Gek 119592

Download as pdf or txt
Download as pdf or txt
You are on page 1of 312

GE

Digital Energy

850
Feeder Protection System
Feeder Protection and Control

COMMUNICATIONS GUIDE
850 version: 1.1
GE publication code: 1601-0299-A1 (GEK-119592)

*1601-0299-A1*
2013 GE Multilin Inc. Incorporated. All rights reserved.
GE Multilin Inc. 850 Feeder Protection System instruction manual for revision 1.1.
850 Feeder Protection System, EnerVista, EnerVista Launchpad, and EnerVista 8 Series
Setup are registered trademarks of GE Multilin Inc. Inc.
The contents of this manual are the property of GE Multilin Inc. Inc. This documentation is
furnished on license and may not be reproduced in whole or in part without the permission
of GE Multilin Inc. The content of this manual is for informational use only and is subject to
change without notice.
Part number: 1601-0299-A1 (December 2013)
GENERAL SAFETY PRECAUTIONS
Note

Failure to observe and follow the instructions provided in the equipment manual(s)
could cause irreversible damage to the equipment and could lead to property
damage, personal injury and/or death.
Before attempting to use the equipment, it is important that all danger and
caution indicators are reviewed.
If the equipment is used in a manner not specified by the manufacturer or
functions abnormally, proceed with caution. Otherwise, the protection provided by
the equipment may be impaired and can result in Impaired operation and injury.
Caution: Hazardous voltages can cause shock, burns or death.
Installation/service personnel must be familiar with general device test practices,
electrical awareness and safety precautions must be followed.
Before performing visual inspections, tests, or periodic maintenance on this device
or associated circuits, isolate or disconnect all hazardous live circuits and sources
of electric power.
Failure to shut equipment off prior to removing the power connections could
expose you to dangerous voltages causing injury or death.
All recommended equipment that should be grounded and must have a reliable
and un-compromised grounding path for safety purposes, protection against
electromagnetic interference and proper device operation.
Equipment grounds should be bonded together and connected to the facilitys
main ground system for primary power.
Keep all ground leads as short as possible.
At all times, equipment ground terminal must be grounded during device
operation and service.
In addition to the safety precautions mentioned all electrical connections made
must respect the applicable local jurisdiction electrical code.
Before working on CTs, they must be short-circuited.

This product cannot be disposed of as unsorted municipal waste in the European


Union. For proper recycling return this product to your supplier or a designated
collection point. For more information go to www.recyclethis.info.
Safety words and definitions
The following symbols used in this document indicate the following conditions

Indicates a hazardous situation which, if not avoided, will result in death or serious
Note

injury.

Indicates a hazardous situation which, if not avoided, could result in death or serious
Note

injury.

Indicates a hazardous situation which, if not avoided, could result in minor or


Note

moderate injury.

Indicates practices not related to personal injury.


Note
Table of Contents
1.INTRODUCTION 1-1
Communications .............................................................................................................................. 1 - 1
For Further Assistance ............................................................................................................................1 - 1

2.COMMUNICATIONS PORTS 2-1


RS485 Port........................................................................................................................................... 2 - 1
RS485 ..............................................................................................................................................................2 - 1
WiFi ......................................................................................................................................................... 2 - 2
WiFi Quick Start Procedure...................................................................................................................2 - 5
USB.......................................................................................................................................................... 2 - 6
Using the Quick Connect Feature via the USB Port...................................................................2 - 6
Ethernet Ports .................................................................................................................................... 2 - 7
Network Settings Menu ..........................................................................................................................2 - 7

3.TIME PROTOCOLS 3-1


Real-time Clock ................................................................................................................................. 3 - 1
IEEE 1588 Precision Time Protocol (PTP) .........................................................................................3 - 2
Clock ................................................................................................................................................................3 - 5

4.DNP 3 4-1
DNP communication ...................................................................................................................... 4 - 6
DNP device profile ........................................................................................................................... 4 - 7
DNP implementation ...................................................................................................................... 4 - 9

5.DNP / IEC104 POINT LISTS 5-1

6.IEC 60870-5-104 6-1


Interoperability.................................................................................................................................. 6 - 3

7.IEC 60870-5-103 7-1


Cause of Transmission .................................................................................................................. 7 - 1
Communications Menus............................................................................................................... 7 - 4
Interoperability.................................................................................................................................. 7 - 7
Physical layer...............................................................................................................................................7 - 7
Link layer .......................................................................................................................................................7 - 7
Application layer ........................................................................................................................................7 - 8

8.IEC 61850 8-1


General.................................................................................................................................................. 8 - 2
Functionality....................................................................................................................................... 8 - 5
The IEC 61850 Configurator........................................................................................................ 8 - 5
Online and Offline Setup ........................................................................................................................8 - 5
IEC 61850 Device Configurator Details ...........................................................................................8 - 7

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


9.TFTP 9-1

10.MODBUS PROTOCOL 10 - 1
Modbus Protocol ............................................................................................................................ 10 - 2

11.MODBUS MEMORY MAP 11 - 1


Reading the Event Recorder..................................................................................................... 11 - 1
Reading Transient Recorder ..................................................................................................... 11 - 1
Reading Fault Reports ................................................................................................................. 11 - 2
Accessing Data via the User Map .......................................................................................... 11 - 2
Memory Map Organization ....................................................................................................... 11 - 3
MODBUS memory map............................................................................................................... 11 - 3
Format Codes .............................................................................................................................11 - 130
Modbus Commands ................................................................................................................11 - 219

TOC-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 1: Introduction

Introduction

The 850 Feeder Protection Systems are microprocessor-based units intended for the
management and primary protection of distribution feeders, as well as for the
management and backup protection of buses, transformers, and transmission lines. The
850 relay is particularly suited to overhead feeders, where automatic reclosing is normally
applied.

Communications
The 850 has a two-stage communications capability. The base CPU supports Modbus
protocol through the Ethernet, USB and serial, as well as WiFi port. In addition, the base
CPU also supports IEC 103, DNP serial, and TFTP protocol. Once the communications
module option is added to the base, the base Ethernet port becomes disabled but the two
Ethernet ports on the communications module have enhanced communications
capabilities such as 61850, IEC62439 parallel redundancy protocol, IEEE 1588 Precision
Time Protocol. The communications CPU also supports IEC 104, DNP tcp, TFTP, and SNTP
protocol.

For Further Assistance


For product support, contact the information and call center as follows:
GE Digital Energy
650 Markland Street
Markham, Ontario
Canada L6C 0M1
Worldwide telephone: +1 905 927 7070
Europe/Middle East/Africa telephone: +34 94 485 88 54
North America toll-free: 1 800 547 8629
Fax: +1 905 927 5098
Worldwide e-mail: [email protected]
Europe e-mail: [email protected]
Website: http://www.gedigitalenergy.com/multilin

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 1-1


COMMUNICATIONS CHAPTER 1: INTRODUCTION

1-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 2: Communications Ports

Communications Ports

The 850 has four communications ports: RS485, WiFi, USB, and Ethernet.

RS485 Port
CHARACTERISTICS
RS485 port: ............................................................ Opto-coupled
Baud rates:............................................................. up to 115 kbps
Response time:..................................................... 6.62 ms typical
Parity:........................................................................ None, Odd, Even
Protocol: .................................................................. Modbus RTU, DNP 3.0, IEC 60870-5-103
Maximum distance: ........................................... 1200 m (4000 feet)
Isolation:.................................................................. 2 kV

RS485
On the rear card the 850 is equipped with one RS485 serial communication port and one
10/100 Mbps Ethernet port. The RS485 port has settings for baud rate and parity. It is
important that these parameters agree with the settings used on the computer or other
equipment connected to these ports. A maximum of 32 relays can be daisy-chained and
connected to a DCS, PLC or a PC using the RS485 ports.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 2-1


WIFI CHAPTER 2: COMMUNICATIONS PORTS

Path: Setpoints > Device > Communications > RS485


BAUD RATE
Range: 9600, 19200, 38400, 57600, 115200
Default: 115200
PARITY
Range: None, Odd, Even
Default: None
PORT PROTOCOL
Range: Modbus, DNP3, IEC 60870-5-103
Default: Modbus

WiFi
WiFi refers to Wireless Local Area Networks (WLANs) that are based on the 802.11 set of
standards. WLANs are essentially providing Local Area Network (LAN) type of connectivity
but without the need of cables, which makes them more convenient for use in limited
spaces. WiFi works on top of the TCP/IP stack, the same as Ethernet. The signal strength
and its range is determined by the wireless devices antenna technology and standard, the
best being IEEE 802.11n.
WiFi defines two modes of operation, namely ad-hoc, used for small deployments, and
infrastructure mode, which supports more robust types of security and better capabilities
for centralized management. The infrastructure mode requires an access point (AP).
Devices operating in this mode pass all data through the AP.
The WiFi module integrated on the 8-Series of products conforms to IEEE 802.11b/g/n
standards. The 8-Series devices operate in infrastructure mode. Security is optional, but
enabled by default and it is advisable that it is left on, as wireless traffic is very susceptible
to cyber-attacks.
The security technology used is WPA2 (Wireless Protected Access version 2), based on the
IEEE 802.11i standard for data encryption. WPA2 is a second version of WPA technology,
designed to solve known security limitations found in one of the encryption algorithms
used by WPA, namely TKIP (Temporal Key Integrity Protocol). WPA2 uses CCMP (Counter
Mode with Cipher Block Chaining Message Authentication Code Protocol), which provides
an enhanced data cryptographic encapsulation mechanism based on AES (Advanced
Encryption Standard). CCMP makes WPA2 much stronger and secure than its predecessors,
WPA and WEP.
Several forms of WPA2 security keys exist. The 8-Series support WPA2 PSK (Pre-Shared
Key), which utilizes 64 hexadecimal digits. The key may actually be entered as a string of 64
hexadecimal digits or as a passphrase of 8 to 32 printable ASCII characters. For user
convenience, the settings accept the key in the form of a passphrase, internally the ASCII
passphrase is used for deriving a 256-bit key.
WiFi Settings
The following are the WiFi network settings for the 8-Series product. Only an Administrator
has the rights to change them.

2-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 2: COMMUNICATIONS PORTS WIFI

Path: Setpoints > Device > Communications > WiFi

WiFi WiFi Enable: Range: Enabled, Disabled


Default: Enabled
Enabled

Message
WiFi IP Address: Range: Standard IPV4 address format
Default: 192.168.0.x
192.168.0.x

Message WiFi Subnet Mask: Range: Standard IPV4 mask format


Default: 255.255.255.0
255.255.255.0

Message WiFi GWY IP Address: Range: Standard IPV4 address format


Default: 0.0.0.0
0.0.0.0

Message
WiFi Security: Range: None, WPA2-PSK
Default: WPA2-PSK
WPA2-PSK

Message WiFi SSID: Any name using up to  characters


Default: provided by vendor
xxxxxxxx

Message Any 8 to  ASCII characters


WiFi WPA2 passphrase: Default: Provided by vendor and not
visible on the user interface
**********
WiFi Enable
This setting switches WiFi functionality on/off. By default WiFi is enabled in the basic
offering, but it is disabled in software options that offer CyberSentry.
WiFi IP Address / Subnet Mask
The default IP address is 192.168.1.x, where x is calculated as:
X = (modulo 252 of the last 3 digits of the serial number) + 2
This is to ensure uniqueness of the default IP address for all 850s present on one wireless
network.
In order for the wireless connection to be established between the AP, the 850s and a
FASTPATH:

laptop, the AP and the laptop must be configured with IP address belonging to the network
192.168.0.0/24. The following two addresses have been reserved for this purpose:
AP: IP address = 192.168.0.1; IP mask = 255.255.255.0
Laptop: IP address = 192.168.0.2; IP mask = 255.255.255.0

WiFi Security
The setting enables WiFi security. If set to None, there is no security and all traffic is open.
By default WiFi Security is set to WPA2-PSK.
WiFi SSID
The SSID is the public name of a wireless network. All of the wireless devices on a WLAN
must use the same SSID in order to communicate with each other. The default for the SSID
is provided by the vendor with the shipment of any new 8-Series device. It is recommended
that the customer modifies this name as needed after initial startup, to ensure unique
SSIDs if several WLANs are configured.
SSID broadcast should be disabled on AP. This provides some extra protection by requiring
FASTPATH:

a user to know an SSID before the user can connect to the device and making it harder for
casual outsiders looking for wireless networks to find the device and attempt to connect.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 2-3


WIFI CHAPTER 2: COMMUNICATIONS PORTS

WiFi WPA2 Passphrase


The WPA2 Passphrase is used for generating the encryption key. The same passphrase
must be set on AP and on all devices communicating on the same WLAN. The passphrase
is a string of 8 to 32 printable ASCII characters. Internally a 256-bit key is calculated by
applying the PBKDF2 key derivation function to this passphrase, using the SSID as the salt
and 4096 iterations of HMAC-SHA1.
The 8-Series devices are configured with a default passphrase, which is provided by
vendor with the shipment of any new 8-Series device.
When choosing a new passphrase, the password complexity rules of CyberSentry must be
used (see the CyberSentry specification).
This field is visible only if the security is set to WPA2-PSK.
Ideally, the passphrase is set through EnerVista and not directly from the Keypad, where
FASTPATH:

there are limitations in terms of space and types of characters supported. However, for
convenience, the key setting is available from the Keypad as well.

WiFi Status
A WiFi symbol is displayed in the caption area of the 8-Series product front panel. The
following table lists all possibilities for this icon:

WiFi State WiFi Icon Color


Disabled Icon is grey and crossed by a red line
Disconnected Grey
Connecting Yellow
Connected Green

WiFi Events

Event Description
WiFi Connected, TIMESTAMP: This event is recorded to indicate a network
connect.
WiFi Disconnected, TIMESTAMP: This event is recorded to indicate a network
disconnect.

WiFi Targets
A target is produced while WiFi is enabled, but left to default settings.
The target looks something like this:

M **WiFi default settings**

What the user is expected to do: Change the WiFi settings from the defaults.

2-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 2: COMMUNICATIONS PORTS WIFI

WiFi Quick Start Procedure


The following provides the settings information and instructions to quickly setup.
Required Equipment
8-Series Relay with WiFi functionality
PC with WiFi
Access Point
Quick Start Procedure
1. The PC WiFi Network Settings are as follows:

TCP/IP Settings WiFi Login Settings


IP address: 192.168.0.2 SSID: provided with the 8-Series relay
Subnet Mask: 255.255.255.0 Security type: WPA2-PSK (WPA2-Personal)
Gateway: 192.168.0.1 Encryption: AES
Passphrase: provided with the 8-Series relay

2. The Access Point Settings are given below:

IP address: 192.168.0.1
Subnet Mask: 255.255.255.0
SSID: same as entered on the PC (provided with the 8-Series relay)
Broadcast disabled
Security type: WPA2-PSK (WPA2-Personal)
Encryption: AES
Passphrase: same as entered on the PC (provided with the 8-Series relay)

3. If the 8-Series relay(s) are in range, they automatically connect to the configured
Access Point.
4. Start EnerVista on a PC and use the Discover function, all relays within range appear
and are populated in Enervista for initial configuration and commissioning.
5. Once the relay is configured, change the 8-Series relay default WiFi SSID and
Passphrase settings to make the relay go into service.
Figure 2-1: Example of WiFi Deployment

850-1
850-2

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 2-5


USB CHAPTER 2: COMMUNICATIONS PORTS

USB
The USB parameters are as follows:
IP Address: 172.16.0.2
IP Mask: 255.255.255.0
IP Gateway: 172.16.0.1
Whenever the device is rebooted, the USB cable needs to be unplugged and plugged in
FASTPATH:

again for proper communication to be established over USB.

Connecting multiple 850 relays over USB to a single PC is not possible because in the case
FASTPATH:

of USB, the IP address of the device 172.16.0.2 is constant.

Using the Quick Connect Feature via the USB Port


From the EnerVista 8 Series Setupsoftware the Quick Connect button can be used to
establish a fast connection through the front panel USB port of a 850 relay.
Before starting, verify that the standard USB cable is properly connected from the laptop
computer to the front panel USB port.
1. Verify that the latest version of the EnerVista 8 Series Setup software is installed
(available from the GE EnerVista CD or online from http://www.GEMultilin.com). See the
software installation section in the 850 Feeder Protection System instruction manual
for installation details.
2. Select the 850 device from the EnerVista Launchpad to start EnerVista 8 Series Setup.
3. Click the Quick Connect button to open the Quick Connect dialog box.

4. Select the Interface, then click Connect.


5. The EnerVista 8 Series Setup software creates a site named Quick Connect with a
corresponding device also named Quick Connect and display them on the upper-left
corner of the screen. Expand the sections to view data directly from the 850 device.

2-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 2: COMMUNICATIONS PORTS ETHERNET PORTS

Ethernet Ports
The following communication offerings are available.
Base Offering
Modes: 10/100 Mbps
One Port: RJ45
Protocol: Modbus TCP, TFTP
Communications Card Option
Modes: 100 MB
Two Ports: ST (with this option both enabled ports are on the communications card; the
Ethernet port located on the base CPU is disabled)
Protocols: Modbus TCP, DNP3.0, IEC60870-5-104, IEC 61850 GOOSE, IEEE 1588, SNTP, IEC
62439-3 clause 4 (PRP)

Network Settings Menu


The following are the network settings menu of the 850 to accommodate the features of
the 850 product. If the communications card is installed network 1 is no longer available.
NETWORK 1, 4, 5, PRT1(4,5) IP ADDRESS
Range: Standard IPV4 Address format
Default: 169.254.3.3 (Port 1)
Default: 0.0.0.0 (Port 4, 5)
The setting sets the ports IPV4 address in standard IPV4 format.
The setting is valid on port 1 if the optional communications card is not present.
FASTPATH:

The setting is valid on port 5 if port 4s OPERATION is set to INDEPENDENT.

PRT1(4,5) SUBNET MASK


Range: Standard IP Address format
Default: 0.0.0.0
The setting sets the ports IPV4 Subnet Mask in standard IPV4 format.
The setting is valid on port 1 if the optional communications card is not present.
FASTPATH:

The setting is valid on port 5 if port 4s OPERATION is set to INDEPENDENT.

PRT1(4,5) GWY ADDRESS


Range: Standard IPV4 Address format
Default: 0.0.0.0
The setting sets the ports IPV4 Gateway Address in standard IPV4 format.
This setting is valid on port 1 if the optional communications card is not present.
FASTPATH:

This setting is valid on port 5 if port 4s OPERATION is set to INDEPENDENT.

LLA: LLA (Link Loss Alert) is a proprietary feature supported by the 850 relay fiber optic
ports. When enabled on a 850 fiber optic port this feature is able to detect a failure of
the fiber link, if port 4s OPERATION is set to LLA, the detection of a link failure by this
feature triggers the transfer of communications from port 4 to port 5. Port 5 mode
supports only full duplex.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 2-7


ETHERNET PORTS CHAPTER 2: COMMUNICATIONS PORTS

Notes:
FASTPATH:

1. The fiber optic ports support only 100 Mbps.


2. Changes to the Ethernet communications settings take effect only after rebooting the
relay.
3. All Ethernet ports have flex operands associated with them. A failure of one of the
Ethernet ports triggers an event, a target message and the corresponding operand
set.
The fiber optic ports support only full duplex mode.
FASTPATH:

PRT4 OPERATION
Range: Independent, LLA, PRP
Default: Independent
This setting determines the mode of operation for ports 4 and 5: INDEPENDENT, LLA or
PRP.
INDEPENDENT operation: ports 4 and 5 operate independently with their own MAC and
IP address.
LLA operation: the operation of ports 4 and 5 are as follows:
Ports 4 and 5 use port 4s MAC and IP address settings while port 5 is in standby mode in
that it does not actively communicate on the Ethernet network but monitors its link. If
PORT4s LLA detects a problem with the link, communications is switched to Port 5. Port
5 is, in effect, acting as a redundant or backup link to the network for port 4.
PRP (Parallel Redundancy Protocol): ports 4 and 5 use the same MAC (physical device)
address and combine information at the link layer. It is intended to only be used if the
two ports are connected to separate parallel LANs. In this mode of operation both ports
cannot be connected to the same LAN. The receiving devices process the first frame
received and discard the duplicate through a link redundancy entity (LRE) or similar
service that operates below layer 2. Aside from LRE, PRP uses conventional Ethernet
hardware but both ports must know they are in PRP. Both ports of PRP devices operate
with the same Internet Protocol (IP) addresses for traffic that uses IP Management
protocols such as Address Resolution Protocol (ARP) must operate correctly.
Duplicate Discard mode (only mode supported by the 8 Series). This is the normal
setting for PRP operation and once set it allows the sender LRE to append a six-octet
field that contains a sequence number, the Redundancy Control Trailer (RCT) to both
frames it sends. The receiver LRE uses the sequence number of the RCT and the source
MAC address to detect duplicates. It forwards only the first frame of a pair to its upper
layers.

2-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 3: Time Protocols

Time Protocols

The 850 supports an internal clock, SNTP, IRIG-B, and PTP 1588 as potential time
references.

Real-time Clock
Path: Setpoints > Device > Real Time Clock
The 850 is capable of receiving a time reference from several time sources in addition to its
own internal clock for the purpose of time-stamping events, transient recorders and other
occurrences within the relay. The accuracy of the time stamp is based on the time
reference that is used. The 850 supports an internal clock, SNTP, IRIG-B, and PTP 1588 as
potential time references.
If two or more time sources are available the time source with the higher priority shown in
table 1 is used where 1 is considered to be the highest priority. Please note that the time
source priority of PTP and IRIG-B can be swapped. If both PTP and IRIG-B are available to
the 850 by default the 850 clock syncs to PTP over IRIG-B. If PTP is not available the
850 CPU syncs the internal clock to IRIG-B.

Time Source Accuracy Priority


PTP (IEEE1588) 1*
IRIG-B 2*
SNTP 3
Internal Clock 4

* The priority of IRIG-B and PTP can be swapped.


Synchronization by IEC103, DNP, Modbus and IEC104 is not going to be issued if there is a
FASTPATH:

synch source from IRIGB, SNTP or PTP.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 3-1


REAL-TIME CLOCK CHAPTER 3: TIME PROTOCOLS

IEEE 1588 Precision Time Protocol (PTP)

PTP Status The present values of the PTP protocol are displayed here.
Path: Status > Clock > PTP Status

The RTC Sync Source actual value is the time synchronizing source the relay is using at
present. Possible sources are: Port 4 PTP Clock, Port 5 PTP Clock, IRIG-B, SNTP and None.
Grandmaster ID is the grandmaster Identity code being received from the present PTP
grandmaster, if any. When the relay is not using any PTP grandmaster, this actual value is
zero. The grandmaster Identity code is specified by PTP to be globally unique, so one can
always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
Accuracy is the estimated maximum time error at present in the Real Time Clock (RTC),
considering the quality information imbedded in the received time signal, how long the
relay has had to lock to the time source, and in the case of time signal interruptions, the
length of the interruption. The value 999,999,999 indicates that the magnitude of the
estimated error is one second or more, or that the error cannot be estimated.
Port 4 (5) PTP State is the present state of the ports PTP clock. The PTP clock state is:
DISABLED
If the ports function setting is Disabled
NO SIGNAL
If enabled but no signal from an active master has been found and selected
CALIBRATING
If an active master has been selected but lock is not at present established
SYNCHD (NO PDELAY)
If the port is synchronized, but the peer delay mechanism is non-operational
SYNCHRONIZED
If the port is synchronized

3-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 3: TIME PROTOCOLS REAL-TIME CLOCK

PTP Configuration Path: Setpoints > Device > Real Time Clock > PTP
REAL TIME CLOCK

PTP PORT 4 PTP FUNCTION: Range: Enabled, Disabled


Default: Disabled
Disabled

Message
PORT 4 PATH DELAY ADDER: Range: 0 to 60000 ns in steps of 1
Default: 0000 ns
00000 ns

Message
PORT 4 PATH DELAY: Range: -1000 to +1000 ns in steps of 1
Default: 0000 ns
ASYMMETRY: 0000 ns

Message PORT 5 PATH DELAY ADDER: Range: 0 to 60000 ns in steps of 1


Default: 0000 ns
00000 ns

Message
PORT 5 PATH DELAY: Range: -1000 to +1000 ns in steps of 1
Default: 0000 ns
ASYMMETRY: 0000 ns

Message STRICT POWER PROFILE: Range: Enabled, Disabled


Default: Enabled
Enabled

Message
PTP DOMAIN NUMBER: Range: 0 to 255
Default: 0
0

Message PTP VLAN PRIORITY: Range: 0 to 7


Default: 4
4

Message
PTP VLAN ID: Range: 0 to 4095
Default: 0
0

Message PTP PRIORITY: Range: 1, 2


Default: 1
1

PORT 4(5) PTP FUNCTION


Range: Disabled, Enabled
Default: Enabled
When the port setting is selected as Disabled, PTP is disabled on the port. The relay
does not generate, or listen to, PTP messages on the port.
PORT 4(5) PATH DELAY ADDER
Range: 0 to 60000 ns in steps of 1 ns
Default: 0 ns
The time delivered by PTP is advanced by the time value in the setting prior to the time
being used to synchronize the relays real time clock. This is to compensate to the extent
practical, for time delivery delays not compensated for in the network. In a fully
compliant PP network, the peer delay and the processing delay mechanisms
compensate for all the delays between the grandmaster and the relay. In such networks,
the setting is zero.
In networks containing one or more switches and/or clocks that do not implement both
of these mechanisms, not all delays are compensated, so the time of message arrival at
the relay is later than the time indicated in the message. The setting can be used to
approximately compensate for the delay. Since the relay is not aware of network
switching that dynamically changes the amount of uncompensated delay, there is no
setting that always completely correct for uncompensated delay. A setting can be
chosen that reduces worst-case error to half of the range between minimum and
maximum uncompensated delay if these values are known.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 3-3


REAL-TIME CLOCK CHAPTER 3: TIME PROTOCOLS

PORT 4(5) PATH DELAY ASYMMETRY


Range: -5000 to +5000 ns in steps of 1 ns
Default: 0 ns
The setting corresponds to Delay Asymmetry in PTP, which is used by the peer delay
mechanism to compensate for any difference in the propagation delay between the two
directions of a link. Except in unusual cases, the two fibers are of essentially identical
length and composition, so the setting is set to zero.
In unusual cases where the length of link is different in different directions, the setting is
be set to the number of nanoseconds longer the Ethernet propagation delay is to the
relay compared with the mean of path propagation delays to and the from the relay. For
instance, if it is known say from the physical length of the fibers and the propagation
speed in the fibers that the delay from the relay to the Ethernet switch it is connected to
is 9 000 ns and that the delay from the switch to the relay is 11 000 ns, then the mean
delay is 10 000 ns, and the path delay asymmetry is +1 000 ns.
STRICT POWER PROFILE
Range: Enabled, Disabled
Default: Enabled
Power profile (IEEE Std C37.238 2011) requires that the relay select as a grandmaster
only power profile compliant clocks, that the delivered time have a worst-case error of
1 s, and that the peer delay mechanism be implemented. With the strict power profile
setting enabled, the relay selects as master only clocks displaying the IEEE_C37_238
identification codes. It uses a port only when the peer delay mechanism is operational.
With the strict power profile setting disabled, the relay uses clocks without the power
profile identification when no power profile clocks are present, and uses ports even if
the peer delay mechanism is non-operational.
The setting applies to all of the relays PTP-capable ports.
PTP DOMAIN NUMBER
Range: 0 to 255
Default: 0
The setting is set to the domain number of the grandmaster-capable clock(s) to which
they can be synchronized. A network may support multiple time distribution domains,
each distinguished with a unique domain number. More commonly, there is a single
domain using the default domain number zero.
The setting applies to all of the relays PTP-capable ports.
PTP VLAN PRIORITY
Range: 0 to 7
Default: 4
The setting selects the value of the priority field in the 802.1Q VLAN tag in request
messages issued by the relays peer delay mechanism. In compliance with PP the default
VLAN priority is 4, but it is recommended that in accordance with PTP it be set to 7.
Depending on the characteristics of the device to which the relay is directly linked, VLAN
Priority may have no effect.
The setting applies to all of the relays PTP-capable ports.

3-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 3: TIME PROTOCOLS REAL-TIME CLOCK

PTP VLAN ID
Range: 0 to 4095
Default: 0
The setting selects the value of the ID field in the 802.1Q VLAN tag in request messages
issued by the relays peer delay mechanism. It is provided in compliance with PP. As
these messages have a destination address that indicates they are not to be bridged,
their VLAN ID serves no function, and so may be left at its default value.
Depending on the characteristics of the device to which the relay is directly linked, VLAN
ID may have no effect.
The setting applies to all of the relays PTP-capable ports.
PTP PRIORITY
Range: 1, 2
Default: 1
The setting sets the priority of PTP time for the relay. If set to 1 and IRIG-B is available, the
relay syncs the relays time reference to the PTP time. If set to 2 and IRIG-B is available,
the relay syncs its reference to IRIG-B time.

Clock
Path: Setpoints > Device > Real Time Clock > Clock
DATE
Format: Month/Day/Year
Range: Month: 1 to 12; Day: 1 to 31; Year: 2008 to 2094
Default: 01/01/2008
TIME
Range: 0 to 23: 0 to 59:0 to 59
Default: 00:00:00
IRIG-B
Range: Disabled, Enabled
Default: Disabled
REAL-TIME CLOCK EVENTS
Range: Disabled, Enabled
Default: Enabled
LOCAL TIME OFFSET FROM UTC
Range: 24.0 to 24.0 hrs in steps of 0.5 hrs
Default: 0.0 hrs
DAYLIGHT SAVINGS TIME
Range: Disabled, Enabled
Default: Disabled
DST START MONTH
Range: January to December (all months)
Default: Not Set
DST START WEEKDAY
Range: Sunday to Saturday (all days of the week)
Default: Not Set
DST START WEEK
Range: First, Second, Third, Fourth, Last
Default: Not Set

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 3-5


REAL-TIME CLOCK CHAPTER 3: TIME PROTOCOLS

DST END MONTH


Range: January to December (all months)
Default: Not Set
DST END WEEKDAY
Range: Sunday to Saturday (all days of the week)
Default: Not Set
DST END WEEK
Range: First, Second, Third, Fourth, Last
Default: Not Set

IRIG-B IRIG-B is available in the basic offering of the product. The IRIG-B state has a flex operand
associated with it. A failure on IRIG-B triggers an event, the flex operand set, and a target
message.
Note that IRIG-B is auto detect. The signal type is detected in hardware, so there are no
FASTPATH:

configurable options.

3-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 4: DNP 3

DNP 3

The 850 supports Distributed Network Protocol (DNP) version 3.0. and the 850 operates as
a DNP slave device. Two DNP masters can actively communicate with the 850 at one time
as the 850 maintains two sets of DNP data change buffers and connection information.
The following is a detailed explanation of the 850 s DNP 3 implementation.
Both DNP and IEC104 protocol can work at the same time, but the user has to consider
FASTPATH:

that there is only one point map. So, both protocols use the same configured points.

The 850 supports two DNP3.0 client connections simultaneously.


FASTPATH:

Figure 4-1: DNP Data Types

850

DATA TYPES
Binary input data: Binary input data is used to monitor two-state device operations
such as the position of a breaker. The user can configure up to 96 Binary inputs. All
binary inputs are configured from Flexlogic operands.
Binary output data: Binary output data is used to control two-state devices such as
the opening and closing of a breaker. The 850 can be configured to support up to 16
Binary outputs. The clients Binary outputs are automatically mapped into the
850 virtual inputs starting at virtual input 1. Please note that the number of Binary/
Control outputs is configurable. Of the total number of outputs configured, the user
can configure a subset that supports dual point control. This subset starts at address
0.
Analog input data: Analog input data is used to monitor analog signals such as
voltages, currents, and power. The 850 has 32 analog inputs.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-1


CHAPTER 4: DNP 3

Analog output data: Not supported in the 850 .


Time stamps
Count input data: Count input data could represent a cumulative quantity such as
kilowatt-hours of energy. The 850 has 16 Count inputs

Table 4-1: Supported Object Numbers


Object DNP Data Type 850
1 Binary Input Status User Assigned FlexLogic Operands
2 Binary Input Change since last
read
10 Binary Output Status for User assigned Virtual Inputs and/
monitoring or Commands (client looks at
status only)
12 Control Relay Output Block User assigned Virtual inputs and/
or Commands (client can write to
the user specified number of
control relay outputs)
20 Counter Value Digital counters 1 through 16.
21 Frozen Counter Value
22 Counter Value Change since last
read
23 Frozen Counter Value Change
since last read by client
30 User configured Analog Input
value
32 User configured Analog Input
value changed since last time
read by client

Analog Variation Numbers Data Format


1 32-bit integer value with flag
2 16-bit integer value with flag
3 32-bit integer value without flag
4 16-bit integer value without flag
5 32-bit floating point value with flag

4-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 4: DNP 3

Path: Setpoints > Device > Communications > DNP Protocol


DNP CHANNEL 1 PORT
Range: NONE, NETWORK - TCP, NETWORK- UDP
Default: NONE
DNP CHANNEL 2 PORT
Range: NONE, NETWORK - TCP, NETWORK- UDP
Default: NONE
The DNP Channel 1 Port and DNP Channel 2 Port settings select the communications
port assigned to the DNP protocol for each channel. When this setting is set to Network
- TCP, the DNP protocol can be used over TCP/IP on channels 1 or 2. When this value is
set to Network - UDP, the DNP protocol can be used over UDP/IP.
If the Communications Board is not present, only RS485 is a possible option. The Network
FASTPATH:

options are hidden in this case and the DNP channel is defaulted to RS485.

DNP ADDRESS
Range: 0 to 65519 in steps of 1
Default: 65519
Sets the DNP slave address. This number identifies this 850 on a DNP communications
link. Each DNP slave should be assigned a unique address.
DNP NETWORK CLIENT ADDRESS 1(2)
Range: Standard IP Address
Default: 0.0.0.0
The DNP Network Client Address settings can force the 850 to respond to a maximum of
two specific DNP masters.
DNP TCP/UDP PORT NUMBER 1 (2)
Range: 1 to 65535 in steps of 1
Default: 20000
The DNP NETWORK CLIENT ADDRESS 1(2) and DNP TCP/UDP PORT NUMBER 1(2) settings
are available only if the communications card is present. DNP Channel 1 Port takes the
Port Number 1 and Client Address 1 to allow or reject connections. The same relation
is used by channel 2.
DNP UNSOL RESPONSE FUNCTION
Range: Enabled, Disabled
Default: Disabled
Should be Disabled for RS485 applications since there is no collision avoidance
mechanism. Unsolicited response settings is hidden if the communication card is not
present, as DNP runs only on RS485 in this case.
DNP UNSOL RESPONSE TIMEOUT
Range: 0 to 60 s in steps of 1 s
Default: 5 s
Sets the time the 850 waits for a DNP master to confirm an unsolicited response.
DNP UNSOL RESPONSE MAX RETRIES
Range: 1 to 255 in steps of 1
Default: 10
Sets the number of times the 850 retransmits an unsolicited response without receiving
confirmation from the master; a value of 255 allows infinite re-tries.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-3


CHAPTER 4: DNP 3

DNP UNSOL RESPONSE DEST ADDRESS


Range: 0 to 65519 in steps of 1
Default: 1
Sets the DNP address to which all unsolicited responses are sent. The IP address to
which unsolicited responses are sent is determined by the 850 from the current TCP
connection or the most recent UDP message.
DNP TIME SYNC IIN PERIOD
Range: 1 to 10080 min in steps of 1 min
Default: 1440 min
This setting determines how often the Need Time Internal Indication (IIN) bit is set by the
850 . Changing this time allows the DNP master to send time synchronization
commands more or less often, as required.
If the requirement for synchronization is more than a couple of seconds the user is advised
FASTPATH:

to consider synchronization via other means such as IRIG-B or 1588, given network
asymmetry, the consistency of the network latency, clock drift and additional delays due to
routers located between the client and the 850 , all of which contribute errors.

DNP MESSAGE FRAGMENT


Range: 30 to 2048 in steps of 1
Default: 240
This setting determines the size, in bytes, at which message fragmentation occurs. Large
fragment sizes allow for more efficient throughput; smaller fragment sizes cause more
application layer confirmations to be necessary which can provide for more robust data
transfer over noisy communication channels.
DNP OBJECT 1(2) DEFAULT VARIATION
Range: 1, 2
Default: 2
These settings allow the user to select the DNP default variation number for object types
1, 2, 20, 21, 22, 23, 30, and 32. The default variation refers to the variation response when
variation 0 is requested and/or in class 0, 1, 2, or 3 scans. The DNP binary outputs
typically map one-to-one to IED data points. That is, each DNP binary output controls a
single physical or virtual control point in an IED. In the 850 relay, DNP binary outputs are
mapped to virtual inputs.
DNP OBJECT 20(22) DEFAULT VARIATION
Range: 1, 2, 5, 6
Default: 1
For explanation, see above.
DNP OBJECT 21 DEFAULT VARIATION
Range: 1, 2, 9, 10
Default: 1
For explanation, see above.
DNP OBJECT 23 DEFAULT VARIATION
Range: 1, 2, 5, 6
Default: 2
For explanation, see above.
DNP OBJECT 30 DEFAULT VARIATION
Range: 1, 2, 3, 4, 5
Default: 1
For explanation, see above.

4-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 4: DNP 3

DNP OBJECT 32 DEFAULT VARIATION


Range: 1, 2, 3, 4, 5, 7
Default: 1
For explanation, see above.
DNP TCP CONNECTION TIMEOUT
Range: 10 to 300 s in steps of 1 s
Default: 120 s
The setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by
the setting, the connection is aborted by the 850 . This frees up the connection to be re-
used by a client.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-5


DNP COMMUNICATION CHAPTER 4: DNP 3

DNP communication
Figure 4-2: DNP communication menu

S1 DNP
DNP GENERAL S1 DNP GENERAL
DNP UNSOL RESPONSE* DNP ADDRESS
DEFAULT VARIATION
DNP TCP/UDP PORT
DNP CLIENT ADDRESS* CHANNEL 1 PORT
DNP POINTS LIST CHANNEL 2 PORT
TME SYNC IIN PER.
* Ethernet only
DNP MSG FRAG SIZE
DNP TCP CONN. T/O

DNP UNSOL RESPONSE*


FUNCTION POINT 0

TIMEOUT POINT 1
MAX RETRIES POINT 2
DEST ADDRESS ...
POINT 63

DEFAULT VARIATION
DNP OBJECT 1 POINT 0 ON

DNP OBJECT 2 POINT 0 OFF
DNP OBJECT 20 POINT 1 ON
DNP OBJECT 21 POINT 1 OFF
DNP OBJECT 22 ...
DNP OBJECT 23 POINT 15 ON
DNP OBJECT 30 POINT 15 OFF
DNP OBJECT 32
POINT 0 ENTRY

DNP CLIENT ADDRESS*
POINT 1 ENTRY
CLIENT ADDRESS 1
POINT 2 ENTRY

...
CLIENT ADDRESS 2
POINT 31 ENTRY
CLIENT ADDRESS 3
CLIENT ADDRESS 4
CLIENT ADDRESS 5

S1 DNP POINTS LIST


BINARY INPUTS
BINARY OUTPUTS
898769A1.cdr
ANALOG INPUTS

The following path is available using the keypad. For instructions on how to use the
keypad, please refer to Chapter 3 - Working with the Keypad.
PATH: SETPOINTS > RELAY SETUP > COMMUNICATIONS > DNP PROTOCOL > DNP GENERAL
To view the list of DNP Binary Inputs please refer to the Format Codes section - FC134B - of
this Guide.

4-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 4: DNP 3 DNP DEVICE PROFILE

DNP device profile

DNP 3.0 Device Profile

(Also see the IMPLEMENTATION TABLE in the following section)


Vendor Name: General Electric Multilin
Device Name: 850 Relay
Highest DNP Level Supported:
For Requests: Level 2
For Responses: Level 2
Device Function:
Master
Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):

Binary Inputs (Object 1)


Binary Input Changes (Object 2)

Binary Outputs (Object 10)


Control Relay Output Block (Object 12)

Binary Counters (Object 20)


Frozen Counters (Object 21)
Counter Change Event (Object 22)
Frozen Counter Event (Object 23)

Analog Inputs (Object 30)


Analog Input Changes (Object 32)
Analog Deadbands (Object 34)
Time and Date (Object 50)
Time Delay Fine (Object 52)

Class Data (Object 60)

Internal Indications (Object 80)


Maximum Data Link Frame Size (octets): Maximum Application Fragment Size (octets):
Transmitted: 292 Transmitted: configurable up to 2048
Received: 292 Received: 2048
Maximum Data Link Re-tries: Maximum Application Layer Re-tries:
None None
Fixed at 3 Configurable
Configurable
Requires Data Link Layer Confirmation:
Never
Always
Sometimes
Configurable
Requires Application Layer Confirmation:
Never
Always
When reporting Event Data
When sending multi-fragment responses
Sometimes
Configurable
Timeouts while waiting for:
Data Link Confirm: None Fixed Variable Configurable
Complete Appl. Fragment: None Fixed Variable Configurable
Application Confirm: None Fixed at 10 s Variable Configurable
Complete Appl. Response: None Fixed at ___ Variable Configurable

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-7


DNP DEVICE PROFILE CHAPTER 4: DNP 3

DNP 3.0 Device Profile


Others:
Transmission Delay: No intentional delay
Need Time Interval: Configurable (default = 24 hrs.)
Select/Operate Arm Timeout: 10 s
Binary input change scanning period: 8 times per power system cycle
Analog input change scanning period: 500 ms
Counter change scanning period: 500 ms
Frozen counter event scanning period: 500 ms
Sends/Executes Control Operations:
WRITE Binary Outputs Never Always Sometimes Configurable
SELECT/OPERATE Never Always Sometimes Configurable
DIRECT OPERATE Never Always Sometimes Configurable
DIRECT OPERATE NO ACK Never Always Sometimes Configurable
Count > 1 Never Always Sometimes Configurable
Pulse On Never Always Sometimes Configurable
Pulse Off Never Always Sometimes Configurable
Latch On Never Always Sometimes Configurable
Latch Off Never Always Sometimes Configurable
Queue Never Always Sometimes Configurable
Clear Queue Never Always Sometimes Configurable
Explanation of Sometimes: Object 12 points are mapped to Virtual Inputs and Commands (Force
Coils). Both Pulse On and Latch On operations perform the same function in the 850 ; that is, the
appropriate Virtual Input or Coil is put into the On state. The On/Off times and Count value are
ignored. Pulse Off and Latch Off operations put the appropriate Virtual Input or Coil into the Off
state. Trip and Close operations both put the appropriate Virtual Input or coil into the On state if
a paired mapping is set, otherwise Trip will put into Off and Close will put into On.
Reports Binary Input Change Events when no Reports time-tagged Binary Input Change
specific variation requested: Events when no specific variation requested:
Never
Never Binary Input Change With Time
Only time-tagged Binary Input Change With Relative Time
Only non-time-tagged Configurable (attach explanation)
Configurable
Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:
Never Never
Configurable When Device Restarts
Only certain objects When Status Flags Change
Sometimes No other options are permitted.
ENABLE/DISABLE unsolicited Function codes
supported
Explanation of Sometimes: It will be disabled
for RS-485 applications, since there is no collision
avoidance mechanism. For Ethernet
communication it will be available and it can be
disabled or enabled with the proper function
code.
Default Counter Object/Variation: Counters Roll Over at:
No Counters Reported No Counters Reported
Configurable (attach explanation) Configurable (attach explanation)
Default Object: 20 16 Bits
Default Variation: 1 32 Bits
Point-by-point list attached Other Value: _____
Point-by-point list attached
Sends Multi-Fragment Responses:
Yes
No

4-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 4: DNP 3 DNP IMPLEMENTATION

DNP implementation

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES (HEX) FUNCTION CODES QUALIFIER CODES
NO. NO. CODES (DEC) (DEC) (HEX)
1 0 Binary Input 1 (read) 00, 01 (start-stop) --- ---
(Variation 0 is used 22 (assign class) 06 (no range, or all)
to request default 07, 08 (limited quantity)
variation) 17, 28 (index)
1 Binary Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
2 Binary Input with 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Status 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
2 0 Binary Input Change 1 (read) 06 (no range, or all) --- ---
(Variation 0 is used 07, 08 (limited quantity)
to request default
variation)
1 Binary Input Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
without Time 07, 08 (limited quantity) 130 (unsol. resp.)
2 Binary Input Change 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
with Time 07, 08 (limited quantity) 130 (unsol. resp.)
3 Binary Input Change 1 (read) 06 (no range, or all) --- ---
with Relative Time 07, 08 (limited quantity)
10 0 Binary Output Status 1 (read) 00, 01(start-stop) --- ---
(Variation 0 is used 06 (no range, or all)
to request default 07, 08 (limited quantity)
variation) 17, 28 (index)
2 Binary Output Status 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
12 1 Control Relay Output 3 (select) 00, 01 (start-stop) 129 (response) echo of request
Block 4 (operate) 07, 08 (limited quantity)
5 (direct op) 17, 28 (index)
6 (dir. op, noack)
20 0 Binary Counter 1 (read) 00, 01 (start-stop) --- ---
(Variation 0 is used 7 (freeze) 06 (no range, or all)
to request default 8 (freeze noack) 07, 08 (limited quantity)
variation) 9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
1 32-Bit Binary 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter 7 (freeze) 06 (no range, or all) 17, 28 (index) (see
8 (freeze noack) 07, 08 (limited quantity) Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
2 16-Bit Binary 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter 7 (freeze) 06 (no range, or all) 17, 28 (index) (see
8 (freeze noack) 07, 08 (limited quantity) Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-9


DNP IMPLEMENTATION CHAPTER 4: DNP 3

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES (HEX) FUNCTION CODES QUALIFIER CODES
NO. NO. CODES (DEC) (DEC) (HEX)
5 32-Bit Binary 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter without Flag 7 (freeze) 06 (no range, or all) 17, 28 (index) (see
8 (freeze noack) 07, 08 (limited quantity) Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
6 16-Bit Binary 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter without Flag 7 (freeze) 06 (no range, or all) 17, 28 (index) (see
8 (freeze noack) 07, 08 (limited quantity) Note 2)
9 (freeze clear) 17, 28 (index)
10 (frz. cl. noack)
22 (assign class)
21 0 Frozen 1 (read) 00, 01 (start-stop) --- ---
Counter(Variation 0 22 (assign class) 06 (no range, or all)
is used to request 07, 08 (limited quantity)
defaultvariation) 17, 28 (index)
1 32-Bit Frozen 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
2 16-Bit Frozen 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
9 32-Bit Frozen 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter without Flag 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
10 16-Bit Frozen 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Counter without Flag 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
22 0 Counter Change 1 (read) 06 (no range, or all) --- ---
Event (Variation 0 is 07, 08 (limited quantity)
used to request
default variation)
1 32-Bit Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event 07, 08 (limited quantity) 130 (unsol. resp.)
2 16-Bit Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event 07, 08 (limited quantity) 130 (unsol. resp.)
5 32-Bit Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time
6 16-Bit Counter 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time
23 0 Frozen Counter 1 (read) 06 (no range, or all) --- ---
Event (Variation 0 is 07, 08 (limited quantity)
used to request
default variation)
1 32-Bit Frozen 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Counter Event 07, 08 (limited quantity) 130 (unsol. resp.)
2 16-Bit Frozen 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Counter Event 07, 08 (limited quantity) 130 (unsol. resp.)
5 32-Bit Frozen 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Counter Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time
6 16-Bit Frozen 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Counter Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time

4-10 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 4: DNP 3 DNP IMPLEMENTATION

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES (HEX) FUNCTION CODES QUALIFIER CODES
NO. NO. CODES (DEC) (DEC) (HEX)
30 0 Analog Input 1 (read) 00, 01 (start-stop) --- ---
(Variation 0 is used 22 (assign class) 06 (no range, or all)
to request default 07, 08 (limited quantity)
variation) 17, 28 (index)
1 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
2 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
3 32-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
4 16-Bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
without Flag 22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
5 short floating point 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
22 (assign class) 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)
32 0 Analog Change 1 (read) 06 (no range, or all) --- ---
Event (Variation 0 is 07, 08 (limited quantity)
used to request
default variation)
1 32-Bit Analog 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event 07, 08 (limited quantity) 130 (unsol. resp.)
without Time
2 16-Bit Analog 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event 07, 08 (limited quantity) 130 (unsol. resp.)
without Time
3 32-Bit Analog 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time
4 16-Bit Analog 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Change Event with 07, 08 (limited quantity) 130 (unsol. resp.)
Time
5 short floating point 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Analog Change 07, 08 (limited quantity) 130 (unsol. resp.)
Event without Time
7 short floating point 1 (read) 06 (no range, or all) 129 (response) 17, 28 (index)
Analog Change 07, 08 (limited quantity) 130 (unsol. resp.)
Event with Time
34 0 Analog Input 1 (read) 00, 01 (start-stop) --- ---
Reporting Deadband 06 (no range, or all)
(Variation 0 is used 07, 08 (limited quantity)
to request default 17, 28 (index)
variation)
1 16-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
(default - see Note 1) 07, 08 (limited quantity) Note 2)
17, 28 (index)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited quantity)
17, 28 (index)
2 32-bit Analog Input 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
Reporting Deadband 06 (no range, or all) 17, 28 (index) (see
07, 08 (limited quantity) Note 2)
17, 28 (index)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 4-11


DNP IMPLEMENTATION CHAPTER 4: DNP 3

OBJECT REQUEST RESPONSE


OBJECT VARIATION DESCRIPTION FUNCTION QUALIFIER CODES (HEX) FUNCTION CODES QUALIFIER CODES
NO. NO. CODES (DEC) (DEC) (HEX)
2 (write) 00, 01 (start-stop) --- ---
07, 08 (limited quantity)
17, 28 (index)
50 1 Time and Date 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(default - see Note 1) 2 (write) 06 (no range, or all) 17, 28 (index) (see
07 (limited qty=1) Note 2)
08 (limited quantity)
17, 28 (index)
52 2 Time Delay Fine 129 (response) 07 (limited quantity) --- ---
(quantity = 1)
60 0 Class 0, 1, 2, and 3 1 (read) 06 (no range, or all) --- ---
Data 20 (enable unsol)
21 (disable unsol)
22 (assign class)
1 Class 0 Data 1 (read) 06 (no range, or all) --- ---
22 (assign class)
2 Class 1 Data 1 (read) 06 (no range, or all) --- ---
20 (enable unsol) 07, 08 (limited quantity)
3 Class 2 Data 21 (disable unsol) --- ---
4 Class 3 Data 22 (assign class) --- ---
80 1 Internal Indications 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop)
(index =7)
2 (write) 00 (start-stop) --- ---
(see Note 3) (index =7)
No Object (function 13 (cold restart) --- --- ---
code only) see Note
3
No Object (function 14 (warm restart) --- --- ---
code only)
No Object (function 23 (delay meas.) --- --- ---
code only)

1. A default variation refers to the variation response when variation 0 is requested and/
FASTPATH:

or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23,
30, and 32 are selected via relay settings. This optimizes the class 0 poll data size.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, will be responded with qualifiers 00 or 01 (for
changeevent objects, qualifiers 17 or 28 are always responded.)
Cold restarts are implemented the same as warm restarts the 850 is not restarted, but
the DNP process is restarted.

4-12 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 5: DNP / IEC104 Point Lists

DNP / IEC104 Point Lists

The menu for the DNP/IEC104 point lists is shown below.


Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists

n DNP / IEC104 n BINARY INPUT / MSP Range: see sub-menu below

n POINT LISTS n POINTS

Message
n ANALOG INPUT / MME Range: see sub-menu below

n POINTS

Message
n BINARY OUTPUT / Range: see sub-menu below

n CSC/CDS POINTS

The binary inputs points for the DNP protocol, or the MSP points for IEC 60870-5-104
protocol, can configured to a maximum of 96 points. The value for each point is user-
programmable and can be configured by assigning FlexLogic operands.
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown
below.
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists > Binary Input/MSP
Points

BINARY INPUT / MSP Point: 0 Range: FlexLogic operand


Default: Off
POINTS Off

Message
Point: 1 Range: FlexLogic operand
Default: Off
Off

Message
Point: 95 Range: FlexLogic operand
Default: Off
Off

Up to 32 analog input points can be configured for the DNP or IEC 60870-5-104 protocols.
The menu for the analog input point (DNP) or MME points (IEC 60870-5-104) is shown
below.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 5-1


CHAPTER 5: DNP / IEC104 POINT LISTS

DNP ANALOG 0 SCALE FACTOR


Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000
Default: 1
The setting specifies a time delay for the detection of dead network TCP connections. If
there is no data traffic on a DNP TCP connection for greater than the time specified by
the setting, the connection is aborted by the 850. This frees up the connection to be re-
used by a client.
DNP ANALOG 0(31) DEFAULT DEADBAND
Range: 1 to 100000000 in steps of 1
Default: 30000
The settings determine when to trigger unsolicited responses containing analog input
data. Each setting represents the default deadband value for the associate analog
input.For example, to trigger unsolicited responses from the 850 when phase A current
changes by 15 A, the DNP CURRENT DEFAULT DEADBAND for Phase A current should be
set to 15. Note that these settings are the deadband default values. DNP object 34
points can be used to change deadband values from the default for each individual
DNPanalog input point. Whenever power is removed and re-applied to the 850 the
default deadbands are in effect.
DNP ANALOG 0(31) SCALE FACTOR
Range: 0.001, 0.01. 0.1, 1, 10, 100, 1000, 10000, 100000
Default: 1
These are numbers used to scale analog input point values. Each setting represents the
scale factor for the analog input point. For example, if the DNP PHASE A VOLTAGE SCALE
FACTOR setting is set to 1000, Phase A voltage is returned with values 1000 times
smaller (for example, a value of 72000 V on the 850 is returned as 72). The settings are
useful when analog input values must be adjusted to fit within certain ranges in DNP
masters.
Note that a scale factor of 0.1 is equivalent to a multiplier of 10 (that is, the value is 10
FASTPATH:

times larger), and that the first 16 analog points are 16 bit integer format and the second
16 analog points are in IEEE 32bit floating point notation

The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown
below.
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists > Analog Input / MME
Points

ANALOG INPUT/MME Point: 0 Range: any FlexAnalog parameter


Default: Off
POINTS Off

Message
Point: 1 Range: any FlexAnalog parameter
Default: Off
Off

Message
Point: 31 Range: any FlexAnalog parameter
Default: Off
Off
The binary outputs points for the DNP protocol, or the CSC/CDC points for IEC 60870-5-104
protocol, can configured to a maximum of 16 points. The value for each point is user-
programmable and can be configured by assigning FlexLogic operands.

5-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 5: DNP / IEC104 POINT LISTS

The menu for the binary output points (DNP) or CSC/CDC points (IEC 60870-5-104) is shown
below.
Path: Setpoints > Device > Communications > DNP/IEC104 Point Lists > Binary Output /
CSC/CDC Points

BINARY OUTPUT / Point: 0 ON Range: FlexLogic operand


Default: Off
CSC / CDC POINTS Off

Message
Point: 0 OFF Range: FlexLogic operand
Default: Off
Off

Message
Point: 15 ON Range: FlexLogic operand
Default: Off
Off

Message
Point: 15 OFF Range: FlexLogic operand
Default: Off
Off

The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first Off
FASTPATH:

value. Since DNP / IEC 60870-5-104 point lists must be in one continuous block, any points
assigned after the first Off point are ignored.

BINARY INPUT POINTS


The DNP binary input data points are configured through the DNP / IEC104 POINT LISTS
BINARY INPUT / MSP POINTS menu. When a freeze function is performed on a binary
counter point, the frozen value is available in the corresponding frozen counter point.
BINARY INPUT POINTS
Static (Steady-State) Object Number: 1
Change Event Object Number: 2
Request Function Codes supported: 1 (read), 22 (assign class)
Static Variation reported when variation 0 requested: 2 (Binary Input with status),
Configurable
Change Event Variation reported when variation 0 requested: 2 (Binary Input Change
with Time), Configurable
Change Event Scan Rate: 8 times per power system cycle
Change Event Buffer Size: 1024
Default Class for All Points: 1
POINT NAME/DESCRIPTION COUNTERS
The following table lists both Binary Counters (Object 20) and Frozen Counters (Object 21).
When a freeze function is performed on a Binary Counter point, the frozen value is
available in the corresponding Frozen Counter point. 850 Digital Counter values are
represented as 16 or 32-bit integers. The DNP 3.0 protocol defines counters to be unsigned
integers. Care should be taken when interpreting negative counter values.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 5-3


CHAPTER 5: DNP / IEC104 POINT LISTS

BINARY COUNTERS
Static (Steady-State) Object Number: 20
Change Event Object Number: 22
Request Function Codes supported: 1 (read), 7 (freeze), 8 (freeze noack), 9 (freeze and
clear), 10 (freeze and clear, noack), 22 (assign class)
Static Variation reported when variation 0 requested: 1 (32-Bit Binary Counter with
Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter
Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3

FROZEN COUNTERS
Static (Steady-State) Object Number: 21
Change Event Object Number: 23
Request Function Codes supported: 1 (read)
Static Variation reported when variation 0 requested: 1 (32-Bit Frozen Counter with
Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter
Change Event without time)
Change Event Buffer Size: 10
Default Class for all points: 3

BINARY AND FROZEN COUNTERS POINT INDEX NAME/DESCRIPTION


0 Digital Counter 1
1 Digital Counter 2
2 Digital Counter 3
3 Digital Counter 4
4 Digital Counter 5
5 Digital Counter 6
6 Digital Counter 7
7 Digital Counter 8
8 Digital Counter 9
9 Digital Counter 10
10 Digital Counter 11
11 Digital Counter 12
12 Digital Counter 13
13 Digital Counter 14
14 Digital Counter 15
15 Digital Counter 16

5-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 5: DNP / IEC104 POINT LISTS

ANALOG INPUTS
The DNP analog input data points are configured through the PRODUCT SETUP/
COMMUNICATIONS/ DNP / IEC104 POINT LISTS / ANALOG INPUT / MME POINTS menu. It
is important to note that 16-bit and 32-bit variations of analog inputs are transmitted
through DNP as signed numbers. Even for analog input points that are not valid as
negative values, the maximum positive representation is 32767 for 16-bit values and
2147483647 for 32-bit values. This is a DNP requirement. The deadbands for all Analog
Input points are in the same units as the Analog Input quantity. For example, an Analog
Input quantity measured in volts has a corresponding deadband in units of volts. Relay
settings are available to set default deadband values according to data type. Deadbands
for individual Analog Input Points can be set using DNP Object 34.
1. A default variation refers to the variation response when variation 0 is requested and/
FASTPATH:

or in class 0, 1, 2, or 3 scans. The default variations for object types 1, 2, 20, 21, 22, 23,
30, and 32 are selected via relay settings. This optimizes the class 0 poll data size.
2. For static (non-change-event) objects, qualifiers 17 or 28 are only responded when a
request is sent with qualifiers 17 or 28, respectively. Otherwise, static object requests
sent with qualifiers 00, 01, 06, 07, or 08, are responded with qualifiers 00 or 01 (for
change event objects, qualifiers 17 or 28 are always responded.
Cold restarts are implemented the same as warm restarts the 850 is not restarted, but
the DNP process is restarted.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 5-5


CHAPTER 5: DNP / IEC104 POINT LISTS

5-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 6: IEC 60870-5-104

IEC 60870-5-104

The IEC 60870-5-104 communications protocol is supported on Ethernet ports 4 and 5


only. Setting changes become active after rebooting.
In 850 both DNP and IEC104 protocol can work at the same time, but the user has to
FASTPATH:

consider that there is only one point map. So, both protocols use the same configured
points

The 850 supports two IEC104 client connections simultaneously.


FASTPATH:

Path: Setpoints > Device > Communications > IEC 60870-5-104

IEC 60870-5-104 IEC104 Range: see sub-menu below

CHANNELS

Message
IEC104 COMMON Range: 0 to 65535 in steps of 1

ADDRESS OF ASDU:0

Message
IEC104 NETWORK Range: see sub-menu below

CLIENT ADDRESSES

Message
IEC104 TCP Range: see sub-menu below

PORTS

Message
IEC104 CYCLIC DATA Range: 0 to 65535 in steps of 1

PERIOD: 60 s

Message IEC104 Obj Info Range: 0 to 16777215 in steps of 1

Addr Binary: 1000

Message
IEC104 Obj Info Range: 0 to 16777215 in steps of 1

Addr Analog: 2000


IEC104 Obj Info Range: 0 to 16777215 in steps of 1
Message
Addr Counter: 3000

Message IEC104 Obj Info Range: 0 to 16777215 in steps of 1

Addr Command: 4000

Message
IEC104 Obj Info Range: 0 to 16777215 in steps of 1

Analog Param: 5000

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 6-1


CHAPTER 6: IEC 60870-5-104

By default the Object Information Address for the different data is as follows:
M_SP (Single Points) = 1000
M_ME (Measured value) = 2000
M_IT (Integrated Totals) = 3000
C_SC or C_DC (Single or Double Command) = 4000
P_ME_NB (Parameter of measured value) = 5000
Each Measured value has a Parameter of measured value (P_ME_NB) associated to its
threshold.
The IEC 60870-5-104 Deadbands settings are used to determine when to trigger
spontaneous responses containing M_ME_NB_1 analog data. Each setting represents the
threshold value for each M_ME_NB_1 analog point.
For example, to trigger spontaneous responses from the 850 when a current value
changes by 15 A, the Analog Point xx Deadband setting should be set to 15. Note that
these settings are the default values of the deadbands. P_ME_NB_1 (parameter of
measured value, scaled value) points can be used to change threshold values, from the
default, for each individual M_ME_NB_1 analog point.There are three ways to send the
measurands to the Master station. The measurands are part of the General Group and
Group 2, so when a general interrogation or group 2 interrogation takes place all the
measurands are included in the response. Also, there is a cyclic data period setting where it
is configured in the scan period to send the measurands to the Master. And the last way, is
by sending spontaneously when a deadband overflow takes place.The IEC104 Channels
sub-menu is shown below.
Commands are executed over the Binary Outputs. The first 8 Binary Outputs are
configured to receive Select/Operate Commands and the next 8 Binary Outputs are
configured to receive Direct Execute Commands.
Path: Setpoints > Device > Communications > IEC 60870-5-104

IEC104 60870-5-104 CHANNEL 1 Range: None, Network-TCP

PORT: NETWORK-TCP

Message
CHANNEL 2 Range: None, Network-TCP

PORT: NETWORK-TCP
The IEC104 CHANNEL 1 PORT and IEC104 CHANNEL 2 PORT settings select the
communications port assigned to the IEC104 protocol for each channel. When this setting
is set to Network - TCP, the IEC104 protocol can be used over TCP/IP on channels 1 or 2.
The IEC104 NETWORK CLIENT ADDRESS settings can force the 850 to respond to a
maximum of two specific IEC104 masters. The settings in this sub-menu are shown below.
Path: Setpoints > Device > Communications > IEC 60870-5-104
IEC104 60870-5-104 CLIENT ADDRESS 1: Range: standard IP address

0.0.0.0

Message
CLIENT ADDRESS 2: Range: standard IP address

0.0.0.0

Path: Setpoints > Device > Communications > IEC 60870-5-104


IEC104 60870-5-104 TCP PORT NUMBER 1: Range: 1 to 65535 in steps of 1

2404

Message TCP PORT NUMBER 2: Range: 1 to 65535 in steps of 1

2404

IEC104 Channel 1 Port takes the Port Number 1 and Client Address 1 to allow or reject
FASTPATH:

connections. The same method is used by channel 2.

6-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY

GROUPS OF DATA
The data is organized into groups in order to provide values when the controlling station
requests them by a general or group interrogation.
Group 1 is set by the 96 Single Points (M_SP).
Group 2 is set by the 32 Measured values (M_ME).
Group 3 is set by the 32 Measured threshold (P_ME).
These 96 Single Points and 32 Measured Values are also sent as a response to a General
Interrogation.
The Integrated Totals (M_IT) has its own Counter Group 1, and it is sent as a response to a
General Request Counter.

Interoperability
This document is adapted from the IEC 60870-5-104 standard. For this section the boxes
indicate the following: used in the standard direction; not used.
IEC 60870-5-104 Interoperability Document
System or device:
System definition.
Controlling station definition (master).
Controlled station definition (slave).
Application layer:Transmission mode for application data:Mode 1 (least significant octet
first), as defined in Clause 4.10 of IEC 60870-5-4, is used exclusively in this companion
standard.Common address of ASDU:
Two octets.Information object address:
Three octets.
Structured
Unstructured
Cause of transmission:
Two octets (with originator address). Originator address is set to zero if not
used.Maximum length of APDU.253 in both directions (the maximum length is a fixed
system parameter).Selection of standard ASDUs.For the following lists, the boxes indicate
the following: used in standard direction;
not used.Process information in monitor direction:
Table 6-1: Process information in monitor direction
Number / description Mnemonic
<1> := Single-point information M_SP_NA_1
<3> := Double-point information M_DP_NA_1
<5> := Step position information M_ST_NA_1
<7> := Bitstring of 32 bits M_BO_NA_1
<9> := Measured value, normalized value M_ME_NA_1
<11> := Measured value, scaled value M_ME_NB_1
<13> := Measured value, short floating point value M_ME_NC_1
<15> := Integrated totals M_IT_NA_1
<20> := Packed single-point information with status change detection M_SP_NA_1
<21> := Measured value, normalized value without quantity descriptor M_ME_ND_1
<30> := Single-point information with time tag CP56Time2a M_SP_TB_1
<31> := Double-point information with time tag CP56Time2a M_DP_TB_1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 6-3


INTEROPERABILITY CHAPTER 6: IEC 60870-5-104

Number / description Mnemonic


<32> := Step position information with time tag CP56Time2a M_ST_TB_1
<33> := Bitstring of 32 bits with time tag CP56Time2a M_BO_TB_1
<34> := Measured value, normalized value with time tag CP56Time2a M_ME_TD_1
<35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
<36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
<37> := Integrated totals with time tag CP56Time2a M_IT_TB_1
<38> := Event of protection equipment with time tag CP56Time2a M_EP_TD_1
<39> := Packed start events of protection equipment with time tag M_EP_TE_1
CP56Time2a
<40> := Packed output circuit information of protection equipment with time M_EP_TF_1
tag CP56Time2a

Table 6-2: Process information in control direction


Number / description Mnemonic
<45> := Single command C_SC_NA_1
<46> := Double command C_DC_NA_1
<47> := Regulating step command C_RC_NA_1
<48> := Set point command, normalized value C_SE_NA_1
<49> := Set point command, scaled value C_SE_NB_1
<50> := Set point command, short floating point value C_SE_NC_1
<51> := Bitstring of 32 bits C_BO_NA_1
<58> := Single command with time tag CP56Time2a C_SC_TA_1
<59> := Double command with time tag CP56Time2a C_DC_TA_1
<60> := Regulating step command with time tag CP56Time2a C_RC_TA_1
<61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1
<62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
<63> := Set point command, short floating point value with time tag C_SE_TC_1
CP56Time2a
<64> := Bitstring of 32 bits with time tag CP56Time2a C_BO_TA_1

Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
Table 6-3: System information in monitor direction
Number / description Mnemonic
<70> := End of initialization M_EI_NA_1

Table 6-4: System information in control direction


Number / description Mnemonic
<100> := Interrogation command C_IC_NA_1
<101> := Counter interrogation command C_CI_NA_1
<102> := Read command C_RD_NA_1
<103> := Clock synchronization command (see Clause 7.6 in standard) C_CS_NA_1
<105> := Reset process command C_RP_NA_1
<107> := Test command with time tag CP56Time2a C_TS_TA_1

Table 6-5: Parameter in control direction


Number / description Mnemonic
<110> := Parameter of measured value, normalized value PE_ME_NA_1

6-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY

Number / description Mnemonic


<111> := Parameter of measured value, scaled value PE_ME_NB_1
<112> := Parameter of measured value, short floating point value PE_ME_NC_1
<113> := Parameter activation PE_AC_NA_1

Table 6-6: File transfer


Number / description Mnemonic
<120> := File ready F_FR_NA_1
<121> := Section ready F_SR_NA_1
<122> := Call directory, select file, call file, call section F_SC_NA_1
<123> := Last section, last segment F_LS_NA_1
<124> := Ack file, ack section F_AF_NA_1
<125> := Segment F_SG_NA_1
<126> := Directory (blank or X, available only in monitor [standard] direction) F_DR_TA_1
<127> := Query log - Request archive file F_SC_NB_1

Type identifier and cause of transmission assignments (station-specific parameters) are


shown in the following tables. In these tables, shaded boxes () are not required, black
boxes () are not permitted in the companion standard, empty cells indicate the functions
or ASDU are not used, and a cross () indicates availability only in the standard direction.
Table 6-7: Cause of transmission numbers
Number Cause of transmission
1 Periodic, cyclic
2 Background scan
3 Spontaneous
4 Initialized
5 Request or requested
6 Activation
7 Activation confirmation
8 Deactivation
9 Deactivation confirmation
10 Activation termination
11 Return information caused by a remote command
12 Return information caused by a local command
13 File transfer
20 20 Interrogated by station interrogation
21 to 36 Interrogated by group <number> interrogation
37 37 Requested by general counter request
38 to 41 Requested by group <number> counter request
44 Unknown type of identification
45 Unknown cause of transmission
46 Unknown command address of ADSU
47 Unknown information object address

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 6-5


INTEROPERABILITY CHAPTER 6: IEC 60870-5-104

Table 6-8: Cause of transmission assignments


Type identification Cause of transmission
No. Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<1> M_SP_NA_1
<2> M_SP_TA_1
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1
<10> M_ME_TA_1
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1
<31> M_DP_TB_1
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1
<59> C_DC_TA_1
<60> C_RC_TA_1
<61> C_SE_TA_1

6-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY

Type identification Cause of transmission


No. Mnemonic 1 2 3 4 5 6 7 8 9 10 11 12 13 20 37 44 45 46 47
to to
36 41
<62> C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
<70> M_EI_NA_1*)
<100> C_IC_NA_1
<101> C_CI_NA_1
<102> C_RD_NA_1
<103> C_CS_NA_1
<104> C_TS_NA_1
<105> C_RP_NA_1
<106> C_CD_NA_1
<107> C_TS_TA_1
<110> P_ME_NA_1
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*)
<127> F_SC_NB_1*)

* blank or X only
FASTPATH:

Basic application functions:


Station initialization:
Remote initialization.
Cyclic data transmission:
Cyclic data transmission.
Read procedure:
Read procedure.
Spontaneous transmission:
Spontaneous transmission.
Double transmission of information objects with cause of transmission spontaneous:
The following type identifications may be transmitted in succession caused by a single
status change of an information object. The particular information object addresses for
which double transmission is enabled are defined in a project-specific list.
Single point information: M_SP_NA_1, M_SP_TA_1, M_SP_TB_1, and M_PS_NA_1.
Double point information: M_DP_NA_1, M_DP_TA_1, and M_DP_TB_1.
Step position information: M_ST_NA_1, M_ST_TA_1, and M_ST_TB_1.
Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific
project).

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 6-7


INTEROPERABILITY CHAPTER 6: IEC 60870-5-104

Measured value, normalized value: M_ME_NA_1, M_ME_TA_1, M_ME_ND_1, and


M_ME_TD_1.
Measured value, scaled value: M_ME_NB_1, M_ME_TB_1, and M_ME_TE_1.
Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and
M_ME_TF_1.
Station interrogation:
Group 1.
Group 2.
Group 3.
Group 4.
Group 5.
Group 6.
Group 7.
Group 8.
Group 9.
Group 10.
Group 11.
Group 12.
Group 13.
Group 14.
Group 15.
Group 16.
Global.
Clock synchronization:
Clock synchronization (optional, see Clause 7.6).
Day of week used.
RESI, GEN (time tag substituted/not substituted)
SU-bit (summertime) used.
Command transmission:
Direct command transmission.
Direct setpoint command transmission.
Select and execute command.
Select and execute setpoint command.
C_SE ACTTERM used.
No additional definition.
Short pulse duration (duration determined by a system parameter in the outstation).
Long pulse duration (duration determined by a system parameter in the outstation).
Persistent output.
Supervision of maximum delay in command direction of commands and setpoint
commands.
Maximum allowable delay of commands and setpoint commands: 5 s.
Transmission of integrated totals:
Mode A: Local freeze with spontaneous transmission.
Mode B: Local freeze with counter interrogation.
Mode C: Freeze and transmit by counter-interrogation commands.
Mode D: Freeze by counter-interrogation command, frozen values reported
simultaneously.
Counter read.

6-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 6: IEC 60870-5-104 INTEROPERABILITY

Counter freeze without reset.


Counter freeze with reset.
Counter reset.
General request counter.
Request counter group 1.
Request counter group 2.
Request counter group 3.
Request counter group 4.
Parameter loading:
Threshold value.
Smoothing factor.
Low limit for transmission of measured values.
High limit for transmission of measured values.
Parameter activation:
Activation/deactivation of persistent cyclic or periodic transmission of the addressed
object.
Test procedure:
Test procedure.
File transfer in monitor direction:
Transparent file.
Transmission of disturbance data of protection equipment.
Transmission of sequences of events.
Transmission of sequences of recorded analog values.
File transfer in control direction:
Transparent file.
Background scan:
Background scan.
Definition of timeouts:

Parameter Default value Remarks Selected value


t0 Timeout of connection establishment N/A
t1 15 s Timeout of send or test APDUs 15 s
t2 10 s Timeout for acknowledgements in case of no 10 s
data messages t2 < t1
t3 20 s Timeout for sending test frames in case of a 20 s
long idle state

Maximum range of values for all time outs: 1 to 255 s, accuracy 1 s.


Maximum number of outstanding I-format APDUs (k) and latest acknowledge APDUs (w):

Parameter Default value Remarks Selected value


k 12 APDUs Maximum difference receive sequence number 12 APDUs
to send state variable
w 8 APDUs Latest acknowledge after receiving w I-format 8 APDUs
APDUs

Maximum range of values k: 1 to 32767 (215 1) APDUs, accuracy 1 APDU.


Maximum range of values w: 1 to 32767 APDUs, accuracy 1 APDU.
Recommendation: w should not exceed two-thirds of k.
Port number:

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 6-9


INTEROPERABILITY CHAPTER 6: IEC 60870-5-104

Parameter Value Remarks


Port number 2404 In all cases

RFC 2200 suite:


RFC 2200 is an official Internet Standard which describes the state of standardization of
protocols used in the Internet as determined by the Internet Architecture Board (IAB). It
offers a broad spectrum of actual standards used in the Internet. The suitable selection of
documents from RFC 2200 defined in this standard for given projects has to be chosen by
the user of this standard.
Ethernet 802.3.
Serial X.21 interface.
Other selection(s) from RFC 2200 (list below if selected).

6-10 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 7: IEC 60870-5-103

IEC 60870-5-103

The point map for the 103 is different from the one shared by the IEC104 and DNP
protocols. IEC 60870-5-103 serial communications protocol is supported on the rear RS485
ports only and is implemented as per the 850.
The DNP, 103 and Modbus can not be enabled simultaneously on the RS485 serial port.
DNP can be enabled on Ethernet and 103 on serial RS485.
Path: Setpoints > Device > Communications > IEC60870-5-103
To view the list of binary inputs, see the 850 Flexlogic Operands table in the Setpoints/
FlexLogic section of the 850 instruction manual.
The user must pay attention when configuring the function type and information number
FASTPATH:

of the different points, because they must be unique. There is no mechanism in the
EnerVista 8 Series Setup or the front panel HMI to detect this situation.

The IEC 60870-5-103 point lists always begin with point 0 and end at the first Off value.
FASTPATH:

Since IEC 60870-5-103 point lists must be in one continuous block, any points assigned
after the first Off point are ignored.

Cause of Transmission
The cause of transmission is an unsigned integer which takes one of the values specified in
the following tables.
Table 7-1: Cause of Transmission in the Monitor Direction
Value Description
<1> Spontaneous
<2> Cyclic
<3> Reset frame count bit (FCB)
<4> Reset communications unit (CU)
<5> Start/Restart
<6> Power on
<8> Time synchronization
<9> General interrogation

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-1


CAUSE OF TRANSMISSION CHAPTER 7: IEC 60870-5-103

Value Description
<10> Termination of general interrogation
<20> Positive ack of command
<21> Nack of command

Table 7-2: Cause of Transmission in the Control Direction


Value Description
<8> Time synchronization
<9> Initiation of general interrogation
<20> General command

IEC 60870-5-103 COMMUNICATIONS MENUS


PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC 60870-5-103 PROTOCOL
IEC 60870-5-103 IEC103 COMMON Range: 0 to 254 in steps of 1

PROTOCOL ADDRESS OF ASDU: 0

Message
IEC103 Sync Timeout: Range: 0 to 1440 min in steps of 1

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS

IEC103 BINARY INPUTS Range: see sub-menu below

POINT LISTS

Message
MEASURANDS Range: see sub-menu below

Message
COMMANDS Range: see sub-menu below

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > BINARY INPUTS

BINAR INPUTS Point 0 Func Type: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 0 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 0: TM
Range: FlexLogic operand
Default: Off
off

Message Point 95 Func Type: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 95 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 95: TM


Range: FlexLogic operand
Default: Off
off

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > MEASURANDS

MEASURANDS FIRST ASDU


SECOND ASDU
THIRD ASDU
FOURTH ASDU

7-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 7: IEC 60870-5-103 CAUSE OF TRANSMISSION

There are four measurand ASDUs with the following sub-menu.


PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > MEASURANDS >
FIRST ASDU

FIRST ASDU First ASDU Range: 3, 9


Default: 3
Indent Type: 0

Message First ASDU Range: 0 to 255 in steps of 1


Default: 0
Func Type: 0

Message
First ASDU Range: 0 to 255 in steps of 1
Default: 0
Info Num: 0

Message First ASDU Range: 0 to 1000 s in steps of 1


Default: 0
Scan Timeout: 0 s

Message First Analog Entry: Range: FlexLogicTM operand


Default: Off
Off

Message First Analog Factor: Range:


Range:0.000
Default:
to 65.535
0 to 255 in steps
in steps of 1 of 0.001
Default:00
0

Message First Analog Factor:


Offset: Range:
Range: -32768
Default:
toin
0 to 255 +32767 in steps
steps of 1 of 1
Default: 00
0

Message Ninth Analog Entry: TM


Range: FlexLogic operand
Default: Off
Off

Message First Analog


Ninth AnalogFactor:
Factor: Range: 0.000
Range: 0 to 255
to 65.535
in steps
in steps
of 1 of 0.001
Default:00
Default:
0

Message NinthAnalog
First AnalogFactor:
Offset: Range: -32768
Range: 0 to 255
toin
+32767
steps of
in steps
1 of 1
Default: 00
Default:
0

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-3


COMMUNICATIONS MENUS CHAPTER 7: IEC 60870-5-103

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > COMMANDS
COMMANDS Command 0 Func Type: Range: 0 to 255 in steps of 1
Default: 0
0

Message Command 0 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message
Command 0 ON: TM
Range: FlexLogic operand
Default: Off
off

Message Command 0 OFF: TM


Range: FlexLogic operand
Default: Off
off

Message
Command 31 Func Type: Range: 0 to 255 in steps of 1
Default: 0
0

Message First Analog31


Command Factor:
Info Num: Range: 0 to 255 in steps of 1
Default: 0
0

Message
Command
First Analog31 ON:
Factor: TM
0 to 255 in
Range: FlexLogic steps of 1
operand
0
Default: Off
off
0

Message Command 31 OFF: Range: FlexLogicTM operand


Default: Off
off

Communications Menus
The following show the menus and sub-menus for the 103 protocols.
PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC 60870-5-103 PROTOCOL
IEC 60870-5-103 IEC103 COMMON Range: 0 to 254 in steps of 1

PROTOCOL ADDRESS OF ASDU: 0

Message
IEC103 Sync Timeout: Range: 0 to 1440 min in steps of 1

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS

IEC103 BINARY INPUTS Range: see sub-menu below

POINT LISTS

Message
MEASURANDS Range: see sub-menu below

Message
COMMANDS Range: see sub-menu below

7-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 7: IEC 60870-5-103 COMMUNICATIONS MENUS

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > BINARY INPUTS

BINAR INPUTS Point 0 Func Type: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 0 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 0: Range: FlexLogicTM operand


Default: Off
off

Message Point 95 Func Type: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 95 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message Point 95: TM


Range: FlexLogic operand
Default: Off
off

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > MEASURANDS

MEASURANDS FIRST ASDU


SECOND ASDU
THIRD ASDU
FOURTH ASDU

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-5


COMMUNICATIONS MENUS CHAPTER 7: IEC 60870-5-103

There are four measurand ASDUs with the following sub-menu.


PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > MEASURANDS >
FIRST ASDU

FIRST ASDU First ASDU Range: 3, 9


Default: 3
Indent Type: 0

Message First ASDU Range: 0 to 255 in steps of 1


Default: 0
Func Type: 0

Message
First ASDU Range: 0 to 255 in steps of 1
Default: 0
Info Num: 0

Message First ASDU Range: 0 to 1000 s in steps of 1


Default: 0
Scan Timeout: 0 s

Message First Analog Entry: Range: FlexLogicTM operand


Default: Off
Off

Message First Analog Factor: Range:


Range:0.000
Default:
to 65.535
0 to 255 in steps
in steps of 1 of 0.001
Default:00
0

Message First Analog Factor:


Offset: Range:
Range: -32768
Default:
toin
0 to 255 +32767 in steps
steps of 1 of 1
Default: 00
0

Message Ninth Analog Entry: TM


Range: FlexLogic operand
Default: Off
Off

Message First Analog


Ninth AnalogFactor:
Factor: Range: 0.000
Range: 0 to 255
to 65.535
in steps
in steps
of 1 of 0.001
Default:00
Default:
0

Message NinthAnalog
First AnalogFactor:
Offset: Range: -32768
Range: 0 to 255
toin
+32767
steps of
in steps
1 of 1
Default: 00
Default:
0

7-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 7: IEC 60870-5-103 INTEROPERABILITY

PATH: SETPOINTS > DEVICE > COMMUNICATIONS > IEC103 POINT LISTS > COMMANDS
COMMANDS Command 0 Func Type: Range: 0 to 255 in steps of 1
Default: 0
0

Message Command 0 Info Num: Range: 0 to 255 in steps of 1


Default: 0
0

Message
Command 0 ON: TM
Range: FlexLogic operand
Default: Off
off

Message Command 0 OFF: TM


Range: FlexLogic operand
Default: Off
off

Message
Command 31 Func Type: Range: 0 to 255 in steps of 1
Default: 0
0

Message First Analog31


Command Factor:
Info Num: Range: 0 to 255 in steps of 1
Default: 0
0

Message
Command
First Analog31 ON:
Factor: TM
0 to 255 in
Range: FlexLogic steps of 1
operand
0
Default: Off
off
0

Message Command 31 OFF: Range: FlexLogicTM operand


Default: Off
off

Interoperability
Physical layer

Electrical interface
EIA RS-485
32 Number of loads for one protection equipment

Optical interface
Glass fibre
Plastic fibre
F-SMA type connector
BFOC/2,5 type connector

Transmission speed
9600 bits/s
19200 bits/s

Link layer
There are no choices for the Link Layer.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-7


INTEROPERABILITY CHAPTER 7: IEC 60870-5-103

Application layer

Transmission mode Mode 1 (least significant octet first), is used exclusively in this companion standard.
for application data

Common address of
ASDU One COMMON ADDRESS OF ASDU (identical with station address)
More than one COMMON ADDRESS OF ASDU

Selection of standard Table 7-3: System functions in monitor direction


information numbers INF Semantics
in monitor direction <0> End of general interrogation
<0> Time synchronization
<2> Reset FCB
<3> Reset CU
<4> Start/restart
<5> Power on

Table 7-4: Status indications in monitor direction


INF Semantics 850 Identifier 850 Data Text
<16> Auto-recloser active
<17> Teleprotection active
<18> Protection active
<19> LED reset
<20> Monitor direction blocked
<21> Test mode
<22> Local parameter setting
<23> Characteristic 1
<24> Characteristic 2
<25> Characteristic 3
<26> Characteristic 4
<27> Auxiliary input 1
<28> Auxiliary input 2
<29> Auxiliary input 3
<30> Auxiliary input 4

Table 7-5: Supervision indications in monitor direction


INF Semantics 850 Identifier 850 Data Text
<32> Measurand supervision I
<33> Measurand supervision V
<35> Phase sequence supervision
<36> Trip circuit supervision
<37> I>> back-up operation
<38> VT fuse failure
<39> Teleprotection disturbed
<46> Group warning
<47> Group alarm

7-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 7: IEC 60870-5-103 INTEROPERABILITY

Table 7-6: Earth fault indications in monitor direction


INF Semantics 850 Identifier 850 Data Text
INF Semantics 850 Identifier 850 Data Text
<48> Earth fault L1
<49> Earth fault L2
<50> Earth fault L3
<51> Earth fault forward, i.e. line
<52> Earth fault reverse, i.e. busbar

Table 7-7: Fault indications in monitor direction


INF Semantics 850 Identifier 850 Data Text
INF Semantics 850 Identifier 850 Data Text
<64> Start / pick-up L1
<65> Start / pick-up L2
<66> Start / pick-up L3
<67> Start / pick-up N
<68> General trip
<69> Trip L1
<70> Trip L2
<71> Trip L3
<72> Trip I>> (back-up operation)
<73> Fault location X in ohms
<74> Fault forward / line
<75> Fault reverse / busbar
<76> Teleprotection signal transmitted
<77> Teleprotection signal received
<78> Zone 1
<79> Zone 2
<80> Zone 3
<81> Zone 4
<82> Zone 5
<83> Zone 6
<84> General start / pick-up
<85> Breaker failure
<86> Trip measuring system L1
<87> Trip measuring system L2
<88> Trip measuring system L3
<89> Trip measuring system E
<90> Trip I>
<91> Trip I>>
<92> Trip IN>
<93> Trip IN>>

Table 7-8: Auto-reclosure indications in monitor direction


INF Semantics 850 Identifier 850 Data Text
<128> CB on by AR
<129> CB on by long-time AR
<130> AR blocked

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-9


INTEROPERABILITY CHAPTER 7: IEC 60870-5-103

Table 7-9: Measurands in monitor direction


INF Semantics 850 Identifier 850 Data Text
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
<147> Measurands In, Ven
<148> Measurands IL123, VL123, P, Q, f

Table 7-10: Generic functions in monitor direction


INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> End of general interrogation of generic data
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry aborted

Selection of standard Table 7-11: System functions in control direction


information numbers INF Semantics
in control direction <0> Initiation of general interrogation
<0> Time synchronization

Table 7-12: General commands in control direction


INF Semantics
<16> Auto-recloser on / off
<17> Teleprotection on / off
<18> Protection on / off
<19> LED reset
<23> Activate characteristic 1
<24> Activate characteristic 2
<25> Activate characteristic 3
<26> Activate characteristic 4

Table 7-13: General functions in control direction


INF Semantics
<240> Read headings of all defined groups
<241> Read values or attributes of all entries of one group
<243> Read directory of a single entry
<244> Read value or attribute of a single entry
<245> General interrogation of generic data
<248> Write entry
<249> Write entry with confirmation
<250> Write entry with execution
<251> Write entry abort

7-10 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 7: IEC 60870-5-103 INTEROPERABILITY

Basic application
functions Test mode
Blocking of monitor direction
Disturbance data
Generic services
Private data

Miscellaneous
Measurand Max. MVAL = times rated value
1,2 or 2,4
Current L1
Current L2
Current L3
Voltage L1-E
Voltage L2-E
Voltage L3-E
Active power P
Reactive power Q
Frequency f
Voltage L1-L2

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 7-11


INTEROPERABILITY CHAPTER 7: IEC 60870-5-103

7-12 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 8: IEC 61850

IEC 61850

The optional communications processor supports both the IEC61850 protocol GOOSE
messaging and server service as per edition 2. The GOOSE messaging service allows the
850 relay the ability to publish digital, analog information and subscribe digital information
with other relays supporting the same service while the server support allows IEC61850
SCADA and HMI devices access to the relay for monitoring and control. The configuration
of IEC61850 services is accomplished using the 850 configuration software. Setting
changes are active after rebooting.
850 SCAN
The 850 has a 2 ms scan during which inputs are read, the data of all general generic
logical nodes is updated, protection elements are executed, Flexlogic is solved, and
outputs are updated.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-1


GENERAL CHAPTER 8: IEC 61850

Digital data in the logical nodes are updated every time they change, by event mechanism.
Analog data are refreshed every 250 millisecond by polling.

Power up self-test

Self-test

Comms Service

Read Inputs

Service GGl

Solve Protection

Solve Logic

Y Update enabled digital


Top of second
nodes
N

Service GGO

Set Outputs

MMS file transfer is not supported by the 850 relay in firmware version 1.10
FASTPATH:

General
IEC61850 SERVER
The information of interest that is exchanged between the relays IEC61850 server and the
substation HMI or SCADA system resides within the logical nodes of the relay.
The following tables list the logical nodes and number of instances that are supported
within the 850 relay.
LOGICAL NODES
Table 8-1: Communication Elements in the 850
850 Communications Elements Corresponding IEC61850 Supported in 850
Logical node and number
of instances
Port status LCCH (3)
Remote Device LGOS (8) Yes
Time master supervision LTMS

8-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 GENERAL

850 Communications Elements Corresponding IEC61850 Supported in 850


Logical node and number
of instances
Time management LTIM
PHYSICAL DEVICE INFORMATION LPHD Yes
Logical Node 0 LLN0 Yes

Table 8-2: Protection and Protection Related Elements in the 850


850 PROTECTION and PROTECTION RELATED Corresponding IEC61850 Supported in 850
ELEMENTS Logical node and number
of instances
GENERIC PROCESS I/O GGIO(6) Yes (GGIO2 to 6 are
supported & GGIO1 is
not supported)
METERING AND MEASUREMENT MMXU(3) Yes (only 2 is supported)
SEQUENCE AND IMBALANCE MSQI(3) Yes (only 1 is supported)
NONE PHASE RELATED METERING MMXN
CIRCUIT BREAKER XCBR(3) Yes (only 1 is supported)
BREAKER FAILURE RBRF
SYNCHROCHECK RSYN
AUTORECLOSING RREC(1) Yes
PHASE TOC 1-3 (51P) PTOC(3) Yes (only 2 is supported)
PHASE IOC 1-3 (50P) PIOC(3) Yes (only 2 is supported)
PHASE DIRECTIONAL OC (67P) RDIR Yes
NEUTRAL TOC1-2 (51N) PTOC(2) Yes
NEUTRAL IOC 1-2 (50N) PIOC(2) Yes
NEUTRAL DIRECTIONAL OC (67N) RDIR Yes
GROUND TOC 1 (51G) PTOC(1) Yes
GROUND IOC 1 (50G) PIOC(1) Yes
GROUND DIRECTIONAL OC (67G) RDIR Yes
SENSITIVE GROUND TOC (51SG) PTOC(1) Yes
SENSITIVE GROUND IOC (50 SG) PIOC(1) Yes
SENS. GROUND DIRECTIONAL OC (67SG) RDIR Yes
NEGATIVE SEQUENCE TOC (51_2) PTOC(1) Yes
NEGATIVE SEQUENCE IOC (50_2) PIOC(1) Yes
NEGATIVE SEQUENCE DIRECTIONAL (67_2) RDIR Yes
PHASE UNDERVOLTAGE 1-2 (27P) PTUV(2) Yes
AUX UNDERVOLTAGE 1 -2(27X) PTUV(2) Yes
AUX OVERVOLTAGE 1 -2(59X) PTOV(2) Yes (only 1 is supported)
PHASE OVERVOLTAGE 1 -2(59P) PTOV(2) Yes
NEUTRAL OVERVOLTAGE (59N) PTOV(1) Yes
NEGATIVE SEQUENCE OVERVOLTAGE (47P) PTOV(1)
VT FUSE FAIL
REVERSE POWER (32RP)
DIRECTIONAL POWER (32) PDOP
WATTMETRIC GND FAULT
UNDERFREQUENCY 1-4 (81U) PTUF(4) Yes
OVERFREQUENCY 1 -2(81O) PTOF(2) Yes
THERMAL OVERLOAD PTTR Yes
FREQUENCY RATE OF CHANGE (81df/dt) PFRC

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-3


GENERAL CHAPTER 8: IEC 61850

850 PROTECTION and PROTECTION RELATED Corresponding IEC61850 Supported in 850


ELEMENTS Logical node and number
of instances
POWER FACTOR 1 POPF(2)
FAULT LOCATOR RFLO
CURRENT LEVEL
MANUAL CLOSE BLOCKING
LOAD ENCROACHMENT
COLD LOAD PICKUP
BUS TRANSFER
UNDERVOLTAGE RESTORATION
UNDERFREQUENCY RESTORATION
EARTH LEAKAGE PHIZ
RESTRICTED EARTH FAULT
LOAD ENCROACHMENT
BROKEN CONDUCTOR
CABLE THERMAL MODEL

Each logical node within the preceding tables support all mandatory attributes in addition
to the optional data attributes (that are supported within the protection element). See
figure PDIF Class.
Figure 8-1: PDIF Class

8-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 FUNCTIONALITY

Functionality
CLIENT CONNECTIONS
The 850 supports four IEC61850 concurrent client connections.
LOGICAL DEVICES AND REPORTS
Supported buffered and un-buffered report triggers are shown in the Supported Triggers
list.
Supported Triggers
Data-change
Integrity
General-interrogation
Supported buffered and un-buffered report option fields are shown in the Field list.
Field
Sequence number
Report time stamp
Reason for inclusion
Data set name
Data-ref
Buffer-overflow (Buffered reports only)
Entry id (Buffered reports only)
Conf- revision
Report control block configuration settings are modified from IEC61850 advanced
configurator writing directly in a CID file. There are no Modbus settings.
The datasets for reports are fully configurable with CDCs from any Logical Node.
The Description field in the LN is fixed text and it is not updated from the Modbus settings.

The IEC 61850 Configurator


The 850 relay supports the IEC 61850 protocol which is identified by order code option 2E.
The IEC 61850 device configurator is found in both the online and offline section of the
EnerVista 8 Series Setup for configuring the online 850 relay and offline 850 settings file
respectively.

Online and Offline Setup


ONLINE SETTINGS FILE
Two options are available to configure the relays online settings file.
1. Configuration
Configure the 850 relay (having order code option: IEC 61850) through the Device
Setup or Quick connect screen.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-5


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

The IEC 61850 Device Configurator tree item is displayed after Maintenance.
See figure below.

Launch the online IEC 61850 Device configurator screen, by double-clicking on


the IEC61850 Device Configurator tree item.
Select the required settings from the different tab displays (in the configurator
screen) to complete the IEC 61850 configuration.
2. Online right-click option
Select any online relay and right click on the selected tree item. More options
become available for selection, as shown in the next examples.
Example of Additional Options
Generate ICD file: The menu option generates a default ICD file with the respective
order code option and saves the file to the path the user has selected previously..

Read Device Settings: The menu option reads all the settings from the relay by TFTP
and creates an 850 relay file with extension *.CID. The created *.CID file consists of
two sections. A private section where all non IEC 61850 settings are available, and a
public section in which IEC 61850 related settings are implemented.

8-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

OFFLINE SETTINGS FILE


The Generate ICD file menu option generates a default ICD file with the respective order
code option and saves the file to the path the user has selected previously.

IEC 61850 Device Configurator Details


The IEC61850 Device Configurator allows the user to edit all sections of the IEC61850 CID
and ICD file. The user cannot perform any other operations in the EnerVista 8 Series
Setup software if the IEC 61850 Device Configurator is open. The user must wait until the
Device Configurator session is closed to perform other operations in the EnerVista
software.
The IEC 61850 Device configurator consists of five sections:
ICD/CID
Settings
Reports
Goose Reception
Goose Transmission

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-7


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

ICD/CID Select the ICD/CID tab in the IEC 61850 Configurator window. The ICD/CID tab consists of
the ICD Explorer window to the left side of the view. The ICD Explorer window allows the
user to navigate through the data model of the relay and change desired IEC 61850
parameters such as the Logical Device Name, MMS port and others.

To Modify the Parameters


1. Select a parameter in the ICD Explorer window to open the Attributes window in the
right part of the screen.
2. In the Attributes window, double click in the Value row of the table and enter the new
value for that parameter.
For example, from the Attributes window the user can set the IED name, description,
and configuration version for the Logical Device, see preceding figure.
Parameters
IP, IP-Subnet, IP-Gateway: The parameters are the configured IP details in the device.
OSI parameters: The parameters must be configured according to the IEC 61850
standard.
MMS TCP Port Number: The range of the setting is 1 to 65535, in steps of 1. The setting
allows the user to change the TCP port number for MMS connections.
TCP Connection timeout: The range of the setting is 10 to 1800 s, in steps of 10. The
setting is useful for detecting dead IEC 61850 connections. The timer must be
application specific for IEC 61850. If there is no data traffic on a TCP connection for

8-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

more than the established timeout, the connection is aborted by the server.

GOOSE Transmission on port -4 and port-5 (which are the 2 fiber optic ports available)
is configurable. The user can choose either port or both of the ports for GOOSE
transmissions and Receptions. The logical nodes displayed under the GEDevice > 850
tree (see figure below) are shown based on the order code. If a particular order code
does not support certain protection and control functions, the respective logical node
is not shown in the list.

Settings The Settings tab consists of General settings and a DAI settings tab.
1. General Settings
IED NameRange:
Up to 64 alphanumeric characters
The IED Name represents the MMS domain name (IEC 61850 logical device) where all
IEC/MMS logical nodes are located. Valid characters for these values are upper and
lowercase letters, numbers, and the underscore (_) character, and the first character
in the string must be a letter. This conforms to the IEC l1850 standard.
LDevice inst
Range: Up to 64 alphanumeric characters
The setting represents the MMS domain name (IEC 61850 logical device) where all IEC/

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-9


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

MMS logical nodes are located. Valid characters for these values are upper and
lowercase letters, numbers, and the underscore (_) character. The first character in the
string must be a letter. This conforms to the IEC 61850 standard.

2. DAI Settings tab


DAI settings contains these features for configuration: MMXU & MSQI logical nodes,
GGIO3 logical node, XCBR logical node.
MMXU & MSQI Logical nodes
Range: 1 to 100.000 %
The MMXU & MSQI deadband settings represent the deadband values used to
determine when to update the MMXU mag and cVal values from the associated
instmag and instcVal values. The mag and cVal values are used for the IEC
61850 buffered and unbuffered reports. The settings correspond to the associated
db data items in the CF functional constraint of the MMXU logical node, as per the
IEC 61850 standard. According to IEC 61850-7-3, the db value shall represent the
percentage of difference between the maximum and minimum in units of 0.001%.
Thus, it is important to know the maximum value for each MMXU measured quantity,
since this represents the 100.00% value for the deadband.
MIN/MAX VALUES FOR MMXU NODES
The equations to calculate minimum (min) and maximum (max) values in the MMXU
nodes are as follows:
Table 8-3: Calculate Min/Max MMXU Node Values
MMXU Node Value To Calculate
TotW max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
Note that the max is divided by 1000 to convert from W to kW
TotVar max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
TotVA max = (Phase CT Primary * 46) * (Phase VT Ratio * 240) / 1000
min = -max
TotPF max = 1
min = -1
Hz max = 90
min = 0
PPV max = Phase VT Ratio * 240
min = 0
PhV max = Phase VT Ratio * 240
min = 0
A$phsA, phsB, phsC max = (Phase CT Primary * 46)
min = 0
A$neut max = (Ground CT Primary * 46)
min = 0
A$net max = (Phase CT Primary * 46)
min = 0

8-10 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

MMXU Node Value To Calculate


A$res max = (Sens. Ground CT Primary * 3)
min = 0
AuxV max = Aux. VT Ratio * 240
min = 0
SeqA$c1, c2 ,c3 max = (Phase CT Primary * 46)
min = 0
SeqV$c1, c2, c3 max = (Phase VT Ratio * 240)
min = 0

See the following list of supported parameters. Note that the same list is also
supported for the MSQI logical node. MSQI parameters are displayed only if the relay
supports sensitive ground CT.

Supported Parameters
850.MMXU1$CF$TotW$db
850.MMXU1$CF$TotVAr$db
850.MMXU1$CF$TotVA$db
850.MMXU1$CF$TotPF$db
850.MMXU1$CF$Hz$db
850.MMXU1$CF$PPV$phsAB$db
850.MMXU1$CF$PPV$phsAB$dbAng
850.MMXU1$CF$PPV$phsBC$db
850.MMXU1$CF$PPV$phsBC$dbAng
850.MMXU1$CF$PPV$phsCA$db
850.MMXU1$CF$PPV$phsCA$dbAng
850.MMXU1$CF$PhV$phsA$db
850.MMXU1$CF$PhV$phsA$dbAng
850.MMXU1$CF$PhV$phsB$db
850.MMXU1$CF$PhV$phsB$dbAng
850.MMXU1$CF$PhV$phsC$db
850.MMXU1$CF$PhV$phsC$dbAng
850.MMXU1$CF$PhV$neut$db
850.MMXU1$CF$PhV$neut$dbAng
850.MMXU1$CF$A$phsA$db
850.MMXU1$CF$A$phsA$dbAng
850.MMXU1$CF$A$phsB$db
850.MMXU1$CF$A$phsB$dbAng
850.MMXU1$CF$A$phsC$db
850.MMXU1$CF$A$phsC$dbAng
850.MMXU1$CF$A$neut$db
850.MMXU1$CF$A$neut$dbAng
850.MMXU1$CF$A$net$db
850.MMXU1$CF$A$net$dbAng
850.MMXU1$CF$A$res$db
850.MMXU1$CF$A$res$dbAng
850.MMXU1$CF$AuxV$db
850.MMXU1$CF$AuxV$dbAng

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-11


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

GGIO3 Logical Node


Range: Enum
These are the control models supported: (0) status only, (1) direct-with-normal-
security. They can be configured under the Value column.

XCBR Logical Node


Range: the sboTimeout setting range is 500 to 60000 msec
The XCBR1 Pos sboTimeout setting is used to select SBO timeout value. To be
successful, the IEC 61850 "operate" command must be executed after the "select"
command within the XCBR1 Pos sboTimeout setting value.
XCBR-POS can be configured for status only, Direct operate, Select before operate,
Direct operate with enhanced, SBO enhanced.

Reports The Reports tab in IEC 61580 Configurator permits configuration of data sets and control
blocks for buffered and unbuffered reports.

8-12 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

Figure 8-2: Reports Screen

The screen helps the user to create, modify and delete Report Control Blocks (RCBs) and
Datasets. Each Report Control Block must have a maximum of 4 different clients up to a
maximum of 4 Report Control Blocks linked to their Datasets. Each dataset must have a
maximum of 64 elements in total.
There are two screens are available in the Report tab window:
Report control block: The user can add the required report control block
Dataset sources: Each report control block can be appended with dataset items in the
screen using a drag and drop operation.
Figure 8-3: Report Control Blocks and DataSet Sources Screen

The following buttons are available in the Reports window.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-13


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

Add Report button and Remove Report button: Both buttons are in the lower side of
the screen.

Note that a Report control block can also be added by right clicking on 850 which is
under the GEDevice tree.

The Remove Report button deletes an existing Report control block.

Note that the Report can also be deleted by right clicking on the configured existing
report.

Save button and Cancel button: Click the Save button to save all configured settings.
Click the Cancel button to discard the modifications just made to the configuration.

Add Report Control Block


1. Click on the Add Report button.

The button is available in the lower side of the screen and is used to add a report
control block. (a Report can also be added by right clicking on 850 under GEDevice
tree.)
The New Report Control Block window appears.
Figure 8-4: New Report Control Block Window

2. In the New Report Control Block window under Select Report Type, select the radio
button for a buffered or unbuffered report.
3. In the IEC61850 Clients N# dropdown list, select 1 or any other available number.
4. Click the Next button to proceed with further configuration (else click Cancel to
discard the new configuration).
5. In the Select DataSet window, select the radio button for New DataSet or Existing
DataSet.

8-14 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

Figure 8-5: Select DataSet Window

Report Properties
The report properties section can be viewed when any configured report available under
GEDevice > 850 is selected
Figure 8-6: Report Properties Window

All the available parameters of the Report control block are displayed when clicking
Report Advanced Configuration. Respective OptFields, TrgOps can be configured by
either selecting True or False. Buffer time is given in milliseconds.
Figure 8-7: Advanced Configuration

Configure Dataset Items


1. Select the required logical node under GEDevice > 850 tree.
2. Go to the required dataset item.
3. Drag and drop the item to the DataSet Elements section, see the following DataSet
Sources/DataSet figure.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-15


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

Figure 8-8: DataSet Sources Window

Change the Order of Configured Dataset Items


1. Select the row in which the order is to be changed.
2. Use the up arrow if you want to shift the row to the top. Use the down arrow to shift
the row down.
Figure 8-9: Re-order DataSet Items

Delete a Dataset Item


The following list gives the two methods that can be used to delete a dataset item.
Select the row in which the dataset item is to be deleted and click the x button.
Figure 8-10: Delete a Dataset Item

Select the row in which the dataset item is to be deleted then right click and select the
displayed Delete FCDA option.
Figure 8-11: Delete FCDA Option

Number of DAs Counter


Depending on the configured dataset items, the Number of DAs counter increases
automatically.

8-16 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

Figure 8-12: Dataset Properties

Maximum Report Control Blocks


The 850 relay supports a maximum of 4 report control blocks. Buffered and unbuffered
reports are both included in the maximum. The user can configure reports based on the
Report Configurations Supported table as follows.
Table 8-4: Report Configurations Supported
Buffered Report Unbuffered Report Total Reports
4 0 4
3 1 4
2 2 4
1 3 4

Goose Transmission The 850 relay has an IEC 61850 server and supports the GOOSE message scheme. A
maximum of three GOOSE control blocks can be added. The GOOSE Configuration has two
sections:
Transmission
Reception
GOOSE transmission configuration is described in this section.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-17


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

Figure 8-13: Goose Transmission Screen

The GOOSE Transmission window has two screens.


GOOSE Tx control blocks: The user can add the required GOOSE control block.
Dataset sources: Each GOOSE control block can be appended with dataset items in
this screen using a drag and drop operation.
Figure 8-14: Goose TX Control Blocks and DataSet Sources Screen

The following buttons are available in the Goose Transmission window:

8-18 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

Add GOOSE Control Block button and Remove GOOSE Control Block button: Both
buttons are in the lower side of the screen.

Note that a GOOSE Control block can also be added by right clicking on 850 which is
under the GEDevice tree.

The Remove Goose Control Block button deletes a configured existing Goose control
block.

Note that the Goose control block can also be deleted by right clicking on the
configured existing report.

Save button and Cancel button: Click the Save button to save all configured settings.
Click the Cancel button to discard the modifications just made to the configuration.

Add GOOSE Transmission Control Block


1. Click on the Add GOOSE Control Block button.

2. The Tx GOOSE control block is added under GEDevice>850 tree node with a default
Control block name.
Figure 8-15: Goose TX Control Blocks

Goose Tx Properties
The properties section can be viewed on selecting any configured GOOSE block available
under GEDevice > 850.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-19


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

Figure 8-16: Goose TX Properties Screen

Parameters for Goose TX


GOOSE ID: The range of the setting is 129-characters
Time to live (ms): The range of the setting is 1000 to 60000 in steps of 1000
Multicast MAC: The standard MAC address limit. Make sure to configure the MAC with
a value of left most binary bit of 1st octet as 1.
Example:
03: 00: 00: 00: 00: 00, where left most bit of 03 (0000 0011) is 1 (or)
A5: 00 :AB: CD :12 :13, where left most bit of A5 (10100101) is 1
VLAN priority: The range of the setting is 0 to 7 in steps of 1
VLAN identifier: The range of the setting is 0 to 4095 in steps of 1
Goose Transmission Dataset Items
The following provides details for working with dataset items.
Change the Order of Configured Dataset Items
1. Select the row in which the order is to be changed.
2. Use the up arrow if you want to shift the row to the top. Use the down arrow to shift
the row down.
Figure 8-17: Re-order DataSet Items

Delete a Dataset Item


The following list gives the two methods that can be used to delete a dataset item.
Select the row in which the dataset item is to be deleted and click the x button.
Figure 8-18: Delete a Dataset Item

Select the row in which the dataset item is to be deleted then right click and select the
displayed Delete FCDA option.

8-20 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 8: IEC 61850 THE IEC 61850 CONFIGURATOR

Figure 8-19: Delete FCDA Option

Number of DAs
Depending on the configured dataset items, the Number of DAs counter increases
automatically.
Figure 8-20: Dataset Properties

Goose Reception The 850 relay can receive Transmitted GOOSE from any IED in GOOSE Reception. For
proper GOOSE reception the relay must be configurated as described in this section. A
maximum of eight IEDs can be added.
GOOSE Reception has two sections:
IDE list: The user can add IED to subscribe GOOSE.
Mapping to Remote Inputs: Each subscribed GOOSE dataset item can be appended in
the screen using the drag and drop method.
Figure 8-21: Goose Reception Screen

The following buttons are available in the Goose Reception window:


Add IED button and Remove IED button: Both buttons are in the lower side of the
screen.

Note that IED can also be added by right clicking in the IED List section.

The Remove IED button deletes a configured IED.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 8-21


THE IEC 61850 CONFIGURATOR CHAPTER 8: IEC 61850

Save button and Cancel button: Click the Save button to save all configured settings.
Click the Cancel button to discard the modifications just made to the configuration.

Configure Dataset Items


1. Select the dataset item being subscribed under the required IED which is available in
Template > LDInst > GOOSEOut 1 tree.
2. Go to the required dataset item.
3. Drag and drop the chosen dataset item to the Mapping to Remote Inputs section as
shown in the figure: Mapping to Remote Inputs.
Figure 8-22: Mapping to Remote Inputs

Delete a Dataset Item


Select the row in which the dataset item is being deleted then right click and select the
Delete Entry button.
Figure 8-23: Delete a Dataset Item

IED Count
Depending on the configured dataset items for IEDs, the IED count increases
automatically. In addition, the GOOSE Id field is updated with the GOOSE ID of the
subscriber relay.
Figure 8-24: IED Count

8-22 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 9: TFTP

TFTP

The 850 relay supports Trivial File Transfer Protocol (TFTP). The default port 69 is always
used. No configuration setting is available.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 9-1


CHAPTER 9: TFTP

9-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 10: Modbus Protocol

Modbus Protocol

All Ethernet ports and serial communication ports support the Modbus protocol. The only
exception is if the serial port has been configured for DNP or IEC 60870-5-103 operation
(see descriptions below). This allows the EnerVista 8 Series Setup software (which is a
Modbus master application) to communicate to the 850 .
The 850 implements a subset of the Modicon Modbus RTU serial communication standard.
The Modbus protocol is hardware-independent. That is, the physical layer can be any of a
variety of standard hardware configurations. This includes USB, RS485, fibre optics, etc.
Modbus is a single master / multiple slave type of protocol suitable for a multi-drop
configuration.
The 850 is always a Modbus slave with a valid slave address range 1 to 254.
DATA FRAME FORMAT AND DATA RATE
One data frame of an asynchronous transmission to or from an 850 typically consists of 1
start bit, 8 data bits, and 1 stop bit. This produces a 10-bit data frame. This is important for
transmission through modems at high bit rates. Modbus protocol can be implemented at
any standard communication speed. The 850 supports operation at 9600, 19200, 38400,
57600, and 115200 baud. The USB interface supports ModBus TCP/IP.

850 SUPPORTED FUNCTIONS


The following functions are supported by the 850 :
FUNCTION CODE 03H - Read Setpoints
FUNCTION CODE 04H - Read Actual Values
FUNCTION CODE 05H - Execute Operation
FUNCTION CODE 06H - Store Single Setpoint
FUNCTION CODE 07H - Read Device Status
FUNCTION CODE 08H - Loopback Test
FUNCTION CODE 10H - Store Multiple Setpoints
FUNCTION CODE 42H - Group Settings Read
FUNCTION CODE 43H - Group Settings Write
When a ModBus master such as the EnerVista 8 Series Setup software communicates to
the 850 over Ethernet, the 850 slave address, TCP port number and the 850 IP address for
the associated port must be configured and are also configured within the Master for this
device. The default ModBus TCP port number is 502.
The following ModBus parameters are configurable:

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 10-1


MODBUS PROTOCOL CHAPTER 10: MODBUS PROTOCOL

Path: Setpoints > Device > Communications > Modbus Protocol

MODBUS SLAVE ADDRESS


Range: 1 to 254 in steps of 1
Default: 254
For the RS485 ports each 850 must have a unique address from 1 to 254. Address 0 is
the broadcast address to which all Modbus slave devices listen. Addresses do not have
to be sequential, but no two devices can have the same address, otherwise conflicts
resulting in errors occur. Generally, each device added to the link uses the next higher
address starting at 1.
MODBUS TCP PORT
Range: 1 to 65535 in steps of 1
Default: 502
The TCP port number used with Modbus over Ethernet. Note that the maximum number
of simultaneous Modbus connections supported over Ethernet is:
three for an 850 relay without the communications card,
five for an 850 relay with the communications card.
MODBUS ERROR RESPONSES
The following exception response codes are implemented.

Error ID Exception Description


01 ILLEGAL FUNCTION The function code transmitted is not one of the
functions supported by the 850.
02 ILLEGAL DATA ADDRESS The address referenced in the data field transmitted
by the master is not an allowable address for the 850.
03 ILLEGAL DATA VALUE The value referenced in the data field transmitted by
the master is not within range for the selected data
address.

Modbus Protocol
Function Code 03H
Modbus implementation: Read Holding Registers850 implementation: Read Setpoints
For the 850 implementation of Modbus, the function code can be used to read any
setpoints (holding registers). Holding registers are 16 bit (two byte) values transmitted
high order byte first. As a result all 350 Setpoints are sent as two bytes. The maximum
number of registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
number of data bytes to follow, the data itself and the CRC. Each data item is sent as a two
byte number with the high order byte sent first.

10-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 10: MODBUS PROTOCOL MODBUS PROTOCOL

For example, consider a request for slave 17 to respond with 3 registers starting at
address006B. For this example the register data in these addresses is as follows:

Function Code 04H


Modbus Implementation: Read Input Registers
850 implementation: Read Actual Values
For the 850 implementation of Modbus, the function code can be used to read any actual
values (input registers). Input registers are 16 bit (two byte) values transmitted high order
byte first. Thus all 350 Actual Values are sent as two bytes. The maximum number of
registers that can be read in one transmission is 125.
The slave response to this function code is the slave address, function code, a count of the
data bytes to follow, the data itself and the CRC. Each data item is sent as a two byte
number with the high order byte sent first.
For example, request slave 17 to respond with 1 register starting at address 0008. For this
example the value in this register (0008) is 0000.

Function Code 05H


Modbus Implementation: Force Single Coil
850 Implementation: Execute Operation

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 10-3


MODBUS PROTOCOL CHAPTER 10: MODBUS PROTOCOL

The function code allows the master to request a 850 to perform specific command
operations.
For example, to request slave 17 to execute operation code 1 (reset), we have the following
master/slave packet format:

Function Code 06H


Modbus Implementation: Preset Single Register
850 Implementation: Store Single Setpoint
The command allows the master to store a single setpoint into the memory of a 850 relay.
The slave response to this function code is to echo the entire master transmission.
For example, request slave 17 to store the value 2 in setpoint address 04 5C. After the
transmission in this example is complete, setpoints address 04 5C contains the value 0002.
The master/slave packet format is shown next.

Function Code 07H


Modbus Implementation: Read Exception Status
850 Implementation: Read Device Status

10-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 10: MODBUS PROTOCOL MODBUS PROTOCOL

The function used to quickly read the status of a selected device. A short message length
allows for rapid reading of status. The status byte returned has individual bits set to 1 or 0
depending on the status of the slave device. For this example, consider the following 850
general status byte:

Function Code 08H


Modbus Implementation: Loopback
850 Implementation: Loopback Test
The function is used to test the integrity of the communication link. The 850 echos the
request.
For example, consider a loopback test from slave 17:

Function Code 10H


Modbus Implementation: Preset Multiple Registers
850 Implementation: Store Multiple Setpoints
The function code allows multiple Setpoints to be stored into the 850 memory. Modbus
registers are 16-bit (two byte) values transmitted high order byte first. Thus all 850
setpoints are sent as two bytes. The maximum number of Setpoints that can be stored in
one transmission is dependent on the slave device. Modbus allows up to a maximum of 60
holding registers to be stored. The 850 response to this function code is to echo the slave
address, function code, starting address, the number of Setpoints stored, and the CRC.

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 10-5


MODBUS PROTOCOL CHAPTER 10: MODBUS PROTOCOL

For example, consider a request for slave 17 to store the value 00 02 to setpoint address
045C and the value 01 F4 to setpoint address 04 5D. After the transmission in this example
is complete, 850 slave 17 has the following setpoints information stored:

10-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


GE
Digital Energy

850 Feeder Protection System

Chapter 11: Modbus Memory Map

Modbus Memory Map

Reading the Event Recorder


To read the entire event recorder contents (the only available format), use the following
filename:
Evt.evt

Reading Transient Recorder


Familiarity with the Transient recorder feature is required to understand the following
description.
The Oscillography_ Number_of_Triggers register is incremented by one every time a new
oscillography file is triggered (captured) and cleared to zero when oscillography data is
cleared. When a new trigger occurs, the associated oscillography file is assigned a file
identifier number equal to the incremented value of the register; the newest file number is
equal to the Oscillography_Number_of_Triggers register. This register can be used to
determine if any new data has been captured by periodically reading it to see if the value
has changed; if the number has increased then new data is available.
The Oscillography Number of Records register specifies the maximum number of files (and
the number of cycles of data per file) that can be stored in the memory of the relay.
The Oscillography Available Records register specifies the actual number of files that are
stored and still available to be read out of the relay. Writing Yes (i.e. the value 1) to the
Oscillography Clear Data register clears oscillography data files, clears both the
Oscillography Number of Triggers and Oscillography Available Records registers to zero,
and sets the Oscillography Last Cleared Date to the present date and time.
To read binary COMTRADE oscillography files, read the following filenames:
OSCnnnn.CFG and OSCnnn.DAT
Replace the nnn with the desired oscillography trigger number. For ASCII format, use the
following filenames:
OSCAnnnn.CFG and OSCAnnn.DAT

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-1


READING FAULT REPORTS CHAPTER 11: MODBUS MEMORY MAP

Reading Fault Reports


Fault report data is available via the file retrieval mechanism in 850 relay. The filename is
FaultReport1_#####.txt and the ##### refers to the fault report record number.
The fault report number is a counter that indicates how many fault reports have ever
occurred. Only the last fifteen fault reports are available for retrieval; a request for a non-
existent fault report file yields a null file.
The current value fault report counter is available in Number of Fault Reports Modbus
register.

Accessing Data via the User Map


The 850 has a powerful feature, called the User Map, which allows a computer to read up
to 125 non-consecutive data registers (setpoints or actual values) by using one Modbus
packet. It is often necessary for a master computer to continuously poll various values in
each of the connected slave relays. If these values are scattered throughout the memory
map, reading them would require numerous transmissions and would burden the
communication link. The User Map can be programmed to join any memory map address
to one in the block of consecutive User Map locations, so that they can be accessed by
reading these consecutive locations.
The 850 contains a user-definable area in the Modbus memory map. This area allows re-
mapping of the addresses of any Actual Values registers. The User Definable area has two
sections.
1. A Register Index area (40524 to 40648) that contains 125 Actual Values register
addresses
2. A Register area (30524 to 30648) that contains the data at the addresses in the
Register Index
Register data that is separated in the rest of the memory map may be re-mapped to
adjacent register addresses in the user-definable registers area. This is accomplished by
writing to register addresses in the user-definable register index area. This allows for
improved throughput of data and can eliminate the need for multiple read command
sequences. The user-definable register index is stored as a setpoint and therefore it is
remembered even when the power is removed.
Default User Map
Common actual values have been defaulted for the user. Below are the default registers.
Table 11-1: Default User Map
User Map Address Description Modbus Address
User Map Address 1,2 LED Status 30712 30713
User Map Address 3,4 LED Status 30708 30709
User Map Address 5,6 Contact Input 1-32 30700 30701
User Map Address 7,8 Contact Output 1-32 30706 30707
User Map Address 9,10 Virtual Input Status 1-32 30714 30715
User Map Address 11, 12 Virtual Output Status 1-32 30718 30719
User Map Address 13,14 Remote Input 1-32 30728 30729
User Map Address 15,16 Remote Output 1-32 30736 30737
User Map Address 17,18 Ia 31270 31271
User Map Address 19,20 Ib 31272 31273

11-2 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MEMORY MAP ORGANIZATION

User Map Address Description Modbus Address


User Map Address 21,22 Ic 31274 31275
User Map Address 23,24 In 31278 31279
User Map Address 25,26 Iavg 31295 31296
User Map Address 27,28 Ig 31276 31277

The 850 supports 32-bit Modbus items to be configured in the user map. When such an
address is configured in the user map for example at user map address 1, user map
address 2 is also consumed by the same item irrespective of the address assigned in
address 2.

Memory Map Organization


The 850 Memory Map describes all the data registers that can be accessed via serial
communications. The Memory Map address range is grouped into several categories as
outlined in the following table. All memory map locations are two byte (16 bit) values. The
remaining pages of this chapter list all locations of the Memory Map. Addresses for all
locations are shown in hexadecimal. Consult the range, step, units, and the data format
(listed after the memory map) to interpret register values.
Many Modbus communications drivers add 40001d to the actual address of the register
addresses. For example, if address 0h was to be read, then 40001d would be the address
required by the Modbus communications driver; similarly, if address 320h (800d) was to be
read, then 40801d would be the address required by the Modbus communications driver.
Table 11-2: Memory Map Organization
Memory Map Section Address Range Description
Product ID 0000h to 007Fh Identification and revision information.
Commands 0080h to 00FFh Substitute command locations. Read and write
access.
User Map 0100h to 01FFh User Map Values and Addresses. See the
previous section for details.
Actual Values 0200h to 0FFFh Actual values data. Read Only.
Setpoints 1000h to 1FFFh Setpoints data. Read and Write.
Event Recorder, Trace 2000h to 2FFFh See relevant sections in this chapter for details.
Memory, and Data Logger
Reserved 3000h to 3FFFh Reserved for future use.
Factory Service Data 4000h to FFFFh Reserved.

MODBUS memory map

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Actual Values
Product Information
30001 0x0000 Product Code 0 65535 1 F0 0 1
30002 0x0001 Hardware Revision 0 26 1 FC110 1 1
30003 0x0002 Firmware Version 0 65535 1 F2 110 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-3


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30005 0x0004 Boot 0 65535 1 F2 0 1
30006 0x0005 Firmware Date 0x010107D8 0x0C1F082E 1 F53 16844760 1
30008 0x0007 Firmware Time 0 0x173B3B63 1 F54 0 1
30010 0x0009 Boot Date 0x010107D8 0x0C1F082E 1 F53 16844760 1
30012 0x000B Boot Time 0 0x173B3B63 1 F54 0 1
30014 0x000D Product Serial # 0 65535 1 F60_12 Serial 12
30021 0x0014 Order Code 0 65535 1 F60_34 OrderCode 34
30038 0x0025 MAC Address 1 0 65535 1 F60_6A 0 6A
30047 0x002E Comms CPU fw Version 0 65535 1 F2 0 1
30049 0x0030 Boot 0 65535 1 F2 0 1
30050 0x0031 Comms CPU Firmware 0x010107D8 0x0C1F082E 1 F53 16844760 1
Date
30052 0x0033 Comms CPU Firmware 0 0x173B3B63 1 F54 0 1
Time
30054 0x0035 Boot Date 0x010107D8 0x0C1F082E 1 F53 16844760 1
30056 0x0037 Boot Time 0 0x173B3B63 1 F54 0 1
30058 0x0039 MAC Address 1 0 65535 1 F60_6A 0 6A
30061 0x003C MAC Address 2 0 65535 1 F60_6A 0 6A
30067 0x0042 FPGA Firmware Version 0 0xFFFFFFFF 1 F71 0 1
30069 0x0044 IO F CPLD 0 0xFFFFFFFF 1 F71 0 1
30071 0x0046 IO G CPLD 0 0xFFFFFFFF 1 F71 0 1
30075 0x004A AN J CPLD 0 0xFFFFFFFF 1 F71 0 1
30077 0x004C AN K CPLD 0 0xFFFFFFFF 1 F71 0 1
30079 0x004E Display CPLD 0 0xFFFFFFFF 1 F71 0 1
Time
30241 0x00F0 Time 0 0x173B3B63 1 F54 0 1
30243 0x00F2 Date 0x010107D8 0x0C1F082E 1 F53 16844760 1
30245 0x00F4 RTC Time 0 0xFFFFFFFF 1 s F52 0 1
30247 0x00F6 System Clock 0 0xFFFFFFFF 1 s F52 0 1
Targets
30257 0x0100 Target Custom Text 0 65535 1 F60_26 26
30270 0x010D Target Count 0 256 1 F0 0 1
30271 0x010E Target Cause 0 0xFFFFFFFF 1 FC134 0 1
30273 0x0110 Target Type 0 2 1 FC101 0 1
30274 0x0111 Target Time 0 60000 1 F0 0 1
PTP Status
30300 0x012B RTC Sync Source 0 4 1 FC342 0 1
30301 0x012C Grandmaster ID 0 65535 1 F60_8A 0 8A
30305 0x0130 RTC Accuracy -999999999 999999999 1 ns F30 0 1
30307 0x0132 Port 4 PTP State 0 4 1 FC343 1 1
30308 0x0133 Port 5 PTP State 0 4 1 FC343 1 1
User Map Values
30524 0x020B User Map Value 1 0 65535 1 F0 0 1
30525 0x020C User Map Value 2 0 65535 1 F0 0 1
30526 0x020D User Map Value 3 0 65535 1 F0 0 1
30527 0x020E User Map Value 4 0 65535 1 F0 0 1
30528 0x020F User Map Value 5 0 65535 1 F0 0 1

11-4 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30529 0x0210 User Map Value 6 0 65535 1 F0 0 1
30530 0x0211 User Map Value 7 0 65535 1 F0 0 1
30531 0x0212 User Map Value 8 0 65535 1 F0 0 1
30532 0x0213 User Map Value 9 0 65535 1 F0 0 1
30533 0x0214 User Map Value 10 0 65535 1 F0 0 1
30534 0x0215 User Map Value 11 0 65535 1 F0 0 1
30535 0x0216 User Map Value 12 0 65535 1 F0 0 1
30536 0x0217 User Map Value 13 0 65535 1 F0 0 1
30537 0x0218 User Map Value 14 0 65535 1 F0 0 1
30538 0x0219 User Map Value 15 0 65535 1 F0 0 1
30539 0x021A User Map Value 16 0 65535 1 F0 0 1
30540 0x021B User Map Value 17 0 65535 1 F0 0 1
30541 0x021C User Map Value 18 0 65535 1 F0 0 1
30542 0x021D User Map Value 19 0 65535 1 F0 0 1
30543 0x021E User Map Value 20 0 65535 1 F0 0 1
30544 0x021F User Map Value 21 0 65535 1 F0 0 1
30545 0x0220 User Map Value 22 0 65535 1 F0 0 1
30546 0x0221 User Map Value 23 0 65535 1 F0 0 1
30547 0x0222 User Map Value 24 0 65535 1 F0 0 1
30548 0x0223 User Map Value 25 0 65535 1 F0 0 1
30549 0x0224 User Map Value 26 0 65535 1 F0 0 1
30550 0x0225 User Map Value 27 0 65535 1 F0 0 1
30551 0x0226 User Map Value 28 0 65535 1 F0 0 1
30552 0x0227 User Map Value 29 0 65535 1 F0 0 1
30553 0x0228 User Map Value 30 0 65535 1 F0 0 1
30554 0x0229 User Map Value 31 0 65535 1 F0 0 1
30555 0x022A User Map Value 32 0 65535 1 F0 0 1
30556 0x022B User Map Value 33 0 65535 1 F0 0 1
30557 0x022C User Map Value 34 0 65535 1 F0 0 1
30558 0x022D User Map Value 35 0 65535 1 F0 0 1
30559 0x022E User Map Value 36 0 65535 1 F0 0 1
30560 0x022F User Map Value 37 0 65535 1 F0 0 1
30561 0x0230 User Map Value 38 0 65535 1 F0 0 1
30562 0x0231 User Map Value 39 0 65535 1 F0 0 1
30563 0x0232 User Map Value 40 0 65535 1 F0 0 1
30564 0x0233 User Map Value 41 0 65535 1 F0 0 1
30565 0x0234 User Map Value 42 0 65535 1 F0 0 1
30566 0x0235 User Map Value 43 0 65535 1 F0 0 1
30567 0x0236 User Map Value 44 0 65535 1 F0 0 1
30568 0x0237 User Map Value 45 0 65535 1 F0 0 1
30569 0x0238 User Map Value 46 0 65535 1 F0 0 1
30570 0x0239 User Map Value 47 0 65535 1 F0 0 1
30571 0x023A User Map Value 48 0 65535 1 F0 0 1
30572 0x023B User Map Value 49 0 65535 1 F0 0 1
30573 0x023C User Map Value 50 0 65535 1 F0 0 1
30574 0x023D User Map Value 51 0 65535 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-5


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30575 0x023E User Map Value 52 0 65535 1 F0 0 1
30576 0x023F User Map Value 53 0 65535 1 F0 0 1
30577 0x0240 User Map Value 54 0 65535 1 F0 0 1
30578 0x0241 User Map Value 55 0 65535 1 F0 0 1
30579 0x0242 User Map Value 56 0 65535 1 F0 0 1
30580 0x0243 User Map Value 57 0 65535 1 F0 0 1
30581 0x0244 User Map Value 58 0 65535 1 F0 0 1
30582 0x0245 User Map Value 59 0 65535 1 F0 0 1
30583 0x0246 User Map Value 60 0 65535 1 F0 0 1
30584 0x0247 User Map Value 61 0 65535 1 F0 0 1
30585 0x0248 User Map Value 62 0 65535 1 F0 0 1
30586 0x0249 User Map Value 63 0 65535 1 F0 0 1
30587 0x024A User Map Value 64 0 65535 1 F0 0 1
30588 0x024B User Map Value 65 0 65535 1 F0 0 1
30589 0x024C User Map Value 66 0 65535 1 F0 0 1
30590 0x024D User Map Value 67 0 65535 1 F0 0 1
30591 0x024E User Map Value 68 0 65535 1 F0 0 1
30592 0x024F User Map Value 69 0 65535 1 F0 0 1
30593 0x0250 User Map Value 70 0 65535 1 F0 0 1
30594 0x0251 User Map Value 71 0 65535 1 F0 0 1
30595 0x0252 User Map Value 72 0 65535 1 F0 0 1
30596 0x0253 User Map Value 73 0 65535 1 F0 0 1
30597 0x0254 User Map Value 74 0 65535 1 F0 0 1
30598 0x0255 User Map Value 75 0 65535 1 F0 0 1
30599 0x0256 User Map Value 76 0 65535 1 F0 0 1
30600 0x0257 User Map Value 77 0 65535 1 F0 0 1
30601 0x0258 User Map Value 78 0 65535 1 F0 0 1
30602 0x0259 User Map Value 79 0 65535 1 F0 0 1
30603 0x025A User Map Value 80 0 65535 1 F0 0 1
30604 0x025B User Map Value 81 0 65535 1 F0 0 1
30605 0x025C User Map Value 82 0 65535 1 F0 0 1
30606 0x025D User Map Value 83 0 65535 1 F0 0 1
30607 0x025E User Map Value 84 0 65535 1 F0 0 1
30608 0x025F User Map Value 85 0 65535 1 F0 0 1
30609 0x0260 User Map Value 86 0 65535 1 F0 0 1
30610 0x0261 User Map Value 87 0 65535 1 F0 0 1
30611 0x0262 User Map Value 88 0 65535 1 F0 0 1
30612 0x0263 User Map Value 89 0 65535 1 F0 0 1
30613 0x0264 User Map Value 90 0 65535 1 F0 0 1
30614 0x0265 User Map Value 91 0 65535 1 F0 0 1
30615 0x0266 User Map Value 92 0 65535 1 F0 0 1
30616 0x0267 User Map Value 93 0 65535 1 F0 0 1
30617 0x0268 User Map Value 94 0 65535 1 F0 0 1
30618 0x0269 User Map Value 95 0 65535 1 F0 0 1
30619 0x026A User Map Value 96 0 65535 1 F0 0 1
30620 0x026B User Map Value 97 0 65535 1 F0 0 1

11-6 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30621 0x026C User Map Value 98 0 65535 1 F0 0 1
30622 0x026D User Map Value 99 0 65535 1 F0 0 1
30623 0x026E User Map Value 100 0 65535 1 F0 0 1
30624 0x026F User Map Value 101 0 65535 1 F0 0 1
30625 0x0270 User Map Value 102 0 65535 1 F0 0 1
30626 0x0271 User Map Value 103 0 65535 1 F0 0 1
30627 0x0272 User Map Value 104 0 65535 1 F0 0 1
30628 0x0273 User Map Value 105 0 65535 1 F0 0 1
30629 0x0274 User Map Value 106 0 65535 1 F0 0 1
30630 0x0275 User Map Value 107 0 65535 1 F0 0 1
30631 0x0276 User Map Value 108 0 65535 1 F0 0 1
30632 0x0277 User Map Value 109 0 65535 1 F0 0 1
30633 0x0278 User Map Value 110 0 65535 1 F0 0 1
30634 0x0279 User Map Value 111 0 65535 1 F0 0 1
30635 0x027A User Map Value 112 0 65535 1 F0 0 1
30636 0x027B User Map Value 113 0 65535 1 F0 0 1
30637 0x027C User Map Value 114 0 65535 1 F0 0 1
30638 0x027D User Map Value 115 0 65535 1 F0 0 1
30639 0x027E User Map Value 116 0 65535 1 F0 0 1
30640 0x027F User Map Value 117 0 65535 1 F0 0 1
30641 0x0280 User Map Value 118 0 65535 1 F0 0 1
30642 0x0281 User Map Value 119 0 65535 1 F0 0 1
30643 0x0282 User Map Value 120 0 65535 1 F0 0 1
30644 0x0283 User Map Value 121 0 65535 1 F0 0 1
30645 0x0284 User Map Value 122 0 65535 1 F0 0 1
30646 0x0285 User Map Value 123 0 65535 1 F0 0 1
30647 0x0286 User Map Value 124 0 65535 1 F0 0 1
30648 0x0287 User Map Value 125 0 65535 1 F0 0 1
Event Recorder
30660 0x0293 Date/Time Of Last Clear 0 0xFFFFFFFF 1 F50 0 1
30662 0x0295 Time Of Last Clear (us) 0 999999 1 us F51 0 1
30664 0x0297 Events Since Last Clear 0 1024 1 F0 0 1
Input / Output Status
30700 0x02BB CI Inputs 1-32 0 0xFFFFFFFF 1 FC194 0 1
30706 0x02C1 CO Outputs 0 0xFFFFFFFF 1 FC198 0 1
30708 0x02C3 LED 1-32 0 0xFFFFFFFF 1 F10 0 1
30712 0x02C7 Device Status 0 0xFFFFFFFF 1 FC135 0 1
30714 0x02C9 Virtual Inputs 1-32 0 0xFFFFFFFF 1 F10 0 1
30718 0x02CD Virtual Outputs 1-32 0 0xFFFFFFFF 1 F10 0 1
30728 0x02D7 Remote Inputs 1 0 0xFFFFFFFF 1 FC191 0 1
30740 0x02E3 Element Status 1 (Any 0 65535 1 FC151 0 1
Trip)
30741 0x02E4 Element Status 2 (Any 0 65535 1 FC151 0 1
Alarm)
30744 0x02E7 Element Status 5 (Any 0 65535 1 FC151 0 1
Block)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-7


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30745 0x02E8 Element Status 6 (Any 0 65535 1 FC151 0 1
Pickup)
30746 0x02E9 Element Status 7 (Any OP) 0 65535 1 FC151 0 1
30747 0x02EA Element Status 8 (Reset) 0 65535 1 FC151 0 1
30748 0x02EB Element Status 9 (Setpoint 0 65535 1 FC151 0 1
Access)
30749 0x02EC Element Status 10 0 65535 1 FC151 0 1
(Targets Active)
30750 0x02ED Element Status 11 (In 0 65535 1 FC151 0 1
Service)
30751 0x02EE Element Status 12 (Test 0 65535 1 FC151 0 1
Mode)
30752 0x02EF Element Status 13 (Any 0 65535 1 FC151 0 1
Major Error)
30753 0x02F0 Element Status 14 (Any 0 65535 1 FC151 0 1
Minor Error)
30754 0x02F1 Element Status 15 (Output 0 65535 1 FC151 0 1
Relay 1)
30755 0x02F2 Element Status 16 (Output 0 65535 1 FC151 0 1
Relay 2)
30756 0x02F3 Element Status 17 (Output 0 65535 1 FC151 0 1
Relay 3)
30757 0x02F4 Element Status 18 (Output 0 65535 1 FC151 0 1
Relay 4)
30758 0x02F5 Element Status 19 (Output 0 65535 1 FC151 0 1
Relay 5)
30759 0x02F6 Element Status 20 (Output 0 65535 1 FC151 0 1
Relay 6)
30760 0x02F7 Element Status 21 (Critical 0 65535 1 FC151 0 1
Fail)
30761 0x02F8 Element Status 22 0 65535 1 FC151 0 1
(Comms OK)
30762 0x02F9 Element Status 23 (Phase 0 65535 1 FC151 0 1
TOC 1)
30763 0x02FA Element Status 24 (Phase 0 65535 1 FC151 0 1
TOC 2)
30765 0x02FC Element Status 26 (Phase 0 65535 1 FC151 0 1
IOC 1)
30766 0x02FD Element Status 27 (Phase 0 65535 1 FC151 0 1
IOC 2)
30768 0x02FF Element Status 29 (Phase 0 65535 1 FC151 0 1
Directional OC)
30769 0x0300 Element Status 30 0 65535 1 FC151 0 1
(Neutral TOC 1)
30770 0x0301 Element Status 31 0 65535 1 FC151 0 1
(Neutral TOC 2)
30771 0x0302 Element Status 32 0 65535 1 FC151 0 1
(Neutral IOC 1)
30772 0x0303 Element Status 33 0 65535 1 FC151 0 1
(Neutral IOC 2)
30773 0x0304 Element Status 34 0 65535 1 FC151 0 1
(Neutral Directional OC)
30774 0x0305 Element Status 35 0 65535 1 FC151 0 1
(Ground TOC 1)
30778 0x0309 Element Status 39 0 65535 1 FC151 0 1
(Ground IOC 1)

11-8 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30782 0x030D Element Status 43 0 65535 1 FC151 0 1
(Ground Directional OC)
30783 0x030E Element Status 44 0 65535 1 FC151 0 1
(Sensitive Ground TOC 1)
30784 0x030F Element Status 45 0 65535 1 FC151 0 1
(Sensitive Ground TOC 2)
30785 0x0310 Element Status 46 0 65535 1 FC151 0 1
(Sensitive Ground IOC 1)
30786 0x0311 Element Status 47 0 65535 1 FC151 0 1
(Sensitive Ground IOC 2)
30787 0x0312 Element Status 48 0 65535 1 FC151 0 1
(Sensitive Ground
Directional OC)
30788 0x0313 Element Status 49 0 65535 1 FC151 0 1
(Restricted Ground Fault
1)
30791 0x0316 Element Status 52 0 65535 1 FC151 0 1
(Negative Sequence TOC
1)
30793 0x0318 Element Status 54 0 65535 1 FC151 0 1
(Negative Sequence IOC
1)
30795 0x031A Element Status 56 0 65535 1 FC151 0 1
(Negative Sequence Dir
OC)
30796 0x031B Element Status 57 (Broken 0 65535 1 FC151 0 1
Conductor)
30797 0x031C Element Status 58 (Load 0 65535 1 FC151 0 1
Encroachment)
30798 0x031D Element Status 59 (Cable 0 65535 1 FC151 0 1
Thermal Model)
30799 0x031E Element Status 60 (Cable 0 65535 1 FC151 0 1
Thermal Model Alarm)
30800 0x031F Element Status 61 (Phase 0 65535 1 FC151 0 1
UV 1)
30801 0x0320 Element Status 62 (Phase 0 65535 1 FC151 0 1
UV 2)
30802 0x0321 Element Status 63 (Phase 0 65535 1 FC151 0 1
OV 1)
30803 0x0322 Element Status 64 (Phase 0 65535 1 FC151 0 1
OV 2)
30804 0x0323 Element Status 65 0 65535 1 FC151 0 1
(Auxiliary UV 1)
30805 0x0324 Element Status 66 0 65535 1 FC151 0 1
(Auxiliary UV 2)
30806 0x0325 Element Status 67 0 65535 1 FC151 0 1
(Auxiliary OV)
30807 0x0326 Element Status 68 0 65535 1 FC151 0 1
(Neutral OV 1)
30809 0x0328 Element Status 70 0 65535 1 FC151 0 1
(Negative Sequence OV 1)
30811 0x032A Element Status 72 (Dir 0 65535 1 FC151 0 1
Power 1)
30812 0x032B Element Status 73 (Dir 0 65535 1 FC151 0 1
Power 2)
30813 0x032C Element Status 74 0 65535 1 FC151 0 1
(WattMetric 1)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-9


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30815 0x032E Element Status 76 0 65535 1 FC151 0 1
(Underfrequency 1)
30816 0x032F Element Status 77 0 65535 1 FC151 0 1
(Underfrequency 2)
30817 0x0330 Element Status 78 0 65535 1 FC151 0 1
(Underfrequency 3)
30818 0x0331 Element Status 79 0 65535 1 FC151 0 1
(Underfrequency 4)
30819 0x0332 Element Status 80 0 65535 1 FC151 0 1
(Overfrequency 1)
30820 0x0333 Element Status 81 0 65535 1 FC151 0 1
(Overfrequency 2)
30821 0x0334 Element Status 82 0 65535 1 FC151 0 1
(Frequency Rate Of
Change 1)
30825 0x0338 Element Status 86 (Group 0 65535 1 FC151 0 1
1)
30826 0x0339 Element Status 87 (Group 0 65535 1 FC151 0 1
2)
30827 0x033A Element Status 88 (Group 0 65535 1 FC151 0 1
3)
30828 0x033B Element Status 89 (Group 0 65535 1 FC151 0 1
4)
30829 0x033C Element Status 90 (Group 0 65535 1 FC151 0 1
5)
30830 0x033D Element Status 91 (Group 0 65535 1 FC151 0 1
6)
30831 0x033E Element Status 92 (Local 0 65535 1 FC151 0 1
Mode)
30832 0x033F Element Status 93 (Open 0 65535 1 FC151 0 1
Breaker 1)
30835 0x0342 Element Status 96 (Close 0 65535 1 FC151 0 1
Breaker 1)
30838 0x0345 Element Status 99 (Trip 0 65535 1 FC151 0 1
Bus 1)
30839 0x0346 Element Status 100 (Trip 0 65535 1 FC151 0 1
Bus 2)
30840 0x0347 Element Status 101 (Trip 0 65535 1 FC151 0 1
Bus 3)
30841 0x0348 Element Status 102 (Trip 0 65535 1 FC151 0 1
Bus 4)
30842 0x0349 Element Status 103 (Trip 0 65535 1 FC151 0 1
Bus 5)
30843 0x034A Element Status 104 (Trip 0 65535 1 FC151 0 1
Bus 6)
30844 0x034B Element Status 105 0 65535 1 FC151 0 1
(Breaker Fail 1)
30847 0x034E Element Status 108 0 65535 1 FC151 0 1
(Synchrocheck 1)
30849 0x0350 Element Status 110 0 65535 1 FC151 0 1
(Manual Close Blocking)
30850 0x0351 Element Status 111 (VT 0 65535 1 FC151 0 1
Fuse Fail 1)
30852 0x0353 Element Status 113 (Cold 0 65535 1 FC151 0 1
Load Pickup 1)

11-10 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30854 0x0355 Element Status 115 0 65535 1 FC151 0 1
(Undervoltage
Restoration)
30855 0x0356 Element Status 116 (Bus 0 65535 1 FC151 0 1
Transfer)
30856 0x0357 Element Status 117 0 65535 1 FC151 0 1
(AutoReclose 1)
30857 0x0358 Element Status 118 (AR1 0 65535 1 FC151 0 1
Shot Cnt)
30858 0x0359 Element Status 119 (AR1 0 65535 1 FC151 0 1
Shot Cnt Reduction)
30859 0x035A Element Status 120 (AR1 0 65535 1 FC151 0 1
Rate Supervision)
30864 0x035F Element Status 125 0 65535 1 FC151 0 1
(Underfrequency
Restoration)
30865 0x0360 Element Status 126 (BKR1 0 65535 1 FC151 0 1
Status Closed)
30866 0x0361 Element Status 127 (BKR1 0 65535 1 FC151 0 1
Status Opened)
30867 0x0362 Element Status 128 (BKR1 0 65535 1 FC151 0 1
Status Unknown)
30868 0x0363 Element Status 129 (BKR1 0 65535 1 FC151 0 1
Status Disconnected)
30869 0x0364 Element Status 130 (BKR1 0 65535 1 FC151 0 1
52a Contact)
30870 0x0365 Element Status 131 (BKR1 0 65535 1 FC151 0 1
52b Contact)
30883 0x0372 Element Status 144 (Trip 0 65535 1 FC151 0 1
Coil Monitor 1)
30886 0x0375 Element Status 147 (Close 0 65535 1 FC151 0 1
Coil Monitor 1)
30889 0x0378 Element Status 150 0 65535 1 FC151 0 1
(Breaker 1 Arcing Current)
30892 0x037B Element Status 153 0 65535 1 FC151 0 1
(Breaker1 Health)
30895 0x037E Element Status 156 0 65535 1 FC151 0 1
(Breaker1 Arc Health)
30898 0x0381 Element Status 159 0 65535 1 FC151 0 1
(Power Factor 1)
30899 0x0382 Element Status 160 0 65535 1 FC151 0 1
(Power Factor 2)
30900 0x0383 Element Status 161 0 65535 1 FC151 0 1
(Current Demand)
30901 0x0384 Element Status 162 (Real 0 65535 1 FC151 0 1
Power Demand)
30902 0x0385 Element Status 163 0 65535 1 FC151 0 1
(Reactive Power Demand)
30903 0x0386 Element Status 164 0 65535 1 FC151 0 1
(Apparent Power
Demand)
30904 0x0387 Element Status 165 (Fault 0 65535 1 FC151 0 1
Locator)
30941 0x03AC Element Status 202 (Pulse 0 65535 1 FC151 0 1
Out)
30942 0x03AD Element Status 203 0 65535 1 FC151 0 1
(Digital Counter 1)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-11


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30943 0x03AE Element Status 204 0 65535 1 FC151 0 1
(Digital Counter 2)
30944 0x03AF Element Status 205 0 65535 1 FC151 0 1
(Digital Counter 3)
30945 0x03B0 Element Status 206 0 65535 1 FC151 0 1
(Digital Counter 4)
30946 0x03B1 Element Status 207 0 65535 1 FC151 0 1
(Digital Counter 5)
30947 0x03B2 Element Status 208 0 65535 1 FC151 0 1
(Digital Counter 6)
30948 0x03B3 Element Status 209 0 65535 1 FC151 0 1
(Digital Counter 7)
30949 0x03B4 Element Status 210 0 65535 1 FC151 0 1
(Digital Counter 8)
30950 0x03B5 Element Status 211 0 65535 1 FC151 0 1
(Digital Counter 9)
30951 0x03B6 Element Status 212 0 65535 1 FC151 0 1
(Digital Counter 10)
30952 0x03B7 Element Status 213 0 65535 1 FC151 0 1
(Digital Counter 11)
30953 0x03B8 Element Status 214 0 65535 1 FC151 0 1
(Digital Counter 12)
30954 0x03B9 Element Status 215 0 65535 1 FC151 0 1
(Digital Counter 13)
30955 0x03BA Element Status 216 0 65535 1 FC151 0 1
(Digital Counter 14)
30956 0x03BB Element Status 217 0 65535 1 FC151 0 1
(Digital Counter 15)
30957 0x03BC Element Status 218 0 65535 1 FC151 0 1
(Digital Counter 16)
30958 0x03BD Element Status 219 (NV 0 65535 1 FC151 0 1
Latch 1)
30959 0x03BE Element Status 220 (NV 0 65535 1 FC151 0 1
Latch 2)
30960 0x03BF Element Status 221 (NV 0 65535 1 FC151 0 1
Latch 3)
30961 0x03C0 Element Status 222 (NV 0 65535 1 FC151 0 1
Latch 4)
30962 0x03C1 Element Status 223 (NV 0 65535 1 FC151 0 1
Latch 5)
30963 0x03C2 Element Status 224 (NV 0 65535 1 FC151 0 1
Latch 6)
30964 0x03C3 Element Status 225 (NV 0 65535 1 FC151 0 1
Latch 7)
30965 0x03C4 Element Status 226 (NV 0 65535 1 FC151 0 1
Latch 8)
30966 0x03C5 Element Status 227 (NV 0 65535 1 FC151 0 1
Latch 9)
30967 0x03C6 Element Status 228 (NV 0 65535 1 FC151 0 1
Latch 10)
30968 0x03C7 Element Status 229 (NV 0 65535 1 FC151 0 1
Latch 11)
30969 0x03C8 Element Status 230 (NV 0 65535 1 FC151 0 1
Latch 12)
30970 0x03C9 Element Status 231 (NV 0 65535 1 FC151 0 1
Latch 13)

11-12 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
30971 0x03CA Element Status 232 (NV 0 65535 1 FC151 0 1
Latch 14)
30972 0x03CB Element Status 233 (NV 0 65535 1 FC151 0 1
Latch 15)
30973 0x03CC Element Status 234 (NV 0 65535 1 FC151 0 1
Latch 16)
30974 0x03CD Element Status 235 0 65535 1 FC151 0 1
(Programmable PB 1)
30975 0x03CE Element Status 236 0 65535 1 FC151 0 1
(Programmable PB 2)
30976 0x03CF Element Status 237 0 65535 1 FC151 0 1
(Programmable PB 3)
30977 0x03D0 Element Status 238 0 65535 1 FC151 0 1
(Active Security Login)
30978 0x03D1 Element Status 239 (Data 0 65535 1 FC151 0 1
Logger)
30979 0x03D2 Element Status 240 0 65535 1 FC151 0 1
(Transfer Initiated)
31252 0x04E3 Active Group 0 0xFFFF 1 FC132 1 1
31253 0x04E4 Last Key Pressed 0 65535 1 FC118 0 1
Current Values 1
31270 0x04F5 J1 Ia 0 0xFFFFFFFF 1 A F13 0 1
31272 0x04F7 J1 Ib 0 0xFFFFFFFF 1 A F13 0 1
31274 0x04F9 J1 Ic 0 0xFFFFFFFF 1 A F13 0 1
31276 0x04FB J1 Ig 0 0xFFFFFFFF 1 A F13 0 1
31278 0x04FD J1 In 0 0xFFFFFFFF 1 A F13 0 1
31280 0x04FF J1 Ia RMS 0 0xFFFFFFFF 1 A F13 0 1
31282 0x0501 J1 Ib RMS 0 0xFFFFFFFF 1 A F13 0 1
31284 0x0503 J1 Ic RMS 0 0xFFFFFFFF 1 A F13 0 1
31286 0x0505 J1 Ig RMS 0 0xFFFFFFFF 1 A F13 0 1
31288 0x0507 J1 In RMS 0 0xFFFFFFFF 1 A F13 0 1
31290 0x0509 J1 Ia Angle -3599 0 1 F21 0 1
31291 0x050A J1 Ib Angle -3599 0 1 F21 0 1
31292 0x050B J1 Ic Angle -3599 0 1 F21 0 1
31293 0x050C J1 Ig Angle -3599 0 1 F21 0 1
31294 0x050D J1 In Angle -3599 0 1 F21 0 1
31295 0x050E J1 I AVG 0 0xFFFFFFFF 1 A F13 0 1
31297 0x0510 J1 I_0 0 0xFFFFFFFF 1 A F13 0 1
31299 0x0512 J1 I_1 0 0xFFFFFFFF 1 A F13 0 1
31301 0x0514 J1 I_2 0 0xFFFFFFFF 1 A F13 0 1
31303 0x0516 J1 I_0 Angle -3599 0 1 F21 0 1
31304 0x0517 J1 I_1 Angle -3599 0 1 F21 0 1
31305 0x0518 J1 I_2 Angle -3599 0 1 F21 0 1
31306 0x0519 J1 Igd 0 0xFFFFFFFF 1 A F13 0 1
31308 0x051B J1 Igd Angle -3599 0 1 F21 0 1
31309 0x051C J1 Load 0 2000 1 % F1 0 1
Current Values 2
31326 0x052D K1 Isg 0 0xFFFFFFFF 1 A F13 0 1
31336 0x0537 K1 Isg RMS 0 0xFFFFFFFF 1 A F13 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-13


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
31343 0x053E K1 Isg Angle -3599 0 1 F21 0 1
Voltages 1
31430 0x0595 J2 Van 0 200000000 1 V F12 0 1
31432 0x0597 J2 Vbn 0 200000000 1 V F12 0 1
31434 0x0599 J2 Vcn 0 200000000 1 V F12 0 1
31436 0x059B J2 Vab 0 200000000 1 V F12 0 1
31438 0x059D J2 Vbc 0 200000000 1 V F12 0 1
31440 0x059F J2 Vca 0 200000000 1 V F12 0 1
31442 0x05A1 J2 Vn 0 200000000 1 V F12 0 1
31444 0x05A3 J2 Vaux 0 200000000 1 V F12 0 1
31446 0x05A5 J2 Van RMS 0 200000000 1 V F12 0 1
31448 0x05A7 J2 Vbn RMS 0 200000000 1 V F12 0 1
31450 0x05A9 J2 Vcn RMS 0 200000000 1 V F12 0 1
31452 0x05AB J2 Vab RMS 0 200000000 1 V F12 0 1
31454 0x05AD J2 Vbc RMS 0 200000000 1 V F12 0 1
31456 0x05AF J2 Vca RMS 0 200000000 1 V F12 0 1
31458 0x05B1 J2 Vn RMS 0 200000000 1 V F12 0 1
31460 0x05B3 J2 Vaux RMS 0 200000000 1 V F12 0 1
31462 0x05B5 J2 Van Angle -3599 0 1 F21 0 1
31463 0x05B6 J2 Vbn Angle -3599 0 1 F21 0 1
31464 0x05B7 J2 Vcn Angle -3599 0 1 F21 0 1
31465 0x05B8 J2 Vab Angle -3599 0 1 F21 0 1
31466 0x05B9 J2 Vbc Angle -3599 0 1 F21 0 1
31467 0x05BA J2 Vca Angle -3599 0 1 F21 0 1
31468 0x05BB J2 Vn Angle -3599 0 1 F21 0 1
31469 0x05BC J2 Vaux Angle -3599 0 1 F21 0 1
31470 0x05BD J2 V AVG L-L 0 200000000 1 V F12 0 1
31472 0x05BF J2 V AVG L-N 0 200000000 1 V F12 0 1
31474 0x05C1 J2 V0 0 200000000 1 V F12 0 1
31476 0x05C3 J2 V1 0 200000000 1 V F12 0 1
31478 0x05C5 J2 V2 0 200000000 1 V F12 0 1
31480 0x05C7 J2 V0 Angle -3599 0 1 F21 0 1
31481 0x05C8 J2 V1 Angle -3599 0 1 F21 0 1
31482 0x05C9 J2 V2 Angle -3599 0 1 F21 0 1
Harmonics 1
31610 0x0649 J1 Phase A THD 0 65535 1 % F1 0 1
31611 0x064A J1 Phase B THD 0 65535 1 % F1 0 1
31612 0x064B J1 Phase C THD 0 65535 1 % F1 0 1
31613 0x064C J1 Phase A 2 0 65535 1 % F1 0 1
31614 0x064D J1 Phase B 2 0 65535 1 % F1 0 1
31615 0x064E J1 Phase C 2 0 65535 1 % F1 0 1
31616 0x064F J1 Phase A 3 0 65535 1 % F1 0 1
31617 0x0650 J1 Phase B 3 0 65535 1 % F1 0 1
31618 0x0651 J1 Phase C 3 0 65535 1 % F1 0 1
31619 0x0652 J1 Phase A 4 0 65535 1 % F1 0 1
31620 0x0653 J1 Phase B 4 0 65535 1 % F1 0 1

11-14 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
31621 0x0654 J1 Phase C 4 0 65535 1 % F1 0 1
31622 0x0655 J1 Phase A 5 0 65535 1 % F1 0 1
31623 0x0656 J1 Phase B 5 0 65535 1 % F1 0 1
31624 0x0657 J1 Phase C 5 0 65535 1 % F1 0 1
31625 0x0658 J1 Phase A 6 0 65535 1 % F1 0 1
31626 0x0659 J1 Phase B 6 0 65535 1 % F1 0 1
31627 0x065A J1 Phase C 6 0 65535 1 % F1 0 1
31628 0x065B J1 Phase A 7 0 65535 1 % F1 0 1
31629 0x065C J1 Phase B 7 0 65535 1 % F1 0 1
31630 0x065D J1 Phase C 7 0 65535 1 % F1 0 1
31631 0x065E J1 Phase A 8 0 65535 1 % F1 0 1
31632 0x065F J1 Phase B 8 0 65535 1 % F1 0 1
31633 0x0660 J1 Phase C 8 0 65535 1 % F1 0 1
31634 0x0661 J1 Phase A 9 0 65535 1 % F1 0 1
31635 0x0662 J1 Phase B 9 0 65535 1 % F1 0 1
31636 0x0663 J1 Phase C 9 0 65535 1 % F1 0 1
31637 0x0664 J1 Phase A 10 0 65535 1 % F1 0 1
31638 0x0665 J1 Phase B 10 0 65535 1 % F1 0 1
31639 0x0666 J1 Phase C 10 0 65535 1 % F1 0 1
31640 0x0667 J1 Phase A 11 0 65535 1 % F1 0 1
31641 0x0668 J1 Phase B 11 0 65535 1 % F1 0 1
31642 0x0669 J1 Phase C 11 0 65535 1 % F1 0 1
31643 0x066A J1 Phase A 12 0 65535 1 % F1 0 1
31644 0x066B J1 Phase B 12 0 65535 1 % F1 0 1
31645 0x066C J1 Phase C 12 0 65535 1 % F1 0 1
31646 0x066D J1 Phase A 13 0 65535 1 % F1 0 1
31647 0x066E J1 Phase B 13 0 65535 1 % F1 0 1
31648 0x066F J1 Phase C 13 0 65535 1 % F1 0 1
31649 0x0670 J1 Phase A 14 0 65535 1 % F1 0 1
31650 0x0671 J1 Phase B 14 0 65535 1 % F1 0 1
31651 0x0672 J1 Phase C 14 0 65535 1 % F1 0 1
31652 0x0673 J1 Phase A 15 0 65535 1 % F1 0 1
31653 0x0674 J1 Phase B 15 0 65535 1 % F1 0 1
31654 0x0675 J1 Phase C 15 0 65535 1 % F1 0 1
31655 0x0676 J1 Phase A 16 0 65535 1 % F1 0 1
31656 0x0677 J1 Phase B 16 0 65535 1 % F1 0 1
31657 0x0678 J1 Phase C 16 0 65535 1 % F1 0 1
31658 0x0679 J1 Phase A 17 0 65535 1 % F1 0 1
31659 0x067A J1 Phase B 17 0 65535 1 % F1 0 1
31660 0x067B J1 Phase C 17 0 65535 1 % F1 0 1
31661 0x067C J1 Phase A 18 0 65535 1 % F1 0 1
31662 0x067D J1 Phase B 18 0 65535 1 % F1 0 1
31663 0x067E J1 Phase C 18 0 65535 1 % F1 0 1
31664 0x067F J1 Phase A 19 0 65535 1 % F1 0 1
31665 0x0680 J1 Phase B 19 0 65535 1 % F1 0 1
31666 0x0681 J1 Phase C 19 0 65535 1 % F1 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-15


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
31667 0x0682 J1 Phase A 20 0 65535 1 % F1 0 1
31668 0x0683 J1 Phase B 20 0 65535 1 % F1 0 1
31669 0x0684 J1 Phase C 20 0 65535 1 % F1 0 1
31670 0x0685 J1 Phase A 21 0 65535 1 % F1 0 1
31671 0x0686 J1 Phase B 21 0 65535 1 % F1 0 1
31672 0x0687 J1 Phase C 21 0 65535 1 % F1 0 1
31673 0x0688 J1 Phase A 22 0 65535 1 % F1 0 1
31674 0x0689 J1 Phase B 22 0 65535 1 % F1 0 1
31675 0x068A J1 Phase C 22 0 65535 1 % F1 0 1
31676 0x068B J1 Phase A 23 0 65535 1 % F1 0 1
31677 0x068C J1 Phase B 23 0 65535 1 % F1 0 1
31678 0x068D J1 Phase C 23 0 65535 1 % F1 0 1
31679 0x068E J1 Phase A 24 0 65535 1 % F1 0 1
31680 0x068F J1 Phase B 24 0 65535 1 % F1 0 1
31681 0x0690 J1 Phase C 24 0 65535 1 % F1 0 1
31682 0x0691 J1 Phase A 25 0 65535 1 % F1 0 1
31683 0x0692 J1 Phase B 25 0 65535 1 % F1 0 1
31684 0x0693 J1 Phase C 25 0 65535 1 % F1 0 1
Harmonics 2
31695 0x069E J2 Phase A THD 0 65535 1 % F1 0 1
31696 0x069F J2 Phase B THD 0 65535 1 % F1 0 1
31697 0x06A0 J2 Phase C THD 0 65535 1 % F1 0 1
31698 0x06A1 J2 Phase A 2 0 65535 1 % F1 0 1
31699 0x06A2 J2 Phase B 2 0 65535 1 % F1 0 1
31700 0x06A3 J2 Phase C 2 0 65535 1 % F1 0 1
31701 0x06A4 J2 Phase A 3 0 65535 1 % F1 0 1
31702 0x06A5 J2 Phase B 3 0 65535 1 % F1 0 1
31703 0x06A6 J2 Phase C 3 0 65535 1 % F1 0 1
31704 0x06A7 J2 Phase A 4 0 65535 1 % F1 0 1
31705 0x06A8 J2 Phase B 4 0 65535 1 % F1 0 1
31706 0x06A9 J2 Phase C 4 0 65535 1 % F1 0 1
31707 0x06AA J2 Phase A 5 0 65535 1 % F1 0 1
31708 0x06AB J2 Phase B 5 0 65535 1 % F1 0 1
31709 0x06AC J2 Phase C 5 0 65535 1 % F1 0 1
31710 0x06AD J2 Phase A 6 0 65535 1 % F1 0 1
31711 0x06AE J2 Phase B 6 0 65535 1 % F1 0 1
31712 0x06AF J2 Phase C 6 0 65535 1 % F1 0 1
31713 0x06B0 J2 Phase A 7 0 65535 1 % F1 0 1
31714 0x06B1 J2 Phase B 7 0 65535 1 % F1 0 1
31715 0x06B2 J2 Phase C 7 0 65535 1 % F1 0 1
31716 0x06B3 J2 Phase A 8 0 65535 1 % F1 0 1
31717 0x06B4 J2 Phase B 8 0 65535 1 % F1 0 1
31718 0x06B5 J2 Phase C 8 0 65535 1 % F1 0 1
31719 0x06B6 J2 Phase A 9 0 65535 1 % F1 0 1
31720 0x06B7 J2 Phase B 9 0 65535 1 % F1 0 1
31721 0x06B8 J2 Phase C 9 0 65535 1 % F1 0 1

11-16 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
31722 0x06B9 J2 Phase A 10 0 65535 1 % F1 0 1
31723 0x06BA J2 Phase B 10 0 65535 1 % F1 0 1
31724 0x06BB J2 Phase C 10 0 65535 1 % F1 0 1
31725 0x06BC J2 Phase A 11 0 65535 1 % F1 0 1
31726 0x06BD J2 Phase B 11 0 65535 1 % F1 0 1
31727 0x06BE J2 Phase C 11 0 65535 1 % F1 0 1
31728 0x06BF J2 Phase A 12 0 65535 1 % F1 0 1
31729 0x06C0 J2 Phase B 12 0 65535 1 % F1 0 1
31730 0x06C1 J2 Phase C 12 0 65535 1 % F1 0 1
31731 0x06C2 J2 Phase A 13 0 65535 1 % F1 0 1
31732 0x06C3 J2 Phase B 13 0 65535 1 % F1 0 1
31733 0x06C4 J2 Phase C 13 0 65535 1 % F1 0 1
31734 0x06C5 J2 Phase A 14 0 65535 1 % F1 0 1
31735 0x06C6 J2 Phase B 14 0 65535 1 % F1 0 1
31736 0x06C7 J2 Phase C 14 0 65535 1 % F1 0 1
31737 0x06C8 J2 Phase A 15 0 65535 1 % F1 0 1
31738 0x06C9 J2 Phase B 15 0 65535 1 % F1 0 1
31739 0x06CA J2 Phase C 15 0 65535 1 % F1 0 1
31740 0x06CB J2 Phase A 16 0 65535 1 % F1 0 1
31741 0x06CC J2 Phase B 16 0 65535 1 % F1 0 1
31742 0x06CD J2 Phase C 16 0 65535 1 % F1 0 1
31743 0x06CE J2 Phase A 17 0 65535 1 % F1 0 1
31744 0x06CF J2 Phase B 17 0 65535 1 % F1 0 1
31745 0x06D0 J2 Phase C 17 0 65535 1 % F1 0 1
31746 0x06D1 J2 Phase A 18 0 65535 1 % F1 0 1
31747 0x06D2 J2 Phase B 18 0 65535 1 % F1 0 1
31748 0x06D3 J2 Phase C 18 0 65535 1 % F1 0 1
31749 0x06D4 J2 Phase A 19 0 65535 1 % F1 0 1
31750 0x06D5 J2 Phase B 19 0 65535 1 % F1 0 1
31751 0x06D6 J2 Phase C 19 0 65535 1 % F1 0 1
31752 0x06D7 J2 Phase A 20 0 65535 1 % F1 0 1
31753 0x06D8 J2 Phase B 20 0 65535 1 % F1 0 1
31754 0x06D9 J2 Phase C 20 0 65535 1 % F1 0 1
31755 0x06DA J2 Phase A 21 0 65535 1 % F1 0 1
31756 0x06DB J2 Phase B 21 0 65535 1 % F1 0 1
31757 0x06DC J2 Phase C 21 0 65535 1 % F1 0 1
31758 0x06DD J2 Phase A 22 0 65535 1 % F1 0 1
31759 0x06DE J2 Phase B 22 0 65535 1 % F1 0 1
31760 0x06DF J2 Phase C 22 0 65535 1 % F1 0 1
31761 0x06E0 J2 Phase A 23 0 65535 1 % F1 0 1
31762 0x06E1 J2 Phase B 23 0 65535 1 % F1 0 1
31763 0x06E2 J2 Phase C 23 0 65535 1 % F1 0 1
31764 0x06E3 J2 Phase A 24 0 65535 1 % F1 0 1
31765 0x06E4 J2 Phase B 24 0 65535 1 % F1 0 1
31766 0x06E5 J2 Phase C 24 0 65535 1 % F1 0 1
31767 0x06E6 J2 Phase A 25 0 65535 1 % F1 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-17


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
31768 0x06E7 J2 Phase B 25 0 65535 1 % F1 0 1
31769 0x06E8 J2 Phase C 25 0 65535 1 % F1 0 1
Synchrocheck 1 Metering
31960 0x07A7 Bus Volts Magnitude 0 200000000 1 V F12 0 1
31962 0x07A9 Bus Volts Angle -3599 0 1 F21 0 1
31963 0x07AA Bus Volts Frequency 0 120000 1 Hz F13 0 1
31965 0x07AC Line Volts Magnitude 0 200000000 1 V F12 0 1
31967 0x07AE Line Volts Angle -3599 0 1 F21 0 1
31968 0x07AF Line Volts Frequency 0 120000 1 Hz F13 10 1
31970 0x07B1 Voltage Difference 0 0xFFFFFFFF 1 V F12 0 1
31972 0x07B3 Angle Difference 0 180 1 F1 0 1
31973 0x07B4 Frequency Difference 0 120000 1 Hz F13 10 1
Power Values 1
32020 0x07E3 Pwr1 Real -2147483648 2147483647 1 kW F31 0 1
32022 0x07E5 Pwr1 Reactive -2147483648 2147483647 1 kvar F31 0 1
32024 0x07E7 Pwr1 Apparent -2147483648 2147483647 1 kVA F31 0 1
32026 0x07E9 Pwr1 Ph A Real -2147483648 2147483647 1 kW F31 0 1
32028 0x07EB Pwr1 Ph B Real -2147483648 2147483647 1 kW F31 0 1
32030 0x07ED Pwr1 Ph C Real -2147483648 2147483647 1 kW F31 0 1
32032 0x07EF Pwr1 Ph A Reactive -2147483648 2147483647 1 kvar F31 0 1
32034 0x07F1 Pwr1 Ph B Reactive -2147483648 2147483647 1 kvar F31 0 1
32036 0x07F3 Pwr1 Ph C Reactive -2147483648 2147483647 1 kvar F31 0 1
32038 0x07F5 Pwr1 Ph A Apparent -2147483648 2147483647 1 kVA F31 0 1
32040 0x07F7 Pwr1 Ph B Apparent -2147483648 2147483647 1 kVA F31 0 1
32042 0x07F9 Pwr1 Ph C Apparent -2147483648 2147483647 1 kVA F31 0 1
32044 0x07FB Pwr1 PF -99 100 1 F22 0 1
32045 0x07FC Pwr1 Ph A PF -99 100 1 F22 0 1
32046 0x07FD Pwr1 Ph B PF -99 100 1 F22 0 1
32047 0x07FE Pwr1 Ph C PF -99 100 1 F22 0 1
Energy Values 1
32110 0x083D Reset Energy D/T 0 0xFFFFFFFF 1 F50 0 1
32112 0x083F Reset Energy Time (us) 0 999999 1 us F51 0 1
32114 0x0841 Pwr1 Pos WattHours -2147483648 2147483647 1 MWh F33 0 1
32116 0x0843 Pwr1 Pos WattHours Cost 0 0xFFFFFFFF 1 $ F12 0 1
32118 0x0845 Pwr1 Neg WattHours -2147483648 2147483647 1 MWh F33 0 1
32120 0x0847 Pwr1 Neg WattHours 0 0xFFFFFFFF 1 $ F12 0 1
Cost
32122 0x0849 Pwr1 Pos VarHours -2147483648 2147483647 1 Mvarh F33 0 1
32124 0x084B Pwr1 Neg VarHours -2147483648 2147483647 1 Mvarh F33 0 1
Current Demand Values 1
32180 0x0883 J1 Reset Demand Date/ 0 0xFFFFFFFF 1 F50 0 1
Time
32182 0x0885 J1 Reset Demand Time 0 999999 1 us F51 0 1
(us)
32184 0x0887 J1 Ph A Demand 0 0xFFFFFFFF 1 A F13 0 1
32186 0x0889 J1 Ph B Demand 0 0xFFFFFFFF 1 A F13 0 1
32188 0x088B J1 Ph C Demand 0 0xFFFFFFFF 1 A F13 0 1

11-18 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
32190 0x088D J1 Max Ph A Demand 0 0xFFFFFFFF 1 A F13 0 1
32192 0x088F J1 Max Ph B Demand 0 0xFFFFFFFF 1 A F13 0 1
32194 0x0891 J1 Max Ph C Demand 0 0xFFFFFFFF 1 A F13 0 1
32196 0x0893 J1 Date/Time Ph A 0 0xFFFFFFFF 1 F50 0 1
Demand
32198 0x0895 J1 Date/Time Ph B 0 0xFFFFFFFF 1 F50 0 1
Demand
32200 0x0897 J1 Date/Time Ph C 0 0xFFFFFFFF 1 F50 0 1
Demand
32202 0x0899 J1 Ph A Demand Time (us) 0 999999 1 us F51 0 1
32204 0x089B J1 Ph B Demand Time (us) 0 999999 1 us F51 0 1
32206 0x089D J1 Ph C Demand Time (us) 0 999999 1 us F51 0 1
Power Demand Values 1
32310 0x0905 Pwr1 Reset Dmd Date/ 0 0xFFFFFFFF 1 F50 0 1
Time
32312 0x0907 Pwr1 Reset Dmd Time (us) 0 999999 1 us F51 0 1
32314 0x0909 Pwr1 Real Dmd -2147483648 2147483647 1 kW F31 0 1
32316 0x090B Pwr1 Max Real Dmd -2147483648 2147483647 1 kW F31 0 1
32318 0x090D Pwr1 Date/Time Real 0 0xFFFFFFFF 1 F50 0 1
Dmd
32320 0x090F Pwr1 Real Dmd Time (us) 0 999999 1 us F51 0 1
32322 0x0911 Pwr1 Reactive Dmd -2147483648 2147483647 1 kvar F31 0 1
32324 0x0913 Pwr1 Max Reactive Dmd -2147483648 2147483647 1 kvar F31 0 1
32326 0x0915 Pwr1 D/T Reactive Dmd 0 0xFFFFFFFF 1 F50 0 1
32328 0x0917 Pwr1 Reactive Dmd 0 999999 1 us F51 0 1
Time(us)
32330 0x0919 Pwr1 Apparent Dmd -2147483648 2147483647 1 kVA F31 0 1
32332 0x091B Pwr1 Max Apparent Dmd -2147483648 2147483647 1 kVA F31 0 1
32334 0x091D Pwr1 D/T Apparent 0 0xFFFFFFFF 1 F50 0 1
Demand
32336 0x091F Pwr1 Apparent Dmd 0 999999 1 us F51 0 1
Time(us)
AutoReclose 1 Status
32580 0x0A13 Shot Number In Effect 0 65535 1 shots F0 0 1
32581 0x0A14 Shots Remaining 0 65535 1 shots F0 0 1
32582 0x0A15 Shot Rate Per Hour 0 65535 1 sh/hr F0 0 1
32583 0x0A16 Total Shot Count 0 65535 1 shots F0 0 1
32584 0x0A17 Shot Cnt Last Rst D/T 0 0xFFFFFFFF 1 F50 0 1
32586 0x0A19 Shot Cnt Last Rst (us) 0 999999 1 us F51 0 1
Fault Location
32670 0x0A6D Fault Date/Time 0 0xFFFFFFFF 1 F50 0 1
32672 0x0A6F Fault Time (us) 0 999999 1 us F51 0 1
32674 0x0A71 Type 0 65535 1 F0 0 1
32676 0x0A73 Distance 0 65535 1 F0 0 1
Fault Report Summary
32690 0x0A81 Number of Reports 0 65535 1 F0 0 1
32691 0x0A82 Fault Report 1 Time 0 0xFFFFFFFF 1 F50 0 1
32693 0x0A84 Fault Report 2 Time 0 0xFFFFFFFF 1 F50 0 1
32695 0x0A86 Fault Report 3 Time 0 0xFFFFFFFF 1 F50 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-19


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
32697 0x0A88 Fault Report 4 Time 0 0xFFFFFFFF 1 F50 0 1
32699 0x0A8A Fault Report 5 Time 0 0xFFFFFFFF 1 F50 0 1
32701 0x0A8C Fault Report 6 Time 0 0xFFFFFFFF 1 F50 0 1
32703 0x0A8E Fault Report 7 Time 0 0xFFFFFFFF 1 F50 0 1
32705 0x0A90 Fault Report 8 Time 0 0xFFFFFFFF 1 F50 0 1
32707 0x0A92 Fault Report 9 Time 0 0xFFFFFFFF 1 F50 0 1
32709 0x0A94 Fault Report 10 Time 0 0xFFFFFFFF 1 F50 0 1
32711 0x0A96 Fault Report 11 Time 0 0xFFFFFFFF 1 F50 0 1
32713 0x0A98 Fault Report 12 Time 0 0xFFFFFFFF 1 F50 0 1
32715 0x0A9A Fault Report 13 Time 0 0xFFFFFFFF 1 F50 0 1
32717 0x0A9C Fault Report 14 Time 0 0xFFFFFFFF 1 F50 0 1
32719 0x0A9E Fault Report 15 Time 0 0xFFFFFFFF 1 F50 0 1
Fault Report
32740 0x0AB3 Date/Time 0 0xFFFFFFFF 1 F50 0 1
32742 0x0AB5 Time (us) 0 999999 1 us F51 0 1
32744 0x0AB7 Type of Fault 0 10 1 FC270 0 1
32745 0x0AB8 Distance to Fault 1 9999 1 F2 1 1
32746 0x0AB9 Distance to Fault 1 9999 1 F2 1 1
Transient Recorder Status
32760 0x0AC7 Total Transient Records 0 16 1 F0 0 1
Transient Recorder Date/Time
32780 0x0ADB Oscill. Record 1 0 0xFFFFFFFF 1 F50 0 1
32782 0x0ADD Oscill. Record 1 (us) 0 999999 1 us F51 0 1
32786 0x0AE1 Oscill. Record 2 0 0xFFFFFFFF 1 F50 0 1
32788 0x0AE3 Oscill. Record 2 (us) 0 999999 1 us F51 0 1
32792 0x0AE7 Oscill. Record 3 0 0xFFFFFFFF 1 F50 0 1
32794 0x0AE9 Oscill. Record 3 (us) 0 999999 1 us F51 0 1
32798 0x0AED Oscill. Record 4 0 0xFFFFFFFF 1 F50 0 1
32800 0x0AEF Oscill. Record 4 (us) 0 999999 1 us F51 0 1
32804 0x0AF3 Oscill. Record 5 0 0xFFFFFFFF 1 F50 0 1
32806 0x0AF5 Oscill. Record 5 (us) 0 999999 1 us F51 0 1
32810 0x0AF9 Oscill. Record 6 0 0xFFFFFFFF 1 F50 0 1
32812 0x0AFB Oscill. Record 6 (us) 0 999999 1 us F51 0 1
32816 0x0AFF Oscill. Record 7 0 0xFFFFFFFF 1 F50 0 1
32818 0x0B01 Oscill. Record 7 (us) 0 999999 1 us F51 0 1
32822 0x0B05 Oscill. Record 8 0 0xFFFFFFFF 1 F50 0 1
32824 0x0B07 Oscill. Record 8 (us) 0 999999 1 us F51 0 1
32828 0x0B0B Oscill. Record 9 0 0xFFFFFFFF 1 F50 0 1
32830 0x0B0D Oscill. Record 9 (us) 0 999999 1 us F51 0 1
32834 0x0B11 Oscill. Record 10 0 0xFFFFFFFF 1 F50 0 1
32836 0x0B13 Oscill. Record 10 (us) 0 999999 1 us F51 0 1
32840 0x0B17 Oscill. Record 11 0 0xFFFFFFFF 1 F50 0 1
32842 0x0B19 Oscill. Record 11 (us) 0 999999 1 us F51 0 1
32846 0x0B1D Oscill. Record 12 0 0xFFFFFFFF 1 F50 0 1
32848 0x0B1F Oscill. Record 12 (us) 0 999999 1 us F51 0 1
32852 0x0B23 Oscill. Record 13 0 0xFFFFFFFF 1 F50 0 1

11-20 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
32854 0x0B25 Oscill. Record 13 (us) 0 999999 1 us F51 0 1
32858 0x0B29 Oscill. Record 14 0 0xFFFFFFFF 1 F50 0 1
32860 0x0B2B Oscill. Record 14 (us) 0 999999 1 us F51 0 1
32864 0x0B2F Oscill. Record 15 0 0xFFFFFFFF 1 F50 0 1
32866 0x0B31 Oscill. Record 15 (us) 0 999999 1 us F51 0 1
32870 0x0B35 Oscill. Record 16 0 0xFFFFFFFF 1 F50 0 1
32872 0x0B37 Oscill. Record 16 (us) 0 999999 1 us F51 0 1
Breaker Health Values
32900 0x0B53 Total Breaker Trips 0 100000 1 F10 0 1
32902 0x0B55 Trips Since Last Reset 0 100000 1 F10 0 1
32904 0x0B57 Alarm Counter 0 100 1 F0 0 1
32905 0x0B58 Last Trip Time 0 4294967295 1 ms F10 0 1
32907 0x0B5A Avg. of 5 Trip Time 0 4294967295 1 ms F10 0 1
32909 0x0B5C Avg. of Trip Time 0 4294967295 1 ms F10 0 1
32911 0x0B5E Last Close Time 0 4294967295 1 ms F10 0 1
32913 0x0B60 Avg. of 5 Close Time 0 4294967295 1 ms F10 0 1
32915 0x0B62 Avg. of Close Time 0 4294967295 1 ms F10 0 1
32917 0x0B64 Last PH A Arc Time 0 4294967295 1 ms F10 0 1
32919 0x0B66 Avg. of 5 PH A Arc Time 0 4294967295 1 ms F10 0 1
32921 0x0B68 Avg. of PH A Arc Time 0 4294967295 1 ms F10 0 1
32923 0x0B6A Last PH B Arc Time 0 4294967295 1 ms F10 0 1
32925 0x0B6C Avg. of 5 PH B Arc Time 0 4294967295 1 ms F10 0 1
32927 0x0B6E Avg. of PH B Arc Time 0 4294967295 1 ms F10 0 1
32929 0x0B70 Last PH C Arc Time 0 4294967295 1 ms F10 0 1
32931 0x0B72 Avg. of 5 PH C Arc Time 0 4294967295 1 ms F10 0 1
32933 0x0B74 Avg. of PH C Arc Time 0 4294967295 1 ms F10 0 1
32935 0x0B76 Last Spring Charge Time 0 6000000 1 s F13 0 1
32937 0x0B78 Avg. of 5 Charge Time 0 6000000 1 s F13 0 1
32939 0x0B7A Avg. of Charge Time 0 6000000 1 s F13 0 1
32941 0x0B7C Last PH A Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
32943 0x0B7E Avg. of 5 PH A Arc Ener 0 4294967295 1 kA2-cyc F12 0 1
32945 0x0B80 Avg. of PH A Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
32947 0x0B82 Last PH B Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
32949 0x0B84 Avg. of 5 PH B Arc Ener 0 4294967295 1 kA2-cyc F12 0 1
32951 0x0B86 Avg. of PH B Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
32953 0x0B88 Last PH C Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
32955 0x0B8A Avg. of 5 PH C Arc Ener 0 4294967295 1 kA2-cyc F12 0 1
32957 0x0B8C Avg. of PH C Arc Energy 0 4294967295 1 kA2-cyc F12 0 1
Breaker 1 Arcing Current
33100 0x0C1B Arcing Current Phase A 0 4294967295 1 kA2-cyc F12 0 1
33102 0x0C1D Arcing Current Phase B 0 4294967295 1 kA2-cyc F12 0 1
33104 0x0C1F Arcing Current Phase C 0 4294967295 1 kA2-cyc F12 0 1
33106 0x0C21 Total Arcing Current 0 4294967295 1 kA2-cyc F12 0 1
Digital Counter Status 1
33140 0x0C43 Counter 1 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-21


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
33142 0x0C45 Counter 1 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33144 0x0C47 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33146 0x0C49 Counter 1 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 2
33152 0x0C4F Counter 2 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33154 0x0C51 Counter 2 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33156 0x0C53 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33158 0x0C55 Counter 2 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 3
33164 0x0C5B Counter 3 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33166 0x0C5D Counter 3 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33168 0x0C5F Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33170 0x0C61 Counter 3 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 4
33176 0x0C67 Counter 4 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33178 0x0C69 Counter 4 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33180 0x0C6B Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33182 0x0C6D Counter 4 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 5
33188 0x0C73 Counter 5 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33190 0x0C75 Counter 5 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33192 0x0C77 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33194 0x0C79 Counter 5 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 6
33200 0x0C7F Counter 6 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33202 0x0C81 Counter 6 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33204 0x0C83 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33206 0x0C85 Counter 6 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 7
33212 0x0C8B Counter 7 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units

11-22 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
33214 0x0C8D Counter 7 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33216 0x0C8F Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33218 0x0C91 Counter 7 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 8
33224 0x0C97 Counter 8 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33226 0x0C99 Counter 8 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33228 0x0C9B Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33230 0x0C9D Counter 8 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 9
33236 0x0CA3 Counter 9 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33238 0x0CA5 Counter 9 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33240 0x0CA7 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33242 0x0CA9 Counter 9 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 10
33248 0x0CAF Counter 10 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33250 0x0CB1 Counter 10 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33252 0x0CB3 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33254 0x0CB5 Counter 10 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 11
33260 0x0CBB Counter 11 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33262 0x0CBD Counter 11 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33264 0x0CBF Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33266 0x0CC1 Counter 11 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 12
33272 0x0CC7 Counter 12 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33274 0x0CC9 Counter 12 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33276 0x0CCB Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33278 0x0CCD Counter 12 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 13
33284 0x0CD3 Counter 13 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-23


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
33286 0x0CD5 Counter 13 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33288 0x0CD7 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33290 0x0CD9 Counter 13 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 14
33296 0x0CDF Counter 14 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33298 0x0CE1 Counter 14 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33300 0x0CE3 Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33302 0x0CE5 Counter 14 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 15
33308 0x0CEB Counter 15 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33310 0x0CED Counter 15 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33312 0x0CEF Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33314 0x0CF1 Counter 15 us - Frozen 0 999999 1 us F51 0 1
Digital Counter Status 16
33320 0x0CF7 Counter 16 Accumulated -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33322 0x0CF9 Counter 16 Frozen -2147483648 2147483647 1 User- F30 0 1
Programma
ble Units
33324 0x0CFB Date/Time - Frozen 0 0xFFFFFFFF 1 F50 0 1
33326 0x0CFD Counter 16 us - Frozen 0 999999 1 us F51 0 1
Breaker 1 Status
33370 0x0D29 Breaker State 0 4 1 FC264 0 1
33371 0x0D2A Trip Coil 0 2 1 FC289 0 1
33372 0x0D2B Close Coil 0 2 1 FC289 0 1
Thermal Capacity
33430 0x0D65 Phase A Thermal Cap 0 1500 1 % F1 0 1
33431 0x0D66 Phase B Thermal Cap 0 1500 1 % F1 0 1
33432 0x0D67 Phase C Thermal Cap 0 1500 1 % F1 0 1
Directional Power
33450 0x0D79 Directional Power 1 -2147483648 2147483647 1 kW F31 0 1
33452 0x0D7B Directional Power 2 -2147483648 2147483647 1 kW F31 0 1
Wattmetric Ground Fault
33460 0x0D83 Wattmetric Ground Fault -2147483648 2147483647 1 W F32 0 1
Communications Status
33470 0x0D8D 61850 Status 0 0xFFFF 1 FC228 0 1
33471 0x0D8E Remote GOOSE Status 1 0 0xFFFFFFFF 1 FC323 0 1
33473 0x0D90 Remote GOOSE Status 2 0 0xFFFFFFFF 1 FC323 0 1
33475 0x0D92 Rem GOOSE Hdr Status 1 0 0xFFFFFFFF 1 FC323 0 1
33477 0x0D94 Rem GOOSE Hdr Status 2 0 0xFFFFFFFF 1 FC323 0 1

11-24 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
33479 0x0D96 SNTP Status 0 65535 1 F0 0 1
J Module Frequency
33540 0x0DD3 J1-CT Frequency 0 120000 1 Hz F13 0 1
33542 0x0DD5 J1-CT Frq Rate of Chge -12000 12000 1 Hz/sec F22 0 1
33543 0x0DD6 J2-3VT Frequency 0 120000 1 Hz F13 0 1
33545 0x0DD8 J2-3VT Frq Rate of Chge -12000 12000 1 Hz/sec F22 0 1
33546 0x0DD9 J2-Vx Frequency 0 120000 1 Hz F13 0 1
33548 0x0DDB J2-Vx Frq Rate of Chge -12000 12000 1 Hz/sec F22 0 1
K Module Frequency
Setpoints
Firmware Build Signature
40001 0x0000 Version 110 110 1 F0 110 1
40002 0x0001 Date 0x0B1807DD 0x0B1807DD 1 F10 0x0B1807D 1
D
40004 0x0003 Time 0x12032E00 0x12032E00 1 F10 0x12032E0 1
0
40006 0x0005 SPChangeDateTime 0 0xFFFFFFFF 1 F50 0 1
40008 0x0007 SPChangeuSeconds 0 999999 1 us F51 0 1
Modbus Commands
40129 0x0080 Command Address 0 65535 1 F1 0 1
40130 0x0081 Command Function 0 65535 1 F1 0 1
40131 0x0082 Command Data 1 0 65535 1 F1 0 1
40132 0x0083 Command Data 2 0 65535 1 F1 0 1
40133 0x0084 Command Data 3 0 65535 1 F1 0 1
40134 0x0085 Command Data 4 0 65535 1 F1 0 1
40135 0x0086 Command Data 5 0 65535 1 F1 0 1
40136 0x0087 Command Data 6 0 65535 1 F1 0 1
40137 0x0088 Command Data 7 0 65535 1 F1 0 1
40138 0x0089 Command Data 8 0 65535 1 F1 0 1
40139 0x008A Command Data 9 0 65535 1 F1 0 1
40140 0x008B Command Data 10 0 65535 1 F1 0 1
Targets Selection
40230 0x00E5 Select Target Index 1 256 1 F0 1 1
Clock
40241 0x00F0 Time 0 0x173B3B63 1 F54 0 1
40243 0x00F2 Date 0x010107D8 0x0C1F082E 1 F53 16844760 1
40245 0x00F4 RTC Time 0 0xFFFFFFFF 1 s F52 0 1
40247 0x00F6 Local Time Offset from -240 240 5 hrs F21 0 1
UTC
40248 0x00F7 Real Time Clock Events 0 1 1 FC126 1 1
40249 0x00F8 Daylight Savings Time 0 1 1 FC126 0 1
40250 0x00F9 DST Start Month 0 12 1 FC169 0 1
40251 0x00FA DST Start Week 0 5 1 FC170 0 1
40252 0x00FB DST Start Weekday 0 7 1 FC171 0 1
40253 0x00FC DST Start Hour 0 23 1 F0 2 1
40254 0x00FD DST End Month 0 12 1 FC169 0 1
40255 0x00FE DST End Week 0 5 1 FC170 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-25


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
40256 0x00FF DST End Weekday 0 7 1 FC171 0 1
40257 0x0100 DST End Hour 0 23 1 F0 2 1
40258 0x0101 IRIG-B 0 1 1 FC126 0 1
User Map Setpoints
40524 0x020B User Map Address 1 30001 49999 1 F0 30712 1
40525 0x020C User Map Address 2 30001 49999 1 F0 30713 1
40526 0x020D User Map Address 3 30001 49999 1 F0 30708 1
40527 0x020E User Map Address 4 30001 49999 1 F0 30709 1
40528 0x020F User Map Address 5 30001 49999 1 F0 30700 1
40529 0x0210 User Map Address 6 30001 49999 1 F0 30701 1
40530 0x0211 User Map Address 7 30001 49999 1 F0 30706 1
40531 0x0212 User Map Address 8 30001 49999 1 F0 30707 1
40532 0x0213 User Map Address 9 30001 49999 1 F0 30714 1
40533 0x0214 User Map Address 10 30001 49999 1 F0 30715 1
40534 0x0215 User Map Address 11 30001 49999 1 F0 30718 1
40535 0x0216 User Map Address 12 30001 49999 1 F0 30719 1
40536 0x0217 User Map Address 13 30001 49999 1 F0 30728 1
40537 0x0218 User Map Address 14 30001 49999 1 F0 30729 1
40538 0x0219 User Map Address 15 30001 49999 1 F0 30736 1
40539 0x021A User Map Address 16 30001 49999 1 F0 30737 1
40540 0x021B User Map Address 17 30001 49999 1 F0 31270 1
40541 0x021C User Map Address 18 30001 49999 1 F0 31271 1
40542 0x021D User Map Address 19 30001 49999 1 F0 31272 1
40543 0x021E User Map Address 20 30001 49999 1 F0 31273 1
40544 0x021F User Map Address 21 30001 49999 1 F0 31274 1
40545 0x0220 User Map Address 22 30001 49999 1 F0 31275 1
40546 0x0221 User Map Address 23 30001 49999 1 F0 31278 1
40547 0x0222 User Map Address 24 30001 49999 1 F0 31279 1
40548 0x0223 User Map Address 25 30001 49999 1 F0 31295 1
40549 0x0224 User Map Address 26 30001 49999 1 F0 31296 1
40550 0x0225 User Map Address 27 30001 49999 1 F0 31276 1
40551 0x0226 User Map Address 28 30001 49999 1 F0 31277 1
40552 0x0227 User Map Address 29 30001 49999 1 F0 31446 1
40553 0x0228 User Map Address 30 30001 49999 1 F0 31447 1
40554 0x0229 User Map Address 31 30001 49999 1 F0 31448 1
40555 0x022A User Map Address 32 30001 49999 1 F0 31449 1
40556 0x022B User Map Address 33 30001 49999 1 F0 31450 1
40557 0x022C User Map Address 34 30001 49999 1 F0 31451 1
40558 0x022D User Map Address 35 30001 49999 1 F0 31452 1
40559 0x022E User Map Address 36 30001 49999 1 F0 31453 1
40560 0x022F User Map Address 37 30001 49999 1 F0 31454 1
40561 0x0230 User Map Address 38 30001 49999 1 F0 31455 1
40562 0x0231 User Map Address 39 30001 49999 1 F0 31456 1
40563 0x0232 User Map Address 40 30001 49999 1 F0 31457 1
40564 0x0233 User Map Address 41 30001 49999 1 F0 31470 1
40565 0x0234 User Map Address 42 30001 49999 1 F0 31471 1

11-26 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
40566 0x0235 User Map Address 43 30001 49999 1 F0 31472 1
40567 0x0236 User Map Address 44 30001 49999 1 F0 31473 1
40568 0x0237 User Map Address 45 30001 49999 1 F0 32020 1
40569 0x0238 User Map Address 46 30001 49999 1 F0 32021 1
40570 0x0239 User Map Address 47 30001 49999 1 F0 32024 1
40571 0x023A User Map Address 48 30001 49999 1 F0 32025 1
40572 0x023B User Map Address 49 30001 49999 1 F0 32044 1
40573 0x023C User Map Address 50 30001 49999 1 F0 33540 1
40574 0x023D User Map Address 51 30001 49999 1 F0 33541 1
40575 0x023E User Map Address 52 30001 49999 1 F0 31965 1
40576 0x023F User Map Address 53 30001 49999 1 F0 31966 1
40577 0x0240 User Map Address 54 30001 49999 1 F0 31967 1
40578 0x0241 User Map Address 55 30001 49999 1 F0 31968 1
40579 0x0242 User Map Address 56 30001 49999 1 F0 31969 1
40580 0x0243 User Map Address 57 30001 49999 1 F0 32114 1
40581 0x0244 User Map Address 58 30001 49999 1 F0 32115 1
40582 0x0245 User Map Address 59 30001 49999 1 F0 32026 1
40583 0x0246 User Map Address 60 30001 49999 1 F0 32027 1
40584 0x0247 User Map Address 61 30001 49999 1 F0 32038 1
40585 0x0248 User Map Address 62 30001 49999 1 F0 32039 1
40586 0x0249 User Map Address 63 30001 49999 1 F0 32045 1
40587 0x024A User Map Address 64 30001 49999 1 F0 32028 1
40588 0x024B User Map Address 65 30001 49999 1 F0 32029 1
40589 0x024C User Map Address 66 30001 49999 1 F0 32040 1
40590 0x024D User Map Address 67 30001 49999 1 F0 32041 1
40591 0x024E User Map Address 68 30001 49999 1 F0 32046 1
40592 0x024F User Map Address 69 30001 49999 1 F0 32030 1
40593 0x0250 User Map Address 70 30001 49999 1 F0 32031 1
40594 0x0251 User Map Address 71 30001 49999 1 F0 32042 1
40595 0x0252 User Map Address 72 30001 49999 1 F0 32043 1
40596 0x0253 User Map Address 73 30001 49999 1 F0 32047 1
40597 0x0254 User Map Address 74 30001 49999 1 F0 32022 1
40598 0x0255 User Map Address 75 30001 49999 1 F0 32023 1
40599 0x0256 User Map Address 76 30001 49999 1 F0 32032 1
40600 0x0257 User Map Address 77 30001 49999 1 F0 32033 1
40601 0x0258 User Map Address 78 30001 49999 1 F0 32034 1
40602 0x0259 User Map Address 79 30001 49999 1 F0 32035 1
40603 0x025A User Map Address 80 30001 49999 1 F0 32036 1
40604 0x025B User Map Address 81 30001 49999 1 F0 32037 1
40605 0x025C User Map Address 82 30001 49999 1 F0 30001 1
40606 0x025D User Map Address 83 30001 49999 1 F0 30001 1
40607 0x025E User Map Address 84 30001 49999 1 F0 30001 1
40608 0x025F User Map Address 85 30001 49999 1 F0 30001 1
40609 0x0260 User Map Address 86 30001 49999 1 F0 30001 1
40610 0x0261 User Map Address 87 30001 49999 1 F0 30001 1
40611 0x0262 User Map Address 88 30001 49999 1 F0 30001 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-27


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
40612 0x0263 User Map Address 89 30001 49999 1 F0 30001 1
40613 0x0264 User Map Address 90 30001 49999 1 F0 30001 1
40614 0x0265 User Map Address 91 30001 49999 1 F0 30001 1
40615 0x0266 User Map Address 92 30001 49999 1 F0 30001 1
40616 0x0267 User Map Address 93 30001 49999 1 F0 30001 1
40617 0x0268 User Map Address 94 30001 49999 1 F0 30001 1
40618 0x0269 User Map Address 95 30001 49999 1 F0 30001 1
40619 0x026A User Map Address 96 30001 49999 1 F0 30001 1
40620 0x026B User Map Address 97 30001 49999 1 F0 30001 1
40621 0x026C User Map Address 98 30001 49999 1 F0 30001 1
40622 0x026D User Map Address 99 30001 49999 1 F0 30001 1
40623 0x026E User Map Address 100 30001 49999 1 F0 30001 1
40624 0x026F User Map Address 101 30001 49999 1 F0 30001 1
40625 0x0270 User Map Address 102 30001 49999 1 F0 30001 1
40626 0x0271 User Map Address 103 30001 49999 1 F0 30001 1
40627 0x0272 User Map Address 104 30001 49999 1 F0 30001 1
40628 0x0273 User Map Address 105 30001 49999 1 F0 30001 1
40629 0x0274 User Map Address 106 30001 49999 1 F0 30001 1
40630 0x0275 User Map Address 107 30001 49999 1 F0 30001 1
40631 0x0276 User Map Address 108 30001 49999 1 F0 30001 1
40632 0x0277 User Map Address 109 30001 49999 1 F0 30001 1
40633 0x0278 User Map Address 110 30001 49999 1 F0 30001 1
40634 0x0279 User Map Address 111 30001 49999 1 F0 30001 1
40635 0x027A User Map Address 112 30001 49999 1 F0 30001 1
40636 0x027B User Map Address 113 30001 49999 1 F0 30001 1
40637 0x027C User Map Address 114 30001 49999 1 F0 30001 1
40638 0x027D User Map Address 115 30001 49999 1 F0 30001 1
40639 0x027E User Map Address 116 30001 49999 1 F0 30001 1
40640 0x027F User Map Address 117 30001 49999 1 F0 30001 1
40641 0x0280 User Map Address 118 30001 49999 1 F0 30001 1
40642 0x0281 User Map Address 119 30001 49999 1 F0 30001 1
40643 0x0282 User Map Address 120 30001 49999 1 F0 30001 1
40644 0x0283 User Map Address 121 30001 49999 1 F0 30001 1
40645 0x0284 User Map Address 122 30001 49999 1 F0 30001 1
40646 0x0285 User Map Address 123 30001 49999 1 F0 30001 1
40647 0x0286 User Map Address 124 30001 49999 1 F0 30001 1
40648 0x0287 User Map Address 125 30001 49999 1 F0 30001 1
Event Recorder Configuration
40660 0x0293 Enable Events 0 1 1 FC126 1 1
Clear Records
40700 0x02BB All Records 0 1 1 FC126B 0 1
40701 0x02BC Targets 0 1 1 FC126B 0 1
40702 0x02BD Event Records 0 1 1 FC126B 0 1
40703 0x02BE Transient Records 0 1 1 FC126B 0 1
40705 0x02C0 Fault Reports 0 1 1 FC126B 0 1
40706 0x02C1 Max Current Demand 0 1 1 FC126B 0 1

11-28 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
40707 0x02C2 Max Real Power Demand 0 1 1 FC126B 0 1
40708 0x02C3 Max Reactive Power 0 1 1 FC126B 0 1
Demand
40709 0x02C4 Max Apparent Power 0 1 1 FC126B 0 1
Demand
40710 0x02C5 Energy Use Data 0 1 1 FC126B 0 1
40711 0x02C6 Thermal Capacity 0 1 1 FC126B 0 1
40712 0x02C7 Digital Counters 0 1 1 FC126B 0 1
40713 0x02C8 BKR1 Arcing Current 0 1 1 FC126B 0 1
40714 0x02C9 BKR1 Health Data 0 1 1 FC126B 0 1
40720 0x02CF Autoreclose 0 1 1 FC126B 0 1
Modbus Protocol
40730 0x02D9 Modbus Slave Address 1 254 1 F0 254 1
40731 0x02DA Modbus TCP Port Number 1 65535 1 F0 502 1
RS485 Port 1
40750 0x02ED Baud Rate 0 4 1 FC210 4 1
40751 0x02EE Parity 0 2 1 FC211 0 1
40752 0x02EF Port Protocol 0 2 1 FC209 0 1
Ethernet Port 1
40800 0x031F PRT1 IP Address 0 0xFFFFFFFF 1 F70 0xA9FE030 1
3
40802 0x0321 PRT1 Subnet IP Mask 0 0xFFFFFFFF 1 F70 0xFFFFFF00 1
40804 0x0323 PRT1 GWY IP Address 0 0xFFFFFFFF 1 F70 0xA9FE030 1
1
40806 0x0325 PRT4 IP Address 0 0xFFFFFFFF 1 F70 0 1
40808 0x0327 PRT4 Subnet IP Mask 0 0xFFFFFFFF 1 F70 0 1
40810 0x0329 PRT4 GWY IP Address 0 0xFFFFFFFF 1 F70 0 1
40812 0x032B PRT4 Operation 0 2 1 FC219 0 1
40814 0x032D PRT5 IP Address 0 0xFFFFFFFF 1 F70 0 1
40816 0x032F PRT5 Subnet IP Mask 0 0xFFFFFFFF 1 F70 0 1
40818 0x0331 PRT5 GWY IP Address 0 0xFFFFFFFF 1 F70 0 1
WiFi
40840 0x0347 WiFi Enable 0 1 1 FC126 1 1
40841 0x0348 WiFi IP Address 0 0xFFFFFFFF 1 F70 0xC0A8000 1
2
40843 0x034A WiFi Subnet Mask 0 0xFFFFFFFF 1 F70 0xFFFFFF00 1
40845 0x034C WiFi GWY IP Address 0 0xFFFFFFFF 1 F70 0xC0A8000 1
1
40847 0x034E WiFi Security 0 1 1 FC226 1 1
40848 0x034F WiFi SSID 0 65535 1 F60_14 GEMULTILIN 14
40864 0x035F WiFi WPA2 passphrase 0 65535 1 F60_14 Ge1wx9s31 14
23!4
Precision Time Protocol
40920 0x0397 Port 4 PTP Function 0 1 1 FC126 0 1
40921 0x0398 Port 4 Path Delay Adder 0 60000 1 ns F0 0 1
40922 0x0399 Port4 Path Delay -1000 1000 1 ns F20 0 1
Asymetry
40923 0x039A Port 5 PTP Function 0 1 1 FC126 0 1
40924 0x039B Port 5 Path Delay Adder 0 60000 1 ns F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-29


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
40925 0x039C Port5 Path Delay -1000 1000 1 ns F20 0 1
Asymetry
40926 0x039D Strict Power Profile 0 1 1 FC126 1 1
40927 0x039E PTP Domain Number 0 255 1 F0 0 1
40928 0x039F PTP VLAN Priority 0 7 1 F0 4 1
40929 0x03A0 PTP VLAN ID 0 4095 1 F0 0 1
40930 0x03A1 PTP Priority 1 2 1 F0 1 1
SNTP
40950 0x03B5 SNTP Function 0 1 1 FC126 0 1
40951 0x03B6 SNTP Server IP Address 0 0xFFFFFFFF 1 F70 0 1
40953 0x03B8 SNTP UDP Port Number 0 65535 1 F0A 123 1
40954 0x03B9 SNTP Source Port Number 4 5 1 F0 4 1
Resetting
40970 0x03C9 Reset Input 1 0 0xFFFFFFFF 1 FC142 0 1
40972 0x03CB Reset Input 2 0 0xFFFFFFFF 1 FC142 0 1
40974 0x03CD Reset Input 3 0 0xFFFFFFFF 1 FC142 0 1
Installation
40990 0x03DD Device Name 0 65535 1 F60_26 Relay 1 26
41003 0x03EA Device In Service 0 1 1 FC114 0 1
41004 0x03EB Service Command 0 65535 1 F0 0 1
Front Panel Properties
41020 0x03FB Flash Message Time 1 10 1 s F0 5 1
41021 0x03FC Message Timeout 10 900 1 s F0 30 1
41022 0x03FD Screen Saver 0 1 1 FC126A 0 1
Default Screens
41040 0x040F Function 0 1 1 FC126 0 1
41042 0x0411 Display Time 5 900 1 s F0 10 1
41043 0x0412 Default Screen 1 0 56 1 FC290 0 1
41044 0x0413 Default Screen 2 0 56 1 FC290 0 1
41045 0x0414 Default Screen 3 0 56 1 FC290 0 1
Programmable LED 1
41060 0x0423 LED 1 Name 0 65535 1 F60_26 In Service 26
41073 0x0430 LED 1 Color 0 3 1 FC157 2 1
41074 0x0431 LED 1 Trigger 0 0xFFFFFFFF 1 FC142 0x801402 1
41076 0x0433 LED 1 Type 0 1 1 FC199 0 1
Programmable LED 2
41077 0x0434 LED 2 Name 0 65535 1 F60_26 Trip 26
41090 0x0441 LED 2 Color 0 3 1 FC157 1 1
41091 0x0442 LED 2 Trigger 0 0xFFFFFFFF 1 FC142 0x800002 1
41093 0x0444 LED 2 Type 0 1 1 FC199 1 1
Programmable LED 3
41094 0x0445 LED 3 Name 0 65535 1 F60_26 Alarm 26
41107 0x0452 LED 3 Color 0 3 1 FC157 3 1
41108 0x0453 LED 3 Trigger 0 0xFFFFFFFF 1 FC142 0x800202 1
41110 0x0455 LED 3 Type 0 1 1 FC199 0 1
Programmable LED 4

11-30 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41111 0x0456 LED 4 Name 0 65535 1 F60_26 Pickup 26
41124 0x0463 LED 4 Color 0 3 1 FC157 2 1
41125 0x0464 LED 4 Trigger 0 0xFFFFFFFF 1 FC142 0x800A02 1
41127 0x0466 LED 4 Type 0 1 1 FC199 0 1
Programmable LED 5
41128 0x0467 LED 5 Name 0 65535 1 F60_26 Test Mode 26
41141 0x0474 LED 5 Color 0 3 1 FC157 3 1
41142 0x0475 LED 5 Trigger 0 0xFFFFFFFF 1 FC142 0x801602 1
41144 0x0477 LED 5 Type 0 1 1 FC199 0 1
Programmable LED 6
41145 0x0478 LED 6 Name 0 65535 1 F60_26 Message 26
41158 0x0485 LED 6 Color 0 3 1 FC157 3 1
41159 0x0486 LED 6 Trigger 0 0xFFFFFFFF 1 FC142 0x801202 1
41161 0x0488 LED 6 Type 0 1 1 FC199 0 1
Programmable LED 7
41162 0x0489 LED 7 Name 0 65535 1 F60_26 Local Mode 26
41175 0x0496 LED 7 Color 0 3 1 FC157 3 1
41176 0x0497 LED 7 Trigger 0 0xFFFFFFFF 1 FC142 0x80B608 1
41178 0x0499 LED 7 Type 0 1 1 FC199 0 1
Programmable LED 8
41179 0x049A LED 8 Name 0 65535 1 F60_26 BKR Open 26
41192 0x04A7 LED 8 Color 0 3 1 FC157 2 1
41193 0x04A8 LED 8 Trigger 0 0xFFFFFFFF 1 FC142 0x80FC02 1
41195 0x04AA LED 8 Type 0 1 1 FC199 0 1
Programmable LED 9
41196 0x04AB LED 9 Name 0 65535 1 F60_26 BKR Closed 26
41209 0x04B8 LED 9 Color 0 3 1 FC157 2 1
41210 0x04B9 LED 9 Trigger 0 0xFFFFFFFF 1 FC142 0x80FA02 1
41212 0x04BB LED 9 Type 0 1 1 FC199 0 1
Programmable LED 10
41213 0x04BC LED 10 Name 0 65535 1 F60_26 LED 10 26
41226 0x04C9 LED 10 Color 0 3 1 FC157 2 1
41227 0x04CA LED 10 Trigger 0 0xFFFFFFFF 1 FC142 0 1
41229 0x04CC LED 10 Type 0 1 1 FC199 0 1
Programmable LED 11
41230 0x04CD LED 11 Name 0 65535 1 F60_26 LED 11 26
41243 0x04DA LED 11 Color 0 3 1 FC157 2 1
41244 0x04DB LED 11 Trigger 0 0xFFFFFFFF 1 FC142 0 1
41246 0x04DD LED 11 Type 0 1 1 FC199 0 1
Programmable LED 12
41247 0x04DE LED 12 Name 0 65535 1 F60_26 LED 12 26
41260 0x04EB LED 12 Color 0 3 1 FC157 3 1
41261 0x04EC LED 12 Trigger 0 0xFFFFFFFF 1 FC142 0 1
41263 0x04EE LED 12 Type 0 1 1 FC199 0 1
Programmable LED 13
41264 0x04EF LED 13 Name 0 65535 1 F60_26 LED 13 26

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-31


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41277 0x04FC LED 13 Color 0 3 1 FC157 3 1
41278 0x04FD LED 13 Trigger 0 0xFFFFFFFF 1 FC142 0 1
41280 0x04FF LED 13 Type 0 1 1 FC199 0 1
Programmable LED 14
41281 0x0500 LED 14 Name 0 65535 1 F60_26 LED 14 26
41294 0x050D LED 14 Color 0 3 1 FC157 3 1
41295 0x050E LED 14 Trigger 0 0xFFFFFFFF 1 FC142 0 1
41297 0x0510 LED 14 Type 0 1 1 FC199 0 1
Programmable LED 15
41298 0x0511 LED 15 Name 0 65535 1 F60_26 PB 1 26
41311 0x051E LED 15 Color 0 3 1 FC157 3 1
41312 0x051F LED 15 Trigger 0 0xFFFFFFFF 1 FC142 0x81D402 1
41314 0x0521 LED 15 Type 0 1 1 FC199 0 1
Programmable LED 16
41315 0x0522 LED 16 Name 0 65535 1 F60_26 PB 2 26
41328 0x052F LED 16 Color 0 3 1 FC157 3 1
41329 0x0530 LED 16 Trigger 0 0xFFFFFFFF 1 FC142 0x81D602 1
41331 0x0532 LED 16 Type 0 1 1 FC199 0 1
Programmable LED 17
41332 0x0533 LED 17 Name 0 65535 1 F60_26 PB 3 26
41345 0x0540 LED 17 Color 0 3 1 FC157 3 1
41346 0x0541 LED 17 Trigger 0 0xFFFFFFFF 1 FC142 0x81D802 1
41348 0x0543 LED 17 Type 0 1 1 FC199 0 1
Programmable Pushbutton 1
41360 0x054F Function 0 2 1 FC101 1 1
41361 0x0550 ID Text 0 65535 1 F60_26 Open BKR1 26
41374 0x055D ON Text 0 65535 1 F60_26 PB1 On 26
41387 0x056A OFF Text 0 65535 1 F60_26 PB1 Off 26
41400 0x0577 Hold Pressed 0 100 1 s F1 0 1
41401 0x0578 Autoreset 0 1 1 FC126 0 1
41402 0x0579 Autoreset Delay 2 6000 1 s F1 10 1
41403 0x057A Lock 0 0xFFFFFFFF 1 FC142 0 1
41405 0x057C Dropout Time 0 6000 1 s F1 0 1
41406 0x057D Events 0 1 1 FC126 1 1
Programmable Pushbutton 2
41408 0x057F Function 0 2 1 FC101 1 1
41409 0x0580 ID Text 0 65535 1 F60_26 Close BKR1 26
41422 0x058D ON Text 0 65535 1 F60_26 PB2 On 26
41435 0x059A OFF Text 0 65535 1 F60_26 PB2 Off 26
41448 0x05A7 Hold Pressed 0 100 1 s F1 0 1
41449 0x05A8 Autoreset 0 1 1 FC126 0 1
41450 0x05A9 Autoreset Delay 2 6000 1 s F1 10 1
41451 0x05AA Lock 0 0xFFFFFFFF 1 FC142 0 1
41453 0x05AC Dropout Time 0 6000 1 s F1 0 1
41454 0x05AD Events 0 1 1 FC126 1 1
Programmable Pushbutton 3

11-32 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41456 0x05AF Function 0 2 1 FC101 1 1
41457 0x05B0 ID Text 0 65535 1 F60_26 F1 26
41470 0x05BD ON Text 0 65535 1 F60_26 PB3 On 26
41483 0x05CA OFF Text 0 65535 1 F60_26 PB3 Off 26
41496 0x05D7 Hold Pressed 0 100 1 s F1 0 1
41497 0x05D8 Autoreset 0 1 1 FC126 0 1
41498 0x05D9 Autoreset Delay 2 6000 1 s F1 10 1
41499 0x05DA Lock 0 0xFFFFFFFF 1 FC142 0 1
41501 0x05DC Dropout Time 0 6000 1 s F1 0 1
41502 0x05DD Events 0 1 1 FC126 1 1
Fault Report 1
41520 0x05EF Function 0 1 1 FC126 0 1
41521 0x05F0 Pre-Fault Trigger 0 0xFFFFFFFF 1 FC142 0 1
41523 0x05F2 Fault Trigger 0 0xFFFFFFFF 1 FC142 0 1
41525 0x05F4 Analog Channel 1 0 33560 1 FC273 0 1
41526 0x05F5 Analog Channel 2 0 33560 1 FC273 0 1
41527 0x05F6 Analog Channel 3 0 33560 1 FC273 0 1
41528 0x05F7 Analog Channel 4 0 33560 1 FC273 0 1
41529 0x05F8 Analog Channel 5 0 33560 1 FC273 0 1
41530 0x05F9 Analog Channel 6 0 33560 1 FC273 0 1
41531 0x05FA Analog Channel 7 0 33560 1 FC273 0 1
41532 0x05FB Analog Channel 8 0 33560 1 FC273 0 1
41533 0x05FC Analog Channel 9 0 33560 1 FC273 0 1
41534 0x05FD Analog Channel 10 0 33560 1 FC273 0 1
41535 0x05FE Analog Channel 11 0 33560 1 FC273 0 1
41536 0x05FF Analog Channel 12 0 33560 1 FC273 0 1
41537 0x0600 Analog Channel 13 0 33560 1 FC273 0 1
41538 0x0601 Analog Channel 14 0 33560 1 FC273 0 1
41539 0x0602 Analog Channel 15 0 33560 1 FC273 0 1
41540 0x0603 Analog Channel 16 0 33560 1 FC273 0 1
41541 0x0604 Analog Channel 17 0 33560 1 FC273 0 1
41542 0x0605 Analog Channel 18 0 33560 1 FC273 0 1
41543 0x0606 Analog Channel 19 0 33560 1 FC273 0 1
41544 0x0607 Analog Channel 20 0 33560 1 FC273 0 1
41545 0x0608 Analog Channel 21 0 33560 1 FC273 0 1
41546 0x0609 Analog Channel 22 0 33560 1 FC273 0 1
41547 0x060A Analog Channel 23 0 33560 1 FC273 0 1
41548 0x060B Analog Channel 24 0 33560 1 FC273 0 1
41549 0x060C Analog Channel 25 0 33560 1 FC273 0 1
41550 0x060D Analog Channel 26 0 33560 1 FC273 0 1
41551 0x060E Analog Channel 27 0 33560 1 FC273 0 1
41552 0x060F Analog Channel 28 0 33560 1 FC273 0 1
41553 0x0610 Analog Channel 29 0 33560 1 FC273 0 1
41554 0x0611 Analog Channel 30 0 33560 1 FC273 0 1
41555 0x0612 Analog Channel 31 0 33560 1 FC273 0 1
41556 0x0613 Analog Channel 32 0 33560 1 FC273 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-33


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Transient Recorder Setup
41610 0x0649 Number of Records 1 16 1 F0 5 1
41611 0x064A Samples per Cycle 0 4 1 FC182 2 1
41612 0x064B Trigger Mode 0 1 1 FC181 0 1
41613 0x064C Trigger Position 0 100 1 % F0 20 1
41614 0x064D Trigger Source 0 0xFFFFFFFF 1 FC142 0 1
41616 0x064F Trigger on Any Pickup 0 1 1 FC126A 0 1
41617 0x0650 Trigger on Any Operate 0 1 1 FC126A 0 1
41618 0x0651 Trigger on Trip 0 1 1 FC126A 0 1
41619 0x0652 Trigger on Alarm 0 1 1 FC126A 0 1
41620 0x0653 Digital Input 1 0 0xFFFFFFFF 1 FC142 0 1
41622 0x0655 Digital Input 2 0 0xFFFFFFFF 1 FC142 0 1
41624 0x0657 Digital Input 3 0 0xFFFFFFFF 1 FC142 0 1
41626 0x0659 Digital Input 4 0 0xFFFFFFFF 1 FC142 0 1
41628 0x065B Digital Input 5 0 0xFFFFFFFF 1 FC142 0 1
41630 0x065D Digital Input 6 0 0xFFFFFFFF 1 FC142 0 1
41632 0x065F Digital Input 7 0 0xFFFFFFFF 1 FC142 0 1
41634 0x0661 Digital Input 8 0 0xFFFFFFFF 1 FC142 0 1
41636 0x0663 Digital Input 9 0 0xFFFFFFFF 1 FC142 0 1
41638 0x0665 Digital Input 10 0 0xFFFFFFFF 1 FC142 0 1
41640 0x0667 Digital Input 11 0 0xFFFFFFFF 1 FC142 0 1
41642 0x0669 Digital Input 12 0 0xFFFFFFFF 1 FC142 0 1
41644 0x066B Digital Input 13 0 0xFFFFFFFF 1 FC142 0 1
41646 0x066D Digital Input 14 0 0xFFFFFFFF 1 FC142 0 1
41648 0x066F Digital Input 15 0 0xFFFFFFFF 1 FC142 0 1
41650 0x0671 Digital Input 16 0 0xFFFFFFFF 1 FC142 0 1
41652 0x0673 Digital Input 17 0 0xFFFFFFFF 1 FC142 0 1
41654 0x0675 Digital Input 18 0 0xFFFFFFFF 1 FC142 0 1
41656 0x0677 Digital Input 19 0 0xFFFFFFFF 1 FC142 0 1
41658 0x0679 Digital Input 20 0 0xFFFFFFFF 1 FC142 0 1
41660 0x067B Digital Input 21 0 0xFFFFFFFF 1 FC142 0 1
41662 0x067D Digital Input 22 0 0xFFFFFFFF 1 FC142 0 1
41664 0x067F Digital Input 23 0 0xFFFFFFFF 1 FC142 0 1
41666 0x0681 Digital Input 24 0 0xFFFFFFFF 1 FC142 0 1
41668 0x0683 Digital Input 25 0 0xFFFFFFFF 1 FC142 0 1
41670 0x0685 Digital Input 26 0 0xFFFFFFFF 1 FC142 0 1
41672 0x0687 Digital Input 27 0 0xFFFFFFFF 1 FC142 0 1
41674 0x0689 Digital Input 28 0 0xFFFFFFFF 1 FC142 0 1
41676 0x068B Digital Input 29 0 0xFFFFFFFF 1 FC142 0 1
41678 0x068D Digital Input 30 0 0xFFFFFFFF 1 FC142 0 1
41680 0x068F Digital Input 31 0 0xFFFFFFFF 1 FC142 0 1
41682 0x0691 Digital Input 32 0 0xFFFFFFFF 1 FC142 0 1
41684 0x0693 Analog Input 1 0 33560 1 FC273 0 1
41685 0x0694 Analog Input 2 0 33560 1 FC273 0 1
41686 0x0695 Analog Input 3 0 33560 1 FC273 0 1
41687 0x0696 Analog Input 4 0 33560 1 FC273 0 1

11-34 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41688 0x0697 Analog Input 5 0 33560 1 FC273 0 1
41689 0x0698 Analog Input 6 0 33560 1 FC273 0 1
41690 0x0699 Analog Input 7 0 33560 1 FC273 0 1
41691 0x069A Analog Input 8 0 33560 1 FC273 0 1
41692 0x069B Analog Input 9 0 33560 1 FC273 0 1
41693 0x069C Analog Input 10 0 33560 1 FC273 0 1
41694 0x069D Analog Input 11 0 33560 1 FC273 0 1
41695 0x069E Analog Input 12 0 33560 1 FC273 0 1
41696 0x069F Analog Input 13 0 33560 1 FC273 0 1
41697 0x06A0 Analog Input 14 0 33560 1 FC273 0 1
41698 0x06A1 Analog Input 15 0 33560 1 FC273 0 1
41699 0x06A2 Analog Input 16 0 33560 1 FC273 0 1
Timer 1
41710 0x06AD Timer 1 Type 0 2 1 FC141 0 1
41711 0x06AE Timer 1 Pickup Delay 0 60000 1 F0 0 1
41712 0x06AF Timer 1 Dropout Delay 0 60000 1 F0 0 1
Timer 2
41713 0x06B0 Timer 2 Type 0 2 1 FC141 0 1
41714 0x06B1 Timer 2 Pickup Delay 0 60000 1 F0 0 1
41715 0x06B2 Timer 2 Dropout Delay 0 60000 1 F0 0 1
Timer 3
41716 0x06B3 Timer 3 Type 0 2 1 FC141 0 1
41717 0x06B4 Timer 3 Pickup Delay 0 60000 1 F0 0 1
41718 0x06B5 Timer 3 Dropout Delay 0 60000 1 F0 0 1
Timer 4
41719 0x06B6 Timer 4 Type 0 2 1 FC141 0 1
41720 0x06B7 Timer 4 Pickup Delay 0 60000 1 F0 0 1
41721 0x06B8 Timer 4 Dropout Delay 0 60000 1 F0 0 1
Timer 5
41722 0x06B9 Timer 5 Type 0 2 1 FC141 0 1
41723 0x06BA Timer 5 Pickup Delay 0 60000 1 F0 0 1
41724 0x06BB Timer 5 Dropout Delay 0 60000 1 F0 0 1
Timer 6
41725 0x06BC Timer 6 Type 0 2 1 FC141 0 1
41726 0x06BD Timer 6 Pickup Delay 0 60000 1 F0 0 1
41727 0x06BE Timer 6 Dropout Delay 0 60000 1 F0 0 1
Timer 7
41728 0x06BF Timer 7 Type 0 2 1 FC141 0 1
41729 0x06C0 Timer 7 Pickup Delay 0 60000 1 F0 0 1
41730 0x06C1 Timer 7 Dropout Delay 0 60000 1 F0 0 1
Timer 8
41731 0x06C2 Timer 8 Type 0 2 1 FC141 0 1
41732 0x06C3 Timer 8 Pickup Delay 0 60000 1 F0 0 1
41733 0x06C4 Timer 8 Dropout Delay 0 60000 1 F0 0 1
Timer 9
41734 0x06C5 Timer 9 Type 0 2 1 FC141 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-35


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41735 0x06C6 Timer 9 Pickup Delay 0 60000 1 F0 0 1
41736 0x06C7 Timer 9 Dropout Delay 0 60000 1 F0 0 1
Timer 10
41737 0x06C8 Timer 10 Type 0 2 1 FC141 0 1
41738 0x06C9 Timer 10 Pickup Delay 0 60000 1 F0 0 1
41739 0x06CA Timer 10 Dropout Delay 0 60000 1 F0 0 1
Timer 11
41740 0x06CB Timer 11 Type 0 2 1 FC141 0 1
41741 0x06CC Timer 11 Pickup Delay 0 60000 1 F0 0 1
41742 0x06CD Timer 11 Dropout Delay 0 60000 1 F0 0 1
Timer 12
41743 0x06CE Timer 12 Type 0 2 1 FC141 0 1
41744 0x06CF Timer 12 Pickup Delay 0 60000 1 F0 0 1
41745 0x06D0 Timer 12 Dropout Delay 0 60000 1 F0 0 1
Timer 13
41746 0x06D1 Timer 13 Type 0 2 1 FC141 0 1
41747 0x06D2 Timer 13 Pickup Delay 0 60000 1 F0 0 1
41748 0x06D3 Timer 13 Dropout Delay 0 60000 1 F0 0 1
Timer 14
41749 0x06D4 Timer 14 Type 0 2 1 FC141 0 1
41750 0x06D5 Timer 14 Pickup Delay 0 60000 1 F0 0 1
41751 0x06D6 Timer 14 Dropout Delay 0 60000 1 F0 0 1
Timer 15
41752 0x06D7 Timer 15 Type 0 2 1 FC141 0 1
41753 0x06D8 Timer 15 Pickup Delay 0 60000 1 F0 0 1
41754 0x06D9 Timer 15 Dropout Delay 0 60000 1 F0 0 1
Timer 16
41755 0x06DA Timer 16 Type 0 2 1 FC141 0 1
41756 0x06DB Timer 16 Pickup Delay 0 60000 1 F0 0 1
41757 0x06DC Timer 16 Dropout Delay 0 60000 1 F0 0 1
Timer 17
41758 0x06DD Timer 17 Type 0 2 1 FC141 0 1
41759 0x06DE Timer 17 Pickup Delay 0 60000 1 F0 0 1
41760 0x06DF Timer 17 Dropout Delay 0 60000 1 F0 0 1
Timer 18
41761 0x06E0 Timer 18 Type 0 2 1 FC141 0 1
41762 0x06E1 Timer 18 Pickup Delay 0 60000 1 F0 0 1
41763 0x06E2 Timer 18 Dropout Delay 0 60000 1 F0 0 1
Timer 19
41764 0x06E3 Timer 19 Type 0 2 1 FC141 0 1
41765 0x06E4 Timer 19 Pickup Delay 0 60000 1 F0 0 1
41766 0x06E5 Timer 19 Dropout Delay 0 60000 1 F0 0 1
Timer 20
41767 0x06E6 Timer 20 Type 0 2 1 FC141 0 1
41768 0x06E7 Timer 20 Pickup Delay 0 60000 1 F0 0 1
41769 0x06E8 Timer 20 Dropout Delay 0 60000 1 F0 0 1

11-36 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Timer 21
41770 0x06E9 Timer 21 Type 0 2 1 FC141 0 1
41771 0x06EA Timer 21 Pickup Delay 0 60000 1 F0 0 1
41772 0x06EB Timer 21 Dropout Delay 0 60000 1 F0 0 1
Timer 22
41773 0x06EC Timer 22 Type 0 2 1 FC141 0 1
41774 0x06ED Timer 22 Pickup Delay 0 60000 1 F0 0 1
41775 0x06EE Timer 22 Dropout Delay 0 60000 1 F0 0 1
Timer 23
41776 0x06EF Timer 23 Type 0 2 1 FC141 0 1
41777 0x06F0 Timer 23 Pickup Delay 0 60000 1 F0 0 1
41778 0x06F1 Timer 23 Dropout Delay 0 60000 1 F0 0 1
Timer 24
41779 0x06F2 Timer 24 Type 0 2 1 FC141 0 1
41780 0x06F3 Timer 24 Pickup Delay 0 60000 1 F0 0 1
41781 0x06F4 Timer 24 Dropout Delay 0 60000 1 F0 0 1
Timer 25
41782 0x06F5 Timer 25 Type 0 2 1 FC141 0 1
41783 0x06F6 Timer 25 Pickup Delay 0 60000 1 F0 0 1
41784 0x06F7 Timer 25 Dropout Delay 0 60000 1 F0 0 1
Timer 26
41785 0x06F8 Timer 26 Type 0 2 1 FC141 0 1
41786 0x06F9 Timer 26 Pickup Delay 0 60000 1 F0 0 1
41787 0x06FA Timer 26 Dropout Delay 0 60000 1 F0 0 1
Timer 27
41788 0x06FB Timer 27 Type 0 2 1 FC141 0 1
41789 0x06FC Timer 27 Pickup Delay 0 60000 1 F0 0 1
41790 0x06FD Timer 27 Dropout Delay 0 60000 1 F0 0 1
Timer 28
41791 0x06FE Timer 28 Type 0 2 1 FC141 0 1
41792 0x06FF Timer 28 Pickup Delay 0 60000 1 F0 0 1
41793 0x0700 Timer 28 Dropout Delay 0 60000 1 F0 0 1
Timer 29
41794 0x0701 Timer 29 Type 0 2 1 FC141 0 1
41795 0x0702 Timer 29 Pickup Delay 0 60000 1 F0 0 1
41796 0x0703 Timer 29 Dropout Delay 0 60000 1 F0 0 1
Timer 30
41797 0x0704 Timer 30 Type 0 2 1 FC141 0 1
41798 0x0705 Timer 30 Pickup Delay 0 60000 1 F0 0 1
41799 0x0706 Timer 30 Dropout Delay 0 60000 1 F0 0 1
Timer 31
41800 0x0707 Timer 31 Type 0 2 1 FC141 0 1
41801 0x0708 Timer 31 Pickup Delay 0 60000 1 F0 0 1
41802 0x0709 Timer 31 Dropout Delay 0 60000 1 F0 0 1
Timer 32
41803 0x070A Timer 32 Type 0 2 1 FC141 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-37


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41804 0x070B Timer 32 Pickup Delay 0 60000 1 F0 0 1
41805 0x070C Timer 32 Dropout Delay 0 60000 1 F0 0 1
Non-Volatile Latch 1
41820 0x071B NV Latch 1 Name 0 65535 1 F60_26 NV Latch 1 26
41833 0x0728 NV Latch 1 Function 0 1 1 FC126 0 1
41834 0x0729 NV Latch 1 Type 0 1 1 FC271 0 1
41835 0x072A NV Latch 1 Set 0 0xFFFFFFFF 1 FC142 0 1
41837 0x072C NV Latch 1 Reset 0 0xFFFFFFFF 1 FC142 0 1
41839 0x072E NV Latch 1 Events 0 1 1 FC126 1 1
41840 0x072F NV Latch 1 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 2
41841 0x0730 NV Latch 2 Name 0 65535 1 F60_26 NV Latch 2 26
41854 0x073D NV Latch 2 Function 0 1 1 FC126 0 1
41855 0x073E NV Latch 2 Type 0 1 1 FC271 0 1
41856 0x073F NV Latch 2 Set 0 0xFFFFFFFF 1 FC142 0 1
41858 0x0741 NV Latch 2 Reset 0 0xFFFFFFFF 1 FC142 0 1
41860 0x0743 NV Latch 2 Events 0 1 1 FC126 1 1
41861 0x0744 NV Latch 2 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 3
41862 0x0745 NV Latch 3 Name 0 65535 1 F60_26 NV Latch 3 26
41875 0x0752 NV Latch 3 Function 0 1 1 FC126 0 1
41876 0x0753 NV Latch 3 Type 0 1 1 FC271 0 1
41877 0x0754 NV Latch 3 Set 0 0xFFFFFFFF 1 FC142 0 1
41879 0x0756 NV Latch 3 Reset 0 0xFFFFFFFF 1 FC142 0 1
41881 0x0758 NV Latch 3 Events 0 1 1 FC126 1 1
41882 0x0759 NV Latch 3 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 4
41883 0x075A NV Latch 4 Name 0 65535 1 F60_26 NV Latch 4 26
41896 0x0767 NV Latch 4 Function 0 1 1 FC126 0 1
41897 0x0768 NV Latch 4 Type 0 1 1 FC271 0 1
41898 0x0769 NV Latch 4 Set 0 0xFFFFFFFF 1 FC142 0 1
41900 0x076B NV Latch 4 Reset 0 0xFFFFFFFF 1 FC142 0 1
41902 0x076D NV Latch 4 Events 0 1 1 FC126 1 1
41903 0x076E NV Latch 4 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 5
41904 0x076F NV Latch 5 Name 0 65535 1 F60_26 NV Latch 5 26
41917 0x077C NV Latch 5 Function 0 1 1 FC126 0 1
41918 0x077D NV Latch 5 Type 0 1 1 FC271 0 1
41919 0x077E NV Latch 5 Set 0 0xFFFFFFFF 1 FC142 0 1
41921 0x0780 NV Latch 5 Reset 0 0xFFFFFFFF 1 FC142 0 1
41923 0x0782 NV Latch 5 Events 0 1 1 FC126 1 1
41924 0x0783 NV Latch 5 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 6
41925 0x0784 NV Latch 6 Name 0 65535 1 F60_26 NV Latch 6 26
41938 0x0791 NV Latch 6 Function 0 1 1 FC126 0 1
41939 0x0792 NV Latch 6 Type 0 1 1 FC271 0 1

11-38 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
41940 0x0793 NV Latch 6 Set 0 0xFFFFFFFF 1 FC142 0 1
41942 0x0795 NV Latch 6 Reset 0 0xFFFFFFFF 1 FC142 0 1
41944 0x0797 NV Latch 6 Events 0 1 1 FC126 1 1
41945 0x0798 NV Latch 6 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 7
41946 0x0799 NV Latch 7 Name 0 65535 1 F60_26 NV Latch 7 26
41959 0x07A6 NV Latch 7 Function 0 1 1 FC126 0 1
41960 0x07A7 NV Latch 7 Type 0 1 1 FC271 0 1
41961 0x07A8 NV Latch 7 Set 0 0xFFFFFFFF 1 FC142 0 1
41963 0x07AA NV Latch 7 Reset 0 0xFFFFFFFF 1 FC142 0 1
41965 0x07AC NV Latch 7 Events 0 1 1 FC126 1 1
41966 0x07AD NV Latch 7 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 8
41967 0x07AE NV Latch 8 Name 0 65535 1 F60_26 NV Latch 8 26
41980 0x07BB NV Latch 8 Function 0 1 1 FC126 0 1
41981 0x07BC NV Latch 8 Type 0 1 1 FC271 0 1
41982 0x07BD NV Latch 8 Set 0 0xFFFFFFFF 1 FC142 0 1
41984 0x07BF NV Latch 8 Reset 0 0xFFFFFFFF 1 FC142 0 1
41986 0x07C1 NV Latch 8 Events 0 1 1 FC126 1 1
41987 0x07C2 NV Latch 8 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 9
41988 0x07C3 NV Latch 9 Name 0 65535 1 F60_26 NV Latch 9 26
42001 0x07D0 NV Latch 9 Function 0 1 1 FC126 0 1
42002 0x07D1 NV Latch 9 Type 0 1 1 FC271 0 1
42003 0x07D2 NV Latch 9 Set 0 0xFFFFFFFF 1 FC142 0 1
42005 0x07D4 NV Latch 9 Reset 0 0xFFFFFFFF 1 FC142 0 1
42007 0x07D6 NV Latch 9 Events 0 1 1 FC126 1 1
42008 0x07D7 NV Latch 9 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 10
42009 0x07D8 NV Latch 10 Name 0 65535 1 F60_26 NV Latch 10 26
42022 0x07E5 NV Latch 10 Function 0 1 1 FC126 0 1
42023 0x07E6 NV Latch 10 Type 0 1 1 FC271 0 1
42024 0x07E7 NV Latch 10 Set 0 0xFFFFFFFF 1 FC142 0 1
42026 0x07E9 NV Latch 10 Reset 0 0xFFFFFFFF 1 FC142 0 1
42028 0x07EB NV Latch 10 Events 0 1 1 FC126 1 1
42029 0x07EC NV Latch 10 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 11
42030 0x07ED NV Latch 11 Name 0 65535 1 F60_26 NV Latch 11 26
42043 0x07FA NV Latch 11 Function 0 1 1 FC126 0 1
42044 0x07FB NV Latch 11 Type 0 1 1 FC271 0 1
42045 0x07FC NV Latch 11 Set 0 0xFFFFFFFF 1 FC142 0 1
42047 0x07FE NV Latch 11 Reset 0 0xFFFFFFFF 1 FC142 0 1
42049 0x0800 NV Latch 11 Events 0 1 1 FC126 1 1
42050 0x0801 NV Latch 11 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 12
42051 0x0802 NV Latch 12 Name 0 65535 1 F60_26 NV Latch 12 26

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-39


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
42064 0x080F NV Latch 12 Function 0 1 1 FC126 0 1
42065 0x0810 NV Latch 12 Type 0 1 1 FC271 0 1
42066 0x0811 NV Latch 12 Set 0 0xFFFFFFFF 1 FC142 0 1
42068 0x0813 NV Latch 12 Reset 0 0xFFFFFFFF 1 FC142 0 1
42070 0x0815 NV Latch 12 Events 0 1 1 FC126 1 1
42071 0x0816 NV Latch 12 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 13
42072 0x0817 NV Latch 13 Name 0 65535 1 F60_26 NV Latch 13 26
42085 0x0824 NV Latch 13 Function 0 1 1 FC126 0 1
42086 0x0825 NV Latch 13 Type 0 1 1 FC271 0 1
42087 0x0826 NV Latch 13 Set 0 0xFFFFFFFF 1 FC142 0 1
42089 0x0828 NV Latch 13 Reset 0 0xFFFFFFFF 1 FC142 0 1
42091 0x082A NV Latch 13 Events 0 1 1 FC126 1 1
42092 0x082B NV Latch 13 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 14
42093 0x082C NV Latch 14 Name 0 65535 1 F60_26 NV Latch 14 26
42106 0x0839 NV Latch 14 Function 0 1 1 FC126 0 1
42107 0x083A NV Latch 14 Type 0 1 1 FC271 0 1
42108 0x083B NV Latch 14 Set 0 0xFFFFFFFF 1 FC142 0 1
42110 0x083D NV Latch 14 Reset 0 0xFFFFFFFF 1 FC142 0 1
42112 0x083F NV Latch 14 Events 0 1 1 FC126 1 1
42113 0x0840 NV Latch 14 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 15
42114 0x0841 NV Latch 15 Name 0 65535 1 F60_26 NV Latch 15 26
42127 0x084E NV Latch 15 Function 0 1 1 FC126 0 1
42128 0x084F NV Latch 15 Type 0 1 1 FC271 0 1
42129 0x0850 NV Latch 15 Set 0 0xFFFFFFFF 1 FC142 0 1
42131 0x0852 NV Latch 15 Reset 0 0xFFFFFFFF 1 FC142 0 1
42133 0x0854 NV Latch 15 Events 0 1 1 FC126 1 1
42134 0x0855 NV Latch 15 Targets 0 2 1 FC101 1 1
Non-Volatile Latch 16
42135 0x0856 NV Latch 16 Name 0 65535 1 F60_26 NV Latch 16 26
42148 0x0863 NV Latch 16 Function 0 1 1 FC126 0 1
42149 0x0864 NV Latch 16 Type 0 1 1 FC271 0 1
42150 0x0865 NV Latch 16 Set 0 0xFFFFFFFF 1 FC142 0 1
42152 0x0867 NV Latch 16 Reset 0 0xFFFFFFFF 1 FC142 0 1
42154 0x0869 NV Latch 16 Events 0 1 1 FC126 1 1
42155 0x086A NV Latch 16 Targets 0 2 1 FC101 1 1
Force Virtual Inputs
42170 0x0879 Force Virtual Input 1 0 1 1 FC126A 0 1
42171 0x087A Force Virtual Input 2 0 1 1 FC126A 0 1
42172 0x087B Force Virtual Input 3 0 1 1 FC126A 0 1
42173 0x087C Force Virtual Input 4 0 1 1 FC126A 0 1
42174 0x087D Force Virtual Input 5 0 1 1 FC126A 0 1
42175 0x087E Force Virtual Input 6 0 1 1 FC126A 0 1
42176 0x087F Force Virtual Input 7 0 1 1 FC126A 0 1

11-40 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
42177 0x0880 Force Virtual Input 8 0 1 1 FC126A 0 1
42178 0x0881 Force Virtual Input 9 0 1 1 FC126A 0 1
42179 0x0882 Force Virtual Input 10 0 1 1 FC126A 0 1
42180 0x0883 Force Virtual Input 11 0 1 1 FC126A 0 1
42181 0x0884 Force Virtual Input 12 0 1 1 FC126A 0 1
42182 0x0885 Force Virtual Input 13 0 1 1 FC126A 0 1
42183 0x0886 Force Virtual Input 14 0 1 1 FC126A 0 1
42184 0x0887 Force Virtual Input 15 0 1 1 FC126A 0 1
42185 0x0888 Force Virtual Input 16 0 1 1 FC126A 0 1
42186 0x0889 Force Virtual Input 17 0 1 1 FC126A 0 1
42187 0x088A Force Virtual Input 18 0 1 1 FC126A 0 1
42188 0x088B Force Virtual Input 19 0 1 1 FC126A 0 1
42189 0x088C Force Virtual Input 20 0 1 1 FC126A 0 1
42190 0x088D Force Virtual Input 21 0 1 1 FC126A 0 1
42191 0x088E Force Virtual Input 22 0 1 1 FC126A 0 1
42192 0x088F Force Virtual Input 23 0 1 1 FC126A 0 1
42193 0x0890 Force Virtual Input 24 0 1 1 FC126A 0 1
42194 0x0891 Force Virtual Input 25 0 1 1 FC126A 0 1
42195 0x0892 Force Virtual Input 26 0 1 1 FC126A 0 1
42196 0x0893 Force Virtual Input 27 0 1 1 FC126A 0 1
42197 0x0894 Force Virtual Input 28 0 1 1 FC126A 0 1
42198 0x0895 Force Virtual Input 29 0 1 1 FC126A 0 1
42199 0x0896 Force Virtual Input 30 0 1 1 FC126A 0 1
42200 0x0897 Force Virtual Input 31 0 1 1 FC126A 0 1
42201 0x0898 Force Virtual Input 32 0 1 1 FC126A 0 1
Contact Input Voltage Threshold
42250 0x08C9 Voltage Threshold / Slot F 0 3 1 FC123 1 1
42251 0x08CA Voltage Threshold / Slot G 0 3 1 FC123 1 1
Contact Input 1
42270 0x08DD Name 0 65535 1 F60_26 CI 1 26
42283 0x08EA Debounce Time 0 160 5 ms F1 100 1
42284 0x08EB Events 0 1 1 FC126 1 1
Contact Input 2
42285 0x08EC Name 0 65535 1 F60_26 CI 2 26
42298 0x08F9 Debounce Time 0 160 5 ms F1 100 1
42299 0x08FA Events 0 1 1 FC126 1 1
Contact Input 3
42300 0x08FB Name 0 65535 1 F60_26 CI 3 26
42313 0x0908 Debounce Time 0 160 5 ms F1 100 1
42314 0x0909 Events 0 1 1 FC126 1 1
Contact Input 4
42315 0x090A Name 0 65535 1 F60_26 CI 4 26
42328 0x0917 Debounce Time 0 160 5 ms F1 100 1
42329 0x0918 Events 0 1 1 FC126 1 1
Contact Input 5
42330 0x0919 Name 0 65535 1 F60_26 CI 5 26

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-41


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
42343 0x0926 Debounce Time 0 160 5 ms F1 100 1
42344 0x0927 Events 0 1 1 FC126 1 1
Contact Input 6
42345 0x0928 Name 0 65535 1 F60_26 CI 6 26
42358 0x0935 Debounce Time 0 160 5 ms F1 100 1
42359 0x0936 Events 0 1 1 FC126 1 1
Contact Input 7
42360 0x0937 Name 0 65535 1 F60_26 CI 7 26
42373 0x0944 Debounce Time 0 160 5 ms F1 100 1
42374 0x0945 Events 0 1 1 FC126 1 1
Contact Input 8
42375 0x0946 Name 0 65535 1 F60_26 CI 8 26
42388 0x0953 Debounce Time 0 160 5 ms F1 100 1
42389 0x0954 Events 0 1 1 FC126 1 1
Contact Input 9
42390 0x0955 Name 0 65535 1 F60_26 CI 9 26
42403 0x0962 Debounce Time 0 160 5 ms F1 100 1
42404 0x0963 Events 0 1 1 FC126 1 1
Contact Input 10
42405 0x0964 Name 0 65535 1 F60_26 CI 10 26
42418 0x0971 Debounce Time 0 160 5 ms F1 100 1
42419 0x0972 Events 0 1 1 FC126 1 1
Contact Input 11
42420 0x0973 Name 0 65535 1 F60_26 CI 11 26
42433 0x0980 Debounce Time 0 160 5 ms F1 100 1
42434 0x0981 Events 0 1 1 FC126 1 1
Contact Input 12
42435 0x0982 Name 0 65535 1 F60_26 CI 12 26
42448 0x098F Debounce Time 0 160 5 ms F1 100 1
42449 0x0990 Events 0 1 1 FC126 1 1
Contact Input 13
42450 0x0991 Name 0 65535 1 F60_26 CI 13 26
42463 0x099E Debounce Time 0 160 5 ms F1 100 1
42464 0x099F Events 0 1 1 FC126 1 1
Contact Input 14
42465 0x09A0 Name 0 65535 1 F60_26 CI 14 26
42478 0x09AD Debounce Time 0 160 5 ms F1 100 1
42479 0x09AE Events 0 1 1 FC126 1 1
Virtual Input 1
42820 0x0B03 Function 0 1 1 FC126 0 1
42821 0x0B04 Name 0 65535 1 F60_26 VI 1 26
42834 0x0B11 Type 0 1 1 FC199 1 1
42835 0x0B12 Events 0 1 1 FC126 1 1
Virtual Input 2
42836 0x0B13 Function 0 1 1 FC126 0 1
42837 0x0B14 Name 0 65535 1 F60_26 VI 2 26

11-42 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
42850 0x0B21 Type 0 1 1 FC199 1 1
42851 0x0B22 Events 0 1 1 FC126 1 1
Virtual Input 3
42852 0x0B23 Function 0 1 1 FC126 0 1
42853 0x0B24 Name 0 65535 1 F60_26 VI 3 26
42866 0x0B31 Type 0 1 1 FC199 1 1
42867 0x0B32 Events 0 1 1 FC126 1 1
Virtual Input 4
42868 0x0B33 Function 0 1 1 FC126 0 1
42869 0x0B34 Name 0 65535 1 F60_26 VI 4 26
42882 0x0B41 Type 0 1 1 FC199 1 1
42883 0x0B42 Events 0 1 1 FC126 1 1
Virtual Input 5
42884 0x0B43 Function 0 1 1 FC126 0 1
42885 0x0B44 Name 0 65535 1 F60_26 VI 5 26
42898 0x0B51 Type 0 1 1 FC199 1 1
42899 0x0B52 Events 0 1 1 FC126 1 1
Virtual Input 6
42900 0x0B53 Function 0 1 1 FC126 0 1
42901 0x0B54 Name 0 65535 1 F60_26 VI 6 26
42914 0x0B61 Type 0 1 1 FC199 1 1
42915 0x0B62 Events 0 1 1 FC126 1 1
Virtual Input 7
42916 0x0B63 Function 0 1 1 FC126 0 1
42917 0x0B64 Name 0 65535 1 F60_26 VI 7 26
42930 0x0B71 Type 0 1 1 FC199 1 1
42931 0x0B72 Events 0 1 1 FC126 1 1
Virtual Input 8
42932 0x0B73 Function 0 1 1 FC126 0 1
42933 0x0B74 Name 0 65535 1 F60_26 VI 8 26
42946 0x0B81 Type 0 1 1 FC199 1 1
42947 0x0B82 Events 0 1 1 FC126 1 1
Virtual Input 9
42948 0x0B83 Function 0 1 1 FC126 0 1
42949 0x0B84 Name 0 65535 1 F60_26 VI 9 26
42962 0x0B91 Type 0 1 1 FC199 1 1
42963 0x0B92 Events 0 1 1 FC126 1 1
Virtual Input 10
42964 0x0B93 Function 0 1 1 FC126 0 1
42965 0x0B94 Name 0 65535 1 F60_26 VI 10 26
42978 0x0BA1 Type 0 1 1 FC199 1 1
42979 0x0BA2 Events 0 1 1 FC126 1 1
Virtual Input 11
42980 0x0BA3 Function 0 1 1 FC126 0 1
42981 0x0BA4 Name 0 65535 1 F60_26 VI 11 26
42994 0x0BB1 Type 0 1 1 FC199 1 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-43


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
42995 0x0BB2 Events 0 1 1 FC126 1 1
Virtual Input 12
42996 0x0BB3 Function 0 1 1 FC126 0 1
42997 0x0BB4 Name 0 65535 1 F60_26 VI 12 26
43010 0x0BC1 Type 0 1 1 FC199 1 1
43011 0x0BC2 Events 0 1 1 FC126 1 1
Virtual Input 13
43012 0x0BC3 Function 0 1 1 FC126 0 1
43013 0x0BC4 Name 0 65535 1 F60_26 VI 13 26
43026 0x0BD1 Type 0 1 1 FC199 1 1
43027 0x0BD2 Events 0 1 1 FC126 1 1
Virtual Input 14
43028 0x0BD3 Function 0 1 1 FC126 0 1
43029 0x0BD4 Name 0 65535 1 F60_26 VI 14 26
43042 0x0BE1 Type 0 1 1 FC199 1 1
43043 0x0BE2 Events 0 1 1 FC126 1 1
Virtual Input 15
43044 0x0BE3 Function 0 1 1 FC126 0 1
43045 0x0BE4 Name 0 65535 1 F60_26 VI 15 26
43058 0x0BF1 Type 0 1 1 FC199 1 1
43059 0x0BF2 Events 0 1 1 FC126 1 1
Virtual Input 16
43060 0x0BF3 Function 0 1 1 FC126 0 1
43061 0x0BF4 Name 0 65535 1 F60_26 VI 16 26
43074 0x0C01 Type 0 1 1 FC199 1 1
43075 0x0C02 Events 0 1 1 FC126 1 1
Virtual Input 17
43076 0x0C03 Function 0 1 1 FC126 0 1
43077 0x0C04 Name 0 65535 1 F60_26 VI 17 26
43090 0x0C11 Type 0 1 1 FC199 1 1
43091 0x0C12 Events 0 1 1 FC126 1 1
Virtual Input 18
43092 0x0C13 Function 0 1 1 FC126 0 1
43093 0x0C14 Name 0 65535 1 F60_26 VI 18 26
43106 0x0C21 Type 0 1 1 FC199 1 1
43107 0x0C22 Events 0 1 1 FC126 1 1
Virtual Input 19
43108 0x0C23 Function 0 1 1 FC126 0 1
43109 0x0C24 Name 0 65535 1 F60_26 VI 19 26
43122 0x0C31 Type 0 1 1 FC199 1 1
43123 0x0C32 Events 0 1 1 FC126 1 1
Virtual Input 20
43124 0x0C33 Function 0 1 1 FC126 0 1
43125 0x0C34 Name 0 65535 1 F60_26 VI 20 26
43138 0x0C41 Type 0 1 1 FC199 1 1
43139 0x0C42 Events 0 1 1 FC126 1 1

11-44 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Virtual Input 21
43140 0x0C43 Function 0 1 1 FC126 0 1
43141 0x0C44 Name 0 65535 1 F60_26 VI 21 26
43154 0x0C51 Type 0 1 1 FC199 1 1
43155 0x0C52 Events 0 1 1 FC126 1 1
Virtual Input 22
43156 0x0C53 Function 0 1 1 FC126 0 1
43157 0x0C54 Name 0 65535 1 F60_26 VI 22 26
43170 0x0C61 Type 0 1 1 FC199 1 1
43171 0x0C62 Events 0 1 1 FC126 1 1
Virtual Input 23
43172 0x0C63 Function 0 1 1 FC126 0 1
43173 0x0C64 Name 0 65535 1 F60_26 VI 23 26
43186 0x0C71 Type 0 1 1 FC199 1 1
43187 0x0C72 Events 0 1 1 FC126 1 1
Virtual Input 24
43188 0x0C73 Function 0 1 1 FC126 0 1
43189 0x0C74 Name 0 65535 1 F60_26 VI 24 26
43202 0x0C81 Type 0 1 1 FC199 1 1
43203 0x0C82 Events 0 1 1 FC126 1 1
Virtual Input 25
43204 0x0C83 Function 0 1 1 FC126 0 1
43205 0x0C84 Name 0 65535 1 F60_26 VI 25 26
43218 0x0C91 Type 0 1 1 FC199 1 1
43219 0x0C92 Events 0 1 1 FC126 1 1
Virtual Input 26
43220 0x0C93 Function 0 1 1 FC126 0 1
43221 0x0C94 Name 0 65535 1 F60_26 VI 26 26
43234 0x0CA1 Type 0 1 1 FC199 1 1
43235 0x0CA2 Events 0 1 1 FC126 1 1
Virtual Input 27
43236 0x0CA3 Function 0 1 1 FC126 0 1
43237 0x0CA4 Name 0 65535 1 F60_26 VI 27 26
43250 0x0CB1 Type 0 1 1 FC199 1 1
43251 0x0CB2 Events 0 1 1 FC126 1 1
Virtual Input 28
43252 0x0CB3 Function 0 1 1 FC126 0 1
43253 0x0CB4 Name 0 65535 1 F60_26 VI 28 26
43266 0x0CC1 Type 0 1 1 FC199 1 1
43267 0x0CC2 Events 0 1 1 FC126 1 1
Virtual Input 29
43268 0x0CC3 Function 0 1 1 FC126 0 1
43269 0x0CC4 Name 0 65535 1 F60_26 VI 29 26
43282 0x0CD1 Type 0 1 1 FC199 1 1
43283 0x0CD2 Events 0 1 1 FC126 1 1
Virtual Input 30

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-45


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
43284 0x0CD3 Function 0 1 1 FC126 0 1
43285 0x0CD4 Name 0 65535 1 F60_26 VI 30 26
43298 0x0CE1 Type 0 1 1 FC199 1 1
43299 0x0CE2 Events 0 1 1 FC126 1 1
Virtual Input 31
43300 0x0CE3 Function 0 1 1 FC126 0 1
43301 0x0CE4 Name 0 65535 1 F60_26 VI 31 26
43314 0x0CF1 Type 0 1 1 FC199 1 1
43315 0x0CF2 Events 0 1 1 FC126 1 1
Virtual Input 32
43316 0x0CF3 Function 0 1 1 FC126 0 1
43317 0x0CF4 Name 0 65535 1 F60_26 VI 32 26
43330 0x0D01 Type 0 1 1 FC199 1 1
43331 0x0D02 Events 0 1 1 FC126 1 1
Output Relay 1 Seal-In
44310 0x10D5 Seal-In Time 0 999 1 s F2 4 1
44311 0x10D6 Block Trip 0 0xFFFFFFFF 1 FC142 0 1
Output Relay 2 Seal-In
44315 0x10DA Seal-In Time 0 999 1 s F2 4 1
44316 0x10DB Block Close 0 0xFFFFFFFF 1 FC142 0 1
Virtual Output 1
45070 0x13CD Name 0 65535 1 F60_26 VO 1 26
45083 0x13DA Events 0 1 1 FC126 0 1
Virtual Output 2
45086 0x13DD Name 0 65535 1 F60_26 VO 2 26
45099 0x13EA Events 0 1 1 FC126 0 1
Virtual Output 3
45102 0x13ED Name 0 65535 1 F60_26 VO 3 26
45115 0x13FA Events 0 1 1 FC126 0 1
Virtual Output 4
45118 0x13FD Name 0 65535 1 F60_26 VO 4 26
45131 0x140A Events 0 1 1 FC126 0 1
Virtual Output 5
45134 0x140D Name 0 65535 1 F60_26 VO 5 26
45147 0x141A Events 0 1 1 FC126 0 1
Virtual Output 6
45150 0x141D Name 0 65535 1 F60_26 VO 6 26
45163 0x142A Events 0 1 1 FC126 0 1
Virtual Output 7
45166 0x142D Name 0 65535 1 F60_26 VO 7 26
45179 0x143A Events 0 1 1 FC126 0 1
Virtual Output 8
45182 0x143D Name 0 65535 1 F60_26 VO 8 26
45195 0x144A Events 0 1 1 FC126 0 1
Virtual Output 9
45198 0x144D Name 0 65535 1 F60_26 VO 9 26

11-46 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
45211 0x145A Events 0 1 1 FC126 0 1
Virtual Output 10
45214 0x145D Name 0 65535 1 F60_26 VO 10 26
45227 0x146A Events 0 1 1 FC126 0 1
Virtual Output 11
45230 0x146D Name 0 65535 1 F60_26 VO 11 26
45243 0x147A Events 0 1 1 FC126 0 1
Virtual Output 12
45246 0x147D Name 0 65535 1 F60_26 VO 12 26
45259 0x148A Events 0 1 1 FC126 0 1
Virtual Output 13
45262 0x148D Name 0 65535 1 F60_26 VO 13 26
45275 0x149A Events 0 1 1 FC126 0 1
Virtual Output 14
45278 0x149D Name 0 65535 1 F60_26 VO 14 26
45291 0x14AA Events 0 1 1 FC126 0 1
Virtual Output 15
45294 0x14AD Name 0 65535 1 F60_26 VO 15 26
45307 0x14BA Events 0 1 1 FC126 0 1
Virtual Output 16
45310 0x14BD Name 0 65535 1 F60_26 VO 16 26
45323 0x14CA Events 0 1 1 FC126 0 1
Virtual Output 17
45326 0x14CD Name 0 65535 1 F60_26 VO 17 26
45339 0x14DA Events 0 1 1 FC126 0 1
Virtual Output 18
45342 0x14DD Name 0 65535 1 F60_26 VO 18 26
45355 0x14EA Events 0 1 1 FC126 0 1
Virtual Output 19
45358 0x14ED Name 0 65535 1 F60_26 VO 19 26
45371 0x14FA Events 0 1 1 FC126 0 1
Virtual Output 20
45374 0x14FD Name 0 65535 1 F60_26 VO 20 26
45387 0x150A Events 0 1 1 FC126 0 1
Virtual Output 21
45390 0x150D Name 0 65535 1 F60_26 VO 21 26
45403 0x151A Events 0 1 1 FC126 0 1
Virtual Output 22
45406 0x151D Name 0 65535 1 F60_26 VO 22 26
45419 0x152A Events 0 1 1 FC126 0 1
Virtual Output 23
45422 0x152D Name 0 65535 1 F60_26 VO 23 26
45435 0x153A Events 0 1 1 FC126 0 1
Virtual Output 24
45438 0x153D Name 0 65535 1 F60_26 VO 24 26
45451 0x154A Events 0 1 1 FC126 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-47


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Virtual Output 25
45454 0x154D Name 0 65535 1 F60_26 VO 25 26
45467 0x155A Events 0 1 1 FC126 0 1
Virtual Output 26
45470 0x155D Name 0 65535 1 F60_26 VO 26 26
45483 0x156A Events 0 1 1 FC126 0 1
Virtual Output 27
45486 0x156D Name 0 65535 1 F60_26 VO 27 26
45499 0x157A Events 0 1 1 FC126 0 1
Virtual Output 28
45502 0x157D Name 0 65535 1 F60_26 VO 28 26
45515 0x158A Events 0 1 1 FC126 0 1
Virtual Output 29
45518 0x158D Name 0 65535 1 F60_26 VO 29 26
45531 0x159A Events 0 1 1 FC126 0 1
Virtual Output 30
45534 0x159D Name 0 65535 1 F60_26 VO 30 26
45547 0x15AA Events 0 1 1 FC126 0 1
Virtual Output 31
45550 0x15AD Name 0 65535 1 F60_26 VO 31 26
45563 0x15BA Events 0 1 1 FC126 0 1
Virtual Output 32
45566 0x15BD Name 0 65535 1 F60_26 VO 32 26
45579 0x15CA Events 0 1 1 FC126 0 1
FlexCurve 1
46183 0x1826 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.00xPKP
46185 0x1828 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.05xPKP
46187 0x182A FlexCurve A Time 0 6000000 1 ms F10 0 1
0.10xPKP
46189 0x182C FlexCurve A Time 0 6000000 1 ms F10 0 1
0.15xPKP
46191 0x182E FlexCurve A Time 0 6000000 1 ms F10 0 1
0.20xPKP
46193 0x1830 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.25xPKP
46195 0x1832 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.30xPKP
46197 0x1834 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.35xPKP
46199 0x1836 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.40xPKP
46201 0x1838 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.45xPKP
46203 0x183A FlexCurve A Time 0 6000000 1 ms F10 0 1
0.48xPKP
46205 0x183C FlexCurve A Time 0 6000000 1 ms F10 0 1
0.50xPKP
46207 0x183E FlexCurve A Time 0 6000000 1 ms F10 0 1
0.52xPKP

11-48 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46209 0x1840 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.54xPKP
46211 0x1842 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.56xPKP
46213 0x1844 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.58xPKP
46215 0x1846 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.60xPKP
46217 0x1848 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.62xPKP
46219 0x184A FlexCurve A Time 0 6000000 1 ms F10 0 1
0.64xPKP
46221 0x184C FlexCurve A Time 0 6000000 1 ms F10 0 1
0.66xPKP
46223 0x184E FlexCurve A Time 0 6000000 1 ms F10 0 1
0.68xPKP
46225 0x1850 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.70xPKP
46227 0x1852 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.72xPKP
46229 0x1854 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.74xPKP
46231 0x1856 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.76xPKP
46233 0x1858 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.78xPKP
46235 0x185A FlexCurve A Time 0 6000000 1 ms F10 0 1
0.80xPKP
46237 0x185C FlexCurve A Time 0 6000000 1 ms F10 0 1
0.82xPKP
46239 0x185E FlexCurve A Time 0 6000000 1 ms F10 0 1
0.84xPKP
46241 0x1860 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.86xPKP
46243 0x1862 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.88xPKP
46245 0x1864 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.90xPKP
46247 0x1866 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.91xPKP
46249 0x1868 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.92xPKP
46251 0x186A FlexCurve A Time 0 6000000 1 ms F10 0 1
0.93xPKP
46253 0x186C FlexCurve A Time 0 6000000 1 ms F10 0 1
0.94xPKP
46255 0x186E FlexCurve A Time 0 6000000 1 ms F10 0 1
0.95xPKP
46257 0x1870 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.96xPKP
46259 0x1872 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.97xPKP
46261 0x1874 FlexCurve A Time 0 6000000 1 ms F10 0 1
0.98xPKP
46263 0x1876 FlexCurve A Time 0 6000000 1 ms F10 0 1
1.03xPKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-49


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46265 0x1878 FlexCurve A Time 0 6000000 1 ms F10 0 1
1.05xPKP
46267 0x187A FlexCurve A Time 1.1xPKP 0 6000000 1 ms F10 0 1
46269 0x187C FlexCurve A Time 1.2xPKP 0 6000000 1 ms F10 0 1
46271 0x187E FlexCurve A Time 1.3xPKP 0 6000000 1 ms F10 0 1
46273 0x1880 FlexCurve A Time 1.4xPKP 0 6000000 1 ms F10 0 1
46275 0x1882 FlexCurve A Time 1.5xPKP 0 6000000 1 ms F10 0 1
46277 0x1884 FlexCurve A Time 1.6xPKP 0 6000000 1 ms F10 0 1
46279 0x1886 FlexCurve A Time 1.7xPKP 0 6000000 1 ms F10 0 1
46281 0x1888 FlexCurve A Time 1.8xPKP 0 6000000 1 ms F10 0 1
46283 0x188A FlexCurve A Time 1.9xPKP 0 6000000 1 ms F10 0 1
46285 0x188C FlexCurve A Time 2.0xPKP 0 6000000 1 ms F10 0 1
46287 0x188E FlexCurve A Time 2.1xPKP 0 6000000 1 ms F10 0 1
46289 0x1890 FlexCurve A Time 2.2xPKP 0 6000000 1 ms F10 0 1
46291 0x1892 FlexCurve A Time 2.3xPKP 0 6000000 1 ms F10 0 1
46293 0x1894 FlexCurve A Time 2.4xPKP 0 6000000 1 ms F10 0 1
46295 0x1896 FlexCurve A Time 2.5xPKP 0 6000000 1 ms F10 0 1
46297 0x1898 FlexCurve A Time 2.6xPKP 0 6000000 1 ms F10 0 1
46299 0x189A FlexCurve A Time 2.7xPKP 0 6000000 1 ms F10 0 1
46301 0x189C FlexCurve A Time 2.8xPKP 0 6000000 1 ms F10 0 1
46303 0x189E FlexCurve A Time 2.9xPKP 0 6000000 1 ms F10 0 1
46305 0x18A0 FlexCurve A Time 3.0xPKP 0 6000000 1 ms F10 0 1
46307 0x18A2 FlexCurve A Time 3.1xPKP 0 6000000 1 ms F10 0 1
46309 0x18A4 FlexCurve A Time 3.2xPKP 0 6000000 1 ms F10 0 1
46311 0x18A6 FlexCurve A Time 3.3xPKP 0 6000000 1 ms F10 0 1
46313 0x18A8 FlexCurve A Time 3.4xPKP 0 6000000 1 ms F10 0 1
46315 0x18AA FlexCurve A Time 3.5xPKP 0 6000000 1 ms F10 0 1
46317 0x18AC FlexCurve A Time 3.6xPKP 0 6000000 1 ms F10 0 1
46319 0x18AE FlexCurve A Time 3.7xPKP 0 6000000 1 ms F10 0 1
46321 0x18B0 FlexCurve A Time 3.8xPKP 0 6000000 1 ms F10 0 1
46323 0x18B2 FlexCurve A Time 3.9xPKP 0 6000000 1 ms F10 0 1
46325 0x18B4 FlexCurve A Time 4.0xPKP 0 6000000 1 ms F10 0 1
46327 0x18B6 FlexCurve A Time 4.1xPKP 0 6000000 1 ms F10 0 1
46329 0x18B8 FlexCurve A Time 4.2xPKP 0 6000000 1 ms F10 0 1
46331 0x18BA FlexCurve A Time 4.3xPKP 0 6000000 1 ms F10 0 1
46333 0x18BC FlexCurve A Time 4.4xPKP 0 6000000 1 ms F10 0 1
46335 0x18BE FlexCurve A Time 4.5xPKP 0 6000000 1 ms F10 0 1
46337 0x18C0 FlexCurve A Time 4.6xPKP 0 6000000 1 ms F10 0 1
46339 0x18C2 FlexCurve A Time 4.7xPKP 0 6000000 1 ms F10 0 1
46341 0x18C4 FlexCurve A Time 4.8xPKP 0 6000000 1 ms F10 0 1
46343 0x18C6 FlexCurve A Time 4.9xPKP 0 6000000 1 ms F10 0 1
46345 0x18C8 FlexCurve A Time 5.0xPKP 0 6000000 1 ms F10 0 1
46347 0x18CA FlexCurve A Time 5.1xPKP 0 6000000 1 ms F10 0 1
46349 0x18CC FlexCurve A Time 5.2xPKP 0 6000000 1 ms F10 0 1
46351 0x18CE FlexCurve A Time 5.3xPKP 0 6000000 1 ms F10 0 1
46353 0x18D0 FlexCurve A Time 5.4xPKP 0 6000000 1 ms F10 0 1

11-50 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46355 0x18D2 FlexCurve A Time 5.5xPKP 0 6000000 1 ms F10 0 1
46357 0x18D4 FlexCurve A Time 5.6xPKP 0 6000000 1 ms F10 0 1
46359 0x18D6 FlexCurve A Time 5.7xPKP 0 6000000 1 ms F10 0 1
46361 0x18D8 FlexCurve A Time 5.8xPKP 0 6000000 1 ms F10 0 1
46363 0x18DA FlexCurve A Time 5.9xPKP 0 6000000 1 ms F10 0 1
46365 0x18DC FlexCurve A Time 6.0xPKP 0 6000000 1 ms F10 0 1
46367 0x18DE FlexCurve A Time 6.5xPKP 0 6000000 1 ms F10 0 1
46369 0x18E0 FlexCurve A Time 7.0xPKP 0 6000000 1 ms F10 0 1
46371 0x18E2 FlexCurve A Time 7.5xPKP 0 6000000 1 ms F10 0 1
46373 0x18E4 FlexCurve A Time 8.0xPKP 0 6000000 1 ms F10 0 1
46375 0x18E6 FlexCurve A Time 8.5xPKP 0 6000000 1 ms F10 0 1
46377 0x18E8 FlexCurve A Time 9.0xPKP 0 6000000 1 ms F10 0 1
46379 0x18EA FlexCurve A Time 9.5xPKP 0 6000000 1 ms F10 0 1
46381 0x18EC FlexCurve A Time 0 6000000 1 ms F10 0 1
10.0xPKP
46383 0x18EE FlexCurve A Time 0 6000000 1 ms F10 0 1
10.5xPKP
46385 0x18F0 FlexCurve A Time 0 6000000 1 ms F10 0 1
11.0xPKP
46387 0x18F2 FlexCurve A Time 0 6000000 1 ms F10 0 1
11.5xPKP
46389 0x18F4 FlexCurve A Time 0 6000000 1 ms F10 0 1
12.0xPKP
46391 0x18F6 FlexCurve A Time 0 6000000 1 ms F10 0 1
12.5xPKP
46393 0x18F8 FlexCurve A Time 0 6000000 1 ms F10 0 1
13.0xPKP
46395 0x18FA FlexCurve A Time 0 6000000 1 ms F10 0 1
13.5xPKP
46397 0x18FC FlexCurve A Time 0 6000000 1 ms F10 0 1
14.0xPKP
46399 0x18FE FlexCurve A Time 0 6000000 1 ms F10 0 1
14.5xPKP
46401 0x1900 FlexCurve A Time 0 6000000 1 ms F10 0 1
15.0xPKP
46403 0x1902 FlexCurve A Time 0 6000000 1 ms F10 0 1
15.5xPKP
46405 0x1904 FlexCurve A Time 0 6000000 1 ms F10 0 1
16.0xPKP
46407 0x1906 FlexCurve A Time 0 6000000 1 ms F10 0 1
16.5xPKP
46409 0x1908 FlexCurve A Time 0 6000000 1 ms F10 0 1
17.0xPKP
46411 0x190A FlexCurve A Time 0 6000000 1 ms F10 0 1
17.5xPKP
46413 0x190C FlexCurve A Time 0 6000000 1 ms F10 0 1
18.0xPKP
46415 0x190E FlexCurve A Time 0 6000000 1 ms F10 0 1
18.5xPKP
46417 0x1910 FlexCurve A Time 0 6000000 1 ms F10 0 1
19.0xPKP
46419 0x1912 FlexCurve A Time 0 6000000 1 ms F10 0 1
19.5xPKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-51


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46421 0x1914 FlexCurve A Time 0 6000000 1 ms F10 0 1
20.0xPKP
FlexCurve 2
46436 0x1923 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.00xPKP
46438 0x1925 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.05xPKP
46440 0x1927 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.10xPKP
46442 0x1929 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.15xPKP
46444 0x192B FlexCurve B Time 0 6000000 1 ms F10 0 1
0.20xPKP
46446 0x192D FlexCurve B Time 0 6000000 1 ms F10 0 1
0.25xPKP
46448 0x192F FlexCurve B Time 0 6000000 1 ms F10 0 1
0.30xPKP
46450 0x1931 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.35xPKP
46452 0x1933 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.40xPKP
46454 0x1935 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.45xPKP
46456 0x1937 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.48xPKP
46458 0x1939 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.50xPKP
46460 0x193B FlexCurve B Time 0 6000000 1 ms F10 0 1
0.52xPKP
46462 0x193D FlexCurve B Time 0 6000000 1 ms F10 0 1
0.54xPKP
46464 0x193F FlexCurve B Time 0 6000000 1 ms F10 0 1
0.56xPKP
46466 0x1941 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.58xPKP
46468 0x1943 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.60xPKP
46470 0x1945 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.62xPKP
46472 0x1947 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.64xPKP
46474 0x1949 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.66xPKP
46476 0x194B FlexCurve B Time 0 6000000 1 ms F10 0 1
0.68xPKP
46478 0x194D FlexCurve B Time 0 6000000 1 ms F10 0 1
0.70xPKP
46480 0x194F FlexCurve B Time 0 6000000 1 ms F10 0 1
0.72xPKP
46482 0x1951 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.74xPKP
46484 0x1953 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.76xPKP
46486 0x1955 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.78xPKP

11-52 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46488 0x1957 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.80xPKP
46490 0x1959 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.82xPKP
46492 0x195B FlexCurve B Time 0 6000000 1 ms F10 0 1
0.84xPKP
46494 0x195D FlexCurve B Time 0 6000000 1 ms F10 0 1
0.86xPKP
46496 0x195F FlexCurve B Time 0 6000000 1 ms F10 0 1
0.88xPKP
46498 0x1961 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.90xPKP
46500 0x1963 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.91xPKP
46502 0x1965 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.92xPKP
46504 0x1967 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.93xPKP
46506 0x1969 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.94xPKP
46508 0x196B FlexCurve B Time 0 6000000 1 ms F10 0 1
0.95xPKP
46510 0x196D FlexCurve B Time 0 6000000 1 ms F10 0 1
0.96xPKP
46512 0x196F FlexCurve B Time 0 6000000 1 ms F10 0 1
0.97xPKP
46514 0x1971 FlexCurve B Time 0 6000000 1 ms F10 0 1
0.98xPKP
46516 0x1973 FlexCurve B Time 0 6000000 1 ms F10 0 1
1.03xPKP
46518 0x1975 FlexCurve B Time 0 6000000 1 ms F10 0 1
1.05xPKP
46520 0x1977 FlexCurve B Time 1.1xPKP 0 6000000 1 ms F10 0 1
46522 0x1979 FlexCurve B Time 1.2xPKP 0 6000000 1 ms F10 0 1
46524 0x197B FlexCurve B Time 1.3xPKP 0 6000000 1 ms F10 0 1
46526 0x197D FlexCurve B Time 1.4xPKP 0 6000000 1 ms F10 0 1
46528 0x197F FlexCurve B Time 1.5xPKP 0 6000000 1 ms F10 0 1
46530 0x1981 FlexCurve B Time 1.6xPKP 0 6000000 1 ms F10 0 1
46532 0x1983 FlexCurve B Time 1.7xPKP 0 6000000 1 ms F10 0 1
46534 0x1985 FlexCurve B Time 1.8xPKP 0 6000000 1 ms F10 0 1
46536 0x1987 FlexCurve B Time 1.9xPKP 0 6000000 1 ms F10 0 1
46538 0x1989 FlexCurve B Time 2.0xPKP 0 6000000 1 ms F10 0 1
46540 0x198B FlexCurve B Time 2.1xPKP 0 6000000 1 ms F10 0 1
46542 0x198D FlexCurve B Time 2.2xPKP 0 6000000 1 ms F10 0 1
46544 0x198F FlexCurve B Time 2.3xPKP 0 6000000 1 ms F10 0 1
46546 0x1991 FlexCurve B Time 2.4xPKP 0 6000000 1 ms F10 0 1
46548 0x1993 FlexCurve B Time 2.5xPKP 0 6000000 1 ms F10 0 1
46550 0x1995 FlexCurve B Time 2.6xPKP 0 6000000 1 ms F10 0 1
46552 0x1997 FlexCurve B Time 2.7xPKP 0 6000000 1 ms F10 0 1
46554 0x1999 FlexCurve B Time 2.8xPKP 0 6000000 1 ms F10 0 1
46556 0x199B FlexCurve B Time 2.9xPKP 0 6000000 1 ms F10 0 1
46558 0x199D FlexCurve B Time 3.0xPKP 0 6000000 1 ms F10 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-53


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46560 0x199F FlexCurve B Time 3.1xPKP 0 6000000 1 ms F10 0 1
46562 0x19A1 FlexCurve B Time 3.2xPKP 0 6000000 1 ms F10 0 1
46564 0x19A3 FlexCurve B Time 3.3xPKP 0 6000000 1 ms F10 0 1
46566 0x19A5 FlexCurve B Time 3.4xPKP 0 6000000 1 ms F10 0 1
46568 0x19A7 FlexCurve B Time 3.5xPKP 0 6000000 1 ms F10 0 1
46570 0x19A9 FlexCurve B Time 3.6xPKP 0 6000000 1 ms F10 0 1
46572 0x19AB FlexCurve B Time 3.7xPKP 0 6000000 1 ms F10 0 1
46574 0x19AD FlexCurve B Time 3.8xPKP 0 6000000 1 ms F10 0 1
46576 0x19AF FlexCurve B Time 3.9xPKP 0 6000000 1 ms F10 0 1
46578 0x19B1 FlexCurve B Time 4.0xPKP 0 6000000 1 ms F10 0 1
46580 0x19B3 FlexCurve B Time 4.1xPKP 0 6000000 1 ms F10 0 1
46582 0x19B5 FlexCurve B Time 4.2xPKP 0 6000000 1 ms F10 0 1
46584 0x19B7 FlexCurve B Time 4.3xPKP 0 6000000 1 ms F10 0 1
46586 0x19B9 FlexCurve B Time 4.4xPKP 0 6000000 1 ms F10 0 1
46588 0x19BB FlexCurve B Time 4.5xPKP 0 6000000 1 ms F10 0 1
46590 0x19BD FlexCurve B Time 4.6xPKP 0 6000000 1 ms F10 0 1
46592 0x19BF FlexCurve B Time 4.7xPKP 0 6000000 1 ms F10 0 1
46594 0x19C1 FlexCurve B Time 4.8xPKP 0 6000000 1 ms F10 0 1
46596 0x19C3 FlexCurve B Time 4.9xPKP 0 6000000 1 ms F10 0 1
46598 0x19C5 FlexCurve B Time 5.0xPKP 0 6000000 1 ms F10 0 1
46600 0x19C7 FlexCurve B Time 5.1xPKP 0 6000000 1 ms F10 0 1
46602 0x19C9 FlexCurve B Time 5.2xPKP 0 6000000 1 ms F10 0 1
46604 0x19CB FlexCurve B Time 5.3xPKP 0 6000000 1 ms F10 0 1
46606 0x19CD FlexCurve B Time 5.4xPKP 0 6000000 1 ms F10 0 1
46608 0x19CF FlexCurve B Time 5.5xPKP 0 6000000 1 ms F10 0 1
46610 0x19D1 FlexCurve B Time 5.6xPKP 0 6000000 1 ms F10 0 1
46612 0x19D3 FlexCurve B Time 5.7xPKP 0 6000000 1 ms F10 0 1
46614 0x19D5 FlexCurve B Time 5.8xPKP 0 6000000 1 ms F10 0 1
46616 0x19D7 FlexCurve B Time 5.9xPKP 0 6000000 1 ms F10 0 1
46618 0x19D9 FlexCurve B Time 6.0xPKP 0 6000000 1 ms F10 0 1
46620 0x19DB FlexCurve B Time 6.5xPKP 0 6000000 1 ms F10 0 1
46622 0x19DD FlexCurve B Time 7.0xPKP 0 6000000 1 ms F10 0 1
46624 0x19DF FlexCurve B Time 7.5xPKP 0 6000000 1 ms F10 0 1
46626 0x19E1 FlexCurve B Time 8.0xPKP 0 6000000 1 ms F10 0 1
46628 0x19E3 FlexCurve B Time 8.5xPKP 0 6000000 1 ms F10 0 1
46630 0x19E5 FlexCurve B Time 9.0xPKP 0 6000000 1 ms F10 0 1
46632 0x19E7 FlexCurve B Time 9.5xPKP 0 6000000 1 ms F10 0 1
46634 0x19E9 FlexCurve B Time 0 6000000 1 ms F10 0 1
10.0xPKP
46636 0x19EB FlexCurve B Time 0 6000000 1 ms F10 0 1
10.5xPKP
46638 0x19ED FlexCurve B Time 0 6000000 1 ms F10 0 1
11.0xPKP
46640 0x19EF FlexCurve B Time 0 6000000 1 ms F10 0 1
11.5xPKP
46642 0x19F1 FlexCurve B Time 0 6000000 1 ms F10 0 1
12.0xPKP

11-54 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46644 0x19F3 FlexCurve B Time 0 6000000 1 ms F10 0 1
12.5xPKP
46646 0x19F5 FlexCurve B Time 0 6000000 1 ms F10 0 1
13.0xPKP
46648 0x19F7 FlexCurve B Time 0 6000000 1 ms F10 0 1
13.5xPKP
46650 0x19F9 FlexCurve B Time 0 6000000 1 ms F10 0 1
14.0xPKP
46652 0x19FB FlexCurve B Time 0 6000000 1 ms F10 0 1
14.5xPKP
46654 0x19FD FlexCurve B Time 0 6000000 1 ms F10 0 1
15.0xPKP
46656 0x19FF FlexCurve B Time 0 6000000 1 ms F10 0 1
15.5xPKP
46658 0x1A01 FlexCurve B Time 0 6000000 1 ms F10 0 1
16.0xPKP
46660 0x1A03 FlexCurve B Time 0 6000000 1 ms F10 0 1
16.5xPKP
46662 0x1A05 FlexCurve B Time 0 6000000 1 ms F10 0 1
17.0xPKP
46664 0x1A07 FlexCurve B Time 0 6000000 1 ms F10 0 1
17.5xPKP
46666 0x1A09 FlexCurve B Time 0 6000000 1 ms F10 0 1
18.0xPKP
46668 0x1A0B FlexCurve B Time 0 6000000 1 ms F10 0 1
18.5xPKP
46670 0x1A0D FlexCurve B Time 0 6000000 1 ms F10 0 1
19.0xPKP
46672 0x1A0F FlexCurve B Time 0 6000000 1 ms F10 0 1
19.5xPKP
46674 0x1A11 FlexCurve B Time 0 6000000 1 ms F10 0 1
20.0xPKP
FlexCurve 3
46689 0x1A20 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.00xPKP
46691 0x1A22 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.05xPKP
46693 0x1A24 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.10xPKP
46695 0x1A26 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.15xPKP
46697 0x1A28 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.20xPKP
46699 0x1A2A FlexCurve C Time 0 6000000 1 ms F10 0 1
0.25xPKP
46701 0x1A2C FlexCurve C Time 0 6000000 1 ms F10 0 1
0.30xPKP
46703 0x1A2E FlexCurve C Time 0 6000000 1 ms F10 0 1
0.35xPKP
46705 0x1A30 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.40xPKP
46707 0x1A32 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.45xPKP
46709 0x1A34 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.48xPKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-55


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46711 0x1A36 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.50xPKP
46713 0x1A38 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.52xPKP
46715 0x1A3A FlexCurve C Time 0 6000000 1 ms F10 0 1
0.54xPKP
46717 0x1A3C FlexCurve C Time 0 6000000 1 ms F10 0 1
0.56xPKP
46719 0x1A3E FlexCurve C Time 0 6000000 1 ms F10 0 1
0.58xPKP
46721 0x1A40 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.60xPKP
46723 0x1A42 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.62xPKP
46725 0x1A44 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.64xPKP
46727 0x1A46 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.66xPKP
46729 0x1A48 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.68xPKP
46731 0x1A4A FlexCurve C Time 0 6000000 1 ms F10 0 1
0.70xPKP
46733 0x1A4C FlexCurve C Time 0 6000000 1 ms F10 0 1
0.72xPKP
46735 0x1A4E FlexCurve C Time 0 6000000 1 ms F10 0 1
0.74xPKP
46737 0x1A50 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.76xPKP
46739 0x1A52 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.78xPKP
46741 0x1A54 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.80xPKP
46743 0x1A56 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.82xPKP
46745 0x1A58 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.84xPKP
46747 0x1A5A FlexCurve C Time 0 6000000 1 ms F10 0 1
0.86xPKP
46749 0x1A5C FlexCurve C Time 0 6000000 1 ms F10 0 1
0.88xPKP
46751 0x1A5E FlexCurve C Time 0 6000000 1 ms F10 0 1
0.90xPKP
46753 0x1A60 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.91xPKP
46755 0x1A62 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.92xPKP
46757 0x1A64 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.93xPKP
46759 0x1A66 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.94xPKP
46761 0x1A68 FlexCurve C Time 0 6000000 1 ms F10 0 1
0.95xPKP
46763 0x1A6A FlexCurve C Time 0 6000000 1 ms F10 0 1
0.96xPKP
46765 0x1A6C FlexCurve C Time 0 6000000 1 ms F10 0 1
0.97xPKP

11-56 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46767 0x1A6E FlexCurve C Time 0 6000000 1 ms F10 0 1
0.98xPKP
46769 0x1A70 FlexCurve C Time 0 6000000 1 ms F10 0 1
1.03xPKP
46771 0x1A72 FlexCurve C Time 0 6000000 1 ms F10 0 1
1.05xPKP
46773 0x1A74 FlexCurve C Time 1.1xPKP 0 6000000 1 ms F10 0 1
46775 0x1A76 FlexCurve C Time 1.2xPKP 0 6000000 1 ms F10 0 1
46777 0x1A78 FlexCurve C Time 1.3xPKP 0 6000000 1 ms F10 0 1
46779 0x1A7A FlexCurve C Time 1.4xPKP 0 6000000 1 ms F10 0 1
46781 0x1A7C FlexCurve C Time 1.5xPKP 0 6000000 1 ms F10 0 1
46783 0x1A7E FlexCurve C Time 1.6xPKP 0 6000000 1 ms F10 0 1
46785 0x1A80 FlexCurve C Time 1.7xPKP 0 6000000 1 ms F10 0 1
46787 0x1A82 FlexCurve C Time 1.8xPKP 0 6000000 1 ms F10 0 1
46789 0x1A84 FlexCurve C Time 1.9xPKP 0 6000000 1 ms F10 0 1
46791 0x1A86 FlexCurve C Time 2.0xPKP 0 6000000 1 ms F10 0 1
46793 0x1A88 FlexCurve C Time 2.1xPKP 0 6000000 1 ms F10 0 1
46795 0x1A8A FlexCurve C Time 2.2xPKP 0 6000000 1 ms F10 0 1
46797 0x1A8C FlexCurve C Time 2.3xPKP 0 6000000 1 ms F10 0 1
46799 0x1A8E FlexCurve C Time 2.4xPKP 0 6000000 1 ms F10 0 1
46801 0x1A90 FlexCurve C Time 2.5xPKP 0 6000000 1 ms F10 0 1
46803 0x1A92 FlexCurve C Time 2.6xPKP 0 6000000 1 ms F10 0 1
46805 0x1A94 FlexCurve C Time 2.7xPKP 0 6000000 1 ms F10 0 1
46807 0x1A96 FlexCurve C Time 2.8xPKP 0 6000000 1 ms F10 0 1
46809 0x1A98 FlexCurve C Time 2.9xPKP 0 6000000 1 ms F10 0 1
46811 0x1A9A FlexCurve C Time 3.0xPKP 0 6000000 1 ms F10 0 1
46813 0x1A9C FlexCurve C Time 3.1xPKP 0 6000000 1 ms F10 0 1
46815 0x1A9E FlexCurve C Time 3.2xPKP 0 6000000 1 ms F10 0 1
46817 0x1AA0 FlexCurve C Time 3.3xPKP 0 6000000 1 ms F10 0 1
46819 0x1AA2 FlexCurve C Time 3.4xPKP 0 6000000 1 ms F10 0 1
46821 0x1AA4 FlexCurve C Time 3.5xPKP 0 6000000 1 ms F10 0 1
46823 0x1AA6 FlexCurve C Time 3.6xPKP 0 6000000 1 ms F10 0 1
46825 0x1AA8 FlexCurve C Time 3.7xPKP 0 6000000 1 ms F10 0 1
46827 0x1AAA FlexCurve C Time 3.8xPKP 0 6000000 1 ms F10 0 1
46829 0x1AAC FlexCurve C Time 3.9xPKP 0 6000000 1 ms F10 0 1
46831 0x1AAE FlexCurve C Time 4.0xPKP 0 6000000 1 ms F10 0 1
46833 0x1AB0 FlexCurve C Time 4.1xPKP 0 6000000 1 ms F10 0 1
46835 0x1AB2 FlexCurve C Time 4.2xPKP 0 6000000 1 ms F10 0 1
46837 0x1AB4 FlexCurve C Time 4.3xPKP 0 6000000 1 ms F10 0 1
46839 0x1AB6 FlexCurve C Time 4.4xPKP 0 6000000 1 ms F10 0 1
46841 0x1AB8 FlexCurve C Time 4.5xPKP 0 6000000 1 ms F10 0 1
46843 0x1ABA FlexCurve C Time 4.6xPKP 0 6000000 1 ms F10 0 1
46845 0x1ABC FlexCurve C Time 4.7xPKP 0 6000000 1 ms F10 0 1
46847 0x1ABE FlexCurve C Time 4.8xPKP 0 6000000 1 ms F10 0 1
46849 0x1AC0 FlexCurve C Time 4.9xPKP 0 6000000 1 ms F10 0 1
46851 0x1AC2 FlexCurve C Time 5.0xPKP 0 6000000 1 ms F10 0 1
46853 0x1AC4 FlexCurve C Time 5.1xPKP 0 6000000 1 ms F10 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-57


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46855 0x1AC6 FlexCurve C Time 5.2xPKP 0 6000000 1 ms F10 0 1
46857 0x1AC8 FlexCurve C Time 5.3xPKP 0 6000000 1 ms F10 0 1
46859 0x1ACA FlexCurve C Time 5.4xPKP 0 6000000 1 ms F10 0 1
46861 0x1ACC FlexCurve C Time 5.5xPKP 0 6000000 1 ms F10 0 1
46863 0x1ACE FlexCurve C Time 5.6xPKP 0 6000000 1 ms F10 0 1
46865 0x1AD0 FlexCurve C Time 5.7xPKP 0 6000000 1 ms F10 0 1
46867 0x1AD2 FlexCurve C Time 5.8xPKP 0 6000000 1 ms F10 0 1
46869 0x1AD4 FlexCurve C Time 5.9xPKP 0 6000000 1 ms F10 0 1
46871 0x1AD6 FlexCurve C Time 6.0xPKP 0 6000000 1 ms F10 0 1
46873 0x1AD8 FlexCurve C Time 6.5xPKP 0 6000000 1 ms F10 0 1
46875 0x1ADA FlexCurve C Time 7.0xPKP 0 6000000 1 ms F10 0 1
46877 0x1ADC FlexCurve C Time 7.5xPKP 0 6000000 1 ms F10 0 1
46879 0x1ADE FlexCurve C Time 8.0xPKP 0 6000000 1 ms F10 0 1
46881 0x1AE0 FlexCurve C Time 8.5xPKP 0 6000000 1 ms F10 0 1
46883 0x1AE2 FlexCurve C Time 9.0xPKP 0 6000000 1 ms F10 0 1
46885 0x1AE4 FlexCurve C Time 9.5xPKP 0 6000000 1 ms F10 0 1
46887 0x1AE6 FlexCurve C Time 0 6000000 1 ms F10 0 1
10.0xPKP
46889 0x1AE8 FlexCurve C Time 0 6000000 1 ms F10 0 1
10.5xPKP
46891 0x1AEA FlexCurve C Time 0 6000000 1 ms F10 0 1
11.0xPKP
46893 0x1AEC FlexCurve C Time 0 6000000 1 ms F10 0 1
11.5xPKP
46895 0x1AEE FlexCurve C Time 0 6000000 1 ms F10 0 1
12.0xPKP
46897 0x1AF0 FlexCurve C Time 0 6000000 1 ms F10 0 1
12.5xPKP
46899 0x1AF2 FlexCurve C Time 0 6000000 1 ms F10 0 1
13.0xPKP
46901 0x1AF4 FlexCurve C Time 0 6000000 1 ms F10 0 1
13.5xPKP
46903 0x1AF6 FlexCurve C Time 0 6000000 1 ms F10 0 1
14.0xPKP
46905 0x1AF8 FlexCurve C Time 0 6000000 1 ms F10 0 1
14.5xPKP
46907 0x1AFA FlexCurve C Time 0 6000000 1 ms F10 0 1
15.0xPKP
46909 0x1AFC FlexCurve C Time 0 6000000 1 ms F10 0 1
15.5xPKP
46911 0x1AFE FlexCurve C Time 0 6000000 1 ms F10 0 1
16.0xPKP
46913 0x1B00 FlexCurve C Time 0 6000000 1 ms F10 0 1
16.5xPKP
46915 0x1B02 FlexCurve C Time 0 6000000 1 ms F10 0 1
17.0xPKP
46917 0x1B04 FlexCurve C Time 0 6000000 1 ms F10 0 1
17.5xPKP
46919 0x1B06 FlexCurve C Time 0 6000000 1 ms F10 0 1
18.0xPKP
46921 0x1B08 FlexCurve C Time 0 6000000 1 ms F10 0 1
18.5xPKP

11-58 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46923 0x1B0A FlexCurve C Time 0 6000000 1 ms F10 0 1
19.0xPKP
46925 0x1B0C FlexCurve C Time 0 6000000 1 ms F10 0 1
19.5xPKP
46927 0x1B0E FlexCurve C Time 0 6000000 1 ms F10 0 1
20.0xPKP
FlexCurve 4
46942 0x1B1D FlexCurve D Time 0 6000000 1 ms F10 0 1
0.00xPKP
46944 0x1B1F FlexCurve D Time 0 6000000 1 ms F10 0 1
0.05xPKP
46946 0x1B21 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.10xPKP
46948 0x1B23 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.15xPKP
46950 0x1B25 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.20xPKP
46952 0x1B27 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.25xPKP
46954 0x1B29 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.30xPKP
46956 0x1B2B FlexCurve D Time 0 6000000 1 ms F10 0 1
0.35xPKP
46958 0x1B2D FlexCurve D Time 0 6000000 1 ms F10 0 1
0.40xPKP
46960 0x1B2F FlexCurve D Time 0 6000000 1 ms F10 0 1
0.45xPKP
46962 0x1B31 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.48xPKP
46964 0x1B33 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.50xPKP
46966 0x1B35 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.52xPKP
46968 0x1B37 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.54xPKP
46970 0x1B39 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.56xPKP
46972 0x1B3B FlexCurve D Time 0 6000000 1 ms F10 0 1
0.58xPKP
46974 0x1B3D FlexCurve D Time 0 6000000 1 ms F10 0 1
0.60xPKP
46976 0x1B3F FlexCurve D Time 0 6000000 1 ms F10 0 1
0.62xPKP
46978 0x1B41 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.64xPKP
46980 0x1B43 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.66xPKP
46982 0x1B45 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.68xPKP
46984 0x1B47 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.70xPKP
46986 0x1B49 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.72xPKP
46988 0x1B4B FlexCurve D Time 0 6000000 1 ms F10 0 1
0.74xPKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-59


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
46990 0x1B4D FlexCurve D Time 0 6000000 1 ms F10 0 1
0.76xPKP
46992 0x1B4F FlexCurve D Time 0 6000000 1 ms F10 0 1
0.78xPKP
46994 0x1B51 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.80xPKP
46996 0x1B53 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.82xPKP
46998 0x1B55 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.84xPKP
47000 0x1B57 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.86xPKP
47002 0x1B59 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.88xPKP
47004 0x1B5B FlexCurve D Time 0 6000000 1 ms F10 0 1
0.90xPKP
47006 0x1B5D FlexCurve D Time 0 6000000 1 ms F10 0 1
0.91xPKP
47008 0x1B5F FlexCurve D Time 0 6000000 1 ms F10 0 1
0.92xPKP
47010 0x1B61 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.93xPKP
47012 0x1B63 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.94xPKP
47014 0x1B65 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.95xPKP
47016 0x1B67 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.96xPKP
47018 0x1B69 FlexCurve D Time 0 6000000 1 ms F10 0 1
0.97xPKP
47020 0x1B6B FlexCurve D Time 0 6000000 1 ms F10 0 1
0.98xPKP
47022 0x1B6D FlexCurve D Time 0 6000000 1 ms F10 0 1
1.03xPKP
47024 0x1B6F FlexCurve D Time 0 6000000 1 ms F10 0 1
1.05xPKP
47026 0x1B71 FlexCurve D Time 1.1xPKP 0 6000000 1 ms F10 0 1
47028 0x1B73 FlexCurve D Time 1.2xPKP 0 6000000 1 ms F10 0 1
47030 0x1B75 FlexCurve D Time 1.3xPKP 0 6000000 1 ms F10 0 1
47032 0x1B77 FlexCurve D Time 1.4xPKP 0 6000000 1 ms F10 0 1
47034 0x1B79 FlexCurve D Time 1.5xPKP 0 6000000 1 ms F10 0 1
47036 0x1B7B FlexCurve D Time 1.6xPKP 0 6000000 1 ms F10 0 1
47038 0x1B7D FlexCurve D Time 1.7xPKP 0 6000000 1 ms F10 0 1
47040 0x1B7F FlexCurve D Time 1.8xPKP 0 6000000 1 ms F10 0 1
47042 0x1B81 FlexCurve D Time 1.9xPKP 0 6000000 1 ms F10 0 1
47044 0x1B83 FlexCurve D Time 2.0xPKP 0 6000000 1 ms F10 0 1
47046 0x1B85 FlexCurve D Time 2.1xPKP 0 6000000 1 ms F10 0 1
47048 0x1B87 FlexCurve D Time 2.2xPKP 0 6000000 1 ms F10 0 1
47050 0x1B89 FlexCurve D Time 2.3xPKP 0 6000000 1 ms F10 0 1
47052 0x1B8B FlexCurve D Time 2.4xPKP 0 6000000 1 ms F10 0 1
47054 0x1B8D FlexCurve D Time 2.5xPKP 0 6000000 1 ms F10 0 1
47056 0x1B8F FlexCurve D Time 2.6xPKP 0 6000000 1 ms F10 0 1
47058 0x1B91 FlexCurve D Time 2.7xPKP 0 6000000 1 ms F10 0 1

11-60 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
47060 0x1B93 FlexCurve D Time 2.8xPKP 0 6000000 1 ms F10 0 1
47062 0x1B95 FlexCurve D Time 2.9xPKP 0 6000000 1 ms F10 0 1
47064 0x1B97 FlexCurve D Time 3.0xPKP 0 6000000 1 ms F10 0 1
47066 0x1B99 FlexCurve D Time 3.1xPKP 0 6000000 1 ms F10 0 1
47068 0x1B9B FlexCurve D Time 3.2xPKP 0 6000000 1 ms F10 0 1
47070 0x1B9D FlexCurve D Time 3.3xPKP 0 6000000 1 ms F10 0 1
47072 0x1B9F FlexCurve D Time 3.4xPKP 0 6000000 1 ms F10 0 1
47074 0x1BA1 FlexCurve D Time 3.5xPKP 0 6000000 1 ms F10 0 1
47076 0x1BA3 FlexCurve D Time 3.6xPKP 0 6000000 1 ms F10 0 1
47078 0x1BA5 FlexCurve D Time 3.7xPKP 0 6000000 1 ms F10 0 1
47080 0x1BA7 FlexCurve D Time 3.8xPKP 0 6000000 1 ms F10 0 1
47082 0x1BA9 FlexCurve D Time 3.9xPKP 0 6000000 1 ms F10 0 1
47084 0x1BAB FlexCurve D Time 4.0xPKP 0 6000000 1 ms F10 0 1
47086 0x1BAD FlexCurve D Time 4.1xPKP 0 6000000 1 ms F10 0 1
47088 0x1BAF FlexCurve D Time 4.2xPKP 0 6000000 1 ms F10 0 1
47090 0x1BB1 FlexCurve D Time 4.3xPKP 0 6000000 1 ms F10 0 1
47092 0x1BB3 FlexCurve D Time 4.4xPKP 0 6000000 1 ms F10 0 1
47094 0x1BB5 FlexCurve D Time 4.5xPKP 0 6000000 1 ms F10 0 1
47096 0x1BB7 FlexCurve D Time 4.6xPKP 0 6000000 1 ms F10 0 1
47098 0x1BB9 FlexCurve D Time 4.7xPKP 0 6000000 1 ms F10 0 1
47100 0x1BBB FlexCurve D Time 4.8xPKP 0 6000000 1 ms F10 0 1
47102 0x1BBD FlexCurve D Time 4.9xPKP 0 6000000 1 ms F10 0 1
47104 0x1BBF FlexCurve D Time 5.0xPKP 0 6000000 1 ms F10 0 1
47106 0x1BC1 FlexCurve D Time 5.1xPKP 0 6000000 1 ms F10 0 1
47108 0x1BC3 FlexCurve D Time 5.2xPKP 0 6000000 1 ms F10 0 1
47110 0x1BC5 FlexCurve D Time 5.3xPKP 0 6000000 1 ms F10 0 1
47112 0x1BC7 FlexCurve D Time 5.4xPKP 0 6000000 1 ms F10 0 1
47114 0x1BC9 FlexCurve D Time 5.5xPKP 0 6000000 1 ms F10 0 1
47116 0x1BCB FlexCurve D Time 5.6xPKP 0 6000000 1 ms F10 0 1
47118 0x1BCD FlexCurve D Time 5.7xPKP 0 6000000 1 ms F10 0 1
47120 0x1BCF FlexCurve D Time 5.8xPKP 0 6000000 1 ms F10 0 1
47122 0x1BD1 FlexCurve D Time 5.9xPKP 0 6000000 1 ms F10 0 1
47124 0x1BD3 FlexCurve D Time 6.0xPKP 0 6000000 1 ms F10 0 1
47126 0x1BD5 FlexCurve D Time 6.5xPKP 0 6000000 1 ms F10 0 1
47128 0x1BD7 FlexCurve D Time 7.0xPKP 0 6000000 1 ms F10 0 1
47130 0x1BD9 FlexCurve D Time 7.5xPKP 0 6000000 1 ms F10 0 1
47132 0x1BDB FlexCurve D Time 8.0xPKP 0 6000000 1 ms F10 0 1
47134 0x1BDD FlexCurve D Time 8.5xPKP 0 6000000 1 ms F10 0 1
47136 0x1BDF FlexCurve D Time 9.0xPKP 0 6000000 1 ms F10 0 1
47138 0x1BE1 FlexCurve D Time 9.5xPKP 0 6000000 1 ms F10 0 1
47140 0x1BE3 FlexCurve D Time 0 6000000 1 ms F10 0 1
10.0xPKP
47142 0x1BE5 FlexCurve D Time 0 6000000 1 ms F10 0 1
10.5xPKP
47144 0x1BE7 FlexCurve D Time 0 6000000 1 ms F10 0 1
11.0xPKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-61


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
47146 0x1BE9 FlexCurve D Time 0 6000000 1 ms F10 0 1
11.5xPKP
47148 0x1BEB FlexCurve D Time 0 6000000 1 ms F10 0 1
12.0xPKP
47150 0x1BED FlexCurve D Time 0 6000000 1 ms F10 0 1
12.5xPKP
47152 0x1BEF FlexCurve D Time 0 6000000 1 ms F10 0 1
13.0xPKP
47154 0x1BF1 FlexCurve D Time 0 6000000 1 ms F10 0 1
13.5xPKP
47156 0x1BF3 FlexCurve D Time 0 6000000 1 ms F10 0 1
14.0xPKP
47158 0x1BF5 FlexCurve D Time 0 6000000 1 ms F10 0 1
14.5xPKP
47160 0x1BF7 FlexCurve D Time 0 6000000 1 ms F10 0 1
15.0xPKP
47162 0x1BF9 FlexCurve D Time 0 6000000 1 ms F10 0 1
15.5xPKP
47164 0x1BFB FlexCurve D Time 0 6000000 1 ms F10 0 1
16.0xPKP
47166 0x1BFD FlexCurve D Time 0 6000000 1 ms F10 0 1
16.5xPKP
47168 0x1BFF FlexCurve D Time 0 6000000 1 ms F10 0 1
17.0xPKP
47170 0x1C01 FlexCurve D Time 0 6000000 1 ms F10 0 1
17.5xPKP
47172 0x1C03 FlexCurve D Time 0 6000000 1 ms F10 0 1
18.0xPKP
47174 0x1C05 FlexCurve D Time 0 6000000 1 ms F10 0 1
18.5xPKP
47176 0x1C07 FlexCurve D Time 0 6000000 1 ms F10 0 1
19.0xPKP
47178 0x1C09 FlexCurve D Time 0 6000000 1 ms F10 0 1
19.5xPKP
47180 0x1C0B FlexCurve D Time 0 6000000 1 ms F10 0 1
20.0xPKP
Power System
47220 0x1C33 Nominal Frequency 0 1 1 FC107 0 1
47221 0x1C34 Phase Rotation 0 1 1 FC124A 0 1
47224 0x1C37 Frequency Tracking 0 1 1 FC126 1 1
47225 0x1C38 Cost of Energy 1 1000 1 c/kWh F1 50 1
Current Sensing 1
47253 0x1C54 Phase CT Primary 1 12000 1 A F0 500 1
47254 0x1C55 Phase CT Secondary 0 1 1 FC258 1 1
47255 0x1C56 Ground CT Primary 1 12000 1 A F0 500 1
47256 0x1C57 Ground CT Secondary 0 1 1 FC258 1 1
47257 0x1C58 Sens. Ground CT Primary 1 12000 1 A F0 500 1
47258 0x1C59 Sens. Ground CT 0 1 1 FC258 1 1
Secondary
Voltage Sensing 1
47323 0x1C9A Phase VT Connection 0 1 1 FC106 0 1
47324 0x1C9B Phase VT Secondary 100 2400 1 V F1 1200 1
47325 0x1C9C Phase VT Ratio 100 500000 1 F12 100 1

11-62 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
47327 0x1C9E Aux. VT Name 0 65535 1 F60_26 Aux VT 1 26
47340 0x1CAB Aux. VT Connection 0 6 1 FC176 0 1
47341 0x1CAC Aux. VT Secondary 100 2400 1 V F1 1200 1
47342 0x1CAD Aux. VT Ratio 100 500000 1 F12 100 1
Breaker Settings 1
47390 0x1CDD BKR 1 Name 0 65535 1 F60_26 BKR 1 26
47403 0x1CEA BKR 1 Contact Input 52a 0 0x25F 1 FC266 0 1
47405 0x1CEC BKR 1 Contact Input 52b 0 0x25F 1 FC266 0 1
47407 0x1CEE BKR 1 Connected 0 0x25F 1 FC266 0 1
Current Demand
47460 0x1D23 Function 0 4 1 FC100A 0 1
47462 0x1D25 Measurement Type 0 2 1 FC254 0 1
47463 0x1D26 Thermal 90% Response 0 4 1 FC255 2 1
Time
47464 0x1D27 Time Interval 0 4 1 FC255 3 1
47465 0x1D28 Pickup 10 10000 1 A F0 1000 1
47466 0x1D29 Relays 0 0xFFFFFFFF 1 FC198 0 1
47468 0x1D2B Block 0 0xFFFFFFFF 1 FC142 0 1
47470 0x1D2D Events 0 1 1 FC126 1 1
47471 0x1D2E Targets 0 2 1 FC101 1 1
Real Power Demand
47520 0x1D5F Function 0 4 1 FC100A 0 1
47522 0x1D61 Measurement Type 0 2 1 FC254 0 1
47523 0x1D62 Thermal 90% Response 0 4 1 FC255 2 1
Time
47524 0x1D63 Time Interval 0 4 1 FC255 3 1
47525 0x1D64 Pickup 1 3000000 1 kW F11 10000 1
47527 0x1D66 Relays 0 0xFFFFFFFF 1 FC198 0 1
47529 0x1D68 Block 0 0xFFFFFFFF 1 FC142 0 1
47531 0x1D6A Events 0 1 1 FC126 1 1
47532 0x1D6B Targets 0 2 1 FC101 1 1
Reactive Power Demand
47570 0x1D91 Function 0 4 1 FC100A 0 1
47572 0x1D93 Measurement Type 0 2 1 FC254 0 1
47573 0x1D94 Thermal 90% Response 0 4 1 FC255 2 1
Time
47574 0x1D95 Time Interval 0 4 1 FC255 3 1
47575 0x1D96 Pickup 1 3000000 1 kvar F11 10000 1
47577 0x1D98 Relays 0 0xFFFFFFFF 1 FC198 0 1
47579 0x1D9A Block 0 0xFFFFFFFF 1 FC142 0 1
47581 0x1D9C Events 0 1 1 FC126 1 1
47582 0x1D9D Targets 0 2 1 FC101 1 1
Apparent Power Demand
47620 0x1DC3 Function 0 4 1 FC100A 0 1
47622 0x1DC5 Measurement Type 0 2 1 FC254 0 1
47623 0x1DC6 Thermal 90% Response 0 4 1 FC255 2 1
Time

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-63


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
47624 0x1DC7 Time Interval 0 4 1 FC255 3 1
47625 0x1DC8 Pickup 1 3000000 1 kVA F11 10000 1
47627 0x1DCA Relays 0 0xFFFFFFFF 1 FC198 0 1
47629 0x1DCC Block 0 0xFFFFFFFF 1 FC142 0 1
47631 0x1DCE Events 0 1 1 FC126 1 1
47632 0x1DCF Targets 0 2 1 FC101 1 1
Fault Locator
47761 0x1E50 Trigger 0 0xFFFFFFFF 1 FC142 0 1
47763 0x1E52 Units of Length 0 1 1 FC268 1 1
47764 0x1E53 Length of Feeder 1 999 1 F1 1 1
47765 0x1E54 Length of Feeder 1 999 1 F1 1 1
47766 0x1E55 Z_1 (Resistive) of Feeder 1 25000 1 ohms F2 1 1
47767 0x1E56 Z_1 (Inductive) of Feeder 1 25000 1 ohms F2 1 1
47768 0x1E57 Z_0 (Resistive) of Feeder 1 65000 1 ohms F2 1 1
47769 0x1E58 Z_0 (Inductive) of Feeder 1 65000 1 ohms F2 1 1
47770 0x1E59 VT Substitution 0 2 1 FC269 0 1
47771 0x1E5A Z_0 (Resistive) of System 1 9999 1 ohms F2 1 1
47772 0x1E5B Z_0 (Inductive) of System 1 9999 1 ohms F2 1 1
Power Factor 1
47790 0x1E6D Function 0 4 1 FC100A 0 1
47792 0x1E6F Switch-In -99 100 1 F22 80 1
47793 0x1E70 Switch-Out -99 100 1 F22 100 1
47794 0x1E71 Delay 0 6000000 1 s F13 50000 1
47796 0x1E73 Minimum Voltage 0 125 1 x VT F2 30 1
47797 0x1E74 Relays 0 0xFFFFFFFF 1 FC198 0 1
47799 0x1E76 Block 0 0xFFFFFFFF 1 FC142 0 1
47801 0x1E78 Events 0 1 1 FC126 1 1
47802 0x1E79 Targets 0 2 1 FC101 1 1
Power Factor 2
47803 0x1E7A Function 0 4 1 FC100A 0 1
47805 0x1E7C Switch-In -99 100 1 F22 80 1
47806 0x1E7D Switch-Out -99 100 1 F22 100 1
47807 0x1E7E Delay 0 6000000 1 s F13 50000 1
47809 0x1E80 Minimum Voltage 0 125 1 x VT F2 30 1
47810 0x1E81 Relays 0 0xFFFFFFFF 1 FC198 0 1
47812 0x1E83 Block 0 0xFFFFFFFF 1 FC142 0 1
47814 0x1E85 Events 0 1 1 FC126 1 1
47815 0x1E86 Targets 0 2 1 FC101 1 1
Pulse Output
47830 0x1E95 Function 0 1 1 FC126 0 1
47831 0x1E96 Pos Whs Pulse Increment 0 1000000 1 MWh F33 10000 1
47833 0x1E98 Pos Whs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
47835 0x1E9A Neg Whs Pulse Increment 0 1000000 1 MWh F33 10000 1
47837 0x1E9C Neg Whs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
47839 0x1E9E Pos VARhs Pulse 0 1000000 1 Mvarh F33 10000 1
Increment

11-64 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
47841 0x1EA0 Pos VARhs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
47843 0x1EA2 Neg VARhs Pulse 0 1000000 1 Mvarh F33 10000 1
Increment
47845 0x1EA4 Neg VARhs Pulse Relays 0 0xFFFFFFFF 1 FC198A 0 1
47847 0x1EA6 Events 0 1 1 FC126 1 1
47848 0x1EA7 Targets 0 2 1 FC101 1 1
Trip Circuit Monitoring
47860 0x1EB3 Function 0 4 1 FC100A 0 1
47861 0x1EB4 Pickup Delay 0 6000000 1 s F13 10000 1
47863 0x1EB6 Dropout Delay 0 6000000 1 s F13 0 1
47865 0x1EB8 Bypass Breaker State 0 1 1 FC126 0 1
47866 0x1EB9 Breaker Status Closed 0 0xFFFFFFFF 1 FC142 0 1
47868 0x1EBB Block 0 0xFFFFFFFF 1 FC142 0 1
47870 0x1EBD Relays 0 0xFFFFFFFF 1 FC198 0 1
47872 0x1EBF Events 0 1 1 FC126 1 1
47873 0x1EC0 Targets 0 2 1 FC101 1 1
Close Circuit Monitoring
47874 0x1EC1 Function 0 4 1 FC100A 0 1
47875 0x1EC2 Pickup Delay 0 6000000 1 s F13 10000 1
47877 0x1EC4 Dropout Delay 0 6000000 1 s F13 0 1
47879 0x1EC6 Bypass Breaker State 0 1 1 FC126 0 1
47880 0x1EC7 Breaker Status Opened 0 0xFFFFFFFF 1 FC142 0 1
47882 0x1EC9 Block 0 0xFFFFFFFF 1 FC142 0 1
47884 0x1ECB Relays 0 0xFFFFFFFF 1 FC198 0 1
47886 0x1ECD Events 0 1 1 FC126 1 1
47887 0x1ECE Targets 0 2 1 FC101 1 1
Digital Counter 1
48120 0x1FB7 Function 0 1 1 FC126 0 1
48121 0x1FB8 Name 0 65535 1 F60_26 Counter 1 26
48134 0x1FC5 Units 0 65535 1 F60_6 units 6
48137 0x1FC8 Pre-set -2147483648 2147483647 1 F30 0 1
48139 0x1FCA Compare -2147483648 2147483647 1 F30 0 1
48141 0x1FCC Up 0 0xFFFFFFFF 1 FC142 0 1
48143 0x1FCE Down 0 0xFFFFFFFF 1 FC142 0 1
48145 0x1FD0 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48147 0x1FD2 Reset 0 0xFFFFFFFF 1 FC142 0 1
48149 0x1FD4 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48151 0x1FD6 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48153 0x1FD8 Block 0 0xFFFFFFFF 1 FC142 0 1
48155 0x1FDA HI 1 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48157 0x1FDC EQL 1 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48159 0x1FDE LO 1 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48161 0x1FE0 Events 0 1 1 FC126 1 1
Digital Counter 2
48162 0x1FE1 Function 0 1 1 FC126 0 1
48163 0x1FE2 Name 0 65535 1 F60_26 Counter 2 26

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-65


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48176 0x1FEF Units 0 65535 1 F60_6 units 6
48179 0x1FF2 Pre-set -2147483648 2147483647 1 F30 0 1
48181 0x1FF4 Compare -2147483648 2147483647 1 F30 0 1
48183 0x1FF6 Up 0 0xFFFFFFFF 1 FC142 0 1
48185 0x1FF8 Down 0 0xFFFFFFFF 1 FC142 0 1
48187 0x1FFA Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48189 0x1FFC Reset 0 0xFFFFFFFF 1 FC142 0 1
48191 0x1FFE Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48193 0x2000 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48195 0x2002 Block 0 0xFFFFFFFF 1 FC142 0 1
48197 0x2004 HI 2 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48199 0x2006 EQL 2 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48201 0x2008 LO 2 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48203 0x200A Events 0 1 1 FC126 1 1
Digital Counter 3
48204 0x200B Function 0 1 1 FC126 0 1
48205 0x200C Name 0 65535 1 F60_26 Counter 3 26
48218 0x2019 Units 0 65535 1 F60_6 units 6
48221 0x201C Pre-set -2147483648 2147483647 1 F30 0 1
48223 0x201E Compare -2147483648 2147483647 1 F30 0 1
48225 0x2020 Up 0 0xFFFFFFFF 1 FC142 0 1
48227 0x2022 Down 0 0xFFFFFFFF 1 FC142 0 1
48229 0x2024 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48231 0x2026 Reset 0 0xFFFFFFFF 1 FC142 0 1
48233 0x2028 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48235 0x202A Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48237 0x202C Block 0 0xFFFFFFFF 1 FC142 0 1
48239 0x202E HI 3 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48241 0x2030 EQL 3 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48243 0x2032 LO 3 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48245 0x2034 Events 0 1 1 FC126 1 1
Digital Counter 4
48246 0x2035 Function 0 1 1 FC126 0 1
48247 0x2036 Name 0 65535 1 F60_26 Counter 4 26
48260 0x2043 Units 0 65535 1 F60_6 units 6
48263 0x2046 Pre-set -2147483648 2147483647 1 F30 0 1
48265 0x2048 Compare -2147483648 2147483647 1 F30 0 1
48267 0x204A Up 0 0xFFFFFFFF 1 FC142 0 1
48269 0x204C Down 0 0xFFFFFFFF 1 FC142 0 1
48271 0x204E Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48273 0x2050 Reset 0 0xFFFFFFFF 1 FC142 0 1
48275 0x2052 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48277 0x2054 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48279 0x2056 Block 0 0xFFFFFFFF 1 FC142 0 1
48281 0x2058 HI 4 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48283 0x205A EQL 4 Output Relays 0 0xFFFFFFFF 1 FC198 0 1

11-66 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48285 0x205C LO 4 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48287 0x205E Events 0 1 1 FC126 1 1
Digital Counter 5
48288 0x205F Function 0 1 1 FC126 0 1
48289 0x2060 Name 0 65535 1 F60_26 Counter 5 26
48302 0x206D Units 0 65535 1 F60_6 units 6
48305 0x2070 Pre-set -2147483648 2147483647 1 F30 0 1
48307 0x2072 Compare -2147483648 2147483647 1 F30 0 1
48309 0x2074 Up 0 0xFFFFFFFF 1 FC142 0 1
48311 0x2076 Down 0 0xFFFFFFFF 1 FC142 0 1
48313 0x2078 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48315 0x207A Reset 0 0xFFFFFFFF 1 FC142 0 1
48317 0x207C Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48319 0x207E Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48321 0x2080 Block 0 0xFFFFFFFF 1 FC142 0 1
48323 0x2082 HI 5 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48325 0x2084 EQL 5 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48327 0x2086 LO 5 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48329 0x2088 Events 0 1 1 FC126 1 1
Digital Counter 6
48330 0x2089 Function 0 1 1 FC126 0 1
48331 0x208A Name 0 65535 1 F60_26 Counter 6 26
48344 0x2097 Units 0 65535 1 F60_6 units 6
48347 0x209A Pre-set -2147483648 2147483647 1 F30 0 1
48349 0x209C Compare -2147483648 2147483647 1 F30 0 1
48351 0x209E Up 0 0xFFFFFFFF 1 FC142 0 1
48353 0x20A0 Down 0 0xFFFFFFFF 1 FC142 0 1
48355 0x20A2 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48357 0x20A4 Reset 0 0xFFFFFFFF 1 FC142 0 1
48359 0x20A6 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48361 0x20A8 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48363 0x20AA Block 0 0xFFFFFFFF 1 FC142 0 1
48365 0x20AC HI 6 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48367 0x20AE EQL 6 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48369 0x20B0 LO 6 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48371 0x20B2 Events 0 1 1 FC126 1 1
Digital Counter 7
48372 0x20B3 Function 0 1 1 FC126 0 1
48373 0x20B4 Name 0 65535 1 F60_26 Counter 7 26
48386 0x20C1 Units 0 65535 1 F60_6 units 6
48389 0x20C4 Pre-set -2147483648 2147483647 1 F30 0 1
48391 0x20C6 Compare -2147483648 2147483647 1 F30 0 1
48393 0x20C8 Up 0 0xFFFFFFFF 1 FC142 0 1
48395 0x20CA Down 0 0xFFFFFFFF 1 FC142 0 1
48397 0x20CC Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48399 0x20CE Reset 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-67


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48401 0x20D0 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48403 0x20D2 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48405 0x20D4 Block 0 0xFFFFFFFF 1 FC142 0 1
48407 0x20D6 HI 7 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48409 0x20D8 EQL 7 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48411 0x20DA LO 7 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48413 0x20DC Events 0 1 1 FC126 1 1
Digital Counter 8
48414 0x20DD Function 0 1 1 FC126 0 1
48415 0x20DE Name 0 65535 1 F60_26 Counter 8 26
48428 0x20EB Units 0 65535 1 F60_6 units 6
48431 0x20EE Pre-set -2147483648 2147483647 1 F30 0 1
48433 0x20F0 Compare -2147483648 2147483647 1 F30 0 1
48435 0x20F2 Up 0 0xFFFFFFFF 1 FC142 0 1
48437 0x20F4 Down 0 0xFFFFFFFF 1 FC142 0 1
48439 0x20F6 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48441 0x20F8 Reset 0 0xFFFFFFFF 1 FC142 0 1
48443 0x20FA Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48445 0x20FC Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48447 0x20FE Block 0 0xFFFFFFFF 1 FC142 0 1
48449 0x2100 HI 8 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48451 0x2102 EQL 8 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48453 0x2104 LO 8 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48455 0x2106 Events 0 1 1 FC126 1 1
Digital Counter 9
48456 0x2107 Function 0 1 1 FC126 0 1
48457 0x2108 Name 0 65535 1 F60_26 Counter 9 26
48470 0x2115 Units 0 65535 1 F60_6 units 6
48473 0x2118 Pre-set -2147483648 2147483647 1 F30 0 1
48475 0x211A Compare -2147483648 2147483647 1 F30 0 1
48477 0x211C Up 0 0xFFFFFFFF 1 FC142 0 1
48479 0x211E Down 0 0xFFFFFFFF 1 FC142 0 1
48481 0x2120 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48483 0x2122 Reset 0 0xFFFFFFFF 1 FC142 0 1
48485 0x2124 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48487 0x2126 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48489 0x2128 Block 0 0xFFFFFFFF 1 FC142 0 1
48491 0x212A HI 9 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48493 0x212C EQL 9 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48495 0x212E LO 9 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48497 0x2130 Events 0 1 1 FC126 1 1
Digital Counter 10
48498 0x2131 Function 0 1 1 FC126 0 1
48499 0x2132 Name 0 65535 1 F60_26 Counter 10 26
48512 0x213F Units 0 65535 1 F60_6 units 6
48515 0x2142 Pre-set -2147483648 2147483647 1 F30 0 1

11-68 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48517 0x2144 Compare -2147483648 2147483647 1 F30 0 1
48519 0x2146 Up 0 0xFFFFFFFF 1 FC142 0 1
48521 0x2148 Down 0 0xFFFFFFFF 1 FC142 0 1
48523 0x214A Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48525 0x214C Reset 0 0xFFFFFFFF 1 FC142 0 1
48527 0x214E Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48529 0x2150 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48531 0x2152 Block 0 0xFFFFFFFF 1 FC142 0 1
48533 0x2154 HI 10 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48535 0x2156 EQL 10 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48537 0x2158 LO 10 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48539 0x215A Events 0 1 1 FC126 1 1
Digital Counter 11
48540 0x215B Function 0 1 1 FC126 0 1
48541 0x215C Name 0 65535 1 F60_26 Counter 11 26
48554 0x2169 Units 0 65535 1 F60_6 units 6
48557 0x216C Pre-set -2147483648 2147483647 1 F30 0 1
48559 0x216E Compare -2147483648 2147483647 1 F30 0 1
48561 0x2170 Up 0 0xFFFFFFFF 1 FC142 0 1
48563 0x2172 Down 0 0xFFFFFFFF 1 FC142 0 1
48565 0x2174 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48567 0x2176 Reset 0 0xFFFFFFFF 1 FC142 0 1
48569 0x2178 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48571 0x217A Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48573 0x217C Block 0 0xFFFFFFFF 1 FC142 0 1
48575 0x217E HI 11 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48577 0x2180 EQL 11 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48579 0x2182 LO 11 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48581 0x2184 Events 0 1 1 FC126 1 1
Digital Counter 12
48582 0x2185 Function 0 1 1 FC126 0 1
48583 0x2186 Name 0 65535 1 F60_26 Counter 12 26
48596 0x2193 Units 0 65535 1 F60_6 units 6
48599 0x2196 Pre-set -2147483648 2147483647 1 F30 0 1
48601 0x2198 Compare -2147483648 2147483647 1 F30 0 1
48603 0x219A Up 0 0xFFFFFFFF 1 FC142 0 1
48605 0x219C Down 0 0xFFFFFFFF 1 FC142 0 1
48607 0x219E Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48609 0x21A0 Reset 0 0xFFFFFFFF 1 FC142 0 1
48611 0x21A2 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48613 0x21A4 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48615 0x21A6 Block 0 0xFFFFFFFF 1 FC142 0 1
48617 0x21A8 HI 12 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48619 0x21AA EQL 12 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48621 0x21AC LO 12 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48623 0x21AE Events 0 1 1 FC126 1 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-69


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Digital Counter 13
48624 0x21AF Function 0 1 1 FC126 0 1
48625 0x21B0 Name 0 65535 1 F60_26 Counter 13 26
48638 0x21BD Units 0 65535 1 F60_6 units 6
48641 0x21C0 Pre-set -2147483648 2147483647 1 F30 0 1
48643 0x21C2 Compare -2147483648 2147483647 1 F30 0 1
48645 0x21C4 Up 0 0xFFFFFFFF 1 FC142 0 1
48647 0x21C6 Down 0 0xFFFFFFFF 1 FC142 0 1
48649 0x21C8 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48651 0x21CA Reset 0 0xFFFFFFFF 1 FC142 0 1
48653 0x21CC Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48655 0x21CE Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48657 0x21D0 Block 0 0xFFFFFFFF 1 FC142 0 1
48659 0x21D2 HI 13 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48661 0x21D4 EQL 13 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48663 0x21D6 LO 13 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48665 0x21D8 Events 0 1 1 FC126 1 1
Digital Counter 14
48666 0x21D9 Function 0 1 1 FC126 0 1
48667 0x21DA Name 0 65535 1 F60_26 Counter 14 26
48680 0x21E7 Units 0 65535 1 F60_6 units 6
48683 0x21EA Pre-set -2147483648 2147483647 1 F30 0 1
48685 0x21EC Compare -2147483648 2147483647 1 F30 0 1
48687 0x21EE Up 0 0xFFFFFFFF 1 FC142 0 1
48689 0x21F0 Down 0 0xFFFFFFFF 1 FC142 0 1
48691 0x21F2 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48693 0x21F4 Reset 0 0xFFFFFFFF 1 FC142 0 1
48695 0x21F6 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48697 0x21F8 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48699 0x21FA Block 0 0xFFFFFFFF 1 FC142 0 1
48701 0x21FC HI 14 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48703 0x21FE EQL 14 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48705 0x2200 LO 14 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48707 0x2202 Events 0 1 1 FC126 1 1
Digital Counter 15
48708 0x2203 Function 0 1 1 FC126 0 1
48709 0x2204 Name 0 65535 1 F60_26 Counter 15 26
48722 0x2211 Units 0 65535 1 F60_6 units 6
48725 0x2214 Pre-set -2147483648 2147483647 1 F30 0 1
48727 0x2216 Compare -2147483648 2147483647 1 F30 0 1
48729 0x2218 Up 0 0xFFFFFFFF 1 FC142 0 1
48731 0x221A Down 0 0xFFFFFFFF 1 FC142 0 1
48733 0x221C Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48735 0x221E Reset 0 0xFFFFFFFF 1 FC142 0 1
48737 0x2220 Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48739 0x2222 Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1

11-70 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48741 0x2224 Block 0 0xFFFFFFFF 1 FC142 0 1
48743 0x2226 HI 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48745 0x2228 EQL 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48747 0x222A LO 15 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48749 0x222C Events 0 1 1 FC126 1 1
Digital Counter 16
48750 0x222D Function 0 1 1 FC126 0 1
48751 0x222E Name 0 65535 1 F60_26 Counter 16 26
48764 0x223B Units 0 65535 1 F60_6 units 6
48767 0x223E Pre-set -2147483648 2147483647 1 F30 0 1
48769 0x2240 Compare -2147483648 2147483647 1 F30 0 1
48771 0x2242 Up 0 0xFFFFFFFF 1 FC142 0 1
48773 0x2244 Down 0 0xFFFFFFFF 1 FC142 0 1
48775 0x2246 Set to Pre-set 0 0xFFFFFFFF 1 FC142 0 1
48777 0x2248 Reset 0 0xFFFFFFFF 1 FC142 0 1
48779 0x224A Freeze/Reset 0 0xFFFFFFFF 1 FC142 0 1
48781 0x224C Freeze/Count 0 0xFFFFFFFF 1 FC142 0 1
48783 0x224E Block 0 0xFFFFFFFF 1 FC142 0 1
48785 0x2250 HI 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48787 0x2252 EQL 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48789 0x2254 LO 16 Output Relays 0 0xFFFFFFFF 1 FC198 0 1
48791 0x2256 Events 0 1 1 FC126 1 1
Breaker Health
48810 0x2269 Function 0 4 1 FC100A 0 1
48811 0x226A Mode 0 1 1 FC277 0 1
48812 0x226B Preset Trip Counter 0 100000 1 F10 0 1
48814 0x226D Trip Trigger 0 0xFFFFFFFF 1 FC142 0 1
48816 0x226F Close Trigger 0 0xFFFFFFFF 1 FC142 0 1
48818 0x2271 Open Status 0 0xFFFFFFFF 1 FC142 0 1
48820 0x2273 Close Status 0 0xFFFFFFFF 1 FC142 0 1
48822 0x2275 Spring Charge Status 0 0xFFFFFFFF 1 FC142 0 1
48824 0x2277 Trip Time Pickup 0 6000000 1 s F13 50 1
48826 0x2279 Close Time Pickup 0 6000000 1 s F13 50 1
48828 0x227B Incomplete Trp/Cls Time 0 6000000 1 s F13 100 1
48830 0x227D Arc Time Pickup 0 6000000 1 s F13 100 1
48832 0x227F Incomplete Arc Time 0 6000000 1 s F13 300 1
48834 0x2281 Spring Charge Time 0 6000000 1 s F13 15000 1
Pickup
48836 0x2283 Incomplete Charge Time 0 6000000 1 s F13 45000 1
48838 0x2285 Arc Energy Pickup 1 100000 1 kA2-cyc F10 1000 1
48840 0x2287 Alarm Counter 1 100 1 F0 5 1
48841 0x2288 Relays 0 0xFFFFFFFF 1 FC198 0 1
48843 0x228A Block 0 0xFFFFFFFF 1 FC142 0 1
48845 0x228C Events 0 1 1 FC126 1 1
48846 0x228D Targets 0 2 1 FC101 1 1
Breaker 1 Arcing Current Config

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-71


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
48930 0x22E1 Function 0 4 1 FC100A 0 1
48932 0x22E3 Initiation 0 0xFFFFFFFF 1 FC142 0 1
48934 0x22E5 Delay 0 6000000 1 s F13 30 1
48936 0x22E7 Alarm Level 0 50000 1 kA2-cyc F0 1000 1
48937 0x22E8 Relays 0 0xFFFFFFFF 1 FC198 0 1
48939 0x22EA Block 0 0xFFFFFFFF 1 FC142 0 1
48941 0x22EC Events 0 1 1 FC126 1 1
48942 0x22ED Targets 0 2 1 FC101 1 1
Change Setpoint Group
49030 0x2345 Active Setpoint Group 0 5 1 FC132A 0 1
49031 0x2346 Set Group 2 Active 0 0xFFFFFFFF 1 FC142 0 1
49033 0x2348 Set Group 3 Active 0 0xFFFFFFFF 1 FC142 0 1
49035 0x234A Set Group 4 Active 0 0xFFFFFFFF 1 FC142 0 1
49037 0x234C Set Group 5 Active 0 0xFFFFFFFF 1 FC142 0 1
49039 0x234E Set Group 6 Active 0 0xFFFFFFFF 1 FC142 0 1
49119 0x239E Change Inhibit 1 0 0xFFFFFFFF 1 FC142 0 1
49121 0x23A0 Change Inhibit 2 0 0xFFFFFFFF 1 FC142 0 1
49123 0x23A2 Change Inhibit 3 0 0xFFFFFFFF 1 FC142 0 1
49125 0x23A4 Change Inhibit 4 0 0xFFFFFFFF 1 FC142 0 1
49127 0x23A6 Change Inhibit 5 0 0xFFFFFFFF 1 FC142 0 1
49129 0x23A8 Change Inhibit 6 0 0xFFFFFFFF 1 FC142 0 1
49131 0x23AA Change Inhibit 7 0 0xFFFFFFFF 1 FC142 0 1
49133 0x23AC Change Inhibit 8 0 0xFFFFFFFF 1 FC142 0 1
49135 0x23AE Change Inhibit 9 0 0xFFFFFFFF 1 FC142 0 1
49137 0x23B0 Change Inhibit 10 0 0xFFFFFFFF 1 FC142 0 1
49139 0x23B2 Change Inhibit 11 0 0xFFFFFFFF 1 FC142 0 1
49141 0x23B4 Change Inhibit 12 0 0xFFFFFFFF 1 FC142 0 1
49143 0x23B6 Change Inhibit 13 0 0xFFFFFFFF 1 FC142 0 1
49145 0x23B8 Change Inhibit 14 0 0xFFFFFFFF 1 FC142 0 1
49147 0x23BA Change Inhibit 15 0 0xFFFFFFFF 1 FC142 0 1
49149 0x23BC Change Inhibit 16 0 0xFFFFFFFF 1 FC142 0 1
49151 0x23BE Events 0 1 1 FC126 1 1
Breaker Control
49170 0x23D1 Local Mode 0 0xFFFFFFFF 1 FC142 0 1
49172 0x23D3 Local Open 0 3 1 FC322 1 1
49173 0x23D4 Local Close 0 3 1 FC322 2 1
49174 0x23D5 Remote Open 0 0xFFFFFFFF 1 FC142 0 1
49176 0x23D7 Remote Close 0 0xFFFFFFFF 1 FC142 0 1
49178 0x23D9 Close Sync Supervision 0 2 1 FC280 0 1
49179 0x23DA Events 0 1 1 FC126 1 1
49180 0x23DB Targets 0 2 1 FC101 1 1
Trip Bus 1
49190 0x23E5 Function 0 4 1 FC100 0 1
49191 0x23E6 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49193 0x23E8 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49195 0x23EA Input 3 0 0xFFFFFFFF 1 FC142 0 1

11-72 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49197 0x23EC Input 4 0 0xFFFFFFFF 1 FC142 0 1
49199 0x23EE Input 5 0 0xFFFFFFFF 1 FC142 0 1
49201 0x23F0 Input 6 0 0xFFFFFFFF 1 FC142 0 1
49203 0x23F2 Input 7 0 0xFFFFFFFF 1 FC142 0 1
49205 0x23F4 Input 8 0 0xFFFFFFFF 1 FC142 0 1
49207 0x23F6 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49209 0x23F8 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49211 0x23FA Input 11 0 0xFFFFFFFF 1 FC142 0 1
49213 0x23FC Input 12 0 0xFFFFFFFF 1 FC142 0 1
49215 0x23FE Input 13 0 0xFFFFFFFF 1 FC142 0 1
49217 0x2400 Input 14 0 0xFFFFFFFF 1 FC142 0 1
49219 0x2402 Input 15 0 0xFFFFFFFF 1 FC142 0 1
49221 0x2404 Input 16 0 0xFFFFFFFF 1 FC142 0 1
49223 0x2406 Latching 0 1 1 FC126 0 1
49224 0x2407 Reset 0 0xFFFFFFFF 1 FC142 0 1
49226 0x2409 Pickup Delay 0 6000000 1 s F13 0 1
49228 0x240B Dropout Delay 0 6000000 1 s F13 0 1
49230 0x240D Relays 0 0xFFFFFFFF 1 FC198 0 1
49232 0x240F Block 0 0xFFFFFFFF 1 FC142 0 1
49234 0x2411 Events 0 1 1 FC126 1 1
49235 0x2412 Targets 0 2 1 FC101 1 1
Trip Bus 2
49237 0x2414 Function 0 4 1 FC100 0 1
49238 0x2415 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49240 0x2417 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49242 0x2419 Input 3 0 0xFFFFFFFF 1 FC142 0 1
49244 0x241B Input 4 0 0xFFFFFFFF 1 FC142 0 1
49246 0x241D Input 5 0 0xFFFFFFFF 1 FC142 0 1
49248 0x241F Input 6 0 0xFFFFFFFF 1 FC142 0 1
49250 0x2421 Input 7 0 0xFFFFFFFF 1 FC142 0 1
49252 0x2423 Input 8 0 0xFFFFFFFF 1 FC142 0 1
49254 0x2425 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49256 0x2427 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49258 0x2429 Input 11 0 0xFFFFFFFF 1 FC142 0 1
49260 0x242B Input 12 0 0xFFFFFFFF 1 FC142 0 1
49262 0x242D Input 13 0 0xFFFFFFFF 1 FC142 0 1
49264 0x242F Input 14 0 0xFFFFFFFF 1 FC142 0 1
49266 0x2431 Input 15 0 0xFFFFFFFF 1 FC142 0 1
49268 0x2433 Input 16 0 0xFFFFFFFF 1 FC142 0 1
49270 0x2435 Latching 0 1 1 FC126 0 1
49271 0x2436 Reset 0 0xFFFFFFFF 1 FC142 0 1
49273 0x2438 Pickup Delay 0 6000000 1 s F13 0 1
49275 0x243A Dropout Delay 0 6000000 1 s F13 0 1
49277 0x243C Relays 0 0xFFFFFFFF 1 FC198 0 1
49279 0x243E Block 0 0xFFFFFFFF 1 FC142 0 1
49281 0x2440 Events 0 1 1 FC126 1 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-73


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49282 0x2441 Targets 0 2 1 FC101 1 1
Trip Bus 3
49284 0x2443 Function 0 4 1 FC100 0 1
49285 0x2444 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49287 0x2446 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49289 0x2448 Input 3 0 0xFFFFFFFF 1 FC142 0 1
49291 0x244A Input 4 0 0xFFFFFFFF 1 FC142 0 1
49293 0x244C Input 5 0 0xFFFFFFFF 1 FC142 0 1
49295 0x244E Input 6 0 0xFFFFFFFF 1 FC142 0 1
49297 0x2450 Input 7 0 0xFFFFFFFF 1 FC142 0 1
49299 0x2452 Input 8 0 0xFFFFFFFF 1 FC142 0 1
49301 0x2454 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49303 0x2456 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49305 0x2458 Input 11 0 0xFFFFFFFF 1 FC142 0 1
49307 0x245A Input 12 0 0xFFFFFFFF 1 FC142 0 1
49309 0x245C Input 13 0 0xFFFFFFFF 1 FC142 0 1
49311 0x245E Input 14 0 0xFFFFFFFF 1 FC142 0 1
49313 0x2460 Input 15 0 0xFFFFFFFF 1 FC142 0 1
49315 0x2462 Input 16 0 0xFFFFFFFF 1 FC142 0 1
49317 0x2464 Latching 0 1 1 FC126 0 1
49318 0x2465 Reset 0 0xFFFFFFFF 1 FC142 0 1
49320 0x2467 Pickup Delay 0 6000000 1 s F13 0 1
49322 0x2469 Dropout Delay 0 6000000 1 s F13 0 1
49324 0x246B Relays 0 0xFFFFFFFF 1 FC198 0 1
49326 0x246D Block 0 0xFFFFFFFF 1 FC142 0 1
49328 0x246F Events 0 1 1 FC126 1 1
49329 0x2470 Targets 0 2 1 FC101 1 1
Trip Bus 4
49331 0x2472 Function 0 4 1 FC100 0 1
49332 0x2473 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49334 0x2475 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49336 0x2477 Input 3 0 0xFFFFFFFF 1 FC142 0 1
49338 0x2479 Input 4 0 0xFFFFFFFF 1 FC142 0 1
49340 0x247B Input 5 0 0xFFFFFFFF 1 FC142 0 1
49342 0x247D Input 6 0 0xFFFFFFFF 1 FC142 0 1
49344 0x247F Input 7 0 0xFFFFFFFF 1 FC142 0 1
49346 0x2481 Input 8 0 0xFFFFFFFF 1 FC142 0 1
49348 0x2483 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49350 0x2485 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49352 0x2487 Input 11 0 0xFFFFFFFF 1 FC142 0 1
49354 0x2489 Input 12 0 0xFFFFFFFF 1 FC142 0 1
49356 0x248B Input 13 0 0xFFFFFFFF 1 FC142 0 1
49358 0x248D Input 14 0 0xFFFFFFFF 1 FC142 0 1
49360 0x248F Input 15 0 0xFFFFFFFF 1 FC142 0 1
49362 0x2491 Input 16 0 0xFFFFFFFF 1 FC142 0 1
49364 0x2493 Latching 0 1 1 FC126 0 1

11-74 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49365 0x2494 Reset 0 0xFFFFFFFF 1 FC142 0 1
49367 0x2496 Pickup Delay 0 6000000 1 s F13 0 1
49369 0x2498 Dropout Delay 0 6000000 1 s F13 0 1
49371 0x249A Relays 0 0xFFFFFFFF 1 FC198 0 1
49373 0x249C Block 0 0xFFFFFFFF 1 FC142 0 1
49375 0x249E Events 0 1 1 FC126 1 1
49376 0x249F Targets 0 2 1 FC101 1 1
Trip Bus 5
49378 0x24A1 Function 0 4 1 FC100 0 1
49379 0x24A2 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49381 0x24A4 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49383 0x24A6 Input 3 0 0xFFFFFFFF 1 FC142 0 1
49385 0x24A8 Input 4 0 0xFFFFFFFF 1 FC142 0 1
49387 0x24AA Input 5 0 0xFFFFFFFF 1 FC142 0 1
49389 0x24AC Input 6 0 0xFFFFFFFF 1 FC142 0 1
49391 0x24AE Input 7 0 0xFFFFFFFF 1 FC142 0 1
49393 0x24B0 Input 8 0 0xFFFFFFFF 1 FC142 0 1
49395 0x24B2 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49397 0x24B4 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49399 0x24B6 Input 11 0 0xFFFFFFFF 1 FC142 0 1
49401 0x24B8 Input 12 0 0xFFFFFFFF 1 FC142 0 1
49403 0x24BA Input 13 0 0xFFFFFFFF 1 FC142 0 1
49405 0x24BC Input 14 0 0xFFFFFFFF 1 FC142 0 1
49407 0x24BE Input 15 0 0xFFFFFFFF 1 FC142 0 1
49409 0x24C0 Input 16 0 0xFFFFFFFF 1 FC142 0 1
49411 0x24C2 Latching 0 1 1 FC126 0 1
49412 0x24C3 Reset 0 0xFFFFFFFF 1 FC142 0 1
49414 0x24C5 Pickup Delay 0 6000000 1 s F13 0 1
49416 0x24C7 Dropout Delay 0 6000000 1 s F13 0 1
49418 0x24C9 Relays 0 0xFFFFFFFF 1 FC198 0 1
49420 0x24CB Block 0 0xFFFFFFFF 1 FC142 0 1
49422 0x24CD Events 0 1 1 FC126 1 1
49423 0x24CE Targets 0 2 1 FC101 1 1
Trip Bus 6
49425 0x24D0 Function 0 4 1 FC100 0 1
49426 0x24D1 Input 1 0 0xFFFFFFFF 1 FC142 0 1
49428 0x24D3 Input 2 0 0xFFFFFFFF 1 FC142 0 1
49430 0x24D5 Input 3 0 0xFFFFFFFF 1 FC142 0 1
49432 0x24D7 Input 4 0 0xFFFFFFFF 1 FC142 0 1
49434 0x24D9 Input 5 0 0xFFFFFFFF 1 FC142 0 1
49436 0x24DB Input 6 0 0xFFFFFFFF 1 FC142 0 1
49438 0x24DD Input 7 0 0xFFFFFFFF 1 FC142 0 1
49440 0x24DF Input 8 0 0xFFFFFFFF 1 FC142 0 1
49442 0x24E1 Input 9 0 0xFFFFFFFF 1 FC142 0 1
49444 0x24E3 Input 10 0 0xFFFFFFFF 1 FC142 0 1
49446 0x24E5 Input 11 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-75


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49448 0x24E7 Input 12 0 0xFFFFFFFF 1 FC142 0 1
49450 0x24E9 Input 13 0 0xFFFFFFFF 1 FC142 0 1
49452 0x24EB Input 14 0 0xFFFFFFFF 1 FC142 0 1
49454 0x24ED Input 15 0 0xFFFFFFFF 1 FC142 0 1
49456 0x24EF Input 16 0 0xFFFFFFFF 1 FC142 0 1
49458 0x24F1 Latching 0 1 1 FC126 0 1
49459 0x24F2 Reset 0 0xFFFFFFFF 1 FC142 0 1
49461 0x24F4 Pickup Delay 0 6000000 1 s F13 0 1
49463 0x24F6 Dropout Delay 0 6000000 1 s F13 0 1
49465 0x24F8 Relays 0 0xFFFFFFFF 1 FC198 0 1
49467 0x24FA Block 0 0xFFFFFFFF 1 FC142 0 1
49469 0x24FC Events 0 1 1 FC126 1 1
49470 0x24FD Targets 0 2 1 FC101 1 1
Breaker Failure 1 Setup
49490 0x2511 Function 0 4 1 FC262 0 1
49492 0x2513 PH Retrip Superv Pickup 50 30000 1 x CT F3 1000 1
49493 0x2514 NTRL Retrip Superv 50 30000 1 x CT F3 1000 1
Pickup
49494 0x2515 Supervision 0 2 1 FC263 0 1
49495 0x2516 Breaker Closed 0 0xFFFFFFFF 1 FC142 0 1
49497 0x2518 T1 Pickup Delay 0 6000000 1 s F13 120 1
49499 0x251A T2 Pickup Delay 0 6000000 1 s F13 120 1
49501 0x251C T3 Pickup Delay 0 6000000 1 s F13 120 1
49503 0x251E Phase Highset Pickup 50 30000 1 x CT F3 1000 1
49504 0x251F Neutral Highset Pickup 50 30000 1 x CT F3 1000 1
49505 0x2520 Lowset Delay 0 6000000 1 s F13 0 1
49507 0x2522 Phase Lowset Pickup 50 30000 1 x CT F3 1000 1
49508 0x2523 Neutral Lowset Pickup 50 30000 1 x CT F3 1000 1
49509 0x2524 Dropout Delay 0 6000000 1 s F13 100 1
49511 0x2526 Relays 0 0xFFFFFFFF 1 FC198 0 1
49513 0x2528 Block 0 0xFFFFFFFF 1 FC142 0 1
49515 0x252A Events 0 1 1 FC126 1 1
49516 0x252B Targets 0 2 1 FC101 1 1
Breaker Failure 1 Initiate
49530 0x2539 External Initiate 0 0xFFFFFFFF 1 FC142 0 1
49532 0x253B Initiate IN1 0 0xFFFFFFFF 1 FC142 0x802C02 1
49534 0x253D Initiate IN2 0 0xFFFFFFFF 1 FC142 0x802E02 1
49536 0x253F Initiate IN3 0 0xFFFFFFFF 1 FC142 0x803202 1
49538 0x2541 Initiate IN4 0 0xFFFFFFFF 1 FC142 0x803402 1
49540 0x2543 Initiate IN5 0 0xFFFFFFFF 1 FC142 0x803A02 1
49542 0x2545 Initiate IN6 0 0xFFFFFFFF 1 FC142 0x803C02 1
49544 0x2547 Initiate IN7 0 0xFFFFFFFF 1 FC142 0x803E02 1
49546 0x2549 Initiate IN8 0 0xFFFFFFFF 1 FC142 0x804002 1
49548 0x254B Initiate IN9 0 0xFFFFFFFF 1 FC142 0x804402 1
49550 0x254D Initiate IN10 0 0xFFFFFFFF 1 FC142 0x804C02 1
49552 0x254F Initiate IN11 0 0xFFFFFFFF 1 FC142 0 1

11-76 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49554 0x2551 Initiate IN12 0 0xFFFFFFFF 1 FC142 0 1
49556 0x2553 Initiate IN13 0 0xFFFFFFFF 1 FC142 0 1
49558 0x2555 Initiate IN14 0 0xFFFFFFFF 1 FC142 0 1
49560 0x2557 Initiate IN15 0 0xFFFFFFFF 1 FC142 0 1
Synchrocheck 1 Setup
49760 0x261F Function 0 1 1 FC126 0 1
49762 0x2621 Bus Volts Input 0x12 0x22 1 FC103A 0x12 1
49764 0x2623 Line Volts Input 0x12 0x22 1 FC103A 0x22 1
49765 0x2624 Max Freq Difference 1 500 1 Hz F2 20 1
49766 0x2625 Max Angle Difference 1 100 1 F0 20 1
49767 0x2626 Max Volt Difference 10 600000 1 V F10 2000 1
49769 0x2628 Max Freq Hysteresis 1 10 1 Hz F2 5 1
49773 0x262C Dead Source Perm 0 5 1 FC283 0 1
49774 0x262D Live Bus Volts Min 0 150 1 x VT F2 80 1
49775 0x262E Live Line Volts Min 0 150 1 x VT F2 80 1
49776 0x262F Dead Bus Volts Max 0 150 1 x VT F2 20 1
49777 0x2630 Dead Line Volts Max 0 150 1 x VT F2 20 1
49778 0x2631 Relays 0 0xFFFFFFFF 1 FC198 0 1
49780 0x2633 Block 0 0xFFFFFFFF 1 FC142 0 1
49782 0x2635 Events 0 1 1 FC126 1 1
49783 0x2636 Targets 0 2 1 FC101 1 1
Manual Close Blocking
49820 0x265B Function 0 4 1 FC100A 0 1
49821 0x265C Manual Cls Block Interval 0 6000000 1 s F13 5000 1
49823 0x265E Block Phase IOC 1 0 1 1 FC126A 0 1
49824 0x265F Block Phase IOC 2 0 1 1 FC126A 0 1
49825 0x2660 Block Neutral IOC 1 0 1 1 FC126A 0 1
49826 0x2661 Block Neutral IOC 2 0 1 1 FC126A 0 1
49827 0x2662 Block Ground IOC 1 0 1 1 FC126A 0 1
49828 0x2663 Block Sens Ground IOC 1 0 1 1 FC126A 0 1
49829 0x2664 Block Neg Sequence IOC 0 1 1 FC126A 0 1
1
49830 0x2665 Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
49831 0x2666 Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
49832 0x2667 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
49833 0x2668 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
49834 0x2669 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
49835 0x266A Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
49836 0x266B Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
49837 0x266C Select Setting Group 0 0xFFFF 1 FC132 65535 1
49838 0x266D Relays 0 0xFFFFFFFF 1 FC198 0 1
49840 0x266F Events 0 1 1 FC126 1 1
49841 0x2670 Targets 0 2 1 FC101 1 1
Cold Load Pickup
49860 0x2683 Function 0 4 1 FC100A 0 1
49862 0x2685 External Initiation 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-77


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49864 0x2687 Outage T Before Cold 0 6000000 1 s F13 1000000 1
Load
49866 0x2689 Cold Load T Before Reset 0 6000000 1 s F13 100000 1
49868 0x268B Block Phase IOC 1 0 1 1 FC126A 0 1
49869 0x268C Block Phase IOC 2 0 1 1 FC126A 0 1
49870 0x268D Block Neutral IOC 1 0 1 1 FC126A 0 1
49871 0x268E Block Neutral IOC 2 0 1 1 FC126A 0 1
49872 0x268F Block Ground IOC 1 0 1 1 FC126A 0 1
49873 0x2690 Block Sens Ground IOC 1 0 1 1 FC126A 0 1
49874 0x2691 Block Neg Sequence IOC 0 1 1 FC126A 0 1
1
49875 0x2692 Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
49876 0x2693 Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
49877 0x2694 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
49878 0x2695 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
49879 0x2696 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
49880 0x2697 Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
49881 0x2698 Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
49882 0x2699 Select Setting Group 0 0xFFFF 1 FC132 65535 1
49883 0x269A Relays 0 0xFFFFFFFF 1 FC198 0 1
49885 0x269C Block 0 0xFFFFFFFF 1 FC142 0 1
49887 0x269E Events 0 1 1 FC126 1 1
49888 0x269F Targets 0 2 1 FC101 1 1
Undervoltage Restoration
49900 0x26AB Function 0 4 1 FC100B 0 1
49901 0x26AC Initiation 0 4 1 FC279 0 1
49903 0x26AE Minimum Voltage 0 1250 1 x VT F13 900 1
49905 0x26B0 Restore Delay 0 6000000 1 s F13 10000 1
49907 0x26B2 Incomplete Sequence 1 10000 1 min F0 100 1
Time
49908 0x26B3 Synchrocheck 0 2 1 FC280 0 1
Supervision
49909 0x26B4 Relays 0 0xFFFFFFFF 1 FC198 0 1
49911 0x26B6 Block 0 0xFFFFFFFF 1 FC142 0 1
49913 0x26B8 Events 0 1 1 FC126 1 1
49914 0x26B9 Targets 0 2 1 FC101 1 1
Underfrequency Restoration
49930 0x26C9 Name 0 65535 1 F60_26 UF Restore 26
49943 0x26D6 Function 0 4 1 FC100B 0 1
49944 0x26D7 Initiation 0 5 1 FC287 0 1
49946 0x26D9 Minimum Voltage 0 1250 1 x VT F13 900 1
49948 0x26DB Minimum Frequency 2000 6500 1 Hz F2 5990 1
49949 0x26DC Restore Delay 0 6000000 1 s F13 10000 1
49951 0x26DE Incomplete Sequence 1 10000 1 min F0 100 1
Time
49952 0x26DF Synchrocheck 0 2 1 FC280 0 1
Supervision
49953 0x26E0 Relays 0 0xFFFFFFFF 1 FC198 0 1

11-78 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
49955 0x26E2 Block 0 0xFFFFFFFF 1 FC142 0 1
49957 0x26E4 Events 0 1 1 FC126 1 1
49958 0x26E5 Targets 0 2 1 FC101 1 1
Transfer Function Selection
49970 0x26F1 Function 0 3 1 FC284 0 1
Transfer Function Incomer 1
49990 0x2705 Inc 1 BKR Connected 0 0xFFFFFFFF 1 FC142 0 1
49992 0x2707 Inc 1 BKR Select To Trip 0 0xFFFFFFFF 1 FC142 0 1
49994 0x2709 Delay Select To Trip 0 6000000 1 s F13 0 1
49996 0x270B Inc 2 BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
49998 0x270D Tie-BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
50000 0x270F Tie-BKR Connected 0 0xFFFFFFFF 1 FC142 0 1
50002 0x2711 Inc 1 Transformer 0 0xFFFFFFFF 1 FC142 0 1
Lockout
50004 0x2713 Inc 1 Source Trip 0 0xFFFFFFFF 1 FC142 0 1
50006 0x2715 Timed UV On This Source 0 0xFFFFFFFF 1 FC142 0 1
50008 0x2717 Block Trip On Double Loss 0 1 1 FC126 0 1
50009 0x2718 Inc 1 BKR Closed 0 0xFFFFFFFF 1 FC142 0 1
50011 0x271A UV On Other Source 0 0xFFFFFFFF 1 FC142 0 1
50013 0x271C Delay Other Source 0 6000000 1 s F13 3000 1
50015 0x271E Inst UV On This Source 0 0xFFFFFFFF 1 FC142 0 1
50017 0x2720 Delay This Source 0 6000000 1 s F13 1000 1
50019 0x2722 Fault Current Pickup In 1 0 0xFFFFFFFF 1 FC142 0 1
50021 0x2724 Fault Current Pickup In 2 0 0xFFFFFFFF 1 FC142 0 1
50023 0x2726 Fault Current Pickup In 3 0 0xFFFFFFFF 1 FC142 0 1
50025 0x2728 Fault Current Pickup In 4 0 0xFFFFFFFF 1 FC142 0 1
50027 0x272A Fault Current Pickup In 5 0 0xFFFFFFFF 1 FC142 0 1
50029 0x272C Fault Current Pickup In 6 0 0xFFFFFFFF 1 FC142 0 1
50031 0x272E Block Transfer 0 0xFFFFFFFF 1 FC142 0 1
50033 0x2730 Events 0 1 1 FC126 1 1
50034 0x2731 Targets 0 2 1 FC101 1 1
Transfer Function Incomer 2
50035 0x2732 Inc 2 BKR Connected 0 0xFFFFFFFF 1 FC142 0 1
50037 0x2734 Inc 2 BKR Select To Trip 0 0xFFFFFFFF 1 FC142 0 1
50039 0x2736 Delay Select To Trip 0 6000000 1 s F13 0 1
50041 0x2738 Inc 1 BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
50043 0x273A Tie-BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
50045 0x273C Tie-BKR Connected 0 0xFFFFFFFF 1 FC142 0 1
50047 0x273E Inc 2 Transformer 0 0xFFFFFFFF 1 FC142 0 1
Lockout
50049 0x2740 Inc 2 Source Trip 0 0xFFFFFFFF 1 FC142 0 1
50051 0x2742 Timed UV On This Source 0 0xFFFFFFFF 1 FC142 0 1
50053 0x2744 Block Trip On Double Loss 0 1 1 FC126 0 1
50054 0x2745 Inc 2 BKR Closed 0 0xFFFFFFFF 1 FC142 0 1
50056 0x2747 UV On Other Source 0 0xFFFFFFFF 1 FC142 0 1
50058 0x2749 Delay Other Source 0 6000000 1 s F13 3000 1
50060 0x274B Inst UV On This Source 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-79


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
50062 0x274D Delay This Source 0 6000000 1 s F13 1000 1
50064 0x274F Fault Current Pickup In 1 0 0xFFFFFFFF 1 FC142 0 1
50066 0x2751 Fault Current Pickup In 2 0 0xFFFFFFFF 1 FC142 0 1
50068 0x2753 Fault Current Pickup In 3 0 0xFFFFFFFF 1 FC142 0 1
50070 0x2755 Fault Current Pickup In 4 0 0xFFFFFFFF 1 FC142 0 1
50072 0x2757 Fault Current Pickup In 5 0 0xFFFFFFFF 1 FC142 0 1
50074 0x2759 Fault Current Pickup In 6 0 0xFFFFFFFF 1 FC142 0 1
50076 0x275B Block Transfer 0 0xFFFFFFFF 1 FC142 0 1
50078 0x275D Events 0 1 1 FC126 1 1
50079 0x275E Targets 0 2 1 FC101 1 1
Transfer Function Bus Tie
50090 0x2769 Tie-BKR Connected 0 0xFFFFFFFF 1 FC142 0 1
50092 0x276B Tie-BKR Select To Trip 0 0xFFFFFFFF 1 FC142 0 1
50094 0x276D Delay Select To Trip 0 6000000 1 s F13 0 1
50096 0x276F Inc 1 BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
50098 0x2771 Inc 2 BKR Conn&Closed 0 0xFFFFFFFF 1 FC142 0 1
50100 0x2773 Tie-BKR Closed 0 0xFFFFFFFF 1 FC142 0 1
50102 0x2775 Close Tie-BKR from Inc 1 0 0xFFFFFFFF 1 FC142 0 1
50104 0x2777 Close Tie-BKR from Inc 2 0 0xFFFFFFFF 1 FC142 0 1
50107 0x277A Block Transfer 0 0xFFFFFFFF 1 FC142 0 1
50109 0x277C Events 0 1 1 FC126 1 1
50110 0x277D Targets 0 2 1 FC101 1 1
AR1 Setup
50130 0x2791 Function 0 1 1 FC126 0 1
50131 0x2792 Maximum Number Shots 1 4 1 F0 1 1
50132 0x2793 Block/Cancel 0 0xFFFFFFFF 1 FC142 0 1
50134 0x2795 Manual Close 0 0xFFFFFFFF 1 FC142 0 1
50136 0x2797 Blk Time Upon Manual Cls 0 6000000 1 s F13 10000 1
50138 0x2799 Breaker Closed 0 0xFFFFFFFF 1 FC142 0 1
50140 0x279B Breaker Opened 0 0xFFFFFFFF 1 FC142 0 1
50142 0x279D Rst Lockout On Manual 0 1 1 FC126A 0 1
Cls
50143 0x279E Rst Lockout If Bkr Closed 0 1 1 FC126A 0 1
50144 0x279F Rst Lockout Delay 0 6000000 1 s F13 60000 1
50146 0x27A1 Manual Reset From 0 0xFFFFFFFF 1 FC142 0 1
Lockout
50148 0x27A3 Add Delay 0 0xFFFFFFFF 1 FC142 0 1
50150 0x27A5 Delay 0 6000000 1 s F13 0 1
50152 0x27A7 Incomplete Sequence 0 6000000 1 s F13 5000 1
Time
50154 0x27A9 Reset Time 0 6000000 1 s F13 60000 1
50156 0x27AB Reduce Maximum To 1 0 0xFFFFFFFF 1 FC142 0 1
50158 0x27AD Reduce Maximum To 2 0 0xFFFFFFFF 1 FC142 0 1
50160 0x27AF Reduce Maximum To 3 0 0xFFFFFFFF 1 FC142 0 1
50162 0x27B1 Synchrocheck Superv 0 2 1 FC280 0 1
50163 0x27B2 Enabled Output Relays 0 0xFFFFFFFF 1 FC198 0 1
50165 0x27B4 In Progress Output Relays 0 0xFFFFFFFF 1 FC198 0 1

11-80 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
50167 0x27B6 Lockout Output Relays 0 0xFFFFFFFF 1 FC198 0 1
50169 0x27B8 Setup Events 0 1 1 FC126 1 1
AR1 Initiate
50180 0x27C3 External Initiate 0 0xFFFFFFFF 1 FC142 0 1
50182 0x27C5 Initiate IN1 0 0xFFFFFFFF 1 FC142 0x802C02 1
50184 0x27C7 Initiate IN2 0 0xFFFFFFFF 1 FC142 0x802E02 1
50186 0x27C9 Initiate IN3 0 0xFFFFFFFF 1 FC142 0x803202 1
50188 0x27CB Initiate IN4 0 0xFFFFFFFF 1 FC142 0x803402 1
50190 0x27CD Initiate IN5 0 0xFFFFFFFF 1 FC142 0x803A02 1
50192 0x27CF Initiate IN6 0 0xFFFFFFFF 1 FC142 0x803C02 1
50194 0x27D1 Initiate IN7 0 0xFFFFFFFF 1 FC142 0x803E02 1
50196 0x27D3 Initiate IN8 0 0xFFFFFFFF 1 FC142 0x804002 1
50198 0x27D5 Initiate IN9 0 0xFFFFFFFF 1 FC142 0x804402 1
50200 0x27D7 Initiate IN10 0 0xFFFFFFFF 1 FC142 0x804C02 1
50202 0x27D9 Initiate IN11 0 0xFFFFFFFF 1 FC142 0 1
50204 0x27DB Initiate IN12 0 0xFFFFFFFF 1 FC142 0 1
50206 0x27DD Initiate IN13 0 0xFFFFFFFF 1 FC142 0 1
50208 0x27DF Initiate IN14 0 0xFFFFFFFF 1 FC142 0 1
50210 0x27E1 Initiate IN15 0 0xFFFFFFFF 1 FC142 0 1
AR1 Shot 1
50230 0x27F5 Dead Time 1 100 6000000 1 s F13 1000 1
50232 0x27F7 Block Phase IOC 1 0 1 1 FC126A 0 1
50233 0x27F8 Block Phase IOC 2 0 1 1 FC126A 0 1
50234 0x27F9 Block Neutral IOC 1 0 1 1 FC126A 0 1
50235 0x27FA Block Neutral IOC 2 0 1 1 FC126A 0 1
50236 0x27FB Block Ground IOC 1 0 1 1 FC126A 0 1
50237 0x27FC Block Sens Ground IOC 1 0 1 1 FC126A 0 1
50238 0x27FD Block Neg Sequence IOC 0 1 1 FC126A 0 1
1
50239 0x27FE Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
50240 0x27FF Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
50241 0x2800 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
50242 0x2801 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
50243 0x2802 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
50244 0x2803 Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
50245 0x2804 Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
50246 0x2805 Select Setting Group 0 0xFFFF 1 FC132 65535 1
AR1 Shot 2
50247 0x2806 Dead Time 2 100 6000000 1 s F13 2000 1
50249 0x2808 Block Phase IOC 1 0 1 1 FC126A 0 1
50250 0x2809 Block Phase IOC 2 0 1 1 FC126A 0 1
50251 0x280A Block Neutral IOC 1 0 1 1 FC126A 0 1
50252 0x280B Block Neutral IOC 2 0 1 1 FC126A 0 1
50253 0x280C Block Ground IOC 1 0 1 1 FC126A 0 1
50254 0x280D Block Sens Ground IOC 1 0 1 1 FC126A 0 1
50255 0x280E Block Neg Sequence IOC 0 1 1 FC126A 0 1
1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-81


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
50256 0x280F Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
50257 0x2810 Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
50258 0x2811 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
50259 0x2812 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
50260 0x2813 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
50261 0x2814 Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
50262 0x2815 Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
50263 0x2816 Select Setting Group 0 0xFFFF 1 FC132 65535 1
AR1 Shot 3
50264 0x2817 Dead Time 3 100 6000000 1 s F13 3000 1
50266 0x2819 Block Phase IOC 1 0 1 1 FC126A 0 1
50267 0x281A Block Phase IOC 2 0 1 1 FC126A 0 1
50268 0x281B Block Neutral IOC 1 0 1 1 FC126A 0 1
50269 0x281C Block Neutral IOC 2 0 1 1 FC126A 0 1
50270 0x281D Block Ground IOC 1 0 1 1 FC126A 0 1
50271 0x281E Block Sens Ground IOC 1 0 1 1 FC126A 0 1
50272 0x281F Block Neg Sequence IOC 0 1 1 FC126A 0 1
1
50273 0x2820 Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
50274 0x2821 Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
50275 0x2822 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
50276 0x2823 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
50277 0x2824 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
50278 0x2825 Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
50279 0x2826 Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
50280 0x2827 Select Setting Group 0 0xFFFF 1 FC132 65535 1
AR1 Shot 4
50281 0x2828 Dead Time 4 100 6000000 1 s F13 4000 1
50283 0x282A Block Phase IOC 1 0 1 1 FC126A 0 1
50284 0x282B Block Phase IOC 2 0 1 1 FC126A 0 1
50285 0x282C Block Neutral IOC 1 0 1 1 FC126A 0 1
50286 0x282D Block Neutral IOC 2 0 1 1 FC126A 0 1
50287 0x282E Block Ground IOC 1 0 1 1 FC126A 0 1
50288 0x282F Block Sens Ground IOC 1 0 1 1 FC126A 0 1
50289 0x2830 Block Neg Sequence IOC 0 1 1 FC126A 0 1
1
50290 0x2831 Raise Phase TOC 1 PKP 0 100 1 % F0 0 1
50291 0x2832 Raise Phase TOC 2 PKP 0 100 1 % F0 0 1
50292 0x2833 Raise Neutral TOC 1 PKP 0 100 1 % F0 0 1
50293 0x2834 Raise Neutral TOC 2 PKP 0 100 1 % F0 0 1
50294 0x2835 Raise Ground TOC 1 PKP 0 100 1 % F0 0 1
50295 0x2836 Raise Sens Gnd TOC 1 PKP 0 100 1 % F0 0 1
50296 0x2837 Raise Neg Seq TOC 1 PKP 0 100 1 % F0 0 1
50297 0x2838 Select Setting Group 0 0xFFFF 1 FC132 65535 1
AR1 Rate Supervision
50310 0x2845 Function 0 2 1 FC267 0 1
50311 0x2846 Maximum Rate Per Hour 1 50 1 /hour F0 25 1

11-82 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
50312 0x2847 Relays 0 0xFFFFFFFF 1 FC198 0 1
50314 0x2849 Events 0 1 1 FC126 1 1
AR1 Current Supervision
50330 0x2859 Function 0 1 1 FC126 0 1
50332 0x285B 3 Shots For Current Above 50 30000 1 x CT F13 17000 1
50334 0x285D 2 Shots For Current Above 50 30000 1 x CT F13 18000 1
50336 0x285F 1 Shots For Current Above 50 30000 1 x CT F13 19000 1
50338 0x2861 Lockout For Current 50 30000 1 x CT F13 20000 1
Above
50340 0x2863 Lockout 0 1 1 FC126 0 1
50341 0x2864 Events 0 1 1 FC126 1 1
AR1 Zone Coordination
50360 0x2877 Function 0 1 1 FC126 0 1
50362 0x2879 Phase Current Pickup 50 30000 1 x CT F13 1000 1
50364 0x287B Neutral Current Pickup 50 30000 1 x CT F13 300 1
50366 0x287D Pickup Time 0 6000000 1 s F13 20 1
50368 0x287F Dropout Time 0 6000000 1 s F13 20 1
50370 0x2881 Events 0 1 1 FC126 1 1
VT Fuse Fail 1
50663 0x29A6 Function 0 4 1 FC100A 0 1
50665 0x29A8 Relays 0 0xFFFFFFFF 1 FC198 0 1
50667 0x29AA Events 0 1 1 FC126 1 1
50668 0x29AB Targets 0 2 1 FC101 1 1
VT Fuse Fail 2
50682 0x29B9 Function 0 4 1 FC100A 0 1
50684 0x29BB Relays 0 0xFFFFFFFF 1 FC198 0 1
50686 0x29BD Events 0 1 1 FC126 1 1
50687 0x29BE Targets 0 2 1 FC101 1 1
Security
50930 0x2AB1 Login 0 8 1 FC252 0 1
50931 0x2AB2 Logout 0 1 1 FC126B 0 1
50932 0x2AB3 Factory Service Mode 0 1 1 FC126 0 1
50933 0x2AB4 Load Factory Defaults 0 1 1 FC126B 0 1
50934 0x2AB5 Access Lockout 0 99 1 F0 3 1
50935 0x2AB6 Access Lockout Period 0 9999 1 min F0 3 1
50936 0x2AB7 Access Timeout 0 999 1 min F0 5 1
50937 0x2AB8 Password Complexity 0 1 1 FC126 0 1
50938 0x2AB9 Setpoint Access 0 0xFFFFFFFF 1 FC142 0 1
50940 0x2ABB Device Authentication 0 1 1 FC126B 1 1
50945 0x2AC0 Force Observer Logoff 0 1 1 FC126B 0 1
Supervisory Settings
51101 0x2B5C Lock Relay 0 1 1 FC126 0 1
51102 0x2B5D Administrator Forced 0 1 1 FC126B 0 1
Logout
51103 0x2B5E Operator Forced Logout 0 1 1 FC126B 0 1
51104 0x2B5F Clear Security Data 0 1 1 FC126B 0 1
Security - Radius

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-83


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
51200 0x2BBF Primary Radius IP Address 0 0xDFFFFFFE 1 F70 0 1
51203 0x2BC2 Primary Accounting Port 0 65535 1 F0 0 1
51204 0x2BC3 Vendor ID 0 65535 1 F0 2910 1
51205 0x2BC4 Radius Authentication 0 0 1 FC341 0 1
Method
51206 0x2BC5 Timeout 0 9999 1 F0 10 1
51207 0x2BC6 Retries 0 9999 1 F0 3 1
Modbus File Transfer Mode
52544 0x30FF Transfer Mode 0 1 1 FC324 0 1
Modbus File Transfer
52545 0x3100 Name of File To Read 0 65535 1 F60_80 Filename 80
Modbus File Transfer Values
52801 0x3200 Char Position in Block 0 4294967295 1 F10 0 1
52803 0x3202 Data Block Size 0 65535 1 F0 0 1
52804 0x3203 DataBlock 0 0 65535 1 F0 0 1
52805 0x3204 DataBlock 1 0 65535 1 F0 0 1
52806 0x3205 DataBlock 2 0 65535 1 F0 0 1
52807 0x3206 DataBlock 3 0 65535 1 F0 0 1
52808 0x3207 DataBlock 4 0 65535 1 F0 0 1
52809 0x3208 DataBlock 5 0 65535 1 F0 0 1
52810 0x3209 DataBlock 6 0 65535 1 F0 0 1
52811 0x320A DataBlock 7 0 65535 1 F0 0 1
52812 0x320B DataBlock 8 0 65535 1 F0 0 1
52813 0x320C DataBlock 9 0 65535 1 F0 0 1
52814 0x320D DataBlock 10 0 65535 1 F0 0 1
52815 0x320E DataBlock 11 0 65535 1 F0 0 1
52816 0x320F DataBlock 12 0 65535 1 F0 0 1
52817 0x3210 DataBlock 13 0 65535 1 F0 0 1
52818 0x3211 DataBlock 14 0 65535 1 F0 0 1
52819 0x3212 DataBlock 15 0 65535 1 F0 0 1
52820 0x3213 DataBlock 16 0 65535 1 F0 0 1
52821 0x3214 DataBlock 17 0 65535 1 F0 0 1
52822 0x3215 DataBlock 18 0 65535 1 F0 0 1
52823 0x3216 DataBlock 19 0 65535 1 F0 0 1
52824 0x3217 DataBlock 20 0 65535 1 F0 0 1
52825 0x3218 DataBlock 21 0 65535 1 F0 0 1
52826 0x3219 DataBlock 22 0 65535 1 F0 0 1
52827 0x321A DataBlock 23 0 65535 1 F0 0 1
52828 0x321B DataBlock 24 0 65535 1 F0 0 1
52829 0x321C DataBlock 25 0 65535 1 F0 0 1
52830 0x321D DataBlock 26 0 65535 1 F0 0 1
52831 0x321E DataBlock 27 0 65535 1 F0 0 1
52832 0x321F DataBlock 28 0 65535 1 F0 0 1
52833 0x3220 DataBlock 29 0 65535 1 F0 0 1
52834 0x3221 DataBlock 30 0 65535 1 F0 0 1
52835 0x3222 DataBlock 31 0 65535 1 F0 0 1

11-84 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
52836 0x3223 DataBlock 32 0 65535 1 F0 0 1
52837 0x3224 DataBlock 33 0 65535 1 F0 0 1
52838 0x3225 DataBlock 34 0 65535 1 F0 0 1
52839 0x3226 DataBlock 35 0 65535 1 F0 0 1
52840 0x3227 DataBlock 36 0 65535 1 F0 0 1
52841 0x3228 DataBlock 37 0 65535 1 F0 0 1
52842 0x3229 DataBlock 38 0 65535 1 F0 0 1
52843 0x322A DataBlock 39 0 65535 1 F0 0 1
52844 0x322B DataBlock 40 0 65535 1 F0 0 1
52845 0x322C DataBlock 41 0 65535 1 F0 0 1
52846 0x322D DataBlock 42 0 65535 1 F0 0 1
52847 0x322E DataBlock 43 0 65535 1 F0 0 1
52848 0x322F DataBlock 44 0 65535 1 F0 0 1
52849 0x3230 DataBlock 45 0 65535 1 F0 0 1
52850 0x3231 DataBlock 46 0 65535 1 F0 0 1
52851 0x3232 DataBlock 47 0 65535 1 F0 0 1
52852 0x3233 DataBlock 48 0 65535 1 F0 0 1
52853 0x3234 DataBlock 49 0 65535 1 F0 0 1
52854 0x3235 DataBlock 50 0 65535 1 F0 0 1
52855 0x3236 DataBlock 51 0 65535 1 F0 0 1
52856 0x3237 DataBlock 52 0 65535 1 F0 0 1
52857 0x3238 DataBlock 53 0 65535 1 F0 0 1
52858 0x3239 DataBlock 54 0 65535 1 F0 0 1
52859 0x323A DataBlock 55 0 65535 1 F0 0 1
52860 0x323B DataBlock 56 0 65535 1 F0 0 1
52861 0x323C DataBlock 57 0 65535 1 F0 0 1
52862 0x323D DataBlock 58 0 65535 1 F0 0 1
52863 0x323E DataBlock 59 0 65535 1 F0 0 1
52864 0x323F DataBlock 60 0 65535 1 F0 0 1
52865 0x3240 DataBlock 61 0 65535 1 F0 0 1
52866 0x3241 DataBlock 62 0 65535 1 F0 0 1
52867 0x3242 DataBlock 63 0 65535 1 F0 0 1
52868 0x3243 DataBlock 64 0 65535 1 F0 0 1
52869 0x3244 DataBlock 65 0 65535 1 F0 0 1
52870 0x3245 DataBlock 66 0 65535 1 F0 0 1
52871 0x3246 DataBlock 67 0 65535 1 F0 0 1
52872 0x3247 DataBlock 68 0 65535 1 F0 0 1
52873 0x3248 DataBlock 69 0 65535 1 F0 0 1
52874 0x3249 DataBlock 70 0 65535 1 F0 0 1
52875 0x324A DataBlock 71 0 65535 1 F0 0 1
52876 0x324B DataBlock 72 0 65535 1 F0 0 1
52877 0x324C DataBlock 73 0 65535 1 F0 0 1
52878 0x324D DataBlock 74 0 65535 1 F0 0 1
52879 0x324E DataBlock 75 0 65535 1 F0 0 1
52880 0x324F DataBlock 76 0 65535 1 F0 0 1
52881 0x3250 DataBlock 77 0 65535 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-85


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
52882 0x3251 DataBlock 78 0 65535 1 F0 0 1
52883 0x3252 DataBlock 79 0 65535 1 F0 0 1
52884 0x3253 DataBlock 80 0 65535 1 F0 0 1
52885 0x3254 DataBlock 81 0 65535 1 F0 0 1
52886 0x3255 DataBlock 82 0 65535 1 F0 0 1
52887 0x3256 DataBlock 83 0 65535 1 F0 0 1
52888 0x3257 DataBlock 84 0 65535 1 F0 0 1
52889 0x3258 DataBlock 85 0 65535 1 F0 0 1
52890 0x3259 DataBlock 86 0 65535 1 F0 0 1
52891 0x325A DataBlock 87 0 65535 1 F0 0 1
52892 0x325B DataBlock 88 0 65535 1 F0 0 1
52893 0x325C DataBlock 89 0 65535 1 F0 0 1
52894 0x325D DataBlock 90 0 65535 1 F0 0 1
52895 0x325E DataBlock 91 0 65535 1 F0 0 1
52896 0x325F DataBlock 92 0 65535 1 F0 0 1
52897 0x3260 DataBlock 93 0 65535 1 F0 0 1
52898 0x3261 DataBlock 94 0 65535 1 F0 0 1
52899 0x3262 DataBlock 95 0 65535 1 F0 0 1
52900 0x3263 DataBlock 96 0 65535 1 F0 0 1
52901 0x3264 DataBlock 97 0 65535 1 F0 0 1
52902 0x3265 DataBlock 98 0 65535 1 F0 0 1
52903 0x3266 DataBlock 99 0 65535 1 F0 0 1
52904 0x3267 DataBlock 100 0 65535 1 F0 0 1
52905 0x3268 DataBlock 101 0 65535 1 F0 0 1
52906 0x3269 DataBlock 102 0 65535 1 F0 0 1
52907 0x326A DataBlock 103 0 65535 1 F0 0 1
52908 0x326B DataBlock 104 0 65535 1 F0 0 1
52909 0x326C DataBlock 105 0 65535 1 F0 0 1
52910 0x326D DataBlock 106 0 65535 1 F0 0 1
52911 0x326E DataBlock 107 0 65535 1 F0 0 1
52912 0x326F DataBlock 108 0 65535 1 F0 0 1
52913 0x3270 DataBlock 109 0 65535 1 F0 0 1
52914 0x3271 DataBlock 110 0 65535 1 F0 0 1
52915 0x3272 DataBlock 111 0 65535 1 F0 0 1
52916 0x3273 DataBlock 112 0 65535 1 F0 0 1
52917 0x3274 DataBlock 113 0 65535 1 F0 0 1
52918 0x3275 DataBlock 114 0 65535 1 F0 0 1
52919 0x3276 DataBlock 115 0 65535 1 F0 0 1
52920 0x3277 DataBlock 116 0 65535 1 F0 0 1
52921 0x3278 DataBlock 117 0 65535 1 F0 0 1
52922 0x3279 DataBlock 118 0 65535 1 F0 0 1
52923 0x327A DataBlock 119 0 65535 1 F0 0 1
52924 0x327B DataBlock 120 0 65535 1 F0 0 1
52925 0x327C DataBlock 121 0 65535 1 F0 0 1
Phase TOC 1
52953 0x3298 Function 0 4 1 FC100 0 1

11-86 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
52955 0x329A Input 0 1 1 FC256 0 1
52956 0x329B Pickup 50 30000 1 x CT F13 1000 1
52958 0x329D Curve 0 21 1 FC161 2 1
52959 0x329E TDM 5 60000 1 F2 100 1
52960 0x329F Reset 0 1 1 FC166 0 1
52961 0x32A0 Voltage Restraint 0 1 1 FC126 0 1
52962 0x32A1 Direction 0 2 1 FC164 0 1
52963 0x32A2 Relays 0 0xFFFFFFFF 1 FC198 0 1
52965 0x32A4 Block 0 0xFFFFFFFF 1 FC142 0 1
52967 0x32A6 Events 0 1 1 FC126 1 1
52968 0x32A7 Targets 0 2 1 FC101 1 1
Phase TOC 2
52986 0x32B9 Function 0 4 1 FC100 0 1
52988 0x32BB Input 0 1 1 FC256 0 1
52989 0x32BC Pickup 50 30000 1 x CT F13 1000 1
52991 0x32BE Curve 0 21 1 FC161 2 1
52992 0x32BF TDM 5 60000 1 F2 100 1
52993 0x32C0 Reset 0 1 1 FC166 0 1
52994 0x32C1 Voltage Restraint 0 1 1 FC126 0 1
52995 0x32C2 Direction 0 2 1 FC164 0 1
52996 0x32C3 Relays 0 0xFFFFFFFF 1 FC198 0 1
52998 0x32C5 Block 0 0xFFFFFFFF 1 FC142 0 1
53000 0x32C7 Events 0 1 1 FC126 1 1
53001 0x32C8 Targets 0 2 1 FC101 1 1
Phase IOC 1
53063 0x3306 Function 0 4 1 FC100 0 1
53065 0x3308 Input 0 1 1 FC256 0 1
53066 0x3309 Pickup 50 30000 1 x CT F13 1000 1
53068 0x330B Direction 0 2 1 FC164 0 1
53069 0x330C Pickup Delay 0 6000000 1 s F13 0 1
53071 0x330E Dropout Delay 0 6000000 1 s F13 0 1
53073 0x3310 Relays 0 0xFFFFFFFF 1 FC198 0 1
53075 0x3312 Block 0 0xFFFFFFFF 1 FC142 0 1
53077 0x3314 Events 0 1 1 FC126 1 1
53078 0x3315 Targets 0 2 1 FC101 1 1
Phase IOC 2
53096 0x3327 Function 0 4 1 FC100 0 1
53098 0x3329 Input 0 1 1 FC256 0 1
53099 0x332A Pickup 50 30000 1 x CT F13 1000 1
53101 0x332C Direction 0 2 1 FC164 0 1
53102 0x332D Pickup Delay 0 6000000 1 s F13 0 1
53104 0x332F Dropout Delay 0 6000000 1 s F13 0 1
53106 0x3331 Relays 0 0xFFFFFFFF 1 FC198 0 1
53108 0x3333 Block 0 0xFFFFFFFF 1 FC142 0 1
53110 0x3335 Events 0 1 1 FC126 1 1
53111 0x3336 Targets 0 2 1 FC101 1 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-87


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Phase DirOC
53173 0x3374 Function 0 1 1 FC126 0 1
53175 0x3376 ECA 0 359 1 F0 30 1
53176 0x3377 Polarizing V Threshold 50 3000 1 x VT F3 700 1
53177 0x3378 REV When V Mem Exp 0 1 1 FC126B 0 1
53178 0x3379 Block 0 0xFFFFFFFF 1 FC142 0 1
53180 0x337B Events 0 1 1 FC126 1 1
53181 0x337C Targets 0 2 1 FC101 1 1
Neutral TOC 1
53213 0x339C Function 0 4 1 FC100 0 1
53215 0x339E Input 0 1 1 FC256 0 1
53216 0x339F Pickup 50 30000 1 x CT F13 1000 1
53218 0x33A1 Curve 0 21 1 FC161 2 1
53219 0x33A2 TDM 5 60000 1 F2 100 1
53220 0x33A3 Reset 0 1 1 FC265 0 1
53221 0x33A4 Direction 0 2 1 FC164 0 1
53222 0x33A5 Relays 0 0xFFFFFFFF 1 FC198 0 1
53224 0x33A7 Block 0 0xFFFFFFFF 1 FC142 0 1
53226 0x33A9 Events 0 1 1 FC126 1 1
53227 0x33AA Targets 0 2 1 FC101 1 1
Neutral TOC 2
53245 0x33BC Function 0 4 1 FC100 0 1
53247 0x33BE Input 0 1 1 FC256 0 1
53248 0x33BF Pickup 50 30000 1 x CT F13 1000 1
53250 0x33C1 Curve 0 21 1 FC161 2 1
53251 0x33C2 TDM 5 60000 1 F2 100 1
53252 0x33C3 Reset 0 1 1 FC265 0 1
53253 0x33C4 Direction 0 2 1 FC164 0 1
53254 0x33C5 Relays 0 0xFFFFFFFF 1 FC198 0 1
53256 0x33C7 Block 0 0xFFFFFFFF 1 FC142 0 1
53258 0x33C9 Events 0 1 1 FC126 1 1
53259 0x33CA Targets 0 2 1 FC101 1 1
Neutral IOC 1
53293 0x33EC Function 0 4 1 FC100 0 1
53296 0x33EF Pickup 50 30000 1 x CT F13 1000 1
53298 0x33F1 Direction 0 2 1 FC164 0 1
53299 0x33F2 Pickup Delay 0 6000000 1 s F13 0 1
53301 0x33F4 Dropout Delay 0 6000000 1 s F13 0 1
53303 0x33F6 Relays 0 0xFFFFFFFF 1 FC198 0 1
53305 0x33F8 Block 0 0xFFFFFFFF 1 FC142 0 1
53307 0x33FA Events 0 1 1 FC126 1 1
53308 0x33FB Targets 0 2 1 FC101 1 1
Neutral IOC 2
53326 0x340D Function 0 4 1 FC100 0 1
53329 0x3410 Pickup 50 30000 1 x CT F13 1000 1
53331 0x3412 Direction 0 2 1 FC164 0 1

11-88 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
53332 0x3413 Pickup Delay 0 6000000 1 s F13 0 1
53334 0x3415 Dropout Delay 0 6000000 1 s F13 0 1
53336 0x3417 Relays 0 0xFFFFFFFF 1 FC198 0 1
53338 0x3419 Block 0 0xFFFFFFFF 1 FC142 0 1
53340 0x341B Events 0 1 1 FC126 1 1
53341 0x341C Targets 0 2 1 FC101 1 1
Neutral Directional OC
53373 0x343C Function 0 1 1 FC126 0 1
53375 0x343E Polarizing Mode 1 3 1 FC156 1 1
53376 0x343F Polarizing Voltage 0 1 1 FC272 0 1
53377 0x3440 Pos-Seq Restraint 0 500 1 F3 63 1
53379 0x3442 Forward ECA -90 90 1 F20 75 1
53380 0x3443 Forward Limit Angle 40 90 1 F0 90 1
53381 0x3444 Forward Pickup 50 30000 1 x CT F3 50 1
53382 0x3445 Reverse Limit Angle 40 90 1 F0 90 1
53383 0x3446 Reverse Pickup 50 30000 1 x CT F3 50 1
53384 0x3447 Block 0 0xFFFFFFFF 1 FC142 0 1
53386 0x3449 Events 0 1 1 FC126 1 1
53387 0x344A Targets 0 2 1 FC101 1 1
Ground TOC 1
53413 0x3464 Function 0 4 1 FC100 0 1
53415 0x3466 Input 0 1 1 FC256 0 1
53416 0x3467 Pickup 50 30000 1 x CT F13 1000 1
53418 0x3469 Curve 0 21 1 FC161 2 1
53419 0x346A TDM 5 60000 1 F2 100 1
53420 0x346B Reset 0 1 1 FC265 0 1
53421 0x346C Direction 0 2 1 FC164 0 1
53422 0x346D Relays 0 0xFFFFFFFF 1 FC198 0 1
53424 0x346F Block 0 0xFFFFFFFF 1 FC142 0 1
53426 0x3471 Events 0 1 1 FC126 1 1
53427 0x3472 Targets 0 2 1 FC101 1 1
Ground IOC 1
53553 0x34F0 Function 0 4 1 FC100 0 1
53556 0x34F3 Pickup 50 30000 1 x CT F13 1000 1
53558 0x34F5 Direction 0 2 1 FC164 0 1
53559 0x34F6 Pickup Delay 0 6000000 1 s F13 0 1
53561 0x34F8 Dropout Delay 0 6000000 1 s F13 0 1
53563 0x34FA Relays 0 0xFFFFFFFF 1 FC198 0 1
53565 0x34FC Block 0 0xFFFFFFFF 1 FC142 0 1
53567 0x34FE Events 0 1 1 FC126 1 1
53568 0x34FF Targets 0 2 1 FC101 1 1
Ground Directional OC
53703 0x3586 Function 0 1 1 FC126 0 1
53705 0x3588 Polarizing Mode 1 3 1 FC156 1 1
53706 0x3589 Polarizing Voltage 0 1 1 FC272 0 1
53708 0x358B Forward ECA -90 90 1 F20 75 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-89


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
53709 0x358C Forward Limit Angle 40 90 1 F0 90 1
53710 0x358D Forward Pickup 50 30000 1 x CT F3 50 1
53711 0x358E Reverse Limit Angle 40 90 1 F0 90 1
53712 0x358F Reverse Pickup 50 30000 1 x CT F3 50 1
53713 0x3590 Block 0 0xFFFFFFFF 1 FC142 0 1
53715 0x3592 Events 0 1 1 FC126 1 1
53716 0x3593 Targets 0 2 1 FC101 1 1
Sensitive Ground TOC 1
53743 0x35AE Function 0 4 1 FC100 0 1
53745 0x35B0 Input 0 1 1 FC256 0 1
53746 0x35B1 Pickup 5 3000 1 x CT F13 1000 1
53748 0x35B3 Curve 0 21 1 FC161 2 1
53749 0x35B4 TDM 5 60000 1 F2 100 1
53750 0x35B5 Reset 0 1 1 FC265 0 1
53751 0x35B6 Direction 0 2 1 FC164 0 1
53752 0x35B7 Relays 0 0xFFFFFFFF 1 FC198 0 1
53754 0x35B9 Block 0 0xFFFFFFFF 1 FC142 0 1
53756 0x35BB Events 0 1 1 FC126 1 1
53757 0x35BC Targets 0 2 1 FC101 1 1
Sensitive Ground TOC 2
53775 0x35CE Function 0 4 1 FC100 0 1
53777 0x35D0 Input 0 1 1 FC256 0 1
53778 0x35D1 Pickup 5 3000 1 x CT F13 1000 1
53780 0x35D3 Curve 0 21 1 FC161 2 1
53781 0x35D4 TDM 5 60000 1 F2 100 1
53782 0x35D5 Reset 0 1 1 FC265 0 1
53783 0x35D6 Direction 0 2 1 FC164 0 1
53784 0x35D7 Relays 0 0xFFFFFFFF 1 FC198 0 1
53786 0x35D9 Block 0 0xFFFFFFFF 1 FC142 0 1
53788 0x35DB Events 0 1 1 FC126 1 1
53789 0x35DC Targets 0 2 1 FC101 1 1
Sensitive Ground IOC 1
53823 0x35FE Function 0 4 1 FC100 0 1
53826 0x3601 Pickup 5 3000 1 x CT F13 1000 1
53828 0x3603 Direction 0 2 1 FC164 0 1
53829 0x3604 Pickup Delay 0 6000000 1 s F13 0 1
53831 0x3606 Dropout Delay 0 6000000 1 s F13 0 1
53833 0x3608 Relays 0 0xFFFFFFFF 1 FC198 0 1
53835 0x360A Block 0 0xFFFFFFFF 1 FC142 0 1
53837 0x360C Events 0 1 1 FC126 1 1
53838 0x360D Targets 0 2 1 FC101 1 1
Restricted Ground Fault 1
53903 0x364E Function 0 4 1 FC100 0 1
53905 0x3650 Pickup 50 30000 1 x CT F3 300 1
53906 0x3651 Slope 0 100 1 % F0 50 1
53907 0x3652 Pickup Delay 0 6000000 1 s F13 100 1

11-90 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
53909 0x3654 Gnd Curr Superv 0 1 1 FC126 0 1
53910 0x3655 Gnd Curr Superv Level 50 30000 1 x CT F3 300 1
53911 0x3656 Relays 0 0xFFFFFFFF 1 FC198 0 1
53913 0x3658 Block 0 0xFFFFFFFF 1 FC142 0 1
53915 0x365A Events 0 1 1 FC126 1 1
53916 0x365B Targets 0 2 1 FC101 1 1
Negative Sequence TOC 1
54013 0x36BC Function 0 4 1 FC100 0 1
54015 0x36BE Pickup 50 30000 1 x CT F13 1000 1
54017 0x36C0 Curve 0 21 1 FC161 2 1
54018 0x36C1 TDM 5 60000 1 F2 100 1
54019 0x36C2 Reset 0 1 1 FC265 0 1
54020 0x36C3 Direction 0 2 1 FC164 0 1
54021 0x36C4 Relays 0 0xFFFFFFFF 1 FC198 0 1
54023 0x36C6 Block 0 0xFFFFFFFF 1 FC142 0 1
54025 0x36C8 Events 0 1 1 FC126 1 1
54026 0x36C9 Targets 0 2 1 FC101 1 1
Negative Sequence IOC 1
54093 0x370C Function 0 4 1 FC100 0 1
54096 0x370F Pickup 50 30000 1 x CT F13 1000 1
54098 0x3711 Direction 0 2 1 FC164 0 1
54099 0x3712 Pickup Delay 0 6000000 1 s F13 0 1
54101 0x3714 Dropout Delay 0 6000000 1 s F13 0 1
54103 0x3716 Relays 0 0xFFFFFFFF 1 FC198 0 1
54105 0x3718 Block 0 0xFFFFFFFF 1 FC142 0 1
54107 0x371A Events 0 1 1 FC126 1 1
54108 0x371B Targets 0 2 1 FC101 1 1
Broken Conductor
54173 0x375C Function 0 4 1 FC100 0 1
54175 0x375E I_2/I_1 Ratio 200 1000 1 % F1 200 1
54176 0x375F I_1 Min 5 100 1 x CT F2 10 1
54177 0x3760 I_1 Max 5 500 1 x CT F2 150 1
54178 0x3761 Pickup Delay 0 6000000 1 s F13 20000 1
54180 0x3763 Relays 0 0xFFFFFFFF 1 FC198 0 1
54182 0x3765 Block 0 0xFFFFFFFF 1 FC142 0 1
54184 0x3767 Events 0 1 1 FC126 1 1
54185 0x3768 Targets 0 2 1 FC101 1 1
Cable Thermal Model
54200 0x3777 Function 0 4 1 FC100 0 1
54202 0x3779 Pickup 50 30000 1 x CT F13 1000 1
54204 0x377B Alarm 700 1100 1 % F1 800 1
54205 0x377C Heat Time Constant (tH) 30 6000 1 min F1 60 1
54206 0x377D Cool Time Constant (tC) 100 600 1 x tH F2 200 1
54207 0x377E Relays 0 0xFFFFFFFF 1 FC198 0 1
54209 0x3780 Block 0 0xFFFFFFFF 1 FC142 0 1
54211 0x3782 Events 0 1 1 FC126 1 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-91


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
54212 0x3783 Targets 0 2 1 FC101 1 1
PUV 1
54243 0x37A2 Function 0 4 1 FC100 0 1
54246 0x37A5 Mode 0 1 1 FC260 0 1
54247 0x37A6 Pickup 0 150 1 x VT F2 100 1
54248 0x37A7 Minimum Voltage 0 150 1 x VT F2 20 1
54249 0x37A8 Phases for Operation 0 2 1 FC261 0 1
54250 0x37A9 Undervoltage Curves 0 1 1 FC131 0 1
54251 0x37AA Pickup Delay 0 6000000 1 s F13 1000 1
54253 0x37AC Relays 0 0xFFFFFFFF 1 FC198 0 1
54255 0x37AE Block 0 0xFFFFFFFF 1 FC142 0 1
54257 0x37B0 Events 0 1 1 FC126 1 1
54258 0x37B1 Targets 0 2 1 FC101 1 1
PUV 2
54276 0x37C3 Function 0 4 1 FC100 0 1
54279 0x37C6 Mode 0 1 1 FC260 0 1
54280 0x37C7 Pickup 0 150 1 x VT F2 100 1
54281 0x37C8 Minimum Voltage 0 150 1 x VT F2 20 1
54282 0x37C9 Phases for Operation 0 2 1 FC261 0 1
54283 0x37CA Undervoltage Curves 0 1 1 FC131 0 1
54284 0x37CB Pickup Delay 0 6000000 1 s F13 1000 1
54286 0x37CD Relays 0 0xFFFFFFFF 1 FC198 0 1
54288 0x37CF Block 0 0xFFFFFFFF 1 FC142 0 1
54290 0x37D1 Events 0 1 1 FC126 1 1
54291 0x37D2 Targets 0 2 1 FC101 1 1
Aux UV 1
54323 0x37F2 Function 0 4 1 FC100 0 1
54326 0x37F5 Pickup 0 150 1 x VT F2 100 1
54327 0x37F6 Minimum Voltage 0 150 1 x VT F2 20 1
54328 0x37F7 Undervoltage Curves 0 1 1 FC131 0 1
54329 0x37F8 Pickup Delay 0 6000000 1 s F13 1000 1
54331 0x37FA Relays 0 0xFFFFFFFF 1 FC198 0 1
54333 0x37FC Block 0 0xFFFFFFFF 1 FC142 0 1
54335 0x37FE Events 0 1 1 FC126 1 1
54336 0x37FF Targets 0 2 1 FC101 1 1
Aux UV 2
54354 0x3811 Function 0 4 1 FC100 0 1
54357 0x3814 Pickup 0 150 1 x VT F2 100 1
54358 0x3815 Minimum Voltage 0 150 1 x VT F2 20 1
54359 0x3816 Undervoltage Curves 0 1 1 FC131 0 1
54360 0x3817 Pickup Delay 0 6000000 1 s F13 1000 1
54362 0x3819 Relays 0 0xFFFFFFFF 1 FC198 0 1
54364 0x381B Block 0 0xFFFFFFFF 1 FC142 0 1
54366 0x381D Events 0 1 1 FC126 1 1
54367 0x381E Targets 0 2 1 FC101 1 1
POV 1

11-92 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
54403 0x3842 Function 0 4 1 FC100 0 1
54406 0x3845 Mode 0 1 1 FC260 0 1
54407 0x3846 Pickup 2 300 1 x VT F2 150 1
54408 0x3847 Phases for Operation 0 2 1 FC261 0 1
54409 0x3848 Pickup Delay 0 6000000 1 s F13 1000 1
54411 0x384A Dropout Delay 0 6000000 1 s F13 1000 1
54413 0x384C Relays 0 0xFFFFFFFF 1 FC198 0 1
54415 0x384E Block 0 0xFFFFFFFF 1 FC142 0 1
54417 0x3850 Events 0 1 1 FC126 1 1
54418 0x3851 Targets 0 2 1 FC101 1 1
POV 2
54436 0x3863 Function 0 4 1 FC100 0 1
54439 0x3866 Mode 0 1 1 FC260 0 1
54440 0x3867 Pickup 2 300 1 x VT F2 150 1
54441 0x3868 Phases for Operation 0 2 1 FC261 0 1
54442 0x3869 Pickup Delay 0 6000000 1 s F13 1000 1
54444 0x386B Dropout Delay 0 6000000 1 s F13 1000 1
54446 0x386D Relays 0 0xFFFFFFFF 1 FC198 0 1
54448 0x386F Block 0 0xFFFFFFFF 1 FC142 0 1
54450 0x3871 Events 0 1 1 FC126 1 1
54451 0x3872 Targets 0 2 1 FC101 1 1
Aux OV
54483 0x3892 Function 0 4 1 FC100 0 1
54486 0x3895 Pickup 0 300 1 x VT F2 150 1
54487 0x3896 Pickup Delay 0 6000000 1 s F13 1000 1
54489 0x3898 Dropout Delay 0 6000000 1 s F13 1000 1
54491 0x389A Relays 0 0xFFFFFFFF 1 FC198 0 1
54493 0x389C Block 0 0xFFFFFFFF 1 FC142 0 1
54495 0x389E Events 0 1 1 FC126 1 1
54496 0x389F Targets 0 2 1 FC101 1 1
Neutral OverVoltage 1
54523 0x38BA Function 0 4 1 FC100 0 1
54526 0x38BD Pickup 2 300 1 x VT F2 30 1
54527 0x38BE Curves 7 19 1 FC161A 7 1
54528 0x38BF Pickup Delay 0 6000000 1 s F13 1000 1
54530 0x38C1 Dropout Delay 0 6000000 1 s F13 1000 1
54532 0x38C3 Relays 0 0xFFFFFFFF 1 FC198 0 1
54534 0x38C5 Block 0 0xFFFFFFFF 1 FC142 0 1
54536 0x38C7 Events 0 1 1 FC126 1 1
54537 0x38C8 Targets 0 2 1 FC101 1 1
Negative Sequence OverVoltage 1
54603 0x390A Function 0 4 1 FC100 0 1
54605 0x390C Pickup 0 300 1 x VT F2 100 1
54606 0x390D Pickup Delay 0 6000000 1 s F13 1000 1
54608 0x390F Dropout Delay 0 6000000 1 s F13 1000 1
54610 0x3911 Relays 0 0xFFFFFFFF 1 FC198 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-93


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
54612 0x3913 Block 0 0xFFFFFFFF 1 FC142 0 1
54614 0x3915 Events 0 1 1 FC126 1 1
54615 0x3916 Targets 0 2 1 FC101 1 1
Directional Power 1
54673 0x3950 Function 0 4 1 FC100 0 1
54675 0x3952 RCA 0 359 1 F0 0 1
54676 0x3953 Calibration 0 95 5 F2 0 1
54677 0x3954 Stage 1 SMIN -1200 1200 1 x Rated F23 100 1
54678 0x3955 Stage 1 Delay 0 6000000 1 s F13 500 1
54680 0x3957 Stage 2 SMIN -1200 1200 1 x Rated F23 100 1
54681 0x3958 Stage 2 Delay 0 6000000 1 s F13 20000 1
54683 0x395A Relays 0 0xFFFFFFFF 1 FC198 0 1
54685 0x395C Block 0 0xFFFFFFFF 1 FC142 0 1
54687 0x395E Events 0 1 1 FC126 1 1
54688 0x395F Targets 0 2 1 FC101 1 1
Directional Power 2
54706 0x3971 Function 0 4 1 FC100 0 1
54708 0x3973 RCA 0 359 1 F0 0 1
54709 0x3974 Calibration 0 95 5 F2 0 1
54710 0x3975 Stage 1 SMIN -1200 1200 1 x Rated F23 100 1
54711 0x3976 Stage 1 Delay 0 6000000 1 s F13 500 1
54713 0x3978 Stage 2 SMIN -1200 1200 1 x Rated F23 100 1
54714 0x3979 Stage 2 Delay 0 6000000 1 s F13 20000 1
54716 0x397B Relays 0 0xFFFFFFFF 1 FC198 0 1
54718 0x397D Block 0 0xFFFFFFFF 1 FC142 0 1
54720 0x397F Events 0 1 1 FC126 1 1
54721 0x3980 Targets 0 2 1 FC101 1 1
Wattmetric Ground Fault 1
54740 0x3993 Function 0 4 1 FC100 0 1
54742 0x3995 Voltage 0 1 1 FC272A 0 1
54743 0x3996 Operating Voltage Pickup 2 300 1 x VT F2 20 1
54744 0x3997 Current 0 1 1 FC276 0 1
54745 0x3998 Operating Current Pickup 2 30000 1 x CT F3 60 1
54746 0x3999 Power Pickup 1 1200 1 CTxVT F3 100 1
54747 0x399A Reference Power Pickup 1 1200 1 CTxVT F3 500 1
54748 0x399B ECA 0 359 1 Lag F0 0 1
54749 0x399C Power Pickup Delay 0 6000000 1 s F13 200 1
54751 0x399E Curve 5 19 1 FC161B 7 1
54752 0x399F Multiplier 1 200 1 s F2 100 1
54753 0x39A0 Relays 0 0xFFFFFFFF 1 FC198 0 1
54755 0x39A2 Block 0 0xFFFFFFFF 1 FC142 0 1
54757 0x39A4 Events 0 1 1 FC126 1 1
54758 0x39A5 Targets 0 2 1 FC101 1 1
Underfrequency 1
54813 0x39DC Function 0 4 1 FC100 0 1
54814 0x39DD Frequency Input 0x12 0x22 1 FC103A 0x12 1

11-94 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
54815 0x39DE Pickup 2000 6500 1 Hz F2 5900 1
54816 0x39DF Pickup Delay 0 6000000 1 s F13 2000 1
54818 0x39E1 Dropout Delay 0 6000000 1 s F13 2000 1
54820 0x39E3 Minimum Voltage 0 1250 1 x VT F13 700 1
54822 0x39E5 Minimum Current 0 30000 1 x CT F13 200 1
54824 0x39E7 Relays 0 0xFFFFFFFF 1 FC198 0 1
54826 0x39E9 Block 0 0xFFFFFFFF 1 FC142 0 1
54828 0x39EB Events 0 1 1 FC126 1 1
54829 0x39EC Targets 0 2 1 FC101 1 1
Underfrequency 2
54847 0x39FE Function 0 4 1 FC100 0 1
54848 0x39FF Frequency Input 0x12 0x22 1 FC103A 0x12 1
54849 0x3A00 Pickup 2000 6500 1 Hz F2 5900 1
54850 0x3A01 Pickup Delay 0 6000000 1 s F13 2000 1
54852 0x3A03 Dropout Delay 0 6000000 1 s F13 2000 1
54854 0x3A05 Minimum Voltage 0 1250 1 x VT F13 700 1
54856 0x3A07 Minimum Current 0 30000 1 x CT F13 200 1
54858 0x3A09 Relays 0 0xFFFFFFFF 1 FC198 0 1
54860 0x3A0B Block 0 0xFFFFFFFF 1 FC142 0 1
54862 0x3A0D Events 0 1 1 FC126 1 1
54863 0x3A0E Targets 0 2 1 FC101 1 1
Underfrequency 3
54881 0x3A20 Function 0 4 1 FC100 0 1
54882 0x3A21 Frequency Input 0x12 0x22 1 FC103A 0x12 1
54883 0x3A22 Pickup 2000 6500 1 Hz F2 5900 1
54884 0x3A23 Pickup Delay 0 6000000 1 s F13 2000 1
54886 0x3A25 Dropout Delay 0 6000000 1 s F13 2000 1
54888 0x3A27 Minimum Voltage 0 1250 1 x VT F13 700 1
54890 0x3A29 Minimum Current 0 30000 1 x CT F13 200 1
54892 0x3A2B Relays 0 0xFFFFFFFF 1 FC198 0 1
54894 0x3A2D Block 0 0xFFFFFFFF 1 FC142 0 1
54896 0x3A2F Events 0 1 1 FC126 1 1
54897 0x3A30 Targets 0 2 1 FC101 1 1
Underfrequency 4
54915 0x3A42 Function 0 4 1 FC100 0 1
54916 0x3A43 Frequency Input 0x12 0x22 1 FC103A 0x12 1
54917 0x3A44 Pickup 2000 6500 1 Hz F2 5900 1
54918 0x3A45 Pickup Delay 0 6000000 1 s F13 2000 1
54920 0x3A47 Dropout Delay 0 6000000 1 s F13 2000 1
54922 0x3A49 Minimum Voltage 0 1250 1 x VT F13 700 1
54924 0x3A4B Minimum Current 0 30000 1 x CT F13 200 1
54926 0x3A4D Relays 0 0xFFFFFFFF 1 FC198 0 1
54928 0x3A4F Block 0 0xFFFFFFFF 1 FC142 0 1
54930 0x3A51 Events 0 1 1 FC126 1 1
54931 0x3A52 Targets 0 2 1 FC101 1 1
Overfrequency 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-95


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
54963 0x3A72 Function 0 4 1 FC100 0 1
54964 0x3A73 Frequency Input 0x12 0x22 1 FC103A 0x12 1
54965 0x3A74 Pickup 2000 6500 1 Hz F2 6050 1
54966 0x3A75 Pickup Delay 0 6000000 1 s F13 5000 1
54968 0x3A77 Dropout Delay 0 6000000 1 s F13 5000 1
54970 0x3A79 Minimum Voltage 0 1250 1 x VT F13 300 1
54972 0x3A7B Relays 0 0xFFFFFFFF 1 FC198 0 1
54974 0x3A7D Block 0 0xFFFFFFFF 1 FC142 0 1
54976 0x3A7F Events 0 1 1 FC126 1 1
54977 0x3A80 Targets 0 2 1 FC101 1 1
Overfrequency 2
54995 0x3A92 Function 0 4 1 FC100 0 1
54996 0x3A93 Frequency Input 0x12 0x22 1 FC103A 0x12 1
54997 0x3A94 Pickup 2000 6500 1 Hz F2 6050 1
54998 0x3A95 Pickup Delay 0 6000000 1 s F13 5000 1
55000 0x3A97 Dropout Delay 0 6000000 1 s F13 5000 1
55002 0x3A99 Minimum Voltage 0 1250 1 x VT F13 300 1
55004 0x3A9B Relays 0 0xFFFFFFFF 1 FC198 0 1
55006 0x3A9D Block 0 0xFFFFFFFF 1 FC142 0 1
55008 0x3A9F Events 0 1 1 FC126 1 1
55009 0x3AA0 Targets 0 2 1 FC101 1 1
Frequency Rate Of Change 1
55043 0x3AC2 Function 0 4 1 FC100 0 1
55044 0x3AC3 Frequency Input 0x12 0x22 1 FC103A 0x12 1
55045 0x3AC4 Trend 0 2 1 FC253 0 1
55046 0x3AC5 Pickup 10 1500 1 Hz/sec F2 50 1
55047 0x3AC6 Pickup Delay 0 6000000 1 s F13 2000 1
55049 0x3AC8 Minimum Frequency 2000 8000 1 Hz F2 4500 1
55050 0x3AC9 Maximum Frequency 2000 8000 1 Hz F2 6500 1
55051 0x3ACA Minimum Voltage 0 1250 1 x VT F13 700 1
55053 0x3ACC Minimum Current 0 30000 1 x CT F13 200 1
55055 0x3ACE Relays 0 0xFFFFFFFF 1 FC198 0 1
55057 0x3AD0 Block 0 0xFFFFFFFF 1 FC142 0 1
55059 0x3AD2 Events 0 1 1 FC126 1 1
55060 0x3AD3 Targets 0 2 1 FC101 1 1
Load Encroachment
55180 0x3B4B Function 0 1 1 FC126 0 1
55182 0x3B4D Minimum Voltage 0 150 1 x VT F2 20 1
55183 0x3B4E Reach 2 25000 1 ohms F2 500 1
55184 0x3B4F Angle 5 50 1 F0 30 1
55185 0x3B50 Pickup Delay 0 6000000 1 s F13 0 1
55187 0x3B52 Dropout Delay 0 6000000 1 s F13 0 1
55189 0x3B54 Block 0 0xFFFFFFFF 1 FC142 0 1
55191 0x3B56 Relays 0 0xFFFFFFFF 1 FC198 0 1
55193 0x3B58 Events 0 1 1 FC126 1 1
55194 0x3B59 Targets 0 2 1 FC101 0 1

11-96 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Negative Sequence Directional OC
55210 0x3B69 Function 0 1 1 FC126 0 1
55212 0x3B6B Pos-Seq Restraint 0 500 1 F3 63 1
55213 0x3B6C Forward ECA 0 90 1 Lag F0 75 1
55214 0x3B6D Forward Limit Angle 40 90 1 F0 90 1
55215 0x3B6E Forward Pickup 50 30000 1 x CT F3 50 1
55216 0x3B6F Reverse Limit Angle 40 90 1 F0 90 1
55217 0x3B70 Reverse Pickup 50 30000 1 x CT F3 50 1
55218 0x3B71 Block 0 0xFFFFFFFF 1 FC142 0 1
55220 0x3B73 Events 0 1 1 FC126 1 1
55221 0x3B74 Targets 0 2 1 FC101 1 1
Sensitive Ground Directional OC
55240 0x3B87 Function 0 1 1 FC126 0 1
55242 0x3B89 Polarizing Mode 1 3 1 FC156 1 1
55243 0x3B8A Polarizing Voltage 0 1 1 FC272 0 1
55244 0x3B8B Forward ECA -90 90 1 F20 75 1
55245 0x3B8C Forward Limit Angle 40 90 1 F0 90 1
55246 0x3B8D Forward Pickup 5 3000 1 x CT F3 50 1
55247 0x3B8E Reverse Limit Angle 40 90 1 F0 90 1
55248 0x3B8F Reverse Pickup 5 3000 1 x CT F3 50 1
55249 0x3B90 Block 0 0xFFFFFFFF 1 FC142 0 1
55251 0x3B92 Events 0 1 1 FC126 1 1
55252 0x3B93 Targets 0 2 1 FC101 1 1
DNP Protocol
56080 0x3ECF DNP Channel 1 Port 0 2 1 FC239 0 1
56081 0x3ED0 DNP Channel 2 Port 0 2 1 FC239 0 1
56082 0x3ED1 DNP Address 0 65519 1 F0 65519 1
56083 0x3ED2 DNP Client Address 1 0 0xFFFFFFFF 1 F70 0 1
56085 0x3ED4 DNP Client Address 2 0 0xFFFFFFFF 1 F70 0 1
56087 0x3ED6 DNP TCP/UDP Port 1 1 65535 1 F0 20000 1
56088 0x3ED7 DNP TCP/UDP Port 2 1 65535 1 F0 20000 1
56089 0x3ED8 DNP Unsol Resp Function 0 1 1 FC126 0 1
56090 0x3ED9 DNP Unsol Resp Timeout 0 60 1 s F0 5 1
56091 0x3EDA Unsol Resp Max Retries 1 255 1 F0 10 1
56092 0x3EDB DNP Unsol Resp Dest 0 65519 1 F0 1 1
Addr
56093 0x3EDC DNP Time Sync IIN Period 1 10080 1 min F0 1140 1
56094 0x3EDD DNP Message Fragment 30 2048 1 F0 240 1
Size
56095 0x3EDE Object 1 Default Variation 1 2 1 FC231 2 1
56096 0x3EDF Object 2 Default Variation 1 2 1 FC232 2 1
56097 0x3EE0 Object 20 Default 1 6 1 FC233 1 1
Variation
56098 0x3EE1 Object 21 Default 1 10 1 FC234 1 1
Variation
56099 0x3EE2 Object 22 Default 1 6 1 FC235 1 1
Variation

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-97


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56100 0x3EE3 Object 23 Default 1 6 1 FC236 2 1
Variation
56101 0x3EE4 Object 30 Default 1 5 1 FC237 1 1
Variation
56102 0x3EE5 Object 32 Default 1 7 1 FC238 1 1
Variation
56103 0x3EE6 TCP Connection Timeout 10 300 1 s F0 120 1
Binary Input Points
56120 0x3EF7 Point 0 Entry 0 0xFFFFFFFF 1 FC142 0 1
56122 0x3EF9 Point 1 Entry 0 0xFFFFFFFF 1 FC142 0 1
56124 0x3EFB Point 2 Entry 0 0xFFFFFFFF 1 FC142 0 1
56126 0x3EFD Point 3 Entry 0 0xFFFFFFFF 1 FC142 0 1
56128 0x3EFF Point 4 Entry 0 0xFFFFFFFF 1 FC142 0 1
56130 0x3F01 Point 5 Entry 0 0xFFFFFFFF 1 FC142 0 1
56132 0x3F03 Point 6 Entry 0 0xFFFFFFFF 1 FC142 0 1
56134 0x3F05 Point 7 Entry 0 0xFFFFFFFF 1 FC142 0 1
56136 0x3F07 Point 8 Entry 0 0xFFFFFFFF 1 FC142 0 1
56138 0x3F09 Point 9 Entry 0 0xFFFFFFFF 1 FC142 0 1
56140 0x3F0B Point 10 Entry 0 0xFFFFFFFF 1 FC142 0 1
56142 0x3F0D Point 11 Entry 0 0xFFFFFFFF 1 FC142 0 1
56144 0x3F0F Point 12 Entry 0 0xFFFFFFFF 1 FC142 0 1
56146 0x3F11 Point 13 Entry 0 0xFFFFFFFF 1 FC142 0 1
56148 0x3F13 Point 14 Entry 0 0xFFFFFFFF 1 FC142 0 1
56150 0x3F15 Point 15 Entry 0 0xFFFFFFFF 1 FC142 0 1
56152 0x3F17 Point 16 Entry 0 0xFFFFFFFF 1 FC142 0 1
56154 0x3F19 Point 17 Entry 0 0xFFFFFFFF 1 FC142 0 1
56156 0x3F1B Point 18 Entry 0 0xFFFFFFFF 1 FC142 0 1
56158 0x3F1D Point 19 Entry 0 0xFFFFFFFF 1 FC142 0 1
56160 0x3F1F Point 20 Entry 0 0xFFFFFFFF 1 FC142 0 1
56162 0x3F21 Point 21 Entry 0 0xFFFFFFFF 1 FC142 0 1
56164 0x3F23 Point 22 Entry 0 0xFFFFFFFF 1 FC142 0 1
56166 0x3F25 Point 23 Entry 0 0xFFFFFFFF 1 FC142 0 1
56168 0x3F27 Point 24 Entry 0 0xFFFFFFFF 1 FC142 0 1
56170 0x3F29 Point 25 Entry 0 0xFFFFFFFF 1 FC142 0 1
56172 0x3F2B Point 26 Entry 0 0xFFFFFFFF 1 FC142 0 1
56174 0x3F2D Point 27 Entry 0 0xFFFFFFFF 1 FC142 0 1
56176 0x3F2F Point 28 Entry 0 0xFFFFFFFF 1 FC142 0 1
56178 0x3F31 Point 29 Entry 0 0xFFFFFFFF 1 FC142 0 1
56180 0x3F33 Point 30 Entry 0 0xFFFFFFFF 1 FC142 0 1
56182 0x3F35 Point 31 Entry 0 0xFFFFFFFF 1 FC142 0 1
56184 0x3F37 Point 32 Entry 0 0xFFFFFFFF 1 FC142 0 1
56186 0x3F39 Point 33 Entry 0 0xFFFFFFFF 1 FC142 0 1
56188 0x3F3B Point 34 Entry 0 0xFFFFFFFF 1 FC142 0 1
56190 0x3F3D Point 35 Entry 0 0xFFFFFFFF 1 FC142 0 1
56192 0x3F3F Point 36 Entry 0 0xFFFFFFFF 1 FC142 0 1
56194 0x3F41 Point 37 Entry 0 0xFFFFFFFF 1 FC142 0 1
56196 0x3F43 Point 38 Entry 0 0xFFFFFFFF 1 FC142 0 1

11-98 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56198 0x3F45 Point 39 Entry 0 0xFFFFFFFF 1 FC142 0 1
56200 0x3F47 Point 40 Entry 0 0xFFFFFFFF 1 FC142 0 1
56202 0x3F49 Point 41 Entry 0 0xFFFFFFFF 1 FC142 0 1
56204 0x3F4B Point 42 Entry 0 0xFFFFFFFF 1 FC142 0 1
56206 0x3F4D Point 43 Entry 0 0xFFFFFFFF 1 FC142 0 1
56208 0x3F4F Point 44 Entry 0 0xFFFFFFFF 1 FC142 0 1
56210 0x3F51 Point 45 Entry 0 0xFFFFFFFF 1 FC142 0 1
56212 0x3F53 Point 46 Entry 0 0xFFFFFFFF 1 FC142 0 1
56214 0x3F55 Point 47 Entry 0 0xFFFFFFFF 1 FC142 0 1
56216 0x3F57 Point 48 Entry 0 0xFFFFFFFF 1 FC142 0 1
56218 0x3F59 Point 49 Entry 0 0xFFFFFFFF 1 FC142 0 1
56220 0x3F5B Point 50 Entry 0 0xFFFFFFFF 1 FC142 0 1
56222 0x3F5D Point 51 Entry 0 0xFFFFFFFF 1 FC142 0 1
56224 0x3F5F Point 52 Entry 0 0xFFFFFFFF 1 FC142 0 1
56226 0x3F61 Point 53 Entry 0 0xFFFFFFFF 1 FC142 0 1
56228 0x3F63 Point 54 Entry 0 0xFFFFFFFF 1 FC142 0 1
56230 0x3F65 Point 55 Entry 0 0xFFFFFFFF 1 FC142 0 1
56232 0x3F67 Point 56 Entry 0 0xFFFFFFFF 1 FC142 0 1
56234 0x3F69 Point 57 Entry 0 0xFFFFFFFF 1 FC142 0 1
56236 0x3F6B Point 58 Entry 0 0xFFFFFFFF 1 FC142 0 1
56238 0x3F6D Point 59 Entry 0 0xFFFFFFFF 1 FC142 0 1
56240 0x3F6F Point 60 Entry 0 0xFFFFFFFF 1 FC142 0 1
56242 0x3F71 Point 61 Entry 0 0xFFFFFFFF 1 FC142 0 1
56244 0x3F73 Point 62 Entry 0 0xFFFFFFFF 1 FC142 0 1
56246 0x3F75 Point 63 Entry 0 0xFFFFFFFF 1 FC142 0 1
56248 0x3F77 Point 64 Entry 0 0xFFFFFFFF 1 FC142 0 1
56250 0x3F79 Point 65 Entry 0 0xFFFFFFFF 1 FC142 0 1
56252 0x3F7B Point 66 Entry 0 0xFFFFFFFF 1 FC142 0 1
56254 0x3F7D Point 67 Entry 0 0xFFFFFFFF 1 FC142 0 1
56256 0x3F7F Point 68 Entry 0 0xFFFFFFFF 1 FC142 0 1
56258 0x3F81 Point 69 Entry 0 0xFFFFFFFF 1 FC142 0 1
56260 0x3F83 Point 70 Entry 0 0xFFFFFFFF 1 FC142 0 1
56262 0x3F85 Point 71 Entry 0 0xFFFFFFFF 1 FC142 0 1
56264 0x3F87 Point 72 Entry 0 0xFFFFFFFF 1 FC142 0 1
56266 0x3F89 Point 73 Entry 0 0xFFFFFFFF 1 FC142 0 1
56268 0x3F8B Point 74 Entry 0 0xFFFFFFFF 1 FC142 0 1
56270 0x3F8D Point 75 Entry 0 0xFFFFFFFF 1 FC142 0 1
56272 0x3F8F Point 76 Entry 0 0xFFFFFFFF 1 FC142 0 1
56274 0x3F91 Point 77 Entry 0 0xFFFFFFFF 1 FC142 0 1
56276 0x3F93 Point 78 Entry 0 0xFFFFFFFF 1 FC142 0 1
56278 0x3F95 Point 79 Entry 0 0xFFFFFFFF 1 FC142 0 1
56280 0x3F97 Point 80 Entry 0 0xFFFFFFFF 1 FC142 0 1
56282 0x3F99 Point 81 Entry 0 0xFFFFFFFF 1 FC142 0 1
56284 0x3F9B Point 82 Entry 0 0xFFFFFFFF 1 FC142 0 1
56286 0x3F9D Point 83 Entry 0 0xFFFFFFFF 1 FC142 0 1
56288 0x3F9F Point 84 Entry 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-99


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56290 0x3FA1 Point 85 Entry 0 0xFFFFFFFF 1 FC142 0 1
56292 0x3FA3 Point 86 Entry 0 0xFFFFFFFF 1 FC142 0 1
56294 0x3FA5 Point 87 Entry 0 0xFFFFFFFF 1 FC142 0 1
56296 0x3FA7 Point 88 Entry 0 0xFFFFFFFF 1 FC142 0 1
56298 0x3FA9 Point 89 Entry 0 0xFFFFFFFF 1 FC142 0 1
56300 0x3FAB Point 90 Entry 0 0xFFFFFFFF 1 FC142 0 1
56302 0x3FAD Point 91 Entry 0 0xFFFFFFFF 1 FC142 0 1
56304 0x3FAF Point 92 Entry 0 0xFFFFFFFF 1 FC142 0 1
56306 0x3FB1 Point 93 Entry 0 0xFFFFFFFF 1 FC142 0 1
56308 0x3FB3 Point 94 Entry 0 0xFFFFFFFF 1 FC142 0 1
56310 0x3FB5 Point 95 Entry 0 0xFFFFFFFF 1 FC142 0 1
Analog Input Point 0
56330 0x3FC9 Analog IP Point 0 Entry 0 33560 1 FC273 0 1
56331 0x3FCA Point 0 Scale Factor 1 9 1 FC229 4 1
56332 0x3FCB Point 0 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 1
56334 0x3FCD Analog IP Point 1 Entry 0 33560 1 FC273 0 1
56335 0x3FCE Point 1 Scale Factor 1 9 1 FC229 4 1
56336 0x3FCF Point 1 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 2
56338 0x3FD1 Analog IP Point 2 Entry 0 33560 1 FC273 0 1
56339 0x3FD2 Point 2 Scale Factor 1 9 1 FC229 4 1
56340 0x3FD3 Point 2 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 3
56342 0x3FD5 Analog IP Point 3 Entry 0 33560 1 FC273 0 1
56343 0x3FD6 Point 3 Scale Factor 1 9 1 FC229 4 1
56344 0x3FD7 Point 3 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 4
56346 0x3FD9 Analog IP Point 4 Entry 0 33560 1 FC273 0 1
56347 0x3FDA Point 4 Scale Factor 1 9 1 FC229 4 1
56348 0x3FDB Point 4 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 5
56350 0x3FDD Analog IP Point 5 Entry 0 33560 1 FC273 0 1
56351 0x3FDE Point 5 Scale Factor 1 9 1 FC229 4 1
56352 0x3FDF Point 5 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 6
56354 0x3FE1 Analog IP Point 6 Entry 0 33560 1 FC273 0 1
56355 0x3FE2 Point 6 Scale Factor 1 9 1 FC229 4 1
56356 0x3FE3 Point 6 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 7
56358 0x3FE5 Analog IP Point 7 Entry 0 33560 1 FC273 0 1
56359 0x3FE6 Point 7 Scale Factor 1 9 1 FC229 4 1
56360 0x3FE7 Point 7 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 8
56362 0x3FE9 Analog IP Point 8 Entry 0 33560 1 FC273 0 1
56363 0x3FEA Point 8 Scale Factor 1 9 1 FC229 4 1

11-100 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56364 0x3FEB Point 8 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 9
56366 0x3FED Analog IP Point 9 Entry 0 33560 1 FC273 0 1
56367 0x3FEE Point 9 Scale Factor 1 9 1 FC229 4 1
56368 0x3FEF Point 9 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 10
56370 0x3FF1 Analog IP Point 10 Entry 0 33560 1 FC273 0 1
56371 0x3FF2 Point 10 Scale Factor 1 9 1 FC229 4 1
56372 0x3FF3 Point 10 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 11
56374 0x3FF5 Analog IP Point 11 Entry 0 33560 1 FC273 0 1
56375 0x3FF6 Point 11 Scale Factor 1 9 1 FC229 4 1
56376 0x3FF7 Point 11 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 12
56378 0x3FF9 Analog IP Point 12 Entry 0 33560 1 FC273 0 1
56379 0x3FFA Point 12 Scale Factor 1 9 1 FC229 4 1
56380 0x3FFB Point 12 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 13
56382 0x3FFD Analog IP Point 13 Entry 0 33560 1 FC273 0 1
56383 0x3FFE Point 13 Scale Factor 1 9 1 FC229 4 1
56384 0x3FFF Point 13 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 14
56386 0x4001 Analog IP Point 14 Entry 0 33560 1 FC273 0 1
56387 0x4002 Point 14 Scale Factor 1 9 1 FC229 4 1
56388 0x4003 Point 14 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 15
56390 0x4005 Analog IP Point 15 Entry 0 33560 1 FC273 0 1
56391 0x4006 Point 15 Scale Factor 1 9 1 FC229 4 1
56392 0x4007 Point 15 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 16
56394 0x4009 Analog IP Point 16 Entry 0 33560 1 FC273 0 1
56395 0x400A Point 16 Scale Factor 1 9 1 FC229 4 1
56396 0x400B Point 16 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 17
56398 0x400D Analog IP Point 17 Entry 0 33560 1 FC273 0 1
56399 0x400E Point 17 Scale Factor 1 9 1 FC229 4 1
56400 0x400F Point 17 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 18
56402 0x4011 Analog IP Point 18 Entry 0 33560 1 FC273 0 1
56403 0x4012 Point 18 Scale Factor 1 9 1 FC229 4 1
56404 0x4013 Point 18 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 19
56406 0x4015 Analog IP Point 19 Entry 0 33560 1 FC273 0 1
56407 0x4016 Point 19 Scale Factor 1 9 1 FC229 4 1
56408 0x4017 Point 19 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 20

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-101


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56410 0x4019 Analog IP Point 20 Entry 0 33560 1 FC273 0 1
56411 0x401A Point 20 Scale Factor 1 9 1 FC229 4 1
56412 0x401B Point 20 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 21
56414 0x401D Analog IP Point 21 Entry 0 33560 1 FC273 0 1
56415 0x401E Point 21 Scale Factor 1 9 1 FC229 4 1
56416 0x401F Point 21 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 22
56418 0x4021 Analog IP Point 22 Entry 0 33560 1 FC273 0 1
56419 0x4022 Point 22 Scale Factor 1 9 1 FC229 4 1
56420 0x4023 Point 22 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 23
56422 0x4025 Analog IP Point 23 Entry 0 33560 1 FC273 0 1
56423 0x4026 Point 23 Scale Factor 1 9 1 FC229 4 1
56424 0x4027 Point 23 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 24
56426 0x4029 Analog IP Point 24 Entry 0 33560 1 FC273 0 1
56427 0x402A Point 24 Scale Factor 1 9 1 FC229 4 1
56428 0x402B Point 24 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 25
56430 0x402D Analog IP Point 25 Entry 0 33560 1 FC273 0 1
56431 0x402E Point 25 Scale Factor 1 9 1 FC229 4 1
56432 0x402F Point 25 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 26
56434 0x4031 Analog IP Point 26 Entry 0 33560 1 FC273 0 1
56435 0x4032 Point 26 Scale Factor 1 9 1 FC229 4 1
56436 0x4033 Point 26 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 27
56438 0x4035 Analog IP Point 27 Entry 0 33560 1 FC273 0 1
56439 0x4036 Point 27 Scale Factor 1 9 1 FC229 4 1
56440 0x4037 Point 27 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 28
56442 0x4039 Analog IP Point 28 Entry 0 33560 1 FC273 0 1
56443 0x403A Point 28 Scale Factor 1 9 1 FC229 4 1
56444 0x403B Point 28 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 29
56446 0x403D Analog IP Point 29 Entry 0 33560 1 FC273 0 1
56447 0x403E Point 29 Scale Factor 1 9 1 FC229 4 1
56448 0x403F Point 29 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 30
56450 0x4041 Analog IP Point 30 Entry 0 33560 1 FC273 0 1
56451 0x4042 Point 30 Scale Factor 1 9 1 FC229 4 1
56452 0x4043 Point 30 Deadband 1 100000000 1 F10 30000 1
Analog Input Point 31
56454 0x4045 Analog IP Point 31 Entry 0 33560 1 FC273 0 1
56455 0x4046 Point 31 Scale Factor 1 9 1 FC229 4 1

11-102 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56456 0x4047 Point 31 Deadband 1 100000000 1 F10 30000 1
Binary Output Point 0
56470 0x4055 Binary Output Point 0 ON 0 47 1 FC230 0 1
56471 0x4056 Binary Output Point 0 OFF 0 47 1 FC230 0 1
Binary Output Point 1
56472 0x4057 Binary Output Point 1 ON 0 47 1 FC230 0 1
56473 0x4058 Binary Output Point 1 OFF 0 47 1 FC230 0 1
Binary Output Point 2
56474 0x4059 Binary Output Point 2 ON 0 47 1 FC230 0 1
56475 0x405A Binary Output Point 2 OFF 0 47 1 FC230 0 1
Binary Output Point 3
56476 0x405B Binary Output Point 3 ON 0 47 1 FC230 0 1
56477 0x405C Binary Output Point 3 OFF 0 47 1 FC230 0 1
Binary Output Point 4
56478 0x405D Binary Output Point 4 ON 0 47 1 FC230 0 1
56479 0x405E Binary Output Point 4 OFF 0 47 1 FC230 0 1
Binary Output Point 5
56480 0x405F Binary Output Point 5 ON 0 47 1 FC230 0 1
56481 0x4060 Binary Output Point 5 OFF 0 47 1 FC230 0 1
Binary Output Point 6
56482 0x4061 Binary Output Point 6 ON 0 47 1 FC230 0 1
56483 0x4062 Binary Output Point 6 OFF 0 47 1 FC230 0 1
Binary Output Point 7
56484 0x4063 Binary Output Point 7 ON 0 47 1 FC230 0 1
56485 0x4064 Binary Output Point 7 OFF 0 47 1 FC230 0 1
Binary Output Point 8
56486 0x4065 Binary Output Point 8 ON 0 47 1 FC230 0 1
56487 0x4066 Binary Output Point 8 OFF 0 47 1 FC230 0 1
Binary Output Point 9
56488 0x4067 Binary Output Point 9 ON 0 47 1 FC230 0 1
56489 0x4068 Binary Output Point 9 OFF 0 47 1 FC230 0 1
Binary Output Point 10
56490 0x4069 Binary Output Point 10 0 47 1 FC230 0 1
ON
56491 0x406A Bnry Output Point 10 OFF 0 47 1 FC230 0 1
Binary Output Point 11
56492 0x406B Binary Output Point 11 0 47 1 FC230 0 1
ON
56493 0x406C Bnry Output Point 11 OFF 0 47 1 FC230 0 1
Binary Output Point 12
56494 0x406D Binary Output Point 12 0 47 1 FC230 0 1
ON
56495 0x406E Bnry Output Point 12 OFF 0 47 1 FC230 0 1
Binary Output Point 13
56496 0x406F Binary Output Point 13 0 47 1 FC230 0 1
ON
56497 0x4070 Bnry Output Point 13 OFF 0 47 1 FC230 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-103


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Binary Output Point 14
56498 0x4071 Binary Output Point 14 0 47 1 FC230 0 1
ON
56499 0x4072 Bnry Output Point 14 OFF 0 47 1 FC230 0 1
Binary Output Point 15
56500 0x4073 Binary Output Point 15 0 47 1 FC230 0 1
ON
56501 0x4074 Bnry Output Point 15 OFF 0 47 1 FC230 0 1
IEC104 Protocol
56550 0x40A5 Channel 1 Port 0 1 1 FC239A 1 1
56551 0x40A6 Channel 2 Port 0 1 1 FC239A 1 1
56552 0x40A7 Common Address of 0 65535 1 F0 0 1
ASDU
56553 0x40A8 Client Address 1 0 0xFFFFFFFF 1 F70 0 1
56555 0x40AA Client Address 2 0 0xFFFFFFFF 1 F70 0 1
56557 0x40AC TCP Port Number 1 1 65535 1 F0 2404 1
56558 0x40AD TCP Port Number 2 1 65535 1 F0 2404 1
56559 0x40AE Cyclic Data Period 0 65535 1 s F0 60 1
56561 0x40B0 Object Info Addrs Bnry 0 16777215 1 F10 1000 1
56563 0x40B2 Object Info Addrs Analog 0 16777215 1 F10 2000 1
56565 0x40B4 Object Info Addrs Countrs 0 16777215 1 F10 3000 1
56567 0x40B6 Object Info Addrs Cmnd 0 16777215 1 F10 4000 1
56569 0x40B8 Object Info Analog Param 0 16777215 1 F10 5000 1
IEC103 Protocol
56590 0x40CD IEC103 Common ASDU 0 254 1 F0 0 1
Addrs
56591 0x40CE IEC103 Sync Timeout 0 1440 1 min F0 0 1
Binary Input Point 0
56610 0x40E1 Point 0 Func Type 0 255 1 F0 0 1
56611 0x40E2 Point 0 Info Num 0 255 1 F0 0 1
56612 0x40E3 Point 0 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 1
56624 0x40EF Point 1 Func Type 0 255 1 F0 0 1
56625 0x40F0 Point 1 Info Num 0 255 1 F0 0 1
56626 0x40F1 Point 1 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 2
56638 0x40FD Point 2 Func Type 0 255 1 F0 0 1
56639 0x40FE Point 2 Info Num 0 255 1 F0 0 1
56640 0x40FF Point 2 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 3
56652 0x410B Point 3 Func Type 0 255 1 F0 0 1
56653 0x410C Point 3 Info Num 0 255 1 F0 0 1
56654 0x410D Point 3 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 4
56666 0x4119 Point 4 Func Type 0 255 1 F0 0 1
56667 0x411A Point 4 Info Num 0 255 1 F0 0 1
56668 0x411B Point 4 0 0xFFFFFFFF 1 FC142 0 1

11-104 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Binary Input Point 5
56680 0x4127 Point 5 Func Type 0 255 1 F0 0 1
56681 0x4128 Point 5 Info Num 0 255 1 F0 0 1
56682 0x4129 Point 5 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 6
56694 0x4135 Point 6 Func Type 0 255 1 F0 0 1
56695 0x4136 Point 6 Info Num 0 255 1 F0 0 1
56696 0x4137 Point 6 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 7
56708 0x4143 Point 7 Func Type 0 255 1 F0 0 1
56709 0x4144 Point 7 Info Num 0 255 1 F0 0 1
56710 0x4145 Point 7 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 8
56722 0x4151 Point 8 Func Type 0 255 1 F0 0 1
56723 0x4152 Point 8 Info Num 0 255 1 F0 0 1
56724 0x4153 Point 8 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 9
56736 0x415F Point 9 Func Type 0 255 1 F0 0 1
56737 0x4160 Point 9 Info Num 0 255 1 F0 0 1
56738 0x4161 Point 9 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 10
56750 0x416D Point 10 Func Type 0 255 1 F0 0 1
56751 0x416E Point 10 Info Num 0 255 1 F0 0 1
56752 0x416F Point 10 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 11
56764 0x417B Point 11 Func Type 0 255 1 F0 0 1
56765 0x417C Point 11 Info Num 0 255 1 F0 0 1
56766 0x417D Point 11 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 12
56778 0x4189 Point 12 Func Type 0 255 1 F0 0 1
56779 0x418A Point 12 Info Num 0 255 1 F0 0 1
56780 0x418B Point 12 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 13
56792 0x4197 Point 13 Func Type 0 255 1 F0 0 1
56793 0x4198 Point 13 Info Num 0 255 1 F0 0 1
56794 0x4199 Point 13 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 14
56806 0x41A5 Point 14 Func Type 0 255 1 F0 0 1
56807 0x41A6 Point 14 Info Num 0 255 1 F0 0 1
56808 0x41A7 Point 14 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 15
56820 0x41B3 Point 15 Func Type 0 255 1 F0 0 1
56821 0x41B4 Point 15 Info Num 0 255 1 F0 0 1
56822 0x41B5 Point 15 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 16
56834 0x41C1 Point 16 Func Type 0 255 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-105


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
56835 0x41C2 Point 16 Info Num 0 255 1 F0 0 1
56836 0x41C3 Point 16 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 17
56848 0x41CF Point 17 Func Type 0 255 1 F0 0 1
56849 0x41D0 Point 17 Info Num 0 255 1 F0 0 1
56850 0x41D1 Point 17 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 18
56862 0x41DD Point 18 Func Type 0 255 1 F0 0 1
56863 0x41DE Point 18 Info Num 0 255 1 F0 0 1
56864 0x41DF Point 18 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 19
56876 0x41EB Point 19 Func Type 0 255 1 F0 0 1
56877 0x41EC Point 19 Info Num 0 255 1 F0 0 1
56878 0x41ED Point 19 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 20
56890 0x41F9 Point 20 Func Type 0 255 1 F0 0 1
56891 0x41FA Point 20 Info Num 0 255 1 F0 0 1
56892 0x41FB Point 20 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 21
56904 0x4207 Point 21 Func Type 0 255 1 F0 0 1
56905 0x4208 Point 21 Info Num 0 255 1 F0 0 1
56906 0x4209 Point 21 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 22
56918 0x4215 Point 22 Func Type 0 255 1 F0 0 1
56919 0x4216 Point 22 Info Num 0 255 1 F0 0 1
56920 0x4217 Point 22 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 23
56932 0x4223 Point 23 Func Type 0 255 1 F0 0 1
56933 0x4224 Point 23 Info Num 0 255 1 F0 0 1
56934 0x4225 Point 23 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 24
56946 0x4231 Point 24 Func Type 0 255 1 F0 0 1
56947 0x4232 Point 24 Info Num 0 255 1 F0 0 1
56948 0x4233 Point 24 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 25
56960 0x423F Point 25 Func Type 0 255 1 F0 0 1
56961 0x4240 Point 25 Info Num 0 255 1 F0 0 1
56962 0x4241 Point 25 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 26
56974 0x424D Point 26 Func Type 0 255 1 F0 0 1
56975 0x424E Point 26 Info Num 0 255 1 F0 0 1
56976 0x424F Point 26 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 27
56988 0x425B Point 27 Func Type 0 255 1 F0 0 1
56989 0x425C Point 27 Info Num 0 255 1 F0 0 1
56990 0x425D Point 27 0 0xFFFFFFFF 1 FC142 0 1

11-106 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Binary Input Point 28
57002 0x4269 Point 28 Func Type 0 255 1 F0 0 1
57003 0x426A Point 28 Info Num 0 255 1 F0 0 1
57004 0x426B Point 28 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 29
57016 0x4277 Point 29 Func Type 0 255 1 F0 0 1
57017 0x4278 Point 29 Info Num 0 255 1 F0 0 1
57018 0x4279 Point 29 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 30
57030 0x4285 Point 30 Func Type 0 255 1 F0 0 1
57031 0x4286 Point 30 Info Num 0 255 1 F0 0 1
57032 0x4287 Point 30 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 31
57044 0x4293 Point 31 Func Type 0 255 1 F0 0 1
57045 0x4294 Point 31 Info Num 0 255 1 F0 0 1
57046 0x4295 Point 31 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 32
57058 0x42A1 Point 32 Func Type 0 255 1 F0 0 1
57059 0x42A2 Point 32 Info Num 0 255 1 F0 0 1
57060 0x42A3 Point 32 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 33
57072 0x42AF Point 33 Func Type 0 255 1 F0 0 1
57073 0x42B0 Point 33 Info Num 0 255 1 F0 0 1
57074 0x42B1 Point 33 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 34
57086 0x42BD Point 34 Func Type 0 255 1 F0 0 1
57087 0x42BE Point 34 Info Num 0 255 1 F0 0 1
57088 0x42BF Point 34 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 35
57100 0x42CB Point 35 Func Type 0 255 1 F0 0 1
57101 0x42CC Point 35 Info Num 0 255 1 F0 0 1
57102 0x42CD Point 35 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 36
57114 0x42D9 Point 36 Func Type 0 255 1 F0 0 1
57115 0x42DA Point 36 Info Num 0 255 1 F0 0 1
57116 0x42DB Point 36 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 37
57128 0x42E7 Point 37 Func Type 0 255 1 F0 0 1
57129 0x42E8 Point 37 Info Num 0 255 1 F0 0 1
57130 0x42E9 Point 37 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 38
57142 0x42F5 Point 38 Func Type 0 255 1 F0 0 1
57143 0x42F6 Point 38 Info Num 0 255 1 F0 0 1
57144 0x42F7 Point 38 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 39
57156 0x4303 Point 39 Func Type 0 255 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-107


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
57157 0x4304 Point 39 Info Num 0 255 1 F0 0 1
57158 0x4305 Point 39 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 40
57170 0x4311 Point 40 Func Type 0 255 1 F0 0 1
57171 0x4312 Point 40 Info Num 0 255 1 F0 0 1
57172 0x4313 Point 40 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 41
57184 0x431F Point 41 Func Type 0 255 1 F0 0 1
57185 0x4320 Point 41 Info Num 0 255 1 F0 0 1
57186 0x4321 Point 41 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 42
57198 0x432D Point 42 Func Type 0 255 1 F0 0 1
57199 0x432E Point 42 Info Num 0 255 1 F0 0 1
57200 0x432F Point 42 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 43
57212 0x433B Point 43 Func Type 0 255 1 F0 0 1
57213 0x433C Point 43 Info Num 0 255 1 F0 0 1
57214 0x433D Point 43 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 44
57226 0x4349 Point 44 Func Type 0 255 1 F0 0 1
57227 0x434A Point 44 Info Num 0 255 1 F0 0 1
57228 0x434B Point 44 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 45
57240 0x4357 Point 45 Func Type 0 255 1 F0 0 1
57241 0x4358 Point 45 Info Num 0 255 1 F0 0 1
57242 0x4359 Point 45 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 46
57254 0x4365 Point 46 Func Type 0 255 1 F0 0 1
57255 0x4366 Point 46 Info Num 0 255 1 F0 0 1
57256 0x4367 Point 46 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 47
57268 0x4373 Point 47 Func Type 0 255 1 F0 0 1
57269 0x4374 Point 47 Info Num 0 255 1 F0 0 1
57270 0x4375 Point 47 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 48
57282 0x4381 Point 48 Func Type 0 255 1 F0 0 1
57283 0x4382 Point 48 Info Num 0 255 1 F0 0 1
57284 0x4383 Point 48 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 49
57296 0x438F Point 49 Func Type 0 255 1 F0 0 1
57297 0x4390 Point 49 Info Num 0 255 1 F0 0 1
57298 0x4391 Point 49 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 50
57310 0x439D Point 50 Func Type 0 255 1 F0 0 1
57311 0x439E Point 50 Info Num 0 255 1 F0 0 1
57312 0x439F Point 50 0 0xFFFFFFFF 1 FC142 0 1

11-108 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Binary Input Point 51
57324 0x43AB Point 51 Func Type 0 255 1 F0 0 1
57325 0x43AC Point 51 Info Num 0 255 1 F0 0 1
57326 0x43AD Point 51 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 52
57338 0x43B9 Point 52 Func Type 0 255 1 F0 0 1
57339 0x43BA Point 52 Info Num 0 255 1 F0 0 1
57340 0x43BB Point 52 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 53
57352 0x43C7 Point 53 Func Type 0 255 1 F0 0 1
57353 0x43C8 Point 53 Info Num 0 255 1 F0 0 1
57354 0x43C9 Point 53 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 54
57366 0x43D5 Point 54 Func Type 0 255 1 F0 0 1
57367 0x43D6 Point 54 Info Num 0 255 1 F0 0 1
57368 0x43D7 Point 54 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 55
57380 0x43E3 Point 55 Func Type 0 255 1 F0 0 1
57381 0x43E4 Point 55 Info Num 0 255 1 F0 0 1
57382 0x43E5 Point 55 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 56
57394 0x43F1 Point 56 Func Type 0 255 1 F0 0 1
57395 0x43F2 Point 56 Info Num 0 255 1 F0 0 1
57396 0x43F3 Point 56 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 57
57408 0x43FF Point 57 Func Type 0 255 1 F0 0 1
57409 0x4400 Point 57 Info Num 0 255 1 F0 0 1
57410 0x4401 Point 57 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 58
57422 0x440D Point 58 Func Type 0 255 1 F0 0 1
57423 0x440E Point 58 Info Num 0 255 1 F0 0 1
57424 0x440F Point 58 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 59
57436 0x441B Point 59 Func Type 0 255 1 F0 0 1
57437 0x441C Point 59 Info Num 0 255 1 F0 0 1
57438 0x441D Point 59 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 60
57450 0x4429 Point 60 Func Type 0 255 1 F0 0 1
57451 0x442A Point 60 Info Num 0 255 1 F0 0 1
57452 0x442B Point 60 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 61
57464 0x4437 Point 61 Func Type 0 255 1 F0 0 1
57465 0x4438 Point 61 Info Num 0 255 1 F0 0 1
57466 0x4439 Point 61 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 62
57478 0x4445 Point 62 Func Type 0 255 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-109


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
57479 0x4446 Point 62 Info Num 0 255 1 F0 0 1
57480 0x4447 Point 62 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 63
57492 0x4453 Point 63 Func Type 0 255 1 F0 0 1
57493 0x4454 Point 63 Info Num 0 255 1 F0 0 1
57494 0x4455 Point 63 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 64
57506 0x4461 Point 64 Func Type 0 255 1 F0 0 1
57507 0x4462 Point 64 Info Num 0 255 1 F0 0 1
57508 0x4463 Point 64 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 65
57520 0x446F Point 65 Func Type 0 255 1 F0 0 1
57521 0x4470 Point 65 Info Num 0 255 1 F0 0 1
57522 0x4471 Point 65 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 66
57534 0x447D Point 66 Func Type 0 255 1 F0 0 1
57535 0x447E Point 66 Info Num 0 255 1 F0 0 1
57536 0x447F Point 66 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 67
57548 0x448B Point 67 Func Type 0 255 1 F0 0 1
57549 0x448C Point 67 Info Num 0 255 1 F0 0 1
57550 0x448D Point 67 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 68
57562 0x4499 Point 68 Func Type 0 255 1 F0 0 1
57563 0x449A Point 68 Info Num 0 255 1 F0 0 1
57564 0x449B Point 68 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 69
57576 0x44A7 Point 69 Func Type 0 255 1 F0 0 1
57577 0x44A8 Point 69 Info Num 0 255 1 F0 0 1
57578 0x44A9 Point 69 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 70
57590 0x44B5 Point 70 Func Type 0 255 1 F0 0 1
57591 0x44B6 Point 70 Info Num 0 255 1 F0 0 1
57592 0x44B7 Point 70 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 71
57604 0x44C3 Point 71 Func Type 0 255 1 F0 0 1
57605 0x44C4 Point 71 Info Num 0 255 1 F0 0 1
57606 0x44C5 Point 71 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 72
57618 0x44D1 Point 72 Func Type 0 255 1 F0 0 1
57619 0x44D2 Point 72 Info Num 0 255 1 F0 0 1
57620 0x44D3 Point 72 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 73
57632 0x44DF Point 73 Func Type 0 255 1 F0 0 1
57633 0x44E0 Point 73 Info Num 0 255 1 F0 0 1
57634 0x44E1 Point 73 0 0xFFFFFFFF 1 FC142 0 1

11-110 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Binary Input Point 74
57646 0x44ED Point 74 Func Type 0 255 1 F0 0 1
57647 0x44EE Point 74 Info Num 0 255 1 F0 0 1
57648 0x44EF Point 74 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 75
57660 0x44FB Point 75 Func Type 0 255 1 F0 0 1
57661 0x44FC Point 75 Info Num 0 255 1 F0 0 1
57662 0x44FD Point 75 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 76
57674 0x4509 Point 76 Func Type 0 255 1 F0 0 1
57675 0x450A Point 76 Info Num 0 255 1 F0 0 1
57676 0x450B Point 76 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 77
57688 0x4517 Point 77 Func Type 0 255 1 F0 0 1
57689 0x4518 Point 77 Info Num 0 255 1 F0 0 1
57690 0x4519 Point 77 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 78
57702 0x4525 Point 78 Func Type 0 255 1 F0 0 1
57703 0x4526 Point 78 Info Num 0 255 1 F0 0 1
57704 0x4527 Point 78 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 79
57716 0x4533 Point 79 Func Type 0 255 1 F0 0 1
57717 0x4534 Point 79 Info Num 0 255 1 F0 0 1
57718 0x4535 Point 79 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 80
57730 0x4541 Point 80 Func Type 0 255 1 F0 0 1
57731 0x4542 Point 80 Info Num 0 255 1 F0 0 1
57732 0x4543 Point 80 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 81
57744 0x454F Point 81 Func Type 0 255 1 F0 0 1
57745 0x4550 Point 81 Info Num 0 255 1 F0 0 1
57746 0x4551 Point 81 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 82
57758 0x455D Point 82 Func Type 0 255 1 F0 0 1
57759 0x455E Point 82 Info Num 0 255 1 F0 0 1
57760 0x455F Point 82 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 83
57772 0x456B Point 83 Func Type 0 255 1 F0 0 1
57773 0x456C Point 83 Info Num 0 255 1 F0 0 1
57774 0x456D Point 83 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 84
57786 0x4579 Point 84 Func Type 0 255 1 F0 0 1
57787 0x457A Point 84 Info Num 0 255 1 F0 0 1
57788 0x457B Point 84 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 85
57800 0x4587 Point 85 Func Type 0 255 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-111


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
57801 0x4588 Point 85 Info Num 0 255 1 F0 0 1
57802 0x4589 Point 85 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 86
57814 0x4595 Point 86 Func Type 0 255 1 F0 0 1
57815 0x4596 Point 86 Info Num 0 255 1 F0 0 1
57816 0x4597 Point 86 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 87
57828 0x45A3 Point 87 Func Type 0 255 1 F0 0 1
57829 0x45A4 Point 87 Info Num 0 255 1 F0 0 1
57830 0x45A5 Point 87 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 88
57842 0x45B1 Point 88 Func Type 0 255 1 F0 0 1
57843 0x45B2 Point 88 Info Num 0 255 1 F0 0 1
57844 0x45B3 Point 88 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 89
57856 0x45BF Point 89 Func Type 0 255 1 F0 0 1
57857 0x45C0 Point 89 Info Num 0 255 1 F0 0 1
57858 0x45C1 Point 89 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 90
57870 0x45CD Point 90 Func Type 0 255 1 F0 0 1
57871 0x45CE Point 90 Info Num 0 255 1 F0 0 1
57872 0x45CF Point 90 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 91
57884 0x45DB Point 91 Func Type 0 255 1 F0 0 1
57885 0x45DC Point 91 Info Num 0 255 1 F0 0 1
57886 0x45DD Point 91 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 92
57898 0x45E9 Point 92 Func Type 0 255 1 F0 0 1
57899 0x45EA Point 92 Info Num 0 255 1 F0 0 1
57900 0x45EB Point 92 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 93
57912 0x45F7 Point 93 Func Type 0 255 1 F0 0 1
57913 0x45F8 Point 93 Info Num 0 255 1 F0 0 1
57914 0x45F9 Point 93 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 94
57926 0x4605 Point 94 Func Type 0 255 1 F0 0 1
57927 0x4606 Point 94 Info Num 0 255 1 F0 0 1
57928 0x4607 Point 94 0 0xFFFFFFFF 1 FC142 0 1
Binary Input Point 95
57940 0x4613 Point 95 Func Type 0 255 1 F0 0 1
57941 0x4614 Point 95 Info Num 0 255 1 F0 0 1
57942 0x4615 Point 95 0 0xFFFFFFFF 1 FC142 0 1
First ADSU
57970 0x4631 First ADSU Ident Type 0 1 1 FC212 0 1
57971 0x4632 First ADSU Func Type 0 255 1 F0 0 1
57972 0x4633 First ADSU Info Num 0 255 1 F0 0 1

11-112 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
57973 0x4634 First ADSU Scan Timeout 0 1000 1 s F0 0 1
57974 0x4635 First Analog Entry 0 33560 1 FC273 0 1
57975 0x4636 First Analog Factor 0 65535 1 F3 0 1
57976 0x4637 First Analog Offset -32768 32767 1 F20 0 1
57977 0x4638 Second Analog Entry 0 33560 1 FC273 0 1
57978 0x4639 Second Analog Factor 0 65535 1 F3 0 1
57979 0x463A Second Analog Offset -32768 32767 1 F20 0 1
57980 0x463B Third Analog Entry 0 33560 1 FC273 0 1
57981 0x463C Third Analog Factor 0 65535 1 F3 0 1
57982 0x463D Third Analog Offset -32768 32767 1 F20 0 1
57983 0x463E Fourth Analog Entry 0 33560 1 FC273 0 1
57984 0x463F Fourth Analog Factor 0 65535 1 F3 0 1
57985 0x4640 Fourth Analog Offset -32768 32767 1 F20 0 1
57986 0x4641 Fifth Analog Entry 0 33560 1 FC273 0 1
57987 0x4642 Fifth Analog Factor 0 65535 1 F3 0 1
57988 0x4643 Fifth Analog Offset -32768 32767 1 F20 0 1
57989 0x4644 Sixth Analog Entry 0 33560 1 FC273 0 1
57990 0x4645 Sixth Analog Factor 0 65535 1 F3 0 1
57991 0x4646 Sixth Analog Offset -32768 32767 1 F20 0 1
57992 0x4647 Seventh Analog Entry 0 33560 1 FC273 0 1
57993 0x4648 Seventh Analog Factor 0 65535 1 F3 0 1
57994 0x4649 Seventh Analog Offset -32768 32767 1 F20 0 1
57995 0x464A Eighth Analog Entry 0 33560 1 FC273 0 1
57996 0x464B Eighth Analog Factor 0 65535 1 F3 0 1
57997 0x464C Eighth Analog Offset -32768 32767 1 F20 0 1
57998 0x464D Ninth Analog Entry 0 33560 1 FC273 0 1
57999 0x464E Ninth Analog Factor 0 65535 1 F3 0 1
58000 0x464F Ninth Analog Offset -32768 32767 1 F20 0 1
Second ADSU
58011 0x465A Second ADSU Ident Type 0 1 1 FC212 0 1
58012 0x465B Second ADSU Func Type 0 255 1 F0 0 1
58013 0x465C Second ADSU Info Num 0 255 1 F0 0 1
58014 0x465D Second ADSU Scan 0 1000 1 s F0 0 1
Timeout
58015 0x465E First Analog Entry 0 33560 1 FC273 0 1
58016 0x465F First Analog Factor 0 65535 1 F3 0 1
58017 0x4660 First Analog Offset -32768 32767 1 F20 0 1
58018 0x4661 Second Analog Entry 0 33560 1 FC273 0 1
58019 0x4662 Second Analog Factor 0 65535 1 F3 0 1
58020 0x4663 Second Analog Offset -32768 32767 1 F20 0 1
58021 0x4664 Third Analog Entry 0 33560 1 FC273 0 1
58022 0x4665 Third Analog Factor 0 65535 1 F3 0 1
58023 0x4666 Third Analog Offset -32768 32767 1 F20 0 1
58024 0x4667 Fourth Analog Entry 0 33560 1 FC273 0 1
58025 0x4668 Fourth Analog Factor 0 65535 1 F3 0 1
58026 0x4669 Fourth Analog Offset -32768 32767 1 F20 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-113


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58027 0x466A Fifth Analog Entry 0 33560 1 FC273 0 1
58028 0x466B Fifth Analog Factor 0 65535 1 F3 0 1
58029 0x466C Fifth Analog Offset -32768 32767 1 F20 0 1
58030 0x466D Sixth Analog Entry 0 33560 1 FC273 0 1
58031 0x466E Sixth Analog Factor 0 65535 1 F3 0 1
58032 0x466F Sixth Analog Offset -32768 32767 1 F20 0 1
58033 0x4670 Seventh Analog Entry 0 33560 1 FC273 0 1
58034 0x4671 Seventh Analog Factor 0 65535 1 F3 0 1
58035 0x4672 Seventh Analog Offset -32768 32767 1 F20 0 1
58036 0x4673 Eighth Analog Entry 0 33560 1 FC273 0 1
58037 0x4674 Eighth Analog Factor 0 65535 1 F3 0 1
58038 0x4675 Eighth Analog Offset -32768 32767 1 F20 0 1
58039 0x4676 Ninth Analog Entry 0 33560 1 FC273 0 1
58040 0x4677 Ninth Analog Factor 0 65535 1 F3 0 1
58041 0x4678 Ninth Analog Offset -32768 32767 1 F20 0 1
Third ADSU
58052 0x4683 Third ADSU Ident Type 0 1 1 FC212 0 1
58053 0x4684 Third ADSU Func Type 0 255 1 F0 0 1
58054 0x4685 Third ADSU Info Num 0 255 1 F0 0 1
58055 0x4686 Third ADSU Scan Timeout 0 1000 1 s F0 0 1
58056 0x4687 First Analog Entry 0 33560 1 FC273 0 1
58057 0x4688 First Analog Factor 0 65535 1 F3 0 1
58058 0x4689 First Analog Offset -32768 32767 1 F20 0 1
58059 0x468A Second Analog Entry 0 33560 1 FC273 0 1
58060 0x468B Second Analog Factor 0 65535 1 F3 0 1
58061 0x468C Second Analog Offset -32768 32767 1 F20 0 1
58062 0x468D Third Analog Entry 0 33560 1 FC273 0 1
58063 0x468E Third Analog Factor 0 65535 1 F3 0 1
58064 0x468F Third Analog Offset -32768 32767 1 F20 0 1
58065 0x4690 Fourth Analog Entry 0 33560 1 FC273 0 1
58066 0x4691 Fourth Analog Factor 0 65535 1 F3 0 1
58067 0x4692 Fourth Analog Offset -32768 32767 1 F20 0 1
58068 0x4693 Fifth Analog Entry 0 33560 1 FC273 0 1
58069 0x4694 Fifth Analog Factor 0 65535 1 F3 0 1
58070 0x4695 Fifth Analog Offset -32768 32767 1 F20 0 1
58071 0x4696 Sixth Analog Entry 0 33560 1 FC273 0 1
58072 0x4697 Sixth Analog Factor 0 65535 1 F3 0 1
58073 0x4698 Sixth Analog Offset -32768 32767 1 F20 0 1
58074 0x4699 Seventh Analog Entry 0 33560 1 FC273 0 1
58075 0x469A Seventh Analog Factor 0 65535 1 F3 0 1
58076 0x469B Seventh Analog Offset -32768 32767 1 F20 0 1
58077 0x469C Eighth Analog Entry 0 33560 1 FC273 0 1
58078 0x469D Eighth Analog Factor 0 65535 1 F3 0 1
58079 0x469E Eighth Analog Offset -32768 32767 1 F20 0 1
58080 0x469F Ninth Analog Entry 0 33560 1 FC273 0 1
58081 0x46A0 Ninth Analog Factor 0 65535 1 F3 0 1

11-114 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58082 0x46A1 Ninth Analog Offset -32768 32767 1 F20 0 1
Fourth ADSU
58093 0x46AC Fourth ADSU Ident Type 0 1 1 FC212 0 1
58094 0x46AD Fourth ADSU Func Type 0 255 1 F0 0 1
58095 0x46AE Fourth ADSU Info Num 0 255 1 F0 0 1
58096 0x46AF Fourth ADSU Scan 0 1000 1 s F0 0 1
Timeout
58097 0x46B0 First Analog Entry 0 33560 1 FC273 0 1
58098 0x46B1 First Analog Factor 0 65535 1 F3 0 1
58099 0x46B2 First Analog Offset -32768 32767 1 F20 0 1
58100 0x46B3 Second Analog Entry 0 33560 1 FC273 0 1
58101 0x46B4 Second Analog Factor 0 65535 1 F3 0 1
58102 0x46B5 Second Analog Offset -32768 32767 1 F20 0 1
58103 0x46B6 Third Analog Entry 0 33560 1 FC273 0 1
58104 0x46B7 Third Analog Factor 0 65535 1 F3 0 1
58105 0x46B8 Third Analog Offset -32768 32767 1 F20 0 1
58106 0x46B9 Fourth Analog Entry 0 33560 1 FC273 0 1
58107 0x46BA Fourth Analog Factor 0 65535 1 F3 0 1
58108 0x46BB Fourth Analog Offset -32768 32767 1 F20 0 1
58109 0x46BC Fifth Analog Entry 0 33560 1 FC273 0 1
58110 0x46BD Fifth Analog Factor 0 65535 1 F3 0 1
58111 0x46BE Fifth Analog Offset -32768 32767 1 F20 0 1
58112 0x46BF Sixth Analog Entry 0 33560 1 FC273 0 1
58113 0x46C0 Sixth Analog Factor 0 65535 1 F3 0 1
58114 0x46C1 Sixth Analog Offset -32768 32767 1 F20 0 1
58115 0x46C2 Seventh Analog Entry 0 33560 1 FC273 0 1
58116 0x46C3 Seventh Analog Factor 0 65535 1 F3 0 1
58117 0x46C4 Seventh Analog Offset -32768 32767 1 F20 0 1
58118 0x46C5 Eighth Analog Entry 0 33560 1 FC273 0 1
58119 0x46C6 Eighth Analog Factor 0 65535 1 F3 0 1
58120 0x46C7 Eighth Analog Offset -32768 32767 1 F20 0 1
58121 0x46C8 Ninth Analog Entry 0 33560 1 FC273 0 1
58122 0x46C9 Ninth Analog Factor 0 65535 1 F3 0 1
58123 0x46CA Ninth Analog Offset -32768 32767 1 F20 0 1
IEC103 Command 0
58150 0x46E5 Command 0 Func Type 0 255 1 F0 0 1
58151 0x46E6 Command 0 Info Num 0 255 1 F0 0 1
58152 0x46E7 Command 0 ON 0 47 1 FC230 0 1
58153 0x46E8 Command 0 OFF 0 47 1 FC230 0 1
IEC103 Command 1
58154 0x46E9 Command 1 Func Type 0 255 1 F0 0 1
58155 0x46EA Command 1 Info Num 0 255 1 F0 0 1
58156 0x46EB Command 1 ON 0 47 1 FC230 0 1
58157 0x46EC Command 1 OFF 0 47 1 FC230 0 1
IEC103 Command 2
58158 0x46ED Command 2 Func Type 0 255 1 F0 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-115


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58159 0x46EE Command 2 Info Num 0 255 1 F0 0 1
58160 0x46EF Command 2 ON 0 47 1 FC230 0 1
58161 0x46F0 Command 2 OFF 0 47 1 FC230 0 1
IEC103 Command 3
58162 0x46F1 Command 3 Func Type 0 255 1 F0 0 1
58163 0x46F2 Command 3 Info Num 0 255 1 F0 0 1
58164 0x46F3 Command 3 ON 0 47 1 FC230 0 1
58165 0x46F4 Command 3 OFF 0 47 1 FC230 0 1
IEC103 Command 4
58166 0x46F5 Command 4 Func Type 0 255 1 F0 0 1
58167 0x46F6 Command 4 Info Num 0 255 1 F0 0 1
58168 0x46F7 Command 4 ON 0 47 1 FC230 0 1
58169 0x46F8 Command 4 OFF 0 47 1 FC230 0 1
IEC103 Command 5
58170 0x46F9 Command 5 Func Type 0 255 1 F0 0 1
58171 0x46FA Command 5 Info Num 0 255 1 F0 0 1
58172 0x46FB Command 5 ON 0 47 1 FC230 0 1
58173 0x46FC Command 5 OFF 0 47 1 FC230 0 1
IEC103 Command 6
58174 0x46FD Command 6 Func Type 0 255 1 F0 0 1
58175 0x46FE Command 6 Info Num 0 255 1 F0 0 1
58176 0x46FF Command 6 ON 0 47 1 FC230 0 1
58177 0x4700 Command 6 OFF 0 47 1 FC230 0 1
IEC103 Command 7
58178 0x4701 Command 7 Func Type 0 255 1 F0 0 1
58179 0x4702 Command 7 Info Num 0 255 1 F0 0 1
58180 0x4703 Command 7 ON 0 47 1 FC230 0 1
58181 0x4704 Command 7 OFF 0 47 1 FC230 0 1
IEC103 Command 8
58182 0x4705 Command 8 Func Type 0 255 1 F0 0 1
58183 0x4706 Command 8 Info Num 0 255 1 F0 0 1
58184 0x4707 Command 8 ON 0 47 1 FC230 0 1
58185 0x4708 Command 8 OFF 0 47 1 FC230 0 1
IEC103 Command 9
58186 0x4709 Command 9 Func Type 0 255 1 F0 0 1
58187 0x470A Command 9 Info Num 0 255 1 F0 0 1
58188 0x470B Command 9 ON 0 47 1 FC230 0 1
58189 0x470C Command 9 OFF 0 47 1 FC230 0 1
IEC103 Command 10
58190 0x470D Command 10 Func Type 0 255 1 F0 0 1
58191 0x470E Command 10 Info Num 0 255 1 F0 0 1
58192 0x470F Command 10 ON 0 47 1 FC230 0 1
58193 0x4710 Command 10 OFF 0 47 1 FC230 0 1
IEC103 Command 11
58194 0x4711 Command 11 Func Type 0 255 1 F0 0 1
58195 0x4712 Command 11 Info Num 0 255 1 F0 0 1

11-116 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58196 0x4713 Command 11 ON 0 47 1 FC230 0 1
58197 0x4714 Command 11 OFF 0 47 1 FC230 0 1
IEC103 Command 12
58198 0x4715 Command 12 Func Type 0 255 1 F0 0 1
58199 0x4716 Command 12 Info Num 0 255 1 F0 0 1
58200 0x4717 Command 12 ON 0 47 1 FC230 0 1
58201 0x4718 Command 12 OFF 0 47 1 FC230 0 1
IEC103 Command 13
58202 0x4719 Command 13 Func Type 0 255 1 F0 0 1
58203 0x471A Command 13 Info Num 0 255 1 F0 0 1
58204 0x471B Command 13 ON 0 47 1 FC230 0 1
58205 0x471C Command 13 OFF 0 47 1 FC230 0 1
IEC103 Command 14
58206 0x471D Command 14 Func Type 0 255 1 F0 0 1
58207 0x471E Command 14 Info Num 0 255 1 F0 0 1
58208 0x471F Command 14 ON 0 47 1 FC230 0 1
58209 0x4720 Command 14 OFF 0 47 1 FC230 0 1
IEC103 Command 15
58210 0x4721 Command 15 Func Type 0 255 1 F0 0 1
58211 0x4722 Command 15 Info Num 0 255 1 F0 0 1
58212 0x4723 Command 15 ON 0 47 1 FC230 0 1
58213 0x4724 Command 15 OFF 0 47 1 FC230 0 1
IEC103 Command 16
58214 0x4725 Command 16 Func Type 0 255 1 F0 0 1
58215 0x4726 Command 16 Info Num 0 255 1 F0 0 1
58216 0x4727 Command 16 ON 0 47 1 FC230 0 1
58217 0x4728 Command 16 OFF 0 47 1 FC230 0 1
IEC103 Command 17
58218 0x4729 Command 17 Func Type 0 255 1 F0 0 1
58219 0x472A Command 17 Info Num 0 255 1 F0 0 1
58220 0x472B Command 17 ON 0 47 1 FC230 0 1
58221 0x472C Command 17 OFF 0 47 1 FC230 0 1
IEC103 Command 18
58222 0x472D Command 18 Func Type 0 255 1 F0 0 1
58223 0x472E Command 18 Info Num 0 255 1 F0 0 1
58224 0x472F Command 18 ON 0 47 1 FC230 0 1
58225 0x4730 Command 18 OFF 0 47 1 FC230 0 1
IEC103 Command 19
58226 0x4731 Command 19 Func Type 0 255 1 F0 0 1
58227 0x4732 Command 19 Info Num 0 255 1 F0 0 1
58228 0x4733 Command 19 ON 0 47 1 FC230 0 1
58229 0x4734 Command 19 OFF 0 47 1 FC230 0 1
IEC103 Command 20
58230 0x4735 Command 20 Func Type 0 255 1 F0 0 1
58231 0x4736 Command 20 Info Num 0 255 1 F0 0 1
58232 0x4737 Command 20 ON 0 47 1 FC230 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-117


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58233 0x4738 Command 20 OFF 0 47 1 FC230 0 1
IEC103 Command 21
58234 0x4739 Command 21 Func Type 0 255 1 F0 0 1
58235 0x473A Command 21 Info Num 0 255 1 F0 0 1
58236 0x473B Command 21 ON 0 47 1 FC230 0 1
58237 0x473C Command 21 OFF 0 47 1 FC230 0 1
IEC103 Command 22
58238 0x473D Command 22 Func Type 0 255 1 F0 0 1
58239 0x473E Command 22 Info Num 0 255 1 F0 0 1
58240 0x473F Command 22 ON 0 47 1 FC230 0 1
58241 0x4740 Command 22 OFF 0 47 1 FC230 0 1
IEC103 Command 23
58242 0x4741 Command 23 Func Type 0 255 1 F0 0 1
58243 0x4742 Command 23 Info Num 0 255 1 F0 0 1
58244 0x4743 Command 23 ON 0 47 1 FC230 0 1
58245 0x4744 Command 23 OFF 0 47 1 FC230 0 1
IEC103 Command 24
58246 0x4745 Command 24 Func Type 0 255 1 F0 0 1
58247 0x4746 Command 24 Info Num 0 255 1 F0 0 1
58248 0x4747 Command 24 ON 0 47 1 FC230 0 1
58249 0x4748 Command 24 OFF 0 47 1 FC230 0 1
IEC103 Command 25
58250 0x4749 Command 25 Func Type 0 255 1 F0 0 1
58251 0x474A Command 25 Info Num 0 255 1 F0 0 1
58252 0x474B Command 25 ON 0 47 1 FC230 0 1
58253 0x474C Command 25 OFF 0 47 1 FC230 0 1
IEC103 Command 26
58254 0x474D Command 26 Func Type 0 255 1 F0 0 1
58255 0x474E Command 26 Info Num 0 255 1 F0 0 1
58256 0x474F Command 26 ON 0 47 1 FC230 0 1
58257 0x4750 Command 26 OFF 0 47 1 FC230 0 1
IEC103 Command 27
58258 0x4751 Command 27 Func Type 0 255 1 F0 0 1
58259 0x4752 Command 27 Info Num 0 255 1 F0 0 1
58260 0x4753 Command 27 ON 0 47 1 FC230 0 1
58261 0x4754 Command 27 OFF 0 47 1 FC230 0 1
IEC103 Command 28
58262 0x4755 Command 28 Func Type 0 255 1 F0 0 1
58263 0x4756 Command 28 Info Num 0 255 1 F0 0 1
58264 0x4757 Command 28 ON 0 47 1 FC230 0 1
58265 0x4758 Command 28 OFF 0 47 1 FC230 0 1
IEC103 Command 29
58266 0x4759 Command 29 Func Type 0 255 1 F0 0 1
58267 0x475A Command 29 Info Num 0 255 1 F0 0 1
58268 0x475B Command 29 ON 0 47 1 FC230 0 1
58269 0x475C Command 29 OFF 0 47 1 FC230 0 1

11-118 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
IEC103 Command 30
58270 0x475D Command 30 Func Type 0 255 1 F0 0 1
58271 0x475E Command 30 Info Num 0 255 1 F0 0 1
58272 0x475F Command 30 ON 0 47 1 FC230 0 1
58273 0x4760 Command 30 OFF 0 47 1 FC230 0 1
IEC103 Command 31
58274 0x4761 Command 31 Func Type 0 255 1 F0 0 1
58275 0x4762 Command 31 Info Num 0 255 1 F0 0 1
58276 0x4763 Command 31 ON 0 47 1 FC230 0 1
58277 0x4764 Command 31 OFF 0 47 1 FC230 0 1
Flex States Configuration
58290 0x4771 Parameter 1 0 0xFFFFFFFF 1 FC142 0 1
58292 0x4773 Parameter 2 0 0xFFFFFFFF 1 FC142 0 1
58294 0x4775 Parameter 3 0 0xFFFFFFFF 1 FC142 0 1
58296 0x4777 Parameter 4 0 0xFFFFFFFF 1 FC142 0 1
58298 0x4779 Parameter 5 0 0xFFFFFFFF 1 FC142 0 1
58300 0x477B Parameter 6 0 0xFFFFFFFF 1 FC142 0 1
58302 0x477D Parameter 7 0 0xFFFFFFFF 1 FC142 0 1
58304 0x477F Parameter 8 0 0xFFFFFFFF 1 FC142 0 1
58306 0x4781 Parameter 9 0 0xFFFFFFFF 1 FC142 0 1
58308 0x4783 Parameter 10 0 0xFFFFFFFF 1 FC142 0 1
58310 0x4785 Parameter 11 0 0xFFFFFFFF 1 FC142 0 1
58312 0x4787 Parameter 12 0 0xFFFFFFFF 1 FC142 0 1
58314 0x4789 Parameter 13 0 0xFFFFFFFF 1 FC142 0 1
58316 0x478B Parameter 14 0 0xFFFFFFFF 1 FC142 0 1
58318 0x478D Parameter 15 0 0xFFFFFFFF 1 FC142 0 1
58320 0x478F Parameter 16 0 0xFFFFFFFF 1 FC142 0 1
58322 0x4791 Parameter 17 0 0xFFFFFFFF 1 FC142 0 1
58324 0x4793 Parameter 18 0 0xFFFFFFFF 1 FC142 0 1
58326 0x4795 Parameter 19 0 0xFFFFFFFF 1 FC142 0 1
58328 0x4797 Parameter 20 0 0xFFFFFFFF 1 FC142 0 1
58330 0x4799 Parameter 21 0 0xFFFFFFFF 1 FC142 0 1
58332 0x479B Parameter 22 0 0xFFFFFFFF 1 FC142 0 1
58334 0x479D Parameter 23 0 0xFFFFFFFF 1 FC142 0 1
58336 0x479F Parameter 24 0 0xFFFFFFFF 1 FC142 0 1
58338 0x47A1 Parameter 25 0 0xFFFFFFFF 1 FC142 0 1
58340 0x47A3 Parameter 26 0 0xFFFFFFFF 1 FC142 0 1
58342 0x47A5 Parameter 27 0 0xFFFFFFFF 1 FC142 0 1
58344 0x47A7 Parameter 28 0 0xFFFFFFFF 1 FC142 0 1
58346 0x47A9 Parameter 29 0 0xFFFFFFFF 1 FC142 0 1
58348 0x47AB Parameter 30 0 0xFFFFFFFF 1 FC142 0 1
58350 0x47AD Parameter 31 0 0xFFFFFFFF 1 FC142 0 1
58352 0x47AF Parameter 32 0 0xFFFFFFFF 1 FC142 0 1
58354 0x47B1 Parameter 33 0 0xFFFFFFFF 1 FC142 0 1
58356 0x47B3 Parameter 34 0 0xFFFFFFFF 1 FC142 0 1
58358 0x47B5 Parameter 35 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-119


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58360 0x47B7 Parameter 36 0 0xFFFFFFFF 1 FC142 0 1
58362 0x47B9 Parameter 37 0 0xFFFFFFFF 1 FC142 0 1
58364 0x47BB Parameter 38 0 0xFFFFFFFF 1 FC142 0 1
58366 0x47BD Parameter 39 0 0xFFFFFFFF 1 FC142 0 1
58368 0x47BF Parameter 40 0 0xFFFFFFFF 1 FC142 0 1
58370 0x47C1 Parameter 41 0 0xFFFFFFFF 1 FC142 0 1
58372 0x47C3 Parameter 42 0 0xFFFFFFFF 1 FC142 0 1
58374 0x47C5 Parameter 43 0 0xFFFFFFFF 1 FC142 0 1
58376 0x47C7 Parameter 44 0 0xFFFFFFFF 1 FC142 0 1
58378 0x47C9 Parameter 45 0 0xFFFFFFFF 1 FC142 0 1
58380 0x47CB Parameter 46 0 0xFFFFFFFF 1 FC142 0 1
58382 0x47CD Parameter 47 0 0xFFFFFFFF 1 FC142 0 1
58384 0x47CF Parameter 48 0 0xFFFFFFFF 1 FC142 0 1
58386 0x47D1 Parameter 49 0 0xFFFFFFFF 1 FC142 0 1
58388 0x47D3 Parameter 50 0 0xFFFFFFFF 1 FC142 0 1
58390 0x47D5 Parameter 51 0 0xFFFFFFFF 1 FC142 0 1
58392 0x47D7 Parameter 52 0 0xFFFFFFFF 1 FC142 0 1
58394 0x47D9 Parameter 53 0 0xFFFFFFFF 1 FC142 0 1
58396 0x47DB Parameter 54 0 0xFFFFFFFF 1 FC142 0 1
58398 0x47DD Parameter 55 0 0xFFFFFFFF 1 FC142 0 1
58400 0x47DF Parameter 56 0 0xFFFFFFFF 1 FC142 0 1
58402 0x47E1 Parameter 57 0 0xFFFFFFFF 1 FC142 0 1
58404 0x47E3 Parameter 58 0 0xFFFFFFFF 1 FC142 0 1
58406 0x47E5 Parameter 59 0 0xFFFFFFFF 1 FC142 0 1
58408 0x47E7 Parameter 60 0 0xFFFFFFFF 1 FC142 0 1
58410 0x47E9 Parameter 61 0 0xFFFFFFFF 1 FC142 0 1
58412 0x47EB Parameter 62 0 0xFFFFFFFF 1 FC142 0 1
58414 0x47ED Parameter 63 0 0xFFFFFFFF 1 FC142 0 1
58416 0x47EF Parameter 64 0 0xFFFFFFFF 1 FC142 0 1
58418 0x47F1 Parameter 65 0 0xFFFFFFFF 1 FC142 0 1
58420 0x47F3 Parameter 66 0 0xFFFFFFFF 1 FC142 0 1
58422 0x47F5 Parameter 67 0 0xFFFFFFFF 1 FC142 0 1
58424 0x47F7 Parameter 68 0 0xFFFFFFFF 1 FC142 0 1
58426 0x47F9 Parameter 69 0 0xFFFFFFFF 1 FC142 0 1
58428 0x47FB Parameter 70 0 0xFFFFFFFF 1 FC142 0 1
58430 0x47FD Parameter 71 0 0xFFFFFFFF 1 FC142 0 1
58432 0x47FF Parameter 72 0 0xFFFFFFFF 1 FC142 0 1
58434 0x4801 Parameter 73 0 0xFFFFFFFF 1 FC142 0 1
58436 0x4803 Parameter 74 0 0xFFFFFFFF 1 FC142 0 1
58438 0x4805 Parameter 75 0 0xFFFFFFFF 1 FC142 0 1
58440 0x4807 Parameter 76 0 0xFFFFFFFF 1 FC142 0 1
58442 0x4809 Parameter 77 0 0xFFFFFFFF 1 FC142 0 1
58444 0x480B Parameter 78 0 0xFFFFFFFF 1 FC142 0 1
58446 0x480D Parameter 79 0 0xFFFFFFFF 1 FC142 0 1
58448 0x480F Parameter 80 0 0xFFFFFFFF 1 FC142 0 1
58450 0x4811 Parameter 81 0 0xFFFFFFFF 1 FC142 0 1

11-120 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58452 0x4813 Parameter 82 0 0xFFFFFFFF 1 FC142 0 1
58454 0x4815 Parameter 83 0 0xFFFFFFFF 1 FC142 0 1
58456 0x4817 Parameter 84 0 0xFFFFFFFF 1 FC142 0 1
58458 0x4819 Parameter 85 0 0xFFFFFFFF 1 FC142 0 1
58460 0x481B Parameter 86 0 0xFFFFFFFF 1 FC142 0 1
58462 0x481D Parameter 87 0 0xFFFFFFFF 1 FC142 0 1
58464 0x481F Parameter 88 0 0xFFFFFFFF 1 FC142 0 1
58466 0x4821 Parameter 89 0 0xFFFFFFFF 1 FC142 0 1
58468 0x4823 Parameter 90 0 0xFFFFFFFF 1 FC142 0 1
58470 0x4825 Parameter 91 0 0xFFFFFFFF 1 FC142 0 1
58472 0x4827 Parameter 92 0 0xFFFFFFFF 1 FC142 0 1
58474 0x4829 Parameter 93 0 0xFFFFFFFF 1 FC142 0 1
58476 0x482B Parameter 94 0 0xFFFFFFFF 1 FC142 0 1
58478 0x482D Parameter 95 0 0xFFFFFFFF 1 FC142 0 1
58480 0x482F Parameter 96 0 0xFFFFFFFF 1 FC142 0 1
58482 0x4831 Parameter 97 0 0xFFFFFFFF 1 FC142 0 1
58484 0x4833 Parameter 98 0 0xFFFFFFFF 1 FC142 0 1
58486 0x4835 Parameter 99 0 0xFFFFFFFF 1 FC142 0 1
58488 0x4837 Parameter 100 0 0xFFFFFFFF 1 FC142 0 1
58490 0x4839 Parameter 101 0 0xFFFFFFFF 1 FC142 0 1
58492 0x483B Parameter 102 0 0xFFFFFFFF 1 FC142 0 1
58494 0x483D Parameter 103 0 0xFFFFFFFF 1 FC142 0 1
58496 0x483F Parameter 104 0 0xFFFFFFFF 1 FC142 0 1
58498 0x4841 Parameter 105 0 0xFFFFFFFF 1 FC142 0 1
58500 0x4843 Parameter 106 0 0xFFFFFFFF 1 FC142 0 1
58502 0x4845 Parameter 107 0 0xFFFFFFFF 1 FC142 0 1
58504 0x4847 Parameter 108 0 0xFFFFFFFF 1 FC142 0 1
58506 0x4849 Parameter 109 0 0xFFFFFFFF 1 FC142 0 1
58508 0x484B Parameter 110 0 0xFFFFFFFF 1 FC142 0 1
58510 0x484D Parameter 111 0 0xFFFFFFFF 1 FC142 0 1
58512 0x484F Parameter 112 0 0xFFFFFFFF 1 FC142 0 1
58514 0x4851 Parameter 113 0 0xFFFFFFFF 1 FC142 0 1
58516 0x4853 Parameter 114 0 0xFFFFFFFF 1 FC142 0 1
58518 0x4855 Parameter 115 0 0xFFFFFFFF 1 FC142 0 1
58520 0x4857 Parameter 116 0 0xFFFFFFFF 1 FC142 0 1
58522 0x4859 Parameter 117 0 0xFFFFFFFF 1 FC142 0 1
58524 0x485B Parameter 118 0 0xFFFFFFFF 1 FC142 0 1
58526 0x485D Parameter 119 0 0xFFFFFFFF 1 FC142 0 1
58528 0x485F Parameter 120 0 0xFFFFFFFF 1 FC142 0 1
58530 0x4861 Parameter 121 0 0xFFFFFFFF 1 FC142 0 1
58532 0x4863 Parameter 122 0 0xFFFFFFFF 1 FC142 0 1
58534 0x4865 Parameter 123 0 0xFFFFFFFF 1 FC142 0 1
58536 0x4867 Parameter 124 0 0xFFFFFFFF 1 FC142 0 1
58538 0x4869 Parameter 125 0 0xFFFFFFFF 1 FC142 0 1
58540 0x486B Parameter 126 0 0xFFFFFFFF 1 FC142 0 1
58542 0x486D Parameter 127 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-121


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58544 0x486F Parameter 128 0 0xFFFFFFFF 1 FC142 0 1
58546 0x4871 Parameter 129 0 0xFFFFFFFF 1 FC142 0 1
58548 0x4873 Parameter 130 0 0xFFFFFFFF 1 FC142 0 1
58550 0x4875 Parameter 131 0 0xFFFFFFFF 1 FC142 0 1
58552 0x4877 Parameter 132 0 0xFFFFFFFF 1 FC142 0 1
58554 0x4879 Parameter 133 0 0xFFFFFFFF 1 FC142 0 1
58556 0x487B Parameter 134 0 0xFFFFFFFF 1 FC142 0 1
58558 0x487D Parameter 135 0 0xFFFFFFFF 1 FC142 0 1
58560 0x487F Parameter 136 0 0xFFFFFFFF 1 FC142 0 1
58562 0x4881 Parameter 137 0 0xFFFFFFFF 1 FC142 0 1
58564 0x4883 Parameter 138 0 0xFFFFFFFF 1 FC142 0 1
58566 0x4885 Parameter 139 0 0xFFFFFFFF 1 FC142 0 1
58568 0x4887 Parameter 140 0 0xFFFFFFFF 1 FC142 0 1
58570 0x4889 Parameter 141 0 0xFFFFFFFF 1 FC142 0 1
58572 0x488B Parameter 142 0 0xFFFFFFFF 1 FC142 0 1
58574 0x488D Parameter 143 0 0xFFFFFFFF 1 FC142 0 1
58576 0x488F Parameter 144 0 0xFFFFFFFF 1 FC142 0 1
58578 0x4891 Parameter 145 0 0xFFFFFFFF 1 FC142 0 1
58580 0x4893 Parameter 146 0 0xFFFFFFFF 1 FC142 0 1
58582 0x4895 Parameter 147 0 0xFFFFFFFF 1 FC142 0 1
58584 0x4897 Parameter 148 0 0xFFFFFFFF 1 FC142 0 1
58586 0x4899 Parameter 149 0 0xFFFFFFFF 1 FC142 0 1
58588 0x489B Parameter 150 0 0xFFFFFFFF 1 FC142 0 1
58590 0x489D Parameter 151 0 0xFFFFFFFF 1 FC142 0 1
58592 0x489F Parameter 152 0 0xFFFFFFFF 1 FC142 0 1
58594 0x48A1 Parameter 153 0 0xFFFFFFFF 1 FC142 0 1
58596 0x48A3 Parameter 154 0 0xFFFFFFFF 1 FC142 0 1
58598 0x48A5 Parameter 155 0 0xFFFFFFFF 1 FC142 0 1
58600 0x48A7 Parameter 156 0 0xFFFFFFFF 1 FC142 0 1
58602 0x48A9 Parameter 157 0 0xFFFFFFFF 1 FC142 0 1
58604 0x48AB Parameter 158 0 0xFFFFFFFF 1 FC142 0 1
58606 0x48AD Parameter 159 0 0xFFFFFFFF 1 FC142 0 1
58608 0x48AF Parameter 160 0 0xFFFFFFFF 1 FC142 0 1
58610 0x48B1 Parameter 161 0 0xFFFFFFFF 1 FC142 0 1
58612 0x48B3 Parameter 162 0 0xFFFFFFFF 1 FC142 0 1
58614 0x48B5 Parameter 163 0 0xFFFFFFFF 1 FC142 0 1
58616 0x48B7 Parameter 164 0 0xFFFFFFFF 1 FC142 0 1
58618 0x48B9 Parameter 165 0 0xFFFFFFFF 1 FC142 0 1
58620 0x48BB Parameter 166 0 0xFFFFFFFF 1 FC142 0 1
58622 0x48BD Parameter 167 0 0xFFFFFFFF 1 FC142 0 1
58624 0x48BF Parameter 168 0 0xFFFFFFFF 1 FC142 0 1
58626 0x48C1 Parameter 169 0 0xFFFFFFFF 1 FC142 0 1
58628 0x48C3 Parameter 170 0 0xFFFFFFFF 1 FC142 0 1
58630 0x48C5 Parameter 171 0 0xFFFFFFFF 1 FC142 0 1
58632 0x48C7 Parameter 172 0 0xFFFFFFFF 1 FC142 0 1
58634 0x48C9 Parameter 173 0 0xFFFFFFFF 1 FC142 0 1

11-122 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58636 0x48CB Parameter 174 0 0xFFFFFFFF 1 FC142 0 1
58638 0x48CD Parameter 175 0 0xFFFFFFFF 1 FC142 0 1
58640 0x48CF Parameter 176 0 0xFFFFFFFF 1 FC142 0 1
58642 0x48D1 Parameter 177 0 0xFFFFFFFF 1 FC142 0 1
58644 0x48D3 Parameter 178 0 0xFFFFFFFF 1 FC142 0 1
58646 0x48D5 Parameter 179 0 0xFFFFFFFF 1 FC142 0 1
58648 0x48D7 Parameter 180 0 0xFFFFFFFF 1 FC142 0 1
58650 0x48D9 Parameter 181 0 0xFFFFFFFF 1 FC142 0 1
58652 0x48DB Parameter 182 0 0xFFFFFFFF 1 FC142 0 1
58654 0x48DD Parameter 183 0 0xFFFFFFFF 1 FC142 0 1
58656 0x48DF Parameter 184 0 0xFFFFFFFF 1 FC142 0 1
58658 0x48E1 Parameter 185 0 0xFFFFFFFF 1 FC142 0 1
58660 0x48E3 Parameter 186 0 0xFFFFFFFF 1 FC142 0 1
58662 0x48E5 Parameter 187 0 0xFFFFFFFF 1 FC142 0 1
58664 0x48E7 Parameter 188 0 0xFFFFFFFF 1 FC142 0 1
58666 0x48E9 Parameter 189 0 0xFFFFFFFF 1 FC142 0 1
58668 0x48EB Parameter 190 0 0xFFFFFFFF 1 FC142 0 1
58670 0x48ED Parameter 191 0 0xFFFFFFFF 1 FC142 0 1
58672 0x48EF Parameter 192 0 0xFFFFFFFF 1 FC142 0 1
58674 0x48F1 Parameter 193 0 0xFFFFFFFF 1 FC142 0 1
58676 0x48F3 Parameter 194 0 0xFFFFFFFF 1 FC142 0 1
58678 0x48F5 Parameter 195 0 0xFFFFFFFF 1 FC142 0 1
58680 0x48F7 Parameter 196 0 0xFFFFFFFF 1 FC142 0 1
58682 0x48F9 Parameter 197 0 0xFFFFFFFF 1 FC142 0 1
58684 0x48FB Parameter 198 0 0xFFFFFFFF 1 FC142 0 1
58686 0x48FD Parameter 199 0 0xFFFFFFFF 1 FC142 0 1
58688 0x48FF Parameter 200 0 0xFFFFFFFF 1 FC142 0 1
58690 0x4901 Parameter 201 0 0xFFFFFFFF 1 FC142 0 1
58692 0x4903 Parameter 202 0 0xFFFFFFFF 1 FC142 0 1
58694 0x4905 Parameter 203 0 0xFFFFFFFF 1 FC142 0 1
58696 0x4907 Parameter 204 0 0xFFFFFFFF 1 FC142 0 1
58698 0x4909 Parameter 205 0 0xFFFFFFFF 1 FC142 0 1
58700 0x490B Parameter 206 0 0xFFFFFFFF 1 FC142 0 1
58702 0x490D Parameter 207 0 0xFFFFFFFF 1 FC142 0 1
58704 0x490F Parameter 208 0 0xFFFFFFFF 1 FC142 0 1
58706 0x4911 Parameter 209 0 0xFFFFFFFF 1 FC142 0 1
58708 0x4913 Parameter 210 0 0xFFFFFFFF 1 FC142 0 1
58710 0x4915 Parameter 211 0 0xFFFFFFFF 1 FC142 0 1
58712 0x4917 Parameter 212 0 0xFFFFFFFF 1 FC142 0 1
58714 0x4919 Parameter 213 0 0xFFFFFFFF 1 FC142 0 1
58716 0x491B Parameter 214 0 0xFFFFFFFF 1 FC142 0 1
58718 0x491D Parameter 215 0 0xFFFFFFFF 1 FC142 0 1
58720 0x491F Parameter 216 0 0xFFFFFFFF 1 FC142 0 1
58722 0x4921 Parameter 217 0 0xFFFFFFFF 1 FC142 0 1
58724 0x4923 Parameter 218 0 0xFFFFFFFF 1 FC142 0 1
58726 0x4925 Parameter 219 0 0xFFFFFFFF 1 FC142 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-123


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
58728 0x4927 Parameter 220 0 0xFFFFFFFF 1 FC142 0 1
58730 0x4929 Parameter 221 0 0xFFFFFFFF 1 FC142 0 1
58732 0x492B Parameter 222 0 0xFFFFFFFF 1 FC142 0 1
58734 0x492D Parameter 223 0 0xFFFFFFFF 1 FC142 0 1
58736 0x492F Parameter 224 0 0xFFFFFFFF 1 FC142 0 1
58738 0x4931 Parameter 225 0 0xFFFFFFFF 1 FC142 0 1
58740 0x4933 Parameter 226 0 0xFFFFFFFF 1 FC142 0 1
58742 0x4935 Parameter 227 0 0xFFFFFFFF 1 FC142 0 1
58744 0x4937 Parameter 228 0 0xFFFFFFFF 1 FC142 0 1
58746 0x4939 Parameter 229 0 0xFFFFFFFF 1 FC142 0 1
58748 0x493B Parameter 230 0 0xFFFFFFFF 1 FC142 0 1
58750 0x493D Parameter 231 0 0xFFFFFFFF 1 FC142 0 1
58752 0x493F Parameter 232 0 0xFFFFFFFF 1 FC142 0 1
58754 0x4941 Parameter 233 0 0xFFFFFFFF 1 FC142 0 1
58756 0x4943 Parameter 234 0 0xFFFFFFFF 1 FC142 0 1
58758 0x4945 Parameter 235 0 0xFFFFFFFF 1 FC142 0 1
58760 0x4947 Parameter 236 0 0xFFFFFFFF 1 FC142 0 1
58762 0x4949 Parameter 237 0 0xFFFFFFFF 1 FC142 0 1
58764 0x494B Parameter 238 0 0xFFFFFFFF 1 FC142 0 1
58766 0x494D Parameter 239 0 0xFFFFFFFF 1 FC142 0 1
58768 0x494F Parameter 240 0 0xFFFFFFFF 1 FC142 0 1
58770 0x4951 Parameter 241 0 0xFFFFFFFF 1 FC142 0 1
58772 0x4953 Parameter 242 0 0xFFFFFFFF 1 FC142 0 1
58774 0x4955 Parameter 243 0 0xFFFFFFFF 1 FC142 0 1
58776 0x4957 Parameter 244 0 0xFFFFFFFF 1 FC142 0 1
58778 0x4959 Parameter 245 0 0xFFFFFFFF 1 FC142 0 1
58780 0x495B Parameter 246 0 0xFFFFFFFF 1 FC142 0 1
58782 0x495D Parameter 247 0 0xFFFFFFFF 1 FC142 0 1
58784 0x495F Parameter 248 0 0xFFFFFFFF 1 FC142 0 1
58786 0x4961 Parameter 249 0 0xFFFFFFFF 1 FC142 0 1
58788 0x4963 Parameter 250 0 0xFFFFFFFF 1 FC142 0 1
58790 0x4965 Parameter 251 0 0xFFFFFFFF 1 FC142 0 1
58792 0x4967 Parameter 252 0 0xFFFFFFFF 1 FC142 0 1
58794 0x4969 Parameter 253 0 0xFFFFFFFF 1 FC142 0 1
58796 0x496B Parameter 254 0 0xFFFFFFFF 1 FC142 0 1
58798 0x496D Parameter 255 0 0xFFFFFFFF 1 FC142 0 1
58800 0x496F Parameter 256 0 0xFFFFFFFF 1 FC142 0 1
Remote Input 1
58820 0x4983 Events 0 1 1 FC126 1 1
58821 0x4984 Name 0 65535 1 F60_26 RI 1 26
Remote Input 2
58834 0x4991 Events 0 1 1 FC126 1 1
58835 0x4992 Name 0 65535 1 F60_26 RI 2 26
Remote Input 3
58848 0x499F Events 0 1 1 FC126 1 1
58849 0x49A0 Name 0 65535 1 F60_26 RI 3 26

11-124 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
Remote Input 4
58862 0x49AD Events 0 1 1 FC126 1 1
58863 0x49AE Name 0 65535 1 F60_26 RI 4 26
Remote Input 5
58876 0x49BB Events 0 1 1 FC126 1 1
58877 0x49BC Name 0 65535 1 F60_26 RI 5 26
Remote Input 6
58890 0x49C9 Events 0 1 1 FC126 1 1
58891 0x49CA Name 0 65535 1 F60_26 RI 6 26
Remote Input 7
58904 0x49D7 Events 0 1 1 FC126 1 1
58905 0x49D8 Name 0 65535 1 F60_26 RI 7 26
Remote Input 8
58918 0x49E5 Events 0 1 1 FC126 1 1
58919 0x49E6 Name 0 65535 1 F60_26 RI 8 26
Remote Input 9
58932 0x49F3 Events 0 1 1 FC126 1 1
58933 0x49F4 Name 0 65535 1 F60_26 RI 9 26
Remote Input 10
58946 0x4A01 Events 0 1 1 FC126 1 1
58947 0x4A02 Name 0 65535 1 F60_26 RI 10 26
Remote Input 11
58960 0x4A0F Events 0 1 1 FC126 1 1
58961 0x4A10 Name 0 65535 1 F60_26 RI 11 26
Remote Input 12
58974 0x4A1D Events 0 1 1 FC126 1 1
58975 0x4A1E Name 0 65535 1 F60_26 RI 12 26
Remote Input 13
58988 0x4A2B Events 0 1 1 FC126 1 1
58989 0x4A2C Name 0 65535 1 F60_26 RI 13 26
Remote Input 14
59002 0x4A39 Events 0 1 1 FC126 1 1
59003 0x4A3A Name 0 65535 1 F60_26 RI 14 26
Remote Input 15
59016 0x4A47 Events 0 1 1 FC126 1 1
59017 0x4A48 Name 0 65535 1 F60_26 RI 15 26
Remote Input 16
59030 0x4A55 Events 0 1 1 FC126 1 1
59031 0x4A56 Name 0 65535 1 F60_26 RI 16 26
Remote Input 17
59044 0x4A63 Events 0 1 1 FC126 1 1
59045 0x4A64 Name 0 65535 1 F60_26 RI 17 26
Remote Input 18
59058 0x4A71 Events 0 1 1 FC126 1 1
59059 0x4A72 Name 0 65535 1 F60_26 RI 18 26
Remote Input 19

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-125


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
59072 0x4A7F Events 0 1 1 FC126 1 1
59073 0x4A80 Name 0 65535 1 F60_26 RI 19 26
Remote Input 20
59086 0x4A8D Events 0 1 1 FC126 1 1
59087 0x4A8E Name 0 65535 1 F60_26 RI 20 26
Remote Input 21
59100 0x4A9B Events 0 1 1 FC126 1 1
59101 0x4A9C Name 0 65535 1 F60_26 RI 21 26
Remote Input 22
59114 0x4AA9 Events 0 1 1 FC126 1 1
59115 0x4AAA Name 0 65535 1 F60_26 RI 22 26
Remote Input 23
59128 0x4AB7 Events 0 1 1 FC126 1 1
59129 0x4AB8 Name 0 65535 1 F60_26 RI 23 26
Remote Input 24
59142 0x4AC5 Events 0 1 1 FC126 1 1
59143 0x4AC6 Name 0 65535 1 F60_26 RI 24 26
Remote Input 25
59156 0x4AD3 Events 0 1 1 FC126 1 1
59157 0x4AD4 Name 0 65535 1 F60_26 RI 25 26
Remote Input 26
59170 0x4AE1 Events 0 1 1 FC126 1 1
59171 0x4AE2 Name 0 65535 1 F60_26 RI 26 26
Remote Input 27
59184 0x4AEF Events 0 1 1 FC126 1 1
59185 0x4AF0 Name 0 65535 1 F60_26 RI 27 26
Remote Input 28
59198 0x4AFD Events 0 1 1 FC126 1 1
59199 0x4AFE Name 0 65535 1 F60_26 RI 28 26
Remote Input 29
59212 0x4B0B Events 0 1 1 FC126 1 1
59213 0x4B0C Name 0 65535 1 F60_26 RI 29 26
Remote Input 30
59226 0x4B19 Events 0 1 1 FC126 1 1
59227 0x4B1A Name 0 65535 1 F60_26 RI 30 26
Remote Input 31
59240 0x4B27 Events 0 1 1 FC126 1 1
59241 0x4B28 Name 0 65535 1 F60_26 RI 31 26
Remote Input 32
59254 0x4B35 Events 0 1 1 FC126 1 1
59255 0x4B36 Name 0 65535 1 F60_26 RI 32 26
Remote Input 96
Factory Service
Setup
101611 0xF0AA Simulation State 0 3 1 FC165 0 1
101613 0xF0AC Aux Relay Sim 0 1 1 FC126 0 1

11-126 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
101614 0xF0AD Noise 0 65535 1 counts F0 0 1
101615 0xF0AE LEDs 0 1 1 FC126 0 1
Pre-Fault
101651 0xF0D2 Bank 1 PreFlt Van Voltage 0 40000 1 V F2 0 1
101652 0xF0D3 Bank 1 PreFlt Vbn Voltage 0 40000 1 V F2 0 1
101653 0xF0D4 Bank 1 PreFlt Vcn Voltage 0 40000 1 V F2 0 1
101654 0xF0D5 Bank1 Pre-Flt Vx Voltage 0 40000 1 V F2 0 1
101655 0xF0D6 Bank 2 PreFlt Van Voltage 0 40000 1 V F2 0 1
101656 0xF0D7 Bank 2 PreFlt Vbn Voltage 0 40000 1 V F2 0 1
101657 0xF0D8 Bank 2 PreFlt Vcn Voltage 0 40000 1 V F2 0 1
101658 0xF0D9 Bank2 Pre-Flt Vx Voltage 0 40000 1 V F2 0 1
101659 0xF0DA Bank 1 PreFlt Van Angle -3599 0 1 F21 0 1
101660 0xF0DB Bank 1 PreFlt Vbn Angle -3599 0 1 F21 0 1
101661 0xF0DC Bank 1 PreFlt Vcn Angle -3599 0 1 F21 0 1
101662 0xF0DD Bank 1 PreFlt Vaux Angle -3599 0 1 F21 0 1
101663 0xF0DE Bank 2 PreFlt Van Angle -3599 0 1 F21 0 1
101664 0xF0DF Bank 2 PreFlt Vbn Angle -3599 0 1 F21 0 1
101665 0xF0E0 Bank 2 PreFlt Vcn Angle -3599 0 1 F21 0 1
101666 0xF0E1 Bank 2 PreFlt Vaux Angle -3599 0 1 F21 0 1
101667 0xF0E2 Bank1 Pre-Flt Vx Freq 200 9000 1 Hz F2 200 1
101668 0xF0E3 Bank2 Pre-Flt Vx Freq 200 9000 1 Hz F2 200 1
101669 0xF0E4 Bank 1 PreFlt Phase Ia 0 65535 1 x CT F3 0 1
101670 0xF0E5 Bank 1 PreFlt Phase Ib 0 65535 1 x CT F3 0 1
101671 0xF0E6 Bank 1 PreFlt Phase Ic 0 65535 1 x CT F3 0 1
101672 0xF0E7 Bank 1 PreFlt Phase Ig 0 65535 1 x CT F3 0 1
101673 0xF0E8 Bank 2 PreFlt Phase Ia 0 65535 1 x CT F3 0 1
101674 0xF0E9 Bank 2 PreFlt Phase Ib 0 65535 1 x CT F3 0 1
101675 0xF0EA Bank 2 PreFlt Phase Ic 0 65535 1 x CT F3 0 1
101676 0xF0EB Bank 2 PreFlt Phase Ig 0 65535 1 x CT F3 0 1
101677 0xF0EC Bank 3 PreFlt Phase Ia 0 65535 1 x CT F3 0 1
101678 0xF0ED Bank 3 PreFlt Phase Ib 0 65535 1 x CT F3 0 1
101679 0xF0EE Bank 3 PreFlt Phase Ic 0 65535 1 x CT F3 0 1
101680 0xF0EF Bank 3 PreFlt Phase Ig 0 65535 1 x CT F3 0 1
101681 0xF0F0 Bank 1 PreFlt Ia Angle -3599 0 1 F21 0 1
101682 0xF0F1 Bank 1 PreFlt Ib Angle -3599 0 1 F21 0 1
101683 0xF0F2 Bank 1 PreFlt Ic Angle -3599 0 1 F21 0 1
101684 0xF0F3 Bank 1 PreFlt Ig Angle -3599 0 1 F21 0 1
101685 0xF0F4 Bank 2 PreFlt Ia Angle -3599 0 1 F21 0 1
101686 0xF0F5 Bank 2 PreFlt Ib Angle -3599 0 1 F21 0 1
101687 0xF0F6 Bank 2 PreFlt Ic Angle -3599 0 1 F21 0 1
101688 0xF0F7 Bank 2 PreFlt Ig Angle -3599 0 1 F21 0 1
101689 0xF0F8 Bank 3 PreFlt Ia Angle -3599 0 1 F21 0 1
101690 0xF0F9 Bank 3 PreFlt Ib Angle -3599 0 1 F21 0 1
101691 0xF0FA Bank 3 PreFlt Ic Angle -3599 0 1 F21 0 1
101692 0xF0FB Bank 3 PreFlt Ig Angle -3599 0 1 F21 0 1
101693 0xF0FC Bank1 Pre-Flt Ix Freq 200 9000 1 Hz F2 200 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-127


MODBUS MEMORY MAP CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
101694 0xF0FD Bank2 Pre-Flt Ix Freq 200 9000 1 Hz F2 200 1
101695 0xF0FE Bank3 Pre-Flt Ix Freq 200 9000 1 Hz F2 200 1
Fault
101706 0xF109 Bank 1 Flt Van Voltage 0 40000 1 V F2 0 1
101707 0xF10A Bank 1 Flt Vbn Voltage 0 40000 1 V F2 0 1
101708 0xF10B Bank 1 Flt Vcn Voltage 0 40000 1 V F2 0 1
101709 0xF10C Bank 1 Flt Vaux Voltage 0 40000 1 V F2 0 1
101710 0xF10D Bank 2 Flt Van Voltage 0 40000 1 V F2 0 1
101711 0xF10E Bank 2 Flt Vbn Voltage 0 40000 1 V F2 0 1
101712 0xF10F Bank 2 Flt Vcn Voltage 0 40000 1 V F2 0 1
101713 0xF110 Bank 2 Flt Vaux Voltage 0 40000 1 V F2 0 1
101714 0xF111 Bank 1 Flt Van Angle -3599 0 1 F21 0 1
101715 0xF112 Bank 1 Flt Vbn Angle -3599 0 1 F21 0 1
101716 0xF113 Bank 1 Flt Vcn Angle -3599 0 1 F21 0 1
101717 0xF114 Bank 1 Flt Vaux Angle -3599 0 1 F21 0 1
101718 0xF115 Bank 2 Flt Van Angle -3599 0 1 F21 0 1
101719 0xF116 Bank 2 Flt Vbn Angle -3599 0 1 F21 0 1
101720 0xF117 Bank 2 Flt Vcn Angle -3599 0 1 F21 0 1
101721 0xF118 Bank 2 Flt Vaux Angle -3599 0 1 F21 0 1
101722 0xF119 Bank 1 Flt Vaux 200 9000 1 Hz F2 200 1
Frequency
101723 0xF11A Bank 2 Flt Vaux 200 9000 1 Hz F2 200 1
Frequency
101724 0xF11B Bank 1 Flt Phase Ia 0 65535 1 x CT F3 0 1
101725 0xF11C Bank 1 Flt Phase Ib 0 65535 1 x CT F3 0 1
101726 0xF11D Bank 1 Flt Phase Ic 0 65535 1 x CT F3 0 1
101727 0xF11E Bank 1 Flt Phase Ig 0 65535 1 x CT F3 0 1
101728 0xF11F Bank 2 Flt Phase Ia 0 65535 1 x CT F3 0 1
101729 0xF120 Bank 2 Flt Phase Ib 0 65535 1 x CT F3 0 1
101730 0xF121 Bank 2 Flt Phase Ic 0 65535 1 x CT F3 0 1
101731 0xF122 Bank 2 Flt Phase Ig 0 65535 1 x CT F3 0 1
101732 0xF123 Bank 3 Flt Phase Ia 0 65535 1 x CT F3 0 1
101733 0xF124 Bank 3 Flt Phase Ib 0 65535 1 x CT F3 0 1
101734 0xF125 Bank 3 Flt Phase Ic 0 65535 1 x CT F3 0 1
101735 0xF126 Bank 3 Flt Phase Ig 0 65535 1 x CT F3 0 1
101736 0xF127 Bank 1 Flt Ia Angle -3599 0 1 F21 0 1
101737 0xF128 Bank 1 Flt Ib Angle -3599 0 1 F21 0 1
101738 0xF129 Bank 1 Flt Ic Angle -3599 0 1 F21 0 1
101739 0xF12A Bank 1 Flt Ig Angle -3599 0 1 F21 0 1
101740 0xF12B Bank 2 Flt Ia Angle -3599 0 1 F21 0 1
101741 0xF12C Bank 2 Flt Ib Angle -3599 0 1 F21 0 1
101742 0xF12D Bank 2 Flt Ic Angle -3599 0 1 F21 0 1
101743 0xF12E Bank 2 Flt Ig Angle -3599 0 1 F21 0 1
101744 0xF12F Bank 3 Flt Ia Angle -3599 0 1 F21 0 1
101745 0xF130 Bank 3 Flt Ib Angle -3599 0 1 F21 0 1
101746 0xF131 Bank 3 Flt Ic Angle -3599 0 1 F21 0 1
101747 0xF132 Bank 3 Flt Ig Angle -3599 0 1 F21 0 1

11-128 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
101748 0xF133 Bank 1 Flt Ix Frequency 200 9000 1 Hz F2 200 1
101749 0xF134 Bank 2 Flt Ix Frequency 200 9000 1 Hz F2 200 1
101750 0xF135 Bank 3 Flt Ix Frequency 200 9000 1 Hz F2 200 1
Post-Fault
101761 0xF140 Bank 1 PstFlt Van Voltage 0 40000 1 V F2 0 1
101762 0xF141 Bank 1 PstFlt Vbn Voltage 0 40000 1 V F2 0 1
101763 0xF142 Bank 1 PstFlt Vcn Voltage 0 40000 1 V F2 0 1
101764 0xF143 Bank1 Post-Flt Vx Voltage 0 40000 1 V F2 0 1
101765 0xF144 Bank 2 PstFlt Van Voltage 0 40000 1 V F2 0 1
101766 0xF145 Bank 2 PstFlt Vbn Voltage 0 40000 1 V F2 0 1
101767 0xF146 Bank 2 PstFlt Vcn Voltage 0 40000 1 V F2 0 1
101768 0xF147 Bank2 Post-Flt Vx Voltage 0 40000 1 V F2 0 1
101769 0xF148 Bank 1 PstFlt Van Angle -3599 0 1 F21 0 1
101770 0xF149 Bank 1 PstFlt Vbn Angle -3599 0 1 F21 0 1
101771 0xF14A Bank 1 PstFlt Vcn Angle -3599 0 1 F21 0 1
101772 0xF14B Bank 1 PstFlt Vaux Angle -3599 0 1 F21 0 1
101773 0xF14C Bank 2 PstFlt Van Angle -3599 0 1 F21 0 1
101774 0xF14D Bank 2 PstFlt Vbn Angle -3599 0 1 F21 0 1
101775 0xF14E Bank 2 PstFlt Vcn Angle -3599 0 1 F21 0 1
101776 0xF14F Bank 2 PstFlt Vaux Angle -3599 0 1 F21 0 1
101777 0xF150 Bank1 Post-Flt Vx Freq 200 9000 1 Hz F2 200 1
101778 0xF151 Bank2 Post-Flt Vx Freq 200 9000 1 Hz F2 200 1
101779 0xF152 Bank 1 PstFlt Phase Ia 0 65535 1 x CT F3 0 1
101780 0xF153 Bank 1 PstFlt Phase Ib 0 65535 1 x CT F3 0 1
101781 0xF154 Bank 1 PstFlt Phase Ic 0 65535 1 x CT F3 0 1
101782 0xF155 Bank 1 PstFlt Phase Ig 0 65535 1 x CT F3 0 1
101783 0xF156 Bank 2 PstFlt Phase Ia 0 65535 1 x CT F3 0 1
101784 0xF157 Bank 2 PstFlt Phase Ib 0 65535 1 x CT F3 0 1
101785 0xF158 Bank 2 PstFlt Phase Ic 0 65535 1 x CT F3 0 1
101786 0xF159 Bank 2 PstFlt Phase Ig 0 65535 1 x CT F3 0 1
101787 0xF15A Bank 3 PstFlt Phase Ia 0 65535 1 x CT F3 0 1
101788 0xF15B Bank 3 PstFlt Phase Ib 0 65535 1 x CT F3 0 1
101789 0xF15C Bank 3 PstFlt Phase Ic 0 65535 1 x CT F3 0 1
101790 0xF15D Bank 3 PstFlt Phase Ig 0 65535 1 x CT F3 0 1
101791 0xF15E Bank 1 PstFlt Ia Angle -3599 0 1 F21 0 1
101792 0xF15F Bank 1 PstFlt Ib Angle -3599 0 1 F21 0 1
101793 0xF160 Bank 1 PstFlt Ic Angle -3599 0 1 F21 0 1
101794 0xF161 Bank 1 PstFlt Ig Angle -3599 0 1 F21 0 1
101795 0xF162 Bank 2 PstFlt Ia Angle -3599 0 1 F21 0 1
101796 0xF163 Bank 2 PstFlt Ib Angle -3599 0 1 F21 0 1
101797 0xF164 Bank 2 PstFlt Ic Angle -3599 0 1 F21 0 1
101798 0xF165 Bank 2 PstFlt Ig Angle -3599 0 1 F21 0 1
101799 0xF166 Bank 3 PstFlt Ia Angle -3599 0 1 F21 0 1
101800 0xF167 Bank 3 PstFlt Ib Angle -3599 0 1 F21 0 1
101801 0xF168 Bank 3 PstFlt Ic Angle -3599 0 1 F21 0 1
101802 0xF169 Bank 3 PstFlt Ig Angle -3599 0 1 F21 0 1

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-129


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Modbus Hex Description Min Max Step Units Format Factory Size in
Address Address Code Default Words
101803 0xF16A Bank1 Post-Flt Ix Freq 200 9000 1 Hz F2 200 1
101804 0xF16B Bank2 Post-Flt Ix Freq 200 9000 1 Hz F2 200 1
101805 0xF16C Bank3 Post-Flt Ix Freq 200 9000 1 Hz F2 200 1
Simulation Contact Inputs
101911 0xF1D6 CI Inputs 1-32 0 0xFFFFFFFF 1 FC194 0 1
Simulation Contact Outputs
101927 0xF1E6 Contact Outputs 0 0xFFFFFFFF 1 FC198 0 1
Test LEDs
101939 0xF1F2 Test LED 1-16 0 0xFFFFFFFF 1 FC302 0 1
Pickup Test
101953 0xF200 Function 0 1 1 FC126 0 1
101954 0xF201 Contact Outputs 0 0xFFFFFFFF 1 F10 0 1
Information
102111 0xF29E PSU Serial # 0 65535 1 F60_14 PCBSerial1 14
102118 0xF2A5 CAN1 Serial # 0 65535 1 F60_14 PCBSerial2 14
102125 0xF2AC CAN2 Serial # 0 65535 1 F60_14 PCBSerial3 14
102132 0xF2B3 CPU Serial # 0 65535 1 F60_14 PCBSerial4 14
102139 0xF2BA COMM Serial # 0 65535 1 F60_14 PCBSerial5 14
102146 0xF2C1 IO_1 Serial # 0 65535 1 F60_14 PCBSerial6 14
102153 0xF2C8 IO_2 Serial # 0 65535 1 F60_14 PCBSerial7 14
102160 0xF2CF IO_3 Serial # 0 65535 1 F60_14 PCBSerial8 14
102167 0xF2D6 AN_1 Serial # 0 65535 1 F60_14 PCBSerial9 14
102174 0xF2DD AN_2 Serial # 0 65535 1 F60_14 PCBSerial1 14
0
102181 0xF2E4 MAG_1 Serial # 0 65535 1 F60_14 PCBSerial1 14
1
102188 0xF2EB MAG_2 Serial # 0 65535 1 F60_14 PCBSerial1 14
2
102195 0xF2F2 FP Serial # 0 65535 1 F60_14 PCBSerial1 14
3
Factory Settings
102240 0xF31F Select Editing Group 0 0xFFFF 1 FC132 0xFFFF 1
102241 0xF320 Response Delay 0 100 1 ms F0 0 1
102242 0xF321 Login 0 8 1 FC252 0 1
102243 0xF322 Login Password 0 65535 1 F60_22 0 22
102254 0xF32D Password 0 65535 1 F60_22 0 22

Format Codes

Code Type Definition


F0 unsigned 16 bits Unsigned Value
Example: 1234 stored as 1234
F0B unsigned 16 bits Unsigned Value, Max Value = OFF
Example: 1234 stored as 1234
F0A unsigned 16 bits Unsigned Value, Min Value = OFF

11-130 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


Example: 1234 stored as 1234
F1 unsigned 16 bits Unsigned Value, 1 Decimal Place
Example: 123.4 stored as 1234
F2 unsigned 16 bits Unsigned Value, 2 Decimal Places
Example: 12.34 stored as 1234
F3 unsigned 16 bits Unsigned Value, 3 Decimal Places
Example: 1.234 stored as 1234
F10 unsigned 32 bits Unsigned Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F11 unsigned 32 bits Unsigned Long Value, 1 Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 12345.6 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F12 unsigned 32 bits Unsigned Long Value, 2 Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 1234.56 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F13 unsigned 32 bits Unsigned Long Value, 3 Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: 123.456 stored as 123456
i.e. 1st word: 0001 hex, 2nd word: E240 hex
F20 signed 16 bits 2's Complement Signed Value
Example: -1234 stored as -1234 i.e. 64302
F21 signed 16 bits 2's Complement Signed Value, 1 Decimal
Place
Example: -123.4 stored as -1234 i.e. 64302
F22 signed 16 bits 2's Complement Signed Value, 2 Decimal
Places
Example: -12.34 stored as -1234 i.e. 64302
F23 signed 16 bits 2's Complement Signed Value, 3 Decimal
Places
Example: -1.234 stored as -1234 i.e. 64302
F30 signed 32 bits 2's Complement Signed Long Value
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -123456 stored as -123456
i.e. 1st word: FFFE hex, 2nd word: 1DC0 hex
F31 signed 32 bits 2's Complement Signed Long Value, 1
Decimal Place
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -12345.6 stored as -123456

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-131


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


i.e. 1st word: FFFE hex, 2nd word: 1DC0 hex
F32 signed 32 bits 2's Complement Signed Long Value, 2
Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -1234.56 stored as -123456
i.e. 1st word: FFFE hex, 2nd word: 1DC0 hex
F33 signed 32 bits 2's Complement Signed Long Value, 3
Decimal Places
1st 16 bits High Order Word of Long Value
2nd 16 bits Low Order Word of Long Value
Example: -123.456 stored as -123456
i.e. 1st word: FFFE hex, 2nd word: 1DC0 hex
F50 unsigned 32 bits Time and Date (unsigned 32-bit integer)
Indicates the current time in
seconds elapsed since 00:00:00
January 1, 1970.
F51 unsigned 32 bits Number of Microseconds (unsigned 32-bit
integer)
Fraction of seconds count
F52 unsigned 32 bits RTC Time in Seconds
F53 unsigned 32 bits Date MM/DD/YYYY
F54 unsigned 32 bits Time HH:MM:SS:hh
F60_18 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 18 characters long
F60_8A unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Grandmaster ID
F60_34 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 34 characters long
F60_26 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 26 characters long
F60_14 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 14 characters long
F60_6 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text For Units
F60_22 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Secure Passwords. 22 characters long
F60_80 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 80 characters long
F60_6A unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
MAC Address
F60_12 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned

11-132 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


Custom Text. 12 characters long
F60_246 unsigned 16 bits Two 8-BIT Characters Packed Into 16-BIT
Unsigned
Custom Text. 246 characters long
F70 unsigned 32 bits IP Address
F71 unsigned 32 bits CPLD / FPGA Version
FC100 unsigned 16 bits Function Enable
0 Disabled
1 Trip
2 Alarm
3 Latched Alarm
4 Configurable
FC100A unsigned 16 bits Alarm Function Enable
0 Disabled
2 Alarm
3 Latched Alarm
4 Configurable
FC100B unsigned 16 bits Function Enable
0 Disabled
1 Close
2 Alarm
3 Latched Alarm
4 Configurable
FC101 unsigned 16 bits Targets
0 Disabled
1 Self-Reset
2 Latched
FC102 unsigned 16 bits Bank Input
0 None
1 J1
2 J2
3 K1
4 K2
FC103 unsigned 16 bits Frequency and Phase Reference
Upper 8 bits Type
1 = 3VT, 2 = Vx, 3 = CT
Lower 8 bits Bank (uses FC102 format)
1 = J1, 2 = J2, 3 = K1, 4 = K2
0 None
0x12 J2-3VT
0x22 J2-Vx
0x31 J1-CT
FC103A unsigned 16 bits Frequency Reference
Upper 8 bits Type
1 = 3VT, 2 = Vx
Lower 8 bits Bank (uses FC102 format)
2 = J2, 4 = K2

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-133


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x12 J2-3VT
0x22 J2-Vx
FC106 unsigned 16 bits Voltage Transformer Connection Type
0 Wye
1 Delta
FC107 unsigned 16 bits Supply Frequency
0 60 Hz
1 50 Hz
FC110 unsigned 16 bits Hardware Revision
1 A
FC114 unsigned 16 bits Relay Status
0 Not Ready
1 Ready
FC118 unsigned 16 bits Simulated Key Press / Last Key Pressed
0 None
129 QuickKey 1
130 QuickKey 2
131 QuickKey 3
132 QuickKey 4
133 QuickKey 5
134 USERPushButton1
135 USERPushButton2
136 USERPushButton3
141 No Key Press
142 Nav Up Key
143 Nav Left Key
144 Nav Down Key
145 Nav Right Key
146 Up Key
147 Down Key
148 Enter Key
149 Menu Key
150 Escape Key
151 Reset Key
152 Help Key
FC119 unsigned 16 bits Temperature Units
0 Celsius
1 Fahrenheit
FC123 unsigned 16 bits Contact Input Voltage Threshold
0 17 Vdc
1 33 Vdc
2 84 Vdc
3 166 Vdc
FC124A unsigned 16 bits Phase Rotation
0 ABC
1 ACB
FC126 unsigned 16 bits Disabled / Enabled Selection

11-134 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0 Disabled
1 Enabled
FC126A unsigned 16 bits Off / On Selection
0 Off
1 On
FC126B unsigned 16 bits No / Yes Selection
0 NO
1 YES
FC131 unsigned 16 bits Phase UV Curve
0 Definite Time
1 Inverse Time
FC132A unsigned 16 bits Active Setpoint Group
0 SP Group 1
1 SP Group 2
2 SP Group 3
3 SP Group 4
4 SP Group 5
5 SP Group 6
FC132 unsigned 16 bits Edit Group
0 SP Group 1 Active
1 SP Group 2 Active
2 SP Group 3 Active
3 SP Group 4 Active
4 SP Group 5 Active
5 SP Group 6 Active
0xFFFF Active Group

Code Type Definition


FC134 unsigned 32 bits Cause of Event
0 No Evnt/Trp ToDate
1 Ctrl. Pwr Lost
2 Ctrl. Pwr Applied
3 Date or Time Set
4 Reset
5 Lockout Rst Closed
6 Factory Reload
7 Clock Not Set
8 IRIG-B Failure
9 Reset Trip Counter
11 Clear Event Rec
12 Clear Transt Rec
13 Clear Therm Cap
14 Comm. Alert 1
15 Comm. Alert 2
16 Comm. Alert 3
19 Ambient Temp. >80C

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-135


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


20 RMIO Mismatch
22 Emergency Restart
23 Trans. Rec Trigger
24 Failed Auth
25 Auth Lockout
26 Firmware Upgd
27 Firmware Lock
28 Setting Chg
29 Setting Lock
30 Login
31 Logoff
32 Event Rate High
33 Not Calibrated
34 Prototype Software
35 Invalid MAC Address
36 General Target Message
37 Relay Not Ready
39 WiFi Connected
40 WiFi Disconnected
41 Order Code Error
42 CPU Serial# Invalid
43 Slot F IO S/N Invalid
44 Slot G IO S/N Invalid
45 Slot H IO S/N Invalid
46 Slot B IO S/N Invalid
47 Slot C IO S/N Invalid
48 Slot J IO S/N Invalid
49 Slot K IO S/N Invalid
50 COMM Serial# Invalid
51 FP Serial# Invalid
52 PSU Serial# Invalid
53 RTC Error
54 FLASH Error
55 Link Error Primary
56 Traffic Error Primary
57 Ambient Temperature >80C
58 Link Error Secondary
59 Traffic Error Secondary
60 Version Mismatch
61 SPI Error
62 CAN_1 Error
63 CAN_2 Error
64 Product Serial Invalid
65 SelfTestFWUpdate
66 WiFi Default Settings
67 SNTP Failure
68 PTP Failure

11-136 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


69 RTC Failure
0x200 CI 1 On
0x201 CI 2 On
0x202 CI 3 On
0x203 CI 4 On
0x204 CI 5 On
0x205 CI 6 On
0x206 CI 7 On
0x207 CI 8 On
0x208 CI 9 On
0x209 CI 10 On
0x20A CI 11 On
0x20B CI 12 On
0x20C CI 13 On
0x20D CI 14 On
0x300 CI 1 Off
0x301 CI 2 Off
0x302 CI 3 Off
0x303 CI 4 Off
0x304 CI 5 Off
0x305 CI 6 Off
0x306 CI 7 Off
0x307 CI 8 Off
0x308 CI 9 Off
0x309 CI 10 Off
0x30A CI 11 Off
0x30B CI 12 Off
0x30C CI 13 Off
0x30D CI 14 Off
0x400 VI 1 On
0x401 VI 2 On
0x402 VI 3 On
0x403 VI 4 On
0x404 VI 5 On
0x405 VI 6 On
0x406 VI 7 On
0x407 VI 8 On
0x408 VI 9 On
0x409 VI 10 On
0x40A VI 11 On
0x40B VI 12 On
0x40C VI 13 On
0x40D VI 14 On
0x40E VI 15 On
0x40F VI 16 On
0x410 VI 17 On
0x411 VI 18 On

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-137


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x412 VI 19 On
0x413 VI 20 On
0x414 VI 21 On
0x415 VI 22 On
0x416 VI 23 On
0x417 VI 24 On
0x418 VI 25 On
0x419 VI 26 On
0x41A VI 27 On
0x41B VI 28 On
0x41C VI 29 On
0x41D VI 30 On
0x41E VI 31 On
0x41F VI 32 On
0x500 VI 1 Off
0x501 VI 2 Off
0x502 VI 3 Off
0x503 VI 4 Off
0x504 VI 5 Off
0x505 VI 6 Off
0x506 VI 7 Off
0x507 VI 8 Off
0x508 VI 9 Off
0x509 VI 10 Off
0x50A VI 11 Off
0x50B VI 12 Off
0x50C VI 13 Off
0x50D VI 14 Off
0x50E VI 15 Off
0x50F VI 16 Off
0x510 VI 17 Off
0x511 VI 18 Off
0x512 VI 19 Off
0x513 VI 20 Off
0x514 VI 21 Off
0x515 VI 22 Off
0x516 VI 23 Off
0x517 VI 24 Off
0x518 VI 25 Off
0x519 VI 26 Off
0x51A VI 27 Off
0x51B VI 28 Off
0x51C VI 29 Off
0x51D VI 30 Off
0x51E VI 31 Off
0x51F VI 32 Off
0x600 VO 1 On

11-138 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x601 VO 2 On
0x602 VO 3 On
0x603 VO 4 On
0x604 VO 5 On
0x605 VO 6 On
0x606 VO 7 On
0x607 VO 8 On
0x608 VO 9 On
0x609 VO 10 On
0x60A VO 11 On
0x60B VO 12 On
0x60C VO 13 On
0x60D VO 14 On
0x60E VO 15 On
0x60F VO 16 On
0x610 VO 17 On
0x611 VO 18 On
0x612 VO 19 On
0x613 VO 20 On
0x614 VO 21 On
0x615 VO 22 On
0x616 VO 23 On
0x617 VO 24 On
0x618 VO 25 On
0x619 VO 26 On
0x61A VO 27 On
0x61B VO 28 On
0x61C VO 29 On
0x61D VO 30 On
0x61E VO 31 On
0x61F VO 32 On
0x700 VO 1 Off
0x701 VO 2 Off
0x702 VO 3 Off
0x703 VO 4 Off
0x704 VO 5 Off
0x705 VO 6 Off
0x706 VO 7 Off
0x707 VO 8 Off
0x708 VO 9 Off
0x709 VO 10 Off
0x70A VO 11 Off
0x70B VO 12 Off
0x70C VO 13 Off
0x70D VO 14 Off
0x70E VO 15 Off
0x70F VO 16 Off

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-139


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x710 VO 17 Off
0x711 VO 18 Off
0x712 VO 19 Off
0x713 VO 20 Off
0x714 VO 21 Off
0x715 VO 22 Off
0x716 VO 23 Off
0x717 VO 24 Off
0x718 VO 25 Off
0x719 VO 26 Off
0x71A VO 27 Off
0x71B VO 28 Off
0x71C VO 29 Off
0x71D VO 30 Off
0x71E VO 31 Off
0x71F VO 32 Off
0x800 Rly 1 On
0x801 Rly 2 On
0x802 Rly 3 On
0x803 Rly 4 On
0x807 Rly 8 On
0x808 Rly 9 On
0x809 Rly 10 On
0x80A Rly 11 On
0x80B Rly 12 On
0x80F Rly 16 On
0x900 Rly 1 Off
0x901 Rly 2 Off
0x902 Rly 3 Off
0x903 Rly 4 Off
0x907 Rly 8 Off
0x908 Rly 9 Off
0x909 Rly 10 Off
0x90A Rly 11 Off
0x90B Rly 12 Off
0x90F Rly 16 Off
0xE00 Rem Ip 1 On
0xE01 Rem Ip 2 On
0xE02 Rem Ip 3 On
0xE03 Rem Ip 4 On
0xE04 Rem Ip 5 On
0xE05 Rem Ip 6 On
0xE06 Rem Ip 7 On
0xE07 Rem Ip 8 On
0xE08 Rem Ip 9 On
0xE09 Rem Ip 10 On
0xE0A Rem Ip 11 On

11-140 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0xE0B Rem Ip 12 On
0xE0C Rem Ip 13 On
0xE0D Rem Ip 14 On
0xE0E Rem Ip 15 On
0xE0F Rem Ip 16 On
0xE10 Rem Ip 17 On
0xE11 Rem Ip 18 On
0xE12 Rem Ip 19 On
0xE13 Rem Ip 20 On
0xE14 Rem Ip 21 On
0xE15 Rem Ip 22 On
0xE16 Rem Ip 23 On
0xE17 Rem Ip 24 On
0xE18 Rem Ip 25 On
0xE19 Rem Ip 26 On
0xE1A Rem Ip 27 On
0xE1B Rem Ip 28 On
0xE1C Rem Ip 29 On
0xE1D Rem Ip 30 On
0xE1E Rem Ip 31 On
0xE1F Rem Ip 32 On
0xF00 Rem Ip 1 Off
0xF01 Rem Ip 2 Off
0xF02 Rem Ip 3 Off
0xF03 Rem Ip 4 Off
0xF04 Rem Ip 5 Off
0xF05 Rem Ip 6 Off
0xF06 Rem Ip 7 Off
0xF07 Rem Ip 8 Off
0xF08 Rem Ip 9 Off
0xF09 Rem Ip 10 Off
0xF0A Rem Ip 11 Off
0xF0B Rem Ip 12 Off
0xF0C Rem Ip 13 Off
0xF0D Rem Ip 14 Off
0xF0E Rem Ip 15 Off
0xF0F Rem Ip 16 Off
0xF10 Rem Ip 17 Off
0xF11 Rem Ip 18 Off
0xF12 Rem Ip 19 Off
0xF13 Rem Ip 20 Off
0xF14 Rem Ip 21 Off
0xF15 Rem Ip 22 Off
0xF16 Rem Ip 23 Off
0xF17 Rem Ip 24 Off
0xF18 Rem Ip 25 Off
0xF19 Rem Ip 26 Off

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-141


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0xF1A Rem Ip 27 Off
0xF1B Rem Ip 28 Off
0xF1C Rem Ip 29 Off
0xF1D Rem Ip 30 Off
0xF1E Rem Ip 31 Off
0xF1F Rem Ip 32 Off
0x800002 Any Trip
0x800202 Any Alarm
0x800802 Any Block
0x800A02 Any PKP
0x800C02 Any OP
0x800E02 Reset OP
0x800E08 Reset OP (PB)
0x800E10 Reset OP (Operand)
0x800E20 Reset OP (Comms)
0x801002 Setpoint Access OP
0x801202 Active Target
0x801402 In-Service
0x801602 Testing ON
0x801802 Any Major Error
0x801A02 Any Minor Error
0x801C02 Von
0x801C04 Voff
0x801E02 Von
0x801E04 Voff
0x802802 Critical Fail OP
0x802C01 Phase TOC 1 PKP
0x802C02 Phase TOC 1 OP
0x802C08 Phase TOC 1 PKP A
0x802C10 Phase TOC 1 PKP B
0x802C20 Phase TOC 1 PKP C
0x802C40 Phase TOC 1 OP A
0x802C80 Phase TOC 1 OP B
0x802D00 Phase TOC 1 OP C
0x802E01 Phase TOC 2 PKP
0x802E02 Phase TOC 2 OP
0x802E08 Phase TOC 2 PKP A
0x802E10 Phase TOC 2 PKP B
0x802E20 Phase TOC 2 PKP C
0x802E40 Phase TOC 2 OP A
0x802E80 Phase TOC 2 OP B
0x802F00 Phase TOC 2 OP C
0x803201 Phase IOC 1 PKP
0x803202 Phase IOC 1 OP
0x803208 Phase IOC 1 PKP A
0x803210 Phase IOC 1 PKP B
0x803220 Phase IOC 1 PKP C

11-142 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x803240 Phase IOC 1 OP A
0x803280 Phase IOC 1 OP B
0x803300 Phase IOC 1 OP C
0x803401 Phase IOC 2 PKP
0x803402 Phase IOC 2 OP
0x803408 Phase IOC 2 PKP A
0x803410 Phase IOC 2 PKP B
0x803420 Phase IOC 2 PKP C
0x803440 Phase IOC 2 OP A
0x803480 Phase IOC 2 OP B
0x803500 Phase IOC 2 OP C
0x803802 Ph Dir OC REV
0x803840 Ph Dir OC REV A
0x803880 Ph Dir OC REV B
0x803900 Ph Dir OC REV C
0x803A01 Neutral TOC 1 PKP
0x803A02 Neutral TOC 1 OP
0x803C01 Neutral TOC 2 PKP
0x803C02 Neutral TOC 2 OP
0x803E01 Neutral IOC 1 PKP
0x803E02 Neutral IOC 1 OP
0x804001 Neutral IOC 2 PKP
0x804002 Neutral IOC 2 OP
0x804208 Ntrl Dir OC FWD
0x804240 Ntrl Dir OC REV
0x804401 Ground TOC 1 PKP
0x804402 Ground TOC 1 OP
0x804C01 Ground IOC 1 PKP
0x804C02 Ground IOC 1 OP
0x805408 Gnd Dir OC FWD
0x805440 Gnd Dir OC REV
0x805601 SGnd TOC 1 PKP
0x805602 SGnd TOC 1 OP
0x805A01 SGnd IOC 1 PKP
0x805A02 Sen Gnd IOC 1 OP
0x805E08 SGnd Dir OC FWD
0x805E40 SGnd Dir OC REV
0x806001 RGF 1 PKP
0x806002 RGF 1 OP
0x806008 RGF 1 Superv ON
0x806601 NegSeq TOC 1 PKP
0x806602 NegSeq TOC 1 OP
0x806A01 NegSeq IOC 1 PKP
0x806A02 NegSeq IOC 1 OP
0x806E08 NegSeq DirOC FWD
0x806E40 NegSeq DirOC REV
0x807001 Broken Cond PKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-143


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x807002 Broken Cond OP
0x807201 Load Encro PKP
0x807202 Load Encro OP
0x807401 Thermal PKP
0x807402 Thermal OP
0x807408 Thermal PKP A
0x807410 Thermal PKP B
0x807420 Thermal PKP C
0x807440 Thermal OP A
0x807480 Thermal OP B
0x807500 Thermal OP C
0x807602 Thermal Alarm
0x807640 Thermal Alarm A
0x807680 Thermal Alarm B
0x807700 Thermal Alarm C
0x807801 Phase UV 1 PKP
0x807802 Phase UV 1 OP
0x807808 Phase UV 1 PKP A
0x807810 Phase UV 1 PKP B
0x807820 Phase UV 1 PKP C
0x807840 Phase UV 1 OP A
0x807880 Phase UV 1 OP B
0x807900 Phase UV 1 OP C
0x807A01 Phase UV 2 PKP
0x807A02 Phase UV 2 OP
0x807A08 Phase UV 2 PKP A
0x807A10 Phase UV 2 PKP B
0x807A20 Phase UV 2 PKP C
0x807A40 Phase UV 2 OP A
0x807A80 Phase UV 2 OP B
0x807B00 Phase UV 2 OP C
0x807C01 Phase OV 1 PKP
0x807C02 Phase OV 1 OP
0x807C08 Phase OV 1 PKP A
0x807C10 Phase OV 1 PKP B
0x807C20 Phase OV 1 PKP C
0x807C40 Phase OV 1 OP A
0x807C80 Phase OV 1 OP B
0x807D00 Phase OV 1 OP C
0x807E01 Phase OV 2 PKP
0x807E02 Phase OV 2 OP
0x807E08 Phase OV 2 PKP A
0x807E10 Phase OV 2 PKP B
0x807E20 Phase OV 2 PKP C
0x807E40 Phase OV 2 OP A
0x807E80 Phase OV 2 OP B
0x807F00 Phase OV 2 OP C

11-144 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x808001 Aux UV 1 PKP
0x808002 Aux UV 1 OP
0x808201 Aux UV 2 PKP
0x808202 Aux UV 2 OP
0x808401 Aux OV PKP
0x808402 Aux OV OP
0x808601 Neutral OV 1 PKP
0x808602 Neutral OV 1 OP
0x808A01 Neg Seq OV 1 PKP
0x808A02 Neg Seq OV 1 OP
0x808E01 DirPwr 1 PKP
0x808E02 DirPwr 1 OP
0x808E08 DirPwr 1 Stg1 PKP
0x808E10 DirPwr 1 Stg2 PKP
0x808E40 DirPwr 1 Stg1 OP
0x808E80 DirPwr 1 Stg2 OP
0x809001 Dir Pwr 2 PKP
0x809002 Dir Pwr 2 OP
0x809008 DirPwr 2 Stg1 PKP
0x809010 DirPwr 2 Stg2 PKP
0x809040 DirPwr 2 Stg1 OP
0x809080 DirPwr 2 Stg2 OP
0x809201 Watt GndFlt 1 PKP
0x809202 Watt GndFlt 1 OP
0x809601 Underfreq 1 PKP
0x809602 Underfreq 1 OP
0x809801 Underfreq 2 PKP
0x809802 Underfreq 2 OP
0x809A01 Underfreq 3 PKP
0x809A02 Underfreq 3 OP
0x809C01 Underfreq 4 PKP
0x809C02 Underfreq 4 OP
0x809E01 Overfreq 1 PKP
0x809E02 Overfreq 1 OP
0x80A001 Overfreq 2 PKP
0x80A002 Overfreq 2 OP
0x80A201 FreqRate1 PKP
0x80A202 FreqRate1 OP
0x80A208 FreqRate1 Up PKP
0x80A210 FreqRate1 Dwn PKP
0x80A240 FreqRate1 Up OP
0x80A280 FreqRate1 Dwn OP
0x80AA02 Group 1 Active
0x80AC02 Group 2 Active
0x80AE02 Group 3 Active
0x80B002 Group 4 Active
0x80B202 Group 5 Active

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-145


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x80B402 Group 6 Active
0x80B608 Local Mode ON
0x80B610 Local Mode OFF
0x80B808 BKR1 Local Open
0x80B810 BKR1 Remote Open
0x80BE08 BKR1 Local Close
0x80BE10 BKR1 Remote Close
0x80C401 Trip Bus 1 PKP
0x80C402 Trip Bus 1 OP
0x80C601 Trip Bus 2 PKP
0x80C602 Trip Bus 2 OP
0x80C801 Trip Bus 3 PKP
0x80C802 Trip Bus 3 OP
0x80CA01 Trip Bus 4 PKP
0x80CA02 Trip Bus 4 OP
0x80CC01 Trip Bus 5 PKP
0x80CC02 Trip Bus 5 OP
0x80CE01 Trip Bus 6 PKP
0x80CE02 Trip Bus 6 OP
0x80D002 BF1 OP
0x80D008 BF1 Retrip
0x80D010 BF1 Highset OP
0x80D020 BF1 Lowset OP
0x80D040 BF1 52b Superv OP
0x80D602 Sync1 Close Perm
0x80D608 Sync1 Live Bus
0x80D610 Sync1 Live Line
0x80D620 Sync1 Dead Src OK
0x80D640 Sync1 Dead Bus
0x80D680 Sync1 Dead Line
0x80D700 Sync1 OK
0x80DA02 Manual Cls Blk OP
0x80DC02 VT Fuse Fail1 OP
0x80DC08 VT Fuse1 V Loss
0x80E001 Cold Load 1 PKP
0x80E002 Cold Load 1 OP
0x80E401 Ph UV Restore PKP
0x80E408 Aux UV Restore PKP
0x80E440 Aux UV Restore OP
0x80E480 Ph UV Restore OP
0x80E500 UV Restore Init
0x80E601 INC1 BKR Con&Clsd
0x80E602 INC1 Close Tie-BKR
0x80E604 INC1 Trnsfr Ready
0x80E608 INC2 BKR Con&Clsd
0x80E610 INC2 Close Tie-BKR
0x80E620 INC2 Trnsfr Ready

11-146 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x80E640 Tie-BKR Trfer Rdy
0x80E680 Tie-BKR Conn&Clsd
0x80E700 Transfer Not Ready
0x80E801 AR1 Disabled
0x80E808 AR1 Enabled
0x80E810 AR1 Initiated
0x80E820 AR1 In Progress
0x80E840 AR1 Close
0x80E880 AR1 Lockout
0x80E900 AR1 Man Cls Blk
0x80EA08 AR1 Shot Cnt 0
0x80EA10 AR1 Shot Cnt 1
0x80EA20 AR1 Shot Cnt 2
0x80EA40 AR1 Shot Cnt 3
0x80EA80 AR1 Shot Cnt 4
0x80EC08 AR1 ShotRdc to 1
0x80EC10 AR1 ShotRdc to 2
0x80EC20 AR1 ShotRdc to 3
0x80EC40 AR1 ShotRdc to LO
0x80EE08 AR1 Rate High
0x80EE10 AR1 Rate HI Lockt
0x80EE20 AR1 Coordinating
0x80F801 UF Restore PKP
0x80F802 UF Restore OP
0x80F840 UF Restore Init
0x80FA02 BKR1 Closed
0x80FC02 BKR1 Opened
0x80FE02 BKR1 Unkwn State
0x810002 BKR1 Disconnected
0x810004 BKR1 Connected
0x811E01 TripCoil Mon 1 PKP
0x811E02 TripCoil Mon 1 OP
0x812401 Cls Coil Mon 1 PKP
0x812402 Cls Coil Mon 1 OP
0x812A02 BKR1 Arc OP
0x813001 BKR1 Charge Fail
0x813002 BKR1 Hlth PKP
0x813008 BKR1 Hlth Trip PKP
0x813010 BKR1 Hlth Cls PKP
0x813020 BKR1 Hlth Chg PKP
0x813040 BKR1 Hlth OP Fail
0x813601 BKR1 Arc Fail
0x813608 BKR1 Arc PKP A
0x813610 BKR1 Arc PKP B
0x813620 BKR1 Arc PKP C
0x813640 BKR1 Engy PKP A
0x813680 BKR1 Engy PKP B

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-147


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x813700 BKR1 Engy PKP C
0x813C08 PF 1 Switch-In
0x813C10 PF 1 Switch-Out
0x813C40 PF 1 Switch-In OP
0x813C80 PF 1 Switch-Out OP
0x813E08 PF 2 Switch-In
0x813E10 PF 2 Switch-Out
0x813E40 PF 2 Switch-In OP
0x813E80 PF 2 Switch-Out OP
0x814001 Current Dmd PKP
0x814008 Current Dmd PKP A
0x814010 Current Dmd PKP B
0x814020 Current Dmd PKP C
0x814201 RealPwr Dmd PKP
0x814401 ReactvPwr Dmd PKP
0x814601 ApprntPwr Dmd PKP
0x819208 Pos Wthrs Pulse OP
0x819210 Neg Wthrs Pulse OP
0x819220 Pos Varh Pulse OP
0x819240 Neg Varh Pulse OP
0x819408 Counter 1 LO
0x819410 Counter 1 EQL
0x819420 Counter 1 HI
0x819440 Counter 1 at Limit
0x819608 Counter 2 LO
0x819610 Counter 2 EQL
0x819620 Counter 2 HI
0x819640 Counter 2 at Limit
0x819808 Counter 3 LO
0x819810 Counter 3 EQL
0x819820 Counter 3 HI
0x819840 Counter 3 at Limit
0x819A08 Counter 4 LO
0x819A10 Counter 4 EQL
0x819A20 Counter 4 HI
0x819A40 Counter 4 at Limit
0x819C08 Counter 5 LO
0x819C10 Counter 5 EQL
0x819C20 Counter 5 HI
0x819C40 Counter 5 at Limit
0x819E08 Counter 6 LO
0x819E10 Counter 6 EQL
0x819E20 Counter 6 HI
0x819E40 Counter 6 at Limit
0x81A008 Counter 7 LO
0x81A010 Counter 7 EQL
0x81A020 Counter 7 HI

11-148 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x81A040 Counter 7 at Limit
0x81A208 Counter 8 LO
0x81A210 Counter 8 EQL
0x81A220 Counter 8 HI
0x81A240 Counter 8 at Limit
0x81A408 Counter 9 LO
0x81A410 Counter 9 EQL
0x81A420 Counter 9 HI
0x81A440 Counter 9 at Limit
0x81A608 Counter 10 LO
0x81A610 Counter 10 EQL
0x81A620 Counter 10 HI
0x81A640 Countr 10 at Limit
0x81A808 Counter 11 LO
0x81A810 Counter 11 EQL
0x81A820 Counter 11 HI
0x81A840 Countr 11 at Limit
0x81AA08 Counter 12 LO
0x81AA10 Counter 12 EQL
0x81AA20 Counter 12 HI
0x81AA40 Countr 12 at Limit
0x81AC08 Counter 13 LO
0x81AC10 Counter 13 EQL
0x81AC20 Counter 13 HI
0x81AC40 Countr 13 at Limit
0x81AE08 Counter 14 LO
0x81AE10 Counter 14 EQL
0x81AE20 Counter 14 HI
0x81AE40 Countr 14 at Limit
0x81B008 Counter 15 LO
0x81B010 Counter 15 EQL
0x81B020 Counter 15 HI
0x81B040 Countr 15 at Limit
0x81B208 Counter 16 LO
0x81B210 Counter 16 EQL
0x81B220 Counter 16 HI
0x81B240 Countr 16 at Limit
0x81B402 NV Latch 1 ON
0x81B404 NV Latch 1 OFF
0x81B602 NV Latch 2 ON
0x81B604 NV Latch 2 OFF
0x81B802 NV Latch 3 ON
0x81B804 NV Latch 3 OFF
0x81BA02 NV Latch 4 ON
0x81BA04 NV Latch 4 OFF
0x81BC02 NV Latch 5 ON
0x81BC04 NV Latch 5 OFF

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-149


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x81BE02 NV Latch 6 ON
0x81BE04 NV Latch 6 OFF
0x81C002 NV Latch 7 ON
0x81C004 NV Latch 7 OFF
0x81C202 NV Latch 8 ON
0x81C204 NV Latch 8 OFF
0x81C402 NV Latch 9 ON
0x81C404 NV Latch 9 OFF
0x81C602 NV Latch 10 ON
0x81C604 NV Latch 10 OFF
0x81C802 NV Latch 11 ON
0x81C804 NV Latch 11 OFF
0x81CA02 NV Latch 12 ON
0x81CA04 NV Latch 12 OFF
0x81CC02 NV Latch 13 ON
0x81CC04 NV Latch 13 OFF
0x81CE02 NV Latch 14 ON
0x81CE04 NV Latch 14 OFF
0x81D002 NV Latch 15 ON
0x81D004 NV Latch 15 OFF
0x81D202 NV Latch 16 ON
0x81D204 NV Latch 16 OFF
0x81D402 PB 1 ON
0x81D404 PB 1 OFF
0x81D602 PB 2 ON
0x81D604 PB 2 OFF
0x81D802 PB 3 ON
0x81D804 PB 3 OFF
0x81DA01 Role Admin Act
0x81DA04 Authentication Lockout
0x81DA10 Authentication Fail
0x81DA20 Unauth Change Attempt
0x81DA40 Role Operator Act
0x81DA80 Role Observer Act
0x81DB00 Radius Srv Unavailable
0x81DE02 Transfer Initiated
FC134 unsigned 32 bits Cause of Event
0 No Evnt/Trp ToDate
1 Ctrl. Pwr Lost
2 Ctrl. Pwr Applied
3 Date or Time Set
4 Reset
5 Lockout Rst Closed
6 Factory Reload
7 Clock Not Set
8 IRIG-B Failure
9 Reset Trip Counter

11-150 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


11 Clear Event Rec
12 Clear Transt Rec
13 Clear Therm Cap
14 Comm. Alert 1
15 Comm. Alert 2
16 Comm. Alert 3
19 Ambient Temp. >80C
20 RMIO Mismatch
22 Emergency Restart
23 Trans. Rec Trigger
24 Failed Auth
25 Auth Lockout
26 Firmware Upgd
27 Firmware Lock
28 Setting Chg
29 Setting Lock
30 Login
31 Logoff
32 Event Rate High
33 Not Calibrated
34 Prototype Software
35 Invalid MAC Address
36 General Target Message
37 Relay Not Ready
39 WiFi Connected
40 WiFi Disconnected
41 Order Code Error
42 CPU Serial# Invalid
43 Slot F IO S/N Invalid
44 Slot G IO S/N Invalid
45 Slot H IO S/N Invalid
46 Slot B IO S/N Invalid
47 Slot C IO S/N Invalid
48 Slot J IO S/N Invalid
49 Slot K IO S/N Invalid
50 COMM Serial# Invalid
51 FP Serial# Invalid
52 PSU Serial# Invalid
53 RTC Error
54 FLASH Error
55 Link Error Primary
56 Traffic Error Primary
57 Ambient Temperature >80C
58 Link Error Secondary
59 Traffic Error Secondary
60 Version Mismatch
61 SPI Error

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-151


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


62 CAN_1 Error
63 CAN_2 Error
64 Product Serial Invalid
65 SelfTestFWUpdate
66 WiFi Default Settings
67 SNTP Failure
68 PTP Failure
69 RTC Failure
0x200 CI 1 On
0x201 CI 2 On
0x202 CI 3 On
0x203 CI 4 On
0x204 CI 5 On
0x205 CI 6 On
0x206 CI 7 On
0x207 CI 8 On
0x208 CI 9 On
0x209 CI 10 On
0x20A CI 11 On
0x20B CI 12 On
0x20C CI 13 On
0x20D CI 14 On
0x300 CI 1 Off
0x301 CI 2 Off
0x302 CI 3 Off
0x303 CI 4 Off
0x304 CI 5 Off
0x305 CI 6 Off
0x306 CI 7 Off
0x307 CI 8 Off
0x308 CI 9 Off
0x309 CI 10 Off
0x30A CI 11 Off
0x30B CI 12 Off
0x30C CI 13 Off
0x30D CI 14 Off
0x400 VI 1 On
0x401 VI 2 On
0x402 VI 3 On
0x403 VI 4 On
0x404 VI 5 On
0x405 VI 6 On
0x406 VI 7 On
0x407 VI 8 On
0x408 VI 9 On
0x409 VI 10 On
0x40A VI 11 On

11-152 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x40B VI 12 On
0x40C VI 13 On
0x40D VI 14 On
0x40E VI 15 On
0x40F VI 16 On
0x410 VI 17 On
0x411 VI 18 On
0x412 VI 19 On
0x413 VI 20 On
0x414 VI 21 On
0x415 VI 22 On
0x416 VI 23 On
0x417 VI 24 On
0x418 VI 25 On
0x419 VI 26 On
0x41A VI 27 On
0x41B VI 28 On
0x41C VI 29 On
0x41D VI 30 On
0x41E VI 31 On
0x41F VI 32 On
0x500 VI 1 Off
0x501 VI 2 Off
0x502 VI 3 Off
0x503 VI 4 Off
0x504 VI 5 Off
0x505 VI 6 Off
0x506 VI 7 Off
0x507 VI 8 Off
0x508 VI 9 Off
0x509 VI 10 Off
0x50A VI 11 Off
0x50B VI 12 Off
0x50C VI 13 Off
0x50D VI 14 Off
0x50E VI 15 Off
0x50F VI 16 Off
0x510 VI 17 Off
0x511 VI 18 Off
0x512 VI 19 Off
0x513 VI 20 Off
0x514 VI 21 Off
0x515 VI 22 Off
0x516 VI 23 Off
0x517 VI 24 Off
0x518 VI 25 Off
0x519 VI 26 Off

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-153


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x51A VI 27 Off
0x51B VI 28 Off
0x51C VI 29 Off
0x51D VI 30 Off
0x51E VI 31 Off
0x51F VI 32 Off
0x600 VO 1 On
0x601 VO 2 On
0x602 VO 3 On
0x603 VO 4 On
0x604 VO 5 On
0x605 VO 6 On
0x606 VO 7 On
0x607 VO 8 On
0x608 VO 9 On
0x609 VO 10 On
0x60A VO 11 On
0x60B VO 12 On
0x60C VO 13 On
0x60D VO 14 On
0x60E VO 15 On
0x60F VO 16 On
0x610 VO 17 On
0x611 VO 18 On
0x612 VO 19 On
0x613 VO 20 On
0x614 VO 21 On
0x615 VO 22 On
0x616 VO 23 On
0x617 VO 24 On
0x618 VO 25 On
0x619 VO 26 On
0x61A VO 27 On
0x61B VO 28 On
0x61C VO 29 On
0x61D VO 30 On
0x61E VO 31 On
0x61F VO 32 On
0x700 VO 1 Off
0x701 VO 2 Off
0x702 VO 3 Off
0x703 VO 4 Off
0x704 VO 5 Off
0x705 VO 6 Off
0x706 VO 7 Off
0x707 VO 8 Off
0x708 VO 9 Off

11-154 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x709 VO 10 Off
0x70A VO 11 Off
0x70B VO 12 Off
0x70C VO 13 Off
0x70D VO 14 Off
0x70E VO 15 Off
0x70F VO 16 Off
0x710 VO 17 Off
0x711 VO 18 Off
0x712 VO 19 Off
0x713 VO 20 Off
0x714 VO 21 Off
0x715 VO 22 Off
0x716 VO 23 Off
0x717 VO 24 Off
0x718 VO 25 Off
0x719 VO 26 Off
0x71A VO 27 Off
0x71B VO 28 Off
0x71C VO 29 Off
0x71D VO 30 Off
0x71E VO 31 Off
0x71F VO 32 Off
0x800 Rly 1 On
0x801 Rly 2 On
0x802 Rly 3 On
0x803 Rly 4 On
0x807 Rly 8 On
0x808 Rly 9 On
0x809 Rly 10 On
0x80A Rly 11 On
0x80B Rly 12 On
0x80F Rly 16 On
0x900 Rly 1 Off
0x901 Rly 2 Off
0x902 Rly 3 Off
0x903 Rly 4 Off
0x907 Rly 8 Off
0x908 Rly 9 Off
0x909 Rly 10 Off
0x90A Rly 11 Off
0x90B Rly 12 Off
0x90F Rly 16 Off
0xE00 Rem Ip 1 On
0xE01 Rem Ip 2 On
0xE02 Rem Ip 3 On
0xE03 Rem Ip 4 On

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-155


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0xE04 Rem Ip 5 On
0xE05 Rem Ip 6 On
0xE06 Rem Ip 7 On
0xE07 Rem Ip 8 On
0xE08 Rem Ip 9 On
0xE09 Rem Ip 10 On
0xE0A Rem Ip 11 On
0xE0B Rem Ip 12 On
0xE0C Rem Ip 13 On
0xE0D Rem Ip 14 On
0xE0E Rem Ip 15 On
0xE0F Rem Ip 16 On
0xE10 Rem Ip 17 On
0xE11 Rem Ip 18 On
0xE12 Rem Ip 19 On
0xE13 Rem Ip 20 On
0xE14 Rem Ip 21 On
0xE15 Rem Ip 22 On
0xE16 Rem Ip 23 On
0xE17 Rem Ip 24 On
0xE18 Rem Ip 25 On
0xE19 Rem Ip 26 On
0xE1A Rem Ip 27 On
0xE1B Rem Ip 28 On
0xE1C Rem Ip 29 On
0xE1D Rem Ip 30 On
0xE1E Rem Ip 31 On
0xE1F Rem Ip 32 On
0xF00 Rem Ip 1 Off
0xF01 Rem Ip 2 Off
0xF02 Rem Ip 3 Off
0xF03 Rem Ip 4 Off
0xF04 Rem Ip 5 Off
0xF05 Rem Ip 6 Off
0xF06 Rem Ip 7 Off
0xF07 Rem Ip 8 Off
0xF08 Rem Ip 9 Off
0xF09 Rem Ip 10 Off
0xF0A Rem Ip 11 Off
0xF0B Rem Ip 12 Off
0xF0C Rem Ip 13 Off
0xF0D Rem Ip 14 Off
0xF0E Rem Ip 15 Off
0xF0F Rem Ip 16 Off
0xF10 Rem Ip 17 Off
0xF11 Rem Ip 18 Off
0xF12 Rem Ip 19 Off

11-156 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0xF13 Rem Ip 20 Off
0xF14 Rem Ip 21 Off
0xF15 Rem Ip 22 Off
0xF16 Rem Ip 23 Off
0xF17 Rem Ip 24 Off
0xF18 Rem Ip 25 Off
0xF19 Rem Ip 26 Off
0xF1A Rem Ip 27 Off
0xF1B Rem Ip 28 Off
0xF1C Rem Ip 29 Off
0xF1D Rem Ip 30 Off
0xF1E Rem Ip 31 Off
0xF1F Rem Ip 32 Off
0x800002 Any Trip
0x800202 Any Alarm
0x800802 Any Block
0x800A02 Any PKP
0x800C02 Any OP
0x800E02 Reset OP
0x800E08 Reset OP (PB)
0x800E10 Reset OP (Operand)
0x800E20 Reset OP (Comms)
0x801002 Setpoint Access OP
0x801202 Active Target
0x801402 In-Service
0x801602 Testing ON
0x801802 Any Major Error
0x801A02 Any Minor Error
0x801C02 Von
0x801C04 Voff
0x801E02 Von
0x801E04 Voff
0x802802 Critical Fail OP
0x802C01 Phase TOC 1 PKP
0x802C02 Phase TOC 1 OP
0x802C08 Phase TOC 1 PKP A
0x802C10 Phase TOC 1 PKP B
0x802C20 Phase TOC 1 PKP C
0x802C40 Phase TOC 1 OP A
0x802C80 Phase TOC 1 OP B
0x802D00 Phase TOC 1 OP C
0x802E01 Phase TOC 2 PKP
0x802E02 Phase TOC 2 OP
0x802E08 Phase TOC 2 PKP A
0x802E10 Phase TOC 2 PKP B
0x802E20 Phase TOC 2 PKP C
0x802E40 Phase TOC 2 OP A

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-157


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x802E80 Phase TOC 2 OP B
0x802F00 Phase TOC 2 OP C
0x803201 Phase IOC 1 PKP
0x803202 Phase IOC 1 OP
0x803208 Phase IOC 1 PKP A
0x803210 Phase IOC 1 PKP B
0x803220 Phase IOC 1 PKP C
0x803240 Phase IOC 1 OP A
0x803280 Phase IOC 1 OP B
0x803300 Phase IOC 1 OP C
0x803401 Phase IOC 2 PKP
0x803402 Phase IOC 2 OP
0x803408 Phase IOC 2 PKP A
0x803410 Phase IOC 2 PKP B
0x803420 Phase IOC 2 PKP C
0x803440 Phase IOC 2 OP A
0x803480 Phase IOC 2 OP B
0x803500 Phase IOC 2 OP C
0x803802 Ph Dir OC REV
0x803840 Ph Dir OC REV A
0x803880 Ph Dir OC REV B
0x803900 Ph Dir OC REV C
0x803A01 Neutral TOC 1 PKP
0x803A02 Neutral TOC 1 OP
0x803C01 Neutral TOC 2 PKP
0x803C02 Neutral TOC 2 OP
0x803E01 Neutral IOC 1 PKP
0x803E02 Neutral IOC 1 OP
0x804001 Neutral IOC 2 PKP
0x804002 Neutral IOC 2 OP
0x804208 Ntrl Dir OC FWD
0x804240 Ntrl Dir OC REV
0x804401 Ground TOC 1 PKP
0x804402 Ground TOC 1 OP
0x804C01 Ground IOC 1 PKP
0x804C02 Ground IOC 1 OP
0x805408 Gnd Dir OC FWD
0x805440 Gnd Dir OC REV
0x805601 SGnd TOC 1 PKP
0x805602 SGnd TOC 1 OP
0x805A01 SGnd IOC 1 PKP
0x805A02 Sen Gnd IOC 1 OP
0x805E08 SGnd Dir OC FWD
0x805E40 SGnd Dir OC REV
0x806001 RGF 1 PKP
0x806002 RGF 1 OP
0x806008 RGF 1 Superv ON

11-158 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x806601 NegSeq TOC 1 PKP
0x806602 NegSeq TOC 1 OP
0x806A01 NegSeq IOC 1 PKP
0x806A02 NegSeq IOC 1 OP
0x806E08 NegSeq DirOC FWD
0x806E40 NegSeq DirOC REV
0x807001 Broken Cond PKP
0x807002 Broken Cond OP
0x807201 Load Encro PKP
0x807202 Load Encro OP
0x807401 Thermal PKP
0x807402 Thermal OP
0x807408 Thermal PKP A
0x807410 Thermal PKP B
0x807420 Thermal PKP C
0x807440 Thermal OP A
0x807480 Thermal OP B
0x807500 Thermal OP C
0x807602 Thermal Alarm
0x807640 Thermal Alarm A
0x807680 Thermal Alarm B
0x807700 Thermal Alarm C
0x807801 Phase UV 1 PKP
0x807802 Phase UV 1 OP
0x807808 Phase UV 1 PKP A
0x807810 Phase UV 1 PKP B
0x807820 Phase UV 1 PKP C
0x807840 Phase UV 1 OP A
0x807880 Phase UV 1 OP B
0x807900 Phase UV 1 OP C
0x807A01 Phase UV 2 PKP
0x807A02 Phase UV 2 OP
0x807A08 Phase UV 2 PKP A
0x807A10 Phase UV 2 PKP B
0x807A20 Phase UV 2 PKP C
0x807A40 Phase UV 2 OP A
0x807A80 Phase UV 2 OP B
0x807B00 Phase UV 2 OP C
0x807C01 Phase OV 1 PKP
0x807C02 Phase OV 1 OP
0x807C08 Phase OV 1 PKP A
0x807C10 Phase OV 1 PKP B
0x807C20 Phase OV 1 PKP C
0x807C40 Phase OV 1 OP A
0x807C80 Phase OV 1 OP B
0x807D00 Phase OV 1 OP C
0x807E01 Phase OV 2 PKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-159


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x807E02 Phase OV 2 OP
0x807E08 Phase OV 2 PKP A
0x807E10 Phase OV 2 PKP B
0x807E20 Phase OV 2 PKP C
0x807E40 Phase OV 2 OP A
0x807E80 Phase OV 2 OP B
0x807F00 Phase OV 2 OP C
0x808001 Aux UV 1 PKP
0x808002 Aux UV 1 OP
0x808201 Aux UV 2 PKP
0x808202 Aux UV 2 OP
0x808401 Aux OV PKP
0x808402 Aux OV OP
0x808601 Neutral OV 1 PKP
0x808602 Neutral OV 1 OP
0x808A01 Neg Seq OV 1 PKP
0x808A02 Neg Seq OV 1 OP
0x808E01 DirPwr 1 PKP
0x808E02 DirPwr 1 OP
0x808E08 DirPwr 1 Stg1 PKP
0x808E10 DirPwr 1 Stg2 PKP
0x808E40 DirPwr 1 Stg1 OP
0x808E80 DirPwr 1 Stg2 OP
0x809001 Dir Pwr 2 PKP
0x809002 Dir Pwr 2 OP
0x809008 DirPwr 2 Stg1 PKP
0x809010 DirPwr 2 Stg2 PKP
0x809040 DirPwr 2 Stg1 OP
0x809080 DirPwr 2 Stg2 OP
0x809201 Watt GndFlt 1 PKP
0x809202 Watt GndFlt 1 OP
0x809601 Underfreq 1 PKP
0x809602 Underfreq 1 OP
0x809801 Underfreq 2 PKP
0x809802 Underfreq 2 OP
0x809A01 Underfreq 3 PKP
0x809A02 Underfreq 3 OP
0x809C01 Underfreq 4 PKP
0x809C02 Underfreq 4 OP
0x809E01 Overfreq 1 PKP
0x809E02 Overfreq 1 OP
0x80A001 Overfreq 2 PKP
0x80A002 Overfreq 2 OP
0x80A201 FreqRate1 PKP
0x80A202 FreqRate1 OP
0x80A208 FreqRate1 Up PKP
0x80A210 FreqRate1 Dwn PKP

11-160 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x80A240 FreqRate1 Up OP
0x80A280 FreqRate1 Dwn OP
0x80AA02 Group 1 Active
0x80AC02 Group 2 Active
0x80AE02 Group 3 Active
0x80B002 Group 4 Active
0x80B202 Group 5 Active
0x80B402 Group 6 Active
0x80B608 Local Mode ON
0x80B610 Local Mode OFF
0x80B808 BKR1 Local Open
0x80B810 BKR1 Remote Open
0x80BE08 BKR1 Local Close
0x80BE10 BKR1 Remote Close
0x80C401 Trip Bus 1 PKP
0x80C402 Trip Bus 1 OP
0x80C601 Trip Bus 2 PKP
0x80C602 Trip Bus 2 OP
0x80C801 Trip Bus 3 PKP
0x80C802 Trip Bus 3 OP
0x80CA01 Trip Bus 4 PKP
0x80CA02 Trip Bus 4 OP
0x80CC01 Trip Bus 5 PKP
0x80CC02 Trip Bus 5 OP
0x80CE01 Trip Bus 6 PKP
0x80CE02 Trip Bus 6 OP
0x80D002 BF1 OP
0x80D008 BF1 Retrip
0x80D010 BF1 Highset OP
0x80D020 BF1 Lowset OP
0x80D040 BF1 52b Superv OP
0x80D602 Sync1 Close Perm
0x80D608 Sync1 Live Bus
0x80D610 Sync1 Live Line
0x80D620 Sync1 Dead Src OK
0x80D640 Sync1 Dead Bus
0x80D680 Sync1 Dead Line
0x80D700 Sync1 OK
0x80DA02 Manual Cls Blk OP
0x80DC02 VT Fuse Fail1 OP
0x80DC08 VT Fuse1 V Loss
0x80E001 Cold Load 1 PKP
0x80E002 Cold Load 1 OP
0x80E401 Ph UV Restore PKP
0x80E408 Aux UV Restore PKP
0x80E440 Aux UV Restore OP
0x80E480 Ph UV Restore OP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-161


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x80E500 UV Restore Init
0x80E601 INC1 BKR Con&Clsd
0x80E602 INC1 Close Tie-BKR
0x80E604 INC1 Trnsfr Ready
0x80E608 INC2 BKR Con&Clsd
0x80E610 INC2 Close Tie-BKR
0x80E620 INC2 Trnsfr Ready
0x80E640 Tie-BKR Trfer Rdy
0x80E680 Tie-BKR Conn&Clsd
0x80E700 Transfer Not Ready
0x80E801 AR1 Disabled
0x80E808 AR1 Enabled
0x80E810 AR1 Initiated
0x80E820 AR1 In Progress
0x80E840 AR1 Close
0x80E880 AR1 Lockout
0x80E900 AR1 Man Cls Blk
0x80EA08 AR1 Shot Cnt 0
0x80EA10 AR1 Shot Cnt 1
0x80EA20 AR1 Shot Cnt 2
0x80EA40 AR1 Shot Cnt 3
0x80EA80 AR1 Shot Cnt 4
0x80EC08 AR1 ShotRdc to 1
0x80EC10 AR1 ShotRdc to 2
0x80EC20 AR1 ShotRdc to 3
0x80EC40 AR1 ShotRdc to LO
0x80EE08 AR1 Rate High
0x80EE10 AR1 Rate HI Lockt
0x80EE20 AR1 Coordinating
0x80F801 UF Restore PKP
0x80F802 UF Restore OP
0x80F840 UF Restore Init
0x80FA02 BKR1 Closed
0x80FC02 BKR1 Opened
0x80FE02 BKR1 Unkwn State
0x810002 BKR1 Disconnected
0x810004 BKR1 Connected
0x811E01 TripCoil Mon 1 PKP
0x811E02 TripCoil Mon 1 OP
0x812401 Cls Coil Mon 1 PKP
0x812402 Cls Coil Mon 1 OP
0x812A02 BKR1 Arc OP
0x813001 BKR1 Charge Fail
0x813002 BKR1 Hlth PKP
0x813008 BKR1 Hlth Trip PKP
0x813010 BKR1 Hlth Cls PKP
0x813020 BKR1 Hlth Chg PKP

11-162 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x813040 BKR1 Hlth OP Fail
0x813601 BKR1 Arc Fail
0x813608 BKR1 Arc PKP A
0x813610 BKR1 Arc PKP B
0x813620 BKR1 Arc PKP C
0x813640 BKR1 Engy PKP A
0x813680 BKR1 Engy PKP B
0x813700 BKR1 Engy PKP C
0x813C08 PF 1 Switch-In
0x813C10 PF 1 Switch-Out
0x813C40 PF 1 Switch-In OP
0x813C80 PF 1 Switch-Out OP
0x813E08 PF 2 Switch-In
0x813E10 PF 2 Switch-Out
0x813E40 PF 2 Switch-In OP
0x813E80 PF 2 Switch-Out OP

Code Type Definition


FC135 unsigned 32 bits Device Status
0x00040000 Self-Test Fault
0x00080000 Maintenance
0x00100000 In Service
0x00200000 SP Group 6 Active
0x00400000 SP Group 5 Active
0x00800000 SP Group 4 Active
0x01000000 SP Group 3 Active
0x02000000 SP Group 2 Active
0x04000000 Pickup State
0x08000000 Breaker Connected
0x10000000 Breaker Closed
0x20000000 Breaker Tripped
0x40000000 Alarm
0x80000000 Trip
FC142 unsigned 32 bits FlexLogic Bit Field (EEETTTTTTTSSSSSS)
0x200 CI 1 On
0x201 CI 2 On
0x202 CI 3 On
0x203 CI 4 On
0x204 CI 5 On
0x205 CI 6 On
0x206 CI 7 On
0x207 CI 8 On
0x208 CI 9 On
0x209 CI 10 On
0x20A CI 11 On
0x20B CI 12 On

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-163


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x20C CI 13 On
0x20D CI 14 On
0x20E CI 15 On
0x20F CI 16 On
0x210 CI 17 On
0x211 CI 18 On
0x212 CI 19 On
0x213 CI 20 On
0x214 CI 21 On
0x215 CI 22 On
0x216 CI 23 On
0x217 CI 24 On
0x218 CI 25 On
0x219 CI 26 On
0x21A CI 27 On
0x21B CI 28 On
0x21C CI 29 On
0x21D CI 30 On
0x21E CI 31 On
0x21F CI 32 On
0x220 CI 33 On
0x221 CI 34 On
0x222 CI 35 On
0x223 CI 36 On
0x224 CI 37 On
0x225 CI 38 On
0x226 CI 39 On
0x227 CI 40 On
0x228 CI 41 On
0x229 CI 42 On
0x22A CI 43 On
0x22B CI 44 On
0x22C CI 45 On
0x22D CI 46 On
0x22E CI 47 On
0x22F CI 48 On
0x230 CI 49 On
0x231 CI 50 On
0x232 CI 51 On
0x233 CI 52 On
0x234 CI 53 On
0x235 CI 54 On
0x236 CI 55 On
0x237 CI 56 On
0x238 CI 57 On
0x239 CI 58 On
0x23A CI 59 On

11-164 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x23B CI 60 On
0x23C CI 61 On
0x23D CI 62 On
0x23E CI 63 On
0x23F CI 64 On
0x240 CI 65 On
0x241 CI 66 On
0x242 CI 67 On
0x243 CI 68 On
0x244 CI 69 On
0x245 CI 70 On
0x246 CI 71 On
0x247 CI 72 On
0x248 CI 73 On
0x249 CI 74 On
0x24A CI 75 On
0x24B CI 76 On
0x24C CI 77 On
0x24D CI 78 On
0x24E CI 79 On
0x24F CI 80 On
0x250 CI 81 On
0x251 CI 82 On
0x252 CI 83 On
0x253 CI 84 On
0x254 CI 85 On
0x255 CI 86 On
0x256 CI 87 On
0x257 CI 88 On
0x258 CI 89 On
0x259 CI 90 On
0x25A CI 91 On
0x25B CI 92 On
0x25C CI 93 On
0x25D CI 94 On
0x25E CI 95 On
0x25F CI 96 On
0x300 CI 1 Off
0x301 CI 2 Off
0x302 CI 3 Off
0x303 CI 4 Off
0x304 CI 5 Off
0x305 CI 6 Off
0x306 CI 7 Off
0x307 CI 8 Off
0x308 CI 9 Off
0x309 CI 10 Off

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-165


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x30A CI 11 Off
0x30B CI 12 Off
0x30C CI 13 Off
0x30D CI 14 Off
0x30E CI 15 Off
0x30F CI 16 Off
0x310 CI 17 Off
0x311 CI 18 Off
0x312 CI 19 Off
0x313 CI 20 Off
0x314 CI 21 Off
0x315 CI 22 Off
0x316 CI 23 Off
0x317 CI 24 Off
0x318 CI 25 Off
0x319 CI 26 Off
0x31A CI 27 Off
0x31B CI 28 Off
0x31C CI 29 Off
0x31D CI 30 Off
0x31E CI 31 Off
0x31F CI 32 Off
0x320 CI 33 Off
0x321 CI 34 Off
0x322 CI 35 Off
0x323 CI 36 Off
0x324 CI 37 Off
0x325 CI 38 Off
0x326 CI 39 Off
0x327 CI 40 Off
0x328 CI 41 Off
0x329 CI 42 Off
0x32A CI 43 Off
0x32B CI 44 Off
0x32C CI 45 Off
0x32D CI 46 Off
0x32E CI 47 Off
0x32F CI 48 Off
0x330 CI 49 Off
0x331 CI 50 Off
0x332 CI 51 Off
0x333 CI 52 Off
0x334 CI 53 Off
0x335 CI 54 Off
0x336 CI 55 Off
0x337 CI 56 Off
0x338 CI 57 Off

11-166 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x339 CI 58 Off
0x33A CI 59 Off
0x33B CI 60 Off
0x33C CI 61 Off
0x33D CI 62 Off
0x33E CI 63 Off
0x33F CI 64 Off
0x340 CI 65 Off
0x341 CI 66 Off
0x342 CI 67 Off
0x343 CI 68 Off
0x344 CI 69 Off
0x345 CI 70 Off
0x346 CI 71 Off
0x347 CI 72 Off
0x348 CI 73 Off
0x349 CI 74 Off
0x34A CI 75 Off
0x34B CI 76 Off
0x34C CI 77 Off
0x34D CI 78 Off
0x34E CI 79 Off
0x34F CI 80 Off
0x350 CI 81 Off
0x351 CI 82 Off
0x352 CI 83 Off
0x353 CI 84 Off
0x354 CI 85 Off
0x355 CI 86 Off
0x356 CI 87 Off
0x357 CI 88 Off
0x358 CI 89 Off
0x359 CI 90 Off
0x35A CI 91 Off
0x35B CI 92 Off
0x35C CI 93 Off
0x35D CI 94 Off
0x35E CI 95 Off
0x35F CI 96 Off
0x400 VI 1 On
0x401 VI 2 On
0x402 VI 3 On
0x403 VI 4 On
0x404 VI 5 On
0x405 VI 6 On
0x406 VI 7 On
0x407 VI 8 On

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-167


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x408 VI 9 On
0x409 VI 10 On
0x40A VI 11 On
0x40B VI 12 On
0x40C VI 13 On
0x40D VI 14 On
0x40E VI 15 On
0x40F VI 16 On
0x410 VI 17 On
0x411 VI 18 On
0x412 VI 19 On
0x413 VI 20 On
0x414 VI 21 On
0x415 VI 22 On
0x416 VI 23 On
0x417 VI 24 On
0x418 VI 25 On
0x419 VI 26 On
0x41A VI 27 On
0x41B VI 28 On
0x41C VI 29 On
0x41D VI 30 On
0x41E VI 31 On
0x41F VI 32 On
0x500 VI 1 Off
0x501 VI 2 Off
0x502 VI 3 Off
0x503 VI 4 Off
0x504 VI 5 Off
0x505 VI 6 Off
0x506 VI 7 Off
0x507 VI 8 Off
0x508 VI 9 Off
0x509 VI 10 Off
0x50A VI 11 Off
0x50B VI 12 Off
0x50C VI 13 Off
0x50D VI 14 Off
0x50E VI 15 Off
0x50F VI 16 Off
0x510 VI 17 Off
0x511 VI 18 Off
0x512 VI 19 Off
0x513 VI 20 Off
0x514 VI 21 Off
0x515 VI 22 Off
0x516 VI 23 Off

11-168 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x517 VI 24 Off
0x518 VI 25 Off
0x519 VI 26 Off
0x51A VI 27 Off
0x51B VI 28 Off
0x51C VI 29 Off
0x51D VI 30 Off
0x51E VI 31 Off
0x51F VI 32 Off
0x600 VO 1 On
0x601 VO 2 On
0x602 VO 3 On
0x603 VO 4 On
0x604 VO 5 On
0x605 VO 6 On
0x606 VO 7 On
0x607 VO 8 On
0x608 VO 9 On
0x609 VO 10 On
0x60A VO 11 On
0x60B VO 12 On
0x60C VO 13 On
0x60D VO 14 On
0x60E VO 15 On
0x60F VO 16 On
0x610 VO 17 On
0x611 VO 18 On
0x612 VO 19 On
0x613 VO 20 On
0x614 VO 21 On
0x615 VO 22 On
0x616 VO 23 On
0x617 VO 24 On
0x618 VO 25 On
0x619 VO 26 On
0x61A VO 27 On
0x61B VO 28 On
0x61C VO 29 On
0x61D VO 30 On
0x61E VO 31 On
0x61F VO 32 On
0x700 VO 1 Off
0x701 VO 2 Off
0x702 VO 3 Off
0x703 VO 4 Off
0x704 VO 5 Off
0x705 VO 6 Off

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-169


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x706 VO 7 Off
0x707 VO 8 Off
0x708 VO 9 Off
0x709 VO 10 Off
0x70A VO 11 Off
0x70B VO 12 Off
0x70C VO 13 Off
0x70D VO 14 Off
0x70E VO 15 Off
0x70F VO 16 Off
0x710 VO 17 Off
0x711 VO 18 Off
0x712 VO 19 Off
0x713 VO 20 Off
0x714 VO 21 Off
0x715 VO 22 Off
0x716 VO 23 Off
0x717 VO 24 Off
0x718 VO 25 Off
0x719 VO 26 Off
0x71A VO 27 Off
0x71B VO 28 Off
0x71C VO 29 Off
0x71D VO 30 Off
0x71E VO 31 Off
0x71F VO 32 Off
0x800 Rly 1 On
0x801 Rly 2 On
0x802 Rly 3 On
0x803 Rly 4 On
0x804 Rly 5 On
0x805 Rly 6 On
0x806 Rly 7 On
0x807 Rly 8 On
0x808 Rly 9 On
0x809 Rly 10 On
0x80A Rly 11 On
0x80B Rly 12 On
0x80C Rly 13 On
0x80D Rly 14 On
0x80E Rly 15 On
0x80F Rly 16 On
0x810 Rly 17 On
0x811 Rly 18 On
0x812 Rly 19 On
0x813 Rly 20 On
0x814 Rly 21 On

11-170 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x815 Rly 22 On
0x816 Rly 23 On
0x817 Rly 24 On
0x818 Rly 25 On
0x819 Rly 26 On
0x81A Rly 27 On
0x81B Rly 28 On
0x81C Rly 29 On
0x81D Rly 30 On
0x81E Rly 31 On
0x81F Rly 32 On
0x900 Rly 1 Off
0x901 Rly 2 Off
0x902 Rly 3 Off
0x903 Rly 4 Off
0x904 Rly 5 Off
0x905 Rly 6 Off
0x906 Rly 7 Off
0x907 Rly 8 Off
0x908 Rly 9 Off
0x909 Rly 10 Off
0x90A Rly 11 Off
0x90B Rly 12 Off
0x90C Rly 13 Off
0x90D Rly 14 Off
0x90E Rly 15 Off
0x90F Rly 16 Off
0x910 Rly 17 Off
0x911 Rly 18 Off
0x912 Rly 19 Off
0x913 Rly 20 Off
0x914 Rly 21 Off
0x915 Rly 22 Off
0x916 Rly 23 Off
0x917 Rly 24 Off
0x918 Rly 25 Off
0x919 Rly 26 Off
0x91A Rly 27 Off
0x91B Rly 28 Off
0x91C Rly 29 Off
0x91D Rly 30 Off
0x91E Rly 31 Off
0x91F Rly 32 Off
0xE00 Rem Ip 1 On
0xE01 Rem Ip 2 On
0xE02 Rem Ip 3 On
0xE03 Rem Ip 4 On

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-171


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0xE04 Rem Ip 5 On
0xE05 Rem Ip 6 On
0xE06 Rem Ip 7 On
0xE07 Rem Ip 8 On
0xE08 Rem Ip 9 On
0xE09 Rem Ip 10 On
0xE0A Rem Ip 11 On
0xE0B Rem Ip 12 On
0xE0C Rem Ip 13 On
0xE0D Rem Ip 14 On
0xE0E Rem Ip 15 On
0xE0F Rem Ip 16 On
0xE10 Rem Ip 17 On
0xE11 Rem Ip 18 On
0xE12 Rem Ip 19 On
0xE13 Rem Ip 20 On
0xE14 Rem Ip 21 On
0xE15 Rem Ip 22 On
0xE16 Rem Ip 23 On
0xE17 Rem Ip 24 On
0xE18 Rem Ip 25 On
0xE19 Rem Ip 26 On
0xE1A Rem Ip 27 On
0xE1B Rem Ip 28 On
0xE1C Rem Ip 29 On
0xE1D Rem Ip 30 On
0xE1E Rem Ip 31 On
0xE1F Rem Ip 32 On
0xF00 Rem Ip 1 Off
0xF01 Rem Ip 2 Off
0xF02 Rem Ip 3 Off
0xF03 Rem Ip 4 Off
0xF04 Rem Ip 5 Off
0xF05 Rem Ip 6 Off
0xF06 Rem Ip 7 Off
0xF07 Rem Ip 8 Off
0xF08 Rem Ip 9 Off
0xF09 Rem Ip 10 Off
0xF0A Rem Ip 11 Off
0xF0B Rem Ip 12 Off
0xF0C Rem Ip 13 Off
0xF0D Rem Ip 14 Off
0xF0E Rem Ip 15 Off
0xF0F Rem Ip 16 Off
0xF10 Rem Ip 17 Off
0xF11 Rem Ip 18 Off
0xF12 Rem Ip 19 Off

11-172 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0xF13 Rem Ip 20 Off
0xF14 Rem Ip 21 Off
0xF15 Rem Ip 22 Off
0xF16 Rem Ip 23 Off
0xF17 Rem Ip 24 Off
0xF18 Rem Ip 25 Off
0xF19 Rem Ip 26 Off
0xF1A Rem Ip 27 Off
0xF1B Rem Ip 28 Off
0xF1C Rem Ip 29 Off
0xF1D Rem Ip 30 Off
0xF1E Rem Ip 31 Off
0xF1F Rem Ip 32 Off
0x2000 End of List
0x2200 NOT
0x2400 XOR
0x2600 LATCH
0x2802 OR (2 Inputs)
0x2803 OR ( 3 Inputs)
0x2804 OR ( 4 Inputs)
0x2805 OR ( 5 Inputs)
0x2806 OR ( 6 Inputs)
0x2807 OR ( 7 Inputs)
0x2808 OR ( 8 Inputs)
0x2809 OR ( 9 Inputs)
0x280A OR ( 10 Inputs)
0x280B OR ( 11 Inputs)
0x280C OR ( 12 Inputs)
0x280D OR ( 13 Inputs)
0x280E OR ( 14 Inputs)
0x280F OR ( 15 Inputs)
0x2810 OR ( 16 Inputs)
0x2A02 AND ( 2 Inputs)
0x2A03 AND ( 3 Inputs)
0x2A04 AND ( 4 Inputs)
0x2A05 AND ( 5 Inputs)
0x2A06 AND ( 6 Inputs)
0x2A07 AND ( 7 Inputs)
0x2A08 AND ( 8 Inputs)
0x2A09 AND ( 9 Inputs)
0x2A0A AND ( 10 Inputs)
0x2A0B AND ( 11 Inputs)
0x2A0C AND ( 12 Inputs)
0x2A0D AND ( 13 Inputs)
0x2A0E AND ( 14 Inputs)
0x2A0F AND ( 15 Inputs)
0x2A10 AND ( 16 Inputs)

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-173


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x2C02 NOR ( 2 Inputs)
0x2C03 NOR ( 3 Inputs)
0x2C04 NOR ( 4 Inputs)
0x2C05 NOR ( 5 Inputs)
0x2C06 NOR ( 6 Inputs)
0x2C07 NOR ( 7 Inputs)
0x2C08 NOR ( 8 Inputs)
0x2C09 NOR ( 9 Inputs)
0x2C0A NOR ( 10 Inputs)
0x2C0B NOR ( 11 Inputs)
0x2C0C NOR ( 12 Inputs)
0x2C0D NOR ( 13 Inputs)
0x2C0E NOR ( 14 Inputs)
0x2C0F NOR ( 15 Inputs)
0x2C10 NOR ( 16 Inputs)
0x2E02 NAND ( 2 Inputs)
0x2E03 NAND ( 3 Inputs)
0x2E04 NAND ( 4 Inputs)
0x2E05 NAND ( 5 Inputs)
0x2E06 NAND ( 6 Inputs)
0x2E07 NAND ( 7 Inputs)
0x2E08 NAND ( 8 Inputs)
0x2E09 NAND ( 9 Inputs)
0x2E0A NAND ( 10 Inputs)
0x2E0B NAND ( 11 Inputs)
0x2E0C NAND ( 12 Inputs)
0x2E0D NAND ( 13 Inputs)
0x2E0E NAND ( 14 Inputs)
0x2E0F NAND ( 15 Inputs)
0x2E10 NAND ( 16 Inputs)
0x3000 TIMER 1
0x3001 TIMER 2
0x3002 TIMER 3
0x3003 TIMER 4
0x3004 TIMER 5
0x3005 TIMER 6
0x3006 TIMER 7
0x3007 TIMER 8
0x3008 TIMER 9
0x3009 TIMER 10
0x300A TIMER 11
0x300B TIMER 12
0x300C TIMER 13
0x300D TIMER 14
0x300E TIMER 15
0x300F TIMER 16
0x3010 TIMER 17

11-174 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x3011 TIMER 18
0x3012 TIMER 19
0x3013 TIMER 20
0x3014 TIMER 21
0x3015 TIMER 22
0x3016 TIMER 23
0x3017 TIMER 24
0x3018 TIMER 25
0x3019 TIMER 26
0x301A TIMER 27
0x301B TIMER 28
0x301C TIMER 29
0x301D TIMER 30
0x301E TIMER 31
0x301F TIMER 32
0x3200 Assign VO 1
0x3201 Assign VO 2
0x3202 Assign VO 3
0x3203 Assign VO 4
0x3204 Assign VO 5
0x3205 Assign VO 6
0x3206 Assign VO 7
0x3207 Assign VO 8
0x3208 Assign VO 9
0x3209 Assign VO 10
0x320A Assign VO 11
0x320B Assign VO 12
0x320C Assign VO 13
0x320D Assign VO 14
0x320E Assign VO 15
0x320F Assign VO 16
0x3210 Assign VO 17
0x3211 Assign VO 18
0x3212 Assign VO 19
0x3213 Assign VO 20
0x3214 Assign VO 21
0x3215 Assign VO 22
0x3216 Assign VO 23
0x3217 Assign VO 24
0x3218 Assign VO 25
0x3219 Assign VO 26
0x321A Assign VO 27
0x321B Assign VO 28
0x321C Assign VO 29
0x321D Assign VO 30
0x321E Assign VO 31
0x321F Assign VO 32

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-175


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x3401 Positive One Shot
0x3402 Negative One Shot
0x3403 Dual One Shot
0x800002 Any Trip
0x800202 Any Alarm
0x800802 Any Block
0x800A02 Any PKP
0x800C02 Any OP
0x800E02 Reset OP
0x800E08 Reset OP (PB)
0x800E10 Reset OP (Operand)
0x800E20 Reset OP (Comms)
0x801002 Setpoint Access OP
0x801202 Active Target
0x801402 In-Service
0x801602 Testing ON
0x801604 Testing OFF
0x801802 Any Major Error
0x801A02 Any Minor Error
0x801C02 Von
0x801C04 Voff
0x801E02 Von
0x801E04 Voff
0x802802 Critical Fail OP
0x802C01 Phase TOC 1 PKP
0x802C02 Phase TOC 1 OP
0x802C08 Phase TOC 1 PKP A
0x802C10 Phase TOC 1 PKP B
0x802C20 Phase TOC 1 PKP C
0x802C40 Phase TOC 1 OP A
0x802C80 Phase TOC 1 OP B
0x802D00 Phase TOC 1 OP C
0x802E01 Phase TOC 2 PKP
0x802E02 Phase TOC 2 OP
0x802E08 Phase TOC 2 PKP A
0x802E10 Phase TOC 2 PKP B
0x802E20 Phase TOC 2 PKP C
0x802E40 Phase TOC 2 OP A
0x802E80 Phase TOC 2 OP B
0x802F00 Phase TOC 2 OP C
0x803201 Phase IOC 1 PKP
0x803202 Phase IOC 1 OP
0x803208 Phase IOC 1 PKP A
0x803210 Phase IOC 1 PKP B
0x803220 Phase IOC 1 PKP C
0x803240 Phase IOC 1 OP A
0x803280 Phase IOC 1 OP B

11-176 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x803300 Phase IOC 1 OP C
0x803401 Phase IOC 2 PKP
0x803402 Phase IOC 2 OP
0x803408 Phase IOC 2 PKP A
0x803410 Phase IOC 2 PKP B
0x803420 Phase IOC 2 PKP C
0x803440 Phase IOC 2 OP A
0x803480 Phase IOC 2 OP B
0x803500 Phase IOC 2 OP C
0x803802 Ph Dir OC REV
0x803840 Ph Dir OC REV A
0x803880 Ph Dir OC REV B
0x803900 Ph Dir OC REV C
0x803A01 Neutral TOC 1 PKP
0x803A02 Neutral TOC 1 OP
0x803C01 Neutral TOC 2 PKP
0x803C02 Neutral TOC 2 OP
0x803E01 Neutral IOC 1 PKP
0x803E02 Neutral IOC 1 OP
0x804001 Neutral IOC 2 PKP
0x804002 Neutral IOC 2 OP
0x804208 Ntrl Dir OC FWD
0x804240 Ntrl Dir OC REV
0x804401 Ground TOC 1 PKP
0x804402 Ground TOC 1 OP
0x804C01 Ground IOC 1 PKP
0x804C02 Ground IOC 1 OP
0x805408 Gnd Dir OC FWD
0x805440 Gnd Dir OC REV
0x805601 SGnd TOC 1 PKP
0x805602 SGnd TOC 1 OP
0x805A01 SGnd IOC 1 PKP
0x805A02 Sen Gnd IOC 1 OP
0x805E08 SGnd Dir OC FWD
0x805E40 SGnd Dir OC REV
0x806001 RGF 1 PKP
0x806002 RGF 1 OP
0x806008 RGF 1 Superv ON
0x806601 NegSeq TOC 1 PKP
0x806602 NegSeq TOC 1 OP
0x806A01 NegSeq IOC 1 PKP
0x806A02 NegSeq IOC 1 OP
0x806E08 NegSeq DirOC FWD
0x806E40 NegSeq DirOC REV
0x807001 Broken Cond PKP
0x807002 Broken Cond OP
0x807201 Load Encro PKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-177


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x807202 Load Encro OP
0x807401 Thermal PKP
0x807402 Thermal OP
0x807408 Thermal PKP A
0x807410 Thermal PKP B
0x807420 Thermal PKP C
0x807440 Thermal OP A
0x807480 Thermal OP B
0x807500 Thermal OP C
0x807602 Thermal Alarm
0x807640 Thermal Alarm A
0x807680 Thermal Alarm B
0x807700 Thermal Alarm C
0x807801 Phase UV 1 PKP
0x807802 Phase UV 1 OP
0x807808 Phase UV 1 PKP A
0x807810 Phase UV 1 PKP B
0x807820 Phase UV 1 PKP C
0x807840 Phase UV 1 OP A
0x807880 Phase UV 1 OP B
0x807900 Phase UV 1 OP C
0x807A01 Phase UV 2 PKP
0x807A02 Phase UV 2 OP
0x807A08 Phase UV 2 PKP A
0x807A10 Phase UV 2 PKP B
0x807A20 Phase UV 2 PKP C
0x807A40 Phase UV 2 OP A
0x807A80 Phase UV 2 OP B
0x807B00 Phase UV 2 OP C
0x807C01 Phase OV 1 PKP
0x807C02 Phase OV 1 OP
0x807C08 Phase OV 1 PKP A
0x807C10 Phase OV 1 PKP B
0x807C20 Phase OV 1 PKP C
0x807C40 Phase OV 1 OP A
0x807C80 Phase OV 1 OP B
0x807D00 Phase OV 1 OP C
0x807E01 Phase OV 2 PKP
0x807E02 Phase OV 2 OP
0x807E08 Phase OV 2 PKP A
0x807E10 Phase OV 2 PKP B
0x807E20 Phase OV 2 PKP C
0x807E40 Phase OV 2 OP A
0x807E80 Phase OV 2 OP B
0x807F00 Phase OV 2 OP C
0x808001 Aux UV 1 PKP
0x808002 Aux UV 1 OP

11-178 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x808201 Aux UV 2 PKP
0x808202 Aux UV 2 OP
0x808401 Aux OV PKP
0x808402 Aux OV OP
0x808601 Neutral OV 1 PKP
0x808602 Neutral OV 1 OP
0x808A01 Neg Seq OV 1 PKP
0x808A02 Neg Seq OV 1 OP
0x808E01 DirPwr 1 PKP
0x808E02 DirPwr 1 OP
0x808E08 DirPwr 1 Stg1 PKP
0x808E10 DirPwr 1 Stg2 PKP
0x808E40 DirPwr 1 Stg1 OP
0x808E80 DirPwr 1 Stg2 OP
0x809001 Dir Pwr 2 PKP
0x809002 Dir Pwr 2 OP
0x809008 DirPwr 2 Stg1 PKP
0x809010 DirPwr 2 Stg2 PKP
0x809040 DirPwr 2 Stg1 OP
0x809080 DirPwr 2 Stg2 OP
0x809201 Watt GndFlt 1 PKP
0x809202 Watt GndFlt 1 OP
0x809601 Underfreq 1 PKP
0x809602 Underfreq 1 OP
0x809801 Underfreq 2 PKP
0x809802 Underfreq 2 OP
0x809A01 Underfreq 3 PKP
0x809A02 Underfreq 3 OP
0x809C01 Underfreq 4 PKP
0x809C02 Underfreq 4 OP
0x809E01 Overfreq 1 PKP
0x809E02 Overfreq 1 OP
0x80A001 Overfreq 2 PKP
0x80A002 Overfreq 2 OP
0x80A201 FreqRate1 PKP
0x80A202 FreqRate1 OP
0x80A208 FreqRate1 Up PKP
0x80A210 FreqRate1 Dwn PKP
0x80A240 FreqRate1 Up OP
0x80A280 FreqRate1 Dwn OP
0x80AA02 Group 1 Active
0x80AC02 Group 2 Active
0x80AE02 Group 3 Active
0x80B002 Group 4 Active
0x80B202 Group 5 Active
0x80B402 Group 6 Active
0x80B608 Local Mode ON

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-179


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x80B610 Local Mode OFF
0x80B808 BKR1 Local Open
0x80B810 BKR1 Remote Open
0x80BE08 BKR1 Local Close
0x80BE10 BKR1 Remote Close
0x80C401 Trip Bus 1 PKP
0x80C402 Trip Bus 1 OP
0x80C601 Trip Bus 2 PKP
0x80C602 Trip Bus 2 OP
0x80C801 Trip Bus 3 PKP
0x80C802 Trip Bus 3 OP
0x80CA01 Trip Bus 4 PKP
0x80CA02 Trip Bus 4 OP
0x80CC01 Trip Bus 5 PKP
0x80CC02 Trip Bus 5 OP
0x80CE01 Trip Bus 6 PKP
0x80CE02 Trip Bus 6 OP
0x80D002 BF1 OP
0x80D008 BF1 Retrip
0x80D010 BF1 Highset OP
0x80D020 BF1 Lowset OP
0x80D040 BF1 52b Superv OP
0x80D602 Sync1 Close Perm
0x80D608 Sync1 Live Bus
0x80D610 Sync1 Live Line
0x80D620 Sync1 Dead Src OK
0x80D640 Sync1 Dead Bus
0x80D680 Sync1 Dead Line
0x80D700 Sync1 OK
0x80D802 Sync2 Close Perm
0x80D808 Sync2 Live Bus
0x80D810 Sync2 Live Line
0x80D820 Sync2 Dead Src OK
0x80D840 Sync2 Dead Bus
0x80D880 Sync2 Dead Line
0x80D900 Sync2 OK
0x80DA02 Manual Cls Blk OP
0x80DC02 VT Fuse Fail1 OP
0x80DC08 VT Fuse1 V Loss
0x80E001 Cold Load 1 PKP
0x80E002 Cold Load 1 OP
0x80E401 Ph UV Restore PKP
0x80E408 Aux UV Restore PKP
0x80E440 Aux UV Restore OP
0x80E480 Ph UV Restore OP
0x80E500 UV Restore Init
0x80E601 INC1 BKR Con&Clsd

11-180 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x80E602 INC1 Close Tie-BKR
0x80E604 INC1 Trnsfr Ready
0x80E608 INC2 BKR Con&Clsd
0x80E610 INC2 Close Tie-BKR
0x80E620 INC2 Trnsfr Ready
0x80E640 Tie-BKR Trfer Rdy
0x80E680 Tie-BKR Conn&Clsd
0x80E700 Transfer Not Ready
0x80E801 AR1 Disabled
0x80E808 AR1 Enabled
0x80E810 AR1 Initiated
0x80E820 AR1 In Progress
0x80E840 AR1 Close
0x80E880 AR1 Lockout
0x80E900 AR1 Man Cls Blk
0x80EA08 AR1 Shot Cnt 0
0x80EA10 AR1 Shot Cnt 1
0x80EA20 AR1 Shot Cnt 2
0x80EA40 AR1 Shot Cnt 3
0x80EA80 AR1 Shot Cnt 4
0x80EC08 AR1 ShotRdc to 1
0x80EC10 AR1 ShotRdc to 2
0x80EC20 AR1 ShotRdc to 3
0x80EC40 AR1 ShotRdc to LO
0x80EE08 AR1 Rate High
0x80EE10 AR1 Rate HI Lockt
0x80EE20 AR1 Coordinating
0x80F801 UF Restore PKP
0x80F802 UF Restore OP
0x80F840 UF Restore Init
0x80FA02 BKR1 Closed
0x80FC02 BKR1 Opened
0x80FE02 BKR1 Unkwn State
0x810002 BKR1 Disconnected
0x810004 BKR1 Connected
0x810202 BKR1 52a CI ON
0x810204 BKR1 52a CI OFF
0x810402 BKR1 52b CI ON
0x810404 BKR1 52b CI OFF
0x811E01 TripCoil Mon 1 PKP
0x811E02 TripCoil Mon 1 OP
0x812401 Cls Coil Mon 1 PKP
0x812402 Cls Coil Mon 1 OP
0x812A02 BKR1 Arc OP
0x813001 BKR1 Charge Fail
0x813002 BKR1 Hlth PKP
0x813008 BKR1 Hlth Trip PKP

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-181


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x813010 BKR1 Hlth Cls PKP
0x813020 BKR1 Hlth Chg PKP
0x813040 BKR1 Hlth OP Fail
0x813601 BKR1 Arc Fail
0x813608 BKR1 Arc PKP A
0x813610 BKR1 Arc PKP B
0x813620 BKR1 Arc PKP C
0x813640 BKR1 Engy PKP A
0x813680 BKR1 Engy PKP B
0x813700 BKR1 Engy PKP C
0x813C08 PF 1 Switch-In
0x813C10 PF 1 Switch-Out
0x813C40 PF 1 Switch-In OP
0x813C80 PF 1 Switch-Out OP
0x813E08 PF 2 Switch-In
0x813E10 PF 2 Switch-Out
0x813E40 PF 2 Switch-In OP
0x813E80 PF 2 Switch-Out OP
0x814001 Current Dmd PKP
0x814008 Current Dmd PKP A
0x814010 Current Dmd PKP B
0x814020 Current Dmd PKP C
0x814201 RealPwr Dmd PKP
0x814401 ReactvPwr Dmd PKP
0x814601 ApprntPwr Dmd PKP
0x819208 Pos Wthrs Pulse OP
0x819210 Neg Wthrs Pulse OP
0x819220 Pos Varh Pulse OP
0x819240 Neg Varh Pulse OP
0x819408 Counter 1 LO
0x819410 Counter 1 EQL
0x819420 Counter 1 HI
0x819440 Counter 1 at Limit
0x819608 Counter 2 LO
0x819610 Counter 2 EQL
0x819620 Counter 2 HI
0x819640 Counter 2 at Limit
0x819808 Counter 3 LO
0x819810 Counter 3 EQL
0x819820 Counter 3 HI
0x819840 Counter 3 at Limit
0x819A08 Counter 4 LO
0x819A10 Counter 4 EQL
0x819A20 Counter 4 HI
0x819A40 Counter 4 at Limit
0x819C08 Counter 5 LO
0x819C10 Counter 5 EQL

11-182 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x819C20 Counter 5 HI
0x819C40 Counter 5 at Limit
0x819E08 Counter 6 LO
0x819E10 Counter 6 EQL
0x819E20 Counter 6 HI
0x819E40 Counter 6 at Limit
0x81A008 Counter 7 LO
0x81A010 Counter 7 EQL
0x81A020 Counter 7 HI
0x81A040 Counter 7 at Limit
0x81A208 Counter 8 LO
0x81A210 Counter 8 EQL
0x81A220 Counter 8 HI
0x81A240 Counter 8 at Limit
0x81A408 Counter 9 LO
0x81A410 Counter 9 EQL
0x81A420 Counter 9 HI
0x81A440 Counter 9 at Limit
0x81A608 Counter 10 LO
0x81A610 Counter 10 EQL
0x81A620 Counter 10 HI
0x81A640 Countr 10 at Limit
0x81A808 Counter 11 LO
0x81A810 Counter 11 EQL
0x81A820 Counter 11 HI
0x81A840 Countr 11 at Limit
0x81AA08 Counter 12 LO
0x81AA10 Counter 12 EQL
0x81AA20 Counter 12 HI
0x81AA40 Countr 12 at Limit
0x81AC08 Counter 13 LO
0x81AC10 Counter 13 EQL
0x81AC20 Counter 13 HI
0x81AC40 Countr 13 at Limit
0x81AE08 Counter 14 LO
0x81AE10 Counter 14 EQL
0x81AE20 Counter 14 HI
0x81AE40 Countr 14 at Limit
0x81B008 Counter 15 LO
0x81B010 Counter 15 EQL
0x81B020 Counter 15 HI
0x81B040 Countr 15 at Limit
0x81B208 Counter 16 LO
0x81B210 Counter 16 EQL
0x81B220 Counter 16 HI
0x81B240 Countr 16 at Limit
0x81B402 NV Latch 1 ON

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-183


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x81B404 NV Latch 1 OFF
0x81B602 NV Latch 2 ON
0x81B604 NV Latch 2 OFF
0x81B802 NV Latch 3 ON
0x81B804 NV Latch 3 OFF
0x81BA02 NV Latch 4 ON
0x81BA04 NV Latch 4 OFF
0x81BC02 NV Latch 5 ON
0x81BC04 NV Latch 5 OFF
0x81BE02 NV Latch 6 ON
0x81BE04 NV Latch 6 OFF
0x81C002 NV Latch 7 ON
0x81C004 NV Latch 7 OFF
0x81C202 NV Latch 8 ON
0x81C204 NV Latch 8 OFF
0x81C402 NV Latch 9 ON
0x81C404 NV Latch 9 OFF
0x81C602 NV Latch 10 ON
0x81C604 NV Latch 10 OFF
0x81C802 NV Latch 11 ON
0x81C804 NV Latch 11 OFF
0x81CA02 NV Latch 12 ON
0x81CA04 NV Latch 12 OFF
0x81CC02 NV Latch 13 ON
0x81CC04 NV Latch 13 OFF
0x81CE02 NV Latch 14 ON
0x81CE04 NV Latch 14 OFF
0x81D002 NV Latch 15 ON
0x81D004 NV Latch 15 OFF
0x81D202 NV Latch 16 ON
0x81D204 NV Latch 16 OFF
0x81D402 PB 1 ON
0x81D404 PB 1 OFF
0x81D602 PB 2 ON
0x81D604 PB 2 OFF
0x81D802 PB 3 ON
0x81D804 PB 3 OFF
0x81DA01 Role Admin Act
0x81DA04 Authentication Lockout
0x81DA10 Authentication Fail
0x81DA20 Unauth Change Attempt
0x81DA40 Role Operator Act
0x81DA80 Role Observer Act
0x81DB00 Radius Srv Unavailable

11-184 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


FC150 unsigned 16 bits 850 Element List
All Elements Available in the 850
1 Any Trip
2 Any Alarm
5 Any Block
6 Any PKP
7 Any OP
8 Reset
9 Setpoint Access
10 Targets Active
11 In Serv.
12 Test Mode
13 Any Major Error
14 Any Minor Error
15 Output Relay 1
16 Output Relay 2
17 Output Relay 3
18 Output Relay 4
21 Critical Fail
22 Comms OK
23 Phase TOC 1
24 Phase TOC 2
26 Phase IOC 1
27 Phase IOC 2
29 Ph Dir OC
30 Ntrl TOC 1
31 Ntrl TOC 2
32 Ntrl IOC 1
33 Ntrl IOC 2
34 Ntrl Dir OC
35 Gnd TOC 1
39 Gnd IOC 1
43 Gnd Dir OC
44 SGnd TOC 1
46 SGnd IOC 1
48 SGnd Dir OC
49 RGF 1
52 Neg Seq TOC 1
54 Neg Seq IOC 1
56 Neg Seq Dir OC
57 BrokenConductor
58 LoadEncr
59 Thermal Model
60 Thermal Model Alrm
61 Ph UV 1
62 Ph UV 2

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-185


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


63 Ph OV 1
64 Ph OV 2
65 Aux UV 1
66 Aux UV 2
67 Aux OV
68 Neutral OV 1
69 Neutral OV 2
70 Neg Seq OV 1
71 Neg Seq OV 2
72 Dir Pwr 1
73 Dir Pwr 2
74 WattMetric 1
75 WattMetric 2
76 UF 1
77 UF 2
78 UF 3
79 UF 4
80 OF 1
81 OF 2
82 Freq RateOfChng1
86 Group 1
87 Group 2
88 Group 3
89 Group 4
90 Group 5
91 Group 6
92 Local Mode
93 Open BKR 1
96 Close BKR 1
99 Trip Bus 1
100 Trip Bus 2
101 Trip Bus 3
102 Trip Bus 4
103 Trip Bus 5
104 Trip Bus 6
105 BKR Fail 1
108 Sync Check 1
110 Manual Cls Blk
111 VTFF 1
113 CLP 1
115 UV Restore
116 Bus Transfer
117 AR1
118 AR1 Shot Cnt
119 AR1 Shot Cnt Reduction
120 AR1 Rate Supervision
125 UF Restore

11-186 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


126 BKR1 Status Closed
127 BKR1 Status Opened
128 BKR1 Status Unknown
129 BKR1 Status Disconnected
130 BKR1 52a Contact
131 BKR1 52b Contact
144 TripCoilMon 1
147 CloseCoilMon 1
150 Breaker 1 Arcing Current
153 Breaker1 Health
156 Breaker1 Arc Health
159 PF 1
160 PF 2
161 Current Dmd
162 RealPwrDmd
163 ReactivePwrDmd
164 ApparentPwrDmd
165 Fault Locator
202 Pulse Out
203 Digital Counter 1
204 Digital Counter 2
205 Digital Counter 3
206 Digital Counter 4
207 Digital Counter 5
208 Digital Counter 6
209 Digital Counter 7
210 Digital Counter 8
211 Digital Counter 9
212 Digital Counter 10
213 Digital Counter 11
214 Digital Counter 12
215 Digital Counter 13
216 Digital Counter 14
217 Digital Counter 15
218 Digital Counter 16
219 NV Latch 1
220 NV Latch 2
221 NV Latch 3
222 NV Latch 4
223 NV Latch 5
224 NV Latch 6
225 NV Latch 7
226 NV Latch 8
227 NV Latch 9
228 NV Latch 10
229 NV Latch 11
230 NV Latch 12

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-187


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


231 NV Latch 13
232 NV Latch 14
233 NV Latch 15
234 NV Latch 16
235 PB 1
236 PB 2
237 PB 3
238 Security Login
239 Data Logger
240 Transfer Initiated
FC151 unsigned 16 bits Element Status
This format shows the meaning of the Element Status values.
Refer to Format FC142 for exact information for each element.
There are cases where different meaning is given to
each bit. PKP meaning "Open", for example.
0x0000 None Active
0x0001 Element PKP
0x0002 Element OP
0x0008 Phase A Pickup
0x0010 Phase B Pickup
0x0020 Phase C Pickup
0x0040 Phase A Operate
0x0080 Phase B Operate
0x0100 Phase C Operate
0x0200 Element Is Latched
0x0400 Configurable Type
0x0800 Alarm Type
0x1000 Trip Type
0x2000 Flexlogic Element
FC157 unsigned 16 bits LED Colour
0 Off
1 Red
2 Green
3 Orange
FC161 unsigned 16 bits OC Curve Selection
0 IEEE Extr. Inverse
1 IEEE Very Inverse
2 IEEE Mod Inverse
3 ANSI Extr. Inverse
4 ANSI Very Inverse
5 ANSI Norm Inverse
6 ANSI Mod Inverse
7 Definite Time
8 IEC Curve A
9 IEC Curve B
10 IEC Curve C
11 IEC Short Inverse

11-188 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


12 IAC Extr. Inverse
13 IAC Very Inverse
14 IAC Inverse
15 IAC Short Inverse
16 Flex Curve A
17 Flex Curve B
18 Flex Curve C
19 Flex Curve D
20 I2t
21 I4t
FC161A unsigned 16 bits Neutral OV Curve Selection
7 Definite Time
16 Flex Curve A
17 Flex Curve B
18 Flex Curve C
19 Flex Curve D
FC161B unsigned 16 bits Wattmetric Ground Fault Curve
5 Inverse
7 Definite Time
16 Flex Curve A
17 Flex Curve B
18 Flex Curve C
19 Flex Curve D
FC165 unsigned 16 bits Simulation Status
0 Disabled
1 Prefault State
2 Fault State
3 Postfault State
4 Harmonics
FC169 unsigned 16 bits Month
0 Not Set
1 January
2 February
3 March
4 April
5 May
6 June
7 July
8 August
9 September
10 October
11 November
12 December
FC170 unsigned 16 bits Count of Week
0 Not Set
1 1st
2 2nd

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-189


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


3 3rd
4 4th
5 Last
FC171 unsigned 16 bits Weekdays
0 Not Set
1 SUN
2 MON
3 TUE
4 WED
5 THU
6 FRI
7 SAT
FC176 unsigned 16 bits Auxiliary VT Connection
0 Vab VT
1 Vbc VT
2 Vca VT
3 Van VT
4 Vbn VT
5 Vcn VT
6 Vn
FC181 unsigned 16 bits Transient Recorder Trigger Mode
0 Overwrite
1 Protected
FC182 unsigned 16 bits Transient Recorder Samples Per Cycle
0 128 /c
1 64 /c
2 32 /c
3 16 /c
4 8 /c
FC183 unsigned 16 bits Data Logger Sample Rate
0 1 Cycle
1 1 Second
2 30 Seconds
3 1 Minute
4 15 Minutes
5 30 Minutes
6 1 Hour
FC186 unsigned 16 bits DataLogger Collection Mode
0 Continuous
1 Triggered
FC191 unsigned 32 bits Remote Input Operation
0x00000001 Remote Input 1
0x00000002 Remote Input 2
0x00000004 Remote Input 3
0x00000008 Remote Input 4
0x00000010 Remote Input 5
0x00000020 Remote Input 6

11-190 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x00000040 Remote Input 7
0x00000080 Remote Input 8
0x00000100 Remote Input 9
0x00000200 Remote Input 10
0x00000400 Remote Input 11
0x00000800 Remote Input 12
0x00001000 Remote Input 13
0x00002000 Remote Input 14
0x00004000 Remote Input 15
0x00008000 Remote Input 16
0x00010000 Remote Input 17
0x00020000 Remote Input 18
0x00040000 Remote Input 19
0x00080000 Remote Input 20
0x00100000 Remote Input 21
0x00200000 Remote Input 22
0x00400000 Remote Input 23
0x00800000 Remote Input 24
0x01000000 Remote Input 25
0x02000000 Remote Input 26
0x04000000 Remote Input 27
0x08000000 Remote Input 28
0x10000000 Remote Input 29
0x20000000 Remote Input 30
0x40000000 Remote Input 31
0x80000000 Remote Input 32
FC192 unsigned 32 bits Remote Output Operation
0x00000001 Remote Output 1
0x00000002 Remote Output 2
0x00000004 Remote Output 3
0x00000008 Remote Output 4
0x00000010 Remote Output 5
0x00000020 Remote Output 6
0x00000040 Remote Output 7
0x00000080 Remote Output 8
0x00000100 Remote Output 9
0x00000200 Remote Output 10
0x00000400 Remote Output 11
0x00000800 Remote Output 12
0x00001000 Remote Output 13
0x00002000 Remote Output 14
0x00004000 Remote Output 15
0x00008000 Remote Output 16
0x00010000 Remote Output 17
0x00020000 Remote Output 18
0x00040000 Remote Output 19
0x00080000 Remote Output 20

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-191


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x00100000 Remote Output 21
0x00200000 Remote Output 22
0x00400000 Remote Output 23
0x00800000 Remote Output 24
0x01000000 Remote Output 25
0x02000000 Remote Output 26
0x04000000 Remote Output 27
0x08000000 Remote Output 28
0x10000000 Remote Output 29
0x20000000 Remote Output 30
0x40000000 Remote Output 31
0x80000000 Remote Output 32
FC194 unsigned 32 bits Contact Input Operation
0x00000001 Contact Input 1
0x00000002 Contact Input 2
0x00000004 Contact Input 3
0x00000008 Contact Input 4
0x00000010 Contact Input 5
0x00000020 Contact Input 6
0x00000040 Contact Input 7
0x00000080 Contact Input 8
0x00000100 Contact Input 9
0x00000200 Contact Input 10
0x00000400 Contact Input 11
0x00000800 Contact Input 12
0x00001000 Contact Input 13
0x00002000 Contact Input 14
0x00004000 Contact Input 15
0x00008000 Contact Input 16
0x00010000 Contact Input 17
0x00020000 Contact Input 18
0x00040000 Contact Input 19
0x00080000 Contact Input 20
0x00100000 Contact Input 21
0x00200000 Contact Input 22
0x00400000 Contact Input 23
0x00800000 Contact Input 24
0x01000000 Contact Input 25
0x02000000 Contact Input 26
0x04000000 Contact Input 27
0x08000000 Contact Input 28
0x10000000 Contact Input 29
0x20000000 Contact Input 30
0x40000000 Contact Input 31
0x80000000 Contact Input 32
FC198 unsigned 32 bits Output Relay Operation

11-192 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


Each bit corresponds to a
particular output relay, and
uses format FC126A
0x00000004 Output Relay 3
0x00000008 Output Relay 4
0x00000010 Output Relay 5
0x00000020 Output Relay 6
0x00000040 Output Relay 7
FC198A unsigned 32 bits Relay Operation
Each bit corresponds to a
particular output relay, and
uses format FC126A
0x00000004 Relay 3
0x00000008 Relay 4
0x00000010 Relay 5
0x00000020 Relay 6
0x00000040 Relay 7
FC199 unsigned 16 bits Output Relay Type
0 Self-Reset
1 Latched
FC208 unsigned 16 bits Relay Operation (Failsafe, Non-Failsafe)
0 Non-Failsafe
1 Failsafe
FC209 unsigned 16 bits Rear 485 Port Protocol
0 Modbus
1 IEC60870-5-103
2 DNP 3.0
FC210 unsigned 16 bits RS 485 Baud Rate
0 9600 baud
1 19200 baud
2 38400 baud
3 57600 baud
4 115200 baud
FC211 unsigned 16 bits RS 485 Parity
0 None
1 Odd
2 Even
FC212 unsigned 16 bits ASDU Ident Type
0 3
1 9
FC217 unsigned 16 bits Ethernet Duplicate
0 Discard
1 Accept
FC218 unsigned 16 bits Ethernet Mode
1 Full-Duplex
FC219 unsigned 16 bits Ethernet Port 4/5 Operation
0 Independent
1 LLA

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-193


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


2 PRP
FC220 unsigned 16 bits IRIG-B Signal Type
0 None
1 DC Shift
2 Amplitude Mod.
FC226 unsigned 16 bits WiFi Infrastructure Security
0 None
1 WPA2-PSK
FC228 unsigned 16 bits 61850 Status
0x0001 Comms NV OK
0x0002 Comms NV Done
0x0004 Comms V OK
0x0008 Comms V Done
0x0010 Main NV OK
0x0020 Main NV Done
0x0040 Main V OK
0x0080 Main V Done
0x0100 NR. Error CID
0x0200 R. Default CID
0x0400 R. Saving CID to Flash
0x0800 CID Handling Done
FC229 unsigned 16 bits DNP Analog Input Point Scale Factor
1 / 0.001
2 / 0.01
3 / 0.1
4 /1
5 / 10
6 / 100
7 / 1000
8 / 10000
9 / 100000
FC230 unsigned 16 bits DNP and 103 Binary Output Points
0 Off
1 Virtual Input 1
2 Virtual Input 2
3 Virtual Input 3
4 Virtual Input 4
5 Virtual Input 5
6 Virtual Input 6
7 Virtual Input 7
8 Virtual Input 8
9 Virtual Input 9
10 Virtual Input 10
11 Virtual Input 11
12 Virtual Input 12
13 Virtual Input 13
14 Virtual Input 14

11-194 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


15 Virtual Input 15
16 Virtual Input 16
17 Virtual Input 17
18 Virtual Input 18
19 Virtual Input 19
20 Virtual Input 20
21 Virtual Input 21
22 Virtual Input 22
23 Virtual Input 23
24 Virtual Input 24
25 Virtual Input 25
26 Virtual Input 26
27 Virtual Input 27
28 Virtual Input 28
29 Virtual Input 29
30 Virtual Input 30
31 Virtual Input 31
32 Virtual Input 32
33 FC: Reset
34 FC: Open BKR1
35 FC: Close BKR1
FC231 unsigned 16 bits DNP Object 1 Default Variation
1 1
2 2
FC232 unsigned 16 bits DNP Object 2 Default Variation
1 1
2 2
FC233 unsigned 16 bits DNP Object 20 Default Variation
1 1
2 2
5 5
6 6
FC234 unsigned 16 bits DNP Object 21 Default Variation
1 1
2 2
9 9
10 10
FC235 unsigned 16 bits DNP Object 22 Default Variation
1 1
2 2
5 5
6 6
FC236 unsigned 16 bits DNP Object 23 Default Variation
1 1
2 2
5 5
6 6

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-195


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


FC237 unsigned 16 bits DNP Object 30 Default Variation
1 1
2 2
3 3
4 4
5 5
FC238 unsigned 16 bits DNP Object 32 Default Variation
1 1
2 2
3 3
4 4
5 5
7 7
FC239 unsigned 16 bits DNP/Ethernet Channel Port
0 None
1 Network-TCP
2 Network-UDP
FC239A unsigned 16 bits IEC104 Channel Port
0 None
1 Network-TCP
FC240 unsigned 32 bits Self Test Error
0 No Error
0x00000001 Order Code Error
0x00000002 System Health Error
0x00000004 CPU Serial# Invalid
0x00000008 Slot F IO S/N Invalid
0x00000010 Slot G IO S/N Invalid
0x00000020 Slot H IO S/N Invalid
0x00000040 Slot B IO S/N Invalid
0x00000080 Slot C IO S/N Invalid
0x00000100 Slot J IO S/N Invalid
0x00000200 Slot K IO S/N Invalid
0x00000400 COMM Serial# Invalid
0x00000800 FP Serial# Invalid
0x00001000 PSU Serial# Invalid
0x00002000 Calibration Error
0x00004000 RTC Error
0x00008000 Reserved
0x00010000 FLASH Error
0x00020000 EEPROM Error
0x00040000 Reserved
0x00080000 Reserved
0x00100000 Reserved
0x00200000 Ambient Temperature >80C
0x00400000 Voltage Rail Error
0x00800000 Critical Path Error
0x01000000 Reserved

11-196 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x02000000 Reserved
0x04000000 Analog Voltage Rail Error
0x08000000 Reserved
0x10000000 Reserved
0x20000000 Reserved
0x40000000 Reserved
0x80000000 Reserved
FC240A unsigned 32 bits Minor Self Test Error
0 No Error
0x00000001 Order Code Error
0x00000002 Event Rate High
0x00000004 CPU Serial# Invalid
0x00000008 Slot F IO S/N Invalid
0x00000010 Slot G IO S/N Invalid
0x00000020 Slot H IO S/N Invalid
0x00000040 Slot B IO S/N Invalid
0x00000080 Slot C IO S/N Invalid
0x00000100 Slot J IO S/N Invalid
0x00000200 Slot K IO S/N Invalid
0x00000400 COMM Serial# Invalid
0x00000800 FP Serial# Invalid
0x00001000 PSU Serial# Invalid
0x00002000 Clock Not Set
0x00004000 RTC Error
0x00008000 COMM Error #1
0x00010000 FLASH Error
0x00020000 COMM Error #2
0x00040000 Link Error Primary
0x00080000 Traffic Error Primary
0x00100000 Comms Checksum Error
0x00200000 Ambient Temperature >80C
0x00400000 Link Error Secondary
0x00800000 Traffic Error Secondary
0x01000000 Version Mismatch
0x02000000 Invalid MAC Address
0x04000000 SPI Error
0x08000000 CAN_1 Error
0x10000000 CAN_2 Error
0x20000000 IRIG-B Error
0x40000000 Product Serial Invalid
0x80000000 SelfTestFWUpdate
FC252 unsigned 16 bits Security Users
1 Administrator
6 Operator
FC253 unsigned 16 bits Trend
0 Decreasing
1 Increasing

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-197


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


2 Bi-directional
FC254 unsigned 16 bits Measurement Type
0 Blk Interval
1 Exponential
2 Rolling Dmd
FC255 unsigned 16 bits Thermal 90% Response Time
0 5 min
1 10 min
2 15 min
3 20 min
4 30 min
FC256 unsigned 16 bits Phase IOC Input
0 Phasor
1 RMS
FC258 unsigned 16 bits CT Secondary
0 1:00 AM
1 5:00 AM
FC259 unsigned 16 bits Source Polarity of ph CTs & VTs
0 Same
1 Reverse
FC260 unsigned 16 bits Mode
0 Phase to Ground
1 Phase to Phase
FC261 unsigned 16 bits Voltages Required For Operation
0 Any One
1 Any Two
2 All Three
FC262 unsigned 16 bits Breaker Failure Function
0 Disabled
1 Retrip
2 Latched Alarm
3 Alarm
4 Configurable
FC263 unsigned 16 bits Breaker Failure Supervision
0 Current
1 52b & Current
2 52b
FC264 unsigned 16 bits Breaker Status
0 State Unknown
1 Opened
2 Closed
3 Disconnected
4 Not Configured
FC265 unsigned 16 bits TOC Reset
0 Instantaneous
1 Timed
FC266 unsigned 32 bits Contact Input Selection

11-198 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


0x0000 Off
0x200 Contact Input 1
0x201 Contact Input 2
0x202 Contact Input 3
0x203 Contact Input 4
0x204 Contact Input 5
0x205 Contact Input 6
0x206 Contact Input 7
0x207 Contact Input 8
0x208 Contact Input 9
0x209 Contact Input 10
0x20A Contact Input 11
0x20B Contact Input 12
0x20C Contact Input 13
0x20D Contact Input 14
FC267 unsigned 16 bits Supervision Function
0 Disabled
1 Lockout
2 Alarm
FC268 unsigned 16 bits Distance Measurement Unit
0 Miles
1 Km
FC269 unsigned 16 bits VT Substitution
0 None
1 I0
2 V0
FC270 unsigned 16 bits Type Of Fault
0 N/A
1 AG
2 BG
3 CG
4 AB
5 BC
6 CA
7 ABG
8 ACG
9 BCG
10 ABC
FC271 unsigned 16 bits Non-Volatile Latch Type
0 Reset-Dominant
1 Set-Dominant
FC272 unsigned 16 bits Directional Polarizing Voltage
0 Calculated V0
1 Measured VX
FC272A unsigned 16 bits Wattmetric Ground Fault Voltage
0 Calculated VN
1 Measured VX

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-199


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


FC273 unsigned 16 bits FlexAnalog Parameters
0 Off
31270 J1 Ia
31272 J1 Ib
31274 J1 Ic
31276 J1 Ig
31278 J1 In
31280 J1 Ia RMS
31282 J1 Ib RMS
31284 J1 Ic RMS
31286 J1 Ig RMS
31288 J1 In RMS
31290 J1 Ia Angle
31291 J1 Ib Angle
31292 J1 Ic Angle
31293 J1 Ig Angle
31294 J1 In Angle
31295 J1 I AVG
31297 J1 I_0
31299 J1 I_1
31301 J1 I_2
31303 J1 I_0 Angle
31304 J1 I_1 Angle
31305 J1 I_2 Angle
31306 J1 Igd
31308 J1 Igd Angle
31309 J1 Load
31320 K1 Ia
31322 K1 Ib
31324 K1 Ic
31326 K1 Isg
31328 K1 In
31330 K1 Ia RMS
31332 K1 Ib RMS
31334 K1 Ic RMS
31336 K1 Isg RMS
31338 K1 In RMS
31340 K1 Ia Angle
31341 K1 Ib Angle
31342 K1 Ic Angle
31343 K1 Isg Angle
31344 K1 In Angle
31345 K1 I AVG
31347 K1 I_0
31349 K1 I_1
31351 K1 I_2
31353 K1 I_0 Angle

11-200 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


31354 K1 I_1 Angle
31355 K1 I_2 Angle
31356 K1 Igd
31358 K1 Igd Angle
31359 K1 Load
31370 K2 Ia
31372 K2 Ib
31374 K2 Ic
31376 K2 Ig
31378 K2 In
31380 K2 Ia RMS
31382 K2 Ib RMS
31384 K2 Ic RMS
31386 K2 Ig RMS
31388 K2 In RMS
31390 K2 Ia Angle
31391 K2 Ib Angle
31392 K2 Ic Angle
31393 K2 Ig Angle
31394 K2 In Angle
31395 K2 I AVG
31397 K2 I_0
31399 K2 I_1
31401 K2 I_2
31403 K2 I_0 Angle
31404 K2 I_1 Angle
31405 K2 I_2 Angle
31406 K2 Igd
31408 K2 Igd Angle
31409 K2 Load
31430 J2 Van
31432 J2 Vbn
31434 J2 Vcn
31436 J2 Vab
31438 J2 Vbc
31440 J2 Vca
31442 J2 Vn
31444 J2 Vaux
31446 J2 Van RMS
31448 J2 Vbn RMS
31450 J2 Vcn RMS
31452 J2 Vab RMS
31454 J2 Vbc RMS
31456 J2 Vca RMS
31458 J2 Vn RMS
31460 J2 Vaux RMS
31462 J2 Van Angle

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-201


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


31463 J2 Vbn Angle
31464 J2 Vcn Angle
31465 J2 Vab Angle
31466 J2 Vbc Angle
31467 J2 Vca Angle
31468 J2 Vn Angle
31469 J2 Vaux Angle
31470 J2 V AVG L-L
31472 J2 V AVG L-N
31474 J2 V0
31476 J2 V1
31478 J2 V2
31480 J2 V0 Angle
31481 J2 V1 Angle
31482 J2 V2 Angle
31493 K2 Van
31495 K2 Vbn
31497 K2 Vcn
31499 K2 Vab
31501 K2 Vbc
31503 K2 Vca
31505 K2 Vn
31507 K2 Vaux
31509 K2 Van RMS
31511 K2 Vbn RMS
31513 K2 Vcn RMS
31515 K2 Vab RMS
31517 K2 Vbc RMS
31519 K2 Vca RMS
31521 K2 Vn RMS
31523 K2 Vaux RMS
31525 K2 Van Angle
31526 K2 Vbn Angle
31527 K2 Vcn Angle
31528 K2 Vab Angle
31529 K2 Vbc Angle
31530 K2 Vca Angle
31531 K2 Vn Angle
31532 K2 Vaux Angle
31533 K2 V AVG L-L
31535 K2 V AVG L-N
31537 K2 V0
31539 K2 V1
31541 K2 V2
31543 K2 V0 Angle
31544 K2 V1 Angle
31545 K2 V2 Angle

11-202 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


31610 J1 Phase A THD
31611 J1 Phase B THD
31612 J1 Phase C THD
31613 J1 Phase A 2
31614 J1 Phase B 2
31615 J1 Phase C 2
31616 J1 Phase A 3
31617 J1 Phase B 3
31618 J1 Phase C 3
31619 J1 Phase A 4
31620 J1 Phase B 4
31621 J1 Phase C 4
31622 J1 Phase A 5
31623 J1 Phase B 5
31624 J1 Phase C 5
31625 J1 Phase A 6
31626 J1 Phase B 6
31627 J1 Phase C 6
31628 J1 Phase A 7
31629 J1 Phase B 7
31630 J1 Phase C 7
31631 J1 Phase A 8
31632 J1 Phase B 8
31633 J1 Phase C 8
31634 J1 Phase A 9
31635 J1 Phase B 9
31636 J1 Phase C 9
31637 J1 Phase A 10
31638 J1 Phase B 10
31639 J1 Phase C 10
31640 J1 Phase A 11
31641 J1 Phase B 11
31642 J1 Phase C 11
31643 J1 Phase A 12
31644 J1 Phase B 12
31645 J1 Phase C 12
31646 J1 Phase A 13
31647 J1 Phase B 13
31648 J1 Phase C 13
31649 J1 Phase A 14
31650 J1 Phase B 14
31651 J1 Phase C 14
31652 J1 Phase A 15
31653 J1 Phase B 15
31654 J1 Phase C 15
31655 J1 Phase A 16
31656 J1 Phase B 16

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-203


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


31657 J1 Phase C 16
31658 J1 Phase A 17
31659 J1 Phase B 17
31660 J1 Phase C 17
31661 J1 Phase A 18
31662 J1 Phase B 18
31663 J1 Phase C 18
31664 J1 Phase A 19
31665 J1 Phase B 19
31666 J1 Phase C 19
31667 J1 Phase A 20
31668 J1 Phase B 20
31669 J1 Phase C 20
31670 J1 Phase A 21
31671 J1 Phase B 21
31672 J1 Phase C 21
31673 J1 Phase A 22
31674 J1 Phase B 22
31675 J1 Phase C 22
31676 J1 Phase A 23
31677 J1 Phase B 23
31678 J1 Phase C 23
31679 J1 Phase A 24
31680 J1 Phase B 24
31681 J1 Phase C 24
31682 J1 Phase A 25
31683 J1 Phase B 25
31684 J1 Phase C 25
31695 J2 Phase A THD
31696 J2 Phase B THD
31697 J2 Phase C THD
31698 J2 Phase A 2
31699 J2 Phase B 2
31700 J2 Phase C 2
31701 J2 Phase A 3
31702 J2 Phase B 3
31703 J2 Phase C 3
31704 J2 Phase A 4
31705 J2 Phase B 4
31706 J2 Phase C 4
31707 J2 Phase A 5
31708 J2 Phase B 5
31709 J2 Phase C 5
31710 J2 Phase A 6
31711 J2 Phase B 6
31712 J2 Phase C 6
31713 J2 Phase A 7

11-204 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


31714 J2 Phase B 7
31715 J2 Phase C 7
31716 J2 Phase A 8
31717 J2 Phase B 8
31718 J2 Phase C 8
31719 J2 Phase A 9
31720 J2 Phase B 9
31721 J2 Phase C 9
31722 J2 Phase A 10
31723 J2 Phase B 10
31724 J2 Phase C 10
31725 J2 Phase A 11
31726 J2 Phase B 11
31727 J2 Phase C 11
31728 J2 Phase A 12
31729 J2 Phase B 12
31730 J2 Phase C 12
31731 J2 Phase A 13
31732 J2 Phase B 13
31733 J2 Phase C 13
31734 J2 Phase A 14
31735 J2 Phase B 14
31736 J2 Phase C 14
31737 J2 Phase A 15
31738 J2 Phase B 15
31739 J2 Phase C 15
31740 J2 Phase A 16
31741 J2 Phase B 16
31742 J2 Phase C 16
31743 J2 Phase A 17
31744 J2 Phase B 17
31745 J2 Phase C 17
31746 J2 Phase A 18
31747 J2 Phase B 18
31748 J2 Phase C 18
31749 J2 Phase A 19
31750 J2 Phase B 19
31751 J2 Phase C 19
31752 J2 Phase A 20
31753 J2 Phase B 20
31754 J2 Phase C 20
31755 J2 Phase A 21
31756 J2 Phase B 21
31757 J2 Phase C 21
31758 J2 Phase A 22
31759 J2 Phase B 22
31760 J2 Phase C 22

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-205


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


31761 J2 Phase A 23
31762 J2 Phase B 23
31763 J2 Phase C 23
31764 J2 Phase A 24
31765 J2 Phase B 24
31766 J2 Phase C 24
31767 J2 Phase A 25
31768 J2 Phase B 25
31769 J2 Phase C 25
31780 K1 Phase A THD
31781 K1 Phase B THD
31782 K1 Phase C THD
31783 K1 Phase A 2
31784 K1 Phase B 2
31785 K1 Phase C 2
31786 K1 Phase A 3
31787 K1 Phase B 3
31788 K1 Phase C 3
31789 K1 Phase A 4
31790 K1 Phase B 4
31791 K1 Phase C 4
31792 K1 Phase A 5
31793 K1 Phase B 5
31794 K1 Phase C 5
31795 K1 Phase A 6
31796 K1 Phase B 6
31797 K1 Phase C 6
31798 K1 Phase A 7
31799 K1 Phase B 7
31800 K1 Phase C 7
31801 K1 Phase A 8
31802 K1 Phase B 8
31803 K1 Phase C 8
31804 K1 Phase A 9
31805 K1 Phase B 9
31806 K1 Phase C 9
31807 K1 Phase A 10
31808 K1 Phase B 10
31809 K1 Phase C 10
31810 K1 Phase A 11
31811 K1 Phase B 11
31812 K1 Phase C 11
31813 K1 Phase A 12
31814 K1 Phase B 12
31815 K1 Phase C 12
31816 K1 Phase A 13
31817 K1 Phase B 13

11-206 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


31818 K1 Phase C 13
31819 K1 Phase A 14
31820 K1 Phase B 14
31821 K1 Phase C 14
31822 K1 Phase A 15
31823 K1 Phase B 15
31824 K1 Phase C 15
31825 K1 Phase A 16
31826 K1 Phase B 16
31827 K1 Phase C 16
31828 K1 Phase A 17
31829 K1 Phase B 17
31830 K1 Phase C 17
31831 K1 Phase A 18
31832 K1 Phase B 18
31833 K1 Phase C 18
31834 K1 Phase A 19
31835 K1 Phase B 19
31836 K1 Phase C 19
31837 K1 Phase A 20
31838 K1 Phase B 20
31839 K1 Phase C 20
31840 K1 Phase A 21
31841 K1 Phase B 21
31842 K1 Phase C 21
31843 K1 Phase A 22
31844 K1 Phase B 22
31845 K1 Phase C 22
31846 K1 Phase A 23
31847 K1 Phase B 23
31848 K1 Phase C 23
31849 K1 Phase A 24
31850 K1 Phase B 24
31851 K1 Phase C 24
31852 K1 Phase A 25
31853 K1 Phase B 25
31854 K1 Phase C 25
31865 K2 Phase A THD
31866 K2 Phase B THD
31867 K2 Phase C THD
31868 K2 Phase A 2
31869 K2 Phase B 2
31870 K2 Phase C 2
31871 K2 Phase A 3
31872 K2 Phase B 3
31873 K2 Phase C 3
31874 K2 Phase A 4

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-207


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


31875 K2 Phase B 4
31876 K2 Phase C 4
31877 K2 Phase A 5
31878 K2 Phase B 5
31879 K2 Phase C 5
31880 K2 Phase A 6
31881 K2 Phase B 6
31882 K2 Phase C 6
31883 K2 Phase A 7
31884 K2 Phase B 7
31885 K2 Phase C 7
31886 K2 Phase A 8
31887 K2 Phase B 8
31888 K2 Phase C 8
31889 K2 Phase A 9
31890 K2 Phase B 9
31891 K2 Phase C 9
31892 K2 Phase A 10
31893 K2 Phase B 10
31894 K2 Phase C 10
31895 K2 Phase A 11
31896 K2 Phase B 11
31897 K2 Phase C 11
31898 K2 Phase A 12
31899 K2 Phase B 12
31900 K2 Phase C 12
31901 K2 Phase A 13
31902 K2 Phase B 13
31903 K2 Phase C 13
31904 K2 Phase A 14
31905 K2 Phase B 14
31906 K2 Phase C 14
31907 K2 Phase A 15
31908 K2 Phase B 15
31909 K2 Phase C 15
31910 K2 Phase A 16
31911 K2 Phase B 16
31912 K2 Phase C 16
31913 K2 Phase A 17
31914 K2 Phase B 17
31915 K2 Phase C 17
31916 K2 Phase A 18
31917 K2 Phase B 18
31918 K2 Phase C 18
31919 K2 Phase A 19
31920 K2 Phase B 19
31921 K2 Phase C 19

11-208 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


31922 K2 Phase A 20
31923 K2 Phase B 20
31924 K2 Phase C 20
31925 K2 Phase A 21
31926 K2 Phase B 21
31927 K2 Phase C 21
31928 K2 Phase A 22
31929 K2 Phase B 22
31930 K2 Phase C 22
31931 K2 Phase A 23
31932 K2 Phase B 23
31933 K2 Phase C 23
31934 K2 Phase A 24
31935 K2 Phase B 24
31936 K2 Phase C 24
31937 K2 Phase A 25
31938 K2 Phase B 25
31939 K2 Phase C 25
31960 Bus Volts Magnitude
31962 Bus Volts Angle
31963 Bus Volts Frequency
31965 Line Volts Magnitude
31967 Line Volts Angle
31968 Line Volts Frequency
31970 Voltage Difference
31972 Angle Difference
31973 Frequency Difference
31985 Bus Volts Magnitude
31987 Bus Volts Angle
31988 Bus Volts Frequency
31990 Line Volts Magnitude
31992 Line Volts Angle
31993 Line Volts Frequency
31995 Voltage Difference
31997 Angle Difference
31998 Frequency Difference
32020 Pwr1 Real
32022 Pwr1 Reactive
32024 Pwr1 Apparent
32026 Pwr1 Ph A Real
32028 Pwr1 Ph B Real
32030 Pwr1 Ph C Real
32032 Pwr1 Ph A Reactive
32034 Pwr1 Ph B Reactive
32036 Pwr1 Ph C Reactive
32038 Pwr1 Ph A Apparent
32040 Pwr1 Ph B Apparent

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-209


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


32042 Pwr1 Ph C Apparent
32044 Pwr1 PF
32045 Pwr1 Ph A PF
32046 Pwr1 Ph B PF
32047 Pwr1 Ph C PF
32058 Pwr2 Real
32060 Pwr2 Reactive
32062 Pwr2 Apparent
32064 Pwr2 Ph A Real
32066 Pwr2 Ph B Real
32068 Pwr2 Ph C Real
32070 Pwr2 Ph A Reactive
32072 Pwr2 Ph B Reactive
32074 Pwr2 Ph C Reactive
32076 Pwr2 Ph A Apparent
32078 Pwr2 Ph B Apparent
32080 Pwr2 Ph C Apparent
32082 Pwr2 PF
32083 Pwr2 Ph A PF
32084 Pwr2 Ph B PF
32085 Pwr2 Ph C PF
32114 Pwr1 Pos WattHours
32118 Pwr1 Neg WattHours
32122 Pwr1 Pos VarHours
32124 Pwr1 Neg VarHours
32140 Pwr2 Pos WattHours
32144 Pwr2 Neg WattHours
32148 Pwr2 Pos VarHours
32150 Pwr2 Neg VarHours
32184 J1 Ph A Demand
32186 J1 Ph B Demand
32188 J1 Ph C Demand
32190 J1 Max Ph A Demand
32192 J1 Max Ph B Demand
32194 J1 Max Ph C Demand
32222 K1 Ph A Demand
32224 K1 Ph B Demand
32226 K1 Ph C Demand
32228 K1 Max Ph A Demand
32230 K1 Max Ph B Demand
32232 K1 Max Ph C Demand
32260 K2 Ph A Demand
32262 K2 Ph B Demand
32264 K2 Ph C Demand
32266 K2 Max Ph A Demand
32268 K2 Max Ph B Demand
32270 K2 Max Ph C Demand

11-210 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


32314 Pwr1 Real Dmd
32316 Pwr1 Max Real Dmd
32322 Pwr1 Reactive Dmd
32324 Pwr1 Max Reactive Dmd
32330 Pwr1 Apparent Dmd
32332 Pwr1 Max Apparent Dmd
32352 Pwr2 Real Dmd
32354 Pwr2 Max Real Dmd
32360 Pwr2 Reactive Dmd
32362 Pwr2 Max Reactive Dmd
32368 Pwr2 Apparent Dmd
32370 Pwr2 Max Apparent Dmd
32620 Arcing Current Phase A
32622 Arcing Current Phase B
32624 Arcing Current Phase C
33430 Phase A Thermal Cap
33431 Phase B Thermal Cap
33432 Phase C Thermal Cap
33450 Directional Power 1
33452 Directional Power 2
33460 Wattmetric Ground Fault
33540 J1-CT Frequency
33542 J1-CT Frq Rate of Chge
33543 J2-3VT Frequency
33545 J2-3VT Frq Rate of Chge
33546 J2-Vx Frequency
33548 J2-Vx Frq Rate of Chge
FC276 unsigned 16 bits Wattmetric Current
0 Calculated IN
1 Measured IG
FC277 unsigned 16 bits Breaker Health Mode
0 Detection
1 Monitoring
FC278 unsigned 16 bits Aux Relay Type
0 Self-Reset
1 Latched
2 Pulsed
FC279 unsigned 16 bits UV Restoration Initiation
0 Off
1 Phase UV 1 OP
2 Phase UV 2 OP
3 Aux UV 1 OP
4 Aux UV 2 OP
FC280 unsigned 16 bits Close Syncrocheck Supervision
0 Bypass
1 Sync1 Close Perm
2 Sync2 Close Perm

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-211


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


FC283 unsigned 16 bits Synchrocheck Dead Source Permit
0 Disabled
1 LB & DL
2 DB & LL
3 DB & DL
4 DB OR DL
5 DB XOR DL
FC284 unsigned 16 bits Transfer Function Scheme
0 Disabled
1 Incomer 1
2 Incomer 2
3 Bus Tie
FC285 unsigned 16 bits Dead Source Permission
0 Sync1 Dead Src OK
FC286 unsigned 16 bits Power Factor Power Input
0 Power 1
1 Power 2
FC287 unsigned 16 bits UF Restoration Initiation
0 Off
1 UnderFreq 1 OP
2 UnderFreq 2 OP
3 UnderFreq 3 OP
4 UnderFreq 4 OP
5 FreqROC DWN OP
FC288 unsigned 16 bits Three State Security Model
0 No Security
1 Passwords Enabled
2 Full Security
FC289 unsigned 16 bits Breaker Status
0 Not Set
1 Fail
2 OK
FC290 unsigned 16 bits Default Screen Index
0 Off
4 BKR1
5 BKR 2
6 BKR 3
8 Inputs
9 Relays
10 V Inputs
11 V Outpts
20 Info
24 Dev Stat
25 Clock
26 PTP
27 Fault Loc
29 Arcing I

11-212 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


32 Summary
33 Phasors
34 Sequence
35 Current 1
36 Current 2
37 Current 3
38 Voltage 1
39 Voltage 2
42 Harm 1
43 Harm 2
44 Harm 3
45 Harm 4
48 Power 1
49 Power 2
50 Energy 1
51 Energy 2
52 Cur Dmd1
53 Cur Dmd2
54 Cur Dmd3
55 Pwr Dmd1
56 Pwr Dmd2
FC302 unsigned 32 bits LEDs 1-16
0x00000003 LED 1
0x0000000C LED 2
0x00000030 LED 3
0x000000C0 LED 4
0x00000300 LED 5
0x00000C00 LED 6
0x00003000 LED 7
0x0000C000 LED 8
0x00030000 LED 9
0x000C0000 LED 10
0x00300000 LED 11
0x00C00000 LED 12
0x03000000 LED 13
0x0C000000 LED 14
0x30000000 LED 15
0xC0000000 LED 16
FC303 unsigned 32 bits LEDs 17-32
0x00000003 LED 17
0x0000000C LED 18
0x00000030 LED 19
0x000000C0 LED 20
0x00000300 LED 21
0x00000C00 LED 22
0x00003000 LED 23
0x0000C000 LED 24

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-213


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


0x00030000 LED 25
0x000C0000 LED 26
0x00300000 LED 27
0x00C00000 LED 28
0x03000000 LED 29
0x0C000000 LED 30
0x30000000 LED 31
0xC0000000 LED 32
FC322 unsigned 16 bits Active Pushbutton
0 Off
1 Pushbutton 1 ON
2 Pushbutton 2 ON
3 Pushbutton 3 ON
FC323 unsigned 32 bits GOOSE Status
0x00000001 GOOSE Status 1
0x00000002 GOOSE Status 2
0x00000004 GOOSE Status 3
0x00000008 GOOSE Status 4
0x00000010 GOOSE Status 5
0x00000020 GOOSE Status 6
0x00000040 GOOSE Status 7
0x00000080 GOOSE Status 8
FC324 unsigned 16 bits File Transfer Mode
0 Read
1 Write
FC340 unsigned 16 bits Security Bypass Access
0 Disabled
1 Local
2 Remote
3 Local&Remote
FC341 unsigned 16 bits Radius Authentication Method
0 EAP-TTLS
FC342 unsigned 16 bits RTC Sync Source
0 None
1 Port 4 PTP Clock
2 Port 5 PTP Clock
3 IRIG B
4 SNTP
FC343 unsigned 16 bits PTP State
0 Disabled
1 No Signal
2 Calibrating
3 Synch'd (No PDelay)
4 Synchronized
FC150 unsigned 16 bits SR8 Element List
All Elements Available in the SR8
1 Any Trip

11-214 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


2 Any Alarm
5 Any Block
6 Any PKP
7 Any OP
8 Reset
9 Setpoint Access
10 Targets Active
11 In Serv.
12 Test Mode
13 Any Major Error
14 Any Minor Error
15 Output Relay 1
16 Output Relay 2
17 Output Relay 3
18 Output Relay 4
21 Critical Fail
22 Comms OK
23 Phase TOC 1
24 Phase TOC 2
26 Phase IOC 1
27 Phase IOC 2
29 Ph Dir OC
30 Ntrl TOC 1
31 Ntrl TOC 2
32 Ntrl IOC 1
33 Ntrl IOC 2
34 Ntrl Dir OC
35 Gnd TOC 1
39 Gnd IOC 1
43 Gnd Dir OC
44 SGnd TOC 1
46 SGnd IOC 1
48 SGnd Dir OC
49 RGF 1
52 Neg Seq TOC 1
54 Neg Seq IOC 1
56 Neg Seq Dir OC
57 BrokenConductor
58 LoadEncr
59 Thermal Model
60 Thermal Model Alrm
61 Ph UV 1
62 Ph UV 2
63 Ph OV 1
64 Ph OV 2
65 Aux UV 1
66 Aux UV 2

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-215


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


67 Aux OV
68 Neutral OV 1
69 Neutral OV 2
70 Neg Seq OV 1
71 Neg Seq OV 2
72 Dir Pwr 1
73 Dir Pwr 2
74 WattMetric 1
75 WattMetric 2
76 UF 1
77 UF 2
78 UF 3
79 UF 4
80 OF 1
81 OF 2
82 Freq RateOfChng1
86 Group 1
87 Group 2
88 Group 3
89 Group 4
90 Group 5
91 Group 6
92 Local Mode
93 Open BKR 1
96 Close BKR 1
99 Trip Bus 1
100 Trip Bus 2
101 Trip Bus 3
102 Trip Bus 4
103 Trip Bus 5
104 Trip Bus 6
105 BKR Fail 1
108 Sync Check 1
110 Manual Cls Blk
111 VTFF 1
113 CLP 1
115 UV Restore
116 Bus Transfer
117 AR1
118 AR1 Shot Cnt
119 AR1 Shot Cnt Reduction
120 AR1 Rate Supervision
125 UF Restore
126 BKR1 Status Closed
127 BKR1 Status Opened
128 BKR1 Status Unknown
129 BKR1 Status Disconnected

11-216 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP FORMAT CODES

Code Type Definition


130 BKR1 52a Contact
131 BKR1 52b Contact
144 TripCoilMon 1
147 CloseCoilMon 1
150 Breaker 1 Arcing Current
153 Breaker1 Health
156 Breaker1 Arc Health
159 PF 1
160 PF 2
161 Current Dmd
162 RealPwrDmd
163 ReactivePwrDmd
164 ApparentPwrDmd
165 Fault Locator
202 Pulse Out
203 Digital Counter 1
204 Digital Counter 2
205 Digital Counter 3
206 Digital Counter 4
207 Digital Counter 5
208 Digital Counter 6
209 Digital Counter 7
210 Digital Counter 8
211 Digital Counter 9
212 Digital Counter 10
213 Digital Counter 11
214 Digital Counter 12
215 Digital Counter 13
216 Digital Counter 14
217 Digital Counter 15
218 Digital Counter 16
219 NV Latch 1
220 NV Latch 2
221 NV Latch 3
222 NV Latch 4
223 NV Latch 5
224 NV Latch 6
225 NV Latch 7
226 NV Latch 8
227 NV Latch 9
228 NV Latch 10
229 NV Latch 11
230 NV Latch 12
231 NV Latch 13
232 NV Latch 14
233 NV Latch 15
234 NV Latch 16

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-217


FORMAT CODES CHAPTER 11: MODBUS MEMORY MAP

Code Type Definition


235 PB 1
236 PB 2
237 PB 3
238 Security Login
239 Data Logger
240 Transfer Initiated
FC151 unsigned 16 bits Element Status
This format shows the meaning of the Element Status values.
Refer to Format FC142 for exact information for each element.
There are cases where different meaning is given to
each bit. PKP meaning "Open", for example.
0x0000 None Active
0x0001 Element PKP
0x0002 Element OP
0x0008 Phase A Pickup
0x0010 Phase B Pickup
0x0020 Phase C Pickup
0x0040 Phase A Operate
0x0080 Phase B Operate
0x0100 Phase C Operate
0x0200 Element Is Latched
0x0400 Configurable Type
0x0800 Alarm Type
0x1000 Trip Type
0x2000 Flexlogic Element
FC157 unsigned 16 bits LED Colour
0 Off
1 Red
2 Green
3 Orange
FC161 unsigned 16 bits OC Curve Selection
0 IEEE Extr. Inverse
1 IEEE Very Inverse
2 IEEE Mod Inverse
3 ANSI Extr. Inverse
4 ANSI Very Inverse
5 ANSI Norm Inverse
6 ANSI Mod Inverse
7 Definite Time
8 IEC Curve A
9 IEC Curve B
10 IEC Curve C
11 IEC Short Inverse
12 IAC Extr. Inverse
13 IAC Very Inverse
14 IAC Inverse
15 IAC Short Inverse

11-218 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE


CHAPTER 11: MODBUS MEMORY MAP MODBUS COMMANDS

Code Type Definition


16 Flex Curve A
17 Flex Curve B
18 Flex Curve C
19 Flex Curve D
20 I2t
21 I4t
FC161A unsigned 16 bits Neutral OV Curve Selection
7 Definite Time

Modbus Commands

Command Value Description


0 None
1 Reset
3 Open
4 Close
9 ChangeToSetpointGroup1
10 ChangeToSetpointGroup2
11 ChangeToSetpointGroup3
12 ChangeToSetpointGroup4
13 ChangeToSetpointGroup5
14 ChangeToSetpointGroup6
15 Active Group
18 Local
19 Remote
96 Clear All Records
97 Clear Targets
98 Clear Events
99 Clear Transient Records
101 Clear Max Current Demand
102 Clear Max Real Power Demand
103 Clear Max Reactive Power Demand
104 Clear Max Apparent Power Demand
105 Clear Energy Use Data
108 Clear BKR1 Arcing Current
109 Clear BKR1 Health Data
124 Reset Unauthorized Access
126 Clear Fault Reports
134 USER PushButton 1
135 USER PushButton 2
136 USER PushButton 3
153 LED Test
154 Force LEDs
202 Trigger Waveform

850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE 11-219


MODBUS COMMANDS CHAPTER 11: MODBUS MEMORY MAP

Command Value Description


4096 Force Virtual Input 1
4097 Force Virtual Input 2
4098 Force Virtual Input 3
4099 Force Virtual Input 4
4100 Force Virtual Input 5
4101 Force Virtual Input 6
4102 Force Virtual Input 7
4103 Force Virtual Input 8
4104 Force Virtual Input 9
4105 Force Virtual Input 10
4106 Force Virtual Input 11
4107 Force Virtual Input 12
4108 Force Virtual Input 13
4109 Force Virtual Input 14
4110 Force Virtual Input 15
4111 Force Virtual Input 16
4112 Force Virtual Input 17
4113 Force Virtual Input 18
4114 Force Virtual Input 19
4115 Force Virtual Input 20
4116 Force Virtual Input 21
4117 Force Virtual Input 22
4118 Force Virtual Input 23
4119 Force Virtual Input 24
4120 Force Virtual Input 25
4121 Force Virtual Input 26
4122 Force Virtual Input 27
4123 Force Virtual Input 28
4124 Force Virtual Input 29
4125 Force Virtual Input 30
4126 Force Virtual Input 31
4127 Force Virtual Input 32

11-220 850 FEEDER PROTECTION SYSTEM COMMUNICATIONS GUIDE

You might also like