ISO 9001, ISO 14001: LG Low Voltage Air Circuit Breakers
ISO 9001, ISO 14001: LG Low Voltage Air Circuit Breakers
ISO 9001, ISO 14001: LG Low Voltage Air Circuit Breakers
LG Low Voltage
Air Circuit Breakers
LBA-A Type
1600A, 500V, 65kA 3150A, 500V, 85kA
The terminal of the control circuit on the front enables easy handling.
3
Type Selection
Type code
S OCR(O)
N OCR()
Number of poles
Rated current 3 Pole
0 6 630A 4 Pole
0 8 800A
1 0 1000A
1 3 1250A
1 6 1600A
2 0 2000A S Standard
2 5 2500A E Economic
3 2 3200A
4 0 4000A
5 0 5000A
4
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
Ratings
Type LBA-06A LBA-08A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
Frame Current (A) 630 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000
Rated Insulation Voltage (V) 660 660 660 660 660 660 660 660 660 660
Rated Operation Voltage (V) 660 660 660 660 660 660 660 660 660 660
Number of Poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
630-504-378 1000-800-600 1250-1000-750 1600-1280-960 3200-2500-1920
Rated Current of 4000-3200-2400
Trip Relay (A) 315-252-189 800-640-480 500-400-300 630-504-378 1000-800-600 2000-1600-1200 2500-2000-1500 2000-1600-1200 5000-4000-3000
2000-1600-1200
126-101-76 200-160-120 500-400-300 500-400-300 1000-800-600
Rated Current of Neutral Pole(A) 630 800 1,000 1,250 1,600 1,600 1,600 1,600 2,500 2,500
IEC AC660V 30/63 30/63 30/63 30/63 42/88.2 42/88.2 42/88.2 50/105 65/143 65/143
Rated BS AC600V 42/88.2 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 65/143 85/187 85/187
Short-Curcuit VDE AC500V 50/105 50/105 50/105 50/105 65/143 65/143 65/143 85/187 100/220 100/220
Breaking
Capacity NEMA AC600V 42/96.6 42/96.6 42/96.6 50/115 50/115 50/115 50/115 65/149.5 85/195.5 85/195.5
(kA r.m.s, ANSI AC480V 50/115 50/115 50/115 65/149.5 65/149.5 65/149.5 65/149.5 85/195.5 100/230 100/230
Symmetrical)/ KS AC550V 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 50/105 65/143 85/195.5 85/195.5
Making
Capacity JEC AC460V 50/105 50/105 50/105 65/143 65/143 65/143 65/143 85/195.5 100/230 100/230
(kA peak values) AC660V 30/63 30/63 30/63 48/88.2 42/88.2 42/88.2 42/88.2 50/105 - -
P-2(O-CO-CO) LR AC600V 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 50/105 65/143 88.1/211 88.1/211
AC500V 50/105 50/105 50/105 65/143 65/143 65/143 65/143 85/195.5 105/256 105/256
KR AC500V 50/105 50/105 50/105 63/138.6 63/138.6 63/138.6 63/138.6 80/176 100/251 100/251
Rated Short Time Current (kA/1s) 42 42 42 50 50 50 50 65 85 85
Total Breaking Time (s) 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.05 0.05
Closing Time (s) 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.08 0.08
Number of Current conductive 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,000 1,000 1,000
operating cycles Current not conductive 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000
1
Fixed Type
2
1 Trip relay part 4
2 Charge handle
3 5
3 Open
button
4 Close
Open
indicator
5 Close
button 6
6 Charge
indicator
1 2
Draw-out Type
1 Arc chamber
2 Auto connection contacts
3 Draw-out rail
1 2 3
Mounting Configurations
Select Fixed Type or Draw-out Type
Fixed Type
Compact design
Direct fixing construction
Compact design reduces
panel board size
Draw-out handle
Draw-out Type
Easy maintenance and inspection
The draw-out rail is stored in the cradle
Safety shutter
Position S/W indicates Connected Test
Disconnected Draw-out Position
Short- Circuit b Contact
Extension rail
-Keep the control circuit on by closing the b contact.
7
Operation
Select Manual Charging Type or Motor Charging Type
8
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
Optional Accessories
Installation location can be accessed from the front for easy
maintenance and inspection.
4
1 5 1 Auxiliary Switch (AX)
6 2 Shunt Tripping Device (SHT)
3 Open-Close Counter (CNT)
2 7
4 Lockout Coil (LC)
5 Auxiliary Switch (AX)
6 Undervoltage Tripping Device (UVT)
3 7 OCR Alarm Switch (AL)
9
Optional Accessories
10
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
Type
Combinations LBA-06A LBA-08A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
L S I
S-A L I
ST-A S I
I
L S I G
L I G
SGT-A S I G
I G
S-A Over current protection(standard) Note (L) Long time delay (S) Short time delay
(I) Instantaneous (G) Ground-fault
ST-A Over current protection,Trip indicator(LED)
SGT-A Over current protection,Trip indicator(LED),Ground-fault protection
Adjustable in 3 steps :
1 Rated current 60, 80 or 100 of the frame current.
6
tripping time Refer to the characteristics curve.
8
2 Instantaneous Adjustable in 4 steps
7 pick-up current of the rated current.
3
4 5 Ground-fault Adjustable in 4 steps (LBA06~32),
8
pick-up current 3steps(LBA40~50)of the rated current.
Ground-fault
9 6 9
tripping time
Adjustable in 2 steps: 0.3 sec or 0.8 sec.
Current(A)
Frame Rated maximum Rated current setting(A) Ground-fault pick-up current setting(A)
Type
size(A) current(A) If
60 If 100
80 If If 20
10 If 30 If 50 If
630 378 504 630 63 126 189 315
LBA-06A 630 315 189 252 315 31.5 63 94.5 157.5
126 75.6 100.8 126 12.6 25.2 37.8 63
LBA-08A 800 800 480 640 800 80 160 240 400
1000 600 800 1000 100 200 300 500
LBA-10A 1000 500 300 400 500 50 100 150 250
200 120 160 200 20 40 60 100
1250 750 1000 1250 125 250 375 625
630 378 504 630 63 126 189 315
LBA-13A 1250
500 300 400 500 50 100 150 250
250 150 200 250 25 50 75 125
1600 960 1280 1600 160 320 480 800
LBA-16A 1600 1000 600 800 1000 100 200 300 500
500 300 400 500 50 100 150 250
LBA-20A 2000 2000 1200 1600 2000 200 400 600 1000
LBA-25A 2500 2500 1500 2000 2500 250 500 750 1250
3200 1920 2560 3200 320 640 960 1600
3000 1800 2400 3000 300 600 900 1500
LBA-32A 3200
2000 1200 1600 2000 200 400 600 1000
1000 600 800 1000 100 200 300 500
LBA-40A 4000 4000 2400 3200 4000 - 800 1200 2000
2000 1200 3200 4000 - 400 600 1000
LBA-50A 5000 5000 3000 4000 5000 - 1000 1500 2500
12
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
Characteristics of protection
LBA-06~32A LBA-40~50A
Operating time(s)
of the rated current
LBA-06~32A LBA-40~50A
Operating time(s)
13
Control Circuit
S-A Type
Control source Control source Control source
(Close)
(Open) (Charge)
Electrical
Trip coil
Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)
Trip Relay
UVT Under voltage tripping device M2+ Self-holding charging control source terminal
CC Closing coil
14
LG LOWVOLTAGE AIR CIRCUIT BREAKERS
ST-A Type
Control source Control source Control source
(Close)
(Open) (Charge)
Electrical
Trip coil
Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)
Trip Relay
SHT Shunt tripping device M2+ Self-holding charging control source terminal
UVT Under voltage tripping device MC- Common terminal for charging and closing
LC Lockout coil R1+ R2- R3- Trip indicator control source terminal
15
Control Circuit
SGT-A Type
Control source Control source Control source
(Close)
(Open) (Charge)
Electrical
Axa
Trip coil
Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)
Trip Relay
16
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
External Dimensions
(LBA-06, 08, 10, 13, 16A)
Fixed Type
Neutral pole
Rear view
Side view
Front view
Neutral pole
Rear view
Side view
Front view
Installation
Dimensions
Terminal
Rear view (Fixed type) Rear view (Draw-out type) Bottom view(Fixed type) Bottom view(Draw-out type)
( ) 4 pole dimensions
17
External Dimensions
(LBA-20, 25A)
Fixed Type
Neutral pole
Front view
Front view
Installation
Dimensions
(Neutral pole)
Rear view(Fixed type) Rear view(Draw out type)
Bottom view Bottom view Terminal
(Fixed type) (Draw-out type)
( ) 4 pole dimensions
18
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
External Dimensions
(LBA-32A)
Rear view
Side view
Front view
Installation
Dimensions
19
External Dimensions
(LBA-40, 50A)
Neutral pole
Front view
Front view
Installation
Dimensions
Terminal(Fixed type)
LBA-06/08 /
Type 10/13/16 / LBA-32A LBA-40 /50A
20/25A
A1 150 150 200
Fixed A2 200 300 300
Type B 100 100 100
C 320 320 320
A1 100 150 200
Draw-out A2 200 300 300
Type B 100 100 100
C 418 418 474
21
Ordering Information
Circuit breaker
Rating V/ Hz/ AF Number of poles 3P 4P
Mounting P(Fixed type) E(with E class cradle)
configuration F (with F2 class and safety shutter)
Control circuit
Housing type(standard) Auto connection type
connection
Control unit
E(Not needed) S(standard) Standard type (combination of L,S,I)
TYPE ST (standard, trip indicator) L (Long time delay), S (Short time delay),
SGT (standard, trip indicator, ground-fault protection) I (Instantaneous)
AC 100~120V AC 200~240V
S,ST type
DC 100~120V DC 125V
Control power
SGT type AC 100~120V AC 200~240V
DC 100~110V DC 125V
22
LG LOW VOLTAGE AIR CIRCUIT BREAKERS
Specifications
Ratings
Model LBA-06A LBA-10A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
Number
of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
Mounting configuration
Fixed type and draw out type (Manual connection type is standard)
Closing method
Manual charging type and motor charging type (select the control voltage)
Accessories
Undervoltage Shunt Condenser Auxiliary Trip OCR Open
Accessories tripping tripping tripping switch switch alarm close
device device device (AX) (TS) switch counter
(UVT) (SHT) (CTD) (AL) (CNT)
Maximum 1 1 1 4a4b 1a 1a 1
number
The economical type of auxiliary switches are 3a3b, Shunt tripping device is also attached.
If selecting 4a4b as an auxiliary, refer to page 9 of auxiliary switches.
Trip relay(OCR)
Not applicable to economy type
S-A Standard type (Overcurrent trip characteristics)
Type ST-A Standard + Trip indicator (LED)
SGT-A Standard + Trip indicator (LED) + Ground-fault protection
Default setting value of the OCR. Trip relay unit
Type LBA-06/08/10/13/16/20/25/32A LBA-40/50A
Continuous conductive current 100% of rated current specificed. 100second trip at 200%
Short-delay triping time Pick up at 400% of the rated current Pick up at 200%
Instantaneous pick-up current Pick up at 1,600% of the rated current Pick up at 1000%
Ground-fault protection Pick up at 50% of the rated current. 0.8 second trip.
23