Boiler Feed and Pump Sizing - C-B and Grundfos July 2016
Boiler Feed and Pump Sizing - C-B and Grundfos July 2016
Boiler Feed and Pump Sizing - C-B and Grundfos July 2016
2
TYPICAL STEAM SYSTEM
HP Steam LP Steam
Strainer PRV
T T
Trap Trap
Motive T T T
Force Trap Trap Trap
H P Cond Return LP Condensate Return
Vent
Legend
DA
D ATank
Tank Steam
Cond Rcvr Cond
& Pump Flash
Boiler Feed Pump Vapor
3
3
BOILER SIZES AND
FEED PUMP SIZES
Typical
Typical
Boiler Max. Feed
Boiler HP Typical Feed Max. Feed Where
Pressure Pump
Range Pump Type Pump Used?
Range Flow
Head
Range
General
Vertical industry;
inline institutional;
100 to 150 to 500 10 to 125
multistage; 1250 feet universities;
1200 psi gpm
regenerative some
turbines commercial
buildings
4
FIRETUBE
Watertube (IWT)
Integral burner
Gun burner
5
HORIZONTAL
FIRETUBE BOILERS
The Dryback
Baffles
Tubesheet
4
2
Refractory Filled Door 1
Two (2) Tubesheets
6
WATERTUBE OR IWT
7
THE WATERTUBE
BOILER Outlet nozzle location Upper Steam Drum
• Opposite of Firetube
• Water in the Tubes Furnace
• Natural and Forced Circulation
• Large Furnace
• Upper & Lower Drums or
• Headers
8
FLUE GAS SEALING
9
CONDENSATE IS
LIQUID GOLD!
A finite resource
10
TYPICAL
STEAM SYSTEM
LP Steam
HP Steam
Strainer PRV
T T
Trap Trap
Motive T T T
Force Trap Trap Trap
H P Cond Return LP Condensate Return
Legend
DA
D ATank
Tank Steam
Cond
Flash
Condensate tank
Boiler Feed Pump Vapor
& Pump system
11
CONDENSATE
RETURN PUMPS
12
FLASH STEAM
150 psig
366 F HP Steam LP Steam 15 psig
Strainer PRV
250 F
T T
Trap Trap
T T T
Motive Trap Trap Trap
Force H P Condensate Return
Flash
Tank
Feed Tank
D A Tank
or DA Low pressure
condensate
Cond. Pump line
Boiler Feed Pump
13
Flash Tank Flash Tank w/Economizer
14
HOT CONDENSATE
RETURNED
Steam
diffusing tube
15
Vent
H.P. Return
PRV
Steam
Exhaust Or
Flash Steam
Cold Make-Up
Level control Water
Make-Up Valve
Overflow
To Boiler Feed Drainer
Boiler Water Pump(s)
16
SPRAY DEAERATOR
Spray cone
17
TRAY DEAERATOR
Trays
steam
18
PACKED COLUMN DA
19
BOILER FEED
WATER TANKS
Spray DA Tray DA Column DA
Vented
Receiver
20
HP CONDENSATE
RECOVERY
150 psig
366 F LP Steam
HP Steam 15 psig
Strainer PRV
250 F
T T
Trap Trap
Cond.
D A Tank Pump
Boiler Feed Pump
Feed Tank or DA
21
HIGH PRESSURE
CONDENSATE
RECEIVER
22
BOILER FEED WATER
TANK OPTIONS
Spray DA Tray DA Column DA
HPCR Vented
Receiver
23
FEED WATER SYSTEMS
For multiple boiler Installations
24
METHOD 1 –
Direct feed for multiple boilers
Deaerator
Boiler A
Controlle
r Boiler A
4-20mA signal
directly to
Grundfos E-
pump instead of
control valve
Boiler B
Controlle
r Boiler B
4-20mA signal
directly to
Grundfos E-
pump instead of
control valve
25
METHOD 2 –
Booster sets for multiple boilers
Deaerator Pressure sensor
Bypass
Multiple
pump
controller
26
STEAM BOILER
PUMP APPLICATIONS
AND TYPES
Boiler feed pumps
Collection tank pumps
Water treatment pumps
Condensate return pumps
Deaerator tank recycle pumps
Deaerator vacuum pumps (vacuum
deaerator tanks only)
Economizer pumps
27
SIZING COMPLEXITY
FOR BOILER FEED PUMPS
28
BASE FLOW
RATE CALCULATION
29
ADD FOR CONTINUOUS
BOILER BLOWDOWN FLOW
30
ADD FOR BYPASS
RECIRCULATION FLOW
Certain feed system control modes
require the use of a bypass line
back to the source tank – such as
back to the deaerator tank
Is orifice flow
Method Pump Speed
Name Duty by-pass line
# Type
required?
1 On/Off control and fixed speed pumps Fixed Intermittent No
2 Feed control valve and fixed speed pumps Fixed Continuous Yes
3 Feed control valve and variable speed pumps Variable Continuous Yes
4 Variable speed pumps only (no control valve) Variable Continuous No
31
RECIRCULATION
FLOW
32
CALCULATING REQUIRED
FEED PUMP HEAD
Elevation of
DA tank
Elevation
of boiler
33
FEED VALVE IMPACTS
PUMPING HEAD CALCULATION
34
CALCULATING THE HEAD
FOR THE FEED PUMP
1) At the duty point flow rate:
Head in feet = Boiler operating pressure X 2.31 X 1.03 ÷ Liquid Specific Gravity
Example: Head = 130 psi X 2.31 X 1.03 ÷ 0.953 = 324 feet
35
NPSH –
FORMULA FOR CALCULATION
To avoid cavitation, NPSHa must be greater than NPSHr
Add two to four feet of safety factor to the NPSHr stated on the curve
NPSHa is calculated:
36
NPSH AND ELEVATION
Deaerator
tank
Difference in elevation
37
NPSH AND SUCTION
LINE CONSIDERATIONS
38
Check list for boiler feed pump selection
Step Action
1 Det ermine cont rol met hod t o be used
5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
8 Add for all discharge piping syst em head component s (including feed valve if required)
10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
39
BOILER FEED PUMPS:
USEFUL FORMULAS
40
SPECIFICATION
FOR EXERCISE
a) Control Method: Continuous duty fixed speed pump with bypass line and feed valve
b) Boiler maximum capacity = 250 HP
c) Boiler safety valve setting = 125 psig
d) Pressure safety factor = 3% above boiler’s safety valve setting
e) Boiler operating pressure = 100 psig
f) Continuous Boiler Blowdown flow - Required
g) Bypass recirculation flow – Required
h) Altitude – Sea level
i) Pressure in deaerator tank above atmospheric pressure = 5 psi (14.7 + 5 = 19.7 psi absolute)
j) Height of deaerator tank minimum water level above pump’s first impeller = 10 feet
k) Friction line loss through suction piping = .5 foot
l) Friction loss through suction side fittings = .5 foot
m) Friction loss through suction side valves = None
n) Friction loss through suction side strainer = 1 feet
o) Friction loss through discharge piping = 1 foot
p) Friction loss through discharge side fittings = 1 foot
q) Pressure drop across feed valve – 15 psi
r) Elevation of boiler maximum water level above pump’s discharge port = 5 feet
s) Liquid Specific Gravity = 0.953
t) Temperature of water in deaerator tank = 227 degrees F
u) Vapor pressure in deaerator tank = 19.7 psi
v) Pump materials all 316 stainless steel to resist treatment chemicals
w) Mechanical seal to be silicon carbide/silicon carbide/EPDM to withstand liquid temperature
41
CONTROL METHOD:
Recirc line
42
STEP 1 –
Determine control method
Feed valve controlled system with a continuous duty fixed speed pump has been specified.
Step Action
5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
8 Add for all discharge piping syst em head component s (including feed valve if required)
10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
43
STEP 2 –
Calculate the BASE feed pump flow rate
Therefore:
44
STEP 3 –
Continuous Boiler Blowdown Flow
Determination:
2. We will on next slide need to add for bypass flow, which can add
10 to 20 percent to the BASE flow rate
45
STEP 4 –
Add for by-pass flow
• Control is via feed valve with fixed speed pump and for continuous duty
• A bypass will be required
46
STEP 5 –
Calculate total flow required
• BASE flow = 20 gpm
• Blowdown flow = 3 gpm
• Recirculation flow = 5 gpm
• Total flow required = 28 gpm
Step Action
X 5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
8 Add for all discharge piping syst em head component s (including feed valve if required)
10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
47
STEP 6 –
Calculate BASE pumping head
Formula: BASE head in feet = Boiler operating pressure X 2.31 X 1.03 ÷ Specific
Gravity
48
STEP 7 –
Add for suction piping system head components
From specification:
Absolute pressure on deaerator tank = 19.7 psi X 2.31 = - 46 feet
Water elevation above first impeller = - 10 feet
Friction loss through suction piping = + .5 feet
Friction loss through suction fittings = + .5 feet
Friction loss through suction side valves and strainer = + 1 feet
Total = - 54 feet
49
STEP 8 –
Add for discharge piping system head components
From specification:
Friction loss through discharge piping = + 1 foot
Friction loss through discharge fittings = + 1 foot
Friction loss through feed valve is 15 psi X 2.31 = + 35 feet
Elevation of boiler maximum water level above pump = + 5 feet
Total = + 42 feet
50
STEP 9 –
Sum of all head components
51
STEP 10 –
Pressure safety valve considerations
At shutoff head (dead head):
Head in feet = Pressure relief valve setting X 2.31 X 1.03 ÷ Liquid Specific Gravity
Example: Head = 125 psi X 2.31 X 1.03 ÷ 0.953 = 312 feet
Step Action
X 5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
X 8 Add for all discharge piping syst em head component s (including feed valve if required)
X 10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
52
STEP 11 –
Determine deaerator tank water temperature
53
STEP 12 –
NPSHa calculation
NPSHa equation:
54
STEP 13 –
Preliminary pump selection
Conditions of Service:
Flow = 28 gpm
Head = 238 Feet
Does this 10
stage pump
pump meet the
required flow
and head
conditions of
service?
YES
55
STEP 14 –
Pressure safety valve considerations
56
STEP 15 –
Check NPSHa vs NPSHr
Conditions of Service:
Flow = 28gpm
Head = 238 Feet
NPSHa = 8 Feet
YES
57
STEP 15 –
NPSH - Continued
Conditions of Service: Flow = 28 gpm Head = 238 Feet NPSHa = 8 Feet
The NPSHa is equal to or exceeds the NPSHr of 8 feet
Step Action
X 5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
X 8 Add for all discharge piping syst em head component s (including feed valve if required)
X 10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
X 14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
58
STEP 16 –
Check material compatibility
59
STEP 17 –
Final pump selection
Pump meets all specification requirements
Step Action
X 5 Sum of base flow, by-pass flow, and Blowdown flow is t he t ot al flow required
X 8 Add for all discharge piping syst em head component s (including feed valve if required)
X 10 Calculat e head at boiler safet y vavle set t ing plus t hree percent
X 14 Assure t hat shut off head equals or exceeds t hree percent above safet y valve set t ing
60
61
SUMMARY
• Steam condensate is a very valuable commodity which needs to saved and used as much as possible.
• Most commonly used boilers for process are industrial firetubes and watertube boilers, IWT,s.
• High pressure condensate flash steam can be used for various purposes such as unit heaters or the
DA
• Condensate can be returned to vented receivers or pressurized deaerators (Spray, Tray & Column)
• Sometimes high pressure condensate receivers are employed. Save considerable losses.
• Boiler feed pump selection involves 17 decision points which need to be carefully considered.
• Calculating the pump’s base flow rate differs when the pump operates continuously (15% safety factor)
or on/off (50% safety factor)
• Sometimes the base flow rate needs to include for continuous pump re-circulation and maybe for
continuous blow down
• Total Dynamic Head (TDH) is a that pressure the pump must overcome to get water in the boiler, and
includes the positive pressure at the pump’s inlet after suction pipe losses, and the piping losses
through the discharge piping before overcoming the boiler’s operating pressure.
• Net Positive Suction Head (NPSH) is the pressure required at the pump’s suction to mitigate
cavitation.
• NPSHA is the NPSH available after all the friction losses on the suction side have been determined in
light of the pump’s minimum and maximum flow rates.
• The seal selection for the pump is very important and can vary based on the boiler’s operating
pressure/temperature, chemicals in the feed water, etc.
62
QUESTIONS?
Gregg Achtenhagen
[email protected]
Jim Swetye
[email protected]
Over 25,000 Grundfos parts are available through your local Cleaver-Brooks Representative.
Visit cleaverbrooks.com/reps for all boiler sales and service.
63