HVAC Equipment List IBP
HVAC Equipment List IBP
HVAC Equipment List IBP
VFD Inventory
CIP
Installation Life Replacement Depreciation SN / Notes
Equip ID Manufacturer Model # Qty Application Size (hp) Voltage Phase Amps Replacement
Year Expectancy Cost Schedule
Year
SN XXXXXXXX, Option Board B5 in slot C, date 5/12/10, systetware
Eaton VS005411A 1 VFD 5.0 0-480 3 8 2000 17 $2,400
Unlabeled VFD1 to HV&AC 1 XXXXXXXX, locked in manual currently
Motor Drive
VFD to HVAC5 MVFD4005H2667-2 1 VFD 5.0 0-460 3 8 2000 17 $2,400 XXXXXXXX
International
Unlabeled to CWP 3,4 Eaton VS02541A-N000 2 VFD 25.0 0-480 3 34 ~2009 17 $5,700 XXXXXXXX
Unlabeled to CWP 1,2 Eaton VS007414A-N000 2 VFD 7.5 0-480 3 11 ~2009 17 $2,750 SN XXXXXXXX. Drive modified with option board B5 and C2 dated 8/16/10
HW VFD 1 Eaton VS015414A-N000 1 VFD 15.0 0-480 3 21 ~2009 17 $4,000 locked to 100% SN:XXXXXXXX
HW VFD 2 Eaton VS015414A-N000 1 VFD 15.0 0-480 3 21 ~2009 17 $4,000 XXXXXXXX
HV&AC 4 SUPPLY GPD GPD 506V-B001 1 VFD 15.0 0-460 3 12 2000 17 $4,000 XXXXXXXX
HV&AC 4 RETURN GPD GPD 506v-B004 1 VFD 3.0 0-460 3 5 2000 17 $2,100 XXXXXXXX
HV&AC 3 SUPPLY GPD GPD 506V-B021 1 VFD 10.0 0-460 3 21 2000 17 $3,150 XXXXXXXX
HV&AC 3 RETURN GPD GPD506V-B008 1 VFD 3.0 0-460 3 9 2000 17 $2,100 XXXXXXXX
HV&AC 2 RETURN GPD CIMR-P5M43P7 1 VFD 5.0 0-460 3 9 2000 17 $2,400 XXXXXXXX
HV&AC 2 SUPPLY EATON V010410A 1 VFD 10.0 0-460 3 16 2000 17 $3,150 XXXXXXXX
HVAC Equipment List
Other Systems
Expected Replacement CIP Replacement Depreciation
Equip ID Manufacturer Model # Qty Serves Tons Size (hp) Yrs Old Notes
Life (yrs) Cost Year Schedule
Chiller-1 Carrier 30HXC146RAE661BA 1 CHW System 145 15 23 $128,000 FLV: 0.754 kW/ton, IPLV: 0.649 kW/ton, Screw Chlr
Chiller-2 Trane RTAA0704YM01A3D0BDFKMNR 1 CHW System 70 12 23 $58,000 FLV: 1.18 kW/ton, IPLV: 0.876 kW/ton, Screw Chlr
Compr-1 Mixed 1 Pneumatics 10 29 20 $8,200 SEVERE leakage, more explanation in compressor section
32.1
HVAC Equipment List
Transformers Inventory
CIP
Impedance Installation Life Replacement Depreciation
Equipment KVA Make Model # Type NEMA Location SN Notes Replacement
% Year Expectancy Cost Schedule
Year
XFMR TL 150 General Electric 9T23Q9877G80 QL 2.8 AA Basement Electrical (B131) XXXXXXXX humming 1984 30 $15,000
XFMR LDP 150 Square D 150T3H SO 6.7 AA West Electrical (B126) XXXXXXXX humming 2000 30 $15,000
XMFR T2 75 General Electric 9T23Q9875G80 QL 2.7 AA 2nd floor electrical XXXXXXXX 2000 30 $6,500
XFMR TE 45 General Electric 9T23Q9874G80 QL 2.8 AA Basement Electrical (B131) XXXXXXXX 1984 30 $5,000
XFMR EL 45 Square D EE45T3H SO 6.2 AA West Electrical (B126) XXXXXXXX 1984 30 $5,000
XMFR L3X 30 General Electric 9T23Q9562G03A QLFK 4 AA Third Floor Electrical (350) NA slightly humming 1984 30 $4,200
XMFR EL3 30 Square D 30T3H SO 5.6 AA Third Floor Electrical (350) XXXXXXXX 1984 30 $4,200
None 25 Square D DT1171H25T5 SCR 4.9 AA Elevator Room XXXXXXXX 1984 30 $3,400
*New high efficiency transformers are available and recommended when an old unit is replaced.
HVAC Equipment List
Actuator Inventory
Equip ID Serves Location Make Model # Inch Notes
None AH1 HW coils Mech Rm Johnson Controls 14-283-8 1 1/2 1 1/2 inch three way valve from original construction moves extremely slow closed approx. 1 hr
from open to 25%, opens fine
None AH1 CW coils Mech Rm Johnson Controls 11-13779 1 1/2 1 1/2 inch three way valve from original construction moves extremely slow closed approx. 1 hr
from open to 25%, opens fine
None HVAC 1 HW B131 Siemens 599-01082 4 Working condition, slow to react to DDC
None HVAC 2 HW 215 Johnson Controls NA 2
None HVAC 2 CW 215 Johnson Controls NA 2
None HVAC 3 HW 2nd Floor Electrical Johnson Controls NA 2
None HVAC 3 CW 2nd Floor Electrical Johnson Controls NA 2 Not responding to DDC controls, failed in closed position
None HVAC 4 HW 245 Johnson Controls NA 2
None HVAC 4 CW 245 Johnson Controls NA 2
HTG-VLV HVAC 5 HW B131 Johnson Controls VA4233-GGA-2 2
CLG-VLV HVAC 5 CW B131 Johnson Controls VA4233-GGA-2 2
106 office 106 B131 HVAC1 supply damper Siemens 3313001 4 Spring Range 3-13psi
4
114 computer room 114 B131 HVAC1 supply damper Barber Colman 8438 Spring Range 3-13psi
4
115 dispatch 115 B131 HVAC1 supply damper Siemens 3313001 Spring Range 3-13psi
HVAC Equipment List
V.A.V Terminal Unit Schedule (VAV)
Inlet Size CFM Maximum Operating Installation Life Replacement
Equip ID Make Model
(inches) Maximum Minimum N.C. @ 1.0 PD Year Expectancy Cost
VAV-1 Titus ESV-3000 8 711 355 <25 1984 20 $1,500
VAV-2 Titus ESV-3000 6 380 190 <25 1984 20 $1,500
VAV-3 Titus ESV-3000 9 820 410 <25 1984 20 $1,500
VAV-4 Titus ESV-3000 6 390 195 <25 1984 20 $1,500
VAV-5 Titus ESV-3000 6 390 195 <25 1984 20 $1,500
VAV-6 Titus ESV-3000 5 330 165 <25 1984 20 $1,500
VAV-7 Titus ESV-3000 6 370 185 <25 1984 20 $1,500
VAV-8 Titus ESV-3000 5 330 165 <25 1984 20 $1,500
VAV-9 Titus ESV-3000 5 350 175 <25 1984 20 $1,500
VAV-10 Titus ESV-3000 8 741 370 <25 1984 20 $1,500
VAV-11 Titus ESV-3000 12 1632 816 <25 1984 20 $1,500
VAV-12 Titus ESV-3000 14 2436 1218 <25 1984 20 $1,500
VAV-13 Titus ESV-3000 7 510 255 <25 1984 20 $1,500
VAV-14 Titus ESV-3000 5 300 150 <25 1984 20 $1,500
VAV-15 Titus ESV-3000 12 1440 720 <25 1984 20 $1,500
VAV-16 Titus ESV-3000 5 330 330 <25 1984 20 $1,500
VAV-17 Titus ESV-3000 5 240 120 <25 1984 20 $1,500
VAV-18 Titus ESV-3000 10 1310 655 <25 1984 20 $1,500
VAV-19 Titus ESV-3000 8 750 375 <25 1984 20 $1,500
VAV-20 Titus ESV-3000 5 340 170 <25 1984 20 $1,500
VAV-21 Titus ESV-3000 9 1050 630 <25 1984 20 $1,500
VAV-22 Titus ESV-3000 4 180 108 <25 1984 20 $1,500
VAV-23 Titus ESV-3000 4 180 108 <25 1984 20 $1,500
VAV-24 Titus ESV-3000 5 270 162 <25 1984 20 $1,500
VAV-25 Titus ESV-3000 5 310 186 <25 2000 20 $1,500
VAV-26 Titus ESV-3000 7 600 360 <25 2000 20 $1,500
VAV-27 Titus ESV-3000 9 960 576 <25 2000 20 $1,500
VAV-28 Titus ESV-3000 10 1166 700 <25 2000 20 $1,500
VAV-29 Titus ESV-3000 6 450 450 <25 2000 20 $1,500
VAV-30 Titus ESV-3000 7 520 312 <25 2000 20 $1,500
VAV-31 Titus ESV-3000 5 230 138 <25 2000 20 $1,500
VAV-32 Titus ESV-3000 7 490 294 <25 2000 20 $1,500
VAV-33 Titus ESV-3000 5 250 150 <25 2000 20 $1,500
VAV-34 Titus ESV-3000 6 400 240 <25 2000 20 $1,500
VAV-35 Titus ESV-3000 9 840 504 <25 2000 20 $1,500
VAV-36 Titus ESV-3000 7 580 348 <25 2000 20 $1,500
VAV-37 Titus ESV-3000 6 360 216 <25 2000 20 $1,500
VAV-38 Titus ESV-3000 7 520 312 <25 2000 20 $1,500
HVAC Equipment List
Reheat V.A.V Terminal Unit Schedule (RVV)
Maximum CFM
Inlet Sixe S.P Down Reheat Head Loss Maximum Operating Installation Life Replacement
Equip ID Make Model GPM ROW EWT (F) LWT (F)
(inches) Cooling Heating Stream (in MBH (ft) N.C. @ 1.0 PD Year Expectancy Cost
WG)
RVV-1 Titus ESV-3000 6 360 180 0.75 4.9 1 1 5 190 170 <25 2000 20 $1,500
RVV-2 Titus ESV-3000 10 1220 610 0.75 16.5 2 1 5 190 170 <25 2000 20 $1,500
RVV-3 Titus ESV-3000 5 240 120 0.75 3.3 1 1 5 190 170 <25 2000 20 $1,500
RVV-4 Titus ESV-3000 14 2310 1155 0.75 31 3 1 5 190 170 <25 2000 20 $1,500
RVV-5 Titus ESV-3000 14 2310 1155 0.75 31 3 1 5 190 170 <25 2000 20 $1,500
RVV-6 Titus ESV-3000 10 1200 800 0.75 35 3.5 1 5 190 170 <25 2000 20 $1,500
RVV-7 Titus ESV-3000 9 830 415 0.75 11.2 1 1 5 190 170 <25 2000 20 $1,500
RVV-8 Titus ESV-3000 9 900 540 0.5 5.8 1 1 5 190 170 <25 2000 20 $1,500
RVV-9 Titus ESV-3000 4 210 126 0.5 1.4 1 1 5 190 170 <25 2000 20 $1,500
RVV-10 Titus ESV-3000 7 500 300 0.5 3.2 1 1 5 190 170 <25 2000 20 $1,500
RVV-11 Titus ESV-3000 8 699 420 0.5 4.5 1 1 5 190 170 <25 2000 20 $1,500
RVV-12 Titus ESV-3000 14 2250 1350 0.5 75 7.5 2 5 190 170 <25 2000 20 $1,500
RVV-13 Titus ESV-3000 14 2280 1368 0.5 14.8 1.5 1 5 190 170 <25 2000 20 $1,500
RVV-14 Titus ESV-3000 5 270 162 0.5 1.7 1 1 5 190 170 <25 2000 20 $1,500
RVV-15 Titus ESV-3000 4 220 132 0.5 1.4 1 1 5 190 170 <25 2000 20 $1,500
RVV-16 Titus ESV-3000 6 435 261 0.5 2.8 1 1 5 190 170 <25 2000 20 $1,500
RVV-17 Titus ESV-3000 5 240 144 0.5 1.6 1 1 5 190 170 <25 2000 20 $1,500
RVV-18 Titus ESV-3000 5 350 210 0.5 2.3 1 1 5 190 170 <25 2000 20 $1,500
RVV-19 Titus ESV-3000 5 230 138 0.5 1.5 1 1 5 190 170 <25 2000 20 $1,500
RVV-20 Titus ESV-3000 5 250 150 0.5 1.6 1 1 5 190 170 <25 2000 20 $1,500
HVAC Equipment List
HV&AC Air Handler Unit Schedule
Supply Fan Return Fan
Equip ID Make Model SN CIP
ESP (in ESP (in Installation Expected Replacement Depreciation
CFM RPM HP Volt/ph CFM RPM HP Volt/ph Replacement
WG) WG) Year Life (yrs) Cost Schedule
Year
AHU-1 Buffalo 75 460/3 25 460/3 1984 30 $168,000
HV&AC-1 Temtrol WF-BZ18 81084 6035 1.5 1750 5 460/3 - - - - - 2000 30 $26,600 17.24286
HV&AC-2 Temtrol 8467 2.5 1970 10 460/3 8467 1.5 1075 3 460/3 2000 30 $37,300 24.19143
HV&AC-3 Temtrol 12952 2.5 1605 15 460/3 12273 1.5 837 5 460/3 2000 30 $57,000 37.00571
HV&AC-4 Temtrol 6421 2.5 2075 7.5 460/3 6421 1.5 1140 2 460/3 2000 30 $28,300 18.34571
U101770-
HV&AC-5 Temtrol WF-DH13 6120 2 1820 5 460/3 - - - - -
001-00 2000 30 $26,900 17.48571
HV&AC-6 Temtrol 6300 1750 460/3 2000 30 $27,700 18
HVAC Equipment List
Motor Inventory
Insulation Installation Life Replacement CIP Depreciation
Equip ID Manufacturer Model # Qty Application Size (hp) Voltage Amps RPM Frame NEMA EFF% Power Factor SF Des Code SN / notes
Class Year Expectancy Cost Replacement Schedule
5C93RA81 elevator
None Montgomery 1 25 240 85.3 850 NA NA NA NA NA NA NA 1984 18 $2,200 shunt wound
9A800 motor
General 5KS365BS2
AH 1 SF 1 fan motor 75 230/460 180.2/90.1 1780 365T 94.1 0.85 F 1.15 BFC G ~2000 18 $6,000 TM625422
Electric 05D21
General Totally incased in insulation can't get
AH 1 RF NA 1 fan motor 25 NA NA NA NA NA NA NA NA NA NA ~1990 18 $2,200
Electric to motor name plate
208-
Pumps 3,4 Baldor M2531T 2 pump motor 25 2 1760 284T 91.7 0.83 B 1.15 B G 1984 18 $2,200 39L031W918H1
230/460
6-338345- 208-
Pumps 1,2 Gould 2 pump motor 7.5 18.3/9.15 1750 E213T 88.5 0.867 B 1.15 B J 1984 18 $950 SN 71509
03 230/460
208- Located in B131, rotation clockwise
CWP 1,2 Baldor JMM33117 2 pump motor 7.5 23-22/11 1725 213JM 85.5 0.75 B 1.15 B H 1998 18 $950
230/460 when looking from behind, pump
HWP 1 Baldor JMM2513T 1 pump motor 15 230-460 41/20.5 1760 254JM 88.5 0.78 B 1.15 B H 1998 18 $1,500
HWP 2 Baldor JMM2513T 1 pump motor 15 230-460 41-38 1760 254JM 91 0.81 F 1.15 A J ~1984 18 $1,500
HV&AC 4
Baldor EM3311T 1 fan motor 7.5 0.5 19.2/9.6 1770 213T 91.7 0.79 F 1.15 A J ~2000 18 $950 37F614S186
SF
HV&AC 2
Baldor EM3211T 1 fan motor 3 230-460 8.2/4.1 1760 182T 89.5 0.77 F 1.15 B K ~2000 18 $650 36G548Y434G1
RF
HV&AC 3
Baldor EM2513T 1 fan motor 15 230-460 35.4/17.7 1765 254T 93 0.86 F 1.15 B G ~2000 18 $1,500 39K037W916
SF
HV&AC 3
Baldor EM2118T 1 fan motor 5 230-460 13.2/6.6 1750 184T 89.5 0.8 F 1.15 B J ~2000 18 $700 36G548S270G1
RF
*Motors traditionally do not have when they were manufactured on their SN. Periodic replacements over the entire building make it hard to determine when each motor was installed. Also maintenance often keep extra motors in-stock and a motor may appear to be old but actually has been recently installed and is in good condition.
Pump Inventory
CIP
Impeller Installation Life Replacement Depreciation
Equip ID Manufacturer Model # RPM GPM Head (ft) hp Voltage Notes Replacement
Size Year Expectancy Cost Schedule
Year
Closed
HWCP 1,2 Bell & Gossett 3E 9.875 1750 352 85 15 460 Couple 1984 20
Design
Closed
CWP 1,2 Bell & Gossett 2-1/2BB 8.75 1750 170 75 7.5 460 Couple 1984 20
Design
CWCP 1 Bell & Gossett 3X3X6.5BF 150 36 3 1984 20
Nameplate
CWP 3,4 Bell & Gossett NA 1984 20
NA
Estimated Estimated Percentage
Estimated Estimated Estimated Estimated CIP Estimated Non- Percentage of Total
Annual Annual Estimated System Depreciation
Demand Annual Gas Simple Remaining Replacement Improved of Total Therms
Energy Conservation Opportunity Electric Energy Capital Costs Age Schedule
Savings Savings Payback System Life* Year Replacement Cost kWh Saved Saved
Savings Savings
(kWh) (kW) (therms) ($) ($) (years) (years) (years) ($) % %
Prescriptive Measures