RISH Delta Energy-Demand
RISH Delta Energy-Demand
RISH Delta Energy-Demand
Application:
RISH Energy measures important electrical parameters in
3 phase 4 Wire and 3 phase 3 Wire Network & replaces the
multiple analog panel meters. It measures electrical parameters
like AC Voltage,AC Current, Frequency, Active, Reactive,
Apparent Power, Import & Export Energy & many more.
Salient Features:
• Fast & Easy Installation on panel with self clicking.
• True RMS measurement.
• MODBUS (Rs485) Communication (optional).
• Pulse/Limit Switch output (optional).
• 3 Line 4 Digits ultra bright LED Display (up to 9999).
• On site Programmable CT/PT Ratios.
• User selectable CT Secondary 1A/5A.
• User selectable PT Secondary from 100 VLL to 500 VLL. True RMS measurement
• User selectable 3ph3wire / 3ph4wire / single phase The instrument measures distorted waveform up to 15th
Network. Harmonic.
• Programmable Energy format & Energy rollover count
Energy Measurement (Import & Export):
• Wide auxillary Power Supply which can accept any input
between 40V – 300V AC/DC. Active Energy (kWh), Reactive Energy (kVArh), Apparent Energy
(VAh). Any of the parameters can be assigned to optional Pulse
• Storage of MIN / MAX values. output.
• Measurement & Display of RPM, Run hours, On hours,
No. of interruption. Programmable Energy format & Energy rollover count:
Products Features: Customer can assign the format for energy display on MODBUS
(RS485) in terms of W, kW or MW. Additional to this, customer
On site programmable PT/CT ratios: can also set a rollover count from 7 to 14 digits depending on the
energy format, after which the energy will roll back to zero.
It is possible to program primary of external potential
Transformer (PT), primary of external Current Transformer (CT)
on site via front panel keys by entering into Programming mode. Optional Pulse Output / Limit switch (Relay output):
The instrument can be programmed as Pulse output or Limit
User selectable CT Secondary 5A/1A switch.
The secondary of external Current Transformer (CT) can be
programmed on site to either 5A or 1A using front panel keys. Pulse Output : The optional pulse output is a potential free,
very fast acting relay contact which can be used to drive an
User selectable PT Secondary external mechanical counter for energy measurement.
The secondary of external Potential Transformer (PT) can be Limit Switch : The instrument will trip the relay if the
programmed on site from 100VLL to 500VLL using front panel programmed parameter exceeds the programmed Trip Limits.
keys.User can set the display in auto scrolling mode or fixed
screen mode using front panel keys. Optional MODBUS (RS485) Output:
The optional Modbus output enables the instrument to transmit
Low back depth: all the measured parameters over standard MODBUS (Rs485).
The instrument has very low back depth (behind the panel) of less
than 55 mm(Without output option). Configuration of Instrument via MODBUS :
The instrumentsetting can be configured locally via front panel
Four function keys: keys by entering into the programming mode or remotely via
Using the four function key, it is possible to go desired parameter MODBUS (Rs485).
screen instantly.. Note: The MODBUS communication parameters can only be set
locally via front panel keys in programming mode.
Demand Measurement
Measures & Displays Current Demand, kVA Demand, kW Import Storage of parameters possible
Demand, kW Export Demand. Any of the parameters can be The instrument stores minimum and maximum values for System
assigned to optional Limit switch. Voltage, System Current, Run Hour, ON Hour & number of
Interrupts. Every 60 sec stored values are updated.
Page 1 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
3 line 4 digits LED display: Enclosure Protection for dust and water:
Conforms to IP 50 (for front face) & IP 20 (for back)
Simultaneous display of 3 Parameters.
IP 65 (for front with seal) as per IEC60529.
Technical Specifications:
Input Voltage:
Nominal input voltage (AC RMS) Phase –Neutral 290V L-N , Line-Line 500V L-L
Max continuous input voltage 120% of rated value
Nominal input voltage burden < 0.3 VA approx. per phase (For external auxiliary meter)
System PT secondary values 100VLL to 500VLL programmable on site.
System PT primary values 100VLL to 692kVLL programmable on site.
Input Current:
Nominal input current 5A / 1A AC RMS
System CT secondary values 1A & 5A programmable on site.
System CT primary values From 1A up to 9999A (for 1 or 5 Amp )
Max continuous input current 120% of rated value
Nominal input current burden < 0.2 VA approx. per phase
Auxiliary Supply:
External Aux 40 V – 300V AC-DC (± 5 % )
Self powered input voltage range from 80% to 100% of Rated value.
(Self powered meter is available only in 3Phase 4 Wire and Single Phase network.)
Auxiliary input is derived from Phase 1 (R phase)
Frequency range 45 to 65 Hz
VA burden < 4 VA Approx.
Overload Withstand:
Voltage 2 x rated value for 1 second, repeated 10 times at 10 second intervals
Current 20x rated value for 1 second, repeated 5 times at 5 min intervals
Page 2 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Technical Specifications:
Accuracy:
Voltage ±1.0% of Nominal Value.
Current ±1.0% of Nominal Value.
Frequency 0.5% of mid frequency
Active Power ±1% of Nominal Value.
Re-Active Power ±1% of Nominal Value.
Apparent Power ±1% of Nominal Value.
Active Energy ±1%
Reactive Energy ±1%
Apparent Energy ±1%
Power Factor 2 % of Unity
Phase angle 2 % of range
Influence of Variations:
Temperature coefficient :
(for rated value range of use (0…50°C)) 0.025%/°C for Voltage
0.05%/°C for Current
Page 3 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Technical Specifications:
Applicable Standards:
EMC IEC 61326-1: 2005
Safety IEC 61010-1-2001 , Permanently connected use
IP for water & dust IEC60529
Safety:
Pollution degree: 2
Installation category: III
High Voltage Test 3.3 kV AC, 50Hz for 1 minute between Aux. and measuring inputs
Environmental:
Operating temperature 0 to +50°C
Storage temperature -25°C to +70°C
Relative humidity 0... 90% non condensing
Warm up time Minimum 3 minute
Shock 15g in 3 planes
Vibration 10... 55 Hz, 0.15mm amplitude
Enclosure:
Front IP 50.
Front with seal (Option) IP 65.
Back IP 20.
Default pulse rate divisor 1 per Wh (up to 3600W) , 1 per kWh (up to 3600kWh) , 1 per MWh (above 3600kW) ,
Other Pulse rate divisors (applicable only when Energy on RS485 is in W)
10 1 per 10 Wh (up to 3600W) , 1 per 10 kWh (up to 3600kWh) , 1 per 10 MWh (above 3600kW) ,
100 1 per 100 Wh (up to 3600W), 1 per 100 kWh (up to 3600kWh) , 1 per 100 MWh (above 3600kW) ,
1000 1 per 1000 Wh (up to 3600W) , 1 per 1000 kWh (up to 3600kWh) , 1 per 1000 MWh (above 3600kW) ,
Page 4 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Page 5 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Electrical Connections:
3 Phase
L N
4 Wire NC + -
AUX
Unbalanced L1 L1
SUPPLY
Load L2 L2
L3 L3
N N
5 8 1 3 7 9 13 14
3 Phase
N
3 Wire + -
AUX
Unbalanced Not Applicable SUPPLY
Load
L2
L3
2 11 1 3 13 14 2 11 1 3 13 14
L N
NC + -
1 Phase AUX
SUPPLY
2 Wire L1 L1
L2 L2
L3 L3
N N
*Note: For Measurement of parameters, Voltage must be present between terminal 2 & 11 for single phase or 3 phase 4 wire
network and between terminal 2 & 5 or 2 & 8 for 3 phase 3 wire network.
Page 6 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Rear Connection
IL1 VL1 IL1’ IL2 VL2 IL2’ IL3 VL3 IL3’ N
1 2 3 4 5 6 7 8 9 11
Installation:
Easy Clip in Installation on Panel.
Easy Clip - in
mounting
Swivel screw
Page 7 of 8
Electro-Meters
Technology for all your measurement needs... 900 Mckay Rd., unit 2, Pickering, Ontario L1W 3X8
Tel: 1-800-617-3413 Fax: 416-428-6086
email: [email protected]
www.electro-meters.com
RISH Delta Energy/Demand
DIGITAL MULTI-FUNCTION TRANSDUCER
Dimension Details:
96 mm 55 mm 62 mm 92mm+0.8
Display Area
92mm+0.8
96 mm
4 mm 4 mm Panel Cutout
42 mm 42 mm
Auxiliary Supply
Self Aux* SA
External Aux
40 V – 300V AC/DC EA
RISH Delta Energy, external aux (40V – 300V AC/DC), with limit switch, with MODBUS output.
*NOTE: Self Auxiliary meter is available only in 3Phase 4 Wire and Single Phase network.
Auxiliary input is derived from Phase 1 (R phase).
In case of external auxiliary meter all three networks are available
(3Phase 4Wire / 3Phase 3Wire / Single Phase)
Page 8 of 8