Un i v e r s a l M e a s u r i n g D e v i c e

NEW!
UMG 96 S

Little
Fieldbus Giant

Modbus / Profibus

Harmonics

Memory

Analogue outputs

Digital I/O
Modem Recorder Profibus Modbus PC I/O

Universal Measuring
Device
Application
The UMG 96 S is a universal measuring device, which is suitable for measuring, saving and supervision of electrical quantities in
low and medium voltage networks. The measurement is designed for one phase and three phase systems with neutral conductor, in
low voltage networks for the range L-N =85...300V; L-L=148...520V and in medium voltage for the range L-N=49...140V;
Application

L-L=85...242V.

One of the main features is the compact design (96x96mm) and the
measurement of harmonic current and voltage in each outer conductor.
In order to reach all features, about 15 other devices such as amperemeter,
voltmeter, voltmeter changeover, power meter (kW, kVA, kvar and cos phi),
pulse senders (real/reactive), transducers etc. would be necessary. Therefore
the costs for the project, installation, wiring and storage are much lower
compared to analogue instruments.

Possible applications are:

Supervision and control of electrical quantities in energy distributions

Transducer for PLC

Memory
Functions The basic model saves energy (total)
and the minimum and maximum values
The three phase electronic measuring system measures and digitizes the true without date and time.
RMS values of voltage and current in 50/60Hz networks. One random test
is carried out each second and 6 periods are scanned for each random test. Data memory
From those scanned values, the inserted microprocessor calculates the It is possible to save up to 160.000
electrical quantities. The scanning frequency is 2.5 kHz at 50 Hz and 3.0 kHz measured values or events in the data
at 60 Hz. Energy and minimum and maximum values, as well as the pro- memory (option). For saving the measu-
grammed data are saved in a none volatile memory (EEPROM). red values and events, 4 defined profiles
are at your disposal. Each profile can be
programmed separately or together with
other profiles.
memory

Versions of UMG 96 S
Memory profile 1
Type UMG 96 S UMG 96 S Mean value P in L1
Profibus Mean value P in L2
Mean value P in L3
Clock / memory Mean value Q Sum
Versions

2 digital inputs Mean value S Sum


Or
Memory profile 2
2 digital outputs
Mean value I in L1
Or Mean value I in L2
2 analogue outputs 4..20 mA Mean value I in L3
Interface RS 485 (Modbus) Mean value I in N
Interface RS 232 (Modbus)*1 Mean value cos phi Sum
Interface Profibus (DP V0)
Memory profile 3
= Existing = Not possible = Option Real energy (consump.)
*1 The interface RS 232 cannot be used along with the interface RS 485 simultaneously.
Reactive energy (ind.)
Baudrates:
Memory profile 4
Modbus: 9.6, 19.2, 38.4 kBit/s
Comparator 1-6
Profibus: 9.6, 19.2, 93.75, 187.5, 500 kBit/s and 1,5 MBit/s.

2
UMG 96 S
Measured values
Quantitiy Indication range Measuring range at L1 L2 L3 Sum Lowest Mean Peak Accuracy
Measured values

scale factor 1 value value*2 value

Current 0,01 .. 60,0 kA 0,01 .. 6 A +-0,5 % vMb


Current, N 0,01 .. 180,0 kA 0,01 .. 18 A +-1,5 % vMb
Voltage L-N 0,0 .. 34 kV 10 .. 300 V +-0,5 % vMb
Voltage L-L 0,0 .. 60 kV 10 .. 520 V +-1,0 % vMb
Frequency (U) 45,00 .. 65,00 Hz 45,00 .. 65,00 Hz +-0,1 % vMw
Real power per phase 0,1 W .. 99,9 MW 0,1 W .. 1,8 kW +-1,0 % vMb
Apparent power per phase 0,1 VA .. 99,9 MVA 0,1 VA .. 1,8 kVA +-1,0 % vMb
Reactive power per phase 0,1 var .. 99,9 Mvar 0,1 var .. 1,8 kvar ind. +-1,0 % vMb
Real power sum 1,0 W .. 99,9 MW 1,0 W .. 5,4 kW +-1,0 % vMb
Apparent power sum 1,0 VA .. 99,9 MVA 1,0 VA .. 5,4 kVA +-1,0 % vMb
Reactive power sum 1,0 var .. 99,9 Mvar 1,0 var .. 5,4 kvar ind. +-1,0 % vMb
cos phi 0,00 kap. .. 1,00 .. 0,00 ind. 0,00 kap. .. 1,00 .. 0,00 ind. +-1,0 Degree
Real energy, consumption 0 .. 999.999.999 kWh Class 1(5A) 2 (1A)
Reactive energy, inductive 0 .. 999.999.999 kvarh Class 1(5A) 2 (1A)
Working hour meter 0 .. 999.999.999 h +-2 min. per day

Total harmonic content THD U,I 0,1 .. 100 % +-2 % vMb


Partial harmonic content I, 1-15*3 0,01 .. 60 kA 1,0 mA .. 6000 mA +-2 % vMb
Partial harmonic content U, 1-15*3 0,0 .. 34 kV 0,1 V .. 300,0 V +-2 % vMb

Omr: of measuring range, Omv: of measured value


*2 Integration over time: 5, 10, 30, 60, 300, 480 and 900 seconds
*3 Only odd partial harmonics

Display examples

Rotating field indicator Peak value THD L3

Programming of current transformer Real energy, consumption


Display examples

Measured value display and display rotation


The measured values are calculated once per second and can be retrieved in measured value displays.
Two methods are available for retrieving the measured data:
The display rotation of selected measured value displays with a changing time of 060 seconds.
The selection of a measured value display via the key from a selected profile.
Four display profiles are available and a specific profile can be created and transmitted to the instrument via PC.

LCD Contrast
The LCD contrast of the LCD display can be adapted by the user. To reach the best possible contrast over the full range of operating
temperature, an automatical setting of the contrast is carried out caused by the measured inner temperature.

Working hour meter


The working hour meter measures the time (solution 0.1 hour), after the device is put into service, and cannot be reset. Furthermore, up
to 6 total running times can be programmed via the six comparators, and detected as total running time for the comparator. Measured values,
limits and operands (>=<) serve as parameters. The total running times can be reset separately.

3
Digital outputs
The digital outputs can be used as pulse outputs (max. 10Hz) for real and reactive energy or as switching outputs. The digital out-
puts can be programmed for supervision of measured data. Up to three comparators can be assigned to each digital output.

The result of the comparators can be overwritten externally via Modbus RTU. The switching outputs can be set via Profibus-
Remote as well.
Digital outputs

Example pulse output Example switching output


External 230V AC External 230V AC
auxiliary voltage auxiliary voltage

24V DC 24V DC
UMG 96 S + - + -
Basic PCB
11
Output 1
Pulse output
Comparator group 1

12
Switching output
1,5k

11

12

Output 2
Comparator group 2

Pulse output 1,5k


13
Switching output 13

RXD
RS485 (MODBUS RTU)
14 Basic device without options
Interface TXD
15
interface
Serial

Comparators Comparator group 1


Tafel
Comparators

Comparator A Comparator B Comparator C


Two comparator groups with 3 compara- Measured value (addr.015) Measured value (addr.020) Measured value (addr.025)
tors (A,B and C) each are available in the Limit (addr.013) Limit (addr.018) Limit (addr.023)
Minimum On time (addr.016) Minimum On time (addr.021) Minimum On time (addr.026)
UMG 96 S. Those compare a measured Run up time (addr. 064) Run up time (addr. 065) Run up time (addr. 066)
value by an operand >=< and the result can Operand ">=", "<" (addr.017) Operand ">=", "<" (addr.022) Operand ">=", "<" (addr.027)
be written into the event memory as event /
total running time. Result (addr.386) Result (addr.387) Result (addr.388)

The result of the comparator can be com- Event memory Event memory Event memory
bined by logic combinations AND or OR (addr.500) (addr.500) (addr.500)
with other comparators. It can be inverted
and given as comparator result at the swit-
ching outputs, or read via Modbus RTU. Total running time Total running time Total running time
(addr.395) (addr.397) (addr.399)

Combine results of comparators A, B and C


- Combine results of the comparators A,B and C AND or OR (addr.043).
- Invert result (addr.044).

Result of combination (addr.389)

Switching output 1 (addr.002 = 1)

Limit supervision 12 11

4
UMG 96 S
Analogue outputs
For the version with analogue outputs, the digital outputs can be configured either as analogue outputs, pulse outputs or switching out-
puts. For each analogue output, the following parameters are available: Measured values, scale starting value (4mA) and scale end value
Analogue outputs

(20mA).

External 230V AC External 230V AC


auxiliary voltage auxiliary voltage

24V DC 24V DC
UMG 96 S + - + -
Basic PCB
Output 1
+ + L+
Additional PCB 1 11 11
Pulse output

Max. 360 Ohm


Comparator group 1
M
Switching output 12 12
Analogue output 1
Measured value (047) Analogue output
Scale starting value, 4mA (050)
Scale end value, 20mA (048) + + M+

Analogue inputs
M-

Analogue-
Output 2 writer M+
Pulse output
Comparator group 2

M-

Analogue output 2 Switching output 13 13


Measured value (052)
SPS
Analogue output
Scale starting value, 4mA (054)
Scale end value, 20mA (053)

RXD
Clock with battery 14
RS485 (MODBUS RTU)
Interface TXD
15 Basic device with options:
interface
Serial

Analogue outputs
Event memory TXD
Clock / memory
Sleeve

RS232 (MODBUS RTU)


RJ11

RXD
Interface GND
RS 232
Digital inputs / Profibus

Digital inputs / Profibus External


auxiliary voltage
230V AC

24V DC
At UMG 96 S Profibus, the two digital UMG 96 S + -

outputs can be used as pulse output, swit- Basic PCB


Input/Output 1
ching output, , Profibus-Remote-switching Additional PCB
Pulse output
11
Comparator group 1

output or digital input. The use as Switching output Alarm message via
12 Profibus-Remote
Profibus-Remote-output or digital input Digital input 1 Digital input
Profibus-Remote
(e.g. for alarms, changeover, signal trans-
mission etc.) is up to the user.
Input/Output 2
For UMG 96 S Profibus very many mea-
Comparator group 2

Pulse output
Condition report via
sured values are available for further pro- Switching output digital input
13
cessing. To keep the number data, trans- Digital input 2 Digital input
Profibus-Remote
mitted via Profibus as small as possible, the
measured data are available in 14 profiles in
integer format and floating point format. RS485 (MODBUS RTU)
RXD
14
As Baud rates are possible: 9.6, 19.2, Interface TXD
15
Profibus DP
93.75, 187.5, 500 kBit/s and 1,5 MBit/s.
interface
Serial

- A B + TXD
Sleeve

RS232 (MODBUS RTU)


RJ11

RXD
Interface GND
5 8 3 6
DSUB 9

SPS
Basic device with options:
Profibus
Digital inputs

5
Example analogue output 4 20 mA
All measured values except real and reactive energy
can be given out at the analogue outputs.

Example Modem communication ...31 devices per modem

Software

RS232 RS485
Interface

Example PLC communication ...31 devices (expandable up to 255 devices by a starrepeater)

Profibus DP VO

RS485

Example PLC communication ...31 devices (expandable up to 255 devices by a starrepeater)

Modbus RTU

RS485

Example PC communication...31 devices (expandable up to 255 devices by a starrepeater)


Software

RS232 RS485

Example Com Server (TCP/IP) 31 devices per Com Server


for local network

Software

RS485

Ethernet
(TCP/IP)
100
BaseT

RS485

Please note: The Com Server is suitable for a


local network only

Example fibre optic network ...31 devices per line

Software

RS232 RS485 RS485

LWL

6
UMG 96 S

Technical data
Overvoltage class: CAT III
Pollution degree: 2
Operating temperature: -10C .. +55C
Technical data

Storage temperature: -20C .. +70C


Humidity: 15% to 95% without dew
Mounting position: Random

Measuring and auxiliary voltage: L-N: 85 .. 300V AC, L-L: 148 .. 520V AC
Frequency: 45 - 65Hz
Current measurement: .. /5A (../1A)
Minimum working current: 5mA
Switching outputs: NPN Transistor, Frequency: max. 10Hz,
max. 50mA, 5 .. 24V DC (max. 27V DC)
Switching inputs: 20 .. 27V DC, max. 5mA
Analogue outputs: 4 .. 20mA 8Bit, Load: max. 300 Ohm, 20 .. 27V DC

Protection front: IP 50 according to IEC 60529


Protection front with seal: IP 65 according to IEC 60529
Protection back side: IP 20 according to IEC 60529

max. 6

Cut out: 92x92mm


96
90

DSUB-9

42 6
49

UMG 96 S Profibus Profibus DP (V0)


UMG 96 S
Modbus RTU
RS485

Voltage Current
measurement measurement
See type plate 0,01 .. 5A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RJ11 DSUB-9 11 12 13 14 15

L1 L2 L3 N 1k 1l 2k 2l 3k 3l
RS485 bus cable

2 .. 10A
Profibus
RS232

Switching outputs
Switching inputs

S1 Profibus
S2
L1 k l
Consumer

L2 ../5(1)A k l
L3 ../5(1)A k l SPS
PEN ../5(1)A + DC - + DC -

UMG 96 S Profibus with switching inputs, RS 232 and Profibus UMG 96 S without options