Wide Area Protection
Wide Area Protection
Wide Area Protection
www.intechopen.com
130
www.intechopen.com
131
control for better management of the system security through advanced control and
protection strategies.
The electricity supply industries need tools for dealing with system wide disturbances that
often cause cascading outages and widespread blackouts in power system networks. When
a major disturbance occurs, protection and control measures overtake the greatest role to
prevent further degradation of the system, restore the system to a normal state, and
minimize the impact of the disturbance. Electrical measurements of the system, which may
include synchronized phasors, are supplied to one or more wind farm controllers, which in
turn perform a control function improving the damping of electromechanical oscillations or
voltage performance in the utility system. The benefits are improved damping to
electromechanical oscillations and better voltage profile and ultimately more efficient
utilization of assets, reducing the necessity for installing new assets. Wide-area protection is
becoming an important issue and a challenging problem in the power industry (Wang et el.,
2005).
This study proposes a novel technique based on wide-area measurements for a power
system. The study is very vital and needed in the current state regarding the electrical utility
and the society as well to face future expansion of the electrical grid and to cover the
demand of the increasing growth and solving the problem of peak period. The study is very
beneficial also from the stability and security of the grid viewpoint in case of interconnection
with other countries.
This study presents a new approach for fault detection and classification for interconnected
system using the time synchronized phasor measurements. The scheme is depending on
comparing positive sequence voltage magnitudes for specified areas and positive sequence
current phase difference angles for each interconnected line between two areas on the
network. The chapter will cover all fault events for fault classification. The Matlab/simulink
program is extensively used to implement the idea. It uses to simulate the power system,
phase measurement unit function, synchronization process, fault detection and
classification.
www.intechopen.com
132
centralization and decentralization. More and more dynamic functions are moving from
local and regional control centers toward central or national control centers. At the same
time we also observe more "intelligence" and "decision power" moving closer towards the
actual power system substations. Greater functional integration is being enclosed in
substation hardware. In view of global security of power systems, the action algorithms of
conventional backup protections possibly are not best choices because the operations of
individual relays are hardly coordinated each other. Therefore, the principle of the
protection design needs innovation to overcome the above problem (Yan et al., 2008;
Xiaoyang et al., 2008; Yangguang et al., 2010; Hui, et al., 2009).
Modem protection devices have sufficient computing and communications capabilities to
allow the implementation of many novel sophisticated protection principles. Therefore, a
novel wide-area backup protection system with fault classification is reported in this
chapter. This system is capable of acting as the substitution of conventional distributed
backup protections in substation. The architecture and algorithm of the system are also
introduced. To ensure the fast responsibility of such a system to the emergent events, the
communication requirements are discussed as well. Conclusively, the proposed system is
designed by two ways. First, in substation, concentrate some conventional backup
protection functions to an intelligent processing system; second, concentrate the coordinated
and optimized processing and controlling arithmetic of all backup protection in a region
into a regional processing unit. The communication of data among them is carried via opticfiber networks (Zhiyuan et al., 2009; 2009).
The proposed system comprises a master system and several local units. The system is
arranged as three layers. The bottom layer consists of PMUs with additional protection
functionality. The next layer consists of several Local Backup Protection Centers (LBPCs),
each of which interfaces directly with a number of PMUs. The top layer, System Backup
Protection Center (SBPC), acts as the coordinator for the LBPCs. Connected together via
fiber-optic communication links, these devices can process intelligent algorithms based on
data collected locally. The structure can be seen as Figure 2 (Seong et al., 2008).
Local part of the proposed wide-area backup system comprises PMUs and LBPC, which are
both installed in the station. PMUs are made up of DSP (Digital Signal Processor) and GPS
(Global Positioning System). The DSP measures instantaneous voltages and currents of
protected power system in real-time, and calculates the state variables, which provide vital
information for backup protection system. Then, power system variable data is transferred
to LBPC, LBPC samples digital inputs, and pre-processes the analog and digital signals, and
then deliver pre processed results to SBPC via fiber-optic communications between the
substation and SBPC. SBPC will be installed at Regional Control Center, and integrates
various well-developed functions, such as data acquisition via communication, system
monitoring, fault location, security analyzing, making tripping strategy and descending
strategy to LBPCs, also, SBPC can do post-event playback and post-event data analyses.
These functions employ PMUs to fulfil real-time demand (Testa et al., 2004).
LBPCs perform the correlative operations on the spot when receiving the strategy from
SBPC, then fault will be isolated rationally. While it is not possible to prevent all
contingencies that may lead to power system collapse, a wide area backup protection system
that provides a reliable security isolated scheme and optimized coordinated actions is able
to mitigate or prevent large area disturbances.
www.intechopen.com
Background
133
SBPC
SCADA
Center Processor
Optical Fiber
Network
Local
part
LBPC
LBPC
PMUs
Control
the breaker
PMUs
Control the
breaker
LBPC
PMUs
Control the
breaker
www.intechopen.com
134
www.intechopen.com
135
Spinning reserve - The spinning reserve quantity, distribution, and the speed of its'
dynamical response are factors that influence the effectiveness of the spinning reserve
during an emergency. The speed of the dynamic response for the hydro units the first few
seconds after a demand is made is relatively slow compared to thermal units.
Consequently, the spinning reserve needs to be distributed throughout the system on both
hydro and thermal units. The spinning reserve needs to be considered in load shedding
schemes to optimize shed load.
Load - Load is a non-linear function of voltage and frequency. These changes in load impact
power system imbalance and frequency behavior. Further, load changes with the season and
the time of the day. In addition, underfrequency load shedding programs specify percent of
the total load that should be shed at each step. As load changes, actual load for shedding
does not correspond to planned load.
Relays and breaker status - Operation of the protective relays (desired or undesired) and
network configuration have an essential impact to disturbance propagation. If undesired
operation may be avoided by detecting hidden failures or by adapting relay settings to
prevailing system conditions, unwanted transition of the system to a less desirable
emergency state may be prevented. Further, equipment unavailability because of
maintenance and testing needs to be recognized and considered.
Modeling of the power network is required to simulate disturbances and to choose features
that will be extracted. The disturbance in the power network usually develops gradually;
however some phenomena, such as a rise of transient instability, can develop in a fraction of
second. Selection of appropriate power network analysis tools is important (load flow,
transient stability, mid and long term dynamic models, EMTP, etc.).
3.3 Performance requirements for wide area measuring system sensors
It is very important to understand the functionality, limitations, and various relevant
performance requirements of wide area measuring systems (WAMS). This information is
helpful in:
Understanding the application benefits and limitations of WAMS for protection and
emergency control of power systems.
System operation (Real time applications, for system protection, or for manual or
automatic control)
www.intechopen.com
136
modern information technology can contribute to improve this situation. Our proposal to
review the present protection strategy to counteract large area disturbances addresses the
potentials that are derived from the advances in system operational, protection and control
techniques. It will be explained how the application of numerical technology can avoid
catastrophic disturbances to occur or at least to keep the impact of single fault within certain
limits.
In contrast to the requirements for protection relays designed to protect individual plant
objects, system protection schemes intended to prevent voltage or frequency instabilities
have to cope with the loss of generation on a large scale and/or loss of one or more
transmission lines. Information technology offers digital applications, in terms of numerical
adaptive protection relays, integrated disturbance recorders and fast broadband
communication much greater functionality and overall efficiencies than conventional
analogue techniques.
TL
CT
VT
www.intechopen.com
137
transform, the signal is assumed to exist from time - to + but in the DFT, the signal exists for
a small duration of time (called window). The components of different frequencies
determined by the DFT analysis can be combined to recreate the original waveform.
(1)
Where = j 120 and Va, Vb, and Vc are the DFT phasor coefficients of each of the three
phases.
Figure 5 shows a simple block diagram explaining the procedure of measured voltage or
current analog signal. The external time source is an absolute time reference from a global
positioning system (GPS) receiver, which delivers a phase-locked sampling clock pulse to
the Analog-to-Digital converter system. The sampled data are converted to a complex
number which represents the phasor of the sampled waveform. Phasors of the three phases
are combined to produce the positive sequence measurement. A time stamp is generated to
associate with the comtrade report via communication port to phasor data concentrator.
The figure includes a hardware low-pass filter (Hardware LPF) for anti-aliasing and an
www.intechopen.com
138
www.intechopen.com
139
incorporated into any power system design or analysis, as excess delays could ruin any
control procedures adopted to stabilize the power grid.
Although more and more control systems are being implemented in a distributed fashion
with networked communication, the unavoidable time delays in such systems impact the
achievable performance. Delays due to the use of PMUs and the communication link
involved are due primarily to the following reasons:
Transducer delays: Voltage transducers (VT) and current transducers (CT) are used to
measure the RMS voltages and currents respectively, at the instant of sampling.
Window size of the DFT: Window size of the DFT is the number of samples required to
compute the phasors using DFT.
Processing time: The processing time is the time required in converting the transducer data
into phasor information with the help of DFT.
Data size of the PMU output: Data size of the PMU message is the size of the information
bits contained in the data frame, header frame and the configuration frame.
Multiplexing and transitions: Transitions between the communication link and the data
processing equipment leads to delays that are caused at the instances when data is retrieved
or emitted by the communication link.
Communication link involved: The type of communication link and the physical distance
involved in transmitting the PMU output to the central processing unit can add to the delay.
Data concentrators: Data concentrators are primarily data collecting centers located at the
central processing unit and are responsible for collecting all the PMU data that is
transmitted over the communication link.
www.intechopen.com
140
Specification
Data Alignment
Streaming Channels
Continuous
Retention
32 Days
9. Conventional problems
The distance relays which are widely applied in the protection today and involve the
determination of impedance achieve operating times of the order of a period of the power
system frequency. A distance relay is designed to only operate for faults occurring between
the relay location and the selected reach point, and remains stable for all faults outside this
region or zone (Horowitz et al., 2009).
www.intechopen.com
141
The resistance of the fault arc takes the fault impedance outside the relays tripping
characteristic and, hence, it does not detect this condition. Alternatively, it is only picked up
either by zone 2 or zone 3 in which case tripping will be unacceptably delayed (Eissa, 2009).
The distance relays are based on standalone decision, while each relay operates
independently according to three different zone of operation, see Figure 7.
The mal-operation or fail-to trip of protection is determined as one of the origins to raise and
propagate major power system disturbances (Tang, et al., 2006). A vast majority of relay
mal-operations is unwanted trips and have been shown to propagate major disturbances.
Backup protections in fault clearance system have the task to operate only when the primary
protection fails to operate or when the primary protection is temporarily out of service. The
recent complexity and enlargement of power systems makes it difficult to coordinate
operation times and reaches among relays. In the areas of power system automation and
substation automation, there are two different trends: centralization and decentralization.
More and more dynamic functions are moving from local and regional control centers
toward central or national control centers. At the same time we also observe more
intelligence and decision power moving closer towards the actual power system
substations. Greater functional integration is being enclosed in substation hardware. In view
of global security of power systems, the action algorithms of conventional backup
protections possibly are not best choices because the operations of individual relays are
hardly coordinated each other. Therefore, the principle of the protection design needs
innovation to overcome the above problem. Modern protection devices have sufficient
computing and communications capabilities to allow the implementation of many novel
sophisticated protection principles. Therefore, a novel wide-area backup protection system
is reported in this paper.
This system is capable of acting as the substitution of conventional distributed backup
protections in substation. To ensure the fast responsibility of such a system to the emergent
events, the communication requirements are discussed as well. Conclusively, the proposed
system is designed by two ways. First, in substation, concentrate some conventional backup
protection functions to an intelligent processing system; second, concentrate the coordinated
and optimized processing and controlling arithmetic of all backup protection in a region
into a regional processing unit.
www.intechopen.com
142
The communication of data among them is carried via optic-fiber networks. The relay
decision is based on collected and shared data through communication network. The
suggested technique satisfies high degree of reliability and stability while it is based on
shared decision rather than stand alone decision. The suggested technique can see all the
power system area and can deal with the transmission lines as unit protection, see Figure 8.
The primary purpose of these systems is to improve disturbance monitoring and system
event analysis. These measurements have been sited to monitor large generating sites, major
transmission paths, and significant control points. Synchronized Phasor measurements
provide all significant state measurements including voltage magnitude, voltage phase
angle, and frequency.
www.intechopen.com
143
bus for each area. This can result in the minimum voltage value that indicates the nearest
area to the fault. In addition to that, the absolute differences of the positive sequence current
angles are calculated for all lines connected with the faulted area. These absolute angles are
compared to each other. The maximum absolute angle difference value is selected to
identify the faulted line. The above two keys of operation can be mathematically described
as follows:
Min {|V1|, |V2|,.. |Vm|, |Vn|}
(2)
where |Vn| is the positive sequence voltage magnitude measured by PMU and located at
area "1", "2", "3",,"m" , to "n". Figure 9 shows the Matlab simulink block diagram
responsible of the selection of the nearest area to the fault based on comparing positive
sequence voltage magnitudes. POSV1, POSV2... POSV5 are the input signals of positive
sequence voltage magnitudes collected from 5 areas on the network. The minimum voltage
magnitude is indicated by the Minimum block which identifies the value and/or position of
the smallest element in each column of the input, or tracks the minimum values in a
sequence of inputs over a period of time.
The Minimum block output is shown in Figure 10. The graph shows the o/p from the
Matlab/Simulink simulation, which is the minimum positive sequence voltage magnitude
during fault. Any decrease in the signal magnitude is indicated by the Detect Decrease block
which determines if the input signal is strictly less than its previous value or not, the status
can be recognize as:
The output is "1", when the input signal is less than its previous value.
The output is "0", when the input signal is greater than or equal to its previous value.
The threshold value of the input signal is detected by the Interval Test block which outputs
"1" if the input is between the values specified by the Lower limit and Upper limit
parameters. The block outputs "0" if the input is outside those values.
www.intechopen.com
144
(3)
where |mn| is the absolute difference of positive sequence current angle for a
transmission line connecting area "m" with area "n". This can be described by (4).
|mn| = |mn - nm|
(4)
Figure 11 shows the Matlab/Simulink block diagram responsible of the selection of the
faulted line from all lines connecting to the faulted areas; the absolute difference between
positive sequence current angles at line terminals for each line is given. The maximum
current angle difference is indicated by the Maximum block which identifies the value
and/or position of the largest element in each column of the input, or tracks the maximum
values in a sequence of inputs over a period of time.
Figure 12 shows the output from the Maximum block shown in Figure 11. The graph shows
the maximum absolute difference of positive sequence current angle during internal fault.
The threshold value of the input signals is detected by the Interval Test block. Figure 13
shows the maximum absolute difference of positive sequence current angle during external
fault. Discrete on/off delay timer block given in Figure 11 is used to ignore big changes in
angle difference which associated with change in current direction in any line due to
external faults.
12
21
13
31
23
32
35
53
24
42
45
54
Fig. 11. The Matlab/Simulink block diagram responsible of the selection of the faulted line.
www.intechopen.com
145
Part of the 500/220 kV Egyptian interconnected electrical network is used for the study; five
main buses that represent five different areas with 500 kV are selected to verify the
suggested technique. Figure 14 shows the selected five areas from the overall network. In
the single line diagram, each bus represents the selected area in the simulation that can
connect the 500 kV network with 220 kV network through three single phase 500/220 kV
power transformers. The system is simulated using the Matlab/Simulink with a sampling
frequency of 20 kHz for a system operating at a frequency of 50 Hz. By means of measuring
positive sequence magnitude of three phase to ground voltage and positive sequence
current angle difference between sending and receiving ends, we make a new criteria to deal
with faults (single, double and three phase to ground faults). This new criteria will detect
faults and select the nearest area to the fault. Also, the new criteria will distinguish between
internal and external faults in the interconnected lines.
Fig. 12. Maximum absolute difference of positive sequence current angle due to internal
fault.
Fig. 13. Maximum absolute difference of positive sequance current angle due to external
fault.
www.intechopen.com
146
Cairo 500
Area 2
Bassous
C.West
Area 3
Shoubra
Korimat
Motamadia
Maghagh
a
A.zaabal
Demo
Samalu
t
Area 5
Selected
W.Houf
Asuit
Area 4
Area 1
C.South
500 kV
Tebbin South
220 kV
Fig. 14. The selected five areas from the overall network.
www.intechopen.com
147
voltage signals measured from Kurimat bus bar is recorded and displayed in Figure 16. The
3-phase current signals for all transmission lines away from Kurimat are recorded and
displayed in Figure 17.
1
I a + Ib + Ic
3
(5)
The fault is classified as a ground fault if zero is greater than threshold value. Once the fault
has been classified, the specific fault type is determined by comparing all rate of change of
phase currents with an predetermined disturbance detection pickup, The fault typing
www.intechopen.com
148
software module is employed when the measured parameter exceeds a prescribed threshold
(e.g., when a measured correct exceeds an overcurrent pickup).
Fig. 17. Three phase current signals for all lines connected to Kurimat.
www.intechopen.com
149
Fig. 19. Positive sequence current angle absolute differences for all lines connected to the
faulted area.
Discrete Fourier transform block computes the fundamental value of the input phase
current signal over a running window of one cycle of the specified fundamental frequency
as shown in Figure 20. First and second outputs return respectively the magnitude and
phase degrees of the fundamental. The magnitude is taken as a percentage from its steady
state value. The rate of change of this percentage is compared with a threshold value. For
the first cycle of simulation, the outputs are held constant to the value specified by the
parameter "Initial input".
As shown in Figure 21, the input three-phase current is used to calculate zero sequence
components to classify the fault type. Then each phase current signal is taken as a
percentage from its steady state value. Then the rate of change of the percentage of phase
current magnitude is compared by a threshold value to identify the faulted phase.
www.intechopen.com
150
Fig. 22. Fault recorder at each terminal display that fault type is three phase fault.
www.intechopen.com
151
13. Conclusion
The chapter outlines a novel idea for fault detection and classification using Phasor
measurement units in a wide area system. The idea has successfully identified the faulted
line on a large power interconnected system. The idea descried in this paper represents a
new state-of-art in the field of interconnected grid protection and classification. The idea is
based on sharing data from many PMUs. The new idea also calssified the fault types for the
interconnected system. The idea used a center protection unit for collecting the data and
issued the tripping signal. The idea is implemented and investigated using the powerful
Matlab/Simulink package. Power system configuration, fault detection, fault calculation,
discrimination, and classification are achieved through the Matlab/Simulink program.
14. Acknowledgment
This chapter is written, revised and analyzed by the author. Some parts of the chapter are
cited from MSc dissertation done in Helwan University-Faculty of Engineering-Cairo-Egypt
by Eng. Mohamed Magdy. The MSc dissertation is supervised by Prof. Mohammed El
Shahat Masoud and the author of the chapter.
15. References
Phadke, A. (2002). Synchronized Phasor Measurements a historical over view. Virginia
Polytechnic Institute and American Electric Power Bhargava.0-7803-7525-4/02/IEEE
Marek Zima. (2002). Special Protection Schemes in Electric Power Systems. Literature survey,
(June 2002).
Thorp, J. S; Phadke A. G; Horowitz, S. W. & Begovic, M. M. (1988). Some Applications of
Phasor Measurements to Adaptive Protection. IEEE Transactions on Power Systems,
Vol. 3, No. 2, (May 1988).
Centeno, V; De La Ree, J; Phadke, A. G.; Mitchell, G; Murphy, J; Burnett, R; (1993). Adaptive
Out-of-Step Relaying Using Phasor Measurement Techniques. IEEE Computer
Applications in Power, (October 1993).
Guzman, A & Tziouvaras, D (2002). Local and Wide-Area Network Protection Systems
improve power system reliabili, Schweitzer Engineering Laboratories, E. O. ty. Inc.
Pullman, WA, USA, Ken E. Martin Bonneville Power Administration Vancouver, WA,
USA, Aviable from, www.naspi.org/resources/archive/prtt/waps_wprc04.pdf
Guzman, A; Mooney, J. B; Benmouyal, G; Fischer, N. (2002). Transmission Line Protection
System for Increasing Power System Requirements. 55th Annual Conference for
Protective Relay Engineers, College Station, Texas, (April 2002).
Gjerde, P. O & Mangelrod, R. (2001). Optimisation of Protection Performance During System
Disturbances. CIGRE 2001 SC 34 Colloquium, (Septemper 2001).
Larsson, M & Rehtanz, C. (2002). Predictive Frequency Stability Control Based on WideArea Phasor Measurements. Proc. 2002 IEEE Power Engineering Society Summer
Meeting, (2002).
Zima, M; Korba, M & Andersson, G. (2003). Power Systems Voltage Emergency Control
Approach Using Trajectory Sensitivities. 2003 IEEE Conference on Control
Application, CCA, Istanbul, (June 2003).
www.intechopen.com
152
Rehtanz C & Westermann, D. (2002). Wide Area Measurement and Control System for
Increasing Transmission Capacity in Deregulated Energy Markets. Proc. 2002 Power
Systems Computation Conference in Sevilla, (2002).
Rehtanz, C. (2001). Wide Area Protection System and Online Stability Assessment based on
Phasor Measurements. Bulk Power System Dynamics and Control - V, Onomichi
City, Japan, (Augest 2001).
Zhang, N & Kezunovic, M. Verifying the Protection System Operation Using An Advanced
Fault Analysis Tool Combined with the Event Tree Analysis. Northern American
Power Symposium, NAPS 2004 Moscow, Idaho, (August 2004).
Lin, Y. L; Liu, C. W. & Chen, C. S. (2004). A new PMU-based fault detection/location
technique for transmission lines with consideration of arcing fault discrimination
Part I: Theory and algorithms. IEEE Trans. Power Del., Vol. 19, No. 4, (October
2004), pp. 15871593.
Yu, C. S; Liu, C. W; Yu, S. L. & Jiang, J. A. (2002). A new PMU-based fault location algorithm
for series compensated lines. IEEE Transaction on Power Deivery, Jan. 2002, Vol. 17,
No. 1, pp. 3346.
Wang, et el. (2005). Design of a novel wide-area backup protection system, Proceedings of
IEEE/PES Transmission Distribution Conference Asia Pac. Dalian, China, (2005), pp. 1-6.
Yan Wang; Yan-Xia Zhang; Song-Xiao Xu; (2008). Wide-area protection against chain overload trip based on multi-agent technology, Interntional Conference on Machine
Learning and Cybernetics, pp. 1548 1552, Volume: 3, Digital Object Identifier:
10.1109/ICMLC.2008.4620652, 2008.
Xiaoyang Tong; Xiaoru Wang; Li Ding (2008). Study of information model for wide-area
backup protection agent in substation based on IEC61850, Third International
Conference on Electric Utility Deregulation and Restructuring and Power Technologies,
pp. 2212 2216, Digital Object Identifier: 10.1109/DRPT.2008.4523778
Yangguang Wang; Xianggen Yin; Dahai You; (2010). Agent-based wide area protection with
high fault tolerance, International Conference on the Modelling, Identification and
Control (ICMIC), (2010), pp. 739 744
Hui Sun; Qianjin Liu (2009). Research of the Structure and Working Mechanisms of WideArea Backup Protection Agent. 1st International Conference on Information Science
and Engineering (ICISE), (2009), Digital Object Identifier: 10.1109/ICISE.2009.926,
(2009), pp. 5037 5042.
Zhiyuan Duan; Zhang, C.; Hu, Z.; Sun, Y. (2009). Design of Robust Controller of
Interconnected Power System Considering Signals Transmission Delay.
International Workshop on Intelligent Systems and Applications, (2009). ISA 2009.
Digital Object Identifier: 10.1109/IWISA.2009.5072823, (2009), pp. 1 - 5
Zhiyuan Duan; Chengxue Zhang; Zhijian Hu; Yuanyuan Zhang (2009). Robust Control of
Interconnected Power System Based on WAMS Considering Signals Transmission
Delay, Power and Energy Engineering Conference, (2009). APPEEC 2009, Asia-Pacific,
Digital Object Identifier: 10.1109/APPEEC.2009.4918729, (2009), pp. 1 4
Seong-Jeong Rim; Seong-Il Lim; Seung-Jae Lee (2008). Multi-agent based reliability
enhancement
scheme
for
IEC61850
substation,
Transmission and Distribution Conference and Exposition, (2008), T&D. IEEE/PES,
Digital Object Identifier: 10.1109/TDC.2008.4517294, (2008), pp. 1 6
www.intechopen.com
153
Testa, S. & Chou, W. (2004). The distributed data center: front-end solutions, IT Professional
Conference, Vol. 6, No. 3, Digital Object Identifier: 10.1109/MITP.2004.24, (2004),
pp. 26 32
Begovic, M. (2004). Wide area protection and emergency control. Power Systems Conference
and
Exposition,
(2004).
IEEE
PES
Digital
Object
Identifier:
10.1109/PSCE.2004.1397488, (2004), pp. 1776 - 1777
Terzija, V.; Cai, D.; Valverde, G.; Regulski, P.; Vaccaro, A.; Osborne, M. & Fitch, J. (2010).
Flexible Wide Area Monitoring, Protection and Control applications in future
power networks Developments in Power System Protection (DPSP 2010), 10th IET
International Conference on Managing the Change, Digital Object Identifier:
10.1049/cp.2010.0361 (2010), pp. 1 5
Terzija, V.; Valverde, G.; Deyu Cai; Regulski, P.; Madani, V.; Fitch, J.; Skok, S.; Begovic, M.
M. & Phadke, A. (2011). Wide-Area Monitoring, Protection, and Control of Future
Electric Power Networks, Proceedings of the IEEE, Vol. 99, No. 1, Digital Object
Identifier: 10.1109/JPROC.2010.2060450, (2011), pp. 80 - 93
Moxley, R. & Wronski, M. (2007). Using time error differential measurement in protection
applications, Power Systems Conference: Advanced Metering, Protection, Control,
Communication, and Distributed Resources, 2007. PSC 2007 Digital Object Identifier:
10.1109/PSAMP.2007.4740918, (2007), pp. 278 - 283
Phadke, A. G. & Kasztenny, B. (2009). Synchronized Phasor and Frequency Measurement
Under Transient Conditions, IEEE Transactions on Power Delivery, Vol. 24, No. 1,
Digital Object Identifier: 10.1109/TPWRD.2008.2002665, (2009), pp. 89 - 95
Jetti, S. R. & Venayagamoorthy, G. K. (2006). Real-Time Implementation of a Dual Function
Neuron based Wide Area SVC Damping Controller, Industry Applications
Conference, (2006), 41st IAS Annual Meeting. Conference Record of the 2006 IEEE,
Vol. 2, Digital Object Identifier: 10.1109/IAS.2006.256598, (2006), pp. 672 - 678
Yi Hu & Novosel, D. (2006). Challenges in Implementing a Large-Scale PMU System Power
System Technology, International Conference on Power Con 2006. Digital Object
Identifier: 10.1109/ICPST.2006.321829, (2006), pp. 1 - 7
Wenxin Liu; Cartes, D. A. & Venayagamoorthy, G. K. (2006). Particle Swarm Optimization
based Defensive Islanding of Large Scale Power System, International Joint
Conference on Neural Networks, IJCNN, (2006), Digital Object Identifier:
10.1109/IJCNN.2006.246642
(2006), pp. 1719 - 1725
Xiupeng Guan; Yuanzhang Sun & Lin Cheng (2007). A load parameter identification method
based on wide area measurement, International Power Engineering Conference, 2007.
IPEC 2007, (2007), pp. 431 - 436
Zhang, G.; Lee, S.; Carroll, R.; Jian Zuo; Beard, L. & Yilu Liu (2010). Wide area power system
visualization using real-time synchrophasor measurements, Power and Energy
Society
General
Meeting,
2010
IEEE
Digital
Object
Identifier:
10.1109/PES.2010.5588188, (2010), pp. 1 - 7
Moraes, R.; Volskis, H. & Yi Hu (2008). Deploying a large-scale PMU system for the
Brazilian interconnected power system, Third International Conference on Electric
Utility Deregulation and Restructuring and Power Technologies, (2008), DRPT
2008, Digital Object Identifier: 10.1109/DRPT.2008.4523392, (2008), pp. 143 - 149
www.intechopen.com
154
Sybille, G. & Hoang Le-Huy (2000). Digital simulation of power systems and power
electronics using the MATLAB/Simulink Power System Blockset, IEEE Power
Engineering Society Winter Meeting, (2000), Vol. 4 Digital Object Identifier:
10.1109/PESW.2000.847358, (2000), pp. 2973- 2981
De La Ree, J.; Centeno, V.; Thorp, J.S. & Phadke, A. G. (2010). Synchronized Phasor
Measurement Applications in Power Systems, IEEE Transactions on Smart Grid, Vol.
1, No. 1, Digital Object Identifier: 10.1109/TSG.2010.2044815, (2010), pp. 20 - 27
Hall, I.; Beaumont, P.G.; Baber, G.P.; Shuto, I.; Saga, M.; Okuno, K. & Uo, H. (2003), New line
current differential relay using GPS synchronization, Power Tech Conference
Proceedings, 2003 IEEE Bologna, Vol. 3 Digital Object Identifier:
10.1109/PTC.2003.1304464, 2003
Naduvathuparambil, B; Valenti, M. C. & Feliachi, A. (2002). Communication delays in wide
area measurement systems, Lane Dept. of Comp. Sci. & Elect. Eng., West Virginia
University, Morgantown, WV, 2002. Avialble from
www.csee.wvu.edu/~mvalenti/documents/SSST_02.pdf
Klump R. & Wilson, R. E. (2005). Visualizing real-time security threats using hybrid
SCADA/PMU measurement displays, Proc. 38th Hawaii Int. Conf. System Sci., 2005,
p. 55c.
Bhargava, B. & Salazar, A. (2008). Use of Synchronized Phasor Measurement system for
monitoring power system stability and system dynamics in real-time, Power and
Energy Society General Meeting-Conversion and Delivery of Electrical Energy in
the 21st Century, 2008 IEEE Digital Object Identifier: 10.1109/PES.2008.4596963,
2008, pp. 1 - 8
Horowitz S. H. & Phake A. G. (2009). Power System Relaying, Taunton Somerset, U.K.
Research Studies Press
Eissa, M. M. (2009). New principle for transmission line protection using phase portrait
plane. IET Generation Transmission Distribution, (2009), Vol. 3, No. 1, pp. 4956
Tang J. & McLaren, P. G. (2006). A wide area differential backup protection scheme for
Shipboard application, IEEE Transaction on Power Delivery, (2006), Vol. 21, No. 3,
pp. 1121-1129
Eissa, M. M. (2008). Development and investigation of a new high-speed directional relay
using field data, IEEE Transaction on Power Delivery, (2008), Vol. 23, No.3, pp. 1302
1309.
Eissa, M. M. (2009). A new digital feed circuit protection using directional element, IEEE
Transaction on Power Delivery, (2009), Vol. 24, No. 2, pp. 531537
Eissa, M. M. (2005). Evaluation of a new current directional protection technique using field
data, IEEE Transaction on Power Delivery, (2005), Vol. 20, No. 2, pp. 566572
Protection of Interconnected Electrical Networks Using Phasor Synchronized Measuring
Technique, Ph.D. dissertation, Helwan University-Faculty of Engineering at
Helwan, Cairo, Egypt, (2008)
www.intechopen.com
ISBN 978-953-307-659-1
Hard cover, 204 pages
Publisher InTech
How to reference
In order to correctly reference this scholarly work, feel free to copy and paste the following:
Mohammed Eissa Moustafa and Mohammed El-Shahat Masoud (2011). A Novel Wide Area Protection
Classification Technique for Interconnected Power Grids Based on MATLAB Simulation, Scientific and
Engineering Applications Using MATLAB, Prof. Emilson Pereira Leite (Ed.), ISBN: 978-953-307-659-1, InTech,
Available from: http://www.intechopen.com/books/scientific-and-engineering-applications-using-matlab/anovel-wide-area-protection-classification-technique-for-interconnected-power-grids-based-on-matlab
InTech Europe
InTech China