SPECIFICATION DATA
Features
Memorized time off
Cycle Per Hour (CPH)
Random startup
LCD display with simple user interface
Room temperature or setpoint temperature display
selectable
Manual or automatic fan speed selectable
Temperature units in either °C or °F
User setting can be stored with power loss
Freeze protection available
Four keypad lock options
Heating and cooling setpoint limitation
Flush mount on standard 86 wall mounting box
General Specifications
Power supply 220(+10%,-15%)VAC, 50Hz
The TF228WN digital thermostat is designed for 3-speed fan
and valve control in a fan coil system, including: Control PI, On/off output
2-pipe cool only/heat only/manual changeover
Ventilation mode Accuracy ±1°C at 21°C
Manual or automatic 3-speed fan control Rating capacity 3A for fan load,
Water valve control
2A for zone valve
Besides the basic controls, TF228WN featuring CPH (Cycle Protection class IP20
Per Hour) better maintains the room temperature to the set-
point and memorized time off function can automatically Set point range 10 ~ 32°C
turn off the thermostat to save energy. Display range 0 ~ 37°C
In addition, Honeywell Random start-up function would help Ambient operating limits 0~ +49°C
to maintain power grid stability. Ambient storage limits -30 ~ +49°C
Humidity limits 5~90% RH, non-condensing
1 ECC-CDS-CT01-14A-E01-EN
Table 1. Model Selection
COOL
2℃
Fan Speed is medium or off
1℃
LCD Display Fan Speed is low or off
Setpoint
Fan Speed is low or off
-1℃
HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off
Temperature Display
The displayed temperature can be set to room temperature or
setpoint. The setting can be changed during ISU (Installation
Set Up) process.
ECC-CDS-CT01-14A-E01-EN 2
Memorized Time 0ff
The time off feature will automatically turn off the thermostat Operating Mode
after a selectable amount of time. To change the time setting,
press and hold the power button for more than 3 seconds and Comfort Mode
press “up” and “down” button to change the value when the In comfort mode, the setpoint can be changed by pressing up
thermostat is working . and down button. Applications include cool only, heat only and
NOTE: The setting range is from 0 to 12 hours. The step is manual heat/cool changeover.
1 hour and the default value is 0.
Ventilation Mode
Press mode button to enter “ventilation” mode. In “ventilation”
mode, no output for valve while the fan will operate at selected
Backlight fan speed.
To turn on the backlight, press any key. The backlight will
timeout 8 seconds after the last key is pressed. When in ISU
and Installation test mode, the backlight will timeout 60 sec-
onds after the last key is pressed.
Keypad Lockout
Keypad lockout can be set in ISU and the default status is “all
keys available”. Keypad lock can be optioned to “mode button
locked”, “Fan and mode buttons locked”, “all buttons (except
power button) locked” and “all buttons locked”.
Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as disabled (default) or
enabled in the ISU. In freeze protection mode (only in heating
applications), when thermostat is off and the temperature is
below 6 ℃, the thermostat will activate heating mode until the
temperature rises to 8℃.
3 ECC-CDS-CT01-14A-E01-EN
Wiring Trouble Shooting Tips
If Then...
Item Terminal Description The system turns Make sure the memorized time off
off automatically value isn’t set to “0”.
1 L 220VAC live wire
ECC-CDS-CT01-14A-E01-EN 4