Eaton - PF Capacitors and Detuned Filters
Eaton - PF Capacitors and Detuned Filters
Eaton - PF Capacitors and Detuned Filters
0-1
December 2015
Sheet 35 001
43
cause overcompensation on the line Total plant power factor improved Utility Billing
reduces or eliminates all forms of
27 during light load conditions
kvar charges The severity of the local electric utility
No need for separate switching. Motor tariff for power factor will affect payback
always operates with capacitor Automatic switching ensures exact
and ROI. In many areas, an optimally
28 amount of power factor correction,
designed power factor correction
eliminates overcapacitance and
system will pay for itself in less than
resulting overvoltages
two years.
29 Table 35.0-1. Summary of Advantages/Disadvantages of Individual, Fixed Banks,
Automatic Banks, Combination National Electrical Code
30 Method Advantages Disadvantages
Requirements for Capacitors
Individual Most technically efficient, most flexible Higher installation and maintenance cost
capacitors Nameplate kvar: Tolerance +15, 0%.
31 Fixed bank Most economical, fewer installations Less flexible, requires switches and/or Discharge resistors: Capacitors rated at
circuit breakers
600 V and less must reduce the charge
Automatic Best for variable loads, prevents Higher equipment cost
32 bank overvoltages, low installation cost
to less than 50 V within 1 minute of
de-energization. Capacitors rated above
Combination Most practical for larger numbers Least flexible 600 V must reduce the charge within
of motors
33 5 minutes.
Selection Criteria Load Size Continuous operation: Up to 135%
rated (nameplate) kvar, including
34 The selection of the type of capacitor Facilities with large loads benefit
the effects of 110% rated voltage
installation will depend on advan- from a combination of individual load,
(121% kvar), 15% capacitance
tages and disadvantages of each type group load and banks of fixed and
tolerance and harmonic voltages over
35 and several plant variables, including automatically-switched capacitor units.
the fundamental frequency (60 Hz).
load type, load size, load constancy, A small facility, on the other hand,
load capacity, motor starting methods may require only one capacitor at the Dielectric strength test: Twice the
36 and manner of utility billing. service entrance. rated AC voltage (or a DC voltage
4.3 times the AC rating for non-
Load Type Sometimes, only an isolated trouble
metallized systems).
37 spot requires power factor correction in
If a facility has many large motors, 50 hp applications such as welding machines, Overcurrent Protection: Fusing
and above, it is usually economical to induction heaters or DC drives. If a between 1.65 and 2.5 times rated
install one capacitor per motor and particular feeder serving a low power
38 switch the capacitor and motor together. factor load is corrected, it may raise
current to protect case from rupture.
Does not preclude NEC requirement
If there are many small motors, 1/2 to overall plant power factor enough that for overcurrent protection in all three
25 hp, motors can be grouped with
39 one capacitor at a central point in the
additional capacitors are unnecessary. ungrounded conductors.
distribution system. Often, the best Load Constancy Note: When capacitor is connected to
solution for plants with large and the load side of the motor overcurrent
40 small motors is to use both types If a facility operates around-the-clock protection, fused disconnects or breaker
of capacitor installations. and has a constant load demand, fixed protection is not required. Fuses are recom-
capacitors offer the greatest economy. mended for all other indoor applications.
41 If load is determined by eight-hour
shifts five days a week, use switched
units to decrease capacitance during
42 times of reduced load.
43
Capacitor Switching Devices ANSI Standard C37.06 (indoor oilless Projects that anticipate requiring
22
circuit breakers) indicates the preferred capacitor bank switching or fault
ratings of Eatons Type VCP-W vacuum interrupting should identify the
Low Voltage Capacitor Switching breaker. For capacitor switching breakers that must have capacitive
Circuit breakers and switches for use careful attention should be paid to current switching ratings on the 23
with a capacitor must have a current the notes accompanying the table. equipment schedules and contract
rating in excess of rated capacitor The definition of the terms are in ANSI drawings used for the project. Manu-
current to provide for overcurrent from Standard C37.04 Article 5.13 (for the facturers standard medium voltage 24
overvoltages at fundamental frequency latest edition). The application guide breakers meeting ANSI C37.xx are not
and harmonic currents. The following ANSI/IEEE Standard C37.012 covers the all rated for switching capacitive loads.
percent of the capacitor-rated current method of calculation of the quantities Special breakers are usually available 25
should be used as a general guideline: covered by C37.06 Standard. from vendors to comply with the ANSI
C37.012 (Application Guide for Capacitor
Fused and unfused Note that the definitions in C37.04 make Current Switching) and other applicable 26
switches. . . . . . . . . . . . . . . . . . . . 165% the switching of two capacitors banks ANSI standards. The use of capacitive
in close proximity to the switchgear current rated breakers can affect the
Molded-case breaker or
equivalent . . . . . . . . . . . . . . . . . . 150%
bus a back-to-back mode of switching. medium voltage switchgear layout, 27
This classification requires a definite thus early identification of these
Power circuit breakers . . . . . . . . . 135% purpose circuit breaker (breakers capacitive loads are critical to the
Insulated case circuit breakers. . . 135%
specifically designed for capacitance design process. 28
switching).
Contactors . . . . . . . . . . . . . . . . . . . 150% For example, the standard 15 kV
We recommend that such application
be referred to Eaton.
Eaton 150 VCP-W 500, 1200 A vacuum 29
The NEC, Section 460.8(c)(4), requires breaker does not have a capacitive
the disconnecting means to be rated A breaker specified for capacitor current switching rating; however,
not less than 135% of the rated capacitor switching should include as applicable: the 15 kV Eaton 150 VCP-W 25C, 30
current (for 600 V and below). See 1200 A vacuum breaker does have the
Page 35.0-4 for more information on 1. Rated maximum voltage. following general purpose ratings:
Low Voltage Capacitor Switching Devices.
2. Rated frequency. 25 A rms cable charging
31
Medium Voltage current switching
3. Rated open wire line charging
Capacitor Switching switching current. Isolated shunt capacitor bank 32
switching current ratings of
Capacitance switching constitutes 4. Rated isolated cable charging and 25 A to 600 A
severe operating duty for a circuit shunt capacitor switching current. Definite purpose back-to-back 33
breaker. At the time the breaker opens capacitor switch ratings required
at near current zero the capacitor is 5. Rated back-to-back cable charging
and back-to-back capacitor when two banks of capacitors are
fully charged. After interruption, when
switching current. independently switched from the 34
the alternating voltage on the source 15 kV switchgear bus
side of the breaker reaches its opposite 6. Rated transient overvoltage factor.
maximum, the voltage that appears The special breakers with these 35
across the contacts of the open breaker 7. Rated transient inrush current and capacitive current ratings do not have
is at least twice the normal peak line- its frequency. UL labels, thus UL assembly ratings
to-neutral voltage of the circuit. If a
8. Rated interrupting time.
are not available. 36
breakdown occurs across the open
Contact Eaton for more details
contact the arc is re-established. Due 9. Rated capacitive current on vacuum breaker and fused load
to the circuit constants on the supply switching life. interrupter switch products with 37
side of the breaker, the voltage across
10. Grounding of system and capacitive switching current ratings
the open contact can reach three times
at medium voltages.
the normal line-to-neutral voltage. capacitor bank. 38
After it is interrupted and with Loadbreak interrupter switches are
subsequent alternation of the supply permitted by ANSI/IEEE Standard
side voltage, the voltage across the C37.30 to switch capacitance but 39
open contact is even higher. they must have tested ratings for
the purpose. Refer to Eaton Type
MVS ratings. 40
41
42
43
Table 35.0-2. Recommended Wire Sizes, Switching Device Ratings Table 35.0-2. Recommended Wire Sizes, Switching Device Ratings
22 and Overcurrent Protection Device Rating for Capacitor Banks and Overcurrent Protection Device Rating for Capacitor Banks
Three-Phase 60 Hz AC System Three-Phase 60 Hz AC System (Continued)
Capacitor Rating Amperes kcmil Capacitor Rating Amperes kcmil
23 kvar Capacitor Fuse Safety Circuit Wire kvar Capacitor Fuse Safety Circuit Wire
Rated Rating 1 Switch Breaker Trip Size AWG Rated Rating 1 Switch Breaker Trip Size AWG
Current Rating Rating 2 (per phase) 3 Current Rating Rating 2 (per phase) 3
24 240 V 600 V
2.5 6 10 30 15 14 5 5 15 30 15 14
5 12 20 30 20 14 7.5 7 15 30 15 14
25 7.5 18 30 30 30 10 10 10 20 30 15 14
10 24 40 60 40 8 15 14 25 30 30 10
15 36 60 60 70 6 20 19 35 60 30 10
26 20
25
48
60
80
100
100
100
0
100
4
4
25
30
24
29
40
50
60
60
40
40
8
8
30 72 125 200 125 2 35 34 60 60 50 8
27 45
50
108
120
200
200
200
200
175
175
1/0
2/0
40
45
38
43
70
80
100
100
70
70
6
6
60 144 250 400 200 4/0 50 48 80 100 70 4
75 180 300 400 250 250 60 58 100 100 100 4
28 90 217 400 400 300 350 75 72 125 200 100 4
100 241 400 400 350 500 80 77 150 200 125 2
120 289 500 600 400 600 100 96 175 200 150 1/0
29 125 301 500 600 500 600 120 115 200 200 175 2/0
135 325 600 600 500 (2) 4/0 125 120 200 200 175 2/0
150 361 600 600 500 (2) 250 150 144 250 400 200 4/0
30 160
200
385
481
800
800
800
800
600
700
(2) 350
(2) 500
160
180
154
173
300
300
400
400
225
250
4/0
250
250 600 1000 1200 1000 (2) 600 200 192 350 400 300 350
300 720 1200 1200 1000 (4) 250 225 217 400 400 300 350
31 350 844 1400 1600 1200 (4) 350 250 241 400 400 260 500
400 965 1600 1600 1600 (4) 500 300 289 500 600 400 600
480 V 350 337 600 600 500 (2) 250
32 2 2 15 30 15 14 400 385 700 800 600 (2) 350
5 6 15 30 15 14 450 433 900 800 800 (2) 350
7.5 9 15 30 15 14 500 481 1000 1200 1000 (2) 500
33 10 12 20 30 20 14 550 529 1200 1200 1000 (2) 500
15 18 30 30 30 10 600 577 1200 1200 1000 (2) 600
20 24 40 60 40 10 660 635 1350 1600 1200 (4) 250
700 674 1400 1600 1200 (4) 250
34 25
30
30
36
50
60
60
60
50
50
6
6 720 693 1500 1600 1200 (4) 350
35 42 70 100 70 6 800 770 1600 1600 1600 (4) 500
900 866 1800 1600 1600 (4) 500
35 40
45
48
54
100
100
100
100
70
100
4
4 1000 962 2000 2000 2000 (4) 500
50 60 100 100 100 2 1100 1059 2500 2000 2000 (4) 500
60 72 125 200 100 2 1200 1155 2500 2000 2000 (4) 750
36 75 90 150 200 125 1/0 1 All feeder protection fuses are recommended to be time delay
80 96 175 200 150 1/0 fuses and sized between 150175% of the full load amperes of the
90 108 200 200 150 2/0 capacitor current.
37 100 120 200 200 175 2/0 2 All feeder protection breakers are recommended to be a minimum
120 144 250 400 200 4/0 of 135% of the full load amperes of the capacitor current.
125 150 250 400 225 4/0 3 80% rated circuit breakers should be derated for effective current rating
38 150 180 300 400 250 250
4
shown above.
Recommended size based on 90 C copper conductors applied at its
160 192 350 400 300 350
180 217 400 400 300 350 75 C rating.
200 241 400 400 350 500 5 For conductor sizes involving multiple runs of 350 kcmil per phase or
39 225 271 500 600 400 500 higher an external pull box may be required. Consult drawings for
250 301 500 600 500 600 available space for termination.
300 361 600 600 500 (2) 250
40 350 421 700 800 600 (2) 350
400 481 800 800 700 (2) 500
450 541 900 800 800 (2) 500
41 500 601 1000 1200 1000 (2) 600
550 662 1200 1200 1000 (4) 250
600 722 1200 1200 1000 (4) 250
42 660
700
794
842
1350
1400
1600
1600
1200
1200
(4) 350
(4) 350
720 866 1500 1600 1200 (4) 350
800 962 1600 1600 1600 (4) 500
43 900 1083 1800 1600 1600 (4) 500
1000 1203 2000 2000 2000 (4) 600
1100 1323 2500 2000 2000 (4) 750
1200 1443 2500 2000 2000 (4) 750
Multi-speed motors
At the Load 23
Starters with open transition and
Because capacitors act as kvar starters that disconnect/reconnect
generators, the most efficient place Fused Switch or
to install them is directly at the motor,
capacitor during cycle
Circuit Breaker 24
Motors that start frequently
where kvar is consumed. Three
options or other low power factor load Motor loads with high inertia, where
exist for installing capacitors at the disconnecting the motor with the Capacitor
25
motor. Use Figures 35.0-135.0-7, and capacitor can turn the motor into Bank
the information below to determine a self-excited generator
which option is best for each motor.
26
At the Service Feeder Figure 35.0-2. Installing Capacitors Online
Location AMotor Side of Overload Relay 1 Refer to Pages 35.0-3 and 35.0-14 for
New motor installations in which
When correcting entire plant loads, switching device considerations and 27
capacitor banks can be installed at the conductor sizing.
overloads can be sized in accor- service entrance, if load conditions
dance with reduced current draw and transformer size permits. If the 28
Existing motors when no overload amount of correction is too large,
change is required some capacitors can be installed at
Location BLine Side of Overload Relay
individual motors or branch circuits. 29
Existing motors when overload When capacitors are connected to the
rating surpasses code (see Appendix bus, feeder, motor control center or
for NEC code requirements) switchboard, a disconnect and over- 30
current protection must be provided.
31
Locating Capacitors on Motor Circuits
32
Thermal
Motor
Feed C B
Overload
A 33
Motor 34
35
Fused Safety
Switch or Breaker
Motor
Starter
36
37
38
Install at Capacitor Capacitor Capacitor
Location: C B A 39
Figure 35.0-1. Locating Capacitors on Motor Circuits
40
41
42
43
33 1 C
A
Figure 35.0-7. Reactor Starting
3 B
34 Line Note: Connect capacitor on motor side of starting contactor (1, 2, 3)
2 C at points ABC.
Motor
1
35 Start: Close 1-2-3 Stator
Run: Close 4-5-6 6
5
36 Soft Start
4
Motor
Line
37 Figure 35.0-5. Part-Winding Starting At Speed Stator
Contact
Note: Connect capacitor on motor side of starting contacts (1, 2, 3)
at points ABC.
38
39
To Capacitor
40
Figure 35.0-8. Soft Start
41 Note: Soft start application considerations. Capacitors should
only be applied after the soft start is at full voltage and the bypass
contactor is closed. An auxiliary contact on the bypass contactor is
42 used to energize the capacitor contactor. When the bypass contactor
in the soft start opens the capacitor contactor will drop out. For
multiple motors on the same bus, as in a motor control center for
example, it is desirable to take all the capacitors off line any time
43 a soft starter is accelerating or decellearting (not in bypass).
37
38
39
40
41
42
43
41
42
43
38
39
40
41
42
43
35 120 2
kvar (120) = kvar (240) --------- = 0.25
240
36 (10 kvar @ 240 V = 2.5 kvar @ 120 V)
(b) Frequency Reduction:
37
kvar (50 Hz) = kvar (60 Hz) ------ = 0.83
50
60
38 (60 kvar @ 480 V 60 Hz = 50 kvar, 480 V, 50 Hz)
39
40
41
42
43
40
41
42
43
Table 35.0-4. Suggested Capacitor Ratings, in kvars, for NEMA Design C, D and Wound-Rotor Motors
22 Induction Design C Motor Design D Motor Wound-Rotor
Motor Rating (hp) 1800 and 1200 r/Minimum 900 r/Minimum 1200 r/Minimum Motor
23 15 5 5 5 5.5
20 5 6 6 7
25 6 6 6 7
24 30
40
7.5
10
9
12
10
12
11
13
50 12 15 15 17.5
60 17.5 18 18 20
25 75 19 22.5 22.5 25
100 27 27 30 33
125 35 37.5 37.5 40
26 150 37.5 45 45 50
200 45 60 60 65
250 54 70 70 75
27 300 65 90 75 85
Note: Applies to three-phase, 60 Hz motors when switched with capacitors as single unit.
Note: Use motor manufacturers recommended kvar as published in the performance data sheets for specific motor types:
28 drip-proof, TEFC, severe duty, high efficiency and NEMA design.
Table 35.0-5. 2400 Volts and 4160 Volt Motors NEMA Design B
29 Nominal Motor Speed in RPM and Number of Poles
Induction 3600 RPM 2 1800 RPM 4 1200 RPM 6 900 RPM 8 720 RPM 10 600 RPM 12
Motor kvar Current kvar Current kvar Current kvar Current kvar Current kvar Current
Rating (hp)
30 Reduction % Reduction % Reduction % Reduction % Reduction % Reduction %
100 25 8 25 10 25 11 25 11 25 12 25 16
120 25 7 25 9 25 10 25 10 25 11 50 15
31 150 25 7 25 8 25 9 25 9 25 11 50 14
200 50 7 50 8 50 9 50 9 50 10 75 14
250 50 7 50 7 50 8 75 9 75 10 75 14
32 300
350
50
50
7
6
50
50
7
6
75
75
8
8
75
75
9
9
75
75
9
9
100
100
13
12
400 75 6 75 6 75 7 100 9 100 9 100 11
450 75 6 75 6 75 6 100 9 100 9 125 10
33 500 75 5 75 6 100 6 125 9 125 9 125 9
600 75 5 100 6 100 6 125 8 150 9 150 9
700 100 5 100 6 125 6 150 8 150 8 150 8
34 800
900
100
125
5
5
150
150
6
6
150
200
6
6
150
200
7
7
200
250
8
8
200
250
8
8
1000 150 5 200 6 250 5 250 6 250 7 250 7
1250 200 5 200 6 250 5 300 6 300 6 300 6
35
Table 35.0-6. NEMA Design B and C 2300 and 4000 V Motors (after 1956)
Nominal Motor Speed in RPM and Number of Poles
36 Induction 3600 RPM 2 1800 RPM 4 1200 RPM 6 900 RPM 8 720 RPM 10 600 RPM 12
Motor kvar Current kvar Current kvar Current kvar Current kvar Current kvar Current
Rating (hp) Reduction % Reduction % Reduction % Reduction % Reduction % Reduction %
37 NEMA Design B 2300 and 4000 V Motors (after 1956)
100 25 7 25 10 25 11 25 11 25 12 25 17
38 120
150
25
25
7
7
25
25
9
8
25
25
10
8
25
25
10
9
25
50
11
11
50
50
15
15
200 25 7 25 6 50 8 50 9 50 10 75 14
250 30 7 30 5 50 8 50 9 75 10 100 14
39 300 50 7 50 5 75 8 75 9 75 9 100 12
350 50 6 50 5 75 8 75 9 75 9 100 11
400 50 5 50 5 75 6 100 9 100 9 100 10
450
40 500
75
75
5
5
50
75
5
5
75
100
6
6
100
125
8
8
100
125
8
8
100
125
8
8
600 75 5 100 5 100 5 125 7 125 8 125 8
700 100 5 100 5 100 5 125 7 150 8 150 8
41 800 100 5 125 5 125 5 150 7 150 8 150 8
900 125 5 150 5 200 5 200 6 250 7 250 7
1000 150 5 200 5 250 5 250 6 250 7 250 7
1250 200 5 200 5 250 5 300 6 300 6 300 6
42 NEMA Design C 2300 and 4000 V Motors (after 1956)
100 25 11 25 11 25 11 25 11
43 125
150
25
25
11
9
25
25
11
9
25
50
11
9
25 11
200 50 9 50 9 50 9
250 50 8 50 9 50 9
300 50 6 75 9 75 9
350 50 6 75 8 75 9
Table 35.0-7. Multipliers to Determine Capacitor Kilovars Required for Power Factor Correction
Original Corrected Power Factor 22
Power 0.80 0.81 0.82 0.83 0.84 0.85 0.86 0.87 0.88 0.89 0.90 0.91 0.92 0.93 0.94 0.95 0.96 0.97 0.98 0.99 1.0
Factor
0.50 0.982 1.008 1.034 1.060 1.086 1.112 1.139 1.165 1.192 1.220 1.248 1.276 1.306 1.337 1.369 1.403 1.440 1.481 1.529 1.589 1.732
23
0.51 0.937 0.962 0.989 1.015 1.041 1.067 1.094 1.120 1.147 1.175 1.203 1.231 1.261 1.292 1.324 1.358 1.395 1.436 1.484 1.544 1.687
0.52 0.893 0.919 0.945 0.971 0.997 1.023 1.050 1.076 1.103 1.131 1.159 1.187 1.217 1.248 1.280 1.314 1.351 1.392 1.440 1.500 1.643
0.53 0.850 0.876 0.902 0.928 0.954 0.980 1.007 1.033 1.060 1.088 1.116 1.144 1.174 1.205 1.237 1.271 1.308 1.349 1.397 1.457 1.600 24
0.54 0.809 0.835 0.861 0.887 0.913 0.939 0.966 0.992 1.019 1.047 1.075 1.103 1.133 1.164 1.196 1.230 1.267 1.308 1.356 1.416 1.559
0.55 0.769 0.795 0.821 0.847 0.873 0.899 0.926 0.952 0.979 1.007 1.035 1.063 1.093 1.124 1.156 1.190 1.227 1.268 1.316 1.376 1.519
0.56 0.730 0.756 0.782 0.808 0.834 0.860 0.887 0.913 0.940 0.968 0.996 1.024 1.054 1.085 1.117 1.151 1.188 1.229 1.277 1.337 1.480 25
0.57 0.692 0.718 0.744 0.770 0.796 0.822 0.849 0.875 0.902 0.930 0.958 0.986 1.016 1.047 1.079 1.113 1.150 1.191 1.239 1.299 1.442
0.58 0.655 0.681 0.707 0.733 0.759 0.785 0.812 0.838 0.865 0.893 0.921 0.949 0.979 1.010 1.042 1.076 1.113 1.154 1.202 1.262 1.405
0.59 0.619 0.645 0.671 0.697 0.723 0.749 0.776 0.802 0.829 0.857 0.885 0.913 0.943 0.974 1.006 1.040 1.077 1.118 1.166 1.226 1.369
26
0.60 0.583 0.609 0.635 0.661 0.687 0.713 0.740 0.766 0.793 0.821 0.849 0.877 0.907 0.938 0.970 1.004 1.041 1.082 1.130 1.190 1.333
0.61 0.549 0.575 0.601 0.627 0.653 0.679 0.706 0.732 0.759 0.787 0.815 0.843 0.873 0.904 0.936 0.970 1.007 1.048 1.096 1.156 1.299
0.62 0.516 0.542 0.568 0.594 0.620 0.646 0.673 0.699 0.726 0.754 0.782 0.810 0.840 0.871 0.903 0.937 0.974 1.015 1.063 1.123 1.266
0.63 0.483 0.509 0.535 0.561 0.587 0.613 0.640 0.666 0.693 0.721 0.749 0.777 0.807 0.838 0.870 0.904 0.941 0.982 1.030 1.090 1.233 27
0.64 0.451 0.474 0.503 0.529 0.555 0.581 0.608 0.634 0.661 0.689 0.717 0.745 0.775 0.806 0.838 0.872 0.909 0.950 0.998 1.068 1.201
0.65 0.419 0.445 0.471 0.497 0.523 0.549 0.576 0.602 0.629 0.657 0.685 0.713 0.743 0.774 0.806 0.840 0.877 0.918 0.966 1.026 1.169
0.66 0.388 0.414 0.440 0.466 0.492 0.518 0.545 0.571 0.598 0.626 0.654 0.682 0.712 0.743 0.775 0.809 0.846 0.887 0.935 0.995 1.138 28
0.67 0.358 0.384 0.410 0.436 0.462 0.488 0.515 0.541 0.568 0.596 0.624 0.652 0.682 0.713 0.745 0.779 0.816 0.857 0.905 0.965 1.108
0.68 0.328 0.354 0.380 0.406 0.432 0.458 0.485 0.511 0.538 0.566 0.594 0.622 0.652 0.683 0.715 0.749 0.786 0.827 0.875 0.935 1.078
0.69 0.299 0.325 0.351 0.377 0.403 0.429 0.456 0.482 0.509 0.537 0.565 0.593 0.623 0.654 0.686 0.720 0.757 0.798 0.846 0.906 1.049 29
0.70 0.270 0.296 0.322 0.348 0.374 0.400 0.427 0.453 0.480 0.508 0.536 0.564 0.594 0.625 0.657 0.691 0.728 0.769 0.817 0.877 1.020
0.71 0.242 0.268 0.294 0.320 0.346 0.372 0.399 0.425 0.452 0.480 0.508 0.536 0.566 0.597 0.629 0.663 0.700 0.741 0.789 0.849 0.992
0.72
0.73
0.214
0.186
0.240
0.212
0.266
0.238
0.292
0.264
0.318
0.290
0.344
0.316
0.371
0.343
0.397
0.369
0.424
0.396
0.452
0.424
0.480
0.452
0.508
0.480
0.538
0.510
0.569
0.541
0.601
0.573
0.635
0.607
0.672
0.644
0.713
0.685
0.761
0.733
0.821
0.793
0.964
0.936
30
0.74 0.159 0.185 0.211 0.237 0.263 0.289 0.316 0.342 0.369 0.397 0.425 0.453 0.483 0.514 0.546 0.580 0.617 0.658 0.706 0.766 0.909
0.75 0.132 0.158 0.184 0.210 0.236 0.262 0.289 0.315 0.342 0.370 0.398 0.426 0.456 0.487 0.519 0.553 0.590 0.631 0.679 0.739 0.882
0.76 0.105 0.131 0.157 0.183 0.209 0.235 0.262 0.288 0.315 0.343 0.371 0.399 0.429 0.460 0.492 0.526 0.563 0.604 0.652 0.712 0.855 31
0.77 0.079 0.105 0.131 0.157 0.183 0.209 0.236 0.262 0.289 0.317 0.345 0.373 0.403 0.434 0.466 0.500 0.537 0.578 0.626 0.685 0.829
0.78 0.052 0.078 0.104 0.130 0.156 0.182 0.209 0.235 0.262 0.290 0.318 0.346 0.376 0.407 0.439 0.473 0.510 0.551 0.599 0.659 0.802
0.79 0.026 0.052 0.078 0.104 0.130 0.156 0.183 0.209 0.236 0.264 0.292 0.320 0.350 0.381 0.413 0.447 0.484 0.525 0.573 0.633 0.776 32
0.80 0.000 0.026 0.052 0.078 0.104 0.130 0.157 0.183 0.210 0.238 0.266 0.294 0.324 0.355 0.387 0.421 0.458 0.499 0.547 0.609 0.750
0.81 0.000 0.026 0.052 0.078 0.104 0.131 0.157 0.184 0.212 0.240 0.268 0.298 0.329 0.361 0.395 0.432 0.473 0.521 0.581 0.724
0.82
0.83
0.000 0.026
0.000
0.052
0.026
0.078
0.052
0.105
0.079
0.131
0.105
0.158
0.132
0.186
0.160
0.214
0.188
0.242
0.216
0.272
0.246
0.303
0.277
0.335
0.309
0.369
0.343
0.406
0.380
0.447
0.421
0.495
0.469
0.555
0.529
0.698
0.672
33
0.84 0.000 0.026 0.053 0.079 0.106 0.134 0.162 0.190 0.220 0.251 0.283 0.317 0.354 0.395 0.443 0.503 0.646
0.85
0.86
0.000 0.027 0.053 0.080
0.000 0.026 0.053
0.108
0.081
0.136
0.109
0.164
0.137
0.194
0.167
0.225
0.198
0.257
0.230
0.291
0.264
0.328
0.301
0.369
0.342
0.417
0.390
0.477
0.450
0.620
0.593
34
0.87 0.000 0.027 0.055 0.083 0.111 0.141 0.172 0.204 0.238 0.275 0.316 0.364 0.424 0.567
0.88 0.000 0.028 0.056 0.084 0.114 0.145 0.177 0.211 0.248 0.289 0.337 0.397 0.540
0.89 0.000 0.028 0.056 0.086 0.117 0.149 0.183 0.220 0.261 0.309 0.369 0.512 35
0.90 0.000 0.028 0.058 0.089 0.121 0.155 0.192 0.233 0.281 0.341 0.484
0.91 0.000 0.030 0.061 0.093 0.127 0.164 0.205 0.253 0.313 0.456
0.92 0.000 0.031 0.063 0.097 0.134 0.175 0.223 0.283
0.252
0.426
0.395
36
0.93 0.000 0.032 0.066 0.103 0.144 0.192
0.94 0.000 0.034 0.071 0.112 0.160 0.220 0.363
0.95
0.96
0.000 0.037 0.079 0.126
0.000 0.041 0.089
0.186
0.149
0.329
0.292
37
0.97 0.000 0.048 0.108 0.251
0.98 0.000 0.060 0.203
0.99 0.000 0.143 38
Note: To obtain required capacitor kvar:
1. Get PF correction factor from Table 35.0-7 above.
2. Required capacitor kvar = kW load x factor. 39
How Much kvar Do I Need? 3. Multiply that number by 4. You need 250 kvar to bring your
The unit for rating power factor
kW demand. plant to 95% power factor. 40
capacitors is kvar, equal to 1000 volt- Example: If you dont know the existing power
amperes of reactive power. The kvar
If your plant consumed 410 kW, was
factor level of your plant, you will 41
rating signifies how much reactive have to calculate it before using the
power the capacitor will provide. currently operating at 73% power factor table above. To calculate existing
and you wanted to correct power factor
Instructions: to 95%, you would:
power factor: 42
kW divided by kVA = Power Factor.
1. Find the present power factor 1. Find 0.73 in column 1. A power factor sizing and ROI
in column 1. calculator is available on-line at
43
2. Read across to 0.95 column.
2. Read across to optimum power www.eaton.com/pfc.
factor column. 3. Multiply 0.607 by 410 = 249
(round to 250).
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
22 Dimensions
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Figure 35.1-1. UNIPUMPDimensions in Inches (mm)
40
Table 35.1-2. UNIPUMP Dimension Chart
41 Case
Size
Dimensions in Inches (mm)
A B C D
43
33
34
35
36
37
38
39
40
41
42
43
35
36
37
38
39
40
41
42
43
Notes:
39 Unfused units available up to 100 kvar at 480 V
480 V units above 50 kvar have 525 V capacitor cells
41
42
43
UNIPAK Low Voltage Fixed Capacitor Banks UNIPAKWith Heavy Duty Cells
Table 35.1-5. 600 Vac UNIPAK Selection Chart Table 35.1-6. Low Voltage Fixed Capacitor Systems
22
kvar Rated Enclosure Shipping Weight Catalog with Heavy Duty Cells
Current Size in Lb (kg) Number kvar Rated Current Enclosure Shipping Catalog 23
(Amperes) Size Weight Number
5 4.9 A1 19 (9) 563PMURF in Lb (kg)
7.5 7.4 A1 19 (9) 7X63PMURF
10 9.8 A1 20 (9) 1063PMURF 240 V 24
12.5 12.3 A1 20 (9) 12X63PMURF 15 36 B1 38.4 (17) 1523HURF
15 14.7 A2 29 (13) 1563PMURF 25 60 B1 38.4 (17) 2523HURF
17.5 17.2 A2 29 (13) 17X63PMURF 30 72 C1 55.2 (25) 3023HURF 25
20 19.6 A2 30 (14) 2063PMURF 50 120 C1 57.6 (26) 5023HURF
22.5 22.1 B1 44 (20) 22X63PMURF 60 144 C2 100.8 (46) 6023HURF
75 180 C2 104.4 (47) 7523HURF
25 24.5 B1 31 (14) 2563PMURF
100 240 D1 136.8 (62) 10023HURF
26
27.5 27 B1 44 (20) 27X63PMURF
30 29.4 B1 45 (20) 3063PMURF 125 300 E1 189.6 (86) 12523HURF
32.5 31.9 B1 45 (20) 32X63PMURF 480 V 27
35 34.3 B1 46 (21) 3563PMURF 15 18 B1 25.2 (11) 1543HURF
37.5 36.8 B1 46 (21) 37X63PMURF 25 30 B1 37.2 (17) 2543HURF
40 39.2 B1 47 (21) 4063PMURF 30 36 B1 38.4 (17) 3043HURF
28
42.5 41.7 B1 47 (22) 42X63PMURF 50 60 C1 39.6 (18) 5043HURF
45 44.1 B1 48 (22) 4563PMURF 60 72 C1 52.8 (24) 6043HURF
50 49 B1 48 (22) 5063PMURF 75 90 C2 55.2 (25) 7543HURF
55 53.9 C1 64 (29) 5563PMURF 100 120 C2 57.6 (26) 10043HURF
29
60 58.8 C1 64 (29) 6063PMURF 125 150 D1 100.8 (46) 12543HURF
65 63.7 C1 65 (30) 6563PMURF 150 180 D1 104.4 (47) 15043HURF
70 68.6 C1 65 (30) 7063PMURF 200 240 E1 136.8 (62) 20043HURF
30
75 73.5 C1 66 (30) 7563PMURF 250 300 E1 186.0 (84) 25043HURF
80 78.4 C1 68 (31) 8063PMURF
600 V
85 83.3 C1 68 (31) 8563PMURF 31
15 15 B1 37.2 (17) 1563HURF
90 88.2 C1 69 (31) 9063PMURF
25 24.5 B1 38.4 (17) 2563HURF
100 98 C1 69 (31) 10063PMURF
30 29.4 B1 39.6 (18) 3063HURF
120 117.6 C2 99 (45) 12063PMURF
50 49 C1 55.2 (25) 5063HURF
32
125 122.5 C2 100 (46) 12563PMURF
14063PMURF 60 58.8 C1 57.6 (26) 6063HURF
140 137.2 C2 101 (46)
75 73.5 C2 100.8 (46) 7563HURF
150 147 C2 103 (47) 15063PMURF
100 98 C2 104.4 (47) 10063HURF
33
160 156.8 D1 135 (61) 16063PMURF
180 176.4 D1 137 (62) 18063PMURF 125 122.5 D1 136.8 (62) 12563HURF
150 147 D1 136.8 (62) 15063HURF
200 196 D1 140 (64) 20063PMURF
200 196 E1 186.0 (84) 20063HURF
34
225 220.5 D1 143 (65) 22563PMURF
250 245 E1 170 (77) 25063PMURF 250 245 E1 189.6 (86) 25063HURF
300
350
294
343
E1
E1
175 (80)
182 (83)
30063PMURF
35063PMURF
Notes: 35
400 392 E1 189 (86) 40063PMURF Replaceable fuses and indicator lights standard
Internally fused only also available for some ratings
Notes: please consult the factory
36
Unfused units available up to 100 kvar at 600 V Ratings based on 60 Hz operation
Ratings based on 60 Hz operation 37
38
39
40
41
42
43
30 200
250
240
300
E1
E1
146.8 (66.6)
196.0 (89.0)
S
T
330.0 (149.8)
570.0 (258.8)
476.8 (216.5)
766.0 (347.8)
200432HMURFY
250432HMURFY
600 V
31 15
25
15
24.5
B1
B1
47.2 (21.4)
48.4 (22.0)
R
R
90.0 (40.9)
90.0 (47.7)
137.2 (62.3)
153.4 (69.6)
15632HMURFY
25632HMURFY
30 29.4 B1 49.6 (22.5) R 105.0 (49.9) 159.6 (72.5) 30632HMURFY
32 50
60
49
58.8
C1
C1
65.2 (29.6)
67.6 (30.7)
R
R
110.0 (59.0)
130.0 (72.6)
195.2 (88.6)
227.6 (103.3)
50632HMURFY
60632HMURFY
75 73.5 C2 110.8 (50.3) R 160.0 (84.0) 295.8 (134.3) 75632HMURFY
33 100
150
98
147
C2
D1
114.4 (51.9)
146.8 (66.6)
R
S
185.0 (109.0)
280.0 (127.1)
354.4 (160.9)
426.8 (193.8)
100632HMURFY
150632HMURFY
200 196 E1 196.0 (89.0) T 330.0 (149.8) 526.0 (238.8) 200632HMURFY
250 245 E1 199.6 (90.6) T 570.0 (258.8) 769.6 (349.4) 250632HMURFY
34
Notes:
Other ratings available, please consult factory
35 Units in table above are 60 Hz
36
Power Lines from Disconnect
37 Lugs
Fuses
38
39 Reactor Enclosure
Low Voltage Fixed Capacitor Banks and Fixed Harmonic FiltersDimensions in Inches (mm)
22
23
24
25
26
27
28
29
30
31
32
33
Figure 35.1-4. Case A1, A2 Figure 35.1-5. Case B1
34
35
36
37
38
39
40
41
42
43
Low Voltage Fixed Capacitor Banks and Fixed Harmonic FiltersDimensions in Inches (mm)
22
23
24
25
26
27
28
29
30
31
32
33
Figure 35.1-6. Case C1, C2 Figure 35.1-7. Case D1, E1
34 Table 35.1-9. UNIPAK Enclosures
Case Dimensions in Inches (mm)
Size
35 A B D E F H L X1 X2 X3 Y Z
A1 5.30 8.50 3.50 3.80 10.60 17.30 6.80 2.00 N/A N/A 7.70 7.20
(133.5) (215.9) (88.7) (96.8) (270.2) (439.4) (173.9) (51.5) (195.6) (181.7)
36 A2 6.00 8.50 5.60 4.50 13.30 22.30 6.80 2.30 N/A N/A 7.70 7.20
(151.2) (215.9) (141.9) (114.6) (336.7) (567.6) (173.9) (58.3) (195.6) (181.7)
B1 11.10 10.10 5.80 9.60 15.70 25.30 8.50 4.10 4.50 N/A 9.30 8.80
37 (280.8) (257.3) (148.0) (244.1) (399.0) (642.6) (215.3) (104.4) (114.3) (237.0) (223.1)
C1 10.60 12.10 7.10 9.10 16.20 26.30 10.40 3.40 1.10 3.6 11.30 10.70
(270.4) (306.8) (180.0) (231.5) (412.5) (668.0) (264.8) (86.9) (27.3) (92.0) (286.5) (272.6)
38 C2 12.00 19.30 16.90 9.50 16.30 36.00 17.70 3.00 1.50 3.8 18.30 18.00
(304.2) (490.7) (428.3) (240.5) (413.0) (914.4) (448.8) (75.3) (38.1) (95.3) (465.3) (456.5)
D1 16.80 19.30 16.90 14.60 N/A 36.00 17.70 5.10 2.40 5.0 18.30 N/A
39 (426.6) (490.7) (428.3) (370.1) (914.4) (448.8) (129.1) (59.7) (127.9) (465.3)
E1 22.30 24.40 16.80 19.50 N/A 36.00 22.70 6.50 4.40 5.0 22.40 N/A
(566.4) (618.7) (425.5) (494.1) (914.4) (576.7) (165.1) (111.9) (127.0) (567.9)
40
Legend:
41 A = Total depth H = Total height
B = Total width L = Width without feet and brackets
42 D = Height of removable front cover X = Depth between front and rear mounting holes in inches
E = Depth of feet Y = Width between floor mounting holes
43 F = Height of middle mounting hole in wall bracket Z = Width between wall bracket mounting holes
AUTOVAR 300 Power line interconnect: Rugged, Visual indication of insufficient kvar
22
power distribution block connection. to reach target power factor
Automatic Power Factor Typical power distribution block can Automatic sensing of kvar values
Correction Capacitor Systems accommodate phase wire sizes from per step
23
4 AWG to 500 kcmil; typical ground Optional communications capable
lug can accommodate wire sizes controller (RS-485/Modbus)
from 14 AWG to 2/0 AWG. Consult
equipment approval drawings for Standard metering capability: 24
actual lug size Voltage
Control wiring: UL type MTW/AWM, Current (sensed phase only)
CSA TEW 105 C copper wire is Frequency
25
standard
Active power (kW)
Fusing: 200,000 A interrupting Reactive power (kvar 26
capacity provided on all three
Apparent power (kVA)
phases of each stage. Blade-type
fuses mounted on insulator Total voltage harmonic distortion 27
stand-offs with cleared-fuse (VTHD)
indicating lights Individual harmonic voltage
distortion (odd orders up to the 28
Cleared-fuse lights: Cleared-fuse
neon indicating lights for each 19th harmonic)
Built-in manual mode allows for
phase and stage located on the door
testing and manual operation
29
Door interlock: Door interlock auto- of stages
matically disengages capacitors.
Power continues to be provided to
Multiple user-friendly alarm 30
displays. Controller provides
the unit until the disconnect is open
easy-to-understand alarms for
Exhaust fan: Provides ventilation; various conditions, such as: 31
AUTOVAR 300 dust filtering included Undervoltage or overvoltage
Undercurrent or overcurrent
General Description Safety: Ground fault interruption 32
provides protection in case of Target power factor not met
Automatically switched power factor accidental contact with control Harmonic overload
correction systems for low voltage power and ground
Faulty step/stages
33
applications. Conduit/cable entry: Available in Overtemperature alarm
top/side cable entry
Wallmount design is ideal for 34
minimum space requirements Thermal sensing: Built-in thermal Contactor
Programmable to automatically sensing, alarming, and protection Fully rated for capacitor switching
add/subtract capacitor stages to feature allows the unit to operate in Integral pre-charge/pre-insertion 35
maintain preset target power factor optimal temperature while alerting module standard. The contactor
Heavy-duty, three-phase capacitor the user of ambient temperature reduces damaging switching
construction exceeding the nominal operating transients, providing safety and 36
Five-year warranty of cells against
range. Stages will be automatically durability for the system
manufacturing defects switched off if temperature exceeds
Lessens the chance of disrupting 37
the maximum specified temperature
sensitive electronic equipment
Temperature range: The operating
Application Description Reduced inrush current extends
temperature range is 20 C to the life of the capacitor cells 38
AUTOVAR 300 is an ideal capacitor +46 C, and the storage temperature
bank to automatically regulate power range is 40 C to +55 C. For optimal Options
factor where floor space is limited and equipment life, the temperature
Optional main molded-case 39
expansion of the facilitys electrical should not exceed 35 C annual
average, and the environment circuit breaker
load is not expected.
should not exceed Pollution NEMA 3R weather-resistant enclosure 40
Degree 2 as defined in UL 61010-1 Hand-Off-Auto switches
Features Remote alarm relay terminal block
Controller Communications capable controller 41
Configuration Visual indication of incorrect
Cabinet: Wallmounting 12 gauge CT polarity Support and Service
steel with ANSI 61 gray, NEMA 1 Digital display of power factor and
42
Renewal parts are available through
(gasketed) number of energized stages local Eaton distributors
Automatic setting of c/k value Factory trained service personnel 43
(sensitivity based on CT ratio and are available through Eatons
kvar available) Electrical Services & Systems
22
Contactor Standards and Certifications
Fully rated for capacitor switching
AUTOVAR 600UL and CSA listed
Integral pre-charge/pre-insertion
ContactorUL/CSA recognized;
23 module standard. The contactor
IEC 6b rated
reduces damaging switching
transients, providing safety and Entire cabinet assembly is UL 508A
24 durability for the system and CSA C22.2 No. 190 Listed
Lessens the chance of disrupting Capacitors are UL 810 recognized
sensitive electronic equipment
25 Reduced inrush current extends
the life of the capacitor cells
26 Additional Features
Optional molded-case main circuit
27 breaker
Ground fault interruption provides
protection in case of accidental con-
28 tact with control power and ground
Control wiringstandard NEC color-
coded modular bundles with quick
29 disconnect feature for ease of trouble-
shooting or ease of expendability.
UL type MTW/AWM, CSA TEW 105 C
30 copper wire is standard
Optional digital meteringIQ 250
31 Mechanical wire lugs are included
as standard equipment. Typical
phase lugs range from (2) 6 AWG
32 350 kcmil to (4) 3 AWG750 kcmil.
Typical ground lug can accept wire
from 6 AWG to 350 kcmil. Lugs are
33 compatible with copper wire 90 C Modular Step Nest Assembly
Heavy-duty capacitor cells are
standard on AUTOVAR detuned
34 filter and optional on AUTOVAR 600.
For 480 V units, standard-duty cells
are 525 V rated, and heavy-duty cells
35 are 600 V rated
39
40
41
42
Bottom Entry Location
43
42
43
Table 35.2-5. AUTOVAR 600 Floor-Mounted Switched Capacitor Banks Units with Heavy-Duty CellsLow Voltage Applications
22 kvar Step x kvar Rated Enclosure Size 1 Base Base Catalog
Current NEMA 1, without NEMA 1, with NEMA 3R, NEMA 1, with Shipping Number
Amperes Main Breaker, Main Breaker, without Main Main Breaker, Weight in (NEMA 1,
23 No Suffix M Suffix Breaker, W Suffix MW Suffix Lb (kg) no options)
240 Vac
24 75
100
3 x 25
4 x 25
180
240
L
L
L
L
L
L
L
L
659 (298.9)
712 (323.0)
75TPHSR231
100TPHSR231
125 5 x 25 300 L L L L 765 (347.0) 125TPHSR231
150 6 x 25 361 L L L L 818 (371.0) 150TPHSR231
25 200 8 x 25 481 L L L L 924 (419.1) 200TPHSR231
250 10 x 25 601 L L L L 994 (450.9) 250TPHSR231
300 12 x 25 720 L L L L 1082 (490.8) 300TPHSR231
26 350 7 x 50 844 L KK KK KK 1686 (764.8) 350TPHSR231
400 8 x 50 965 KK C/F KK C/F 1784 (809.2) 400TPHSR231
480 Vac
27 100 2 x 50 120 L L L L 617 (279.9) 100TPHSR431
150 3 x 50 180 L L L L 677 (307.1) 150TPHSR431
200 4 x 50 240 L L L L 736 (333.8) 200TPHSR431
28 250 5 x 50 300 L L L L 795 (360.6) 250TPHSR431
300 6 x 50 360 L L L L 854 (387.4) 300TPHSR431
350 7 x 50 420 L L L L 913 (414.1) 350TPHSR431
29 400 8 x 50 480 L L L L 972 (440.9) 400TPHSR431
450 9 x 50 540 L L L L 1031 (467.7) 450TPHSR431
500 10 x 50 600 L L L L 1094 (496.2) 500TPHSR431
30 550 11 x 50 660 L L L L 1149 (521.2) 550TPHSR431
600 12 x 50 720 L L L L 1202 (545.2) 600TPHSR431
700 14 x 50 792 L KK KK KK 1826 (828.3) 700TPHSR431
31 800 8 x 100 462 KK C/F KK C/F 1944 (881.8) 800TPHSR431
900 9 x 100 1083 KK C/F KK C/F 2062 (935.3) 900TPHSR431
1000 10 x 100 1203 KK C/F KK C/F 2198 (997.0) 1000TPHSR431
32 1100
1200
11 x 100
12 x 100
1323
1443
KK
KK
C/F
C/F
KK
KK
C/F
C/F
2296 (1041.4)
2404 (1090.4)
1100TPHSR431
1200TPHSR431
600 Vac
33 100 2 x 50 96 L L L L 617 (279.9) 100TPHSR631
150 3 x 50 144 L L L L 677 (307.1) 150TPHSR631
200 4 x 50 192 L L L L 736 (333.8) 200TPHSR631
34 250 5 x 50 240 L L L L 795 (360.6) 250TPHSR631
300 6 x 50 288 L L L L 854 (387.4) 300TPHSR631
350 7 x 50 336 L L L L 913 (414.1) 350TPHSR631
35 400
450
8 x 50
9 x 50
384
432
L
L
L
L
L
L
L
L
972 (440.9)
1031 (467.7)
400TPHSR631
450TPHSR631
500 10 x 50 480 L L L L 1094 (496.2) 500TPHSR631
36 550
600
11 x 60
12 x 50
529
576
L
L
L
L
L
L
L
L
1149 (521.2)
1202 (545.2)
550TPHSR631
600TPHSR631
700 7 x 100 672 L KK KK KK 1826 (828.3) 700TPHSR631
800 8 x 100 768 KK KK KK KK 1944 (881.8) 800TPHSR631
37 900 9 x 100 864 KK KK KK KK 2062 (935.3) 900TPHSR631
1000 10 x 100 962 KK C/F KK C/F 2198 (997.0) 1000TPHSR631
1100 11 x 100 1058 KK C/F KK C/F 2296 (1041.4) 1100TPHSR631
38 1200 12 x 100 1155 KK C/F KK C/F 2404 (1090.4) 1200TPHSR631
1 Enclosure sizing for units with integrated surge protection or bottom entry can vary and may not be available on all kvar sizes.
Contact Eatons Technical Resource Center at 1-800-809-2772, choose option #4, then option #2.
39 C/F = Consult factory
40
41
42
43
32
33
34
35
36
37
38
39
40
41
42
43
23
Standard Customer Conduit
Entry in This Area Option W NEMA 3R
24 Drip Shield
Power
POWER
Conductor
25
FACTOR
CORRECTION
Exhaust
69B1007G01
Lugs
1 Power Factor Controller
BLR-ACX
R
2 Option M
26
esc
DANGER
Molded-Case Ground
HIGH VOLTAGE
CAUTION
Circuit Breaker Lug
DISCONNECT
BEFORE SERVICING
27
78.00
(1981.2)
28
Copper
Busbar
29
30
A A
38.50 Dust/Air Filter Tray 25.00
31 (977.9) (635.0)
35
Figure 35.2-3. AUTOVAR L (Single Door) Enclosure
36
37
38
39
40
41
42
43
23
Conductor Exhaust 25
1 R
Lugs Ground
Power Factor Controller
Lug
BLR-ACX
2
26
esc
Option M
Molded-Case 78.00
Circuit Breaker (1981.2) 27
Copper
Busbar
28
29
A A
30
25.00
Dust/Air Filter Tray (635.0)
77.64 (1972.0)
31
80.40 (2042.1) Legend
1. Controller
Mounting Holes 2. On/Off Switch
3. Cleared Fuse Indicating Lights
32
0.438-Inch Dia. Typ.
25.00 16.00 Air Filter Air Filter
(635.0) (406.4) Notes:
1. 6-Inch Minimum Clearance Each Side 33
2. 45-Inch Front Clearance or per Local Code
Section A-A
34
35
Figure 35.2-4. AUTOVAR KK (One Double Door) Enclosure
36
37
38
39
40
41
42
43
Ease of replacement: Cells can be Multiple user-friendly alarm Mechanical wire lugs are included as
easily replaced individually by displays. Controller provides standard equipment. Typical phase 22
removing the mounting bolt and easy-to-understand alarms for lugs range from (2) 6 AWG350 kcmil
lifting out of the nest without removal various conditions, such as: to (4) 3 AWG750 kcmil. Typical
of any other components Undervoltage or overvoltage ground lug can accept wire from 23
Thermal sensing: Built-in thermal 6 AWG to 350 kcmil. Lugs are
Undercurrent or overcurrent
sensing, alarming, and protection compatible with copper wire 90 C
feature allows the unit to operate in Target power factor not met
Heavy-duty capacitor cells are 24
optimal temperature while alerting Harmonic overload standard on AUTOVAR detuned
the user of ambient temperature Faulty step/stages filter and optional on AUTOVAR 600.
exceeding the nominal operating For 480 V units, standard-duty cells 25
Overtemperature alarm
range. Stages will be automatically are 525 V rated, and heavy-duty cells
switched off if temperature exceeds are 600 V rated
the maximum specified temperature Contactor 26
Temperature range: The operating Fully rated for capacitor switching Support and Service
temperature range is 20 C to Integral pre-charge/pre-insertion
+46 C, and the storage temperature module standard. The contactor
Renewal parts are available through 27
local Eaton distributors
range is 40 C to +55 C. For optimal reduces damaging switching Factory trained service personnel
equipment life, the temperature transients, providing safety and are available through Eatons 28
should not exceed 35 C annual durability for the system Electrical Services & Systems
average, and the environment Lessens the chance of disrupting
should not exceed Pollution sensitive electronic equipment 29
Degree 2 as defined in UL 61010-1
Reduced inrush current extends
Standards and Certifications
the life of the capacitor cells AUTOVAR filterUL and CSA listed
Controller 30
ContactorUL/CSA recognized;
Visual indication of incorrect Reactors IEC 6b rated
CT polarity
Tuning: Standard reactor designs are Entire cabinet assembly is UL 508A 31
Digital display of power factor and detuned to the 4.2nd harmonic and
number of energized stages and CSA C22.2 No. 190 Listed
recommended to protect capacitors
Capacitors are UL 810 recognized
Automatic setting of c/k value
(sensitivity based on CT ratio and
against harmonic resonance. Detun-
ing to the 4.7th harmonic is available
32
kvar available) as an option. The harmonic spectrum
Visual indication of insufficient kvar should be evaluated for applications 33
to reach target power factor involving reactors detuned to the
Automatic sensing of kvar values 4.7th harmonic to ensure optimal
per step equipment life, specifically when 34
used in conjunction with six-pulse
Optional communications capable
motor drives
controller (RS-485/Modbus)
Standard metering capability:
Windings: 80 C temperature rise 35
design 100% copper windings for
Voltage minimal losses
Current (sensed phase only) Thermal overload protection: Each 36
Frequency reactor includes three normally
closed, auto reset thermostats that
Active power (kW) 37
open at 180 C. When thermostats
Reactive power (kvar) engage, the contactor opens
Apparent power (kVA) Insulation: 220 C insulation system
Total voltage harmonic distortion Warranty: One-year replacement
38
(VTHD) of reactors
Individual harmonic voltage 39
distortion (odd orders up to the Additional Features
19th harmonic) Optional molded-case main circuit
Built-in manual mode allows for breaker 40
testing and manual operation Ground fault interruption provides
of stages protection in case of accidental con-
tact with control power and ground 41
Control wiringstandard NEC color-
coded modular bundles with quick 42
disconnect feature for ease of trouble- AUTOVAR FilterReactor Cabinet
shooting or ease of expendability.
UL type MTW/AWM, CSA TEW 105 C 43
copper wire is standard
Optional digital meteringIQ 250
40
41
42
43
1
optional detuning to the 4.7th harmonic 4
28
Not available for AUTOVAR 300.
2 Manual control is available through menu controller on system, if H option is not selected
3 Only available on AUTOVAR 300, AUTOVAR 600 with heavy-duty cells, and AUTOVAR filters using
L + L, L + KK, and KK + KK enclosures.
29
4 Applies only to AUTOVAR detuned filter.
Note: Please include option codes at the end of the part number in alphabetical order. For 30
example, if you ordered a 350THFSR432Y and added a Main Breaker (M) and Remote Alarm
Relay Terminal Block (A), then the part number would be: 350THFSR432AMY. Remember that
if you have any Special (S option)that letter must go at the end. If you would prefer the
4.7th harmonic tuning, do not include the Y in the part number. Other tuning frequencies
31
are available. Contact Eatons Technical Resource Center (TRC) Power Factor Application
Engineers at 1-800-809-2772, choose option #4, then option #2.
32
Note: Current transformers required for operation of AUTOVAR units. Please see IL157001EN
for more information on current transformers.
33
34
35
36
37
38
39
40
41
42
43
22 Dimensions
24 POWER
FACTOR
CORRECTION
69B1007G01
Power
Option M Conductor Exhaust
1 Molded-Case Lugs
25 2 BLR-CX
Circuit Breaker
3 PHASE A PHASE B PHASE C
DANGER DANGER
HIGH VOLTAGE
CAUTION
HIGH VOLTAGE
CAUTION
Ground
DISCONNECT DISCONNECT
Lug
26 BEFORE SERVICING BEFORE SERVICING
78.00
(1981.2)
Capacitor Reactor
Enclosure Enclosure
27 Copper
Busbar
28
29 A A B B
Dust/Air
Filter Tray 38.50 (977.9) Factory Supplied 12-Inch Conduit and
30 Typ. Power/Control Cables. Interconnect in Field
Legend
by Customer/Installing Contractor Required
1. Controller
41.26 (1048.0) 2. On/Off Switch
31 3. Cleared Fuse Indicating Lights
Mounting Holes
25.00 0.438-Inch Dia. Typ. Notes:
32 (635.0)
16.00
(406.4)
Air Filter Air Filter 1. 6-Inch Minimum Clearance Each Side
2. 45-Inch Front Clearance or per Local Code
3. 12-Inch Minimum Separation
Between Enclosures
33 Section A-A Section B-B 4. In Section B-B, the Horizontal Channels
are for Reactor Support.
35
36
37
38
39
40
41
42
43
Power
23
1 Conductor Exhaust
Lugs Ground
24
R
2
BLR-ACX
esc
Lug
3
PHASE A PHASE B PHASE C
DANGER
HIGH VOLTAGE
CAUTION
DISCONNECT
BEFORE SERVICING
78.00
(1981.2) 25
Capacitor Reactor
Enclosure Enclosure
Copper
Busbar
26
27
A A B B
38.50 (977.9) 77.64 (1972.0)
Dust/Air
28
Filter Tray Typ.
Factory Supplied 12-Inch Conduit and
Legend
Power/Control Cables. Interconnect in Field
by Customer/Installing Contractor Required
1. Controller 29
2. On/Off Switch
3. Cleared Fuse Indicating Lights
41.26 (1048.1) 80.40 (2042.1)
Notes:
30
1. 6-Inch Minimum Clearance
25.00 16.00 Air Filter Air Filter Air Filter Each Side
(635.0) (406.4) Mounting Holes
0.438-Inch Dia. Typ.
2. 45-Inch Front Clearance or per 31
Local Code
3. 12-Inch Minimum Separation
Between Enclosures
Section A-A Section B-B
32
Figure 35.2-6. L + KK Enclosure (AUTOVAR Detuned Filter Only)
33
Option W NEMA 3R
Customer Conduit Entry in This Area Drip Shield
34
Power
1 Conductor Exhaust 35
Power Factor Controller
R
Lugs Ground
2
BLR-ACX
esc
Lug
3 36
PHASE A PHASE B PHASE C
DANGER
HIGH VOLTAGE
CAUTION
DISCONNECT
BEFORE SERVICING
78.00
(1981.2)
37
Capacitor Reactor Copper
Enclosure Enclosure Busbar
38
A A B B
39
38.50 (977.9) 77.64 (1972.0)
Dust/Air
Factory Supplied 12-Inch Conduit and
Filter Tray Typ. 40
Legend
Power/Control Cables. Interconnect in Field
1. Controller
by Customer/Installing Contractor Required
2. On/Off Switch
3. Cleared Fuse Indicating Lights
41
41.26 (1048.1) 80.40 (2042.1)
Notes:
1. 6-Inch Minimum Clearance 42
25.00 16.00 Air Filter Air Filter Air Filter Each Side
(635.0) (406.4) Mounting Holes 2. 45-Inch Front Clearance or per
0.438-Inch Dia. Typ. Local Code
3. 12-Inch Minimum Separation
43
Section A-A Section B-B Between Enclosures
22 Option W NEMA 3R
Drip Shield
Standard Customer Conduit Entry in This Area
Exhaust
23
Power
POWER
FACTOR
CORRECTION
69B1007G01
POWER
FACTOR
CORRECTION
69B1007G01
Conductor
1 Lugs
24 Power Factor Controller
BLR-ACX
R
2 esc
Ground
25 Lug
78.00
(1981.2)
26 Copper
Busbar
Capacitor Reactor
Enclosure Enclosure
27
28 A A B B
77.64 (1972.1)
Dust/Air
Filter Tray
29 Factory Supplied 12-Inch Conduit and
Power/Control Cables. Interconnect in Field
by Customer/Installing Contractor Required
30 80.40 (2042.1)
31 25.00 16.00
(635.0)(406.4)
Air Filter Air Filter Air Filter Air Filter Mounting
Holes
0.438-Inch
Dia. Typ.
32 Section A-A Section B-B
Legend Notes:
33 1. Controller 1. 6-Inch Minimum Clearance Each Side
2. On/Off Switch 2. 45-Inch Front Clearance or per Local Code
3. Cleared Fuse Indicating Lights 3. 12-Inch Minimum Separation Between Enclosures
34
Figure 35.2-8. AUTOVAR KK + KK Enclosures
35
36
37
38
39
40
41
42
43
Main 22
23
CT
Main
24
CBPFC
25
26
PFC
Note: Please follow the CT polarities per the arrows.
CT should be installed on the A phase. 27
Figure 35.2-9. Typical Current Transformer Scheme for
Single-Ended Operation 28
MainLeft MainRight 29
CT CT CT CT 30
Main L Tie L Tie R Main R
CB PFC CB PFC 31
L R
32
CT CT
Summ Summ
L
PFC L
PFC R R 33
Note: This configuration provides individual PFC operation
per side regardless of breaker positions. Please follow the CT
polarities per the arrows. CTs should be installed on the A phase.
34
MainLeft MainRight
36
37
CT CT CT CT
Main L Tie L Tie R Main R
38
CB PFC CB PFC
L R
39
40
PFC L
PFC R
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
40
41
42
43
380480 50/60 60 1.3 Wallmount NEMA 1 UL/CSA Bottom No 220 (100) HCU2060D5N1
24 380480
380480
50/60
50/60
120
200
2.8
5.4
Wallmount NEMA 1
Wallmount NEMA 1
UL/CSA
UL/CSA
Bottom
Bottom
No
No
268 (122)
409 (184)
HCU2120D5N1
HCU2200D5N1
380480 50/60 300 7.1 Wallmount NEMA 1 UL/CSA Bottom No 504 (229) HCU2300D5N1
25 380480
380480
50/60
50/60
60
120
1.3
2.8
Chassis mount
Chassis mount
UL/CSA
UL/CSA
Bottom
Bottom
No
No
198 (90)
248 (113)
HCU2060D5IP00
HCU2120D5IP00
380480 50/60 200 5.4 Chassis mount UL/CSA Bottom No 385 (175) HCU2200D5IP00
380480 50/60 300 7.1 Chassis mount UL/CSA Bottom No 484 (220) HCU2300D5IP00
26 380480 50/60 60 1.3 Floor mount IP31 CE Top or bottom Yes 609 (277) HCU2060D5IP31
380480 50/60 120 2.8 Floor mount IP31 CE Top or bottom Yes 631 (287) HCU2120D5IP31
380480 50/60 200 5.4 Floor mount IP31 CE Top or bottom Yes 873 (397) HCU2200D5IP31
27 380480 50/60 300 7.1 Floor mount IP31 CE Top or bottom Yes 928 (422) HCU2300D5IP31
380480 50/60 60 1.3 Floor mount NEMA 2 UL/CSA Top or bottom Yes 609 (277) HCU2060D5N2
380480 50/60 120 2.8 Floor mount NEMA 2 UL/CSA Top or bottom Yes 631 (287) HCU2120D5N2
28 380480 50/60 200 5.4 Floor mount NEMA 2 UL/CSA Top or bottom Yes 873 (397) HCU2200D5N2
380480 50/60 300 7.1 Floor mount NEMA 2 UL/CSA Top or bottom Yes 928 (422) HCU2300D5N2
380480 50/60 60 1.3 Floor mount NEMA 12 UL/CSA Top or bottom Yes 609 (277) HCU2060D5N12
29 380480 50/60 120 2.8 Floor mount NEMA 12 UL/CSA Top or bottom Yes 631 (287) HCU2120D5N12
380480 50/60 200 5.4 Floor mount NEMA 12 UL/CSA Top or bottom Yes 873 (397) HCU2200D5N12
380480 50/60 300 7.1 Floor mount NEMA 12 UL/CSA Top or bottom Yes 928 (422) HCU2300D5N12
30 380480 50/60 60 1.3 Floor mount IP54 CE Top or bottom Yes 609 (277) HCU2060D5IP54
380480 50/60 120 2.8 Floor mount IP54 CE Top or bottom Yes 631 (287) HCU2120D5IP54
380480 50/60 200 5.4 Floor mount IP54 CE Top or bottom Yes 873 (397) HCU2200D5IP54
31 380480 50/60 300 7.1 Floor mount IP54 CE Top or bottom Yes 928 (422) HCU2300D5IP54
600 50/60 47 1.8 Floor mount IP31 CE Top or bottom Yes 1012 (460) HCU2047D6IP31
600 50/60 94 3.9 Floor mount IP31 CE Top or bottom Yes 1096 (498) HCU2094D6IP31
600 50/60 157 7.2 Floor mount IP31 CE Top or bottom Yes 1437 (653) HCU2157D6IP31
32 600 50/60 235 9.9 Floor mount IP31 CE Top or bottom Yes 1665 (757) HCU2235D6IP31
600 50/60 47 1.8 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1012 (460) HCU2047D6N2
600 50/60 94 3.9 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1096 (498) HCU2094D6N2
33 600 50/60 157 7.2 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1437 (653) HCU2157D6N2
600 50/60 235 9.9 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1665 (757) HCU2235D6N2
600 50/60 47 1.8 Floor mount IP54 CE Top or bottom Yes 1036 (471) HCU2047D6IP54
34 600 50/60 94 3.9 Floor mount IP54 CE Top or bottom Yes 1115 (507) HCU2094D6IP54
600 50/60 157 7.2 Floor mount IP54 CE Top or bottom Yes 1485 (675) HCU2157D6IP54
600 50/60 235 9.9 Floor mount IP54 CE Top or bottom Yes 1694 (770) HCU2235D6IP54
35 600 50/60 47 1.8 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1036 (471) HCU2047D6N12
600 50/60 94 3.9 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1115 (507) HCU2094D6N12
600 50/60 157 7.2 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1485 (675) HCU2157D6N12
36 600 50/60 235 9.9 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1694 (770) HCU2235D6N12
690 50/60 40 2.1 Floor mount IP31 CE Top or bottom Yes 1063 (483) HCU2040D7IP31
690 50/60 80 4.5 Floor mount IP31 CE Top or bottom Yes 1173 (533) HCU2080D7IP31
37 690 50/60 133 8.2 Floor mount IP31 CE Top or bottom Yes 1558 (708) HCU2133D7IP31
690 50/60 200 11.4 Floor mount IP31 CE Top or bottom Yes 1817 (826) HCU2200D7IP31
690 50/60 40 2.1 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1063 (483) HCU2040D7N2
38 690 50/60 80 4.5 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1173 (533) HCU2080D7N2
690 50/60 133 8.2 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1558 (708) HCU2133D7N2
690 50/60 200 11.4 Floor mount NEMA 2 UL/CSA Top or bottom Yes 1817 (826) HCU2200D7N2
39 690
690
50/60
50/60
40
80
2.1
4.5
Floor mount IP54
Floor mount IP54
CE
CE
Top or bottom
Top or bottom
Yes
Yes
1087 (494)
1192 (542)
HCU2040D7IP54
HCU2080D7IP54
690 50/60 133 8.2 Floor mount IP54 CE Top or bottom Yes 1606 (730) HCU2133D7IP54
40 690
690
50/60
50/60
200
40
11.4
2.1
Floor mount IP54
Floor mount NEMA 12
CE
UL/CSA
Top or bottom
Top or bottom
Yes
Yes
1846 (839)
1087 (494)
HCU2200D7IP54
HCU2040D7N12
690 50/60 80 4.5 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1192 (542) HCU2080D7N12
690 50/60 133 8.2 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1606 (730) HCU2133D7N12
41 690 50/60 200 11.4 Floor mount NEMA 12 UL/CSA Top or bottom Yes 1846 (839) HCU2200D7N12
42
43
Product Specifications 22
Table 35.3-2. HCU2 Specifications
Description Specification
Technical Specifications
23
Standard rms output 60 A, 120 A, 200 A, 300 A at 380 Vac to 480 Vac
current ratings 47 A, 94 A, 157 A, 235 A at 600 Vac
40 A, 80 A, 133 A, 200 A at 690 Vac
24
Nominal frequency 50/60 Hz, 3 Hz auto sensing
Number of phases Three-phase 25
Topology Digital harmonic FFT
Digital reactive power
Losses To 480 Vac <3%; to 690 VCA <5% 26
CT VA loading 1.0 VA (5 A CT secondary)
Spectrum cancellation 2nd to 51st, discrete; fully selectable per harmonic order
(amplitude and on/off) 27
Control basis Closed loop (for new installations)
Open loop compatible for retrofit applications
Harmonic attenuation Closed Loop: <3% THD(i); max 20:1 THD(i) reduction with load
28
harmonic current above 50% of Eaton HCU2 rating
Open Loop: <5% TDD
Requires 3% or higher inductive impedance per nonlinear load 29
Harmonic operational features % THDi set point
% THDv set point
Harmonic avoidance Output at specific harmonic order turned off if resonance or lack-of impedance detected; or manually turned off 30
Parallel operation Up to 10 units per set of CT (to 51st order), any size combination
Backward compatibility with Eaton HCUE operated in parallel
Contact Eaton for applications of more than 10 units 31
Parallel operation options Master/master (masters receive mains CT)
Master/slave
Multi-master/multi-slave 32
Same as Eaton HCUE for retrofits
Parallel sequence options Lead/lag with unit rotation: one unit operates to full capacity before next unit turns on; timed rotation
Load share: All operating units function at the same output percentage 33
Parallel HMI control Any unit permits viewing and changing parameter settings
of complete system or any other unit in parallel system
Parallel communications Proprietary COM bus between operating units 34
Power factor correction Optimized unity PF, leading (capacitive) or lagging (inductive)
power factor (Cos f) to target
Control response time 25 s 35
Harmonic correction time 2 cycles
Reactive correction time 1/4 cycle
Display 144 mm QVGA TFT 64k-color touchscreen
36
Display parameters Hundreds of parameters are available. Examples include THDi, THDv, oscilloscope for viewing many selected
parameters, phasor diagrams, load power, measured currents for Ih, Is, If, I neg seq, PF (Cos ), injected currents
for Ih, I reactive, I neg seq, etc.
37
Communications capability Modbus RTU, Modbus TCP/IP
Discrete input/outputs 4 input and 4 output dry contacts; assignable 38
Noise level (ISO3746) <70 dB at one meter from unit surface
Earthing (grounding) systems EMC filter ground switch for Isolated Terra, high resistance ground or corner grounded systems
39
40
41
42
43
27 Contaminant levelsoperating
(IEC 60721-3-3)
Chemical Class 3C2
Mechanical Class 3S2
No conductive particles permitted
Reference Standards
28
Design CE EMC Certification IEC/EN 60439-1, EN 61000-6-4 Class A, EN 61000-6-2
Protection (enclosure) IP00, IP20, IP31, IP54, UL Type 1, UL Type 2, UL Type 12, UL Type Open
29 Standards compliance/certification cULus (UL 508, CSA 22.2 No. 14)
CE Certified, ABS, Lloyds, other local standards
Installation
30 Wallmount IP00 (UL Type open) and IP20 (NEMA 1) configurations
Free-standing IP31, IP54, NEMA 2 and NEMA 12
37 Service Provisions
HMI Plain language output (without cryptic codes)
USB port for upload of new software and download of operational records
38 Service port USB port: commission, program, or diagnostics via a laptop computer when power is on or off;
laptop provides power to control board when no unit power is present
Commissioning On-board step-by-step process; CT automatic sizing, phase rotation, and polarity;
39 external transformer ratio and phase shift; heat test, and more
40
41
42
43
Source 28
Typical CT
Placement 29
Transformer
30
31
HCU
Load(s)
32
Figure 35.3-1. Installation Diagram
33
34
35
PFC 37
Load(s)
Typical HCU2
CT Placement 38
41
42
43
22 Model Drawings
Layout Dimensions NEMA 1 Wallmounted Enclosures
23
24
25
26
27
28
29
30
31
60.40
32 (1534.0)
33
34
35
36
37
38
39
40
41
42
13.70 16.80
(348.0) (426.0)
43
Figure 35.3-3. NEMA 1, 60 ADimensions in Inches (mm)
23
24
25
26
27
28
29
30
31
64.30
(1634.0)
32
33
34
35
36
37
38
39
40
41
42
15.10 16.80
(384.0) (426.0) 43
23 17.20
(437.0)
22.90
(581.0)
24
25
26
27
28
29
30
31 62.90
(1598.0)
32
33
34
35
36
37
38
39
40
41
Figure 35.3-5. NEMA 1, 200 ADimensions in Inches (mm)
42
43
24
25
26
27
28
29
30
31
72.20
(1835.0) 32
33
34
35
36
37
38
39
40
41
42
43
24
25
26
27
28
29
30 82.24
(2089.0)
31
32
33
34
35
36
19.69 2.17 31.50
37 (500.0) (55.0) (800.0)
38 Figure 35.3-7. 60 A and 120 A, 380480 V, NEMA 2, NEMA 12, IP31 and IP54 UnitsDimensions in Inches (mm)
39
40
41
42
43
24
25
26
27
28
29
30
82.32 31
(2091.0)
32
33
34
35
36
37
38
23.62
(600.0)
2.09
(53.0)
35.43
(900.0)
39
Figure 35.3-8. 200 A and 300 A, 380480 V, NEMA 2, NEMA 12, IP31 and IP54 UnitsDimensions in Inches (mm)
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
39
40
41
42
43
26 25
50
25243MVF3
50243MVF3
25413MVF3
50413MVF3
25483MVF3
50483MVF3
34.44 (875.0)
34.44 (875.0)
72 (32)
72 (32)
Figure 35.5-1
Figure 35.5-1
75 75243MVF3 75413MVF3 75483MVF3 34.44 (875.0) 72 (32) Figure 35.5-1
27 100
125
100243MVF3
125243MVF3
100413MVF3
125413MVF3
100483MVF3
125483MVF3
36.19 (919.0)
36.19 (919.0)
77 (34)
85 (38)
Figure 35.5-1
Figure 35.5-1
150 150243MVF3 150413MVF3 150483MVF3 36.19 (919.0) 90 (40) Figure 35.5-1
175 175243MVF3 175413MVF3 175483MVF3 36.19 (919.0) 95 (42) Figure 35.5-1
28 200 200243MVF3 200413MVF3 200483MVF3 36.19 (919.0) 101 (45) Figure 35.5-1
225 225243MVF3 225413MVF3 225483MVF3 41.94 (1065.0) 111 (49) Figure 35.5-1
250 250243MVF3 250413MVF3 250483MVF3 41.94 (1065.0) 111 (49) Figure 35.5-1
29 275 275243MVF3 275413MVF3 275483MVF3 41.94 (1065.0) 123 (55) Figure 35.5-1
300 300413MVF3 300483MVF3 41.94 (1065.0) 123 (55) Figure 35.5-1
300 300243MVF3 36.19 (919.0) 176 (78) Figure 35.5-2
30 325 325243MVF3 325413MVF3 325483MVF3 36.19 (919.0) 181 (80) Figure 35.5-2
350 350243MVF3 350413MVF3 350483MVF3 36.19 (919.0) 186 (83) Figure 35.5-2
375 375243MVF3 375413MVF3 375483MVF3 36.19 (919.0) 192 (85) Figure 35.5-2
31 400 400243MVF3 400413MVF3 400483MVF3 36.19 (919.0) 198 (88) Figure 35.5-2
425 425243MVF3 425413MVF3 425483MVF3 41.94 (1065.0) 210 (93) Figure 35.5-2
450 450243MVF3 450413MVF3 450483MVF3 41.94 (1065.0) 218 (97) Figure 35.5-2
32 475
500
475243MVF3
500243MVF3
475413MVF3
500413MVF3
475483MVF3
500483MVF3
41.94 (1065.0)
41.94 (1065.0)
218 (97)
218 (97)
Figure 35.5-2
Figure 35.5-2
525 525243MVF3 525413MVF3 525483MVF3 41.94 (1065.0) 230 (103) Figure 35.5-2
33 550
575
550243MVF3
550413MVF3
575413MVF3
550483MVF3
575483MVF3
41.94 (1065.0)
41.94 (1065.0)
242 (108)
242 (108)
Figure 35.5-2
Figure 35.5-2
575 575243MVF3 36.19 (919.0) 265 (118) Figure 35.5-3
600 600413MVF3 600483MVF3 41.94 (1065.0) 242 (108) Figure 35.5-2
34 600 600243MVF3 36.19 (919.0) 271 (121) Figure 35.5-3
625 625243MVF3 625413MVF3 625483MVF3 41.94 (1065.0) 285 (127) Figure 35.5-3
650 650243MVF3 650413MVF3 650483MVF3 41.94 (1065.0) 293 (131) Figure 35.5-3
35 675 675243MVF3 675413MVF3 675483MVF3 41.94 (1065.0) 301 (134) Figure 35.5-3
700 700243MVF3 700413MVF3 700483MVF3 41.94 (1065.0) 301 (134) Figure 35.5-3
725 725243MVF3 725413MVF3 725483MVF3 41.94 (1065.0) 301 (134) Figure 35.5-3
36 750 750243MVF3 750413MVF3 750483MVF3 41.94 (1065.0) 301 (134) Figure 35.5-3
775 775243MVF3 775413MVF3 775483MVF3 41.94 (1065.0) 313 (140) Figure 35.5-3
800 800243MVF3 800413MVF3 800483MVF3 41.94 (1065.0) 325 (145) Figure 35.5-3
37 825 825243MVF3 825413MVF3 825483MVF3 41.94 (1065.0) 337 (151) Figure 35.5-3
850 850413MVF3 850483MVF3 41.94 (1065.0) 337 (151) Figure 35.5-3
875 875413MVF3 875483MVF3 41.94 (1065.0) 337 (151) Figure 35.5-3
38 900 900413MVF3 900483MVF3 41.94 (1065.0) 337 (151) Figure 35.5-3
40
41
42
43
Dimensions 22
23
24
25
26
27
28
29
Figure 35.5-1. UNIVAR XV 5 kV Class, 25300 kvar
30
31
32
33
34
35
36
37
Figure 35.5-2. UNIVAR XV 5 kV Class, 300600 kvar
38
39
40
41
42
43
22 Dimensions
23
24
25
26
27
28
29
31
32
33
34
35
36
37
38
39
40
41
42
43
36
37
38
39
40
41
42
43
50 50663FKED3 50723FKED3 50123FKED3 50133FKED3 4.25 (108.0) 45.50 (1156.0) 14.46 (367.0) 0.25 (6.0) 198 (90) 5D10243
27 100
150
100663FKED3
150663FKED3
100723FKED3
150723FKED3
100123FKED3
150123FKED3
100133FKED3
150133FKED3
4.25 (108.0)
4.25 (108.0)
45.50 (1156.0)
45.50 (1156.0)
14.46 (367.0)
14.46 (367.0)
0.25 (6.0)
0.25 (6.0)
198 (90)
198 (90)
5D10243
5D10243
200 200663FKED3 200723FKED3 200123FKED3 200133FKED3 5.62 (143.0) 45.50 (1156.0) 14.46 (367.0) 0.25 (6.0) 220 (100) 5D10243
250 250FKY66323 250FKY72323 250FKY12323 250FKY13323 5.62 (143.0) 48.50 (1232.0) 17.46 (443.0) 0.25 (6.0) 246 (112) 5D10243
28 300 300FKY66323 300FKY72323 300FKY12323 300FKY13323 5.62 (143.0) 53.50 (1359.0) 17.46 (443.0) 0.25 (6.0) 246 (112) 5D10243
350 350FKY66323 350FKY72323 350FKY12323 350FKY13323 5.62 (143.0) 53.50 (1359.0) 17.46 (443.0) 0.25 (6.0) 246 (112) 5D10243
400 400FKY66323 400FKY72323 400FKY12323 400FKY13323 5.62 (143.0) 57.25 (1454.0) 22.46 (570.0) 0.25 (6.0) 281 (128) 5D10243
29 450 450FKY12323 450FKY13323 5.62 (143.0) 57.25 (1454.0) 22.46 (570.0) 0.25 (6.0) 281 (128) 5D10243
500 500FKY12323 500FKY13323 5.62 (143.0) 57.25 (1454.0) 26.21 (666.0) 0.25 (6.0) 336 (153) 5D10243
30 Dimensions
31
Removable
Top Cover 0.250-20
32 16.42 34.00
Grd. Scr.
Barriers
33 Solderless Conn.
for A #10 Solid
to A #4 Strd. Conn.
34
B
35
(2) 0.500 x 0.625
36 Slots [13 x 16]
C
D
24.12
37 A 25.08
39
40
41
42
43
AUTOVAR MV (2.414.4 kV) Meets the following requirements: Load Interrupter Air Disconnect Switch
22 ANSI Integral disconnect switch, externally
IEEE operated, mechanically chain driven
with visible blades is available as per
23 NEC
NEC requirements. Disconnect switch
NESC is mechanically interlocked with the
CSA (when specified) ground switch, and with the customers
24 upstream device (if applicable).
Main incoming fuses are rated
Incoming section is front-accessible
50 kAIC to provide main bus
only for safety, and barrier isolates
25 protection, as well as backup
live connections from the user.
protection for the capacitor systems
Standard bus bracing is 25 kA
26 symmetrical
Medium Voltage 4.00-inch base channel is standard
Metal-Enclosed PFC Capacitor Bank
27 Standard Features
General Description Enclosure
28 The AUTOVAR medium voltage auto- Free-standing, 11-gauge steel
matic power factor capacitor systems construction with 3-point padlockable
are designed for power factor correction latching handles and stainless steel
29 in applications where plant power factor hinges. The enclosure is painted with
can be constant or changing, and an a corrosion-resistant ANSI 61 light
engineered solution is required. These gray enamel paint as standard. Other
30 systems can be a fixed amount of colors are available as an option.
capacitance with a disconnect, a number NEMA 3R construction is standard,
of switched capacitance stages or a NEMA 3R stainless steel is available
31 combination of both. The AUTOVAR as an option.
medium voltage capacitor system can
switch stages of capacitance in and out Enclosure is CSA approved. Enclosure
32 automatically based on information design is modular and future sections
collected by the power factor controller can be added on the left or right.
33 on the door-in-door control panel. See Figure 35.6-1 for typical Incoming Main Switch and Fuses
dimensions and elevations.
Features, Benefits See Figure 35.6-2 for a typical
Ground Switch
34 and Functions single-line drawing. A ground switch is provided to ground
the load-side terminals of the incoming
Voltages from 2400 to 14,400 V switch (or MLO) for safety during
35 Reactive power ratings through
maintenance. Optional controls are
available to permit closing contactors
10 MVAR
after the grounding switch has been
36 Harmonic tuned, de-tuned or closed to ground capacitors immedi-
multi-tuned filter designs available ately (rather than waiting 5 minutes
Externally fused capacitor units for full discharge).
37 standard
Blown fuse indication standard
Integral load interrupter switch,
38 NEMA 2- or 4-hole termination pad
Delivered fully assembled, tested
Medium Voltage PFC Enclosure
39 and ready for interconnection
Integral protection and
control system
40 Top or bottom cable entry
Earthing switch
41 60 kV BIL up to 4.8 kV
95 kV BIL from 7.2 kV to 14.4 kV
Up to 12 automatic switched
42 capacitor stages
Warning labels
Removable air filters without
43 opening enclosure doors
Adjustable blocking timers to Bottom Plate Incoming
prevent re-closing of a capacitor Cutout Provided Standard
stage in less than 200 seconds
38 Inrush Reactors
Inrush reactors are provided as
standard on all switched (non-
39 harmonic filtered) capacitor systems Continuous Ground Bus
for protection against transients from with Pad in Each Section
Control Panel
back-to-back switching. Reactors in
40 harmonic filtered applications provide
this same protection.
41
42
43
35
36
Harmonic Filter 37
38
39
40
41
42
43
22 Dimensions
23 Top Power
Cable Entry
Lifting Eyes
Shipping Split
24 Incoming Main Section
25
Main Switch
92.56 24.00
K1 (2351.0) (609.6)
26 Control
Panel 18.00
CAUTION CAUTION CAUTION
Customer (457.2)
DANGER DANGER DANGER
27 Cable
Ground Switch
NAMEPLATE
Termination
Danger Danger Danger Danger
CAUTION
K1 (Approximate
High Voltage High Voltage High Voltage High Voltage
Keep Out Keep Out Keep Out
DANGER
Location, See
28
Keep Out
Actual Unit
D1
for Exact
D2
D3
Dimensions)
29 D2 D3 D2
Door Interlocks
D1
90.33 Gourd Bus
1/4-inch x 1-inch
(2294.4)
Base Channel
30 180.80
(4592.3)
Bottom Power
Cable Entry
8 Tieddown Points 45.00 49.10
per Enclosure Front Elevation 1.50
(1143.0) (1247.1)
31 Front and Rear (38.1)
(Typ)
13.50 15.00 13.50
Right Side Elevation
for 1/2 Inch Hardware Rear Access Doors Optional (342.9) (381.0) (342.9)
32 Base Channel
18.00 21.79
40-Inches High
(457.2) (553.5)
49.00
33 Bottom Entry 18.00 (1244.6)
Cover Plate
(457.2)
5.09 9.07
34 (129.3) (230.4)
36 Floor Plan
Top Entry
37 MV Conduit
19.00
Area
(482.6)
Top Entry
38 Control
16.00
(406.4)
Conduit
4.00 x 4.00 15.00 13.00
39 (381.0) (330.2)
Figure 35.6-1. Typical Engineered Metal-Enclosed Power Factor Correction System Dimensional Data
41
42
43
Utility Line 22
23
Utility
Transformer
24
Main Breaker 25
CT
A-Phase 1 26
27
Feeder Breaker K0 28
29
Plant Loads
30
K-K Interlock
36
Fuse
S1
Enclosure
Door 37
C1 38
Vacuum
Contactor
39
Reactor
40
41
Capacitor Capacitor Capacitor
Delta/Wye Delta/Wye Delta/Wye
42
Figure 35.6-2. Typical Medium Voltage Automatic Power Factor Correction Single-Line Drawing 43
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43