Additional Manual Siemen S7-200 PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 39

GP-PRO/PBIII for Windows

Device/PLC CONNECTION MANUAL

ADDITIONAL MANUAL

SIEMENS
S7-200/300/400 Series
(via MPI)
Reading the GP-PRO/PBIII Device/PLC Connection Manual
This document is designed as an addition to the latest GP-PRO/PBIII for Windows
Device/PLC Connection manuals SIEMENS PLC data, and covers the connecting
information with SIEMENS S7-200/300/400 Series (via MPI).
Please refer to this document when connecting your GP/GLC with SIEMENS S7-200/
300/400 Series via MPI.
For information concerning general type PLC connections and this documents docu-
mentation conventions, please refer to your Device/PLC Connection manual.

The information in this document will be included in the next version of the Device/PLC
Connection manual.
Installation
This CD-ROM includes all the protocol files required by the GP/GLC to communicate
with a SIEMENS PLC. Also, you will need to have the GP Screen Editor software
(GP-PRO/PBIII for Windows95 version 6.0 or higher) installed on your personal
computer's hard disk. For information about the installation of the GP Screen Editor
software, refer to that software's Operation Manual.

1) Be sure to Confirm that the GP Screen Editor software is installed in your PC prior
to starting this driver installation.
2) To install the new SIEMENS MPI driver, execute S7_MPI.exe for S7-200/300/
400 MPI connection.
3) Once the setup program starts, follow the instructions given to install the protocol
files.

When using the MPI protocol of S7-200 Series unit, select [Siemens S-200 via
MPI] and when using the MPI protocol of S7-300/400 Series unit,[Siemens S7-
300/400 via MPI] for the " PLC Type" .
Chapter 2 - PLC-GP Connection 2.16 Siemens

2.16 Siemens

2.16.1 System Structure

The following describes the system structure for connecting the GP to Siemens
PLCs.
Reference The Cable Diagrams mentioned in the following tables are
listed in the section titled "2.16.2 Cable Diagrams".

SIMATIC S5 Series (using Link I/F <3964/3964R via RK512 Protocol>)


CPU Link I/F Cable Diagram GP

90U, 95U, CP521 S1 RS-232C


100U (Cable Diagram 1)
115U CP524
CP525
*1
115U (CPU944) CPU unit Link I/F GP Series
135U, 155U CP524
CP525
*1
135U, 155U CPU unit Link I/F
(CPU928B)

*1 Connect to SI2 Port.

Note: Supports both 3964 and 3964R protocols. The GP automatically dis-
criminates between the two.
For better error detection, the 3964R is recommended.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-1


2.16 Siemens Chapter 2 - PLC-GP Connection

SIMATIC S5 Series (CPU Direct)


CPU *1 Cables GP

90U, 95U, 100U Digital's current loop


(CPU100/102/103), conv erter *2
115U GP000-IS11-O
(CPU941/942/943/ GP Series *3
944),
135U/155U
(CPU922/928/928B)

*1 Connect to the Programming port.


*2 Due to the size of its connector, this cable cannot be used for GP-270, GP-
370 , and GP-377R series units.
*3 Cannot be connected to GP2000 and GLC2000 Series units.

SIMATIC S7-200 Series (PPI Connection)


CPU Cables GP

CPU212, CPU214 RS422


GP Series
(Cable Diagram 2)

SIMATIC S7-200 Series (MPI Direct)

CPU Cable Diagram GP

CPU214, CPU215, RS-422


CPU216, CPU221, (Cable Diagram 11)
CPU222, CPU224, RS-422
GP/GLC Series *1
CPU226 (Cable Diagram 12)
RS-422
(Cable Diagram 13)

*1 Refer to this section's Connectable GP/GLC units for SIMATIC S7-200/


300/400 Series (MPI Direct).

2-16-2 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC S7-300 Series (MPI Direct)


CPU Cable Diagram GP

CPU312IFM RS-422
CPU313 (Cable Diagram 11)
CPU314
CPU314IFM RS-422
CPU315 (Cable Diagram 12) GP/GLC Series *1

CPU315-2DP
CPU316 RS-422
CPU316-2DP (Cable Diagram 13)
CPU318-2

*1 Refer to this section's Connectable GP/GLC units for SIMATIC S7-200/


300/400 Series (MPI Direct).

SIMATIC S7-400 Series (MPI Direct)


CPU Cable Diagram GP

CPU412-1 RS-422
CPU412-2DP (Cable Diagram 11)
CPU413-1
CPU413-2DP
CPU414-1 RS-422
CPU414-2DP (Cable Diagram 12) GP/GLC Series *1

CPU414-3DP
CPU416-1
RS-422
CPU416-2DP
(Cable Diagram 13)
CPU416-3DP
CPU-417-4

*1 Refer to this section's Connectable GP/GLC units for SIMATIC S7-200/


300/400 Series (MPI Direct).

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-3


2.16 Siemens Chapter 2 - PLC-GP Connection

Connectable GP/GLC units for SIMATIC S7-200/300/400 Series


(MPI Direct)
Series Name Product Name *1
187500bps
GP70 Series GP-377 Series GP-377L
GP-377S
GP-37W2 Series GP-37W2B Rev .L or higher
GP77R Series GP-377R Series GP-377RT
GP-477R Series GP-477RE
GP-577R Series GP-577RS
GP-577RT
GP2000 Series GP-2300 Series GP-2300L Rev . I or higher
GP-2300T Rev . I or higher
GP-2301 Series GP-2301L Rev . I or higher
GP-2301S Rev . I or higher
GP-2400 Series GP-2400T Rev . H or higher
GP-2500 Series GP-2500L Rev . B or higher
GP-2500S Rev . A or higher
GP-2500T
Rev . C or higher
(Only GP2500-TC41-24V)
GP-2501 Series GP-2501S
GP-2501T
GP-2600 Series GP-2600T
Rev . C or higher
(Only GP2600-TC41-24V)
GP2000H GP-2301H Series GP-2301HL All Rev .
Series GP-2301HS All Rev .
GP-2401H Series GP-2401HT All Rev .
GLC2000 Series GLC2300 Series GLC-2300L Rev . I or higher
GLC-2300T Rev . I or higher
GLC2300 Series GLC-2400T
GLC2300 Series GLC-2600T

*1 When using a unit that cannot operate at 187500bps, be sure to select an-
other data transfer speed. 2.16.4 Environment Setting Ex-
ample

! When transferring data using a GLC2000 unit at 187500bps, be


Important sure to either set the Ladder Scan Time to 8 times longer than the
Logic Time, or set the Percent Scan at 10%.
For setting information, refer to your "Pro-Control Editor User
Manual".

2-16-4 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

Connection Structure
1:n RS-422 2-wire type
Max. 4 units

S7-200/300/400 Series S7-200/300/400 Series


GP /GLCSeries

RS-422

n:1 RS-422 2-wire type


Max. 3 units

S7-200/300/400 Series
GP /GLCSeries GP /GLCSeries

RS-422

n:m RS-422 2-wire type


Max. 3 units Max. 4 units

GP /GLC Series S7-200/300/400 Series

#1 #3 #1 #3

#2 #4 #2 #4

RS-422

* The connections 1:n and n:1 can be made on the same line.

Note: For details about MPI Network, refer to Siemens's Manual.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-5


2.16 Siemens Chapter 2 - PLC-GP Connection

SIMATIC S7-300 Series (MPI via adapter)


CPU Link I/F Cable Diagram GP

CPU312IFM, CPU313, HMI Adapter RS-232C


CPU314, CPU315, 6ES7-972-0CA 10-0XA0 (Cable Diagram 3)
CPU315-2DP, PC Adapter RS-232C
6ES7-972-0CA21-0XA0 (Cable Diagram 3) GP Series
PC/MPI Cable RS-232C
6ES7901-2BF00-0AA0 (Cable Diagram 4)
Digital's GP070-MPI-41

SIMATIC S7-400 Series (MPI via adapter)


CPU Link I/F Cable Diagram GP

CPU413-2DP HMI Adapter RS-232C


6ES7-972-0CA 10-0XA0 (Cable Diagram 3)
PC Adapter RS-232C
6ES7-972-0CA21-0XA0 (Cable Diagram 3) GP Series
PC/MPI Cable RS-232C
6ES7901-2BF00-0AA0 (Cable Diagram 4)
Digital's GP070-MPI-41

SIMATIC S7-300Series (Using Adapter <3964/RK512 >)


CPU Link I/F Cable Diagram GP

CPU313, CPU314, CP340


*1 RS-232C
CPU315, (Cable Diagram 5) GP Series
CP341
CPU315-2DP

*1 When using the CP340 Link I/F an "Interpreter program" is required on the
PLC. This is contained in the GP-PRO/PBIII for Windows CD-ROM 's "CP340"
folder. Please see "README" file in this folder in order to install this pro-
gram.

Note: This driver cannot be used with the CPU312IFM.

2-16-6 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC S7-400 Series (Using Adapter <3964/RK512 >)


CPU Link I/F Cable Diagram GP

CPU413-2DP CP441-2 RS-422


(Cable Diagram 6)

SIMATIC 505 Series


CPU Cable Diagram GP

545-1101, 545-1102, RS-232C


545-1103, 545-1104, Port 1 Connection
545-1105, 545-1106, (Cable Diagram 7)
555-1101, 555-1102,
555-1103, 555-1104,
555-1105, 555-1106
545-1101, 545-1102, RS-422(4-wire type)
555-1101, 555-1102 Port 2 Connection
(Cable Diagram 8)
545-1104, 545-1105, RS-422(4-wire type)
GP Series
545-1106, 555-1103, Port 2 Connection
555-1104, 555-1105, (Cable Diagram 9)
555-1106
545-1103, 545-1104, RS-232C
545-1105, 545-1106, Port 2 Connection
555-1103, 555-1104, (Cable Diagram 10)
555-1105, 555-1106
545-1101, 545-1102, RS-232C
555-1101, 555-1102 Port 2 Connection
(Cable Diagram 11)

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-7


2.16 Siemens Chapter 2 - PLC-GP Connection

2.16.2 Cable Diagrams

The cable diagrams illustrated below and the cable diagrams recommended by Siemens may
differ, however, using these cables for your PLC operations will not cause any problems.

Careful! Ground your PLCs FG terminal according to your country's appli-


cable standard. For details, refer to the corresponding PLC manual.

! Connect the FG line of the Shield cable to either the GP or PLC,


Important depending on your environment. When using a Housing and
Grounding the FG line, be sure to use an electrical conductor.
For the RS-232C connection, use a cable length 15m or less.
If a communications cable is used, it must be connected to the
SG (signal ground).

Cable Diagram 1 (RS-232C)

NC
ER

Cable Diagram 2 (RS-422)

2-16-8 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

Cable Diagram 3 (RS-232C)

Cable Diagram 4 (RS-232C)

Cable Diagram 5 (RS-232C)

Cable Diagram 6 (RS-422)


Shield

CSA
ERA

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-9


2.16 Siemens Chapter 2 - PLC-GP Connection

Cable Diagram 7 (RS-232C)


Shield
GP Unit (25P) PLC (9P)

Cable Diagram 8 (RS-422)


When using Digitals RS-422 connector terminal adapter, GP070-CN10-O
GP Unit (25P) Shield PLC (9P)

Termination RDA 1 DO+


Resistance 120 RDB 7 DO-
SDA 5 DI+ Termination
SDB 8 DI- Resistance 120
SG 3 GND
GP070-CN10-O FG

When making your own cable connections

GP Unit (25P) Shield PLC (9P)

1 FG 1 DO+
7 SG 7 DO-
9 TRMX 5 DI+ Termination
Termination 10 RDA 8 DI- Resistance 120
Resistance 120 16 RDB 3 GND
11 SDA
15 SDB
18 CSB
19 ERB
21 CSA
22 ERA

2-16-10 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

Cable Diagram 9 (RS-232C)


GP Unit (25P) Shield PLC (9P)

Cable Diagram 10 (RS-232C)

GP Unit (25P) Shield PLC (9P)

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-11


2.16 Siemens Chapter 2 - PLC-GP Connection

Cable Diagram 11 (RS-422 2-wire type)

! Use a cable length 50m or less for a single segment.


Important

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O


PLC
GP Unit (9P male)
Termination
RDA 3 B/B
Resistance
RDB 8 A/A
Termination 220
SDA 5 SG
Resistance
SDB Housing
GP070-CN10-O 220
TERM
SG
FG
Shield

Max. 50m

When making your own cable connections


GP Unit
(25P male) PLC
1 FG (9P male)
7 SG Housing
Termination
9 TERM 5 SG
Resistance
10 RDA 3 B/B
220
16 RDB 8 A/A
Termination
11 SDA
Resistance 15 SDB
220 18 CSB
19 ERB
21 CSA
22 ERA
Shield

Max. 50m

2-16-12 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

When using the following PLCs (MPI and Profibus port are the same type), the
following cable diagram also can be used.
318-2(6ES7 318 2AJ00), 412-1(6ES7 412 1XF03), 412-2DP(6ES7 412
2XG00),414-2DP(6ES7 414 2XG03), 414-3DP(6ES7 414-3XJ00), 416-
2DP(6ES7 416 2XK02), 416-3DP(6ES7 416-3XL00), 417-4(6ES7 417-4XL00)

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O and


Siemens's Profibus Connector.
PLC
GP (9P male)
RDA 3 B/B Termination
RDB 8 A/A Resistance
Termination
SDA Housing 220
Resistance
SDB
220
GP070-CN10-O TERM
SG Shield
FG
Max. 50m

When making your own cable connections


GP
(25P male)
1 FG PLC
7 SG (9P male)
9 TERM Housing
10 RDA 3 B/B Termination
16 RDB 8 A/A Resistance
Termination
11 SDA 220
Resistance
15 SDB
220
18 CSB
19 ERB
21 CSA
22 ERA
Shield

Max. 50m

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-13


2.16 Siemens Chapter 2 - PLC-GP Connection

Cable Diagram 12 (RS-422 2-wire type)

! Use a cable length less than 50m for a single segment.


Important

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O


PLC PLC
GP (9P male) (9P male)
RDA 3 B/B 3 B/B Termination
RDB 8 A/A 8 A/A Resistance
Termination
SDA 5 SG 5 SG 220
Resistance
SDB Housing Housing
220
TERM
Shield
SG
FG
Shield
GP070-CN10-O
Max. 50m

When making your own cable connections

GP
(25P male) PLC PLC
1 FG (9P male) (9P male)
7 SG Housing Housing
9 TERM 5 SG 5 SG
10 RDA 3 B/B 3 B/B Termination
16 RDB 8 A/A 8 A/A Resistance
Termination 220
11 SDA Shield
Resistance
15 SDB
220 18 CSB
19 ERB
21 CSA
22 ERA Shield

Max. 50m

Note: When making your own cable connections, we recommend to use the ter-
minal between the cables because the PLC side connector is Dsub 9-pin
connector.

2-16-14 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

When using the following PLCs (MPI and Profibus port are the same type), the
following cable diagram also can be used.
318-2(6ES7 318 2AJ00), 412-1(6ES7 412 1XF03), 412-2DP(6ES7 412
2XG00),414-2DP(6ES7 414 2XG03), 414-3DP(6ES7 414-3XJ00), 416-
2DP(6ES7 416 2XK02), 416-3DP(6ES7 416-3XL00), 417-4(6ES7 417-4XL00)

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O and


Siemens's Profibus Connector.
PLC PLC
GP (9P male) (9P male)
RDA 3 B/B 3 B/B Termination
RDB 8 A/A 8 A/A Resistance
Termination
SDA Housing Housing 220
Resistance
SDB
220
TERM
Shield
SG
FG
Shield
GP070-CN10-O
Max. 50m

When making your own cable connections

GP
(25P male)
1 FG PLC PLC
7 SG (9P male) (9P male)
9 TERM Housing Housing
10 RDA 3 B/B 3 B/B Termination
16 RDB 8 A/A 8 A/A Resistance
Termination 220
11 SDA Shield
Resistance 15 SDB
220 18 CSB
19 ERB
21 CSA
22 ERA Shield

Max. 50m

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-15


2.16 Siemens Chapter 2 - PLC-GP Connection

Cable Diagram 13 (RS-422 2-wire type)

! Use a cable length less than 50m for a single segment.


Important

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O


PLC
GP GP (9P male)
RDA RDA 3 B/B Termination
RDB RDB 8 A/A Resistance
Termination SDA SDA 5 SG 220
Resistance SDB SDB Housing
220 TERM TERM
SG SG
FG FG
Shield Shield

GP070-CN10-O Within 50m

When using the following PLCs (MPI and Profibus port are the same type), the
following cable diagram also can be used.
318-2(6ES7 318 2AJ00), 412-1(6ES7 412 1XF03), 412-2DP(6ES7 412
2XG00),414-2DP(6ES7 414 2XG03), 414-3DP(6ES7 414-3XJ00), 416-
2DP(6ES7 416 2XK02), 416-3DP(6ES7 416-3XL00), 417-4(6ES7 417-4XL00)

When using Digitals RS-422 connector terminal adapter, GP070-CN10-O and


Siemens's Profibus Connector.
PLC
GP GP (9P male)
RDA RDA 3 B/B Termination
RDB RDB 8 A/A Resistance
Termination
SDA SDA Housing 220
Resistance
SDB SDB
220
TERM TERM
SG SG
FG FG
Shield Shield

GP070-CN10-O
Max. 50m

2-16-16 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

2.16.3 Supported Devices

The following tables describe the range of devices supported by the GP.

SIMATIC S5 Series (using Adapter)


Setup System Area here.
Device Bit Address Word Address Particulars
*1*2
Data Register --- D003000 ~ D255255
Extended Data H/L
*1*2
--- X003000 ~ X255255
Register

SIMATIC S5 Series (CPU Direct)


Setup System Area here.
Device Bit Address Word Address Particulars
*3
Input Relay I0000 ~ I1277 IW000 ~ IW126
*3
Output Relay Q0000 ~ Q1277 QW000 ~ QW126 H/L
*3
Internal Relay F0000 ~ F2557 FW000 ~ FW254

Timer --- T000 ~ T255


L/H
Counter --- C000 ~ C255
*1 *4
Data Register --- D002000 ~ D255255
Extended Data H/L
*1 *4 *5
--- X002000 ~ X255255
Register

* 1 The range for the Data Register and the Extended Data Register must also be
set up in the PLC. Communication will not occur with the GP when the Sys-
tem Area range is not setup.
* 2 The Data Register and Extended Data Register is as illustrated below.
E.g. D003 000
Data Word (DW) No. 000~255
Data Block (DB) No. 003~255

* 3 The bit device illustration for the PLC side is different.


E.g. GP PLC
Q0007 Q0.7

* 4 The Data Register and Extended Data Register is as illustrated below.


E.g. D002 000
Data Word (DW) No. 000~255
Data Block (DB) No. 002~255
* 5 The Extended Data Register is possible only with S5 135U/155U.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-17


2.16 Siemens Chapter 2 - PLC-GP Connection

Note: For information about Bit Write process differences, see the end of this
section.

SIMATIC S7-200 Series (PPI Coonnection)


Setup System Area here.

Device Bit Address Word Address Particulars


*1
Input I00 ~ I77 IW0 ~ IW6
*1
Output Q00 ~ Q77 QW0 ~ QW6
*1
Internal Memory M000 ~ M317 MW00 ~ MW30
*1
Special Memory SM000 ~ SM857 SMW00 ~ SMW84
Timer Bit T000 ~ T127 --- H/L

Counter Bit C00 ~ C63 ---

Variable Memory --- VW0000 ~ VW4094

Timer Word --- TW000 ~ TW127

Counter Word --- CW000 ~ CW127

*1 The bit position is the last digit entered. There is no . delimeter - e.g. I3.7 is
equivalent to 137 in GP-PRO/PBIII.

SIMATIC S7-200 Series (MPI Direct)

Setup System Area here.


Device Bit Address Word Address Particulars

Input I0000.0 ~ I0015.7 IW0000 ~ IW0014

Output Q0000.0 ~ Q0015.7 QW0000 ~ QW0014


Internal M0000.0 ~ M0031.7 MW0000 ~ MW0030
H/L
Timer --- T0000 ~ T0255 *1

Counter --- C0000 ~ C0255 *1

Variable Memory --- VW0000 ~ VW5118

*1 Cannot be written in. When performing data written, a Host communication


Error (02:FB) will occur. 2.16.5 Error Codes

! Pro-Server cannot read/write.


Important
When connecting multiple GP units, be sure to set each unit's
system area top address so that it does not overlap the system
area of another GP.

2-16-18 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC S7-300/400 Series (MPI Direct/MPI via adapter)


Setup System Area here.
Device Bit Address Word Address Particulars

Input E00000.0 ~ E00127.7 EW00000 ~ EW00126 *1

Output A00000.0 ~ A00127.7 AW00000 ~ AW00126 *1

Internal M00000.0 ~ M00255.7 MW00000 ~ MW00254 *1

Timer --- T00000 ~ T00127 *2 *3


H/L
Counter --- Z00000 ~ Z00063 *2 *3

*4
Data Block --- DB1W00000 ~ DB60W65532
DB1.DBX0.0 ~ DB1.DBW0 ~ *5
Data Block
DB65535.DBX65533.7 DB65535.DBW65532

*1 When using a GP70 Series unit (except for GP-377 Series units), only de-
vices of the PLC registered as #1 in the Target Node (PLC) area can be used.
All other GP/GLC units can use PLC device #1 to #4, set up in the Target
Node (PLC) area. For Target Node setting, refer to 2.16.4 Environment Setup.
*2. Data write cannot be performed. If data write is attempted, a Host Commu-
nication error (02:FB) will occur. 2.16.5 Error Codes
*3. Only the PLC device registered as #1 in the Target Node (PLC) area can be
used. For Target Node setting, refer to 2.16.4 Environment Setup.
*4 The addressing format for entering on GP-PRO/PB III is different from the
convention used in the S7-300/400 - e.g. DB63W00020 is equivalent to
DB63.DBW20.
*5 When Data Blocks other than DB61 in a 1:1 Connection or using a 1:n
connection designating data blocks for multiple PLCs, use this address. How-
ever, the maximum number of data blocks is 40. GP70 Series units (except for
GP-377 Series units) cannot use this devices.

! Pro-Server read/write of devices using data blocks DB1.DBW0 to


Important DB65535.DBW65532 is not possible. With other devices, read/
write is possible only with the PLC registered as #1 in the Target
Node (PLC) area. For Target Node setting, refer to 2.16.4 Envi-
ronment Setup.
When designating indirect addresses for E-tags and K-tags, de-
vices using data blocks DB1.DBW0 to DB65535.DBW65532 can-
not be used.
When connecting multiple GP units, be sure to set each unit's
system area top address so that it does not overlap the system
area of another GP.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-19


2.16 Siemens Chapter 2 - PLC-GP Connection

Setting the GP-PRO/PBIII for Windows


To set any Part or Tag on the GP-PRO/PBIII, specify the registration number of the
PLC when entering the address. If not, the last entered device number is assumed.
(The default value is 01).
To use a registration number, previously register that number by selecting MPI Net-
work from the Mode Settings tab of the GP Settings window.

When setting an N-tag connecting to SIMATIC S7-200 Series units


(MPI Direct)

Device name
Address

Bit position

Target PLC No.


Select a PLC 's
registerd Number #1
to #4 in the Target
Node (PLC) area.

2.16.4 Environment
Setup
1_VW0000

Device address

PLC's Registered Number setting in the Target Node (PLC) area.

2-16-20 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

When setting an N-tag connecting to SIMATIC S7-300/400 Series units


(MPI Direct/MPI via Adapter)

Device name

Data Block

Address

Bit position

Target PLC No.


Select a PLC 's
registerd Number #1
to #4 in the Target
Node (PLC) area.

2.16.4 Environment
1_DB1.DBW0 Setup

Device address

PLC's Registered Number setting in the Target Node (PLC) area.

SIMATIC S7-300/400 (via 3964/RK512)


Setup System Area here.
Device Bit Address Word Address Particulars

Data Memory DB1W000000 ~ DB60W002547 DB1W00000 ~ DB60W00254 *1*2 H/L

Note: It is possible to enable/disable the Block Check Character (BCC) in PLC


to GP communications.
This can be performed via the GP's OFFLINE mode, or, via the GP-PRO/
PBIII Editor's Mode Area's "Option" Command.

*1 Some Data Blocks are reserved for the 3964 interpreter program:
DB2,DB3,DB5 & DB10.
*2 The addressing format for entering settings in GP-PRO/PB III is different
from the convention used in the S7-300/400 - e.g. DB63W00020 is equiva-
lent to DB63.DBW20.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-21


2.16 Siemens Chapter 2 - PLC-GP Connection

SIMATIC 505 Series


Setup System Area here.
Device Bit Address Word Adress Particulars

Variable Memory V00001 ~ V26624


*1
Word Input WX00001 ~ WX08192 L/H

Word Output WY00001 ~ WY08192

Discrete Input accessed as bit X0001 ~ X8192

Discrete Output accessed as bit Y0001 ~ Y8192

Control Relay Accessed as bit CR00001 ~ CR32768


*2
Loop Gain LKC0001 ~ LKC0064
*2
Loop Reset LTI0001 ~ LTI0064
*2
Loop Rate LTD0001 ~ LTD0064
*2
Loop Alarm High Limit LHA0001 ~ LHA0064
*2
Loop Low Alarm Limit LLA0001 ~ LLA0064
*2
Loop Process Variable LPV0001 ~ LPV0064
*2
Loop PV High Limit LPVH0001 ~ LPVH0064
*2
Loop PV Low Limit LPVL0001 ~ LPVL0064
*2
Loop Orange Deviation Limit LODA0001 ~ LODA0064
Loop Yellow Deviation Alarm *2
LYDA0001 ~ LYDA0064
Limit
*2
Loop Sample Rate LTS0001 ~ LTS0064
*2
Loop Setpoint LSP0001 ~ LSP0064
*2
Loop Output LMN0001 ~ LMN0064
*1 *2
Loop Error LERR0001 ~ LERR0064
*2
Loop Bias LMX0001 ~ LMX0064
*2
Loop Alarm High-High Limit LHHA0001 ~ LHHA0064
*2
Loop Low-Low Alarm Unit LLLA0001 ~ LLLA0064
Loop Rate of Change Alarm *2
LRCA0001 ~ LRCA0064
Limit
*2
Loop Setpoint High Point LSPH0001 ~ LSPH0064

(Continued on next page)

2-16-22 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC 505 Series


Device Bit Address Word Adress Particulars
*2
Loop Setpoint Low Limit LSPL0001 ~ LSPL0064
*2
Loop Alarm Deadband LADB0001 ~ LADB0064

Loop V-flags LVF0001 ~ LVF0064


Most Significant Word of Loop
LCFH0001 ~ LCFH0064 L/H
C-flags
Least Significant Word of Loop
LCFL0001 ~ LCFL0064
C-flags
Analog Alarm/Alarm *2
AADB0001 ~ AADB0128
Acknowledge Flags
Most Significant Word of Analog
ACFH0001 ~ ACFH0128
Alarm C-flags
L/H
Least Significant Word of Analog
ACFL0001 ~ ACFL0128
Alarm C-flags
*1*2
Analog Alarm Error AERR0001 ~ AERR0128
*2
Analog Alarm High Alarm Limit AHA0001 ~ AHA0128
Analog Alarm High-High Alarm *2
AHHA0001 ~ AHHA0128
Limit
*2
Analog Alarm Low Alarm Limit ALA0001 ~ ALA0128
Analog Alarm Low-Low Alarm *2
ALLA0001 ~ ALLA0128
Limit
Analog Alarm Loop Orange *2
AODA0001 ~ AODA0128
Deviation Alarm Limit
*2
Analog Alarm Process Variable APV0001 ~ APV0128
Analog Alarm Rate of Change *2
ARCA0001 ~ ARCA0128
Alarm Limit
*2
Analog Alarm Setpoint ASP0001 ~ ASP0128
*2
Analog Alarm SP High Limit ASPH0001 ~ ASPH0128
*2
Analog Alarm SP Low Limit ASPL0001 ~ ASPL0128
*2
Analog Alarm Sample Rate ATS0001 ~ ATS0128
Analog Alarm Yellow Deviation *2
AYDA0001 ~ AYDA0128
Alarm Limit
*3
Timer/Counter Preset TCP0001 ~ TCP1024
*3
Timer/Counter Current TCC0001 ~ TCC1024
*3*4
Drum Counter Preset DCP0101 ~ DCP6416
*3*5*6
Drum Step Preset DSP0001 ~ DSP0064 L/H
*3*5*6
Drum Step Current DSC0001 ~ DSC0064
*1
Status Word STW0001 ~ STW0222
*1
Drum Count Current DCC0001 ~ DCC0064

(Continued on next page)

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-23


2.16 Siemens Chapter 2 - PLC-GP Connection

(From previous page)


*1 The GP cannot write data to this device. Use it only for reading.
*2 This device uses Float. When this type of device is used, only the E-tag and
K-tags 32 bit Float setting can be used.
*3 32 bit reading / writing, or reading / writing a K-tags text string cannot be
performed.
*4 Address entry method:
Enter 1.01 as 101
Enter 1.02 as 102
Enter 1.03 as 103

Enter 1.16 as 116
Enter 2.01 as 201
Enter 2.02 as 202

Enter 64.15 as 6415
Enter 64.16 as 6416
*5 Entry range is from 0 to 15 (dec.)
*6 +1 is added to all data input from the GP to the PLC. -1 is added to all data
output from the PLC to the GP.
GP PLC
1 2 ( 1 entered from the GP is changed to 2 in the PLC. )
5 6 ( 6 sent from the PLC to the GP will become 5. )

2-16-24 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

2.16.4 Environment Setup

The following lists Digital's recommended PLC and GP communication settings.

SIMATIC S5 Series (using Link I/F)


GP Setup Link I/F Setup

Baud Rate 19200 bps Baud Rate 19200 bps

Data Length 8 bits Data Bit 8 bits


Stop Bit 1 bit Stop Bit 1 bit

Parity Bit Even Parity Bit Even


Data Flow Control ER Control ---
Communication Format RS-232C
---
(RS-232C)
Communication Format 4-wire type
---
(RS-422)
Unit No. 0 (fixed) ---

SIMATIC S5 Series (CPU Direct)


GP Setup PC Link Unit Setup

Baud Rate 9600 bps (fixed) ---

Data Length 8 bits (fixed) ---

Stop Bit 1 bit (fixed) ---

Parity Bit Even (fixed) ---

Data Flow Control ER Control (fixed) ---

Communication Format RS-232C (fixed) ---

Unit No. 0 (fixed) ---

System Data Area Setup


SYSTEM DATA AREA START DBused to setup the Data Register's Data
Block (DB) Number.
SYSTEM DATA AREA START DWused to setup the Data Register's Data
Word (DW) Number.
Reference "2.16.3 Supported Devices"
If Link I/F is used, the system's number is indicated before the DB (Data Block) on
the INITIALIZE area's [SETUP OPERATION SURROUNDINGS] screen.
Changing this number, however, is not necessary since this data will be used only for
future expansion.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-25


2.16 Siemens Chapter 2 - PLC-GP Connection

STOP The method of writing bits will differ depending on the GP series.
<GP-*30 series>
When the bit write operation (other than Reverse) is performed, the correspond-
ing word address will set the bits to 0 (except the designated bits).
<Except GP-*30 series>
When the bit wirte operation is performed, the GP reads the PLC's correspond-
ing word address and turns a bit ON, then send back to PLC. Do not write to
the word address from the ladder program in the middle of this operation.
When running a GP-*30 Series ladder program, be aware of the above points.

SIMATIC S7-200 Series (PPI Connection)


GP Setup PC Link Unit Setup

Baud Rate 9600 bps ---

Data Bit 8 bits ---

Parity Bit Even ---

Stop Bit 1 bit ---

Data Flow Control ER Control ---


RS-422 2-wire
Communication-format ---
type
GP No. 1 ---

PLC No. 2 2

SIMATIC S7-200 Series (MPI Direct)


GP Setup PLC Setup
*1
Baud Rate 19200 bps Baud Rate 19200 bps
Data Length 8 bits (fixed)
Stop Bit 1 bit (fixed)
Parity Bit Even (fixed)
Data Flow Control ER (fixed)
Communication Format RS-422 2-Wire type (fixed)
*2 *3 *3
Highest Node No. 31 Highest Address 31
*4
GP is Only Master ON
*5
Local Node (GP) 1
*7
No. of PLCs 1
*6
#1 2 MPI Address 2
Depeneding on the PLC's *6
Target Node #2 MPI Address 0 to 126
MPI Address
(PLC) Node Num
*8
Depeneding on the PLC's *6
#3 MPI Address 0 to 126
MPI Address
Depeneding on the PLC's *6
#4 MPI Address 0 to 126
MPI Address

2-16-26 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens
*1 Baude Rate can be 9600bps, 19200bps or 187500bps depending on the PLC
unit's Baud rate. However, certain GP units cannot use the 187500bps speed.
2.16.1 System Structure SIMATIC S7-200 Series (MPI Di-
rect)
If the 187500bps speed is used with incompatible GP Series units, a Host
Communication error (02:F2) will occur.

2.16.5 Error Codes


*2 15/31/63/126 can be selected. Be sure this setting is the same as the PLC
unit's Highest Address setting.
*3 15/31/63/126 can be selected. On a single network, choose the value that is
higher than the maximum value of the GP's Local Node or the PLC's MPI
Address. For example, if the maximum value is 16, then select 31.Specify the
smallest practical value for the maximum node address. This will shorten the
time required for initializing the network.
*4 When MPI master does not exist on a single network, a GP can be master.
When GP is master, set to ON.
*5 Set the GP's unit number. Setting range is from 0 to 126, and the maximum
number of GP units that can be connected is 3. Be sure this number is not
used as a PLC's Node No.
*6 Set the PLC unit's node number. Setting range is from 0 to 126, and the
maximum number of PLCs that can be connected is 4. Be sure this number is
not used as a GP and another PLC unit's Node No.
*7 Select the number of PLCs to use for data communication.
*8 Register the PLC's MPI Address. This setting can only be entered using the
GP-PRO/PBIII software. The GP unit's OFFLINE mode cannot be used.

The following diagram is Siemens S7-200 Series MPI Network setting


Note: window. This window is displayed by clicking on the [MPI Network] but-
ton in the [GP System Setup]-[Mode Settings] tab. The number in the
diagram refers to the footnote number as shown above.

*2 *4

*7

*7 *8
<SIMATIC S7-200 Series MPI Network Setting Window>
GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-27
2.16 Siemens Chapter 2 - PLC-GP Connection

SIMATIC S7-300/400 Series (MPI Direct)


GP Setup PLC Setup
*1
Baud Rate 19200 bps Baud Rate 19200 bpd
Data Length 8 bits (fixed)
Stop Bit 1 bit (fixed)
Parity Bit Even (fixed)
Data flow Control ER (fixed)
Communication Format RS-422 2-wire type (fixed)
*2 *3 *3
Highest Node No. 31 Highest Address 31
*4
Connection Method Direct (fixed)
*5
Local Node (GP) 1
*7
No. of PLCs 1
*6
#1 2 MPI Address 2
Depending on the PLC MPI *6
Target Node #2 MPI Address 0 to 126
Address
(PLC) Node Num
*8
Depending on the PLC MPI *6
#3 MPI Address 0 to 126
Address
Depending on the PLC MPI *6
#4 MPI Address 0 to 126
Address

*1 Baud Rate speed can be 19200 bps or 187500 bps depending on the PLC
unit'sBaud rate. However, certain GP units cannot use the 187500 bps
speed. 2.16.1 System Structure Connectable GP/GLC
units for SIMATIC S7-200/300/400 Series(MPI Direct)
If 187500 bps is used with an incompatible GP Series units, a Host Commu-
nication error (02:F2) will occur. 2.16.5 Error Codes
*2 15/31/63/126 can be selected. Be sure this setting is the same as the PLC
unit's Highest Address setting.
*3 15/31/63/126 can be selected. On a single network, choose the value that is
higher than the maximum value of the GP's Local Node or the PLC's MPI
Address. For example, if the maximum value is 16, then select 31. Specify the
smallest practical value for the maximum node address. This will shorten the
time required for initializing the network.
*4 Set the Connection Method. When connecting to the MPI port directly, set to
"Direct".
*5 Set the GP's unit number. Setting range is from 0 to 126. Maximum number of
GP units that can be connected is 3. Be sure this number is not used as a
PLC's Node No.
*6 Set the PLC unit's node number. Setting range is from 0 to 126, and the
maximum number of PLCs that can be connected is 4. Be sure this number is
not used as a GP and another PLC unit's Node No.
*7 Select the number of PLCs to use for data communication. Setting range is
from 1 to 4.
*8 Register the PLC's MPI Address. Depending on the No. of PLCs setting, from
#2 to #4 can be set. This setting can only be entered using the GP-PRO/PBIII
software. The GP unit's OFFLINE mode cannot be used.

2-16-28 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC S7-300/400 Series (MPI via adapter)


GP Setup PLC Setup
*1 *9
Baud Rate 19200 bps Baud Rate
Data Length 8 bits (fixed)
Stop Bit 1 bit (fixed)
Parity Bit Even (fixed)
Data flow Control ER (fixed)
Communication Format RS-232C (fixed)
*2 *3 *3
Highest Node No. 31 Highest Address 31
*4
Connection Method via Adapter (fixed)
*5
Local Node (GP) 1
*7
No. of PLCs 1
*6
#1 2 MPI Address 2
Depending on the PLC *6
Target Node #2 MPI Address 0 to 126
MPI Address
(PLC) *8
Node Num Depending on the PLC *6
#3 MPI Address 0 to 126
MPI Address
Depending on the PLC *6
#4 MPI Address 0 to 126
MPI Address

*1 When using an HMI Adapter, Baud Rate speed can be 19200 bps, 38400 bps
or 115200 bps. However, when using another adapter, Baud Rate speed can
only be 19200 bps.
*2 15/31/63/126 can be selected. Be sure this setting is the same as the PLC
unit's Highest Address setting.
*3 15/31/63/126 can be selected. On a single network, choose the value that is
higher than the maximum value of the GP's Local Node or the PLC's MPI
Address. For example, if the maximum value is 16, then select 31.Specify the
smallest practical value for the maximum node address. This will shorten the
time required for initializing the network.
*4 Set the Connection Method. When using an adapter, set it to "via Adapter".
*5 Set the GP's unit number. Setting range is from 0 to 126, and the maximum
number of GP units that can be connected is 3. Be sure this number is not
used as a PLC's Node No.
*6 Set the PLC unit's node number. Setting range is from 0 to 126, and the
maximum number of PLCs that can be connected is 4. Be sure this number is
not used as a GP and another PLC unit's Node No.
*7 Select the number of PLCs to use for data communication. Setting range is
from 1 to 4.
*8 Register the PLC's MPI Address. Depending on the No.of PLC setting, from
#2 to #4 can be set. This setting can only be entered using the GP-PRO/PBIII
software. The GP unit's OFFLINE mode cannot be used.
*9 The Baud Rate Setting does not required.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-29


2.16 Siemens Chapter 2 - PLC-GP Connection

Note: The following diagram is Siemens S7-300/400 Series MPI Network set-
ting window. This window is displayed by clicking on the [MPI Network]
button in the [GP System Setup]-[Mode Settings] tab. The number in the
diagram refers to the footnote number as shown above.

*2 *4

*5

*7 *8

<SIMATIC S7-300/400 Series MPI Network Setting Window>

2-16-30 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Chapter 2 - PLC-GP Connection 2.16 Siemens

SIMATIC S7-300 (Using Adapter< 3964/RK512>)


GP Setup PC Link Unit Setup
Communication-format RS-232C ---
Baud Rate 19200 bps ---
Data Bit 8 bits ---
Parity Bit Even ---
Stop Bit 1 bit ---
Data Flow Control ER Control ---

Note: It is possible to enable/disable the Block Check Character (BCC) in com-


munications between the PLC and the GP. This configuration can be per-
formed via the Editor's [Mode] -> [Option] menu.

SIMATIC S7-400 Using Adapter< 3964/RK512>)


GP Setup PC Link Unit Setup
Communication-format RS422 ---
Baud Rate 19200 bps ---
Data Bit 8 bits ---
Parity Even ---
Stop Bit 1 bit ---
Data Flow Control ER Control ---

SIMATIC 505
GP Setup PLC Settings
Baud Rate 19200 bps Baud Rate 19200 bps
Data Length 7 bits Data Length 7bits (fixed)
Stop Bit 1 bit Stop Bit 1bit (fixed)
Parity Bit Odd Parity Bit Odd (fixed)
Data Flow Control ER Control
Communication Format Communication Format Turn on the Dip
RS-232C
(RS-232C) (RS-232C) Switch 1 on CPU.
Communication Format Communication Format Turn on the Dip
RS-422 (4-wire type)
(RS-422) (RS-422) Switch 1 on CPU.

GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual 2-16-31


2.16 Siemens Chapter 2 - PLC-GP Connection

2.16.5 Error Codes

<MPI Error Codes>


An error code specific to the MPI is displayed in the lower left corner of the GP
screen like "Host communication error (02:**:##)." ** stands for the error code
specific to the MPI. ## stands for the Node No. of the PLC on which the error has
occurred. Error Codes F0, F2 and F3 is not displayed the Node No. of the PLC

Error Codes
Error Code Description
F0 The cable is not connected. The PLC's power is OFF.
F1 Unable to locate target node.
F2 GP does not support 187500bps data transfer speed.
F3 A Timeout has occurred on the MPI network.
F4 Failed to connect to Target Node.
F5 Designated device or address does not exist, or other similar problem.

2-16-32 GP-PRO/PBIIIforWindowsVer.6.1 PLCConnectionManual


Appendix

A1 Maximum Number of Consecutive PLC Addresses


The following lists the maximum number of consecutive addresses that can be read
by each PLC. Refer to these tables to utilize Block Transfer.

SIMATIC S7-200 Series (MPI Direct)


Max No. of
Device
Consecutive Address
Input
Output
Internal
64 Words
Timer
Counter
Variable Memory

SIMATIC S7-300/400 Series (MPI Direct and MPI Connection via adapter)
Max No. of
Device
Consecutive Address
Input
Output
Internal
64 Words
Timer
Counter
Data Block

GP-PRO/PBIII for Windows Ver.6.0 PLC Connection Manual Appendix-1


Appendix

A2 Device Codes and Address Codes


Device codes and address codes are used to specify indirect addresses for E-tags
and K-tags.

SIMATIC S7-200 Series (MPI Direct)


Device Word Address Device Address Address Code
Input Node 1 IW0 ~ 9000 word address divided by 2
Node 2 IW0 ~ 9200 word address divided by 2
Node 3 IW0 ~ 9400 word address divided by 2
Node 4 IW0 ~ 9600 word address divided by 2
Output Node 1 QW0 ~ 8800 word address divided by 2
Node 2 QW0 ~ 8A00 word address divided by 2
Bit Device
Node 3 QW0 ~ 8C00 word address divided by 2
Node 4 QW0 ~ 8E00 word address divided by 2
Internal Node 1 MW00 ~ C800 word address divided by 2
Node 2 MW00 ~ CA00 word address divided by 2
Node 3 MW00 ~ CC00 word address divided by 2
Node 4 MW00 ~ CE00 word address divided by 2
Timer Node 1 T000 ~ 0400 word address
Node 2 T000 ~ 0600 word address
Node 3 T000 ~ 1000 word address
Node 4 T000 ~ 1200 word address
Counter Node 1 C00 ~ 0800 word address
Node 2 C00 ~ 0A00 word address
Word Device Node 3 C00 ~ 0C00 word address
Node 4 C00 ~ 0E00 word address
Var. Memory Node 1 VW0000 ~ D000 word address divided by 2
Node 2 VW0000 ~ D200 word address divided by 2
Node 3 VW0000 ~ D400 word address divided by 2
Node 4 VW0000 ~ D600 word address divided by 2
LS area LS0000 ~ 4000 word address

Appendix-2 GP-PRO/PBIII for Windows Ver.6.0 PLC Connection Manual


Appendix

SIMATIC S7-300/400 Series (MPI Direct and MPI Connection via adapter)
Device Word Address Device Address Address Code
Input Node 1 EW000 ~ 8000 word address divided by2
Node 2 EW000 ~ 8200 word address divided by2
Node 3 EW000 ~ 8400 word address divided by2
Node 4 EW000 ~ 8600 word address divided by2
Output Node 1 AW000 ~ 8800 word address divided by2
Node 2 AW000 ~ 8A00 word address divided by2
Bit Device
Node 3 AW000 ~ 8C00 word address divided by2
Node 4 ]AW000 ~ 8E00 word address divided by2
Internal Node 1 MW000 ~ 9000 word address divided by2
Node 2 MW000 ~ 9200 word address divided by2
Node 3 MW000 ~ 9400 word address divided by2
Node 4 MW000 ~ 9600 word address divided by2
Timer T000 ~ 6000 word address
Counter Z00 ~ 7000 word address
Data Block DB1W00000 ~ 0000 word address divided by2
Data Block DB2W00000 ~ 0200 word address divided by2
Data Block DB3W00000 ~ 0400 word address divided by2
: : : :
Data Block DB32W00000 ~ 3E00 word address divided by2
Data Block DB33W00000 ~ 4200 word address divided by2
Word Device : : : :
Data Block DB47W00000 ~ 5E00 word address divided by2
Data Block DB48W00000 ~ 6200 word address divided by2
: : : :
Data Block DB54W00000 ~ 6E00 word address divided by2
Data Block DB55W00000 ~ 7200 word address divided by2
: : : :
Data Block DB60W00000 ~ 7C00 word address divided by2
LS area LS0000 ~ 4000 word address

GP-PRO/PBIII for Windows Ver.6.0 PLC Connection Manual Appendix-3


Appendix

A3 Address Conversion Table

: When the selected conversion mode is [Word], both word and bit addresses
are converted. When the [Bit] is selected, only bit addresses are converted.
: When the selected conversion mode is [Word], only word addresses are con-
verted. When the [Bit] is selected, only bit addresses are converted.
: When the [Word] mode is selected, only word addresses are converted.
: When the [Bit] mode is selected, only bit addresses are converted.
Blank: Cannot be converted.

SIMATIC S7-200 Series (MPI Direct)


After Conversion
I Q M T C VW LS
I
Input
Q
Output
Before Conversion

M
Internal
T
Timer
C
Counter
VW
Variable memory
LS
System Area

SIMATIC S7-300/400 Series (MPI Direct and MPI Connection via adapter)
After Conversion
E A M T C DB LS
E
Input
A
Output
Before Conversion

M
Internal
T
Timer
Z
Counter
DB
Data Block
LS
System Area

Appendix-4 GP-PRO/PBIII for Windows Ver.6.0 PLC Connection Manual

You might also like