ERC 102 Refrigeration Controller: Reference Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 60

MAKING MODERN LIVING POSSIBLE

ERC 102 refrigeration controller


Reference manual
This reference manual is intended to be used primarily by OEMs for the purposes of programming ERC 102.
It may also be useful for technicians. It is not intended as a user guide for end users.

www.danfoss.com/erc
Downloaded from www.Manualslib.com manuals search engine
Table of Content

1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2. CONTENT OF THE BOX


2.1 Main product . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.2 Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
2.3 Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

3. OVERVIEW OF THE PRODUCT


3.1 Control buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Connector inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.3 Connector outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Top label . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4. MOUNTING
4.1 Rear mounting – Option 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Front mounting – Option 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Fully-integrated design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

5. CONTROLLING/NAVIGATION
5.1 KoolProg and Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2 Docking station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Manual operation with buttons (Direct Access) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 ERC Front and Button Functionallity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Direct functions for access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.3.3 Operating the menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3.5 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

6. CONFIGURATION OF INPUTS AND OUTPUTS


6.1 Changing input and output configuration settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
6.2 Program the buttons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
6.3 Set passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
6.4 Set lighting function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

2 ERC 102 Reference manual

Downloaded from www.Manualslib.com manuals search engine


7. PARAMETERS
7.1 Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
7.2 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
7.3 Compressor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
7.4 Defrost . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
7.5 Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.6 Energy management . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
7.7 Pull down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
7.8 Automatic heater control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
7.9 Condenser protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
7.10 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
7.11 Assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
7.12 Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

8. TECHNICAL SPECS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

APPENDIX
I Parameter quick list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
II Code numbers and lenghts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
III Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
IV Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IV.1 Typical Wiring Diagram, ERC 102D, Glass Door Merchandiser,
No-frost freezer / sub-zero cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IV.2 Typical Wiring Diagram, ERC 102C, Glass Door Merchandiser . . . . . . . . . . . . . . . . . . . . . 54
IV.3 Typical Wiring Diagram, ERC 102D, Gastro No-frost freezer . . . . . . . . . . . . . . . . . . . . . . 55
IV.4 Typical Wiring Diagram, ERC 102C, Gastro Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
V Application specificatons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
V.1 Control sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
V.2 Evaporator sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
V.3 Condenser sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
V.4 Ambient light sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
V.5 Door sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
ERC102 Application Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60

ERC 102 Reference manual 3

Downloaded from www.Manualslib.com manuals search engine


1. INTRODUCTION

The ERC 102 is an electronic refrigeration controller with an LED display especially developed for bottle
coolers and commercial fridges and freezers. It is particularly suited for OEM customers where time, easy and
reliable installation and high quality need to go hand in hand with flexibility.

The latest generation CPU, plenty of memory and high-end electronic components allow for a uniquely
versatile software. Three separate password-protected user levels can be used to control more than 200
different parameters to fit all individual requirements.

ERC 102’s IP rated body, advanced materials and internationally approved hardware design open it up for use
in almost any climate globally, indoors as well as outdoors.

Laboratory work with ERC 102 is rendered easy and flexible. Danfoss KoolProg software with a USB-powered
gateway accelerate programming; on the OEM assembly line, just one Danfoss unique Docking station can
easily program up to 3,000 controllers a day – at zero inventory cost.

It uses a globally-compatible, lightweight, switch mode power supply.


All components have been carefully selected to help reduce the CO2 footprint. The globally-compatible
internal power supply uses an average of just 0.7W – 4 times less than an average controller today.

Sensors include ambient light for display brightness, which also detect shop opening hours for
energy-saving routines. Door and temperature sensors provide input for controlling the compressor,
the light, the fan and automatic defrosting.

4 ERC 102 Reference manual

Downloaded from www.Manualslib.com manuals search engine


2. CONTENT OF THE BOX

If delivered in a sample box the following content


is shipped. The sample box is not available for other
than sample purposes.

See Appendix II for code numbers and lengths.


For box lots (pcs per box), please contact your local
Danfoss representative.

2. 1 Main product
ERC 102 control unit without front frame.

NOTE: The front frame is included in the sample box.

2.2 Accessories
Control temperature sensor: see Appendix II for
different lengths and connector types.

Defrost temperature sensor: should be mounted on


the evaporator. For detailed mounting instructions,
please contact your local Danfoss representative.

NOTE: Defrost sensors can also be used as condenser


sensors.

Condenser temperature sensor: should be


mounted on the condenser. For detailed
mounting instructions, please contact your
local Danfoss representative.

NOTE: This sensor is not included in the sample box .


Defrost sensors can also be used as condenser
sensors.

ERC 102 Reference manual – 2 CONTENT OF THE BOX 5

Downloaded from www.Manualslib.com manuals search engine


Door sensor connector cable: please see Appendix II
for lengths and code numbers.

NOTE: Door sensor: is optional and is a connector


and cable with spade terminals compatible with door
contacts used in refrigeration applications.

Light sensor: is optional and is used to measure the


level of ambient light around the cabinet so
that night and day (Economy / Normal) modes
of operation can automatically be set, as well
as the brightness of the display.

Power plug: for laboratory use, low quantity


OEM production or whenever spade connectors are
not available.

Clips: are used to secure the ERC 102 in place in


the case of rear mounting. They are not used with
front mounting. There are two identical clips, one
placed on either side of the ERC 102. See Chapter 4
– Mounting – for further details.

6 ERC 102 Reference manual – 2 CONTENT OF THE BOX

Downloaded from www.Manualslib.com manuals search engine


2.3 Connections
Programming an individual unit in a laboratory:
the USB gateway requires KoolProg Software
running on a PC. It enables parameters to be set in
real time and an array of status information to be
read (bidirectional connection). This method is used
to determine the correct parameters during R&D.

Once the desired settings have been determined,


a KoolProg ERC specific parameter file is saved to the
EKA183 USB copy key for later mass programming.

The USB Gateway is a laboratory tool, offering fast


and easy programming of any ERC102 controller.
KoolProg software installation is provided;
the gateway is standard inventory for OEM labs.

Mass programming on an assembly line:


the docking station is used for high volume
programming of ERC controllers, for example
on an assembly line. The docking station is a
write-only device.

See above (Programming an individual unit) for


preparing the EKA183 USB copy key, which is to
be inserted into the docking station. The settings
are then loaded into each successive controller
in a matter of seconds.

KoolProg software is not required for mass


programming.

Note: please refer to the koolprog manual for more


details about programming.

KoolProg: is the software from Danfoss for


programming the ERC 102 via a USB cable and
a PC rather than with the front panel buttons.
Please refer to the KoolProg manual for details.

ERC 102 Reference manual – 2 CONTENT OF THE BOX 7

Downloaded from www.Manualslib.com manuals search engine


3. OVERVIEW OF THE PRODUCT
The ERC 102 is a state-of-the art, IP65 (front)-rated
refrigeration controller for use in both Glass Door The ERC 102 can also be programmed via USB using
Merchandising and Commercial Fridges and Freezer the Danfoss KoolProg software, allowing the most
applications. suitable parameter findings to be found quickly
during the application development process.
With four inputs and four outputs, powerful
algorithms and input from multiple sensors, the ERC It is also possible to operate and program the
102 delivers both energy-saving routines and controller using the control buttons (only when
compressor, light, fan and defrost control. actually installed in a refrigerator / freezer).

Together with the Danfoss docking station, Overview of ERC 102 models:
programming of pre-prepared parameter sets can
Model: Digital outputs:
be achieved in just five seconds. There are over 200
parameters (see Chapter 7) including innovative ERC 102A 1 relay
features such as night mode detection, ERC 102C 3 relays
store opening detection, door open alarm control
and display dimming for restaurants. ERC 102D 4 relays

3.1 Control buttons

The ERC 102 has four buttons (circled in image)


on the front which can be programmed to perform
different functions. See Chapter 6 – Configuration of
inputs and outputs for detailed information.

3.2 Connector inputs


Connect up to four Danfoss original sensors according The ambient light sensor can be used for determin-
to your application needs. ing shop open / closed times for economy mode
switching, for determining the brightness of the LED
There are three analogue inputs: S1, S2 and display or both.
S3 ( a ).

Supported input options:


· Ambient light - analogue data [luminens]
· Cabinet (air) temperature - analogue data [°C]
· Evaporator temperature - analogue data [°C]
· Condenser temperature - analogue data [°C]
· Digital input - binary data [on/off ]

There is one digital input: diC ( b ) for PC


communication being used either with a door S1 S2 S3
sensor or with the USB Gateway. b
a
NOTE: for detailed information refer to section 6.1.

8 ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT

Downloaded from www.Manualslib.com manuals search engine


3.3 Connector outputs

All four outputs ( c ) are digitally controlled


on/off relays.
C
Functions controlled are:
• Compressor
• Pilot Relay
• Heater
• Defrost heater / valve for hot gas
• Alarm
• Fan
• Light

3.4 Top label


The illustration shows an example of a top label
affixed to an ERC 102D. The examples show what
is connected:

• Output 1 is used to switch the compressor


on and off.
• Outputs 2 and 3 are power – Live and Neutral.
• Output 4 is used to switch the heater on and off.
• Output 5 is used to switch the fan on and off.
• Output 6 is used to switch the light on and off.

• Input D (S1) is connected to a Cabinet Sensor to


measure temperature inside the cabinet.
• Input C(di) is used for Communications – a docking
station or KoolProg software running on a PC.
• Input B(S2) is connected to an Evaporator
Temperature Sensor.
• Input A(S3) is connected to an Ambient Light Sensor.

NOTE: Parameters depend on the code number sup-


plied. Please refer to the code number
specific technical drawing or use the KoolProg infor-
mation menu. For other applications,
a condenser sensor and a door sensor may
be used.

ERC 102 Reference manual – 3 OVERVIEW OF THE PRODUCT 9

Downloaded from www.Manualslib.com manuals search engine


4. MOUNTING

There are three options for mounting the ERC 102


in a freezer or refrigerator.

SAFETY INFO
Risk of electrocution!
For mounting: Do not connect mains power until
the controller is correctly mounted.
For unmounting: Disconnect the power supply
before unmounting.

4.1 Rear mounting – Option 1


1. Insert the ERC 102 into the cabinet.

2. Attach the clips to each side of the ERC 102.

3. Place the front frame on to the ERC 102 and click


it into place.

4. Connect the sensors and outputs as required and


then the power cable (see Chapter 6 – parameters
for information about programming which inputs
and outputs are applicable to your configuration).

10 ERC 102 Reference manual – 4 MOUNTING

Downloaded from www.Manualslib.com manuals search engine


4.1.1 Unmounting
1. Disconnect the power cable and then the sensors.

2. Use a flat head screwdriver (ideally the one


supplied with the ERC 102 sample package)
and insert it carefully between the front frame
and the controller.

3. Gently twist the screwdriver to remove the


front frame. Do this in four places next to each
clip area.

5. Reach around the side to the clips.

ERC 102 Reference manual – 4 MOUNTING 11

Downloaded from www.Manualslib.com manuals search engine


6. Press the centre section of each clip to release
them in turn. Push the controller carefully out
of the cabinet.

4.2 Front mounting – Option 2


1. Connect all the cables as required (see Chapter 6
– parameters for information about programming
which inputs and outputs are applicable to your
configuration).

2. Insert the ERC 102 into place in the cabinet.

3. Press the front frame into place – this locks the


ERC 102 into position.

 OTE: there is no need to use the clips for


N
front mounting.

12 ERC 102 Reference manual – 4 MOUNTING

Downloaded from www.Manualslib.com manuals search engine


4.2.1 Unmounting

1. Use a flat head screwdriver (ideally the


one supplied with the ERC 102 sample package)
and insert it carefully between the front frame
and the controller.

2. Gently twist the screwdriver to remove the


front frame. Do this in four places next to each
clip area.

3. Cabinet. Do not use a different type of


screwdriver or a sharp item such as a knife
which risks causing damage.

4.3 Fully integrated design – Option 3

An option is available for OEMs wanting to use the ERC


102 in a fully-integrated design. Please contact your
local Danfoss representative for more information.

ERC 102 Reference manual – 4 MOUNTING 13

Downloaded from www.Manualslib.com manuals search engine


5. CONTROLLING / NAVIGATION AND ACCESS LEVELS

The ERC 102 can be controlled in three ways:


using KoolProg software, the Danfoss Docking
Station or manually by means of the buttons
on the front panel.

5.1 KoolProg/Gateway
KoolProg is licenced Danfoss software offering easy
parameter setup via a USB gateway. This software
is supplied separately; for technical literature and
further information, please contact your local
Danfoss representative.

5.2 Docking station


The ERC 102 controller docking station is supplied
separately. For further information, please contact
your local Danfoss representative.

5.3 Manual operation with buttons


(Direct Access)
Danfoss ERC 102
Explained as follows:

ERC Front and Button Functionallity:


5.3.1 ERC Front and Button Functionallity

1 Press: Variable direct function, e.g.ECO/Night mode 1 Press: Temperature setpoint


1Sub
Click: VariableBack
function: direct function, e.g.ECO/Night mode
1Sub function:
Click: Up setpoint
Temperature
Sub function: Back Sub function: Up

1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint


1Hold 3 sec:
Press: Menu direct function, e.g. light
Variable Sub function:
1 Press: Down setpoint
Temperature
Sub function: OK
Sub function: OK Sub function: Down

14 ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS

Downloaded from www.Manualslib.com manuals search engine


s ERC 102
5.3.2 Direct functions for access
d Button Functionallity:

s ERC 102Changing the Desired Temperature Setpoint (applies similarly when using Fahrenheit scale):
function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Up

d Button Functionallity:
1.)

s ERC 102
The display shows the current
function, e.g.ECO/Night mode temperature.
1 Click: Temperature setpoint
Sub function: Up

(Current temperature)
d Button Functionallity:
2.)
function, e.g. light 1 Click: Temperature setpoint

s ERC 102
function, e.g.ECO/Night mode
Sub
Press: function:toDown
up/down adjust setpoint
1 Click: Temperature setpoint
Sub function: Up

(Flashing: temperature setpoint)


d Button Functionallity:
3.) After 30 seconds, the display automatically
reverts to showing the current temperature
function, e.g. light 1 Click: Temperature setpoint
Sub function: Down
function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Up

(Flashing: temperature setpoint)


4.)
unction, e.g. light 1 Click: Temperature setpoint
Sub function: Down

nfoss ERC 102


function, e.g. light 1 Click: Temperature setpoint
Sub function: Down
C Front and Button Functionallity:

nfoss ERC 102


Variable direct function, e.g.ECO/Night mode
Turning
nction: Back On/Off the ECO Function: 1 Click: Temperature setpoint
Sub function: Up

C Front and Button Functionallity:


1.)
Press briefly
to enter
Variable direct function, e.g.ECO/Night mode
ECO mode 1 Click: Temperature setpoint
nction: Back Sub function: Up

2.)
Variable direct function, e.g. light ECO ˚C 1 Click: Temperature setpoint
sec: Menu Sub function: Down
nction: OK
The green ECO symbol
is lit when in ECO mode

Variable direct function, e.g. light 1 Click: Temperature setpoint


sec: Menu Sub function: Down
nction: OK

ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS 15

Downloaded from www.Manualslib.com manuals search engine


anfoss ERC 102
C Front and Button Functionallity:

k: Variable direct function, e.g.ECO/Night mode


1 Click: Temperature setpoint
unction: Back
Turn ON/Off the Light Sub function: Up

1.)

Press the

anfoss ERC 102


Danfoss ERC 102
Light button
briefly To turn off the Light
Press the light button again

C Front and Button Functionallity:


ERC Front and Button Functionallity:
k: Variable direct function, e.g. light 1 Click: Temperature setpoint
3 sec: Menu Sub function: Down
unction: OK

anfoss ERC 102 Alarms:


k: Variable direct function, e.g.ECO/Night mode
Acknowledging
unction: Back
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Up

C Front and Button Functionallity:


1.)

k: Variable direct function, e.g.ECO/Night mode


1 Click: Temperature setpoint
unction: Back Sub function: Up

Flashing
Press any button to acknowlege
2.)
k: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down
unction: OK Sub function: OK

k: Variable direct function, e.g. light 1 Click: Temperature setpoint


3 sec: Menu Sub function: Down
unction: OK

5.3.3 Operating the menu

Button assignments in this manual refer


to the Glass Door Merchandiser default ERC 102.
For customised controls you may assign different
shortcuts (ASI menu --> button configuration).
Use this feature only when the ERC 102 is supplied
without button prints.

INFO: Some parameters may be hidden to you.


When scrolling through menus, the parameters
available will have been pre-determined using
KoolProg software. Your access level will determine
which parameters you can view and edit.

16 ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS

Downloaded from www.Manualslib.com manuals search engine


Danfoss ERC 102
ERC Front and Button Functionallity:

Danfoss ERC 102


1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
Example of Changing a Parameter:
1 Click: Temperature setpoint
Sub function: Up

ERC Front and Button Functionallity:


1.)

Press and hold for 5 seconds to enter the menu

Danfoss ERC 102


1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up

ERC Front and Button Functionallity:


2.)
1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint
Hold 3 sec: Menu Sub function:toDown

Danfoss ERC 102


Press: up/down scroll
Sub function: OK through the menu
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back Sub function: Up

(scroll through parameter groups)


ERC Front and Button Functionallity:
3.)
1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint
Hold 3 sec: Menu Sub function: Down

Danfoss ERC 102


1Sub function:
Click:
To select:
Sub
OKdirect function, e.g.ECO/Night mode
Variable
press
function: the lower left button (OK)
Back
1 Click: Temperature setpoint
Sub function: Up

ERC Front and Button Functionallity:


4.)
1 Click: Variable direct function, e.g. light 1 Click:
Press: Temperature
up/down to find setpoint

Danfoss ERC 102


Hold 3 sec: Menu Sub function: Down
the desired parameter
1Sub function:
Click: OKdirect function, e.g.ECO/Night mode
Variable
1 Click: Temperature setpoint
Sub function: Back Sub function: Up

(scroll through group “dEf” parameters)


ERC Front and Button Functionallity:
5.)
1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint
Hold 3 sec: Menu

Danfoss ERC 102


Sub function: Down
Sub function: OK
1 Click: Variable direct function, e.g.ECO/Night mode
To confirm: press the lower left button (OK) 1 Click: Temperature setpoint
Sub function: Back Sub function: Up

ERC Front and Button Functionallity:


6.)
1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint

Danfoss ERC 102


Hold 3 sec: Menu
1Sub
Click: Variable
function: OKdirect function, e.g.ECO/Night mode
Sub function: Back
Press:
Subup/down
function:toDown
the desired value
enter
1 Click: Temperature setpoint
Sub function: Up

ERC Front and Button Functionallity:


7.)

Danfoss ERC 102


1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint
Hold 3 sec:Press:
MenuOK to accept Sub function: Down
1Sub
Click: Variable
function: direct function, e.g.ECO/Night mode
andOK
Sub function: return to parameter name
Back
1 Click: Temperature setpoint
Sub function: Up

ERC Front and Button Functionallity:


8.)
1 Click: Variable
Press:direct
upperfunction, e.g. light
left button (back) 1 Click: Temperature setpoint
1Hold 3 sec:
Click: toMenu
return
Variable to function,
direct parameter group
e.g.ECO/Night mode Sub function: Down
Sub 1 Click: Temperature setpoint
Sub function:
function: OK
Back Sub function: Up

9.)
Press:direct
1 Click: Variable upperfunction,
left button (back)
e.g. light 1 Click: Temperature setpoint
Hold 3 sec:toMenu
return to the menu Sub function: Down
Sub function: OK

1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint


Hold 3 sec: Menu Sub function: Down
Sub function: OK

ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS 17

Downloaded from www.Manualslib.com manuals search engine


ERC 102 Danfoss ERC 102

Danfoss ERC 102


Button Functionallity: ERC Front and Button Functionallity:

tion, e.g.ECO/Night mode

Danfoss
ERC Front and ERC
Sub function: Back
5.3.4 Menu structure 102
1 Click: Variable direct function, e.g.ECO/Night mode1 Click: Temperature setpoint
Button Functionallity:
Sub function: Up
1 Click: Temperature setpoint
Sub function: Up

Danfoss
ERC Front and ERC
Sub function: Back 102
Button Functionallity:
1 Click: Variable direct function, e.g.ECO/Night mode
Press and hold 5 1. ) Parameter groups
sec to access the
1 Click: Temperature setpoint
Sub function: Up
menu

Danfoss
ERC Front and ERC 102Danfoss ERC 102
Button Functionallity:
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up
Lower left button

tion, e.g. light


Danfoss ERC 102Danfoss ERC 102Danfoss ERC 102
1 ERC Frontdirect
Click: Variable
Sub function: Back
and Button
function, Functionallity:
e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode
ERC Front and Button Functionallity:1 Click: Temperature setpoint
1 Click: Temperature setpoint 1Sub function:
Click: Up
Temperature setpoint
Hold 3 sec: Menu Sub function: Down Sub function: Down
Sub function: OK

Danfoss ERC 102Danfoss ERC 102


1 ERC Frontdirect
Click: Variable
Sub function: Back
and Button
function, e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode1 Click: Variable direct function, e.g.ECO/Night mode ERC Front and Button Functionallity:
Functionallity:
ERC Front and Button Functionallity:1 Click: Temperature setpoint
Sub function: Back Sub function: Up
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Up
Hold 3 sec: Menu Sub function: Down
Sub function: OK

Danfoss ERC 102Danfoss ERC 102


1 ERC Front and Button Functionallity:
Click: Variable
Sub function: Back
direct function, e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode1 ERC Frontdirect
Click: Variable
Sub function: Back
and Button
function, e.g.ECO/Night mode 1 Click:
Functionallity:
Variable
1 Click:
Sub function:
direct function, e.g.ECO/Night mode
Temperature setpoint
Back
2.) Parameter
Sub function: Up
names
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Up
1 Cli
Sub
Hold 3 sec: Menu Sub function: Down
Sub function: OK Lower left button
Danfoss ERC 102Danfoss ERC 102
1 ERC Front and Button Functionallity:
Click: Variable
Sub function: Back
direct function, e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode1 ERC
Click: Front
Variable
Sub function: Back
and
direct Button
function, Functionallity:
e.g.ECO/Night mode 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
1 3.)
Click: Temperature
Parameter
Sub function: Up
setpoint
value

Hold 3 sec: Menu Sub function: Down


Sub function: OK

Danfoss ERC 102


1 ERC Front and Button Functionallity:
Click: Variable
Sub function: Back
direct function, e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode1 ERC Frontdirect
Click: Variable
Sub function: Back
and Button
function, Functionallity:
e.g.ECO/Night

1 Click: Variable direct function, e.g. light


mode 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down
Sub function: OK

Danfoss ERC 102


Sub function: OK
1 ERC Front and Button Functionallity:
Click: Variable direct function, e.g.ECO/Night mode1 Click: Variable direct function, e.g.ECO/Night mode 1 Click: Temperature setpoint 1 Click: Temperature setpoint
Sub function: Back Sub function: Back Sub function:function,
Up
1 Click: Variable Sub function: Up
1 Click: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: direct e.g. light
Temperature setpoint 1 Click: Temperature setpoint 1 Cli
Hold 3 sec: Menu Hold 3 sec: Menu Hold 3 sec:SubMenu
function: Down Sub function: Down Sub
Sub function: OK Sub function: OK

Danfoss ERC 102


Sub function: OK
1 ERC Frontdirect
Click: Variable and Button
function, Functionallity:
e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back Sub function: Up
1 Click: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down
Sub function: OK Sub function: OK
1 ERC Front and Button Functionallity:
Click: Variable direct function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back Sub function: Up
1 Click: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down
(scroll through parameters) Sub function: Down
Sub function: OK Sub function: OK
1 Click: Variable direct function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Back Sub function: Up
1 Click: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
Hold 3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down
Sub function: OK Sub function: OK

ERC 102 Danfoss ERC 102Danfoss ERC 102


1 Click: Variable direct function, e.g. light
Hold 3 sec: Menu
1 Click: Temperature setpoint
Sub function: Down
Sub function: OK

Button Functionallity: 1 Click:


ERC Front
Variable directand Button
function, e.g. light Functionallity:
ERC Front and Button
(scroll throughFunctionallity:
menu group) 1 Click: Temperature setpoint
Hold 3 sec: Menu Sub function: Down
Sub function: OK

tion, e.g.ECO/Night mode 1 Click: Variable direct function,


e.g.e.g.ECO/Night mode
1 Click: Variable direct function, light 1 Click:1 Temperature
Click: Variablesetpoint
direct function, e.g.ECO/Night mode 1 Click: Temperature
1 Click: setpoint
Temperature setpoint 1 Click: Temperature setpoint
Sub function:
MenuBack Sub function:
Up Back
5.3.5
Hold
Password
3 sec:
Sub function: OK
protection Sub function: SubSub
function: Down
function: Up Sub function: Up

Press and hold 5


sec to access the
menu

Password protection on three levels


Level 1: Shop (daily use by shop personnel)
Level 2: Ser (service technician)
tion, e.g. light 1 Click: Variable direct function, e.g. light 1 Click:1 Temperature
Click: Variablesetpoint
direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
Hold 3 sec: Menu Hold 3 sec: Menu
Level 3: OEM (OEM programming)
Sub function: Down Sub function: Down Sub function: Down
Sub function: OK Sub function: OK

18 ERC 102 Reference manual – 5 CONTROLLING / NAVIGATION AND ACCESS LEVELS

Downloaded from www.Manualslib.com manuals search engine


102 6. CONFIGURATION OF INPUTS AND OUTPUTS
unctionallity:
The ERC 102 inputs and outputs are configurable by For instance: Danfoss supplies only 2-pole defrost
the customer. Before getting started it is a good idea sensors, so input S3 will most likely be used as a
to check if all inputs are configured correctly and defrost / evaporator temperature sensor input.
match the sensors attached.
Please contact your local Danfoss representative for
Night mode Input and output configuration settings are part of information about default settings.
1 Click: Temperature setpoint
the assignment menu (ASi).
Sub function: Up
NOTE: Coded sensors will impact on the number of
possible configurations.

Assignments / ASi

6.1 Changing input and output configuration settings


There are two steps to inputting the configuration:
1 Click: Temperature setpoint
1. Define the type of sensor attached to the input: Subapplication
2. Define the function: for
Down
the sensor:
- Temperature / light / digital - Temperature: control / condenser / evaporator
- Light: ECO / display / both
- Digital: door sensor

Example: Input S1 is attached to a temperature sensor. The sensor measures cabinet temperature.
Example: Input S2 is attached a digital on/off sensor which is a door open / closed switch.

S1 S2 S3
b
a
Connector inputs: analogue ( a ), digital ( b ) Connector outputs ( c )

ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 19

Downloaded from www.Manualslib.com manuals search engine


ERC menu Default Min Max Unit Conv Unit Scale Default Access
code Shop Ser OEM

Assignments ASi

S1 Config S1C Stn Stn dig no -- -- RW

S2 Config S2C Stn Stn dig no -- -- RW

S3 Config S3C Stn Stn dig no -- -- RW

S1 Application S1A SCo nC doo no -- -- RW

S2 Application S2A nC nC doo no -- -- RW

S3 Application S3A nC nC doo no -- -- RW

DI Config diC dio doC dio no -- -- RW

DO1 Config 01C CoP CoP HEt no -- -- RW

DO2 Config o2C dEF 0 Lig no -- -- RW

DO3 Config o3C FAn 0 Lig no -- -- RW

DO4 Config o4C dEF 0 Lig no -- -- RW

Button 1 Short Config b1C noP tP noP no -- -- RW

Button 1 Long Config b1L PoF tP PoF no -- -- RW

Button 2 Short Config b2C dEF tP noP no -- -- RW

Button 3 Short Config b3C tP tP noP no -- -- RW

Button 3 Long Config b3L ECo tP PoF no -- -- RW

Button 4 Short Config b4C tn tP noP no -- -- RW

Button 4 Long Config b4L Lig tP PoF no -- -- RW

Password level1 PS1 0 0 999 no RW RW RW

Password level2 PS2 0 0 999 no -- -- RW

Password level3 PS3 0 0 999 no -- -- RW

Cabinet Light Control CLC Lig Lig LEC no -- -- RW


Source

Light off delay Lod 0 0 300 no Sec 1 -- -- RW

20 ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS

Downloaded from www.Manualslib.com manuals search engine


102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up

ight mode
1 Click: Temperature setpoint
nctionallity:
S1 ConfigSub /function:
S1C Up
S2 Config / S2C
102
ight mode
S3 Config / S3C
Available1 Click: Temperature
options are: setpoint
Sub function: Up
Stn for a temperature sensor (values given in Celsius)

102
nctionallity: Ldr for a light sensor (values given in Luminens)
Dig for a digital sensor with simple on/off indication
1 Click: Temperature setpoint
Sub function: Down

102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
ight mode
nctionallity: 1 Click: Temperature setpoint
S1 Application / Up
Sub function: S1A
S2 Application / S2A setpoint
1 Click: Temperature
Sub function: Down
S3 Application / S3A
ight mode
Available options are: setpoint
1 Click: Temperature
Sub function: Up
nC: Not connected
SCo: Temperature control
102 EuA: Evaporator temperature
1 Click: Temperature setpoint
Con: Condenser temperature (Condenser cleaning)
Sub function: Down
LS1: Light sensor (Ldr), Luminens, dedicated to Eco mode switching detection
nctionallity: LS2: Light sensor (Ldr), Luminens, dedicated to determining LED intensity
LS3: Light sensor(Ldr),
1 Click: Luminens, used for both Eco mode detection and
Temperature setpoint
determining LED intensity
Sub function: Down

ight mode
doC: Door contact, contact closed when door closed
1 Click: Temperature setpoint
doo: Door contact, contact open when door closed
Sub function: Up
1 Click: Temperature setpoint

102 Sub function: Down

DI Config / diC
nctionallity: This is the digital input used for a digital sensor or bus communications.
doC: Door contact, contact closed when door closed
doo: Door contact, contact open when door closed
ight mode bus: Modbus communication (used only for KoolProg)
1 Click: Temperature setpoint
diO: OneSubWire Communication
function: Up

1 Click: Temperature setpoint


Sub function: Down

D01 Config / D1C


CoP: Direct compressor control
Pil: Pilot Relay (No Zero Cross) – if using pilot relay to control a compressor,
this option must be used instead of CoP
Het: Heating application, inverse output.

1 Click: Temperature setpoint


Sub function: Down

ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 21

Downloaded from www.Manualslib.com manuals search engine


ight mode

102
nctionallity: 1 Click: Temperature setpoint
Sub function: Up

ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function:
D02 Config / o2CUp
D03 Config / o3C
ight mode
D04 Config / o4C
1 Click: Temperature setpoint
Sub function: Up
nO: not used
dEF: Electric Defrost Heater / Valve for hot gas
ALA: Alamr Output
102 1 Click: Temperature setpoint
Fan: FanSub
control
function: Down
LIG: Light control

102
nctionallity: 1 Click: Temperature setpoint
Sub function: Down

102
ight mode
nctionallity: 11 Click:
Click: Temperature
Temperature setpoint
setpoint
Sub
Subfunction:
function:Up
Down
6.2 Program the buttons
ight mode

102
nctionallity: 1 Click: Temperature setpoint
Button Sub
1 Config
function: (short
Up press) / b1C
Lower left button
Button 1 config (long press) / b1L
ight mode
1 Click:
Lower left Temperature setpoint
button
102
nctionallity: Sub function: Up
Button 2 Config (short press) / b2C
Upper left button
ight mode Button 3 Config (short press) / b3C
1 Click: Temperature setpoint

102
nctionallity: Upper right
Sub button
Subfunction:
function:Up
Down
Button 3 config (long press) / b3L
Upper right button
ight mode Button 141 Click:
Config (short
Click: Temperature
press) / b4C
Temperature setpoint
setpoint

102
nctionallity: Sub
Lower right function:
button
Sub function: Down
Up
Button 4 Config (long press) / b4L
Lower right button
ight mode 1 Click: Temperature setpoint
1Sub
Click: Temperature
Down setpoint
nctionallity: The buttons
function:
Sub function:
can be Up programmed as follows:

Short press function Long Press function


ight mode 1 Click:
tP: Increase Temperature setpoint
Setpoint tP: Increase Setpoint
1Sub
Click: Temperature
function: Down setpoint
tn: Decrease setpoint
Sub function: Up tn: Decrease setpoint
ECo: Toggle Eco mode ECo: Toggle Eco mode
Lig: Toggle light Lig: Toggle light
dEF: Toggle defrost
1 Click: Temperature setpoint dEF: Toggle defrost
SuP: ToggleSubSuper-Cool
function: Down
/Pull-down SuP: Toggle Super-Cool /Pull-down
diP : Increase display intensity diP : Increase display intensity
din : Decrease display intensity din : Decrease display intensity
Not operating
1 Click: Temperature setpoint
Sub function: Down ERC power ON/OFF

NOTE: Buttons 1, 3 and 4 can be assigned to operate with 2 functions (short press or long press).
1 Click: Temperature setpoint
NOTE: Your assignments may notSub befunction:
shownDown on the printed buttons. We advice to use this functionality
together with the fully integrated mounting model only.

22 ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS

Downloaded from www.Manualslib.com manuals search engine


102
nctionallity:

102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
6.3 Set passwords
ight mode
nctionallity: 1 Click: Temperature setpoint
Password Sub level
function:1Up
/ PS1
Password Level 2 / PS2
Password Level 3 / PS3
ight mode
1 Click: Temperature
These assign passwords setpoint
to the three levels of access. The password is a three-digit
Sub function: Up
number. Access levels are Shop, Service and OEM. You may not therefore have ac-
cess to change all the passwords. Passwords are entered by using the up and down
arrow buttons.
102 1 Click: Temperature setpoint
Danfoss Sub
advises against using passwords which are easy to remember or enter, for
function: Down
example 111, 222, 123 etc.

NOTE: When
1 Click: accessing the controller with 3 wrong password in a sequence ERC will
nctionallity: Temperature setpoint
automatically block access for 15 minutes.
Sub function: Down

ight mode 1 Click: Temperature setpoint


Sub
Subfunction:
function:Up
Down
6.4 Set lighting function

102 Cabinet Light Source Control / CLC


This parameter can be set to one of these alternatives to control the light in the
nctionallity: cabinet:
Lig: button only – the light will only come on when the light button on the ERC
102 is pressed (toggle functionality).
Ldo: door (and button if defined) only
LEC: economy (and button if defined) only
1 Click: Temperature setpoint
Sub function: Down

Light off delay / Lod


Number of seconds the light will stay on after the
door has been closed.

ERC 102 Reference manual – 6 CONFIGURATION OF INPUTS AND OUTPUTS 23

Downloaded from www.Manualslib.com manuals search engine


7. PARAMETERS
This chapter details all user-accessible parameters The access level can be set separately for each

102
in ERC 102 software 5.05. parameter using KoolProg software. There are three
levels of access – 1, 2 and 3. Level 1 is for shop access,
NOTE: Incorrect parameter settings can lead to level 2 for technicians and level 3 for OEMs. The access
inadequate cooling, excessive energy consumption, levels cannot be set using the buttons. Passwords for
unnecessary alarms and in the case of temperature- the different levels can however be altered for the
sensitive food storage, breaches in food hygiene level of access you have – for example a level 2 user
unctionallity: principles and regulations. Only a trained operator
should make changes to parameters.
can change the password for level 1 and level 2 but
not level 3.

INFO! Some parameters may be hidden to you. When


scrolling through menus, the parameters available will
Night mode have been pre-determined using KoolProg software.
Your access level will determine which parameters you 1 Click: Temperature setpoint
can view and edit. Sub function: Up

7.1 Thermostat / tHE

ERC 102 can handle both Celsius and


Fahrenheit. Changing from C to F and vice-versa
is done in the Display menu. When the change
is made, all temperature values are automatically 1 Click: Temperature setpoint
re-calculated and updated in all other
Sub function: Down
parameters accordingly.

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Thermostat tHE

Set point adjustment ratio SPr 0.5 0.0 1.0 no .1 -- -- RW

Differential diF 2.0 0.0 20.0 C/F r K .1 -- RW RW

High Set Point HSE 50.0/122.0 -50.0/122.0 80.0/176.0 C/F a °C/°F .1 -- RW RW

Low Set Point LSE -35.0/-31.0 -35.0/-31.0 80.0/176.0 C/F a °C/°F .1 -- RW RW

Air Temp Adj. tAd 0.0/0.0 0.0/0.0 20.0/36.0 C/F r K/°R .1 -- -- RW

24 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


ight mode
1 Click: Temperature setpoint

102
Sub function: Up

Set point / StP


nctionallity:
StP is visible with KoolProg software only. This parameter defines the desired
temperature (set point). In standard operation the set point is changed by
simply pressing the “temperature up / down” buttons on ERC102; for laboratory

102
ight mode
1 Click: Temperature
and assembly line yousetpoint
may opt for software controlled set point adjustment
Sub function: Up
(speed improvement)
1 Click: Temperature setpoint
Sub function: Down
nctionallity:
Set point adjustment ratio / SPr
The default value is set to 0.5 and the parameter is hidden by default.

102
ight mode
Spr defines the position of the setpoint in relation to cut-in and cut-out.
Spr = 0,51 Click:
setsTemperature setpointmid between cut-in and cut-out. Spr = 0 sets
the setpoint
Sub function: Up
the setpoint at the cutout. Spr =1 sets the setpoint at cut-in.

nctionallity:

102
1 Click: Temperature setpoint
Differential / diF Down
Sub function:
This defines the difference between the cut-out and the cut-in. The desired
ight mode
1 Click: is
temperature Temperature setpointby SPr and diF.
determined
Sub function: Up
nctionallity:

High Set Point / HSE


ight mode 11 Click:
Click: Temperature
Temperature setpoint
setpoint
Low SetSubPoint
Sub / LSE
function:
function: Down
Up
These parameters define the temperature range limit of the controller. Once set,
the desired temperatue (setpoint) can not go above HSE or below LSE.

LSE Sets the minimum value for the set point


HSE Sets the maximum value for the set point
1 Click: Temperature setpoint
Sub function: Down
Cut-in and cut-out are automatically calculated from the desired setpoint (set
bybuttons on the control) and the differential. By default, cut-out and cut-in are
0,5*DiF above or below the desired temperature.

1 Click:
TheTemperature setpoint temperature in the cabinet is 5 degrees, and the

102
Example: desired average
Sub function: Down
differential is set to 2 degrees:

nctionallity:

ight mode
1 Click: Temperature setpoint
Sub function: Up

Air Temperature Adjustment / tAd


This parameter is a relative value and allows adjustment of the
control sensor temperature.
For instance, at a measured temperature of 7*C and tAd set to -2K,
the input from the control sensor will be 5*C instead.

1 Click: Temperature setpoint ERC 102 Reference manual – 7 PARAMETERS 25


Sub function: Down
Downloaded from www.Manualslib.com manuals search engine
Night mode
1 Click: Temperature setpoint
Sub function: Up

7.2 Alarms / ALA

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
1 Click: Temperature setpoint
Alarm ALA
Sub function: Down
High Alarm delay Htd 30 0 240 no min 1 -- RW RW

Low Alarm delay Ltd 0 0 240 no min 1 -- RW RW

High Temp Alarm HAt 15.0/59.0 -50.0/-58.0 80.0/176.0 C/Fa °C/°F .1 -- RW RW

Low Temp Alarm LAt -50.0/-58.0 -50.0/-58.0 80.0/176.0 C/F a °C/°F .1 -- RW RW

Pulldown delay Pdd 240 0 960 no min 1 -- RW RW

Door Open delay dod 2 0 60 no min 1 -- RW RW

Alarm Buzzer Duration Abd 0 0 999 no min 1 -- RW RW

Auto Clearance of
ACA yES no yES no 1 -- RW RW
Alarm/Error

26 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up

102
ight mode
1 Click: Temperature setpoint
High Temp AlarmUp/ HAt
Sub function:
Low Temp Alarm / Lat
102
nctionallity: High temperature alarm and low temperature alarm allow for individual alarm
setpoints. Both are absolute values. By setting HAt to the maximum value and LAt
to the minimum value, alarms will be deactivated.
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down

102
ight mode
1 Click: Temperature setpoint
High Alarm Delay
Sub function: Up/ Htd
1 Click: Temperature setpoint
Low Alarm Delay / Ltd
Sub function: Down
nctionallity: These parameters express the number of minutes to wait before sounding an
alarm once the High/Low Temp Alarm temperature is reached. Immediately prior
to the alarm sounding, another check of the temperature is made to see if the
ight mode temperature
1 Click: is still in the
Temperature alarm zone; if it is not, the then the alarm is not sounded.
setpoint
In most Sub
situations,
function: Upthe Low Alarm Delay will be set to 0 to warn about too low a

102
1 Click: Temperature setpoint
temperature immediately.
Sub function: Down

Pulldown Delay / Pdd


1 Click: Temperature setpoint
nctionallity: Normally, it is not necessary or desirable to sound an alarm during a pull down
Sub function: Down
(the initial phase of reaching the desired temperature). This parameter prevents
the High Temp Alarm HAt sounding during pull down and after a defrost for the
ight mode number1of minutes set for the parameter.
Click: Temperature setpoint
Sub function: Up
NOTE: It does not apply to the Low Temp Alarm LAt.
1 Click: Temperature setpoint
Sub function: Down

Door Open Delay / dod

102 It is possible to indicate to customers that a door has accidentally been left open.
This parameter sets the delay in minutes before the alarm sounds. This is useful in
environments where customers / users may hold the door open while making their
selection. If the door is closed again before the set number of minutes is reached,
nctionallity: the alarm does not sound.

NOTE: A1Sub
Click: Temperature setpoint
door sensor is required if this parameter is to be activated.
function: Down
ight mode
1 Click: Temperature setpoint
Sub function: Up

Alarm Buzzer Duration / Abd


The ERC 102 alarm sounds for 10 seconds, followed by silence for 50 seconds. One
alarm sequence therefore lasts 60 seconds. These values cannot be changed. This
parameter determines how long in minutes an audible alarm will continue while
there is still a reason to have an alarm. If set to 999, the alarm will continue to
sound until the reason for the alarm is cleared – for example the temperature has
dropped enough or the door closed. In some cases, it may be necessary for a user
1 Click: Temperature setpoint
or technician to take action in order to clear the alarm. If set to 0, the alarm will
Sub function: Down
never sound.

ERC 102 Reference manual – 7 PARAMETERS 27

Downloaded from www.Manualslib.com manuals search engine


ight mode
1 Click: Temperature setpoint
Sub function: Up

Auto Clear of Alarm / Error / ACA


If this parameter is set to nO:
The alarm status will not disappear automatically even if the condition which
caused the alarm is no longer valid or present.
If set to yES:

102
As soon as the condition which caused the alarm is no longer valid or present, the
1 Click: Temperature setpoint
alarm status will automatically change back to inactive. There will be no trace of
Sub function: Down
the alarm having occurred.
In general, Glass Door Merchandise applications will be set to yES and Commercial
Fridges and Freezers set to nO. For example, if the temperature goes too high for
a period there may be food safety considerations in a freezer containing food but
unctionallity: not in a fridge with cold drinks.

Night mode
1 Click: Temperature setpoint
Sub function: Up

7.3 Compressor / CoP

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Compressor CoP

Min run time Crt 0 0 30 no1 Click:


minTemperature
1 setpoint
-- RW RW

Min Stop time CSt 0 0 30 no Sub function:


min Down
1 -- RW RW

Max Off time Cot 0 0 480 no min 1 -- -- RW

Error run time Ert 0 0 60 no min 1 -- -- RW

Error stop time ESt 1 0 60 no min 1 -- -- RW

Minimum cut-in voltage uLi 0 0 270 no Vac 1 -- -- RW

Minimum cut-out voltage uLo 0 0 270 no Vac 1 -- -- RW

Maximum voltage uHi 270 0 270 no Vac 1 -- -- RW

Power On Delay Pod 300 0 300 no Sec 1 -- RW RW

Power Factor PFA 0 -90 90 no Degree 1 -- -- RW

Initial cut in iCi no no yes no 1 -- R- RW

Compressor door open delay Cdd 0 0 15 no min 1 -- RO RW

28 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


ight mode
1 Click: Temperature setpoint
Sub function: Up

102 Minimum Run Time / Crt


This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must run before a
nctionallity: Temperature cut-out can take effect. For example, if the temperature sensor indi-
cated that the cut-out temperature has been reached, but the number of minutes
set in this parameter have not elapsed since the compressor last started, then the
ight mode
compressor1 Click:will continue.
Temperature It will only stop once the duration given by Crt has been
setpoint
1Sub
Click: Temperature
function: Up setpoint
reachedSub – provided the temperature is still low enough.
function: Down
Crt thus overrides the cut-out.

102 Minimum Stop Time / CSt


This parameter is a number of minutes from 0 to 30.
It determines the minimum number of minutes the compressor must remain idle
nctionallity: before a Temperature cut-in can take effect. For example, if the temperature sensor
indicates that the cut-in temperature has been reached, but the number of minutes
set in this parameter have not elapsed since the compressor last stopped, then the
102
ight mode
compressor will stay off. It will only start once the duration given by CSt has been
11 Click: Temperature
Temperature setpoint
reachedSub –Click:
provided
Subfunction:
function:Up
thesetpoint
Down
temperature is still high enough.
CSt thus overrides the cut-in.

102
nctionallity:

Maximum Off Time/ Cot


ight mode This is the maximum time in minutes the compressor is allowed to idle – up to 480
nctionallity: 1 Click: Temperature setpoint
minutes.Sub Cot is setUpto zero by default (inactive). If ERC102 is to be used on a draft
function:
beer (ice bank) application, this parameter can be used to control the ice thickness.

ight mode
1 Click: Temperature setpoint
Error Run
SubTime
function:/ Up
Ert
Error Stop Time / ESt setpoint
1 Click: Temperature
Sub function: Down
These two parameters only become active in the unlikely event of a broken tem-
perature sensor. They are then used to run the application in safety mode. At the
same time the sensor error will be shown in the display.

Ert and ESt values are based on OEM experience and are by default inactive.
1 Click: Temperature setpoint
Ert and ESt define the duration the compressor will run (Ert) and be idle (ESt).
Sub function: Down
Example: Ert = 4 [min] and ESt = 16 [min] will provide an average cooling system
activity of 20%.
1 Click: Temperature setpoint
Sub function: Down

ERC 102 Reference manual – 7 PARAMETERS 29

Downloaded from www.Manualslib.com manuals search engine


102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up

ight mode
nctionallity: 1 Click: Temperature setpoint
Minimum Sub cut-in voltage / uLi
function: Up
Minimum cut-out voltage / uLo
Maximum voltage / uHi
ight mode
1 Click: Temperature setpoint
These three parameters provide voltage protection to the compressor. Start by
Sub function: Up
setting uHi, followed by uLo and uLi.

uLi: When the compressor is due to start, the voltage of the power supply will be
1 Click: Temperature setpoint
checkedSuband the compressor will only be allowed to start if it is at least the value
function: Down
given in this parameter.

uLo: When the


1 Click: compressor
Temperature setpointis running, it will be switched off if the voltage goes
Sub function:
below that given inDown
this parameter.

uHi: When the compressor is running, it will be switched off if the voltage exceeds
1 Click: Temperature setpoint
that given in this parameter. If the compressor is already stopped, it will remain
Sub function: Down

102 switched off.

nctionallity:
102
ight mode
1 Click: Temperature setpoint
nctionallity: Sub function: Up

102
ight mode
Power On Delay
1 Click: / Podsetpoint
Temperature
Sub function: Up
This is the delay in seconds between power-on and the compressor being
activated. Depends on the Power on Temperature setting as explained below.
Functionallity:
102 Power Factor / PFA
This value is hidden by default. The parameter is used by the Zero Cross function
O/Night mode to optimize1 Click:
the Temperature
switchingsetpoint
position of the relay contact.
1 Click: Temperature setpoint
unctionallity: SubSub function:
function: DownUp
Warning: Do not change without first consulting your local
Danfoss representative.
Night mode Initical 1Cut-in
1Click: / iCi setpoint
Click:Temperature
Temperature setpoint
Sub
Sub function:
function: Down
Up
if the control temperature is between cut-in and cut-out at power up customers can
determine if the compressor shall start immediatly (yes) or wait for cut-in tempera-
ture to start (no).
Power on Temperature / PoT
This parameter is used to accelerate the first application test on the OEM assembly
ht line; if the cabinet temperature
1 Click: Temperature setpoint is higher than this parameter the Power On Delay is
Sub function: Down
overruled and the outputs are activated without delay.

Compressor Door Open Delay / Cdd


This parameter sets the delay in minutes before the compressor stops when the
door is opened. If set tosetpoint
1 Click: Temperature zero, the function is disabled.
Sub function: Down

30 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.4 Defrost / dEF

Note: ERC controllers feature Safe Defrost


functionality (patents pending) by de-
fault. This function ensures proper defrost
under poor power conditions.

For more details please contact Danfoss.

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Defrost dEF 1 Click: Temperature setpoint


Def type dFt no no Hgd no Sub function: Down -- RW RW
Def reset temp drt 5 0 80 C/F a °C 1 -- RW RW

Def Min Interval dii 6 0 96 no hour 1 -- RW RW

Def Max Interval dAi 7 0 96 no hour 1 -- RW RW

Def Min Time dit 5 0 240 no min 1 -- RW RW

Def Max time dAt 30 0 480 no min 1 -- RW RW

Drip off time dot 0 0 60 no min 1 -- -- RW

Fan delay after Defrost Fdd 0 0 60 no min 1 -- -- RW

Fan start Temp Ftd 25.0/77.0 -25.0/13.0 25.0/77.0 C/F a °C/°F .1 -- -- RW

Defrost Fan on dFA no no yES no 1 -- -- RW

Initial Defrost Interval idi 3 0 96 no hour 1 -- -- RW

Initial Defrost Duration idd 100 0 999 no 1 -- RW RW

Defrost on compressor
dCt no no yES no 1 -- -- RW
time

ERC 102 Reference manual – 7 PARAMETERS 31

Downloaded from www.Manualslib.com manuals search engine


ight mode
1 Click: Temperature setpoint

102 Sub function: Up

nctionallity: Defrost Type / dFt


When set to nO, the defrost function is disabled and no automatic defrosting

102
ight mode
will occur.
1 Click: Temperature setpoint
When setSubto EL orUp
function: nAt, electrical, natural or off-cycle defrosting is used. An ad-
ditional setting of Hgd (hot gas defrosting) is available.
nctionallity:
1 Click: Temperature setpoint

102
Sub function: Down
Terminate Temperature / dtt
ight mode This parameter defines at what temperature the defrost cycle will stop.
1 Click: Temperature setpoint
The temperature is given by the evaporator sensor or by the cabinet
Sub function: Up
temperature sensor if no evaporator sensor is used.
nctionallity:

Defrost reset temperature / drt

102
ight mode 1 Click:counter
The defrost Temperature
issetpoint
saved and restored at power-up, but if the temperature
1Sub
Click: Temperature
function: Down setpoint
sensor, used for defrost,
Sub function: Up is higher than this value at power-up, it is assumed that
the evaporator is free of ice and the defrost counter will be cleared.

nctionallity:

102 Minimum Interval / dii


This parameter can besetpoint
1 Click: Temperature
Sub function: Down
set to between 0 and 96 hours and defines the minimum
ight mode time period between the start of two defrost cycles. Once the minimum interval
1 Click: Temperature setpoint
has expired, the defrost
Sub function: Up cycle will start at the following cut-out or once the maxi-
nctionallity: mum interval dAi has been reached.

ight mode Maximum Interval


1 Click: / dAi
Temperature setpoint
1Sub
Click: Temperature
function: Down setpoint
This parameter can
Sub function: Up be set to between 0 and 96 hours and defines the maximum
time period between the start of two defrost cycles.
102
Minimum Time / dit
nctionallity: This parameter can be set to between 0 and 240 minutes and defines the mini-
mum duration of a defrost
1 Click: Temperature cycle. During this period, the ERC 102 will not check
setpoint
Sub function: Down
the temperature. Once the minimum time has expired, the temperature will be

102
ight mode
checked and if the Terminate Temperature dtt has been reached, the defrost
1 Click: Temperature setpoint
cycle willSubend. If dtt has not been reached, defrost will continue until either dtt is
function: Up
reached or the Maximum Time dAt reached, whichever occurs first.
1 Click: Temperature setpoint
Sub function: Down
nctionallity:
Maximum Time / dAt
This parameter can be set to between 0 and 240 minutes and defines the maxi-
ight mode mum duration of a defrost
1 Click: Temperature cycle.
setpoint
The ERCSub
102 will not
function: Up allow a maximum time to be entered which is less than the
minimum time, or a minimum time which is more than the maximum time.

Drip Off1 Time / dot setpoint


Click: Temperature
This is only used with
Sub function: Downan electrical heater. This parameter can be set to between
0 and 60 minutes and defines how long the delay is between the heater being
switched off and the compressor starting again.

32 ERC 102 Reference manual – 7 PARAMETERS


1 Click: Temperature setpoint
Downloaded from www.Manualslib.com manuals search engine
Sub function: Down
102
ight mode
1 Click: Temperature setpoint
Sub function: Up

nctionallity:

Fan Delay after Defrost / Fdd


ight mode This parameter can be set to between 0 and 60 seconds and defines how
1 Click: Temperature setpoint
long theSub
delay is between
function: Up the start of the compressor after defrost and the
fan starting again.

102 Fan Start Temperature / Ftd


This only1 Click: Temperature
applies setpoint
if an evaporator temperature sensor is fitted. This parameter
Sub function: Down
nctionallity: determines at what evaporator temperature the fan will start after a defrost cycle

02
is complete.
If the time set in Fdd occurs before the temperature set in Ftd, the fan will start
ight mode in line with Fdd. If the temperature set in Ftd occurs first, then the fan will start in
1 Click: Temperature setpoint
line withSubFtd. It is Up
function: therefore a case of whichever parameter’s setting is reached first
1 Click: Temperature setpoint
ctionallity: which determines when the fan starts.
Sub function: Down

ht mode Defrost Fan On / dFA


1 Click: Temperature setpoint
Set to Sub
yES,function:
the fanUp will constantly run during defrost cycles.
02 Set to nO, the fan will not run during defrost cycles.

ctionallity: Initial Defrost Interval / idi


The initial defrost interval determines the time for first defrost after power-up. The
1 Click: Temperature
initial defrost is mainlysetpoint
intended for factory testing of the defrost functionality and
Sub function: Down
t mode can be set to expire after a number compressor cycles according to the setting
1 Click: Temperature setpoint
of parameter iddUp. During normal operation, the defrost counter will be saved in
102
Sub function:
memory and restored after power loss, making the initial defrost unnecessary.
1 Click: Temperature setpoint
Sub function: Down
nctionallity: Initial Defrost Duration / idd
The initial defrost duration is the number of compressor cycles before the initial
defrost is deactivated.
ight mode 0: idi No initial defrost
1 Click: Temperature setpoint
1-998: number of Up
Sub function: compressor cycles before deactivation
999: Initial defrost always active.
1 Click: Temperature setpoint
Sub function: Down
Defrost On Compressor Time / dCt
If this parameter is set to yES, then defrost cycles are based on the total time
the compressor has been running.

If this parameter is set to nO, then defrost cycles are related to elapsed time,
regardless of how long and how often the compressor has been on.

1 Click: Temperature setpoint


Sub function: Down

ERC 102 Reference manual – 7 PARAMETERS 33

Downloaded from www.Manualslib.com manuals search engine


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.5 Fan / FAn


The fan parameters are all related to energy saving,
and to redistribution of air within the cabinet to
reduce the amount of energy spent on cooling.

102 ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Fan FAn
nctionallity: Fan always On FAo yES no yES no 1 Click: Temperature
1 setpoint
-- -- RW

102 Fan stop time on door open


Fan On Delay
Fdt
Fod
999
0
0
0
999
240
no
no
Sub function: Down -- -- RW
Sec
Sec
1
1 -- -- RW
ight mode Fan Stop delay FSd 0 Temperature
0 setpoint240 no Sec 1 -- -- RW
1 Click:
Fan On Cycle FoC Sub function:
0 Up 0 960 no Sec 1 -- -- RW
nctionallity: Fan Stop Cycle FSC 0 0 960 no Sec 1 -- -- RW

102
ight mode
Fan Always On / FAo
1 Click: Temperature setpoint
If this parameter
Sub function:is
Upset to yES, all other parameters in this section
about the fan are deactivated.

102
nctionallity: NOTE: If FAo is set to nO, then the following parameters will be applied.

Fan stop time on door open: Fdt


The maximum time the fan will be stopped after the door has been opened.
ight mode
nctionallity: 1 Click:
0: fan will notTemperature
stop undersetpoint
opening
Sub
Subfunction:
function:Up
Down
1-998: number of seconds fan will be stopped during door opening
999: fan will be stopped as long as the door is open
ight mode

102
1 Click: Temperature setpoint
Fan On SubDelay / Fod
function: Up
1 Click: Temperature setpoint
Fan StopSubDelay / FSd
function: Down
If this parameter and FSd are both set to zero then the fan runs whenever the

102
nctionallity: compressor runs.

Fod defines the fan delay


ight mode
(in seconds) after a compressor
nctionallity: 1 Click: Temperature setpoint
cut-in. Sub
Subfunction:
function:Up
Down
FSd defines the fan delay after a
compressor cut-out.
ight mode 1 Click: Temperature setpoint
Fan On Sub
Cycle / FoC
Subfunction:
function: Up
Down
Fan Stop Cycle / FSC
When the compressor is off, and FoC or FSC are not zero, the fan runs in cycles
according to FoC and FSC.
Example: FoC = 120 [sec] and FSC = 120 [sec] means that the fan runs for half the
time when the compressor is off. When the compressor is on, the fan is always on
(according to FAo and Fod).
1 Click: Temperature setpoint
Sub function: Down

34 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine 1 Click: Temperature setpoint


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.6 Energy Management / Eng

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Energy management Eng
Shop Light Day SLd 50 0 100 no 1 Click:
% Temperature
1 setpoint
RW RW RW
Shop Light Night SLn 50 0 100 no % 1 RW RW RW
Sub function: Down
102 Eco Activity delay
Eco Light delay
EAd
ELd
0
5
0
0
360
10
no
no
min
min
1
1
RW RW RW
-- RW RW
Light Blocking delay Lbd 0 0 360 no min 1 -- RW RW
Eco Temperature Offset Eto 4.0/7.2 0,0 10.0/18.0 C/F r K/°R .1 -- RW RW

102
nctionallity:
NOTE: Some of these parameters require the installation of the Danfoss Ambient Light Sensor.
ight mode
nctionallity: The Danfoss USB Gateway in combination
1 Click: Temperature setpoint
with KoolProg software allows for real time measurement of the
Sub function: Up
current light intensity. Danfoss recommends testing and adjusting SLd and SLn values according to custom-
ers’ specific needs.
ight mode
1 Click: Temperature setpoint

102 Shop Light Day /Up


Sub function: SLd
Shop Light Night / SLn
These parameters are set as the percentage of the maximum light and determine
when the device moves into or out of Eco mode for power-saving purposes.
nctionallity:
SLd is the amount of ambient light which will cause the device to move to normal /
102
ight mode
serving mode from Eco mode (normally occurs in the morning).
11 Click:
Click: Temperature
Temperature setpoint
setpoint
Subfunction:
Sub function:Up
Down
SLn is the amount of ambient light which will cause the device to move to Eco
mode from normal / serving mode (normally occurs in the evening).
nctionallity:
1 Click: Temperature setpoint
Eco Door SubDelay
function:/ Down
EAd
ight mode
The transition from Eco to normal mode and vice versa occurs on a change in light
1 Click: Temperature setpoint
level or door activity.
Sub function: Up

NOTE: A door sensor is required.

Eco Light Delay / ELd


1 Click: Temperature setpoint
This parameter causes a delay to the switch from Normal to Eco mode when the
Sub function: Down
shop lights are switched on or off. The ambient light sensor detects the change in
light level and causes a switch mode. With this parameter set to zero, the switch
off mode occurs immediately. If not set to zero (max: 10 minutes), then the change
will be delayed by the number of minutes set.

1 Click: Temperature setpoint


Sub function: Down ERC 102 Reference manual – 7 PARAMETERS 35

Downloaded from www.Manualslib.com manuals search engine


102
Light Blocking delay / Lbd
If the cooler is placed where the ambient light is unstable, the ambient light sensor
nctionallity: can cause the cooler to toggle between ECO and normal mode.

102
The light blocking delay disables the light-sensor for a given time after ambient
light change from bright to dark, so that the cooler stays in ECO mode for at least
ight mode this time.1 Click:
When the cooler is in serving or pull-down mode, the light sensor is
Temperature setpoint
de-activated and Up
Sub function: a change to ECO mode will be determined by the door-sensor.
0: No blocking of the ambient light sensor.

unctionallity: Eco Temperature Offset / Eto


This parameter gives a relative temperature in degrees. It is the difference in
temperature for Eco mode operation compared to Normal mode.

NOTE: Setting a temperature offset may be illegal in


Night mode some jurisdictions. 1 Click: Temperature setpoint
1 Click: Temperature setpoint Sub function: Up
Sub function: Down

7.7 Pull Down / Pud


Pull down (sometimes known as Super Cool) is
a procedure for improving cooling performance,
accelerating the time used to reach the desired
temperature. Pull Down settings overrule all
other settings.

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv 1 Click: Temperature setpoint
Shop Ser OEM

Pull Down Pud


Sub function: Down
Pull-down Initiate Pit 50.0/122.0 -40.0/-40.0 50.0/122.0 C/F a °C/°F .1 -- -- RW
­Temperature

Pull-down Cycling PCy 30 0 360 no min 1 -- -- RW

Pull-down defrost Interval Pdi 15 0 48 no hour 1 -- -- RW

Pull-down duration Pdd 24 0 48 no hour 1 -- -- RW

Pull-down limit temp PLt 0.0/32.0 -55.0/-67.0 55.0/131.0 C/F a °C/°F .1 -- -- RW

Pull-down reduction Prt 0.1/0.2 0,0 10.0/16.0 C/F r K/°R .1 -- -- RW


temp △t

36 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


102
nctionallity:

ight mode

102
1 Click: Temperature setpoint
Sub function: Up

nctionallity: Pull Down Initiate Temperature / Pit


This parameter indicates the temperature which causes a pull down to start. If the
temperature measured inside the cabinet exceeds this value for longer than one

102
ight mode hour, then pull down will start. The compressor will have already cut-in, so the only
1 Click: Temperature setpoint
effect is Sub
to function: Up
stop defrost cycles until the desired temperature is reached. The period
of one hour is fixed and cannot be altered.

nctionallity: Pull Down


1 Click: Temperature setpoint
Cycling / PCy
Sub function: Down
This is the duration in minutes of the compressor cycling at the reduced set point
temperature. Once the desired Pull Down Limit Temperature PLt has been reached
ight mode
during Pulldown, the compressor will continue to cycle on / off for the duration of
102
1 Click: Temperature setpoint
Sub function: Up
PCy. At the end of the period defined by PCy, the Set Point temperature will return
to normal and Pulldown will cease.

1 Click: Temperature setpoint


nctionallity: Pull Down Defrost
Sub function: Interval / Pdi
Down
Even though most applications do not need Defrost during Pull Down, an extended
102
ight mode
defrost during pull down can be applied. This is the time between defrost cycles
during Pull Down. It is setpoint
measured in hours and can be up to 48 hours. During Pull
1 Click: Temperature
Down, this settingUpoverrides the Defrost Interval and Defrost Time settings (see the
Sub function:

nctionallity: Defrost section).

1 Click: Temperature setpoint


Pull Down Duration
Sub function: Down/ Pdd
ight mode You can 1choose to limitsetpoint
the maximum Pull Down time. Once this time value
102
Click: Temperature
(max. 48Sub
hours) isUp
function: reached, Pull Down will stop regardless of whether the desired
pull-down temperature has been reached.

nctionallity: Pull Down Limit Temperature / PLt


This parameter sets thesetpoint
1 Click: Temperature minimum allowed temperature during pull-down,
Sub function: Down
In order to protect valuable contents you must always specify the absolute mini-
ight mode
mum temperature allowed
1 Click: Temperature setpointin your application.
Sub function: Up
For Glass Door Merchandisers 0°C/32°F protects bottles from freezing;
for Commercial Fridges you may opt for a slightly higher temperature (e.g. 2°C)
1 Click: Temperature setpoint
Pull Down Reduction
Sub function: Down Temperature Δt / Prt
ERC 102 calculates a lower set-point during Pull Down mode to increase the cool-
ing capacity of your appliance. For each hour the cabinet temperature is above the
Pull down initiate temperature, the set-point is reduced with the value of Prt.

ERC 102 Reference manual – 7 PARAMETERS 37


1 Click: Temperature setpoint
Downloaded from www.Manualslib.com manuals search engine
Sub function: Down
Night mode
1 Click: Temperature setpoint
Sub function: Up

7.8 Automatic Heater Control / AHC


Automatic Heater Control applies reverse cooling
mode (heating) to your refrigeration appliance.
This feature requires:

A) that your appliance is exposed to ambient tem-


peratures below the desired temperature in your
cabinet (e.g. very cold climates and outdoor use)

B) a special heater (for example a large defrost


heater) built in to your appliance.

ERC menu Default Min Max Unit 1 Click:


Unit Temperature
Scale setpoint
Default Access
code Conv Sub function: Down Shop Ser OEM

Auto-Heater Control AHC

Automatic heater mode AuH no no yES no -- -- RW


enable

Energy mode delay End 60 0 360 no min 1 -- -- RW


o
Heater displacement Hdi 2.0/3.0 0.0/0.0 50.0/90.0 C/F r K/ R .1 -- -- RW
temperature

102
nctionallity:

102
ight mode
1 Click: Temperature setpoint
Sub function: Up

nctionallity:
Automatic Heater Mode Enable / AuH

102
This setting is normally set to nO.
ight mode
When set to yES,
1 Click: parameters
Temperature setpoint End and Hdi apply.
Sub function: Up

nctionallity:
Energy 1Mode Delay /setpoint
Click: Temperature End
This is the
Subdelay inDown
function: minutes between the heater and the compressor operation.
ight mode
The heater1 Click:
is Temperature
not allowedsetpoint
to start until this number of minutes has expired after
Sub function: Up
the compressor has cut out and vice versa.

Heater Displacement Temperature / Hdi


1 Click: Temperature setpoint
This is the
Subtemperature
function: Down relative to (below) the desired temperature.

38 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine 1 Click: Temperature setpoint


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.9 Condenser Protection / Con


NOTE: A condensor temperature sensor is
required to use these parameters.
Condenser protection is generally used in dusty
environments where the condenser may accumu-
late a layer of dust or dirt and therefore be at risk of
overheating.

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Condenser Protection Con


1 Click: Temperature setpoint
Condenser Alarm Limit CAL 80/176 0/32 85/185 C/F a
Sub°C/°F
function:1 Down -- -- RW
Condenser Block Limit CbL 85/185 0/32 85/185 C/F a °C/°F 1 -- -- RW

Condenser OK limit CoL 60/140 0/32 85/185 C/F a °C/°F 1 -- -- RW

Condenser Low Limit CLL 5 -20/-4 20/68 C/F a °C/°F 1 -- -- RW

102
nctionallity:

102
ight mode
1 Click: Temperature setpoint
Sub function: Up

nctionallity:

102 Condenser Alarm Limit / CAL


ight mode
This parameter sets thesetpoint
1 Click: Temperature temperature for the condenser at which an alarm will
Sub function: Up
be generated.
nctionallity:

102
ight mode
Condenser Block Limit / CbL
1 Click: Temperature setpoint
This parameter
1Sub
sets
function:
Click: Up
thesetpoint
Temperature
temperature which if reached will cause the compressor
to switchSuboff.
function: Down
nctionallity:

Condenser OK Limit / CoL


ight mode
1 Click: Temperature
This parameter sets the setpoint
temperature at which the compressor is allowed to
1Sub function:
Click: Up
Temperature setpoint
start again after the
Sub function: Downtemperature set in CbL above has been exceeded and the
compressor stopped.

Condenser Low Limit / CLL


This parameter sets the
1 Click: Temperature lowest (condenser) temperature at which the
setpoint
compressor is allowed
Sub function: Down to start.

ERC 102 Reference manual – 7 PARAMETERS 39

Downloaded from www.Manualslib.com manuals search engine 1 Click: Temperature setpoint


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.10 Display / diS

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Display diS

Display Unit CFu -C -C -F no 1 Click: Temperature RW


setpoint
RW RW

Display Resolution rES 0.1 0.1 1 no Sub function: Down -- -- RW


Display Range Limit rlt no no yES no -- -- RW

Display Delay ddL 0 0 10 no Sec 1 -- -- RW


o
Display Offset doF 0.0/0.0 -10.0/-18.0 10.0/18.0 C/F r K/ R -- -- RW

102 Lock-time After defrost dLt 15 0 60 no min 1 -- -- RW

Show Economy state SEC no no yES no -- -- RW

Show Pull Down state SSC no no yES no -- -- RW


nctionallity:
102 Show Defrost SdF yES no yES no -- -- RW

Display Intensity din 10 1 10 no 1 RW RW RW

ight mode
This section deals with parameters1for the
Click: display.setpoint
Temperature
nctionallity: Sub function: Up
NOTE: Some display parameters can be set in such as way that they may be illegal in some jurisdictions. Please
check local legislation.
ight mode
1 Click: Temperature setpoint
DisplaySub
Unit / CFu
function: Up
This parameter sets the display to Fahrenheit or Celsius. Switching from one to the
102 other will cause all temperature settings to be automatically updated accordingly.

Display Resolution / rES


nctionallity: This parameter can be set to 0.1, 0.5 or 1 and affects the way the temperature is
displayed. With the parameter set to 1, the display will only ever show tempera-
1 Click: Temperature setpoint
tures rounded to the nearest whole degree. At 0.5, it will round the temperature to
Sub function: Down
ight mode
the nearest half degree for display.
1 Click: Temperature setpoint
For example, 3.3 degrees will be shown in the display as 3.5 degrees and 3.9 as 4.0.
Sub function: Up
With the parameter set to 0.1, no rounding occurs.
1 Click: Temperature setpoint
This parameter does
Sub function: Down not affect the temperature itself, merely the display.

Display Range Limit / rLT


In some Point of Sales applications you may want to show the desired instead of
the real temperature. This parameter sets whether the displayed temperature is
the actual temperature or whether it is restricted to the cut-in / cut-out limits. Set
to nO means that the actual temperature will de displayed.
The parameter is set to nO by default.

1 Click: Temperature setpoint


40 Sub function: Down
ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


ight mode
1 Click: Temperature setpoint
Sub function: Up

Display Delay/ ddL


In order to provide a realistic temperature appearance for an application,
a display delay can be set.
The parameter sets the time constant τ (tau) of the moving average filter
for the display.
Physically, one time constant represents the time it takes the system’s
step-response to reach 66% of its final value and five time-constants the time
1 Click: Temperature setpoint
it takes to reach 99% of its final value.
Sub function: Down
The parameter can be set from 0 to 10 minutes.

102
nctionallity:

102
ight mode
1 Click: Temperature setpoint
Sub function: Up

nctionallity:

Display Offset / doF


This parameter is a relative value and allows the temperature displayed to be
102
ight mode
1 Click: Temperature setpoint
differentSub
tofunction:
the temperature
Up measured. For instance, at a measured temperature
of 7°C and doF set to -2K, the displayed temperature will be 5°C instead.

nctionallity:
Lock Time After Defrost / dLt
In order1not
Click:to
Temperature
show a setpoint
rising temperature during defrosting, the displayed tem-
102
ight mode
Sub function: Down
perature is locked at the temperature shown at the start of the defrost cycle for the
1 Click: Temperature setpoint
numberSubof function:
minutes Up set in this parameter.
0 = no lock.
nctionallity:
1 Click: Temperature
Show Economy Statesetpoint
/ SEC
102
ight mode
ECO mode.
Sub function: Down
If set to yES, this parameter causes the display to show ECO when the system is in
1 Click: Temperature setpoint
Sub function: Up
If set to nO, the temperature continues to be displayed.
nctionallity:

Show Pull down state / SSC


1 Click: Temperature setpoint
ight mode If set to yES, this parameter causes the display to show SC when the system is in
1Sub function:
Click: Down setpoint
Temperature
Pull Down Sub mode.
function: Up
If set to nO, the temperature continues to be displayed.

Show Defrost / SdF


If set to1yES,
Click: Temperature setpoint
this parameter causes the display to show DEF when the system is in
Sub function: Down
defrost mode. If set to nO, the temperature continues to be displayed.

ERC 102 Reference manual – 7 PARAMETERS 41

Downloaded from www.Manualslib.com manuals search engine 1 Click: Temperature setpoint


ight mode
1 Click: Temperature setpoint
Sub function: Up

Display Intensity / din


ERC 102 can have its display intensity (brightness) set in one of two ways:
A) with a Danfoss ambient light sensor attached, the brightness of the display is
adjusted automatically according to the ambient light level (see the Assignments
section)
B) when no ambient light sensor is attached, the display intensity can be set to
a fixed intensity.
1 Click: Temperature setpoint
Sub function: Down
Both options are on a scale of 1 to 10, where 10 is the brightest.

7.11 Assignments / ASi

For more details on how to set parameters


- see chapter 6.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM

Assignments ASi

S1 Config S1C Stn Stn dig no -- -- RW

S2 Config S2C Stn Stn dig no -- -- RW

S3 Config S3C Stn Stn dig no -- -- RW

S1 Application S1A SCo nC doo no -- -- RW

S2 Application S2A nC nC doo no -- -- RW

S3 Application S3A nC nC doo no -- -- RW

DI Config diC dio doC dio no -- -- RW

DO1 Config o1C CoP CoP HEt no -- -- RW

DO2 Config o2C dEF 0 Lig no -- -- RW

DO3 Config o3C FAn 0 Lig no -- -- RW

DO4 Config o4C Lig 0 Lig no -- -- RW

Button 1 Short Config b1C noP tP noP no -- -- RW

Button 1 Long Config b1L PoF tP PoF no -- -- RW

Button 2 Short Config b2C dEF tP noP no -- -- RW

Button 3 Short Config b3C tP tP noP no -- -- RW

Button 3 Long Config b3L ECo tP PoF no -- -- RW

Button 4 Short Config b4C tn tP noP no -- -- RW

Button 4 Long Config b4L Lig tP PoF no -- -- RW

Pass-word level1 PS1 0 0 999 no RW RW RW

Pass-word level2 PS2 0 0 999 no -- RW RW

Pass-word level3 PS3 0 0 999 no -- -- RW

Cabinet Light Control CLC Lig Lig LEC no -- -- RW


Source

Door close delay dCd 0 0 300 no Sec 1 -- -- RW

Light off delay Lod 0 0 300 no Sec 1 -- -- RW

42 ERC 102 Reference manual – 7 PARAMETERS

Downloaded from www.Manualslib.com manuals search engine


Night mode
1 Click: Temperature setpoint
Sub function: Up

7.12 Service Information / Ser

The parameters in the following section are READ


ONLY and cannot be changed by the user. They pro-
vide information for technicians and OEM users.

NOTE: the only parameters that can be configured are:


oEL, oEn, oEH.
These parameters allow OEMs to enter their own
product code.

ERC menu Default Min Max Unit Unit Scale Default Access
code Conv 1 Click: Temperature setpoint
Shop Ser OEM

Service SEr Sub function: Down


DI Sdi --- oFF on no -- R- R-

Voltage value uAC --- 0 270 no Vac 1 -- R- R-

DOs Status ouS --- IIII IIII no -- R- R-

Relay 1 counter rL1 --- 0 999 no 1000 1000 -- R- R-

Relay 2 counter rL2 --- 0 999 no 1000 1000 -- R- R-

Relay 3 counter rL3 --- 0 999 no 1000 1000 -- R- R-

Relay 4 counter rL4 --- 0 999 no 1000 1000 -- R- R-

interval Counter int --- 0 999 no min 1 -- R- R-

Defrost time counter dnt --- 0 999 no min 1 -- R- R-

Door open counter ont --- 0 999 no 1 1 -- R- R-

SW version Fir SWVER -32768 32767 no R- R- R-

HW version HAr HWVER -32768 32767 no R- R- R-

OrderNoLow OnL ORNOL -32768 32767 no -- -- --

OrderNoHigh OnH ORNOH -32768 32767 no -- -- --

OEM code Low oEL 0 0 999 no R- R- R-

OEM code Middle oEn 0 0 999 no R- R- R-

OEM code High oEH 0 0 999 no R- R- R-

Parameter version PAr PARVER -32768 32767 no R- R- R-

Last change CHA 0 0 999 no 1 -- -- --

Manufacturing date CHd 0 0 999 no 1 -- R- R-

Copy Key ID Cid 0 0 999 no 1 -- -- R-

Set as Default SFC no no yES no RW RW RW

ERC 102 Reference manual – 7 PARAMETERS 43

Downloaded from www.Manualslib.com manuals search engine


8. TECHNICAL SPECS

Power Supply 100 V AC - 240 V AC, switch mode power supply


Average 0 7 W
Rated Power
4 Inputs: 3 Analogue & Digital, 1 Digital; user specific assignment
• Air / Evaporator / Condenser • Door sensor: All types, user specific
Input
• Light sensor: Danfoss ECO light sensor • DP for remote communication
UL60730 EN60730
DO1 120 V ac: 16A resistive/ FLA16 / LRA72.
16(16)A
(Compressor relay): 240 V ac: 10A resistive /FLA10 /LRA60.
DO4 8 A resistive, FLA2/ LRA12, TV-1 8 A resistive, 2(2) A
Output
DO5 FLA2/ LRA12, TV-1 8 A resistive, 2(2) A
DO6 FLA2/ LRA12, TV-1 8 A resistive, 2(2) A
Max 10 A total DO4-6
Probes Danfoss NTC sensors and Danfoss ECO accessories (300 - 3,000 mm)
Modular connector system for OEM customers, with optional output screw terminal adapter; Input connector
Connectors
type: Rast2 5 Edge connectors; Output connector type: RAST 5 Standard
Programming Programming with Danfoss ERC docking station, integrated system
3 types for all controls: Front mounting (patents pending); brackets; fully integrated solution (requires OEM
Assembly
specific design of mounting hole)
Display LED display, 3 digit, decimal point and multi functionality icons; °C/F scale
Keypad 4 buttons (integrated IP65 design), 2 left, 2 right; user programmable
Operating Conditions 0 °C to 55 °C, 93% rH
Storage Conditions -40 °C to 85 °C, 93% rH
Range of Measurement -40 °C to 85 °C
Protection front: IP65/rear: water and dust protection corresponds to IP31, accessibility of connectors limit rear part rating to IP00
Environmental Pollution degree II, non-condensing
Resistance to heat & fire Category D (UL94-V0)
EMC category Category I
Operating Cycles Compressor relay: more than 175,000 at full load (16A(96A))
Approvals R290/R600a : EN/IEC 60079-15:2005
Glow wire according to EN/IEC 60335-1
IEC/EN 60730
Note: These approvals UL60730
are only valid when NSF
using the accessories CQC
listed in this document GOST R 60730

Dimensions:

71 mm
36,5 mm
28,5 mm

78,25 mm Front mounting

28 mm 71 mm
30 mm

78,25 mm
82,25 mm Rear mounting

44 ERC 102 user manual – 8 TECHNICAL SPECS

Downloaded from www.Manualslib.com manuals search engine


APPENDIX I: PARAMETER QUICK LIST

ERC menu
Description
code

Thermostat tHE Thermostat settings

Set point adjustment ratio SPr Current setpoint adjustment value diF * SPr

Differential diF Thermostat differential

High Set Point HSE Upper limit of thermostat set point

Low Set Point LSE Lower limit of thermostat set point

Air Temp Adj. tAd Applies to non-Danfoss temperature sensors only

ERC menu
Description
code

Alarm ALA Alarm settings

High Alarm delay Htd Alarm delay on high temperature

Low Alarm delay Ltd Alarm delay on low temperature

High Temp Alarm HAt Alarm is activated above this temperature (Celsius)

Low Temp Alarm LAt Alarm is activated below this temperature (Celsius)

Pulldown delay Pdd Alarm delay during pulldown (0-960 minutes) (high temperature only)

Door Open delay dod Alarm delay for door open (0-60 minutes)

Alarm Buzzer Duration Abd Alarm buzzer duration in minutes (0=no buzzer)

Auto Clearance of ACA yES: alarm auto-clears if system returns to normal; nO : alarm state maintained regardless
Alarm/Error

ERC menu
Description
code

Compressor CoP Compressor settings

Min run time Crt Minimum time compressor must run 0-30 minutes

Min Stop time CSt Min time compressor must idle 0-30 minutes

Max Off time Cot Max time compressor must idle 0-480 minutes

Compressor door open Cdd Minutes before compressor stops when door opened
delay

Error run time Ert Compressor run time if temperature sensor is not working (0-60 minutes)

Error stop time ESt Compressor stop time if temperature sensor is not working (0-60 minutes)

Minimum Cutin voltage uLi When compressor is off: Lowest compressor start voltage (0-270 V)

Minimum cut-out voltage uLo When compressor is on: Lowest operation voltage (0-270 V)

Maximum voltage uHi When compressor is on: Highest operation voltage (0-270 V)

Power On Delay Pod Delay in seconds after power-on before outputs active (change with care)

Power Factor PFA Phasic angle in degrees. Changing this may give decreased relay lifetime

Power-on temperature Pot If the temperature of compressor at power-on exceeds this then Power On Delay does not apply

ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 45

Downloaded from www.Manualslib.com manuals search engine


ERC menu
Description
code

Defrost dEF Defrost Settings

Def. type dFt no: Defrost function is disabled


EL: Electrical or time defrost
Hgd: Hot gas defrost (contact Danfoss for details)
nat:Off-cycle defrost (natural defrost)

Def terminate temp dtt Temperature at which defrost cycle will stop

Def Min Interval dii The minimum time in hours between the start of each defrost cycle

Def Max Interval dAi The maximum time in hours between the start of each defrost cycle

Def Min Time dit The minimum duration of a defrost cycle in minutes

Def Max time dAt The maximum duration of a defrost cycle in minutes

Drip off time dot The duration in minutes of the drip-off time at the end of a defrost cycle

Fan delay after Defrost Fdd The duration in minutes before the fan starts after a defrost cycle

Fan start Temp Ftd The temperature at which the fan will start after a defrost

Defrost Fan on dFA Whether the fan will run during a defrost cycle

Initial Defrost Interval idi The number of hours after power-up before the first defrost cycle starts

Defrost on compressor dCt Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
time

ERC menu
Description
code

Fan FAn Fan settings

Fan always On FAo nO: fan parameters below active. yES: Fan is always on

Fan On Delay Fod Delay in seconds before fan starts after compressor starts

Fan Stop delay FSd Delay in seconds before fan stops after compressor stops

Fan On Cycle FoC The number of seconds the fan runs when the compressor is off

Fan Stop Cycle FSC The number of seconds the fan does not run when the compressor is off

ERC menu
Description
code

Energy management Eng Energy Management

Shop Light Day SLd When ambient light is above this level, Eco mode is cancelled. Requires light sensor

Shop Light Night SLn When ambient light is below this level, Eco mode is enabled. Requires light sensor

Eco Activity delay EAd Minutes delay after last door opening until ECO mode is enabled; 0: disable

Eco Light delay ELd Delay [min] between detection of shop light on/off and ECO mode activation / suspension

Eco Temperature Offset Eto Temperature increase for Eco mode relative to normal mode

46 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST

Downloaded from www.Manualslib.com manuals search engine


ERC menu
Description
code

Pull Down Pud Pull down settings

Pull-down Initiate Pit If the cabinet temperature is above this temperature for >1h, pull-down mode is activated
­Temperature

Pull-down Cycling PCy Minimum duration [min] of the pull-down mode, starting at PiT

Pull-down defrost Interval Pdi Defrost interval during pull-down. Over-rules the defrost interval in normal mode.

Pull-down duration Pdd Maximum duration [min] of the pull-down mode, starting at PiT

Pull-down limit temp PLt A safety feature; the lowest temperature allowed during pull-down.

Pull-down reduction Prt A calculation value for pull-down performance improvement. Instructions: See manual
temp Δt

ERC menu
Description
code

Auto-Heater Control AHC Auto-Heater settings (only if heater fitted for outdoor use in cold climates)

Automatic heater mode AuH yES: Activate heater if ambient temperature is below desired cabinet temperature
enable

Energy mode delay End Delay in minutes between heater and compressor operation

Heater displacement Hdi Heater displacement or OFFSET temperature relative to desired temperature.
temperature

ERC menu
Description
code

Condenser Protection Con Condenser protection settings

Condenser Alarm Limit CAL If condenser sensor exceeds this temperature, alarm is activated

Condenser Block Limit CbL If this temperature is exceeded, compressor will be stopped.

Condenser OK limit CoL Temperature at which compressor may start after a stop due to exceeding CbL

Condenser Low Temp. CLL Temperature below which the compressor is not allowed to start
Limit

ERC menu
Description
code

Display diS Display settings

Display Unit CFu F: Fahrenheit; C: Celsius

Display Resolution rES Display resolution for temp: 0.1, 0.5 or 1.0 C/F

Display Range Limit rlt Limits displayed temperature to actual setpoint +/- differential; may be illegal in some countries

Display Delay ddL Time period for moving average temperature display

Display Offset doF Display a different temperature relative to measured temperature

Lock-time After defrost dLt Display lock time after defrost [0-60 min]

Show Economy state SEC yES: display will show “Eco” when in Eco mode. nO: temperature will be shown

Show Pull Down state SSC yES: “SC “ will be displayed during Pull down; nO: “SC “ will not be displayed.

Show Defrost SdF yES: display will show deF during defrost ; no: Display will show temp

Display Intensity din Display intensity when no ambient sensor; min intensity with sensor

ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 47

Downloaded from www.Manualslib.com manuals search engine


ERC menu
Description
code

Assignments ASi Assignment of inputs and outputs

S1 Config S1C Sensor type input 1 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input

S2 Config S2C Sensor type input 2 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input

S3 Config S3C Sensor type input 3 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input

S1 Application S1A Application to be controlled with Sensor D.


nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(Ldr), Luminens, delicated for Economy detection
LS2: Light sensor(Ldr), Luminens, delicated for LED intensity scope
LS3: Light sensor(Ldr), Luminens, delicated for both Economy detection and LED intensity scope
doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed

S2 Application S2A Application to be controlled with Sensor C.


nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(LDR), Luminens, delicated for Economy detection
LS2: Light sensor(LDR), Luminens, delicated for LED intensity scope
LS3: Light sensor(LDR), Luminens, delicated for both Economy detection and LED intensity scope
doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed

S3 Application S3A Application to be controled with Sensor B.


nC: Not connected
SCo: Temperature control
EuA: Evaporator temperture
Con: Condenser temperature (Condenser cleaning)
LS1: Light sensor(LDR), Luminens, delicated for Economy detection
LS2: Light

DI Config diC Sensor A (digital)


doC: Door contact, Contact closed when door closed
doo: Door contact, Contact open when door closed
dio: One wire digital communication
buS: MODBUS communication

DO1 Config o1C CoP: Compressor; PiL: Pilot Relay (No zero-cross); HEt: Inverse output, Heating application

DO2 Config o2C no:Not used; dEF: Elec defr heater/hot gas valve;ALA:Alarm output;FAn:Fan control;Lig:Light control

DO3 Config o3C nO: Not used; ALA: Alarm output; FAn: Fan control; Lig: Light control

DO4 Config o4C nO: Not used; ALA: Alarm output; Lig: Light control

Button 1 Config b1C Lower left button configuration.


tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating

48 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST

Downloaded from www.Manualslib.com manuals search engine


ERC menu
Description
code

Assignments ASi Assignment of inputs and outputs

Button 2 Config b2C Upper left button configuration.


tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating

Button 3 Config b3C Upper right button configuration.


tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating

Button 4 Config b4C Lower right button configuration.


tP:Increase Setpoint
tn: Decrease setpoint
ECo: Toggle Eco mode
Lig: Toggle light
dEF: Toggle defrost
SuP: Activate Super-Cool /Pull-down
diP : Increase display intensity
din : Decrease display intensity
noP: Not operating

Pass-word level1 PS1 Level 1 Password (End user, shop owner), 0= disabled

Pass-word level2 PS2 Level 2 Password (Technical field service), 0= disabled

Pass-word level3 PS3 Level 3 Password (OEM), 0= disabled; choose a secure number, e.g. 735

Cabinet Light Control CLC Cabinet light management


Source Lig: button only”
Ldo: door (and button if defined) only
LEC: Economy (and button if defined) only

Light off delay Lod Light off delay [sec] after door has been closed

ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST 49

Downloaded from www.Manualslib.com manuals search engine


ERC menu
Description
code

Service SEr Service

DI Sdi DI: physcial DI pin state (ON; OFF)

Voltage value uAC Current main power supply voltage

DOs Status ouS Current relay open / closed status.


IIII = All Relay on (Upper bar for on, Lower bar for off )
II = DO1 On, DO2 Off, DO3 & DO4 NA (No bar if relay not mounted)
IIII = All Relay off (Upper bar for on, Lower bar for off )

Relay 1 counter rL1 Thousands of cycles of compressor relay since manufacture

Relay 2 counter rL2 Thousands of cycles of no.2 relay since manufacture

Relay 3 counter rL3 Thousands of cycles of no. 3 relay since manufacture

Relay 4 counter rL4 Thousands of cycles of no. 4 relay since manufacture

interval Counter int Compressor run time since last defrost

Defrost time counter dnt Duration of last defrost cycle [min]

Door open counter ont ont/100 = Number of door openings since last reset

Serial numbe Snu Serial number given at manufacturing

SW version Fir Danfoss software version number

HW version HAr Danfoss hardware version number

OrderNoLow OnL Danfoss order code number

OrderNoHigh OnH Danfoss order code number

Parameter version PAr OEM parameter version number [requires EKA copy key update]

Last change CHA Not used

Manufacturing date CHd Programme date WWY: week number and year number (2010-19)

Copy Key ID Cid Copy key used for last program

Set as Default SFC Resets all parameters to last good OEM settings

50 ERC 102 Reference manual – APPENDIX I: PARAMETER QUICK LIST

Downloaded from www.Manualslib.com manuals search engine


APPENDIX II: CODE NUMBERS AND LENGHTS

Code no. I-Pack Code no. I-Pack

Type Approvals Type Approvals


230V, CQC/UL/CE 230V, CQC/UL/CE

GDM-front Defrost sensors*

ERC 102C RED LED without buzzer 080G3102 PVC Standard (C2), 470 mm, 2-pole 077F8780

ERC 102D RED LED without buzzer 080G3103 PVC Standard (C2), 1000 mm, 2-pole 077F8786

ERC 102C BLUE LED without buzzer 080G3106 PVC Standard (C2), 1500 mm, 2-pole 077F8790

ERC 102D BLUE LED without buzzer 080G3107 PVC Standard (C2), 2000 mm, 2-pole 077F8794

PVC Standard (C2), 3000 mm, 2-pole 077F8798

CFF-front PVC Standard (C3), 470 mm, 3-pole 077F8750

ERC 102C RED LED with buzzer 080G3113 PVC Standard (C3), 1000 mm, 3-pole 077F8756

ERC 102D RED LED with buzzer 080G3112 PVC Standard (C3), 1500 mm, 3-pole 077F8760

ERC 102C BLUE LED with buzzer 080G3116 PVC Standard (C3), 2000 mm, 3-pole 077F8764

ERC 102D BLUE LED with buzzer 080G3117 PVC Standard (C3), 2200 mm, 3-pole 077F8766

PVC Standard (C3), 3000 mm, 3-pole 077F8768

Light-sensors

Light sensor, 1000 mm (C3), 3-pole 080G3311 Other sensors

Light sensor, 2000 mm (C3), 3-pole 080G3313 TPFE low temp (C1), 1000 mm, 3-pole 077F8657

Light sensor, 3000 mm (C3), 3-pole 080G3315 TPFE low temp (C1), 2000 mm, 3-pole 077F8665

TPE precision (C1), 500 mm, 3-pole 077F8724

Door-sensors TPE precision (C1), 1000 mm, 3-pole 077F8725

Door-sensor, 1000 mm (C4), 3-pole 080G3332 TPE precision (C1), 1500 mm, 3-pole 077F8726

Door-sensor, 2000 mm (C4), 3-pole 080G3334 TPE precision (C1), 2000 mm, 3-pole 077F8727

Door-sensor, 3000 mm (C4), 3-pole 080G3336 TPE precision (C1), 2500 mm, 3-pole 077F8728

TPE precision (C1), 3000 mm, 3-pole 077F8729

Temperature sensors

PVC Standard (C1), 470 mm, 3-pole 077F8751 Clamps

PVC Standard (C1), 1000 mm, 3-pole 077F8757 Black (2 needed per controller) 080G3308

PVC Standard (C1), 1500 mm, 3-pole 077F8761

PVC Standard (C1), 2000 mm, 3-pole 077F8765 Programming

OEM Docking station, production line 080G9701


PVC Standard (C1), 2200 mm, 3-pole 077F8767
Gateway incl USB Cable, R&D 080G9711
PVC Standard (C1), 3000 mm, 3-pole 077F8769
Copy Stick EKA-183A 080G9740

Note: For more information about temperature sen- C: connector type


sor types and connectors, please refer to Danfoss’
technical brochure “NTC type temperature sensors * Defrost sensors can also be used as condenser
for ETC & ERC controllers” sensors. .

ERC 102 Reference manual – APPENDIX II: CODE NUMBERS AND LENGHTS 51

Downloaded from www.Manualslib.com manuals search engine


APPENDIX III: TROUBLESHOOTING

Problem Probable cause Remedy

Compressor does not start Waiting for compressor delay timer Check CoP->CSt

Defrost in progress Check CoP ->Pot /Pod

Line voltage to compressor too low Check dEF ->dit, dot


or too high
Check CoP->uLi, uLo, uHi

Fan does not start Door is open or door contact is defective Fan stops when door is opened

Check that door contact is ok

Defrost does not start Controller in pull-down mode Defrost might be delayed during pull-down

Check parameter Pud->Pdi

Alarm does not sound Alarm delayed Check ALA->Htd, Abd

Check Pud->Pdd

Display brightness is weak Ambient light sensor broken Replace sensor

Shift between Eco and Normal mode does Ambient light sensor broken Check Eng->SLd, SLn
not happen on ambient light change or light level not set properly

E01, E02 or E03 is shown on display E01: Sensor S1 defective Replace sensor

E02: Sensor S2 defective

E03: Sensor S3 defective

Display alternates between Con and Condenser too hot Clean condenser
temperature
Check Con ->CAL, CbL

Display alternates between Hi and Temperature too high Check ALA->HAt


temperature

Display alternates between Lo and Temperature too low Check ALA -> LAt
temperature

Display shows dEf Defrost in progress Check diS ->SdF

52 ERC 102 Reference manual – APPENDIX III: TROUBLE SHOOTING

Downloaded from www.Manualslib.com manuals search engine


APPENDIX IV: TYPICAL APPLICATIONS – WIRING DIAGRAMS
IV.1 ERC 102D
Glass Door Merchandiser
No-frost freezer / sub-zero cooler

100 – 240VAC SMPS


L N

ERC 102C
3 relays

Red LED without buzzer 080G3101


Lights
Defrost Heater

Fan
Compressor

Blue LED without buzzer 080G3106

ERC102D
1 2 3 4 5 6 DO’s
Controller

DO1 DO2 DO3 DO4

AI/DI’s D(S1) C(S2) B(S3) A(di)

LL

Temperature Sensor for


Temperature Sensor for Cabi-
Evaporator Temperature Ambient Light Door input
net Temperature Control
Control
PVC Standard PVC Standard Light sensor Door-sensor cable
Connector type (C1) 3-pole Connector type (C2) 2-pole Connector type (C3) 3-pole Connector type (C4) 3-pole
470 mm 077F8751 470 mm 077F8780 1000 mm 080G3311 1000 mm 080G3332
1000 mm 077F8757 1000 mm 077F8786 2000 mm 080G3313 2000 mm 080G3334
1500 mm 077F8761 1500 mm 077F8790 3000 mm 080G3315 3000 mm 080G3336
2000 mm 077F8765 2000 mm 077F8794
2200 mm 077F8767 3000 mm 077F8798
3000 mm 077F8769

ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS 53

Downloaded from www.Manualslib.com manuals search engine


IV.2 ERC 102C
Glass Door Merchandiser

100 – 240VAC SMPS


L N
ERC 102C Controller

Red LED without buzzer 080G3102

Blue LED without buzzer 080G3106


Lights
Fan
Compressor

ERC102C
1 2 3 4 5 DO’s
Controller

DO1 DO2 DO3

AI/DI’s D(S1) C(S2) B(S3) A(di)

LL

Temperature Sensor for


Temperature Sensor for Cabi-
Evaporator Temperature Ambient Light Door input
net Temperature Control
Control
PVC Standard PVC Standard Light sensor Door-sensor cable
Connector type (C1) 3-pole Connector type (C2) 2-pole Connector type (C3) 3-pole Connector type (C4) 3-pole
470 mm 077F8751 470 mm 077F8780 1000 mm 080G3311 1000 mm 080G3332
1000 mm 077F8757 1000 mm 077F8786 2000 mm 080G3313 2000 mm 080G3334
1500 mm 077F8761 1500 mm 077F8790 3000 mm 080G3315 3000 mm 080G3336
2000 mm 077F8765 2000 mm 077F8794
2200 mm 077F8767 3000 mm 077F8798
3000 mm 077F8769

54 ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS

Downloaded from www.Manualslib.com manuals search engine


IV.3 ERC 102D
Gastro No-frost freezer

ERC 102D Controller


100 – 240VAC SMPS
Red LED without buzzer 080G3103
L N
Blue LED without buzzer 080G3107
Lights
Defrost Heater

Fan
Compressor

ERC102D
1 2 3 4 5 6 DO’s
Controller

DO1 DO2 DO3 DO4

AI/DI’s D(S1) C(S2) B(S3) A(di)

Temperature Sensor for


Temperature Sensor for Cabi- Temperature Sensor for Con-
Evaporator Temperature Door input
net Temperature Control denser Temperature Control
Control
PVC Standard PVC Standard PVC Standard Door-sensor cable
Connector type (C1) 3-pole Connector type (C2) 2-pole Connector type (C3) 3-pole Connector type (C4) 3-pole
470 mm 077F8751 470 mm 077F8780 470 mm 077F8750 1000 mm 080G3332
1000 mm 077F8757 1000 mm 077F8786 1000 mm 077F8756 2000 mm 080G3334
1500 mm 077F8761 1500 mm 077F8790 1500 mm 077F8760 3000 mm 080G3336
2000 mm 077F8765 2000 mm 077F8794 2000 mm 077F8764
2200 mm 077F8767 3000 mm 077F8798 2200 mm 077F8766
3000 mm 077F8769 3000 mm 077F8768

ERC 102 Reference manual – APPENDIX IV: – WIRING DIAGRAMS 55

Downloaded from www.Manualslib.com manuals search engine


IV.4 ERC 102C
Gastro Cooler

100 – 240VAC SMPS ERC 102C Controller


L N
Red LED without buzzer 080G3102

Blue LED without buzzer 080G3106


Lights
Fan
Compressor

ERC102C
1 2 3 4 5 DO’s
Controller

DO1 DO2 DO3

AI/DI’s D(S1) C(S2) B(S3) A(di)

Temperature Sensor for


Temperature Sensor for Cabi- Temperature Sensor for Con-
Evaporator Temperature Door input
net Temperature Control denser Temperature Control
Control
PVC Standard PVC Standard PVC Standard Door-sensor cable
Connector type (C1) 3-pole Connector type (C2) 2-pole Connector type (C3) 3-pole Connector type (C4) 3-pole
470 mm 077F8751 470 mm 077F8780 470 mm 077F8750 1000 mm 080G3332
1000 mm 077F8757 1000 mm 077F8786 1000 mm 077F8756 2000 mm 080G3334
1500 mm 077F8761 1500 mm 077F8790 1500 mm 077F8760 3000 mm 080G3336
2000 mm 077F8765 2000 mm 077F8794 2000 mm 077F8764
2200 mm 077F8767 3000 mm 077F8798 2200 mm 077F8766
3000 mm 077F8769 3000 mm 077F8768

Note: This is a typical (default) wiring diagram since both inputs(AI/DI’s) and outputs (DO’s) can be assigned
differently. Please see manual for further details, folder “ASi”, Assignment.

56 ERC 102 Reference manual – 8 TYPICAL APPLICATIONS – WIRING DIAGRAMS

Downloaded from www.Manualslib.com manuals search engine


APPENDIX V: APPLICATION SPECIFICATON

V.1 Control sensor


The control sensor must always be connected and
is used for controlling the cut-in and cut-out of the
compressor according to the set-point. The sensor is
also used for the displayed temperature.

Placement of sensor:

Vertical coolers with fan


Most common placement is in the return air to the
evaporator. The sensor can be placed close to the
fan – even when the fan is pulsed during compres-
sor off periods: The updating of the temperature is
blocked when the fan is stopped and only updated
when the fan has been running for a while, so that
the heat from the fan does not affect the tempera-
ture reading.
For applications sensitive to sub-zero temperatures,
sensor placement in the evaporator outlet air can be
considered.

Vertical freezers with fan


Placement in the return air or in the freezer
compartment

Coolers without fan


the best results are normally obtained when the
sensor is placed at the side-wall, 10 cm from the
back and approximately at 1/3 from the bottom or
where the evaporator ends.
The control sensor must always be connected and
is used for controlling the cut-in and cut-out of the
compressor according to the set-point. The sensor is
also used for the displayed temperature.

ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION 57

Downloaded from www.Manualslib.com manuals search engine


V.2 Evaporator sensor
The evaporator sensor is only used for de-icing of
the evaporator and has no control purpose.

Placement of sensor:
Place the sensor where the ice melts last.
Please be aware of that sharp finns can damage the
cable.

V.3 Condenser sensor


The condenser sensor is used to protect the com-
pressor against high pressure when the condenser is
blocked or the condenser fan fails.

Placement of sensor:
Place the sensor at the liquid side of the condenser.
Use a metal bracket or metal tape to ensure good
thermal conductivity. Be sure that the cable does not
pass hot spots at the compressor or condenser that
exceeds 80°C.

58 ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION

Downloaded from www.Manualslib.com manuals search engine


V.4 Ambient light sensor
The ambient light sensor is used to detect opening
hours of the shop.

Placement of sensor:
The sensor must be placed so that the interior light
does not affect the sensor.
Possible placement could be in the front of the
cooler or at the top.

V.5 Door sensor


The door sensor is used to detect buying activity and
to stop the fan when the door is opened.

Danfoss does not supply the door-switch. Use the


door-switch you have and connect it to the cable
supplied by Danfoss.

ERC 102 Reference manual – APPENDIX V: APPLICATION SPECIFICATION 59

Downloaded from www.Manualslib.com manuals search engine


ERC102 Application Matrix

Output Input
Application ERC type
DO1 DO2 DO3 DO4 S1 (C1) S2 (C2) S3 (C3) Di (C4)
Standard Beverage Condenser or
ERC102C Comp Fan Lamp Control Defrost Door
cooler Ambient Light
Sub-zero beverage Condenser or
ERC102D Comp Heater Fan Lamp Control Defrost Door
cooler Ambient Light
Out-door beverage
ERC102D Comp Heater Fan Lamp Control Condenser Ambient Light Door
cooler
Nofrost freezer w. Condenser or
ERC102D Comp Heater Fan Lamp Control Evaporator Door
glassdoor Ambient Light
CFF Refrigerator ERC102C Comp Fan Lamp Control Defrost Condenser Door
CFF Freezer ERC102D Comp Heater Fan Lamp Control Defrost Condenser Door

C: connector type

NOTE:
• Select only one function per input, e.g. condenser sensor or ambient light sensor.
• Make sure that the accessory you select has a matching connector to the input, e.g. a sensor for input S2 must
have C2 connector.
• Condenser sensor or light sensor are optional and can be omitted.
• Defrost sensor is mandatory when electrical heater is used for defrost. For natural defrost it can be omitted.

DKRCC.PS.RL0.A7.02 / 520H5635 Copyright Danfoss A/S www.danfoss.com – 09/2011

Downloaded from www.Manualslib.com manuals search engine