Continuity Testing Procedure For
Continuity Testing Procedure For
Continuity Testing Procedure For
1. Place reference electrode in contact with the soil at a location remote (25 – 100 feet) from
all cathodically protected structures. You must ensure that the remote reference electrode
placement is not in proximity to any other cathodic protection systems (e.g. natural gas
pipelines) or directly over any buried metallic structure in order to minimize the chances of
unwanted interference.
2. Be sure that reference electrode is firmly placed in moist soil and is not in contact with any
vegetation.
3. Connect reference electrode to the negative terminal of voltmeter using a long spool of
suitable wire.
4. Connect positive lead wire to voltmeter. This lead wire should have a sharp test prod
(scratch awl or similar) in order to assure good contact with the metallic structures under
test.
5. Place voltmeter on 2 volt DC scale.
6. Contact each buried metallic structure with the positive test lead without moving the
reference electrode. Typical items that would be tested during a continuity survey include:
all tanks, tank risers, submersible pump heads, piping, flex connectors/swing joints, vent
lines, electrical conduits, dispensers, utilities, etc.
7. Obtain voltage for each component and record on the continuity testing portion of the form
8. Voltages for each component that is tested must be obtained as quickly as possible since
the observed potential can change over time. This is because the conditions in the soil
where the reference electrode is placed can change over a relatively short period of time.
If two or more structures exhibit potentials that vary by 2 mV or less, the structures are
considered to be electrically continuous.
If two or more structures exhibit potentials that vary by 10 mV or greater, the structures are
considered to be electrically isolated.
If two or more structures exhibit potentials that vary by more than 2 mV but less than 10 mV,
the result is inconclusive and further testing (point-to-point) is necessary.
Note: Testing with this method does not require a reference electrode. The two structures of interest
are simply connected in parallel with the voltmeter and a determination made as to whether or not
any potential difference exists between them.
Point-to-Point Data Interpretation
If the voltage difference observed between the two structures is 1 mV or less, this indicates
that the two structures are considered to be electrically continuous with each other.
If the voltage difference observed between the two structures is 10 mV or greater, this
indicates that the two structures are considered to be electrically isolated from each other.
If the voltage difference observed between the two structures is greater than 1mV but less
than 10 mV, the result is inconclusive and further testing beyond the scope of this document
is necessary.
Data Interpretation
If the instant off potential is -850 mV or more negative, the 850 off criterion is satisfied and it
is judged that adequate cathodic protection has been provided.
If the instant off potential is more positive than -850 mV, the tank may or may not be
adequately protected and a 100 mV polarization test is necessary.
If the structure exhibits more than 100 mV polarization, the 100 mV polarization criterion is
met and it is judged that adequate cathodic protection has been provided. If you are unable
to meet either the 850 instant off or the 100 mV polarization criteria, it is judged that
adequate cathodic protection has not been provided and repairs/modification are indicated.
Alternatively, a person qualified as a corrosion expert could evaluate/conduct the survey and
determine that cathodic protection is adequate based on their interpretation.
-850 or MORE Steel structure protected by impressed current system meets regulatory requirements and
NEGATIVE cathodic protection is judged to be adequate. A potential measurement of -850 mV or more
“OFF” negative with the protective current temporarily interrupted (850 off) is considered to be the
best indicator that adequate cathodic protection has been provided.
MORE Instant off potentials more negative than -1220 mV are theoretically not possible. If you
NEGATIVE observe an instant off potential more negative than -1220 mV, you should suspect stray
THAN -1220 mV current is affecting the protected structure. Consult a corrosion expert immediately since
“OFF” stray current can cause a rapid corrosion failure of the protected structure.
Usually means that a high resistance exists in the ground bed that is causing a large
MORE voltage drop. This condition is normally evident by checking the rectifier output since the
NEGATIVE voltage is very high but the amperage is relatively low. However, you should be cautious
THAN -2000 when abnormally high voltages are observed since this can have a detrimental effect on
“ON” cathodically protected structures or the anodes may be rapidly depleted. Stray current may
also be generated that can adversely affect other buried metallic structures such as
waterlines and other utilities. Consult a corrosion expert whenever it is suspected that
too much voltage is being generated.
If the voltmeter readings vary, you should suspect that stray current may be affecting
VARIABLE the cathodically protected structure. Sometimes, the stray current can cause a pattern to
“ON” or “OFF” develop that is recognizable. An example would be the on/off pattern of a nearby DC
powered welding operation. A corrosion expert must be contacted immediately since stray
current can cause a corrosion failure in a relatively short period of time.
RAPIDLY If the voltmeter will not stabilize, it usually means that there is a high electrical resistance
somewhere. Check all lead wires and connections and make sure that you are making
FLUCTUATING a solid and clean metal-to-metal connection. Soil where the reference electrode is placed
“ON” or “OFF” could be too dry. Add water to the soil or wait until a heavy rain occurs and try again.
Petroleum contaminated soils may cause a high contact resistance. The tip of the reference
electrode may need to be cleaned or replaced.