RISH Delta Energy-Demand

Download as pdf or txt
Download as pdf or txt
You are on page 1of 8

RISH Delta Energy/Demand

DIGITAL MULTI-FUNCTION TRANSDUCER

Application:
RISH Energy measures important electrical parameters in
3 phase 4 Wire and 3 phase 3 Wire Network & replaces the
multiple analog panel meters. It measures electrical parameters
like AC Voltage,AC Current, Frequency, Active, Reactive,
Apparent Power, Import & Export Energy & many more.

Salient Features:
• Fast & Easy Installation on panel with self clicking.
• True RMS measurement.
• MODBUS (Rs485) Communication (optional).
• Pulse/Limit Switch output (optional).
• 3 Line 4 Digits ultra bright LED Display (up to 9999).
• On site Programmable CT/PT Ratios.
• User selectable CT Secondary 1A/5A.
• User selectable PT Secondary from 100 VLL to 500 VLL. True RMS measurement
• User selectable 3ph3wire / 3ph4wire / single phase The instrument measures distorted waveform up to 15th
Network. Harmonic.
• Programmable Energy format & Energy rollover count
Energy Measurement (Import & Export):
• Wide auxillary Power Supply which can accept any input
between 40V – 300V AC/DC. Active Energy (kWh), Reactive Energy (kVArh), Apparent Energy
(VAh). Any of the parameters can be assigned to optional Pulse
• Storage of MIN / MAX values. output.
• Measurement & Display of RPM, Run hours, On hours,
No. of interruption. Programmable Energy format & Energy rollover count:
Products Features: Customer can assign the format for energy display on MODBUS
(RS485) in terms of W, kW or MW. Additional to this, customer
On site programmable PT/CT ratios: can also set a rollover count from 7 to 14 digits depending on the
energy format, after which the energy will roll back to zero.
It is possible to program primary of external potential
Transformer (PT), primary of external Current Transformer (CT)
on site via front panel keys by entering into Programming mode. Optional Pulse Output / Limit switch (Relay output):
The instrument can be programmed as Pulse output or Limit
User selectable CT Secondary 5A/1A switch.
The secondary of external Current Transformer (CT) can be
programmed on site to either 5A or 1A using front panel keys. Pulse Output : The optional pulse output is a potential free,
very fast acting relay contact which can be used to drive an
User selectable PT Secondary external mechanical counter for energy measurement.
The secondary of external Potential Transformer (PT) can be Limit Switch : The instrument will trip the relay if the
programmed on site from 100VLL to 500VLL using front panel programmed parameter exceeds the programmed Trip Limits.
keys.User can set the display in auto scrolling mode or fixed
screen mode using front panel keys. Optional MODBUS (RS485) Output:
The optional Modbus output enables the instrument to transmit
Low back depth: all the measured parameters over standard MODBUS (Rs485).
The instrument has very low back depth (behind the panel) of less
than 55 mm(Without output option). Configuration of Instrument via MODBUS :
The instrumentsetting can be configured locally via front panel
Four function keys: keys by entering into the programming mode or remotely via
Using the four function key, it is possible to go desired parameter MODBUS (Rs485).
screen instantly.. Note: The MODBUS communication parameters can only be set
locally via front panel keys in programming mode.
Demand Measurement
Measures & Displays Current Demand, kVA Demand, kW Import Storage of parameters possible
Demand, kW Export Demand. Any of the parameters can be The instrument stores minimum and maximum values for System
assigned to optional Limit switch. Voltage, System Current, Run Hour, ON Hour & number of
Interrupts. Every 60 sec stored values are updated.
Page 1 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

3 line 4 digits LED display: Enclosure Protection for dust and water:
Conforms to IP 50 (for front face) & IP 20 (for back)
Simultaneous display of 3 Parameters.
IP 65 (for front with seal) as per IEC60529.

RPM Measurement: The instrument display Rotation per EMC Compatibility


minutes for generator applications. Number of poles can be set Compliance to International standard IEC 61326.
on site depending upon application requirement. Interference Emission : IEC 61326-1 : 2005, Class A
Interference Immunity : IEC 61326-1 : 2005
Energy Count Storage: Electrostatic discharge : IEC 61000-4-2 -- 4kV/8kV
In case of power failure, the instrument memorizes the last contact/air. (ESD)
energy count. Every 1 min, the instrument updates the energy EM Field : IEC 61000-4-3 -- 10 V/m
counter in the non-volatile memory. (80 MHz to 1 GHz)
– 3 V/m (1.4 Ghz to 2 GHz)
-- 1 V/m (2 GHz to 2.7 GHz)
User selectable 3 phase 3Wire or 4Wire or Single phase
Burst : IEC 61000-4-4 -- 2 kV (5/50 ns, 5 kHz)
Network
Surge : IEC 61000-4-5 -- 1 kVLL / 2 kVLN.
User can program on site the network connection as either 3
Conducted RF : IEC 61000-4-5 -- 3 V (150 kHz to 80 MHz)
Phase 3 Wire or 4 Wire or single phase network using front panel
Rated Power Frequency
keys.
magnetic Field : IEC 61000-4-8 -- 30 A/m
Voltage dip : IEC 61000-4-11 -- 0% during 1 cycle.
In case of self powered Rish Delta only either 3 Phase 4 wire or
-- 40% during 10/12 cycles.
single phase network are available.
-- 70% during 25/30 cycles.
Short interruptions : IEC 61000-4-11 -- 0% during 25/30 cycles.
cycles. 25 cycles for 50 Hz test.
Onsite selection of Auto scroll / Fixed Screen 30 cycles for 60 Hz test.
User can set the display in auto scrolling mode or fixed screen
mode using front panel keys.

Technical Specifications:

Input Voltage:
Nominal input voltage (AC RMS) Phase –Neutral 290V L-N , Line-Line 500V L-L
Max continuous input voltage 120% of rated value
Nominal input voltage burden < 0.3 VA approx. per phase (For external auxiliary meter)
System PT secondary values 100VLL to 500VLL programmable on site.
System PT primary values 100VLL to 692kVLL programmable on site.

Input Current:
Nominal input current 5A / 1A AC RMS
System CT secondary values 1A & 5A programmable on site.
System CT primary values From 1A up to 9999A (for 1 or 5 Amp )
Max continuous input current 120% of rated value
Nominal input current burden < 0.2 VA approx. per phase

Auxiliary Supply:
External Aux 40 V – 300V AC-DC (± 5 % )

Self powered input voltage range from 80% to 100% of Rated value.
(Self powered meter is available only in 3Phase 4 Wire and Single Phase network.)
Auxiliary input is derived from Phase 1 (R phase)
Frequency range 45 to 65 Hz
VA burden < 4 VA Approx.

Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times at 10 second intervals
Current 20x rated value for 1 second, repeated 5 times at 5 min intervals
Page 2 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Technical Specifications:

Operating Measuring Ranges:


Voltage Range With External Aux 10… 120% of rated value
Voltage Range With Self Power 80… 120% of rated value
Current Range 10 … 120% of rated value
Frequency 45…65 Hz.
Power Factor 0.5 Lead ... 1 ... 0.5 Lag.

Reference conditions for Accuracy:


Reference temperature 23°C +/- 2°C
Input waveform Sinusoidal (distortion factor 0.005)
Input frequency 50 or 60 Hz ±2%
Auxiliary supply voltage Rated Value ±1%
Auxiliary supply frequency Rated Value ±1%
Voltage Range 20... 100% of Nominal Value.
Current Range 10... 100% of Nominal Value.
Power Cos phi / sin phi = 1 for Active / Reactive Power & Energy.
10... 100% of Nominal Current &
20... 100% of Nominal Voltage.
Power Factor / Phase Angle 40... 100% of Nominal Current &
20... 100% of Nominal Voltage.

Accuracy:
Voltage ±1.0% of Nominal Value.
Current ±1.0% of Nominal Value.
Frequency 0.5% of mid frequency
Active Power ±1% of Nominal Value.
Re-Active Power ±1% of Nominal Value.
Apparent Power ±1% of Nominal Value.
Active Energy ±1%
Reactive Energy ±1%
Apparent Energy ±1%
Power Factor 2 % of Unity
Phase angle 2 % of range

Measurement error is normally much less than error specified above.


Variation due to influence quantity is less than twice the error allowed for reference condition.

Limit Switch (Relay):


Switching Voltage & Current for Relay 240 VDC ,5 A (1NO+1NC)

Influence of Variations:
Temperature coefficient :
(for rated value range of use (0…50°C)) 0.025%/°C for Voltage
0.05%/°C for Current

Display update rate:


Response time to step input 1 sec approx.

Page 3 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Technical Specifications:

Applicable Standards:
EMC IEC 61326-1: 2005
Safety IEC 61010-1-2001 , Permanently connected use
IP for water & dust IEC60529

Safety:
Pollution degree: 2
Installation category: III
High Voltage Test 3.3 kV AC, 50Hz for 1 minute between Aux. and measuring inputs

Environmental:
Operating temperature 0 to +50°C
Storage temperature -25°C to +70°C
Relative humidity 0... 90% non condensing
Warm up time Minimum 3 minute
Shock 15g in 3 planes
Vibration 10... 55 Hz, 0.15mm amplitude

Enclosure:
Front IP 50.
Front with seal (Option) IP 65.
Back IP 20.

Dimensions and Weights:


Bezel size 96 mm x 96 mm DIN 43 718.
Panel cut-out 92 +0.8 mm x 92 + 0.8 mm.
Overall depth 55 mm.(without output option)
Panel Thickness 1 - 3 mm for self clicking,
1 – 6 mm for swivel screws.
Weight 320 gm. Approx.(with output option)

Pulsed Output Option:

Energy (can be programmed for different energy parameters simultaneously):


Relay contact (1NO+1NC)
Switching Voltage & current for Relay 240 VDC ,5 A

Default pulse rate divisor 1 per Wh (up to 3600W) , 1 per kWh (up to 3600kWh) , 1 per MWh (above 3600kW) ,
Other Pulse rate divisors (applicable only when Energy on RS485 is in W)
10 1 per 10 Wh (up to 3600W) , 1 per 10 kWh (up to 3600kWh) , 1 per 10 MWh (above 3600kW) ,
100 1 per 100 Wh (up to 3600W), 1 per 100 kWh (up to 3600kWh) , 1 per 100 MWh (above 3600kW) ,
1000 1 per 1000 Wh (up to 3600W) , 1 per 1000 kWh (up to 3600kWh) , 1 per 1000 MWh (above 3600kW) ,

Pulse Duration : 60 msec, 100 msec, 200 msec.


Above options are also applicable to Apparent and Reactive Energy.

Page 4 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Parameter measurement and Display:

S r No Parameter 3 Phase 4 Wire 3 Phase 3 Wire 1 Phase 2 Wire


1 System Volts
2. System Current
3. Volts R–N (Phase Voltage for Single phase)
4. Volts Y–N
5. Volts B–N
6. Volts R-Y
7. Volts Y–B
8. Volts B–R
9. Current R (Phase Current for Single phase)
10. Current Y
11. Current B
12. Frequency
13. System Active Power (kW)
14. Active Power R (Phase Power for Single phase) (kW)
15. Active Power Y (kW)
16. Active Power B (kW)
17. System Re-active Power (kVAr)
18. Re-active Power R (Phase Power for Single phase) (kVAr)
19. Re-active Power Y (kVAr)
20. Re-active Power B (kVAr)
21. System Apparent Power (kVA)
22. Apparent Power R (Phase Power for Single phase) (kVA)
23. Apparent Power Y (kVA)
24. Apparent Power B (kVA)
25. System Phase Angle
26. System Power Factor
27. Power Factor R
28. Power Factor Y
29. Power Factor B
30. Phase Angle R
31. Phase Angle Y
32. Phase Angle B
33. Active Energy Import (kWh)
34. Active Energy Export (kWh)
35. Reactive Energy Import (kVArh)
36. Reactive Energy Export (kVArh)
37. Apparent Energy (kVAh)
38. RPM
39. Max (System Voltage / System Current)
40. Min (System Voltage / System Current)
41. Hour Run
42. ON Hour
43. Number of auxiliary interrupt
- Available - Not available

Page 5 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Parameter measurement and Display:

S r No Parameter 3 Phase 4 Wire 3 Phase 3 Wire 1 Phase 2 Wire


44 Current Demand
45. kVA Demand
46 kW Demand Import
47. kW Demand Export
48. Max Current Demand
49. Max kVA Demand
50. Max kW Demand Import
51 Max kW Demand Export

- Available - Not available

Electrical Connections:

Self Powered Aux External Power ed Aux


2 5 8 11 1 3 4 6 7 9 13 14 2 5 8 11 1 3 4 6 7 9 13 14

3 Phase
L N
4 Wire NC + -
AUX
Unbalanced L1 L1
SUPPLY
Load L2 L2
L3 L3
N N

5 8 1 3 7 9 13 14
3 Phase
N
3 Wire + -
AUX
Unbalanced Not Applicable SUPPLY
Load
L2
L3

2 11 1 3 13 14 2 11 1 3 13 14

L N
NC + -
1 Phase AUX
SUPPLY
2 Wire L1 L1
L2 L2
L3 L3
N N

*Note: For Measurement of parameters, Voltage must be present between terminal 2 & 11 for single phase or 3 phase 4 wire
network and between terminal 2 & 5 or 2 & 8 for 3 phase 3 wire network.

Page 6 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Rear Connection
IL1 VL1 IL1’ IL2 VL2 IL2’ IL3 VL3 IL3’ N
1 2 3 4 5 6 7 8 9 11

IL1 VL1 IL1’ IL2 VL2 IL2’ IL3 VL3 IL3’ N


1 2 3 4 5 6 7 8 9 11
Multifunction Meter
MODEL : RISH DELTA Energy
INPUT :500VL-L, 5A/1A, 45-65Hz
AUX SUPPLY :40V-300V AC-DC , 3VA
SR NO : 11/02/3232
ORDER CODE : RISH DELTA Energy - EA -LS - R
+. AUX. -. RS485 LIMIT SW.
~. ~.
13 14 B A G COM NO NC

Installation:
Easy Clip in Installation on Panel.

Easy Clip - in
mounting

Swivel screw

Panel Thickness : 1 - 3 mm for self clicking,


1 – 6 mm for swivel screws. Optional Limit Switch pluggable module.

Page 7 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER

Dimension Details:

With optional MODBUS / Limit switch .

96 mm 55 mm 62 mm 92mm+0.8

Display Area

92mm+0.8
96 mm

4 mm 4 mm Panel Cutout
42 mm 42 mm

Ordering information Ordering Code


RISH Delta Energy

Auxiliary Supply
Self Aux* SA
External Aux
40 V – 300V AC/DC EA

Pulse / Limit switch (Relay) - Optional


With Pulse output (Limit switch) LS
Without Pulse output (Limit switch) Z

MODBUS (RS485) Output - Optional R


MODBUS option not used Z

Order Code Example:

RISH Delta Energy– EA – LS - R

RISH Delta Energy, external aux (40V – 300V AC/DC), with limit switch, with MODBUS output.

*NOTE: Self Auxiliary meter is available only in 3Phase 4 Wire and Single Phase network.
Auxiliary input is derived from Phase 1 (R phase).
In case of external auxiliary meter all three networks are available
(3Phase 4Wire / 3Phase 3Wire / Single Phase)

Page 8 of 8

Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com

You might also like