LNG Terminal - Draft PCS
LNG Terminal - Draft PCS
LNG Terminal - Draft PCS
REVISION INDEX
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
DISCLAIMER
Because of the variety of uses for this information, the user of and those responsible for applying this information
must satisfy themselves as to the acceptability of each application and use of the program. In no event will
Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use of
or application of this information. The illustrations, charts, and examples shown in this document are intended
solely to illustrate the principles of Programmable Automation Controllers (PAC) and some of the methods used to
apply them. Particularly because of the many requirements associated with any particular installation, Rockwell
Automation, Inc. cannot assume responsibility or liability for actual use based upon the illustrative uses and
applications.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment,
or software described in this text.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
TABLE OF CONTENTS
1. INTRODUCTION.................................................................................................................................... 4
1.1Purpose.......................................................................................................................................... 4
1.2Project Overview............................................................................................................................. 4
1.3Terms and Definitions..................................................................................................................... 6
1.4CODES, STANDARDS, AND REFERENCES................................................................................7
2. ICSPCS OVERVIEW.............................................................................................................................. 8
3. SPECIFICATIONS OF BPCS............................................................................................................... 10
3.1BPCS Controllers:......................................................................................................................... 11
3.2BPCS Input / Output Sub-System.................................................................................................12
3.3Advanced Process Control (APC) Capabilities:............................................................................14
3.4BPCS Communication System:.................................................................................................... 15
1. INTRODUCTION.................................................................................................................................... 4
1.1Purpose.......................................................................................................................................... 4
1.2Project Overview............................................................................................................................. 4
1.3Terms and Definitions..................................................................................................................... 6
1.4CODES, STANDARDS, AND REFERENCES................................................................................7
2. ICSS OVERVIEW................................................................................................................................... 8
3. SPECIFICATIONS OF BPCS................................................................................................................. 9
3.1BPCS Controllers:......................................................................................................................... 10
3.2BPCS Input / Output Sub-System................................................................................................. 11
3.3Advanced Process Control (APC) Capabilities:............................................................................13
3.4BPCS Communication System:.................................................................................................... 14
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
1. INTRODUCTION
1.1 PURPOSE
The purpose of this document is to define the Design Basis and establish the general specifications for the
design, fabrication, and testing of the IntegratedProcess Control and Safety System (ICSS)System for the HaiLinh
Limited Company’s LNG Receiving and Re-gasification Plant at PCai Mep Tank Farm Area, Vung Tau province,
Vietnam.
This specification is not intended to specify the complete details of design and construction and should be used in
conjunction with the Control System Architecture Block Diagram. In general any necessary but not covered in this
specifications should be taken care by the PCS vendor.
Integrated Control and Safety System (ICSSProcess Controls )System that will be comprised of a basic process
control system (BPCS),hardware and software Safety Instrumented System (SIS), and a Fire and Gas System
(FGS), and other miscellaneous systems that interact with the above mentioned systems.
It is the responsibility of the ICSS Supplier to supply a full and complete working system compliant with this
specification. However, Compliance with the requirements of this document does not relieve SUPPLIER from any
obligation to supply equipment that is safe to operate and maintain.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
Utility systems
- Firefighting system;
- Fire & Gas system;
- Emergency shutdown system;
- Control system;
- Power supply system;
- Lighting system;
- Lightning system;
- Grounding system;
- Piping system;
- Instrument air system;
- Plant air system;
- Nitrogen system;
- Infrastructure items.
Unloading system
The LNG terminal shall be designed to receive LNG cargo transfer from LNG carrier at maximum unloading rate
of 12,000m3/h to inside terminal’s facilities within 10 - 18 hours period, the system consists of:
- 03 unloading arm 16”;
- 01 vapor return arm 16”;
- 01 vapor return knock out drum;
- 01 jetty control system
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
AI Analog Input
AIO Analog Input and Output
AO Analog Output
BPCS Basic Process Control System
CCR Central Control Room
DCS Distributed Control System
DI Discrete/Digital Input
DIO Digital Input and Output
DO Discrete/Digital Output
ESD Emergency Shutdown System
EWS Emergency Work Station
FGS Fire and Gas System
FAT Factory Acceptance Test
FF Foundation Fieldbus
GPS Global Positioning System
HART Highway Addressable Remote Transducer Also, protocol to communicate with such
devices
HMI Human Machine Interface
ICSS Integrated Control and Safety System
IO Input/ Output
OPC OLE for Process Control
OWS Operator Workstation
PCS Process Control System
PFD Probability of Failure on Demand
MTA Marshaling Termination Assembly
QA Quality Assurance
RTD Resistance Temperature Detector
SAT Site Acceptance Test
SOE Sequence of Events
SIL Safety Integrity Level
SIS Safety Instrumentation System
TMR Triple-Modular Redundant
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
ISA/ANSI
S88.01 – Batch Control Part 1: Models and Terminology
• DIN 40 050 / IEC 529 / VDE 0470/ EN 60529
Defines Degrees of Protection
• EEMUA Publication 191
– Alarm Systems: A guide to Design, Management and Procurement
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
2. ICSPCS OVERVIEW
The LNG Terminal and the re-gasification facility will be designed with an overall facility Integrated Process
Control System.and Safety
System (ICSS) approach. The individual systems to be integrated will include the BPCS, the SIS, the FGS, and
the packaged equipment control systems.
The BPCS will be responsible for the process control functions and monitoring of the facility, including regulatory
control, process-related interlocks, Human Machine Interface (HMI) and process-related reporting functions.
The BPCS shall provide the sole means of process control and supervision of the Terminal from the Main Control
Room.
Plant BPCS design will be based on conventional hardwired I/O with HART capability and should have the
capability to communicate with the packaged equipment control systems over Modbus Serial, Modbus TCP/IP,
and EtherNet/IP.
SIS will be responsible for the safety related functions of the facility, including all end devices for process safety-
related interlocks and safety-related reporting functions, Operator initiated emergency shutdowns and all
interlocks.
The SIS Logic Solver shall have the capability of implementing Safety Instrumented Functions of up to Safety
Integrity Level (SIL) 3.
The SIS will be safety Logic solver based system comprising a different hardware technology than BPCS but
should ideally be from the same manufacturer as BPCS. The specification of the SIS system is to be referred to
the Document number –xxxxxxx.
The FGS will be responsible for the detection of fire or the presence of hydrocarbon vapors outside of pressure
containment. Primary elements (sensors/detectors) include fire, smoke, thermal, and combustible gas detectors.
FGS will have alarm devices, interfaces to SIS and HMI consoles, and fire & gas related alarm/report functions.
FGS should be based on the same hardware platform as SIS. The specification of the SIS FGS system is to be
referred to the Document number –xxxxxxx.
Packaged equipment control systems will be responsible for the control, operation, and machine monitoring of the
associated mechanical equipment, like BOG Compressors, Vaporizer Systems, Custody Transfer Metering, Tank
Gauging and Loading/unloading systems. These equipment will each have a dedicated control system with
regulatory control from the BPCS.
The ICSS PCS should have the capability to connect process, discrete, power, information, and safety control into
one plant-wide infrastructure.
Even though the ICSS will be fully integrated, Tthe essential functions of the three (3) main subsystems are
mutually independent whereby single failure of one subsystem cannot affect the other subsystems.
The following Systems will be controlled by the individual packaged system PLC controllers:
BOG Compressor Controls
Vaporizer System
Marine Mooring Systems
LNG Tank Gauging System
Flue Gas Heaters
Unloading Arms Packaged System
Custody Transfer/Metering System
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
3. SPECIFICATIONS OF BPCS
The Basic Process Control System (BPCS) shall use open, industry-standard networking technologies like
EtherNet/IP to support and enable integration to plant systems, optimization, information, and business
processes.
The BPCS shall be an open architecture client/server based system. It shall be an integrated, modular, and
scalable architecture of robust control hardware and software, with the ability to share data between applications.
A major consideration of the BPCS shall be its modular, field expandable design allowing the system to be tailored
to the Terminal process control application needs. The capability shall exist to allow for expansion of the system
by the addition of hardware and/or software.
The system should have ability to view remotely via Web and therefore Cybersecurity for data at rest and motion
should be considered in the design.
The BPCS shall use 4-20 mA and HART protocol as the platform to interface with field devices.
The BPCS Control Systems Equipment will reside in the Main Control Room. All the components of the BPCS
shall be located in controlled environmental room. Remote I/Os in the field are envisioned for this project but and
they may be used after approval by the Owner.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The points in the regulatory control must be able to access values from and send values to other regulatory
control points and data acquisition points
To ensure control strategy integrity, a reliable means of controller redundancy shall be provided. Any active-
controller failure shall cause the failed controller to switch over to the redundant controller without upsetting the
process or causing interruption or loss of control, within minimum possible time. During a switchover, a Scan time
delay of no more than 10ms should be ensured while the Primary and Secondary controller should always remain
fully synched.
The BPCS Controller shall use multiple independent, asynchronous scans. These concurrent scans shall be
designated for processing of input and output information, program logic, and background processing of other
controller functions. Input and output devices located in the same backplane (local I/O) as the CPU will produce
at the rate of the configured RPI (Requested Packet Interval), and for discrete input modules enabled for Change
Of State (COS), at the time any point changes state.
BPCS controller should have the capability to do regulatory controls as well as to meet the demands of high-
speed applications that require scan rates of 10-20 milliseconds.
All BPCS Control Processors Shall be Redundant and “hot swap” type.
All system modules including the controller may be removed from the chassis or inserted in to the chassis while
power is being supplied to the chassis without faulting the controller or damaging the modules. This is known as
Removal and Insertion Under Power (RIUP). Alternately a software configurable option shall exist to fault the
controller if required.
In a single chassis system all system and signal power to the controller and support modules shall be distributed
on a single backplane. No interconnecting wiring between these modules via plug-terminated jumpers shall be
acceptable.
BPCS Controller shall have the ability to be updated electronically to interface with new modules.
Modules should be pluggable into a chassis and keyed to allow installation in only one direction. The design must
prohibit upside down insertion of the modules as well as safeguard against the insertion of a module into the
wrong slot or chassis via an electronic method for identifying a module. Electronic keying performs an electronic
check to insure that the physical module is consistent with what was configured. The Controller modes should be
able to change from the hardware keyswitch located on the Processor module itself.
The CPU operating system firmware shall be contained in non-volatile memory. An option shall be possible to
store both the user program and system firmware in a removable non-volatile memory for backup/restore
purposes.
Load criteria of Control Processors: The system shall be designed such that, the loading criteria of Control
Processors shall not exceed 50% including spare capacity.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The I/O modules shall be capable of accepting the following types of inputs and outputs:
- Analog inputs (4-20mA DC) (HART)
- Thermocouple inputs
- RTD inputs
- Pulse input (frequency input, 24 VDC)
- Digital inputs (dry contacts)
- Digital outputs (dry contacts)
- Digital outputs (wet contacts/relays)
- 24 VDC input Proximity Switches
Apart from standard Modules, the BPCS system should also have the cards with 08 or 16 isolated, individually
configurable input channels with a separate HART modem on each channel.
Channel-to-channel, channel-to-backplane, and channel-to-frame ground galvanic isolation at a continuous level
of 250V AC rms.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The Digital input modules will convert the AC or DC On/Off signals from field devices to appropriate logic level for
use within the processor. Typical input devices should include the following:
-• Proximity switches
-• Limit switches
-• Selector switches
-• Float switches
-• Push button switches
The available input modules shouldall provide isolated or non-isolated wiring options offering point to point
isolation, channel to-channel isolation and no isolation options.
The available I/O modules shouldall also have diagnostic features option.
The BPCS should offer Time Stamping options. Dedicated Time stamp resolutions of up to 10 msec (through
separate SOE modules) should be available.
All BPCS inputs are should be updated asynchronously in relation to the controller’s task execution. In other
words, an input may be updated in the controller at any time during the controller’s execution of the tasks it is
configured to run.
RTD Modules:
The RTD input must be capable of measuring and linearizing the following type of 3 and 4 wire RTD’s
Type: PT100
Digital Accuracy: + 0.28ºC, (0.5ºF)
Resolution: Minimum 12 bits
IO Summary:
IOCOUNT DI DO AI AO
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
Spares: 20% spares should be considered for future expansion. Expansion space of 20% should be
considered.
Some Critical Digital and analog outputs shall be considered for redundancy.
Note: The number of IS and non-IS will be decided during the detail engineering of the project.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
Control Network:
The control network shall be dedicated to the BPCS. The control network shall be high performance, EtherNet/IP
based, single-fault-tolerant ring network type with the following characteristics:
Media redundancy
Fast-network fault detection and reconfiguration
Resiliency of a single-fault-tolerant network
Easy implementation without more hardware requirements
One Control network should be able to support up to 50 nodes, and 100 megabits/seconds speed. The network
should allow to build fast recovering and fault tolerant network topologies that do not influence the controlling
applications. (Recovery Time up to max of 3 milliseconds).
The control Network in structure and components (Switches/media converters wherever applicable), should be
deducted and not shared for any other communication purposes.
The Modbus TCP/IP should have option for local and remote configuration and diagnostics through the module's
Ethernet port, CIPconnect technology for bridging though BPCS EtherNet/IP network, and an on-board web
server for access to module documentation and sample program files.
Configurable floating point data movement should be possible, including support for Enron or Daniel floating point
formats. Error codes, counters, and module status should be available from module memory through the Server,
through the Client, or through the ladder logic and controller tags.
HMI Network:
The HMI network should include a high availability architecture with fully redundant Layer-2 and layer 3 network
switches for communication with fault Tolerant Servers for Visualization, Historization and Asset Management.
The architecture should offer industrial grade network rationalizing common IT infrastructure.
It should ensure redundancy of the network with no single point of failure, fault tolerance of all network
component, high availability and increased reliability offering benefits of a centralized infrastructure management
and scalable management of engineers, supervisors and operators.
The Terminal HMI Network will utilize Redundant Star network, where every Layer 2 access switch has dual
connections to a Layer 3 distribution switch. Devices, such as servers and workstations, are connected via a Dual
connection by using NIC teaming.
The system should support high availability by offering redundancy options at each level of the architecture in a
modular and selectable way.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The system shall be capable of managing system security, including user and groups on a single unified
administrative server.
The system shall be based on hardware and software whose compatibility is managed by the manufacturer, and
has public web sites to confirm compatibility of hardware & software revisions.
The Process Automation System Server (PASS) will host essential software components to run the
Visualization /Supervisory layer. The essential software components will include the data server, HMI server, and
alarm server. The total number of server machines required will be determined by the supplier depending on the
system size, but as minimum one set of redundant HMI/Data Servers must be provided. Specification of the
server should be adequate to avoid memory/network loading.
The server must meet the recommended system requirements of the HMI applications, but as min should comply
to below:
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The manufacturer shall provide a process library for both function blocks and their corresponding display
elements Operator faceplates, compliant to ISA standards.
The system shall include modular, configurable process objects developed by the manufacturer (controller
functions and HMI templates) for operator control, maintenance & engineering functions. All process
objects must have manufacturer supplied documentation and supported by the manufacturer’s standard
technical support service.
The system shall include configurable process objects developed by the manufacturer (controller
functions and HMI templates) for standard procedural control, such as sequence control. All process
objects must have manufacturer supplied documentation and supported by the manufacturer’s standard
technical support service
The system shall have pre-engineered device objects from the manufacturer displaying Ethernet network
switch status and diagnostics.
The system shall have pre-engineered device objects from the manufacturer displaying system controller
status, HMI server status, Variable Frequency Drives control and status, soft starter control and status,
and electronic overload control and status.
The system shall have pre-engineered device objects from the manufacturer for integrated motor control
with the capability to display motor control inhibits, faults, status information and preventative
maintenance diagnostic information. Integrated motor control profiles must be available as a standard
feature in the controller development environment.
Alarming Capabilities:
Persons involved, departments, or organizations responsible for the specification, design, and implementation of
SIS shall be competent to perform the activities for which they are accountable.
Persons involved in the design, configuration, integration, testing, installation, and training of the Safety
Instrumented System Logic Solvers and associated equipment shall be TUV Functional Safety Engineer certified.
The SIS platform should provide a set of components that can be configured to meet a range of safety
and fault tolerance user requirements within a single system such as - fault tolerant topologies 1oo1,
1oo2D and 2oo3.
The SIS Logic Solver should be IEC 61508 certified, reviewed and approved for safety systems up to SIL
3 by TÜV.
The processor modules should be designed to meet the requirements for SIL 2 in a simplex configuration
and SIL 3 in a dual or triplicated configuration.
Individual input modules should be designed to meet the requirements for SIL 3 in simplex, dual or triple
configurations.
Individual output modules have been designed to meet the requirements for SIL 3 in a simplex or dual
configurations.
The SIS Logic Solver should support SIL-3 rated communication (to be used between SIS or FGS Logic
Solvers)
Support SIL 2 architectures for fail-safe low demand applications. All SIL 2 architectures can be used for energize or
de-energize to trip applications.
Should support SIL 3 de-energize to trip applications and SIL 3 energize to action applications (with Dual
Modules)
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
The Intelligent Terminal Automation System (TAS) should provide monitoring, control and management of the
entire product handling process from receiving to storage to distribution. With data integration as the system’s
core, TAS combines automatic control and business management functions. It should an integrated, modular,
open and scalable solution that helps ensure the safe and stable operation & optimal terminal management. The
TAS software should not reside in Computer/Server but rather integrated as part of the process automation
hardware.
Nearly all operations to be transaction based. Every transaction should be recorded and used for
commercial purpose.
Terminal Automation software platform should include customer account, product list, inventory, Truck Loading
order creation and processing, bay queue, sales order and reporting depending on the application and should be
flexible ,easily manageable and maintainable by the customer. Obsolescence of the Computer should not affect
the TAS software to larger extent.
Below features are necessary but not limited to the project requirement.
Easy maintenance
Modular TAS module/library– Standard library is available.
Scalable/expandable – For future terminal expansion e.g adding loading bay
Less or no mapping or coordination between software platform
TAS are accessible from any client windows / laptop via Internet Explorer
TAS Module (standard library) is available, thus will mitigate a risk during upgrade process.
Diagnostics and Analytics of all Information
Information & reconciliation of transactions across multi terminals available in single system.
Integrated Terminal Management system at MES layer
Web Interface Client
Modular and customizable based on requirements
Modules in Terminal Management System
Customer management
Inventory management
Product management
Truck management
Vessel management
Order and contract management
Reporting
ERP Interface
Forecasting
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.
Integrated Control and Safety System (ICSS)The Control system should be able to integrate with MCC on a
common platform without using any gateways or proprietary protocol. The low voltage MCC should be
configurable and ability to view them as note on the network. The diagnostics and troubleshooting information
should be available to the operator. The MCC should be type tested for IEC60439/61439 standards. The variable
speed drives shall be part of the MCC and should be able to interface with PCS on the process network and
ability to perform remote operations, maintenance for troubleshooting remotely. The forms of separation shall be
2b,3a,3b & 4b as required at various location of the plant. The technology shall be proven with a minimum of 10
years.
interface with MCC and other power equipment using open protocol without need of any interface convertors.
The information contained in this document consists of technical, commercial and/or financial information which is confidential and proprietary to Rockwell Automation, Inc. This information is furnished in confidence and with the
understanding that it may not be disclosed to third parties or reproduced or used, in whole or in part, for any purpose other than evaluation of this document. The recipient agrees to return the document to Rockwell Automation upon
request.