Altivar 11
561250
1 2
3 4
5 6
7 8
Altivar 11
Applications
The Altivar 11 is a frequency inverter for 3-phase squirrel cage asynchronous motors
rated between 0.18 kW and 2.2 kW.
There are three types of power supply:
b 100 V to 120 V single phase,
b 200 V to 240 V single phase,
b 200 V to 230 V 3-phase.
The Altivar 11 incorporates specific features for local markets (Europe range,
America range, Asia range) and has functions suitable for the most common
applications, including:
b horizontal materials handling (small conveyors, etc),
b ventilation, pumping, access control, automatic doors,
b special machines (mixers, washing machines, centrifuges, etc).
Functions
The main functions incorporated in the Altivar 11 drive are:
b starting and speed control,
b reversal of operation direction,
b acceleration, deceleration, stopping,
b motor and drive protection,
b 2-wire/3-wire control,
b 4 preset speeds,
b saving the configuration in the drive,
b d.c. injection on stopping,
b ramp switching,
b catching a spinning load,
b local controls (Asia range only).
Several functions can be assigned to one logic input.
Standard versions
The Altivar 11 offer consists of 3 ranges designed for 3 different markets:
b Europe range: ATV 11pUppM2E (items 1 , 2 )
v single phase 240 V power supply,
v positive logic operation,
v integrated class B EMC filter.
b America range: ATV 11pUppppU (items 1 , 2 , 3 , 4 )
v power supplies: 120 V single phase, 240 V single phase or 230 V 3-phase,
v positive logic operation,
v meets current requirement in standard NEC 1999 208 V.
b Asia range: ATV 11pUppppA (items 5 , 6 )
v power supplies: 120 V single phase, 240 V single phase or 230 V 3-phase,
v positive or negative logic operation,
v local controls: Run and Stop keys, and potentiometer.
Altivar 11 drives are supplied either with heatsink (items 1 , 3 , 5 ) for normal
environments and ventilated enclosures, or on a base plate (items 2 , 4 , 6 ) for
mounting on a machine frame, when the size of the frame enables dissipation of the
heat.
Electromagnetic compatibility EMC
The incorporation of EMC filters in ATV 11pUppM2E drives simplifies installation of
machines and provides an economical means of meeting e marking requirements.
ATV 11pUppppU and ATV 11pUppppA drives are available without EMC filter. Filters
are available as an option for customer assembly, if conformity to EMC standards is
required.
Options
The drive only communicates, in point-to-point mode, with the following tools and
software:
b PowerSuite advanced dialogue solution:
v powerSuite software workshop for configuring the drive (item 7 ),
v powerSuite for Pocket PC (item 8 ),
v converter for connecting a PC or a Pocket PC.
Altivar 11
Environment
Conformity to standards Altivar 11 drives have been developed to conform to the strictest international
standards and the recommendations relating to electrical industrial control devices
(IEC, EN), in particular:
EN 50178, EMC immunity and EMC conducted and radiated emissions.
Drive characteristics
Output frequency range Hz 0200
Switching frequency kHz 216
Speed range 120
Transient overtorque 150% of the nominal motor torque
Braking torque - 20% of the nominal motor torque without braking resistor at no-load with the
deceleration ramp adaptation function enabled
- 80% of the nominal motor torque with braking resistor (available as an option) at no-
load
- Up to 150% of the nominal motor torque with braking resistor (available as an option)
at high inertia
Maximum transient current 150% of the nominal drive current for 60 seconds
Voltage/frequency ratio Sensorless flux vector control with PWM motor control signal (1)
Factory-set for most constant torque applications
Frequency loop gain Factory-set with the speed loop stability and gain
Possible correction for machines with high resistive torque or high inertia, or for
machines with fast cycles
Slip compensation Factory-set, according to the rating of the drive (adjustment possible)
(1) Pulse width modulation
Altivar 11
Electrical characteristics
Power supply Voltage V 200 - 15% to 240 + 10% single phase for ATV 11pUpp M2p
200 - 15% to 230 + 15% 3-phase pour ATV 11pUpp M3p
100 - 15% to 120 + 10% single phase for ATV 11pUpp F1p
Frequency Hz 50 5% or 60 5%
Isc A 1000 (prospective short-circuit current at the connection point) for single phase
power supply
5000 (prospective short-circuit current at the connection point) for 3-phase power
supply
Output voltage Maximum 3-phase voltage equal to:
- the line supply voltage for ATV 11pUppMpp
- double the line supply voltage for ATV 11pUppF1 p
Maximum connection capacity Drive ATV 11pU05 ppp, U09 ppp , 1.5 mm 2 (AWG 14)
of the power supply, the motor U12Mpp, U18M pp
and the braking module Drive ATV 11p 4 mm2 (AWG 10)
U18F1p, U29 ppp, U41 ppp
Max. length of motor cables m - 50, shielded cable
- 100, non-shielded cable
Electrical isolation Electrical isolation between power and control (inputs, outputs, power supplies)
Available internal supplies Short-circuit and overload protection:
- One + 5 V (0/+ 5%) supply for the reference potentiometer (2.2 to 10 kW), maximum
current 10 mA
- One + 15 V ( 15%) supply for the control inputs, maximum current 100 mA
Analog input AI1 1 configurable analog input
Max. sampling time: 20 ms, resolution 0.4%, linearity 5%:
- voltage 0-5 V (internal power supply only) or 0-10 V, impedance 40 kW
- current 0-20 mA or 4-20 mA (without addition of a resistor), impedance 250 W
Logic inputs LI 4 assignable logic inputs, impedance 5 kW
+ 15 V internal or 24 V external power supply (min. 11 V, max. 30 V).
Factory-set with 2-wire control in transition mode for machine safety, for Europe and
America ranges:
- LI1: forward
- LI2: reverse
- LI3/LI4: 4 preset speeds
- Local controls for the Asia range
Multiple assignment makes it possible to mix several functions on one input (example:
LI1 assigned to forward and preset speed 2
LI3 assigned to reverse and preset speed 3)
Positive logic State 0 if < 5 V, state 1 if > 11 V
Max. sampling time: 20 ms
Negative logic Available by programming on the Asia range only
State 0 if > 11 V or logic input not wired, state 1 if < 5 V
Max. sampling time: 20 ms
DO output Factory setting:
- 2 kHz PWM (1) open collector output. Can be used for electromagnetic
galvanometer
- Max. current 10 mA
- Output impedance 1 kW, linearity 1%, max. sampling time 20 ms.
Assignable as logic output:
- Open collector logic output, output impedance 100 W, 50mA max
- Internal voltage (see above, available internal supplies)
- External voltage 30 V max: 50 mA
Relay outputs (RA-RC) 1 protected relay logic output (contact open on fault).
Minimum switching capacity: 10 mA for c 24 V.
Maximum switching capacity:
b On resistive load (cos j = 1 and L/R = 0 ms): 5 A for a 250 V or c 30 V
b On inductive load (cos j = 0.4 and L/R = 7 ms): 2 A for a 250 V or c 30 V
Maximum I/O connection capacity 1.5 mm 2 (AWG 14)
Acceleration and deceleration ramps Ramp profiles: linear from 0.1 to 99.9 s.
Automatic adaptation of deceleration ramp time if braking capacities exceeded,
possible inhibition of this adaptation (use of braking module).
Braking to a standstill By d.c. injection: automatically to a standstill as soon as the frequency drops to zero.
Period adjustable from 0.1 to 30 s or continuous, current adjustable from 0 to 1.2 In
Main protection and safety features of the drive b Thermal protection against overheating
b Protection against short-circuits between output phases
b Protection against overcurrent between output phases and earth, at power-up only
b Line supply overvoltage and undervoltage safety circuits
b Line supply phase loss safety function, for 3-phase supply.
Motor protection Thermal protection integrated in the drive by continuous calculation of the l2t.
Thermal memory reset on power down.
Insulation resistance to earth MW > 500 (electrical isolation)
Frequency resolution Display units: 0.1 Hz
Analog inputs: 0.1 Hz for 200 Hz max.
Time constant for reference change ms 5
(1) Pulse width modulation
Altivar 11
T/Tn
2
4
1,7
1,5
3
1,25
1
2
0,75
1
0,5
0,25
0 N (Hz)
0 12 25 37 50 75 100
0 15 30 45 60 90 120
Special uses
Use with a motor with a different rating to that of the drive
The device can supply any motor which has a power rating lower than that for which
it is designed.
For motor ratings slightly higher than that of the drive, check that the current
absorbed does not exceed the permanent output current of the drive.
Altivar 11
Altivar 11
ATV 11ppppppE Europe range
kW A A A W kg
Single phase supply voltage: 200240 V 50/60 Hz
0.18 2.9 1.1 1.6 12 ATV 11HU05M2E 0.900
Altivar 11
ATV 11ppppppU America range
(5)
1.5/2 17.1 7.5 11.2 77 ATV 11HU29M2U 1.800
(5)
2.2/3 24.1 10.6 15 101 ATV 11HU41M2U 1.800
(5)
3-phase supply voltage: 200230 V 50/60 Hz
0.18/0.25 1.8 1.6 2.4 13.5 ATV 11HU05M3U 0.900
(1) The line current value is given for the measurement conditions indicated in the table below.
Drive rating Prospective Isc Line voltage
ATV 11pUF1U 1 kA 100 V
ATV 11pUM2U 1 kA 208 V
ATV 11pUM3U 5 kA 208 V
(2) The current value is given for a 4 kHz switching frequency.
(3) For 60 seconds.
(4) Drive supplied without EMC filter. To order an EMC filter separately, see page 60252/5.
(5) With integrated fan.
ATV 11HU41M3U
Altivar 11
ATV 11ppppppA Asia range
(1) The line current value is given for the measurement conditions indicated in the table below.
Drive rating Prospective Isc Line voltage
ATV 11pUF1A 1 kA 100 V
ATV 11pUM2A 1 kA 200 V
ATV 11pUM3A 5 kA 200 V
(2) The current value is given for a 4 kHz switching frequency.
(3) For 60 seconds.
(4) Drive supplied without EMC filter. To order an EMC filter separately, see page 60252/5.
(5) With integrated fan.
ATV 11HU41M3A
Altivar 11
kg
Advanced dialogue solution All ratings See page 60200/3
PowerSuite
Braking resistors Not protected ATV 11pU05 ppp (1) VW3 A58702 0.600
(IP 00) ATV 11pU09 ppp (1)
ATV 11pU12 ppp (1)
ATV 11pU18 ppp (1)
ATV 11pU29 ppp (2)
Plates for mounting on 5 rail ATV 11pU05 ppp VW3 A11851 0.220
(width 35 mm) ATV 11pU09 ppp
VW3 A5873p ATV 11pU12 ppp
ATV 11pU18Mpp
Adaptor plate for replacing Altivar 08 All ratings VW3 A11811 0.220
Earthing plate for EMC mounting All ratings VW3 A11831 0.100
550494
VW3 A11852
Altivar 11
5,5
=
2x
142
120
H
b
c G
=
125 = 60 =
16,5
= =
a 72
ATV 11 a b c G H
HU05ppE/U, 72 142 101 601 1311 5
PUppppE/U
HU05ppA, 72 142 108 601 1311 5
PUppppA
ATV 11HU09ppU/A ATV 11HU12M2E, ATV 11HU18M2E
5,5
=
2x
142
120
H
b
c G 138 = 60 =
16,5
=
= =
a 72
ATV 11 a b c G H
HU09ppU 72 142 125 601 1311 5
HU09ppA 72 142 132 601 1311 5
ATV 11HU18MpU/A ATV 11HU18F1U/A, ATV 11HU29MpE/U/A, ATV 11HU41MpE/U/A
=
2x 4x
b
b
H
c G c = G =
=
=
= =
a a
ATV 11 a b c G H ATV 11 a b c G H
HU18MpU 72 147 138 601 1311 5 HU18F1U, HU29MpE/U, HU41MpE/U 117 142 156 1060,5 1311 5
HU18MpA 72 142 145 601 1311 5 HU18F1A, HU29MpA, HU41MpA 117 142 163 1060,5 1311 5
EMC input filters VW3 A11401 to A11404 Protected braking resistors Non protected braking resistors VW3
VW3 A58732 and A58733 A58702 and A58704
(2-wire output, length 0.5 m)
=
154
170
8,5
H
b
310
30 = 40 =
332
60
Braking module VW3 A11701
(for mounting on AM1-ED rail)
c = G =
a
90
VW3 a b c G H
61 = =
=
Altivar 11
ATV 08 adaptor plate VW3 A11811 Plates for mounting on 7 rail VW3 A11851 and A11852
142
143,6
143,6
32,9 77,5 37,9 77,5 39,9 122,8
(1)
59,9
(2)
61
23,3 59
15 67,6
(1) 2 screws supplied for fixing the earthing plate.
(2) 5 x M4 mm screws for fixing EMC clamps.
Mounting recommendations
b Install the unit vertically, at 10.
b Do not place it close to heating elements.
b Leave sufficient free space to ensure that the air required for cooling purposes can circulate, by natural convection or by ventilation, from the
bottom to the top of the unit.
b Free space in front of unit: 10 mm minimum.
-10 C to 40 C
d 50 mm: no special precautions.
d = 0 (mounted side by side): remove the protective cover from the top of the drive.
40 C to 50 C
d 50 mm: remove the protective cover from the top of the drive.
50 C to 60 C
d 50 mm: remove the protective cover from the top of the drive, and derate the
nominal current of the drive by 2.2% per C above 50 C.
When the operating conditions are close to the maximum limits (power, cycle and
temperature), this type of use must be checked beforehand, by monitoring the
thermal state of the drive.
Altivar 11
5
1
Q1 Q1
6
2
(4)
3
1
(4)
KM1 KM1
4
2
L1
N/L2
RA
RC
LI1
LI2
LI3
LI4
+ 15 V
DO
L1
L2
L3
RA
RC
LI1
LI2
LI3
LI4
+ 15 V
DO
+5V
+5V
PA/+
PA/+
PC/
PC/
AI1
0V
AI1
0V
W
W
U
U
V
V
W1
W1
U1
V1
U1
V1
A2 A2
+
+
PA
PB
PA
PB
speed speed
3 3 0 -20 mA
reference 0 -20 mA reference
or or
4 -20 mA 4 -20 mA
Braking Braking
resistor resistor
0-10 V 0-10 V
(external power supply) (external power supply)
2-wire control 3-wire control Analog voltage input Analog current input
External 10 V use 0-20 mA or 4-20 mA
ATV 11 control terminals ATV 11 control terminals ATV 11 control terminals ATV 11 control terminals
+ 15 V
+ 15 V
LI1
LI1
LI2
LIx
LIx
AI1
0V
AI1
0V
Speed Source
LI1: Forward LI1: Stop reference 0 -20 mA
LIx: Reverse LI2: Forward potentiometer or
LIx: Reverse 2.2 to 10 k 4 -20 mA
For combinations of KM1, Q1, etc, components (see the table on page 60251/5).
Altivar 11
Electromagnetic compatibility
b Earths between the drive, the motor and the cable shielding must have "high frequency" equipotentiality.
b Use shielded cables with shielding connected to earth at 360 at both ends for the motor cables, and if necessary the braking module and
resistor and control-signalling cables. Conduit or metal ducting can be used for part of the shielding length provided that there is no break in
continuity.
b Ensure maximum separation between the power supply cable (line supply) and the motor cable.
7 6
8
Note: If using an additional input filter, it must be mounted under the drive and connected directly to the line supply via a non-shielded cable. Link 3 on the drive is
then via the filter output cable.
Although there is an HF equipotential earth connection between the drive, the motor and the cable shielding, it is still necessary to connect the PE protective
conductors (green-yellow) to the appropriate terminals on each of the devices.
Altivar 11
Summary of functions
Operating speed range page 60255/3
Acceleration and deceleration ramp times page 60255/3
Second ramp page 60255/3
Deceleration ramp adaptation page 60255/3
Preset speeds page 60255/4
Configuration of analog input AI1 page 60255/4
Analog or logic output DO page 60255/4
Forward/reverse operation page 60255/4
2-wire control page 60255/5
3-wire control page 60255/5
Automatic d.c. injection page 60255/5
Switching frequency, noise reduction page 60255/5
Fault relay, unlocking page 60255/5
Fault reset page 60255/6
Automatic restart page 60255/6
Automatic catching a spinning load with speed detection page 60255/6
Controlled stop on loss of line supply page 60255/6
Drive thermal protection page 60255/6
Motor thermal protection page 60255/6
Monitoring page 60255/7
Incompatible functions page 60255/7
Functions specific to the Asia range page 60255/7
Drive factory setting
To facilitate the setting up of the drive, the functions have been programmed to the meet the
requirements of the most common applications.
Altivar 11
ESC ENT 4
2
5 RUN STOP 6
Altivar 11
f (Hz)
LSP
Reference
0V 5V
0V 10 V (external power supply)
0 mA 20 mA
4 mA 20 mA
f (Hz) f (Hz)
50/60 50/60
0 t 0 t
t1 t2
Linear acceleration ramp Linear deceleration ramp
Adjustment of t1 : 0.1 to 99.9 s Adjustment of t2 : 0.1 to 99.9 s
factory setting 3 s. factory setting 3 s.
b Second ramp
Used to switch 2 acceleration or deceleration ramp times, which can be adjusted separately.
Enabled by means of 1 reassignable logic input.
It is suitable for machines with fast continuous speed correction and high speed lathes with
acceleration and deceleration limiting above certain speeds.
f(Hz)
1
LI4 0 t
Altivar 11
b Preset speeds
Used to switch preset speed references.
Choice between 2 or 4 preset speeds.
Enabled via 1 or 2 logic inputs.
The preset speeds can be adjusted in increments of 0.1 Hz from 0 Hz to 200 Hz.
They take priority over the reference given via the analog input or, for the Asia range, on the
drives potentiometer.
f (Hz)
The speed obtained with inputs
LIx and LIy at state 0 is LSP or the
speed reference, depending on
the level of analog input AI1.
Factory settings :
LSP
1st speed : LSP (low speed or
t reference)
1 4th speed : 50 Hz
LIx 0 t
LIy 0
Example of operation with 4 preset speeds.
0V
AI1
0V
Speed Supply
0-20 mA
reference
potentiometer or
2.2 to 10 kW 4-20 mA
Diagram with internal power supply Diagram with external power supply
0V
DO
DO
Z Z
+U
0V
Power supply
Altivar 11
b 2-wire control
Used to control the direction of operation by means of a maintained contact.
Run (forward or reverse) and stop are controlled by the same logic input.
Enabled by means of 1 or 2 logic inputs (one or two directions).
This function is suitable for all non-reversing and reversing applications.
3 operating modes are possible :
v detection of the state of the logic inputs
v detection of a change in state of the logic inputs
v detection of the state of the logic inputs with forward operation always having priority over
reverse
f (Hz)
0 t
Stop 1
0 t
Forward 1
0 t
Reverse 1
0 t
Altivar 11
b Fault reset
Used to clear the stored fault and restart the drive if the cause of the fault has disappeared.
The fault is cleared by a transition of the logic input LI which is assigned to this function.
Factory setting : function inactive.
The restart conditions after a reset to zero are the same as those of a normal power-up.
The following faults can be reset : drive thermal overload, motor thermal overload, line supply
overvoltage, overvoltage on deceleration, overspeed, line phase loss (1), line supply
undervoltage (2).
b Automatic restart
Enables the drive to be restarted automatically after locking following a fault if this fault has
disappeared and if the other operating conditions permit a restart.
This restart is performed by a series of automatic attempts separated by increasingly longer
waiting periods: 1 s, 5 s, 10 s, then 1 minute for the following periods.
If the drive has not restarted after 6 minutes, the drive locks and the procedure is abandoned
until the drive is powered down and back up again.
Factory setting : function inactive.
Restart authorised with the following faults : drive thermal overload, motor thermal overload, line
supply overvoltage, overvoltage on deceleration, line phase loss (1), line supply undervoltage
(2).
If the function is enabled, the drives safety relay remains activated until one of these faults
appears. This function requires the speed reference and the direction of operation to be
maintained, and is only compatible with 2-wire level control.
This function is suitable for machines or installations in continuous operation or without
monitoring, and where a restart will not endanger equipment or personnel in any way.
b Automatic catching a spinning load with speed detection ("catch on the fly")
Used to restart the motor smoothly after one of the following events:
v loss of line supply or power down
v fault reset or automatic restart
v freewheel stop triggered by a fault.
On restarting, the effective speed of the motor is detected in order to restart on the ramp at this
speed and return to the reference speed. The speed detection time can be up to 1 s depending
on the initial deviation.
Factory setting : function inactive.
This function requires the activation of 2-wire level control and is not compatible with the
continuous d.c. injection function.
This function is suitable for machines for which the loss of motor speed is negligible during the
line supply loss time (machines with high inertia).
f (Hz)
1 Fast stop
2 Normal stop on deceleration ramp
3 Freewheel stop
1 2 3
t
Altivar 11
b Monitoring
The display shows the state of the drive or, if selected, one of the following values :
v Frequency reference
v Output frequency applied to the motor
v Motor current
v Line voltage
v Motor thermal state
v Drive thermal state
Incompatible functions
The choice of the last function configured is enabled, whatever the configuration of the previous
functions.
Application functions can be assigned to the same logic input, in which case one logic input
enables a number of functions (for example : direction of operation and 2nd ramp).
A check must be carried out to ensure that the functions are compatible.
b Direction of operation and 2-wire control : forward operation can only be assigned to LI1.
b Direction of operation and 3-wire control : forward operation can only be assigned to LI2.
b Automatic restart : requires the configuration of 2-wire level control. Changing the
configuration of the type of control disables automatic restart.
b Automatic catching a spinning load with speed detection :
v requires the configuration of 2-wire level control. Changing the configuration of the type of
control disables automatic catching a spinning load.
v not compatible with continuous d.c. injection braking to a standstill. Configuring this function
disables automatic catching a spinning load.
Telemecanique
Altivar 11
Real efficiency
at a reduced size!...
Altivar 11 :
The little one with
big prospects...
Voltage ranges:
120 V single-phase.
240 V single-phase.
230 V 3-phase.
...for all
your applications
from 0.18 to 2.2 kW
Thanks to the the advanced flux vector
control and specific application
functions of the Altivar 11:
Parking barriers
Exceptional dynamics:
Use of an advanced flux vector motor control
minimises cycle times.
Customisation of "Up / Down" cycles due to the
assignment of several functions on the same logic input:
Different ramps for up / down cycles.
Up priority if obstructed going down.
Different pre-selectable speeds both for up / down
cycles.
Answers to abrupt weather changes:
Perfect for simple mechanical Operation assured down to -10C.
applications in industrial and
commercial sectors:
Hoardings
Serial configurations and simplified maintenance:
Mechanical handling: Use of PowerSuite software workshop
conveyors, garage doors, parking on standard PC or Pocket PC.
barriers, supplying conveyors, etc... Optimisation of size
Use of baseplate version.
Special machines: Solutions for power supply line noise:
grinders, saws, drills, exercise Built-in EMC class B filters.
equipment, hoardings, Reduction in generated pollution:
extractors, dough mixers, etc... Switching frequency of 16 kHz.
The performance and simplicity
of the Altivar 11 will make you Dough mixers
forget multispeed motors, Perfect control of this motor drive application:
mechanical drives, DC drives, Without tripping as the dough hardens.
special motors and electro- Protection of personnel:
mechanical starters, etc. Due to the low leakage current of the Altivar 11,
It easily replaces all these solutions. the drive can be associated with a 30 mA differential
circuit-breaker. This also includes models with a
built-in EMC class B filter.
Conveyors
Tailored ergonomics, as near to the operator
as possible:
Simple setting-up using local controls:
start / stop buttons and potentiometer for
setting speed available on the drive.
mep ATV 11 flash corAng 10/07/02 13:23 Page 5
Identical performance
to the Greats
Total control of your machines:
Uninterrupted
service
High degree of monitoring and protection at all levels:
Of the motor
thermal protection by continuous calculation of I2t.
Robustness
to meet every Of the drive
challenge thermal protection by PTC probe integrated in the
Even in severe power module,
environments from protection against short-circuits between output
-10 up to +50 C, phases.
the Altivar 11 is safety related to the supply line:
perfectly - overvoltage,
operational - undervoltage,
without any - phase failure (on 3-phase)
degradation in its
performance. Of personnel
Due to the low leakage current of the Altivar 11,
the drive can be associated with a 30 mA differential
circuit-breaker. This also includes models with a
built-in EMC class B filter.
mep ATV 11 flash corAng 10/07/02 13:24 Page 6
Perfect suitability
The smallest drive for any application
in the world !
The compactness of the Altivar 11 considerably
reduces the size of your enclosures and, in
addition, reduces the size yet again due to the
possibility of mounting several drives side by side.
The closest
possible to
machines...
International coverage
The Altivar 11 could
not be closer to
your machine:
it can be installed
directly on its
framework (version Built-in
on baseplate). EMC
class B Local
The use of natural Current NEC filter controls
convection up to 208 V 1999 (Europe). and
0.75 kW makes (North negative
them ideal where America). logic.
silent operation is
necessary.
(Asia).
Protect
everything in
memory with
PowerSuite* software
* Replace the letter " H " by " P " to obtain the reference of the version on a baseplate.
** Add 7 mm to the depth for the Asia range.
mep ATV 11 flash corAng 10/07/02 13:23 Page 2
A comprehensive range
of Motor Starters
Increase your performance with
Variable speed drives the associated TeSys components*
Circuit-breakers,
Differential
circuit-breakers,
Altivar 11 Altivar 38
0.18 to 2.2 kW 0.75 to 315 kW
Contactors.
Altivar 28
0.37 to 15 kW
Altivar 58 Altivar 68
0.37 to 75 kW 75 to 630 kW
A unique partner,
a global presence
Head office
89 boulevard Franklin Roosevelt
92504 Rueil Malmaison Cedex Owing to changes in standards and equipment, the characteristics given in the text
VVDED102051EN
FRANCE and images in this document are not binding until they have been confirmed with us.
http://www.schneider-electric.fr Production: 3000 NR
Photos: Schneider Electric - ImageBank
038996 06/2002