501/453/UNIV

Group II Cable Glands


Flameproof, Increased Safety, Dust Protection
n& 'T' 'G'
Restricted Breathing
'C'
Class - Zones - Divisions
Certified ATEX / IECEx / c CSA us

Application

ø 'B'
 Outdoor or indoor use.

'A'
'F'
 For use with single wire armour ‘W’, wire braid ‘X’, steel
tape armour ‘Z’, elastomer and plastic insulated cables.
 For particular use with Cables that exhibit ‘Cold Flow’
characteristics.
 See technical section for installation rules and regulations.
s.

CABLE GLAND SELECTION TABLE


Entry Thread Size ‘F’ Cable Acceptance Details Hexagon Dimensions
Size Ref. NPT * Inner Sheath ‘A’ Outer Sheath ‘B’ Armour / Braid ‘C’ 'G' Across Across
Metric Standard or
Min. Max. Min. Max. Orientation 1 Orientation 2 Flats Corners
Option
Os M20² ½" 3.5 8.1 5.5 12.0 0.8 / 1.25 0.0 / 0.8 61.6 24.0 26.5
O M20² ½" 6.5 11.4 9.5 16.0 0.8 / 1.25 0.0 / 0.8 61.6 24.0 26.5
A M20 ¾" or ½" 8.4 14.3 12.5 20.5 0.8 / 1.25 0.0 / 0.8 63.0 30.0 32.5
B M25 1" or ¾" 11.1 19.7 16.9 26.0 1.25 / 1.6 0.0 / 0.7 69.9 36.0 39.5
C M32 1¼" or 1" 17.6 26.5 22.0 33.0 1.6 / 2.0 0.0 / 0.7 73.2 46.0 50.5
C2 M40 1½" or 1¼" 23.1 32.5 28.0 41.0 1.6 / 2.0 0.0 / 0.7 77.9 55.0 60.6
D M50 2" or 1½" 28.9 44.4 / 42.3¹ 36.0 52.6 1.8 / 2.5 0.0 / 1.0 93.5 65.0 70.8
E M63 2½" or 2" 39.9 56.3 / 54.3¹ 46.0 65.3 1.8 / 2.5 0.0 / 1.0 94.0 80.0 88.0
F M75 3" or 2½" 50.5 68.2 / 65.3¹ 57.0 78.0 1.8 / 2.5 0.0 / 1.0 103.0 95.0 104.0
G M80 3½" 67.0 73.0 75.0 89.5 2.0 / 3.5 0.0 / 1.0 90.6 106.4 115.0
H M90 3½" 67.0 77.6 75.0 89.5 2.0 / 3.5 0.0 / 1.0 90.6 115.0 130.0
J M100 4" 75.0 91.6 88.0 104.5 2.5 / 4.0 0.0 / 1.0 90.6 127.0 142.0
'T' — Os - F size metric entry threads are 1.5mm pitch as standard, 15mm length of thread. For G size glands and above, a 2mm pitch is supplied as
standard, 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering.
G size and above are available in the 501/453/RAC design style.
All dimensions in millimetres (except * where dimensions are in inches).

¹ Smaller value is applicable when selecting reduced NPT entry option.


² Sizes Os and O are available with an M16 thread size. For O size with M16 thread, the maximum cable inner sheath diameter is 10.9mm

Technical Data Features


ATEX/IECEx  Provides armour clamping using one clamping arrangement
 Flameproof Exdb IIC Gb, Increased Safety Exeb IIC Gb, for all armour / braid types.
Dust Extb IIIC Db and ExnR IIC Gc II 2 / 3GD.  Provides a diaphragm seal on inner sheath of cable which will
 Certificate No’s: Baseefa06ATEX0057X, Baseefa09ATEX0233X not damage cables that exhibit ‘Cold Flow’ characteristics.
and IECEx BAS 06.0014X.  Provides an outer deluge seal to prevent moisture ingress to
 Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22. the cable armour / braid.
 Construction and Test Standards: IEC/EN 60079-0,  Provides a cable retention and low smoke and fume, zero
IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15 and halogen seal onto the cables outer sheath.
IEC/EN 60079-31.  Manufactured in Brass (standard), Nickel Plated Brass, 316
 Ingress Protection: IP66, IP67 and IP 68* (30 metres for 7 days) Stainless Steel or Aluminium.
to IEC/EN 60529 and NEMA 4X.  Brass NPT entries are nickel plated as standard.
Alternative Reversible Armour Clamping Rings (RAC)
 Deluge Protection to DTS01.
SELECTION TABLE
 Operating Temperature Range: -60°C to +80°C.
Steel Wire Armour / Braid / Tape
 Assembly Instruction Sheet: AI 300.
Alternative certification options available:

Size Ref.
Orientation 1 Orientation 2
* Additional installation procedures required. B 0.9 - 1.25 0.5 - 0.9
C 1.2 - 1.6 0.6 - 1.2
C2 1.2 - 1.6 0.6 - 1.2
c CSA us D 1.45 - 1.8 1.0 - 1.45
 Flameproof AExd IIC Gb, Increased Safety AExe IIC Gb and Dust E 1.45 - 1.8 1.0 - 1.45
AExtD Zone 21. F 1.45 - 1.8 1.0 - 1.45
 Explosion-proof Class 1 Division 2 Groups ABCD, Class II
Division 2 Groups EFG, Class III. Ordering Information
 Certificate No’s: CSA1015065 for Marine Shipboard Cable. Format for ordering is as follows: Alternative Clamping Ring (AR),
 Construction and Test Standards: UL 60079-0, UL 60079-1, UL add suffix AR to ordering information.
60079-7, ISA 60079-31, CSA 22.2 No: 60079-0, CSA 22.2 No: Cable Gland Type Size Thread Material (Optional)
60079-1, CSA 22.2 No: 60079-7, CSA 22.2 No: 60079-31, UL 2225 501/453/UNIV C M32 Brass AR
501/453/UNIV C 1 ¼" NPT Brass AR

Connection Solutions
81
UPD 260318 www.ehawke.com