Air-Cooled/Fluid-Cooled - 50/60 Hz
ACRD100
ACRD101
ACRD200
ACRD201
ACRD500
ACRD501
ACRD502
Technical Data
American Power Conversion Legal Disclaimer
The information presented in this manual is not warranted by the American Power Conversion Corporation
to be authoritative, error free, or complete. This publication is not meant to be a substitute for a detailed
operational and site specific development plan. Therefore, American Power Conversion Corporation
assumes no liability for damages, violations of codes, improper installation, system failures, or any other
problems that could arise based on the use of this Publication.
The information contained in this Publication is provided as is and has been prepared solely for the purpose
of evaluating data center design and construction. This Publication has been compiled in good faith by
American Power Conversion Corporation. However, no representation is made or warranty given, either
express or implied, as to the completeness or accuracy of the information this Publication contains.
Copyright, intellectual, and all other proprietary rights in the content (including but not limited to software,
audio, video, text, and photographs) rests with American Power Conversion Corporation or its licensors.
All rights in the content not expressly granted herein are reserved. No rights of any kind are licensed or
assigned or shall otherwise pass to persons accessing this information.
Standard Features........................................................... 4
Cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Shutdown Input/Alarm Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Variable Speed Fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Bay Kit-InRow RD/NetShelter SX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Counterflow Cooling Coil/Condensate Pan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Selectable Top or Bottom Piping Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Network Management Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Condensate Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Remote Temperature Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Optional Features............................................................ 5
Cable Water Detector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Network Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Power Trough . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Data Partition . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Height Adapters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
InRow RD Models............................................................ 8
Exterior components: ACRD100 and ACRD200 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Interior components (front): ACRD100 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Interior components (rear): ACRD100 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Interior components (front): ACRD200 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Interior components (rear): ACRD200 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Exterior components: ACRD500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Interior components (front): ACRD500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Electrical panel: ACRD500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
User interface panel: ACRD500 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
APC warrants all parts for 12 months ACRD100 series and ACRD200
from the date of purchase. Extended series only:
warranties are available. • Insulated cabinet
• Washable filter
Capacities • Condensate management with two
InRow RD units are available in two dual float condensate pumps
sizes (300mm and 600mm) with
• Scroll compressor
nominal capacities ranging from
2-10kW (300mm) and 10-29kW • Hot gas bypass
(600mm). ACRD100 series only:
• Liquid line solenoid valve
Room Air Distribution
Row-based systems are placed in line ACRD500 series only:
with rack enclosures. At least one • Backward inclined impeller
system is used per hot aisle. Air is • Pleated 100-mm (4-in) filter
drawn in through the rear of the sys-
• NPT to BSPT pipe adapters
tem, cooled, and discharged into the
cold aisle, thereby neutralizing the • Condensate management with one
sensible heating effects of the data dual float condensate pump
processing equipment. The InRow • Variable speed reciprocating
RD delivers high volumes of airflow compressor using VFD control
to eliminate hot spots in densely pop- • Pressure equalization solenoid
ulated environments. • Pipe adapters
Configuration
• Air-cooled
• Fluid-cooled
na2860a
Critical
Status LED
Escape key
Enter key
Help key
Open Architecture
The InRow RD protocol is open for
integration with all building manage-
ment systems. Communication
interface on the system can be Mod-
bus RS485 or Ethernet.
na2625a
na2626a
na2627a
Sight glass
na2633a
na2635a
Sight glass
na1824a
na2720b
na2723a
Table 1:
Evaporator coil Shutoff valves
Condensate drain pan Air filters
Sight glass Pipe chase
Filter dryer Return air temperature sensor
Condensate pump
na2664a
Transformers
Relay board
Ground lug
A-Link IN
A-Link OUT
Network port
Console port
Remote shutdown-
BMS D1 (RXTX+)
BMS D0 (RXTX–)
BMS GND
Display interface
na2009a
Fluid-cooled
MODEL ACRD200 Series
AIR SYSTEM - FAN (Standard Filter Installed)
Size - mm (in) 200 (7.9)
Air Volume - l/s (SCFM) 1080 (2290)
Fan Motor - W (HP) each 115 (0.15)
Number of Fans 6
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m2 (ft2) 0.37 (3.97)
Rows Deep 2
FILTERS - WASHABLE (STANDARD)
Quantity 2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 13 (1/2)
Efficiency (%) <20% MERV 1
FILTERS - PLEATED (OPTIONAL)
Quantity 2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 51 (2)
Efficiency (%) 30% MERV 8
PHYSICAL DATA
Weight - kg (lbs) 199.09 (438)
Height - mm (in) 1991 (78.39)
Width - mm (in) 300 (11.8)
Depth - mm (in) 1070 (42.13)
CONNECTION SIZES
Liquid
In 7/8-in O DF brazed
Return 7/8-in ODF brazed
Condensate Drain
Drain Line - in 3/16-in ID, 5/16-in OD
REFRIGERANT
Type R410A
Charge - kg (oz) 2.2 (78)
Electrical Data
Compressor
SKU MCA MOP FLA Power
LRA RLA
ACRD100 - 208-240V, 60Hz 25 40 N/A 87.5 16.0 4.6
ACRD101 - 220-240V, 50Hz N/A N/A 21 97.0 16.3 4.4
ACRD200 - 208-240V, 60Hz 25 40 N/A 87.5 16.0 4.6
ACRD201 - 220-240V, 50Hz N/A N/A 21 97.0 16.3 4.4
ACRD500 - 200-240V, 50/60Hz 54.0 90 - 160* 50 15
ACRD501 - 460-480V, 60Hz 27.0 40 - 139* 23.2 16
ACRD502 - 380-415V, 50Hz - - 26.0 139* 23.2 16
Note: Above data is based on maximum operating condition MCA-Minimum Circuit Ampacity
Note: Installation must comply with national and/or local electrical codes. MOP-Maximum Overcurrent Protection
Note: Use LRA for estimation of inrush current. LRA-Compressor Locked Rotor Amps
* The compressor is powered by the VFD. RLA-Compressor Rated Load Amps
FLA-Full Load Amps
na2231b
na2465a
na2784a
NetShelter SX to VX Height Adapter: ACRD500 series
na2445a
NetShelter SX to 48-U SX Height Adapter: ACRD100 and ACRD200 series
na2788a
Condenser Condenser
Hot gas
Hot gas
Liquid
Liquid
na2543a
RD
Receiver RD Receiver
Note: Shutoff valves shown nearest to the condensers are not supplied by APC.
ACRD500 series: The shutoff valves nearest to the cooling unit are supplied by APC.
ACRD100 series: The shutoff valves are not supplied and must be ordered.
Note: Route piping through the top or bottom of the InRow RD.
Note: All lines are Type L ACR copper tubing.
Note: Trap the vertical discharge line every 6 m (20 ft) to ensure proper oil return.
Note: Pipe size should change after the P-trap based on the recommended piping charts
provided with the installation manual. See the piping diagram created for your site.
Note: The maximum piping run is 61 m (200 ft) equivalent length. Size the piping pursuant
to accepted refrigeration practice.
Note: ACRD100 series only: any equivalent length greater than 46 m (150 ft) will result in a
5% decrease in capacity.
Warning: Do not install the air-cooled condenser below the InRow RD. The condenser
must be positioned above or at the same level as the InRow RD to ensure proper
function.
na2765a
InRow RD Gate valve
Strainer, 20 mesh
na2766a
InRow RD
42.6 (1.7)
38.2 (1.5)
109.7
(4.3)
(3.4)
87.6
154.6
143.4
(6.1)
(5.6)
na2813a
102 (4.0)
88.9 (3.5)
55.1 (2.2)
102.1
(4.0)
122.1
(4.4)
133.6
(4.8)
113
(5.3)
168.8
(6.6)
na2814a
Low voltage wiring input Hot discharge gas line (ACRD100 series)
Water/glycol out (ACRD200 series)
Liquid line (ACRD100 series)
Water/glycol in (ACRD200 series)
547 (21.54)
40 (1.58)
REAR—HOT AISLE 558 (21.97)
73 (2.86)
123 (4.84)
75 (2.95)
325 (12.78)
380 (14.94)
738 (29.04)
47 (1.85)
na2725a
FRONT—COLD AISLE
480 (18.90)
345 (13.58)
404 (15.91) REAR—HOT AISLE
115 (4.53)
184 (7.24)
199 (7.84)
420 (16.54)
796 (31.34)
893 (35.16)
57 (2.25)
na2726a
140 (5.51)
Connection Weight
Ambient Air Quantity Fan Unit Size Capacity
Sound Sound (inches)
SKU Temp Pressure * Pressure **
°C (°F) Hot MBH/1F
l/s (CFM) Qty. kW Gas Liquid Kg (Lbs) kW/1C TD
TD
163
ACCD75201 95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 1 3/8 8.8 4.6
(360)
10383 290
ACCD75202 105 (40) 70 65 2 4.4 1 5/8 1 5/8 14.6 7.7
(22000) (640)
14819 458
ACCD75203 115 (46) 72 68 3 6.6 2 1/8 2 1/8 (1010) 25.8 13.6
(31400)
163
ACCD75204 95 (35) 67 62 4955 (10500) 1 2.2 1 3/8 1 3/8 8.8 4.6
(360)
10383 290
ACCD75205 105 (40) 70 65 2 4.4 1 5/8 1 5/8 14.6 7.7
(22000) (640)
14819 458
ACCD75206 115 (46) 72 68 3 6.6 2 1/8 2 1/8 (1010) 25.8 13.6
(31400)
173
ACCD75207 95 (35) 54 51 5711 (12100) 1 2.2 42 22 17.6 9.3
(381)
11940 307
ACCD75208 105 (40) 57 54 2 4.4 42 28 27.1 14.3
(25300) (677)
11374 360
ACCD75209 115 (46) 57 55 2 4.4 54 35 48.2 25.4
(24100) (792)
* (dbA) at 10 ft and 100% Fan Speed
** (dbA) at 10 ft set area level, and Max Compressor Speed Selected Ambient Temp
Specifications given for conditions at sea level.
na2449a
ACCD75202 and ACCD75205
na2450a
na2452a
ACCD75208 and ACCD75209
na2453a
Condensers shown above have 16 mm (0.63 in) mounting holes on each of their lower legs.
ACCD75214
na2891a
ACCD75215
na2895a
na2893a
ACCD75217 and ACCD75219
na2896a
ACFC75210
na2890a
ACFC75255
na2899a
na2894a
ACFC75257
na2898a
Dimensions are shown in mm (in).
Available in one to three fan configurations, APC offers air-cooled condensers with a vertical air discharge pat-
tern. The RD500 series condensers utilize variable speed EC motor technology for improved sound and energy
performance. All other condensers utilize variable speed motors.
60 Hz specific features:
PART 2 — PRODUCT
2.01 STANDARD COMPONENTS
A. Cabinet Construction
1 . Front and rear exterior panels shall be 18 gauge perforated steel with 69.5% open free area,
and equipped with a keyed lock to provide a means of securing access to the internal
components of the unit.
a. ACRD100 and ACRD200 series only: Exterior panels shall be 18 gauge steel with
80 kg/m3 (5 lb/ft3) density foam insulation. Insulation complies with UL94-5VA ASTM
E84 flame spread and smoke developed rating of 25/50.
2 . The frame shall be constructed of 16 gauge formed steel welded for maximum strength. All
units shall provide maintenance from the front and rear, allowing units to be placed within a
row of racks.
Voltage kAIC
200-240V 50/60Hz 50
380-415V 50Hz 36
460-480V 60Hz 22
2 . Units shall include a main disconnect switch located on the electrical panel in order to
disconnect the power input.
3 . A condenser disconnect shall be field-supplied.
D. Microprocessor Controller
1 . Monitoring and configuration: The display interface shall allow monitoring and configuration
of the air conditioning unit through a menu-based control. Functions include status reporting,
set-up, and temperature set points. Four LEDs report the operational status of the connected air
conditioning unit.
2 . Controls: The microprocessor controller shall come equipped with control keys to allow the
user to navigate between menus, select items, and input alpha numeric information.
For information on how to obtain local customer support, contact the APC representative or other distributors
from whom you purchased your APC product.
© 2010 APC by Schneider Electric. APC, the APC logo, and InRow are owned by Schneider Electric
Industries S.A.S., American Power Conversion Corporation, or their affiliated companies. All other
trademarks are property of their respective owners.
990-3236D-001 6/2010