Compressor Manual
Compressor Manual
Compressor Manual
1.0 INTRODUCTION
1.1 GENERAL
1.1.1 Use of the Design Manual
1.1.2 Organization of the Design Manual
1.1.3 Glossary of Terms and Abbreviations
1.2 TYPES OF COMPRESSORS
2.9 STARTING/UNLOADING
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
4.6 FILTERS/PIPING/SEPARATION
5.1 GENERAL
5.1.1 Objectives
5.1.2 System Sketch
5.1.3 Requirements
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
15.0 TROUBLESHOOTING
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION TOC
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL TABLE OF CONTENTS
DATE 06-94
17.0 REFERENCES
17.1 REFERENCES
18.0 APPENDIX
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL INTRODUCTION
DATE 06-94
1.0 INTRODUCTION
1.1 GENERAL
This section of the manual provides a brief introduction to the subject and the
organization of the manual followed by a glossary of terms, expressions, and
abbreviations to make this manual easier to understand.
In the broad sense, compressors and blowers are mechanical devices used to
increase the pressure of a gas or vapor for:
providing the required operating pressure in various processes encountered,
such as in reactors, gas scrubbers, flue gas systems, separation units, and refrigeration units
ventilating buildings
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL INTRODUCTION
DATE 06-94
Identify the preferred type of machine and driver for the particular
application.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL INTRODUCTION
DATE 06-94
descriptions and form numbers, and procedures for providing process data.
Section 9 provides the theory of the operation of each driver and discusses
ideal and real operating cycles. Electric motor theory is not covered in this
manual.
Section 10, covers the various types of drivers. Drivers are described
including their principle of operation, operating range and any factors
relevant to driver selection.
Section 13 covers the methods of controlling and protecting the driver and
the instrumentation involved.
Section 15 includes a description of the problems that can occur with drivers,
the cause and possible means of preventing or alleviating them.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL INTRODUCTION
DATE 06-94
Mach number The ratio of the actual gas velocity to the velocity
of sound in the medium under consideration.
perfect intercooling Occurs when the gas is cooled to first stage inlet
cooling temperature following each stage of
compression.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL INTRODUCTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL INTRODUCTION
DATE 06-94
The classification tree illustrated on the following page shows compressors are
divided into three (3) main categories depending on their principle of operation.
These categories are:
Dynamic compressors which operate by applying inertial forces to the gas with
revolving bladed impellers. The gas enters the eye of the impeller and is accelerated
in a peripheral direction. Then it flows through some type of diffuser, and exits to the
process if a single stage unit is used; otherwise the gas returns to the eye of the next
impeller, and the process is repeated. The impeller is the only means of adding
energy to the gas or vapor. Conversion of kinetic energy into pressure is with the
stationary parts, such as the diffusers, guide vanes, and return channels. There is no
mechanical means of preventing backflow with this type of machine as the flow
passages are open throughout. To prevent backflow and running the machine
backwards non-return (check) valves are placed in the discharge piping.
This group includes centrifugal and axial flow compressors, and fan and blowers.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL INTRODUCTION
DATE 06-94
This group is subdivided into reciprocating and rotary compressors, and each of these
has numerous special construction features to handle various applications.
Ejectors increase the pressure of a gas or vapor stream at the expense of another
fluid. In their simplest form, they consist of an actuating nozzle, a suction chamber
and a diffuser. The actuating or motive fluid, at a high pressure is expanded at high
velocity through the nozzle. This action entrains the low pressure gas in the suction
chamber. As the mixed gas exits the diffuser, it is compressed to the discharge
conditions by rapid deceleration. They have limited use in gas compression since
there must be a high pressure stream which can be throttled, and mixed with a lower
pressure gas stream. Then, the resultant blended intermediate pressure vapor must be
in the correct proportions for downstream use. Examples of ejectors in compression
applications are steam jet thermo-compressors, and steam jet air compressors.
However, ejectors are most widely used in vacuum processes. The design and
selection of ejectors is not discussed in this manual.
Details on the operation of the two main classes of compressors (dynamic and
positive displacement) will be discusses in subsequent sections of this manual.
However, as an introduction it is important to summarize some the technical features
of each machine, their operating characteristics, and range of operation. In the
preliminary selection process the pressure volume map of Figure 1-2 illustrates
operating ranges for the various types of compressors. Some the critical technical
features are displayed in Table 1-1.
Reciprocating units have found the widest range of application in industry. They are
generally cheaper than centrifugal machines when their power requirements are less
than 500 hp, and the compression ratios are greater than or equal to 3.0. Rotary
compressors are typically chosen for operations in the 1,000 to 5,000 ACFM (suction
conditions) range. These machines have the characteristic of meeting a wide variety
of pressure ratios at near constant flow. When only a small differential pressure is
required (for example between 0.5 to 50 psi) then the lobe root blower is the
preferred machine.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL INTRODUCTION
DATE 06-94
Centrifugal fans gain prominence to move gases and vapors when only a differential
pressure of 0.25 to 16 inches of water is required.
With the overlap in applicable operating range for the different compressor types, the
selection process is not always straight forward. Where this occurs, the following
types are listed in order of preference:
Axial or centrifugal compressors. With these machines spare units are normally
not required.
Reciprocating compressors are acceptable at the low volume high head part of
the map overlap. Three (3) 60 % capacity units should be specified when their
size is greater than or equal to 500 hp, while two (2) 110 % units should be
indicated at lower capacities.
Screw compressors are preferred for the higher volume with moderate head part
of the map overlap with positive displacement type machines.
Final compressor selection shall be made after consultation with the client,
mechanical group, or vendors.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL INTRODUCTION
DATE 06-94
Figure 1-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL INTRODUCTION
DATE 06-94
Figure 1-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL INTRODUCTION
DATE 06-94
Figure 1-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL INTRODUCTION
DATE 06-94
Table 1-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL INTRODUCTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL INTRODUCTION
DATE 06-94
The operation of compressor systems is linked directly with the theory of gas
behavior and equations of state and an understanding of these is necessary
for compression plant design.
pV = nRO T (1.3.1)
where:
p = absolute pressure, psia
V = volume, ft3
n' = number of moles
T = absolute temperature, oR
RO = Universal Gas Constant, ftlb/lbmole oR
All gases deviate from the ideal gas laws and it is necessary to take these
deviations into account in compressor calculations. Computing PVT
properties of a real gas can be accomplished by the use of equations or state
or by the introduction of compressibility factors in the ideal gas equation.
The compressibility of a gas or vapor is determined experimentally and used
to derive the compressibility factor, Z. The compressibility factor has its
basis in the law of corresponding states. (The law of corresponding states
imply that at the critical condition (P c, Tc) all substances behave the same.) A
simple equation to account for the real gas behavior is illustrated below:
pV = nZRO T (1.3.2)
It should be noted that the value of this factor varies with pressure and
temperature.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL INTRODUCTION
DATE 06-94
Figure 1-4
Figure 1-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL INTRODUCTION
DATE 06-94
a) Isothermal Compression
pV = Constant (1.3.3)
Adiabatic Compression
where:
Cp MCp
K (1.3.5)
Cv MCp 1.986
where:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL INTRODUCTION
DATE 06-94
n 1
T2
p 2
n
(1.3.7)
T1 p
1
T2
n 1 (1.3.8)
T1 r n
where:
T1 = inlet temperature, oR
T2 = outlet temperature, oR
p1 = inlet pressure, psia
p2 = outlet pressure, psia
r = pressure ratio
n 1 k 1
(1.3.9)
n kp
where:
Work is required to compress a gas and this work is represented by the area
under the process curve on a pressure-volume graph. Referring to Figure 1-
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 18
PROCESS MANUAL INTRODUCTION
DATE 06-94
H = H2- H1 (1.3.10)
where:
The compressor adiabatic efficiency, ad is the ratio of the theoretical to the
actual work and does not include mechanical friction losses. It is expressed
as follows:
where:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 19
PROCESS MANUAL INTRODUCTION
DATE 06-94
Figure 1-6
Figure 1-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 20
PROCESS MANUAL INTRODUCTION
DATE 06-94
k ( k 1) / k
p 2
had = ZavRT1 k 1
1 (1.3.12)
p
1
where:
p
( k 1) / k
The bracketed expression: 2 1 (1.3.14)
p
1
k
had = ZavRT1 X (1.3.15)
k 1
h ad
h act (1.3.16)
ad
whad
Pad (1.3.17)
550
where:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 21
PROCESS MANUAL INTRODUCTION
DATE 06-94
The discharge temperature of the gas from the compressor is found by first
calculating the theoretical discharge temperature from the temperature ratio
equation.
k 1
T' 2 p k
2
T1 p1
(1.3.18)
For low and medium pressure applications the theoretical temperature T
is used to find the actual discharge temperature:
T2 T1
T2 T1
(1.3.19)
ad
1.3.6 Multistaging
discharge temperature
differential pressure
compression ratio (dynamic units)
effects of clearance (reciprocating units)
power losses
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 22
PROCESS MANUAL INTRODUCTION
DATE 06-94
Table 1-2
ADIABATIC EQUATIONS
Hisen H2 H1
Efficiency, ad (1.3.20)
H H2 H1
Ro 1545
Specific gas constant, R (1.3.21)
M M
p
( k 1) / k
X Factor, X = 2 1 (1.3.22)
p
1
k
Head, ft, had ZavRT1 X (1.3.23)
k 1
had
Actual Head, ft, hact (1.3.24)
ad
wh ad
Power, hp, Pad
550
(1.3.25)
k 1
T2 T1
Actual Discharge Temperature, T2 T1 (1.3.28)
ad
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 23
PROCESS MANUAL INTRODUCTION
DATE 06-94
Table 1-3
POLYTROPIC EQUATIONS
n 1
Temperature Ratio, T2 p 2
n
(1.3.29)
T1 p1
n 1 k 1
(1.3.30)
n k p
n 1 / n
p
X Factor, X = 2 1 (1.3.31)
p
1
n
Head, ft, hp ZavRT 1
n 1
X (1.3.32)
hp
Actual Head, ft, hactual (1.3.33)
p
whactual
Power, hp, Pactual (1.3.34)
550
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 1.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 24
PROCESS MANUAL INTRODUCTION
DATE 06-94
rs = r1/s = s
r (1.3.36)
NQ 1 / 2
Ns (1.3.37)
hp 3 / 4
where:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-3 shows the variation of gas pressure, temperature and velocity as
the gas is passed through a single stage compressor. The gas enters the unit
axially through the suction and is accelerated radially by the impeller and
then decelerated as it passes through radial diffusers into the discharge where
further deceleration is produced by the action of discharge diffusers.
Maximum gas velocity is thus reached at the impeller vane tips before
passage of the gas through the radial diffusers. Compression and resultant
temperature increase principally occur at the impeller and radial diffusers
where maximum acceleration and deceleration are produced respectively.
The axial compressor Figure 2-4 consists of a rotating drum or rotor mounted
in a casing. Attached to the rotor is a series of blades which move between
rows of fixed blades held by the casing. The gas enters at the low pressure
end and moves with almost constant velocity through the main part of the
machine. As it progresses through the compressor it undergoes a virtually
constant rate of compression and corresponding temperature increase as can
be seen from Figure 2-5 where gas conditions in a typical seven stage unit
are represented.
In centrifugal fans, the air is introduced in an axial direction into the centre of
a revolving wheel or rotor with peripheral blades. Air is drawn through the
blades and forced out in centrifugal flow into a scroll or volute housing
where a portion of the kinetic energy is converted to pressure or static head.
The centrifugal fan is illustrated by Figure 2-6. There are basically four
impeller designs that may be used. They are illustrated by Figure 2-7 with
their performance curves and discussed as follows.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-1
Figure 2-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-4
Figure 2-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
When running at a given speed and handling a specific gas a dynamic compressor
will produce a polytropic head that varies with inlet capacity in accordance with a
characteristic curve, Figure 2-8(a) and 2-8(b). Because the polytropic head is largely
independent of the gas property the compressor will produce similar curves for other
gases. Any variation between the curves is due to the relative Mach number and any
volume reduction through the impeller.
Variations in speed, operating conditions and gas characteristics may alter the
pressure, temperature and velocity through the compressor and also the polytropic
head produced by it. Table 2-1 gives qualitatively the effects on these items for
changes in inlet temperature and pressure, molecular weight and the adiabatic
exponent of the gas.
It can be seen that it is the average density through the machine that has been
changed and it is this that causes the variation in the compressor characteristics and
performance. It makes no difference to the machine what causes the density to alter.
The density of the gas determines the pressure rise and compression ratio possible for
a given compressor design, the greater the density, the greater the possible pressure
increase.
To illustrate this, consider the compression of 14,700 ACFM of gas from atmospheric
pressure to 6 psig. If the gas is air it will be a simple single stage centrifugal but with
hydrogen it would require a multistage centrifugal, probably in two casings [17].
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-8
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
It should be noted that although the characteristic head-capacity curve of the axial
compressor is quite different from that of the centrifugal type, the effects of speed,
gas properties and operating conditions are similar. The steepness of the curves gives
the axial compressor a more limited operating range.
The fan laws apply to centrifugal compressors and give approximately the effect of
speed on compressor performance. For multistage units they should be applied to
each stage individually although results are sufficiently accurate when used overall
for speed variations of less than 15 %. Since compressor efficiency does not vary
significantly with small speed variations, the brake power also varies with the cube of
the speed.
Figure 2-9(a) illustrates graphically the effect of speed variation on the compressor
characteristic curves of polytropic head and power.
From these curves it will be seen that the centrifugal compressor is largely a constant
pressure machine and that power consumption is almost directly proportional to the
volume delivered.
The relationship between head and speed is much the same for axial compressors and
is illustrated by Figure 2-9(b).
Speed change is extensively used for capacity control of dynamic units but more
particularly for centrifugal units because of their flatter head-flow characteristic
curves.
The stability line, shown on Figure 2-9 is the lower flow limit for a given
head of the dynamic compressor operating range and represents the
conditions under which pumping or surge may occur. This is, for any speed,
the capacity under which compressor operation becomes unstable and it is
determined by the compressor design and the properties of the gas being
compressed.
The primary cause of surge lies in the shape of the characteristic curve and
particularly in that area where pressure falls off rapidly at low capacity after
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
reaching a peak of pressure. When the capacity is reduced below this peak
the pressure in the discharge line exceeds that produced by the machine and
flow tends to momentarily reverse. Reversal causes a drop in discharge
pressure which initiates normal flow. High speed pulsations are produced by
this phenomenon which leads to noisy operation, vibration and machine
distress. In practice, the surge limit should be defined by test for each
machine installed and its operation kept sufficiently above it.
2.4.2 Stonewalling
The upper limit of the operating range for dynamic compressors is defined by
the occurrence of stonewalling. Although infrequent in compressor
installations, it occurs when the velocity of flow approaches the sonic
velocity in the gas being compressed. The phenomenon is represented in
Figure 2-10 by the almost vertical dip of the pressure curve. Stonewalling
may be avoided by using a different impeller design or a greater number of
stages at a lower rotational speed.
Many gases, including air, contain moisture which must be taken into consideration
in compressor design. This is because moisture affects almost all properties of the
gas and an increase in moisture leads to a reduced discharge pressure and
compression ratio.
Gas cooling during compression reduces power by lowering the average gas
temperature within the unit, increasing the average density and decreasing the
polytropic head required for a given discharge pressure. Intercooling may be
introduced for power saving or to reduce the discharge temperature to satisfy process
limitations. It may also be cost effective to use it to reduce the number of compressor
stages or the operating speed. Cooling is achieved by use of direct liquid injection
into the gas, water cooled interstage diaphragms or by passage of the gas through an
external heat exchanger between successive stages.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-9
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
When larger units are involved, moveable guide vanes are installed ahead of
the first impeller. These not only throttle but give pre-rotation to the gas
entering the impeller. This has the effect of altering the characteristic of the
first impeller and lowering the surge limit as indicated by Figure 2-12.
Power savings are also achieved. The effect of guide vanes on compressor
performance depends on the number of stages, decreasing as stages increase.
The stator blades are attached to the casing and in some compressor types
may be adjusted manually or automatically. Adjustable stator blading has an
appreciable effect on the stable operating range as can be seen from Figure 2-
13 and is frequently used for range extension. It is also used to permit the
compressor to operate in the narrow peak efficiency range under varying
inlet conditions or changes in gas composition.
2.8 MULTISTAGING
Because compressor performance moves further from the design point with
successive staging it is necessary to ensure that the last stages are selected to give a
sufficiently wide overall range of operation; shortness of the last stage characteristic
leads to a very short overall performance characteristic. As an axial compressor
generally has a high number of stages and a relatively steep performance curve this
factor is of much greater significance than in centrifugal compressor.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-10
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-11
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
2.9 STARTING/UNLOADING
Steam turbines have excellent starting torque characteristics and offer no problems.
For electric motor and combustion gas turbine drives, some type of unloading may be
required. On small units, this can frequently be done with a butterfly valve in the
suction line. On many of the more complicated process units, it can be done by
utilizing adjustable inlet guide vanes, throttling valves, or, in some cases, by reducing
pressure levels in the process. In all cases, this subject should be discussed with the
compressor manufacturer.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 2.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL DYNAMIC COMPRESSORS
DATE 06-94
Figure 2-12
Figure 2-13
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
3.1.1 General
Reciprocating compressor speeds may range from 125 to 515 rpm with
piston speeds between 11.5 and 14.8 ft/sec. Nominal gas velocity is usually
in the range of 72 to 131 ft/sec and discharge pressures of 87,000 - 100,000
psig may be reached. Compression ratio per stage is generally limited to four
by maximum allowable discharge temperatures although ratios of up to eight
may be reached with low capacity machines.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
It should be noted that for a particular machine the volume flow rate of
compressed gas increases with volumetric efficiency. Improvement in
volumetric efficiency is achieved by reducing the effect of the re-expanding
clearance gas by using a smaller clearance. The volumetric efficiency is
usually higher for compressor with lower compression ratios and for gases
with higher adiabatic exponent. The effects of r and k on volumetric
efficiency are shown by Figures 3-2(b) and 3-2(c).
1
r k
V.E. 100 c 1 L
f
(3.1.2a)
1
pd Zs k
100 c 1 L
ps Zd
(3.1.2b)
where:
c = clearance (%)
r = compression ratio (pd/ps)
k = adiabatic exponent
L = internal losses (%)
f = ratio of compressibility factors (Zd/Zs)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Where exit pressure is constant but inlet pressure varies such as with
some types of booster compressor applications.
Where inlet pressure is constant but exit pressure varies such as with
pipeline and gas storage applications.
The compressor must first be sized to meet certain specified conditions and
then analyzed for power variations due to changing pressures. It will be
found in both of the above cases, Figure 3-3, that over a sufficiently wide
change in pressures there exists a peak of maximum compressor power. It
should be noted that the clearance in Figure 3-3(b) is high and that the
resulting power curve is flatter and lower than that of Figure 3-3(a). The
effect of clearance on power is illustrated by Figure 3-4.
Save power
Limit gas discharge temperature
Limit pressure differential
Attain high discharge pressures
The curves of Figures 3-5 and 3-6 show the theoretical effect of two and
three staging on the discharge temperature per stage and the power required
for compressors handling air at atmospheric pressure using equal ratios for
all stages and interstage cooling. In practice, when reciprocating compressor
staging exceeds four, the power savings with subsequent stage addition are
insignificant because of greater gas frictional losses through valves, piping
and heat exchangers.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-4
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Most multistage units also employ interstage cooling. The power saving due
to intercooling of a two stage unit is illustrated by Figure 3-7 where cooling
is provided after the first stage and before the second stage along curve AB.
The power saving is represented by the difference in area under the uncooled
and cooled system curves and is that enclosed by points ABCD shown
shaded in the figure.
Interstage coolers require the coolest possible water while cylinder jackets
prefer warmer water. The multistage compressor cooling system, thus passes
water first through the interstage cooler and then around the cylinders. With
properly cooled units it may be assumed that heat not removed in the
jackets will be removed in the subsequent intercooler and that the
compressor discharge temperature is dependent upon the effects of
compression in the last cylinder only.
It should be noted that when compressing a saturated gas the cooling water
inlet temperature to the cylinders must be five to ten degrees centigrade
higher than the suction temperature of the gas to prevent any condensation
within the compressor.
Speed. This is rarely applied since the use of variable speed drivers is
limited and it is expensive.
Clearance control. See Section 3.1.3. In addition to the normal
clearance in a compressor cylinder, a number of clearance pockets can be
incorporated at each end of the cylinder. These clearance pockets can be
closed or opened to the compressor cylinder by manually operated
valves. The amount of clearance added or reduced is proportional to the
movement of the clearance pocket piston.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-5
Figure 3-6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
b) Screw Compressor
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
These units, Figure 3-10 are offered for operating pressures of up to 115
or 130 psig and capacities of up to 2.9 x 10 3 ft3/min. Generally, pressure
ratios per stage are limited to four to one. Lubrication of the sliding
vanes is required, so the discharge air or gas stream contains lubricant.
Vane type rotaries should not be used with dirty air or gas, or wear will
be unduly accelerated, so these units are almost always fitted with filters.
It is not recommended that gases containing liquid be handled although
the machine will cope with occasional light carryover as long as
lubrication is not destroyed. Vane breakage can occur when heavy slugs
of liquid are permitted to enter.
The vane rotary has higher unloaded power than the corresponding
reciprocating and water cooled units and may generally be classified as
heavy duty compressors suitable for long periods at full load.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-8
Figure 3-9
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-10
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-11
If the operating pressure is lower than the in-built pressure ratio, the gas
expands through the discharge port into the discharge pipework. When the
pressure in the discharge main is higher than that developed by the in-built
pressure ratio, further compression takes place as the gas passes through the
discharge port into the discharge pipework.
Power required for compression is calculated using the formula for adiabatic
power, Equation 1.3.17, and the proven mechanical efficiency of the unit.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
If the internal leakage losses are referred to the quantity of gas handled
within a unit of time, they constantly decrease with increasing
circumferential speed of the machine set.
3.2.5 Multistaging
Multistaging usually requires the use of a separate machine for each stage
with intercoolers between stages. The reasons for multistaging are the same
as for reciprocating units. The stages are sized as closely as possible to
obtain the best interstage pressures.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
3.3.1 General
The mechanical compression cycle traces the hydraulic system pressure from
the process suction pressure to the process discharge pressure, then to the
hydraulic pressure limiter setting and back to the process suction pressure.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 18
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
Figure 3-12
Figure 3-13
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 19
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
On the compression portion of the stroke, the hydraulic piston moves from
bottom dead centre, compressing the hydraulic fluid and forcing the
diaphragm group into the cavity in the process cavity plate. Gas volume in
the process cavity is reduced with an accompanying rise in pressure. This
compares to points 1 and 2 on Figure 3-12.
Compressed gas is flowing out of the discharge check valve and into the
discharge piping during the discharge portion of the stroke. When the
diaphragm group is fully deflected or displaced into the cavity plate, the
discharge check valve will close. This compares to points 2 and 3 on
Figure 3-12. Gas at pressure P2 is still in the cylinder.
The expansion cycle of the metal diaphragm compressor begins once the
hydraulic pressure lifter has closed and the hydraulic piston has started its
reversal. The suction and discharge valves remain closed and the gas trapped
in the clearance volume begins to expand, resulting in a pressure reduction.
This compares to points 3 and 4 on Figure 3-12.
The cavity pressure eventually drops below the suction pressure. The suction
valve will then open and gas will flow into the process cavity until the
diaphragm group reaches its maximum deflection in the hydraulic cavity
plate. It is during this phase of the cycle that the hydraulic injection pump
will add the "extra volume" which will eventually become the overpump at
the discharge portion of the cycle.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 3.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 20
PROCESS MANUAL POSITIVE DISPLACEMENT COMPRESSORS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
Compressors width metal sliding parts can not operate without lubrication.
When contamination of the compressed gas by lube oil cannot be tolerated, non-
lubricated cylinder designs are available which use piston rings and rod packing
(usually carbon or teflon) which do not require lubrication. Naturally, more
maintenance is required for these cylinders than for lubricated ones. To prevent
carryover of oil from the crankcase to the cylinder, a special long distance piece must
be inserted between the frame and the cylinder.
A separate frame lubrication system supplies oil to all other moving parts such as
crank shaft bearings, crosshead guides, etc. This is similar to centrifugal compressor
lube oil consoles in that it includes pumps (main and auxiliary), coolers and filters.
The lube oil reservoir is in the crankcase.
Centrifugal compressors require lube and seal systems. Lubrications oil is always
required for the main journal bearings and thrust bearing. Seals may require a buffer
gas, seal oil or both.
Lubrication oil is supplied from a reservoir by a lube oil pump. This pump may be
integral with the compressor shaft, but an external main oil pump and an auxiliary oil
pump are preferred. One is a motor driven unit and the other is usually a steam
turbine driven unit. These are operated through adequate pressure controls so that if
the main oil pump fails to deliver oil pressure, the auxiliary will start. Each pump is
good for continuous duty and should be able to carry all requirements of the
compressor, including the driver if applicable.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
a) Labyrinth Seals
The standard shaft seal for a rotary compressor is the labyrinth seal,
Figure 4-1. Labyrinth seals are also widely used on dynamic air
compressors. It is the simplest type of seal and sealing the action is the
result of flow resistance by repeated throttling across the labyrinth teeth.
For low pressure applications, only the labyrinth seal has teeth but for
higher pressure applications a balanced or interlocking labyrinth seal
should be used where the teeth of the seal interlock with teeth on the
rotor shaft.
Leakage across the seal depends upon the number of teeth, diameter of
the packing ring, clearance and the pressure to be sealed and care should
be taken to ensure that leakage does not present a hazard. This seal type
can be used for dirty gas.
Carbon is the usual ring material since it does not readily wear the shaft
should there be contact and the seal can be purged or vented like the
labyrinth type.
c) Mechanical Seals
The design of this seal type varies and one arrangement is illustrated by
Figure 4-4 where sealing is accomplished by maintaining an oil film
between the rotating shaft and the shaft sleeve. The oil is circulated
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
The seal must be installed carefully and properly and can quickly be
damaged by dirt and liquid carryover. Proper break-in is very important
since it must wear-in to a satisfactory seal on the rod before being
loaded.
Seal faces are often made from carbon which is compatible with most
process media, but affected by strong oxidizing agents such as hydrogen
chloride and high temperature air (above 600 oF). Normal mating materials
for carbon for use in mechanical seals are tungsten or chromium chloride,
hard steel, stainless steal or cast iron.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
Figure 4-1
LABYRINTH SEAL
Figure 4-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
Figure 4-3
Figure 4-4
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
For compressors fitted with seals requiring circulated sealant oil, a sealant
system is provided which usually forms part of the lubrication system
providing oil to shaft and thrust bearings, etc.
Figure 4-5
Mechanical vibration of shaft and casing and axial shaft displacements are important
indications of possible hazard to compressor operating reliability. Modern
technology renders it possible to detect even the slightest of changes in these
parameters.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
Seismic pickups are employed for measuring casing or bearing pedestal vibrations.
This method does not supply such precise results as shaft vibration measurement, but
it offers the advantage of permitting measurements to be performed on running
machines without having to make modifications first.
The shaft position indicator monitors the axial position of the shaft relative to the
casing. The cause of axial displacement of the shaft may be wear of the thrust
bearing or sudden loads that may occur when the compressor is operating in the
unstable region. Detection of axial shaft shift is usually by electrical, or less
frequently, by hydraulic means. Electrical measurement basically involves the same
probes as are used for contactless vibration measurement.
All devices can be fitted with switches that trigger alarms or initiate shut-down of the
plant to prevent damage when limit values are exceeded. Modern shutdown devices
use the input from several sensors into a logic module. The machine would be
automatically taken off-line if, for instance, a temperature sensor and vibration sensor
would independently confirm a violation of two setpoints.
Multistage compressors require pulse dampeners at the suction and discharge nozzles
of each stage. The suction pulse dampeners usually are combination of suction
bottles and K.O. drums.
On most Fluor Daniel jobs an analog study (computer simulation) is made of the
compressor and piping system by the compressor vendor or an independent
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 4.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL COMPRESSOR AUXILIARIES
DATE 06-94
Most reciprocating compressor cylinders are provided with coolant jackets which
may be operated in three different modes depending on cooling requirements.
4.6 FILTERS/PIPING/SEPARATION
In addition to a reservoir and pumps, a lube oil system for a centrifugal compressor
will include a cooler and a filter. Twin coolers and filters should be employed with
suitable switching arrangement. This allows one item to be cleaned while the other is
in operation. The only real requirement for these coolers is that they have removable
tube bundles and that they be adequate for the heat rejection service expected of
them. Modern high speed bearings, in general, should have oil supplied to them at
temperatures not in the excess of 120 oF, and in sufficient quantity so that the heat
which they generate may be removed without an oil temperature rise of more than
40 oF.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
5.1 GENERAL
5.1.1 Objectives
Also, in some cases, the relative costs of utilities can have a strong influence
on driver selection. The compressor required can be influenced by the driver
chosen, and the final selection must be the most economical compressor -
driver combination, which will satisfy the process requirements.
In grass roots plants, economic studies to determine the cost and availability
of steam and electricity may fix the selection of the compressor driver.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
5.1.3 Requirements
a) General
b) Gas Composition
The presence of water vapor must be included as part of the gas analysis.
c) Flow Rate
The gas flow rate is a major factor in the selection of compressor types.
If multiple stages of compression are required, some services may be
best served by combinations of different types of compressors.
d) Temperature
e) Pressure
The pressure survey will establish the pressure available at the suction
nozzle and the required pressure at the discharge nozzle.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
The process gas compressor is called upon to handle many and diverse types of
gases. Its capacity-control requirements have a low range (50 % being a quite
frequent minimum even with reciprocating units where control possibilities are
usually greatest), and they are often run continuously for many months at a time
without shutdown. Operational reliability is usually therefore of great importance.
Consideration must also be given to the possibility of gas flowrate and composition
variation during the life of the installation, particularly when designing for offshore
applications.
Table 5-1
(a)
ACFM is actual cubic feet per minute at compressor inlet.
In any compression application, for a given compression ratio the flow rate to
be handled establishes the physical size of the equipment under
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
The variation in flow rate from maximum to minimum can likewise affect
selection. If the process requires a change in flow rate from the maximum
down to or near zero, the reciprocating compressor can do it with a
reasonable sustained efficiency.
Screw compressors are best applied as base load machines when constant
speed drivers are used but with variable speed drivers, turndown with a
proportionate reduction in power is achieved. A 50 % turndown is the
average maximum permissible.
5.2.3 Efficiency
The axial compressor has a high compression efficiency, as can be seen from
Figure 5-2 where the efficiency of centrifugal and axial compressors are
compared. For the usual high capacity application, efficiency is in the range
80-82 %.
Rotary screw compressors, Figure 5-3, have lower efficiencies than the
reciprocating compressor at the higher pressures in its range, but efficiencies
are comparable at lower pressures.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Screw compressors are limited to about 338 oF for low pressure units and
about 446 oF for high pressure machines while rotary vane types should not
be operated with a discharge temperature of more than about 374 oF to ensure
a satisfactory vane service life.
It is important that the suction and discharge pressures and their variation be
evaluated correctly and their influence on power requirements realized.
Conversely, if the suction pressure to the first stage is raised, the power demand
of the complete machine is raised, differential pressure on all stages up to the last
stage is raised, while differential on the last stage and its temperature rise is
lowered. Theoretically, if a six-stage compressor designed for atmospheric
pressure intake and a 5,000 psig discharge pressure has the suction pressure
raised to 5 psig, the power demand is increased by about 25 %. The reason is
that the density of the gas at first stage suction, in proportion with pressure,
increased 33 %, while the compression ratio component (X factor) decreased
only 6 %. At higher suction pressure this effect is less significant.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-2
Figure 5-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
At times, a gas may have certain limiting conditions within which it must be
kept during compression. These conditions, if exceeded, may cause
problems of corrosion, dangerous reaction of the gas or its components, or a
cracking of lubricating oil resulting in constituents that cannot always be
tolerated by a process. Limiting conditions are usually those of discharge
temperature which may be reduced by intercooling or lowering of the inlet
gas temperature.
5.2.7 Reliability
Properly applied, operated and maintained all compressor designs will give
years of good service. Heavy duty units are available for centrifugal, axial,
reciprocating and screw type compressors and require major overhaul very
seldom in their life. The modern reciprocating compressor is a highly
reliable machine and when evaluating centrifugal versus the reciprocating
compressor factors other than maintenance should be considered in making a
selection for a particular application.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Rotary type compressors are slightly smaller and do not produce large
vibrating loads whilst centrifugal and axial types possesses the lowest weight
to power ratio and are generally preferred for offshore applications where
weight is of importance.
It should be noted that the power cost throughout the service life of a
compressor is many times the first cost. While it is possible that the more
efficient machine may be higher in original installed cost, the power savings
over a period of years usually will quickly pay off the differential and return
a profit for the remaining life.
Maintenance costs for reciprocating compressors are higher than for dynamic
compressors, although when handling dirty or corrosive gases costs for both
increase and the difference between the two is reduced.
Air pressure compressor requirements are typically between 125 psig and 1,500 psig
which is generally available from both centrifugal or rotary compressors. For
pressure requirements above 200 psig reciprocating compressors should be used.
Variation in demand for compressed air usually ranges from zero to full
compressor capacity. For such variations, dynamic compressors cannot be
used because of their relatively small operating range while the higher
efficiency of reciprocating types makes them preferable to rotary types.
Any requirement for oil free air prevents use of vane type rotary
compressors. The screw and dynamic units require no oil in the compression
space at any time and the reciprocating compressor can be obtained in a
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Load factor is a consideration for smaller installations where only one or two
compressors are to be installed. It is the ratio of actual compressed air output
to that if the machine were operated at rated full load and should never be
100 %. Compressor selection should be made with a load factor of between
50 % and 80 % depending upon size, type and number of units as this leads
to:
For most process plant and offshore applications, the use of a centrifugal
compressor is considered optimum as this offers high reliability and
efficiency at low cost.
For very high or very low flowrates, or for very high discharge pressures, the
use of alternative machines should be considered.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Listed below are some of the terms, and expressions commonly used in the
refrigeration business.
Liquefied Natural Gas (LNG): The light hydrocarbon portion of natural gas
(methane) which is liquefied.
Natural Gas Liquids (NGL): These are hydrocarbons liquefied at either the
field facilities or the gas processing plant, and normally include propane,
butanes, and natural gasoline (pentanes plus).
Refrigeration Effect (RE): This is the heat absorbed by the refrigerant in the
evaporator or chiller (Btu/lb). It is the difference in enthalpy of the vapor
leaving the evaporator with that of the liquid upstream of the expansion
valve.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-4
Vi
CFM / TON 200
Hve Hlex
(5.4.4)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Table 5-2 identifies the three most common types of refrigeration systems
along with their suggested economic operating temperature range, and the
type of refrigerant used.
Capacity Temperature
System Range, tons Range, oF Refrigerant
b) Absorption Refrigeration
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Applications include:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Table 5-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 18
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
a) Basic System
Condenser
Receiver (Surge Drum or Complete System Drainage Tank)
Expansion Valve or Evaporator Level Control Valve
Evaporator/Chiller
Compressor Suction Scrubber
Compressor and Driver
The condenser removes the evaporator heat plus the heat from
compression. Cooling can be accomplished with air or water. Because
of varying ambient conditions, provisions to control the condensing
temperature are necessary. Air cooler control can be achieved with
variable pitch and variable speed fans, and with air dampeners. Cooling
water flow can be regulated with a control valve into the water cooled
exchangers. The condenser should be free draining to keep the tube
surface free of liquid accumulation.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 19
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
In a spray type evaporator, the refrigerant wets the tube surface rather
than flooding the tubes (see Figure 5-7).
The compressor suction scrubber is used to prevent damage to the
compressor from possible liquid carryover from the evaporators or
economizers, or condensation in the suction line. The scrubber should be
equipped with a mist eliminator or stripping vanes. It should have high
level alarm and compressor shutdown controls. A vaporizing coil in the
bottom of the vessel is advisable to remove any accumulated liquids
(depending on the vapor pressure of the refrigerant, even cooling water
can be used as the heating medium).
b) Auxiliary Equipment
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 20
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-6
Figure 5-7
SPRAY EVAPORATOR
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 21
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Figure 5-8
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 22
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
The oil injected screw compressors provides a direct seal between the rotors
and housing as the gas flows without pulsations radially, and axially. The oil
injected adsorbs much of the heat from compression, so the discharge gas
temperatures are seldom above 200 oF. The oil is removed from the
refrigerant in a multistage oil (vertical or horizontal) separators with an
internal coalescing element. It is cooled, filtered, and then re-injected at the
appropriate points of the machine. To ensure oil free operation, gas filters
with replaceable elements are added downstream of the separators. The
developed pressure is predetermined by the design of the machine, and is not
a function of speed. Positioning of the slide valve changes the point of where
compression begins.
Step 1
Determine the refrigerant load or duty from the process material balance.
Add a 20 % safety factor to this load - this safety factor accounts for the
design contingencies added on the process side, and for approximately 1 - 5
% system heat losses.
Step 2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 23
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
is between 10 and 15 oF lower than that required by the process outlet. With
the temperature established, the pressure is determined. Allow 2 -10 psi
pressure drop to the compressor inlet (depending on distance). The suction
pressure should be above atmospheric conditions.
Step 3
Determine the latent heat at the chiller pressure and temperature. Calculate
the amount of refrigerant vaporized (this is not the amount circulated, as
there is flashing across the expansion valve upstream of the chiller).
Step 4
With the cooling medium selected for the condenser, its outlet temperature
can be determined as follows:
For air coolers allow a 15 to 40 oF approach
For water cooled condensers allow a 10 to 30 oF approach
The high end approach temperatures were extracted from the Fluor Daniel
Process Design Criteria Manual. The low end approach temperatures are
what can be expected from package refrigeration vendors if cooling
temperatures are not specified on the condenser data sheet.
Now with the condenser outlet temperature set, the refrigerant pressure as a
saturated liquid is known. Allow approximately 5 psi pressure drop through
the condenser.
Step 5
Now that when the conditions at the receiver and chiller are set, the amount
of vapor flashed across the expansion valve can be determined, and hence the
total circulation rate.
wv
Circulating Refrigerant w (5.4.6)
1 Xg
where:
Step 6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 5.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 24
PROCESS MANUAL COMPRESSOR SELECTION
DATE 06-94
Step 7
Line Sizing: Use approximately 1.0 psi/100 ft pressure drop in the liquid line
from the receiver to the evaporator or economizer for a first estimate. Allow
a maximum velocity of 2.5 ft/sec out of the condenser to the receiver. This
line should not be trapped so liquids can drain freely from the condenser.
Keep the piping runs short downstream of the expansion valve because of
two phase flow. Check the flow to ensure it is not in the slug flow regime. If
it is, consider decreasing the line size.
Previous jobs and Fluor Daniel Design Manuals are helpful in the selection of materials
of construction. Material selection is the responsibility of the Fluor Daniel metallurgist.
The article "Selecting Centrifugal Compressor Materials for Harsh Environments"
provides some general guidelines for material selection and emphasizes points to
consider (see Reference No. 8).
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
Codes and standards applicable for the specification and rating of compression
equipment and their drivers are listed in Section 16.1.
This problem does not exist for reciprocating or rotary type compressors as
they are essentially constant volume machines but if connected to a common
suction manifold, pulsations should be removed both upstream and
downstream of the units.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
Receivers are not so commonly used with gas compression systems but are
necessary if stop-start control is employed and when the system volume
without the receiver is relatively small.
There are many installations where intake and possibly discharge silencers
are required, particularly with rotary type compressors. Reciprocating and
dynamic air compressors may require inlet silencers but their use is more
usual for pulsation dampening than high frequency abatement. The noise
produced by a compressor depends upon the size and type of unit and the
equipment supplier should be able to provide further details.
Inlet filters should be used with all types of compressor type to prevent
damage.
Permanent filters should be installed in front of first stage suction when the
source can not ascertain gas purity. Temporary start-up screens shall be
placed in front of all compressors to prevent damage by foreign objects
during initial operation.
Fast, reliable estimates of compressor power and operating conditions are frequently
needed for process studies, economic evaluations and plant engineering. Such
estimates need not be of the highest accuracy because exact designs will ultimately
be made by the manufacturer based on actual mechanical designs and operating
conditions. The methods for making such quick estimates before manufacturers
quotations are received are outlined as follows, using equations and information
already provided.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
a) General
Usually the inlet gas conditions and exit pressure are known and the
compressor power and outlet temperature are required. Where this
information is required to assist in the selection of a compressor type, the
calculation process should be repeated for each of the types under
consideration.
From Figure 5-1 it can be seen that the types of compressor capable of
delivering this relatively high capacity are centrifugal and axial. The
following information required for the power calculation is available
from tables included in this manual or from readily available texts:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
b) Centrifugal Compressor
The procedure for calculating the power and discharge temperature for a
centrifugal compressor is given below:
The ratio (n-1)/n is related to the ratio (k-1)/k and the polytropic
efficiency is thus easily found.
n 1 k 1
(1.3.9)
n k p
= (1.40-1)/(1.40 x 0.758)
= 0.377
T2 = T1 x 1.532
= 560 x 1.532
= 858 oR
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
The specific gas constant is related to the universal gas constant and
molecular weight by the following equation
Ro
R= (1.3.13)
M
= 1,545/28.964
= 53.34 ftlbf/lboR
n 1 / n
p 2
X = 1 (1.3.21)
p
1
X = (45/14.5)0.377 - 1
= 0.532
n
hp = ZavRT1 X
n 1
(1.3.22)
= 42,151 ft
The actual power required to compress the gas is related to the actual
head and weight of gas handled by the following equation
whactual
Pactual =
550
(1.3.24)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
whp
=
550p
= (115.2 x 42,151)/(550 x 0.758)
= 11,647 hp
k 1
p 2 k
X
1 (1.3.14)
p1
X = (45/14.5)(1.40-1)/1.40 -1
= 0.382
k
had = ZavRT 1
k 1
X (1.3.15)
= 39,937 ft
whad
Pad = (1.3.17)
550
= 8,365 hp
ad = Pad/Pactual
= 8,365/11,647
= 0.718
= 71.8%
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
c) Axial Compressor
The steps one to eight of the procedure of the centrifugal compressors are
followed to determine the discharge temperature and power requirements
for an axial compressor under similar operating conditions.
= (1.40-1)/(1.40 x 0.816)
= 0.350
= (45/14.5)0.350
= 1.486
3) Discharge Temperature, T2
T2 = T1 x 1.486
= 560 x 1.486
= 832 oR
R = 53.34 ftlbf/lboR
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
n 1 / n
p 2
X = p1 1 (1.2.21)
= (45/14.5)0.350 -1
= 0.486
= 41,477 ft
whactual
Pactual = (1.3.24)
550
whp
=
550p
= 10,647 hp
Pad = 8,365 hp
ad = Pad/Pactual
= 8,365/10,647
= 0.785
= 78.5%
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
d) Reciprocating Compressors
k 1 / k
p 2
X = p1 1 (1.3.14)
= 0.286
X-factor = (45/14.5)0.286 -1
= 0.3821
= 39,907 ft
= (590/60) x 0.0783
= 0.77 lb/s
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
= 0.77 x 39,907/550
= 55.9 hp
Pactual = Pad/0.92
= 55.9/0.92
= 60.8 hp
k 1
T2 p 2 k
(1.3.18)
T1 p1
= (45/14.5)0.286
= 1.3821
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
T2 = 1.3821 x T1
= 1.3821 x 560
= 774 oR
Figures 6-1, 6-2 and Figure 6-3 obtained from NGPSA Data Book (1972)
provide quick method for centrifugal and reciprocating compressors
respectively.
a) Using the charts for establishing power demand for the centrifugal
compressor shown in the example in 6.3.1.b results P actual = 12,000 bhp
based on 60 -70 % adiabatic efficiency.
b) Using the chart for the sample shown in 6.3.1.d for a reciprocating
compressor the power demand is established as P = 61.1 bhp.
For processes when the material balance calculations performed by PCs the
power demand can be calculated quickly by the sanctioned GPC or HYSIM
programs. The required input data for these programs should be available
from the material balance. HYSIM can handle a wider range of gas
compositions than GPC. Selection of the program is the option by the user.
Adiabatic and polytropic efficiencies must be handled as separate input data
and multistage machines must be calculated stage-by-stage.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
Figure 6-1
HEAD
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
Figure 6-2
CENTRIFUGAL COMPRESSOR
HORSEPOWER DETERMINATION
EFFICIENCY CONVERSION
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 6.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL DESIGN PROCEDURES
DATE 06-94
Figure 6-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
7.1.1 General
Nearly all types of capacity control may be arranged for manual operation.
There are many examples, particularly in process industries, where changes
in demand are infrequent and slow enough to permit manual operation.
Automatic control systems are used in most applications and may often be
complex.
Automatic start and stop is almost entirely limited to use with electric motor
driven units although there are cases where turbine or gas engine drives can
be so arranged. The compressor is run at full load for a period and is then
stopped. This type of arrangement is usually used to maintain a relatively
constant receiver pressure in an air system.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
b) Suction Throttling
Suction throttling is used for dynamic units only and should never be
attempted with reciprocating or rotary type compressors without the
guidance of the compressor manufacturer. By throttling the flow to a
dynamic unit the gas density at suction is reduced, resulting in a smaller
mass flow for a given inlet volume flow and a reduction in power. The
drop in power is slightly offset by an increase due to increasing
compressor head which is caused by the lower suction pressure. In low
power machines throttling is carried out with a butterfly valve on the
intake; larger machines use inlet guide vanes.
For services where the normal suction pressure is low, beware of the
possibility of creating a vacuum by the use of suction throttling. This
could cause undesirable (or unsafe) in-leakage of air.
c) Discharge Throttling
d) External Bypassing
External bypassing of compressed gas back to the intake can be used for
continuous modulation of the compressor output but requires that it operate
at full load and capacity at all times and is therefore uneconomical at part
load. The returned gas must be cooled prior to its return to the suction to
avoid excessive discharge temperatures. This method of control is valuable
in a few process applications, usually for fine adjustments unobtainable by
other acceptable methods. It is applicable to all types of compressors and is
used with dynamic types for anti-surge control, see Section 7.2.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
e) Blow-off
f) Clearance
g) Valve Unloading
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
This section covers the anti-surge control systems used in the protection of dynamic
compressors. It should be understood that the primary function of these systems is
not to control capacity (as this is carried out by other control systems) but to
recognize the limit of stability under a variety of conditions of speed, compressor
vane position and pressure for values of gas flow and to ensure that under no
conditions does flow rate fall to the point where surge is initiated and is shown on
Figure 7-2 (a) and Figure 7-2 (b).
Minimum flow uses a predetermined flow as the set-point for the surge
protection controller (in this case a flow indicating controller, FIC), Figure 7-
3(b). Surge protection is activated when the flow (calculated from the flow
transmitted signal representing the pressure differential across an orifice plate
at the compressor suction), falls to the set-point and a portion of compressed
gas is bypassed from the discharge to the suction.
The bypass line contains a heat exchanger where gas cooling takes place to
prevent compressor overheating. For this system to work properly, the
compressor must be operating at constant speed with constant gas properties
and with constant suction pressure and temperature to prevent the surge limit
from rising above the set-point.
This system type, Figure 7-4, provides surge protection by changing the
compressor speed and thus changing the limit of stability with respect to
capacity. The surge protection controller in this system is the speed
indicating controller, SIC.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
Figure 7-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
Figure 7-2(a)
Figure 7-2(b)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
In a constant speed system, inlet guide vanes and stator vanes are used for
flow regulation. The principle of operation of the anti-surge system, Figure
7-6, is similar to that of the flow-speed system except that the set-point of the
surge protection controller is varied with the signal received from the
position transmitter, ZT representing vane angle. The amount of gas to be
bypassed is determined by the controller using input from the flow
transmitter, FT.
This system, Figure 7-7, is the most accurate of the more popular systems
because it is independent of compressor speed and suction conditions.
The surge protection controller determines the amount of gas bypassed from
signals received from the flow transmitter, FT, via the amplifying relay, FY,
and from the pressure differential transmitter, dpT.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
Figure 7-3(a)
Figure 7-3(b)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
Figure 7-4
Figure 7-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 7.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL CONTROL AND INSTRUMENTATION
DATE 06-94
Figure 7-6
Figure 7-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
The Fluor Daniel compressor and compressor auxiliary specification forms are listed
below. Many of these forms were extracted from the API standards.
The Compressor Requirements form provides an easy reference one page description,
with all the pertinent process information. This form is usually sufficient when
preparing preliminary quotations, and/or proposals.
When specifying a compressor competitive bid and purchase, the process engineer
will originate and issue the appropriate compressor data sheets along with the
auxiliary, and driver data sheets. Of course most of the information required to
complete these forms will be furnished by either the mechanical engineer or the
compressor vendor.
DYNAMIC COMPRESSORS
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
AUXILIARY EQUIPMENT
Cases shall include normal, rated, minimum conditions and other conditions
such as start-of-Run (SOR), End-of-Run (EOR) or fouled exchanger, etc.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
Compressibility (Z)
Relative humidity
Discharge pressure
Process engineer shall fill out Process Specification Form E-537 completely
as far as data are available.
Suction pressure
Suction temperature
Relative humidity
Compressibility (Z)*
Discharge pressure
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
a) Centrifugal Compressors
b) Reciprocating Compressors
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
This value shall include the pressure drop in the suction and
discharge pulse dampeners, intercooler, K.O. drum and some
allowance for interstage piping. If the responsibility is split for
supplying these items between compressor manufacturer, pulse
dampener vendor and installer, then the final pressure drop
coordination shall be followed up by the responsible process
engineer.
DS-617-1
DS-617-2
Centrifugal Compressor
DS-617-6
D6-618-1
DS-618-2
Reciprocating Compressor DS-618-6
DS-618-13
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 8.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL COMPRESSOR SPECIFICATION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
Air gap The annular air space between the rotor and stator in
which the magnetic field rotates.
Slip Ns N
Slip, S, is defined by: S
Ns
where:
Ns = synchronous speed
N = rotor speed
Synchronicity The condition that exists when the rotor turns at the
same speed as, and in step with, the rotating
magnetic field produced by the current in the stator.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
cross over tubes These are tubes connecting combustion chamber cans
to ensure an equalization of pressure.
bottom dead center The lowest position of the piston in its stroke.
top dead center The uppermost position of the piston in its stroke.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
The theory of electric motors is not part of the scope of this manual and is therefore
not covered here.
The ideal cycle for steam plant is shown by Figure 9-1. It is called the
Rankine cycle and comprises four processes which are described in Table 9-
1. A typical simple steam turbine plant is shown diagrammatically by Figure
9-2.
The process carried out by the steam turbine is the expansion of superheated
steam which is illustrated by that part of the curve between points 3 and 4.
For an ideal cycle this process is adiabatic and frictionless and therefore
isentropic.
The thermal efficiency and specific work of the plant is given as follows:
Efficiency
(H3 H 4 ) V1(p 2 p1 )
= (9.3.1)
H3 H 2
(H 3 H 4 ) (H 2 H1 )
= (approximately)
H3 H 2
H3 H 4
= (approximately)
H3 H1
Specific Work
where:
H = enthalpy, Btu/lb
p = pressure, psi
v = specific volume, ft3/lb
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
Figure 9-1
Figure 9-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
In real cycles there are losses in the turbine so the expansion process is not
therefore isentropic. It may be
The curve between points 3 and 4 in figure 9-1. The difference in entropy
between points e and 4’ is a measure of the losses in the system and the
overall turbine efficiency is obtained by comparing the work
Done by the which would have been done under an ideal system. Thus,
overall
Where,
H3 = enthalpy at turbine inlet, Btu/lb
H 4' = enthalpy at turbine outlet under real cycle, Btu/lb
H4 = enthalpy at turbine outlet under ideal cycle, Btu/lb
Ishould be noted that the cycle need not be closed as indicated in figure 9-2,
but could be open in which case the steam the trubine may be condensed but
not returned to the boiler.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
The ideal cycle for a gas turbine plant is the Joule cycle which is shown by
Figure 9-3. It comprises four processes which are described in Table 9-2.
The three major components of the system are a compressor which raises the
pressure of the working medium, a heater where heat transfer to the fluid
occurs and a turbine where the fluid is expanded; in a closed cycle a cooler is
necessary to remove heat from the fluid. In an ideal system the compression
and expansion processes are isentropic and the heat transfer processes occur
at constant pressure. Assuming no changes in potential and kinetic energy:
Wcyc = Wt - W c (9.4.3)
W cyc
cyc = (9.4.5)
Q 23
By assuming that the mass flow rate of air is much greater than that of the
fuel, that the specific heat capacity ratio is constant and that all components
operate without loss, efficiency can be further represented by:
(T3 T4 ) (T2 T1 )
cyc =
T3 T2
(9.4.6)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
Figure 9-3
Figure 9-4
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
which by substitution of
( K 1) / K
T3 T2 p 2
T4 T1 p1
reduces to:
Specific work
Process
Step Action and Equipment Involved Energy
Equation
1-2 Reversible adiabatic compression in a s -w = H2 - H 1
rotary compressor
= Cp (T2 - T1)
Subscripts:
1 = compressor inlet
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
2 = compressor outlet
3 = turbine inlet
4 = turbine outlet
a = air
act = actual cycle
c = compressor
cyc = cycle
f = fuel
i = ideal cycle
t = turbine
In a real gas turbine plant, shown diagrammatically by Figure 9-4, the cycle
is usually an open one with the cooling process omitted. The compressor and
turbine both operate with losses and the compression and expansion
processes are not therefore isentropic. They are represented on Figure 9-5 by
the curves between points 1 and 2 and points 3 and 4 respectively. The
heat transfer to the fluid is accomplished by use of a combustion chamber
which operates with pressure losses and this process is represented by the
curve from point 2 to 3.
Wc m a (H 2 H1 )
Wc (9.4.9)
c c
(m a m f )(H3 H 4 )
W ta (9.4.10)
t
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
Figure 9-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
The actual fuel required to raise the temperature from 2' to 3' is:
H3 H 2
mf
LHV b
(9.4.12)
where:
Thus, the overall cycle efficiency can be calculated from the following
equations:
Wact
cyc (9.2.13)
m f (LHV )
The heat cycle of the gas engine follows the constant volume curve shown in
Figure 9-6. Ideally it
assumes an adiabatic and isentropic compression of the charge, addition of
the fuel heat by instantaneous combustion and then adiabatic expansion of
the burnt gases.
The real heat cycle departs quantitatively from the ideal cycle in that:
The heat energy is not added instantaneously (the nearest approach to this
is violent detonation which soon leads to pre-ignition and cannot be tolerated in practice). The fuel
starts to burn before top center and continues for an appreciable time during expansion. Since it can be
shown that the cycle efficiency is dependent on the expansion ratio, it is evident that the fuel which
burns later is not used as efficiently as that burned at top center.
The specific heat of gases rises with temperature, so that the addition of a
certain quantity of heat does not produce the rise in temperature (and therefore pressure) which would
result if the specific heat were constant.
Figure 9-6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
Heat loss, with consequent falling off in pressure, occurs during burning
and expansion and as it is greatest at the highest temperature, this loss produces its effects throughout
the working stroke.
Since the process of evacuating the cylinder takes some time, the exhaust
valve or ports must be opened well before the end of the stroke, thus lowering the real expansion ratio.
The ideal heat cycle for the Diesel engine follows the constant pressure curve
illustrated by Figure 9-6(b). The chief difference between this cycle and the
constant volume cycle is that the pressure of combustion rises above that of
compression and then remains roughly constant for a part of the expansion
process. In practice, the Diesel engine follows more closely the dual cycle
Figure 9-6(c) which is a combination of the constant volume and constant
pressure cycles. The comments of Section 9.5.1 that differentiate real from
ideal cycles applies to the Diesel heat cycle.
ip
ti = (9.5.1)
1.415 cb m f LHVp
where:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
DH
cb =
LHVp
(9.5.2)
where:
bp
m = (9.5.3)
ip
The turbo-expander is used to obtain low temperature and refrigeration and its use as
a driver is secondary; while the power recovery turbine is used to recover the energy
from a high pressure and usually large volume fluid stream.
Qe
He (9.6.1)
0 .9 e
Qe T2
0.9e T1
(9.6.2)
Figure 9-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
The actual compressor work Wc, is this latter quantity, divided by the compressor
isothermal efficiency, c thus:
Qe T 2
Wc =
0. 9 e c T1
(9.6.3)
Qe
W = Wc
0.9
Qe T2 Qe
=
0.9 e c T1 0.9
Q e T2
= 1
0.9 e c T1
Qe T2 ecT1
W = (9.6.4)
0.9 ecT1
Qe( T 2 T1)
Wtheor = (9.6.5)
T1
Qe(T2 T1 ) / T1
W theor
= Qe T2 ecT1
W
0.9 ecT1
0.9(T2 T1 )ec
= (9.6.6)
T2 ecT1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 9.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL DRIVERS THEORY
DATE 06-94
It is well known that all parts of a machine which are subjected to recurring or
periodic forces are prone to vibrate. Even a small force, applied at regular intervals,
may set up a dangerous state of vibration. Such a vibration is termed a forced
vibration, as distinct from a natural or free vibration, which occurs when a part of the
machine is displaced from its normal static position, and then suddenly released and
allowed to oscillate freely.
The amplitude of a forced vibration depends upon two things, namely the frequency
with which the disturbing force is being applied, and the forces which tend to damp
out any vibrations set up, in short, the damping forces.
Every plastic body when vibrating freely does so with a certain definite frequency,
which is usually termed the natural frequency. If the frequency with which the
disturbing force is applied is the same as the natural frequency, it will be apparent
that, at first, the disturbing force will set up small displacements of the body, and that
during these small displacements the body will be displaced always in the direction
of the applied periodic force. Consequently, the disturbing force will be doing work
on the body, and so building up bigger and bigger amplitudes. This is the
phenomenon of resonance of synchronism, and is obviously a condition to be
avoided. When the frequency is different from the natural frequency, vibration still
occurs, but with small amplitude or movement, and only when the natural frequency
is approached does the amplitude tend to become large. Damping forces, due to fluid
friction, internal friction in the material, etc., always tend to limit vibration. In steam
turbine work, however, the damping forces are usually negligible.
The shaft, rotating at a high speed, is subjected to a periodic force having the same
frequency as the speed of rotation, owing to the small out-of-balance forces which
are inevitable, no matter how carefully the rotor is constructed and balanced. At a
certain speed, known as the critical or whirling speed, resonance occurs, and the shaft
whips or whirls.
The critical speed is always determined by calculation during the design stage, and
that the dimensions of the shaft are so chosen that the critical speed is well removed
from the normal running speed and in the case of turbo-generators from any speed
within the range from normal speed to overspeed. In turbines of moderate output, the
critical speed would be made from 1.2 to 1.25 times the rated full speed, giving for a
speed of 3,000 rpm a margin of 600 - 750 rpm at rated speed and of 300 - 450 rpm at
overspeed.
Shaft vibration may also be caused by a badly balanced rotor or a badly aligned shaft.
Another cause of vibration is a bent shaft caused by previous whirling, by the
unsymmetrical heating of the shaft and rotor, or some such cause.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
There are essentially two types of A.C. electric motors: Induction and synchronous.
The A.C. electric motor comprises a bearing mounted rotor which is able to
turn within a stator. A three phase alternating electric power supply is
applied to the stator or field winding which produces a rotating magnetic
field in the air gap. The rotating magnetic field crossed through, or "cuts" the
rotor winding and induces in it a voltage and thus a current. The induced
current reacts with the magnetic field and a torque is produced which causes
the rotor to turn. Clearly if the rotor is synchronous with the rotating
magnetic field, the latter no longer "cuts" the rotor winding and torque is
zero.
This never occurs with A.C. induction motors and there always exists a
certain amount of slip under load, typically 2-1/2 % for units of about 7 hp
to 1/2 % for larger units of about 1,350 hp. An induction motor will thus
always run at such a speed so that the induced rotor current can provide
sufficient torque to balance the load.
The A.C. induction motor may have either a squirrel cage or a three-phase
winding type of rotor.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The A.C. induction motor operates continuously on the same winding under start-up
and under normal running conditions and its design is necessarily compromised.
The synchronous motor, however, has a rotor with an induction motor type
cage which is used during start-up and a set of electro-magnets spaced
around its periphery which are used during normal running.
Once start-up has been achieved, i.e., the motor is running at about 95 %
operating speed, direct current is applied to the stator. Torque is developed
by the interaction of the rotor magnetic field and the stator current.
The characteristics of this type of motor are a very high efficiency and
complete synchroneity which means a high degree of speed control. The
high efficiency makes this type of motor attractive for large power
applications where power losses are expensive.
Table 10-1 shows speed combinations for multispeed A.C. induction motors.
It is possible to give an induction motor more than one pole arrangement and
thus more than one speed although this is not possible with synchronous
motors due to the complexity of their rotor. Multiple pole arrangements are
achieved by supplying a rotor with more than one winding of different pole
numbers or by using a P.A.M. (Pole Amplitude Modulating) winding which
is tapped off at different points to give two pole arrangements.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
speed motors.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Two Speed for 950/710 1140/852 6/8 1420/950 1704/1140 4/6 1420/560 1704/672 4/10
Constant Torque or
Fan Torque
Torque Only Three 950/710/560 1140/852/672 6/8/10 1420/950/710 1704/1140/852 4/6/8 2850/1420/560 3420/1704/672 2/4/10
Speed for Fans
710/560/470 852/682/564 8/10/12 1420/950/470 1704/1140/564 4/6/12 2850/710/560 3420/852/672 2/8/10
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
A.C. electric motor gear drives have been successfully developed to handle
most speed and power applications, within limits. They are most useful for
low speed use where a high speed motor with a reduction gear is preferred to
the higher cost and larger size (attributable to the larger number of rotor
poles) of a standard low speed motor. The comparative costs of a standard
and geared 75 hp motor are given in Figure 10-1 where reference is made to
the cost of a standard four pole motor. It is seen that for motors with eight
poles or more, a geared motor is cheaper.
The sizes of the two types are compared in Figure 10-2 where, for example;
an 11 kW, eight pole standard motor, is heavier and larger than a four pole
geared unit of the same power and speed output.
A.C. electric motor speed may be varied by one of the following methods:
This device is used also by other types of drive and is therefore discussed
in Section 10.6.
This method of speed variation is capital intensive and in the past it was
rarely used in the U.S. It is installed more frequently in Europe where
power costs are higher. In recent years, however, usage picked up in the
U.S. and in certain applications became economically competitive. It is
used mostly for medium and large load applications where variable speed
and/or associated capacity control can not be achieved by other type of
drivers. This method comprises a complex arrangement of electrical
components that convert the characteristics of a power source into one
that may be manipulated to vary both voltage and frequency. In the
future with the availability of more sophisticated electronic controls this
method may become more widespread. (See recent Centrifugal
Compressor application in Section 18.0)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
There are means to alleviate this problem, they are discussed in Section
13.1.1.
Motor efficiencies depend on the motor size and type, and on the load
imposed on the motor. Generally, induction motor efficiencies vary from 75
- 94 % for smaller machines to 97 % for larger motors; this is illustrated by
Figure 10-3. Table 10-2 shows the variation of efficiency of currently
available high efficiency induction motors with 2, 4, 6 and 8 poles. At
reduced loads the efficiencies are lower by 1-2 %. Synchronous motors are
more efficient, particularly at larger sizes. Figure 10-4, shows efficiency
variations for synchronous motors.
Motors used with reduction gearing have slightly reduced efficiencies though
gearbox efficiencies as high as 98 % are common.
A.C. electric motors are very reliable machines and if properly maintained and
protected from electrical damage from dirt, moisture etc., (by providing the correct
motor enclosure) they will continue to perform for many years without loss of
efficiency, speed or power output. Maintenance of motors is generally uncomplicated
and is usually limited to bearing replacement and reconditioning of insulation windings
(which are subject to aging). No derating of electric motors is necessary.
The steam turbine, Figure 10-5, comprises two main components: a casing which
contains the working fluid and a rotor mounted within the casing. The steam enters
at the high pressure end of the turbine and passes through guide vanes or inlet nozzles
which direct the steam at a moving row of blades. The steam turbine may have a
number of fixed and moving rows of blades (stages) through which the steam is
directed and is made to undergo stages of expansion. The blading shape, of which
there are two types determines the way in which the steam is expanded.
Pure impulse blading, Figure 10-6, is shaped such that the whole pressure drop in a
stage occurs at the stationary nozzles so that the heat energy of the steam is converted
into the kinetic energy of the steam jet issuing from the nozzles. The steam jet so
produced does work on the rotor by impinging on its blading.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-1
Figure 10-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-3
Figure 10-4
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-6
Figure 10-7
REACTION STAGE
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The thermal efficiency of the turbine cycle may be improved by using bled
steam feed heating (regenerating). A fraction of the total amount of steam
entering the turbine is extracted at a point in its expansion in the turbine and
utilized for preheating the condensate before it enters the boiler. The
regeneration system is shown diagrammatically by Figure 10-9 and the
effect of regeneration on a particular turbine system is illustrated by Figure
10-10. It should be noted that efficiency improves not only with an increased
number of regeneration stages but also with turbine inlet pressure. Thus it
may be concluded that the number of regeneration units that are
economically justified in a system increases with pressure.
Other than regeneration and reheating, inlet conditions also affect the thermal
efficiency of the steam turbine cycle. The effects upon efficiency are shown
in Figure 10-13 where it can be seen that an increase in both pressure and
temperature show improvement but that the rate of efficiency improvement
falls with pressure.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Steam turbines are available for duties from 100 hp and up with speeds
generally in the range of 1,500 rpm to 15,000 rpm. The characteristics of
steam turbines are shown in Table 10-4. The speed of a turbine is relatively
flexible and often may be varied within 70 to 105 % of its rated speed. The
means by which this is accomplished is discussed in Section 13.2.
Table 10-4
Figure 10-15 indicates the ranges of the most widely used turbines. The
majority of those under 1,350 hp and 5,500 rpm are single stage machines
and at 1,800 rpm and 3,600 rpm are the turbo-electric generator drives with
capacities up to 1.5 x 106 hp.
The consumption of steam varies significantly for different types of turbine and is
best determined by consultation with the machine supplier. Generally, steam
consumption is made up of two parts. A portion of steam is required to turn the
turbine under no load to overcome back pressures and losses and is approximately a
fixed quantity. The second portion of steam performs the work in the turbine and is
directly proportional to the turbine output for machines that are t hrottle governed.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-8
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-9
Figure 10-10
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-11
Figure 10-12
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 18
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 19
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-15
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 20
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The steam consumption rate is given for various multistage units in Table
10-3. Back pressure steam turbines use slightly more steam than condensing
turbines because the fixed portion is larger due to work done against the back
pressure.
Steam turbines are very reliable machines but they do suffer long term
deterioration which affects their performance. Among the problems
encountered with steam turbines are blade erosion, blade corrosion and blade
deposits which affect the efficiency of steam expansion, and gland leakage
which permits loss of steam energy. The cause of these problems is
discussed in Section 15.2. It is sufficient to point out that the aging of a
steam turbine and its subsequent loss in efficiency should be taken into
consideration at design stage. A value of 5 % is usually taken to allow for
such losses.
For condensing turbines a drop in design vacuum of at least 0.6 psi is quite
common. The effect on turbine power heat rate also depends on steam inlet
conditions but the combined effect of reduced turbine efficiency and loss of
vacuum can be 10-15 % in most applications after about five years
operation. For critical services involving a condensing turbine, a
conservative power margin is therefore recommended.
Gas turbines are open cycle machines using air as the working medium and
burning relatively clean fuels. They comprise three main components: a
compressor, a combustion chamber and a turbine. A simple gas turbine
system components are shown in Figure 10-16. Each component performs
one of the processes in the cycle, refer Section 9.4.2, which are discussed as
follows.
a) Compressor
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 21
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-16
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 22
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
b) Combustion Chamber
High pressure air from the compressor, and fuel from an injector enter
the chamber where combustion occurs producing hot gases which are
passed to the turbine. The combustion chamber is designed such that
combustion occurs at maximum efficiency and that the heat transfer
process follows the constant pressure curve as closely as possible. This
leads to consideration of the following points.
1) Pressure Drop
2) Combustion Efficiency
4) Stability
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 23
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
c) Turbine
In gas turbine systems, the axial flow type of turbine is almost always
used. Its operation is similar to that of steam turbines which has been
covered in Section 10.2 of this handbook, and only departures from
steam turbine characteristics will be covered here.
Air Cooling
Water Cooling
The simple gas turbine system comprises only the three main components
already discussed. The power required to drive the air compressor is
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 24
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The gas turbine differs from other prime movers in being particularly
sensitive to inlet, or ambient, air temperatures as shown by Figure 10-17.
The output, curve (a), increases markedly at low air temperatures (which
may be important in peak load applications where peak loads occur in
winter). The efficiency, indicated by the fuel consumption curve (b), also
improves but less markedly; this is mainly because at a given speed, the
compressor aspirates a mass of air roughly proportional to the air density.
Therefore, the mass flow is increased both by low temperature, and high
atmospheric pressure. There are increased losses due to the change in
pressure ratio resulting from a greater volume flow through the turbine,
but in most cases these can be ignored.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 25
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-17
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 26
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The amount of fuel required to maintain the same turbine inlet temperature can be
reduced by the use of a regenerator thus increasing the thermal efficiency.
Improvements in efficiency of about 40 % may be achieved; however, output is
unaffected by regeneration. The point of maximum efficiency in the regenerative
cycle occurs at a lower pressure ratio than that of the simple cycle but the
optimum pressure ratio for the maximum work is the same in the two cycles.
d) Intercooled-Regenerative-Reheat-Cycle
There exists a wide variety of possible gas turbine arrangements other than
those already discussed. Only the most important of these will be discussed
briefly.
This system combines the gas turbine with the steam turbine, making it
particularly attractive for electric utilities and process industries where
steam is being used. The arrangement is shown in Figure 10-19.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 27
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
b) Steam Injection
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 28
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-18
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 29
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-19
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 30
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-20
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 31
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Table 10-5
a) Speed Variation
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 32
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The popularity of the single shaft gas turbine is due to its low cost and
compactness. Its disadvantage is a relatively low operating speed range
and its sensitivity to atmospheric temperatures. The low operating speed
range is caused by the following:
At low speeds the turbine power is decreased by low air flows. At low
air flows the decreased back pressure at the turbine inlet may require a
reduced turbine inlet temperature to keep the exhaust temperature within
design limitations. This results in a further loss of power. The normal
operating range is given in Figure 10-21 for a single shaft gas turbine.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 33
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-21
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 34
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-22
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 35
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
b) Start-up
10.3.6 Fuels
The gas turbine's major advantage is its flexibility with regard to fuel type.
Gaseous fuels include natural gas, process gas, coal gas and vaporized fuel
oil gas. The requirements of a suitable fuel are listed below.
The heating capabilities of a fuel affect the overall size of the plant.
Generally, liquid fuels show small heating value variations but gaseous
fuels can vary from 300 Btu/ft3 for process gas to 1,050 Btu/ft3 for
natural gas. The fuel system for process gas will of necessity be larger
than that for natural gas to accomplish the same heating effect.
b) Cleanliness
c) Corrosivity
Gas turbines suffer from the same long term deterioration as steam turbines,
but in addition are subject to temporary performance deterioration due to
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 36
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
deposition. Deposition and fouling may occur in the fuel system and in the
hot sections of the turbine. Certain compounds contained in the fuel may
form a residue of combustion which may cause fouling as solid particles.
Fouling also occurs from deposition of oil or water soluble traces of metallic
elements such as sodium.
Gas turbines are generally either of the aeroderivative type, developed for the
aero industry but down-rated for industrial use, or of the industrial type
developed specifically for industrial applications.
The aeroderivative gas turbine is likely to cost less than the industrial gas
turbine but more to maintain. The main difference in the repair procedure is
that in the event of an internal failure the aeroderivative type is usually
removed and overhauled in a workshop. This is often necessitated by the use
of special tooling, delicate components and critical settings during assembly.
A replacement gas turbine may be installed within a few hours minimizing
plant downtime but usually at high cost.
The industrial gas turbine, which typically has an overhaul life of 25,000 -
100,000 hours, is usually repaired on site and is likely to require attention
less often than the aeroderivative type which has an overhaul life of 10,000 -
40,000 hours.
The aeroderivative gas turbine is the more efficient type (up to 37 %), but
this may be matched by regeneration in the industrial type.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 37
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Gas and diesel engines may be divided into two categories determined by
their method of operation. The first class includes engines that operate on the
two stroke cycle which comprises a power stroke and gas exchange once per
revolution. Two stroke engines are used either for very small or very high
power applications. The second class of engine operates on a four stroke
cycle.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 38
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 39
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Since the inlet and exhaust pressures are above ambient the induction
temperature is higher and more fuel is burnt in the engine. The cylinder
pressure throughout the cycle is substantially higher than for a naturally
aspirated cycle. In practice, the compression ratio of turbo-charged diesel
engines must be reduced to avoid an excessive maximum cylinder pressure.
For gas engines the pressure ratio is limited by the fuel quality; the increase
in induction and thus compression temperature with supercharging increases
the probability of detonation. To avoid detonation, lower pressure ratios and
higher quality fuels are used.
Diesel engines operating on heavy residual fuel oils require two fuel systems,
a heavy fuel oil system for normal operation and a light fuel oil system for
starting and stopping.
The operating characteristics of the gas and diesel engine, whether two or
four stroke, are basically the same regardless of fuel type. The speed and
load carrying capacity (which can range from zero to full torque for all
speeds within the operating range) is varied by adjusting the fuel input. All
engines use a governor, refer to Section 13.4, to control the fuel input rate
and maintain constant speed under load variation. The characteristics of
diesel and gas engines are shown in Table 10-6.
Diesel and gas engines are available in sizes up to 1,500 hp and diesel
engines up to 40,000 hp. Efficiencies are in the range 28 % - 43 %.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 40
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Table 10-6
In general, the fuel must have a heat capacity of over 600 Btu/ft 3. In
addition, gas engines require that the fuel will vaporize in the carburetor.
Diesel engines will burn any fuel that can be injected, provided that it will
burn under controlled conditions, possess sufficient lubricity to lubricate the
injection plungers, will supply enough heat, and is grit-free. Preheating of
the fuel will lower viscosity.
10.4.6 Maintenance/Reliability
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 41
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
10.5.1 Turbo-expanders
The pressurized process stream is guided radially into the rotor by a set
of primary nozzles which are a series of vanes forming nozzles jetting
the gas tangentially and inwardly into the rotor. The nozzle vanes are
held between two flat rings and are pivoted so that they can be opened or
closed together to vary the nozzle throat areas. This enables the flow to
be varied widely through the expander without wasteful throttling: all the
expansion energy is recovered on the rotor. The variable nozzles thus
behave as a throttling valve but without throttling losses and can easily
be controlled by conventional instrumentation.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 42
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-23
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 43
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
c) Turbo-expander Capabilities
The potential for power recovery from liquid streams exists whenever a
liquid flows from a high pressure source to one of lower pressure in such a
manner that throttling to dissipate energy occurs. A power recovery turbine
may be installed into a process system to behave as a pressure reducing valve
while at the same time providing a source of power. An example of such an
application is illustrated in Figure 10-25 where a recovery turbine is used to
power a pump in another process stream.
Like a pump, a power recovery unit will follow its characteristic curve
and seek a point at which its particular relationship to operating
conditions of head, capacity speed and power output is satisfied. In most
applications the head available is largely composed of static pressure
difference (which is nearly constant) and varies only with flow related
line friction losses. Thus the unit behaves as an orifice in a relatively
fixed differential system with a definite flow limit and thus with definite
torque and horsepower limits.
Speed control of the unit may be necessary to match the generated power
of the turbine with the absorbed power of the pump at the common
speed. Speed control is accomplished by throttling the process flow,
refer to Section 13.5.2.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 44
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-24
COMPONENTS OF A TURBO–EXPANDER
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 45
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-25
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 46
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
d) Over Capacity
At design head, capacity does not change markedly with speed so that
once the design point has been passed the unit behaves as a restriction in
the line. Little or no benefit is realized from any over-capacity in terms
of fluid flow available to the unit.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 47
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-26
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 48
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-27
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 49
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
The simplest form of rigid coupling and the type normally used when high
speeds and large powers are involved is the integral coupling where the
connecting flange is formed as part of the forging from which the shaft or
rotor is machined. A disadvantage of this type is that all bearings, glands
etc., must be split to be assembled and shaft alignment must be kept within
very tight tolerances to prevent excess shaft stressing and bearing
overloading.
The drive and driven shafts are terminated in drive cones, Figure 10-28,
which are connected by balls of equal diameters mounted on spindles.
Speed control from 30 % to 300 % is achieved by varying the spindle
angle. With the spindles in the M-M position output speed is equal to
that of the input.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 50
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
pump and sets up a vortex of oil which drives the runner like a turbine
wheel. The runner is connected to the output shaft. By changing the
amount of oil in the vortex the output speed is adjusted. This type is
used in applications up to 350 hp, though by using an external oil
reservoir and a pump to control the amount of oil in the vortex, the
hydraulic coupling can be used in applications from 100 hp to 2,000 hp.
Continuous Vee Belt drives are essentially friction drives and therefore be
used only for low power transmission, usually to provide an output speed
different from that of the input. This is achieved by using different sized
pulleys on the input and output shafts. They are most commonly employed
with small electric motor drivers where input shaft speed does not exceed
3,000 rpm and power transmitted is less than 70 hp.
Gear units are used to transmit power from the driver to the driven equipment
at an output speed different from that of the input. The most commonly used
gear units employ spur gears for general purpose applications because of
their relative economy and simplicity of construction. They do not produce
axial thrust but are very noisy at high speed. High speed applications require
units with helical or spiral bevel gears which will sometimes require a
balancing idler wheel. The tooth action of this type of gear produces axial
thrust which must be catered for in the box design. Worm and wheel gears
are used for low speed applications and will permit large speed reduction
ratios.
Generally, gearboxes require lubrication to lubricate the teeth and to carry the
heat away. Commonly, the oil is sprayed over the gears, collected in a
reservoir and then passed back to the top of the gearbox via a water cooled
heat exchanger.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 51
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-28
Figure 10-29
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 10.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 52
PROCESS MANUAL DRIVER DESCRIPTION
DATE 06-94
Figure 10-30
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 11.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DRIVER SELECTION
DATE 06-94
As can be seen the use of gas turbines is not applicable in the smaller ranges
while gas and diesel engines, which have low power to weight ratios, are
limited by physical size to outputs of less than about five megawatts.
Electric motor size is limited by the problems of high starting current and
output speed is limited by the frequency of the power source. Steam and gas
turbines are also high speed machines and cannot therefore be used for low
speed equipment such as reciprocating compressors without the use of
expensive gearing.
Table 11-1
Safety considerations
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 11.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DRIVER SELECTION
DATE 06-94
0 - 1 MW 1 MW - 5 MW 6 MW - 40 MW Output
Shaft Speed
rpm
Notes:
(a) Use of motors is restricted by starting and voltage stability considerations.
(b) Use of steam turbines is restricted by steam availability
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 11.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DRIVER SELECTION
DATE 06-94
gas/diesel engines are variable speed machines and are therefore suited to:
Although electric motors are potentially the least flexible process drive, they
give the highest reliability at a low installed cost. They are also suitable for
both infrequent use and the smaller sized motors for frequent starting. A
comparison of driver reliabilities and relative process availabilities, Table 11-
3, shows that steam turbines are equally reliable but are used mainly for
continuous running applications as they are not suited to frequent starting.
Both of these driver types also require little maintenance thus keeping
downtime to a minimum. For large driver applications, such as for
centrifugal compressors the problems of start-up and shutdown must also be
considered. Steam turbines are often selected where electric motor start-up
currents are prohibitive. They may be directly connected to the driven
equipment which can be started without speed increasing gears.
Table 11-3
REALATIVE DRIVER
RELIABILITY/AVAILABILITY
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 11.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DRIVER SELECTION
DATE 06-94
In these plants choice will normally be between electric motors or steam turbines.
Generally, the electric motors are used for both standby and duty process equipment
with the steam turbine being allocated to critical services, such as those listed in
Table 11-4, where operation is essential during power failure. Steam turbines may
also be selected to satisfy the plant steam balance. The driver selection procedure
starts by selecting the drivers that may be used for particular applications based on
the required capacity, speed etc. (More than one driver type may satisfy these
requirements). The selection process continues by considering the type of energy
available for the drivers. The selection process is shown in Figure 11-1. Generally, if
a particular form of energy is readily and inexpensively available then that energy
should be used. Low operating costs will usually compensate for the capital outlay of
the equipment and services.
Overall energy consumption levels and costing should however be reviewed together
with process integration concepts to determine an optimum configuration.
Table 11-4
For an offshore oil production facility, major power consumption is associated with
the compression of associated gas and the availability of relatively cheap gas means
that energy consumption levels are less critical than for onshore installations. Wide
use is therefore made of gas turbines.
The problems of gas turbine starting is overcome by using the gas to drive a turbo-
expander which in turn is used to bring the gas turbine up to starting speed. The
procedure of Section 11.2 may be used for driver selection for offshore facilities
though in addition to the considerations already discussed, the weight of drivers is of
importance in order that platform topside weight may be minimized.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 11.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DRIVER SELECTION
DATE 06-94
Figure 11-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Refer to Section 16.2 of this manual for applicable codes and standards.
12.2.1 General
Table 12-1
Motor Rating
Voltage Levels
Speed
Motor Temperature Rise
Starting Currents
System Voltage Stability
The selected motor size for any process service must include an appropriate
design margin which is provided in the appropriate specification and the API
Specifications listed in the preface.
Electric motors are available in a range of standard sizes which are the same
for both 50 Hz and 60 Hz supplies.
These are listed in Table 12-2 with preferred motor voltages given in
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
kW hp kW hp kw hp
0.25 0.33 168 225 7,500 10,000
0.37 0.5 185 250 8,250 11,000
0.55 0.75 200 270 9,000 12,000
0.75 1 224 300 9,750 13,000
1.1 1.5 260 350 10,500 14,000
1.5 2 300 400 11,250 15,000
2.2 3 337.5 450 12,000 16,000
3 4 375 500 12,750 17,000
4 5.5 450 600 13,500 18,000
5.5 7.5 525 700 14,250 19,000
7.5 10 600 800 15,000 20,000
11 15 675 900 16,875 22,500
15 20 750 1,000 18,750 25,000
18.5 25 937.5 1,250 20,625 27,500
22 30 1,125 1,500 22,500 30,000
30 40 1,312.5 1,750 24,375 32,500
37 50 1,500 2,000 26,250 35,000
45 60 1,687.5 2,250 28,125 37,500
55 75 1,875 2,500 30,000 40,000
75 100 2,250 3,000 33,750 45,000
90 125 2,625 3,500 37,500 50,000
105 140 3,000 4,000 41,250 55,000
110 150 3,375 4,500 45,000 60,000
115 155 3,750 5,000 48,750 65,000
120 160 4,125 5,500 52,500 70,000
125 167 4,500 6,000 56,250 75,000
132 175 5,250 7,000 60,000 80,000
140 190 6,000 8,000 62,500 90,000
150 200 6,750 9,000 75,000 100,000
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Table 12-3
The time required to accelerate the motor to full speed is a function of the
motor torque and driver torque versus speed. The net accelerating torque at a
given speed is the difference in motor torque and driver torque. These torque
characteristics must be considered in selecting the motor for large drivers. It
should be noted that for compressors or pumps driven by large synchronous
motors, the torque requirements must usually be reduced during starting by
unloading the compressor or pump.
It should be noted that the electrical system voltage stability may limit the
maximum size of electric motor driver utilized in any design. This relates
directly to system stability on both starting and tripping the motor. As a rule
of thumb, for preliminary evaluation purposes, the maximum size process
load should not exceed 25 % of the total plant or system demand.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Table 12-4
MOTOR SPEEDS
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
The type of turbine selected will usually depend on the overall steam balance
considerations. Condensing turbines are generally applicable only to large
loads such as drivers for turbo-generators or large compressors and have
found reduced process plant applications in recent years as a consequence of
the reduced overall cycle efficiency. A summary of overall considerations
relating to steam turbine application and systems design is shown in Table
12-5.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Table 12-5
Turbine type
Turbine efficiency
Turbine cost will increase with pressure and temperature, alloy steel
being required above 750 oF. The selection of pressure levels for turbine
drivers will take into consideration turbine costs, overall steam system
design and costs. In a refinery or petrochemical plant there will usually
be turbines at more than one pressure level.
b) Steam Quality
c) Special Precautions/Hazards
Turbines must not be operated close to their critical speeds. API 611 and
API 612 specify criteria for critical speeds relative to operating speeds.
An independent emergency trip device and a shut-off valve which is
separate from the speed control valve, are required.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
d) Condensers
Condensers for condensing turbines may be shell and tube water cooled
condensers or air cooled condensers. Auxiliary equipment will include
vacuum ejectors, condensate drums and pumps.
e) Equipment Sizing
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
or:
11.4 lb/hphr
Theoretical steam rate tables such as Table 12-6 may also be used to
determine steam rates.
The actual steam rate is shown in Table 12-7 for single, five, seven
and nine stage turbines and as discussed in Section 10.2.3, it is seen
that efficiency significantly increases with the number of stages and
that the increased number of stages corresponds to larger turbine
power outputs. For each stage, as characterized by diameter and
speed there is a power drop that gives the best efficiency provided
that there is sufficient steam to fill the stage so that it operates with
minimum friction and windage loss per lb of steam.
Curves such as those of Figure 12-1(a) and (b) can be used for estimating
steam rates for single stage turbines only. Consider a steam turbine
operating at the following conditions:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
10) By using Figure 12-1(a) and (b) for other turbine wheel diameters, a
selection table such as Table 12-8 can be prepared for comparison.
From this table the most efficient turbine can be selected and
balanced against price for the steam conditions of the above
example. It is apparent that for a turbine output of 225 kW (301.7
hp) the 710 mm (28") diameter bladed unit achieves no gain over the
560 mm (22") turbine because of increased power losses while for
560 mm (22") versus 460 mm (18") the gain is small and may be
offset by higher capital cost.
150 psig 200 psig 250 psig 400 psig 600 psig 600 psig 850 psig 850 psig
Exhaust 367 oF 388 oF 500 oF 750 oF 750 oF 826 oF 826 oF 900 oF
Pressure 61 oF S.H. 270 oF S.H. 311 oF S.H. 304 oF S.H. 266 oF S.H. 340 oF S.H.
psig lb/hphr lb/hphr lb/hphr lb/hphr lb/hphr lb/hphr lb/hphr lb/hphr
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-1(a)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-1(b)
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Diameter Rate
kg/kWhr KW kW kg/hr kg/kWhr
mm (in) (lb/hphr) (hp) (hp) (lb/hr) (lb/hphr)
360 27.17 2.24 227.24 6,174.11 27.44
(14) (44.67) (3.00) (304.73) (13,611.73) (45.11)
460 23.51 6.34 231.34 5,438.80 24.17
(18) (38.65) (8.50) (310.23) (11,990.38) (39.74)
Steam flowrate can be calculated using a Mollier Diagram for steam (i.e.,
an Entropy/Enthalpy Diagram).
The source for the Mollier Diagram used below is Elliott Multivalve
Turbines, Bulletin H-378 which is readily available from them.
From the Mollier chart at inlet conditions of 42.38 bara (614.5 psia) and
399 oC (750 oF) the following can be read off:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 15
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
TSR
ASR = kg / Whr
where:
η = turbine efficiency
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 16
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-2
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 17
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 18
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-4
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 19
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-5
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 20
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Thus in the example case, inlet condition of steam is 42.38 bara (614.5
psia) at 399 oC (750 oF). Using the Mollier chart, follow the isobaric line
of 42.38 bara (614.5 psia) until it crosses the saturation line. Where the
isothermal line crosses this point gives the saturation temperature of the
steam. At 42.38 bara (614.5 psia) the saturation temperature on the
saturation line is approximately 252 oC (486 oF). Therefore degrees of
superheat is given by: 399 - 252 = 147 oC (264 oF). From Figure 12-2
(note that at the outlet condition of 4.48 bara approximately 2.4 % of the
steam has condensed), SCF = 1.03
From Figure 12-4, assuming a rated speed of 7,000 rpm and turbine
rating of 5,000 kW, speed factor is 0.955:
ASR =
TSR
SCFxBExSF
7
=
1.03x 0.73x 0.955
where:
The outlet condition of steam can be found from the Mollier chart as
follows:
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 21
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
The slope of the line from the steam inlet conditions, H 1, to the actual
outlet conditions at Ha2 gives the system efficiency, 0 % efficiency is a
horizontal line, i.e., at constant enthalpy, 100 % is a vertical line, i.e., at
constant entropy.
The power output and efficiency of the turbine is very dependent upon the
fuel firing temperature. In general, every 100 oF decrease in firing
temperature will result in a 10 % decrease in the machine output and 1 % to
4 % decrease in machine thermal efficiency. The maximum firing
temperature is largely dictated by mechanical and corrosion limitations;
consequently, the selection of fuel is very important in turbine design.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 22
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
The gas turbine supplier should be consulted regarding fuel consumption and
developed power.
The engine heat losses as percentages of heat input are shown for various gas
engines in Table 12-10. Plant fuel costs chargeable to power production can
be reduced if heat losses can be utilized to provide process or other heating.
401 - 800 32
801 - 3,000 38
over 3,000 43
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 23
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 24
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Table 12-10
HEAT BALANCE FOR A PARTICULAR TWO AND FOUR CYCLE GAS ENGINE
WITH AIR AND WATER COOLING
Two Four
Cycle
Water Air Cycle
Atmosp Superchar
Cooled
Btu/hp % Cooled
Btu/hp % heric
Btu/hph % ged Air
Btu/hphr %
hr hr r
Heat input (LHV) 8,013 .... 7,679 .... 8,572 .... 6,900 ....
Lube Oil 511 6.40 559 7.2 500 5.80 334 4.80
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 25
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
12.6.1 Turbo-expanders
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 26
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Figure 12-7
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 27
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Mechanical Efficiency of
power transmission is: - 100 % for direct coupling
- 95 - 97 % for fluid coupling or gear
coupling at full load
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 28
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 12.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 29
PROCESS MANUAL DRIVER DESIGN PROCEDURES
DATE 06-94
Reciprocating
Integral - - - 1.05
Separate 1.1 1.15 1.1 1.1
Reciprocating
Integral - - - 1.05
Separate 1.05 1.1 1.05 1.05
Pumps
Centrifugal 1.1(b) 1.15 1.10 1.10
Reciprocating 1.00 - 1.0 1.0
Vacuum 1.05 - 1.05 1.05
Notes:
(a) The service factor for gas turbines includes a 5 % allowance for fouling of the driver during
service.
(b) For pumps specified in accordance with API Standard 610, electrical motor drivers (Section
3.1.2 of the Standard) shall have power ratings, including service factor, if any, at least equal
to the following percentage of pump rated power:
<25 hp 125
30 - 75 hp 115
100 hp 110
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
A.C. electric motor control is divided here into the following categories:
Start-up
Braking
protection
b) Star-delta Starting
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
c) Part-winding Starting
This method uses a motor with an additional winding that is used only on
start-up and which draws 50 % of normal start-up current resulting in
50 % start-up torque. Disadvantages are the fixed value of available
torque and possible imbalance. It should only be used in applications
requiring infrequent start-up.
a) Plugging
b) Magnetic Brakes
These are used to obtain quick, accurate stopping and to hold the load
after stopping. Most brakes are electrically released and spring-set, so
that braking will be obtained even though an electrical failure occurs.
Disk-type brakes are supplied for mounting directly on the end of a
motor. Shoe-type brakes are supplied with floor mounting bases.
a) Overload Protection
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
d) Undervoltage Protection
This ensures that motors are electrically isolated when a power outage
occurs to prevent excessive system starting current surges when power is
re-established. It is also unsafe to have drives starting indiscriminately
when electrical power is resumed.
e) Surge Protection
Steam turbine speed is invariably controlled by throttling the steam with a supply
valve upstream of the machine. There are four cases for control:
The required speed is predetermined and fixed and the duty of the control
system is to maintain that speed. The control signal comes directly from the
turbine, using either a mechanical, mechanical-hydraulic or electrohydraulic
system.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
The control signal comes from a process instrument and directly regulates the
throttling valve.
3) Speed Limitation
4) Vibration Limitation
a) Speed Governor
b) Speed Changer
A device which varies the set point of the speed. Item (b) of Figure 13-1
illustrates one type of speed changer.
c) Governing Valve
A simple type of steam control valve is shown by Item (c) of Figure 13-
1. It is operated directly by a link from the governor and is thus part of
what is known as a direct acting flyball governor system. Excessive
speed will tend to force the weights apart which push the spindle to the
right and via the link, throttle the steam supply to the turbine.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
The force required to position the steam control valve limits the use of direct
acting systems. The mechanical-hydraulic system overcomes this limitation
by using the governor output to regulate the flow of high pressure oil which
is used to operate the valve. The components of such a system are listed and
described as follows and illustrated by Figure 13-2.
a) Pilot
b) Servomotor
The servomotor, Item (b), is operated by the high pressure oil and is used
to translate the differential pressure between the servomotor's upper and
lower cavities into vertical movement of the servo spindle which is
directly connected to the steam throttle valve.
The electro-hydraulic speed control system has advantages over the control
systems already discussed. These are briefly:
More accurate speed control
Figure 13-3 shows a speed sensing device that may be used in an electro-
hydraulic control system. It comprises a toothed wheel which, as it
rotates, generates small electrical pulses in a pickup. The pulses
constitute a digital input to the amplifier which produces a signal which
drives an electrohydraulic convertor. This device uses the electrical
signal to control the hydraulic pressure in an oil line to the pilot.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
Figure 13-1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
Figure 13-2
MECHANICAL-HYDRAULIC SPEED
GOVERNING SYSTEM
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
Figure 13-3
ELECTRO-HYDRAULIC SPEED
CONTROL SYSTEM
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
b) Hydraulic Speed/Control
All steam turbines, except the smallest, are equipped with an emergency or
runaway governor, whose function it is to shut off the steam supply to the
unit in the event of excessive speeding arising from any cause. To ensure
absolute reliability the emergency governor is usually fitted to the turbine
rotor.
Vibration monitors and controls are fitted to large steam turbines for the
purpose of detecting and monitoring vibration and for protecting the unit
from abnormally high vibration. They are usually fitted to the pedestal at the
high pressure end of each turbine stage and comprise pickup units, an
electronic amplifier, indicating instruments and recorder movements.
Proximity monitors are located at the shaft between the driver and the driven
equipment to ensure alignment within tolerances during operation.
The gas turbine is provided with a control system, by the manufacturer, which is
responsible for three functions:
Steady running
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
To carry out these functions the gas turbine control system requires input
signals provided by monitoring the following monitoring devices:
a) Speed Monitoring
b) Overspeed Protection
The panel receives a voltage signal from a separate speed sensor usually
mounted on an accessory gear or shaft. It usually initiates trip at 110 %
of maximum design speed.
c) Temperature Control
e) Vibration Protection
f) Flame Detection
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 11
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
The control panel, using temperature and speed inputs, will maintain the gas
turbine speed to its set level by fine adjustment of the fuel supply to the
combustor using modulating solenoid valves or pneumatic control valves.
Engine-governing systems for diesel and gas engines may be broadly divided into
two categories:
Those which control not only speed but load as well to achieve a preplanned
program of power output in response to one or more external conditions or
demands.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 12
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
System response time is dependent upon the engine type, the time required to
convert a fuel-output change to a torque-out change, the inertia of the
rotating assembly, the basic speed, and the number of cylinders.
a) Overspeed Governor
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 13
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
c) Fuel-Air-Ratio Control
These controls provide for visual and/or audio alarm and shutdown of
the engine when some malfunction, such as excessive temperature or
insufficient pressure, occurs. A wide variety of control features are
available, and the extent of an installation will depend on the needs of
the plant and the desires of the operator. Most systems utilize pneumatic
relays coupled to sensing devices such as pressure switches, vibration
switches, and temperature-sensing elements. The sensing elements are
set for predetermined values, and if these values are met,they will initiate
an automatic shutdown of the engine by cutting off the fuel or by other
means.
f) Starting Controls
h) Load Controls
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 13.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 14
PROCESS MANUAL CONTROL AND ISNTRUMENTATION
DATE 06-94
13.5.1 Turbo-expanders
The operation of the turbo-expander variable inlet nozzles has already been
described in Section 10.5.1.
The means of speed control depends on the process flow condition. For
systems where more liquid is available to the unit than is needed to generate
the power required by the pump, speed is regulated by using a control valve
in parallel with the turbine to bypass a portion of the process flow.
Where the capacity available to the unit is less than that required at available
head and design speed, speed control is achieved by throttling the available
pressure so that the unit sees only a portion of that available head needed to
satisfy its head-speed-capacity relationship at the desired speed. The bypass
and throttling valves are usually operated automatically by process
instrumentation.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 14.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL DRIVER SPECIFICATION
DATE 06-94
The preparation of the driver specification data sheets is the joint responsibility of the
mechanical engineer and the compressor manufacturer. The mechanical engineer
shall originate these forms after discussion with the process engineer. The process
engineer's responsibility is to identify the type of driver needed and the required
control flexibility. For steam turbine drivers the process engineer shall specify the
supply steam pressure/temperature and the discharge conditions while ensuring that
the steam consumption fits into the steam balance.
The applicable driver specification form descriptions and form numbers are shown
below.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
15.0 TROUBLESHOOTING
The electric motor will give trouble free service for the greater part of its useful life
providing that it is properly maintained. Maintenance requirements fall into two
categories:
Electric
Winding insulation resistance must be kept up and contact resistance kept down.
Mechanical
Apart from regular maintenance, electric motors must also be protected from
electrical problems such as surge etc., refer to Section 13.1.3, and from moisture, oil,
grit and dust by using the proper motor enclosure.
Problems that are likely to occur from improperly maintained or protected electrical
motors are shown in Table 15-1.
Steam turbines may suffer from problems such as shaft, disc or blade vibration which
are usually associated with design, manufacture, or material selection. Such
problems are beyond the scope of this manual.
All steam turbines suffer from long term deterioration, usually of the blading and
glands. Damage of this nature is detected by careful log keeping of pressures,
temperatures, steam flows and power outputs. Erosion and corrosion of the blading
will result in decreased steam flow with reduced output and lower pressure drops per
stage. Deposits on the blades will increase intermediate stage pressures and reduce
steam flow and output. Loss of pressure and output may also be caused by leakage.
Deterioration of this nature may be reduced by improving the quality of the steam
feed by removal of impurities and by ensuring that the wetness fraction of the steam
is minimized. Severe erosion tends to occur at wetness in excess of 12 %.
Table 15-2 summarizes the most common problems likely to occur with steam
turbines and possible means of their prevention or alleviation.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
There are many types of failure associated with gas turbines since these units are very
complex. The majority of failures (up to 80 % in all types and ranges of gas turbine)
are associated with the very high temperatures of the hot sections of the machine and
are usually connected with the fuel. Table 15-3 shows some of the more frequent
causes of failure and their frequencies of occurrence.
Fuel nozzles clog easily and can come loose. In most cases the nozzle does
not go through the turbine but it permits a large amount of fuel to enter the
combustion chamber. The liquid fuel is transported to the transition piece
and on towards the first stage nozzles. These nozzles act as flame holders
causing the fuel to ignite and create a large flame which burns out the first
stage nozzles and rotor blading.
Failure of liners is usually caused in gas turbines using steam injection, refer
to Section 10.3.4.b, where improper mixing occurs and the free steam causes
differential cooling resulting in high thermal stresses.
Table 15-4 summaries the most frequent gas turbine problems and steps that
may be taken to prevent or alleviate them.
Both diesel and gas engines are subject to wear of moving mechanical parts and wear
and fatigue caused by vibration. Proper regular servicing and systematic checking of
such items as oil consumption, compression, pressures and temperatures will ensure
that the engine operates reliably.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Table 15-1
Failure Cause of Failure Effect of Failure Preventative Measures
Bearings Grit, Dust, Age Uneven air gap and mechanical damage Frequent check of bearing condition. Proper
(possibly severe) to insulation or windings motor enclosure selection to prevent ingress of
dirt
Windings Worn bearings Check bearings regularly
Short circuit in motor terminal Loss of phase winding by mechanical or Check terminal box seals, use short circuit
box electrical damage: overheating protection
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Heavy Blade Contaminated steam from Loss of turbine power and steam flow Chemical dosing of feed steam. Regular
Deposits reciprocating engines washing with saturated steam, water injection or
Failure of thrust bearings chemicals
Impurities carried over from
boiler
Excessive Gland Worn, distorted or damaged Loss of heat energy from steam Proper seal maintenance and replacement.
Leakage gland seals Proper maintenance of clearances
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Output Service Nozzle Liners Tube Place Nozzle Nozzle Blade Disc Vane
1-5 Continuous
MW Base load 30 5 5 15 5 20 3
Intermittent 5 11 5 20 10 20 5
Peaking 5 15 10 20 9 20 6
5-15 Continuous
MW Base load 20 10 7 10 5 15 5 1 5
Intermittent 17 15 10 15 8 15 5 4
Peaking 15 18 10 15 7 15 5 22 4
15-35 Continuous
MW Base load 20 10 5 3 5 4 10 3 2 6
Intermittent 10 10 5 5 8 5 15 5 4 6
Peaking 10 10 7 7 10 5 15 5 4 6
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Power Type of Com- Com- Radial Thrust Seals Coupl Foreign Lube Misalign Gear Sha
Output Service pressor pressor Bearings Bearings -ings Object System -ment Failur ft
Disc Diffuser Damage Failure es
I-5 Continuous
MW base load 2 3 5 2 4 1
Intermittent 2 4 4 5 3 2 2 2
Peaking 2 4 4 3 2
5-15 Continuous
MW base load 1 4 3 4 2 2 1 2 3
Intermittent 3 3 3
Peaking 3 3 3
15-35 Continuous
MW base load 1 5 3 3 4 2 3 3 5 3
Intermittent 1 7 3 3 4 2 1 1 3 2
Peaking 1 7 3 3 4 2 1
Above Base
15 MW Loaded 2 3 4 3 2 2 1 3 2 1
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 7
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Lubricating oils and hydraulic fluids transport the debris produced by wear
and corrosion. By monitoring the quantity, size and shape of the debris it is
possible to tell what is deteriorating.
b) Oil Analysis
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 8
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 9
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 15.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 10
PROCESS MANUAL TROUBLE SHOOTING
DATE 06-94
Both turbo-expanders and power recovery units tend to suffer the long term
deterioration by erosion and corrosion of blading, wheels and impellers common to
steam turbines - refer to Section 15.2.
The supplier should also be consulted regarding problems related to the use of
lubricating oil at the low temperatures at which turbo-expanders operate which affect
particularly bearings, seals and wear of moving mechanical parts.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
API Standard 673, "Special Purpose Centrifugal Fans for General Refinery
Service."
16.1.3 Drivers
API Standard 611, "General Purpose Steam Turbines for General Refinery
Services."
API Standard 612, "Special Purpose Steam Turbines for General Refinery
Services."
API Standard 616, "Type H Industrial Combustion Gas Turbines for General
Refinery Services."
API Standard 613, "Special Purpose Gear Units for Refinery Service."
API Standard 614, "Lubrication, Shaft Sealing, and Control Oil Systems for
Special Purpose Application."
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
OpCon Practice 000 225 1131, "Hydraulic Design - Single Phase Flow -
Gas."
OpCon Practice 000 225 9510, "Computer Programs - Selection and Use."
OpCon Practice 000 250 2475, "Compressor Piping - Pulse Dampener Type,
and Location of Mounting on Reciprocating Compressors.
SP-5.1.1, "General Piping - Process and Utility Design, Layout, and Drawing
Specification - Compressor, Section 5.9."
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
16.2 SYMBOLS
bp = brake power, hp
c = clearance
= efficiency
FT = flow transmitter
FY = amplifying relay
h = head, ft
H = enthalpy, Btu/lb
ip = indicated power, hp
k = adiabatic exponent
L = losses, hp
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 4
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
n = polytropic exponent
Ns = specific speed
P = power, hp
Q = capacity, ft3/min
Rp = pressure ratio
s = number of stages
ST = speed transmitter
T = temperature, oF, oR
V = volume, ft3
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 5
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
W = work, hp
X = X factor
Z = compressibility factor
Subscripts:
a = air
av = average
c = compressor
cb = combustion
cyc = cycle
e = turbo-expander
f = fuel
i = ideal cycle
o = overall
t = turbine
theor = theoretical
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 16.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 6
PROCESS MANUAL CODES/STANDARDS AND SYMBOLS
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 17.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL REFERENCES
DATE 06-94
17.0 REFERENCES
17.1 REFERENCES
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 17.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 2
PROCESS MANUAL REFERENCES
DATE 06-94
20) "High Power Electric Drives Save Energy" Hydrocarbon Processing, July
1984.
21) "NEMA Standards Publication, Motors and Generators" Publication MG1-
1972, Part 1.
22) "Gas Turbine World Handbook" (Annual).
23) "Selection Guide for Expansion Turbines", Hydrocarbon Processing, August
1979.
24) "Process Application and Design of Large Power output Turbo-expanders",
Journal of Engineering for Industry, February 1973.
25) "Turbo-expanders and Condensate Recovery", The Oil and Gas Journal,
March 1973.
26) "Comparison of four different systems shows best FCC Power Recovery
Option", Oil and Gas Journal, September 17, 1984.
27) Bathe, W.N., Fundamentals of Gas Turbines, John Wiley and Sons, New
York (1984).
28) Kempe, Kempe's Engineering Yearbook for 1978, 83rd Edition, Morgan-
Grampian (Publishers) Ltd., London (1978).
29) Boyce, P.B., Gas Turbine Engineering Handbook, Gulf Publishing Company,
Houston (1987).
30) Kearton, W.J., Steam Turbine Operation, Pitman, London (1964).
31) Parrish, A., Mechanical Engineering Reference Book, 11th Edition, Newnes-
Butterworth, London (1973).
32) Werninck, E.H., Electric Motor Handbook, McGraw-Hill, London (1978).
33) Lilly, L.C.R., Diesel Engine Reference Book, Butterworths, London (1984).
34) Lyle, O., The Efficient Use of Steam, H.M.S.O., London (1960).
35) Fink, D.G., Standard Electrical Handbook for Electrical Engineers, McGraw-
Hill, London (1978).
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 17.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 3
PROCESS MANUAL REFERENCES
DATE 06-94
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794
SECTION 18.0
FLUOR DANIEL COMPRESSOR AND DRIVER
PAGE 1
PROCESS MANUAL APPENDIX
DATE 06-94
18.0 APPENDIX
Note: The sample data sheets include typical information provided by Process
Engineering.
105\OS\101\206\PROCESS\PUMPS\02-00/WP51-051794