FUJI FRENIC LIFT GEARLESS MOTOR PARAMETERS

F01 0 P01 Number of pole


F03 Max. Speed (Motor RPM) (Set P01 parameter before setting F03 parameter)
F04 Motor RPM P02 Motor power.... KW (Set)
F05 Motor Voltage P03 Motor current In...A (Set)
F07 2.5sn (Acceleration time) P06 000A (No-load current)
F08 2,0sn (Deceleration time) P07 5%
F23 00 rpm (Start frequency) P08 10%
F24 0.60sn- Start frequency(Hold time) H06 3 min.(Cooling fan control)
F25 00 rpm (Stop frequency) L01 4 or 5 (Encoder type)
F26 10-15 Khz L02 Encoder pulse.....P/R
F42 1 (Gearless Motor) L12 011
E01 0---FAST (SS1) L13 110
E02 2---SLOW (SS4) L14 100
E03 1---JOG (SS2) L15 111
E04 8---RESET L16 001
E07 7---BX L17 010
E08 63---BATRY L18 101
E14 1sn L19 S-Curve setting 1 30%
E20 (Y1) 12--- Main contactors control L20 S-Curve setting 2 25%
E22 (Y3) 2 ---FDT (Speed detected) L21 S-Curve setting 3 25%
E23 (Y4) 37---ID (Current detected) L26 S-Curve setting 4 30%
E24 (Y5) 57--- Brake control L28 S-Curve setting 10 20%
E31 20 L36 2.00
E32 3 L38 2.00
E34 0.8xIn (Direction test) L65 1
E35 2.5sn L68 2,5 (ASR P constant)
E48 Led monitor 3 (Motor speed) L69 0,01 (ASR I constant)
C03 6 rpm Battery operation speed (Set) L80 1
C06 45 rpm Jog speed (Set) L81 100%
C07 6 rpm Low speed (Set) L82 0.2 s Brake ON delay time
C09 Third speed (Set) L83 0.1 s Brake OFF delay time
C11 Motor rpm High speed (Set) L85 0.2 s Main contactors start-up delay time
C21 0---r/min Speed command unit L86 0.1 s Main contactors OFF delay time

GEARLESS MOTOR POLE-TUNING PROCEDURE


1-Be sure that motor encoder is connected to optional board in inverter
2-Connect a cable from PLC terminal to EN input. (In order to make pole-tuning EN input must be active.)
3-Push REM/LOC button a few seconds to set inverter to LOCAL position.
4- Connect motor cables to inverter directly or press K1-K2 contactors manually.
5-Set L03 parameter to (2)and press FUNC/DATA button.In order to start process press FWD or REV button. (In this
process inverter will learn motor characteristics, the motor will not rotate and you can hear some noise).Inverter will
save result of pole-tuning process to L04 parameter.If ER7 error is displayed change motor phases (for example U
and V) and try again steps 4 and 5.
6-In order to verify pole-tuning process perform again steps 4&5.
7-Disconnect the jumper between PLC&EN. EN Input must be passive. Push REM/LOC button for a while to set
inverter to REMOTE position