Gas XP 60 2 GB
Gas XP 60 2 GB
Gas XP 60 2 GB
Burners for gas, double stage, aluminium frame , fan at high pressurisation, combustion
head with adjustment at high efficiency and high flame stability.
Available in the versions Methane (natural gas) or G.P.L. (to specify at the order) on
demand specific versions for town gas, coal gas or biogas.
Disposition rationalized of the components with accessibility facilitated for the operations
of setting and maintenance.
Gas train complete of working valve double stage with flow adjustment, safety valve,
gas pressure switch, filter stabiliser of gas pressure, completely assembled, electrically
linked and tested.
TECHNICAL DATA
MODEL GAS XP60/2CE
Mcal/h 100/200-450
Thermal power min.1°st./min 2° st.-max 2° st. *
kW 116/232-522
Flow-rate G20 (NATURAL GAS) min.1°st./min 2° st.-max
Nm3/h 11,7/23,4-52,6
2° st. *
Flow-rate G31 (G.P.L.) min.1°st./min 2° st.-max 2° st. * Nm3/h 4,5/9-20,3
Fuel: NATURAL GAS (second family) - LPG (third family)
Combustible category
Intermittent operation (min. 1 Stop every 24 hours) at double stages
Allowed enviroment conditions on running/stock
Maximum inlet pressure to the valves °C 60
Min. pressure train D1” FS32 NATURAL GAS/LPG ** mbar 47/30
Min. pressure train D1” 1/2 FS40 NATURAL GAS/LPG ** mbar 15/18
Min. pressure train D1” 1/2 FS50 NATURAL GAS/LPG ** mbar 12/16
Max pressure on the valve’s inlet mbar 200
Nominal electric power W 935
Fan motor W 740
Power absorbed A 2
Auxiliary power absorbed A 0,5
Power supply 3~400V,1/N~230V-50Hz
Degree of electric protection
Noisiness *** min-max dBA 73-76
Weight **** kg 32
* Reference conditions: Room temperature 20°C - Athmospheric pressure 1013 mbars - Altitude 0 (sea level).
** Least pressure of feeding of the gas to the train to get the maximum power of the burner considering against pressure in chamber of
value combustion 0 (zero)
*** Measured sonorous pressure in the laboratory combustion, with functional burner on beta boiler to 1 m of distance. (UNI EN ISO 3746)
Thermal power
OVERALL DIMENSIONS (mm)