4 Power Transformer Protection Devices Explained in Details
4 Power Transformer Protection Devices Explained in Details
4 Power Transformer Protection Devices Explained in Details
electrical-engineering-portal.com/4-power-transformer-protection-devices-explained-in-details
Google+
20/04/2015
4 Power Transformer Protection Devices explained in details (on photo: Bayer 69KV Substation Transformer; credit: ietc-team.com)
Protection Devices //
The following discusses protection devices typically delivered as a part of the power transformer delivery .
1. Buchholz (Gas) Relay
2. Pressure Relay
3. Oil Level Monitor Device
4. Winding Thermometer
1/8
The power transformer protection as a whole and the utilization of the below presented protection devices are not
discussed here.
They therefore produce a steep buildup of pressure and displace oil. This sets up a rapid flow from the transformer
towards the conservator. The vane (V) responds to high oil and gas flow in the pipe to the conservator. In this case,
the mercury switch closes a trip circuit. The operating time of the trip contact depends on the location of the fault
and the magnitude of the fault current.
2/8
Tests carried out with simulated operating conditions have shown that operation in the time range 0.050-0.10
seconds is possible. The operating time should not exceed 0.3 seconds.
The gas accumulator relay also provides a long-term accumulation of gasses associated with overheating of
various parts of the transformer conductor and insulation systems. This will detect fault sources in their early stages
and prevent significant damage.
When the transformer is first put into service, the air trapped in
the windings may give unnecessary alarm signals. It is
customary to remove the air in the power transformers by
vacuum treatment during the filling of the transformer tank with
oil.
The gas accumulated without this treatment will, of course, be
air, which can be confirmed by seeing that it is not inflammable.
In addition, the Buchholz relay can detect if the oil level falls
below that of the relay as a result of a leakage from the
transformer tank.
Other technical articles related to Buchholz relay //
1. Protecting Oil Type Transformer with Buchholz Relay
2. The Purpose Of Transformer Gas Relay
Go back to Index
2. Pressure Relay
Many power transformers with an on-tank-type tap changer have a pressure protection for the separate tap changer
oil compartment. This protection detects a sudden rate-of-increase of pressure inside the tap changer oil
enclosure.
Figure 3 shows the principle of a pressure relay.
3/8
When the pressure in front of the piston exceeds the counter force of the spring, the piston will move operating the
switching contacts. The micro switch inside the switching unit is hermetically sealed and pressurized with nitrogen
gas.
An internal fault in an oil-filled transformer is usually accompanied by overpressure in the transformer tank.
The simplest form of pressure relief device is the widely used frangible disk. The surge of oil caused by a heavy
internal fault bursts the disk and allows the oil to discharge rapidly. Relieving and limiting the pressure rise prevent
explosive rupture of the tank and consequent fire.
Also, if used, the separate tap changer oil enclosure can be fitted with a pressure relief device.
The pressure relief device can be fitted with contact unit(s) to provide a signal for circuit breaker(s) tripping
circuits.
4/8
A drawback of the frangible disk is that the oil remaining in the tank is left exposed to the atmosphere after a
rupture. This is avoided in a more effective device, the pressure relief valve, which opens to allow the discharge of oil
if the pressure exceeds the pre-adjusted limit.
By providing the transformer with a pressure relief valve, the overpressure can be limited to a magnitude harmless to
the transformer.
If the abnormal pressure is relatively high, this spring-controlled valve can operate within a few milliseconds and
provide fast tripping when suitable contacts are fitted. The valve closes automatically as the internal pressure falls
below a critical level.
Go back to Index
5/8
The top-oil thermometer has a liquid thermometer bulb in a pocket at the top of the transformer. The thermometer
measures the top-oil temperature of the transformer. The top-oil thermometer can have one to four contacts, which
sequentially close at successively higher temperature.
With four contacts fitted, the two lowest levels are commonly used to start fans or pumps for forced cooling , the
third level to initiate an alarm and the fourth step to trip load breakers or de-energize the transformer or both.
The figure below shows the construction of a capillary-type top-oil thermometer, where the bulb is situated in a
pocket surrounded by oil on top of the transformer. The bulb is connected to the measuring bellow inside the main
unit via a capillary tube. The bellow moves the indicator through mechanical linkages, resulting in the operation of the
contacts at set temperatures.
The top-oil temperature may be considerably lower than the winding temperature, especially shortly after a sudden
load increase. This means that the top-oil thermometer is not an effective overheating protection.
However, where the policy towards transformers loss of life permits, tripping on top-oil temperature may be
satisfactory. This has the added advantage of directly monitoring the oil temperature to ensure that it does not reach
the flash temperature.
Go back to Index
4. Winding Thermometer
The winding thermometer, shown in the figure below, responds to both the top-oil temperature and the heating
effect of the load current.
6/8
The winding thermometer creates an image of the hottest part of the winding. The top-oil temperature is
measured with a similar method as introduced earlier. The measurement is further expanded with a current signal
proportional to the loading current in the winding.
This current signal is taken from a current transformer located inside the bushing of that particular winding. This
current is lead to a resistor element in the main unit. This resistor heats up, and as a result of the current flowing
through it, it will in its turn heat up the measurement bellow, resulting in an increased indicator movement.
Figure 9 Top-oil thermometer and winding thermometer main units fitted on the side of a power
transformer
7/8
The temperature bias is proportional to the resistance of the electric heating (resistor) element.
The result of the heat run provides data to adjust the resistance and thereby the temperature bias. The bias
should correspond to the difference between the hot-spot temperature and the top-oil temperature. The time constant
of the heating of the pocket should match the time constant of the heating of the winding.
The temperature sensor then measures a temperature that is equal to the winding temperature if the bias is equal to
the temperature difference and the time constants are equal.
The winding thermometer can have one to four contacts, which sequentially close at successively higher
temperature.
With four contacts fitted, the two lowest levels are commonly used to start fans or pumps for forced cooling , the
third level to initiate an alarm and the fourth step to trip load breakers or de-energize the transformer or both .
In case a power transformer is fitted with top-oil thermometer and winding thermometer, the latter one normally takes
care of the forced cooling control.
Go back to Index
Reference // Distribution Automation Handbook ABB