2) The tubing, as a minimum, shall be seamless 316L stainless steel, 3/8 inch o.d., 0.035 inch wall with Swagelok fittings.
Where required, 1/2 inch o.d. tubing with 0.049 wall thickness may be used.
3) Deleted
4) In addition to the manufacturers data plate, each instrument shall have a stainless steel tag embossed with the instrument tag number.
The tags shall be permanently attached with 16 AWG stainless steel wire.
5) The solenoid valve shall be fitted between the I/P output and the quick exhaust valve input.
The actuator vents and fails the control valve opened when the solenoid valve is de-energized.
6) The solenoid valve shall have a diode surge suppression assembly equal to CRA part number ZR1.
The assembly consists of 1N4751 zener diode and 1N4005 diode soldered anode to anode and fully encapsulated with GE RTV615A.
The sleeving shall be marked to differentiate leads. (Zener is the negative)
The assembly shall be suitable for Cenelec Flameproof, Zone 1 areas.
7) Stainless steel bug screens shall be installed on all pneumatic exhaust ports.
8) Calibration and check out per Solar standards for Surge Control Valves required.
9) Actuator to be dust and moisture protected; provide actuator as a "closed loop" system.
10) The electrical items and the components of the electronic circuits of the instruments shall be in materials suitable to avoid the formation of
foulings or mildew, and properly protected to operate in the project environmental conditions.
11) All vendor drawings, dimensions and documents shall be in S.I. units and in the English language.
12) The valve must reach 63.2% open in 100 + 100 inches of port size (milliseconds).