Signaling Line Circuit
Signaling Line Circuit
Signaling Line Circuit
The ADT
SLC
Signaling Line Circuit
Manual
Document 51348
8/29/00 Revision: A
PN 51348:A ECN 00-394
While a fire alarm system may lower insurance
Fire Alarm System Limitations rates, it is not a substitute for fire insurance!
An automatic fire alarm system–typically made up of smoke Heat detectors do not sense particles of combustion and
detectors, heat detectors, manual pull stations, audible warn- alarm only when heat on their sensors increases at a prede-
ing devices, and a fire alarm control with remote notification termined rate or reaches a predetermined level. Rate-of-rise
capability–can provide early warning of a developing fire. heat detectors may be subject to reduced sensitivity over time.
Such a system, however, does not assure protection against For this reason, the rate-of-rise feature of each detector
property damage or loss of life resulting from a fire. should be tested at least once per year by a qualified fire pro-
The Manufacturer recommends that smoke and/or heat detec- tection specialist. Heat detectors are designed to protect
tors be located throughout a protected premise following the property, not life.
recommendations of the current edition of the National Fire IMPORTANT! Smoke detectors must be installed in the
Protection Association Standard 72 (NFPA 72), same room as the control panel and in rooms used by the sys-
manufacturer's recommendations, State and local codes, and tem for the connection of alarm transmission wiring, communi-
the recommendations contained in the Guide for Proper Use cations, signaling, and/or power. If detectors are not so lo-
of System Smoke Detectors, which is made available at no cated, a developing fire may damage the alarm system, crip-
charge to all installing dealers. A study by the Federal Emer- pling its ability to report a fire.
gency Management Agency (an agency of the United States Audible warning devices such as bells may not alert people
government) indicated that smoke detectors may not go off in if these devices are located on the other side of closed or
as many as 35% of all fires. While fire alarm systems are de- partly open doors or are located on another floor of a building.
signed to provide early warning against fire, they do not guar- Any warning device may fail to alert people with a disability or
antee warning or protection against fire. A fire alarm system those who have recently consumed drugs, alcohol or medica-
may not provide timely or adequate warning, or simply may not tion. Please note that:
function, for a variety of reasons:
• Strobes can, under certain circumstances, cause seizures
Smoke detectors may not sense fire where smoke cannot in people with conditions such as epilepsy.
reach the detectors such as in chimneys, in or behind walls, on
• Studies have shown that certain people, even when they
roofs, or on the other side of closed doors. Smoke detectors
hear a fire alarm signal, do not respond or comprehend the
also may not sense a fire on another level or floor of a build-
meaning of the signal. It is the property owner's responsibil-
ing. A second-floor detector, for example, may not sense a
ity to conduct fire drills and other training exercise to make
first-floor or basement fire.
people aware of fire alarm signals and instruct them on the
Particles of combustion or "smoke" from a developing fire proper reaction to alarm signals.
may not reach the sensing chambers of smoke detectors be-
• In rare instances, the sounding of a warning device can
cause:
cause temporary or permanent hearing loss.
• Barriers such as closed or partially closed doors, walls, or
A fire alarm system will not operate without any electrical
chimneys may inhibit particle or smoke flow.
power. If AC power fails, the system will operate from standby
• Smoke particles may become "cold," stratify, and not reach batteries only for a specified time and only if the batteries
the ceiling or upper walls where detectors are located. have been properly maintained and replaced regularly.
• Smoke particles may be blown away from detectors by air Equipment used in the system may not be technically com-
outlets. patible with the control. It is essential to use only equipment
• Smoke detectors may be drawn into air returns before listed for service with your control panel.
reaching the detector. Telephone lines needed to transmit alarm signals from a
The amount of "smoke" present may be insufficient to alarm premise to a central monitoring station may be out of service
smoke detectors. Smoke detectors are designed to alarm at or temporarily disabled. For added protection against tele-
various levels of smoke density. If such density levels are not phone line failure, backup radio transmission systems are rec-
created by a developing fire at the location of detectors, the ommended.
detectors will not go into alarm. The most common cause of fire alarm malfunction is inade-
Smoke detectors, even when working properly, have sensing quate maintenance. To keep the entire fire alarm system in
limitations. Detectors that have photoelectronic sensing excellent working order, ongoing maintenance is required per
chambers tend to detect smoldering fires better than flaming the manufacturer's recommendations, and UL and NFPA stan-
fires, which have little visible smoke. Detectors that have ion- dards. At a minimum, the requirements of Chapter 7 of NFPA
izing-type sensing chambers tend to detect fast-flaming fires 72 shall be followed. Environments with large amounts of
better than smoldering fires. Because fires develop in differ- dust, dirt or high air velocity require more frequent mainte-
ent ways and are often unpredictable in their growth, neither nance. A maintenance agreement should be arranged
type of detector is necessarily best and a given type of detec- through the local manufacturer's representative. Maintenance
tor may not provide adequate warning of a fire. should be scheduled monthly or as required by National and/
Smoke detectors cannot be expected to provide adequate or local fire codes and should be performed by authorized pro-
warning of fires caused by arson, children playing with fessional fire alarm installers only. Adequate written records
matches (especially in bedrooms), smoking in bed, and violent of all inspections should be kept.
explosions (caused by escaping gas, improper storage of
flammable materials, etc.).
Precau-Lg.p65 01/18/2000
Installation Precautions Adherence to the following will aid in problem-free
installation with long-term reliability:
WARNING - Several different sources of power can be con- Like all solid state electronic devices, this system may
nected to the fire alarm control panel. Disconnect all sources operate erratically or can be damaged when subjected to light-
of power before servicing. Control unit and associated equip- ning-induced transients. Although no system is completely
ment may be damaged by removing and/or inserting cards, immune from lightning transients and interferences, proper
modules, or interconnecting cables while the unit is energized. grounding will reduce susceptibility. Overhead or outside
Do not attempt to install, service, or operate this unit until this aerial wiring is not recommended, due to an increased sus-
manual is read and understood. ceptibility to nearby lightning strikes. Consult with the Techni-
CAUTION - System Reacceptance Test after Software cal Services Department if any problems are anticipated or
Changes. To ensure proper system operation, this product encountered.
must be tested in accordance with NFPA 72 Chapter 7 after Disconnect AC power and batteries prior to removing or in-
any programming operation or change in site-specific soft- serting circuit boards. Failure to do so can damage circuits.
ware. Reacceptance testing is required after any change, ad- Remove all electronic assemblies prior to any drilling, filing,
dition or deletion of system components, or after any modifica- reaming, or punching of the enclosure. When possible, make
tion, repair or adjustment to system hardware or wiring. all cable entries from the sides or rear. Before making modifi-
All components, circuits, system operations, or software func- cations, verify that they will not interfere with battery, trans-
tions known to be affected by a change must be 100% tested. former, and printed circuit board location.
In addition, to ensure that other operations are not inadvert- Do not tighten screw terminals more than 9 in-lbs.
ently affected, at least 10% of initiating devices that are not Over-tightening may damage threads, resulting in reduced
directly affected by the change, up to a maximum of 50 de- terminal contact pressure and difficulty with screw terminal
vices, must also be tested and proper system operation veri- removal.
fied.
Though designed to last many years, system components
This system meets NFPA requirements for operation at can fail at any time. This system contains static-sensitive
0-49° C/32-120° F and at a relative humidity of 85% RH (non- components. Always ground yourself with a proper wrist strap
condensing) at 30° C/86° F. However, the useful life of the before handling any circuits so that static charges are re-
system's standby batteries and the electronic components moved from the body. Use static-suppressive packaging
may be adversely affected by extreme temperature ranges to protect electronic assemblies removed from the unit.
and humidity. Therefore, it is recommended that this system
Follow the instructions in the installation, operating, and
and all peripherals be installed in an environment with a nomi-
programming manuals. These instructions must be followed
nal room temperature of 15-27° C/60-80° F.
to avoid damage to the control panel and associated
Verify that wire sizes are adequate for all initiating and equipment. FACP operation and reliability depend upon
indicating device loops. Most devices cannot tolerate more proper installation by authorized personnel.
than a 10% I.R. drop from the specified device voltage.
FCC Warning
WARNING: This equipment generates, uses, and can Canadian Requirements
radiate radio frequency energy and if not installed and This digital apparatus does not exceed the Class A
used in accordance with the instruction manual, may limits for radiation noise emissions from digital
cause interference to radio communications. It has apparatus set out in the Radio Interference Regulations
been tested and found to comply with the limits for class of the Canadian Department of Communications.
A computing device pursuant to Subpart B of Part 15 of
Le present appareil numerique n'emet pas de bruits
FCC Rules, which is designed to provide reasonable
radioelectriques depassant les limites applicables aux
protection against such interference when operated in a
appareils numeriques de la classe A prescrites dans le
commercial environment. Operation of this equipment in
Reglement sur le brouillage radioelectrique edicte par le
a residential area is likely to cause interference, in which
ministere des Communications du Canada.
case the user will be required to correct the interference
at his own expense.
Precau-Lg.p65 01/18/2000
This Page Intentionally Left Blank
Table of Contents
Introduction
Scope............................................................................................................................. 9
Overview ...................................................................................................................... 9
Devices .......................................................................................................................... 9
Isolator Modules .................................................................................................... 9
Monitor Modules.................................................................................................... 9
Control Modules .................................................................................................... 9
Relay Modules ....................................................................................................... 9
Transponders........................................................................................................ 10
Plug-in Detector Bases......................................................................................... 10
Intelligent Detectors ............................................................................................. 10
Manual Pull Stations ............................................................................................ 10
Reference Documentation......................................................................................... 11
SLC Capacity............................................................................................................. 12
SLC Performance...................................................................................................... 12
LED Operation .......................................................................................................... 12
Surge Suppression ..................................................................................................... 12
Wiring Requirements
Overview .................................................................................................................... 13
Two-Wire SLC - Style 4 (Class B) ........................................................................... 13
Measuring Loop Resistance ................................................................................. 13
Measuring Total Wire Length.............................................................................. 13
Four-Wire SLC Style 6 & 7 (Class A) ..................................................................... 14
Measuring Loop Resistance ................................................................................. 14
Measuring Total Wire Length.............................................................................. 14
Monitor Modules
Description ................................................................................................................. 25
M300MADT Monitor Module ............................................................................. 25
M300DADT Dual Monitor Module..................................................................... 25
M302MADT Monitor Module ............................................................................. 25
M301MADT Monitor Module ............................................................................. 25
Installation.................................................................................................................. 26
Setting an SLC address for a Module................................................................... 26
M300MADT Wiring Diagrams ................................................................................ 27
Wiring a NFPA Style B IDC with an M300MADT............................................ 27
Wiring a NFPA Style D IDC with an M300MADT ........................................... 28
M300DADT Wiring Diagrams ................................................................................. 29
Wiring a NFPA Style B IDC with an M300DADT ............................................. 29
M302MADT Wiring Diagrams ................................................................................ 30
Wiring a NFPA Style B IDC with an M302MADT............................................. 30
Wiring a NFPA Style D IDC with an M302MADT ............................................ 31
Control Modules
Description ................................................................................................................. 33
Installation.................................................................................................................. 33
Setting an SLC address for an M300CADT Module ........................................... 33
Wiring a Notification Appliance Circuit (NAC) with an M300CADT ............... 33
Wiring an M300CADT Module ............................................................................... 34
Wiring a Style Y NAC (Two-Wire).................................................................... 34
Wiring a Style Z NAC (Four-Wire) ..................................................................... 35
Relay Module
Description ................................................................................................................. 37
Installation.................................................................................................................. 37
Setting an SLC address for an M300RADT Module ........................................... 37
Wiring an M300RADT Module (Form-C Relay) ................................................ 37
Unimode 300/400
This document also provides basic information that applies to ADT SLC loops in general, such as the
branch resistance measurements.
Additional information about each control panel and the modules and detectors referenced in this
document can be found in the respective installation manual as listed in Table 1, “Reference
Documentation,” on page 11.
Overview
Communication between the control panel and intelligent and addressable initiating, monitor, and
control devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the
requirements of NFPA Style 4, Style 6, or Style 7.
Devices
Isolator Modules
Isolator Modules permit a zone of detectors and modules to be fault isolated from the remainder of the
SLC loop, allowing critical components to function in the event of a circuit fault. Isolator modules are
required to meet the requirements of an NFPA Style 7 circuit.
Monitor Modules
These addressable modules allow the control panel to monitor entire circuits of conventional alarm
initiating devices, such as manual pull stations, smoke detectors, heat detectors, waterflow and
supervisory devices.
Control Modules
Through these addressable modules, the control panel can selectively activate Notification Appliance
Circuits (NAC).
Relay Modules
This addressable module provides the control panel with a dry-contact output for activating a variety of
auxiliary devices.
Transponders
ADT-XP5-M - Supervises five Class-B addressable Initiating Device Circuits which monitor normally
open contact initiating devices.
ADT-XP5-C - Acts as a NAC or a speaker/telephone circuit (Class B only) or a Form-C relay.
XP Series - (XPP-1, XPC-8, XPM-8 & XPZ-8) Provides the FACP with an efficient multiplex
subsystem capability. It communicates with the FACP and functions as a data-gathering panel for alarm
Initiating Device Circuits (IDC) and as a remote switching center for Notification Appliance Circuits
(NAC), telephone circuits or relays.
For information on connecting these transponders to the SLC, refer to the ADT XP5 Series Manual or
the ADT XP Transponder Manual.
Intelligent Detectors
1351ADT - Analog, addressable, low profile intelligent smoke detector that incorporates an ionization
sensing chamber. Designed to provide open area protection.
2351ADT - Same as 1351ADT, but uses a photoelectric sensing chamber. The 2351TADT adds thermal
sensors that will alarm at a fixed temperature of 135° F. Designed to provide open area protection.
5351ADT - Intelligent thermistor sensing circuit for fast response. Designed to provide open area
protection with 50 foot spacing capability. The 5351RADT incorporates a thermal rate of rise of 15°F
(9.4°C).
DH300PADT - Photoelectric smoke detector designed to detect smoke in an air duct. Model
DH300PRADT contains housing and relay.
Reference Documentation
The table below gives a list of document sources containing additional information regarding a
Signaling Line Circuit:
SLC Capacity
The individual control panel determines the capacity of devices that can be incorporated into an SLC.
See the specific installation manual for this information.
SLC Performance
SLC performance depends on the type of circuit: Style 4, Style 6, or Style 7.
Note: SLC operation meeting Style 7 requirements isolates each device on the SLC from faults that may occur on the
SLC.
Wiring style requirements are determined by national and local codes. Consult with the Authority
Having Jurisdiction before wiring the SLC.
The table below lists the trouble conditions that result when a fault exists on an SLC.
• Trouble indicates a trouble signal will be generated at the control panel during the abnormal
condition.
• Alarm/Trouble indicates an alarm signal can be transmitted to the control panel during the
abnormal condition.
LED Operation
The table below lists the LED operation on the various devices of an SLC.
LED Indication
Surge Suppression
At least one secondary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building. For detailed information refer to "Appendix B: Surge Suppression" on page 47.
Wire size should be no smaller than 18 AWG (1.0 mm2) and no larger than 12 AWG (3.25 mm2) wire.
Short Point
SLC Out
SLC-meas1.cdr
Branch
SLC Terminal
Block
B+ B–
SLC Out
SLC-meas3.cdr
Short Point
SLC Return
SLC Terminal
Block
B+ A+ B– A–
No-Conduit
Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Connect the shield
drain wire to the connector screw as shown below. Do not allow the shield drain wire to enter the
system cabinet.
Shield Drain Wire Cabinet
Foil
SLC-swterm1.cdr
Figure 5 Shield Termination – No Conduit
Full-Conduit
Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire through
the conduit, into the control box. The shield drain wire must be connected to the “reference” or “shield”
terminal on the SLC terminal block, or connected to the negative side of the loop if there is no
“reference” or “shield” terminal on the SLC terminal block. Do not let the shield drain wire or the shield
foil touch the system cabinet or be connected to earth ground at any point.
Shield Drain Wire
Cabinet
Example at right illustrates Foil
shield drain wire connection
SLC-swterm2.cdr
Cabinet
Foil
+
Example at right illustrates
shield drain wire connection Conduit
Shield2.cdr
Partial-Conduit
If the length of conduit from the control panel cabinet exceeds 20 feet (6.1 meters), terminate the shield
as shown. If using a metal box, you must use a metal conduit.
Connect the shielded wire to the junction box by using a proper connector. Scrape the paint on the
cabinet to bare metal to provide a good electrical connection. Connect the metal conduit between the
junction box and the cabinet by using the proper connectors.
Feed the twisted-pair wire into the junction box, through the conduit, into the cabinet box. Within the
junction box, connect the appropriate wires together using wire nuts. Connect the shield drain wire to
the junction box, at the end of the conduit run, as shown below.
Do not allow the shield drain wire to enter the system cabinet or the conduit.
Foil Shield Drain Wire
Cabinet
SLC-swterm3.cdr
Figure 7 Shield Termination – Partial Conduit
Floating Shield
Where shielding of the SLC is not recommended (when using the LIB-200A or LIB-400):
1. The SLC is less than 3000 feet (914.4 meters).
2. The shield is divided into floating segments of less than 1000 feet (304.8 meters).
To divide the shield wire into floating segments, cut shield even with jacket and tape as shown:
Tape
Cabinet
SLC-swterm4.cdr
Addressable Detector
Addressable Module
T-tapped Circuits
B+ B–
SLC-style4.cdr
Control Panel
SLC
Addressable Detector
SLC Out
Addressable Module
SLC Return
B+ B– A– A+
SLC-style6.cdr
Control Panel
SLC
IN
IN
OUT
OUT
SLC-isowire.cdr
SLC Out X
OUT IN OUT IN
4 F E D 3
SLC Return
SLC-isowork.cdr
Control Panel Isolator Base Non-Isolating Device
Note: Refer to Figure 30 for an illustration of “IN” and “OUT” isolator base wiring.
1
2 M500X
3 Two-wire Addressable
4 Detector
Isolated Branch
1
2 M500X
3
4
Isolated Branch
B– B+
SLC-style4iso.cdr
Control Panel
SLC
1 3 1 3
M500X M500X
2 4 2 4
Section B
Two-wire
Addressable Section C
Detector
Addressable
Pull Station
Section A
3 4 2 1
M500X M500X
1 2 SLC Out 4 3
SLC Return
1 3
M500X
2 4
3 4 Two-wire Isolator 2 1
M500X Detector Base
M500X
1 2
4 3
Two-wire
Addressable
Addressable
Pull Station
Detector
2 1
3 4
M500X M500X
1 2 4 3
Notes
Rotary Switches
IDC Return + 9 0
6 7 8 910
5
IDC Return - 8
4
3
11
12 1 SLC-
2 13
1 0 1 51 4
IDC Out + 7 TENS 2 SLC+
6789
5
IDC Out - 6 4
3 24 VDC - M302MADT only)
3
2
5 10
4 24 VDC + (M302MADT only)
O NES
LO
LOOOPP A
ADDD
DRRES
ESSS
FMM-1.cdr
Installation
When installing any of the modules, note the following:
3. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps @ 24 VDC
(nominal).
4. The IDC provides the following services (do not mix):
• Fire alarm service
• Automatic and manual waterflow alarm service with normally open contact devices
• Sprinkler supervisory service with normally open contact devices
• Security service
6 7 8 9 10
Rotary Switches 5
4 11
3 12
2 13
1 0 1514
TENS
6789
5
4
3
SLC-setadd.cdr
2
10
ONES
Figure 18 Setting SLC Address on Module
24 VDC Four-wire
Detector Base
24 VDC Power
Filtered, Regulated, Resettable
Manual pull
station 3.9K ELR
(supplied
with module)
SLC
M300MADT
Heat
detector
9 6 7 8 9 10 0
5 10
4 11
8 33 12
12
13
1
2
1 0 1514
14
7 TENS 2
IDC Out 6 7 88 9
5
6 44
3 3
2
11 0
5 O NES 4 SLC-idcB1.cdr
LO
LOOP
OP AD
ADDR
DRES
ESSS
24 VDC Four-wire
Detector Base
24 VDC Power
Filtered, Regulated, Resettable
Manual pull
station
SLC
M300MADT
Heat
detector
9 6 7 8 9 10 0
IDC Return 5 10
11
4
8 33 12
12
13
1
2
1 0 1514
14
7 TENS 2
6 7 88 9
IDC Out 5
6 44
3 3
2
11 0
5 O NES 4
SLC-idcD1.cdr
LO
LOOP
OP AD
ADDR
DRES
ESSS
Manual Pull
Station
47K ELR
SLC
M300DADT
Circuit H
9 6 7 8 9 10 0
5 10
4 11
8 3 12
12
13
1
2
1 0 1514
7 TENS 2
6 7 88 9
5
6 4
3
3
2
11 0
Circuit L 5 ONES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
Heat
Detector
47K ELR
SLC-idcB3.cdr
Two-wire
smoke
3.9K ELR
detectors
(supplied with module)
SLC
M302MADT
9 6 7 8 9 10 0
5
4 11
11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
IDC Out 5
6 7 8 99
6 4
3 3
22
1 00
5 O NES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
SLC-idcB2.cdr
3.9K ELR
Two-wire
(supplied with module)
smoke
detectors
SLC
M302MADT
IDC Return
9 6 7 8 9 10 0
5
4 11
11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
IDC Out 6 7 8 99
5
6 4
3 3
22
1 00
5 O NES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
SLC-idcD2.cdr
24 VDC Resettable power
Figure 23 Typical Style D IDC Wiring with M302MADT
Notes
Installation
This resistor
Label must be
removed when
using the
The label must be cut M300CADT on
and removed from an FFT-7 or
over the recessed area FFT-7S
to access the resistor. telephone
circuit.
Remove the resistor,
then place a piece of
FMM-1back.cdr
M300CADT
SLC-nacY.cdr
24 VDC Nonresettable power
SLC
M300CADT
24 VDC
notification
appliances
9 6 7 8 99 10 0
NAC Return 5 10
11
4
8 3 12
12
13
1
22 13
1 00 15
1514
14
NAC Out
7 TEN S 2
66 7 8 9
5
6 4
3 3
2
10
5 O N ES 4
LO
LO OP
OP AD
AD DR
DRES
ESSS
SLC-nacZ.cdr
24 VDC Nonresettable power
Notes
Installation
SLC
M300RADT
C 9
55
6 77 8 9 10 0
11
NC 8
4
3
2
12
13
1
1 0 15 14
NO 7 TENS
6789
2
5
C 6 4
33 3
NC 5
2
O NES
10
4 NO
LO
LOOP
OP AD
ADDR
DRES
ESSS
9 0
8 1
7 2
SLC-frmC.cdr
6 3
5 4
LO
LOOP
OP
Notes
Installation
2(+)
To next device
on SLC
3 1(–) –
S H IE L D
For connection of
cable shield
RA400Z
SLC-B501wire.cdr
+ –
Conduit
SLC Out
– +
SLC-224BIwire.cdr
SLC In
– +
Installation
SLC-nbg12.cdr
Notes
(Vms - Vom)
Rmax =
(N)(Is) + (Na)(Ia) + (Ir)
Where:
Rmax = maximum resistance of the 24 VDC wires
Vms = minimum supply voltage (see Table 3 below)
Vom = minimum operating voltage of the detector or end-of-line relay, whichever is greater, in volts
N = total number of detectors on the 24 VDC supply circuit
Is = detector current in standby
Na = number of detectors on the 24 VDC power circuit which must function at the same time in alarm
Ia = detector current in alarm
Ir = end-of-line relay current
The minimum supply voltages produced by ADT power supplies are listed below:
9 6 7 8 9 10 0
Supervised NAC or IDC 4
5 10
11
8 33 12
12
13
1
2
1 0 15 14
7 TEN S 2
6 7 88 9
5
6 44
3 3
2
11 0
5 ON ES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
Power Supervision
Relay
(A77-716B)
9 6 7 88 9 10 0
5
44 11
8 3 12
13
1
2
11 0 1514
7 TEN S 2
6789
5
6 4
3 3
2
10
5 ON
ONES
ES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
9 6 7 88 9 10 0
5
44 11
8 3 12
13
1
2
11 0 1514
7 TEN S 2
6789
5
6 4
3 3
2
10
5 ON
ONES
ES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
SLC-psr.cdr
M300CADT – +
SLC
9 66 77 8 9 10 0
55
4 11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
6789
5
6 4
33 3 ELR
2
10
5 O NES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
Circuit supervised
by control panel
M300CADT
9 66 77 8 9 10 0
55
4 11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
6789
5
6 4
33 3
2
10
5 O NES 4
LO
LOOP
OP AD
ADDR
DRES
ESSS
SLC-nacY1.cdr
NAC Terminal
Block (24 VDC)
+ –
Figure 33 NFPA Style Y NAC Power (Alternate)
9 6 7 8 9 10 0
5
4 11
11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
6 7 8 99
5
6 4
3 3
22
1 00
5 O NES 4
LO
LOOP
OP AD DR ES S
Circuit supervised
M300CADT by control panel
9 6 7 8 9 10 0
5
4 11
11
8 3 12
13
1
2
1 0 15 14
7 TENS 2
6 7 8 99
5
6 4
3 3
22
1 00
5 O NES 4
LO
LOOP
OP AD DR ES S
SLC-nacZ1.cdr
One primary surge protector must be used with each SLC wiring pair whenever SLC wiring runs
outside the building.
• Install primary protection only as shown in this document.
• Refer to NEC Article 800 and local building code requirements.
Additional primary surgesuppressors may be added as required by the NEC. Add these additional
suppressors in series with the SLC wiring at the building entry/exit.
Wiring connected to the surge suppressor output must remain within the building while wiring
connected to the surge suppressor input may be routed outside the building as shown below.
Building #2 Building #1
O U T IN IN O U T
S u rg e S up pre ss o r
O U T IN IN O U T FACP
SLC-ssbuild.cdr
Installation
Mounting is inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use.
• Locate on an available stud and secure with nut.
• Unit is connected in series with the SLC Loop to protect the Control Panel.
• Provide a common ground to eliminate the possibility of a differential in ground potentials.
Unimode 300/400
DTK-2LVLP-F Connections
2 LV LP -F
IN OUT
+
–
SLC-lvlp2.cdr
SLC Loop
IN OUT
PLP-42N Connections
P L P -4 2 N
GRND
L4
L4
Optional 4-wire Return Loop
O U TP UT
L3
IN P UT
L3
Style 6 (Class A)
L2
L2
L1
L1
+
GRND
L4
L4
–
O U T PUT
L3
IN P UT
L3
SLC-plpn2.cdr
L2
L2
SLC Loop
L1
L1
Note: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground
terminal to equipment ground. Wire length must be minimized to provide best protection
SLCP-030 Connections
S LC P -30
IN OUT
IN OUT
DTK-2LVLP-F Connections
2 LV L P -F
SLC-lvlp3.cdr
IN OUT
Note: Do not connect shield (if present) to surge protector or fire panel.
PLP-42N Connections
P LP -42 N
GRND
L4
L4
O UTPUT
L3
IN P U T
L3
SLC Loop
L2
L2
L1
SLC-plpn3.cdr
L1
Note: Use 12AWG (3.25mm2) to 18AWG (0.75mm2) wire with crimp-on connectors to connect the unit’s ground
terminal to equipment ground. Wire length must be minimized to provide best protection. Do not connect shield (if
present) to surge protector or fire panel.
SLCP-030 Connections
S L C P -3 0
IN OUT
Note: Do not connect shield (if present) to surge protector or fire panel.
A
G
address capacity 19
addressable general alarm 45
devices 19
modules 9 I
ADT-NBG-12LX 41 Initiating Device Circuits 10, 25, 26, 27, 29
Authority Having Jurisdiction 12 Intelligent Detector Bases 39
Isolator Base 10, 19, 20, 23
B Isolator Base, wiring of 40
Isolator Module 9, 19, 22, 23
B210LP detector base 39
B501 detector base 39
building entry/exit 47 J
junction box 16
C
cabinet 15, 16 K
capacity of devices 12 key-lock reset feature 41
CAUTION
Maximum number of devices between isolators 19
circuit fault 9
L
circuit, speaker/telephone 10 LED operation 12
coded output 45 LIB-200A 13
connector screw 15 LIB-400 13
Control Modules 9, 33 local building code 47
Loop Resistance 13, 14
loops 14
D
DC resistance 13, 14
detector base, wiring diagram 39
M
detectors M300CADT 33, 35, 44, 45
listing 10 resistor on the back 33
devices M300CADT, Wiring Diagrams 34
addressable 19 M300DADT 25, 29
document sources 11 M300MADT 25, 27, 28
dry relay contacts 37 M300RADT 37
dry-contact output, relay modules 9 M300RADT, wiring diagram 37
DTK-2LVLP-F 47 M301MADT 25
duplicate addressing 29 M302MADT 25, 30, 44
metal box 16
metal conduit 15, 16, 22
E minimum resistance, to determine 43
electrical interference 13 Minimum Supply Voltage 43
ELR, external 45, 46 module circuits, configuring 25
End-of-Line Resistor 34 modules
addressable 9
F control 9
FACP 47 monitor 9
factory preset address value 26, 40, 41 relay 9
fault 19, 20, 22 Monitor Modules 9, 25
Fault Isolator Module M500X 19 multiplex subsystem 10
FFT-7 or FFT-7S telephone circuit 33 Multi-Sensor Detector-3251 19
Fire Alarm Control Panels 9