Pomona, CA, May 24 & 25, 2016

Tertiary Winding Design in


wye-wye Connected Transformers

Restricted © Siemens Energy 2013 All rights reserved.


Scope of Presentation > Tertiary vs. Stabilizing
Winding?

• Tertiary vs. Stabilizing Winding?

• Need for Stabilizing Windings

• Need for Tertiary Windings

• Some options – no tertiary?

• Concern – protected tertiary?

Page 2 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Autotransformer Windings

Inter-connection (Auto) Transformers 525kV


HV MV

Delta connected TV
winding provided for
local loads and the 13.8kV 230kV
suppression of
harmonics.

MV Bushings
HV Bushings HV & MV windings are “power
TV Bushings windings”, delivering converted
power to the network. Does
delta-connected tertiary provide
a power function?
Page 3 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Is it a Tertiary or a Stabilizing Winding?

• Stabilizing Winding

• “Delta-connected, aux wdg” solely to stabilize wye-wye


• Not intended for connected loads, reactors, house pwr
• Buried -or- temp external connections, only for testing

• Tertiary Winding

• Similar to stabilizing (delta-connected, aux)


• Can be used for connected loads, reactors, house power
• Winding connections brought out (bushings)
• Thermal, loading & impedance considerations
• Exposure to external bus faults – short circuit problematic

Page 4 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Shunt Reactors
MV connection via Tertiary

Reactor Application: Var supply on the cheap


Page 5 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Reactor Type -
Oil-filled (direct connect) or Dry-type (MV tertiary)

Page 6 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
When tertiary windings used >
Transformer cost (& complexity) increased

• Added material - tertiary winding, leads, bushings


• Increase of winding diameter & weight
Also, winding losses will increase
• Increase in tank dimension, core weight & oil volume

Are Tertiary Windings still needed?

Page 7 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Reasons for using Stabilizing Windings

1. Transformer stabilization in case of wye unbalance


(neutral loading)
2. Influencing zero sequence impedance of transformer and
of the system (relaying considerations)
3. Compensation of transformer’s third harmonics (legacy
core steel vs. modern low-loss designs)

Page 8 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Reasons for using Tertiary Windings

1. Auxiliary power supply and/or creating access for reactive


power compensation
2. Assure the interchangeability of transformers

Page 9 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Stabilization of wye-wye transformer operation
in case of starpoint loading

Starpoints are loaded during unbalanced faults, either continuously or


short time

Page 10 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Stabilization of wye-wye transformer operation
in case of starpoint loading

Sum of ampere-turns per


transformer limb is no
longer zero.
Uncompensated Ampere-
Winding
turns have same phase &
magnitude in all three
Tank limbs.

Zero Seq. Flux Core Zero-sequence magnetic


field & flux in core limbs
Fig.3 Zero Sequence flux in a 3-limb core
(has same orientation in
all three limbs).

Page 11 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Stabilization of wye-wye transformer operation
in case of starpoint loading

Symmetrical Zero Sequence Changed voltages


voltage Voltage

Unbalanced flux induces zero sequence voltages in transformer


windings
Level of transferred voltage depends on networks’ grounding
condition.
High Zo may cause relaying trips of healthy system (i.e. HV gets
activated during unbalanced fault on LV side of the transformer).
Page 12 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Stabilization of wye-wye transformer operation
in case of starpoint loading

Zero Zero
sequence sequence
Winding
flux flux
Winding Core Core
Fig.5 Zero sequence flux in case of 5-limb and sigle phase
transformers

Flux’s return path is most favorable in case of 5-limb, single phase and
shell form cores. Zero sequence currents will produce a high flux.
Therefore induced zero sequence voltage will be much higher than
for 3-limb transformers.

Page 13 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Unbalanced fault w/help of delta-connected
stabilizing winding

Fig.6 Transformer with tertiary winding


The sum of the ampere-turns is zero on each limb

Sum of ampere-turns is zero on each limb.


Zero sequence flux is deleted by stabilizing winding.
Induced zero sequence voltages are minimized. Additional eddy loss
does not occur.

Page 14 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
1. Stabilization of the transformer operation in
case of starpoint loading

Primary Secondary
Winding Winding

Fig.7 The sum of the ampere-turns is zero on each limb

A stabilizing winding may not be required if neutral loop for zero


sequence current is closed & zero sequence impedances of the
supplying network are low enough.
The degree of compensation without stabilization depends on total zero
sequence impedance in the primary system.

Page 15 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
2. Influence of stabilizing winding on zero
sequence impedance (relaying concerns)

Transformer Number of limbs Zo/Z1


connection
Yy(d) 1, 3, 5 1 .. 2.4
Yy 1 10 .. 100
3 3 .. 15
5 10 .. 100

Page 16 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
2. Stabilizing winding Influence on the zero
sequence impedance

Transformers with solidly grounded neutrals


•Ground current involves zero sequence during phase-ground faults.
•Io must have minimum magnitude & predictable with good accuracy.
•When stabilizing winding used, transformer’s zero sequence
impedance will be linear and of low value.
•Wye-wye connections w/o stabilization can used > if a multiple path to
ground is available via station’s other transformer’s neutrals
•Ideally, transformer’s contribution to system’s zero sequence must be
analyzed before deciding if a stabilizing winding is needed.

Page 17 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
3. Compensation of 3rd Order Internal Harmonics

Harmonics are generated in transformer cores due to nonliniarity of


core’s magnetizing curve.

3rd order voltage harmonic cannot flow between phases.

Page 18 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
3. Compensation of 3rd Order Harmonics

Magnetizing current is nowadays in the range of 0.03 to 0.15% of the


rated current.
With modern reduction of no load currents, influence of third harmonics
generated by transformers has less relevance.

Page 19 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Is tertiary winding needed for auxiliary power
supply or reactive power compensation?

• A separate source for auxiliary power may be more economical.


• In the case of a brought-out tertiary, winding must be designed for
rated load (thermal) and especially for withstanding short circuit
currents which flow during bus faults.

If sized for thermal load only, tertiary would be massively under-sized!!


ANSI C57 requires windings to be self-protecting >
Mechanical over-sizing of tertiary required
1/3 MVA rating?
Available system impedance & calc?
Tertiary reactors?

Page 20 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Concern for excessive fault currents in tertiary
windings

Air-core,
Tertiary reactors?
oil-immersed
Air-core,
CL Reactoroil-immersed current-limiting
reactor (typical)
(typical)
For brought-out tertiary application
for tertiary to high short-circuits.
w/exposure

Page 21 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Additional Risks when Tertiary Windings are used

• Transferred lightning and switching voltages


• Capacitively transferred 60 Hz voltages during unbalanced faults
It is recommended, that the three terminals of the winding are not
left floating. Capacitors or surge arresters shall be used.
• Very high 3-phase short circuit current w/tertiary bushings.

If only stabilizing function is needed, buried tertiary is recommended.

In general there is no additional benefit for testing, so 3 stabilizing


bushings not needed.

Page 22 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Considerations for the use of Tertiary Windings

1. Stabilization of the transformer operation in case of starpoint loading


• Can unbalanced loading occur continuously?
• Is the amount of load unbalance significant?
• What is the effect of the transferred zero sequence voltage?
2. Influencing the zero sequence impedance of the transformer and of the system
• What is the required zero sequence impedance of the system?
• What are the requirements for the protection design?
3. Compensation of third harmonics
• Is there any negative impact of the 3rd harmonic current to other equipment?
4. Auxiliary power supply and/or creating access for reactive power compensation
• Is it worth to invest so much for auxiliary power supply?
• Tertiary access for compensation equipment may be ineffective.
5. Assure the interchangeability of transformers
• Do all tertiaries need to be equivalent?

Page 23 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.
Siemens US – Transformers Contact

James McIver
Principal Application Engineer
E T TR US
6860 Bermuda Road, STE 100
Las Vegas NV 89119
USA

Mobile: (702) 241-0157


E-mail:
[email protected]

Siemens.com/transformers

Page 24 AEP_Tertiaries_ McIver Restricted © Siemens Energy 2013 All rights reserved.

You might also like