N. SCHUSTER1, M. SPANGLER2
Siemens AG1(GER), Siemens AG2(GER)
SUMMARY
With the extensive use of IEC61850 and the GOOSE technology in today’s power systems, it is
possible to make network SMART. For teleprotection or signal comparison, interoperability is
possible for direct communication links. The paper will describe the use of GOOSE messages as
signal comparison or teleprotection messages across substations for feeder protection.
Overcurrent or distance protection devices can only clear faults that occur on the protected line
selectively after a delay time. In such cases to achieve non-delayed and selective tripping on 100% of
the line length for all faults, the protection devices should exchange and process information with the
opposite end by means of signal transmission systems. The signal transmission system consists of the
signal transmission equipment and the communication media over which the information are sending
between substations.
Today the transmission of teleprotection information is typically done with dedicated and / or
proprietary extra equipment, e.g. via direct fiber links, via multiplexers with 2MBps or also 64kBps
connections. These connections are reserved exclusively for the directional or teleprotection signal and
no other information can be transmitted via this channels.
The use of GOOSE messages for transmitting high-speed binary information within a substation or
protection scheme is now widely accepted. However, until now the exchange of GOOSE messages is
typically done only with devices located within the same substation. Using IEC61850 and the GOOSE
mechanism it is possible to transmit all sorts of information via the Ethernet network, such as
indications, counters and measurement values.
The evolution of Ethernet and its substation-to-substation (ss2ss) connection has opened up new
possibilities for replacing the conventional teleprotection equipment by effective use of the GOOSE
messages for the information exchange between substations. Tagging of telegrams together with
modern switching technology allow new communication topologies.
This paper will highlight the use of GOOSE messages for inter substation communication. Detailed
description of the engineering process will show how to setup the application with modern system
configuration tools. Nevertheless if the principle and the functionality of GOOSE is understood and
one has a powerful system configuration tool , the means to apply a ss2ss communication interface
with the same functionality and reliability as we would exchange a GOOSE message from one relay to
another inside a substation.
This paper will describe different transmission schemes with the use of GOOSE messages instead of
conventional teleprotection techniques. Comparison of the transfer time with GOOSE and a
conventional teleprotection system will be done.
The use of GOOSE for the teleprotection and directional comparison not only minimizes the need for
separate communication equipment but also reduces the need for extra inputs and outputs in the relay
hardware and thereby reducing the initial overall investment and later the asset management costs of
the widely used distance protection scheme. Especially if high bandwidth connections are available
between substations GOOSE will become a full alternative to conventional teleprotection solutions.
KEYWORDS
1
1. INTRODUCTION
The use of GOOSE messages to transmit high-speed information via an IEC61850 station bus within a
substation or protection scheme is now widely accepted and almost regarded as ‘old hat’. However, up
until recently the exchange of GOOSE messages was typically only done for devices located within
the same substation over an Ethernet network.
With the IEC61850 standard becoming so widely accepted around the world and its application in
more than a thousand systems / substations around the world its application has begun to evolve into
areas not previously thought of. The need for exchanging GOOSE messages from one substation to
another or one V-LAN to another has become quite apparent and it is this that we try to describe in
more detail here.
With relatively basic knowledge of the GOOSE messages and the systematic application thereof in the
DIGSI system configuration, it is quite easy to create a setup for inter substation communication via
GOOSE.
In this example we describe the exchange of a directional signal of two directional phase overcurrent
relays. The directional signals are transmitted bi-directionally between the two substations, that being
substation A and substation B using an IEC 61850 GOOSE message. The relays in both substations
will use the directional indication from the local and remote end to make an instantaneous trip
decision, this if the fault is in the overhead line or cable between the devices protecting it. Measured
voltages and currents are used for the directional decision on both sides. This application is similar to
teleprotection schemes used for distance protection. For teleprotection also directional indications are
exchanged.
Today the transmission of teleprotection information is typically done with dedicated and/or
proprietary equipment, e.g. via direct fiber links, via multiplexers with 2 Mbit/s or also 64 kbit/s
connections. Also low bandwidth PLC – equipment is used widely. These connections exclusively
used for teleprotection information, so other information cannot be transmitted via this connection in
parallel.
A typical setup for teleprotection is shown in figure 1. It is assumed that the protection device has an
integrated digital interface in this example. This digital interface allows mirroring binary signals over
a serial communication link. Converters allow the adaptation to communication equipment or a direct
fiber optical link is used. This configuration is very similar to the configuration used later for GOOSE,
because the digital interface is directly integrated in the device. However propriety telegrams are used
and devices from the same vendor must be placed on both sides. Traditional schemes using a contact
as relay output and connect it with a binary input of the teleprotection equipment. Signal transfer is
then done between teleprotection equipment from the same manufacturer. In the other substation, a
contact of the teleprotection equipment is again used to indicate the directional information on a
binary input of the relay.
2
Figure 1: Existing setup for teleprotection communication with integrated digital serial
interface.
3
3. FUNCTIONAL CHART OF DIRECTIONAL COMPARISON
The following chart shows the principle of the directional comparison of two O/C relays.
Teleprotection schemes look very similar. This paper will not discuss directional comparisons or
teleprotection methods and focus on the transfer of signals required for the specific applications.
TRIP TRIP
R R
A I
S I B
& S &
Data link
t1 t1
t1 Time delay
At the beginning and end of the line A to B respectively, the application of directional time-over
current protection with directional comparison logic function is installed. In the instance of a fault on
the line part A – B both devices sense “short circuit forward”. In this instance no blocking signal is
transferred to the remote end and both protection devices trip with a time delay t1. This time is set to
30-50 ms in order to safely receive the blocking signal.
Using IEC61850 and the GOOSE mechanism it is possible to transmit all sorts of information via the
Ethernet network, such as SP (single point indications), DP (double point indications), counters and
measurement values. At present the ss2ss-communication philosophy is not described in the IEC61850
standard Edition 1, but will be included in editions 2 of the IEC standard in more detail together with
the file exchange and engineering process. Nevertheless if the principle and functionality of GOOSE is
understood and one has a powerful system configuration tool such as DIGSI, you have the means to
apply a ss2ss-communication interface with the same functionality and reliability as you would have
exchanging a GOOSE message from one relay to another inside a substation.
The network sketch in figure 4 shows a typical setup for communicating between different
substations. The IEC 61850 network in each substation in built by one or more optical Ethernet ring
configurations, which are connected with switches. GOOSE – messages are send between the devices
inside the substation and client – server communication is running between devices and a substation
controller. If the substations are linked by a layer 2 communication network, which may be also a fiber
optical link, one must avoid that all GOOSE – messages from one substation are transferred to the
other substation via this link. Only one or a few selected telegrams that contain the exchanged
directional signals must pass through this link.
5
Figure 4: Setup for inter substation communication
The representation of the cloud in-between the substations can be affected in a number of different
ways and is dependant on the existing infrastructure as to how to best establish this interconnection.
This topic is touched on in more detail in the chapter 6. The task for this application to work is to
transfer a layer 2 Ethernet datagram over an IP – network.
This chapter shows in detail the engineering in the configuration tools. Traditional wiring is done now
by drawing logical connections in system configuration software. Using devices of different vendors
on both sides this logic must be tested intensive, because the IEC 61850 standard does not describe the
application.
Prerequisite: In the DIGSI projects for each of the substations the internal communication - all the
devices / IEDs must be configured for a client / server communication relationship using the IEC
61850 protocol for GOOSE functionality between the devices. In our example only the additional
settings for ss2ss communication are mentioned, but not the settings for normal substation internal
communication.
First the blocking signals, which shall be transmitted, must be calculated in a CFC-Chart, (Continuous
Function Chart), by the phase segregated directional indications. This reverse or forward indication is
calculated by the relay after a pickup condition from the measured currents and voltages. These
indications are assigned as inputs of a CFC-Chart (see Fig. 5). The output signal ´Reverse Direction´
of the CFC – chart must be created as a single point indication and is assigned as an output (source) of
the CFC-chart. The application will be named substation-to-substation communication (SS2SS Com)
(see Fig. 5).
6
Fig. 5: Assignment of directional signals as input of a CFC – chart
The signal output of the logical block must now be transmitted to the other substation. Therefore, the
signal is configured to the IEC 61850 substation control interface (S) as a destination (output) and can
be used later in the System Configurator as an input for a GOOSE message. By assigning this signal to
S the configuration software automatically, create an entry in the ICD-file, which is a XML –
description of the signals of the device, which can be used in the System Configurator and must later
be imported in the system configuration of the other substation.
In the CFC-chart the calculation must be done in a “fast-plc”-task (see Fig. 6) to generate the output
with an approximate 5 – 10 millisecond delay. An OR-Gate is used to create the group indication for
´reverse´.
7
Fig. 6: CFC – Chart for group indication ´reverse´ from the phase segregated inputs
That indication ´reverse´ will also be created in substation B and must be transmitted via GOOSE to
substation A. A single point indication must be created to subscribe that information of the other
substation (see Fig. 7) in each relay.
The directional blocking information has to be configured to the CFC as a source (see Fig. 8).
This information will be connected via the CFC-chart to block the directional overcurrent (see Fig. 9).
8
Fig. 7: Create an external single point indication for receiving the ‘reverse’ indication
Fig. 9: CFC-chart for interconnecting the “reverse direction” information to BLOCK I>
Directional
9
Export the ICD-files of both devices (Fig. 10) and import them in the respectively other DIGSI project
(Fig. 11) and integrate them in the station configurator (Fig. 12 and 13).
Fig. 10: Export of ICD-file of substation A Fig. 11: Import of ICD-file in substation B
Fig. 12: Integration in station configurator of Fig. 13: Integration in station configurator
of substation A substation B
Set the interconnections for the GOOSE messages in both DIGSI projects, as shown in Fig. 14 for
substation A. Pleases ensure and check that the properties of the GOOSE application (Fig. 14 ) and the
datasets (Fig. 15 and 16) are identical in both projects.
These properties will be automatically created by DIGSI (APP-ID, VLAN-ID, VLAN priority, Dataset
name, GOOSE Control Name, GOOSE-ID, Config revision and MAC-address). Under normal
conditions the values proposed by the system can be taken without changes, but not the VLAN-ID.
The VLAN-ID shall have a unique value, which is just used for the ss2ss communication. One
telegram with the GOOSE properties is used for the exchange the information. The ss2ss – application
should be the first GOOSE application in an IEC 61850 project for both substations, to ensure that
they both have identical parameters automatically.
An expert mode in the system configurator allows adapting single values of this GOOSE – telegram.
10
Fig. 14: Configuration of GOOSE – messages for SS2SS – communication in
substation A. The same engineering step must be done for B.
11
Fig. 16: Properties of the GOOSE message in substation B
Save and close the station configurator. The content of the substation configuration file (SCD – file) is
automatically created and the devices are updated afterwards with this information by the
configuration tool of the vendor. The GOOSE – telegram which is exchanged between the substations
is now content of both SCD – files and will be sending out by both devices after the update. This can
be checked online with test tools or by a Browser on each sending device.
Different connections for intersubstation communication are available. Low bandwidth connections
can not be used for the direct transfer of GOOSE – messages like in traditional teleprotection schemes.
A typical GOOSE – message for this application have 160 – 200 Bytes. Bandwidth calculation must
consider how often this message is repeated if a change occurs. If it’s repeated heavily every
millisecond 1,6 Mbit/s are enough.
This type of connection is achieved through a dedicated fibre optical connection. Switches of different
substations can be connected together directly or via a router (see Fig. 18). These devices must be able
to support layer 2 - GOOSE tunnelling, this more dependent on the size and design of the network.
Bandwidths of up to 1 Gbit/s is possible, but is really not necessary for this application because only
160 – 200 Bytes must be transmitted over this 100 Mbit/s or 1 Gbit/s connection. Even if the GOOSE
– telegram is repeated every 1 ms the channel will be loaded with max. 1,6% if a 100 Mbit/s
connection is used. Typically a GOOSE – message will be repeated every second under steady state
conditions and after a change in a signal rapidly after 1 ms – 5 ms only for a short time. This fast
repetition time (maxGOOSE) is settable for each GOOSE – telegram in the sending device.
12
Fig. 17: Different communication opportunities for ss2ss – communication with GOOSE
VDSL-switches
This type of connection is achieved via available substation hardened VDSL-switches. Distances of up
to 4 km between substations are possible. The switches are directly connected with simple pilot wires
(1 pair). The bandwidth will be dependant on the distance and diameter of the pilot wires and will
have a bandwidth of up to 40 Mbit/s or more.
Routing layer 2 GOOSE – messages to an E1 – interface (2 MBit/s G.703.6 interface)
A converter is connected with the Ethernet network and receives the dedicated GOOSE – messages for
ss2ss communication from a port of a switch which is programmed to pass the layer 2 telegrams
through, with their specific VLAN-ID or multicast address.
The other side of the converter is connected to a G703.6 – interface with a multiplexer. Through a
switched SDH – network the telegrams will be transferred via a point to point connection to the other
substation and converted again into Ethernet based GOOSE – telegrams.
One parameters of a GOOSE – telegram is the VLAN-ID. With this ID you split one physical layer 2
network into multiple logical networks. This sounds complex, but is in fact a simple way to separate
GOOSE messages and is ideal for the described application. For ss2ss communication it is neither
necessary nor useful to transmit all available GOOSE messages between the different substations. You
just want to transmit the one GOOSE telegram you have created for ss2ss communication. So in the
system configurator you provide a unique VLAN-ID for this ss2ss GOOSE.
13
Fig. 18: VLAN-ID setting in DIGSI station configurator
The default value for the VLAN-ID is “0” in the IEC61850 standard. Typically it is not necessary to
change this default value, but for ss2ss communication it is quite useful to avoid useless network
traffic via the inter substation connection which will often be the bottleneck of any network, if there is
any.
The port of the Ethernet switch, which is connected to the other substation, has to be configured as a
member of the same VLAN. This has to be done in both substations. That’s all. Now all other GOOSE
messages are separated and will not be transmitted to the other substation.
If existing or other settings for VLAN-IDs for other GOOSE-messages have to be considered in the
Ethernet switch configurations, the same can be achieved by setting a multicast filter in the Ethernet
switch. This means that one has to set a filter for every GOOSE which is available at the bus, but not
the GOOSE you want to transmit. This requires a little more work and effort to configure on all the
affected switches, because every GOOSE message has to be considered. It would be nice if switch
vendors who provide substation hardened switches, would focus their energy now, into creating more
convenient or efficient ways for GOOSE separation via multicast filter tables. This can help to reduce
network traffic on the overall network if GOOSE is used intensively for all connections between
relays. VLAN-ID or multicast – filtering are features of substation hardened switches which allow to
separate the GOOSE – telegram for this application easily.
For the delay time we will not consider the pickup or tripping time of each relay. After the directional
indication is generated logically in the device a group – indication is calculated in a CFC – chart. In
the fast – PLC the maximum delay will be 5 - 10 ms. To avoid this delay the phase-segregated signals
can be directly assigned into a GOOSE – message but then more logic in necessary on the receiver
side. Max. 3 - 5 ms later the telegram will be on the network. The delay in the local network is
typically < 1 ms. For the transfer the delay time depend on the used communication media. Best
choice is a fiber optical link (< 1ms) but even if a SDH – network is used the delay time is < 5 ms.
Receiving the blocking telegram need another max. 5 ms. Normally a GOOSE – message will be
faster than a contact and binary input interface on the sender and receiver side which need 10- 20 ms
14
in total. The performance of integrated digital interfaces (see fig. 1) is equal to the GOOSE –
application.
Special logic blocks allow monitoring the repetition of GOOSE – telegrams on the receiving relay.
This integrated comms–supervision feature will generate an alarm if there is a failure on the
communication link. In addition, monitoring functions for missing or faulty telegrams are available via
an integrated Web-Server on the receiver side.
BIBLIOGRAPHY
[1] Dipl. Ing. Norbert Schuster (51) works as Product Manager for communication in the sales
department of the Energy Distribution of the Siemens AG in Nuremberg. Since 1990, he works for
Siemens for the relay protection business, first in the development in Berlin. Afterward he changed to
the product marketing for protection relays in Nuremberg with the main topics line and transformer
differential, test devices and the PC-software DIGSI. Since 2002, he is responsible for communication
components and communication protocols and IEC 61850 related topics.
[2] Dipl. Ing. (FH) Markus Spangler (39) works as Product Manager for communication in the sales
department of the Energy Distribution of the Siemens AG in Nuremberg, Germany. In 1996, he joined
Siemens Communications division. There he was responsible as technical consultant and project
leader for corporate voice and data networks. In 2006, he moved to the Energy Sector of Siemens,
Division Energy Automation, and is responsible for Ethernet communication and IEC61850 standard.
15