30gx Pro
30gx Pro
30gx Pro
ECG-UG-00-001
SPECIFICATION
N
06/12/00
DATE
USER'S GUIDE
REV: original
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONTENTS
1 - INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.1 - About This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.2 - Manual Structure and contents . . . . . . . . . . . . . . . . . . 4 4.2.4.7 - Service 4 configuration from Service
Tool . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
2 - GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 4.2.4.8 - Service 4 configuration from Main
2.1 - Generalities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Interface, runtime sub menu . . . . . . 31
2.1 - Software Reference Number . . . . . . . . . . . . . . . . . . . . 7
2.3 - Abbreviations Used . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4.2.5 - User Configuration . . . . . . . . . . . . . . . . . . . . . . 32
3 - HARDWARE DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . 8
3.1 - Produc Component . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 4.2.6 - Network Configuration . . . . . . . . . . . . . . . . . . 32
3.1.1 - Basic Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 4.2.6.1 - General . . . . . . . . . . . . . . . . . . . . . . . 32
3.1.2 - CCN/Clock Option Board . . . . . . . . . . . . . . . . . 10 4.2.6.2 - Configuring a Control as a
3.1.3 - Screw Compressor Protection Module . . . . . 11 Broadcast Acknowledger . . . . . . . . 32
3.1.3.1 - Screw Compressor Module Layout 11 4.2.6.3 - Setting Time and Date . . . . . . . . . . 32
3.1.3.2 - Compressor Part Number/MTA Header 4.2.6.4 - Alarm Configuration Table . . . . . . 33
Configuration . . . . . . . . . . . . . . . . . . . . 12 4.2.6.5 - Master/Slave Configuration . . . . . 35
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONTENTS
6 - CCN COMPATIBILITY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
1 - INTRODUCTION
1.1 - ABOUT THIS MANUAL
This manual is intended to be used as an additional guide for using and configuring the Pro-Dialog control for
the 30GX & HX chillers. The use of this document does not substitute the IOM.
This manual is intended for use by Service organizations inside the Carrier corporation. It is delivered on
the express condition that it is not to be disclosed, reproduced in whole or in part, or used for
manufacture by anyone other than Carrier Corporation.
v Hardware description
v Control description
v Appendixes
The introduction and product general description sections contain information about this manual as an overview
of the 30GX&HX Pro-Dialog Plus controls.
The hardware section provides complete information on boards, devices and connections used by the product.
The control description section is divided in several subsections. First provides a main description of hardware
configuration. This subsection provides sufficient information to runs the control in the most operating cases. For
more complete information, use the remaining sections and also IOM. Second subsection describes all the unit
configuration and the methods to modify it. The last subsections describe the unit control logics.
2 - GENERAL DESCRIPTION
2.1 - GENERALITIES
PRO-DIALOG controls compressors and loaders needed to maintain the desired leaving or entering water
control point. It automatically sets the position of the electronic expansion valve to maintain a correct refrigerant
flow in the cooler. For air cooled units it controls the operation of the fans to maintain the correct condensing
pressure in each circuit.
Safety circuits in the unit are constantly monitored by PRO-DIALOG to ensure its safe operation. PRO-DIALOG
also gives access to a Quick Test program covering all inputs and outputs excepted compressors outputs.
The control features of the 30GX&HX Pro-Dialog Plus are divided into standard features and options
(additional board needed):
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Standard features:
w Local control
w CCN control
w Compressor & loader sequence control (up to 4 compressors - two loaders per compressor)
w Ramp loading
w Delay at startup
w Temperature reset
w Diagnostics function
w Alarm POC
w Reclaim sensors
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Fans x x
2 Separate Circuits with 1 to 8 fans per circuit
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CSA-SR-208410XX
The two last digits (XX) provides the software version (e.g. 2.0).
15 digits reference number can be displayed in the CCN configuration Ctrl_ID table through the Building
Supervisor, the Network Service Tool or the 30GX&HX Downloader.
Unit Main Interface Configuration Menu allows to display the software version: item #13, user 1 menu.
In this manual, the refrigeration circuits are called circuit A and circuit B. The compressors in circuit A are
labeled A1, and A2. Those in circuit B are B1 and B2.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
3 - HARDWARE DESCRIPTION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
COMPONENT USAGE
UNIT TYPE : AIR COOLED - MORE THAN 2 FAN STAGES (if no AUX board) or MORE
THAN 4 FAN STAGES (AUX BOARD) PER CIRCUIT
NUMBER OF COMPRESSORS
COMPONENTS
1 2 3 4
PD4 - BASIC BOARD 1 1 1 1
PD4 - SCPM BOARD 1 2 3 4
PD4 - EXV BOARD 1 2[2] 2[2] 2[2]
4x DO BOARD 2[3] 2[3] 2[3] 2[3]
AUX 2 BOARD (8xDO) 1[3] 1[3] 1[3] 1[3]
NRCP BASIC BOARD 0 1[4] 1[4] 1[4]
4 x AI-2xAO BOARD 1[1] 1[1] 1[1] 1[1]
AUX 1 BOARD 1[1] 1[1] 1[1] 1[1]
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The PD4 - Basic board is 24VAC power supplied. It contains 8 Discrete Inputs (Switch type), 8 Digital Outputs (5
triacs and 3 relays), 10 Analog Inputs (five thermistors and four pressure transducers) and 1 analog input (0-10
Vdc) . See the schemes in Appendix E. The software is contained in a Flash EPROM (downloadable only with
Downloader). All the setpoints, runtime and configuration parameters are contained in an EEPROM (data
storage at power down).
J4 & J5 15 a & 15 b Cooler flow switch & customer interlock (lock_1) All
The PD4 - Global chiller controller has a small option board that can be connected to the Basic Board via a
single 10 pin header and 4 metal standoff. This option board contains one RS-485 driver for CCN
communication, a real time clock and super cap for two weeks backup. There are two connectors for CCN. One
is a 3 pin screw connector ( 1= + signal, 2 = ground signal, 3 = - signal) and the other is a 6 pins phone jack.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This board shall monitor compressor pressure transducer, temperature sensors, oil level, high pressure switch,
motor cooling solenoids, oil pumps, motor current, compressor wye-delta startup and compressor protection.
N.B :Only Y dip switch of the 4 is used to configure start-delta startup procedure (when in ON
position), the 3 others shall remain OFF ! If not, MTA header configuration alarm will occur.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DO #1 TO CONTACTOR # 1
DO #2 TO CONTACTOR # 2
DO #4 TO OTHER CONTACTORS
11 12 12 4 3 2 1 TERMINAL J4
24 VAC DO
POWER SUPPLY
TRIAC
pins 12 are connected together
TRIAC
TRIAC
TRIAC
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
143 mm ( 5.60 in )
l l
------
PD4-AUX1 32GB 500 322 EE CEPL130487-01 STATUS SIO
J9
J1
-- G +
3 2 1
24VAC
12 11
SIO
-- G +
3 2 1
CH14
T
P
J8
V 75 mm
R S V
CH14
T (2.95
P in)
V
R S V
CH13
CH13
J4 J5
J3
J2
J7
CH -- CH -- CH -- CH -- CH -- CH -- CH -- CH -- CH CH
J6
CH -- CH -- -- --
1 2 3 4 5 6 7 8 9 10 11 12
------
All are standard 24 VAC/10%. All 24Vac common ground must be connected together on board and to 24Vac
ground pin of J1. All DOs total consomption = 115VA
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The EXV board shall be able to drive both unipolar and bipolar stepper motors via a common connector. The
default configuration shall be unipolar, 30 steps/s step rates and 1500 steps range such as to allow easy retrofit
with Pro-Dialog phase 1, 2 and 3 units fitted with Mueller Brass EXVs. It shall be able to handle 12V @ 0.5 A per
coil and maintain a step rate of at least 200 steps per second (unipolar or bipolar).
Note: board shall be able to handle a total coil load of 1 Amp for unipolar and 2 Amps for bipolar.
Connection to the EXV shall be done through two Molex, 5 pin, 3.91 pitch (one per EXV) [J2A & J2B].
This board provides 4 analog inputs (labeled AI #1, AI #2, AI #3, and AI #4 on the terminal J2) and 2 analog
outputs (labeled AO #1 and AO #2 on the terminal J1). It allows to use the following features:
w Optional reclaim thermistors when reclaim option is not used
w Remote discharge transducer on remote condenser on split units.
w Optional varifan on air cooled units or water valve on water cooled units
Each input can be independently configured with a bridge allowing to close 3 pair of pins named T,C or V.
J2
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
J2
C unused 1-R 1: +
R: -
C unused 1-R 1: +
R: -
Each output can be independently configured with a bridge allowing to close 2 pair of pins named C or V.
J1
ANALOG BRIDGE FUNCTION PINS REMARKS
OUTPUT POSITION
V 0- 10 Vdc Varifan circuit 5-R 5: +
A or water valve R: -
AO #1
C 4 - 20 mA Varifan 5-R 5: +
circuit A or water valve R: -
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This board is used on global chiller as slave board for air cooled units with reclaim option or cooler heater option.
It contains 8 Discrete Inputs (switch type), 10 Digital Outputs (8 triacs and 2 relays), 6 Analog Inputs (four 5K or
10K thermistors and two active pressure transducer types) and 1 analog output (0-10 Vdc).
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
w Suction pressure
w Economizer pressure
w Economizer pressure on first compressor and also in the second compressor if unit is not equipped
with economizer
They are electronic sensors which linearise the output signal and deliver a 0 to 5 Vdc to either the basic board or
to an analog board. Three types of sensors are used.
They are used to measure discharge pressure and oil pressures when large band oil pressure transducer is not
selected. Carrier part: OP12DA039
4
Voltage (VDC)
0 50 100 150 200 250 300 350 400 450 500 PSI
345 689 1034 1379 1724 2068 2414 2758 3103 3447 kPa
Pressure
They are used to measure oil pressures for unit operating with low ambient (when large band oil pressure
transducer is selected). Carrier part: OP12DA057
4
Voltage (VDC)
-6.6 50 100 155 215 276 327 387 420 500 PSI
-45 345 689 1068 1484 1904 2252 2670 2895 3447 kPa
Pressure
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
These are in the low pressure side. Suction pressure transducer takes the place of the low pressure switches,
low pressure gauges and the low pressure safety switch (where these are usually fitted). Economizer pressure is
used to measure the intermediary pressure between low and high pressure. The oil pressure is subtracted from
this pressure to determine the oil differential pressure for oil pressure safety purpose.
4
Voltage (VDC)
3.3 - THERMISTORS
All thermistor, excepted the reset sensor, have similar characteristics (see next page).
They have Carrier Part No. HH 79 NZ 047
This is installed on the discharge pipe of each compressor. It is used to control the discharge superheat. The
discharge gas temperature (lowest discharge compressor temperature or average discharge temperature of both
compressors) is subtracted to the saturated condensing temperature to determine the discharge superheat.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Temp. Resistanc Temp. Resistanc Temp. Resistanc Temp. Resistanc Temp. Resistanc
e e e e e
(C) (OHMS) (C) (OHMS) (C) (OHMS) (C) (OHMS) (C) (OHMS)
-32,0 100 049,0 -3,5 20 075,9 24,0 5 203,2 52,0 1 694,0 80,0 602,4
-31,5 97 006,4 -3,5 19 560,8 24,5 5 088,1 52,5 1 663,5 80,5 592,4
-31,0 94 060,8 -3,0 19 060,6 25,0 4 976,0 53,0 1 633,5 81,0 582,8
-30,5 91 209,3 -2,5 18 574,8 25,5 4 866,8 53,5 1 604,1 81,5 573,4
-30,0 88 449,0 -2,0 18 102,9 26,0 4 760,2 54,0 1 575,2 82,0 564,4
-29,5 85 777,0 -1,5 17 644,5 26,5 4 656,4 54,5 1 546,9 82,5 555,7
-29,0 83 190,7 -1,0 17 199,1 27,0 4 555,2 55,0 1 519,0 83,0 547,2
-28,5 80 687,1 -0,5 16 766,3 27,5 4 456,6 55,5 1 491,6 83,5 539,1
-28,0 78 263,9 0,0 16 345,7 28,0 4 630,4 56,0 1 464,7 84,0 531,2
-27,5 75 918,3 0,5 15 936,9 28,5 4 266,7 56,5 1 438,3 84,5 523,6
-27,0 73 648,0 1,0 15 539,5 29,0 4 175,4 57,0 1 412,3 85,0 516,2
-26,5 71 450,6 1.5 15 153,1 29,5 4 086,3 57,5 1 386,8 85,5 509,2
-26,0 69 323,7 2,0 14 777,5 30,0 3 999,6 58,0 1 361,6 86,0 502,3
-25,5 67 265,0 2.5 14 412,2 30,5 3 915,0 58,5 1 336,9 86,5 495,7
-25,0 65 272,4 3.0 14 056,9 31,0 3 832,5 59,0 1 312,6 87,0 489,4
-24,5 63 343,7 3,5 13 711,4 31,5 3 752,1 59,5 1 288,7 87,5 483,2
-24,0 61 476,9 4,0 13 375,3 32,0 3 673,7 60,0 1 265,2 88,0 477,4
-23,5 59 670,0 4.5 13 048,3 32,5 3 597,3 60,5 1 242,1 88,5 571,6
-23,0 57 920,9 5,0 12 730,1 33,0 3 522,9 61,0 1 219,3 89,0 466,1
-22,5 56 227,9 5,5 12 420,5 33,5 3 450,2 61,5 1 196,9 89,5 460,8
-22,0 54 589,1 6,0 12 119,2 34,0 3 379,4 62,0 1 174,8 90,0 455,6
-21,5 53 002,7 6.5 11 826,0 34,5 3 310,4 62,5 1 153,2 90,5 450,6
-21,0 51 467,0 7.0 11 540,5 35,0 3 243,1 63,0 1 131,8 91,0 445,7
-20,5 49 980,4 7,5 11 262,7 35,5 3 177,5 63,5 1 110,9 91,5 440,9
-20,0 48 541,1 8,0 10 992,1 36,0 3 113,4 64,0 1 090,2 92,0 436,3
-19,5 47 147,7 8,5 10 728,8 36,5 3 051,0 64,5 1 069,9 92,5 431,8
-19,0 45 798,6 9.0 10 472,3 37,0 2 990,1 65,0 1 050,0 93,0 427,4
-18,5 44 492,4 9.5 10 222,6 37,5 2 930,7 65,5 1 030,3 93,5 423,0
-18,0 43 227,6 10,0 9979.3 38,0 2 872,8 66,0 1 011,0 94,0 418,8
-17,5 42 002,9 10,5 9742.5 38,5 2 816,2 66,5 992,1 94,5 414,5
-17,0 40 816,9 11,0 9 511,7 39,0 2 761,1 67,0 973,4 95,0 410,3
-16,5 39 668,3 11,5 9287.0 39,5 2 707,2 67,5 955,1 95,5 406,0
-16,0 38 555,9 12,0 9068.0 40,0 2 654,7 68,0 937,1 96,0 401,8
-15,5 37 478,4 12,5 8854.7 40,5 2 603,4 68,5 919,4 96,5 397,6
-15,0 36 434,7 13,0 8 469,9 41,0 2 553,3 69,0 902,1 97,0 393,3
-14,5 35 423,7 13,5 8 444,5 41,5 2 504,4 69,5 885,1 97,5 389,0
-14,0 34 444,2 14,0 8 247,2 42,0 2 456,6 70,0 868,4 98,0 384,7
-13,5 33 495,2 14,5 8 055,0 42,5 2 410,0 70,5 952,0 98,5 380,3
-13,0 32 575,6 15,0 7 867,7 43,0 2 364,4 71,0 836,0 99,0 375,8
-12,5 31 684,6 15,5 7 685,1 43,5 2 319,9 71,5 820,2 99,5 371,1
-12,0 30 821,0 16,0 7 507,2 44,0 2 276,3 72,0 804,8 100,0 366,5
-11,5 29 984,0 16,5 7 333,9 44,5 2 233,8 72,5 789,8 100,5 361,6
-11,0 29 172,7 17,0 7164.9 45,0 2 192,2 73,0 775,0 101,0 356,7
-10,5 28 386,3 17,5 7 000,3 45,5 2 151,5 73,5 760,6 101,5 351,5
-10,0 27 623,8 18,0 6 839,8 46,0 2 111,7 74,0 746,5 102,0 346,3
-9,5 26 884,4 18,5 6 683,4 46,5 2 072,8 74,5 732,6 102,5 341,1
-9,0 26 167,5 19,0 6 530,9 47,0 2 034,7 75,0 719,2 103,0 335,3
-8,5 25 472,2 19,5 6 382,3 47,5 1 997,4 75,5 706,1 103,5 329,7
-8,0 24 797,8 20,0 6 237,5 48,0 1 960,9 76,0 693,3 104,0 323,8
-7,5 24 143,6 20,5 6 096,3 48,5 1 925,1 76,5 680,8 104,5 317,9
-7,0 23 509,0 21,0 5 958,7 49,0 1 890,1 77,0 668,6 105,0 311,6
-6,5 22 893,2 21,5 5 824,6 49,5 1 855,7 77,5 656,8 105,5 305,3
-6,0 22 295,6 22,0 5 693,9 50,0 1 822,1 78,0 645,2 106,0 298,6
-5,5 21 715,7 22,5 5 566,4 50,5 1 789,1 78,5 634,0 106,5 292,1
-5,0 21 152,6 23,0 5 442,2 51,0 1 756,8 79,0 623,2 107,0 285,2
-4,5 20 606,4 23,5 5 321,2 51,5 1 725,1 79,5 612,6
-4,0 20 075,9 24,0 5 203,2 52,0 1 694,0 80,0 602,4
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.2 - CONFIGURATION
4.2.1 - General
Four types of configuration are available:
w The factory configuration. It describes the "hardware" structure of the unit (e.g. the number of compressors,
valve...). This configuration is accessible through the Main Interface Factory menu Menus or the Network
Service Tool and can be done by Carrier factory or service only.
w The Service configuration. It allows to modify operating parameters. This configuration is accessible
through the Main Interface Service Menus or the Network Service Tool and can be done by Carrier
factory or service only.
w The User configuration. It allows to modify a limited number of simple parameters (i.e. loading sequence,
start-up delay, cooler pumps control, reset select...). This configuration can be done through the Main
Interface or through the Network Service Tool. This configuration can be modified by the customer.
w The network configuration. It allows to modify parameters used by network functions (i.e. Alarm POC,
Broadcast ...). This is accessible through the Building Supervisor or the Network Service Tool.
4.2.2 -Main interface configuration sub menu tree structure
CONFIGURATION SUB MENUS
USER SERVICE FACTORY
0 USEr MEnu SErViCE MEnu "FACtorY MEnu"
1 USEr 1 SErViCE 1 "FACtorY 1 MEnu"
2 USEr 2 SErViCE 2 "FACtorY 2 MEnu"
I 3 dAtE SErViCE 3
T 4 SCHEduLE 1 MAStEr SLAvE
E 5 SCHEduLE 2
M 6 HoLidAY
S 7 broAdCASt
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Network Service tool allows to view and modify the factory configuration (table FACTORY in 'Modify
Controller').
Parameters from 1 to 16 in version 1.x are the same than those in the new version 2.X.
For Retrofit from verson 1.x to the new 2.x, it is better to write down in a paper, configuration items
from 1 to 16. Use Service Tool to upload all the configuration from version 1 (example address 1).
Then use address search function to change the address to 2 before downloading the new software
version 2.x. Use Service Tool to add a new controller with a different addresse (example address 1 for
version 1 and address 2 for version 2). Once Upload configuration is done, fill factory configuration in
FACTORY table and then download this.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
13. Yes = Use Pro_dialog 4 auxiliary boards instead of old 4xAO-2xAO board and 4xDO board
No = Use old 4xAO-2xAO board & 4x DO board (shall be set to no for version 1 retrofit)
3. When this item is selected, both compressor use the common economizer transducer in the economizer.
Otherwise, each compressor uses it own economizer transducer, located in the refrigerant injection pipe
line, near the motor cooling valve. Economizer pressure represents the intermediary pressure between
high pressure and low pressure. It is used to determine the oil differential pressure (oil pressure -
economizer pressure).
4. The use of large band oil pressure transducer is required for low ambient application and is only applied on
oil pressure transducers since high pressure range transducer can not read pressure lower than 2.4 bars,
Calibration is automatically determined each time the control is in OFF mode and both suction and
discharge pressures are equalized. Differences between oil pressures and suction pressure are then
stored as offset (if less than 0.4 bar).
5. MTA configuration is required for capacity calculation, motor current measurement and protection. This
value shall match the one read from MTA header configuration on screw compressor board, if not an alarm
will be generated.
6. If only reclaim sensor is selected and reclaim option is not, an 4xAI-2xAO board is required, and reclaim
temperature sensor are used for information only.
7. Reclaim option requires an Aquasnap Basic board for reclaim entering and leaving temperatures,
solenoids, an analogue output to control the reclaim condenser water valve, 2 transducers for reclaim
pumpdown injection pressure.
8. This items indicates the number of pass the cooler fluid goes through the cooler. For example, if cooler
enters from circuit A and goes out by circuit A and only 1 time, then a number of 2 shall be entered. This
item is used for exv control when caculating cooler pinch.
9. This items indicates if cooler leaving temperature sensor is in the circuit A or not. If cooler leaving pipe line
is on side A, then Yes shall be entered, otherwise, no shall be required. This item is used for exv control
when caculating cooler pinch.
10. Cooler heater option requires an Aquasnap Basic board for refrigerant isolation solenoids and heater
output.
11. Factory password is required when accessing the main interface factory menu. Factory password can be
used to access to service and user configuration sub menus.
12. 1500 = For Muller valve, Unipolar, 1500 steps, 33 steps/s (1500 steps shall be kept !!!)
15000 = For Muller valve phase 3, Bipolar, 15300 steps, 300 steps/s (for future use,)
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
SCPM A1
TQ output (done)
THA
THB
EXV BOARD
TQ output (done)
SCPM B1
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Network Service tool allows to view and modify the service configuration table SERVICE1. Unit shall be
stopped and under CCN Operating Type control.
Note: this table canl be downloadable at any time. However, modified value shall not be used by tasks until the
unit is in off state . This shall not apply to the Varifan/water valves gains that shall be modified at any time and
used immediately by the head pressure control tasks even if the unit is in operation.
1. > 1 = Water
2 = Brine
3 = Low Brine
2. Used to set fan cycling. Decreasing this value will increase fan cycling. This timer can be reduced since the
unit is fitted with an important number of fan stages, as to increase the condensing control accuracy. But in
certain cases, notably on units with few fan stages, at too small value can causes superheat hunting
problems.
3. Used to set fan cycling. Default value is 5 ^C, 11.1^C or higher value are recommanded if unit has varifan.
This value can be increased on units with few fan stages to avoid superheat hunting problems.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4. This configuration applies to varifan or water valve upon unit type. It is used to adjust the head pressure
control PID loop. Normally this decision has not to be modified for Varifan. For water valve it can be
adjusted upon water valve type and installation.
6. This setpoint is used by the EXV control in order to maintain an optimal cooIer exchange delta temperature
between leaving temperature and saturated suction temperature. This is done in compensation with
discharge superheat temperature which has higher priority.
9. The Global chillers use compressors which have better performance at full load than at part load.
Therefore the loading sequence strategy will be different from the one for flotronic II or pro-dialog 30 G & H
control. When compressor is on, it will try to avoid the compressor operate at low capacity (no loader ON).
If this item is enable, the control will use any stage of capacity in order to keep the exchanger leaving
temperature as closed at possible to the control point what ever the compressor performance. When the
circuit is in capacity override (compressor status LEDs in the synopsis are blinking), the control will force
the close control capacity variable to enable until the circuit is no more in override.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
10. This decision allows to set the setpoint which is used for auto Z Multiplier calculation. The Z Multiplier
calculation tries to maintain, for each compressor, a maximum number of starts per hour equal to [zm_spt].
Thus, decreasing the setpoint shall increase the reactivity of the auto Z Multiplier to compressors cycling.
11. The Z Multiplier parameter allows to adjust the on/off time delay between compressors staging. It doesn't
affect loaders staging. Increasing this value shall increase the on/off time delay but shall reduce the
accuracy on the leaving temperature control.
w Tthe current Z Multiplier is the result of calculation based on the number of starts of compressors.
However, the maximum Z multiplier calculation will be limited to the value entered in this decision.
12. This item allows the entering fluid control. Default is leaving fluid control. Entering fluid control can be used
for small charge.
The main interface allows to view and modify the service configuration table SERVICE1. Unit shall be stopped
and service password or factory password are required.
4 [2] hd_sp_pg Setpoint head pressure control - Proportional gain for Varifan or water valve control. Masked if
the Varifan or the water valve is not selected (hd_selec = 0).
5 [2] hd_sp_ig Setpoint head pressure control - Integral gain for Varifan or water valve control. Masked if the
Varifan or the water valve is not selected (hd_selec = 0).
6 [2] hd_sp_dg Setpoint head pressure control - Derivative gain for Varifan or water valve control. Masked if the
Varifan or the water valve is not selected (hd_selec = 0).
8 [2] dsh_sp_b Discharge superheat setpoint circuit B (displayed only if cap_b1 > 0).
10 [2] pinc_p_b Cooler pinch T setpoint Circuit B (lwt - sst setpoint displayed only if cap_b1 > 0).
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Network Service tool allows to view and modify the service configuration table SERVICE2. Unit shall be
stopped and under CCN Operating Type control.
3. This decision allows to limit the setpoint of the customer (control point shall be higher than this value). It is
mostly used for brine application, as freezing condition depends on ratio on glycol and water.
4. Used for cooler heater operation, this item is applied to outside temperature to determine the freeze
conditions (see cooler heater operation section).
5. This item allows to use capabilities and functions based on CCN and clock..
6. If enable, when chiller looses communication with the System Manager, it shall force the its CHIL_S_S
variable to enable and auto all other variables. Chiller restarts in stand alone mode with default setpoint .
7. This decision allows to enter the entering temperature dead band for reclaim operation mode. See reclaim
operation description.
8. This decision allows to enter the delay between two air cooled to reclaim injection sessions. See reclaim
operation description.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
9. This decision allows to set the minimum position in percent of the reclaim condenser water valve. See
reclaim operation description.
10. This decision allows to set the maximum position in percent of the reclaim condenser water valve. See
reclaim operation. See reclaim operation description.
11. coefficient A in delta F / percent for circuit. This decision allows to set the coefficient A of the saturated
condensing temperature control point determination (rsp_a, for circuit A or rsp_b for circuit B) for each
circuit when reclaim operation is active. See the items description below and reclaim operation description.
12. offset B in delta F. This decision allows to set the offset B of the saturated condensing temperature control
point determination (rsp_a, for circuit A or rsp_b for circuit B) for each circuit when reclaim operation is
active.
The main interface allows to view and modify the service configuration table SERVICE2. Unit shall be stopped
and service password or factory password are required.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Network Service tool allows to view and modify the service configuration table MAINCFG. Unit should be
stopped and under CCN Operating Type control.
1 MAINTENANCE CONFIG
2
3 Servicing Alert Enable/Disable Disable - s_alert
4
5 Refrigerant Charge Ctrl Enable/Disable Disable - charge_c
6 Water Loop Control Enable/Disable Disable - wloop_c
7 Air Exchanger Control Enable/Disable Disable - aexch_c
8
9 CPump 1 Ctl Delay (days) 0 to 1000 0 - cpump1_c
10 CPump 2 Ctl Delay (days) 0 to 1000 0 - cpump2_c
11 HPump Ctrl Delay (days) 0 to 1000 0 hpump_c
12 Water Filter Ctrl (days) 0 to 1000 0 - wfilte_c
13 A1 Oil Filter Ctl (days) 0 to 1000 0 ofila1_c
14 A2 Oil Filter Ctl (days) 0 to 1000 0 ofila2_c
15 B1 Oil Filter Ctl (days) 0 to 1000 0 ofilb1_c
16 B2 Oil Filter Ctl (days) 0 to 1000 0 ofilb2_c
The main interface allows to view and modify the service configuration table MAINCFG. Unit should be stopped
and service password or factory password are required.
This table is used for service maintenance alert and not available today.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Network Service tool allows to view and modify the service configuration table UPDTHOUR. Unit should be
stopped and under CCN Operating Type control.
Note: this table shall be used for purposes of transplanting the devices on time or starts number in the event of a
module hardware failure or software upgrade via downloading. It shall be usable only if all items are still nul.
Afterwards, its access shall be denied.
4.2.4.8 - Service 4 configuration table from main interface, runtime sub menu
The main interface allows to view and modify the service configuration table UPDTHOUR. Unit shalld be stopped
and service password or factory password are required.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This configuration is accessible by the customer. Parameters can be modified either through the unit main
interface (see iom manual), the Network Service Tool (see appendix).
4.2.6.1 - General
This configuration is used to set network functions. It can be done through the Building Supervisor or the Network
Service Tool.
In order for CCN functions to operate properly, one and only one Broadcast Acknowledger is required per bus.
The modification of the time and date of a Pro-dialog controller can be done through the network. Setting the
correct date and time is necessary for units connected on a network which collects alarms.
Select Building-Time. This allows to send time of day, date, day of week to all controllers
connected to the network.
When Building-Time is selected, the Service Tool clock is displayed:
Press F2 to transmit this data to the network. If the displayed time is incorrect, modify your PC
time or set the correct time and date on screen.
Note: If no broadcast aknowledger has been configured on the bus, a communication error will be
displayed. However, controller connected on the network will be set to the date displayed on
screen.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Pro-Dialog control has an alarm configuration table associated with it: ALARMDEF. This table can be
accessed through the Modify Controller menu of the Network Service Tool. This table needs to be configured
only if the unit is network connected to a Building Supervisor, an Autodial Gateway or a Dataport 2, and only if
these options are configured to receive network alarms.
The parameters which are configured in this table determine the handling of alarms.
This decision determines which CCN system elements will receive and process alarms sent by the
Pro-Dialog. Input for the decision consists of eight digits, each of which can be set to either 0 or 1. Setting a
digit to 1 specifies that alarm will be sent to the system element that correspond to that digit. Setting all digits
to 0 disables alarm processing. Digits in this decision correspond to CCN elements in the following manners:
Dataport 2
Autodial Gateway(s)
Local Building
Supervisor(s)
00000000
Note: If the CCN network does not contain a Building Supervisor, Autodial Gateway, or Dataport 2 to
serve as an alarm acknowledger, all digits in this decision shall be set to 0 in order to prevent
unnecessary activity on the CCN communication bus.
Default 00000000
A Building Supervisor uses the value in this decision when sorting alarms by level. Within any group of
alarms that all have the same level, the Building Supervisor sorts alarms according to Alarm Equipment
Priority.
Default 4
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This decision specifies the amount of time that will be allowed to elapse between alarm retries. Retries occur
when an alarm is not acknowledged by a network alarm acknowledger, which may be either a Building
Supervisor, an Autodial Gateway, or a Dataport 2. If the acknowledgement is not received, the alarm will be
retransmitted after the number of minutes specified in this decision.
Default 10 minutes
REALARM TIME
This decision specifies the amount of time that will be allowed to elapse between re-alarms. A re-alarm
occurs when the condition that caused the initial alarm continues to persist for the number of minutes
specified in this decision. Re-alarming will continue to occur at the specified interval until the condition
causing the alarm is corrected.
Default 30 minutes
This decision specifies the system element name that will appear in alarms generated by the Pro-Dialog
control.
Default PRO_30GX
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The MST_SLV table can be accessed through the Modify Controller menu of the Network Service Tool or the
main interface. This table needs to be configured if the master/slave function is used. Master/slave function
allows the Pro-Dialog unit to operate as master or a slave in a two chillers plant. See section 4.20.
1 MASTER/SLAVE CONTROL
2
3 Master/Slave Select: 0/1/21 0 - ms_sel
4 0 = Disable
5 1 = Master
6 2 = Slave
7 Master Control Type: 1/2/3 1 - ms_ctrl
8 1 = Local Control
9 2 = Remote Control
10 3 = CCN Control
11 Slave Address 1 to 236 1 - slv_addr
12 Lag Start Timer 2 to 302 10 min lstr_tim
13 Lead/Lag Balance Yes/No3 No - ll_bal
14 Lead/Lag Balance Delta 40 to 4004 168 hours ll_bal_d
15 Lag Unit Pump Control 0/1 0 - lag_pump
16 0 = Stop if Unit Stops
17 1 = Run if Unit Stops
18 Lead Pulldown Time 0 to 605 0 minutes lead_pul
Decisions description:
1. This decision allows the unit to operate as master or a slave in a two chillers master/slave. The master
chiller monitors all external commands as start/stop, demand limiting, setpoint select or reset via CCN bus.
Control of the slave chiller is done through commands (start/stop, demand limit, setpoint, heat cool)
emitted by the master chiller. The slave will not be allowed to operate as a slave if its CHIL_S_S,
CTRL_PNT or DEM_LIM, HC_SEL variables has a force priority higher than a control force.
2. This timer is started when all conditions to start the lag chiller are satisfied. Lag chiller shall not be started
until this timer is elapsed. To be set in the master unit table only.
3. This decision allows to activate two chillers lead/lag balance function. It is used for master/slave chiller
running time equalization. When this function is active, once per day or each time the master chiller is
switched from the off to the on state the control determines the lead chiller based on both chillers run hours
delta. When the run hours delta is greater than the configured lead/lag balance delta then a changeover
will occur and the unit with the smallest operating hours value will become the lead. This function cannot
operate if the master chiller demand limit is less than 100%. In that case, the master chiller will always be
the lead. To be set in the master unit table only.
4. This function allows to set the lead/lag balance delta used for master/slave chiller running time
equalization. Lead/lag changeover occurs when the lead/lag operating time delta overlaps the configured
balance value and provided that master unit is not under demand limit control.
5. This decision allows to set the lead chiller pull down duration before the lag chiller starts.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
A contact to check the status of a safety loop is provided (cooler flow switch and customer interlock are wired
internally in series). Its function is to prevent the unit from starting if the contact is open while the delay at startup has
expired. The contact must also stay closed as long as the unit is not stopped through Local, Remote or CCN control.
If the cooler pump is controlled by the pro-dialog and if the cooler contact is closed after 2 minutes the cooler pump
is turned OFF provided that the contact is failed CLOSED, the alarm 75 shall be active and the unit can't no more
start until manual reset.
This function is applied only for air cooled units and is related to the cooler pump function when the unit state is OFF
or when unit operates as a lag chiller in master/slave operation and in standby mode. This is provided on outdoor
unit as a safeguard against the cooler freezing. The cooler heater is associated with refrigerant isolation solenoids,
one output per circuit whose goal is to prevent the refrigerant from migrating into the condenser when chiller is
stopped.
w If the outdoor air temperature is below the cooler heater trip point and if either the saturated suction temperature
of circuit A or saturated suction temperature of circuit B are lower than the cooler heater trip point plus 3.3 ^C,
the cooler heater shall be activated.
w Normally the isolation valves shall prevent refrigerant in the cooler from migrating into the condenser. For this
case, cooler heater can ensure cooler protection efficiently without the need of using cooler pump.
w If it is not the case (SST remain low), the pump shall be turned on every 7 minutes to check freezing conditions
and additional heat to the cooler : cooler fluid temp (< 3 - [SSTa + SSTb]/2). Pump shall be turned of if cooler
fluid temp > (8C - [SSTa + SSTb]/2).
w If both saturated suction temperatures of circuit A and circuit B are greater than the cooler heater trip point plus
5.5 ^C, the cooler heater shall be turned off. The pump shall be allowed to stop.
Each circuit has its own oil separator fitted with an oil heater. Both circuit oil heater are controlled independently .
Since there is no oil temperature sensor, the oil heater will be controlled based on the saturated condensing
temperature as follows :
wOil heater ON when outside temperature is below 17C.
wOil heater OFF when outside temperature is above 25C
wOil heater OFF when circuit is in operation or oil level is low (oil_sw is OPEN).
The screw compressor motors used in the Global Chiller control are refrigerant cooled. The control strategy for motor
cooling relies on vapor at light loads, and supplementary liquid refrigerant at high loads. Each compressor will have
its own cooling solenoid. An additional motor cooling solenoid is required when operating in high condensing
temperature. It is automatically controlled by pro-dialog even if it is not mounted in the units. The motor cooling
solenoids shall be cycled to allow liquid to cool the motor. The main motor cooling solenoid control is based on the
motor temperature and its setpoint (83C) using a quasi-fuzzy logic. The additional motor cooling solenoid control is
just based on the discharge gas temperature.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The sub cooling plate exchanger replaces the old economizer for simple maintenance and cost reduction. Thus the
screw compressor motors are cooled by refrigerant from the plate exchanger, located between condenser and exv
(see scheme below). The refrigerant flow through this exchanger for motor cooling purpose is controlled by a
thermal expansion valve. The opening of this valve is done by heating its internal resistor via 24 vac ouput signal
from the screw compressor board, channel 13. For circuit which has 2 compressors, an additional solenoid (see
scheme below, x=a for circuit A, x=b for circuit B) shall be controlled to balance motor temperatures. These solenoid
output are located at channel 14 of the screw compressor board.
compressor 1
plate exchanger cpx1_mc2
Condenser
sub-cooling compressor 2
cpx2_mc2
Evaporator
EXV
(refer to factory configuration and wiring for retrofit, pages, 21, 23 and 24)
Tq valve opening position depends on the heat (resistor is the image) on the TQ valve and also the equali-
sation pressure located at plate exchanger (in our application, quite the same than economiser pressure).
With the same economiser pressure, the higher heating signal is commanded (CPA1_PUL, or
CPB1_PUL), the lower is the resistor and the more the valve is opened.
With same heating signal value, if the economiser pressure increases, the valve will tend to close. And
vice versa
Based on this relation, if the feedback signal is enabled, the control will check all the time the relation TQ
position = F (economiser pressure/TQ resistor) and shall make a kind of override (absolutely required at
the start-up, resistor is very high)
When a value of 200 is sent on CPA1_PUL or CPB1_PUL (hardware SIO variable) some time, that means
resistor value is a little above the minimum position, preheat is sent.
This value is sent also when loading capacity.
When the economiser pressure is steady, and TQ resistor is near to the pre-opening position, regular
control (PID) is used.
TQ resistor sensor is connected to the EXV board. The value read is in K Ohms MTQ_RESA (for circuit
A), MTQ_RESB (for circuit B). During regular operation, value read shall be from 0.7 k Ohm to 4 k
Ohms.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This function adjusts the number of active compressors and loaders to keep the leaving water temperature at the
setpoint. The precision with which this is achieved depends upon the capacity of the water loop, the water flow
rate, the load and the number of capacity control steps available. The control continuously takes account of the
temperature error with respect to the control point, the rate of change of the leaving fluid temperature and the delta
of temperatures between the entering and leaving fluid in order to determine the optimum time to add or subtract
steps of capacity.
Note: a too important number of starts of a particular compressor will automatically cause a limitation of the
compressors starts. This will affect the precision of the water loop temperature control.
The control calculates the SMZ: load/unload factor. It is compared to the z_multiplier to determine when to add or
remove stage:
w If (sum/z) > +z_multiplier -> stage = +1 (add a compressor)
w If (sum/z) > +0.6 and if a loader is available (loader is OFF) -> stage = +1 (add a loader)
w If (sum/z) < - z_multiplier -> stage = -1 (remove one compressor)
w If sum/z) < -0.6 and loader is avaialble (loader is ON) -> stage = -1 (turn off one loader)
The z_multiplier factor allows to indirectly increase the compressor on/off time delay. In consequence, it can be
adjusted (increased) to avoid compressors short cycling. This function requires the following Service configuration:
vAuto Z Multiplier sepoint (zm_spt). Default to 6.
vCooling and heating Z Multiplier max value (hc_zm). default to 6.0.
This function adapts the z_multiplier to the unit compressor cycles number (the cycle number shall be based on
the compressor which has been the most started during an hour). The significant period for compressors cycling
shall be of one hour.
If the cycle counter exceeds the setpoint (zm_spt), then the z_multiplier value shall be increased based on the
cycle number (PID loop). The function shall not take care of the loaders cycling.
The calculated value of the z_multiplier shall not exceed the configured hc_zm.
If the unit returns to normal operating condition with a cycles counter going down then the calculated z_multiplier
shall progressively return to its normal value (zm = 1.0). The rate at which the calculated z_multiplier returns to
normal shall be lower than the rate at which it is increased.
The setpoint value shall allow to adapt the auto z multiplier calculation to the installation. The setpoint ranges
from 4 to 6.
During normal operation, each modification of the unit capacity is followed by a dead time when no capacity
modification is possible. The duration of this dead time is 90 seconds.
4.8.1.3 - Overrides
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
sum/z ratio will be overridden if any one of the following conditions is satisfied.
Note : When overrides 2,3 , 5, 6, 16, 17, 18, 19, 20, 21 are active, the variable close control (cls_ctrl) shall be
enabled whatever the configuration to allow unloading the last loader in the circuit.
This function allows customer to limit the total current (it does not include current of fans, valves, heaters, oil pumps
...) of all the compressors during operation. The chiller current limit can be modified through USER configuration
(USER table or User configuration by main interface). This function is similar to demand limit function.
wIf the chiller current is greater than the chiller current limit , then a stage of capacity will be removed.
wIf chiller current plus the added current of selected compressor is greater than the chiller current limit, the
increase of capacity will not be allowed. If the compressors is OFF, its added current is 80% of its MTA. If the
selected compressor is on but deos not reach 100% capacity, an added stage on the same compressor will add
40% of its current.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Global chillers uses compressors which have better performance at full load than at part load. Therefore, the
loading sequence strategy will be different than for the flotronic II or for the Pro-dialog 30 G & H. The following list
applies only to capacity control. For High Ambient Unloading, it can be overridden.
1. A compressor will not be started until all other running compressors are 100% loaded.
2. On units with 3 compressors, both circuits cannot have their loaders off at the same time once 3 or
more of the compressors in the unit are on. Where possible, the circuit which is starting a
compressor will be the one which is to be unloaded.
3. Any time a lag compressor in a circuit is starting, the loaders in the circuit shall be turned off
(unloading all compressors in the circuit). This shall be done 15 seconds prior to starting the new
compressor. 15 seconds after the new compressor has started, the loaders shall be set to their
desired state. When a lead compressor is starting, all loaders shall be turned off when the
compressor relay is turned on (+/- 2 seconds), and shall be set to their desired state 15 seconds
after the compressor has been started.
4. There shall be a configuration decision for "close control", which (when selected) will cause the
control to utilize all of the loading devices to achieve better leaving water temperature control.
5. Whenever any compressor in a circuit is going to be stopped normally, the circuit shall be fully
unloaded for 15 seconds prior to shutting down the compressor. This shall not apply when the
reason for a shutdown is due to an alarm condition.
7. For any shutdown, all compressors and loaders will be shut down at the same time.
For more than 2 compressors, two types of sequencing are available and configurable by the user through either the
Main Interface or through the CCN network:
w Equal circuit loading: The control shall attempt to maintain equal capacity between the circuits as the machine
loads and unloads.
w Staged circuit loading: The control shall load the lead circuit completely before the lag circuit is started. When
the load is decreasing the lag circuit shall be unloaded first.
Circuit compressors sequence select shall try to equalize the compressor starts number. That means any
compressor in the circuit can become the lead compressor if it has the lowest starts number, however, this shall be
balanced with the operating hours.
Loaders in the same circuit are commanded simultaneously. Thus one loader variable is displayed.
When a circuit is overridden (compressor status are blinking in the synopsis) because of low suction
temperature, low or high discharge temperature or high condensing temperature (high pressure), or high
current then no capacity increase shall be allowed on the affected circuit. This circuit is selected to unload
capacity first when unloading capacity condition is required.
Each compressor has three stages capacity. Simulation had been done to determine the average capacity
corresponding to those stages as following :
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.10.1 - General
The EXV is controlled to maintain minimum pinch for insuring the cooler exchange performance through the delta
temperature between the cooler fluid and the saturated suction temperature. EXV opening movement will normally
decrease the cooler pinch and thus increase the cooler exchange performance. But it shall not open too much
provided a drop in discharge superheat , low oil pressure and refrigerant flow.
The EXV control shall deal with two goals : Smaller Cooler Pinch and Discharge Superheat Protection.
Additional protection against excessive EXV opening is applied to ensure the condenser heat transfer (sub cooling).
It may happen when operating in high condensing temperature and indirectly high discharge superheat, exv would
tend to open continuously to get the lower pinch due to the setpoint and unfortunately in certain conditions, this value
has reached the limit, though it is higher than the setpoint. Therefore, EXV position limit shall be set when there is
no more variation in cooler pinch for a variation of EXV position of 4 percent.
EXV position shall also be limited to avoid hunting problem due to low discharge superheat protection. It may occur
when operating in a low condensing temperature, the discharge superheat protection can switch from enable to
disable in few scans and so on.
This control uses a kind of auto adaptive method whose goal is to find out the optimal position of EXV for insuring an
optimal pinch with a correct discharge superheat and sub cooling.
4.10.2 - Overrides
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Head pressure differential value and head pressure differential timer can be adjusted in the Service menu.
Decreasing these values will increase fan cycling. This differential value and timer can be reduced since the unit is
fitted with an important number of fan stages, as to increase the condensing control accuracy. But in certain cases,
notably on units with few fan stages, at too small value can causes superheat hunting problems.
Varifan PID gains can be modified in the Service menu (not recommended). See section 4.2.3.
To avoid fan cycles and also to ensure a minimum expected SCT for oil pressure, SCT control shall be
adjusted based on OAT, the same for SCT differential as
55C (13F1)
SC + 1 fan
T
co
nt
ro
lp
oin
t
SCT Diff
40C (104F)
35C (95F)
35C (95F)
- 1 fan
0c 20c OAT
32F 68F
4.12.1 - Air Cooled Condensing Pressure Control - Fan staging with Aux board
Each DO shall support only one fan. The first DO is not used if varifan is present to standardize the way
of making connection and to avoid wiring mistake.
The combination described here below is for 4 fans configured maximum, each DO commands 1 fan
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The following combinations are used for a circuit with more than 4 fans configured
The control of a common water valve for both circuits is required. The water valve control will be based on the
highest saturated condensing temperature of both circuit or based on the operating circuit if the other is OFF.
Water valve PID gains can be modified in the Service menu (when unit is OFF). See section 4.2.3. They are
accessible though the table SERVICE1 and can be modified during operation.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This function shall be used to avoid circuit high pressure trip while the condensing pressure reaches a configurable
override threshold (Service 1 Configuration).
wIf the saturated condensing temperature is greater than the maximum condensing temperature (mct_sp) minus
the maximum condensing temperature override differential (mct_diff) but less than the maximum condensing
temperature (mct_sp) then the circuit capacity increase shall be inhibited.
wIf the saturated condensing temperature is greater than the maximum condensing temperature (mct_sp) then the
circuit capacity shall be reduced. The first capacity stage shall never be turned off even if that causes a circuit
high pressure trip.
wIf the circuit capacity has been reduced due to high condensing temperature override then the circuit capacity
increase will not be allowed for 5 minutes even if the saturated condensing temperature is below the maximum
condensing temperature (mct_sp) minus the maximum condensing temperature override differential. This shall
avoid compressor cycling.
This function shall be used to avoid circuit high current trip while the motor current reaches a configurable override
threshold (Service 1 Configuration).
wIf the current is greater than the maximum current threshold (curr_max) minus the maximum current override
differential (curr_diff) but less than the maximum current threshold (curr_max) then the circuit capacity increase
shall be inhibited.
wIf the current is greater than the maximum current threshold (curr_max) then the circuit capacity shall be reduced
by removing a loader or the affected compressor.
wIf the circuit capacity has been reduced due to current override then the circuit capacity increase will not be
allowed for 5 minutes what ever current measured. This shall avoid compressor cycling.
If the selected compressor is operating with at least one loader ON, then all the loaders in the same circuit shall be
de-energized for 15 seconds before stopping the compressor.
Both circuit shall decrease its capacity progressively every 15 seconds. One loader is immediately de-energized. The
last loader will be de-energized in 15 seconds later. Then all compressors, oil solenoids and oil pump will be
de-energized in 15 seconds after the last loader is turned OFF.
Here is an example of the stopping function with time indicator for a circuit with both loaders ON before receiving a
STOP command.
t = t0 loader_2 = OFF
t = t0 + 15s loader_1 = OFF,
t = t0 + 30s All the compressors, oil solenoids and oil pumps shall be de-energized
The exv shall be closed in one minute after the last compressor is de-energized or after the difference between
discharge and suction pressure is lower than 58 psi
note : Both circuits can be stopped in different timing depending on the status of their loaders when the
STOP command is received. Maximum duration for stopping the unit is 30 seconds. A circuit can be stopped
immediately if no loader is ON before going to stopping procedure.
If the circuit or the hole unit are failed by alarms freeze, low sst, cooler flow, all the compressors are shut off
immediately. Otherwise, it shall respect procedure above.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Suction pressure (kpa) < 240 240 < AND <350 > 350
Oil setpoint 1(kpa) 70 86 104
DP - SP (kpa) < 861 861 < AND < 1137 > 1137
Oil setpoint 2(kpa) 0.235* (DP - SP) + 4 2* (DP - SP) - 1516 0.63645* (DP - SP) + 35
* DP = Discharge Pressure
* SP = Suction pressure
The oil pump is generally used to provide pre-lubrification of the compressor. Moreover, it is controlled to insure a
correct oil pressure during capacity transition or during operation with low condensing temperature that cause a drop
of oil pressure to avoid tripping in alarm.
Thus the oil pump is turned ON when the Differential Oil Pressure is lower than Oil Setpoint 1 plus 13 kpa.
and remained ON until Differential Oil Pressure is greater than Oil Setpoint 1 plus 35 kpa AND difference between
discharge and economizer pressure is greater than Oil Setpoint 1 plus 150 kpa to avoid oil pump cycles.
ALARM 68 for Compressor A1, ALARM 69 for Compressor A2, ALARM 70 for Compressor B1, ALARM 71 for
Compressor B2.
DOP: Differential Oil Pressure for the appropriate compressor. DOP = Oil pressure - Economizer pressure.
Economizer pressure is the common (econ_sel = YES) Economizer Pressure transducer reading for the
circuit involved or the appropriate economizer pressure transducer (econ_sel = NO) associated to the
compressor.
A. Compressor has started with Normal Ambient (oat > 10 C) or or condenser temperature (temp > 18C)
1. If the compressor has been running for less than 5 seconds then ignore the alarm.
2. If the compressor has been running for more than 5 seconds but less than 30 seconds and
DOP < (Oil Setpoint1/30)*(Comp. Running Time [in seconds])
for 3 continuous readings, then the alarm shall be tripped.
3. If the compressor has been running for 30 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds,
then the alarm shall be tripped
B. Compressor has started with Low Ambient (oat < 10 C) or low condenser temperature (temp < 18C)
1. If the compressor has been running for less than 90 seconds then ignore the alarm.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
2. If the compressor has been running for more than 90 seconds but less than 180 seconds and
DOP < (Oil Setpoint1/90)*(Comp. Running Time [in seconds] - 90)
for 3 continuous readings, then the alarm shall be tripped.
3. If the compressor has been running for 180 seconds or more, then if:
a). DOP < Oil pressure setpoint1 for 15 continuous seconds,
OR
b). (Poil - Psuction) < Oil pressure setpoint2 for 15 continuous seconds,
then the alarm shall be tripped.
Action To Be Taken
1. If the alarm is tripped then the affected compressor shall be stopped. The other compressors shall
continue to run.
oil setpoint1
15 s delay
15 s delay
3 continued
3 continued reading values
reading values
0
5s 30s 90s 180s time from start
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
This function shall control the air cooled to reclaim or the reclaim to air cooled changeover process.
If the reclaim function has been selected, the reclaim shall become active when the entering reclaim temperature
comes below the reclaim setpoint minus the reclaim deadband and delay between the last air cooled to reclaim
session is elapsed. It shall become inactive when the entering reclaim temperature comes over the reclaim setpoint
plus the reclaim deadband.
During reclaim operation, if the pumpdown pressure is greater than 400 kpa (59 psi), the pumpdown procedure in
non_reclaim to reclaim session shall be initiated. When the number of these abnormal sessions exceeds 2 times,
the reclaim operation shall be aborted, the circuit shall return to air cooled mode and an alarm shall be displayed.
At power up or after reset or after the unit capacity goes down to 0%, the function shall return to air cooled mode.
This shall determine whether the unit shall return to air cooled mode. This can be caused by the following:
Cause #1: Reclaim operation active and reclaim select is no more active
Cause #2: Reclaim mode is active and the entering reclaim temperature is above the range of the reclaim
setpoint + the reclaim dead band divided by 2 : HR_EWT >rsp + hr_deadb/2
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
A non-reclaim to reclaim injection session has been required and at least one compressor is on and the unit is not
failed and the entering reclaim temperature is not failed and this one is below the reclaim setpoint - half of configured
reclaim deadband and delay between the last reclaim injection has elapsed.
Information on reclaim operation is available on table RECLAIM (hrstatus) or on INFORMATION menu (hr_status).
hr_status parameter shall contain reclaim operation indicator of both circuit in two digits, one digit per circuit (left digit
for circuit A, the other for circuit B) with the following description :
*note : in case of reclaim operation failure (alarm # 83 for circuit A, alarm # 84 for circuit B), hr_status will not be
initialized until the manual reset on main interface is done.
To avoid high pressure problem, the remained condenser (hr_val_x) can be turned ON if SCT is above reclaim
setpoint + 8.3 deg C and all fans are ON provided that fans staging is not enough to avoid the risk of exceeding high
pressure override threshold. When turning ON, the remained condenser (hr_val_a) is kept to ON for at least 3
minutes to let fans staging to be stabilized. This condenser can be turned OFF if it has been ON for more than 3
minutes and if saturated condensing temperature is below the reclaim setpoint (rsp) to ensure the reclaim operation
performance.
if unit is not in reclaim operation, then the reclaim condenser water valve remains in minimum position.
In reclaim operation :
wIf reclaim entering temperature is below 20 deg C, then reclaim condenser valve is at minimum position.
wIf reclaim entering temperature is above 40 deg C, then reclaim condenser valve is at maximum position.
wIf entering temperature is within the range 20 degC and 40 deg C, then reclaim condenser water valve position
will be an interpolation between minimum and maximum position.
Reclaim condenser heater is ON when entering or leaving fluid are lower than 3.0 deg C( 37.4 degF). It is turned
OFF when both temperatures are above 4.4 deg C (40.0 deg F).
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
4.19.1 - General
This function allows to perform master/slave plant control between two chillers linked by the CCN network. Master
and slave chiller need to operate on the same bus. Master/slave operations shall operate in cooling or heating mode.
To operate properly, the master and the slave chillers must have an additional CHWS sensor located on the
common chilled leaving piping when the water control is done on the outlet side. This CHWS sensor shall be
connected on each chiller basic board. When the water system control is done on the inlet side no additional CHWS
sensor is required.
Parallel chiller control with dedicated pumps is recommended. Chiller must start and stop its own water pump
located on its own piping. If pumps are not dedicated for each chiller pimping, chiller isolation valves are required:
each chiller must open and close its own isolation valve through the control (valve shall be connected to the pump
outputs).
Water system control with no individual chiller pump control is feasible. It is not recommended when the system load
is low or if the control point is close from the freeze water tripping point (because of system instability that can be
caused by the freeze protection override). System flow is constant even if the master or the slave chiller is stopped.
In that case, the system pump shall be controlled by the master chiller.
Series chillers with dedicated primary pumping and constant flow shall be feasible but not recommended. Pump
start/stop must be controlled externally. Each series chiller must control its own isolation and bypass valves: stopped
chiller must be isolated from water flow (chiller pump command shall be used for valves control. Each chiller must
open and close its own chilled isolation valve).
The master chiller shall monitor all external commands as start/stop, demand limiting or setpoint select. It needs to
be started in Master operating type. The slave chiller must operate in CCN mode. If the master chiller is turned off
while the master/slave function is active then, the slave chiller shall be stopped.
The master/slave linkage shall not be allowed to operate if any one of the slave chiller CTRL_PNT, DEM_LIM,
LAG_LIM, CTRL_PNT HC_SEL or LCW_STPT variables has a force priority higher than a control force. In that case,
the master slave operations shall not be allowed or shall be disabled.
The control of the slave chiller shall be done through commands emitted by the master chiller. The slave chiller has
no action in the master/slave operations: it shall only verify that CCN communication with its master is correct.
The master function shall provide the ability to select a lead chiller among the master and the slave. Selection shall
be based on the delta between the master and the slave run hours and shall try to optimize the runtime hours. If this
function is unused then, the lead chiller shall always the master. Lead/lag changeover between the master and the
slave due to hour balance shall occur during chiller operations odd days at 12:00 a.m. or at startup.
The lead chiller shall always be started first and the lag chiller shall be maintained at zero percent capacity through
master forcing the lag demand limit value (LAG_LIM) to 0%. The lag water pump shall be maintained off. When the
lead chiller cannot be loaded anymore (because it is loaded at its full available capacity or at the master demand
limit value) then the lag start timer is started. When the lag start timer is elapsed, if the error on the master controlled
setpoint is greater than 3^F and if the pulldown time is elapsed then, the lag chiller water pump shall be turned on (if
required by configuration) and the lag chiller shall be allowed to start through master forcing the lag chiller demand
limit value (LAG_LIM) to its own demand limit value. To ensure that the lag chiller will be unloaded first in case of
water load decrease then, the lead chiller setpoint error shall be reset of upwards 4^F provided that the lag capacity
is not zero.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The lead pulldown time tells how long after starting the lead chiller (one time after the master chiller status has been
manually started) before checking whether to start an additional chiller. This time delay gives the lead chiller a
chance to pull down the loop temperature before starting another chiller.
If a communication failure is detected between the master and the slave then, all master/slave functions shall be
disabled and chillers shall return to standalone operations until communication is reestablished.
Note: to ensure that no compressor is started before the flow rate is correctly established then, the water flow control
is absolutely required on the lag chiller for master slave operations.
The figures below illustrate master/slave application for the most common plant layouts. Those figures are not
exhaustive.
COOL_LWT
MASTER
SLAVE
LOAD
COOL_EWT COOL_EWT
COOL_LWT
MASTER
SLAVE
LOAD
COOL_EWT COOL_EWT
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
COOL_LWT
COOL_LWT
MASTER
SLAVE
LOAD
COOL_EWT COOL_EWT
COOL_LWT
COOL_LWT
MASTER
SLAVE
LOAD
COOL_EWT COOL_EWT
LOAD
BYPASS (controlled by chillers)
VALVES
If a communication failure is detected between the master and the slave then all master/slave functions shall be
disabled and chillers shall return to standalone operations until communication is reestablished.
If any chiller is stopped due to failure then the other chiller will be allowed to start with no delay.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Master/Slave Error
The following error shall be updated in the M_MSTSLV Maintenance table (priority order):
Master/slave sequence can be controlled through the Network Service Tool or PCDCT tools (see appendix,
M_MSTSLV Maintenance Table)
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
The Building Supervisor displays current alarms messages and their return to normal provided that the CCN table
ALARMDEF has been correctly configured.
The Network Service Tool Diagnostic Menu allows to display 5 current alarms messages (even if the ALARDEF table
is not configured).
The following gives the messages that shall be displayed by the Building Supervisor or from main interface.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
Alarms compressor
Alarm 101 Compressor A1 Motor Temperature Too High
Alarm 102 Compressor A1 Motor Temperaure Out of Range
Alarm 103 Compressor A1 High Pressure Switch
Alarm 104 Compressor A1 Over Current
Alarm 105 Compressor A1 Lock Rotor
Alarm 106 Compressor A1 Ground Fault
Alarm 107 Compressor A1 Phase Loss L1
Alarm 108 Compressor A1 Phase Loss L2
Alarm 109 Compressor A1 Phase Loss L3
Alarm 110 Compressor A1 Unbalance > 14 %
Alarm 111 Compressor A1 Unbalance > 18 %
Alarm 112 Compressor A1 No Motor Current
Alarm 113 Compressor A1 Star Delta Starter Failure
Alarm 114 Compressor A1 Contactor Failure
Alarm 115 Compressor A1 Unable To Stop
Alarm 116 Compressor A1 Phase Reversal
Alarm 117 Compressor A1 MTA Configuration Header Fault
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
6 - CCN COMPATIBILITY
30GX&HX Pro-Dialog 4 Control is compatible with:
wThe Building Supervisor
wThe Network Service Tool
The CESRNRCP53-10 shal be used for Aquasnap basic board download when cooler heater and reclaim option
are selected.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: GENUNIT PIC TABLE TYPE : 11H, instance 1
1 GENERAL PARAMETERS
2
3 Control Type Local/CCN/Remote1 - ctr_type N
4 Run Status running/Off/Stopping/Delay2 - status N
5 CCN Chiller Start/Stop Enable/Dsable3 - CHIL_S_S Y
6 Chiller Occupied? Yes/No4 - CHIL_OCC Y
7 Minutes Left for Start 0-15 min MIN_LEFT N
8 Heat/Cool Select Heat/Cool5 - HC_SEL Y
9 Heat Reclaim Select Yes/No10 - RECL_SEL Y
10
11 Alarm State Normal6 - ALM N
12 Current Alarm 1 nnn - alarm_1 N
13 Current Alarm 2 nnn - alarm_2 N
14 Current Alarm 3 nnn - alarm_3 N
15 Current Alarm 4 nnn - alarm_4 N
16 Current Alarm 5 nnn - alarm_5 N
17
18 Percent Total Capacity nnn % CAP_T N
19 Active Demand Limit Val nnn7 % DEM_LIM Y
20 Lag Capacity Limit Value nnn % LAG_LIM N
21 Current Setpoint nnn.n F SP N
22 Setpoint Occupied? Yes/No4 - SP_OCC Y
23 Control Point nnn.n8 F CTRL_PNT Y
24 Controlled Water Temp nnn.n F CTRL_WT N
25 External Temperature nnn.n F OAT N
26
27 Emergency Stop Enable/Emstop9 - EMSTOP Y
3 : Allows to Start/Stop the chiller only when unit under CCN control type. Forced value is displayed but unused
when the unit is not under CCN control.
4 : Occupied state. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real occupancy state. If the unit is not in CCN mode the forced value shall be unused and the regular time
schedule shall be used. Forced value and force code shall appear in the GENUNIT Points Display table only if the
unit is under CCN control.
5: Heat/cool select. This item can be forced. If the unit is in CCN mode, the forced value shall be used whatever the
status of the remote heat/cool contacts. If the unit is not in CCN mode the forced value shall be unused. Forced
value and force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
6 : Alarm status
wNormal (no alarm)
wPartial (alarm but unit is not down)
wShutdown (unit is down)
7: Active Demand Limit Value. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the external limit switch contact and whatever the value of the demand limit switch setpoint.
If the unit is not in CCN mode the forced value shall be unused. Forced value and force code shall appear in the
GENUNIT Points Display table only if the unit is under CCN control.
8: Control Point. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead of the
real control point calculation. If the unit is not in CCN mode the forced value shall be unused. Forced value and
force code shall appear in the GENUNIT Points Display table only if the unit is under CCN control.
9 : Active all the time even if the unit is not in CCN control type.
10: Heat Reclaim Select. This item can be forced. If the unit is in CCN mode, the forced value shall be used
whatever the status of the remote reclaim switch. Forced value and force code shall appear in the GENUNIT
Points Display table only if the unit is under CCN control.
DISPLAY SCREEN
TABLE NAME: CIRCA_AN PIC TABLE TYPE : 11H, instance 2
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: CIRCA_D PIC TABLE TYPE : 11H, instance 3
1 CIRCUIT A DISCRETE
2
3 Compressor 1 Output On/Off - CP_A1 N
4 Cp1 Mtr Cool Solenoid 1 On/Off - cpa1_mc1 N
5 Cp1 Mtr Cool Solenoid 2 On/Off - cpa1_mc2 N
6 Cp1, Oil Solenoid Out On/Off - cpa1_ols N
7 Compressor 2 Output On/Off - CP_A2 N
8 Cp2 Mtr Cool Solenoid 1 On/Off - cpa2_mc1 N
9 Cp2 Mtr Cool Solenoid 2 On/Off - cpa2_mc2 N
10 Cp2, Oil Solenoid Out On/Off - cpa2_ols N
11 Cir A, Loader 1 Output On/Off - ldr_1_a N
12 Cir A, Loader 2 Output On/Off - ldr_2_a N
13 Cir A, Oil Heater Output On/Off - oil_h_a N
14 Cir A, Oil Level Input Low/High - oil_l_a N
15 Cir A, Oil Pump Output On/Off - oilpmp_a N
16 Cir A Refrig Isolate Out On/Off - refa_iso N
17
18 FANS OUTPUT
19 Fan Output DO # 1 On/Off - fan_a1 N
20 Fan Output DO # 2 On/Off - fan_a2 N
21 Fan Output DO # 3 On/Off - fan_a3 N
22 Fan Output DO # 4 On/Off - fan_a4 N
23 Fan Output DO # 5 On/Off - fan_a5 N
24 Fan Output DO # 6 On/Off - fan_a6 N
25 Fan Output DO # 7 On/Off - fan_a7 N
26 Fan Output DO # 8 On/Off - fan_a8 N
27 Fan Staging Number 0-8 - FAN_ST_A N
DISPLAY SCREEN
TABLE NAME: CIRCB_AN PIC TABLE TYPE : 11H, instance 4
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: CIRCB_D PIC TABLE TYPE : 11H, instance 5
1 CIRCUIT B DISCRETE
2
3 Compressor 1 Output On/Off - CP_B1 N
4 Cp1 Mtr Cool Solenoid 1 On/Off - cpb1_mc1 N
5 Cp1 Mtr Cool Solenoid 2 On/Off - cpb1_mc2 N
6 Cp1, Oil Solenoid Out On/Off - cpb1_ols N
7 Compressor 2 Output On/Off - CP_B2 N
8 Cp2 Mtr Cool Solenoid 1 On/Off - cpb2_mc1 N
9 Cp2 Mtr Cool Solenoid 2 On/Off - cpb2_mc2 N
10 Cp2, Oil Solenoid Out On/Off - cpb2_ols N
11 Cir B, Loader 1 Output On/Off - ldr_1_b N
12 Cir B, Loader 2 Output On/Off - ldr_2_b N
13 Cir B, Oil Heater Output On/Off - oil_h_b N
14 Cir B, Oil Level Input Low/High - oil_l_b N
15 Cir B, Oil Pump Output On/Off - oilpmp_b N
16 Cir B Refrig Isolate Out On/Off - refb_iso N
17
18 FANS OUTPUT
19 Fan Output DO # 1 On/Off - fan_b1 N
20 Fan Output DO # 2 On/Off - fan_b2 N
21 Fan Output DO # 3 On/Off - fan_b3 N
22 Fan Output DO # 4 On/Off - fan_b4 N
23 Fan Output DO # 5 On/Off - fan_b5 N
24 Fan Output DO # 6 On/Off - fan_b6 N
25 Fan Output DO # 7 On/Off - fan_b7 N
26 Fan Output DO # 8 On/Off - fan_b8 N
27 Fan Staging Number 0-8 - FAN_ST_B N
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
TABLE NAME: OPTIONS PIC TABLE TYPE : 11H, instance 6
1 UNIT DISCRETE IN
2 Remote On/Off Switch Open/Close - onoff_sw N
3 Remote Heat/Cool Switch Open/Close - hc_sw N
4 Remote Reclaim Switch Open/Close - recl_sw N
5 Remote Setpoint Switch Open/Close - setp_sw N
6 Limit Switch Status Open/Close - limit_sw N
7 Interlock Status Open/Close - lock_1 N
8 Pump Run status On/Off - pump_def N
9 Condenser Flow Status Open/Close - condflow N
10 Electrical Box Thermostat Open/Close4 - elec_box N
11
12 UNIT DISCRETE OUT
13 Cooler Pump #1 Command On/Off1 - CLPUMP_1 Y
14 Cooler Pump #2 Command On/Off1 - CLPUMP_2 Y
15 Rotate Pumps Now? Yes/No1 - ROT_PUMP Y
16 Condenser Pump Command On/Off3 - COND_PMP Y
17 Cooler Heater Command On/Off - coolheat N
18 Critical Alarm Signal On/Off5 - SAFE_ALM N
19
20 UNIT ANALOG
21 Cooler Entering Fluid nnn.n F COOL_EWT N
22 Cooler Leaving Fluid nnn.n F COOL_LWT N
23 Condenser Entering Fluid nnn.n F COND_EWT N
24 Condenser Leaving Fluid nnn.n F COND_LWT N
25 CHWS Temperature nnn.n F CHWSTEMP N
26 External 0-10Vdc Signal nn.n Volts EXT_VDC N
27 Current Cond Setpoint nnn.n2 F COND_SP Y
28 Chiller Total Current nnn.n amps tot_curr N
1: Cooler pump control. This item can be forced On or Off if the unit is in CCN mode and if the CHIL_S_S is
disabled. If the unit is not in CCN mode the forced value shall be unused and the regular calculation shall be
used. Forced value and force code shall appear in the OPTIONS Points Display table only if the unit is under CCN
control and if CHIL_S_S is disabled.
If PUMP#1 is forced, no force shall be allowed on PUMP_2 and vice versa.
2: Condensing Setpoint. This item can be forced. If the unit is in CCN mode, the forced value shall be used instead
of the real control point calculation. If the unit is not in CCN mode the forced value shall be unused and the
regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display table
only if the unit is under CCN control.
3: Condenser pumpcontrol. This item can be forced On but not Off. If the unit is in CCN mode, the forced value shall
be used instead of regular pump control point. If the unit is not in CCN mode the forced value shall be unused and
the regular calculation shall be used. Forced value and force code shall appear in the OPTIONS Points Display
table only if the unit is under CCN control.
4: Electrical box Thermostat. This item indicates the electrical box thermostat and network power reverse phase
detection status (wired internally in series 16a and 16b on PD4-BASIC BOARD). These contacts, when opened
will prevent the unit from starting.
5: This output is energized when a contact failure is reported by any SCPM board
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
DISPLAY SCREEN
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
1 OPERATING MODES
2 Startup Delay in Effect Yes/No - Mode[07] N
3 Second Setpoint in Use Yes/No - Mode[08] N
4 Reset in Effect Yes/No - Mode[09] N
5 Demand Limit Active Yes/No - Mode[10] N
6 Ramp Loading Active Yes/No - Mode[11] N
7 Low Source Protection Yes/No - Mode[12] N
8 Low Cooler Suction Cir A Yes/No - Mode[13] N
9 Low Cooler Suction Cir B Yes/No - Mode[14] N
10 Low Dis Superheat Cir A Yes/No - Mode[15] N
11 Low Dis Superheat Cir B Yes/No - Mode[16] N
12 High Pres Override Cir A Yes/No - Mode[17] N
13 High Pres Override Cir B Yes/No - Mode[18] N
14 High Current Over Cir A Yes/No - Mode[19] N
15 High Current Over Cir B Yes/No - Mode[20] N
16 Reclaim Active? Yes/No - Mode[21] N
17 Cooler Heater Active? Yes/No - Mode[22] N
18 Cooler Pumps Rotation? Yes/No - Mode[23] N
19 Pump Periodic Start? Yes/No - Mode[24] N
20 Night Capacity Active? Yes/No - Mode[25] N
21 System Manager Active? Yes/No - Mode[26] N
22 Master Slave Active? Yes/No - Mode[27] N
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONFIGURATION SCREEN
TABLE NAME: USER PIC TABLE TYPE : 10H, instance 2
1 USER CONFIGURATION
2
3 Circuit Loading Sequence 0/1/2 0 - lead_cir
4 0 = Auto
5 1 = Circuit A First
6 2 = Circuit B First
7 Loading Sequence 0/1 0 - seq_typ
8
9 Ramp Loading Select Yes/No No - ramp_sel
10
11 Unit Off to On Delay 1 to 15 1 min off_on_d
12
13 Cooler Pumps Sequence 0/1/2/3/4 0 - pump_seq
14 0 = No Pump
15 1 = One Pump Only
16 2 = Two Pumps Auto
17 3 = Pump#1 Manual
18 4 = Pump#2 Manual
19 Pump Auto Rotation Delay 24 to 3000 48 hours pump_del
20 Periodic Pumps Start Yes/No No - pump_per
21
22 Reset Type Select 0 to 3 0 - res_sel
23 0 = None
24 1 = Voltage Control
25 2 = Delta T Control
26 3 = OAT Control
27
28 Demand Limit Type Select 0 to 2 0 - lim_sel
29 0 = None
30 1 = Switch Control
31 2 = 0-10vdc Control
32 Vdc For 100% Demand Lim 0 to 10 0 volts lim_mx
33 Vdc For 0% Demand Limit 0 to 10 10 volts lim_ze
34
35 Night Control
36 Start Hour 00:00 to 24:00 00:00 - nh_start
37 End Hour 00:00 to 24:00 00:00 - nh_end
38 Capacity Limit 0 to 100 100 % nh_limit
39 Capacity Limit 0 to 100 100 % nh_limit
40
41 Chiller Comp Current Limit 90 to 15001 1500 amps curr_lim
42 Menu Description Select Yes/No Yes - menu_des
43 Pass For All User Config Yes/No No - all_pass
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CONFIGURATION SCREEN
TABLE NAME: OCCDEFCS / OCCPC01S and OCCPC02S PIC TABLE TYPE : 14H, instance 2
TABLE NAME: HOLIDAY / HOLDY01S to HOLDY016S PIC TABLE TYPE : 14H, instance 3
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
SETPOINT SCREEN
1 COOLING
2 Cooling Setpoint 1 - 20 to 101 44.0 F csp1
3 Cooling Setpoint 2 - 20 to 101 44.0 F csp2
4 Voltage No Reset Value 0 to 10 0.0 volts v_cr_no
5 Voltage Full Reset Value 0 to 10 0.0 volts v_cr_fu
6 Delta T No Reset Value 0 to 25 0.0 ^F dt_cr_no
7 Delta T Full Reset Value 0 to 25 0.0 ^F dt_cr_fu
8 OAT No Reset Value 14 to 125 0.0 F oatcr_no
9 OAT Full Reset Value 14 to 125 0.0 F oatcr_fu
10 Cooling Reset Deg. Value -30 to 30 0.0 ^F cr_deg
11 Cooling Ramp Loading 0.2 to 2.0 1.0 ^F cramp_sp
12
13 HEATING
14 Heating Setpoint 80 to 153 100.0 F hsp
15 Voltage No Reset Value 0 to 10 0.0 volts v_hr_no
16 Voltage Full Reset Value 0 to 10 0.0 volts v_hr_fu
17 Delta T No Reset Value 0 to 25 0.0 ^F dt_hr_no
18 Delta T Full Reset Value 0 to 25 0.0 ^F dt_hr_fu
19 Heating Reset Deg. Value -30 to 30 0.0 ^F hr_deg
20 Heating Ramp Loading 0.2 to 2.0 1.0 ^F hramp_sp
21
22 HEAD PRESSURE
23 Sat Cond Temp Setpoint 95 to 1401 104.0 F headsp
24 Reclaim Setpoint 95 to 140 122.0 F rsp
25
26 DEMAND LIMIT
27 Switch Demand Limit Setp 0 to 100 100 % lim_sp
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: LOADFACT PIC TABLE TYPE : 12H, instance 1
DESCRIPTION STATUS UNITS POINT
1 CAPACITY CONTROL
2 Average Ctrl Water Temp nnn.n F ctrl_avg
3 Differential Water Temp nnn.n F diff_wt
4 Water Delta T nnn.n ^F delta_t
5 Control Point nnn.n F CTRL_PNT
6 Reset Amount nnn.n ^F reset
7 Controlled Temp Error nnn.n ^F tp_error
8 Actual Capacity nnn % cap_t
9 Actual Capacity Limit nnn % cap_lim
10 Current Z Multiplier Val n.n - zm
11 Load/Unload Factor nnn.n - smz
12 Active Capacity Override nn - over_cap
13
14 CIRCUIT A EXV CONTROL
15 EXV Position nnn.n % EXV_A
16 EXV Position Limit nnn.n % exvlim_a
17 Cooler Exchange Delta T n.n ^F PINCH_A
18 Discharge Superheat n.n F DSH_A
19 Economizer pinch offset n.n ^F offset_a
20 EXV Override nn - ov_exv_a
21
22 CIRCUIT B EXV CONTROL
23 EXV Position nnn.n % EXV_B
24 EXV Position Limit nnn.n % exvlim_b
25 Cooler Exchange Delta T n.n ^F PINCH_B
26 Discharge Superheat n.n F DSH_B
27 Economizer pinch offset n.n ^F offset_b
28 EXV Override nn - ov_exv_b
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: M_MSTSLV PIC TABLE TYPE : 12H, instance 3
1 MASTER/SLAVE CONTROL
2 Unit is Master or Slave Disable/Master/Slave - mstslv
3 Master Control Type Local/Remote/CCN3 - ms_ctrl
4 Master/Slave Ctrl Active True/False - ms_activ
5 Lead Unit is the: Master/Slave - lead_sel
6 Slave Chiller State 0/1/2/3/4/51 - slv_stat
7 Slave Chiller Total Cap 0-100 % slv_capt
8 Lag Start Delay 1 to 302 minutes l_strt_d
9 Lead/Lag Hours Delta nnnnn3 hours ll_hr_d
10 Lead/Lag Changeover? Yes/No4 - ll_chang
11 Lead Pulldown? Yes/No4 - ll_pull
12 Master/Slave Error nn - ms_error
13 Max Available Capacity ? True/False5 - cap_max
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MAINTENANCE SCREEN
TABLE NAME: STRTHOUR PIC TABLE TYPE : 12, instance 3
1 MACHINE
2 Total Operating Hours nnnnn hours HR_MACH
3 Starts Number nnnnn - st_mach
4 Compressor A1 Hours nnnnn hours HR_CP_A1
5 Compressor A2 Hours nnnnn hours HR_CP_A2
6 Compressor A1 Starts nnnnn - st_cp_a1
7 Compressor A2 Starts nnnnn - st_cp_a2
8 Compressor B1 Hours nnnnn hours HR_CP_B1
9 Compressor B2 Hours nnnnn hours HR_CP_B2
10 Compressor B1 Starts nnnnn - st_cp_b1
11 Compressor B2 Starts nnnnn - st_cp_b2
12 Starts Max During 1 Hour nn - st_cp_mx
13 Starts/hr From Last 24 h nn - st_cp_av
14 Cooler Pump #1 Hours nnnnn hours hr_cpum1
15 Cooler Pump #2 Hours nnnnn hours hr_cpum2
16 Condenser Pump Hours nnnnn hours hr_hpump
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
APPENDIX B
CCN Variables
The following variables can be used for trace functions (Network Service Tool-Trace, Data Collection).
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
MUX_FAN2 Fan 4xDO board #2, multiplexed DO's - H-DO nbfan_a > 2 and
b4b3b2b1b0 nbfan_b> 2
b0: fan_b1 Fan output 1, circuit B
b1: fan_b2 Fan output 2, circuit B
b2: fan_b3 Fan output 3, circuit B
b3: fan_b4 Fan output 4, circuit B
Fan Aux board , multiplexed DO's H-DO unit_typ = 1
b7b6b5b4b3b2b1b0
b0: fan_b1 Fan output 1, circuit B
b1: fan_b2 Fan output 2, circuit B
b2: fan_b3 Fan output 3, circuit B nb_fan_b> 0
b3: fan_b4 Fan output 4, circuit B
b4: fan_b5 Fan output 5, circuit B
b5: fan_b6 Fan output 6, circuit B total comp > 6
b6: fan_b7 Fan output 7, circuit B
b7: fan_b8 Fan output 8, circuit B
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION
EXV BOARD #1
Address = 29
Channel 29 EXV ST A
Channel 33 -
Channel 37 AI -MTQ RESA
Channel 38 AI -
Channel 47 AI -
Channel 48 AI -
Channel 49 AI -
Channel 50 AI - Channel 27-28: virtual -
Channel 51 AO HD A -
Channel 52 AO HD B
EXV BOARD
Address = 29
Channel 29 EXV ST A
Channel 33
Channel 37 AI MTQ RESA
Channel 38 AI -
EXV BOARD
Address = 29
Channel 29 EXV ST A
Channel 33
Channel 37 AI MTQ RESA
Channel 38 AI -
Channel 47 AI
Channel 48 AI
Channel 49 AI HR LWT
Channel 50 AI HR EWT
Channel 51 AO HD A Channel 27-28: virtual
Channel 52 AO HD_B
SCHEME 9 : Air Cooled < 5 separate fan stages 2 to 4 compressors, Aux Board, no varifan
BASIC BOARD SCPM BOARD #1 SCPM BOARD #3 AUXILIARY BOARD # 1 Address = 49
Address = 1 Address =84 Address =106
SCHEME 10 : Air Cooled > 4 separate fan stages 2 to 4 compressors, Aux Board, no varifan
BASIC BOARD SCPM BOARD #1 SCPM BOARD #3 AUXILIARY BOARD # 1 Address = 49
Address = 1 Address =84 Address =106
SCHEME 11: Air Cooled < 5 separate fan stages 2 to 4 compressors Aux Board, varifan
BASIC BOARDAddress = 1 SCPM BOARD #1 Address =84 SCPM BOARD #3 Address =106 AUXILIARY BOARD # 1 Address = 49
SCHEME 12 : Air Cooled > 4 separate fan stages 2 to 4 Compressors Aux Board, varifan
BASIC BOARDAddress = 1 SCPM BOARD #1 Address =84 SCPM BOARD #3 Address =106 AUXILIARY BOARD # 1 Address = 49
SCHEME 13 : Air Cooled Chillers >2 separate fan stages, 2 to 4 Compressors, Cooler heater = NO, Reclaim option = no,
No Aux Board
BASIC BOARD SCPM BOARD #1 SCPM BOARD #3
Address = 1 Address =84 Address =106
SCHEME 14 : Air Cooled Chillers < 3 separate fan stages 2 to 4 Compressors, Cooler heater = YES or Reclaim option
= YES, No Aux Board
BASIC BOARD SCPM BOARD #1 SCPM BOARD #3 NRCP BASIC BOARD
Address = 1 Address =84 Address =106 Address = 53
Channel 47 AI
Channel 48 AI
Channel 49 AI -
Channel 50 AI - Channel 26 : DO unused
Channel 51 AO HD A Channel 27-28: virtual
Channel 52 AO HD B Channel 80 - 83 : free
SCHEME 15 : Air Cooled Chillers > 2 separate fan stages 2 to 4 Compressors, Cooler heater = YES or Reclaim option
= YES, No Aux Board
BASIC BOARD SCPM BOARD #1 SCPM BOARD #3 NRCP BASIC BOARD
Address = 1 Address =84 Address =106 Address = 53
J-BUS/RS-485 TO
CCN/JBUS
PRO-DIALOG 30GX & HX GATEWAY BMS
COMFORT
ASCII/RS-232 TO
PRO-DIALOG 30DQ
DATAPORT II
BMS NETWORK
ASCII/RS-232 TO
DATAPORT I BMS
PRO-DIALOG 30GH
FLOTRONIC II
BUILDING AUTODIAL
SUPERVISOR GATEWAY
FSM
REPEATER
MODEM
39 L
FLOTRONIC I
GW
TSM SECONDARY BUS NETW
ORK
TSM SERV
ICE
TOOL
19XL 39 L
SER
VIC
EW
IND
OW
WSM 2
39 L
3200 MP REPEATER
GW
FLOTRONIC I
GW REMOTE BUILDING SUPERVISOR
CARRIER
CONFORT
NETWORK
ON - COOLING 05-20-94 15:00
! NORMAL
ENTERING LEAVING
255 hours
OUTDOOR
12.5 6.7 12
CAPACITY HEATCOOL PUMP
50 0 0
CTRL PNT CTRL WT LIMIT
6.0 6.7 100
CCN LOCAL
LOCAL REMOTE MENU
CARRIER S.A
NOT TO BE DISCLOSED TO PERSONS OUTSIDE CARRIER ORGANIZATION