Zr81kce TFD PDF

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ZR81KCE-TFD

HFC, R-407C, Dew Point, 50 Hz, 3 - Phase, 380/420 V


Air Conditioning
Production Status: Available for sale to all U.S. customers. Please check with your local Emerson Climate Technologies representative
for international availability.

Performance Mechanical
Evap(F)/Cond(F) 45/130 45/100 Number of Cylinders: 0 Displ (in^3/Rev): 6.577
RG(F)/Liq(F) 65/115 65/85 Bore Size (in): 0.0 Displ (ft^3/hr): 662.2644
Stroke (in): 0.0
Capacity (Btu/hr): 63500 77000
Power (Watts): 5900 3990 Overall Length (in): 9.48 Mounting Length (in): 7.5
Current (Amps): 10.9 8.6 Overall Width (in): 9.71 Mounting Width(in): 7.5
EER (Btu/Wh): 10.8 19.3 Overall Height (in): 17.955 Mounting Height (in): 18.205*
Mass Flow (lbs/hr): 925.0 955.0
Suction Size (in): 7/8 Stub
Sound Power(dBA): 72 Ave 77 Max Discharge Size (in): 3/4 Stub
Vibration (mils(peak-peak)): 2.0 Ave 3.0 Max Initial Oil Charge (oz): 60
Oil Recharge (oz): 56
Record Date: 2005-04-15 Net Weight (lbs): 86.0
Internal Free Volume (in^3): 258.0
HorsePower
* Overall compressor height on Copeland Brand Product's specified
mounting grommets.

Electrical
LRA-High*: 101.0 MCC (Amps): 17.0 UL File No.: SA-2337
LRA-Half Winding: RPM: 2900 UL File Date: 26-Jul-1993
LRA-Low*: 90.5 Max Operating Current: 15.0 CSA File No.: LR3104C
RLA(=MCC/1.4; use for contactor selection): 12.1
RLA (=MCC/1.56; use for breaker & wire size selection): 10.9
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.

Alternate Applications
Refrigerant Frequency(Hz) Phase Voltage Application

R-134a HFC 60 3 460 Air Conditioning


R-407C HFC 60 3 460 Air Conditioning
R-134a HFC 50 3 380/420 Air Conditioning

Thai Nair Equipment, Tel 02-282-3822, 281-6295. Page 1 of 1


5/18/2009

Copyright 2008 Emerson Climate Technologies, Inc. All rights reserved.