ERC 102 Refrigeration Controller: Reference Manual
ERC 102 Refrigeration Controller: Reference Manual
ERC 102 Refrigeration Controller: Reference Manual
www.danfoss.com/erc
Downloaded from www.Manualslib.com manuals search engine
Table of Content
1. INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
4. MOUNTING
4.1 Rear mounting – Option 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.1.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4.2 Front mounting – Option 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
4.2.1 Unmounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
4.3 Fully-integrated design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
5. CONTROLLING/NAVIGATION
5.1 KoolProg and Gateway . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.2 Docking station . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3 Manual operation with buttons (Direct Access) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.1 ERC Front and Button Functionallity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5.3.2 Direct functions for access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5.3.3 Operating the menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
5.3.4 Menu structure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
5.3.5 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
8. TECHNICAL SPECS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
APPENDIX
I Parameter quick list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
II Code numbers and lenghts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
III Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
IV Typical applications – wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IV.1 Typical Wiring Diagram, ERC 102D, Glass Door Merchandiser,
No-frost freezer / sub-zero cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
IV.2 Typical Wiring Diagram, ERC 102C, Glass Door Merchandiser . . . . . . . . . . . . . . . . . . . . . 54
IV.3 Typical Wiring Diagram, ERC 102D, Gastro No-frost freezer . . . . . . . . . . . . . . . . . . . . . . 55
IV.4 Typical Wiring Diagram, ERC 102C, Gastro Cooler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
V Application specificatons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
V.1 Control sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
V.2 Evaporator sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
V.3 Condenser sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
V.4 Ambient light sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
V.5 Door sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
ERC102 Application Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
The ERC 102 is an electronic refrigeration controller with an LED display especially developed for bottle
coolers and commercial fridges and freezers. It is particularly suited for OEM customers where time, easy and
reliable installation and high quality need to go hand in hand with flexibility.
The latest generation CPU, plenty of memory and high-end electronic components allow for a uniquely
versatile software. Three separate password-protected user levels can be used to control more than 200
different parameters to fit all individual requirements.
ERC 102’s IP rated body, advanced materials and internationally approved hardware design open it up for use
in almost any climate globally, indoors as well as outdoors.
Laboratory work with ERC 102 is rendered easy and flexible. Danfoss KoolProg software with a USB-powered
gateway accelerate programming; on the OEM assembly line, just one Danfoss unique Docking station can
easily program up to 3,000 controllers a day – at zero inventory cost.
Sensors include ambient light for display brightness, which also detect shop opening hours for
energy-saving routines. Door and temperature sensors provide input for controlling the compressor,
the light, the fan and automatic defrosting.
2. 1 Main product
ERC 102 control unit without front frame.
2.2 Accessories
Control temperature sensor: see Appendix II for
different lengths and connector types.
Together with the Danfoss docking station, Overview of ERC 102 models:
programming of pre-prepared parameter sets can
Model: Digital outputs:
be achieved in just five seconds. There are over 200
parameters (see Chapter 7) including innovative ERC 102A 1 relay
features such as night mode detection, ERC 102C 3 relays
store opening detection, door open alarm control
and display dimming for restaurants. ERC 102D 4 relays
SAFETY INFO
Risk of electrocution!
For mounting: Do not connect mains power until
the controller is correctly mounted.
For unmounting: Disconnect the power supply
before unmounting.
5.1 KoolProg/Gateway
KoolProg is licenced Danfoss software offering easy
parameter setup via a USB gateway. This software
is supplied separately; for technical literature and
further information, please contact your local
Danfoss representative.
s ERC 102Changing the Desired Temperature Setpoint (applies similarly when using Fahrenheit scale):
function, e.g.ECO/Night mode
1 Click: Temperature setpoint
Sub function: Up
d Button Functionallity:
1.)
s ERC 102
The display shows the current
function, e.g.ECO/Night mode temperature.
1 Click: Temperature setpoint
Sub function: Up
(Current temperature)
d Button Functionallity:
2.)
function, e.g. light 1 Click: Temperature setpoint
s ERC 102
function, e.g.ECO/Night mode
Sub
Press: function:toDown
up/down adjust setpoint
1 Click: Temperature setpoint
Sub function: Up
2.)
Variable direct function, e.g. light ECO ˚C 1 Click: Temperature setpoint
sec: Menu Sub function: Down
nction: OK
The green ECO symbol
is lit when in ECO mode
1.)
Press the
Flashing
Press any button to acknowlege
2.)
k: Variable direct function, e.g. light 1 Click: Variable direct function, e.g. light 1 Click: Temperature setpoint 1 Click: Temperature setpoint
3 sec: Menu Hold 3 sec: Menu Sub function: Down Sub function: Down
unction: OK Sub function: OK
9.)
Press:direct
1 Click: Variable upperfunction,
left button (back)
e.g. light 1 Click: Temperature setpoint
Hold 3 sec:toMenu
return to the menu Sub function: Down
Sub function: OK
Danfoss
ERC Front and ERC
Sub function: Back
5.3.4 Menu structure 102
1 Click: Variable direct function, e.g.ECO/Night mode1 Click: Temperature setpoint
Button Functionallity:
Sub function: Up
1 Click: Temperature setpoint
Sub function: Up
Danfoss
ERC Front and ERC
Sub function: Back 102
Button Functionallity:
1 Click: Variable direct function, e.g.ECO/Night mode
Press and hold 5 1. ) Parameter groups
sec to access the
1 Click: Temperature setpoint
Sub function: Up
menu
Danfoss
ERC Front and ERC 102Danfoss ERC 102
Button Functionallity:
1 Click: Variable direct function, e.g.ECO/Night mode
Sub function: Back
1 Click: Temperature setpoint
Sub function: Up
Lower left button
Assignments / ASi
Example: Input S1 is attached to a temperature sensor. The sensor measures cabinet temperature.
Example: Input S2 is attached a digital on/off sensor which is a door open / closed switch.
S1 S2 S3
b
a
Connector inputs: analogue ( a ), digital ( b ) Connector outputs ( c )
Assignments ASi
ight mode
1 Click: Temperature setpoint
nctionallity:
S1 ConfigSub /function:
S1C Up
S2 Config / S2C
102
ight mode
S3 Config / S3C
Available1 Click: Temperature
options are: setpoint
Sub function: Up
Stn for a temperature sensor (values given in Celsius)
102
nctionallity: Ldr for a light sensor (values given in Luminens)
Dig for a digital sensor with simple on/off indication
1 Click: Temperature setpoint
Sub function: Down
102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
ight mode
nctionallity: 1 Click: Temperature setpoint
S1 Application / Up
Sub function: S1A
S2 Application / S2A setpoint
1 Click: Temperature
Sub function: Down
S3 Application / S3A
ight mode
Available options are: setpoint
1 Click: Temperature
Sub function: Up
nC: Not connected
SCo: Temperature control
102 EuA: Evaporator temperature
1 Click: Temperature setpoint
Con: Condenser temperature (Condenser cleaning)
Sub function: Down
LS1: Light sensor (Ldr), Luminens, dedicated to Eco mode switching detection
nctionallity: LS2: Light sensor (Ldr), Luminens, dedicated to determining LED intensity
LS3: Light sensor(Ldr),
1 Click: Luminens, used for both Eco mode detection and
Temperature setpoint
determining LED intensity
Sub function: Down
ight mode
doC: Door contact, contact closed when door closed
1 Click: Temperature setpoint
doo: Door contact, contact open when door closed
Sub function: Up
1 Click: Temperature setpoint
DI Config / diC
nctionallity: This is the digital input used for a digital sensor or bus communications.
doC: Door contact, contact closed when door closed
doo: Door contact, contact open when door closed
ight mode bus: Modbus communication (used only for KoolProg)
1 Click: Temperature setpoint
diO: OneSubWire Communication
function: Up
102
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function:
D02 Config / o2CUp
D03 Config / o3C
ight mode
D04 Config / o4C
1 Click: Temperature setpoint
Sub function: Up
nO: not used
dEF: Electric Defrost Heater / Valve for hot gas
ALA: Alamr Output
102 1 Click: Temperature setpoint
Fan: FanSub
control
function: Down
LIG: Light control
102
nctionallity: 1 Click: Temperature setpoint
Sub function: Down
102
ight mode
nctionallity: 11 Click:
Click: Temperature
Temperature setpoint
setpoint
Sub
Subfunction:
function:Up
Down
6.2 Program the buttons
ight mode
102
nctionallity: 1 Click: Temperature setpoint
Button Sub
1 Config
function: (short
Up press) / b1C
Lower left button
Button 1 config (long press) / b1L
ight mode
1 Click:
Lower left Temperature setpoint
button
102
nctionallity: Sub function: Up
Button 2 Config (short press) / b2C
Upper left button
ight mode Button 3 Config (short press) / b3C
1 Click: Temperature setpoint
102
nctionallity: Upper right
Sub button
Subfunction:
function:Up
Down
Button 3 config (long press) / b3L
Upper right button
ight mode Button 141 Click:
Config (short
Click: Temperature
press) / b4C
Temperature setpoint
setpoint
102
nctionallity: Sub
Lower right function:
button
Sub function: Down
Up
Button 4 Config (long press) / b4L
Lower right button
ight mode 1 Click: Temperature setpoint
1Sub
Click: Temperature
Down setpoint
nctionallity: The buttons
function:
Sub function:
can be Up programmed as follows:
NOTE: Buttons 1, 3 and 4 can be assigned to operate with 2 functions (short press or long press).
1 Click: Temperature setpoint
NOTE: Your assignments may notSub befunction:
shownDown on the printed buttons. We advice to use this functionality
together with the fully integrated mounting model only.
102
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
6.3 Set passwords
ight mode
nctionallity: 1 Click: Temperature setpoint
Password Sub level
function:1Up
/ PS1
Password Level 2 / PS2
Password Level 3 / PS3
ight mode
1 Click: Temperature
These assign passwords setpoint
to the three levels of access. The password is a three-digit
Sub function: Up
number. Access levels are Shop, Service and OEM. You may not therefore have ac-
cess to change all the passwords. Passwords are entered by using the up and down
arrow buttons.
102 1 Click: Temperature setpoint
Danfoss Sub
advises against using passwords which are easy to remember or enter, for
function: Down
example 111, 222, 123 etc.
NOTE: When
1 Click: accessing the controller with 3 wrong password in a sequence ERC will
nctionallity: Temperature setpoint
automatically block access for 15 minutes.
Sub function: Down
102
in ERC 102 software 5.05. parameter using KoolProg software. There are three
levels of access – 1, 2 and 3. Level 1 is for shop access,
NOTE: Incorrect parameter settings can lead to level 2 for technicians and level 3 for OEMs. The access
inadequate cooling, excessive energy consumption, levels cannot be set using the buttons. Passwords for
unnecessary alarms and in the case of temperature- the different levels can however be altered for the
sensitive food storage, breaches in food hygiene level of access you have – for example a level 2 user
unctionallity: principles and regulations. Only a trained operator
should make changes to parameters.
can change the password for level 1 and level 2 but
not level 3.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Thermostat tHE
102
Sub function: Up
102
ight mode
1 Click: Temperature
and assembly line yousetpoint
may opt for software controlled set point adjustment
Sub function: Up
(speed improvement)
1 Click: Temperature setpoint
Sub function: Down
nctionallity:
Set point adjustment ratio / SPr
The default value is set to 0.5 and the parameter is hidden by default.
102
ight mode
Spr defines the position of the setpoint in relation to cut-in and cut-out.
Spr = 0,51 Click:
setsTemperature setpointmid between cut-in and cut-out. Spr = 0 sets
the setpoint
Sub function: Up
the setpoint at the cutout. Spr =1 sets the setpoint at cut-in.
nctionallity:
102
1 Click: Temperature setpoint
Differential / diF Down
Sub function:
This defines the difference between the cut-out and the cut-in. The desired
ight mode
1 Click: is
temperature Temperature setpointby SPr and diF.
determined
Sub function: Up
nctionallity:
1 Click:
TheTemperature setpoint temperature in the cabinet is 5 degrees, and the
102
Example: desired average
Sub function: Down
differential is set to 2 degrees:
nctionallity:
ight mode
1 Click: Temperature setpoint
Sub function: Up
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
1 Click: Temperature setpoint
Alarm ALA
Sub function: Down
High Alarm delay Htd 30 0 240 no min 1 -- RW RW
Auto Clearance of
ACA yES no yES no 1 -- RW RW
Alarm/Error
102
ight mode
1 Click: Temperature setpoint
High Temp AlarmUp/ HAt
Sub function:
Low Temp Alarm / Lat
102
nctionallity: High temperature alarm and low temperature alarm allow for individual alarm
setpoints. Both are absolute values. By setting HAt to the maximum value and LAt
to the minimum value, alarms will be deactivated.
ight mode
nctionallity: 1 Click: Temperature setpoint
Sub function: Up
1 Click: Temperature setpoint
Sub function: Down
102
ight mode
1 Click: Temperature setpoint
High Alarm Delay
Sub function: Up/ Htd
1 Click: Temperature setpoint
Low Alarm Delay / Ltd
Sub function: Down
nctionallity: These parameters express the number of minutes to wait before sounding an
alarm once the High/Low Temp Alarm temperature is reached. Immediately prior
to the alarm sounding, another check of the temperature is made to see if the
ight mode temperature
1 Click: is still in the
Temperature alarm zone; if it is not, the then the alarm is not sounded.
setpoint
In most Sub
situations,
function: Upthe Low Alarm Delay will be set to 0 to warn about too low a
102
1 Click: Temperature setpoint
temperature immediately.
Sub function: Down
102 It is possible to indicate to customers that a door has accidentally been left open.
This parameter sets the delay in minutes before the alarm sounds. This is useful in
environments where customers / users may hold the door open while making their
selection. If the door is closed again before the set number of minutes is reached,
nctionallity: the alarm does not sound.
NOTE: A1Sub
Click: Temperature setpoint
door sensor is required if this parameter is to be activated.
function: Down
ight mode
1 Click: Temperature setpoint
Sub function: Up
102
As soon as the condition which caused the alarm is no longer valid or present, the
1 Click: Temperature setpoint
alarm status will automatically change back to inactive. There will be no trace of
Sub function: Down
the alarm having occurred.
In general, Glass Door Merchandise applications will be set to yES and Commercial
Fridges and Freezers set to nO. For example, if the temperature goes too high for
a period there may be food safety considerations in a freezer containing food but
unctionallity: not in a fridge with cold drinks.
Night mode
1 Click: Temperature setpoint
Sub function: Up
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Compressor CoP
102
nctionallity:
ight mode
1 Click: Temperature setpoint
Error Run
SubTime
function:/ Up
Ert
Error Stop Time / ESt setpoint
1 Click: Temperature
Sub function: Down
These two parameters only become active in the unlikely event of a broken tem-
perature sensor. They are then used to run the application in safety mode. At the
same time the sensor error will be shown in the display.
Ert and ESt values are based on OEM experience and are by default inactive.
1 Click: Temperature setpoint
Ert and ESt define the duration the compressor will run (Ert) and be idle (ESt).
Sub function: Down
Example: Ert = 4 [min] and ESt = 16 [min] will provide an average cooling system
activity of 20%.
1 Click: Temperature setpoint
Sub function: Down
ight mode
nctionallity: 1 Click: Temperature setpoint
Minimum Sub cut-in voltage / uLi
function: Up
Minimum cut-out voltage / uLo
Maximum voltage / uHi
ight mode
1 Click: Temperature setpoint
These three parameters provide voltage protection to the compressor. Start by
Sub function: Up
setting uHi, followed by uLo and uLi.
uLi: When the compressor is due to start, the voltage of the power supply will be
1 Click: Temperature setpoint
checkedSuband the compressor will only be allowed to start if it is at least the value
function: Down
given in this parameter.
uHi: When the compressor is running, it will be switched off if the voltage exceeds
1 Click: Temperature setpoint
that given in this parameter. If the compressor is already stopped, it will remain
Sub function: Down
nctionallity:
102
ight mode
1 Click: Temperature setpoint
nctionallity: Sub function: Up
102
ight mode
Power On Delay
1 Click: / Podsetpoint
Temperature
Sub function: Up
This is the delay in seconds between power-on and the compressor being
activated. Depends on the Power on Temperature setting as explained below.
Functionallity:
102 Power Factor / PFA
This value is hidden by default. The parameter is used by the Zero Cross function
O/Night mode to optimize1 Click:
the Temperature
switchingsetpoint
position of the relay contact.
1 Click: Temperature setpoint
unctionallity: SubSub function:
function: DownUp
Warning: Do not change without first consulting your local
Danfoss representative.
Night mode Initical 1Cut-in
1Click: / iCi setpoint
Click:Temperature
Temperature setpoint
Sub
Sub function:
function: Down
Up
if the control temperature is between cut-in and cut-out at power up customers can
determine if the compressor shall start immediatly (yes) or wait for cut-in tempera-
ture to start (no).
Power on Temperature / PoT
This parameter is used to accelerate the first application test on the OEM assembly
ht line; if the cabinet temperature
1 Click: Temperature setpoint is higher than this parameter the Power On Delay is
Sub function: Down
overruled and the outputs are activated without delay.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Defrost on compressor
dCt no no yES no 1 -- -- RW
time
102
ight mode
will occur.
1 Click: Temperature setpoint
When setSubto EL orUp
function: nAt, electrical, natural or off-cycle defrosting is used. An ad-
ditional setting of Hgd (hot gas defrosting) is available.
nctionallity:
1 Click: Temperature setpoint
102
Sub function: Down
Terminate Temperature / dtt
ight mode This parameter defines at what temperature the defrost cycle will stop.
1 Click: Temperature setpoint
The temperature is given by the evaporator sensor or by the cabinet
Sub function: Up
temperature sensor if no evaporator sensor is used.
nctionallity:
102
ight mode 1 Click:counter
The defrost Temperature
issetpoint
saved and restored at power-up, but if the temperature
1Sub
Click: Temperature
function: Down setpoint
sensor, used for defrost,
Sub function: Up is higher than this value at power-up, it is assumed that
the evaporator is free of ice and the defrost counter will be cleared.
nctionallity:
102
ight mode
checked and if the Terminate Temperature dtt has been reached, the defrost
1 Click: Temperature setpoint
cycle willSubend. If dtt has not been reached, defrost will continue until either dtt is
function: Up
reached or the Maximum Time dAt reached, whichever occurs first.
1 Click: Temperature setpoint
Sub function: Down
nctionallity:
Maximum Time / dAt
This parameter can be set to between 0 and 240 minutes and defines the maxi-
ight mode mum duration of a defrost
1 Click: Temperature cycle.
setpoint
The ERCSub
102 will not
function: Up allow a maximum time to be entered which is less than the
minimum time, or a minimum time which is more than the maximum time.
nctionallity:
02
is complete.
If the time set in Fdd occurs before the temperature set in Ftd, the fan will start
ight mode in line with Fdd. If the temperature set in Ftd occurs first, then the fan will start in
1 Click: Temperature setpoint
line withSubFtd. It is Up
function: therefore a case of whichever parameter’s setting is reached first
1 Click: Temperature setpoint
ctionallity: which determines when the fan starts.
Sub function: Down
If this parameter is set to nO, then defrost cycles are related to elapsed time,
regardless of how long and how often the compressor has been on.
102 ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Fan FAn
nctionallity: Fan always On FAo yES no yES no 1 Click: Temperature
1 setpoint
-- -- RW
102
ight mode
Fan Always On / FAo
1 Click: Temperature setpoint
If this parameter
Sub function:is
Upset to yES, all other parameters in this section
about the fan are deactivated.
102
nctionallity: NOTE: If FAo is set to nO, then the following parameters will be applied.
102
1 Click: Temperature setpoint
Fan On SubDelay / Fod
function: Up
1 Click: Temperature setpoint
Fan StopSubDelay / FSd
function: Down
If this parameter and FSd are both set to zero then the fan runs whenever the
102
nctionallity: compressor runs.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Energy management Eng
Shop Light Day SLd 50 0 100 no 1 Click:
% Temperature
1 setpoint
RW RW RW
Shop Light Night SLn 50 0 100 no % 1 RW RW RW
Sub function: Down
102 Eco Activity delay
Eco Light delay
EAd
ELd
0
5
0
0
360
10
no
no
min
min
1
1
RW RW RW
-- RW RW
Light Blocking delay Lbd 0 0 360 no min 1 -- RW RW
Eco Temperature Offset Eto 4.0/7.2 0,0 10.0/18.0 C/F r K/°R .1 -- RW RW
102
nctionallity:
NOTE: Some of these parameters require the installation of the Danfoss Ambient Light Sensor.
ight mode
nctionallity: The Danfoss USB Gateway in combination
1 Click: Temperature setpoint
with KoolProg software allows for real time measurement of the
Sub function: Up
current light intensity. Danfoss recommends testing and adjusting SLd and SLn values according to custom-
ers’ specific needs.
ight mode
1 Click: Temperature setpoint
102
The light blocking delay disables the light-sensor for a given time after ambient
light change from bright to dark, so that the cooler stays in ECO mode for at least
ight mode this time.1 Click:
When the cooler is in serving or pull-down mode, the light sensor is
Temperature setpoint
de-activated and Up
Sub function: a change to ECO mode will be determined by the door-sensor.
0: No blocking of the ambient light sensor.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv 1 Click: Temperature setpoint
Shop Ser OEM
ight mode
102
1 Click: Temperature setpoint
Sub function: Up
102
ight mode hour, then pull down will start. The compressor will have already cut-in, so the only
1 Click: Temperature setpoint
effect is Sub
to function: Up
stop defrost cycles until the desired temperature is reached. The period
of one hour is fixed and cannot be altered.
102
nctionallity:
102
ight mode
1 Click: Temperature setpoint
Sub function: Up
nctionallity:
Automatic Heater Mode Enable / AuH
102
This setting is normally set to nO.
ight mode
When set to yES,
1 Click: parameters
Temperature setpoint End and Hdi apply.
Sub function: Up
nctionallity:
Energy 1Mode Delay /setpoint
Click: Temperature End
This is the
Subdelay inDown
function: minutes between the heater and the compressor operation.
ight mode
The heater1 Click:
is Temperature
not allowedsetpoint
to start until this number of minutes has expired after
Sub function: Up
the compressor has cut out and vice versa.
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
102
nctionallity:
102
ight mode
1 Click: Temperature setpoint
Sub function: Up
nctionallity:
102
ight mode
Condenser Block Limit / CbL
1 Click: Temperature setpoint
This parameter
1Sub
sets
function:
Click: Up
thesetpoint
Temperature
temperature which if reached will cause the compressor
to switchSuboff.
function: Down
nctionallity:
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv Shop Ser OEM
Display diS
ight mode
This section deals with parameters1for the
Click: display.setpoint
Temperature
nctionallity: Sub function: Up
NOTE: Some display parameters can be set in such as way that they may be illegal in some jurisdictions. Please
check local legislation.
ight mode
1 Click: Temperature setpoint
DisplaySub
Unit / CFu
function: Up
This parameter sets the display to Fahrenheit or Celsius. Switching from one to the
102 other will cause all temperature settings to be automatically updated accordingly.
102
nctionallity:
102
ight mode
1 Click: Temperature setpoint
Sub function: Up
nctionallity:
nctionallity:
Lock Time After Defrost / dLt
In order1not
Click:to
Temperature
show a setpoint
rising temperature during defrosting, the displayed tem-
102
ight mode
Sub function: Down
perature is locked at the temperature shown at the start of the defrost cycle for the
1 Click: Temperature setpoint
numberSubof function:
minutes Up set in this parameter.
0 = no lock.
nctionallity:
1 Click: Temperature
Show Economy Statesetpoint
/ SEC
102
ight mode
ECO mode.
Sub function: Down
If set to yES, this parameter causes the display to show ECO when the system is in
1 Click: Temperature setpoint
Sub function: Up
If set to nO, the temperature continues to be displayed.
nctionallity:
Assignments ASi
ERC menu Default Min Max Unit Unit Scale Default Access
code Conv 1 Click: Temperature setpoint
Shop Ser OEM
Dimensions:
71 mm
36,5 mm
28,5 mm
28 mm 71 mm
30 mm
78,25 mm
82,25 mm Rear mounting
ERC menu
Description
code
Set point adjustment ratio SPr Current setpoint adjustment value diF * SPr
ERC menu
Description
code
High Temp Alarm HAt Alarm is activated above this temperature (Celsius)
Low Temp Alarm LAt Alarm is activated below this temperature (Celsius)
Pulldown delay Pdd Alarm delay during pulldown (0-960 minutes) (high temperature only)
Door Open delay dod Alarm delay for door open (0-60 minutes)
Alarm Buzzer Duration Abd Alarm buzzer duration in minutes (0=no buzzer)
Auto Clearance of ACA yES: alarm auto-clears if system returns to normal; nO : alarm state maintained regardless
Alarm/Error
ERC menu
Description
code
Min run time Crt Minimum time compressor must run 0-30 minutes
Min Stop time CSt Min time compressor must idle 0-30 minutes
Max Off time Cot Max time compressor must idle 0-480 minutes
Compressor door open Cdd Minutes before compressor stops when door opened
delay
Error run time Ert Compressor run time if temperature sensor is not working (0-60 minutes)
Error stop time ESt Compressor stop time if temperature sensor is not working (0-60 minutes)
Minimum Cutin voltage uLi When compressor is off: Lowest compressor start voltage (0-270 V)
Minimum cut-out voltage uLo When compressor is on: Lowest operation voltage (0-270 V)
Maximum voltage uHi When compressor is on: Highest operation voltage (0-270 V)
Power On Delay Pod Delay in seconds after power-on before outputs active (change with care)
Power Factor PFA Phasic angle in degrees. Changing this may give decreased relay lifetime
Power-on temperature Pot If the temperature of compressor at power-on exceeds this then Power On Delay does not apply
Def terminate temp dtt Temperature at which defrost cycle will stop
Def Min Interval dii The minimum time in hours between the start of each defrost cycle
Def Max Interval dAi The maximum time in hours between the start of each defrost cycle
Def Min Time dit The minimum duration of a defrost cycle in minutes
Def Max time dAt The maximum duration of a defrost cycle in minutes
Drip off time dot The duration in minutes of the drip-off time at the end of a defrost cycle
Fan delay after Defrost Fdd The duration in minutes before the fan starts after a defrost cycle
Fan start Temp Ftd The temperature at which the fan will start after a defrost
Defrost Fan on dFA Whether the fan will run during a defrost cycle
Initial Defrost Interval idi The number of hours after power-up before the first defrost cycle starts
Defrost on compressor dCt Whether the defrost cycles are measured by elapsed time (nO) or compressor run time (yES)
time
ERC menu
Description
code
Fan always On FAo nO: fan parameters below active. yES: Fan is always on
Fan On Delay Fod Delay in seconds before fan starts after compressor starts
Fan Stop delay FSd Delay in seconds before fan stops after compressor stops
Fan On Cycle FoC The number of seconds the fan runs when the compressor is off
Fan Stop Cycle FSC The number of seconds the fan does not run when the compressor is off
ERC menu
Description
code
Shop Light Day SLd When ambient light is above this level, Eco mode is cancelled. Requires light sensor
Shop Light Night SLn When ambient light is below this level, Eco mode is enabled. Requires light sensor
Eco Activity delay EAd Minutes delay after last door opening until ECO mode is enabled; 0: disable
Eco Light delay ELd Delay [min] between detection of shop light on/off and ECO mode activation / suspension
Eco Temperature Offset Eto Temperature increase for Eco mode relative to normal mode
Pull-down Initiate Pit If the cabinet temperature is above this temperature for >1h, pull-down mode is activated
Temperature
Pull-down Cycling PCy Minimum duration [min] of the pull-down mode, starting at PiT
Pull-down defrost Interval Pdi Defrost interval during pull-down. Over-rules the defrost interval in normal mode.
Pull-down duration Pdd Maximum duration [min] of the pull-down mode, starting at PiT
Pull-down limit temp PLt A safety feature; the lowest temperature allowed during pull-down.
Pull-down reduction Prt A calculation value for pull-down performance improvement. Instructions: See manual
temp Δt
ERC menu
Description
code
Auto-Heater Control AHC Auto-Heater settings (only if heater fitted for outdoor use in cold climates)
Automatic heater mode AuH yES: Activate heater if ambient temperature is below desired cabinet temperature
enable
Energy mode delay End Delay in minutes between heater and compressor operation
Heater displacement Hdi Heater displacement or OFFSET temperature relative to desired temperature.
temperature
ERC menu
Description
code
Condenser Alarm Limit CAL If condenser sensor exceeds this temperature, alarm is activated
Condenser Block Limit CbL If this temperature is exceeded, compressor will be stopped.
Condenser OK limit CoL Temperature at which compressor may start after a stop due to exceeding CbL
Condenser Low Temp. CLL Temperature below which the compressor is not allowed to start
Limit
ERC menu
Description
code
Display Resolution rES Display resolution for temp: 0.1, 0.5 or 1.0 C/F
Display Range Limit rlt Limits displayed temperature to actual setpoint +/- differential; may be illegal in some countries
Display Delay ddL Time period for moving average temperature display
Lock-time After defrost dLt Display lock time after defrost [0-60 min]
Show Economy state SEC yES: display will show “Eco” when in Eco mode. nO: temperature will be shown
Show Pull Down state SSC yES: “SC “ will be displayed during Pull down; nO: “SC “ will not be displayed.
Show Defrost SdF yES: display will show deF during defrost ; no: Display will show temp
Display Intensity din Display intensity when no ambient sensor; min intensity with sensor
S1 Config S1C Sensor type input 1 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
S2 Config S2C Sensor type input 2 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
S3 Config S3C Sensor type input 3 :Stn: Standard NTC 5k @25°C (EKS211); Ldr: Light sensor; dig: binary input
DO1 Config o1C CoP: Compressor; PiL: Pilot Relay (No zero-cross); HEt: Inverse output, Heating application
DO2 Config o2C no:Not used; dEF: Elec defr heater/hot gas valve;ALA:Alarm output;FAn:Fan control;Lig:Light control
DO3 Config o3C nO: Not used; ALA: Alarm output; FAn: Fan control; Lig: Light control
DO4 Config o4C nO: Not used; ALA: Alarm output; Lig: Light control
Pass-word level1 PS1 Level 1 Password (End user, shop owner), 0= disabled
Pass-word level3 PS3 Level 3 Password (OEM), 0= disabled; choose a secure number, e.g. 735
Light off delay Lod Light off delay [sec] after door has been closed
Door open counter ont ont/100 = Number of door openings since last reset
Parameter version PAr OEM parameter version number [requires EKA copy key update]
Manufacturing date CHd Programme date WWY: week number and year number (2010-19)
Set as Default SFC Resets all parameters to last good OEM settings
ERC 102C RED LED without buzzer 080G3102 PVC Standard (C2), 470 mm, 2-pole 077F8780
ERC 102D RED LED without buzzer 080G3103 PVC Standard (C2), 1000 mm, 2-pole 077F8786
ERC 102C BLUE LED without buzzer 080G3106 PVC Standard (C2), 1500 mm, 2-pole 077F8790
ERC 102D BLUE LED without buzzer 080G3107 PVC Standard (C2), 2000 mm, 2-pole 077F8794
ERC 102C RED LED with buzzer 080G3113 PVC Standard (C3), 1000 mm, 3-pole 077F8756
ERC 102D RED LED with buzzer 080G3112 PVC Standard (C3), 1500 mm, 3-pole 077F8760
ERC 102C BLUE LED with buzzer 080G3116 PVC Standard (C3), 2000 mm, 3-pole 077F8764
ERC 102D BLUE LED with buzzer 080G3117 PVC Standard (C3), 2200 mm, 3-pole 077F8766
Light-sensors
Light sensor, 2000 mm (C3), 3-pole 080G3313 TPFE low temp (C1), 1000 mm, 3-pole 077F8657
Light sensor, 3000 mm (C3), 3-pole 080G3315 TPFE low temp (C1), 2000 mm, 3-pole 077F8665
Door-sensor, 1000 mm (C4), 3-pole 080G3332 TPE precision (C1), 1500 mm, 3-pole 077F8726
Door-sensor, 2000 mm (C4), 3-pole 080G3334 TPE precision (C1), 2000 mm, 3-pole 077F8727
Door-sensor, 3000 mm (C4), 3-pole 080G3336 TPE precision (C1), 2500 mm, 3-pole 077F8728
Temperature sensors
PVC Standard (C1), 1000 mm, 3-pole 077F8757 Black (2 needed per controller) 080G3308
ERC 102 Reference manual – APPENDIX II: CODE NUMBERS AND LENGHTS 51
Compressor does not start Waiting for compressor delay timer Check CoP->CSt
Fan does not start Door is open or door contact is defective Fan stops when door is opened
Defrost does not start Controller in pull-down mode Defrost might be delayed during pull-down
Check Pud->Pdd
Shift between Eco and Normal mode does Ambient light sensor broken Check Eng->SLd, SLn
not happen on ambient light change or light level not set properly
E01, E02 or E03 is shown on display E01: Sensor S1 defective Replace sensor
Display alternates between Con and Condenser too hot Clean condenser
temperature
Check Con ->CAL, CbL
Display alternates between Lo and Temperature too low Check ALA -> LAt
temperature
ERC 102C
3 relays
Fan
Compressor
ERC102D
1 2 3 4 5 6 DO’s
Controller
LL
ERC102C
1 2 3 4 5 DO’s
Controller
LL
Fan
Compressor
ERC102D
1 2 3 4 5 6 DO’s
Controller
ERC102C
1 2 3 4 5 DO’s
Controller
Note: This is a typical (default) wiring diagram since both inputs(AI/DI’s) and outputs (DO’s) can be assigned
differently. Please see manual for further details, folder “ASi”, Assignment.
Placement of sensor:
Placement of sensor:
Place the sensor where the ice melts last.
Please be aware of that sharp finns can damage the
cable.
Placement of sensor:
Place the sensor at the liquid side of the condenser.
Use a metal bracket or metal tape to ensure good
thermal conductivity. Be sure that the cable does not
pass hot spots at the compressor or condenser that
exceeds 80°C.
Placement of sensor:
The sensor must be placed so that the interior light
does not affect the sensor.
Possible placement could be in the front of the
cooler or at the top.
Output Input
Application ERC type
DO1 DO2 DO3 DO4 S1 (C1) S2 (C2) S3 (C3) Di (C4)
Standard Beverage Condenser or
ERC102C Comp Fan Lamp Control Defrost Door
cooler Ambient Light
Sub-zero beverage Condenser or
ERC102D Comp Heater Fan Lamp Control Defrost Door
cooler Ambient Light
Out-door beverage
ERC102D Comp Heater Fan Lamp Control Condenser Ambient Light Door
cooler
Nofrost freezer w. Condenser or
ERC102D Comp Heater Fan Lamp Control Evaporator Door
glassdoor Ambient Light
CFF Refrigerator ERC102C Comp Fan Lamp Control Defrost Condenser Door
CFF Freezer ERC102D Comp Heater Fan Lamp Control Defrost Condenser Door
C: connector type
NOTE:
• Select only one function per input, e.g. condenser sensor or ambient light sensor.
• Make sure that the accessory you select has a matching connector to the input, e.g. a sensor for input S2 must
have C2 connector.
• Condenser sensor or light sensor are optional and can be omitted.
• Defrost sensor is mandatory when electrical heater is used for defrost. For natural defrost it can be omitted.