Tube Well BOQ

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 42

Estimate for costing of Sinking & Installation of 200mm x 400mm dia G.I.

Pipe Deep Tubewell with


Name of 38mm dia test & observation well including 75 HP Submersible Pump Motor Set & water supply line
Work: in the Joynogar Residential Flat Project at Mirpur, Dhaka Under Mirpur H&S division-2, national
housing authority, mirpur, Dhaka.
Part: "A" 38mm dia uPVC pipe test & observation well
Item Code Item Description Qty. Unit Unit Price
Mobilization for test boring or observation well: Transportation
of materials, equipments, tools and plants and boring rig to work
1 site. Construction of derrick and dismantling the same. Cleaning 1.00 Set
the site after completion of the work accepted by the Engineer.
Boring by using 100 mm dia cutter and 40 mm dia heavy type
G.I pipe having wall thickness 2.9 mm, outside diameter min
47.8 mm, weight 3.517 kg/m, capability to withstand 50 kg/cm2
and other equipments capable of drilling up to a depth 500 meter
by water jet system through all sorts of strata. Protection of
2
caving by supplying necessary casing pipe. Collection of soil
samples at every 3 meter interval and at every change of strata
and preserve them in a controlled environment for analysis and
laboratory test. Finally withdrawal of boring and casing pipes etc.
complete and accepted by the Engineer.
i From 0.0m to 50.0 m 50.00 Rm
ii From 50.0m to 100.0 m 50.00 Rm
iii From 100.0m to 152.0 m 52.00 Rm
iv From 152.0m to 200.0 m 48.00 Rm
v From 200.0m to 250.0 m 50.00 Rm
vi From 250.0m to 350.0 m 100.00 Rm
Installation of tube-well fixture for observation well: Supplying
and lowering of 40/38 mm inside dia best quality uPVC pressure
tube well pipe having specific gravity 1.35 - 1.45, wall thickness
2.5 mm - 3.0 mm, capability to withstand a minimum hydrostatic
pressure of 170 psi for 1 hr. fitted and fixed in position with all
accessories, uPVC sand trap of length 3.00m with uPVC strainer
of desired slot installing in or at mid depth of the most suitable
3 water bearing strata. 38 mm dia G.I. pipe of best quality of length
1.52 m with M.S. welded flat bar on each side to prevent from
rotation up to desired depth, fitting fixing the best quality No. 6
C.I. head hand-pump etc including the cost of solvent cement,
socket adaptor, filling medium sand up to 18.00 m above strainer
and the remaining portion with available soil from boring etc.
complete as per standard specification and accepted by the
Engineer.
Fitting, fixing No. 6 Hand-pump set including all necessary
(a) accessories etc complete and accepted by the Engineer.For 1 1.00 Nos
Nos test & observation well :
38/40 mm dia heavy type G.I pipe conforming to standard BS-
1387 & BDS-1031, having chemical composition (in%) Carbon
0.17-0.25, Manganese 0.95-1.20, Sulphur 0.060 max,
Phosphorous 0.060 max, Tensile properties: minimum Yield
Strength 188 MPa, minimum Tensile Strength 313 MPa and
(b) marking for a) Manufacturer b) Material c) Wall thickness d) 6.10 Rm
Nominal outside dia e) Intended use etc. on the body of the pipe
having wall thickness 2.9 mm, weight 3.517 kg/m capability to
withstand 50 kg/cm2 hydraulic pressure. 1 Nos test &
observation well

38/40 mm dia water grade uPVC pipe having thickness 2.5-3.00


© mm 1 Nos test & observation well 310.88 Rm
38/40 mm dia water grade uPVC strainer having thickness 2.5-
(d) 3.00 mm 1 Nos test & observation well 30.48 Rm

38/40 mm dia uPVC socket adapter For 1 Nos test & observation
€ well : 69.00 Nos

For 1 Nos test & observation well : For 1 Nos test & observation
(f) well : 1.00 Nos

Supplying, fitting fixing observation well inside the housing pipe


of the deep tube well: 100'-0" depth For 1 Nos test &
(g) 1.00 Nos
observation well :

Supplying, fitting fixing tube-well log describing technical


(h) information of the tube-well as per instruction and accepted by 1.00 Nos
the Engineer. For 1 Nos test & observation well :
Filling the top 0.6 meter of the bore hole around the top pipe with
sanitary seal of concrete of proportion 1:2:4 as per design
(i) 1.00 Nos
accepted by the Engineer.. For 1 Nos test & observation well :

Complete development of the tube well to obtain sand and


turbidity free water at a satisfactory yield confirmed by
tests as per specification and accepted by the Engineer.
4 Water sample must be taken from 3 separate aquifers from 350.00 Rm
three tube-well.
Wells beyond 200 meter depth
For 1 Nos. test tube-wells
filling in sterilized air-tight glass bottles having no air
space inside; collecting soil (sand, solids etc) at 3 m
interval and at each change of soil strata from the bores,
arranging them in the cell of a box in an orderly manner.
carrying out test of water for (1) pH, (2) CO2 (3) Chloride,
(4) Fluoride, (5) Iron, (6) Manganese, (7) Nitrate-Nitrogen,
(8)Total alkalinity, (9) Total hardness, (10) Arsenic, (11)
Turbidity, followed by test reports along with Bangladesh
Standards of potable water and (12) Sieve analysis on soils
throughout a bore, leading to ascertain the best suitable
sustained aquifers, depths and slot sizes of strainer, types
and dia of tube well for specific yield, thickness of
shrouding around strainer, fineness modulus of shrouding
materials, mechanical units (pumps, compressor) for
testing and operation of the tube well, maintaining test
bore functional till tube well installation, testing etc. is
finished, finally filling and sealing the left over test bore
permanently, including carrying water and soil samples
5 under direct responsibility of Engineer-in-charge to BRTC, 1.00 Nos
BUET or other reputed laboratory, approved by the
authority, submitting the report and design details all
complete and accepted by the Engineer and maintaining
the mobilized tools and plant at site till satisfactory test
results are found (if not, next test bore may be executed
with the approval of concern S.E. / Design Office)
Total No. of test on water: 11 types of test x 1 test bore x
one set sample (3 specimen) = 11 Nos. test (each
specimen 1.5 liter of water)
Sieve analysis: min 9 Nos. Sample x one test x One bore =
9 Nos. test (Samples are of 1 kg dry wt. each)"
There are about 55 (fifty-five) tests for potable water
Quality Standard according to Bangladesh Environment
Conservation Rules-12 (Schedule-3), 1997, under ECA
1995 of Ministry of Environment and Forest. Therefore,
additional test/ tests on water or sieve analysis of soil if
required, other than the above specified 12 (twelve) tests,
may be carried out for public interest as per direction of
Disinfections of the well by using minimum 3 kg of
bleaching powder of 33% strength or any other
6 disinfectant as per standard specification and accepted by 1.00 Nos
the Engineer.
For 1 Nos test & observation well :

Construction of platform of size 1.4 m x 1.0 m outlet drain


up to 1 meter long as per drawing with 75 mm thick
cement concrete of fc min 17MPa with brick chips and
cement content relates to1:2:4 over a brick flat soling and
7 providing 125 mm x 75 mm brick band in 1:6 all around, 1.00 Nos
including finished with 12 mm thick cement plaster 1:4
followd by neat cement finishing all complete and
accepted by the Engineer.
For 1 Nos test & observation well :

Part: "B" Installation of 200mm x 400mm dia G.I. Pipe deep tube well

Mobilization: Preparation for installation of tube-well and


transportation of complete boring equipments, labour and
materials to the work site and remove the materials after
completion of the works. Installation of drilling rig and
accessories, making arrangements for electricity, water,
labour shed, site office and stores, digging mud pit etc,
8 1.00 Nos
leveling, dressing and clearing of the site as per original
condition and a testing for discharge using minimum 1000
liter water tub etc. all complete as per specifications and
accepted by the Engineer.using minimum 1000 liter water
tub etc. all complete as per specifications and accepted by
the Engineer. For Tube-wells beyond 200 meter depth

Boring: Execution of 800 mm dia of boring through all


sorts of strata by reverse circulation or any other approved
method (Method other than reverse circulation is to be
applied only for wells deeper than 152 meter). Boring for
800 mm dia vertical hole up to designed depth and
collection of soil samples at every 3 meter interval or as
9 required and at every change in soil stratum including
sinking and withdrawing necessary casing pipe and all
necessary arrangements complete as per specification and
accepted by the Engineer.
(Measurement will be allowed from E.G.L. to bottom of
the blind pipe and the rate is inclusive of the cost of extra
depth or of boring required due to caving and siltation)

i From 0.0 m to 50 m 50.00 Rm


ii From 50 m to 100 m 50.00 Rm
iii From 10 m to 152 m 52.00 Rm
iv From 152 m to 200 m 48.00 Rm
v From 200 m to 250 m 50.00 Rm
vi From 250 m to 350 m 100.00 Rm
Supplying the following tube-well fixtures and pipes
conforming to standard BS-1387 & BDS-1031, having
chemical composition (in%) carbon 0.17-0.25, Manganese
0.95-1.20, Sulphur 0.060 max, phosphorous 0.060 max,
Tensileproperties: miminum Yield strength 188 MPa,
10
Minimum Tensile Strength 313 MPa and marking for a)
Manufactureer b) Material c) Wall thickness d) Nominal
outside dia e) Intended use etc. on the body of the pipe at
working site as per standard practice and accepted by the
Engineer.

a 200 mm dia M.S. cap 6mm thick for blind pipe/ sand strap. 1.00 nos

200 mm dia 6 mm thick tube well pipe and blank G.I. pipe
b of wt. 33.45 kg per meter can withstand minimum 700 psi 85.34 Rm
hydraulic pressure. For 1 Nos Tube well :

200 mm dia strainer of slot opening as per design


including tagging 4 Nos. 12 mm dia M.S. rod
continuously.
200 mm dia stainless steel strainer of continuous slot
c having 38.36 kg per meter. 200 mm dia strainer of slot 36.57 Rm
opening as per design including tagging 4 Nos. 12 mm dia
M.S. rod continuously.
200 mm dia stainless steel strainer of continuous slot
having 38.36 kg per meter. For 1 Nos Tube well :

200 mm x 400 mm dia 6 mm thick M.S. reducer. For 1 1.00 nos


d
Nos Tube well :
400 mm dia 6 mm thick M.S. housing pipe (Seamless). 231.64 Rm
e
For 1 Nos Tube well :
Centralizer made with 12 mm dia M.S. rod of approved 25.00 nos
f
design. For 1 Nos Tube well :
450 mm dia M.S. cap of 6 mm thick for housing pipe 1.00 nos
g
covering. For 1 Nos Tube well :

Complete installation of 200 mm dia deep tube well


fixtures such as expanded top pipes, reducer, and tube well
pipes, strainer, blind pipe. Pipe cap etc. Fitting and fixing
socket, welding and additional welding with fibre and
11 placing in position with proper size M.S. centralizer @ 3 353.55 Nos
meter c/c in strainer position including blind pipe etc.
complete as per standard practice and accepted by the
Engineer. For 1 Nos Tube well :
(i) Housing Pipe: (ii) G.I. Pipe & Strainer

Complete development of the tube well by suitable air


compressor and pump of suitable capacity by alternate
surging and pumping until satisfactory yield, sand free
water and the turbidity condition is reached using
necessary quantity of calgon and conducting step draw 1.00 Nos
12
down test before and after the development as per
specification and accepted by the Engineer.
(Development should be started within 24 hours of
completion of shrouding). Wells Beyond 200 m depth
For 1 Nos Tube well :
Pumping test of the well by designed turbine/submersible
pump with supply of testing equipments for pressure/
velocity/ discharge etc. and all materials for 72 hours 72.00 hr
13
including yield drawn and recovery test etc. complete as
per specification and accepted by the Engineer. For 1 Nos
Tube well :

Disinfections of the well including supply of sufficient


quantity of bleaching powder (33% strength) chlorinated
14 water having 150 ppm available free chlorine complete as 1.00 Nos
per standard specification and accepted by the Engineer.
For 1 Nos Tube well :

Preparation and making gravel pack around the tube well


fixtures with supply of designed graded pea gravels free
from any substance harmful to pipe and health confirmed
by test (Passing through 10 mesh and retained on 40 mesh)
including sieving, washing etc. complete as per standard
specification and accepted by the Engineer. 47.58 Nos
15
(The rate is inclusive of the cost of extra amount required
for caving and extra depth below the tube well fixtures,
shrouding should not be more than 15 m above the strainer
and measurement should be allowed from bottom of the
tube-well fixture to top of the gravel pack) For G.I Pipe &
stainer For 1 Nos Tube well :

Making a sanitary seal up to a minimum depth of 6 meter


from G.L. or as specified including the supply of approved
16 quality of cement, sand and khoa (12 mm down graded) in 2.38 Cum
ratio (1:1:5:3) as per standard specification and accepted
by the Engineer. For 1 Nos Tube well :

Cement Concrete for loose joint made with cement & soda
poring by 100 mm dia G.I. Pipe up to a depth 500'-0" ect. 1.00 Nos
17
Complete as per standard specification and accepted by the
Engineer. For 1 Nos Tube well :

Part: "C" Supplying & Installation 75 HP Submersible Pump Motor Set

Providing of following capacity multistage Submersible


water pump motor set manufactured according to DIN/
NEMA/ IEC/ BS/ VDE/ JIS & ISO 9001 standard
compressing of 2900 RPM, 3-phase submersible motor
having Insulation: Class F & protection: IP68 (Minimum),
suitable for operation at 400/230 + 5% volt, 50 Hz. AC
supply with 18.29 meter (60’-0”) column pipe (AP 1-5L,
grade B) with flange gasket. Non return valve, pressure
18 gauge 40 meter (131’-0”) long required marine cable in a 2.00 Set
single length etc. complete in all respect manufactured by
CE certified/ UL listed countries as per sample approved/
accept by the Engineers.
Motor : 75 HP
Discharge : 15000-32000 IGPH
Head : 104-63 meter.
Column pipe : 150 mm dia.
For 1 Nos Tube well :
Providing & fixing of following dia 3.78 meter (10'-0")
long column pipe to be connected with submersible pump
motor set made of steel column pipe (API-5L, grade-B)
with all standard accessories including special flange at 32.00 job
19
both ends including anticorrosive painting etc. as per
sample approved/accepted by the Engineers.
125mm (5”)/150 mm (6'') dia
For 1 Nos Tube well :

Providing & fixing additional marine cable for


submersible pump motor set manufactured according to
DIN/ NEMA/ IEC/ BS/ VDE/ JIS & ISO 9001 standard 300.00 Rm
20
(Foreign made) & as per sample approved & accepted by
the Engineers.
3C- 25 sq.mm. For 1 Nos Tube well :

Installation, testing & commissioning of the following


capacity Deep well submersible pump motor set by
lowering down & connecting pump bowl assembly &
column pipes with marine cable with the help of chain
pulley after checking & testing the pump motor set
21 including filling distilled water, supplying & fixing a long 1.00 job
bend, 6.35mm thick M.S sheet tube- well cover, required
heavy duty holding clamp with nuts, bolts & making all
electrical & pipe connection complete as required as per
direction of the Engineers.
52 H.P to 85 H.P.

Supply & installation of metal clad surface mounting type


3-phase 400 Volt. + 5% 50Hz. automatic star- delta motor
control panel for submersible/ centrifugal pump motor set
main component manufactured in accordance with DIN/
NEMA/ IEC/ BS/ VDE/ JIS & ISO 9001 standard
comprising of circuit breaker of required capacity,
ammeter and voltmeter with selector switch of proper 1.00 Nos
22
current ratio & burden, indicating light for 3-phase, on -
trip indicating lamp, main auxiliary contactors, thermal
over load relay, timer, on - off push button, electric relay
for protection against phase failure, phase reverse
complete with necessary wares, cables lugs, cables tiles,
connections etc. of the following as per direction of the
Engineers. 60 /62 HP For 1 Nos Tube well :

Earthling the electrical installation with 40 mm (1.5”) dia


G.I pipe (Earth electrode) having 6.35 mm. dia hole across
the pipe at 305 mm interval securedly bonded by soldering
with 2 nos. of No 2 SWG HDBC earth leads with its
protection by 20 mm ( ¾“ ) dia G.I Pipe up to plinth level
23 run at a depth of 609.6mm (2 feet) bellow G.L up to main 1.00 Set
board to be earthed including necessary connecting copper
sockets, bolts, nuts, etc. complete for maintaining earth
resistance within 1 ohm.
Depth of bottom of main electrode at 37338mm (122.5 ft)
from G.L & length of electrode 36576 mm (120 ft.)
Providing & fixing on a prepared board 500 volt grade
following Triple-pole molded case circuit breaker
(TPMCCB) with thermal over-current and instantaneous
electromagnetic short circuit release provision,
manufactured & tested in accordance with relevant IEC/
24 VDE/ NEMA/ BS/ JIS standards. 2.00 nos
TPMCCB of ABB/ AEG/ DORMAN SMITH/
LEGRAND/ SCHNEIDER/ Eaton/ HAGER/MEM/
MERLIN GERIN/ VITZRO/ Kawamura/FEDERAL or
equivalent Brand accepted/approved by the Engineer.
150/160 Amps (Minimum 16-KA) For 1 Nos Tube well :

Supplying different inside dia uPVC pressure pipe C-


Grade/Having density 1350 Kg./M3 Opacity 0.2% of
visible light as per ISO 7686, Min. required strength 25
MPa conferring to BDS-1:2013, 4.4.1, 4.4.2 for water
supply having specific gravity 1.35 - 1.45, and other
physical, chemical, thermal, fire resistivity properties etc.
as per BSTI approved manufacturer standards or ASTM, 10.00 Rm
25
BS/ISO/IS standards fitted and fixed in position with
sockets, bends, with all accessories such as Round
grating/domed roof grating, bends, sockets etc. approved
and accepted by the Engineer. (length: 6000 mm each) 75
mm dia wall thickness 4.8 mm - 5.5 mm
(For protection of underground marine cable) For 1 Nos
Tube well :

Providing & laying of the following PVC insulated &


sheathed cable of (NYY)/ XLPE insulated & PVC
Sheathed cable (2XY) with PVC insulated green/white
coloured ECC wire (BYA) connecting at both ends,
through PVC Pipe & accessories in tie following manner:
all electrical contracts shall be of Brass/ Copper connected
through connector or soldering (no twisting shall be
allowed) and cables shall be manufactured and tested
according to relevant IEC/ VDS/ BS/ VDE standards as
per detailed specification mentioned in Annexure-A. The
26
work shall be carried out as per direction/ approval/
acceptance of the Engineer
i. In kutcha ground by cutting 45.70 cm width X 91.40 cm
depth trench with necessary brick or tile protection and
mending the damages good by refilling trench with proper
compaction.
ii. In pucca floor through PVC pipe by cutting trench of
necessary size and mending the damages good by brick
soling, 75mm (1:2:4) cc work with neat cement finishing
etc.

i In Kutcha Ground 300.00 Rm


ii In Pucca Floor 200.00 Rm
Providing & fixing cast iron reflux vales (Non-Return
valve) with cast iron body, reflux vale cover plate, flap,
valve disc & flap lined with leather, cast iron hanging arm,
stainless steel louver shaft & bolt with cover gasket etc.
27 including all other standard accessories manufactured 1.00 Nos
according to DIN/NEMA/IEC/BS/VDE/JIS & ISO 9001
standard) as per sample accepted/approved by the
Engineers.
Dia 150mm (6”)

Part: "D" Different Dia Water Supply Pipe Line

Supplying, fitting and fixing G.I. pipe conforming to the


standard BS-1387 & BDS-1031, having chemical
composion (in%) carbon 0.17-0.25, Manganese 0.95-1.20,
Sulphur 0.060 max, Phosphorous 0.060 max, Tensile
properties : minimum Yield Strength 188 MPa, minimum
Tensile Strength 313 MPa and marking for a)
Manufacturer b) Material c) Wall thickness d) Nominal
outside dia e) Intended use etc. on the body of the pipe
with all special fittings, such as bends, elbows, sockets,
reducing sockets, Tee, unions, jam-nuts etc. including
28 cutting trenches where necessary and fitting the same with 762.57 Rm
earth duly rammed and fixing in walls with holder bats and
making hole in floors, walls and consequent mending good
the damages etc. all complete in all respects approved and
accepted by the Engineer.
( Pipes manufactured by National Tubes Limited under
Steel & Engineeing Corporation Ministry of Industries,
Government of Bangladesh shall be given priority) (a) 100
mm dia G.I. Pipe with wall thickness 3.65 mm, outside
diameter min 113 mm, weight 10.42kg/m, can withstand
min 50 kg/cm2 hydraulic pressure.

Supplying, fitting & fixing best quality flange type


Different dia fittings for G.I pipe line such as Flange Tee,
Flange Bend, Flange Reducing Socket, Flange Reducing
29
Tee, Flange Tail piece, sluice valve & Flange
Shade/dresser etc. complete as per direction of the
Engineer-in-charge.
i 100 mm dia flange tee 30.00 Nos
ii 100 mm dia flange bend 50.00 Nos
iii 100 mm dia flange tail piece 50.00 Nos
iv 100 mm dia flange shade/dresser 50.00 Nos
v 100 mm dia sluice valve 20.00 Nos

Construction of sluice valve chamber inside measurement


(4’X4’X4’) with 250mm thick brick work cement mortar
(6:1) with 100mm thick R.C.C top slab (4:2:1) with
reinforcement 450mm dia C.I manhole cover with locking 15.00 Nos
30
arrangement including necessary earth cutting side filling
one brick flat soling 75mm thick (1:3:6) C.C. and 12mm
thick (1:2) C.C. with N.C.F. finishing etc. all complete as
per direction of the Engineer-in-charge.

Sub Total Part D


Pump House
Earth work in excavation in all kinds of soil for foundation
trenches including. layout, providing center lines, local
bench-mark pillars, leveling, ramming and preparing the
base, fixing bamboo spikes and marking layout with chalk
powder, providing necessary tools and plants, protecting
and maintaining the trench dry etc., stacking, cleaning the
31 excavated earth at a safe distance out of the area enclosed
by the layout etc. all complete and accepted by the
Engineer, subject to submit method statement of carrying
out excavation work to the Engineer for approval.
However, Engineer’s approval shall not relieve the
contractor of his responsibilities and obligations under the
contract.

Layout and marking for earthwork in excavation in


a foundation accepted by the Engineer. [Plinth area of the 34.83 Sqm
structure shall be considered for measurement]
Earthwork in excavation in foundation trenches up to 1.5
b m depth and maximum 10 m lead: in soft clayey soil / 42.83 Cum
loose sand / silt
Estra Rate for each aditional 0.5 meter depth exceeding 1.5 Cum
c 8.56
meter. (i) 1.5 Meter to 2.00 Meter

Sand filling in foundation trenches and plinth with sand


having F.M. 0.5 to 0.8 in 150mm layers including leveling,
watering and compaction to achieve minimum dry density
32 of 90% with optimum moisture content (Modified proctor 5.66 no
test) by ramming each layer up to finished level as per
design supplied by the design office only etc. all complete
and accepted by the Engineer.

,Earth filling in foundation trenches and plinth in 150 mm


layer with earth available within 90 m of the building site
to achive minimum dry density of 90% with optimum
33 moisture content (Modified proctor test) including carrying 10.27 Cum
watering, leveling, dressing and compacting to a specified
percentage each layer up to finished level etc. all complete
and accepted by the Engineer.

Clearing and disposing of excavated earth from the


construction site by truck or any other means to a place
34 within 30 km radius of the city or town area including 41.12 Cum
loading, unloading at both ends, leveling and dressing the
carried earth etc. complete accepted by the Engineer.

One layer of brick flat soling in foundation or in floor with


first class or picked jhama bricks including preparation of 32.90 Sqm
35
bed and filling the interstices with local sand, leveling etc.
complete and accepted by the Engineer.
Mass concrete (1:2:4) in foundation or floor with cement,
sand (F.M. 1.2) and picked jhama chips including breaking
chips, screening, mixing, laying, compacting to levels and
36 curing for at least 7 days including the supply of water,
electricity and other charges and costs of tools and plants
etc. all complete and accepted by the Engineer. (Cement:
CEM-II/A-M)
Mass concrete in foundation (1:2:4) with brick chips and
i. 1.58 Cum
local sand of F.M. 1.2
Mass concrete in foundation (1:2:4) with brick chips and
ii. 1.41 Cum
local sand of F.M. 1.2

Damp proof course (DPC) (1:1.5:3) in cement concrete


with cement, sand (F.M. 1.2) and picked jhama or stone
chips including breaking chips, screening, centering,
shuttering, casting, curing and finished with a coat of
bitumen including the supply of water, electricity and other 5.97 Sqm
37
charges and costs of tools and plants etc. all complete and
accepted by the Engineer. (Cement: CEM-II/A-M)
75 mm or 3" thick damp proof course (1:1.5:3) with brick
chips and 50% Sylhet sand (F.M. 2.2) and 50% local sand
(F.M. 1.2)

Supplying and laying of single layer polythene sheet


weighing one kilogram per 6.5
38 square meter in floor or any where below cement concrete 32.90 Sqm
complete in all respect
and accepted by the Engineer

Brick works with first class bricks in cement sand (F.M. of


sand 1.2) mortar (1:6)
in foundation and plinth, filling the joints/interstices fully
with mortar, racking out the
39 joints, cleaning and soaking the bricks at least for 24 hours 15.11 Cum
before use and curing at
least for 7 days etc. all complete including cost of water,
electricity and other charges
and accepted by the Engineer. (Cement: CEM-II/A-M)

Brick works of width one brick or one and a half brick


length with first class
bricks in cement sand (F.M. 1.2) mortar (1:6) in
superstructure including raking
out joints, filling the interstices with mortar, cleaning and
soaking the bricks at least
40 for 24 hours before use and washing of sand, necessary 14.62 Cum
scaffolding, curing at least
for 7 days etc. all complete (measurement to given as 250
mm width for one brick
length and 375 mm for one brick and a half brick length)
and accepted by the
Engineer.(Cement: CEM-II/A-M)In ground floor
125 mm brick work with first class bricks in cement sand
(F.M. 1.2) mortar (1:6)
and making bond with connected walls including
necessary scaffolding, raking out
joints, cleaning and soaking the bricks for at least 24 hours
before use and washing
41 6.46 Sqm
of sand curing at least for 7 days in all floors including
cost of water, electricity and
other charges etc. all complete and accepted by the
Engineer. (Cement: CEM-II/AM)
In ground floor

Reinforced cement concrete works using wooden shutter,


with minimum
cement content relates to mix ratio 1:2:4 having minimum
f 'cr = 24 Mpa, and
satisfying, specified compressive strength f’'c= 19 Mpa at
28 days on standard
cylinders as per standard practice of Code
ACI/BNBC/ASTM & cement conforming to
BDS EN-197-1- CEM1, 52.5N (52.5MPa)/ ASTM-C 150
Type – I, best quality sand
[50% quantity of best local sand (F.M. 1.2) and 50%
quantity of Sylhet sand or
coarse sand of equivalent F.M. 2.2] and 20 mm down well
graded picked jhama brick
chips conforming ASTM C-33 including breaking chips
and screening, making,
42
placing shutter in position and maintaining true to plumb,
making shutter watertight
properly, placing reinforcement in position; mixing in
standard mixer machine
with hoper fed by standard measuring boxes, casting in
forms, compacting by
vibrator machine and curing for 28 days,and removing
centering-shuttering after
specified time approved; including cost of water,
electricity, additional testing
charges of materials and cylinders required by engineer,
other charges etc. all
complete approved and accepted by the Engineer.
(Rate is excluding the cost of reinforcement and its
fabrication, placing and
binding etc)

A) Floor and Roof Slab


i) Concrete 2.79 Cum
ii) Formwork/shuttering, prop and necessary 27.77 Sqm
supports etc. (wooden)
B) Tie Beams and Lintels
i) Concrete 0.92 Cum
ii) Formwork/shuttering, prop and necessary 10.35 Sqm
supports etc. (wooden)
Grade 400 (RB 400 / 400W: complying BDS ISO
6935-2:2006) ribbed or deformed
bar produced and marked according to Bangladesh
Standard, with minimum yield
strength, fy (ReH)= 400 Mpa but fy not exceeding
43 418MPa and what ever is the 473.33 kg
yield strength within allowable limit as per BNBC sec
8.3.3.5 /ACI 318-11 sec
21.1.5.2, the ratio ultimate tensile strength fu to
yield strength fy, shall be at
least 1.25 and minimum elongation after fracture
and minimum total elongation at
maximum force is 16% and 8% respectively : up to
ground floor
a. Roof
b. lintel

Supplying fan hook 300-grade ( RB300) of 16 mm


diameter M.S. rod (one meter
44 straight length) having rounded hook at the middle 2.00 Nos
of bar in proper size so as to be
concealed within fan cup including fabrication and
fitting fixing in all floor accepted by
the Engineer.

Supplying and making door and window frames


(Chowkat) for all floors with
matured natural seasoned wood of required size
45 0.08 Cum
including painting two coats of coal
tar to the surface in contact with wall, fitting and
fixing in position etc. complete and
accepted by the Engineer. (All sizes of wood are
finished)
Teak Chambal /Jarul

Supplying, fitting and fixing 38 mm thick well


matured, seasoned (min 10" wide
plank) solid wood single leaf door shutter having top
rail style of sections 100 mm
x 38 mm, lock rail 125 x 38 mm and bottom rail 225 x 3.28 Sqm
46
38 mm. Closed joints with 25
mm x 12 mm size wooden peg and provided with
best quality 4 Nos. 100 mm iron
hinges 2 (two) Nos. best quality 12 mm dia 300 mm
and 200 mm long iron tower and
socket bolts, 2 (two) Nos. heavy type nickel plated
handle, hinged cleats, buffer
blocks and finished by sand papering etc. all
complete in all floors and accepted by
the Engineer.(All sizes of wood are finished)
Supplying, fitting and fixing M.S. flat bar clamp of
225 x 38 x 6 mm size having
47 bifurcated ends to door and window frames with 12.00 Nos
necessary screws and encasing
inside the wall with cement concrete (1:2:4) etc.
complete and accepted by the
Engineer.

Supplying, fitting and fixing best quality heavy type


48 19 mm dia and to 300 mm long 4.00 nos
brass hasp bolt including cutting grooves in door
shutter and frames, screws etc. all
complete approved and accepted by the Engineer.

Supplying, fitting, fixing window grills of any design


made with approx 25 x 6 mm F.I.
bar as inner section but no outer frame; including
49 fabrication, welding, cost of 5.01 sqm
electricity workshop charges, carriage, cutting
grooves, mending good the damages,
tools and plants etc. complete for all floors accepted
by the Engineer. (Total weight
per sqm should be approx 18 kg. and add or deduct
@ Tk. 108 for each kg. excess
or less respectively)
Supplying, fitting and fixing of Aluminium sliding
window as per the U.S.
Architectural Aluminium Manufacturer‟s Association
(AAMA) standard specification
having 1.2 mm thick outer bottom (size 75.50 mm,
32mm), 1.2 mm thick outer top
(size 75.50 mm, 16.80 mm), 1.2 mm thick shutter top
(size 33 mm.26.80, 22 mm),
1.2 mm thick shutter bottom (size 60mm, 24.40
mm), 1.2 mm thick outer side (size
50 75.50 mm,19.90 mm), 1.2 mm thick sliding fixed side 5.01 sft
(size 31 mm, 26 mm),1.2 mm
thick shutter lock (size 49.20 mm 26.20 mm) and 1.2
mm thick inter lock (size 34.40
mm, 32.10 mm) sections all aluminium members
(total weight kg/sqm) will be
anodized to aluminium bronze/silver colour with a
coat not less than 15 micron in
thickness and density of 4 mg per square cm etc.
including all accessories like
sliding door key lock, sliding door wheel, sliding door
mohiar, sliding door neoprene,
bolts and nuts including sealants, keeping provision
for fitting 5 mm thick glass
including labour charge for fitting of accessories,
making grooves and mending good
damages, carriage, and electricity complete in all
respect as per drawing and
accepted by the Engineer.

Supplying, fitting and fixing in Aluminium door


frames, windows, partitions and
51 curtain wall distortion free glass of approved quality 5.01 sqm
and shade including cost of
fitting fixing all necessary accessories etc. complete
in all respect as per drawing and
accepted by the Engineer.

Minimum 12 mm thick cement sand (F.M. 1.2)


plaster with neat cement finishing
to plinth wall (1:4) with cement up to 150 mm below
52 ground level with neat cement 19.82 sqm
finishing including washing of sand, finishing the
edges and corners and curing at
least for 7 days, cost of water, electricity and other
charges etc. all complete in all
respect as per drawing and accepted by the
Engineer. (Cement: CEM-II/A-M)
Ground floor.
Minimum 12 mm thick cement sand (F.M. 1.2)
plaster (1:6) having with fresh
cement to wall both inner-and outer surface,
53 finishing the corner and edges including 133.22 sqm
washing of sand cleaning the surface, scaffolding and
curing at least for 7 days, cost
of water, electricity and other charges etc. all
complete in all respect as per drawing
and accepted by the Engineer.(Cement: CEM-II/A-
M)Ground floor.

Minimum 6 mm thick cement sand (F.M. 1.2) plaster


(1:4) with fresh cement to
ceiling R.C.C. columns, beams, surface of stair case,
sunshades, cornices, railings, 27.77 sqm
54 drop wall, louvers, fins and finishing the corners and
edges including washing of
sand cleaning the surface, scaffolding and curing at
least for 7 days, cost of water,
electricity and other charges etc. all complete in all
respect as per drawing and
accepted by the Engineer. (Cement: CEM-II/A-M).
Ground floor.

Pre-cast ventilators of minimum 25 mm thick of any


design with cement sand
55 (F.M.1.2) mortar (1:4) fitted and fixed in position, 0.46 sqm
finished with cement sand (F.M.
1.2) plaster (1:6) including necessary scaffolding and
curing, in all floors accepted by
the Engineer. (Cement: CEM-II/A-M

On exterior surface applying as per manufacturer


56 instructions 3 coat of weather coat 71.23 sqm
of approved quality and colour delivered from
authorized local agent of the
manufacturer in a sealed container complete in all
respect in all floors and accepted
by the Engineer.
Plastic emulsion paint of approved best quality and
colour delivered from
authorized local agent of the manufacturer in a
sealed container, applying to wall and
ceiling in two coats over lime putty of specified
brand applied on primer or sealer
57 elapsing specified time for drying/recoating 99.64 sqm
including cleaning drying, making free
from dirt, grease, wax, removing all chalked and
scaled materials, fungus, mending
good the surface defects, sand papering the surface
and necessary scaffolding,
spreading by brush/ roller/spray etc. all complete in
all floors accepted by the
Engineer.
Lime putty to be applied as per manufacturer
instructions approved and accepted by
the Engineer.
Walls & Ceiling

Average 100 mm thick finished lime terracing with


20 mm down graded first class
brick chips (Khoa), surki from 1st class bricks and min
lime content 500kg per
2.83cubic meter (stone lime brought at site, not
being powdered in open air and to be
58 slaked in presence of engineer-in-charge and to be 2.79 cum
measured in volume three days
after slaking for using in the mix) in the proportion
7:2:2 (brick chips : surki : lime)
including preparation of the mix on the ground by
making a suitable platform under
proper polythene cover. Cutting the mix twice daily
with limewater (1:10) at least for 7
days until the mix attain desirable consistency. Laying
the mix in proper slope,
beating the same with standard „koppa‟ for
minimum 7 days to gain maximum
consolidation, making ghoondy and neat finishing
with lime Surki mortar (1:2) and
curing for 21 days providing polythene cover after
each day work and cleaning etc.
complete in all respect accepted by the Engineer
Constructing surface drain of 300 mm clear width
and depth up to 300 mm in
brick masonry with 125 mm thick check wall in
cement sand (F.M. 1.2) mortar (1:6)
over av. 75 mm thick cement concrete base (1:3:6) 20.32 Rm
59
over one layer of brick flat soling.
The surface having minimum 12 mm thick cement
sand (F.M. 1.2) plaster (1:3) and
neat cement finishing with cement curing at least for
7 days including excavation in
all kinds of soil, back filling with fine sand (F.M. 0.8),
consolidating and dressing, cost
of water, electricity, other charges etc. complete and
accepted by the Engineer.
(Cement: CEM-II/A-M)

Providing apron with 50 mm thick cement concrete


(1:2:4) with cement, coarse sand
and picked jhama chips including breaking chips and
one layer brick flat soling at 12.39 sqm
60 bottom with first class or picked jhama bricks
including cutting earth for preparation
of bed and filling the interstices with local sand (F.M.
0.8) including finishing,
dressing, curing at least for 7 days etc. all complete,
including cost of water,
electricity, other charges accepted by the Engineer.
(Cement: CEM-II/A-M)

Supplying, fitting and fixing Bangladesh pattern, long


pan with foot-rest, made of
Vitreous China and preparing the base of pan with
61 cement mortar (1:4) and with wire 1.00 Cum
mesh or rods, if necessary in all floors including
making holes wherever required and
mending good the damages and fitting, fixing,
finishing etc. complete with all
necessary fittings and connection approved and
accepted by the Engineer
For Toilet
Supplying, fitting and fixing European type glazed
porcelain low-down, capacity 10
62 liter, 490 x 190 x 350 mm in size, approximately 14 1.00 Nos
kg by weight, on walls by screws
and F.I. bar clamps, rowel plugs, making holes
wherever required and mending good
the damages and fitting, fixing finishing etc.
complete with all necessary fittings and
connection approved and accepted by the Engineer.
For Toilet

Supplying, fitting and fixing white glazed vitreous


W/H Wash Basin including
excluding pedastal, fitting, fixing the same in position 1.00 Nos
63 with heavy type C.I. Brackets.
30 mm dia PVC waste water pipe with brass coupling
(not exceeding 750 mm in
length), basin waste with chain plug including
making holes in walls and floors and
fitting with wooden blocks, screws and mending
good the damages, finishing etc. all
complete approved and accepted by the Engineer.

Supplying, fitting and fixing of 450 x 600 mm size and


5 mm thick unframed super
quality mirror with hard boards at the back with all
64 1.00
necessary fitting including
making holes in walls and mending good the
damages with cement mortar (1:4) etc.
all complete approved and accepted by the Engineer.
(Made in Japan or equivalent)
Over Basin

Supplying, fitting and fixing super quality 600 x 125


mm coloured glass (plate)
shelf having 5 mm thickness with fancy C.P. brackets,
65 1.00 nos
screws and frames including
making holes in walls and mending good the
damages with cement mortar (1:4) etc.
all complete approved and accepted by the Engineer.
Over Basin

Supplying, fitting and fixing medium quality C.P.


Towel rail of 600 mm long and 20
66 mm in dia with C.P. holder including making holes in 1.00 nos
walls and mending good the
damages with cement mortar (1:4) etc. all complete
approved and accepted by the
Engineer. For Toilet
Supplying, fitting and fixing standard toilet paper
holder of 150 x 150 x 126 mm size
67 including making holes in walls and mending good 1.00 nos
the damages with cement mortar
(1:4) etc. all complete approved and accepted by the
Engineer.
For Toilet

Supplying, fitting and fixing standard size soap tray


68 including making holes in walls 1.00 nos
and mending good the damages with cement mortar
(1:4) etc. all complete approved
and accepted by the Engineer. For Toilet

Supplying 100 mm inside dia best quality uPVC soil,


waste and ventilation pipe
having specific gravity 1.35-1.45, wall thickness 3.4-
4.0 mm, and other physical, 6.09 Rm
69 chemical, thermal, fire resistivity properties etc. as
per BSTI approved manufacturer
standards or ASTM, BS/ISO/IS standards fitted and
fixed in position with sockets,
bends, with all accessories such as Round
grating/domed roof grating bands,
sockets etc. approved and accepted by the Engineer
(length: 6000 mm each).

Supplying 50 mm inside dia best quality uPVC soil,


waste and ventilation pipe
having specific gravity 1.35 - 1.45, wall thickness 2.5
- 3.0 mm, and other physical,
70 chemical, thermal, fire resistivity properties etc. as 4.57 Rm
per BSTI approved manufacturer
standards or ASTM, BS/ISO/IS standards fitted and
fixed in position with sockets,
bends, of uPVC Pipe with all accessories such as
Round grating /domed roof grating
bands, sockets etc. approved and accepted by the
Engineer (length: 6000 mm
each).
Supplying, fitting and fixing G.I. pipe conforming to
the standard BS-1387 & BDS1031,
having chemical composition (in%) Carbon 0.17-
0.25, Manganese 0.95-1.20,
Sulphur 0.060 max, Phosphorous 0.060 max, Tensile
71 properties : miminum Yield
Strength 188 MPa, minimum Tensile Strength 313
MPa and marking for a)
Manufacturer b) Material c) Wall thickness d)
Nominal outside dia e) Intended
use etc. on the body of the pipe with all special
fittings, such as bends, elbows,
sockets, reducing sockets, tee, unions, jam-nuts etc.
including cutting trenches
where necessary and fitting the same with earth
duly rammed and fixing in walls with
holder bats and making hole in floors, walls and
consequent mending good the
damages etc. all complete in all respects approved
and accepted by the Engineer.

20 mm dia G.I. Pipe with wall thickness 2.65 mm,


72 outside diameter min 26.5 mm, 6.09 Rm
weight 1.70 kg/m, can withstand min 50 kg/cm2
hydraulic pressure.

73 25 mm G.I. pipe with wall thickness 4.05 mm, 15.23 Rm


outside diameter min 33.4 mm, weight 2.97 kg/m,
can withstand min 50 kg/cm2 hydraulic pressure

Supplying, fitting and fixing G.I. Union with sealant


74 etc. complete in all respects 1.00 nos
approved and accepted by the Engineer.
12 mm dia G.I. Union
For Water Line

Supplying, fitting and fixing best quality G.I. gate


75 valve with sealant etc. complete 1.00 nos
approved and accepted by the Engineer.
For Water Line

Supplying, fitting and fixing European type HCI P-


Trap drainage pipe preparing the
base with cement concrete in 1:2:4 and with wire
76 2.00 nos
mesh or rods if necessary, in all
floors including making holes wherever required and
mending good the damages
and fitting, fixing complete with all necessary fittings
and connection approved and
accepted by the Engineer
Supplying, fitting and fixing best quality faucets etc.
77 complete approved and 2.00 nos
accepted by the Engineer
For Toilet Room

Supplying, fitting and fixing Special/Fancy quality C.P.


concealed/ surface stop
78 cock with all necessary hardware and consumables 2.00 nos
approved and accepted by the
Engineer. 12 mm CP Stop Cock for Surface Mount
(medium quality)

Supply and fitting-fixing cleansing shower for


79 ablution including holder of following 1.00 nos
types: Moving type 100 mm CP shower rose

Supply and installation of food-grade plastic internal


mini water tank for the use in
kitchen, bathroom and toilet for emergency storage
and supply of water
manufactured from liner low density polyethylene 1.00 nos
80
(ILDPE) roto-grade (ultra violet)
stabilized which complies FDA (Federal Department
of Agriculture, USA) regulations
21 CFR 1277. 152, having food grade quality where
no recycled material is used
carrying, lifting, fitting, fixing in position including
supply of necessary hardware,
consumables, fittings etc. all complete approved and
accepted by the Engineer.
300 liter capacity

Construction of masonry inspection pit with 250 mm


thick brick work in cement
mortar (1:4) including necessary earth work, side
81 filling and one layer brick flat 2.00 nos
soling, 75 mm thick (1:3:6) base concrete for making
invert channel and 12 mm thick
(1:2) cement plaster with neat finishing etc. all
complete up to a depth of 700 mm
approved and accepted by the Engineer.
Clear 600 x 600 mm and depth 750 to 900 mm,
average 825 mm for single 300 mm
dia R.C.C. pipes and 375 mm and 400 mm PVC pipe.

Toatal
Wasa Charge
City Corporation Charge
Grand total
Pipe Deep Tubewell with
or Set & water supply line
&S division-2, national

Total Price
0.00
ell
0.00
Set
0.00

0.00

0.00
0.00
0.00