Splice Design
Splice Design
Splice Design
End Plate Type Splice Connection - End Plate Welded to column & two end plate Bolted at splice location
REFER DWG. 321-657-DETAIL E (635)
SPLICE DESIGN CONNECTION BY LRFD METHOD
Load From Beam 1-PG1 Shear Fy,Sd = 2117 kN
Shear Fz,Sd = 112 kN
Resultant Shear , FvSd = 2119.96 kN
Axial Compression Fxc, Sd = 3387.00
Axial Tension Fxt, Sd = 0.00 kN
Bending Moment, MzSd = 639 kNm
Bending Moment, MySd = 37 kNm
Additional pull/push due to Bending moment ,Mz = 600.56 kN
Additional pull/push due to Bending moment ,My = 411.11 kN
Upper Column
PG1
MATERIAL PROPERTIES :
INPUT DATA :
SPLICE CONNECTION
B) BOLTS
1) Grade Of Material Used For Bolt A 8.8 M LRFD METHOD
2
a) Yield Stress Fyb = 640 N/mm
2
b) Minimum Specified Tensile Stress Fub = 800 N/mm
Design Check
1 Bearing Check for Bolt Hole
Dia. Of the bolt used = 30 mm
No of bolts used for the bearing = 22
Allowable bearing strength per Bolt shall be minimum value of following two cases:
1. Allowable bearing strength = (1/a2) x 3.0 x Fup x db x tp
(Ref NBR8800:2008,CL.6.3.3.3, Page No. 78) = 2.22 x Fup xdb x tp x N/1000
(where ,a2 =1.35 ) = 2.22 x 400 x 30 x 25 x 22/1000.
= 14652 KN
2. Allowable bearing strength = (1/a2) x 1.5 x Fup x Lc x tp x nc
(Ref NBR8800:2008,CL.6.3.3.3, Page No. 78) = 1.11 x Fup x Lc x tp x nc
(where ,a2 =1.35 ) = 1.11 x 400 x (1020-(11 x 30)) x 25 x 2/1000
= 15318 KN
Therefore Allowable bearing strength = 14652 KN
14652 > 2120.0 KN
Hence ok
90
s1
s1
s2
SPLICE CONNECTION
Mininum tp required =
tpmin required = 6.0 x T x b = SQRT{ (6.0 x 187.51 x 1000 x(90 - 36)/2) / (225 x 225) }
Dp x Fup
8 Check for Weld Strength between column web and End plate
Height of Web = 1028.0 mm
Weld length available ( lw) = 2056 mm
Thickness of the weld used (w) = 8 mm
Total load carrying capacity of the weld required = 2120 KN
Total load carrying capacity of the weld = (1/w2) x 0.60 x fw x Aw
(Ref AISC 13th Ed. Eq. J2-4 , = (1/w2) x 0.60 x fw x 0.707 x s x 2 x L /1000
Page No. 16.1-100 ) = (0.44 x 415 x 2056 x 8 x 0.707 )/1000
= 2123.4 KN
2123.4 > 2120.0 KN
Hence ok
9 Check for Weld Strength between column flange and End plate
Width of Flange = 450.0 mm
Weld length available ( lw) = 864 mm
Thickness of the weld used (w) = 8 mm
Total load carrying capacity of the weld required = 750 KN
Total load carrying capacity of the weld = (1/w2) x 0.60 x fw x Aw
(Ref AISC 13th Ed. Eq. J2-4 , = (1/w2) x 0.60 x fw x 0.707 x s x 2 x L /1000
Page No. 16.1-100 ) = (0.44 x 415 x 864 x 8 x 0.707 )/1000
= 892.33 KN
892.3 > 750.1 KN
Hence ok
SUMMARY
END PLATE TYPE SPLICE CONNECTION
Single plate welded to Main beam and bolted to connecting beam
Top End Plate Size : (wp x Dp x tp) : 450 x 1020 x 25 thick A36 Grade plate
Bottom End Plate Size : (wp x Dp x tp) : 450 x 1020 x 25 thick A36 Grade plate
SPLICE CONNECTION
Upper Column
PG1
8 mm fillet weld all around
90 mm
450 x 1020 x 25 thick A36 Grade plate
s1
10mm stiffener
s2
450 x 1020 x 25 thick A36 Grade plate
s2
22-30 dia A8.8 Grade bolts
s3
Lower Column 450 x 1020 x 25 thick A36 Grade plate
PG1