105
5 104
1 104
b
5 103
1 103
4 7 10 20 40 70 100 200
13 - 6
13. CHARACTERISTICS
The following table indicates the inrush currents (reference value) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped
by an inrush current.
13 - 7
13. CHARACTERISTICS
MEMO
13 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
Before connecting any option or peripheral equipment, turn off the power and wait
for 15 minutes or more until the charge lamp turns off. Then, confirm that the
WARNING voltage between P and N is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo
amplifier whether the charge lamp is off or not.
Use the specified auxiliary equipment and options. Unspecified ones may lead to a
CAUTION fault or fire.
14.1 Options
The specified combinations of regenerative options and servo amplifiers may only
CAUTION be used. Otherwise, a fire may occur.
From the permissible duty, find whether the regenerative option is required or not.
Permissible duty number of positioning times [times/min]
Select the regenerative option out of the combinations in (1) of this section.
14 - 1
14. OPTIONS AND AUXILIARY EQUIPMENT
Time
Unbalance torque
M Down
t1 t2 t3 t4
Firiction Tpsa1 Tpsd1 Tpsa2 Tpsd2
torque 1)
( )
(Driving)
Generated torque
TF
2) 4) 8)
5)
TU
6)
3)
(Regenerative) 7)
( )
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative
energies.
14 - 2
14. OPTIONS AND AUXILIARY EQUIPMENT
Inverse efficiency ( ) :Efficiency including some efficiencies of the servo motor and servo
amplifier when rated (regenerative) torque is generated at rated speed.
Since the efficiency varies with the speed and generated torque, allow for
about 10%.
Capacitor charging (Ec) :Energy charged into the electrolytic capacitor in the servo amplifier.
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by
the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J] Es Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation period tf
[s] to select the necessary regenerative option.
PR [W] ER/tf
Selection of regenerative
0: Not used. (The built-in regenerative resistor is used. However, the MR-J2S-10CP
does not have a built-in regenerative resistor and therefore cannot use it.)
1: FR-RC, FR-BU2
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50(Cooling fan is required)
8: MR-RB31
9: MR-RB51(Cooling fan is required)
14 - 3
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
When the MR-RB50 MR-RB51 is used, a cooling fan is required to cool it.
The cooling fan should be prepared by the customer.
The regenerative option will generate heat of about 100 . Fully examine heat dissipation, installation
position, used cables, etc. before installing the option. For wiring, use flame-resistant cables and keep
them clear of the regenerative option body. Always use twisted cables of max. 5m (16.4ft) length for
connection with the servo amplifier.
Cooling fan(Note 1)
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
Thermal relay
(5.24)
133
14 - 4
14. OPTIONS AND AUXILIARY EQUIPMENT
5m(16.4ft) or less
Cooling fan(Note 1)
Note 1. When using the MR-RB50 MR-RB51, forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative
resistor terminals (across P-C), fit them back to back, and secure them to the frame with the
accessory screw as shown below.
Mounting method
Accessory screw
Accessory screw
Accessory screw
14 - 5
14. OPTIONS AND AUXILIARY EQUIPMENT
(3.25)
82.5
Thermal relay
(5.24)
133
Bottom 82.5 40 (1.58)
(3.25)
14 - 6
14. OPTIONS AND AUXILIARY EQUIPMENT
LA
6 (0.24) mounting hole
6 (0.24)
LB
12 (0.47)
MR-RB
168 (6.61)
156 (6.14)
144 (5.67)
TE1
5 (0.20) Terminal block
G3
G3
G4
G4
TE1 P
C
P
C
12 (0.47)
Terminal screw: M3
Tightening torque:
0.5 to 0.6 [N m](4 to 5 [lb in])
6 (0.24)
P
C Terminal screw: M4
G3 Tightening torque: 1.2 [N m] (10.6 [Ib in])
G4
Mounting screw
Screw: M6
7 (0.28) 318 (12.52) Tightening torque: 5.4 [N m] (47.79 [Ib in])
17 335 (13.19)
10 90 (3.54) (0.67)
Regenerative
(0.39) 100 (3.94) Mass [kg] (Ib)
option
MR-RB30
MR-RB31 2.9 (6.4)
MR-RB32
14 - 7
14. OPTIONS AND AUXILIARY EQUIPMENT
Mounting screw
7 14 Screw: M6
slot Tightening torque: 5.4 [N m]
(47.79 [Ib in])
2.3 7 (0.28)
(0.09) 200 (7.87) 17 12 108 (4.25) Approx.30 (1.18)
217 (8.54) (0.67) (0.47) 120 (4.73) 8 (0.32)
14 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
Use a 200V class brake unit and a resistor unit with a 200V class servo
amplifier. Combination of different voltage class units and servo amplifier
cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When
the unit is installed horizontally or diagonally, the heat dissipation effect
diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep
cables and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 (14 )
and 50 (122 ). Note that the condition is different from the ambient
temperature condition of the servo amplifier (between 0 (32 ) and
55 (131 )).
Configure the circuit to shut down the power-supply with the alarm
output of the brake unit and resistor unit under abnormal condition.
Use the brake unit with a combination indicated in this section (1).
For executing a continuous regenerative operation, use FR-RC power
regeneration converter.
Brake unit and regenerative options (Regenerative resistor) cannot be
used simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option,
the brake unit can return larger power. Use the brake unit when the regenerative option cannot provide
sufficient regenerative capability.
When using the brake unit, set the parameter No.0 of the servo amplifier to " 01 ".
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
(1) Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
14 - 9
14. OPTIONS AND AUXILIARY EQUIPMENT
Parameter Change
possible/ Remarks
No. Name
impossible
0 Brake mode switchover Impossible Do not change the parameter.
1 Monitor display data selection Possible Refer to the FR-BU2-(H) Brake Unit
Instruction Manual.
2 Input terminal function selection 1 Impossible Do not change the parameter.
3 Input terminal function selection 2
77 Parameter write selection
78 Cumulative energization time
carrying-over times
CLr Parameter clear
ECL Alarm history clear
C1 For manufacturer setting
14 - 10
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
Connecting PR terminal of the brake unit to P terminal of the servo
amplifier results in brake unit malfunction. Always connect the PR
terminal of the brake unit to the PR terminal of the resistor unit.
Servo amplifier
NFB MC CN1B
(Note 1) L1 (Note 9) EMG
Power L2 10 SG
supply FR-BR
L3 3 VDD
(Note 4) TH1
L11 13 COM P
TH2
L21 18 ALM RA1 PR
FR-BU2
D (Note 6) PR MSG
P P/ SD
(Note 3) A
(Note 7) N/
B
N
C
C BUE
(Note 8)(Note 5)
SD
(Note 2)
14 - 11
14. OPTIONS AND AUXILIARY EQUIPMENT
P P P P P Twist P P Twist P
N N PR PR N N PR PR
(b) Cables
1) Cables for the brake unit
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended.
a) Main circuit terminal
Main Crimping Cable size
Tightening
circuit terminal N/ , P/ , PR,
torque
Brake unit terminal
N/ , P/ , [N m] HIV cables,
screw AWG
PR, ([Ib in]) etc. [mm2]
N/ P/ PR size
FR-BU2-15K M4 5.5-4 1.5(13.3) 3.5 12
FR-BU2-30K M5 5.5-5 2.5(22.1) 5.5 10
Terminal block
14 - 12
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
Undertightening can cause a cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to damage to
the screw or the brake unit.
Sheath
PC BUE SD RES SD MSG MSG SD SD Core
A B C
Jumper
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable
from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N m
Cable size: 0.3mm2 to 0.75 mm2
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
POINT
Always use recommended crimping terminals or equivalent since some
crimping terminals cannot be installed depending on the size.
Number of
Servo amplifier Brake unit connected Crimping terminal Applicable tool Manufacturer
units
MR-J2S-350CP FR-BU2-15K 1
FR-BU2-15K 1 Japan Solderless
MR-J2S-500CP FVD5.5-S4 YNT-1210S
FR-BU2-30K 1 Terminal
MR-J2S-700CP FR-BU2-30K 1
14 - 13
14. OPTIONS AND AUXILIARY EQUIPMENT
Rating
plate
5 4
6 56 6 18.5 52 62
68 132.5
FR-BU2-30K
2- 5 hole
(Screw size: M4)
Rating
plate
5 5
6 96 6 18.5 52 59
108 129.5
14 - 14
14. OPTIONS AND AUXILIARY EQUIPMENT
2 C
(Note)
C C
Approx. 35 W1 1 Approx. 35
W 5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Approximate
Resistor unit W W1 H H1 H2 H3 D D1 C mass
[kg]([Ib])
FR-BR-15K 170 100 450 410 20 432 220 3.2 6 15(33.1)
FR-BR-30K 340 270 600 560 20 582 220 4 10 30(66.1)
50
30
20
0 50 75 100 150
Nominal regenerative power (%)
14 - 15
14. OPTIONS AND AUXILIARY EQUIPMENT
L11
L21
Power factor improving reactor
NFB MC FR-BAL
L1
(Note 3)
Power L2
supply
L3
VDD
SG COM
EMG
SON ALM RA2
(Note 2)
N P C
5m(16.4ft) or less
N/ P/
RDY
Ready A
SE
RDY B
B
output
C
C
R/L1 Alarm
S/L2 output
T/L3
RX
R
(Note 1)
SX Phase detection
S terminals
TX
T
Power regeneration
converter FR-RC
FR-RC Operation ready
RA2 EMG OFF ON
B C
MC MC
SK
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed, the
FR-RC will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected to P terminal
and C terminal.
3. Refer to section 1.2 for the power supply specification.
14 - 16
14. OPTIONS AND AUXILIARY EQUIPMENT
E
movable
Rating plate
Display
Front cover panel
window
BA
B
Cooling fan
D EE F K
AA
C
A
Power
Approx.
regeneration A AA B BA C D E EE K F
Mass [kg(Ib)]
converter
270 200 450 432 195 10 10 8 3.2 87 19
FR-RC-15K
(10.630) (7.874) (17.717) (17.008) (7.677) (0.394) (0.394) (0.315) (0.126) (3.425) (41.888)
340 270 600 582 195 10 10 8 3.2 90 31
FR-RC-30K
(13.386) (10.630) (23.622) (22.913) (7.677) (0.394) (0.394) (0.315) (0.126) (3.543) (68.343)
14 - 17
14. OPTIONS AND AUXILIARY EQUIPMENT
9)
Operation CN1A CN1B
panel
Personal
computer
CN2 CN3
14)
Controller
13)
10) 12)
11)
10)
11) To U, V, W,
19) 20)
HC-KFS
HC-MFS
1) 2)
HC-UFS 3000 r/min
6)
HC-SFS
15) 16) 17) 18) HC-RFS
HC-UFS 2000r/min
3) 4) 5)
7) 8)
14 - 18
14. OPTIONS AND AUXILIARY EQUIPMENT
14 - 19
14. OPTIONS AND AUXILIARY EQUIPMENT
14 - 20
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
The encoder cable is not oil resistant.
Refer to section 13.4 for the flexing life of the encoder cable.
When the encoder cable is used, the sum of the resistance values of the
cable used for P5 and the cable used for LG should be within 2.4 .
When soldering the wire to the connector pin, insulate and protect the
connection portion using heat-shrinkable tubing.
Generally use the encoder cable available as our options. If the required length is not found in the
options, fabricate the cable on the customer side.
Symbol Specifications
L Standard flexing life
H Long flexing life
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Encoder cable
Servo amplifier
supplied to servo motor
Encoder connector Encoder connector
Servo motor 172161-9 (Tyco Electronics)
Encoder cable
(option or fabricated)
1 2 3
MR MRR BAT
CN2 Encoder
4 5 6
14 - 21
14. OPTIONS AND AUXILIARY EQUIPMENT
P5 19 7 P5 19 7 P5 19 7
LG 11 LG 11 LG 11
P5 20 P5 20 P5 20
LG 12 LG 12 LG 12
P5 18 P5 18 P5 18
LG 2 LG 2 LG 2
8 8 8
MR 7 1 MR 7 1 MR 7 1
MRR 17 2 MRR 17 2 MRR 17 2
MD 6 4 MD 6 4 MD 6 4
MDR 16 5 MDR 16 5 MDR 16 5
BAT 9 3 BAT 9 3 BAT 9 3
LG 1 LG 1 LG 1
(Note) (Note) (Note)
SD Plate 9 SD Plate 9 SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNM connector set for encoder cable fabrication, and fabricate an encoder cable as shown in the
following wiring diagram. Referring to this wiring diagram, you can fabricate an encoder cable of up to
50m(164.0ft) length including the length of the encoder cable supplied to the servo motor.
When the encoder cable is to be fabricated by the customer, the wiring of MD and MDR is not required.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according to
the servo motor installation environment.
For use of AWG22
Servo amplifier side Encoder side
(3M)
P5 19 7
LG 11
P5 20
LG 12
P5 18
LG 2
8
MR 7 1
MRR 17 2
BAT 9 3
LG 1
(Note)
SD Plate 9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
14 - 22
14. OPTIONS AND AUXILIARY EQUIPMENT
Symbol Specifications
L Standard flexing life
H Long flexing life
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Servo amplifier
Encoder connector Encoder connector Pin Signal Pin Signal
Encoder cable Servo motor A MD K
M AB
(Optional or fabricated) L C B MDR L
N
C MR M
KT P D
J D MRR N SHD
CN2 Encoder S R E E P
H G F F BAT R LG
G LG S P5
50m(164.0ft) max. H T
J
14 - 23
14. OPTIONS AND AUXILIARY EQUIPMENT
P5 19 S P5 19 S P5 19 S
LG 11 LG 11 LG 11
P5 20 P5 20 P5 20
LG 12 R LG 12 LG 12
MR 7 C P5 18 P5 18
MRR 17 D LG 2 LG 2
P5 18
LG 2 R R
BAT 9 F MR 7 C MR 7 C
LG 1 G MRR 17 D MRR 17 D
(Note1)
SD Plate N
BAT 9 F BAT 9 F
(Note2) Use of AWG24
LG 1 G LG 1 G
(Less than 10m(32.8ft))
(Note1) (Note1)
Note1: This wiring is required for use in the absolute SD Plate N SD Plate N
position detection system. This wiring is not Use of AWG22 Use of AWG24
needed for use in the incremental system. (10m(32.8ft) to 50m(164.0ft)) (10m(32.8ft) to 50m(164.0ft))
2: AWG28 can be used for 5m(16.4ft) or less.
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNS connector set for encoder cable fabrication, and fabricate an encoder cable in accordance with
the optional encoder cable wiring diagram given in this section. You can fabricate an encoder cable of
up to 50m(164.0ft) length.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according
to the servo motor installation environment.
14 - 24
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
This cable may not be used with some personal computers. After fully
examining the signals of the RS-232C connector, refer to this section and
fabricate the cable.
When fabricating the cable, refer to the connection diagram in this section.
The following must be observed in fabrication.
1) Always use a shielded, multi-core cable and connect the shield with FG securely.
2) The optional communication cable is 3m(10ft) long. When the cable is fabricated, its maximum
length is 15m(49ft) in offices of good environment with minimal noise.
14 - 25
14. OPTIONS AND AUXILIARY EQUIPMENT
POINT
When using the junction terminal block, you cannot use SG of CN1A-20
and CN1B-20. Use SG of CN1A-4 and CN1B-4.
Ground the junction terminal block cable on the junction terminal block side with the standard
accessory cable clamp fitting (AERSBAN- ESET). For the use of the cable clamp fitting, refer to
section 13.2.6, (2)(c).
11
17
17
12
16
19
12
16
19
13
15
18
13
15
18
10
14
10
14
1
7
7
6
6
2
9
0
B1 B10
50(1.97)
60(2.36)
A1 A10
MITSUBISHI
MR-TB20
10 11 12 13 14 15 16 17 18 19
Terminal
block No.
0 1 2 3 5 6 7 8 9 2- 4.5(0.18)
4
46.2(1.82)
14 - 26
14. OPTIONS AND AUXILIARY EQUIPMENT
Junction terminal block side connector (Hirose Electric) Servo amplifier side (CN1A CN1B) connector (3M)
HIF3BA-20D-2.54R (connector) 10120-6000EL (connector)
10320-3210-000 (shell kit)
Pin
Terminal block label Junction terminal Pin No.
For CN1A For CN1B block terminal No. No.
LG LG 10 B1 1
NP VC 0 A1 2
PP VDD 11 B2 3
P15R CPO 1 A2 4
DI0 12 B3 5
MEND 2 A3 6
MD0 13 B4 7
DOG ST1 3 A4 8
COM ST2 14 B5 9
SG SG 4 A5 10
OPC P15R 15 B6 11
NG TLA 5 A6 12
PG COM 16 B7 13
DI1 6 A7 14
SON 17 B8 15
LSP 7 A8 16
LSN 18 B9 17
ZP ALM 8 A9 18
RD 19 B10 19
SD SD 9 A10 20
Plate
14 - 27
14. OPTIONS AND AUXILIARY EQUIPMENT
(1) Usage
The maintenance junction card (MR-J2CN3TM) is designed for use when a personal computer and
analog monitor are used at the same time.
Servo amplifier Communication cable
Bus cable Maintenance junction card (MR-J2CN3TM)
MR-J2HBUS M
CN3B
CN3 CN3A
CN3C
A1 A2 A3 A4 B4 B3 B2 B1 B5 B6 A5 A6
VDD COM EM1 DI MBR EMGO SG PE LG LG MO1 MO2
Analog monitor 2
Not used.
Analog monitor 1
14 - 28
14. OPTIONS AND AUXILIARY EQUIPMENT
75(2.95)
MR-J2CN3TM
A1 A6
B1 B6
TE1
3(0.12)
88(3.47) 41.5(1.63)
100(3.94)
Mass: 110g(0.24Ib)
MR-J2HBUS05M
MR-J2HBUS1M
MR-J2HBUS5M
1 1
11 11
2 2
12 12
3 3
13 13
4 4
14 14
5 5
15 15
6 6
16 16
7 7
17 17
8 8
18 18
9 9
19 19
10 10
20 20
Plate Plate
14 - 29
14. OPTIONS AND AUXILIARY EQUIPMENT
The data equivalent to the servo amplifier status display can be displayed on the MR-DP60. When using
the MR-DP60, set " 1 4" in parameter No. 16. The items that appear at the time of power-on can be
selected in parameter No.18.
(1) Specifications
Item Specifications
Display Red seven-segment LED, signed, six digits
Power supply Permissible voltage fluctuation Single-phase, 85 to 253VAC, 50/60Hz
Current consumption Within 200mA
Communication Interface Conforms to RS-422
Baud rate 4800bps, asynchronous
Bit length Start bit 1, date bit 8, parity bit 1, stop bit 1
Protocol MELSERVO protocol
Communication commands Commands dedicated to MELSERVO
Operating temperature / humidity range 0 to 60 (32 to 140 ),
90%RH or less, non-condensing
Storage temperature range 5 to 70 (23 to 158 )
NFB MC
L1
(Note)
Power supply L2 Servo amplifier
L3
External digital display
L11
MR-DP60
L21 L1
L2
CN3
5 RDP TXD
15 RDN TXD
9 SDP RXD
19 SDN RXD
1 LG LG
Plate SD
14 - 30
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
[Unit: mm (in)]
(0.79)
(2.09)
Square hole Square hole
20
53
2- 5 (0.20) 2- 5 (0.20)
141(5.55) 95(3.74)
150(5.91) 150(5.91)
TB2
58(2.28)
29(1.14)
TB1
MITSUBISHI MR-DP60
7.5 150(5.91) 7.5
(0.30) 165(6.50) (0.30) 2- 4.5 (0.18) mounting hole
2- 6.5 (0.26), depth 1 (0.04)
(0.16)
4
38(1.50)
43(1.69)
48(1.89)
14 - 31
14. OPTIONS AND AUXILIARY EQUIPMENT
(1) Specifications
Item Specifications
Voltage 4.5 to 13.2VDC
Power supply
Current consumption 60mA max.
Interface Output current max. 20mA for open collector output
Pulse signal form A-phase and B-phase signals with 90°phase difference
Pulse resolution 100pulse / rev
Max. speed Instantaneous max. 600r/min, ordinary 200r/min
Operating temperature range 10 to 60 (14 to 140 )
Storage temperature range 30 to 80 ( 22 to 176 )
CN1B
VDD 3
CN1A
SV OPC 11
Manual pulse generator A PP 3
MR-HDP01 OV SG 10
B NP 2
External +5 SD Plate
power
supply GND
14 - 32
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
[Unit: mm(in)]
1)
44
(2.
62
35)
72(2.8
80 1(3.15 0.04)
TYPE
50(1.969)
70(2.756)
5V to
12V 0V A B
POINT
The revision (Edition 44) of the Dangerous Goods Rule of the
International Air Transport Association (IATA) went into effect on
January 1, 2003 and was enforced immediately. In this rule, "provisions of
the lithium and lithium ion batteries" were revised to tighten the
restrictions on the air transportation of batteries. However, since this
battery is non-dangerous goods (non-Class 9), air transportation of 24 or
less batteries is outside the range of the restrictions. Air transportation of
more than 24 batteries requires packing compliant with the Packing
Standard 903. When a self-certificate is necessary for battery safety tests,
contact our branch or representative. For more information, consult our
branch or representative. (As of September, 2007).
14 - 33
14. OPTIONS AND AUXILIARY EQUIPMENT
Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-
UL (CSA) Standard, use the products which conform to the corresponding standard.
L11
6) Power regeneration L21 5) Electromagnetic
converter lead 2) Control power supply lead brake lead
Electro-
Power regeneration N B1 magnetic
converter B2 brake
Regenerative option
C
Encoder
P
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the
wiring distance is 30m(98.4ft) max. If the wiring distance is over 30m(98.4ft), choose the wire size in
consideration of voltage drop.
The alphabets (a, b, c) in the table correspond to the crimping terminals (Table 14.2) used to wire the
servo amplifier. For connection with the terminal block TE2 of the MR-J2S-100CP or less, refer to
section 3.11.
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to
section 3.8.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140) or
more for wiring.
Table 14.1 Recommended wires
(Note 1) Wires [mm2]
Servo amplifier
1) L1 L2 L3 2) L11 L21 3) U V W 4) P C 5) B1 B2
MR-J2S-10CP(1)
MR-J2S-20CP(1)
MR-J2S-40CP(1) 1.25 (AWG16) : a
2 (AWG14) : a
MR-J2S-60CP
MR-J2S-70CP
2 (AWG14) : a
MR-J2S-100CP 1.25 (AWG16) 2 (AWG14) : a 1.25 (AWG16)
MR-J2S-200CP 3.5 (AWG12) : b 3.5 (AWG12) : b
(Note 2)
MR-J2S-350CP
5.5 (AWG10) : b 5.5 (AWG10) : b
MR-J2S-500CP 5.5 (AWG10) : b
MR-J2S-700CP 8 (AWG8) : c 8 (AWG8) : c 3.5(AW12) : c
Note 1. For the crimping terminals and applicable tools, refer to table 14.2.
2. 3.5mm2 for use of the HC-RFS203 servo motor.
14 - 34
14. OPTIONS AND AUXILIARY EQUIPMENT
Use wires 6) of the following sizes with the power regeneration converter (FR-RC).
Model Wires[mm2]
FR-RC-15K 14(AWG6)
14 - 35
14. OPTIONS AND AUXILIARY EQUIPMENT
Always use one circuit breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the circuit breaker, use the one having the specifications given in this section.
Fuse
Servo amplifier Circuit breaker Magnetic contactor
Class Current [A] Voltage [V]
MR-J2S-10CP(1) 30 frame 5A K5 10
MR-J2S-20CP 30 frame 5A K5 10
MR-J2S-40CP 20CP1 30 frame 10A K5 15
S-N10
MR-J2S-60CP 40CP1 30 frame 15A K5 20
MR-J2S-70CP 30 frame 15A K5 20
250AC
MR-J2S-100CP 30 frame 15A K5 25
MR-J2S-200CP 30 frame 20A K5 40 S-N18
MR-J2S-350CP 30 frame 30A K5 70 S-N20
MR-J2S-500CP 50 frame 50A K5 125 S-N35
MR-J2S-700CP 100 frame 75A K5 150 S-N50
The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be
slightly lower than 90%.
Servo amplifier
[Unit : mm] FR-BAL MR-J2S- CP
([Unit : in.]) NFB MC
R X
L1
3-phase S Y
L2
H 5(0.2)
200 to 230VAC
T Z
L3
Servo amplifier
FR-BAL MR-J2S- CP
NFB MC
D1 R X
W L1
(Note)
Installation screw
1-phase S Y
L2
230VAC
D 5(0.2)
T Z
L3
RXSY T Z
Servo amplifier
C W1 FR-BAL MR-J2S- CP
NFB MC
1-phase R X
L1
100 to120VAC
S Y
L2
T Z
Note. Connect a 1-phase 230VAC power supply to L1/L2 and keep L3 open.
14 - 36
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.4 Relays
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Maximum rating Static
Maximum capacity Varistor voltage
Permissible circuit Surge Energy Rated limit voltage rating (range) V1mA
(reference
voltage immunity immunity power
value)
AC[Vma] DC[V] [A] [J] [W] [A] [V] [pF] [V]
(Note) 220
140 180 5 0.4 25 360 300
500/time (198 to 242)
Note. 1 time 8 20 s
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
Vinyl tube
3.0 (0.12)
or less
30.0 (1.18)
or more
14 - 37
14. OPTIONS AND AUXILIARY EQUIPMENT
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and
those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier
is an electronic device which handles small signals, the following general noise reduction techniques are
required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle
them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal
transmission, and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 3.10).
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many
relays which make a large amount of noise) near the servo amplifier and the servo amplifier may
malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp
fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and
other equipment against large exogenous noise and lightning surge, attaching a varistor to the
power input section of the equipment is recommended.
14 - 38
14. OPTIONS AND AUXILIARY EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral devices to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected
to the servo amplifier and its main circuits (input and output circuits), those induced
electromagnetically or statically by the signal cables of the peripheral devices located near the
main circuit cables, and those transmitted through the power supply cables.
Magnetic induction
noise Routes 4) and 5)
Static induction
noise Route 6)
Noises transmitted
Noise transmitted through
through electric Route 7)
power supply cable
channels
5)
7) 7)
2)
7)
Sensor
power
1) supply
Servo
2)
amplifier
Instrument Receiver
3)
8)
6)
4) Sensor
3)
Servo motor M
14 - 39
14. OPTIONS AND AUXILIARY EQUIPMENT
(1.34 0.04)
(1.18 0.04)
TDK
14 - 40
14. OPTIONS AND AUXILIARY EQUIPMENT
MC
Relay
Surge suppressor
Surge suppressor
Cable
Cable clamp
(A,B) Earth plate
40(1.57)
14 - 41
14. OPTIONS AND AUXILIARY EQUIPMENT
Outline drawing
[Unit: mm]
([Unit: in.])
30(1.18)
L or less
B 0.3(0.01)
10(0.39)
(0.940)
A
C
6 (0.24)
3 (0.12)
35 (1.38)
7 (0.28)
0.2
(0.940)
0
0.3
0
24
24
(Note)M4 screw 6 22(0.87)
(0.24) 35(1.38)
11(0.43)
Note: Screw hole for grounding. Connect it to the earth plate of the control box.
14 - 42
14. OPTIONS AND AUXILIARY EQUIPMENT
(0.45 0.02)
11.25 0.5
supply, passes must be four times or less. Do not pass the
Approx.65 (2.56)
grounding (earth) wire through the filter, or the effect of the filter
33(1.30)
will drop. Wind the wires by passing through the filter to satisfy the
required number of passes as shown in Example 1. If the wires
Approx.65(2.56)
are too thick to wind, use two or more filters to have the required
number of passes as shown in Example 2. Place the line noise
4.5(0.18)
filters as close to the servo amplifier as possible for their best
performance.
Example 1 NFB MC Servo amplifier
Power
L1 FR-BLF (MR-J2S-350CP or more)
supply
L2
31.5(1.24)
7(0.28)
Line noise L3
7(0.28)
filter
(Number of turns: 4) 130(5.12)
Example 2 NFB MC 85(3.35)
Servo amplifier
2.3(0.09) 80(3.15)
(1.38)
Power
35
L1
supply
L2 160(6.30)
Line noise L3 180(7.09)
filter
Two filters are used
(Total number of turns: 4)
L1
Power
L2 29 (1.14)
supply
42 (1.65)
L3 5 (0.20)
4 (0.16)
hole
14 - 43
14. OPTIONS AND AUXILIARY EQUIPMENT
[Unit: mm]
D H T E (Note)L d W
D T Model
Max. Max. Max. 1.0 min. 0.05 1.0
TND20V-431K 6.4 3.3
21.5 24.5 20 0.8 10.0
H
W E
L
14 - 44
14. OPTIONS AND AUXILIARY EQUIPMENT
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(14.1)
Ig1: Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 14.1.)
Ig2: Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 14.1.)
Ign: Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Iga: Leakage current of the servo amplifier (Found from Table 14.5.)
Igm: Leakage current of the servo motor (Found from Table 14.4.)
14 - 45
14. OPTIONS AND AUXILIARY EQUIPMENT
NV
Servo
amplifier M HC-MFS73
MR-J2S-60CP
5
Ig1 20 0.1 [mA]
1000
5
Ig2 20 0.1 [mA]
1000
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/ SW/CW/HW series.
14 - 46
14. OPTIONS AND AUXILIARY EQUIPMENT
For compliance with the EMC Directive of the EN Standard, it is recommended to use the following filter.
Some EMC filters are large in leakage current.
1 Surge protector 1
(RAV-781BYZ-2)
2
(OKAYA Electric Industries
3 Co., Ltd.)
1 2 3 Surge protector 2
(RAV-781BXZ-4)
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 230VAC power supply, connect the power supply to L1,L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
2. Connect when the power supply has earth.
14 - 47
14. OPTIONS AND AUXILIARY EQUIPMENT
L1
L2 LINE L1
L2 LINE
L3 L3
(input side) (input side)
LINE
LINE
168.0(6.614)
156.0(6.142)
140.0(5.512)
168.0(6.614)
156.0(6.142)
140.0(5.512)
LABEL
LABEL
LOAD
LOAD
L1'
L2' LOAD L1'
L2' LOAD
L3'
(output side) L3'
(output side)
HF3040-TM HF-3050A-TM
6-K
3-L 3-L
G 1
D 2
E 1
F 2
J 2
C 1 C 1
H 2
B 2
A 5
Dimensions [mm(in)]
Model
A B C D E F G H J K L M
260 210 85 155 140 125 44 140 70
HF3040A-TM M5 M4
(10.23) (8.27) (3.35) (6.10) (5.51) (4.92) (1.73) (5.51) (2.76) R3.25,
290 240 100 190 175 160 44 170 100 length 8
HF3050A-TM M6 M4
(11.42) (9.45) (3.94) (7.48) (6.89) (6.30) (1.73) (5.51) (3.94)
14 - 48
14. OPTIONS AND AUXILIARY EQUIPMENT
1) 2) 3)
Black Black Black
5.5 1
11 1
4.2 0.2
28.5 1.0
UL-1015AWG16
30
0
200
1 2 3
4.5 0.5
28 1.0
41 1.0
1) 2) 3) 4)
5.5 1
11 1
4.2 0.2
28.5 1.0
UL-1015AWG16
30
0
200
1 2 3
4.5 0.5
28 1.0
41 1.0
14 - 49
14. OPTIONS AND AUXILIARY EQUIPMENT
The following variable resistors are available for use with analog inputs.
(1) Single-revolution type
WA2WYA2SEBK2K (Japan Resistor make)
Resistance Dielectric strength Insulation Mechanical
Rated power Resistance Rotary torque
tolerance (for 1 minute) resistance rotary angle
2W 2k 10% 700V A.C 100M or more 300 5 10 to 100g-cm or less
6 (0.24) hole
10 (0.39) 2.8 (0.11)
2.5 (0.10)
12 (0.47)
1.6 (0.06) 10 (0.37) hole
12 (0.47)
1 2 3
M9 0.75 (0.03)
8)
.9
(0
5 3
R2
(0.08)
3- 1.54 (0.56) hole
1 30 30 3
2
CW
9.5 (0.37)
2
9 (0.35) hole
M9 0.75 (0.03)
(0.37)
(0.04)
9.5
1.0
(0.24)
6
12 (0.47) 6 (0.24)
1.2
(0.05) 20.5
7.5 (0.81)
L (0.3) 23 (0.91)
14 - 50
15. COMMUNICATION FUNCTIONS
This servo amplifier has the RS-422 and RS-232C serial communication functions. These functions can be
used to perform servo operation, parameter changing, monitor function, etc.
However, the RS-422 and RS-232C communication functions cannot be used together. Select between RS-
422 and RS-232C with parameter No.16. (Refer to section 15.2.2.)
15.1 Configuration
(1) Outline
Up to 32 axes of servo amplifiers from stations 0 to 31 can be operated on the same bus.
Servo amplifier Servo amplifier Servo amplifier
MITSUBISHI MITSUBISHI MITSUBISHI
Controller such as
personal computer
15 - 1
15. COMMUNICATION FUNCTIONS
(1) Outline
A single axis of servo amplifier is operated.
Servo amplifier
MITSUBISHI
CHARGE
To CN3
RS-232C
Controller such as
personal computer
Plate FG
TXD 3 2 RXD
1 GND
RXD 2 12 TXD
GND 5 11 GND
RTS 7
CTS 8
DSR 6
DTR 4
15 - 2
15. COMMUNICATION FUNCTIONS
This servo amplifier is designed to send a reply on receipt of an instruction. The device which gives this
instruction (e.g. personal computer) is called a master station and the device which sends a reply in
response to the instruction (servo amplifier) is called a slave station. When fetching data successively, the
master station repeatedly commands the slave station to send data.
Item Description
Baud rate 9600/19200/38400/57600 asynchronous system
Start bit : 1 bit
Data bit : 8 bits
Transfer code
Parity bit : 1 bit (even)
Stop bit : 1 bit
Transfer protocol Character system, half-duplex communication system
(LSB) (MSB)
Next
Start 0 1 2 3 4 5 6 7 Parity Stop start
Data
1 frame (11bits)
15 - 3
15. COMMUNICATION FUNCTIONS
When the RS-422/RS-232C communication function is used to operate the servo, set the communication
specifications of the servo amplifier in the corresponding parameters.
After setting the values of these parameters, they are made valid by switching power off once, then on
again.
15 - 4
15. COMMUNICATION FUNCTIONS
15.3 Protocol
POINT
Whether station number setting will be made or not must be selected if
the RS-232C communication function is used. Note that choosing "no
station numbers" in parameter No. 57 will make the communication
protocol free of station numbers.
Since up to 32 axes may be connected to the bus, add a station number or group to the command, data
No., etc. to determine the destination servo amplifier of data communication. Set the station number to
each servo amplifier using the parameter and set the group to each station using the communication
command. Transmission data is valid for the servo amplifier of the specified station number or group.
When "*" is set as the station number added to the transmission data, the transmission data is made
valid for all servo amplifiers connected. However, when return data is required from the servo amplifier
in response to the transmission data, set "0" to the station number of the servo amplifier which must
provide the return data.
10 frames (data)
Command
S S E
Controller side Data Check Station number
O T Data* T
(Master station) No. sum or
H X X
group
Error code
S E
Servo side Station number Check
T T
(Slave station) or sum
X X
group
6 frames
Positive response: Error code A
Negative response: Error code other than A
S S E
Data Check Station number
Controller side O T T
No. sum or
(Master station) H X X
group
Error code
S E
Station number Check
Servo side T Data* T
or sum
(Slave station) X X
group
6 frames (data)
15 - 5
15. COMMUNICATION FUNCTIONS
Servo side
(Slave station)
4 frames 8 frames
15 - 6
15. COMMUNICATION FUNCTIONS
b8 to C
b4 b3 b2 b1 0 1 2 3 4 5 6 7
b5 R
0 0 0 0 0 NUL DLE Space 0 @ P ` p
0 0 0 1 1 SOH DC1 ! 1 A Q a q
0 0 1 0 2 STX DC2 “ 2 B R b r
0 0 1 1 3 ETX DC3 # 3 C S c s
0 1 0 0 4 $ 4 D T d t
0 1 0 1 5 % 5 E U e u
0 1 1 0 6 & 6 F V f v
0 1 1 1 7 ‘ 7 G W g w
1 0 0 0 8 ( 8 H X h x
1 0 0 1 9 ) 9 I Y i y
1 0 1 0 10 : J Z j z
1 0 1 1 11 ; K [ k {
1 1 0 0 12 , L l |
1 1 0 1 13 M ] m }
_
1 1 1 0 14 . N ^ n
1 1 1 1 15 / ? O _ o DEL
Station number 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
ASCII code G H I J K L M N O P Q R S T U V
For example, "30H" is transmitted in hexadecimal for the station number of "0" (axis 1).
(4) Group
Group a b c d e f All group
ASCII code a b c d e f
For example, "61H" is transmitted in hexadecimal for group a.
15 - 7
15. COMMUNICATION FUNCTIONS
Error codes are used in the following cases and an error code of single-code length is transmitted.
On receipt of data from the master station, the slave station sends the error code corresponding to that
data to the master station.
The error code sent in upper case indicates that the servo is normal and the one in lower case indicates
that an alarm occurred.
Error code
Error name Description Remarks
Servo normal Servo alarm
[A] [a] Normal operation Data transmitted was processed properly. Positive response
[B] [b] Parity error Parity error occurred in the transmitted data.
[C] [c] Checksum error Checksum error occurred in the transmitted data.
Character not existing in the specifications was
[D] [d] Character error
transmitted.
Negative response
Command not existing in the specifications was
[E] [e] Command error
transmitted.
Data No. not existing in the specifications was
[F] [f] Data No. error
transmitted.
15.6 Checksum
The checksum is a ASCII-coded hexadecimal representing the lower two digits of the sum of ASCII-coded
hexadecimal numbers up to ETX, with the exception of the first control code (STX or SOH).
Station number (Example)
or
group S E
T [0] [A] [1] [2] [5] [F] T [5] [2]
X X
02H 30H 41H 31H 32H 35H 46H 03H
STX or ETX Check
SOH
30H 41H 31H 32H 35H 46H 03H
152H
Checksum range
Lower 2 digits 52 is sent after conversion into ASCII code [5][2].
15 - 8
15. COMMUNICATION FUNCTIONS
The master station transmits EOT when the slave station does not start reply operation (STX is not
received) 300[ms] after the master station has ended communication operation. 100[ms] after that, the
master station retransmits the message. Time-out occurs if the slave station does not answer after the
master station has performed the above operation three times. (Communication error)
100ms 100ms 100ms *Time-out
300ms 300ms 300ms 300ms
Message
Message
Message
Message
E E E
Controller O O O
(Master station) T T T
Servo
(Slave station)
When a fault occurs in communication between the master and slave stations, the error code in the
response data from the slave station is a negative response code ([B] to [F], [b] to [f]). In this case, the
master station retransmits the message which was sent at the occurrence of the fault (Retry operation). A
communication error occurs if the above operation is repeated and results in the error three or more
consecutive times.
*Communication error
Message
Message
Message
Controller
(Master station)
Servo S S S
(Slave station) T T T
X X X
Similarly, when the master station detects a fault (e.g. checksum, parity) in the response data from the
slave station, the master station retransmits the message which was sent at the occurrence of the fault. A
communication error occurs if the retry operation is performed three times.
15 - 9
15. COMMUNICATION FUNCTIONS
15.9 Initialization
After the slave station is switched on, it cannot reply to communication until the internal initialization
processing terminates. Hence, at power-on, ordinary communication should be started after.
(1) 1s or more time has elapsed after the slave station is switched on; and
(2) Making sure that normal communication can be made by reading the parameter or other data which
does not pose any safety problems.
The following example reads the set value of parameter No.2 "function selection 1" from the servo
amplifier of station 0.
Data item Value Description
Station number 0 Servo amplifier station 0
Command 05 Read command
Data No. 02 Parameter No.2
Addition of SOH to make Transmission data SOH 0 05 STX 02 ETX F C 46H 43H
up transmission data
Master station slave station
Data transmission
Master station slave station
Data receive
No
Is there receive data?
Yes No
300ms elapsed?
Yes
No
3 consecutive times?
Master station slave station
Yes Yes
Other than error code
[A] [a]? 100ms after EOT transmission
No
3 consecutive times?
No Error processing
Yes Receive data analysis
Error processing
End
15 - 10
15. COMMUNICATION FUNCTIONS
POINT
If the command/data No. is the same, its data may be different from the
interface and drive units and other servo amplifiers.
15 - 11
15. COMMUNICATION FUNCTIONS
15 - 12
15. COMMUNICATION FUNCTIONS
15 - 13
15. COMMUNICATION FUNCTIONS
15 - 14
15. COMMUNICATION FUNCTIONS
15 - 15
15. COMMUNICATION FUNCTIONS
15 - 16
15. COMMUNICATION FUNCTIONS
When the master station transmits a command data No. or a command data No. data to a slave
station, the servo amplifier returns a reply or data according to the purpose.
When numerical values are represented in these send data and receive data, they are represented in
decimal, hexadecimal, etc.
Therefore, data must be processed according to the application.
Since whether data must be processed or not and how to process data depend on the monitoring,
parameters, etc., follow the detailed explanation of the corresponding command.
The following methods are how to process send and receive data when reading and writing data.
The following example indicates how to process the receive data "003000000929" given to show.
The receive data is as follows.
0 0 3 0 0 0 0 0 0 9 2 9
Data 32-bits length (hexadecimal representation)
(Data conversion is required as indicated in the display type)
Display type
0: Data must be converted into decimal.
1: Data is used unchanged in hexadecimal.
Since the display type is "0" in this case, the hexadecimal data is converted into decimal.
00000929H 2345
As the decimal point position is "3", a decimal point is placed in the third least significant digit.
Hence, "23.45" is displayed.
15 - 17
15. COMMUNICATION FUNCTIONS
0
Data is transferred in hexadecimal.
By way of example, here is described how to process the set data when a value of "15.5" is sent. Since
the decimal point position is the second digit, the decimal point position data is "2". As the data to be
sent is hexadecimal, the decimal data is converted into hexadecimal.
155 9B
Hence, "0200009B" is transmitted.
15 - 18
15. COMMUNICATION FUNCTIONS
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
15 - 19
15. COMMUNICATION FUNCTIONS
15.12.3 Parameter
(b) Reply
The slave station sends back the data and processing information of the requested parameter No.
Read enable/disable
0: Read enable
1: Read disable
Enable/disable information changes according to the setting of parameter No.19 "parameter write
inhibit". When the enable/disable setting is read disable, ignore the parameter data part and
process it as unreadable.
15 - 20
15. COMMUNICATION FUNCTIONS
Write mode
0: Write to EEP-ROM
3: Write to RAM
When the parameter data is changed frequently through communication,
set "3" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
15 - 21
15. COMMUNICATION FUNCTIONS
(b) Reply
The slave station sends back the statuses of the input pins.
b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
(b) Reply
The ON/OFF statuses of the input pins are sent back.
b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
15 - 22
15. COMMUNICATION FUNCTIONS
(b) Reply
The slave station sends back the statuses of the input pins.
b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
(b) Reply
The slave station sends back the ON/OFF statuses of the output pins.
b31 b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
15 - 23
15. COMMUNICATION FUNCTIONS
(b) Reply
The slave station sends back the statuses of the output devices.
b31 b1 b0
1:ON
0:OFF
POINT
The ON/OFF states of all devices in the servo amplifier are the states of
the data received last. Hence, when there is a device which must be kept
ON, send data which turns that device ON every time.
Each input device can be switched on/off. However, when the device to be switched off exists in the
external input signal, also switch off that input signal.
Send command [9][2], data No. [6][0] and data.
Command Data No. Set data
[9][2] [6][0] See below.
b31 b1 b0
1:ON
0:OFF
15 - 24
15. COMMUNICATION FUNCTIONS
Inputs can be disabled independently of the I/O devices ON/OFF. When inputs are disabled, the input
signals (devices) are recognized as follows. Among the input devices, EMG, LSP and LSN cannot be
disabled.
Signal Status
Input devices (DI) OFF
External analog input signals 0V
Pulse train inputs None
(1) Disabling/enabling the input devices (DI), external analog input signals and pulse train inputs with
the exception of EMG, LSP and LSN.
Transmit the following communication commands.
(a) Disable
Command Data No. Data
[9][0] [0][0] 1EA5
(b) Enable
Command Data No. Data
[9][0] [1][0] 1EA5
(b) Enable
Command Data No. Data
[9][0] [1][3] 1EA5
15 - 25
15. COMMUNICATION FUNCTIONS
Each input devices can be turned on/off for test operation. when the device to be switched off exists in the
external input signal, also switch off that input signal.
Send command [9] [2], data No. [0] [0] and data.
Command Data No. Set data
[9][2] [0][0] See below
b31 b1 b0
1: ON
0: OFF
Command of each bit is transmitted to the slave
station as hexadecimal data.
15 - 26
15. COMMUNICATION FUNCTIONS
5) Start.
15 - 27
15. COMMUNICATION FUNCTIONS
(b) Start
Turn on the input devices SON LSP LSN and ST1/ST2 by using command [9][2] data No.
[0][0].
Item Command Data No. Data
Forward rotation start [9][2] [0][0] 00000807: Turns on SON LSP LSN and ST1.
Reverse rotation start [9][2] [0][0] 00001007: Turns on SON LSP LSN and ST2.
Stop [9][2] [0][0] 00000007: Turns on SON LSP and LSN.
15 - 28
15. COMMUNICATION FUNCTIONS
Retransmit the same communication commands as at the start time to resume operation.
To stop positioning operation after a temporary stop, retransmit the temporary stop
communication command. The remaining moving distance is then cleared.
15 - 29
15. COMMUNICATION FUNCTIONS
15.12.9 Output signal pin ON/OFF output signal (DO) forced output
In the test operation mode, the output signal pins can be turned on/off independently of the servo status.
Using command [9][0], disable the output signals in advance.
(1) Choosing DO forced output in test operation mode
Transmit command [8][B] data No. [0][0] data "0004" to choose DO forced output.
0 0 0 4
Selection of test operation mode
4: DO forced output (output signal forced output)
bit External output pin bit External output pin bit External output pin bit External output pin
0 CN1A-19 8 16 24
1 CN1A-18 9 17 25
2 CN1B-19 10 18 26
3 CN1B-6 11 19 27
4 CN1B-4 12 20 28
5 CN1B-18 13 21 29
6 CN1A-14 14 22 30
7 15 23 31
15 - 30
15. COMMUNICATION FUNCTIONS
(b) Reply
The alarm No. corresponding to the data No. is provided.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(b) Reply
For example, data [0][1][F][5] indicates that the alarm occurred 501 hours after start of operation.
15 - 31
15. COMMUNICATION FUNCTIONS
(b) Reply
The slave station sends back the alarm currently occurring.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(b) Reply
The slave station sends back the requested status display data at alarm occurrence.
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Conversion into decimal required
1: Used unchanged in hexadecimal
15 - 32
15. COMMUNICATION FUNCTIONS
Hexadecimal data
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Speed data write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 33
15. COMMUNICATION FUNCTIONS
2) Reply
The slave station sends back the acceleration time constant of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Accelevation time constant write type
0: Valid after write
1: Valid when power is switched on again after write
2) Reply
The slave station sends back the deceleration time constant of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Deceleration time constant write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 34
15. COMMUNICATION FUNCTIONS
(e) Dwell
Read the dwell of the point table.
1) Transmission
Transmit command [6][0] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the dwell of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Dwell write type
0: Valid after write
1: Valid when power is switched on again after write
2) Reply
The slave station sends back the auxiliary function of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Auxiliary function write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 35
15. COMMUNICATION FUNCTIONS
Hexadecimal data
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
15 - 36
15. COMMUNICATION FUNCTIONS
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
15 - 37
15. COMMUNICATION FUNCTIONS
(e) Dwell
Write the dwell of the point table.
Transmit command [C][A], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command Data No. Data
[0][1] to
[C][A] See below.
[0][F]
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
15 - 38
15. COMMUNICATION FUNCTIONS
With group setting made to the slave stations, data can be transmitted simultaneously to two or more
slave stations set as a group through RS-422 communication.
0 0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
Set whether data can be sent back or not in
response to the read command of the master station.
0: Response disable
Data cannot be set back.
1: Response enable
Data can be set back.
(b) Reply
The slave station sends back the group setting of the point table requested.
0 0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
0: Response disable
1: Response enable
15 - 39
15. COMMUNICATION FUNCTIONS
(b) Reply
The slave station returns the software version requested.
15 - 40
APPENDIX
Electronic gear
CMX Position Speed Current
Command generator PWM M Servo motor
CDV control control control
App - 1
Speed feedback
Absolute
Auto position
tuning section encoder
Load inertia
moment ratio
App - 2
10 10 10 10
LG
0 0 0 0
11 11 11 11
PP
1 1 1 1
12 12 12 12
NP P15R
2 2 2 2
13 13 13 13
3 3 3 3
14 14 14 14
4 4 4 4
15 15 15 15
5 5 5 5
DOG SG NG
16 16 16 16
COM OPC PG
6 6 6 6
17 17 17 17
7 7 7 7
18 18 18 18
8 8 8 8
19 19 19 ZP 19
The servo amplifier software versions compatible with the servo motors are indicated in the parentheses.
The servo amplifiers whose software versions are not indicated can be used regardless of the versions.
App - 3
APPENDIX
Connector sets (options) in the following table are changed to the RoHS compatible products after September,
2006 shipment.
Please accept that the current products might be mixed with RoHS compatible products based on availability.
App - 4
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data *Manual Number Revision
Jan., 2002 SH(NA)030017-A First edition
Oct., 2002 SH(NA)030017-B Addition of Note to the environment conditions in Safety Instructions 4 (1)
Addition of "About processing of waste"
Addition of "EEP-ROM life"
COMPLIANCE WITH EC DIRECTIVES 1. (1): Sentence change
(1): HA-LFS , HC-LFS addition
(6) (a): Deletion
(7) (c): Sentence change
CONFORMANCE WITH UL/C-UL STANDARD (1): HA-LFS , HC-LFS
addition
(7): Addition
Section 1.5: HA-LFS , HC-LFS addition
Section 2.4 (2): Sentence change
Section 3.3.2 (1) (c): Sentence change to "Position range (POT)"
Section 3.5: Addition of Note into Figure
Section 3.8.1: POINT addition
Section 3.8.3 (1) Lead wire color deletion
Section 4.1.1 (1) (b): Sentence change
Section 4.2.6 (2) (a) 1): Figure change
2): Figure change
(b): Figure change
(c) 1): Figure change
2): Figure change
(3): Figure change
Section 5.2.1 (2): Addition of sentence to parameters No. 50, 51
Change of No. 55 setting
Section 6.2 (1): Change to display contents
Section 7.1: Change to initial screen of point table
Section 7.2.2: POINT addition
Section 7.5.1: Figure change
Section 7.5.3 (1): Figure change, Note addition
(2): Figure change, Note addition
Section 7.6.2 (2): Signed 5-digit parameter addition
Section 8.2.2: POINT addition
Section 11.2.1: Addition of Note to AL.30
Addition of AL.61 home operation alarm
Section 11.2.2: Deletion of Cause 4 from AL.16
Addition of Causes 3 - 6 to AL.37
Addition of AL.61 home operation alarm
Section 13.1: Note addition
Section 13.2: Change of "zero torque" representation to "servo off"
Section 14.1.1 (1): Note described for MR-RB50, MR-RB51
(4): Note addition, cooling fan mounting diagram addition
Section 14.1.4 (2) (a): POINT addition
Fabricating connection diagram change
Section 14.2.6 (2) (b): Figure change
Section 14.2.8: Sentence addition
Section 14.2.9: Figure change
Print data *Manual number Revision
Oct., 2002 SH(NA)030017-B Section 15.10: Figure change
Section 15.12.3 (2): POINT addition
Mar., 2004 SH(NA)030017-C Safety Instructions: Overall reexamination
Section 1.1.1: Partial figure reexamination
Section 1.5: Note addition
Section 1.7 (3): Note addition
Section 1.7 (4): Note addition
Section 3.1: Partial figure reexamination/Addition of Note 13
Section 3.6.1: Partial figure reexamination
Section 3.8.2: Figure reexamination
Section 3.8.3: Overall reexamination
Section 3.9: Figure reexamination of CAUTION
Section 4.1.2: Partial addition of CAUTION sentence
Section 4.1.2 (f): Partial table change
Section 4.2.2 (3): Partial table addition
Section 4.2.3 (3): Partial table addition
Section 4.2.4: Overall reexamination
Section 4.3.2: Partial table deletion
Section 4.4.2 (3): Partial changing of text/Partial figure addition
Section 4.4.3: Partial changing of figure, table and text
Section 4.4.4: Partial changing of figure, table and text
Section 4.4.5: Partial changing of figure, table and text
Section 4.4.6: Partial changing of figure, table and text
Section 4.4.7 (2): Partial changing of table and text/Partial figure addition
Section 4.4.8 (2): Partial changing of table and text/Partial figure addition
Section 4.4.9 (2): Partial changing of table and text/Partial figure addition
Section 4.4.11: Partial figure addition
Section 5.1.2 (2): Partial addition of parameter No.0/change Setting range of
parameter No.35 to No.37, Partial text addition of parameter
No.63
Section 5.2.3: Partial text change
Chapter 6: Title reexamination
Section 6.2 (1): Table change
Section 6.7.2: Partial addition of POINT sentence
Section 6.7.5: POINT addition
Section 6.4 (2): Change
Section 11.2: Partial text change
Section 11.2.2: Changing of alarm 12 to 15/addition of alarm 37 cause 7/Partial
text change of alarm 51 52
Section 12.1: Overall reexamination
Section 13.2: Table reexamination
Section 13.3: Partial addition of text
Section 13.5: Addition
Section 14.1.1 (3): Partial figure change
Section 14.1.1 (4): Partial text change
Section 14.1.1 (5): Partial reexamination
Section 14.1.2: Partial addition of text
Section 14.1.2 (2): Changing of Note 2
Section 14.1.3: Partial addition of text
Section 14.1.3 (2): Partial figure reexamination/Addition of Note 2
Section 14.1.7: Partial addition of text
Print data *Manual number Revision
Mar., 2004 SH(NA)030017-C Section 14.1.9: POINT addition
Section 14.2.8 (3): Partial figure reexamination
Section 14.2.6 (2) (d): Partial figure change
Section 14.2.6 (2) (e): Partial figure change
Section 14.2.8: Partial figure change
Appendix: Addition
Mar., 2005 SH(NA)030017-D COMPLIANCE WITH EC DIRECTIVES: “1. WHAT ARE EC DIRECTIVES?“
Sentence reexamination
Section 1. 1. 1 (1): Reexamination of words in figure
Section 1. 1. 1 (2): Addition, reexamination of the function block diagram for
MR-J2S-500CP, 700CP
Section 1. 4 (2): Note reexamination
Section 3. 1: Figure reexamination
Section 3. 3. 1 (2): Signal arrangement Deletion of PG, NG
Section 3. 3. 2 (1) (c): Sentence addition of rough match device
Section 3. 3. 2 (2): Input signal Deletion of PG, NG
Section 3. 5: Addition of CAUTION sentence (3) Sentence reexamination
Section 3. 6. 2 (3) 2): Figure reexamination of output pulse
Section 3. 6. 2 (6): Figure correction
Section 3. 7. 2: Addition of explanation on the power supply terminals
Section 3. 7. 3 (1) 1): Sentence addition
Section 3.9: Sentence reexamination (3) (d), (e) Figure change
Section 3. 11: POINT addition (1) Sentence reexamination
Section 4. 2. 1 (2) (b): Note reexamination
Section 4. 3. 2 (3) (b): Reexamination of sentence in table, note
Section 4. 5: POINT addition, reexamination (1) Sentence reexamination
Section 5. 1. 2 (1): No.60, No.87 Correction of initial value
Reexamination of words in table
Section 5. 1. 2 (2): No.46 Figure reexamination No.87 Changing of initial
value
No.55 Reexamination of words in table
Reexamination of words in table
Section 6. 2 (1): Note sentence addition
Section 7. 5. 3 (2): Partial changing of figure
Section 7. 6: Reexamination of words in POINT
Section 7. 6. 2 (2): Partial changing of figure
Section 9. 4 (1): Calculation reexamination
Section 11. 2. 1: Addition of words in table
Section 11. 2. 2: AL. 10 Sentence reexamination
AL. 17, AL. 19 Sentence reexamination, addition
AL. 33 Sentence addition
AL. 46 Sentence reexamination
Section 11. 2. 3: Addition of CAUTION sentence
AL. E3 Sentence addition
Section 13.1: Note change
Section 13.3: Addition of HC-LFS series graph Sentence reexamination
Section 14. 1. 1 (2): (b) Figure addition
Section 14. 1. 1 (4): POINT addition
Section 14. 1. 1 (4) (a): Sentence reexamination
Section 14. 1. 1 (4) (b): Sentence reexamination
Section 14. 1. 1 (5) (b): Reexamination of words in figure
Print data *Manual number Revision
Mar., 2005 SH(NA)030017-D Section 14. 1. 1 (5) (c): Partial changing of figure
Section 14. 1. 2 (2): Note reexamination
Section 14. 1. 3 (2): Note reexamination
Section 14. 1. 4 (1): Sentence reexamination (2) Sentence reexamination
Section 14. 1. 9: Correction of words in POINT
Section 14. 2. 3: Addition of MR-J2S- CP
Crossing change
Section 14. 2. 6 (2): (d) Sentence reexamination (e) Connection diagram change
Section 15. 8: Sentence reexamination
App 3: Partial change
Jan., 2006 SH(NA)030017-E Safety Instructions: 4. (2) (4) Sentence addition
Section 1.1.1: Correction of error in writing
Section 1.4 (2): Note reexamination
Section 1.6.1: Correction of instructions
Section 1.7: Note reexamination
Chapter 2: CAUTION addition
Section 3.6.2 (3) (b): 2) Addition of descriptions
Section 3.8.3: Change of signal expression
Section 3.9: CAUTION addition
Section 4.1.2 (2) (b): Sentence change
Section 4.2.3 (2) (c): Sentence change/Partial figure reexamination
Section 4.2.4 (2) (c): Sentence change/Partial figure reexamination
Section 4.2.5 (2) (c): Sentence change/Partial figure reexamination
Section 4.4.10: Home position return automatic return function: Correction of
error in writing
Section 5.1.2 (2): Note addition of parameter No. 17, No. 30
Section 5.2.4: Sentence change
Section 5.2.4 (2): Note addition
Section 11.2.3: Sentence addition
Section 12.1: Correction of error in writing
Section 14.2.6 (2) (d): Change of outline drawing
Section 15.2.3 (2): Change of POINT sentence
Section 15.12.12: POINT addition
Section 15.12.12 (3): Correction of error in writing
Section 15.12.12 (4): Correction of error in writing
Section 15.12.12 (5): Correction of error in writing
Section 15.12.12 (6): Correction of error in writing
Jul., 2006 SH(NA)030017-F Safety Instructions: 4. Additional instructions (2) Figure change
Section 1.1 (2): Figure correction
Section 1.1.2: Correction of description for auxiliary functions
Section 1.6.2: Correction of words in CAUTION
Chapter 2: Addition of CAUTION sentence
Chapter 3: Addition of CAUTION sentence
Section 3.7.2: Addition of sentence in Table
Section 3.7.3 (3): CAUTION addition
Section 3.8.2: CAUTION addition
Section 4.2.2 (2): Sentence reexamination
Section 4.4.8: Correction of POINT sentence
Section 4.5 (1): Sentence reexamination
Section 5.2.1: Correction of POINT sentence
Section 6.2 (1): Table change
Print data *Manual number Revision
Jul., 2006 SH(NA)030017-F Section 7.2.3: Correction of description for command position
Section 8.3.1 (1) (a): Addition of parameter in Table
Section 8.4 (2): Correction of description for Step 5
Section 11.2.2: Correction of name for Al. 17
Section 11.2.3: Correction of description for Al. 90
Section 12.2 (1) (b): Correction of error in dimensions
Section 14.1.1 (2): Correction of formula in Table
Section 14.1.1 (4): Sentence reexamination
Section 14.1.5 (3): Addition of pin No. in figure
Section 14.1.7 (2): Correction of signal name for CN3-1 pin
Section 14.1.9: POINT reexamination
Section 15.12.3 (2): Correction of POINT sentence
Section 15.12.5: Sentence addition
Section 15.12.12: Description reexamination
Sep., 2007 SH(NA)-030017-G Safety Instructions
1. To prevent electric shock: Partial change of sentence
2. To prevent fire: Partial change of sentence
4. Additional Instructions
(2) Wiring: Addition of sentence
Section 1.1.1: Addition of Note
Section 1.6.2: WARNING Change of sentence
Section 1.7: Addition of Note
Chapter 3: WARNING Change of sentence
Section 3.6.2 (2): Addition of sentence Addition of Note
Section 3.6.2 (6): Addition of Note
Section 3.7: CAUTION Change of sentence
Section 3.9 (3): Change of timing chart
Section 4.4.5 (3): Addition of Note
Section 4.4.8: POINT Change of sentence
Section 4.5: POINT addition
Section 4.5 (5): CAUTION Change of sentence
Section 5.1.2 (2): Partial change of parameter No.0
Chapter 10: WARNING Change of sentence
Section 11.2: Addition of AL. 20 Definition
Change of sentence in AL. 32. Definition
Change of sentence in AL. 33. Definition
Addition of Cause 6 for AL. 50
Change of sentence in AL. 51. Definition
Section 11.3: New addition
Chapter 14: WARNING Change of sentence
Section 14.1.1 (3): Change of parameter No.0 definition
Section 14.1.1 (5) (b), (c): Change of outline dimension drawing
Section 14.1.2: Overall change to FR-BU2
Section 14.1.4: Change of some connectors to RoHS compatible products
Section 14.2.1 (1): Partial change of table 14.2
Section 14.2.6 (2) (d): Change of sentence
Section 14.2.8: Addition of connection diagram and surge protector
Appendix 6: Addition
General-Purpose AC Servo
J2-Super Series
Built-In Positioning Function
MODEL
J2-Super Series
MR-J2S- CP
SERVO AMPLIFIER
INSTRUCTION MANUAL
MR-J2S- CP
Servo Amplifier Instruction Manual
MODEL
G
MODEL
CODE