Performance Corrections For Steam Turbines With Multi-Pressure Condenser
Performance Corrections For Steam Turbines With Multi-Pressure Condenser
Performance Corrections For Steam Turbines With Multi-Pressure Condenser
POWER2014
July 28-31, 2014, Baltimore, Maryland, USA
POWER2014-32177
Condenser
There are several mechanisms that can result in condenser
Condenser
ShellA ShellB performance deterioration which drive condenser pressures to
be higher than expected. These mechanisms may include air
removal effectiveness, tube fouling and reduced cooling
water flow. These mechanisms primarily impact heat transfer
effectiveness through either increased resistance, reduced
surface area, or a combination of both.
Figure 1.1Series Cooling Water Path Air accumulation in the condenser reduces the heat transfer
rate and is caused by either reduced vent capacity or too high
of an air ingress rate. In the first case, the low vent rate is
related to the air removal effectiveness and the associated
equipment used (Vacuum Pump or Steam Jet Air Ejector),
while in the latter case the increased ingress rate is caused by
excessive air leakage into the condenser system.
Condenser Condenser
ShellA ShellB
Tube fouling typically occurs on the tube side (Cooling Water
side) by the accumulation of foreign material (Biological,
chemical, etc) on the inside diameter surfaces. This increases
heat transfer resistance from tube side to shell side, resulting
in the condenser operating at an elevated pressure.
Tube plugging is caused by the accumulation of debris and
Figure 1.2Parallel Cooling Water Path results in blocking the flow to some of the tubes and therefore
reducing the active heat-transfer surface area of the
condenser. Tubes could also be intentionally plugged to
In the case of a series cooling water path the cooling water
mitigate tube leaks.
enters and exits Shell A (Low Pressure) before entering Shell
B (High pressure). The increased temperature of the cooling Reduced Cooling Water flow rate is typically caused by a
water entering Shell B is the main factor contributing to a reduction in pump capacity. Significant amounts of tube
higher pressure in Shell B. In the case of a parallel cooling plugging can impact pump capacity by a reduction in flow as
water path, the temperature of the cooling water at the inlet of a consequence to a corresponding increase in discharge head.
each Shell is equal, resulting in similar shell pressures. For a given condenser duty, reduced cooling water flow rate
However, the resulting pressure in each shell in a parallel typically results in an elevated temperature difference across
cooling water path may again differ due to other factors such the water box.
as shell-side fouling, cooling water tube fouling and
Additional factors to consider are properly filled water boxes
and properly installed pass rib gaskets for multi-pass water
box designs. A water box that is not properly vented can pass causing an elevated condenser pressure. A lower than
result in a significant amount of air trapped at the top of the expected water box differential pressure, a lower than
water box. This trapped air can blanket the upper tubes and anticipated water box differential temperature and a lower
reduce the effective surface area. Typically the symptom of than expected outlet temperature for a given inlet temperature
an insufficiently vented water box is an elevated temperature and condenser duty are possible symptoms of a dislodged or
difference across the water box for a given condenser duty missing water box pass rib gasket.
along with a lower than expected water box differential
All the factors mentioned above may result in higher than
pressure.
expected condenser shell pressures. Table 1.1 gives
On multi-pass water box designs, a pass rib gasket prevents approximate sensitivities of several key condenser design and
cooling water flow from bypassing one water box chamber to operating variables on condenser pressure. The data from
another. A damaged or missing gasket would result in Table 1.1 shows that cooling water inlet temperature has the
reduced cooling water flow through a particular tube bundle largest impact on condenser pressure indicating that the
cooling water arrangement (series vs parallel) is the biggest
Approximate factor in driving pressure differences between condenser
Mechanism Impact on Con- shells.
denser Pressure
Each last stage bucket (LSB) and exhaust hood configuration Cond 1 1.5 870 2.9
is characterized by an exhaust loss curve. The exhaust loss
Cond 2 3.5 400 2.6
includes the effects of loss due to steam velocity not
converted to work, pressure drop through the exhaust hood, Cond Avg 2.5 540 1.1
and inefficiencies related to LP stage performance with low
velocities. Figure 3.2 shows a typical exhaust loss curve as a Table 3.1Exhaust Loss Calculation
function of annulus velocity leaving the last stage. For most
last stage bucket and hood configurations, the optimum point
In order to correct measured turbine performance to a set of
with minimum exhaust loss occurs around 600 ft/s. Below
reference conditions in accordance with ASME PTC 6
600 ft/s results in operating in the turn-up region where
methodology, Group 1 and Group 2 correction curves
lower velocities can result in flow recirculation leading to
supplied by the turbine OEM are used. Correction curves for
increased losses. Above 600 ft/s results in operation in a
exhaust pressure are included in the Group 2 corrections. The
region dominated by hood loss and leaving loss that increase
curve is generated using a heat balance modeling program
with increasing annulus velocity
and takes into account exhaust loss, changes in available
Annulus velocity (VAN) is a function of annulus area, flow, energy and turbine efficiency, and moisture effects. Figure
steam quality (moisture), and specific volume. Specific 3.3 shows an example exhaust pressure correction curve for a
volume increases exponentially with decreasing exhaust large steam turbine configuration operating at a single
pressure so small changes in pressure can result in large condenser pressure. The curve shows how output changes
changes in velocity. For a unit operating with multiple flow with variations in exhaust pressure. This curve could also be
ends, there is assumed to be equal flow leaving all turbine generated to show heat rate variation with exhaust pressure.
ends. With this assumption, turbines operating with multiple A single curve is shown on Figure 3.3 representing full load
condenser pressures will operate with different annulus throttle flow while an actual curve would cover a wider range
velocities entering each condenser shell. Due to the parabolic of expected operating flows. This curve could be applied to
10
0
0 200 400 600 800 1000 1200 1400 1600
Annulus Velocity (ft/sec)
4.0% 2.0%
LP Condenser
3.0% 1.5%
HP Condenser
2.0% 1.0%
1.0% 0.5%
% Change in Output
% Change in Output
0.0% 0.0%
-1.0% -0.5%
-2.0% -1.0%
-3.0% -1.5%
-4.0% -2.0%
-5.0% -2.5%
-6.0% -3.0%
0.0 1.0 2.0 3.0 4.0 5.0 6.0 0.0 1.0 2.0 3.0 4.0 5.0 6.0
Figure 3.3Typical Steam Turbine Exhaust Figure 3.4Typical Steam Turbine Exhaust
Pressure Correction Curve for Single Pressure Pressure Correction Curve for Multi-Pressure
Operation Operation
Figure 3.4 HP Correction 0.9932 With any reading, measurement errors can contribute to
errors in calculated results. As indicated in ASME PTC 6,
Corrected Output 541,303 discrepancies in excess of 0.1 HgA in redundant exhaust
pressure readings should be investigated further. Two
Output Corrected for Average Pressure common issues related to exhaust pressure measurement
Average of HP and LP errors are damaged/missing basket tips or moisture
2.25 HgA accumulation in the sensing lines. Plants are encouraged to
Condenser Pressures
inspect basket-tip connections during outages to verify that
Figure 3.3 Correction at
1.0189 they are intact and undamaged. Horizontal runs in the
Average Pressure
sensing lines should be avoided as they can result in moisture
Corrected Output 536,092 build-up. Its good practice to open the transmitter vent and
allow the condenser vacuum to pull the moisture out of the
Error in Corrected Output sensing line prior to testing/assessment activities as long as
% Difference -0.98% the transmitter is not a turbine trip sensor.
The installation of the basket tips (the exact position and
Table 4.3Sample Calculation of Corrected angle of the basket tip to the flow) may vary from one
Output Error
condenser shell to another. This can introduce small
differences in the measured pressure between two shells.
4.2) Case Study 2: 26 Last Stage Buckets Local variations of the flow field may also contribute to
erroneous exhaust pressure measurements. If all basket-tips
If the turbine cycle modeled in Case Study 1 was expected to cannot be utilized for test purposes, judgment should be used
operate with higher condenser pressures in the range of 2.5 - to select a mix of Left/Right and Corner/Middle basket-tips in
3.0 HgA, a 26 LSB might be the more optimum choice. In an attempt to capture flow field variations.
this backpressure range, VAN is in the range of 650700 ft/s
and again results in operation close to the minimum point on 5.2) Data Evaluation, Analysis and Trending
the exhaust loss curve. As condenser pressure increases, Table 3.1 of ASME PTC 6 specifies criteria for the allowable
specific volume and volume flow decrease. As such less deviations of test average conditions from reference
annulus area is required to maintain the same annulus conditions. For exhaust pressure the allowable deviation is +/
- 0.05 psi or +/- 2.5% of the absolute pressure, or whichever