Janitza UMG96S
Janitza UMG96S
Janitza UMG96S
NEW!
UMG 96 S
Little
Fieldbus Giant
Modbus / Profibus
Harmonics
Memory
Analogue outputs
Digital I/O
Modem Recorder Profibus Modbus PC I/O
Universal Measuring
Device
Application
The UMG 96 S is a universal measuring device, which is suitable for measuring, saving and supervision of electrical quantities in
low and medium voltage networks. The measurement is designed for one phase and three phase systems with neutral conductor, in
low voltage networks for the range L-N =85...300V; L-L=148...520V and in medium voltage for the range L-N=49...140V;
Application
L-L=85...242V.
One of the main features is the compact design (96x96mm) and the
measurement of harmonic current and voltage in each outer conductor.
In order to reach all features, about 15 other devices such as amperemeter,
voltmeter, voltmeter changeover, power meter (kW, kVA, kvar and cos phi),
pulse senders (real/reactive), transducers etc. would be necessary. Therefore
the costs for the project, installation, wiring and storage are much lower
compared to analogue instruments.
Memory
Functions The basic model saves energy (total)
and the minimum and maximum values
The three phase electronic measuring system measures and digitizes the true without date and time.
RMS values of voltage and current in 50/60Hz networks. One random test
is carried out each second and 6 periods are scanned for each random test. Data memory
From those scanned values, the inserted microprocessor calculates the It is possible to save up to 160.000
electrical quantities. The scanning frequency is 2.5 kHz at 50 Hz and 3.0 kHz measured values or events in the data
at 60 Hz. Energy and minimum and maximum values, as well as the pro- memory (option). For saving the measu-
grammed data are saved in a none volatile memory (EEPROM). red values and events, 4 defined profiles
are at your disposal. Each profile can be
programmed separately or together with
other profiles.
memory
Versions of UMG 96 S
Memory profile 1
Type UMG 96 S UMG 96 S Mean value P in L1
Profibus Mean value P in L2
Mean value P in L3
Clock / memory Mean value Q Sum
Versions
2
UMG 96 S
Measured values
Quantitiy Indication range Measuring range at L1 L2 L3 Sum Lowest Mean Peak Accuracy
Measured values
Display examples
LCD Contrast
The LCD contrast of the LCD display can be adapted by the user. To reach the best possible contrast over the full range of operating
temperature, an automatical setting of the contrast is carried out caused by the measured inner temperature.
3
Digital outputs
The digital outputs can be used as pulse outputs (max. 10Hz) for real and reactive energy or as switching outputs. The digital out-
puts can be programmed for supervision of measured data. Up to three comparators can be assigned to each digital output.
The result of the comparators can be overwritten externally via Modbus RTU. The switching outputs can be set via Profibus-
Remote as well.
Digital outputs
24V DC 24V DC
UMG 96 S + - + -
Basic PCB
11
Output 1
Pulse output
Comparator group 1
12
Switching output
1,5k
11
12
Output 2
Comparator group 2
RXD
RS485 (MODBUS RTU)
14 Basic device without options
Interface TXD
15
interface
Serial
The result of the comparator can be com- Event memory Event memory Event memory
bined by logic combinations AND or OR (addr.500) (addr.500) (addr.500)
with other comparators. It can be inverted
and given as comparator result at the swit-
ching outputs, or read via Modbus RTU. Total running time Total running time Total running time
(addr.395) (addr.397) (addr.399)
Limit supervision 12 11
4
UMG 96 S
Analogue outputs
For the version with analogue outputs, the digital outputs can be configured either as analogue outputs, pulse outputs or switching out-
puts. For each analogue output, the following parameters are available: Measured values, scale starting value (4mA) and scale end value
Analogue outputs
(20mA).
24V DC 24V DC
UMG 96 S + - + -
Basic PCB
Output 1
+ + L+
Additional PCB 1 11 11
Pulse output
Analogue inputs
M-
Analogue-
Output 2 writer M+
Pulse output
Comparator group 2
M-
RXD
Clock with battery 14
RS485 (MODBUS RTU)
Interface TXD
15 Basic device with options:
interface
Serial
Analogue outputs
Event memory TXD
Clock / memory
Sleeve
RXD
Interface GND
RS 232
Digital inputs / Profibus
24V DC
At UMG 96 S Profibus, the two digital UMG 96 S + -
output or digital input. The use as Switching output Alarm message via
12 Profibus-Remote
Profibus-Remote-output or digital input Digital input 1 Digital input
Profibus-Remote
(e.g. for alarms, changeover, signal trans-
mission etc.) is up to the user.
Input/Output 2
For UMG 96 S Profibus very many mea-
Comparator group 2
Pulse output
Condition report via
sured values are available for further pro- Switching output digital input
13
cessing. To keep the number data, trans- Digital input 2 Digital input
Profibus-Remote
mitted via Profibus as small as possible, the
measured data are available in 14 profiles in
integer format and floating point format. RS485 (MODBUS RTU)
RXD
14
As Baud rates are possible: 9.6, 19.2, Interface TXD
15
Profibus DP
93.75, 187.5, 500 kBit/s and 1,5 MBit/s.
interface
Serial
- A B + TXD
Sleeve
RXD
Interface GND
5 8 3 6
DSUB 9
SPS
Basic device with options:
Profibus
Digital inputs
5
Example analogue output 4 20 mA
All measured values except real and reactive energy
can be given out at the analogue outputs.
Software
RS232 RS485
Interface
Profibus DP VO
RS485
Modbus RTU
RS485
RS232 RS485
Software
RS485
Ethernet
(TCP/IP)
100
BaseT
RS485
Software
LWL
6
UMG 96 S
Technical data
Overvoltage class: CAT III
Pollution degree: 2
Operating temperature: -10C .. +55C
Technical data
Measuring and auxiliary voltage: L-N: 85 .. 300V AC, L-L: 148 .. 520V AC
Frequency: 45 - 65Hz
Current measurement: .. /5A (../1A)
Minimum working current: 5mA
Switching outputs: NPN Transistor, Frequency: max. 10Hz,
max. 50mA, 5 .. 24V DC (max. 27V DC)
Switching inputs: 20 .. 27V DC, max. 5mA
Analogue outputs: 4 .. 20mA 8Bit, Load: max. 300 Ohm, 20 .. 27V DC
max. 6
DSUB-9
42 6
49
Voltage Current
measurement measurement
See type plate 0,01 .. 5A
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 RJ11 DSUB-9 11 12 13 14 15
L1 L2 L3 N 1k 1l 2k 2l 3k 3l
RS485 bus cable
2 .. 10A
Profibus
RS232
Switching outputs
Switching inputs
S1 Profibus
S2
L1 k l
Consumer
L2 ../5(1)A k l
L3 ../5(1)A k l SPS
PEN ../5(1)A + DC - + DC -
UMG 96 S Profibus with switching inputs, RS 232 and Profibus UMG 96 S without options
7
Janitza electronics GmbH