Cast Resin Transformer
Cast Resin Transformer
Cast Resin Transformer
R eserves-equipped
Overloads are permissible due to the thermal reserves provided by specific primary insulation.
E ndurance-enhanced
Cooling ducts guarantee long service life.
S urge-proof
The double layer winding technology enables the control of high impulse voltages.
Q uantum-leap
Glass fiber reinforcement of windings ensures that during operation, when the winding heats and
expands, the design has the flexibility to react without damage to the winding even under short
circuit conditions.
For our customers these specific features mean a high level of safety both in relation to operation
and their investment decision.
4
R eserves equipped
Thermal loads make overload possible
SGB Cast Resin Transformers not only have an advantage over oil transformers but also cast
resin transformers incorporating established alternative designs. These transformers use a high voltage
winding design where the conductor consists of copper foil strip and the coil/layer insulation is
plastic. The insulation level of this type of system can only be considered as class F, when considering
the insulation system as a whole. It is quite different with SGB Cast Resin Transformers as SGB uses
insulated profile wires for a double layer winding where the primary insulation either consists of a
high heat resistant polyesterimide coating with a temperature index of 200C or Nomex thread
winding of the temperature class C (220 C).
5
E ndurance-enhanced
Guaranteed high service life
Cast resin transformers must emit the resulting heat in the windings over the surface
area of the coils to the cooler air surrounding the transformer. This has to be achieved
with respect to the winding insulation class and without exceeding the average winding
temperature, or the Hot-Spot temperature. The necessary cooling requirements can be
calculated by considering the heat transfer coefficient, the ambient temperature, the surface
temperature of the coil, and the size of the surface area.
With cast resin transformers of alternative designs, only the inner and outer surface
areas of the high voltage cylindrical coil are available for cooling. To provide the necessary
surface areas for cooling, the coils must be larger. SGB's design of a double layer winding
in comparison simply allows for the introduction of additional cooling ducts inside the coil.
In this way very efficient cooling is achieved. SGB Cast Resin Coils can therefore be equipped
with several cooling ducts.
SGB Cast Resin Transformers use appropriate materials and design to guarantee
a consistent distribution of temperature inside the coil. The optimized cooling enables a
reduction in temperature for the high voltage winding and furthermore a consistently
distributed temperature for the entire transformer.
6
S urge-proof
High impulse voltages are controlled safely
Only SGB Cast Resin Transformers mould their high voltage coils in vacuum combined with
a double layer winding. This ensures safety in the control of impulse voltages brought about by, for
example, lightning strikes or vacuum switches.
Regular coil winding of other transformers leads to much greater voltage stress, especially on the
input coils, because 70% of the shock impact does not apply on the first 30% of the coils. The risk of
winding short circuits therefore increases significantly.
The SGB double layer winding by contrast guarantees linear fault distribution for all windings.
7
Q uantum-leap
Overcome temperature shocks reliably
Cast resin transformers are subject to great mechanical and thermal shocks and strains in
their transport and in particular when operated. Therefore of great importance is the ability of the
transformers to safely control spasmodic temperature increases.
Core
With the calculation of cores for Cast resin transformers, no-load losses, noises and no-load currents
are quite considerable and in many cases, crucial quality features. As a result, the choice of high-quality
materials for core design and manufacture is vital.
For SGB Cast Resin Transformers a cold-rolled, grain-oriented magnetic plate is used and has a
typical loss factor of 0.85 W/kg. In most cases of application, values according to the requirements for no-
load losses and noises can be reached. For special requests a so-called Hi-B plate is used with which the
no-load losses can then be reduced further by approximately 15% and the noise level by around 5-7dB(A),
so that for specific applications, e.g. in hospitals, low losses and reduced noise requirements are met.
The cores themselves are manufactured on modern transverse and core-laying machines, which
guarantee a shift in the so-called step lap process with extreme precision. Put simply, the single sheets
are tapped in the usual step lap process by means of a repeated overlap and as a result the losses are
reduced.
For corrosion protection, a high temperature 2-component coating is used. This coating gives
protection to the core against the environmental elements to which it would be subjected. The coating also
infiltrates between the individual core sheets and sticks them together which gives further benefits when
handling noise and vibrations.
The core is fixed with a holding frame consisting of lower and upper clamping bars and flat-rolled
tie rods directly on the core. The tie rods consist of magnetic flat-rolled steel and connect the lower and
upper clamping bars together. The holding frame is constructed in such a way that the core plates are kept
free from tensile load and compressive stress as far as possible because, as such, they retain their excellent
features in relation to losses and noises. The lower yoke is allowed to rest, supported through mouldings
made from glass fiber-strengthened synthetic material onto the lower chassis pillar to which bidirectional
adjustable coils can be fixed. Different attachments such as additional footbridges, tubs, vibration-reducing
components and others can indeed be chosen depending on the individual project and client requirements.
9
Benefits:
- No metallurgic changes of the winding material
by means of a temperature process.
- No foreign bodies which can occur with moulding.
By using multi-layer prepregs, there is a high-strength, thick-walled cylinder, which can accommodate
the radial short circuit force unsupported-compared with the otherwise standard solutions.
10
11
12
Quality
Guaranteed high service life
The manufacture of cast resin transformer is of course certified within SGB in accordance with
ISO 9001 and ISO 14001. As a provider to OEM customers with high quality standards, we are familiar
with challenging quality systems such as, Six-sigma. Classification societies such as Germanischer Lloyd,
RINA or Bureau Veritas have approved SGB Cast Resin Transformer. SGB has been producing cast resin
transformers for over 30 years and therefore has the greatest wealth of experience in this field worldwide.
This remarkable know how is reflected in exceptionally high quality coefficients, such as MTBF of over
1,700 years. SGB Cast Resin Transformers naturally comply with all the usual quality standards such as:
Tests
SGB Cast Resin Transformers are designed and produced as standard in accordance with
IEC 60076-11. SGB Cast Resin Transformers comply with all the tests required in IEC 60076-11
All detailed inspections and type tests, e.g. short circuit tests or temperature rise tests as well
as many special tests have been completed in the course of our supply. In this way the specific
properties stipulated in the customer specification can also be checked, and met. In conjunction
with external institutes, we have also completed detailed measurements for the following areas:
24 kV.
Capacity No-load Load Total Impedance Effciency Voltage Noise Outline Dimension Total Material
(kVA.) Loss Loss Loss at 75C P.F. = 1 Regulation Level Approx. (mm.) Weight H.V. / L.V.
(W) at 75C at 75C (%) P.F. = 1 (%) dB(A):1m. (kgs.) Winding
(W) (W) 1/2 Load (%) Full Load (%) H L W
1000 2650 9600 12250 6 99.00 98.79 1.14 59 1845 1760 980 2450 AL/AL
1250 3100 11800 14900 6 99.04 98.82 1.12 60 1935 1840 980 2780 AL/AL
1600 3500 14000 17500 6 99.13 98.92 1.05 61 2125 1900 980 3170 AL/AL
2000 4500 17000 21500 6 99.13 98.94 1.03 64 2095 2060 1270 4130 AL/AL
12/24 kV.
Capacity No-load Load Total Impedance Effciency Voltage Noise Outline Dimension Total Material
(kVA.) Loss Loss Loss at 75C P.F. = 1 Regulation Level Approx. (mm.) Weight H.V. / L.V.
(W) at 75C at 75C (%) P.F. = 1 (%) dB(A):1m. (kgs.) Winding
(W) (W) 1/2 Load (%) Full Load (%) H L W
1000 2650 9600 12250 6 99.00 98.79 1.14 59 1740 1695 980 2525 CU/AL
1250 3100 11800 14900 6 99.04 98.82 1.12 60 1855 1820 980 2900 CU/AL
1600 3500 14000 17500 6 99.13 98.92 1.05 61 1940 2020 980 3485 CU/AL
2000 4500 17000 21500 6 99.13 98.94 1.03 64 2090 2140 1270 4420 CU/AL
*Technical Data / Specifications are subject to change without notice.
Manufacturing range
Cast Resin Transformers up to and including 25 MVA
and service voltage up to 36 kV.