Thermoelectric tripping device BAE72-S BC

Application
The BAE72-S Thermoelectric tripping de-
vice operates in conjunction with a
spring-return actuator to drive a motor-
ized fire damper to its “safe” position in
the event of the preset maximum tem-
perature being exceeded.
The device is normally connected to the
BKN230-24… communications and power
unit. In systems with no such unit, the
BAE72-S device is connected in series
with the power supply of the spring-return
actuator (use only 24 V actuators).
Mode of operation
The BAE72-S tripping device employs
two thermal trips Tf1 and Tf2.

p0034806
Thermal trip Tf1 operates if the ambient
temperature exceeds 72 °C. Replaceable
thermal trip Tf2 operates if the tempera-
ture inside the duct exceeds 72 °C. Both
trips cause the power supply to be inter-
rupted permanently so that it cannot be
uncancelled. If the power supply is inter-
Wiring diagram rupted, the energy stored in the spring
moves the damper back to its safe posi-
T ~ AC 24 V Connect via safety
tion.
!
Tf2 - + DC 24 V isolating transformer
Local function check
This version of the BAE tripping device in-
Tf2
corporates a test button for performing
a local function check on the safety
damper.
Tf1
BAE72-S The operating of the thermal trips Tf1 or
Tf2 can be simulated like this.
Tf1
BAE72-S Note: In an installation incorporating a
1 2 BKN230-24… unit, the BAE test is followed
by an automatic check routine performed
1 2 by BKS24-… device which then initiates a
* Remove factory-
fitted jumper! fault alarm.
* Installation
1 2 3 4 5 6 7
The Thermoelectric tripping device must
BKN230-24... be mounted on the duct or on the side of
1 2 the damper by means of the prefixed self-

ENG-93001-93327-10.02-500 · Printed in Switzerland · ZSD · Subject to technical changes


tapping screws in such a manner that
BLF24…-ST there is an unobstructed flow of air to
w0403210

M 5° M BLF24, BF(G)24 thermal trip from the appropriate source.


80° BF24…-ST 5° 80°

Spare parts (Order-N°)


Thermal trip Tf2 (ZBAE72)
Technical data BAE72-S Thermal trip Tf2/95 °C (ZBAE95)
Rated voltage AC/DC 24 V
Rated current max. 3 A
Through resistance < 1Ω Dimensions / Drilling template
Connection cable 1.2 m long, 2 × 0.5 mm2, BETAflam 145 ø 55
(interchangeable wires) 40 6
Operating temperature Tf1: duct outside temperature 72 °C
thermal trips Tf2: duct inside temperature 72 °C (replaceable)
27
Testing – VdS Verband der Sachversicherer, D-Köln,
to DIN 4102, Part 06 98
– CNPP Centre National de Prévention et Protection, ø 9.0 65
F-Vernon, to NF S61-937
Protection class III (safety extra-low voltage)
Degree of protection IP 54
Ambient temperature range – 30… + 50 °C
ø 9.5…11
Non-operating temperature – 40… + 50 °C ø 3.0 ø 3.0
Humidity test to EN 60335-1
EMC CE according to 89/336/EEC, 92/31/EEC, 93/68/EEC
d0020806

20 20
Maintenance maintenance-free
Weight 85 g