Zigzag Transformer - Wikipedia, The Free Encyclopedia

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Zigzag transformer - Wikipedia, the free encyclopedia http://en.wikipedia.

org/wiki/Zigzag_transformer

From Wikipedia, the free encyclopedia

A zigzag transformer is a special-purpose transformer with a zigzag or "interconnected star" winding


connection, such that each output is the vector sum of two phases offset by 120°.[1] Its applications are for
the creation of a missing neutral connection from an ungrounded 3-phase system to permit the grounding of
that neutral to an earth reference point and also harmonic mitigation, as it can suppress triplet (3rd, 9th, 15th,
21st, etc.) harmonic currents,[2] to supply 3-phase power as an autotransformer (serving as the primary and
secondary with no isolated circuits),[3] and to supply non-standard, phase-shifted, 3-phase power.[4]

Nine-winding, three-phase transformers typically have 3 primaries and 6


identical secondary windings, which can be used in zigzag winding connection
as pictured.[5] As with the conventional delta or wye winding configuration
three-phase transformer, a standard, stand-alone transformer containing only six
windings on three cores can also be used in zigzag winding connection, such
9-winding zigzag
transformer sometimes being referred to as a zigzag bank.[4] In all cases, six or
transformer
nine winding, the first coil on each zigzag winding core is connected
contrariwise to the second coil on the next core. The second coils are
then all tied together to form the neutral, and the phases are
connected to the primary coils. Each phase, therefore, couples with
each other phase, and the voltages cancel out. As such, there would
be negligible current through the neutral point, which can be tied to
ground.[6]

Each of the three "limbs" are split into two sections. The two halves
of each limb have an equal number of turns and are wound in
opposite directions. With the neutral grounded, during a phase-
to-ground short fault, a third of the current returns to the fault Zigzag transformer
current, and the remainder must go through two of the three phases
when used to derive a grounding point from a delta source.[7]

If one or more phases fault to earth, the voltage applied to each phase of the transformer is no longer in
balance; fluxes in the windings no longer oppose. (Using symmetrical components, this is Ia0 = Ib0 = Ic0.)
Zero-sequence (earth fault) current exists between the transformer’s neutral to the faulting phase. The
purpose of a zigzag transformer in this application is to provide a return path for earth faults on delta-
connected systems. With negligible current in the neutral under normal conditions, providing the defective
load will be automatically disconnected in a fault condition, an undersized transformer may be used only as
short-time rating is required (i.e. the transformer can only carry full rated current for, say, 60 s). Impedance
should not be too low for desired maximum fault current. Impedance can be added after the secondaries are
summed to limit maximum fault currents (the 3Io path).[8]

An application example: A combination of Y (wye or star), delta, and zigzag windings may be used to
achieve a vector phase shift. For example, an electrical network may have a transmission network of 110
kV/33 kV star/star transformers, with 33 kV/11 kV delta/star for the high-voltage distribution network. If a
transformation is required directly between the 110 kV/11 kV network, an option is to use a 110 kV/11 kV
star/delta transformer. The problem is that the 11 kV delta no longer has an earth reference point. Installing a
zigzag transformer near the secondary side of the 110 kV/11 kV transformer provides the required earth
reference point.

1 of 2 1/5/2015 6:44 PM
Zigzag transformer - Wikipedia, the free encyclopedia http://en.wikipedia.org/wiki/Zigzag_transformer

1. Lawhead, Larry et al (2006). "Three phase transformer winding configurations and differential relay
compensation" (http://www4.hcmut.edu.vn/~nqnam/3phXfmrs.pdf) (PDF). pp. 8–10. Retrieved 3 March 2014.
2. Khera, P.P. (1990). "Application of zigzag transformers for reducing harmonics in the neutral conductor of low
voltage distribution system" (http://ieeexplore.ieee.org/stamp/stamp.jsp?tp=&arnumber=152320). IEEE Trans. on
IA.
3. Sankaran, C. (2000). "The Basics of Zigzag Transformers" (http://ecmweb.com
/mag/electric_basics_zigzag_transformers/). EC&M Magazine. Retrieved 22 February 2012.
4. Lawhead (2006), p. 8
5. Lawhead (2006), pp. 8–10
6. Post Glover – Zigzag Grounding Transformers (http://www.postglover.com/Literature
/GT210-08_Zigzag_Trans.pdf)
7. Das, J.C. (2002). Short-Circuit Load Flow and Harmonics (http://books.google.com
/books?id=AExV1jvJH5AC&pg=PA25). CRC Press. pp. 25–28.
8. Blackburn, J. Lewis, Protective Relaying, Marcel Dekker, Inc., New York, 1998

Retrieved from "http://en.wikipedia.org/w/index.php?title=Zigzag_transformer&oldid=646797828"

Categories: Transformers (electrical)

This page was last modified on 12 February 2015, at 14:05.


Text is available under the Creative Commons Attribution-ShareAlike License; additional terms may
apply. By using this site, you agree to the Terms of Use and Privacy Policy. Wikipedia® is a registered
trademark of the Wikimedia Foundation, Inc., a non-profit organization.

2 of 2 1/5/2015 6:44 PM

You might also like