4 TF228WN

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

TF228WN Digital Thermostat

220 VAC, Fan Coil Control

SPECIFICATION DATA

Features
 Memorized time off
 Cycle Per Hour (CPH)
 Random startup
 LCD display with simple user interface
 Room temperature or setpoint temperature display
selectable
 Manual or automatic fan speed selectable
 Temperature units in either °C or °F
 User setting can be stored with power loss
 Freeze protection available
 Four keypad lock options
 Heating and cooling setpoint limitation
 Flush mount on standard 86 wall mounting box

General Specifications
Power supply 220(+10%,-15%)VAC, 50Hz
The TF228WN digital thermostat is designed for 3-speed fan
and valve control in a fan coil system, including: Control PI, On/off output
 2-pipe cool only/heat only/manual changeover
 Ventilation mode Accuracy ±1°C at 21°C
 Manual or automatic 3-speed fan control Rating capacity 3A for fan load,
 Water valve control
2A for zone valve
Besides the basic controls, TF228WN featuring CPH (Cycle Protection class IP20
Per Hour) better maintains the room temperature to the set-
point and memorized time off function can automatically Set point range 10 ~ 32°C
turn off the thermostat to save energy. Display range 0 ~ 37°C
In addition, Honeywell Random start-up function would help Ambient operating limits 0~ +49°C
to maintain power grid stability. Ambient storage limits -30 ~ +49°C
Humidity limits 5~90% RH, non-condensing

1 ECC-CDS-CT01-14A-E01-EN
Table 1. Model Selection

Model Number Backlight Application Power supply Ventilation Automatic Packing


Mode Fan
TF228WN White 2-pipe FCU 220 Vac, 50Hz Y Y bulk packing

TF228WN/U White 2-pipe FCU 220 Vac, 50Hz Y Y unit packing

Product Design Function


Thermostat Appearance Valve Control
Thermostat measures the room temperature via integrated
sensor and maintains the setpoint by delivering on/off valve
control command outputs.
The fan setting can be selected as manual or automatic 3-
speed operation. When in “manual” mode, the fan is switched
to the selected speed via control output FH (high), FM
(Medium) , FL (Low).
While in “automatic“ mode, fan speed depends on the differ-
ence between room temperature and setpoint. When room
temperature reaches the setpoint, the valve will be closed, and
the fan will be closed in the meanwhile.

Fan Speed is high or off


Difference between RT and SP

COOL
2℃
Fan Speed is medium or off
1℃
LCD Display Fan Speed is low or off
Setpoint
Fan Speed is low or off
-1℃

HEAT
Fan Speed is medium or off
-2℃
Fan Speed is high or off

Fig. 1. Fan Speed Ramping Control Algorithm

Temperature Display
The displayed temperature can be set to room temperature or
setpoint. The setting can be changed during ISU (Installation
Set Up) process.

Cycle Per Hour (CPH)


In order to achieve more accurate temperature control, the
CPH function enables the thermostat to open the valve several
times per hour as the room temperature gets close to the se-
point.
The value can be changed in the ISU, but the default values
are 4 for heating and 3 for cooling.

ECC-CDS-CT01-14A-E01-EN 2
Memorized Time 0ff
The time off feature will automatically turn off the thermostat Operating Mode
after a selectable amount of time. To change the time setting,
press and hold the power button for more than 3 seconds and Comfort Mode
press “up” and “down” button to change the value when the In comfort mode, the setpoint can be changed by pressing up
thermostat is working . and down button. Applications include cool only, heat only and
NOTE: The setting range is from 0 to 12 hours. The step is manual heat/cool changeover.
1 hour and the default value is 0.

Ventilation Mode
Press mode button to enter “ventilation” mode. In “ventilation”
mode, no output for valve while the fan will operate at selected
Backlight fan speed.
To turn on the backlight, press any key. The backlight will
timeout 8 seconds after the last key is pressed. When in ISU
and Installation test mode, the backlight will timeout 60 sec-
onds after the last key is pressed.

Keypad Lockout
Keypad lockout can be set in ISU and the default status is “all
keys available”. Keypad lock can be optioned to “mode button
locked”, “Fan and mode buttons locked”, “all buttons (except
power button) locked” and “all buttons locked”.

Dimensions (mm)
Freeze Protection Mode
Freeze protection can be selected as disabled (default) or
enabled in the ISU. In freeze protection mode (only in heating
applications), when thermostat is off and the temperature is
below 6 ℃, the thermostat will activate heating mode until the
temperature rises to 8℃.

3 ECC-CDS-CT01-14A-E01-EN
Wiring Trouble Shooting Tips
If Then...

Heating system  Set the mode to heating by press-


does not respond ing the mode button.
 Make sure the temperature is set
above the room temperature.
 Make sure “heat on” icon shows on
the display.
 Wait 5 minutes for the system to
respond.

Cooling system  Set the mode to cooling by press-


Fig. 2. Honeywell VC4013/VN4013/VS4016 Wiring does not respond ing the mode button.
 Make sure the temperature is set
below the room temperature.
 Make sure “cool on” icon shows on
the display.
 Wait 5 minutes for the system to
respond.

The fan doesn’t  Make sure fan mode isn’t set to


work auto.
 Check heating or cooling system
works well.

The mode or fan  Make sure keypad is unlocked.


button doesn’t  Check that thermostat is on.
work
Fig. 3. Honeywell VC6013/VN6013 Wiring
The up or down  Make sure keypad is unlocked.
button doesn’t  Make sure the system doesn’t
work
Terminal Designations 
work in ventilation mode.
Check that thermostat is on.

Item Terminal Description The system turns  Make sure the memorized time off
off automatically value isn’t set to “0”.
1 L 220VAC live wire

2 N 220VAC neutral wire

3 vC Heating / Cooling valve close


4 vO Heating / Cooling valve open

5 FH High speed fan

6 FM Medium speed fan


7 FL Low speed fan