SIPROTEC 5 Application Note

Extension of BI/BO for busbar protection


SIPROTEC 7SS85
SIP5-APN-040, Edition 1

www.siemens.com/protection
Extension of BI/BO for SIPROTEC 7SS85
SIPROTEC 5 Application Note

SIPROTEC 5 – Application Note


Extension of BI/BO for busbar protection
SIPROTEC 7SS85
SIP5-APN-040, Edition 1

Content

1 Extension of BI/BO for busbar protection SIPROTEC 7SS85 3


1.1 Introduction 3
1.2 SIPROTEC 5 communication modules 3
1.3 Protection Data Interface PDI and Protection Topology 4
1.4 Test results 5
1.5 Conclusion 5

SIP5-APN-040 2 Edition 1
Extension for BI/BO of SIPROTEC 7SS85
SIPROTEC 5 Application Note

1 Extension of BI/BO for busbar protection


SIPROTEC 7SS85
1.1 Introduction
A SIPROTEC 5 device consists of a base module, up to 9 expansion modules and a power supply module for
the optitional second row. In some applications for busbar protection SIPROTEC 7SS85 one device is not
sufficient due to the required amount of binary inputs and outputs.
The hardware extension of the SIPROTEC 7SS85 with binary inputs and outputs can be realized by the
connection of additional SIPROTEC 5 devices, e.g. bay controller SIPROTEC 6MD8x by using the protection
data interface , a SIPROTEC 5 wide system feature. Alternatively also the data transmission via IEC 61850
GOOSE messaging on the IEC 61850 system interface is possible.
This application describes the recommended extensions of binary inputs and outputs by using the protection
data interface PDI.

1.2 SIPROTEC 5 communication modules


SIPROTEC 5 devices are equipped with high-performance communication interfaces. The SIPROTEC 5 can be
ordered with configured communication modules as well exchangeable and upgradable during the complete
life cycle. The pluggable communication modules can be installed in the base module or the 1/3 module and
in the expansion module CB202. The base module can be extended via module slots E and F. The expansion
module CB202 is designed for 3 additional plug-in modules, if the two in the based module are not sufficient.
The communication modules can be installed in slots N and P. Slot M is restricted to analog expansion
modules. SIPROTEC 5 devices can only be equipped with one CB202.

Fig 1: USART-AD-1FO Fig 2: USART-AE-2FO


Serial for asynchronous or synchronous communication module with 1 independent optical interface (USART-
AD-1FO) or 2 independent optical interfaces (USART-AE-2FO) are required and need to be installed in each of
the connected devices, max. distance of 2 km.

Fig. 3:
The USART plug-in module types can be used in slots E and F in the base module as well as in slots N and P in
the CB202 expansion module. The plug-in module position M is intended for a measuring-transducer module
only.
With the communication module USART-AE-2FO a ring topology can be created which provides more safety.

Edition 1 3 SIP5-APN-040
Extension of BI/BO for SIPROTEC 7SS85
SIPROTEC 5 Application Note

The communication ring has the advantage over the communication chain that the entire communications
system also works if one of the communication connections fails or if a device in the topology is taken out of
operation. The devices detect failure or logging off, and switch over automatically to the remaining
communication routes within 20 ms.

1.3 Protection Data Interface PDI and Protection Topology


The protection data interface function enables data exchange between the devices via synchronous serial
point-to-point connections from 64 Kbits/s to 2048 kbits/s. The communication takes place via direct fiber-
optic connections, via communication networks or via 2-wire copper conductors. The direct fiber-optic
connection is recommended, as this offers the highest transmission rate of 2048kBit/s and is immune to
failures in the communication route while offering the shortest transmission time. This also enables the
interchange of a large amount of information from e.g. bay controller SIPROTEC 6MD8x to the SIPROTEC
7SS85.

The protection communication in a device can be either type 1 or type 2. Type 2 is created for devices like the
busbar protection SIPROTEC 7SS85, and is used for data transmission. Using type 2 protection communication,
a maximum of two additional SIPROTEC 5 devices can be connected to one SIPROTEC 7SS85.
There are 3 different priorities in the Type 2 when transferring protection-interface information:
· Priority 1: Use Priority 1 for the transmission of fast protection signals that are transferred and
updated at a maximum of every 20 ms in a telegram. Transfer up to 96bit.
· Priority 2: Use Priority 2 for the transmission of fast single-point or double-point indications that are
transferred and updated at a maximum of every 40 ms. Transfer up to 200bit.
· Priority 3: Use Priority 3 for all indications, measured, and metered values that are transferred and
updated a maximum of every 100 ms. Transfer up to 1.024bit.
The PDI supports variable baud rates. From a baud rate of 256kBit/s onward there is no priority difference
between priority 1 and 2.
To sum up, priority 1 and 2 are available with high priority. Thus 296 Bit can be transmitted fast, either 296 BI
or 296 BO or 148 BI and 148 BO. Measured values can also be transmitted, but not for protection purposes.
Further information of the protection data interface are described in the device manual of the line protection
devices e.g. 7SA87 as well in the application note SIP5-APN-005.

SIP5-APN-040 4 Edition 1
Extension for BI/BO of SIPROTEC 7SS85
SIPROTEC 5 Application Note

1.4 Test results


The below table with real measure delay time is the result from the input measurement of an Omicron device.

In total nine time measurements. The used BO are for all cases is the commonly BO “fast” which is
recommended for trip circuit control. The trip decision derived from BBP and a heavy fault current internal
fault. The 9,100ms up to 9,600 ms are typically for this fault cases tripped by a 7SS85 BBP.
The first three measurements are tripping times of the internal BO of the device. The next three are coming
from the same feeders. The tripping relays are in a second device. The signal transfer is with the protection
data interface PDI. The resulting average delay time is 5.5ms.
The last three values are again from the same feeder. The signal transfer to the second device is via IEC 61850
GOOSSE message. The resulting delay time is between 4,4 and 9,3ms.

1.5 Conclusion
By using the well proven high-performance protection data interface PDI a fast and secure data transmission
between devices can be realized. Therefore a high amount of binary inputs and outputs can be extended
easily on a SIPROTEC 5 device, mainly in applications with the central busbar protection SIPROTEC 7SS85 with
a high amount of binary inputs.
Due to the faster transmission time of the tests and the easier engineering the protection data interface is
recommended. Nevertheless, IEC 61850 GOOSE can also be used.

Edition 1 5 SIP5-APN-040
SIPROTEC 5 Application
Error! Reference source not found.

Published by and copyright © 2016:


Siemens AG
Energy Management Division
Humboldtstr. 59
90459 Nuremberg, Germany
www.siemens.com/siprotec

For more information, please contact your Siemens


Partner or our Customer Support Center.
Phone: +49 180 524 70 00
Fax: +49 180 524 24 71
(Charges depending on the provider)
Email: [email protected]

Application Note: SIP5-APN-040, Edition 1

Printed on elementary chlorine-free bleached paper. For all products using security features of OpenSSL
All rights reserved. the following shall apply:
Trademarks mentioned in this document are the This product includes software developed by the
property of Siemens AG, its affiliates, or their respective OpenSSL Project for use in the OpenSSL Toolkit
owners. (www.openssl.org).
Subject to change without prior notice.
This product includes cryptographic software written
by Eric Young ([email protected]).
The information in this document contains general
descriptions of the technical options available, which
may not apply in all cases. The required technical
options should therefore be specified in the contract.