ISO 9001, ISO 14001: LG Low Voltage Air Circuit Breakers

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

ISO 9001, ISO 14001

LG Low Voltage
Air Circuit Breakers

LBA-A Type
1600A, 500V, 65kA 3150A, 500V, 85kA

According to IEC 947-2


2 Passed the KEMA Test
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Features LBA-A Type has the following features.

The terminal of the control circuit on the front enables easy handling.

Optimized design for efficient panel board.


Two standardized heights and depths for each type (fixed type and draw-out type.)
Four standardized external dimensions
(630, 800, 1000, 1250, 1600AF/2000, 2500AF/3200AF/4000,5000AF).
Light weight contributes to easy installation into the board.

Standard Ampere Frame & Poles.


630AF, 800AF, 1000AF, 1250AF, 1600AF, 2000AF, 2500AF, 3200AF, 4000AF, 5000AF.
Every type is available as 3 -pole or 4-pole.

Standard manual connection. (Auto connection optional)

Easy and safe handling of draw-out type with rail.

Variety of accessories (refer to page 10).

Economic product containing a large element of customer


inputs right from the design stage.

3
Type Selection

Type code

S OCR(O)
N OCR()

Mounting configuration type


P Fixed type
E E class cradle
F F2 class cradle
* F types have cradle with shutter.

Number of poles
Rated current 3 Pole
0 6 630A 4 Pole
0 8 800A
1 0 1000A
1 3 1250A
1 6 1600A
2 0 2000A S Standard
2 5 2500A E Economic
3 2 3200A
4 0 4000A
5 0 5000A

* For further information refer to page 22, 23

4
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Ratings
Type LBA-06A LBA-08A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
Frame Current (A) 630 800 1,000 1,250 1,600 2,000 2,500 3,200 4,000 5,000
Rated Insulation Voltage (V) 660 660 660 660 660 660 660 660 660 660
Rated Operation Voltage (V) 660 660 660 660 660 660 660 660 660 660
Number of Poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4
630-504-378 1000-800-600 1250-1000-750 1600-1280-960 3200-2500-1920
Rated Current of 4000-3200-2400
Trip Relay (A) 315-252-189 800-640-480 500-400-300 630-504-378 1000-800-600 2000-1600-1200 2500-2000-1500 2000-1600-1200 5000-4000-3000
2000-1600-1200
126-101-76 200-160-120 500-400-300 500-400-300 1000-800-600
Rated Current of Neutral Pole(A) 630 800 1,000 1,250 1,600 1,600 1,600 1,600 2,500 2,500
IEC AC660V 30/63 30/63 30/63 30/63 42/88.2 42/88.2 42/88.2 50/105 65/143 65/143
Rated BS AC600V 42/88.2 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 65/143 85/187 85/187
Short-Curcuit VDE AC500V 50/105 50/105 50/105 50/105 65/143 65/143 65/143 85/187 100/220 100/220
Breaking
Capacity NEMA AC600V 42/96.6 42/96.6 42/96.6 50/115 50/115 50/115 50/115 65/149.5 85/195.5 85/195.5
(kA r.m.s, ANSI AC480V 50/115 50/115 50/115 65/149.5 65/149.5 65/149.5 65/149.5 85/195.5 100/230 100/230
Symmetrical)/ KS AC550V 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 50/105 65/143 85/195.5 85/195.5
Making
Capacity JEC AC460V 50/105 50/105 50/105 65/143 65/143 65/143 65/143 85/195.5 100/230 100/230
(kA peak values) AC660V 30/63 30/63 30/63 48/88.2 42/88.2 42/88.2 42/88.2 50/105 - -
P-2(O-CO-CO) LR AC600V 42/88.2 42/88.2 42/88.2 50/105 50/105 50/105 50/105 65/143 88.1/211 88.1/211
AC500V 50/105 50/105 50/105 65/143 65/143 65/143 65/143 85/195.5 105/256 105/256
KR AC500V 50/105 50/105 50/105 63/138.6 63/138.6 63/138.6 63/138.6 80/176 100/251 100/251
Rated Short Time Current (kA/1s) 42 42 42 50 50 50 50 65 85 85
Total Breaking Time (s) 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.04 0.05 0.05
Closing Time (s) 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.06 0.08 0.08
Number of Current conductive 3,000 3,000 3,000 3,000 3,000 3,000 3,000 2,000 1,000 1,000
operating cycles Current not conductive 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000 10,000

Exterior Dimensions (mm)


Fixed type Draw-out type

Fixed Type Draw-out Type


Type 3Pole 4Pole 3Pole 4Pole
a b c d a b c d a b c d a b c d
LBA-06A
LBA-08A
LBA-10A 295 380 343 428
LBA-13A
LBA-16A 35 35 459 472 35 459 472 35
424 374 424 374
LBA-20A
430 515 478 563
LBA-25A
LBA-32A 536 621 584 669
LBA-40A
687 85 817 85 742 521 528 80 872 521 528 80
LBA-50A
5
Design features & Structure

1
Fixed Type
2
1 Trip relay part 4
2 Charge handle
3 5
3 Open
button
4 Close

Open
indicator
5 Close
button 6
6 Charge
indicator

1 2

Draw-out Type
1 Arc chamber
2 Auto connection contacts
3 Draw-out rail

1 2 3

1 Trip relay device


2 Arc contact(moving)
4
3 Arc contact(fixed)
15
4 Arc chamber
5 CT 5
6 Main connector 6
7 Main contact 7
8 Contact spring 14
9 Load connector 8
13
10 Moving conduct 9
11 Charging spring
12
12 Charging device
13 Link device 10
14 Trip device
15 Charging handle
6 11
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Mounting Configurations
Select Fixed Type or Draw-out Type

Fixed Type
Compact design
Direct fixing construction
Compact design reduces
panel board size

Draw-out handle

Draw-out Type
Easy maintenance and inspection
The draw-out rail is stored in the cradle
Safety shutter
Position S/W indicates Connected Test
Disconnected Draw-out Position
Short- Circuit b Contact
Extension rail
-Keep the control circuit on by closing the b contact.

Positions of Draw-out Type


Main circuit and control
circuit are connected.
Connected (Manual connection)
Position Normal operation
condition

Main circuit disconnected,


control circuit connected.
Test Testing is possible with
Position
the panel door closed.

Main circuit and control


circuit are disconnected.
Disconnected (Manual disconnected)
Position
Panel door can be closed.

The breaker can be


removed in this position.
The breaker can be
Draw-out removed from the
Position cradle by use of the
extension rails.

7
Operation
Select Manual Charging Type or Motor Charging Type

Manual Charging Type


For closing, first charge the spring by using the The buttons lock automatically so that the open
charging handle and then press the close button. and close buttons can not be operated at the
For opening, an open button disconnects the circuit. same time.
If the closing spring is fully charged, the charge Main contacts status of main circuit is indicated
indicator indicates CHARGED. by CLOSE or OPEN.

Motor Charging Type


Closing is performed by a closing spring which is
remotely controlled. Pressing the charges button
activates a motor that automatically charges the
closing spring, which then closes the breaker.
Charging Handle
Motor charging and electrical closing is permitted Close Open Indicator
between 85% and 110% of the rated voltage.
Manual charging operation can also be performed. Open Button Close Button
With breaker closed, charging is possible
by manual action, but motor charging of closing
spring can not be performed. Charging Indicator
With the open button pressed, closing operation
can not be performed (electrical and mechanical lock).
Closing operation can not be performed when
off-lock is being used (electrical and mechanical lock).
Circuit to prevent pumping is included Ratings of motor charging Minimum operating : 300VA

(electrical lock). Rated Voltage (V) Inrush Continuous Charging


Current (A) Current (A) Time (s)
Caution is required, because lower closing
100~110V 10.5 3
signal voltage may reset pumping prevention circuit.
AC 120V 11 3
Closing operation should follow at least one second 50/60Hz 200~220V 6 1.5 Max.3
after completion of charge. 240V 7 1.5
DC 100~125V 11 4

Power Source Resetting Voltage


AC 50%
DC 20%

Ratings of closing coil

Rated Voltage (V) Inrush Closing


Current (A) Time (ms)
100~110V 5.5
AC 120V 5.5
Max. 60
50 / 60Hz 200~220V 5
(Contact time)
240V 5
DC 100~125V 5

8
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Optional Accessories
Installation location can be accessed from the front for easy
maintenance and inspection.

4
1 5 1 Auxiliary Switch (AX)
6 2 Shunt Tripping Device (SHT)
3 Open-Close Counter (CNT)
2 7
4 Lockout Coil (LC)
5 Auxiliary Switch (AX)
6 Undervoltage Tripping Device (UVT)
3 7 OCR Alarm Switch (AL)

The Trip Relay (OCR) Alarm Switch (AL)


OCR alarm switch is an accessory needed if over current Alarm switch operating
trip relay is required. The OCR alarm switch (AL)
Breaker Condition acontact
electrically alarms when breaker is tripped by trip
relay activation. Tripped either by long-delay,
short-delay or instantaneous On
This is activated by long-delay,
tripping
short-delay and instantaneous
Tripped either by the OPEN
tripping. However, it is not button, SHT,UVT or
activated by ground-fault tripping, ground-fault tripping Off
open button, undervoltage and Open
shunt tripping devices. Close
It is an instantaneous action (15ms), so that
the alarm circuit needs a self-holding circuit.

Auxiliary Switch (AX) Ratings of AX and AL contacts


The auxiliary switch, which is installed AC DC
in the breaker, displays the status of the breaker, Rated Current(A) Rated Current(A)
either CLOSED or OPEN. Contact
Voltage Resistive Inductive Voltage Resistive Inductive
(V) load load (V) load load
3a3b is standard, maximum 4a4b. Ratings
460 5 2.5 250 5 3
Special use (Maximum) 250 10 10 125 10 6
-Motor charging type : 4a3b 125 10 10 30 10 10
-Shunt trip device type : 3a4b
-Both of the above types : 3a3b
Breaker condition a Contact b Contact Counter(CNT)
Close On Off The counter mechanically indicates the number
Open Off On of operations of the breaker, counting
at each closing operation.

9
Optional Accessories

Undervoltage Tripping Device (UVT)


The undervoltage tripping device (UVT), with Two options are available: 0.5 second delayed action
UVT coil, lock-out coil and voltage controller, or instantaneous action when the UVT control
is installed in the breaker to automatically trip voltage falls below the
if the control power voltage is dropped below drop-out voltage.
the drop-out voltage. The Drop-out voltage remains
The voltage controller controls the voltage the same regardless
supplied to UVT coil and lockout coil. of the frequency due to
Cooperative action is allowed, because the conversion into DC.
UVT coil and lockout coil can be
simultaneously picked up and dropped out. Voltage
Controller
Instantaneous UVT-S Control
Type Circuit
0.5S Delay UVT-05S Control
Power
Rated Voltage Pick-up Voltage Drop-out Voltage Supply
LC Coil
Breaker
AC 100V~120V 70V~80V 40V~60V UVT Coil
AC 200V~240V 140V~170V 80V~120V
AC 380V~460V 266V~323V 152V~228V

Lockout Coil (LC)


When UVT is specified,
Even when the UVT is activated, the Air Circuit Breaker,
lockout coil is also included.
may instantaneously come into contact by
It is possible to specify
the closing spring force. A lockout coil prevents
the lockout coil only.
this by anti-electrical and mechanical closing
action if voltage is lower than the drop-out voltage. Rated Voltage Pick-up Voltage Drop-out Voltage
Pick-up voltage and drop-out voltage are AC 100~120V 70V~85V 40V~60V
controlled by voltage controller AC 200~240V 140V~170V 80V~120V
AC 380~460V 266V~323V 152V~228V

Condenser Tripping Device (CTD) Type CTD-100 CTD-200


This device enables breaker opening within
Rated Input Voltage (V) AC100/110 AC200/220
a definite time by remote electrical operation,
Rated Frequency (Hz) 50/60 50/60
even when there is Rated Charging Voltage (V) 145/145 280/310
no control power supply. Charging Time 5s (max) 5s (max)
This device is combined Tripping Time Capacity 3m (min) 2m (min)
with a SHT tripping device. Applicable SHT Voltage (V) DC 100/110 DC 200/220
Internal Circuit Voltage FIuctuation 85~110% 85~110%
CTD is installed outside of the Air Circuit Breaker.

Shunt Tripping Device (SHT) AC


The shunt tripping device (SHT) trips the breaker Rated Voltage Inrush Current Peak(A) Operating Time(ms)
remotely by electric signal. 100~125 5.5 40
The shunt tripping device 200~220 2.0 40
240 2.0 40
utilizes auxiliary switch
(1a) to prevent damage. DC
Rated Voltage Inrush Current Peak(A) Operating Time (ms)
Tripping is permitted
100~125 5 40
between 70% and 110% of rated voltage.

10
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Trip Relay (OCR)


Solid-state trip device characteristics and combinations

Type
Combinations LBA-06A LBA-08A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
L S I
S-A L I
ST-A S I
I

L S I G

L I G
SGT-A S I G
I G

S-A Over current protection(standard) Note (L) Long time delay (S) Short time delay
(I) Instantaneous (G) Ground-fault
ST-A Over current protection,Trip indicator(LED)
SGT-A Over current protection,Trip indicator(LED),Ground-fault protection

Trip Indicator(T) Feature of Trip Indicator


The trip indicator consists of the lamps which
display trip state of the breaker (long-delay,
short-delay, instantaneous and ground-fault trip)
To reset the trip indicator, push the reset button
on the front of the trip relay or cut the control power.
Control power is needed (refer to the below chart)

Ground-fault protection(G) Control Power


Take adequate precautions since the following Control power supply (power consumption:2VA)
conditions are present when the ground fault Type Ground-Fault Trip
protection is needed. Protection Indicator
The OCR alarm switch will not operate S-A - -
when the ground fault protection is tripped. ST-A - AC100-120V/200-240V,
If needed, please use the indicator contact. DC100-110V/125V
SGT-A AC100~120V/200~240V,DC100~110V/125V
The ground-fault protection and the shunt
tripping device use the same control power.
11
Abundant Protections

Adjustable in 3 steps :
1 Rated current 60, 80 or 100 of the frame current.

The current which the solid-state trip


Ampere setting device can carry continuously
2
continuous Adjustable in 3 steps :
80, 90 or 100 of the rated current.
Long-delay 105-120 of the ampere setting continuous.
3 pick-up current
Long-delay 100 seconds at 200 of the ampere setting
4
tripping time continuous.
Short-delay Adjustable in 4 steps (LBA 06~32),
5
pick-up current 3steps(LBA40~50)of the rated current.
Short-delay Adjustable in 3 steps: max., med., or min.
1
Operating time(S)

6
tripping time Refer to the characteristics curve.
8
2 Instantaneous Adjustable in 4 steps
7 pick-up current of the rated current.
3
4 5 Ground-fault Adjustable in 4 steps (LBA06~32),
8
pick-up current 3steps(LBA40~50)of the rated current.

Ground-fault
9 6 9
tripping time
Adjustable in 2 steps: 0.3 sec or 0.8 sec.

Current(A)

Frame Rated maximum Rated current setting(A) Ground-fault pick-up current setting(A)
Type
size(A) current(A) If
60 If 100
80 If If 20
10 If 30 If 50 If
630 378 504 630 63 126 189 315
LBA-06A 630 315 189 252 315 31.5 63 94.5 157.5
126 75.6 100.8 126 12.6 25.2 37.8 63
LBA-08A 800 800 480 640 800 80 160 240 400
1000 600 800 1000 100 200 300 500
LBA-10A 1000 500 300 400 500 50 100 150 250
200 120 160 200 20 40 60 100
1250 750 1000 1250 125 250 375 625
630 378 504 630 63 126 189 315
LBA-13A 1250
500 300 400 500 50 100 150 250
250 150 200 250 25 50 75 125
1600 960 1280 1600 160 320 480 800
LBA-16A 1600 1000 600 800 1000 100 200 300 500
500 300 400 500 50 100 150 250
LBA-20A 2000 2000 1200 1600 2000 200 400 600 1000
LBA-25A 2500 2500 1500 2000 2500 250 500 750 1250
3200 1920 2560 3200 320 640 960 1600
3000 1800 2400 3000 300 600 900 1500
LBA-32A 3200
2000 1200 1600 2000 200 400 600 1000
1000 600 800 1000 100 200 300 500
LBA-40A 4000 4000 2400 3200 4000 - 800 1200 2000
2000 1200 3200 4000 - 400 600 1000
LBA-50A 5000 5000 3000 4000 5000 - 1000 1500 2500

12
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Characteristics of protection

Characteristics of over current protection

LBA-06~32A LBA-40~50A

Continuous current Continuous current


in 3 steps: in 3 steps:
80%,90%,100% of the 80%,90%,100% of the
rated current rated current

Short time delay pick-up current


Short time delay pick-up current in 4 steps:
in 4 steps: 200%~1000% of rated current
400%~1000%
Operating time(s)

Operating time(s)
of the rated current

Short delay tripping time


Short delay tripping time in 3 steps:
in 3 steps: Max. Med. Min.
Max. Med. Min.
Instantaneous pick-up current
in 4 steps: Instantaneous pick-up current
400, 800, 1200% ,1600% in 4 steps:
of rated current. 400%~1000% of rated current.
Default setting value
of the current

Default setting value of the current

Rated current(%) Rate current(%)

Characteristics of ground-fault protection

LBA-06~32A LBA-40~50A

Ground pick-up current range Ground pick-up current range


in 4 steps: in 3 steps:
10% of frame-size current 20% of frame-size current
20% of frame-size current 30% of frame-size current
50% of frame-size current
Operating time(s)

Operating time(s)

30% of frame-size current


50% of frame-size current

Default setting value Default setting value

Ground tripping Ground tripping


time range time range
in 2 steps: in 2 steps:
0.3 sec. 0.3 sec.
0.8 sec. 0.8 sec.

Rated current(%) Rated current(%)

13
Control Circuit

S-A Type
Control source Control source Control source
(Close)

(Open) (Charge)

Electrical

Control source controller


operation
circuit
Trip relay unit
(S-A)

Trip coil

Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)

Trip Relay

Users wiring S1+ S2- SHT control source terminal

Plant wiring US+ US- UVT short circuit terminal

Junction UL1+ UL2- UVT control source terminal

Terminal CC+ Closing control source terminal

SHT Shunt tripping device M1+ Charging control source terminal

UVT Under voltage tripping device M2+ Self-holding charging control source terminal

LC Lockout coil MC- Common terminal for charging and closing

CC Closing coil

CH Charge complete signal


output terminal

14
LG LOWVOLTAGE AIR CIRCUIT BREAKERS

ST-A Type
Control source Control source Control source
(Close)

(Open) (Charge)

Electrical

Control source controller


operation
circuit
Trip relay unit
(ST-A)

Trip coil

Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)

Trip Relay

Users wiring US - US + UVT short circuit terminal

Plant wiring UL1+ UL2- UVT control source terminal

Junction CC+ Closing control source terminal

Terminal M1+ Charging control source terminal

SHT Shunt tripping device M2+ Self-holding charging control source terminal

UVT Under voltage tripping device MC- Common terminal for charging and closing

LC Lockout coil R1+ R2- R3- Trip indicator control source terminal

CC Closing coil E+ Trip indicating common terminal


Charge complete signal Long time delay trip indicating terminal
CH E1-
output terminal
S1+ S2- SHT control source terminals E2- Short time delay trip indicating terminal
E3- Instantaneous trip indicating terminal

15
Control Circuit

SGT-A Type
Control source Control source Control source
(Close)
(Open) (Charge)

Electrical

Control source controller


operation
Trip relay circuit
unit

Axa

Trip coil

Undervoltage
tripping Electrical
Shunt Auxiliary OCR
device control circuit Trip Position
Main circuit Trip relay unit tripping alarm
switch (lockout coil (Motor charging, switch switch
device switch
included) closing circuit)

Trip Relay

Users wiring S1+ S2- SHT control source terminal


Plant wiring UL1+ UL2- UVT control source terminal
Junction CC+ Closing control source terminal
Terminal signal M1+ Charging control source terminal
SHT Shunt tripping device M2+ Self-holding charging control source terminal
UVT Under voltage tripping device M3-
Self-holding charging control source terminal
LC Lockout coil MC- Common terminal for charging source terminal
CC Closing coil R1+ R2- R3- Trip indicator control source terminal
CH
Charge complete signal
output terminal
E+ Trip indicating common terminal
G1- Ground fault indicating terminal E1- Long time delay trip indicating terminal
S3+ UVT short circuit terminal for
ground fault trip
E2- Short time delay trip indicating terminal
E3- Instantaneous trip indicating terminal

16
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

External Dimensions
(LBA-06, 08, 10, 13, 16A)

Fixed Type
Neutral pole

Rear view
Side view
Front view

Draw -out Type

Neutral pole

Rear view
Side view
Front view

Installation
Dimensions

Terminal

Rear view (Fixed type) Rear view (Draw-out type) Bottom view(Fixed type) Bottom view(Draw-out type)
( ) 4 pole dimensions

17
External Dimensions
(LBA-20, 25A)

Fixed Type
Neutral pole

Side view Rear view

Front view

Draw -out Type


Neutral pole

Side view Rear view

Front view

Installation
Dimensions

(Neutral pole)
Rear view(Fixed type) Rear view(Draw out type)
Bottom view Bottom view Terminal
(Fixed type) (Draw-out type)
( ) 4 pole dimensions

18
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

External Dimensions
(LBA-32A)

Fixed Type Neutral pole

Front view Side view Rear view

Draw -out Type Neutral pole

Rear view
Side view
Front view

Installation
Dimensions

Rear view(Fixed type) Rear view(Draw out type)


(Neutral pole)
Bottom view Bottom view
( ) 4 pole dimensions (Fixed type) Terminal
(Draw-out type)

19
External Dimensions
(LBA-40, 50A)

Fixed Type Draw -out Type

Neutral pole

Front view
Front view

Side view Side view

Rear view Rear view


20 ( ) 4 pole dimensions
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Installation
Dimensions

Rear view(Fixed type) Rear view(Draw-out type)

Terminal(Fixed type)

Bottom view(Fixed type) Bottom view(Draw-out type) Terminal(Draw-out type)

Arc insulation space


When braking the short circuit current, ionized gas
evacuates from the arc extinguish chamber.
In order to allow the gas to evacuate insulation
space should be reserved.

LBA-06/08 /
Type 10/13/16 / LBA-32A LBA-40 /50A
20/25A
A1 150 150 200
Fixed A2 200 300 300
Type B 100 100 100
C 320 320 320
A1 100 150 200
Draw-out A2 200 300 300
Type B 100 100 100
C 418 418 474

21
Ordering Information

Circuit breaker
Rating V/ Hz/ AF Number of poles 3P 4P
Mounting P(Fixed type) E(with E class cradle)
configuration F (with F2 class and safety shutter)
Control circuit
Housing type(standard) Auto connection type
connection

Control unit
E(Not needed) S(standard) Standard type (combination of L,S,I)
TYPE ST (standard, trip indicator) L (Long time delay), S (Short time delay),
SGT (standard, trip indicator, ground-fault protection) I (Instantaneous)

AC 100~120V AC 200~240V
S,ST type
DC 100~120V DC 125V
Control power
SGT type AC 100~120V AC 200~240V
DC 100~110V DC 125V

Operation & accessories


Operating mechanism manual charge motor charge
Rating of motor charging AC 100~110V AC 120V
and closing coil (50/60Hz) AC 200~220V AC 240V DC 100~125V
Not needed UVT-S UVT-05S
Under voltage trip device(UVT)
AC 100~120V AC 200~240V AC 380~460V

Shunt trip device(SHT) AC 100~125V AC 200~220V AC 240V DC 100~125V

Condenser trip device(CTD) CTD-100 CTD-200

Alarm s/w (AL) Not needed Needed


Maximum number of AX :
3a3b (standard) 3a4b Motor charging type : 4a3b
Auxiliary s/w (AX) 4a3b 4a4b Shunt trip device : 3a4b
Motor charging + Shunt trip device : 3a3b

Trip s/w (TS) Not needed Needed


Safety shutter(SS) Not needed Needed
Short circuit b contact Not needed Needed ( ea)
Cell s/w (CL) Not needed CL-C ( ea), CL-D ( ea)

Mechanical and installation accessories


Counter (CNT) Not needed Needed
Lockout coil(LC) AC 100~120V AC 200~240V AC 380~460V

When ordering, please send us this sheet together.

22
LG LOW VOLTAGE AIR CIRCUIT BREAKERS

Specifications

Ratings
Model LBA-06A LBA-10A LBA-10A LBA-13A LBA-16A LBA-20A LBA-25A LBA-32A LBA-40A LBA-50A
Number
of poles 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4 3 4

Rated 630-504-378 100-800-600 1250-1000-750 1600-1280-960 3200-2500-1920


4000-3200-2400
current 315-252-189 810-640-480 500-400-300 630-504-378 1000-800-600 2000-1600-1200 2500-2000-1500 2000-1600-1200 5000-3000-3000
2000-1600-1200
(OCR) 126-101-76 200-160-120 500-400-300 500-400-300 1000-800-600

Standard IES 947-2, BS 4752, NEMA SG 3, VDE 0660, JEC 160

Mounting configuration
Fixed type and draw out type (Manual connection type is standard)

Closing method
Manual charging type and motor charging type (select the control voltage)

Accessories
Undervoltage Shunt Condenser Auxiliary Trip OCR Open
Accessories tripping tripping tripping switch switch alarm close
device device device (AX) (TS) switch counter
(UVT) (SHT) (CTD) (AL) (CNT)

Maximum 1 1 1 4a4b 1a 1a 1
number

The economical type of auxiliary switches are 3a3b, Shunt tripping device is also attached.
If selecting 4a4b as an auxiliary, refer to page 9 of auxiliary switches.

Trip relay(OCR)
Not applicable to economy type
S-A Standard type (Overcurrent trip characteristics)
Type ST-A Standard + Trip indicator (LED)
SGT-A Standard + Trip indicator (LED) + Ground-fault protection
Default setting value of the OCR. Trip relay unit
Type LBA-06/08/10/13/16/20/25/32A LBA-40/50A
Continuous conductive current 100% of rated current specificed. 100second trip at 200%
Short-delay triping time Pick up at 400% of the rated current Pick up at 200%
Instantaneous pick-up current Pick up at 1,600% of the rated current Pick up at 1000%
Ground-fault protection Pick up at 50% of the rated current. 0.8 second trip.

23
2003-02

ACB(A) 2001 / Feb. 2003 Printed in Korea STAFF

You might also like