Solar Brochure 20180615 Def
Solar Brochure 20180615 Def
Solar Brochure 20180615 Def
SOLAR
SOLUTIONS INVERTERS | STATIONS
PURE ENERGY Pure Energy is our motivation for leading the renewable energy
generation, it is the search for product and service perfection,
it is our vision of a world, clean and sustainable for our children
and future generations.
CONTENTS
POWER ELECTRONICS 03
HOW WE WORK 05
POWER ON SUPPORT 07
WORLDWIDE09
PRODUCT RANGE 11
SOLAR INVERTERS 13
HEM15
HEMK29
HEC V1500 43
HEC PLUS 65
HE PLUS 85
SOLAR STATIONS 97
MV SKID 99
HEK107
REFERENCES121
INTERNATIONAL PRESENCE
SUSTAINABLE GROWTH
POWER ELECTRONICS
Energy projects often require customer specific solutions, Flexibility and specialization play a key role in the manufactu-
for this reason our clients also have our Engineering and Con- re of standard products, but even more so in personalized pro-
sulting department at their disposal, which is comprised of a ducts. We design and manufacture integrally the mechanics
wide number of highly skilled and experienced engineers that of our equipment. Vertical integration gives us the flexibility to
are available to modify our standard product to suit customer adapt to customer requirements and still provide very short
demands and ensure our clients get the product they need. delivery times.
AVAILABILITY
COMMISSIONING
CUSTOMER SUPPORT
ONSITE ASSISTANCE
TRAINING SEMINARS
5 WARRANTY
POWER ON SUPPORT
WORLDWIDE PRESENCE
HEADQUARTERS
UNITED
STATES
MEXICO
PANAMA
COLOMBIA
+20 PERU
DELEGATIONS BRAZIL
+100 CHILE
SALES COUNTRIES
+12GW
SOLAR INVERTERS INSTALLED
+12GW
ANNUAL CAPACITY PRODUCTION
WORLDWIDE 9
UNITED
KINGDOM
POLAND
GERMANY
FRANCE
ITALY
SPAIN
TURKEY
PORTUGAL JAPAN
S. KOREA
CHINA
MOROCCO
DUBAI
INDIA
SINGAPORE
SOUTH AFRICA
AUSTRALIA
NEW
ZEALAND
POWER ELECTRONICS
PRODUCT RANGE
SOLAR INVERTERS
SOLAR STATIONS
SOLAR
INVERTERS
13
UTILITY SCALE
OUTDOOR AND INDOOR INVERTERS
HEM
UTILITY SCALE MV CENTRAL STRING INVERTER
OUTDOOR DURABILITY
IP65 AVAILABLE
ICOOL 3
ACTIVE HEATING
3 LEVEL TOPOLOGY
ECON MODE
THE INNOVATIVE
MEDIUM VOLTAGE
CENTRAL STRING
MULTI MPPT AVAILABLE INVERTER
ROBUST DESIGN
IP65 Available.
POWER ELECTRONICS
With the HEM, Power Electronics offers a real turn-key By providing full front access the HEM series simplifies
solution, including the MV transformer and switchgear fully the maintenance tasks, reducing the MTTR (and achieving
assembled and tested at the factory. The HEM is a compact a lower OPEX). The total access allows a fast swap of the
turn-key solution that will reduce site design, installation and FRUs without the need of qualified technical personnel.
connection costs.
MV MV STRING INVERTERS DC
SWITCHGEAR TRANSFORMER CABINET RECOMBINER
Based on more than 3 years of experience with our MV of reaching up to IP65 degree of protection, without having to
Variable Speed Drive, the iCOOL3 is the first air-cooling maintain cumbersome dust filters or having to use liquid-coo-
system allowing IP65 degree of protection in an outdoor solar ling systems, avoiding the commonly known inconveniences
inverter. iCOOL3 delivers a constant stream of clean air to the of it (complex maintenance, risk of leaks, higher number of
FRUs and the MV transformer, being the most effective way components…), therefore resulting in an OPEX cost reduction.
MULTILEVEL TOPOLOGY
The multilevel IGBT topology is the most efficient approach design is the result of our experience with 3 level topologies.
to manage high DC link voltages and makes the difference in The 3 level IGBT topology reduces stage losses, increases
the 1,500 Vdc design. Power Electronics has many years of inverter efficiency and minimizes total harmonic distortion.
power design in both inverters and MV drives and the HEMK
TWO-LEVEL
TWO-LEVELINVERTER
INVERTER THREE-LEVEL
THREE-LEVELINVERTER
INVERTER
VOLTAGE (V)
(V)
VOLTAGE (V)
(V)
VOLTAGE
VOLTAGE
VAR AT NIGHT
At night, the HEM inverter can shift to reactive power compensation mode. The inverter can respond to an external dynamic
signal, a Power Plant Controller command or pre-set reactive power level (kVAr).
ACTIVE HEATING
At night, when the unit is not actively exporting power, the This autonomous heating system is the most efficient and
inverter can import a small amount of power to keep the homogeneous way to prevent condensation, increasing the
inverter internal ambient temperature above -20°C, without inverters availability and reducing maintenance. PATENTED
using external resistors.
ECON MODE
This innovative control mode allows increasing the efficiency savings. Available as an optional kit, this feature has a pay-
of the MV transformer up to 25%, reducing the power con- back time of less than a few years, therefore resulting in the
sumption of the plant and therefore providing considerable increase of the plant lifetime overall revenue.
EASY TO MONITOR
HEM firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive power
curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT ). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
SLOW
U 0.6 0.6 1.08 1.08
Voltage
Voltage
U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
Qmax(ind) SLOW
Qmax(cap) -Q(max) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 250
500 625375 750500 625
875 750
1000 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
POI Utility
PV array HEC breaker
inverter
POWER ELECTRONICS
FRONT VIEW
BACK VIEW
HEM 23
REFERENCE FS3300M
OUTPUT AC Output Power(kVA/kW) @50°C [1] 3300
AC Output Power(kVA/kW) @25°C [1] 3630
Operating Grid Voltage(VAC) [2] 34.5kV ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 934V-1310V
Maximum DC voltage 1500V
Number of inputs [2] Up to 36
Max. DC continuous current (A) 3970
Max. DC short circuit current (A) 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [4] 2000m
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003.
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for other altitudes.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
REFERENCE FS3225M
OUTPUT AC Output Power(kVA/kW) @50°C [1] 3225
AC Output Power(kVA/kW) @25°C [1] 3550
Operating Grid Voltage(VAC) [2] 34.5kV ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 913V-1310V
Maximum DC voltage 1500V
Number of inputs [2] Up to 36
Max. DC continuous current (A) 3970
Max. DC short circuit current (A) 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [4] 2000m
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003.
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for other altitudes.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEM 25
REFERENCE FS3150M
OUTPUT AC Output Power(kVA/kW) @50°C [1] 3150
AC Output Power(kVA/kW) @25°C [1] 3465
Operating Grid Voltage(VAC) [2] 34.5kV ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 891V-1310V
Maximum DC voltage 1500V
Number of inputs [2] Up to 36
Max. DC continuous current (A) 3970
Max. DC short circuit current (A) 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [4] 2000m
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003.
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for other altitudes.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
REFERENCE FS3075M
OUTPUT AC Output Power(kVA/kW) @50°C [1] 3075
AC Output Power(kVA/kW) @25°C [1] 3380
Operating Grid Voltage(VAC) [2] 34.5kV ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 870V-1310V
Maximum DC voltage 1500V
Number of inputs [2] Up to 36
Max. DC continuous current (A) 3970
Max. DC short circuit current (A) 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [4] 2000m
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003.
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for other altitudes.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
HEM 27
REFERENCE FS3000M
OUTPUT AC Output Power(kVA/kW) @50°C [1] 3000
AC Output Power(kVA/kW) @25°C [1] 3300
Operating Grid Voltage(VAC) [2] 34.5kV ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 849V-1310V
Maximum DC voltage 1500V
Number of inputs [2] Up to 36
Max. DC continuous current (A) 3970
Max. DC short circuit current (A) 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98% including MV transformer (preliminary)
Max. Power Consumption (KVA) 20
CABINET Dimensions [WxDxH] (ft) 21.7 x 7 x 7
Dimensions [WxDxH] (m) 6.6 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) [4] 2000m
Noise level [5] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection MV Switchgear (configurable)
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003.
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Consult Power Electronics for other altitudes.
[2] Consult Power Electronics for other configurations. [5] Readings taken 1 meter from the back of the unit.
POWER ELECTRONICS
29
HEMK
UTILITY SCALE CENTRAL STRING INVERTER
OUTDOOR DURABILITY
IP65 AVAILABLE
ICOOL 3
ACTIVE HEATING
3 LEVEL TOPOLOGY
COMBINING
THE BENEFITS
OF CENTRAL AND
STRING INVERTERS
ROBUST DESIGN
IP65 available.
POWER ELECTRONICS
By providing full front access the HEMK series simplifies With the HEMK, Power Electronics offers its most compact
the maintenance tasks, reducing the MTTR (and achieving solution, achieving 3.8MW in just 12ft long, reducing installa-
a lower OPEX). The total access allows a fast swap of the tion costs and labor time.
FRUs without the need of qualified technical personnel.
Based on more than 3 years of experience with our MV degree of protection, without having to maintain cumber-
Variable Speed Drive, the iCOOL3 is the first air-cooling some dust filters or having to use liquid-cooling systems,
system allowing IP65 degree of protection in an outdoor solar avoiding the commonly known inconveniences of it (complex
inverter. iCOOL3 delivers a constant stream of clean air to the maintenance, risk of leaks, higher number of components…),
FRUs, being the most effective way of reaching up to IP65 therefore resulting in an OPEX cost reduction.
VAR AT NIGHT
At night, the HEMK inverter can shift to reactive power compensation mode. The inverter can respond to an external dynamic
signal, a Power Plant Controller command or pre-set reactive power level (kVAr).
ACTIVE HEATING
At night, when the unit is not actively exporting power, the the most efficient and homogeneous way to prevent conden-
inverter can import a small amount of power to keep the sation, increasing the inverters availability and reducing the
inverter internal ambient temperature above -20°C, without maintenance. PATENTED
using external resistors. This autonomous heating system is
POWER ELECTRONICS
MULTILEVEL TOPOLOGY
The multilevel IGBT topology is the most efficient approach design is the result of our experience with 3 level topologies.
to manage high DC link voltages and makes the difference in The 3 level IGBT topology reduces stage losses, increases
the 1,500 Vdc design. Power Electronics has many years of inverter efficiency and minimizes total harmonic distortion.
power design in both inverters and MV drives and the HEMK
TWO-LEVEL
TWO-LEVELINVERTER
INVERTER THREE-LEVEL
THREE-LEVELINVERTER
INVERTER
VOLTAGE (V)
(V)
VOLTAGE (V)
(V)
VOLTAGE
VOLTAGE
EASY TO MONITOR
HEMK firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive power
curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT ). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
SLOW
U 0.6 0.6 1.08 1.08
Voltage
Voltage
U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
Qmax(ind) SLOW
Qmax(cap) -Q(max) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 250
500 625375 750500 625
875 750
1000 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
POI Utility
PV array HEC breaker
inverter
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2300K FS3450K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2300 3450
AC Output Power(kVA/kW) @25°C [1]
2530 3800
Max. AC Output Current (A) @25°C 2120 3175
Operating Grid Voltage(VAC) [2] 690V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 976V-1310V
Maximum DC voltage 1500V
Number of inputs [2]
Up to 36
Number of MPPts Up to 4 Up to 6
Max. DC continuous current (A) 2645 3970
Max. DC short circuit current (A) 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98.5% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 9x7x7 12.3 x 7 x 7
Dimensions [WxDxH] (m) 2.7 x 2.2 x 2.2 3.7 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [4] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
HEMK 37
FRAME 1 FRAME 2
REFERENCE FS2200K FS3300K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2200 3300
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2150K FS3225K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2150 3225
AC Output Power(kVA/kW) @25°C [1]
2365 3550
Max. AC Output Current (A) @25°C 2120 3175
Operating Grid Voltage(VAC) [2] 645V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 913V-1310V
Maximum DC voltage 1500V
Number of inputs [2]
Up to 36
Number of MPPts Up to 4 Up to 6
Max. DC continuous current (A) 2645 3970
Max. DC short circuit current (A) 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98.5% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 9x7x7 12 x 7 x 7
Dimensions [WxDxH] (m) 2.7 x 2.2 x 2.2 3.7 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [4] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
HEMK 39
FRAME 1 FRAME 2
REFERENCE FS2100K FS3150K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2100 3150
AC Output Power(kVA/kW) @25°C [1]
2310 3465
Max. AC Output Current (A) @25°C 2120 3175
Operating Grid Voltage(VAC) [2] 630V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 891V-1310V
Maximum DC voltage 1500V
Number of inputs [2]
Up to 36
Number of MPPts Up to 4 Up to 6
Max. DC continuous current (A) 2645 3970
Max. DC short circuit current (A) 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98.5% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 9x7x7 12 x 7 x 7
Dimensions [WxDxH] (m) 2.7 x 2.2 x 2.2 3.7 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [4] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
POWER ELECTRONICS
FRAME 1 FRAME 2
REFERENCE FS2050K FS3075K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2050 3075
AC Output Power(kVA/kW) @25°C [1]
2225 3380
Max. AC Output Current (A) @25°C 2120 3175
Operating Grid Voltage(VAC) [2] 615V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 870V-1310V
Maximum DC voltage 1500V
Number of inputs [2]
Up to 36
Number of MPPts Up to 4 Up to 6
Max. DC continuous current (A) 2645 3970
Max. DC short circuit current (A) 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98.5% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 9x7x7 12 x 7 x 7
Dimensions [WxDxH] (m) 2.7 x 2.2 x 2.2 3.7 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [4] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
HEMK 41
FRAME 1 FRAME 2
REFERENCE FS2000K FS3000K
OUTPUT AC Output Power(kVA/kW) @50°C [1] 2000 3000
AC Output Power(kVA/kW) @25°C [1]
2200 3300
Max. AC Output Current (A) @25°C 2120 3175
Operating Grid Voltage(VAC) [2] 600V ±10%
Operating Grid Frequency(Hz) 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [3] 0.5 leading … 0.5 lagging adjustable / Reactive Power injection at night
INPUT MPPt @full power (VDC) 849V-1310V
Maximum DC voltage 1500V
Number of inputs [2]
Up to 36
Number of MPPts Up to 4 Up to 6
Max. DC continuous current (A) 2645 3970
Max. DC short circuit current (A) 4000 6000
EFFICIENCY & AUXILIARY SUPPLY Max. Efficiency PAC, nom (η) 98.5% (preliminary)
Max. Power Consumption (KVA) 8 10
CABINET Dimensions [WxDxH] (ft) 9x7x7 12 x 7 x 7
Dimensions [WxDxH] (m) 2.7 x 2.2 x 2.2 3.7 x 2.2 x 2.2
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA3R - IP54 / IP65 available
Permissible Ambient Temperature -35°C to +60°C / >50°C Active Power derating
Relative Humidity 4% to 100% non condensing
Max. Altitude (above sea level) 2000m; >2000m power derating (Max. 4000m)
Noise level [4] < 79 dBA
CONTROL INTERFACE Interface Graphic Display
Communication protocol Modbus TCP
Plant Controller Communication Optional
Keyed ON/OFF switch Standard
PROTECTIONS Ground Fault Protection GFDI and Isolation monitoring device
General AC Protection Circuit Breaker
General DC Protection Fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2
CERTIFICATIONS Safety UL1741, CSA 22.2 No.107.1-01, UL62109-1, IEC62109-1, IEC62109-2
Compliance NEC 2014 / NEC 2017 (optional)
Utility interconnect IEEE 1547-2003
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult Power Electronics for other configurations.
POWER ELECTRONICS
43
HEC V1500
UTILITY SCALE SOLAR INVERTER
OUTDOOR DURABILITY
ICOOL V
ACTIVE HEATING
3 LEVEL TOPOLOGY
AUTOMATIC REDUNDANT
POWER MODULE SYSTEM
ROBUST DESIGN
The HEC V1500 topology combines the advantages of a by a dual redundant main control. As the main governor of
central inverter with the availability of string inverters. HEC the system it is responsible for the MPPt tracking, synchro-
V1500 is a modular central inverter based on an Automatic nization sequence and overall protection. The automatic
Redundant Power Module (350kVA to 500kVA per stage). redundant capability based on our industrial systems is able
If there is a fault in one power module, it is taken off-line and to shift the main control in the event of a fault, restoring the
its power is distributed evenly among the remaining functio- backup control and restarting the station to guarantee high
ning modules. All power modules work in parallel controlled availability. PATENT PENDING
2500
POWER (KW)
15kW
2000
10kW
1500
5kW
1000
500
0 3 5 7 9 11 13 15 17 19 21
TIME (h)
A modular inverter is more efficient than a standard central With lower losses, a modular inverter can provide power
inverter. During low radiation conditions, a modular architec- earlier in the morning and stop later at the end of the day. As
ture uses the correct number of power modules to provide a result, throughout the entire service life of the PV plant, the
power, while a central inverter must consume power interna- HEC V1500 inverter generates higher yields than a standard
lly to support the entire system. central inverter with a higher reliability than string inverters.
EFFICIENCY
POWER
HEC V1500
HEC V1500 47
During solar power plant normal operation, the solar trac- ment, extra energy consumption and battery replacement.
kers are powered by the grid via the auxiliary service transfor- In order to avoid these disadvantages, HEC V1500 inverter
mer. In case of a loss of mains, a UPS with battery systems is is able to provide the safety power supply required without
needed for powering the solar trackers and ensures achieving using battery systems, taking profit of the energy available
the safety position. Battery systems increase the CAPEX and in the PV field, and therefore offering the most cost-effective
the OPEX of the project, due to a high maintenance require- solution in the market.
BLACKOUT EVENT
Energy Flow
POWER ELECTRONICS
The Power Electronics HEC V1500 series includes the and use a temperature control low flow cooling system that
innovative and sophisticated iCOOL V performance that reduces filters clogging and maintenance intervals. The
allows HEC V1500 to work up to 50°C at nominal power. hot area integrates a speed controlled fan for each module,
The cooling system, iCOOL V, smartly cools the inverter, simplifying the cooling system and reducing the maintenance
regulating the cooling system capacity depending on the tasks. Furthermore, due to the modular topology, the iCOOL
data from the temperature sensors. HEC V1500 modules V reduces the Stand-by consumption at low capacity to the
are divided into two main areas: clean area (electronics) maximum, boosting the cooling capacity for photovoltaic
and hot area (heat sink). The electronics are totally sealed installations situated up to 4000 meters above sea level.
PATENT PENDING
ELECTRONICS
HEAT SINKS
VAR AT NIGHT
The HEC V1500 inverter family is a high modularity solution with its 25 different models based on 5 frames, from 3 up to
7 power modules. With its modular and flexible design, Power Electronic offers a smart solution for meeting all our clients’
needs, providing high modularity and redundancy to any solar power plant.
Its extensive product range, a wide power and voltage range and a redundant control system, makes the HEC V1500 inverter
family an optimal solution to guarantee high availability in every small-medium utility scale project.
MULTILEVEL TOPOLOGY
The multilevel IGBT topology makes the difference when the the HEC V1500 takes profit of the three level IGBT topology
DC voltage is above 1000V, being the most efficient way to reducing the power stage losses, increasing the efficiency
manage high DC link voltages. Based in our long IGBT expe- and offering a very low total harmonic distortion.
rience components used in our Solar and Industrial division,
TWO-LEVEL
TWO-LEVELINVERTER
INVERTER THREE-LEVEL
THREE-LEVELINVERTER
INVERTER
VOLTAGE (V)
(V)
VOLTAGE (V)
(V)
VOLTAGE
VOLTAGE
ACTIVE HEATING
At night, when the unit is not actively exporting power, the This autonomous heating system is the most efficient and
inverter can import a small amount of power to keep the homogeneous way to prevent condensation, increasing the
inverter internal ambient temperature above -20°C, without inverters availability and reducing the maintenance. PATENTED
using external resistors.
POWER ELECTRONICS
By mounting this kit, the inverter and the PV plant will be tive voltage relative to their surroundings at any time. This
able to shift its running conditions from negative grounded running mode can be transfered to a floating array configura-
array to floating array and viceversa. Under regular conditions tion enabling an isolation monitoring device that the O&M can
the inverter will be running with a negative pole grounded use for: regular PV plant isolation control, identification of the
and therefore, a GDFI will provide protection against unlikely array affected by a ground fault defect and most important,
ground fault defects and the solar cells will not suffer a nega- increase the operator safety under O&M service activities.
To inverter INVERTER
+ CONTROL
SCADA
M
ISOLATION RS485
GFDI
MONITORING
Fault signal
Control signal
*Illustrative
EASY TO MONITOR
HEC V1500 firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive
power curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT ). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
SLOW
U 0.6 0.6 1.08 1.08
Voltage
Voltage
U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
Qmax(ind) SLOW
Qmax(cap) -Q(max) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 250
500 625375 750500 625
875 750
1000 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
POI Utility
PV array HEC breaker
inverter
POWER ELECTRONICS
HEC V1500 is available with an external DC disconnection and protection unit (DU unit) that will be coupled together with the
inverter by a mounting kit. The DC subsystems are fully customizable and can be featured with up to 32 inputs. The disconnec-
ting unit goes one step further by improving the PV plant safety and operation for those who apply the best engineering.
ZONE MONITORING
63A - 400A FUSE
TECHNICAL INFORMATION
CONFIGURATION TABLE
FAMILY Freesun Disconnnecting Unit
TYPE U UL H IEC
INSULATION MONITORING DEVICE VOLTAGE AND CURRENT MONITORING LOW STRING INSULATION DETECTOR
Insulation monitoring can detect cable insulation The FSDK Voltage and Current monitoring option Using the individual DC contactors and the
issues in the PV array. If low insulation resistance is provides data for zone current values, as well as the Insulation Monitoring option, the FSDK unit can au-
detected between the array and ground, the device open circuit voltage for every DC input. DC Voltage tomatically identify which input has low insulation
disconnects the inverter and writes a fault message and current monitoring allows an operator to safely and isolate it from the rest of the PV field. After the
in the system fault log. In grounded systems, an check the PV array operation without opening the DC faulted line is disconnected, the inverter will log
additional contactor connected in series with the cabinet. With the Voltage and Current monitoring op- the error and send a warning to the O&M team to
GFDI disconnects the pole from the ground every tion, a remote SCADA operator will be able to receive provide information about the faulty input. Detailed
morning, prior to the startup sequence of the inver- fault messages like “unbalanced currents”, “unbalan- troubleshooting information will reduce service
ter, in order to allow the monitoring device to check ced voltages” or “blown fuse” and take appropriate time and quickly get a system back on-line.
the insulation between both poles and ground. action based on the status of the PV field. PATENTED
1200 CURRENT
i1,P
MONITORING
- or + Grounded
i32,P
+
FSDK15
Series RECOMBINER
CONTACTORS FUSE
1200
-
i1,n
i32,n
FSDK15
2266
Series RECOMBINER
1566
CURRENT
i1,P
MONITORING
Floating Array
i16,P
CONTACTORS FUSE +
CONTACTORS FUSE
-
i1,n
i16,n
995
995
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC V1500 55
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC V1500 57
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC V1500 59
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC V1500 61
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC V1500 63
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
65
HEC PLUS
UTILITY SCALE SOLAR INVERTER
OUTDOOR DURABILITY
ICOOL
ACTIVE HEATING
AUTOMATIC REDUNDANT
MODULAR MULTI-MASTER SYSTEM
ROBUST DESIGN
TOPOLOGY
NO CONDENSATION
The active cabinet heating regulates temperature
and prevents internal water condensation.
SPECIAL PAINT
Anti-corrosive polymeric paint
(C4) ISO-9223 is used on all
HEC inverters.
INSULATION
50mm of insulation material
protects internal components from
external solar heat gains.
FSDK Recombiner
· Up to 32 fuse protected inputs.
· Zone monitoring. CT’s in each input.
· Up to 32 contactors with lockout/ tagout
safety features.
DC CABINET
HEC PLUS 69
COUPLING AC CLOSE
The HEC PLUS is a central inverter based on an Automatic production. Modularity allows for the use of fewer type of
Redundant Modular Multi-Master System (200kVA to 250kVA components throughout the product range, reducing mainte-
per module). The unit’s redundant multi-master capability nance costs and simplifying the stock of spare parts.
translates into more availability and therefore more power
In Power Electronics we don’t believe in cost cutting when it HEC PLUS modules are divided into two main areas: clean
affects the quality of the product and that’s why we oversize area (electronics) and hot area (filters and heat sink). The
sensitive components and improve the sophisticated iCOOL electronics are totally sealed and use a temperature control
performance that allow HEC PLUS to work at 50°C. Our know low flow cooling system that reduces filters clogging and
how in mining, water treatment plants and CSP facilities loca- maintenance intervals. The hot area integrates independent
ted in the most demanding locations all over the world have and speed controlled fans per each module, reducing to the
given us the necessary experience to develop the perfectte- maximum the Stand-by consumption at low capacity and
chnical solution for our outdoor solar inverters. boosting the cooling capacity for PV installation situated at
higher altitudes than 3000 meters above sea level.
ELECTRONICS
HEAT SINKS
HEC PLUS 71
EASY TO SERVICE
By providing full front and rear access the HEC series simpli-
fies the maintenance tasks. The frontal access allows the
checking of the whole electronic cabinet (electronics boards,
semiconductors, power supply, contactors... ) while the rear
access permits the revision of AC fuses and LCL filter.
POWER ELECTRONICS
By mounting this kit, the inverter and the PV plant will be tive voltage relative to their surroundings at any time. This
able to shift its running conditions from negative grounded running mode can be transfered to a floating array configura-
array to floating array and viceversa. Under regular conditions tion enabling an isolation monitoring device that the O&M can
the inverter will be running with a negative pole grounded use for: regular PV plant isolation control, identification of the
and therefore, a GDFI will provide protection against unlikely array affected by a ground fault defect and most important,
ground fault defects and the solar cells will not suffer a nega- increase the operator safety under O&M service activities.
To inverter INVERTER
+ CONTROL
SCADA
M
ISOLATION RS485
GFDI
MONITORING
Fault signal
Control signal
*Illustrative
EXTENDED MPPT
ACTIVE HEATING
At night, when the unit is not actively exporting power, the the most efficient and homogeneous way to prevent conden-
inverter can import a small amount of power to keep the sation, increasing the inverters availability and reducing the
inverter internal ambient temperature above -20°C, without maintenance. PATENTED
using external resistors. This autonomous heating system is
VAR AT NIGHT
HEC PLUS firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive
power curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT ). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
SLOW
0.6 0.6 1.08 1.08
Voltage
Voltage
U U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
SLOW
Qmax(cap) Qmax(cap) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) -Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 500
250 625
375 750
500 875
625 1000
750 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
POI Utility
PV array HEC breaker
inverter
POWER ELECTRONICS
HEC PLUS is available with an external DC disconnection and protection unit (DU unit) that will be coupled together with the
inverter by a mounting kit. The DC subsystems are fully customizable and can be featured with up to 40 inputs. The disconnec-
ting unit goes one step further by improving the PV plant safety and operation for those who apply the best engineering.
ZONE MONITORING
70A - 400A FUSE
TECHNICAL INFORMATION
CONFIGURATION TABLE
FAMILY FSDK Recombiner
LIGHTNING AND
OVERVOLTAGE O Type 2 L Type 1 + Type 2
PROTECTIONS
FRAME 2 FRAME 1
CURRENT CURRENT
i1,P i1,P
FSDK FSDK MONITORING MONITORING
Series RECOMBINER Series RECOMBINER
- or + Grounded
FSDK FSDK
Series RECOMBINER
i40,n Series
i40,n RECOMBINER
1470
50”
CURRENT CURRENT
i1,P i1,P
MONITORING MONITORING
Floating Array
i20,P i20,P
CONTACTORS FUSE + CONTACTORS FUSE +
CONTACTORS
- CONTACTORS FUSE
-
i1,n i1,n
i20,n i20,n
960
960
960
960
POWER ELECTRONICS
FRAME 4
5900 7300
2400
2270
2400
1470
FRAME 3
4900 6300
2400
2400
2270
1470
FRAME 2
3900 5300
2400
2270
2400
1470
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC PLUS 79
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC PLUS 81
NORTH AMERICA
FRAME 2 FRAME 3 FRAME 4
NUMBER OF MODULES 5 6 7 8 9 10
REFERENCE FS1112CU FS1331CU FS1550CU FS1770CU FS1991CU FS2200CU
OUTPUT AC Output Power(kVA/kW) @50°C 1110 1330 1550 1770 1990 2200
AC Output Power(kVA/kW) @25°C 1220 1460 1710 1950 2190 2440
Max. Power (kW@PF=0.9, @50°C) 1000 1190 1390 1590 1790 1980
Max. AC Output Current (A) @25°C 1600 1920 2240 2560 2880 3200
Operating Grid Voltage(VAC) 440Vac ±10%
Operating Grid Frequency 60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi) [1] 0.00 leading … 0.00 lagging adjustable/ Reactive Power injection at night
Power Curtailment 0...100%/0.1% Steps
INPUT MPPt Voltage Window (VDC) [2] 623V-900V
MPPt window @full power (VDC) [2] 642V–820V @50°C / 712V–820V @25°C
Maximum DC Voltage 1000V
Minimum Start Voltage 700V - User configurable
Max. DC continuous current (A) 1750 2100 2450 2800 3150 3500
Max. DC short circuit current (A) 2275 2730 3185 3640 4095 4550
EFFICIENCY & Max. Efficiency / CEC (η) 98.6% / 98.0%
AUXILIARY Euroeta (η) 98.3% 98.4%
SUPPLY
Max. Standby Consumption (Pnight) < approx. 40W/per module
Control Power Supply 120V / 208VAC–1kVA power supply available for external equipment
Max. Power Consumption 2300W 2760W 3220W 3680W 4140W 4600W
CABINET Dimensions [WxDxH] [ft] 153.5”x40.12”x94.5” 192.9”x40.12”x94.5” 232.3”x40.12”x94.5”
Dimensions [WxDxH] [mm] 3900x1050x2400 4900x1050x2400 5900x1050x2400
Weight (lbs) 7804 8487 10119 10802 12434 13117
Weight (kg) 3540 3850 4590 4900 5640 5950
Air Flow Bottom intake. Exhaust top vent (Front or Rear option)
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R
Permissible Ambient Temperature -22°F to +122°F, -30°C[3] to +50°C / Active Power derating >50°C/122°F
Relative Humidity 0% to 100% non condensing
Max. Altitude (above sea level) 1000m; >1000m power derating 1% Sn (kVA) per 100m
Noise level [4] < 79 dBA
CONTROL Interface Alphanumeric Display (inside cabinet) / Optional Freesun App
INTERFACE Communication Protocol RS232 / RS485 / USB / Ethernet, (Modbus RTU, Modbus TCP/IP)
Power Plant Controller Optional
Keyed ON/OFF switch Standard
PROTECTIONS Floating PV array: Isolation Monitoring per MPP
Ground Fault Protection NEC2014 Grounded PV Array: GFDI protection
Optional PV Array transfer kit: GFDI and Isolation monitoring device
Humidity control Active Heating
General AC Protection & Disconn. Circuit Breaker
General DC Protection & Disconn. External Disconnecting Unit Cabinet (FSDK)
Module AC Protection & Disconn. AC contactor & fuses
Module DC Protection & Disconn. DC contactor & DC fuses
Overvoltage Protection AC and DC protection (type 2)
CERTIFICATIONS Safety UL 1741; CSA 22.2 No.107.1-01
Utility interconnect IEEE 1547 with Utility Interactive Control functions
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
NORTH AMERICA
FRAME 2 FRAME 3 FRAME 4
NUMBER OF MODULES 5 6 7 8 9 10
REFERENCE FS1051CU FS1271CU FS1480CU FS1690CU FS1901CU FS2110CU
OUTPUT AC Output Power(kVA/kW) @50°C 1050 1270 1480 1690 1900 2110
AC Output Power(kVA/kW) @25°C 1160 1400 1630 1860 2100 2330
Max. Power (kW@PF=0.9, @50°C) 940 1140 1330 1520 1710 1900
Max. AC Output Current (A) @25°C 1600 1920 2240 2560 2880 3200
Operating Grid Voltage(VAC) 420Vac ±10%
Operating Grid Frequency 60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi)[1] 0.00 leading … 0.00 lagging adjustable/ Reactive Power injection at night
Power Curtailment 0...100%/0.1% Steps
INPUT MPPt Voltage Window (VDC)[2] 594V-900V
MPPt window @full power (VDC)[2] 616V–820V @50°C / 680V–820V @25°C
Maximum DC Voltage 1000V
Minimum Start Voltage 700V - User configurable
Max. DC continuous current (A) 1750 2100 2450 2800 3150 3500
Max. DC short circuit current (A) 2275 2730 3185 3640 4095 4550
EFFICIENCY & Max. Efficiency / CEC (η) 98.6% / 98.0%
AUXILIARY Euroeta (η) 98.3% 98.4%
SUPPLY
Max. Standby Consumption (Pnight) < approx. 40W/per module
Control Power Supply 120V / 208VAC–1kVA power supply available for external equipment
Max. Power Consumption 2300W 2760W 3220W 3680W 4140W 4600W
CABINET Dimensions [WxDxH] [inches] 153.5”x40.12”x94.5” 192.9”x40.12”x94.5” 232.3”x40.12”x94.5”
Dimensions [WxDxH] [mm] 3900x1050x2400 4900x1050x2400 5900x1050x2400
Weight (lbs) 7804 8487 10119 10802 12434 13117
Weight (kg) 3540 3850 4590 4900 5640 5950
Air Flow Bottom intake. Exhaust top vent (Front or Rear option)
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R
Permissible Ambient Temperature -22°F to +122°F, -30°C[3] to +50°C / Active Power derating >50°C/122°F
Relative Humidity 0% to 100% non condensing
Max. Altitude (above sea level) 1000m; >1000m power derating 1% Sn (kVA) per 100m
Noise level [4] < 79 dBA
CONTROL Interface Alphanumeric Display (inside cabinet) / Optional Freesun App
INTERFACE Communication Protocol RS232 / RS485 / USB / Ethernet, (Modbus RTU, Modbus TCP/IP)
Power Plant Controller Optional
Keyed ON/OFF switch Standard
PROTECTIONS Floating PV array: Isolation Monitoring per MPP
Ground Fault Protection NEC2014 Grounded PV Array: GFDI protection
Optional PV Array transfer kit: GFDI and Isolation monitoring device
Humidity control Active Heating
General AC Protection & Disconn. Circuit Breaker
General DC Protection & Disconn. External Disconnecting Unit Cabinet (FSDK)
Module AC Protection & Disconn. AC contactor & fuses
Module DC Protection & Disconn. DC contactor & DC fuses
Overvoltage Protection AC and DC protection (type 2)
CERTIFICATIONS Safety UL 1741; CSA 22.2 No.107.1-01
Utility interconnect IEEE 1547 with Utility Interactive Control functions
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HEC PLUS 83
NORTH AMERICA
FRAME 2 FRAME 3 FRAME 4
NUMBER OF MODULES 5 6 7 8 9 10
REFERENCE FS1004CU FS1201CU FS1401CU FS1600CU FS1801CU FS2000CU
OUTPUT AC Output Power(kVA/kW) @50°C 1000 1200 1400 1600 1800 2000
AC Output Power(kVA/kW) @25°C 1110 1330 1550 1770 2000 2220
Max. Power (kW@PF=0.9, @50°C) 900 1080 1260 1440 1620 1800
Max. AC Output Current (A) @25°C 1600 1920 2240 2560 2880 3200
Operating Grid Voltage(VAC) 400Vac ±10%
Operating Grid Frequency 60Hz
Current Harmonic Distortion (THDi) < 3% per IEEE519
Power Factor (cosine phi)[1] 0.00 leading … 0.00 lagging adjustable/ Reactive Power injection at night
Power Curtailment 0...100%/0.1% Steps
INPUT MPPt Voltage Window (VDC)[2] 566V-900V
MPPt window @full power (VDC)[2] 584V–820V @50°C / 648V–820V @25°C
Maximum DC Voltage 1000V
Minimum Start Voltage 700V - User configurable
Max. DC continuous current (A) 1750 2100 2450 2800 3150 3500
Max. DC short circuit current (A) 2275 2730 3185 3640 4095 4550
EFFICIENCY & Max. Efficiency / CEC (η) 98.6% / 98.0%
AUXILIARY Euroeta (η) 98.3% 98.4%
SUPPLY
Max. Standby Consumption (Pnight) < approx. 40W/per module
Control Power Supply 120V / 208VAC–1kVA power supply available for external equipment
Max. Power Consumption 2300W 2760W 3220W 3680W 4140W 4600W
CABINET Max. Power Consumption 153.5”x40.12”x94.5” 192.9”x40.12”x94.5” 232.3”x40.12”x94.5”
Dimensions [WxDxH] [mm] 3900x1050x2400 4900x1050x2400 5900x1050x2400
Weight (lbs) 7804 8487 10119 10802 12434 13117
Weight (kg) 3540 3850 4590 4900 5640 5950
Air Flow Bottom intake. Exhaust top vent (Front or Rear option)
Type of ventilation Forced air cooling
ENVIRONMENT Degree of protection NEMA 3R
Permissible Ambient Temperature -22°F to +122°F, -30°C[3] to +50°C / Active Power derating >50°C/122°F
Relative Humidity 0% to 100% non condensing
Max. Altitude (above sea level) 1000m; >1000m power derating 1% Sn (kVA) per 100m
Noise level [4] < 79 dBA
CONTROL Interface Alphanumeric Display (inside cabinet) / Optional Freesun App
INTERFACE Communication Protocol RS232 / RS485 / USB / Ethernet, (Modbus RTU, Modbus TCP/IP)
Power Plant Controller Optional
Keyed ON/OFF switch Standard
PROTECTIONS Floating PV array: Isolation Monitoring per MPP
Ground Fault Protection NEC2014 Grounded PV Array: GFDI protection
Optional PV Array transfer kit: GFDI and Isolation monitoring device
Humidity control Active Heating
General AC Protection & Disconn. Circuit Breaker
General DC Protection & Disconn. External Disconnecting Unit Cabinet (FSDK)
Module AC Protection & Disconn. AC contactor & fuses
Module DC Protection & Disconn. DC contactor & DC fuses
Overvoltage Protection AC and DC protection (type 2)
CERTIFICATIONS Safety UL 1741; CSA 22.2 No.107.1-01
Utility interconnect IEEE 1547 with Utility Interactive Control functions
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
85
HE PLUS
UTILITY SCALE SOLAR INVERTER
MULTI MPPT
ICOOL
ACTIVE HEATING
AUTOMATIC REDUNDANT
MODULAR MULTI-MASTER SYSTEM
INDOOR
PROACTIVE ATTITUDE
TOPOLOGY
NO CONDENSATION
The Active cabinet heating regulates temperature
and prevents internal water condensation.
WITHDRAWABLE MODULES
Withdrawable modules allow easy
front access to all components
reducing service time.
DC CLOSE COUPLING
Positive and negative
terminals are ready for
busbar or wiring connection
HE PLUS 87
POWER BLOCK
INVERTER
CONTROL AREA
MAIN AC
CIRCUIT BREAKER
AC CLOSE COUPLING
The inverter can be easily connected to
the transformer using an efficient busbar
connection.
POWER ELECTRONICS
The HE PLUS is a central inverter based on an Automatic production. Modularity allows for the use of fewer type of
Redundant Modular Multi-Master System (200kVA to 250kVA components throughout the product range, reducing mainte-
per module). The unit’s redundant multi-master capability nance costs and simplifying the stock of spare parts.
translates into more availability and therefore more power
100%
90%
80%
70% VSD CONTROLLED FANS
60%
LCL HARMONIC FILTER
50%
40%
30%
AIR INTAKE
20%
10%
45 50 55 60 65 70 75 80
IGBT TEMPERATURE [ºC]
ACTIVE HEATING
At night, when the unit is not actively exporting power, the This autonomous heating system is the most efficient and
inverter can import a small amount of power to keep the homogeneous way to prevent condensation, increasing the
inverter internal ambient temperature above -20°C, without inverters availability and reducing the maintenance. PATENTED
using external resistors.
VAR AT NIGHT
HE PLUS firmware includes the latest utility interactive features (LVRT, OVRT, FRS, FRT, Anti-islanding, active and reactive power
curtailment…), and can be configured to meet specific utility requirements.
1.4
100%
p.u. VOLTAGE
1.2
1.2
1
1
0.8
0.8
0.6 50%
0.6 50%
0.4
0.4
0.2
0.2
0
0 -1 0 1 2 3 4
-1 0 1 2 3 4 SECONDS 0%
50Hz 52Hz
PO12.3 BDEW PREPA SECONDS
CEI-016 HECO 0%
50Hz FREQUENCY (Hz) 52Hz
PO12.3 BDEW PREPA CEI-016 HECO FREQUENCY (Hz)
Low Voltage Ride Through (LVRT or ZVRT ). Inverters can withstand any Frequency Regulation System (FRS). Frequency droop algorithm curtails the
voltage dip or profile required by the local utility. The inverter can immediately active power along a preset characteristic curve supporting grid stabilization.
feed the fault with full reactive current, as long as the protection limits are not
exceeded.
SLOW
0.6 0.6 1.08 1.08
Voltage
Voltage
U U
0.5 0.5 1.075 1.075
0.2 0.2
P>0.2Pn P>0.2Pn 1.06 1.06
(lock in) (lock in) TIME (s)
0.1 0.1 1.055 1.055
SLOW
Qmax(cap) Qmax(cap) 0 0 P>0.5Pn 1.05 P>0.5Pn 1.05
-Q(max) -Q(max) (lock out) (lock out)
-0.1 -0.1 1.045 1.045
1 125 250 1 375125 500
250 625
375 750
500 875
625 1000
750 875 1000
Time (s) Time (s)
Q P QV P V
Q(V) curve. It is a dynamic voltage control function which provides reactive power in order to maintain the voltageFAST
as close as possible to its nominal value.
FAST
ISLANDING CONDITION
FREQUENCY (Hz)
SLOW
Transformer Grid
POI Utility
PV array HEC breaker
TIME (s) inverter
SLOW
R L C Loads
FAST
Frequency Ride Through (FRT). Freesun solar inverters have flexible frequency Anti-islanding. This protection combines passive and active methods that
POI Utility
PV array HEC breaker
inverter
POWER ELECTRONICS
EASY TO SERVICE
3370 1020
3370 1020
2080
2080
FRAME 2 FRAME 3
2080
HE PLUS 91
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
NUMBER OF MODULES 5 6 7 8 9 10
REFERENCE FS1112CH FS1331CH FS1550CH FS1770CH FS1991CH FS2200CH
OUTPUT AC Output Power(kVA/kW) @50°C[1] 1110 1330 1550 1770 1990 2200
AC Output Power(kVA/kW) @25°C[1] 1220 1460 1710 1950 2190 2440
Max. AC Output Current (A) @25°C 1600 1920 2240 2560 2880 3200
Operating Grid Voltage(VAC) 440Vac
Operating Range, Grid Frequency 50Hz/60Hz
Current Harmonic Distortion (THDi) < 3% at any load condition
Power Factor (cosine phi)[2] 0.00 leading … 0.00 lagging adjustable / Reactive Power injection at night
Power Curtailment 0...100%/0.1% Steps
INPUT MPPt Voltage Window (VDC)[1] 623V-900V
MPPt window @full power (VDC)[1] 642V–820V @50°C / 712V–820V @25°C
Maximum DC and Starting voltage 1000V
Max. DC continuous current (A) 1750 2100 2450 2800 3150 3500
Max. DC short circuit current (A) 2275 2730 3185 3640 4095 4550
EFFICIENCY & Max. Efficiency PAC, nom (η) 98.6% 98.6% 98.6%
AUXILIARY Euroeta (η) 98.3% 98.4% 98.4%
SUPPLY
Max. Standby Consumption (Pnight) < approx. 40W/per module
Max. Power Consumption (W) 2300W 2760W 3220W 3680W 4140W 4600W
Max. Apparent Power (VA) 4800VA 5600VA 6500VA 7300VA 8200VA 9000VA
CABINET Dimensions [WxDxH] [mm] 3370x1020x2080 4400x1020x2080 5260x1020x2080
Weight (kg) 2500 2900 3300 3700 4100 4500
Air Flow Intake through rear lower part blown out through upper side
Type of ventilation VSD Forced air cooling
ENVIRONMENT Degree of protection Indoor IP21
Permissible Ambient Temperature -20°C to +60°C
Relative Humidity 10% to 95% Non condensing
Max. Altitude (above sea level) 4000m; >1000m power derating
Noise level [4] < 79 dBA
CONTROL Interface Alphanumeric Display / Optional Freesun App display or Web display
INTERFACE Communication RS232 / RS485 / USB / Ethernet, (Modbus RTU Protocol, Modbus TCP/IP)
Analogue Inputs 1 programmable and differential inputs; (0-20mA or ± 10mV to ± 10V) and PT100
String Supervisor Communication RS485 / Modbus RTU
Plant Controller Communication Ethernet / Modbus TCP/IP
Digital Outputs 1 electrically-isolated programmable switched relays (250VAC, 8A or 30VDC, 8A)
PROTECTIONS Floating PV array: Isolation Monitoring per MPP
Ground Fault Protection Grounded PV array (Positive pole and negative pole): GFDI protection
PV Array transfer kit: GFDi and Isolation Monitoring Device (requires 1 Digital Output)
Humidity control Active Heating
ON / OFF Pushbutton Standard
General AC Protection & Disconn. Circuit Breaker
General DC Protection & Disconn. Optional External Wall mounted cabinets
Module AC Protection & Disconn. AC contactor & fuses
Module DC Protection & Disconn. DC contactor & DC fuses
Overvoltage Protection AC, DC Inverter and auxiliary supply type 2 - Internal Standard
DC Lightning Protections Optional (Integrated in the inverter)
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HE PLUS 93
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
POWER ELECTRONICS
[1] Values at 1.00•Vac nom and cos Ф= 1. [3] Heating resistors kit option below -20°C.
Consult Power Electronics for derating curves. [4] Readings taken 1 meter from the back of the unit.
[2] Consult P-Q charts available: Q(kVAr)=√(S(kVA)2-P(kW)2).
HE PLUS 95
POWER ELECTRONICS
SOLAR
STATIONS
97
UTILITY SCALE
OUTDOOR AND INDOOR INVERTERS
MV SKID
UTILITY SCALE SOLAR STATION
TURN-KEY SOLUTION
HIGH RELIABILITY
EASY TO INSTALL
OUTDOOR DURABILITY
SECTIONS
FRAME 1 INVERTERS
SOLAR FRAME 2 INVERTERS
SOLAR
SUITABLE WITH MV SKID: SUITABLE WITH MV SKID:
HEMK HEMK
HEC V1500 HEC V1500
SOLAR
HECINVERTERS
PLUS SOLAR
HECINVERTERS
PLUS
SUITABLE WITH MV SKID: SUITABLE WITH MV SKID:
HEMK HEMK
HEC V1500 HEC V1500
HEC PLUS HEC PLUS
LV LARGE
CABINET
AUX. SERVICES
ELECTRICAL PANEL AUX. SERVICES
ELECTRICAL PANEL
LV LARGE
CABINET
AUX. SERVICES
ELECTRICAL PANEL AUX. SERVICES
ELECTRICAL PANEL
MV CABINET MV CABINET
For customized solutions, contact Power Electronics.
LV COMPACT
CABINET
MV SKID 101
[1] Depending on customer configuration. [3] Other temperature range, consult Power Electronics.
[2] Optional. For additional information or available configurations, [4] By demand.
please consult Power Electronics.
POWER ELECTRONICS
103
TWIN SKID
UTILITY SCALE SOLAR STATION
TURN-KEY SOLUTION
HIGH RELIABILITY
EASY TO INSTALL
OUTDOOR DURABILITY
CUSTOMIZED SOLUTIONS
I-TWIN SKID
U-TWIN SKID
OPERATIONAL DIAGRAM
MV TRANSFORMER MV SWITCHGEAR
Dy 11
400Vac-690Vac / 11kV-34.5kV
To inverter
To inverter
MV TRANSFORMER
Dy 11
400Vac-690Vac / 11kV-34.5kV
TWIN SKID 105
[1] Depending on customer configuration. [3] Other temperature range, consult Power Electronics.
[2] Optional. For additional information or available configurations, [4] By demand.
please consult Power Electronics.
POWER ELECTRONICS
107
HEK
UTILITY SCALE SOLAR STATION
TURN-KEY SOLUTION
HIGH RELIABILITY
EASY TO INSTALL
OUTDOOR DURABILITY
TOPOLOGY
BACK-TO-BACK
INVERTER CONFIGURATION
SCADA
PANEL
BOARD
AC MAIN
INVERTER
DC BOTTOM FLEXIBLE CONDUIT CIRCUIT AUX. SERVICES
INPUT CHASES ARRANGEMENT BREAKER TRANSFORMER
AC
Fuse &
Contactor
DC
Contactors
& Fuses
3~ 3~ 3~ 3~ PAD MOUNT
TRANSFORMER
= = = =
DC
Contactor
& Fuses
400V-690V/34.5kV
Expulsion
Fuse T BLADE
HA
HEC-US PLUS AC Gen.
Circ. Breaker
Current
Limiting
Fuse HB
AC
Fuse &
Contactor
DC
Contactors
& Fuses 3~ 3 3~ 3~
= = = =
DC
Contactor
& Fuses
HEK 109
TRACKERS
PANEL BOARD
FIRE
EXTINGUISHER
POWER METER
PANEL BOARD
(OPTIONAL)
CONCRETE OR STEEL
SKID AVAILABLE
MV INPUT
CHASSIS
BUILT-IN
OIL CONTAINMENT
PANEL BOARD
(OPTIONAL)
STRUCTURE
CONFIGURATIONS
1MW - 3.5MW 2MW - 7MW
30kVA 30kVA
AUX. BOTTOM AUX.
XFMR AU. PANEL BOARD DC CHASE HEC-US INVERTER #2 XFMR AU. PANEL BOARD
AU. PANEL BOARD #2
AU. PANEL BOARD
[1] Other configurations, please consult Power Electronics. Some HEK units may differ from the concept shown in the images.
POWER ELECTRONICS
CONTROL AND
MONITORING SOLUTIONS
111
FREESUN PPC
FREESUN APP
FREESUN PORTAL
POWER ELECTRONICS
PPC
UTILITY SCALE POWER PLANT CONTROLLER
TECHNICAL CHARACTERISTICS
GENERAL DATA Dimensions (WxDxH) mm 415 x 230 x 515
Weight (kg) 10
Mounting system Wall mounted
Compatible Inverters HE, HEC, HEM, HEMK and Freemaq PCS
Power Supply 250W
I/O and Programmable inputs and active high (24Vdc).
4 x Digital Inputs
COMMUNICATIONS [1] Optically isolated.
1 x RS485 Port 3 wires (GND,A,B), Modbus RTU
PC connectable using a master.Modbus configurator (ModScan or similar).
1 x USB Port
Reserved for TS.
1 x CAN Port 3 wires (LO, GND, HI), Modbus RTU
1 x Ethernet Port (RJ45) Modbus TCP/IP
ENVIRONMENTAL Operation Temperature 0~50°C (32°~122°F)
CONDITIONS Storage temperature -20~80°C (-4°~176°F)
Humidity 5-95% non-condensing
Degree of protection IP42
CERTIFICATIONS CE
OTHERS Web interface for local and remote monitoring
Customized solution
[1] Communication ports can be customised depending on PV plant design without prior notice.
POWER PLANT CONTROLLER 113
The Power Electronics Power Plant Controller is a device The PPC includes the latest utility interactive specifications
used to manage PV plants in order to comply with all the to support the grid, by controlling the reactive and active
utility and customer requirements, thanks to its fast and power at the POI with a fast response time. This flexible plant
flexible control algorithms. The PPC helps the grid controller control device allows the user to customize the unit, in order
to manage the performance of the PV plant, guaranteeing to comply with any grid code standards and regulations.
grid quality requirements.
1.08
VOLTAGE
P(p.u.)
P1 1.06
1.04
P0
1.02
0.98
TIME
0.96
P2
0.94
0.92
f1 fDB- 1.00 fDB+ f2
f(p.u.) Voltage at POI Voltage at POI with VRS activated
POWER ELECTRONICS
The Power Plant Controller (PPC) can be the main governor analogue signals and communication ports (Modbus TCP).
of the most complex Multi PCS systems by monitoring the The PPC together with the Freesun solar inverter or the Free-
point of interconnection (POI) and at the same time contro- maq series can be customized for those countries (Puerto
lling the power generation and storage equipment. Rico, Hawaii….) that require full compliance to stringent
The PPC is equipped with the latest PLC based micropro- dynamic grid support response at POI.
cessor that interacts through the programmable digital/
2000kW
1500kW
00:00 02:00 04:00 06:00 08:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 24:00
2000kW
decentralized PV.
00:00 02:00 04:00 06:00 08:00 10:00 12:00 14:00 16:00 18:00 20:00 22:00 24:00
FREESUN PORTAL
GO ONLINE
FREESUN APP
GO WIRELESS
BRAZIL BRAZIL´S 1ST 1500V INVERTER ARGENTINA ARGENTINA’S 1ST 1500V INVERTER
MEXICO
UNITED STATES
Huzlehurst, 52MW
HEC-US V1500
UNITED STATES
Payne, 105MW
HEM
PANAMA MAURITANIA
PORTUGAL PORTUGAL’S 1ST 1500V INVERTER BOLIVIA BOLIVIA 1ST 1500V INVERTER
CHILE
Los Andes, 24 MW
HEC PLUS
URUGUAY BARBADOS
UNITED STATES
Gala, 56MW
HEC-US V1500
UNITED STATES
HEC-US V1500
5
WARRANTY
Power Electronics (the Seller) warrants that their SOLAR INVERTER Products are by using the following contact email: quality@powerelectronics. com, of the
free of faults and defects for a period of 5 years, valid from the date of delivery to presence of any fault or defect within 15 days of the fault or defect event. The
the Buyer. It shall be understood that a product is free of faults and defects when serial number of the defective product plus a brief description of the fault must
its condition and performance is in compliance with its specification. be included in the email. Failure to notify the Seller of fault or defect within this
The warranty shall not extend to any Products whose defects are due to time period may result in the warranty becoming invalid.
(i) careless or improper use, (ii) failure to observe the Seller’s instructions In the event of replacement of defective Product or part thereof, the property
regarding the transport, installation, functioning, maintenance and the storage of the Product or part shall be transferred to the Seller.
of the Products, (iii) repairs or modifications made by the Buyer or third party The Seller shall bear no liability for damages to property or third persons,
without prior written authorization of the Seller, (iv) negligence during the even as manufacturer of the Products, other than that expressly provided by
implementation of authorized repairs or modifications, (v) if serial numbers are virtue of applicable mandatory law provisions. In any case, the Seller shall not
modified or illegible, (vi) anomalies caused by, or connected to, the elements be liable for indirect or consequential damages of whatsoever nature as, by
coupled directly by the Buyer or by the final customer, (vii) accidents or events way of example, production losses or unearned profits.
that place the Product outside its storage and operational specification, (viii) The Seller shall, at their discretion, forfeit all warranty rights of the Buyer if
continued use of the Products after identification of a fault or defect. the total sum of the contract and payment has not been reached in accordance
The warranty excludes components that must be replaced periodically such as with the agreed conditions of the contract.
fuses, lamps & air filters or consumable materials subject to normal wear and tear. No other warranties, express or implied, are made with respect to the
The warranty excludes external parts that are not manufactured by the Seller Products including, but not limited to, any implied warranty of merchantability
The Seller undertakes to replace or to repair, himself, at their discretion, any In any case, the Buyer’s right to damages shall be limited to a maximum
Product or its part that demonstrates a fault or defect, which is in conformance amount equal to no more than the price obtained by the Seller of the faulty or
with the aforementioned terms of the warranty. Reasonable costs associated defective Products.
with the disassembly/assembly, transport and customs of equipment will also These conditions shall apply to any repaired or replacement products. Not
be undertaken by the Seller except in cases of approved intervention by the withstanding the above, the replacement of a Product does not imply an
Buyer and/or their representative where cost allocation has been previously extension of the term of warranty outside that of the original term.
agreed. In case of fault or defect, the Buyer shall notify the Seller in writing
20
ADDITIONAL WARRANTY
Power Electronics stands by the quality and durability of our inverters. That
This is why we have made it our top priority to create a robust and reliable
product and give the best service and warranty along with it. To boost your
HEADQUARTERS
SPAIN
C/ Leonardo da Vinci, 24 - 26
Tel. 902 40 20 70
INTERNATIONAL SUBSIDIARIES
Tel. (+61) 7 3386 1993 Tel. (+49) 911 99 43 99 0 Tel. (+64 3) 379 98 26
Tel. (+55) 11 5891 9612 Tel. (+91) 80 6569 0489 Tel. (+51) 979 749 772
Tel. (+56) 9 8587 4347 Tel. (+39) 342 50 73 691 Tel. +971 4 364 1200
Tel. (+86 10) 6437 9197 Tel. (+81) 80 9386 6107 Tel. (+44) 149 437 00 29
Tel. (+57) 322 3464855 Tel. (+82) 2 3462 4656 Tel. (+1) 602-354-4890
FRANCE MEXICO
[email protected] [email protected]