IEEE Terms Used by Power System Protection Engineers PDF
IEEE Terms Used by Power System Protection Engineers PDF
IEEE Terms Used by Power System Protection Engineers PDF
~\)\"EEIIJ4'q~
~ ~
C). ~
~ -<
IEEt
Prepared by the
Terms Used by Power System Engineers Working Group
of the
Relay Standards Subcommittee
1997 -July-31
Terms Used by Power System Protection Engineers
This special report was prepared for and approved by the "Power System Relaying Committee" of the "IEEE Power Engi-
neering Society". It was prepared by the "Terms Used by Power System Engineers Working Group" of the "Relaying Stan-
dards Subcommittee".
At the time of its approval, January 1997, the Working Group Membership was
Abstracting is permitted with credit to the source. For other copying, reprint, or republication permission, write to the
IEEE Copyright Manager, IEEE Operations Center, 445 Hoes Lane, Piscataway, NJ 08855-1331. All rights reserved.
Copyright 1998 by The Institute of Electrical and Electronics Engineers, Inc.
Members of the "Power System Relaying Committee" entrants in the area of power system protection in under-
have expressed concern from time to time that recently standing them properly.
graduated engineers, technologists and engineers from
To keep the explanations from conflicting with the defmi-
other disciplines usually experience difficulty with prop-
tions of terms provided in the standards, the Working
erly interpreting the terminology used in the area of Power
Group maintained liaison with the "Terminology Usage
System Protection. The consequence is that they experi-
Review Working Group" (of the "Relay Standards Sub-
ence difficulty in communicating effectively with their
committee" of the "Power System Relaying Committee"
colleagues.
of the IEEE "Power Engineering Society") that recom-
To overcome this difficulty, the "Power System Relaying mends adoption of new definitions for inclusion in the
Committee" of the IEEE formed, in January 1991, the IEEE dictionary and IEEE/ANSI standards.
"Terms Used by Power System Protection Engineers
The explanations of the terms were written and then re-
Working Group". This working group was assigned the
vised several times to avoid conflict with the official defi-
task of preparing a special publication which should de-
nitions and to make the explanations suitable for achieving
scribe in a straight forward manner the terms commonly
the intended objectives of this report. The Working Group
used by power system protection engineers.
hopes that this document will be found useful by recent
Almost all the terms, discussed in this report, are defined engineering graduates, technologists, and engineers who
in the IEEE Std 100-1992 "The New IEEE Dictionary of do not have formal training in Power System Protection
Electrical and Electronics Terms", the "International Elec- but have to interact with protection engineers.
trotechnical Commission's" publication, "IEC Multilin-
gual Dictionary of Electricity" and standards published by
various organizations. The objective of the report was not M.S. Sachdev
to redefine the terms but provide brief explanations to as- Working Group Chair
sist the recent graduate engineers, technologists and new
- iii -
Terms Used by Power System Protection Engineers
CopyrightCO The Instituteof Electrical and Electronics Engineers, Inc.
Table of Contents
- iv -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
List of Figures
- v -
Terms Used by Power System Protection Engineers
Copyright o The Institute of Electrical and Electronics Engineers, Inc.
1. INTRODUCTION
There is considerable concern among power system engi- The Working Group appreciated at the outset that defini-
neers in general, and power system protection engineers in tions of almost all the terms used by power system protec-
particular, that recent graduates and engineers from other tion engineers are included in the IEEE Std 100-1992
disciplines usually experience difficulty with properly "The New IEEE Dictionary of Electrical and Electronics
interpreting the terminology used in applying relays, ana- Terms" [2], the "International Electrotechnical Commis-
lyzing their performance and designing protection sys- sion's" publication, "IEC Multilingual Dictionary of Elec-
tems. tricity" [9] and standards published by various organiza-
tions.
This makes it difficult for relay engineers to communicate
effectively with their colleagues and convey their inter- The Working Group discussed and decided
pretations of relaying issues and questions effectively. To
neither to redefme the terms already included in the
overcome this difficulty, the "Power System Relaying
dictionaries and standards,
Committee" of the IEEE "Power Engineering Society"
nor to reproduce the established definitions from
decided to prepare a special publication that would pro-
standards, and also
vide, in simple and straightforward language, interpreta-
not to provide historical development of terms.
tions of the terms used in the area of power system pro-
tection. The "Terms Used by Power System Protection The Working Group decided to provide, in its special re-
Engineers Working Group" was formed in January 1991 port, explanations of the terms in a straight forward man-
and was assigned the task of preparing a special publica- ner so that recent graduate engineers, technologists and
tion describing the terms commonly used by power system new entrants in the area of power system protection can
protection engineers. understand them properly and become useful participants
in their work without unnecessary frustration.
- 1-
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
2. GENERAL TERMS
Device Assigned
Number
Distance relay 21
Undervoltage relay 27
Instantaneous overcurrent relay 50
Ac time overcurrent relay 51
Overvoltage relay 59
Ac directional overcurrent relay 67
Frequency relay 81
Differential relay 87
- 4-
Terms Used by Power SystemProtectionEngineers
CopyrightCO The Instituteof Electrical and ElectronicsEngineers, Inc.
3. RELAY TYPES
This section briefly describes the following terms used for Most electromagnetic relays use one of the following phe-
describing different types of relays. nomena.
-5-
Terms Used by Power System Protection Engineers
Copyright (g The Institute of Electrical and Electronics Engineers, Inc.
galvanic isolation for the relay from the power system,
1-----. Contact
Output
reduces the level of the input voltages, converts currents to
equivalent voltages and removes high frequency compo-
POWER. SYSTEM
,r
Analog Input
Subsystem
"
Digital Input
Subsystem
Digital Output
Subsystem
,r I
Analog Micro-
Interface processor
RAM ROM
Control Communication
MICRO-COMPUTER
Power
Supply
RELAY
-7-
Terms Used by Power System Protection Engineers
Copyright o The Institute of Electrical and Electronics Engineers, Inc.
Analog Input Low pass Sample Multi- AID
Isolation Shunt Filter Amplifier and Hold plexer Conversion
1'1 * -{>-
Analog to
AI S/H MUX AID Digital
Converson
Digital
Filters Numerical
*
COM MMI Signal
Z<
~
Processing
I>
etc. Serial
Com m unication
Fault/Event
Binary Input Trip Recording Binary Output
Isolation Algorithm PLC Isolation Binary
Processing AR Signal
etc. Processing
BI
V~k
Logic Function
~ DO
Processing
- 8-
TermsUsed by Power SystemProtection Engineers
Copyright ~ The Instituteof Electrical and Electronics Engineers, Inc.
4. OVERCURRENT RELAY
The terms used in the area of overcurrent relay are de- air gap of an electro-magnet which is excited by current
scribed in this section. These include flowing in its coil. The current in the coil produces flux in
the air gap. Because the current in the coil is alternating in
instantaneous overcurrent relay,
nature, the flux in the air gap is also time varying. The
inverse time overcurrent relay,
flux induces eddy currents in the disk. The air gap flux
directional overcurrent relay,
and the eddy currents interact with each other producing a
time dial (time lever, time multiplier),
torque that tries to rotate the disk. Since the disk is held
connection angle, and
back with a spring, it does not start to rotate until the
polarizing quantity.
torque exceeds a specified level.
4.1 Instantaneous Overcurrent Relay A moving contact, which is attached to the shaft, as well as
a stationary contact are provided in the relay. The coil of
This type of relay has been assigned by ANSI the device the electromagnet is provided with taps which allows the
number 50. The term instantaneous has at least two relay engineers to change the effective turns on the elec-
meanings and functions. The first concerns the operation tromagnet. These settings are used to select the pickup
of a relay or the tripping of a circuit breaker. It means that current of the relay.
no intentional time delay is added to the trip function. The
relay operates when it detects that the current level has
4.2.1 Time dial (Time lever, Time multiplier)
exceeded the threshold setting. These relays operate typi-
cally in 4 to 16 ms on a 60 Hz system. The second func- The time dial (also referred to as time lever or time multi-
tion concerns the reclosing of circuit breakers. In this plier) is the means for controlling the operating time of the
context, it means that reclosing of a circuit breaker is not relay. This is achieved by changing the angle through
intentionally delayed after it has been tripped. There is, which the disk must rotate before its contacts are closed.
however, an inherent albeit small time delay in performing Since the moving contact travels in an arc, it can be length-
these functions. ened or shortened by selecting an appropriate time dial
setting. The adjustment of the arc is calibrated in the form
4.2 Overcurrent Relay Time-Current of an index which is known as the time dial.
Characteristic Figure 7 shows how the operating time of a relay changes
Inverse time overcurrent relays (device number 51), oper- when the time dial setting is changed from 0.5 to 7.
t
ate when the current in the relay exceeds a threshold. In-
\
verse time delay means that the higher the relay current,
the lower is the operating time. Some of the commonly
used time delay characteristics are ~ Extremely inverse
CI)
E
inverse time, ;
Very inverse
very inverse time,
extremely inverse time, and
definite minimum time.
Sample current-time characteristics are shown in Figure 5.
These curves represent the operating time of the relay
within specified tolerance. Notice that the definite mini-
mum time characteristic has approximately constant time
delay for relay currents larger than three times the set
value. Relay engineers use these curves, that are published
by the manufacturers, to predict the time the relay would
take to operate for different levels of relay current. current
An induction disk inverse time overcurrent relay is shown Figure 5. Time current characteristics commonly
in Figure 6. It has a non-magnetic disk, usually made of used in inverse time overcurrent relays.
aluminum, mounted on a shaft. The disk is placed in the
-9-
Terms Used by Power System Protection Engineers
Copyright o The Institute of Electrical and Electronics Engineers, Inc.
~-1IllIIo... Time Dial - only dial
C.T.
6 numbers 6-9 shown
Stationary
cont~
~~ingContact
Disk rotor,
Figure 6. Electrical and mechanical arrangement of a typical inverse time overcurrent relay.
- 10 -
Terms Used by Power SystemProtection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
angle of the residual current is checked with respect to a Example: Consider that directional relays using Op-
neutral current of a source that provides a constant refer- tion 2 for connecting the voltage elements have been
ence no matter where the fault is located. applied at a relay location. Figure 9 (a) shows the
phase voltages, Va' Vb and Vc' and the currents I, , I,
4.3.1 Connection angle and I, when the system is operating normally. The
polarizing voltages (Vb-Vc ' v.v, and Va-Vb) and the
In the phase directional relays, the phase angle between the currents during normal operation are also shown in this
current and voltage is used to decide if the fault is in the figure. Now consider that a phase A to phase B fault
forward direction. Different combinations of currents and has occurred on the line side of the relay and the fault is
voltages can be used for this comparison. Consider that very close to the relay location. The voltages and cur-
the three directional relays are applied currents from rents for this situation are shown in Figure 9 (b). No-
phases A, B and C. Two of the several options for select- tice that the current I, leads the polarizing voltage (Ve-
ing the voltages for use in these relays are listed in Table 1. V J by a small angle, from 10 to 30. Also, the current
In Option 1, the voltage element of the relay, which re- I, leads the polarizing voltage (Va-Vc) by a small angle.
ceives phase A current, is applied voltage from phase C. This ensures that the relays sense that the fault is in the
As shown in Figure 8, unity power factor load current forward direction.
leads the applied voltage by 60. This is also true for the
relays which receive phase B and phase C currents using 4.3.2 Polarizing quantity
connections of Option 1. The relays which use this combi- Many relays use a voltage or current as a reference for
nation of currents and voltages are identified as having a comparing their operating signal. This quantity has a pre-
connection angle of 60. dictable phasor relationship to the current flowing to a
Similarly, when connections of Option 2 are used, the re- fault, irrespective of the location of the fault. The refer-
lay, which receives phase A current, is applied the voltage ence voltage or current is referred to as the polarizing sig-
from phase B minus the voltage from phase C. In this nal.
case, the unity power factor current leads the applied volt- Example: A healthy phase voltage, in addition to the
age by 90. This is also true for the relays that receive faulted phase voltage, is sometimes used in a relay as a
phase B and phase C currents. The relays using this com- polarizing voltage to assist in accurately determining
bination of currents and voltages are identified as having a the direction of the fault. This helps in correctly iden-
connection angle of 90. The phasor diagram for this tifying the direction of the fault especially when the
situation is also shown in Figure 8. The polarizing voltage, magnitude of the faulted phase voltage is small. If a
Vb-Vc, and fault current for phase A to ground fault. la' are fault, between phase b and phase c is experienced very
also shown in this figure. Notice that the phase displace- close to the relay location, the phase b to phase c volt-
ment between the fault current and the polarizing voltage is age collapses. The phase voltages for this situation and
less than 30. the currents are shown in Figure 9 (b). The polarizing
The voltages, which are referred to as polarizing voltages, voltages and fault currents are also shown in this fig-
are selected in such a manner that they remain relatively ure. It is obvious from this figure that even if the phase
unchanged during a fault. This ensures that during system b and phase c voltages have collapsed to low values, the
faults, when the currents have substantial magnitudes, the polarizing voltages are substantial to ensure relay op-
polarizing voltages are as close to the nominal value as eration.
possible.
Table 1. Voltage and current combinations for 60 and 90 connections for directional relays.
- 11 -
Terms Used by Power System Protection Engineers
Copyright <0 The Institute of Electrical and Electronics Engineers, Inc.
Vc Vc
\
Va I~ Ia Va
\
~ Ib
Vb Vpo1= -Vc Vb
y
6cP Connection Vpo1= 'b-Vc
v c-V a V -V
a b
V -V
b c
Phase voltages andcurrents Polarizing voltages andcurrents
during normal operation during normal operation
Figure 9 (a). Phase and polarizing voltages, and phase currents during normal operation.
Figure 9 (b). Phase currents and polarizing voltages for identifying the direction of a phase-b to phase-c fault.
- 12 -
Terms Usedby Power SystemProtectionEngineers
Copyright C The Instituteof Electrical and Electronics Engineers, Inc.
5. OHMIC RELAY APPLICATIONS
This class of relays was originally used to protect transmis- predominantly resistive. But, during faults, this impedance
sion lines and were believed to measure the distance from is lower and highly reactive in nature. A change in the
the relay location to a fault. Currently, several types are detected impedance is used to determine if a fault has oc-
applied to power systems for protecting lines during faults, curred, and also if the fault is in its zone of protection or is
generators during loss of excitation, and the system during elsewhere on the system. This is accomplished by limiting
power swings. The terms most commonly used and de- the operation of the relay to a certain range of the observed
scribed in this section are impedance, commonly called, "reach." When a fault oc-
curs within the protected zone of a distance relay protect-
distance relay,
ing an end to end line, only the faulted transmission line is
impedance relay,
isolated.
mho relay, and
Blinder. The operating characteristics of these relays are expressed
in terms of impedance or its components, resistance and
5.1 Distance Relay reactance. Plotted on a rectangular coordinate system,
(using resistance, R, as the abscissa and reactance, X, as
Faults on transmission lines are commonly detected by the ordinate) the characteristics usually form simple geo-
protective relays that measure and respond to one or an- metric figures. Commonly used operating characteristics
other form of the ratio of voltage to current. This ratio is are shown in Figure 11. The point of measurement for a
impedance or a component of impedance. These relays are distance relay is located at the origin of the figures, and the
termed distance relays because (ideally) the measured im- relay is designed to generally operate when the measured
pedance is proportional to the distance along a homogene- impedance falls within the shaded area in the figures.
ous transmission line from the relay location to the fault.
This class of relays is assigned device number 21. The major advantage of using a distance relay for multi-
phase faults, not involving ground, is that its zone of op-
The portion of line that is being protected by a distance eration is a function of only the impedance of the protected
relay is called the "zone of protection" or the "protected line and the fault resistance (except for the situations when
zone." Figure 10 shows that the zone of protection of Re- there is current in-feed from the remote terminal of the line
lay A, installed at bus 1, is from the relay location to a lo- or there is mutual coupling with lines on the same right of
cation close to bus 2. Similarly, the zone of protection of way). This is approximately a fixed constant, irrespective
Relay B, installed at bus 2, is from the relay location to a of the levels of fault current magnitudes. Therefore, a dis-
location close to bus 1. If the line impedance is Z, the tance relay has a fixed reach, as opposed to an overcurrent
reach of each relay is nZ; n ranging from 0.75 to 0.90 in relay whose reach varies as the system operating condi-
some applications, and more than 1.0 in some others. tions change. Consequently, it is not necessary to change
the settings of distance relays unless the line characteristics
Relay A Reach Location of
~l
Zone of Protection of Relay A I
-----nZ .1
jaYB change. This makes distance relays ideally suited for pri-
mary and backup protection for faults on transmission
lines.
I
t--_----
Y I
Z I
1 Transmission Line I 5.2 Impedance Relay
I"
Busl I~ nZ----- Bus 2
1 Zone of Protecuon of Relay 8 Relays that respond to the magnitude of the measured im-
Location of pedance are classified as impedance relays. The measure-
Relay A Relay BReach ment is taken by determining the ratio of the rms voltage of
the line at the relay location to the rms current flowing in
the line at the relay location. These relays are commonly
Figure 10. Protection zones for relays protecting a applied to detect faults on transmission lines. A compari-
transmission line. son of the measured impedance with the line impedance
provides an indication whether the fault is in the protected
The impedance measured during normal operation of a line zone of the relay or not. This type of relay is also assigned
is the ratio of the voltage at the line terminal and the cur- a device number of21.
rent flowing in the line; this value is usually high and is
- 13 -
Terms Used by PowerSystem Protection Engineers
Copyright o The Institute of Electrical and Electronics Engineers, Inc.
jX Line Impedance jX Line Impedance
Restraint
Maximum
R Sensitivity Angle
Mho Characteristic
Impedance Characteristic
- Forward Reach
jX jX
Restraint Restraint
R R
The operating characteristics of the impedance relay, and power crossing the air gap being less than the load on the
the "reach," plotted on a rectangular coordinate system, is shaft, which is a function of the supply voltage and its
shown in Figure 12. Since an impedance relay responds to phase displacement from the voltage of the receiving sys-
measurements in all quadrants, a directional unit is gener- tem.
ally used to limit the reach to the line side of the relay, as is
shown in this figure. With this combination, the impedance 5.3 Mho Relay
relay responds only to the measured impedances which are
Distance relays can be designed to have circular operating
in the shaded portion of this diagram.
characteristics, plotted on an impedance plane, that passes
A variation of the impedance relays, called "offset imped- through the origin of the plane as shown in Figure 13. This
ance relays," whose characteristic is also shown in Figure type of relay is called a Mho relay or Admittance relay. A
12, are used to start power line carrier protection. These fraction n of the line impedance ZL is a measure of dis-
relays look from the circuit breaker towards the line as well tance of the fault on the line from the relay location. The
as the station bus. In addition, impedance relays can be Mho relay is inherently directional; that is, it will "see"
used to protect generators and transmission lines from out- and, therefore, respond only to transmission line faults in
of-step conditions. On generators, this condition is due to one direction from the relay location. Maximum torque
- 14 -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
angle is the impedance angle at which the relay is most the reach of the third zone setting of the line protection
sensitive. relays. A distance relay which has a straight-line non-
directional characteristic is used to block the line relay
5.4 Blinder
from tripping during normal operation of the line. The
Sometimes transmission lines are heavily loaded . The characteristic takes advantage of the fact that the apparent
power being transmitted is such that the voltage to current impedance is predominantly resistive. The typical charac-
ratio (apparent impedance) at the line terminal is less than teristic ofa blinder is shown in Figure 13.
jX Line Impedance
Restraint
Maximum
Sensitivity Angle
R
Operating characteristic
of an impedance and a
directional relay
jX jX
Line Impedance
Restraint
Maximum
Sensitivity Angle
Restraint
R R
Mho Characteristic
- Forward Reach Blinder Characteristic
- 15 -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electricaland Electronics Engineers, Inc.
6. OTHER RELAYS
Several other relays are used in power systems. Terms differential relay is used and an internal fault occurs, the
used for the following relays are described in this section. total ct secondary current flows through the high imped-
ance overvoltage coil, producing operation.
Differential relays
Inrush phenomenon
Combustible gas relay
Gas accumulation relay Protected ...._..,......~. ._ _
Static pressure relay ---. Device
Sudden pressure relay I.
In
Thermal relay
Replica or replica temperature relay
RTD relay
Phase disagreement
Breaker failure
Pole flash-over
Single phase tripping ---. I-
In
---. I
out
Figure 14. A typical current differential relay.
6.1 Differential Relays
Differential relays, which are assigned the device number Since the fault currents are large and the cts are not perfect,
87 by ANSI, are used for protecting lines, transformers, there is always a relay operating current when a fault oc-
generators, buses and other components of power systems. curs outside the differential relay zone. This current could
They function on the principal of comparing two or more cause an undesired operation of the relay. One of the
electrical quantities (usually currents) and operating if the measures used to keep the differential relays from operat-
difference between the values of any signal, observed at ing during external faults is the use of the percentage dif-
the input and output terminals of the protected component ferential principle. Figure 15 shows one phase of a typical
of the power system, exceeds a specified threshold. percentage current differential relay. Two restraining
coils, R1 and R2, are included to provide the restraint. The
Current differential relays are based on Kirchhoffs current
operating coil is excited by the difference between the cur-
law which states that the sum of currents entering a node in
rents lin and lout, but the relay operates only when the
a network must be zero. Cts are used to provide the cur-
operating current, lin-lout, is more than a specified per-
rents entering and leaving a zone to a current differential
centage of the restraint currents.
relay. The currents entering a zone are compared with
those leaving the zone. The operating current is the phasor
difference between these currents.
When there is a fault in the protected zone, the currents Protected t--..,....~...--
entering and leaving the protected zone do not add to zero ---. Device
and, therefore, the differential relay operates. On the other I-In
hand, when there is a fault outside the protected zone, the
currents entering and leaving the zone add to approxi-
mately zero and the differential relay does not operate. tI I.In
Figure 14 shows one phase of a differential relay circuit. j Iop=1.-1
In out
The cts are connected to each other and to the operating
coil of the differential relay. The current in the operating
coil is the difference between lin and lout. ---.
I.
---.
I
In low impedance current differential relays, the difference In out
current flows in the operating coil and the relay operates
like an overcurrent relay. When a high impedance current Figure 15. A typical percentage differential relay.
- 16 -
TermsUsedby PowerSystem Protection Engineers
Copyright (0 The Institute of Electrical and Electronics Engineers, Inc.
6.1.1 Transformer differential protection The phase shift matching can also be achieved (incorrectly)
by connecting the wye-side cts in wye and delta-side cts in
The ratio of the cts provided at the two terminals of the delta. This arrangement would not compensate for the
protected zone and the differences in their characteristics zero-sequence currents that would flow in the wye-
are always of concern in most applications. When differ- connected winding and not in the delta-connected winding.
ential relays are used to protect transformers, the issues In the arrangement of Figure 16, zero-sequence currents
that are given special consideration include flow in the wye-connected winding but circulate in the
matching of ct ratios and performance, delta winding when a single phase to ground fault on the
phase shift due to transformer winding interconnec- system connected to the wye winding of the transformer is
tions, experienced. The outputs of the cts provided on the delta
elimination of zero sequence currents, and side do not contain the zero-sequence currents. The solu-
transformer inrush. tion is to eliminate the zero-sequence currents from the
outputs of the cts connected to the wye connected winding.
The volt-amperes at the primary and secondary terminals This can be done by using a zero-sequence shunt (or trap)
of a two-winding transformer are equal if the magnetizing or by connecting the ct secondaries in delta, which also
currents are negligible. If a transformer steps up the pri- solves the phase shift problem described above.
mary voltage to a higher level, the current at the high volt-
age terminal is proportionately reduced. Selection of ap-
propriate ct ratios is used to match the magnitudes of the
currents entering and leaving the protected zone as applied
to the relay.
The connections of the windings of the protected trans-
former may introduce a phase shift. For example, a trans-
former with the high-side winding connected in delta and No 10 flow Singleline-
the low-side winding connected in wye, would shift the to-ground
phase angle of the low-side current by 30. To compensate fault
for this phase shift, the cts of the wye side are connected in Figure 16. Zero-sequence currents in a delta-wye
delta and cts outside the delta winding are connected in transformer.
wye.
Example: Consider a three-phase 100 MV A delta-
6.1.2 Magnetizing inrush currents
wye 13.8/230 kV transformer. The nominal currents on When a transformer is disconnected from the system and
the 13.8 kV and 230 kV sides are the flow of current is interrupted, the transformer core re-
tains a residual flux. The next time the transformer is en-
100 *1000.;. (13.8 *~) = 4,184 A ergized, the core may saturate and, therefore, draw large
100 * 1000.;. (230 *~) =
magnetizing currents from the source even if no load is
251 A
connected to the transformer. Since the magnetizing cur-
If the primary cts are of 5,000/5 ratio and the secondary rent is supplied by the source and is not reflected on the
cts are of 400/5 ratio, the outputs of the primary and output side of the transformer, it shows up as operating
secondary cts will be 4.18 A and 3. 14 A respectively, current in the differential relay circuit. Therefore, the relay
when the transformer is supplying rated current. must be restrained from operating for this current.
Since cts on the wye-side of the transformer are connected The waveforms of magnetizing inrush currents are not si-
in delta, the outputs applied to the relay by the secondary nusoids of a single frequency; they contain substantial
cts will be 3.14*"3 = 5.43 A. The difference between the amounts of harmonics. Figure 17 shows two examples of
4.18 A current from the primary cts and 5.43 A current the magnetizing inrush currents flowing into a delta wind-
from the secondary cts is eliminated by using ratio match- ing of a delta-wye transformer. These currents decay over
ing cts provided in the relays (or installed outside the relay) a period of time, which depends on the size and type of the
or taps provided on the relay. In some microprocessor transformer and the nature of the system.
relays, this is achieved by including a multiplier in the re-
lay software.
- 17 -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
2O',-------,-----.----..------r---
-.---,---~
portion of the gas released by the protected equipment. It
operates when the volume of gas reaches a certain level.
The accumulator relay can only be applied to transformers
with conservator tanks . Another name for this device is a
gas detection relay .
!
~
5
011--------"
low the oil level on the transformer tank wall and is acti-
vated by the pressure in the tank . Because of the many
incorrect operations of the static pressure relays over the
jl<
years, most have been superseded by sudden pressure re-
~ -5 lays.
.'O!----=----f;;---~-__.;;---___,;il-____,;O-_;:
IO , 40
20 eo
(b)
00 '00 120
TlWE-'" 6.2.4 Sudden pressure relay
Two types of sudden pressure relays (assigned device
Figure 17. Typical magnetizing inrush currents in a number 63) generally used to protect transformers are the
delta-wye transformer. sudden gas pressure and sudden oil pressure relays.
6.2 Other Relays for Transformer Protection Sudden gas pressure relays operate if the rate of rise of
pressure in the transformer exceeds a specified level.
Other relays generally used for transformer protection in- These relays can be applied on all gas cushioned oil-
clude immersed transformers and are mounted in the gas space
combustible gas relay, above the oil.
gas accumulation relay, Sudden oil pressure relays measure the rate of rise of oil
static pressure relay, pressure and operate if it exceeds a specified value. These
sudden pressure relay, relays can be applied on all oil-immersed transformers and
thermal replica relay , are usually mounted near the bottom of the transformer
RTD relay, tank wall.
loss-of-field (excitation) relay, and
out-of-step relay. These relays are commonly used to protect transformers
and are generally connected to trip circuit breakers to dis-
These relays are briefly described in this section . connect the transformer from the rest of the power system.
Because the micro-switch contacts used in sudden pressure
6.2.1 Combustible gas relay relays are sensitive to control circuit disturbances, an aux-
iliary relay is often included in the sudden pressure circuit.
The combustible gas relay is applied to transformers which
are equipped with positive pressure inert gas-oil preserva-
tion systems . This device measures the presence of com- 6.3 Thermal Relay
bustible gas in the transformer in the inert gas blanket. The A thermal relay, (assigned device number 49) operates if
presence of the combustible gas indicates the decomposi- the heat developed within the relay as a result of external
tion of insulating materials due to faults or corona. Since and internal conditions exceeds a specified level. The re-
these faults are not accompanied with large fault currents, lay uses input(s) from ct(s) to monitor the 12R heating in
they are usually not detected by other relays until they de- the protected equipment. This relay is different from a
velop into major short circuits which usually cause sub- temperature relay which uses a temperature sensing device,
stantial damage . The combustible gas relay is expensive either in or on the equipment being monitored. The circuit
and is not normally applied on substation transformers. of a typical thermal relay is shown in Figure 19.
- 18 -
Terms Usedby Power SystemProtectionEngineers
Copyright <I} The Instituteof Electrical and Electronics Engineers, Inc.
Monitoring of the temperature is accomplished by using an temperature rise of the protected apparatus, or conductor,
RTD, gas bulb, thermocouple or another temperature over a range of values. A current proportional to the cur-
sensing device located at the point to be monitored. The rent in the protected equipment is passed through a heating
mounting of a typical temperature relay is shown in Figure element in the relay. The relay is designed to simulate the
20. heating and cooling of the protected apparatus. The mod-
eling of the cooling of the equipment is essential to protect
6.4.1 Replica relay or replica temperature the equipment from being returned to service too soon after
relay a thermal overload. A typical circuit for a replica relay is
shown in Figure 21.
These relays (assigned device number 49) are designed to
achieve an internal temperature rise proportional to the
Transformer
tank wall
Bellows Enlarged
. --. -
view
~
Trip
circuit Sudden / .....
Micro-switch
pressure relay
T r ansformer tank
Sealed
chamber Equalizing
mounted on orifice
the outside
of the tank
wall
Simplified scheme for a sudden gaspressure relay Sudden gas pressure relay mounting onthe
sideof a transformer above theoillevel
Figure 18. Mounting and schematic arrangement of a sudden gas pressure relay.
Electrical To protected!
Source monitored equipment Electrical Source to Equipment
Thermal
Relay
Figure 19. Thermal relay monitors IZR losses in the Figure 20. The mounting of a typical temperature re-
protected equipment. lay.
- 19 -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
of the system experiencing a disturbance, the magnetic
Electrical To protected! field must be changed to maintain the system voltage (at or
Source monitored equipment near the generator terminals) at the nominal value.
The excitation system can be supplied current from an
auxiliary generator mounted on the shaft of the main tur-
Bi-metal
bine-generator unit, or from the plant auxiliary bus, or the
main generator. Several circumstances can result in loss-
of-field; these include
Resistoror
accidental tripping of the field circuit breaker,
heat source
poor brush contact in the slip rings of the rotor, and
loss of ac supply to the excitation system.
Figure 21. The circuit diagram of a replica relay. Reduced levels of excitation, or complete loss of field can
result in loss of synchronism, instability and, possibly,
6.4.2 RTD relay damage to the generator. When a disturbance is experi-
enced, the generator output oscillates (accompanied with
A temperature relay, assigned device number 49, uses a
rotor oscillations) in an attempt to stay in synchronous op-
resistance temperature detector (RTO) to monitor the tem-
eration with the system. If the disturbance is accompanied
perature of the protected equipment. An RTO is a resistor
by a substantial decrease in the terminal voltage, system
made of a material whose resistance changes in a prede-
stability is threatened. For these reasons, a loss-of-field
termined manner when the temperature changes. Electro-
relay is applied to protect the generator and the system to
mechanical RTD relays normally use a Wheatstone bridge
which it is connected. The relay is usually designed to trip
(or an equivalent circuit) to sense the temperature changes
the generator when the relationship between the alternating
and respond with a predetermined output. One form of
voltages and currents, measured at the generator terminals,
microprocessor RTD relay applies a low level of current to
indicates that a loss-of-field condition has occurred. ANSI
the resistor and measures the voltage drop across the re-
has assigned device number 40 to loss-of-field relays.
sistor. From this measurement, it calculates the resistance
and the temperature. The electrical circuit of a RTD relay
is shown in Figure 22.
6.6 Out-or-step Relay
When two or more interconnected synchronous generators
or systems have lost synchronism with respect to one an-
other and are operating at different frequencies, they are
To~ said to be operating under an out-of-step condition. This
condition can be caused by a mismatch between the elec-
Power
trical output of the generator and the mechanical input to
SUP~
--I----~--t_'
the generator. Distance relays (in conjunction with blind-
Monitored ers) are applied to detect and trip the generators when this
Equipment is suspected to have happened. Generally, the protection is
designed either to trip the generator breaker or to open the
Figure 22. Circuit of a typical RTD relay. line interconnecting the two systems. The disconnected
generator, or the interconnecting line are brought back in
6.5 Loss-or-field (excitation) Relay service after the condition has stabilized. The out-of-step
The magnetic field is set up in a generator by providing dc relays are assigned the device number 78.
currents to the field winding of the generator. In the event
- 20-
Terms Used by Power SystemProtection Engineers
Copyright C The Instituteof Electrical and Electronics Engineers, Inc.
7. CIRCUIT BREAKER APPLICATIONS
breaker failure, B c D
phase disagreement,
pole flashover, or
single-phase tripping.
These terms are briefly described in this section.
Circuit breaker A fails to
7.1 Breaker Failure interrupt the fault current
tion, the breaker failure relay initiates the clearing of all the I
circuits that can feed current to the fault via the failed I
breaker. _I
- 21 -
Terms Usedby PowerSystemProtection Engineers
Copyright0 The Institute of Electrical and Electronics Engineers, Inc.
,-- the contacts of interrupters in the other two
-------------,
Remote i __[L-II- H phases are closed
- 22-
Terms Used by Power System Protection Engineers
Copyright o The Institute of Electrical and Electronics Engineers, Inc.
8. SYSTEM DISTURBANCES
The importance of protection from system disturbances has ating frequency decreases to a specified level below the
increased with the development of interconnections be- nominal frequency or if its rate of decay (df/dt) exceeds a
tween power systems. Load generation unbalance may be specified level. They trip selected loads to prevent a sys-
caused in a system by loss of generators or interconnec- tem from collapsing, or experiencing a major blackout, by
tions with the neighboring utilities. If the load of a system restoring the balance between load and generation.
exceeds the available generation, the frequency decreases.
Underfrequency relays are usually installed at distribution
Severe overloads produce rapid frequency decay. Rotating
substations and industrial installations, and are generally
machinery, especially steam turbines, cannot operate safely
set between 59.7 and 58.5 Hz. Time delays are usually
at frequencies less than a few percent below the rated fre-
applied to provide system security. In addition, particu-
quency. Frequency relays are, therefore, used to shed load
larly for solid-state underfrequency relays, an undervoltage
to restore generation-load balance.
inhibit function is included to further improve security.
Relays may have multiple settings to ensure that loads are
8.1 Underfrequency Relay tripped in small increments as the frequency decreases.
Underfrequency relays (assigned device number 81) are
applied to automatically shed load when the system oper-
- 23 -
Terms Used by PowerSystem Protection Engineers
Copyright (g The Institute of Electrical and Electronics Engineers, Inc.
9. DISTURBANCE ANALYSIS
Fault analysis has become an important activity because it records the state of discrete events, such as, "on" or "off'
provides a better insight in the operation of the system as status of a circuit breaker, "closing" or "opening" of a cir-
well as its equipment. Power system engineers, especially cuit breaker, activation of an alarm or its deactivation. In
protection engineers had been recording waveforms of addition to this binary information, the sequential event
voltages and currents during faults for many year. recorders note the absolute or relative time of the occur-
rence of the observed events. Other names used for a se-
Before the use of the digital electronics technology became
quential event recorder include sequence of events re-
wide spread in power systems, light beam oscilloscopes
corder, SER and data logger.
were being used. As the manufacturers developed digital
relays, they found that some capabilities for recording
waveforms of power system signals could be include in the 9.2 Transient Fault Recorder
relays. Consequently, several devices were made available A transient fault recorder is a device that records the mag-
that could record voltages and currents during systems nitudes of system quantities (typically currents, voltages,
disturbances. However, many stand-alone devices have etc.) along with the time when those magnitudes were ob-
been developed and used in power systems to record volt- served. Each recorder has a frequency response and a dy-
ages and currents during system disturbances. The differ- namic range that dictates the quality of the observations.
ence between the capabilities of the commercial relays and Depending on the design of the recorder, the signals can be
dedicated recording devices is that the resolution of the recorded for monitoring transient system changes, includ-
recording made by the relays are usually not as good as the ing the high frequency components in them, or for ob-
recordings made by the dedicated devices. serving long term changes, such as monitoring power sys-
Out of the several terms used in this area, the following tem swings. Often, a transient recorder includes the ability
terms are briefly described in this section. to record binary changes of states as described for the se-
quential events recorder.
Sequential events recorder
Transient fault recorder 9.3 Pre-fault, Fault and Post-Fault Periods
Pre-fault, fault and post-fault periods
Pre-fault period is the time before the inception of a fault.
9.1 Sequential Events Recorder Fault period is the time during which the system continues
to experience a fault. The post-fault period is the time that
A sequential events recorder is a system that monitors and starts from the instant a fault has been cleared.
- 24-
Terms Usedby PowerSystem Protection Engineers
Copyright C The Institute of Electrical and Electronics Engineers, Inc.
Bibliography
- 25 -
Terms Used by Power System Protection Engineers
Copyright The Institute of Electrical and Electronics Engineers, Inc.
Standards 39. ANSI/IEEE C37.97-1979 (R 1990), Guide
25. ANSI/IEEE C37.90-1989 (R 1994), Stan- for Protective Relay Applications to
dard for Relays and Relay Systems Asso- Power System Buses.
ciated with Electric Power Apparatus. 40. ANSI/IEEE C37.99-1990 (R 1994), Guide
26. ANSI/IEEE C37.90.1-1989 (R 1994), Stan- for Protection of Shunt Capacitor Banks.
dard Surge Withstand Capability (SWC) 41. ANSI/IEEE C37.101-1993, Guide for Gen-
Tests for Protective Relays and Relay erator Ground Protection.
Systems.
42. ANSI/IEEE C37.102-1987 (R 1990), Guide
27. ANSI/IEEE C37.90.2-1995, Standard With- for AC Generator Protection.
stand Capability of Relay Systems to Ra-
diated Electromagnetic Interference from 43. ANSI/IEEE C37.103-1990, Guide for Dif-
Transceivers. ferential and Polarizing Relay Circuit
Testing.
28. ANSI/IEEE C37.98-1987 (R 1990), Stan-
dard for Seismic Testing of Relays. 44. ANSI/IEEE C37.106-1987 (R 1992), Guide
for Abnormal-Frequency Protection for
29. ANSI/IEEE C37.100-1992, Standard Defi- Power Generating Plants.
nitions of Power Switchgear.
45. ANSI/IEEE C37.108-1989 (R 1994), Guide
30. ANSI/IEEE C37.105-1987 (R 1990), Stan- for the Protection of Network Transform-
dard for Qualifying Class IE Protective ers.
Relays and Auxiliaries for Nuclear Power
Generating Stations. 46. ANSI/IEEE C37.109-1988 (R 1993), Guide
for the Protection of Shunt Reactors.
31. ANSI/IEEE C37.111-1991, Standard Com- 47.
mon Format for Transient Data Exchange ANSI/IEEE C57.13.1-1981 (R 1992), Guide
(COMTRADE) for Power Systems. for Field Testing of Relaying Current
Transformers.
32. ANSI/IEEE C57.13.2-1991, Standard Con-
formance Test Procedures for Instrument 48. ANSI/IEEE C57.13.3-1983 (R 1990), Guide
Transformers. for the Grounding of Instrument Trans-
former Secondary Circuits and Cases.
33. IEEE Std 141-1993, Recommended Practice
for Electric Power Distribution for In- 49. ANSI/IEEE 643-1980 (R 1992), Guide for
dustrial Plants. Power Line Carrier Applications.
34. IEEE Std 242-1991, Recommended Practice 50. ANSI/IEEE 1001-1988, Guide for Interfac-
for Protection and Coordination of Indus- ing Dispersed Storage anad Generation
trial and Commercial Power Systems. Facilities with Electric Utility Systems.
- 26-
Terms Usedby PowerSystem Protection Engineers
Copyright C The Institute of Electrical and Electronics Engineers, Inc.
54. "Protection Aspects of Multi-Terminal 58. "Intertie Protection of Consumer-Owned
Lines." IEEE Publication No. 79TH Sources of Generation." IEEE Publica-
0056-2 PWR, 1979. tion No. 88 TH 0224-6 PWR, 1988.
55. "Sine-Wave Distortions in Power Systems 59. "Voltage Stability of Power Systems: Con-
and the Impact on Protective Relaying." cepts, Analytical Tools, and Industry Ex-
IEEE Publication No. 84 TH 0115-6 perience." IEEE Publication No. 90 TH
PWR,1985. 0358-2 PWR, 1990.
56. "Microwave Communication Channels for 60. "System Protection and Voltage Stability."
Protective Relaying Applications." IEEE IEEE Publication No. 93 TH 0596-7
Publication No. 85 TH 0129-7 PWR. PWR,1993.
57. "Application of Fault and Disturbance Re- 61. "Relay Performance Testing", IEEE publi-
cording Devices for Protective System cation No. 96 TP 115-0, 1996.
Analysis." IEEE Publication No. 87 TH
0195-8 PWR, 1987.
- 27-
Terms Used by PowerSystem Protection Engineers
Copyright <0 The Institute of Electrical and Electronics Engineers, Inc.