Select Instrum Transfmer
Select Instrum Transfmer
Select Instrum Transfmer
Note: The source of the technical material in this volume is the Professional
Engineering Development Program (PEDP) of Engineering Services.
Warning: The material contained in this document was developed for Saudi
Aramco and is intended for the exclusive use of Saudi Aramcos
employees. Any material contained in this document which is not
already in the public domain may not be copied, reproduced, sold, given,
or disclosed to third parties, or otherwise used in whole, or in part,
without the written permission of the Vice President, Engineering
Services, Saudi Aramco.
CONTENTS PAGES
Frequency ...............................................................................25
Primary and Secondary Currents ............................................27
Accuracy Classes ....................................................................27
Continuous Current.................................................................31
Short-Time Current.................................................................31
Selection Factors ................................................................................32
Currents...................................................................................32
CT Burden...............................................................................33
Relay Energy Requirements....................................................35
Saturation (Excitation Curve) .................................................37
ANSI/IEEE Accuracy and Voltage Class ...............................41
Improving CT Accuracy .........................................................45
Altitude ...................................................................................45
Temperature ............................................................................46
GLOSAARY..................................................................................................65
A CT is designed to connect in series with the line and transform the line current to the
standard 5-ampere coil rating of a meter, relay, or other device. This Information Sheet will
describe briefly the four most common types of CTs (bushing, bar, window, and wound-
types) as well as two other types of CTs (core balance and auxiliary types) that are commonly
used in industrial and commercial power systems.
Bushing-Type CT
The bushing-type CT (Figure 2) is almost invariably used for transformers and circuit
breakers. This type CT is chosen for relaying in higher voltage circuits because it is less
expensive than any other types of CTs. Bushing-type CTs are not used in circuits below 5
kV. The bushing-type CT consists only of an annular-shaped core with a secondary winding.
This CT is built into the equipment such as circuit breakers, power transformers, generators,
or switchgear, with the core being arranged to encircle an insulating bushing through which a
power conductor passes. Most of the bushing-type CTs have a well or area that is constructed
for the CT to set in. The well area is below the area of the transformer liquid. Therefore, the
liquid acts as an insulation factor for the CT.
Because the internal diameter of the bushing-type CT core has to be large to accommodate the
main device bushing, the mean length of the magnetic path is greater than in other CTs. To
compensate for this mean length, and also the fact that there is only one primary turn, the
cross section of the core is made larger. Because there is less saturation in a core of greater
cross section, a bushing-type CT tends to be more accurate than other CTs at high multiples of
the primary current rating. At low currents, a bushing-type CT is generally less accurate
because of its larger exciting current.
Bar-Type CT
A bar-type CT (Figure 3) has a piece of bar as a primary turn with ends developed for ease of
termination with bus or cable. It has a fixed insulation over the bar to insulate the primary or
bar from the secondary windings. This bar primary provides the magnetic field for the
secondary winding. The secondary windings are wound around a metal core that the bar
passes through. This type of CT is used on indoor switchgear, motor starters, switchboards,
and any other equipment or device that has a bus bar current conductor.
Figure 2. Bushing-Type CT
Figure 3. Bar-Type CT
Window-Type CT
A window-type CT (Figure 4) is the most popularly used CT. The CT has a window or hole
in the center that can be round or square. The hole is formed (surrounded) by a metal which
serves as a type of core. The secondary windings are wound around this core material. The
secondary windings are insulated from, and permanently assembled on, the core. The
window-type CT has no primary winding constructed as an integral part of the structure. The
complete or partial insulation is provided for a primary conductor or winding to pass through
the window. This primary conductor provides the current and voltage that generate the
magnetic field that is induced into the secondary windings. Window-type CTs are used for
numerous types of application. This type of CT can be used for measuring the magnetic field
of a single conductor.
Figure 4. Window-Type CT
Wound-Type CT
A wound-type CT (Figure 5) has a primary winding that consists of one or more turns that are
mechanically encircling the core or cores. The primary and secondary windings are insulated
from each other and from the core, and they also are constructed as an integral structure.
Wound-type CTs can be used in switchboard, switchgear, motor starters, and other indoor and
outdoor applications. The outdoor wound-type CTs have different types of insulation as
weatherproofing.
Figure 5. Wound-Type CT
The core balance method of transformation is based on the principle of primary current vector
addition or flux summation. A core balance CT is often called a zero-sequence, ring or
window-type CT, but core balance is the IEEE preferred term because it more specifically
describes the CT function. Figure 6 illustrates non-shielded conductors running through the
window of a core balance CT and Figure 7 illustrates a similar configuration, except that the
conductor (cable) is shielded.
Auxiliary CTs
Voltage transformers (VTs), which were formerly called potential transformers (PTs), are
connected between the lines whose potential difference is to be determined, and they are used
to step the voltage down (usually to 120 V) to supply the voltage circuits of the connected
instrument burden. A VTs basic construction is similar to that of a power transformer
operating at the same input voltage, except that it is designed for optimum performance with
the high-impedance secondary loads of the connected instruments. The VT core is operated
at high flux density, and the insulation must be appropriate for the line-to-ground voltage.
Inductively coupled VTs are nothing more than small step-down transformers. Since an
inductively coupled voltage transformer is simply a small step-down transformer, the basic
construction of an inductively coupled VT is the same as any voltage transformer.
Inductively coupled VTs are designed for use in relaying, indication, metering, and control
circuits. Inductively coupled VTs may be mounted indoors or outdoors. For indoor use, the
inductively coupled VT preferably should be a dry-type. For outdoor use, either oil-immersed
or dry- types are acceptable. An inductively coupled VT may form an integral part of a
switchgear assembly or be a separate item of equipment. Figure 9a illustrates a 480 to 120-
volt (4:1) VT and Figure 9b illustrates a 12,000 to 120-volt (35:1) VT.
Coupling capacitor voltage transformers (CCVT) are used in applications where the input
voltage is too high for conventional inductively coupled VTs. An example of an input
voltage that is too high for a conventional inductively coupled VT is a transmission line
voltage. CCVTs are designed for use in relaying, metering, indication, and control circuits
that are associated with high voltage transmission lines. Figure 10 illustrates the schematic
diagram of a CCVT that uses a capacitive divider circuit to reduce high voltage V1 ( 115-230
kV) to a lower voltage V2 ( 10-20 kV). The voltage transformer itself further reduces the
voltage to a relay or metering voltage Vm ( 120 V).
The voltage needed to operate a control circuit is normally taken from the main power circuit
of, for example, the motor starter shown in Figure 11. To connect the power circuit to the
control circuit, a control power transformer (CPT) is used. The transformer is a standard
single-phase design consisting of two windings wound on a common core. Power is
transformed from the primary winding to the secondary winding in accordance with the
principles of magnetic induction. The CPT is selected and sized according to the voltage
rating and voltampere capacity of its windings.
Control circuits are designed to operate at relatively low voltage levels (110 to 120 volts ac)
in order to provide safety for operating personnel. Motor starter power circuits, however,
operate typically at one of several higher voltage levels. For this reason, CPTs are available
in a variety of voltage ratings and voltage ratio combinations. When sizing a CPT to the
power circuit, the winding voltage ratings must be selected to match the voltages of the
control and power circuits. More commonly, the CPT is sized and provided by the
manufacturer as an integral part of the controller.
In addition to the voltage rating of the windings, the CPT is also rated in accordance with its
voltampere capacity. With the voltage rating of the windings identified, the voltampere rating
determines the maximum current that the winding can carry without overheating. Typical
voltampere ratings available for CPTs range from 50 VA to 2000 VA. Similar to the voltage
rating of the windings, the voltampere rating of the CPT is commonly determined by the
manufacturer when the CPT is supplied as part of the controller. Figure 11 illustrates a CPT
that is providing power to the control circuit of a non-reversing motor starter.
Marked Ratios
The marked ratio of an instrument transformer is the ratio of the rated primary value to the
rated secondary value as stated (marked) on the instrument transformer. Both CTs and VTs
are commercially available as single-ratio or multiratio CTs/VTs.
Single-Ratios
Current Transformers (CTs) - The ratio of the primary current to the secondary current is a
constant and is called the CT current ratio. Note: The CT current ratio is more commonly
called the CT ratio. A standard single-ratio CT has a single primary turn (i.e., the conductor
in a window-type CT) and multiple secondary turns or windings (Figure 12). The CT current
ratio and turns ratio are represented by the following formulas:
= Is/Ip
CT secondary ratings should normally be 5 A but, secondary ratings of 5/3 A are required if
delta connected secondary windings are used, for example, when phase correcting in
transformer differential protection schemes. Secondary ratings of 1 A may also be required,
for example, for use with solid state relays.
75:5
Source: C57.13
2. Ip = Is x CT Ratio
Example B: If the CT identified in Example A has a single primary turn, how many turns
are there in the secondary winding?
= Ns = Np (Is/Ip)
Voltage Transformers VTs - The ratio of the primary voltage to the secondary voltage is a
constant and is called the VT voltage ratio. The VT voltage ratio is more commonly called
the VT ratio and it is represented by the following formula:
The standard secondary voltages for VTs manufactured in the United States are 120 V and
69.3 V. Secondary voltages of 115 V and 66.4 V are also available. Figure 14 lists several of
the standard VT ratios that are specified in ADP-P-121.
Aramco
Rated
Nominal
ANSI Primary Voltage
System Voltage
Group (kV rms) Marked Ratio
(kV rms)
Example C: The marked ratios of the Group I VTs shown in Figure 15 are 35:1 (4200:120).
What reading should the voltmeters (V) indicate if the actual primary voltage is
4.16 kV?
2. Vs = 4160/35 118.9 V
Multiratios
Current Transformers (CTs) - Multiratio CTs have a single primary winding and a tapped
secondary winding (Figure 16). Similar to single-ratio CTs, the secondary current is also 5 A.
Figure 17 lists the standard ratios of multiratio CTs.
Source: C57.13
Figure 17. Standard Ratios of Multi-Ratio CTs
oltage Transformer (VTs) - Although not as commonly used as multiratio CTs, VTs are also
manufactured with taps in the secondary winding for additional (different) ratio connections.
For example, a 8400/12000/14000 VT that has a ratio of 70/100/120:1 is a multiratio VT.
Polarity Markings
Polarity is the designation of the relative instantaneous directions of the current entering the
primary terminals and leaving the secondary terminals during most of each half-cycle. The
primary and secondary terminals of an instrument transformer are said to have the same
polarity when, at a given instant during most of each half-cycle, the current enters the
identified, similarly marked primary terminal and leaves the identified, similarly marked
secondary terminal in the same direction as though the two terminals formed a continuous
circuit. Proper polarity means the secondary current is substantially in phase with the
primary current (Figure 18). For single-input (voltage or current) actuated relays, polarity has
no significance; correct operation of dual-input relays (current-current, voltage-voltage,
current-voltage) usually depends on the relative instantaneous direction.
Subtractive Polarity implies that the current flowing into primary terminal H1 is substantially in
phase with current flowing out of the secondary terminal X1. The term substantially in phase
allows for the small phase angle error. Virtually all medium voltage transformers are
subtractive polarity.
Additive Polarity implies that current flowing into primary terminal H1 is substantially in phase
with the current flowing out of the secondary terminal X2. Additive polarity is seldom used
except for pole-mounted distribution transformers (physical location of terminals) and several
other instances for directional applications on VTs.
Terminal Markings
All instrument transformer vendors must clearly indicate polarity by permanent markings on
the CT or VT. For example, a particular vendor may paint a white dot on an instrument
transformer to indicate polarity. Figure 19 shows 3 typical means of marking polarity on a
one-line diagram, with the square marking being the most common marking.
Primary Terminals (Hn) - Where polarity is also indicated by letters; the letter H is used to
distinguish the primary side terminals from the secondary side terminals. Each lead must be
numbered as well, for example, H1, H2, ..., Hn or H1, H2, ..., Hn.
Secondary Terminals (Xn) - Where polarity is also indicated by letters, the letter X is used to
distinguish the low side terminals from the primary side terminals, for example, X1, X2, ..., Xn
or X1, X2, ..., Xn.
Current Transformers
CTs are connected in wye for most applications; however, they are also, for special
applications, connected in vee (open-delta) or delta.
Wye Connection - In the wye connection (Figure 20), a CT is placed in each phase with phase
relays in two or three of the secondaries to detect phase faults. On grounded systems, a relay
in the CT common wire detects any ground or neutral currents. Wye-connected CTs
reproduce positive, negative, and zero-sequence currents as they are in the CT primary, and
the secondary currents are in phase with primary currents.
Vee or Open-Delta Connection - This vee CT connection (Figure 21), which uses only two CTs
(economical reasons), is basically a wye connection with one leg omitted. This vee
connection provides protection against phase-to-phase faults on all phases of a three-phase
system, but will only protect against those phase-to-ground faults that are above the relay
settings on the phases in which the CTs are installed. Since there is no way of sensing zero-
sequence currents with this connection, it is rarely used as the only means of protection in a
circuit. The vee connection is, however, frequently applied with the addition of a zero-
sequence CT, as shown in Figure 21.
Delta Connection - The delta connection (Figure 22) uses three CTs with the secondaries
connected in delta before the connections are made to the relays. The delta connection is only
used for power transformer differential relay protection schemes where the power transformer
has delta-wye connected windings. The CTs on the delta side of the power transformer are
connected in wye, and the CTs on the wye side of the power transformer are connected in
delta. These wye-delta and delta-wye connection arrangements compensate for the 30o phase
angle shift introduced by the wye-delta bank, and they also block the zero-sequence current
from the differential circuit on external ground faults.
Voltage transformer (VT) primary connections are distinguished by Group. Although there
are 5 ANSI/IEEE Standard C57.13 groups, this Information Sheet will limit discussion to
Groups 1, 2, and 3.
Group 1 voltage transformers are for application with 100 percent of rated primary voltage
across the primary winding when connected line-to-line or line-to-ground. For typical Group
1 VT connections, see Figures 23a and 23b.
Group 2 voltage transformers are primarily for line-to-line service, and they may be applied
line-to-ground or line-to-neutral at a winding voltage equal to the primary voltage rating
divided by 3 . For typical Group 2 VT connections, see Figures 24a and 24b.
Group 3 voltage transformers are for line-to-ground connection only and they have two
secondaries. They may be insulated-neutral- or grounded-neutral-terminal type VTs. For a
typical Group 3 VT connection, see Figure 24c.
Note: Work Aid 1 has been developed to teach the Participant procedures to select current
transformers.
Introduction
The major criteria for selecting a current transformer ratio are the continuous current ratings
of the connected equipment (relays, auxiliary current transformers, instruments, etc.) and of
the secondary winding of the current transformer itself. In practice, with load current
normally flowing through the phase relays or devices, the ratio is selected so that the
secondary output is around 5 amperes at maximum primary load current. Where delta-
connected current transformers are used, the square root of three ( 3 ) factor must be
included.
Although the performance required of current transformers varies with the relay application,
high quality transformers should always be used. The better quality transformers reduce
application problems, they present fewer hazards, and they generally provide better relaying.
The quality of the current transformers is most critical for differential schemes, where the
performance of all the transformers must match. In differential schemes, relay performance is
a function of the accuracy of reproduction, not only at load currents, but at all fault current
levels as well.
Ratings
The BIL rating levels of CTs are in terms of full-wave test voltage, as listed in Figure 25.
Voltage
Voltage rating levels are based on the nominal system or maximum voltages, which are also
listed in Figure 25.
Frequency
0.6 0.38 10
2.4 1.53 45
4.8 3.06 60
8.32 5.29 75
The primary current that is selected for the basis of performance specifications of a CT is
called the rated primary current. Figure 13 listed the rated primary currents of standard
single-ratio CTs and Figure 17 listed the rated primary currents of standard multiratio CTs.
The rated primary current of a CT divided by the marked ratio of a CT is called the rated
secondary current of a CT. As previously mentioned, the rated secondary current of most
CTs manufactured in the United States is 5 A.
Accuracy Classes
The accuracy classes of CTs are based on standard burdens, which are the loads (wires,
relays, meters, etc.) that are connected to the CT secondary. CTs are assigned accuracy
classifications for either metering service or relaying service. Accuracy up to one times rated
current is important for metering, whereas accuracy at up to 20 times rated current is
important for relaying. The difference being that meters must operate under normal
conditions, whereas relays must properly operate under both normal and abnormal (overload
and fault) conditions. Some CTs are assigned accuracy classifications for both metering and
relaying; however, it is preferable to use separate CTs for metering and relaying where
possible.
Metering Accuracy - Calculating, or even defining accuracy class for metering, is beyond the
scope of this Module; however, the following criteria, which is copied from ADP-P-121, is
presented for the Participants information.
Accuracy classes should be specified either to ANSI C57.13 or to IEC 185 convention.
The two conventions are different and a comparison is shown in Figure 26. In the
comparison shown, the IEC class is equal to or better than the ANSI class.
0.3 0.2
0.6 0.5
1.2 1.0
Source: ADP-P-121
For revenue metering, ANSI CT accuracy class 0.3 should be used, and for indication or
auxiliary purposes, ANSI CT accuracy class 1.2 should be used.
Relaying Accuracy - Relays commonly operate at currents of several times the rated current of
the CT and performance up to 20 times normal (100 A) is the basis of accuracy specification.
At the same time there is usually little need to limit the ratio error to less than 10% and hardly
any need to limit the phase angle. Accordingly, the basis for classification of performance for
relaying is an error limit of 10% at any current from 1.0 to 20 times the normal current. The
accuracy classification is not really a description of accuracy, but turns out to be a
description of how much voltage the transformer can supply to the output circuit or burden.
The performance of CTs is specified in terms of the secondary voltage that can be supplied by
the CT at 20 times normal current (20 x 5A) without exceeding the error limit of 10%. For
instance, the accuracy class is specified as 200 if the CT can supply a 2 ohm burden at 100 A
(20 times normal) without exceeding 10% error.
Standard values which may be assigned for the voltage that a transformer can deliver are
listed in ADP-P-121 (Figure 27).
C 10 or T 10 2.5 VA 10P20
C 20 or T 20 5 VA 10P20
C 50 or T 50 15 VA 10P20
Source: ADP-P-121
This form of definition of accuracy has other uses. For example, if the error is 10% at 20
times normal current or 100 A secondary output, it must be that the exciting current which is
by-passed by the exciting branch is not over 10 A. It also follows that if the current is lower,
the burden can be higher in proportion without exceeding the output voltage limit, and the
exciting current bypassed can still not exceed 10 A. If the transformer will carry 2 at 100 A
and deliver 200 V, it can also carry 4 at 50 A, and deliver 200 V, losing not more than the
same 10 A through the exciting branch.
It does not follow, however, that the transformer can carry 1 burden at 200 A, because the
total real burden includes the internal impedance of the transformer (Figure 28b) and the
voltage applied to the exciting branch will actually include the drop in the internal impedance,
which may be significant in comparison to 1.0 .
Continuous Current
The continuous current thermal ratings of CTs are based on an average 30 oC ambient
temperature. CTs may be operated at temperatures above 30 oC, however, they must be
derated in accordance with Figure 1 of ANSI/IEEE Standard C57.13. As a general rule of
thumb, at temperatures over the standard 30 oC daily average ambient temperature, CTs
should be derated 1% for each degree over 30 oC (up to 55 oC ambient).
Thermal current rating factors (RF) at 30 oC ambient air temperatures are 1.0, 1.33, 2.0, 3.0
and 4.0, with a 1.33 RF being the most common rating. Note: ADP-P-121 specifies that the
continuous thermal rating factor for Saudi Aramco installations should be 1.0. At 30 oC
ambient, a 55 oC average winding temperature rise is standard and a hottest-spot winding
temperature rise of 65 oC is also standard. CTs that are used in switchgear are based on a 55
o
C ambient temperature and a 30 oC temperature rise.
Short-Time Current
Mechanical Current Rating is the RMS value of the ac component of a completely displaced
(asymmetrical) primary current wave that the CT is capable of withstanding with the
secondary short-circuited. Withstanding means no damage and it is capable of meeting all
other requirements of ANSI/IEEE Standard C57.13. In switchgear, a typical mechanical
rating for CTs is 180 times rated primary current for 10 cycles.
Thermal Current Rating is the RMS symmetrical primary current that the CT can carry for 1-
second with the secondary winding short-circuited without exceeding the limiting temperature
in any winding. For 55 oC transformers, the limiting temperature is 250 oC.
The short-time thermal current rating up to 5 seconds may be determined by dividing the
current for the 1-second rating by the square root of the specified number of seconds. A
typical short-time thermal rating is 100 times rated primary current for 1-second.
Example D: What is the 3-second short-time thermal rating for a 200:5 CT where the 1-
second rating is 20 kA (100 x 200)?
= 20000/
= 11.6 KA
Selection Factors
Currents
CT Data (Burden)
Relay Data
Currents
Continuous Load - Generally, the selection of the CT ratio is based on the continuous maximum
circuit load current. The secondary current of the CT at maximum load should not exceed
rated secondary current, and, because most relays have a wide range of taps, the CT ratio is
not critical for relay operation; therefore, the CT ratio is usually chosen based on the criteria
to provide secondary full load current that would deflect an ammeter pointer to approximately
1/2 (2.5 A) to 2/3 (3.33 A) of full scale. This criteria (1/2 to 2/3 deflection) implies sizing
CTs at 150% [1 (2/3)] to 200% [1 (1/2)] of full-load. For differential relaying
applications, CTs are usually sized as close as possible to the actual full-load amperes, which
improves the differential relays sensitivity for detecting faults. For grounding resistance
applications, CTs are typically sized at 50% of the current rating of the resistor. For example,
for a 400-ampere grounding resistor inserted into the neutral conductor, the CT is sized at
200:5 (50% x 400 A).
Short Circuits - Another criterion for the CT ratio is determined by the maximum system fault
current. Devices connected to the CT secondary have a published one-second rating.
Therefore, the maximum fault current should be divided by the one-second current rating of
the connected devices, and this number should be less than the CT ratio; otherwise, a further
check is necessary that would necessitate calculating the total time any device would
experience a maximum fault. This time would be determined by the trip time of the
protective relays involved and it would normally be less than one second. The thermal
capacity for the shorter time is calculated on the basis of allowable fault time being inversely
proportional to the square of the fault current (for example, I2t = K, where K is the square of
the 1-second current rating). The result of the maximum fault current divided by the short
time thermal rating should be less than the CT ratio; otherwise, a more refined calculation is
necessary. See Example D.
CT Burden
The equivalent circuit for a CT is shown in Figure 29, where Rs is the burden or ohmic
resistance of the CT itself and ZB is the burden of the relays, meters, etc.
ANSI/IEEE Standard C57 defines burden as that property of the circuit connected to the
secondary winding that determines the active and reactive power at the secondary terminals.
The burden is expressed either as total ohms impedance with the effective resistance and
reactance components, or as the total voltamperes and power factor at the specified value of
current or voltage, and frequency.
The energy requirements of a relay, at the different tap values, include the following:
continuous rating in amperes, one-second rating in amperes, and the burden (impedance) in
voltamperes.
At At At At
(D =
0.91)
2.0
2.5
10.0
12.0
A CT characteristic is best illustrated by the CT excitation curve (Figure 31). This curve
defines the relationship of the secondary exciting current (Ie) to the secondary voltage (Es).
The unsaturated slope is determined by the magnetic core material. When the CT core is
unsaturated, the error due to exciting current is normally negligible. When the secondary
voltage is above the knee of the excitation curve, the CT is said to be operating in its saturated
region. The knee of the excitation curve, as defined in ANSI/IEEE Standard C57.13
(Requirement for Instrument Transformers), is shown in Figure 31 as the solid line, which has
a 45 degree slope and it is tangent to the excitation curve. The knee represents the voltage
magnitude where the exciting current increases much more rapidly than the secondary
voltage, and, therefore, the ratio error of the CT becomes much greater beyond the knee, and
this area is referred to as the saturated region.
The dashed lines in Figure 31 represent the IEC (International Electrotechnical Commission)
method of determining the knee of the excitation curve. The two dashed lines are an
extension of the unsaturated slope and the saturated, or air core, slope. This voltage
magnitude is always greater than the knee voltage defined by ANSI/IEEE Standard C57.13.
The knee for a particular turns ratio is determined by the quantity of steel in the core. As the
core becomes saturated, the excitation curve approaches a zero slope such that a very large
change in exciting current is required for a very small increase in excitation voltage. At very
large multiples of rated current, normally greater than 20 times, the CT will produce a voltage
due to its air-core effect (i.e., the steel is completely saturated).
Example E: Referring to the one-line diagram and system and CT data that are shown in
Figure 32, evaluate the CT for saturation at the given tap-value amperes (Part I)
and at the maximum fault level of 6 kA
(Part II).
MC Switchgear
3000:5, 4000:5
SC Switchgear
3000:5, 4000:5
5000:5, 6000:5
Source: C37.20.2
Note: ANSI/IEEE Standard C57.13 lists an additional standard burden of B8.0 with a
secondary terminal voltage of 800 V.
With the standard burden or any lower value burden, the ratio error will not exceed 10 percent
for 1 to 20 times rated secondary current. The ohmic burden for any relaying CT is
determined by dividing the numerical voltage classification by 20 times the rated secondary
current. The relay accuracy class ratings apply only to the full winding in the case of
multiratio CTs. CT standard voltage classes and their associated burdens are also listed in
Figure 34.
Answer:
= 100/(20 x 5) = 1.0
Because CT accuracy classes have definite voltage values (Vcl), for example 10, 20, 50, 100,
200, 400, and 800 volts, a judgment of CT accuracy should not be based on accuracy class
alone. CTs are classified at the nearest standard voltage below the calculated value of VT
(Figure 34), as represented by the following formula:
VT = ES - ISRCT
The burden rating on a current transformer is also based on the use of the whole winding.
When fewer turns are used, as in a multiratio CT, only a portion of the burden can be supplied
without exceeding the 10 percent error. The permissible burden of a multiratio CT can be
determined by using the following formula:
Example G: A multiratio CT is rated at 1200:5 and it is being used on the 800:5 tap. Its
accuracy class is C200. The total circuit burden is 2.4 ohms (burden of the
relays). Note: Ignore RCT. The available fault current is 12 kA. Will the error
of the CT exceed the 10 percent limit?
Example H: What is the voltage class (Vcl) of a CT where Ie = 10 A, Es = 600 V, and RCT =
1 .
Answer: 1. VT = Es - Is RCT
= 600 - [(20 x 5)(1)] = 500 V
Example I: Repeat Example G where Ie and RCT are the same and Es = 495 V.
Improving CT Accuracy
When low ratios are required, standard CTs may not be available to supply the required
burden (Figure 34). It is sometimes possible to apply two standard higher ratio CTs that have
a higher relaying accuracy classification voltage (with the primaries connected in series and
the secondaries connected in parallel) to supply this burden. The desired overall low ratio is
achieved with a substantially improved accuracy.
If the circuit burden exceeds the calculated permissible burden, it may be necessary to reduce
the burden (a different relay, larger lead wires, etc.), or to use a higher CT ratio or a CT with a
higher voltage class to reduce saturation and to improve accuracy.
Altitude
CTs may be operated at altitudes greater than 1000 meters without exceeding established
temperature limits provided that the current is reduced below rated current, or below rated
current times the continuous thermal current rating factor (RF), by 0.3 percent for each 100
meters that the operating altitude exceeds 1000 m.
Example J: What is the continuous current rating of a 1.0 RF, 400:5 CT that is being
operated at 1400 m?
= 395.2 A
Temperature
CTs that are designed for a 55 oC temperature rise above 30 oC ambient air temperatures may
be loaded in accordance with the curves of Figure 36 for any given average cooling air
temperature and continuous-thermal current rating factor (RF). The percent of rated primary
current that can be carried continuously without causing established temperature limitations to
be exceeded is shown by the curves in Figure 36.
Answer: Per Figure 36, The CT can be used at approximately 150% of rated current at
55 oC ambient temperatures.
Note: Work Aid 2 has been developed to teach the Participant procedures to select voltage
transformers (VTs).
Introduction
Voltage transformers (VTs), which were formerly called potential transformers (PTs), are
primarily selected according to two criteria: the system voltage level and the basic impulse
insulation level that is required by the system on which they are to be used. Two nominal
secondary voltages of 115 and 120 volts are allowed for voltage transformers and the
corresponding line-to-neutral values are 115/ and 120/ . The applicable voltage depends
on the primary voltage rating as listed in ANSI/IEEE Standard C57.13.
Ratings
The BIL rating is the full-wave test voltage that the VT should be able to withstand without
failure. These BIL ratings typically indicate how well a VT can withstand a surge in voltage
caused by a lightning strike, switching transients, etc. ANSI/IEEE Standard C57.13 (Work
Aid 2A, Handout 1) lists all of the BIL ratings for the 3 groups (1, 2, and 3) of VTs that are
manufactured in the United States. Figure 37 summarizes the BIL ranges for the same 3
groups of VTs.
1 10 - 110 kV
2 10 - 250 kV
3 125 - 2050 kV
Voltages
VTs, according to ANSI/IEEE Standard C57.13, are capable of operating continuously, and of
maintaining their accuracy at 110% of rated voltage. Group 2 transformers need do no more
than this (110%), Group 1 transformers must be able to operate (but not necessarily maintain
accuracy) at 125% voltage during emergencies, while Group 3 transformers must be able to
operate for one minute at line-to-line voltage, which is the times their rating.
Primary - The primary voltage that may be applied to a VT is limited not only by the
permissible voltage to ground, as it is in a CT, but by the insulation between turns, between
layers, and between coil sections, and by the ability of the core to carry enough magnetic flux
to induce the voltage. The VT is somewhat different from the distribution transformer, and
certainly from the power transformer, in that it has a very limited capacity to store energy.
ANSI/IEEE Standard C57.13 (Work Aid 2A, Handout 1) lists the primary voltages for the 3
groups of VTs. Figure 38 summarizes the voltage ranges for the same 3 groups.
Secondary - When connected line-to-line, the nominal secondary voltage ratings of VTs are
120 V and 115 V, and when connected line-to-neutral, the nominal secondary voltages of VTs
are 69.3 (120/ ) and 66.4 V (115/ ).
Frequency
All ANSI/IEEE Standard C57.13 VT ratings are based on a system frequency of 60 Hz.
Thermal Burden
The thermal burden rating of a VT shall be specified in terms of the maximum burden in
voltamperes that the transformer can carry at rated secondary voltage without exceeding the
temperature rise, as listed in Figure 39.
30 oC Ambient 44 oC Ambient
Type of VT Average Temperature Rise Average Temperature Rise
55 oC Rise 55 oC 30 oC
80 oC Rise o
80 C
o
55 C
(Dry Type)
Establishment of standard burdens to be used for testing and comparing VTs must take into
account the two standard secondary voltage ratings of 69.3 and 120 volts. Actually,
inspection of standard VT ratings will show that there are really two voltages, 115 and 120
volts in the 120-volt class, and several voltages from 65 to 70 in the 69.3-volt class. The
standard burdens to be used for testing are rated at 120 volts and at 69.3 volts, and
ANSI/IEEE Standard C57.13 specifies that the 120-volt rated burden will be used for any
transformer with the secondary voltage in the range of 115 to 120, while the 69.3-volt burden
will be used for any transformer with the secondary voltage in the range of 65 to 72 volts.
This means that the actual voltamperes in the burden in a given test may be somewhat
different than the nominal value of the burden in voltamperes. For example, if the standard
burden is 25 voltamperes, the actual burden, when it is used for testing a transformer with a
115-volt secondary, is (115/120)2 or .918 times the nominal value of 25.
It should be noted that the burdens that are rated 69.3 volts have an impedance only 1/3 of
that of burdens rated 120 volts, and that they should not be used in testing or rating
transformers that are rated at 115 to 120 volts. Transformers rated at 115 or 120 volts should
be treated as 115-volt or 120-volt transformers, and, if they are actually used at reduced
voltage the performance will not actually be different if the 120 volt burden is used as a basis
for performance. This is because the performance of a transformer down to voltages of about
5% of its rating is not significantly different from the performance at 100% voltage.
Y 75 0.85 192 64
Z 200 0.85 72 24
Z 400 0.85 36 12
Z
Accuracy Classes
Saudi Aramco standards state that the accuracy class for VTs that are used on 13.8 kV
systems and below should be 0.3% for burden classifications W, X, Y, and Z, and the
accuracy class for VTs that are used on 34.5 kV systems and above should be 0.3% for
standard burdens W, X, Y, Z, and ZZ.
VT Fusing
Primary fuses are used with VTs primarily to take the transformer off the line in the event of
an internal failure. Although modern VTs are much less liable to fail than older ones, and
fuses therefore may never be operated due to internal transformer failure, transformer failure
may still be caused by overload or short circuit on the secondary. If such failure does occur,
it may involve other apparatus and perhaps cause an outage.
Modern fuses are much more substantial and reliable than older fuses and the chance of fuse
failure is now much smaller. Only the exceptional installation will be so dependent on
continuity of voltage that the transformer must be connected solidly to the primary circuit.
With modern fuses, the principal disadvantages are the cost of fuses and mounting and the
space required to install the fuses.
Primary fuses may be mounted on indoor transformers at the factory, or they may be in
separate mountings, which in general would increase the cost and the space that is required
for installation.
Whether to use fuses or not is determined by the operators established practice, but it appears
that operation without fuses has proven satisfactory in the majority of installations. Note:
ADP-P-121 specifies that VTs rated 13.8 kV or less shall be fused.
For outdoor VTs the same considerations apply, as to whether or not to use fuses and the fuse
rating, but separately mounted fuses in outdoor mountings must be used because the fuses are
not mounted on outdoor VTs.
The use of secondary fuses (or circuit breakers) is relatively rare and is a matter of personal
choice with the operator. Such fuses should be rated so that they will carry the secondary
current indicated by the thermal VA rating of the transformer, but should blow in a short time
at any higher current to protect the transformer. Obviously, if blowing or mechanical failure
of a fuse occurs and is not quickly detected, a considerable loss of protection may occur.
Selection Factors
System Voltage
The rated primary voltage selected for the VT depends on the nominal system voltage as well
as the ANSI Group. Work Aid 2 lists the rated primary voltages of VTs based on the Saudi
Aramco installation nominal system voltages.
Example L: Using Work Aid 2 procedures, what is the standard VT rated primary voltage
for a Saudi Aramco installation where the nominal system voltage is 34.5 kV?
Answer: Per Figure 48, the rated primary voltage of the VT should be 20.125 kV using
an ANSI Group 3 connection.
VT Data
ANSI Accuracy Class - 0.3 thru Burden Y, 0.3 thru Burden Z, etc.
Although ANSI/IEEE Standard C57.13 specifies accuracy classes of 0.3, 0.6, and 1.2 percent,
Saudi Aramco standards only permit 0.3 percent accuracy class VTs.
The accuracy class for VTs that are used on 13.8 kV systems and below should be ANSI 0.3
for ANSI standard burdens W, X, Y and Z (Ref. ADP-P-121), and the accuracy class for VTs
that are used on 34.5 kV systems and above should be ANSI 0.3 for ANSI Standard burdens
W, X, Y, Z and ZZ (Ref. ADP-P-121).
The secondary circuit load is the impedance, measured or listed in voltamperes (VA), that is
connected to the secondary side of the VT. For the purposes of this Module, the secondary
circuit load is a known (given) quantity. The standard burdens for VTs for accuracy rating
purposes are listed in Figure 40.
The thermal burden rating of the VT should be specified as the maximum possible burden that
it would be expected to carry when installed under specified ambient temperature conditions.
If the vendors descriptive literature does not state a thermal burden rating, then the thermal
burden rating should be assumed to be equal to the maximum standard burden for which an
accuracy rating is given.
Temperature
VTs should be thermally rated for direct application in Saudi Arabia (Ref: ADP-P-121). The
temperature rise requirements for VTs are listed in Figure 39.
Altitude
ANSI/IEEE Standard C57.13 states that VTs may be applied at higher altitudes than 1000
meters (m), but the performance may be affected and special consideration (e.g., vendor
consultation) should be given to these higher altitude applications.
Work Aid 1B: Vendors Data, OEM Instrument Transformer Reference Guide, SA-
11374A
Work Aid 1D: Vendors Data, Multiratio CT (1200:5) Saturation (Excitation) Curve
Work Aid 1E: Vendors Data, IL41-100I, Type CO-11 Time/Overcurrent Relay
Energy Requirements
At At At At
ONE Power Tap 3 Times 10 Times 20 Times
CONTINUOUS SECOND
Factor Value Tap Tap Tap
RATING RATING
Current
Amper Tap (AMPERES) (AMPERES) Angle f Value Value Value
e (D =0.86)
Current Current Current
Range
(D = 0.88) (D = 0.9) (D =
0.91)
Work Aid 1F: Vendors Data, DB41-081, Type IT Instantaneous Trip Overcurrent
Relay Energy Requirements
IL = kVA/( x kV) or
IL = kW/( x kV x p.f.)
Step 2. Size the continuous current rating of the CT at 150 to 200% of the load current.
Ic = 1.5 IL or 2.0 IL
Step 3. Select the next standard size window-type CT from Work Aid 1B (Handout 2),
pages 50 and 51.
Step 4. Evaluate the loading capability [Rating Factor (RF)] of the selected CT either from
Work Aid 1A (Figure 1, page 13, Handout 1) or from Work Aid 1B (Handout 2,
pages 50 and 51) at an ambient temperature of 55 oC.
Step 5. Evaluate the mechanical (short circuit) current rating (Imech). The mechanical
rating (Imech) of the selected CT must be greater than or equal to the available RMS
asymmetrical short circuit current (Iasy).
Step 6. Sketch and label the CT equivalent circuit diagram (Figure 47).
System voltage -
ZT = RS + ZB
ZB = Rwire + Rrelay
Es = IsZT
f. Determine the excitation current (Ie) from the saturation curves (Work Aids 1C
and 1D).
h. Evaluate the results. Note: This criteria is usually a judgment call; if in doubt,
pick another CT and re-evaluate the CT for saturation.
IST = IS + Ie
Work Aid 2B: Vendors Data, OEM Instrument Transformer Reference Guide, SA-
11374A
Step 2. Select a VT standard ratio from Figure 48 based on the Saudi Aramco nominal
system voltage determined from Step 1.
Aramco
Rated
Nominal
ANSI Primary Voltage
System Voltage
Group (kV RMS) Marked Ratio
(kV RMS)
Step 4. Select a burden designation from Figure 40 based on the voltamperes (VA)
calculated in Step 3.
Y 75 0.85 192 64
Z 200 0.85 72 24
ZZ 400 0.85 36 12
Step 5. Select an accuracy class of 0.3% based on Saudi Aramco requirements (ADP-P-
121).
Step 6. Select a VT from Work Aid 2B (Handout 2). Note: ADP-P-121 requires fused
type VTs for system voltages 13.8 kV.
GLOSAARY
additive polarity A term that implies that the current flowing into the
H1 primary terminal is substantially in phase with the
current flowing out of the secondary X2 terminal.
basic impulse level A factor test that shows how well an insulation system
can withstand a high voltage surge. Usually
abbreviated as BIL.
continuous current rating The amount of current that a device can allow to pass
through it without causing excessively high
temperature or equipment failure.
current limiting fuse A type of fuse that interrupts a fault current, but limits
it to some value usually well below the peak current
and it operates in one-half cycle (.008 sec) or less.
excitation losses The watts that are required to supply the energy
(instrument transformer) necessary to excite the transformer, which include the
dielectric watts, the core watts, and the watts in the
excited winding due to the excitation current.
induction disc relay A form of relay armature in the shape of a disc that
usually serves the combined function of providing an
operating torque by its location within the fields of an
electromagnet excited by the input quantities, and a
restraining force by motion within the field of a
permanent magnet.
inverse time relay A relay in which the input quantity and operating
time are inversely related throughout at least a
substantial portion of the performance range.
knee (saturation curve) The knee of a saturation curve represents the point of
voltage magnitude where the exciting current (Ie)
increases much more rapidly than the secondary
voltage (Es).
marked ratio The ratio of the rated primary value to the rated
secondary value as stated on the nameplate of an
instrument transformer.
rated voltage (voltage The primary voltage selected for the basis of
transformer) performance specifications of a voltage transformer.
rating factor (RF) A term that describes the loading capability of a CT.
RF Rating Factor
subtractive polarity A term that implies that the current flowing into the
H1 primary terminal is substantially in phase with the
current flowing out of the secondary X1 terminal.
thermal burden rating The voltampere output that the transformer will
(voltage transformer) supply continuously at rated secondary voltage
without causing the specified temperature limitations
to be exceeded.
turn ratio (current The ratio of the secondary winding turns to the
transformer) primary winding turns.
turn ratio (voltage The ratio of the primary winding turns to the
transformer) secondary winding turns.