Siemens MXL IQ Operation Installation Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 218
At a glance
Powered by AI
The document contains technical manuals for Siemens Cerberus Division fire alarm control panels. It provides information on installing, operating and maintaining the MXL/MXLV and MXL-IQ control panels.

There are three ways to navigate through the manual: using the left hand index column, using the green buttons above to get to the corresponding manual, and using the arrows in the menu bar.

There are two ways to change the page view: using the magnifying glass in the menu bar and using the three different page views in the menu bar.

Technical Manuals Online! - http://www.tech-man.

com

Cerberus Division
Table of Contents

Version 1.0

This CD-Rom contains


the information necessary to
install, operate and maintain
the Siemens, Cerberus Division
MXL/MXLV and MXL-IQ
Fire Protection Control Panels
Contents

MXL/MXLV Control Panel


P/N 315-092036CD-8

Personalize/
Printout Cover

MXL-IQ Control Panel


P/N 315-093624CD-9

Personalize/
Printout Cover

Navigation
There are three ways to navigate:
1) Use the left hand index column (which appears as you proceed)
2) Use the green buttons above to get to the corresponding manual
3) Use the arrows in the menu bar above
There are 2 ways to enlarge or reduce:
1) Use the magnifying glass in the menu bar above
2) Use the three different page views in the menu bar.

Cerberus Division

CERBERUS PYROTRONICS

MXL-IQ CONTROL PANEL


Operation, Installation, and Maintenance Manual

Siemens Building Technologies, Inc.


8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-093624CD-9
Technical Manuals Online! - http://www.tech-man.com

Siemens Building Technologies, Ltd.


50 East Pearce Street
Richmond Hill, Ontario L4B 1B7 CN

CAUTION
ALL WIRING MUST BE DONE AS DESCRIBED BELOW
TO OBTAIN SAFE AND PROPER SYSTEM OPERATION.
1. Earth ground the MXL-IQ enclosure properly; see the latest edition of the National
Electrical Code for approved methods. Conduit ground is NOT adequate.
2. Separate all wiring for initiating devices (i.e., detectors, manual stations, TRI
modules, etc.) from all other wiring in the MXL-IQ enclosure. To wire the System in compliance with UL 864, refer to the Installation and Power Limited
Wiring Instructions for the MSE-3L Enclosure, P/N 315-095445.
3. INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded
electrical box, including those in the MXL-IQ enclosure.
4. Connect shield cable drain wire ONLY inside the MXL-IQ enclosure.
5. No wiring used for any of the following can run outside the building:
an ALD loop
a RS-485 network
an NAC circuit used for audibles
a CZM-1B6 or CZM-4 initiating device loop
For additional wiring information, refer to this manual or call Siemens
Building Technologies, Inc. Technical Support Department at
1-800-248-7976.

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Description ______________________________ 1 - 1

Chapter 1

Introduction ___________________________________________________ 1 - 1
Software ______________________________________________________ 1 - 1
Minimum MXL-IQ Control Panel Configuration ________________________ 1 - 3

Components Of The Basic System __________________________________ 1 - 4


SMB-2 Main Board _____________________________________________ 1 - 4
MPS-6 Power Supply ___________________________________________ 1 - 5
MPS-12 Power Supply __________________________________________ 1 - 5
MKB-4 Keyboard/Annunciator Panel _______________________________ 1 - 5
PIM-1 Peripheral Interface Module _________________________________ 1 - 6
PIM-2 Peripheral Interface Module _________________________________ 1 - 6
PAL-1 _______________________________________________________ 1 - 6
TSW-2 Tamper Switch __________________________________________ 1 - 6
BP-61 Batteries ________________________________________________ 1 - 7
BTX Batteries _________________________________________________ 1 - 7

Optional Modules _______________________________________________ 1 - 7


MOM-2 Card Cage _____________________________________________ 1 - 8
MOM-4 Card Cage _____________________________________________ 1 - 8
CSM-4 Signal Module ___________________________________________ 1 - 8
CMI-300 Interface Module________________________________________ 1 - 9
CRM-4 Relay Module ___________________________________________ 1 - 9
CZM-4 Conventional Zone Module _________________________________ 1 - 9
ALD-2I Analog Loop Driver ______________________________________ 1 - 10
MOI-7 Voice and Annunciator Driver_______________________________ 1 - 10
MOD-16 Output Driver _________________________________________ 1 - 10
MID-16 Input Driver ____________________________________________ 1 - 11
NIM-1R Network Interface Module ________________________________ 1 - 11

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Intelligent/Analog Devices _______________________________________ 1 - 12


FP Intelligent Detector Series ____________________________________ 1 - 12
ICP Intelligent Control Point _____________________________________ 1 - 12
ICP-B6 Intelligent Control Point __________________________________ 1 - 12
ID Intelligent/Analog Detector Series ______________________________ 1 - 12
IL Intelligent/Analog Detector Series _______________________________ 1 - 13
LIM-1 Loop Isolator Module _____________________________________ 1 - 14
MSI Intelligent Manual Station Series ______________________________ 1 - 14
TRI Intelligent Interface Module Series _____________________________ 1 - 14
CZM-1B6 Remote Conventional Zone Module _______________________ 1 - 14

Conventional Devices ___________________________________________ 1 - 15


DI Ionization Detector Series ____________________________________ 1 - 15
DT-11 Thermal Detector ________________________________________ 1 - 15
PE Photoelectric Detector Series _________________________________ 1 - 15
PBA-1191 Linear Beam Smoke Detector ___________________________ 1 - 15

Chapter 2

Installation ______________________________ 2 - 1
General Guidelines For Installing The MXL-IQ ________________________ 2 - 1

Installation Instructions For The MXL-IQ Control Panel __________________ 2 - 2


Install the MSE-3L Enclosure _____________________________________ 2 - 2
Install The TSW-2 Tamper Switch _________________________________ 2 - 2
Pull All Field Wiring Into The Backbox ______________________________ 2 - 3
Install the SMB-2 _______________________________________________ 2 - 3
Install the MPS-6/12 ____________________________________________ 2 - 3
Install the MKB-4 Keyboard/Annunciator ____________________________ 2 - 4
Install the PIM-1, PIM-2, and PAL-1 ________________________________ 2 - 5
Install the MOM-2 or MOM-4 ______________________________________ 2 - 6
Install the MOI-7, MOD-16, and MID-16 ____________________________ 2 - 9
Install Field Wiring _____________________________________________ 2 - 10
Check Field Wiring ____________________________________________ 2 - 10

ii

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Start Up Procedure ____________________________________________ 2 - 10


System Function Checkout ______________________________________ 2 - 16

Operation _______________________________ 3 - 1

Chapter 3

Introduction ___________________________________________________ 3 - 1
Addresses ____________________________________________________ 3 - 1
System Modules _______________________________________________ 3 - 2
Remote System Modules ________________________________________ 3 - 2

Using The MKB-4 Keyboard/Annunciator Panel In Local Mode ____________ 3 - 3


The Display ___________________________________________________ 3 - 3
Internal Audible Alarm ___________________________________________ 3 - 4
Modes Of Operation ____________________________________________ 3 - 5

Alarm ________________________________________________________ 3 - 6
How The System Annunciates Fire Alarms __________________________ 3 - 6
Viewing the List of Alarms ________________________________________ 3 - 7
How to Block Acknowledge A Fire Alarm ____________________________ 3 - 7
How to Individually Acknowledge A Fire Alarm ________________________ 3 - 7
Silencing The System ___________________________________________ 3 - 7

Supervisories __________________________________________________ 3 - 8
How The System Annunciates Supervisories _________________________ 3 - 8
Viewing the List of Supervisories __________________________________ 3 - 8
How to Block Acknowledge a Supervisory ___________________________ 3 - 8
How to Individually Acknowledge a Supervisory _______________________ 3 - 9

Troubles ______________________________________________________ 3 - 9
How The System Annunciates Troubles _____________________________ 3 - 9
Viewing The List of Troubles ______________________________________ 3 - 9
How to Block Acknowledge a Trouble______________________________ 3 - 10
How to Individually Acknowledge a Trouble _________________________ 3 - 10

Technical Manuals Online! - http://www.tech-man.com

iii

Table of Contents

Security Conditions_____________________________________________ 3 - 10
How The System Annunciates Security Conditions ___________________ 3 - 10
Viewing the List of Security Conditions _____________________________ 3 - 11
How to Individually Acknowledge a Security Condition _________________ 3 - 11

Reset Procedures ______________________________________________ 3 - 11


Hard Reset __________________________________________________ 3 - 11
Soft Reset ___________________________________________________ 3 - 11

Using The MKB Keyboard/Annunciator Panel in Global Mode ____________ 3 - 12


Limitations/Restrictions _________________________________________ 3 - 12
Global MKB Display Format _____________________________________ 3 - 12
Global Keypad Operation _______________________________________ 3 - 13

Using The Menu _______________________________________________ 3 - 14


Operation of the Keys on the MXL-IQ Annunciator Panel ______________ 3 - 14
Numeric Keypad ______________________________________________ 3 - 14
The Command Keypad _________________________________________ 3 - 14
Overview of the Menus Structure _________________________________ 3 - 15
Beginning a Menu Session ______________________________________ 3 - 16
Introduction to the Acknowledge Menu _____________________________ 3 - 16
Introduction to the List Menu _____________________________________ 3 - 16
Introduction to the Control Menu __________________________________ 3 - 16
Introduction to the Test Menu ____________________________________ 3 - 16
Entering Your Password ________________________________________ 3 - 17
Entering a Module Number and Device Number _____________________ 3 - 17
Entering a Device Number with the Module Number __________________ 3 - 17

ACKNOWLEDGE Menu __________________________________________ 3 - 18


Entering the Acknowledge Menu _________________________________ 3 - 18
Acknowledge Alarm ___________________________________________ 3 - 18
Acknowledge Supervisory _______________________________________ 3 - 19
Acknowledge Trouble __________________________________________ 3 - 20
Acknowledge Security __________________________________________ 3 - 21

iv

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

LIST Menu ____________________________________________________ 3 - 22


Entering the List Menu _________________________________________ 3 - 22
List Status ___________________________________________________ 3 - 23
List Alarm ___________________________________________________ 3 - 23
List Supervisory _______________________________________________ 3 - 24
List Trouble __________________________________________________ 3 - 24
List Security Conditions _________________________________________ 3 - 25
List Sensitivity Settings _________________________________________ 3 - 26
List Voltages _________________________________________________ 3 - 26
List Temp ____________________________________________________ 3 - 28
List Module Type ______________________________________________ 3 - 28
List Device Type ______________________________________________ 3 - 29
List Message _________________________________________________ 3 - 29
List Software Version __________________________________________ 3 - 30
List Output States _____________________________________________ 3 - 31
List Device Usages ____________________________________________ 3 - 31
List Node Address _____________________________________________ 3 - 32
List ANALASER ______________________________________________ 3 - 32
List ANALASER SMOKE_LEV __________________________________ 3 - 32
List ANALASER FLOW_LEV ___________________________________ 3 - 33
List ANALASER TRIP_PTS ____________________________________ 3 - 33
List Percent/ft ________________________________________________ 3 - 34
List Percent/ft Senstvty _______________________________________ 3 - 35
List Percent/ft Pre-alarm ______________________________________ 3 - 35
List Percent/ft Analog _________________________________________ 3 - 35
List ASD_apps _______________________________________________ 3 - 35

CONTROL Menu _______________________________________________ 3 - 36


Entering the Control Menu ______________________________________ 3 - 37
Control Reset ________________________________________________ 3 - 37
Control Sensitivity _____________________________________________ 3 - 37
Control Arm/dis _______________________________________________ 3 - 38

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Control Output on/off ___________________________________________ 3 - 38


Control Loop Arm _____________________________________________ 3 - 39
Control Loop Disarm ___________________________________________ 3 - 39
Control Net Link Request _______________________________________ 3 - 40
Control ANALASER ___________________________________________ 3 - 40
Control Percent/ft _____________________________________________ 3 - 41
Control Percent/ft - Senstvty _____________________________________ 3 - 41
Control Percent/ft - Pre-alarm ____________________________________ 3 - 41
Control Change Apps __________________________________________ 3 - 42

TEST Menu ___________________________________________________ 3 - 42


Entering the Test Menu _________________________________________ 3 - 43
Test Set Time ________________________________________________ 3 - 43
Test Ground Fault _____________________________________________ 3 - 44
Test Power __________________________________________________ 3 - 44
Lamp Test ___________________________________________________ 3 - 45
Test Device LED ______________________________________________ 3 - 45
Test MOI Lamp Test ___________________________________________ 3 - 46
Test Network (X-Network, M-Network) _____________________________ 3 - 46
Test Override _________________________________________________ 3 - 46
Detector Cleaning _____________________________________________ 3 - 47
Event Log ___________________________________________________ 3 - 47
Test Pre-alarm ________________________________________________ 3 - 47
Test ASD Devices _____________________________________________ 3 - 48
Test Summarize ______________________________________________ 3 - 48
Test Manual Activate ___________________________________________ 3 - 49

Chapter 4

Testing and Troubleshooting _________________ 4 - 1


System Test ____________________________________________________ 4 - 1
Every Six Months ______________________________________________ 4 - 1
Every Year ____________________________________________________ 4 - 1
Fuse Replacement _____________________________________________ 4 - 1
Troubleshooting _______________________________________________ 4 - 2

vi

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Walktest Operating Instructions______________ 5 - 1

Chapter 5

Introduction ___________________________________________________ 5 - 1
System w/AUD ________________________________________________ 5 - 2
System SIL ___________________________________________________ 5 - 2
Loop w/AUD __________________________________________________ 5 - 2
Loop SIL _____________________________________________________ 5 - 2
Zone wAUD ___________________________________________________ 5 - 2
Zone SIL _____________________________________________________ 5 - 2
Cancel _______________________________________________________ 5 - 2
Extend _______________________________________________________ 5 - 2

Suggested Walktest Proedure _____________________________________ 5 - 2


Walktest the System ____________________________________________ 5 - 3
Walktest Ending Sequence _______________________________________ 5 - 4
Walktest Entire ALD Loop, MOI-7 (MID-16), or CZM-4 Module ___________ 5 - 4
Walktest Ending Sequence _______________________________________ 5 - 5
Walktest Individual CZM-1B6 or CZM-4 Zone ________________________ 5 - 5

History Log ______________________________ 6 - 1

Chapter 6

CSG-M History Options__________________________________________ 6 - 1

Logging Methods _______________________________________________ 6 - 2


Enabling the History Option in CSG-M ______________________________ 6 - 4
From the MKB Menu ____________________________________________ 6 - 4
Local History Log Query _________________________________________ 6 - 5
Query Selection ________________________________________________ 6 - 5
Query Filters __________________________________________________ 6 - 5
Navigating The History Display ____________________________________ 6 - 6
History Display Formats _________________________________________ 6 - 6
Device Event __________________________________________________ 6 - 6
Reset Event ___________________________________________________ 6 - 6
Set Time Event ________________________________________________ 6 - 7
Block Acknowledge Event ________________________________________ 6 - 7

Technical Manuals Online! - http://www.tech-man.com

vii

Table of Contents

Audible Silenced Event __________________________________________ 6 - 8


Override Event ________________________________________________ 6 - 8
Audible Unsilenced Event ________________________________________ 6 - 8
Password Event _______________________________________________ 6 - 8
Configuration Changed Event _____________________________________ 6 - 9
Manual Sensitivity Set Event ______________________________________ 6 - 9
Auto Sensitivity Set Event ________________________________________ 6 - 9
Logic Sensitivity Set Event ______________________________________ 6 - 10
History Print Formats At The MXL-IQ Panel _________________________ 6 - 10
MXL-IQ To CSG-M Download Formats _____________________________ 6 - 13
History Download Sequence _____________________________________ 6 - 14

Chapter 7

Connections and Ratings ___________________ 7 - 1


ALD-2I ________________________________________________________ 7 - 1
CMI-300 _______________________________________________________ 7 - 3
CRM-4 ________________________________________________________ 7 - 5
CSM-4 ________________________________________________________ 7 - 7
CZM-1B6 _____________________________________________________ 7 - 13
CZM-4 _______________________________________________________ 7 - 17
MOI-7, MOD-16, MID-16 __________________________________________ 7 - 19
MOM-2 ______________________________________________________ 7 - 25
MOM-4 ______________________________________________________ 7 - 27
NIM-1R ______________________________________________________ 7 - 29
Silent Knight Model 5128/5129 ____________________________________ 7 - 33
SMB-2 _______________________________________________________ 7 - 35

viii

Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Compatible Devices _____________________________________________ A - 1

Appendix

Device Analog Voltages __________________________________________ B - 1


MXL-IQ Battery Calculations _______________________________________ C - 1
MXL-IQ Power Supply Load Calculations _____________________________ D - 1
Alarm Verification _______________________________________________ E - 1
Envirolink _____________________________________________________ F - 1
Latching/Non-Latching Troubles ____________________________________ G - 1
Installing A Security Point ________________________________________ H - 1
Application Specific Detection (ASD) ________________________________I - 1
MXL-IQ Trouble Messages _________________________________________ J - 1
Power Limited Wiring ____________________________________________ K - 1
New Two Stage Alarm ___________________________________________ L - 1
Pre-alarm, Dual Criteria Logic Functions, and Percent Per Foot
Obscuration Features ___________________________________________ M - 1
MXL-IQ Spare Parts List __________________________________________ N - 1
New Features for MXL-IQ Revision 6.0 and Higher ______________________ O - 1

Technical Manuals Online! - http://www.tech-man.com

ix

Table of Contents

Technical Manuals Online! - http://www.tech-man.com

+D=FJAH

Description
The CERBERUS PYROTRONICS MXL-IQ
Control Panel is an advanced fire protection
and alarm control panel that provides superior
fire protection and multiplexed alarm reporting.
The MXL-IQ Control Panel can monitor up
to 4 analog loops, each containing up to 60
CERBERUS PYROTRONICS intelligent
devices.
The MXL-IQ Control Panel can control a
wide variety of System outputs, such as:
Conventional Form C relay contacts
Solid State outputs
Supervised outputs to control Alarm
Notification Appliances
Municipal Tie outputs
Leased Line outputs
The MXL-IQ Control Panel can process
logical decisions based on the status of
initiating devices. The System can respond
with customer-specified sequences of
output circuit operation.
The System continuously checks all
software and hardware for proper operation. It continuously checks all System
memory components, control panel electronic hardware, and the System program.
A hardwire watchdog circuit is provided to
ensure that System programs are functioning properly. If a problem develops with the
program or processor, the watchdog circuit
places the System into a trouble condition
and resets it.

To ensure reliable operation, the MXL-IQ


System is composed of independent
modules, each with its own microprocessor.
If the main panels central processing unit
stops, these modules, operating in default,
still annunciate any alarm or trouble
through common lines called Any Alarm
and Any Trouble. All of the modules
communicate with the MXL-IQ Panel
through a serial communications System.

INTRODUCTION

All modules are continuously supervised for


their presence and for proper operation.
Problems are shown on the display to aid in
servicing and troubleshooting (See Using
the Menu in the OPERATIONS section).
The MXL-IQ System is designed so that fire
alarm operation has first priority over all
other modes of operation. If the System
loses battery and commercial power, it
automatically goes through an initialization
routine when power returns.

The MXL-IQ software was written in a highlevel language for ease of maintenance.
The software incorporates a multitasking
operating system that allows the microprocessor to handle many tasks almost
simultaneously. This enables the MXL-IQ
System to handle communications to all
initiating and output option boards and to
the annunciator. This also enables the
MXL-IQ System to check that everything is
running.

SOFTWARE

1-1
Technical Manuals Online! - http://www.tech-man.com

Description

ALARM

POWER

AUDIBLE
SILENCE

PARTIAL
SYSTEM
DISABLE

SUPERVISORY

DISPLAY

TROUBLE

NEXT

HOLD

SECURITY

CERBERUS PYROTRONICS

MXL-IQ
Exterior View

Interior View

Figure 1
The MXL-IQ Control Panel

1-2

Technical Manuals Online! - http://www.tech-man.com

Description
When the MXL-IQ Control Panel receives
power, the System runs a start-up procedure that sets up all initial conditions. The
System then starts the operating system
and the initialization routines for all of the
tasks, most of which concern handling
System modules. When the display task is
finished initializing, it displays the default
time and date at power-up. Initialization of
other modules may take several seconds,
but this takes place in the background and
so does not affect System operation.

fied modules. Any modules or devices that


do not agree with the programmed data are
reported as troubles on the annunciator.

Minimum MXL-IQ Control Panel


Configuration To Meet NFPA 72 Local,
Municipal Tie, Remote Station,
Proprietary, And Central Station,
UL 1076, And NFPA 12A, 13, And 2001

Table 1 presents the minimum configuration necessary to meet NFPA 72 Local,


Municipal Tie, Remote Station, Proprietary,
and Central Station, UL 1076, and NFPA
12A, NFPA 13 and NFPA 2001.

The MXL-IQ System polls all network


addresses to see that all specified modules
are present and that there are no unspeci-

NFPA Minimum Quantity


Module

Description

72
Local

72
Auxiliary

72
Remote
Station

72
Proprietary

72 Central
Station(a)

UL
1076(b,d)

12A,
13, or 20 01

SMB-2(c)

MXL-IQ Main Unit

1*

1*

1*

MPS-6/12

Power Supply

MKB-4

Keyboard/Annunciator Panel

MOM-2

Optional Module Card Cage

MOM-4

Optional Module Card Cage

1 or 2**

1(h)

***

***

***

***

***

***

CSM-4

Signal Module

CZM-4

Conventional Zone Module

ALD-2I

Analog Loop Driver

***

***

***

***

***

****

***

CZM-1B6

Remote Conventional Zone Module

***

***

***

***

***

***

-----------

Batteries(e,f)

1(e)

1(e)

1(e)

1(e)

1(d)

1(e)

TSW-2

Tamper Switch

1(d)

PIM-1

Peripheral Interface Module

PIM-2

Peripheral Interface Module

PAL-1

Logging Printer

NET-7

Communication Interface

MOI-7

Voice and Annunciator Driver

MOD-16

Output Driver

MID-16

Input Module

CRM-4

Relay Module

CMI-30 0

MXL/CXL Interface

X = not required
*
**

Use Silent Knight listed models 5128/5129 and 5230.


One CSM-4 circuit must be configured for alarm
transmission. In addition, depending on the local authority
having jurisdiction, additional circuits may be required for
Supervisory or Trouble transmission.
*** Any one of these modules is sufficient as an initiating
device.
**** Only TRI-60/B6, TRI-60R/B6R, and TRI-60D/B6D can be
used as security devices.

NOTES:
a. See pages 7-33 to 7-34 for NFPA 72 Central Station.
b. Refer to the MXL-IQ Wiring Diagram, P/N 575-293638 at the end of the manual.
c. The SMB-2 must be programmed by CSG-M for all System configurations (See CSG-M
Programming Manual, P/N 315-090381).
d. UL 1076 requires a Model TSW-2 tamper switch and a PAL-1 printer.
e. The batteries available are: BP-61, BTX-1, and BTX-2. The BP-61 is a module consisting of four
6V, 15 AH batteries. The BTX-1 batteries are a pair of 12V, 31 AH batteries. The BTX-2 batteries
are a pair of 12V, 55 AH batteries. Actual battery size depends on System configuration.
f. See Appendix C for Battery Calculations.
g. The CMI-300 is not listed for UL 1076 application.
h. Refer to the CSM-4 Installation Instructions (P/N 315-090854) for programming.

TABLE 1
Minimum MXL-IQ Configuration to Meet NFPA 72 Local, Auxiliary, Remote Station, Proprietary, and Central
Station Connections, UL 1076, and NFPA 12A, NFPA 13, and NFPA 2001
Technical Manuals Online! - http://www.tech-man.com

1-3

Description

Components Of The Basic


System
The basic MXL-IQ Control Panel consists
of the following components:
SMB-2 Main Board
MPS-6 or MPS-12 Power Supply
MKB-4 Keyboard/Annunciator
PAL-1 Logging Printer
(NFPA Proprietary and UL 1076 configurations)
PIM-1 Peripheral Interface Module
(NFPA Proprietary and UL 1076 configurations)
PIM-2 Peripheral Interface Module
(NFPA Proprietary and UL 1076 configurations)
MSE-3L Enclosure
TSW-2 Tamper Switch
(UL 1076 configuration only)
BP-61, BTX-1, or BTX-2 Batteries
P1

BATTERY

F2
20A

P14

MPS-6

CB1
NAC1
CB2
NAC2

MPS-12

P2
BATTERY

F3
F4
MOM-4
15 AMP

P3
POWER TO MOM-4
2 AMP MAX.

F1
MPS-6
8 AMP
P8

NAC 2

P13

NAC 1

16-bit central processing unit (CPU)


NOT
USED

System read-only memories (EPROMs)


System random-access memory (RAM)
FLASH memory for CSG-M

3
2
1

Watchdog circuitry
Network interface circuitry

DO NOT USE

MNET

TB1
S7
S4
1

D2300CP

PROGRAMMER
P4
PRINTER

P6

1
P5

I
C
1
1
4

I
C
1
1
3

I
C
1
1
2

I
C
1
1
1

I
C
1
1
0

P15

P10

TO ANN-1

GND FAULT
DISCONNECT

12A TO MOM-4

6
4

LOOP 1

7
5

TB2

10
8

4
3

11
9

SMB-2

LOOP 2

CZM-1B6
POWER

TB3

The SMB-2 Main Board contains:

12

4
3

SMB-2 Main Board

CZM-1B6 POWER
2 AMP

TRBL

4
OFF
1

ON
P17

ALR

24V regulator

2
1

MOM-4

Battery charger

AC transfer relay
CZM-1B6 auxiliary power

Figure 2
SMB-2 Main Board

24 VDC unregulated supply


Two analog loops (initiating/control)
Two notification appliance circuits
(audible circuits)
Two dry-contact relays (Form C)

1-4

Technical Manuals Online! - http://www.tech-man.com

Description

MPS-6 Power Supply


The MPS-6 is a supervised power supply
that converts 120 VAC, 60 Hz to unregulated 24 VDC at 6A.

MPS-12 Power Supply


The MPS-12 is a high current power supply
that provides the MXL-IQ System with
primary 24 VDC power. It is rated at 12
amps and is unfiltered and unregulated.
The MPS-12 supplies the SMB-2 with the
power required for normal operation. The
module incorporates a 5 amp resettable circuit
breaker on the primary input, a 15 amp fuse
on the 24V output, and a built-in AC line filter
for surge and noise suppression.

Figure 3A
MPS-6 Power Supply

Figure 3B
MPS-12 Power Supply

MKB-4 Keyboard/Annunciator Panel


The MKB-4 Annunciator communicates with
the SMB-2 Main Control Board through the
System network link. This module provides
the MXL-IQ with its primary control and
annunciation.
The MKB-4 module has an 80-character,
backlit LCD alphanumeric display that
continuously updates information about the
System status and user-defined device
messages. If there are multiple alarms,
and/or troubles, including supervisories and
security conditions, the MKB-4 displays the
highest priority event that occurred. The
user can see additional alarm and trouble
data by pressing the NEXT key. Press the
HOLD key at any time to stop the display
from scrolling.
The Control Panel contains the following
indicators:

Figure 4
MKB-4 Keyboard
The MKB-4 has switches for the following functions:

Alarm

Acknowledging fire alarms (ALARM ACK)

Power

Silencing audibles (AUD SIL)

Audible Silence

Acknowledging supervisories (SUPV ACK)

Partial System Disable

Acknowledging System troubles (TRBL ACK)

Supervisory

Acknowledging security conditions (SEC ACK)

Trouble

Resetting the Control Panel (RESET)

Security

Technical Manuals Online! - http://www.tech-man.com

In addition the module has display keys (NEXT and HOLD), a numerical keypad, PRINT, HELP, and CLEAR keys, and user-configurable
function keys.

1-5

Description

PIM-1 Peripheral Interface Module


The PIM-1 module is an interface for an
MXL-IQ System to remote peripheral
devices such as printers. It connects an
RS-232C device to an MXL-IQ System
without the peripheral device's protective
ground causing a ground fault. The interface operates at up to 9600 baud without
losing any characters.

PIM-2 Peripheral Interface Module


Figure 5
PIM-1 Peripheral Interface Module

The PIM-2 module is an interface that


allows the connection of UL listed EDP
Centronics parallel printers to the MXL-IQ
System. It converts the RS-232C (serial)
printer output to a Centronics parallel
interface. When used with the PAL-1, the
PIM-2 provides a supervised parallel printer
(NFPA 72 Proprietary or UL 1076) for the
MXL-IQ System. However, this configuration is not supervised for data integrity.

PAL-1
The PAL-1 Logging Printer provides a
paper record of the activity of the MXL-IQ
System.

Figure 6
PAL-1 Parallel Printer

TSW-2 Tamper Switch


The TSW-2 Tamper Switch is a 3-position
switch that monitors the opening of the
MXL-IQ enclosure and reports a security
alarm. Closing the door automatically
returns the switch to its normal operating
position. The switch can be pulled out to
indicate a closed position for maintenance
purposes.

Figure 7
TSW-2 Tamper Switch

1-6

Technical Manuals Online! - http://www.tech-man.com

Description

BP-61 Batteries
The BP-61 is a module consisting of four 6V,
15 AH batteries. The BP-61 is recommended
for the NFPA 72 Local and Proprietary, and
the UL 1076 Systems. Actual battery size
depends on System configuration. See
Appendix C for battery calculations.

Figure 8
BP-61 Batteries

BTX Batteries
The BTX-1 batteries are a pair of 12V, 31
AH batteries. The BTX-2 batteries are a
pair of 12V, 55 AH batteries. Actual battery
size depends on System configuration. See
Appendix C for battery calculations.

Figure 9
BTX Batteries

The following modules are available as


options to the MXL-IQ Control Panel:
MOM-2 Card Cage
MOM-4 Card Cage
CSM-4 Signal Module

ALD-2I Analog Loop Driver


MOI-7 Voice and Annunciator Driver*

OPTIONAL
MODULES

MOD-16 Output Driver*


MID-16 Input Module*
NIM-1R Network Interface Module

CMI-300 Interface Module


CRM-4 Relay Module
CZM-4 Conventional Zone Module

Technical Manuals Online! - http://www.tech-man.com

* This module does not mount in the MSE-3L


enclosure.

1-7

Description

MOM-2 Card Cage


The MOM-2 Card Cage contains 2 slots for
optional module cards; it can handle 2 halfwidth cards or 1 full-width card. The MOM-2
provides 2 power-connector receptacles and
2 data-connector receptacles. A 24 VDC
cable that provides the main power used by
the optional modules, and an 8-wire ribbon
cable for connection of 5 VDC and data, are
provided with the MOM-2 installation kit.

Figure 10
MOM-2 Card Cage

MOM-4 Card Cage


The MOM-4 Card Cage contains 4 slots for
optional module cards; it can handle 4 halfwidth cards or 2 full-width cards. The MOM-4
provides 2 power-connector receptacles
and 2 data-connector receptacles. A 24 VDC
cable that provides the main power used by
the optional modules, and an 8-wire ribbon
cable for connection of 5 VDC and data, are
provided with the MOM-4 installation kit.

Figure 11
MOM-4 Card Cage

CSM-4 Signal Module


The CSM-4 Signal module controls 2
supervised notification appliance circuits.
Each circuit is capable of either Style Z
(Class A) or Style Y (Class B) operation.
Each circuit can be individually configured
for notification appliances, municipal tie,
leased line, or releasing service per NFPA
12A, NFPA 13, and NFPA 2001.

S1

S3

G1

S2

G2

S4

Figure 12
CSM-4 Signal Module

1-8

Technical Manuals Online! - http://www.tech-man.com

Description

CMI-300 Interface Module


The CMI-300 provides modem communications between an MXL-IQ System and a CXL
System. The CMI-300 module is located on
the MOM-2/4 board in the MXL-IQ enclosure. The CMI-300 plugs into a half slot in
the MOM-2/4. It translates signals from the
MXL-IQ communication lines of the SMB-2
to CXL modem signals. This signal is then
transmitted along suitable cable to the CXM-1
module in the CXL enclosure.

Figure 13
CMI-300 Interface Module

CRM-4 Relay Module


The CRM-4 Relay module is an output
control module that contains 4 relay outputs. Form C contacts are rated at 2A, 30
VDC/120 VAC resistive.
The CRM-4 has 4 LEDs. Two of the LEDs
are user programmable.

Figure 14
CRM-4 Relay Module

CZM-4 Conventional Zone Module


The CZM-4 Conventional Zone module
provides four initiating device circuits
capable of Style D (Class A) or Style B
(Class B) operation. Each zone has its own
address. You can use CSG-M to write a
custom message for each zone
(See CSGM Programming Manual,
P/N 315-090381).

Figure 15
CZM-4 Conventional Zone Module

Technical Manuals Online! - http://www.tech-man.com

1-9

Description

ALD-2I Analog Loop Driver


The ALD-2I Analog Loop Driver provides two
initiating device circuits capable of Class A
or Class B operation for monitoring analog
devices. Each loop is capable of monitoring
up to 60 analog devices. Each device has
its own address. You can use CSG-M to
write a custom message for each device
(See CSG-M Programming Manual, P/N
315-090381).

Figure 16
ALD-2I Analog Loop Driver

MOI-7 Voice and Annunciator Driver


The MOI-7 module is an MXL-IQ network
module that connects to a graphic annunciator using MOD-16s or MID-16s.

The MOI-7 has two LEDs to indicate the


status of the MXL-IQ network interface:

S1

the TRANSMIT LED blinks when the


MXL-IQ/MOI-7 communication is
working
the TROUBLE LED goes to steady
when MOI cannot communicate

Figure 17
MOI-7 Voice and Annunciator Driver

MOD-16 Output Driver


The MOD-16 Output Driver module is an
annunciator driver controlled by the MOI-7
module. Up to 8 MOD-16s can be used with
an MOI-7. Each MOD-16 can activate up to
16 outputs for a total of 128 outputs.

Figure 18
MOD-16 Output Driver

1-10

Technical Manuals Online! - http://www.tech-man.com

Description

MID-16 Input Driver


The MID-16 module provides 16 general
purpose inputs for user-defined operations
for the MXL-IQ.
The MID-16 is controlled by the MOI-7
module. Up to 8 MID-16s can be used with
an MOI-7. The function of each individual
input is defined by the use assigned to it in
CSG-M.

Figure 19
MID-16 Input Driver

NIM-1R Network Interface Module


The NIM-1R provides a communication path
for the following uses:
as an MXL-IQ networking interface
as a connection to Foreign Systems
as a connection to AnaLASER detectors
When used as a networking interface the
NIM-1R supports the connection of up to 63
MXL-IQ Systems. This network also supports
a Network Command Center (NCC) that
monitors all the MXL-IQs in the networked
group.
Output logic between MXL-IQ panels is made
using CSG-M programming. CSG-M versions
6.01 and higher include options for networked
MXL-IQ systems. Each MXL-IQ System is
assigned a panel number. This panel
number allows interactive programming
between panels using CSG-M.
The NIM-1R supports Style 4/7 connection.
In the event of an NIM-1R communication
failure, each MXL-IQ System continues to
operate as a stand-alone panel.

Figure 20
NIM-1R Network Interface Module

The NIM-1R can also be configured as an


RS-232 or RS-485 two-wire interface to
foreign systems. This operation is called
FSI (Foreign System Interface). The FSI
responds to a protocol and gathers information about the MXL-IQ status. The interface
supports both single MXL-IQ Systems and
networked systems. Typical use of this
interface is between the MXL-IQ and
building management systems.

Technical Manuals Online! - http://www.tech-man.com

1-11

Description
The intelligent/analog devices described
below are available for use with the MXL-IQ
Control Panel (SMB-2).
The UL identifiers for compatibility are the
same as the model names specified below.

INTELLIGENT/
ANALOG DEVICES

FP-11 Intelligent/Analog Photoelectric


Detector
The FP-11 is an intelligent/analog photoelectric detector that can be used as an
area or duct detector [FP-11(d)]. It uses
either a DB-11 low profile mounting base or
DB-3S mounting base with the DB-ADPT
adapter, a DB-X11RS mounting base with
relay or DB-X3RS mounting base with relay
with the DB-ADPT adapter, an ADBI-60
audible base with the DB-ADPT adapter, or
an AD-11P or AD-11XPR air duct housing.
The FP-11 requires MXL-IQ Rev. 6.0 or
higher firmware.

FPT-11 Intelligent Thermal Detector


The FPT-11 is an intelligent/analog ratecompensated/fixed-temperature type
thermal and photoelectric detector. It can
only be used as an area detector. It uses
either a DB-11 low profile mounting base or
DB-3S mounting base with the DB-ADPT
adapter, a DB-X11RS mounting base with
relay or DB-X3RS mounting base with relay
with the DB-ADPT adapter, or an ADBI-60
audible base with the DB-ADPT adapter.
The FPT-11 requires MXL-IQ Rev. 6.0 or
higher firmware.

ICP Intelligent Control Point


The ICP is an intelligent control point that
can be used as an independent, remotely
located notification appliance circuit (NAC).
It communicates through the analog loop of
the MXL-IQ System.

ICP-B6 Intelligent Control Point


The ICP-B6 is an intelligent control point
that can be used as an independent,
remotely located notification appliance
circuit (NAC). It communicates through the
analog loop of the MXL-IQ System.

ID-60P Intelligent/Analog
Photoelectric Detector
The ID-60P is an intelligent/analog photoelectric detector that can be used as an area or

1-12

Technical Manuals Online! - http://www.tech-man.com

duct detector [ID-6OP(d)]. It uses either a


DB-3S low profile mounting base, a DB-X3RS
mounting base with relay, an AD-3P duct
housing, or an ADBI-60 audible base.

ID-60PT Intelligent/Analog Photoelectric Detector with Heat Sensor


The ID-60PT is an intelligent/analog ratecompensated/fixed-temperature type
thermal and photoelectric detector. It can
only be used as an area detector. It uses
either a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, or an
ADBI-60 audible base.

ID-60I Intelligent/Analog Ionization


Detector
The ID-60I is an intelligent/analog ionization
detector for use in open areas at altitudes
of 0 to 4000 feet. It uses either a DB-3S low
profile mounting base, a DB-X3RS mounting base with relay, or an ADBI-60 audible
base.

ID-60IH Intelligent/Analog Ionization


High Altitude Detector
The ID-60IH is an intelligent/analog ionization detector for use in open areas at
altitudes of 3000 to 8000 feet. It uses either
a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, or an
ADBI-60 audible base.

ID-60IA Intelligent/Analog Ionization


High Air-Velocity Detector
The ID-60IA is an intelligent/analog ionization high air-velocity detector for use in
open areas, computer facilities, and air
ducts at altitudes of 0 to 4000 feet. It uses
either a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, or an
ADBI-60 audible base.

ID-60IAH Intelligent/Analog Ionization


High Air-Velocity, High Altitude
Detector
The ID-60IAH is an intelligent/analog
ionization high air-velocity, high altitude
detector for use in open areas, computer
facilities, and air ducts at altitudes of 3000 to
8000 feet. It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.

Description

ID-60IB Intelligent/Analog Ionization


Air-Duct Detector

ILI-1B Intelligent/Analog Ionization AirDuct Detector

The ID-60IB is an intelligent/analog ionization detector for use in air duct applications
at altitudes of 0 to 4000 feet. It uses either
the AD-3I housing or the AD-3XRI housing.

The ILI-1B is an intelligent/analog ionization


detector for use in air duct applications at
altitudes of 0 to 4000 feet. It uses either the
AD-3I housing or the AD-3XRI housing.

ID-60IBH Intelligent/Analog Ionization


Air-Duct High Altitude Detector

ILI-1BH Intelligent/Analog Ionization


Air-Duct High Altitude Detector

The ID-60IBH is an intelligent/analog


ionization detector for use in air duct
applications at altitudes of 3000 to 8000
feet. It uses either the AD-3I housing or the
AD-3XRI housing.

The ILI-1BH is an intelligent/analog ionization detector for use in air duct applications
at altitudes of 3000 to 8000 feet. It uses
either the AD-3I housing or the AD-3XRI
housing.

ILI-1 Intelligent/Analog Ionization


Detector

ILP-1 Intelligent/Analog Photoelectric


Detector

The ILI-1 is an intelligent/analog ionization


detector for use in open areas at altitudes
of 0 to 4000 feet. It uses either a DB-3S low
profile mounting base, a DB-X3RS mounting base with relay, or an ADBI-60 audible
base.

The ILP-1 is an intelligent/analog photoelectric detector that can be used as an


area or duct detector [ILP-1(d)]. It uses either
a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, an
AD-3ILP or AD-3XRILP duct housing, or an
ADBI-60 audible base.

ILI-1H Intelligent/Analog Ionization


High Altitude Detector
The ILI-1H is an intelligent/analog ionization
detector for use in open areas at altitudes
of 3000 to 8000 feet. It uses either a DB-3S
low profile mounting base, a DB-X3RS
mounting base with relay, or an ADBI-60
audible base.

ILI-1A Intelligent/Analog Ionization


High Air-Velocity Detector
The ILI-1A is an intelligent/analog ionization
high air-velocity detector for use in open
areas, computer facilities, and air ducts at
altitudes of 0 to 4000 feet. It uses either a
DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, or an
ADBI-60 audible base.

ILI-1AH Intelligent/Analog Ionization


High Air-Velocity, High Altitude
Detector
The ILI-1AH is an intelligent/analog ionization high air-velocity, high altitude detector
for use in open areas, computer facilities,
and air ducts at altitudes of 3000 to 8000
feet. It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.

Technical Manuals Online! - http://www.tech-man.com

ILPT-1 Intelligent/Analog Photoelectric


Detector with Heat Sensor
The ILPT-1 is an intelligent/analog ratecompensated/fixed-temperature type
thermal and photoelectric detector. It can
only be used as an area detector. It uses
either a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, or an
ADBI-60 audible base.

ILP-2 Intelligent/Analog Photoelectric


Detector
The ILP-2 is an intelligent/analog photoelectric detector that can be used as an
area or duct detector [ILP-2(d)]. It uses
either a DB-3S low profile mounting base, a
DB-X3RS mounting base with relay, an
AD-3ILP or AD-3XRILP duct housing, or an
ADBI-60 audible base. The ILP-2 requires
MXL-IQ Rev. 3.0 or higher firmware.

ILT-1 Intelligent Thermal Detector


The ILT-1 is an intelligent rate-compensated/fixed-temperature type thermal
detector. It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.

1-13

Description

LIM-1 Loop Isolator Module


The LIM-1 is a loop isolator module that
isolates short circuits on MXL-IQ analog
loops. The LIM-1 operates in both Class A
and Class B circuits.

MSI-10/20 Intelligent Manual Station


The MSI-10/20 is an intelligent manual
station designed to interface with an analog
loop. The MSI can be flush mounted or
surface mounted using the SB-5R mounting
box.

MSI-10B/20B Intelligent Manual Station


The MSI-10B/20B is an intelligent manual
station designed to interface with an analog
loop. The MSI-10B/20B can be flush
mounted or surface mounted using the
SB-5R mounting box.

MSI-B6F Intelligent Manual Station


The MSI-B6F is an intelligent manual station
designed to interface with an analog loop.
The MSI-B6F is a single-action station;
when used with the MS-FD adapter, the
MSI-B6F is a double-action station. The
MSI-B6F can be flush mounted or surface
mounted using the MS-FB backbox.

MSI-MB6 Intelligent Manual Station


The MSI-MB6 is an intelligent manual
station designed to interface with an analog
loop. The MSI-MB6 is a single-action
station; when used with the MS-DA plate,
the MSI-MB6 is a double-action station.
The MSI-MB6 can be flush mounted or
surface mounted using the MS-SB
backbox.

MS-MI Intelligent Manual Station


The MS-MI is an intelligent manual station
designed to interface with an analog loop.
The MS-MI is a single-action station; when
used with the MS-DA plate, the MS-MI is a
double-action station. The MS-MI can be
flush mounted or surface mounted using
the MS-SB backbox.

1-14

Technical Manuals Online! - http://www.tech-man.com

TRI-60, TRI-60R, and TRI-60D Intelligent


Interface Modules
The TRI-60 series modules are intelligent
interface modules that interface direct
shorting contact devices with the analog
loops. The TRI-60 is a single-input module;
the TRI-60R is a single-input module with
an independently controllable Form C relay;
the TRI-60D is a dual-input module.

TRI-B6, TRI-B6R, and TRI-B6D


Intelligent Interface Modules
The TRI-B6 series modules are intelligent
interface modules that interface direct
shorting contact devices with the analog
loops. The TRI-B6 is a single-input module;
the TRI-B6R is a single-input module with
an independently controllable Form C relay;
the TRI-B6D is a dual-input module.

TRI-B6M Addressable Interface Module


The TRI-B6M addressable interface module
interfaces direct shorting contact devices
with the analog loops. The TRI-B6M can
monitor a normally open or closed dry
contact and it can report the status of the
contact

TRI-S, TRI-R, and TRI-D Intelligent


Interface Modules
The TRI-S/R/D series modules are intelligent interface modules that interface direct
shorting contact devices with the analog
loops. The TRI-S is a single-input module;
the TRI-R is a single-input module with an
independently controllable Form C relay;
the TRI-D is a dual-input module.

CZM-1B6 Remote Conventional Zone


Module
The CZM-1B6 Remote Conventional Zone
Module supports one zone of non-addressable initiating devices in either Style D
(Class A) or Style B (Class B) configuration,
for a maximum of 15 compatible 2-wire
smoke detectors and an unlimited number
of shorting devices.

Description
The conventional devices described below
are available for use with the MXL-IQ
Control Panel.
The UL identifiers for compatibility are the
same as the model numbers.

DI-3 Ionization Detector


The DI-3 is an ionization detector for use in
open areas at altitudes of 0 to 4000 feet. It
uses the DB-3S low profile surface mounting base.

DI-3H Ionization High Altitude Detector


The DI-3H is an ionization detector for use
in open areas at altitudes of 3000 to 8000
feet. It uses the DB-3S low profile surface
mounting base.

DI-A3 Ionization High Air-Velocity


Detector
The DI-A3 is an ionization high air velocity
detector for use in open areas, computer
facilities, and air ducts at altitudes of 0 to
4000 feet and at air velocities of 0 to 1200
feet per minute. It uses the DB-3S low
profile surface mounting base.

DI-A3H Ionization High Air-Velocity,


High Altitude Detector
The DI-A3H is an ionization high air
velocity, high altitude detector for use in air
ducts only at altitudes of 3000 to 8000 feet
and at air velocities of 300 to 1200 feet per
minute. It uses the DB-3S low profile
surface mounting base.

DI-B3 Ionization Air Duct Detector


The DI-B3 is an ionization detector for use
only in air ducts at altitudes of 0 to 4000
feet. It must be used with a Series 3 air
duct housing (AD-3I or AD-3RI).

DI-B3H Ionization Air Duct High


Altitude Detector
The DI-B3H is an ionization detector for use
only in air ducts at altitudes of 3000 to 8000
feet. It must be used with a Series 3 air
duct housing (AD-3I or AD-3RI).

DT-11 Thermal Detector


The DT-11 is a thermal detector for use in
open areas. It uses the DB-11 low profile
surface mounting base or the DB-3S
mounting base with the DB-ADPT adapter.

PE-3 Photoelectric Detector


The PE-3 is a photoelectric detector that
responds to a wide range of both flaming
and smoldering fire conditions. It uses
either the DB-3S low profile surface mounting base or the AD-3ILP or AD-3XRILP air
duct housing.

CONVENTIONAL
DEVICES

PE-3T Photoelectric Detector with Heat


Sensor
The PE-3T is a photoelectric detector with
heat sensor that responds to a wide range
of both flaming and smoldering fire conditions. It uses the DB-3S low profile surface
mounting base.

PE-11 Photoelectric Detector


The PE-11 is a photoelectric detector that
responds to a wide range of both flaming
and smoldering fire conditions. It uses the
DB-11 low profile surface mounting base,
the DB-3S mounting base with the
DB-ADPT adapter, or the AD-11P/11PR
air duct housing.

PE-11T Photoelectric Detector with


Heat Sensor
The PE-11T is a photoelectric detector with
heat sensor that responds to a wide range
of both flaming and smoldering fire conditions. It uses the DB-11 low profile surface
mounting base or the DB-3S mounting base
with the DB-ADPT adapter.

PBA-1191 Linear Beam Smoke Detector


The PBA-1191 can detect light or dark
smoke buildup at distances between the
transmitter (X) and receiver (R) of 17 feet to
280 feet. The PBA-1191 can be used in a
variety of areas, including large, narrow, or
high rooms, and rooms with high air
turbulence. The PBA-1191 requires the
PBB-1191 base.
NOTE: Only one PBA-1191, and no
additional devices, can be connected to a
CZM-4 initiating zone.

Technical Manuals Online! - http://www.tech-man.com

1-15

Description

1-16

Technical Manuals Online! - http://www.tech-man.com

+D=FJAH

Installation
Remove all system power
before installation, first
battery and then AC.

General Guidelines For Installing The


MXL-IQ

This section provides general installation


instructions for mounting, wiring, and
checkout of the CERBERUS PYROTRONICSTM
MXL-IQ Control System.

NOTE:

Read this section before installing the


equipment to ensure proper installation. If
you are not familiar with the MXL-IQ, also
read the first section of the manual. Be sure
to ask Siemens Building Technologies, Inc.
Technical Support or an authorized Representative if you have any questions.
Install and use the MXL-IQ System in
accordance with the appropriate Local,
NFPA, and NEC Code requirements.

INTRODUCTION

Always remove power (battery and AC)


and wait at least 10 seconds to allow the
supply voltages to decay before installing or
removing any module, cable, or wiring.
If available, use a printer during
the installation procedure as a
debugging tool.

Follow Steps 1 through 13 for installation.


Each step is thoroughly explained in the
following pages.
1. Install the enclosure (page 2-2).
2. Install the TSW-2 Tamper Switch
where required (page 2-2).
3. Pull the field wiring into the backbox
and dress it to approximately where it
will go (page 2-3).
4. Install the SMB-2 (page 2-3).
5. Install the MPS-6 (page 2-3).
6. Install the MKB-4 (page 2-4).

WARNING!
Refer to the last page of the
manual for a Warning Note
required by the FCC for all
commercial Class A computing
equipment producing a clock
frequency of 10K Hz or greater.

7. Install the PIM-1, PIM-2, and PAL-1 (If


applicable) (page 2-5).
8. Install the MOM-2 or MOM-4 card
(page 2-6).
9. Install the MOI-7, MOD-16, and MID-16
(If applicable) (page 2-9).
10. Install Field Wiring (page 2-10).
11. Check Field Wiring (page 2-10).
12. Start-up Procedure (page 2-10).
13. System Function Checkout (page 2-16).

Technical Manuals Online! - http://www.tech-man.com

2-1

Installation

1. Install the MSE-3L Enclosure


The MSE-3L is the enclosure for the MXL-IQ.
Consider the following when mounting the
backbox:

INSTALLATION
INSTRUCTIONS
FOR THE MXL-IQ
CONTROL PANEL

Mounting height for visual and manual


access to the MKB-4 Keyboard/annunciator
Weight and size of enclosure
Local Mounting codes
Fasten the backbox securely to a clean,
dry, shock-free, and vibration-free surface.
Position the backbox clear of obstructions
so that the door opens freely and so that

the indicators and controls are easily


accessible.
NOTE: When the backbox is mounted
semi-flush using the MET-3L kit, be sure
that the position of the backbox permits the
door to swing fully open. (See MET-3L
Installation Instructions, P/N 315-095447.)
When deadfront construction is required,
use the IQ-DFL panel (See IQ-DFL Installation Instructions, P/N 315-095446.)
When the MSE-3L is used for remote
applications, use the IQ-Blank where there
is no MKB-4 installed (See IQ-Blank
Installation Instructions, P/N 315-095482.)
To install the backbox: (Refer to Figure 21)
a. Slip the door off the hinges of the box
and put it to one side temporarily.
b. Remove the knockouts in the backbox
where field wiring is required (Refer to
MSE-3L Power Limited Wiring
Instructions, P/N 315-095445, for
location of knockouts).
c. Hold the empty enclosure against the
wall at a height that provides easy
access.
d. Mark drill points on the wall in the center
of the two slots on the upper rear of the
MSE-3L.
e. Drill the two holes and screw in the top
screws, leaving a small gap between the
wall and each top screw.
f. Mount the MSE-3L on the 2 bolts and
then install the bottom bolts.

Figure 21
Mounting the MSE-3L Enclosure

g. Slip the door back on the hinges of the


enclosure.

2. Install The TSW-2 Tamper Switch

(Refer to Figure 22)


If your configuration (UL 1076) requires the
TSW-2 Tamper Switch, install it now.
The TSW-2 mounts into the rectangular
slot located in the lower right side of the
MKB-4 panel.
1. Place the cable/connector and the switch
terminals through the opening and press
firmly into place.

Figure 22
TSW-2 Tamper Switch

2-2

Technical Manuals Online! - http://www.tech-man.com

2. Plug the cable on the TSW-2 into P9 on


the SMB-2 after installing the SMB-2.

Installation

3. Pull All Field Wiring Into The Backbox


Pull all field wiring into the backbox and
dress the wiring to the approximate location
to which it will go. Refer to the MSE-3L
Power Limited Wiring Instructions, P/N 315095445.

4. Install the SMB-2

(Refer to Figure 23)


Unpack the SMB-2. Inspect the module,
looking for such things as integrated
circuits (ICs) not firmly seated in their
sockets, bent IC pins, connectors not
properly installed, dirt, packing material on
the board, etc.
The installation kit consists of the following
items:
Two #6 nuts
Four #6 screws
Six #6 washers
Six #6 lockwashers
Two resistors
Battery cable with a wire
a. Place the SMB-2 over the two studs in
the upper right-hand portion of the
backbox (See Figure 23).

Figure 23
Installing the SMB-2

b. Secure in place using the hardware


provided.
Be sure the screws and nuts are tight, as
they provide the earth ground connection
for the SMB-2

5. Install the MPS-6/12

(See Figure 24)


The MXL-IQ is designed to operate from a
120 VAC, 60 Hz power source. Use a
separate or dedicated circuit-breaker. Wire
in accordance with local codes and Article
760 of the NEC, NFPA 70, latest edition.
Run the earth ground from a suitable
source to the MPS-6/12. Check local
requirements. Conduit is not an acceptable conductor.
Make sure that the dedicated circuit-breaker
for the MXL-IQ is turned off at the mains.
Place the mounting bracket for the MPS-6/
12 over the two studs provided in the
enclosure as shown in Figure 24.
Secure the MPS-6/12 to the MSE-3L by
slipping the flat washers, then the

Technical Manuals Online! - http://www.tech-man.com

Figure 24
Installing the MPS-6

2-3

Installation
lockwashers, and finally the nuts over the
two studs. Tighten them securely.
Connect the AC mains to MPS-6/12 as
follows:
Terminal
Black (hot)
White (neutral)
Green (earth ground)

1
2
3

Install the 14 gauge green ground strap


spade lug side to Terminal 3 (green, earth
ground) of the MPS-6 or MPS-12. Secure
the ring lug side of the ground strap to the
nearest available stud in the enclosure. The
stud size may vary depending on the actual
system modules and enclosure used.
Because the stud may be either a #10
thread of " thread, nuts for both have
been provided. The ground strap provided
is long enough for all applications and the
ring lug is good for both #10 and " studs.
If possible, install the ring lug under one of
the lockwashers and nuts which secure the
MPS-6 or MPS-12 itself.
Connect the 3-wire cable coming from the
MPS-6 to the SMB-2, P1, or connect the 8wire cable coming from the MPS-12 to the
SMB-2, P14.250

6. Install the MKB-4 Keyboard/


Annunciator

Remove all system power


before installation, first
battery and then AC.

Unpack the MKB-4. Inspect the module for


such things as integrated circuits (ICs) not
firmly seated in their sockets, bent IC pins,
connectors not properly installed, dirt, and
packing material on the board.
NOTE: The MKB-4 is supplied with the
keyboard/annunciator mounted to the
hinged panel.
Setting the Network Address
(See Figure 25)
a. Before installing the MKB-4 panel, set its
network address on S1, the switch on
the ANN-1 board located on the back of
the MKB-4. Use dipswitches SW1 and
SW2 on switch S1 to set the network
address of the MKB-4. Refer to Table 2
for switch settings.
b. The MKB-4 module address is always
set within network addresses 248
through 251.
c. One supervised MKB-4 must be
installed at network address 251.
Other supervised MKBs may be at the
other addresses.

TABLE 2
SWITCH SETTINGS ON THE ANN-1
ADDRESS SETTINGS FOR:
SWITCH

248

249

250

251

S1-SW1

OpenOFF

ClosedON

OpenOFF

ClosedON

S1-SW2

OpenOFF

OpenOFF

ClosedON

ClosedON

S1-SW3

ClosedON

ClosedON

ClosedON

ClosedON

S1-SW4

ClosedON

ClosedON

ClosedON

ClosedON

S1-SW5

See Setting Supervision

NOTE: Switches S1-SW3 and S1-SW4 are for future use.


Switch S1-SW5 is used to select suptervision.

Figure 25
Setting S1 on the ANN-1 Board

2-4

Technical Manuals Online! - http://www.tech-man.com

Setting Supervision:
Use switch S1-SW5 on the ANN-1 to select
or deselect supervision. If your ANN-1 has
a switch with position 1 indicated on the
left-hand side, ignore the printing on the
switch. SW1 on S1 is at the extreme righthand side of S1, regardless of any other
marking.

Installation
NOTE: When you select non-supervision
for an annunciator, there must also be one
and only one supervised annunciator at
the same address. The supervisory mode
is independent of the network address.
To set for supervision
S1-SW5 = Closed (ON)
To set for non-supervision
S1-SW5 = Open (OFF)
Mounting the MKB-4
(Refer to Figure 26)
1. Install three screws in the first group of
three tapped holes in the right flange.
Leave a 1/8-inch gap between the head
of the screw and the flange. Slide the
slots of the MKB-4 panel hinge under the
head of the screws and tighten.
2. After the MKB-4 is mounted to the
enclosure, connect the cable (P/N 555192238) between P1 on the ANN-1 (on
the back of the MKB-4) and P8 on the
SMB-2.

Figure 26
Installing the MKB-4 Keyboard/Annunciator

MSE-3L

CAUTION:
Be sure the black tracer wire on the edge of
the cable is close to the 1 on position 1 of
connector P1 on the ANN-1 and the 1 on
position 1 of P8 on the SMB-2.

d
Cable supplie
with PIM-1
2)
24
92
(P/N 555-1

1
P1
P1 P2

7. Install the PIM-1, PIM-2, and PAL-1

Back of MKB-

TB1

PIM-1

ANN-1

To P8
o
(Cable n the SMB
-2
suppli
ed wit
h MK

B-4)

PIM-1
1. Install the PIM-1 on the back of the
MKB-4 panel as shown in Figure 27.
Position the PIM-1 so the TB1 is on the
left side of the board.
2. Mount the PIM-1 module on the raised
studs with the hardware provided.
3. Using the cable supplied with the PIM-1,
connect PIM-1, P-1 to ANN-1, P1 (See
Figure 27).
4. Using the cable supplied with the MKB-4,
connect PIM-1, P2 to SMB-2, P8 (See
Figure 27).

Figure 27
Installing a PIM-1 on the Back of an MKB-4

Technical Manuals Online! - http://www.tech-man.com

2-5

Installation
PIM-2/PAL-1
The PIM-2 and printer require a standby
power source in the event of a loss of
primary input power (AC mains). Refer to
Figure 28 for the connection of a UPS to
meet this requirement.

5. Set the dipswitches on the back of the


PIM-2 to agree with the communications
parameters configured in the CSG-M.
Refer to Table 4 for the dipswitch
definitions.

1. Before installing a PIM-2 in the MXL-IQ


system, a PIM-1 must be already
installed.

8. Install the MOM-2 or MOM-4

2. Wiring from the PIM-1 to the PIM-2 must


be within 25 feet in rigid conduit (Refer to
Table 3).
TABLE 3
PIM-1 TO PIM-2 INTERFACE REQUIREMENTS
(Supplied by installer)
PIM-1, TB
4 (Rx)
5 (Tx)
7
3 (BUSY)
2 (COMMON)

TO

PIM-2 Inpt Pin No.


2 (TxD)
3 (RxD)
4, 5 (RTS, CTS)
20 (DTR)
7 (GRD)

Use 18 AWG wire minimum.

3. Figure 29 shows the proper installation


of the PIM-2 with the MXL-IQ system.
4. Programming the CSG-M is required
when using a PIM-2 and parallel printer.
Configure one of the following four
printer types on the MKB-4:
Supervised PIM-2

80 column color

Supervised PIM-2

132 column color

Supervised PIM-2

80 column

Supervised PIM-2
132 column (for
PAL-1 and NFPA 72 Proprietary)
NOTES:
1. All wires 14 AWG min,
600V insulation.
2. Wiring to the printer and
PIM-2 must be 14 AWG
min, 600V insulation in
conduit.
3. Use the UPS ICS Lifeline
Model 9300057.
4. Standby Power
requirements: 120 VAC,
0.6A for 24 hours.
5. Standby Power
requirements: 120 VAC,
0.15A for 24 hours.

Figure 28
UPS Wiring Diagram

2-6

Technical Manuals Online! - http://www.tech-man.com

If a system requires the MOM-2 or MOM-4


optional card cage (Figures 10 and 11,
page 20), now is the time to install it.
Unpack the card cage and its attached
backplate and inspect it, looking for such
things as connectors not properly
installed, dirt, and packing material on the
board.
The MOM-2/4 installation kits include the
following items

MOM-2

MOM-4

3 #10 nut s

4 #10 nut s

3 #10 flat washers

4 #10 flat washers

3 #10 lockwashers

4 #10 lockwashers

4 #6 x 7/16 screws

1 8-conductor ribbon cable

2 #6-32 x 5/16 screws

2 2-wire cables

1 8-conductor ribbon cable

4 card guides

2 2-wire cables
2 card guides

Installation
TABLE 4
SERIAL INTERFACE COMMUNICATION PARAMETERS
Dipswitch Position (SW1) -Located at rear of PIM-2

BAUD RATE
960 0
480 0
240 0
120 0
30 0

OFF
ON
OFF
ON
ON

ON
ON
OFF
OFF
ON

OFF
OFF
ON
ON
ON

DATA BITS
8
7

OFF
ON

PARITY
Even
Odd

OFF
ON

PARITY
Disable
Enable

OFF
ON

FLOW CONTROL
Hardware
Software

OFF
ON

PORT TYPE

OFF

NOTE:
When setting Switch S1,
OFF=UP=OPEN
ON=DOWN=CLOSED
ANN-1

MKB-4
PIM-1
SEE INSTL. INSTR.
P/N 315-091462
TB1

CABLE NOT SUPPLIED


(SEE NOTE 1)
SUPERVISED

PARALLEL PRINTER (REAR VIEW)

PIM-2 (REAR VIEW)


(REFER TO TABLE 4)

120 VAC
60 Hz

CENTRONICS PARALLEL

OUTPUT

CABLE SUPPLIED WITH PIM-2


(SEE NOTE 2)
SUPERVISED
(REFER TO NOTES 9 AND 10)
THE CONNECTION IS NOT
SUPERVISED FOR DATA
INTEGRITY BETWEEN PIM-2
AND THE PRINTER.

Figure 29
PIM-2 to MXL-IQ Wiring Diagram

Technical Manuals Online! - http://www.tech-man.com

PIM-2 POWER TRANSFORMER


SUPPLIED WITH PIM-2 (SEE NOTE 3)

INPUT

SW1

PWR

XFMR

INSTALL IN UL LISTED GANGBOX

PIM-2 POWER CABLE


MUST BE IN CONDUIT

NOTES:
1. Maximum cable
distance from PIM-1 to
PIM-2 cable is 25 feet.
The two modules must
be in the same room.
2. The maximum distance
from the PIM-2 to the
parallel printer is 6 feet.
The two modules must
be in the same room.
3. PIM-2 power (PWR) is
connected to the 5
VDC, 600mA transformer supplied with the
PIM-2. The transformer
requires 120 VAC, 60
Hz, 0.5A max.
4. For NFPA 72 Local,
Auxiliary, and Remote
Station configurations,
connect the output of
the PIM-2 to any UL
listed EDP Centronics
parallel printer.
5. The parallel printer must
support the EPSON FX
command set.
6. The PIM-2 input and
output connectors are
DB-25 female.
7. Pressing RESET on the
PIM-2 causes the unit
to read the SW1
settings. The status
LED is lit when the unit
is powered. Do not use
the COPY button.
8. For NFPA Proprietary
and UL 1076
configurations, use
parallel printer Model
PAL-1, a UL listed for
fire Centronics parallel
printer.
9. The parallel printer is
supervised for AC, on/
off line, paper out, paper
jam, and connection to
the PIM-2.
10. The PIM-2 is
supervised for power,
connection to the
printer, and connection
to the PIM-1.
11. After loading paper in
the PAL-1 printer, turn
off the power and follow
the steps below:
While pressing the
LOAD PARK button,
turn on the power to
the PAL-1 printer.
Continue pressing
the LOAD PARK
button for 5 seconds.
Release the LOAD
PARK button.
The current setting
will print.
When printing is
completed, the ON
LINE indicator will be
lit. If the ON LINE
indicator is not lit,
press the ON LINE
button.

2-7

Installation
To mount the MOM-2/4 in an MSE-3L
enclosure:
1. Hold the MOM-2/4 so that terminal
blocks TB2 and TB4 are on the left.
2. Place the module vertically on the
mounting studs near the top left of the
enclosure as shown in Figure 23 on
page 2-3.
3. Fasten the MOM-2/4 in position with the
No. 10 flatwashers, lockwashers, and
nuts provided.
To install the card guides
(See Figures 30 and 31):
Install the card guides included in the
package using the #6 x 7/16 screws
provided. (The MOM-4 is shipped with the

MOM-2

mounting screws for the card guides


already installed.)
1. Mount the long screws.
2. Make sure that the locating pin on the
guide is seated in the hole on the
MOM-2/4.
3. Tighten the screw.
Repeat this process for the remaining card
guide(s). The MOM-2/4 is now ready to
accept the optional modules. If the system
does not require the installation of any halfwidth modules, install the two #6 x 5/16
screws in the center holes where the
additional card guides would be placed.
Plug-in Cards for the MOM-2/4
Determine which optional plug-in modules
are used in your CSG-M configuration.
Next, decide where they should be installed
by checking the following factors:
1. The size of each module. The CSM-4
and CRM-4 each occupy two adjacent
slots.
2. How the field wiring will be installed.

Figure 30
Installing the MOM-2 Card Guides

3. The maximum load current permitted for


the MOM-2/4 is 6 amps for the MPS-6 or
12 amps for the MPS-12. This current
must be derated by the current drawn
from SMB TB5 (CZM-1B6 power and
NAC #1 and NAC #2). When the system
includes an external auxiliary power
supply, the maximum load current
permitted depends on the application.
Refer to Table 5 for the maximum
current required by each module under
full load conditions.
MOM-2/4 Electrical Installation
1. Attach the 8-conductor ribbon cable to
P6 on the SMB-2, engaging the locking
rib of the cable with the locking tab on P6.
2. Attach the other end of the 8-conductor
ribbon cable to P7 on the MOM-2/4,
engaging the locking rib of the cable with
the locking tab on P7.
3. Connect one end of the 2-wire 24 VDC
cable to P3 on the SMB-2, using the
locking tab to lock the cable onto P3.

Figure 31
Installing the MOM-4 Card Guides

2-8

Technical Manuals Online! - http://www.tech-man.com

Installation
4. Connect the other end of the 2-wire
cable into P5 on the MOM-2/4. The
2-wire cable that attaches P5 on the
MOM-2/4 with P3 on the SMB-2 feeds
24 VDC full-wave unfiltered DC power to
the MOM-2/4. This is the main power
used by the optional modules. The
8-conductor ribbon cable supplies 5 VDC
and communication between the SMB-2
and the MOM-2/4.

9. Install the MOI-7, MOD-16, and


MID-16
MOI-7
1. Mount the MOI-7.

TABLE 5
MAXIMUM MODULE LOAD CURRENTS
ALD-2I
CMI-30 0
CRM-4
CSM-4
CZM-4
NIM-1R

90mA (120 devices in alarm)


96mA
75mA (4 relays energized)
34mA (no alarm indicating appliances connected)
720mA (maximum with 4 zones in alarm)
0mA

The following example assumes that no power is drawn from SMB-2 TB5
(CZM-1B6 power and NAC #1, NAC #2).

Example:
With 1 CZM-4 + 1 CRM-4 + 1 CSM-4, the total load current = 0.72 +
0.075 + 0.034 = 0.83A
The remaining available current = 12.0 (MPS-12) or 6.0 (MPS-6) - 0.83 =
11.83 (MPS-12) or 5.83 (MPS-6).

The MOI-7 mounts on a System 3 rail in


two module spaces. Mount the MOI-7
using the four screws provided.

The remaining current may be used for NAC power.

2. Set the network address on S1.


Set the address according to Table 16 at
the end of this chapter so that it agrees
with the address assigned in CSG-M.
3. Use P6 to set the mode for common
alarm relay K1. (See Figure 17,
page 1-10, for the location of P6.)
K1 is a common alarm relay that can be
programmed to transfer back to normal
when the MXL-IQ is silenced.
Use jumper P6 on the MOI-7 to select the
desired mode according to the table below.
P6 Position

Mode

Alarm Relay Silenceable

Alarm Relay Non-silenceable

3. If a connection to a MOD-16 module on


another rail is required, use the optional
cable P/N 555-190941.
MID-16 (See Figure 19, page 1-11)
1. Mount the MID-16 in one System 3 type
module space using the four screws
provided.
2. Connect the MID-16 to the module to its
left with the 10-position ribbon cable P/N
555-190940 provided. This module may
be either an MOI-7, MOD-16, or MID-16.
3. If a connection to a module on another
rail is required, use the optional cable
P/N 555-190941.

MOD-16 (See Figure 18, page 1-10)


1. Mount the MOD-16 in one System 3 type
module space using the four screws
provided.
2. Connect the MOD-16 to the MOI-7 with
the 10-position ribbon cable P/N 555190940 provided with the MOI-7.

Technical Manuals Online! - http://www.tech-man.com

2-9

Installation

10. Install Field Wiring

TABLE 6
WIRING TO THE SMB-2
Screw Terminal

Application

TB5 12-9
TB5 8-5
TB5 4-1

CZM-1B6 Power
Notification Appliance Circuit 2
Notification Appliance Circuit 1

TB4
TB4

6-4
3-1

Trouble Relay
Alarm Relay

TB3
TB2

4-1
4-1

Analog Loop 2
Analog Loop 1

TB1
TB1
TB1

1-2
3
4-5

MXL-IQ Network for MOI-7 and RCC-1/1F


Do Not Use
MPS-6/12 and MOM-2/4

NOTE: See SMB-2 Connections and Ratings for a more detailed description of the
screw terminals.

Wiring to the SMB-2


Refer to Table 6. Dress the field wiring that
will be going to the SMB-2. Strip the
insulation from the wiring, but do not
connect the wires to the screw terminals.
Wiring to the MOM-2/4 Optional Modules (if
Required)
Refer to Table 7. Dress the field wiring that
will be going to the MOM-2/4 modules. Strip
the insulation from the wiring and connect
the wires to the appropriate screw terminals.

11. Check Field Wiring


TABLE 7
WIRING TO THE MOM-2/4 OPTIONAL MODULES
Module
CSM-4

Screw Terminal
1-4
9-12

Application
Notification Appliance Circuit 1
Notification Appliance Circuit 2

NOTE: See CSM-4 Connections and Ratings for a more detailed description of the screw
terminals.

CRM-4

1-3
4-6
11-13
14-16

Dry Contact 1
Dry Contact 2
Dry Contact 3
Dry Contact 4

NOTE: See CRM-4 Connections and Ratings for a more detailed description of the screw
terminals.

CZM-4

1-4
5-8
9-12
13-16

Conventional
Conventional
Conventional
Conventional

Zone 1
Zone 2
Zone 3
Zone 4

NOTE: See CZM-4 Connections and Ratings for a more detailed description of the screw
terminals.
CMI-30 0

1-4

CXL Modem Connection

NOTE: See CMI-30 0 Connections and Ratings for a more detailed description of the screw
terminals.
NIM-1R

1-2
3-4
12-16

XNET Network Pair A / FSI / AnaLASER


XNET Network Pair B
NCC XNET Interface

NOTE: See NIM-1R Connections and Ratings for a more detailed description of the screw
terminals.
ALD-2I

1-4
5-8

Initiating Devices
Install all initiating device bases and end-ofline devices where applicable. Install all
initiating devices. Refer to the specific
installation instructions provided with each
device.
Notification Appliances
Install all notification appliances (bells,
strobes, etc.) Refer to the specific installation instructions provided with each device.
Check Resistance Between Wiring Circuits
Start with the wire that goes to TB5-12 on
the SMB-2. Check the resistance between
that wire and all other field wires that will be
connected to the SMB-2. Also, check the
resistance between that wire and all wires
connected to the screw terminals on the
MOM-2/4. Refer to Table 8 for acceptable
resistance readings. If the readings are
good, connect the wire to TB5-12. Repeat
the above procedure for the next wire on
the SMB-2.
When the SMB-2 is complete, continue with
the MOM-2/4 (if it is installed).

Analog Loop 1
Analog Loop 2

NOTE: See ALD-2I Connections and Ratings for a more detailed description of the screw
terminals.

12. Start Up Procedure


NOTE: Throughout this section, refer to the
TROUBLESHOOTING GUIDE as an aid to
resolving trouble conditions.

2-10

Technical Manuals Online! - http://www.tech-man.com

Installation
1.System Status
When beginning the start-up procedure, the
condition of the system is as follows:
All field wiring is connected to all screw
terminals, except for the analog loops
they should be disconnected. All field
devices are installed.

TABLE 8
FIELD WIRING CHECKOUT
SMB-2 EXTERNAL WIRING AND TROUBLESHOOTING GUIDE
TB-5

Resistance
Between Wires

1.

Chassis to 1-12

2.

Desired Results

Probable Cause Of Problem

>1 Meg

Short in wiring.

11 to 12

<1.5 ohms

Line open; Line too long.

3.

9 to 10

<1.5 ohms

Line open; Line too long.

4.

7 to 8

<1.5 ohms

Line open; Line too long.

5.

5 to 6

<1.5 ohms

Line open; Line too long.

6.

3 to 4

<1.5 ohms

Line open; Line too long.

7.

1 to 2

<1.5 ohms

Line open; Line too long.

8.

9 to 12

>1 Meg

Line shorted.

9.

5 to 8

>1 Meg

Line shorted.

3.SMB-2 Checkout Minus the Analog Loops


Turn on the AC power to the system.

10.

1 to 4

>1 Meg

Line shorted.

11.

9-12 to 1-8

>1 Meg

Line shorted.

The power light on the MKB-4 turns on

12.

5-8 to 1-4

>1 Meg

Line shorted.

No modules are installed in the MOM-2/4


cage.
2.Create a Test Configuration
Create a test configuration on your CSG-M
that includes every module that will be on
your final system. Do not include any
initiating devices. You will use this test
configuration in checking out the System.

the System displays the default message:


13.

8 (+) to 5 (-)

2.2K 10%

Line shorted; Line open; Wrong


EOL device; No EOL device; Device
wired backward; Device not
polarized.

14.

4(+) to 1 (-)

2.2K 10%

Line shorted; Line open; Wrong


EOL device; No EOL device; Device
wired backward; Device not
polarized.

15.

>1 Meg
>1 Meg
>1 Meg

Line shorted.

After the transfer process is complete,


MXL-IQ resets itself; after 5 minutes, the
state of the system should be as follows:

12 to 1-8
12 to TB2/3 1-4
12 to all MOM-2/4

16.

>1 Meg
>1 Meg
>1 Meg

Line shorted.

No trouble condition for the signaling


circuits on the main board.

8 to 1-4
8 to TB2/3 1-4
8 to all MOM-2/4

17.

4 to TB2/3 1-4
4 to all MOM-2/4

>1 Meg
>1 Meg

Line shorted.

TB-2
and
TB-3

Resistance
Between Wires

1.

Chassis to all
terminals

2.

CERBERUS PYROTRONICS
MXL

Transfer the test configuration from your


computer to the MXL-IQ. Refer to the
CSGM Manual (P/N 315-090381) for the
correct procedure.

A battery trouble condition if the battery


option was selected.
All optional modules configured on the
system are in trouble since they are not
yet installed.
4.SMB-2 Analog Loop Checkout
Modify your test configuration by adding to
it the analog devices that are connected to
analog loop 1.
Turn off the power and connect the field
wiring to analog loop 1 on the SMB-2.
Turn on the power. Wait for the System
to initialize (approximately 3 minutes).

Desired Results

Probable Cause Of Problem

>1 Meg

Short in wiring.

1 to 2

<50 ohms

Open in wiring; Line too long.

3.

3 to 4

<50 ohms

Open in wiring; Line too long.

4.

1 to 4

<.4F

Too much wire.

5.

1 (+) to 4 (-)

>10K ohms

Line shorted.

6.

TB-2 (1-4) TB-3 (1-4)

>1 Meg

Line shorted.

7.

TB-2 (1-4) TB-5 (1-12)

>1 Meg

Line shorted.

8.

TB-3 (1-4) TB-5 (1-12)

>1 Meg

Line shorted.

(+) and (-) indicate meter lead polarity.


> = greater than; < = less than

Technical Manuals Online! - http://www.tech-man.com

2-11

Installation
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among
the following (See Appendix J for a
complete list of Trouble Messages):
Device multiple response
Input device not responding
Incorrect device ID
Unspecified device responding
Identify the addresses of the devices
with troubles and eliminate them, reset
the system, and verify that the troubles
have cleared before proceeding.
Modify your test configuration by adding
to it the analog devices that are connected to analog loop 2.

To install the card guide that comes with


the CRM-4 and the CSM-4 module:
a Loosen the appropriate screw in the
center of the MOM-2/4 and set the card
guide in place.
Make sure that the locating pin on the
bottom of the card guide is in the hole on
the MOM-2/4.
b. Tighten the screw on the MOM-2/4 to
secure the card guide.

Turn off the power and connect the field


wiring to analog loop 2 on the SMB-2.

6.ALD-2I Checkout

Turn on the power. Wait for the System


to initialize (approximately 3 minutes).

Installing the ALD-2I

Check the trouble list on the MKB for


troubles on the devices that were just
added. The troubles will be from among
the following (See Appendix J for a
complete list of Trouble Messages):

Set the address of each ALD-2I. Refer to


the CSG-M printout of the final configuration for the address to which each ALD-2I
should be set. Refer to the ALD-2I Installation Instructions (P/N 315-091464) to set
the address dipswitch.

Device multiple response


Input device not responding
Incorrect device ID
Unspecified device responding
Identify the addresses of the devices
with troubles and eliminate them, reset
the system, and verify that the troubles
have cleared.

5.MOM-2/4 Optional Modules Checkout

Remove all system power


before installing any
optional module
(ALD-2I, CMI-300, CRM-4,
CSM-4, CZM-4, NIM-1R).

2-12

Unpack each module just before installation. Inspect the module, looking for such
things as integrated circuits (ICs) not firmly
seated in their sockets, bent IC pins,
connectors not properly installed, dirt, and
packing material on the board.

Technical Manuals Online! - http://www.tech-man.com

Install the ALD-2Is one at a time by inserting them in the appropriate card guides on
the MOM-2/4. Make sure that the card is
firmly seated in the card edge connector.
Eliminate all troubles from each module
before installing the next one.
Modify your test configuration by adding to
it any initiating devices that are connected
to the first analog loop on the ALD-2I.
Turn off the power; connect the field wiring
to analog loop 1 on the ALD-2I. Turn on
the power.
Turn off the power and connect the field
wiring to analog loop 1 on the SMB-2.
Turn on the power. Wait for the System
to initialize (approximately 3 minutes).
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among

Installation
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among
the following (See Appendix J for a
complete list of Trouble Messages):

the following (See Appendix J for a


complete list of Trouble Messages):
Device multiple response
Input device not responding
Incorrect device ID

Device multiple response

Unspecified device responding

Input device not responding


Incorrect device ID

Identify the addresses of the devices


with troubles and eliminate them, reset
the system, and verify that the troubles
have cleared before proceeding.

Unspecified device responding


Identify the addresses of the devices
with troubles and eliminate them, reset
the system, and verify that the troubles
have cleared before proceeding.

Modify your test configuration by adding to


it any initiating devices that are connected
to the second analog loop on the ALD-2I.
Turn off the power; connect the field wiring
to analog loop 2 on the ALD-2I. Turn on
the power.
Turn off the power and connect the field
wiring to analog loop 1 on the SMB-2.
Turn on the power. Wait for the System
to initialize (approximately 3 minutes).

Installing the CMI-300 Interface Module


Before installing the CMI-300 in the
MOM-2/4, you must do the following:
1. Check that there is a jumper installed for
jumper J2, pins 1 and 2 on the CMI-300
module.

TABLE 9
Panel Number Programming (SW2)
ADDR

87654321

ADDR

000
0 01
0 02
0 03
0 04
0 05
0 06
0 07
0 08
0 09
010
011
012
013
014
015
---

FSI
SOOOOOOX
SOOOOOXO
SOOOOOXX
SOOOOXOO
SOOOOXOX
SOOOOXXO
SOOOOXXX
SOOOXOOO
SOOOXOOX
SOOOXOXO
SOOOXOXX
SOOOXXOO
SOOOXXOX
SOOOXXXO
SOOOXXXX
------------

016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
031
---

87654321
SOOXOOOO
SOOXOOOX
SOOXOOXO
SOOXOOXX
SOOXOXOO
SOOXOXOX
SOOXOXXO
SOOXOXXX
SOOXXOOO
SOOXXOOX
SOOXXOXO
SOOXXOXX
SOOXXXOO
SOOXXXOX
SOOXXXXO
SOOXXXXX
------------

ADDR

87654321

ADDR

87654321

032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047
---

SOXOOOOO
SOXOOOOX
SOXOOOXO
SOXOOOXX
SOXOOXOO
SOXOOXOX
SOXOOXXO
SOXOOXXX
SOXOXOOO
SOXOXOOX
SOXOXOXO
SOXOXOXX
SOXOXXOO
SOXOXXOX
SOXOXXXO
SOXOXXXX
------------

048
049
050
051
052
053
054
055
056
057
058
059
060
061
062
063
064

SOXXOOOO
SOXXOOOX
SOXXOOXO
SOXXOOXX
SOXXOXOO
SOXXOXOX
SOXXOXXO
SOXXOXXX
SOXXXOOO
SOXXXOOX
SOXXXOXO
SOXXXOXX
SOXXXXOO
SOXXXXOX
SOXXXXXO
SOXXXXXX
SXOOOOOO

S = Closed selects Style 7


S = Open selects Style 4

O = Open or OFF
X = Closed or ON

NOTE:
To open a dipswitch, press down on the side of the dipswitch marked OPEN.
To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
To open a slide switch, push the slide to the side opposite the side marked ON.
To close a slide switch, push the slide to the side marked ON.

Technical Manuals Online! - http://www.tech-man.com

2-13

Installation
2. Set the CMI-300 network address by
using the dipswitch settings on switch
SW1. Use Table 16 at the end of this
chapter to set the network address.
Plug the CMI-300 module in the MOM-2/4
card cage and connect the wiring as shown
in CMI-300 Connections and Ratings.
Eliminate all troubles from each module
prior to installing the next one.
Installing CRM-4 and CZM-4 Modules
Set the address of each module. Refer to
the CSG-M printout of the final configuration for each module address setting. Refer
to the installation instructions for each
module to set the address dipswitch.
Install the optional modules one at a time
by inserting them in the appropriate card
guides on the MOM-2/4. Eliminate all
troubles from each module prior to installing the next one.
Installing the NIM-1R Network Interface
Module
The NIM-1R installs into the MOM-2/4 card
cage where it occupies one full width slot.
The wiring is connected to TB4 of the
MOM-2 or TB3 of the MOM-4.
The NIM-1R has two configuration
dipswitches. Set the dipswitches before
installing the NIM-1R into the MOM-2/4.
Use switch SW1 to set the MXL-IQ network
address. Set this switch according to the
address where the NIM-1R is installed in
the MXL-IQs network map. Refer to the
CSG-M configuration printout for the
address of the module. See Table 16 at the
end of this chapter for settings.
Use switch SW2 to set either the panel
number for networked systems or to select
FSI or AnaLASER operation. Refer to Table
9 for panel settings, Table 10 for FSI
settings, or Table 11 for AnaLASER
settings.
1. When installing the NIM-1R in a
networked system, set the panel number
to agree with the panel number for the
NIM-1R assigned to the MXL-IQ System
in CSG-M.
2. Switch position 8 selects Style 4 or 7
operation for the NIM-1R network.

2-14

Technical Manuals Online! - http://www.tech-man.com

3. When installing the NIM-1R for FSI


operation, set the switch to all open (or
OFF).
TABLE 10
FSI Programming
ADDR

87654321

000

OOOOOOOO
O = Open or OFF

4. When installing the NIM-1R for


AnaLASER connection, set the switch as
follows:
TABLE 11
AnaLASER Programming
ADDR

87654321

AnaL ASER

XOOOOOOO

O = Open or OF F
X = Closed or ON

After setting the switches, install the


NIM-1R into the MOM-2/4 card cage. Make
sure that the module is in the card guides
and the card edge is firmly seated in the
connectors on the MOM-2/4.

Installing the CSM-4 Signal Module


Before installing the CSM-4 in the
MOM-2/4, you must set the network
address, configure each circuit according to
the CSG-M program [as Local (NACs),
Municipal Tie, Leased Line, or Releasing
Service], and set the default modes (trouble
and alarm) as follows. Refer to Table 12 for
the Modes of Operation.
a.Set the Network Address
The network address is set on dipswitch S1
(See Figure 12, page 1-8). See the CSG-M
printout for the proper address. Use Table
16 at the end of this chapter to set the
switches.

Installation

TABLE 12
Modes of Operation

b.Set the Mode of Operation for Each Circuit


The CSM-4 has one programming slide
switch and one jumper for each of its two
circuits. (See slide switches S3 and S4 and
jumpers G1 and G2 on the CSM-4 board,
Figure 12, page 1-8.) Setting these slide
switches and jumpers allows the selection
of four possible modes of operation. These
modes correspond with NFPA standards 72
Local, Municipal Tie, Leased Line, and
NFPA 12A, 13, and 2001 Releasing
Service.
Each circuit on the CSM-4 can be set
independently for the type of operation
desired. Table 12 shows how to set the
switches and jumpers for circuits 1 and 2.
The CSG-M printout shows the mode for
each circuit.

c.Set the Degrade Modes of Operation


There are two sources of degrade activation, the degrade alarm bus and the degrade trouble bus. These two buses
become active ONLY when the MXL-IQ
communication network fails. Dipswitch S2
on the CSM-4 sets the degrade mode of
operation for each circuit.

Technical Manuals Online! - http://www.tech-man.com

TABLE 13
Setting the Mode of Operation for the CSM-4
(Using S3, S4 and G1, G2)
For Circuit 1
Local (NAC)
Municipal Tie
Leased Li ne
Rel eas i ng Ser v i c e
Illegal (Results in a trouble
on t he CSM - 4)
For Circuit 2
Local (NAC)
Municipal Tie
Leased Li ne
Rel eas i ng Ser v i c e
Illegal (Results in a trouble
on t he CSM - 4)

S3
Position

G1

1
1
2
1
2

No t C u t
Cut
No t C u t
Cut
Cut

S4
Position

G2

1
1
2
1
2

No t C u t
Cut
No t C u t
Cut
Cut

Each circuit operates independently in the


degrade mode. Dipswitch S2, positions
SW1 and SW2, determines the degrade
mode of operation when the trouble bus
activates. Dipswitch S2, positions SW3SW6, determines the degrade mode of
operation when the alarm bus activates.

2-15

Installation
d.Degrade Trouble Activation
The degrade trouble bus may ONLY be
used when the circuit is used as a Leased
Line trouble indicating circuit. (See Table
12.) When enabled, this trouble degrade
mode ensures that a trouble will be transmitted to the receiving station even when
the MXL-IQ communication network fails.

Determine which type of degrade mode you


want for each circuit and set dipswitch S2
(SW3-SW6) as shown in Table 15.

Using the CSG-M printout, determine if


either of the circuits is configured as a
Leased Line trouble. Table 14 shows how
to set dipswitch S2 (SW1 and SW2) to
enable the degrade trouble activation for
the desired circuit.

The status of the MXL-IQ before checkout


must be as listed below:

TABLE 14
Setting the Degrade Trouble Modes
for the CSM-4 on S2
SW1
G1

For Circuit 1
Leased Line Trouble
No Trouble Activation

On (Closed)
Off (Open)
SW2
G2

For Circuit 2
Leased Line Trouble
No Trouble Activation

On (Closed)
Off (Open)

No t e :
If Circuit 1 or Circuit 2 is not used for Leased Line trouble,
switches SW1 or SW2 must be off (open).

e.Degrade Alarm Activation


Each circuit on the CSM-4 can be set with
dipswitch S2, positions SW3-SW6, to
determine when the degrade alarm bus
activates (See Table 12). There are three
degrade alarm modes. Each circuit can be
set independently from the other.

TABLE 15
Setting the Degrade Alarm Modes for the CSM-4 on S2
For Circuit 1
OFF (no degrade activation)
CONTINUOUS (active on degrade alam)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE
For Circuit 2
OFF (no degrade activation)
CONTINUOUS (active on degrade alam)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE

SW4

SW3

OFF (Open)
OFF (Open)
ON (Closed)
ON (Closed)

OFF (Open)
ON (Closed)
OFF (Open)
ON (Closed)

SW4

SW3

OFF (Open)
OFF (Open)
ON (Closed)
ON (Closed)

OFF (Open)
ON (Closed)
OFF (Open)
ON (Closed)

NOT E : When circuits are used for leased line supervisory, the alarm degrade modes must
be OFF (Open).

2-16

Technical Manuals Online! - http://www.tech-man.com

13. System Function Checkout

1. AC and battery power connected and


turned on.
2. All modules installed and all field wiring
connected.
3. All initiating devices installed and
addressed.
4. All field wiring checked out.
5. The start-up procedure completed.
6. An CSG-M printout of the summary of
the System Configuration available.
7. For documentation purposes, set the
MXL-IQ time before proceeding.
8. Transfer the final version of the System
Configuration to MXL-IQ.
Follow the steps listed in System Operation Checkout.

System Operation Checkout

WARNING!
Prior to activating any initiating device,
take steps to prevent output circuits
from being activated. Failure to do so
may result in building EVAC (bells),
notification of fire department, elevator recall, etc.
Test these operations in accordance
with local codes and follow the direction of the authority having jurisdiction.
Observe all safety precautions.

Installation

Test
1. Observe the display on the MKB-4.

Response
The POWER LED should be on steady.
The TROUBLE LED should be off.
The following message should appear on the alphanumeric
display:
(Time and Date)
(System Custom Message)

SYSTEM
NORMAL

(It may take a few minutes after power-up before the message
System Normal appears.)

2. Activate every alarm causing initiating


device on the System in groups of 100 or
fewer. Reset the System prior to
activating each group of 100.

Every device alarms and there are no troubles annunciated.


Device LEDs should come on when the device is in alarm.
As each device is alarmed, the custom message appears on the
display, is recorded on the printer (if installed), and corresponds
to the CSG-M printout for that device.
The messages listed on the printer are in the order in which the
devices were alarmed.
Pressing the NEXT key on the MKB-4 displays the devices in
reverse order.
Check that all appropriate responses are activated.

3. Activate all supervisory devices on the


System.

Each device should cause a supervisory.


As each device changes state, the custom message appears on
the display, is recorded on the printer (if installed), and corresponds to the CSG-M printout for that device.
The messages listed on the printer are in the order in which the
devices were activated.
Pressing the NEXT key displays the devices in reverse order.
Check that all the appropriate responses are activated.

4. Activate all security devices on the


System.

Each device should cause a security condition.


As each device is activated, the custom message appears on
the display, is recorded on the printer (if installed), and corresponds to the CSG-M printout for that device.
Check that all appropriate responses are activated.

Technical Manuals Online! - http://www.tech-man.com

2-17

Installation

Test
5. Activate all status devices on the
System.

Response
None of the devices should cause an alarm or trouble condition.
If there is a printer, the System should print the status of reporting devices.
As each device is activated, the custom message recorded on
the printer corresponds to the CSG-M printout for that device.
Check that all appropriate responses are activated.

6. CRM-4 relays:

Verifies proper operation of the connected relay.

Refer to Control Output On/Off, page


3-38, and toggle each CRM-4 relay
assigned to the System.
Reset the System when this test is
complete.

7. CSM-4 relays:

Verifies proper operation of the connected relay.

Refer to Control Output On/Off, page


3-38, and toggle each CSM-4 relay
assigned to the System.
Reset the System when this test is
complete.

8. System Functions:
Check all functions that are defined in
the customer specifications.

Check that the correct relationships between initiating devices


and output functions occur as defined by the customer specifications.
Check that the appropriate NFPA and local codes are met
(Refer to the CSG-M Logical Function Summary.)

2-18

Technical Manuals Online! - http://www.tech-man.com

Installation
TABLE 16
NETWORK ADDRESS PROGRAMMING
ADDR
000
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
031
032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047
048
049
050
051
052
053
054
055
056
057
058
059
060
061
062
063

&%$#"!

ILLEGAL
ILLEGAL
ILLEGAL
OOOOOOXX
OOOOOXOO
OOOOOXOX
OOOOOXXO
OOOOOXXX
OOOOXOOO
OOOOXOOX
OOOOXOXO
OOOOXOXX
OOOOXXOO
OOOOXXOX
OOOOXXXO
OOOOXXXX
OOOXOOOO
OOOXOOOX
OOOXOOXO
OOOXOOXX
OOOXOXOO
OOOXOXOX
OOOXOXXO
OOOXOXXX
OOOXXOOO
OOOXXOOX
OOOXXOXO
OOOXXOXX
OOOXXXOO
OOOXXXOX
OOOXXXXO
OOOXXXXX
OOXOOOOO
OOXOOOOX
OOXOOOXO
OOXOOOXX
OOXOOXOO
OOXOOXOX
OOXOOXXO
OOXOOXXX
OOXOXOOO
OOXOXOOX
OOXOXOXO
OOXOXOXX
OOXOXXOO
OOXOXXOX
OOXOXXXO
OOXOXXXX
OOXXOOOO
OOXXOOOX
OOXXOOXO
OOXXOOXX
OOXXOXOO
OOXXOXOX
OOXXOXXO
OOXXOXXX
OOXXXOOO
OOXXXOOX
OOXXXOXO
OOXXXOXX
OOXXXXOO
OOXXXXOX
OOXXXXXO
OOXXXXXX

Technical Manuals Online! - http://www.tech-man.com

&%$#"! 
ADDR
OXOOOOOO
064
OXOOOOOX
065
OXOOOOXO
066
OXOOOOXX
067
OXOOOXOO
068
OXOOOXOX
069
OXOOOXXO
070
OXOOOXXX
071
OXOOXOOO
072
OXOOXOOX
073
OXOOXOXO
074
OXOOXOXX
075
OXOOXXOO
076
OXOOXXOX
077
OXOOXXXO
078
OXOOXXXX
079
OXOXOOOO
080
OXOXOOOX
081
OXOXOOXO
082
OXOXOOXX
083
OXOXOXOO
084
OXOXOXOX
085
OXOXOXXO
086
OXOXOXXX
087
OXOXXOOO
088
OXOXXOOX
089
OXOXXOXO
090
OXOXXOXX
091
OXOXXXOO
092
OXOXXXOX
093
OXOXXXXO
094
OXOXXXXX
095
OXXOOOOO
096
OXXOOOOX
097
OXXOOOXO
098
OXXOOOXX
099
OXXOOXOO
100
OXXOOXOX
101
OXXOOXXO
102
OXXOOXXX
103
OXXOXOOO
104
OXXOXOOX
105
OXXOXOXO
106
OXXOXOXX
107
OXXOXXOO
108
OXXOXXOX
109
OXXOXXXO
110
OXXOXXXX
111
OXXXOOOO
112
OXXXOOOX
113
OXXXOOXO
114
OXXXOOXX
115
OXXXOXOO
116
OXXXOXOX
117
OXXXOXXO
118
OXXXOXXX
119
OXXXXOOO
120
OXXXXOOX
121
OXXXXOXO
122
OXXXXOXX
123
OXXXXXOO
124
OXXXXXOX
125
OXXXXXXO
126
OXXXXXXX
127
O = OPEN (or OFF)

&%$#"! 
ADDR
XOOOOOOO
128
XOOOOOOX
129
XOOOOOXO
130
XOOOOOXX
131
XOOOOXOO
132
XOOOOXOX
133
XOOOOXXO
134
XOOOOXXX
135
XOOOXOOO
136
XOOOXOOX
137
XOOOXOXO
138
XOOOXOXX
139
XOOOXXOO
140
XOOOXXOX
141
XOOOXXXO
142
XOOOXXXX
143
XOOXOOOO
144
XOOXOOOX
145
XOOXOOXO
146
XOOXOOXX
147
XOOXOXOO
148
XOOXOXOX
149
XOOXOXXO
150
XOOXOXXX
151
XOOXXOOO
152
XOOXXOOX
153
XOOXXOXO
154
XOOXXOXX
155
XOOXXXOO
156
XOOXXXOX
157
XOOXXXXO
158
XOOXXXXX
159
XOXOOOOO
160
XOXOOOOX
161
XOXOOOXO
162
XOXOOOXX
163
XOXOOXOO
164
XOXOOXOX
165
XOXOOXXO
166
XOXOOXXX
167
XOXOXOOO
168
XOXOXOOX
169
XOXOXOXO
170
XOXOXOXX
171
XOXOXXOO
172
XOXOXXOX
173
XOXOXXXO
174
XOXOXXXX
175
XOXXOOOO
176
XOXXOOOX
177
XOXXOOXO
178
XOXXOOXX
179
XOXXOXOO
180
XOXXOXOX
181
XOXXOXXO
182
XOXXOXXX
183
XOXXXOOO
184
XOXXXOOX
185
XOXXXOXO
186
XOXXXOXX
187
XOXXXXOO
188
XOXXXXOX
189
XOXXXXXO
190
XOXXXXXX
191
X = CLOSED (or ON)

ADDR
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255

&%$#"!

XXOOOOOO
XXOOOOOX
XXOOOOXO
XXOOOOXX
XXOOOXOO
XXOOOXOX
XXOOOXXO
XXOOOXXX
XXOOXOOO
XXOOXOOX
XXOOXOXO
XXOOXOXX
XXOOXXOO
XXOOXXOX
XXOOXXXO
XXOOXXXX
XXOXOOOO
XXOXOOOX
XXOXOOXO
XXOXOOXX
XXOXOXOO
XXOXOXOX
XXOXOXXO
XXOXOXXX
XXOXXOOO
XXOXXOOX
XXOXXOXO
XXOXXOXX
XXOXXXOO
XXOXXXOX
XXOXXXXO
XXOXXXXX
XXXOOOOO
XXXOOOOX
XXXOOOXO
XXXOOOXX
XXXOOXOO
XXXOOXOX
XXXOOXXO
XXXOOXXX
XXXOXOOO
XXXOXOOX
XXXOXOXO
XXXOXOXX
XXXOXXOO
XXXOXXOX
XXXOXXXO
XXXOXXXX
XXXXOOOO
XXXXOOOX
XXXXOOXO
XXXXOOXX
XXXXOXOO
XXXXOXOX
XXXXOXXO
XXXXOXXX
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL

2-19

Installation

2-20

Technical Manuals Online! - http://www.tech-man.com

+D=FJAH

Operation
This section provides instructions for
operating the MXL-IQ Control Panel.
Please review the introduction to the
MXL-IQ Control Panel at the beginning of
this manual.

ules and leaving gaps in the numbering,


provided you do not use the fixed addresses.

INTRODUCTION

The specific addresses of the System


modules are described in Table 17.

NOTE: See the Table of Contents pages at


the beginning of this manual for the order
of this chapter. Use it to find the answers to
specific questions when you are working
with the System.
TABLE 17
Fixed Module Addresses

Addresses
All modules and devices annunciated on the
MXL-IQ are identified by an address (MMMDDD). Each address is in two partsa
module address (MMM) and a device
address (DDD). The number identifying the
module may be as high as 254, and the
number identifying the device may be as
high as 248. Thus a device on a module
may be identified by any number between
001-001 and 253-250. (See Table 17.)
Fixed Addresses
A module may be assigned to any address
on the System, except for some fixed
addresses that have already been assigned
(See Table 17). The modules communicate
to the MXL-IQ Control Panel through a serial
communications network. The System
continuously supervises all of the modules
for presence and proper operation.

Module
Address

0
1
2
3
*
*
*
248
249
250
251
252
253
254
255

Module

Do not use
Analog loop 1 (SMB-2)
Analog loop 2 (SMB-2)

MKB-4
MKB-4
MKB-4
MKB-4, No. 1
Reserved
SMB-2
Programmer CSG-M
Global (reserved)

Device
Address
(Range)

0 01-060
0 01-060

0 01 to 250

You may assign a module to any address


on the System, and assign addresses in
any order, mixing different types of mod-

Technical Manuals Online! - http://www.tech-man.com

3-1

Operation

System Modules
ALD-2I Analog Loop Module
The ALD-2I takes two adjoining module
addresses. Loop 1 of the ALD-2I is at any
module address and loop 2 at the next
address. The analog loops on the SMB-2
are at module addresses 1 and 2 (See
Table 17, page 3-1) and cannot be moved.
The table below illustrates ALD-2I module
addresses:
ALD at Module
Addresses 3 and 4
Loop 1
Loop 2

Devices
003-001 to 003-060
004-001 to 004-060

ALD at Module
Addresses 15 and 16 Devices
Loop 1
015-001 to 015-060
Loop 2
016-001 to 016-060
CSM-4 Signal Module
The CSM-4 module contains two circuits
and two programmable LEDs.
Their device addresses on the module are
as follows:
Circuit 1

001

Circuit 2

002

LED 1

005

LED 2

006

For example, the address of circuit 2 on the


CSM-4 at module address 3 is 003-002.
CRM-4 Relay Module
The CRM-4 Relay module contains four
relays and two controllable LEDs.
Their device addresses on the module are
as follows:
Relay 1

001

Relay 2

002

Relay 3

003

Relay 4

004

LED 1

005

LED 2

006

For example, the address of relay 4 on the


CRM-4 at module address 20 is 020-004.

3-2

Technical Manuals Online! - http://www.tech-man.com

CZM-4 Conventional Zone Module


The CZM-4 Conventional Zone module
contains four conventional initiating device
zones and two programmable LEDs. Their
device addresses on the module are as
follows:
Zone 1

001

Zone 2

002

Zone 3

003

Zone 4

004

LED 1

005

LED 2

006

For example, the address of zone 1 on the


CZM-4, at module address 105, is 105-001.
MKB-4 Keyboard/Annunciator
The MKB-4 Keyboard/Annunciator occupies
the fixed module address 251 (See Table
17, page 3-1).
SMB-2 Main Board
The SMB-2 occupies module addresses 1,
2, and 253. The module addresses 1 and 2
are analog loops.
Module address 253 contains two notification appliance circuits (NACs) and two
relays. The device addresses at module
253 are as follows:
Common alarm relay
Common trouble relay
NAC 1
NAC 2

001
002
004
005

For example, the address of the common


alarm relay at module address 253 is
253-001.

Remote System Modules


MOI-7 Voice and Annunciator Driver
The MOI-7 occupies one network address
and one network node in the MXL-IQ
System. Set the address on S1 (See Figure
17, page 1-10) according to Table 16, page
2-19, so that it agrees with the address
assigned in CSG-M.
The MOI-7 has a set of 128 subaddresses
reserved for the MOD-16 open collector

Operation
outputs and MID-16 general purpose
inputs. This gives a maximum of 8 MOD-16
boards and 8 MID-16 boards.
The MOI-7 subaddress map is as follows.
001-016 MOD-16/MID-16
#1
017-032 MOD-16/MID-16
#2
033-048 MOD-16/MID-16
#3
049-064 MOD-16/MID-16
#4
065-080 MOD-16/MID-16
#5
081-096 MOD-16/MID-16
#6
097-112 MOD-16/MID-16
#7
113-128 MOD-16/MID-16
#8
The MOI-7 has two status LEDs:
The TRANSMIT LED indicates that the
MOI-7 is sending information to the SMB-2.
During normal operation this LED flashes
periodically when the SMB-2 requests the
MOI-7s status.
The TROUBLE LED only lights when the
MOI-7 cannot communicate with the
MXL-IQ. This is an indication that the
network connection between the MOI-7 and
SMB-2 is damaged.
MOD-16 (Open Collector Output Module)
The MOD-16 does not occupy a network
address. The MOD-16 is at a subaddress
of the MOI-7 to which it is connected. The
subaddresses of any given MOD-16s are
determined by their position in the string of
MOD-16s.
The output cable from the MOI-7 connects
to the first MOD-16, which has the
subaddress of 001-016 as shown above.
Each additional MOD-16 in the chain has
the next block of 16 addresses.
You may connect a maximum of 8
MOD-16s and MID-16s to an individual
MOI-7 for a total of 128 open collector
outputs and 128 general purpose inputs.

Technical Manuals Online! - http://www.tech-man.com

Using The MKB-4


Keyboard/Annunciator
Panel in Local Mode

See Figure 32, page 3-4, for the location of


the display keys and LEDs.
When the MKB-4 Keyboard/ Annunciator
Panel is installed, only the display, LEDs,
and display control keys are visible. The
ACKnowledge keys and other controls are
hidden behind a locked door. Unlock and
open the door to gain access to those keys
and controls.

The Display
The display has two lines of 40 characters
each. What is shown on the display depends on the state of the System. The
display contains a back light which turns on
automatically when any key is pressed or
an event is reported. The back light turns
off automatically after 5 minutes of system
inactivity.
The System has several displays. When
the System is Normal, the display shows:
[time/date]
[system message]

SYSTEM
NORMAL

When an event has been annunciated, the


System alternates between the following
three displays:
[address] [custom message] [ACK STATUS or BLANK]
[event number] [device type] [trouble type] [IN or 0UT]

[address] [type of device in trouble] or [BLANK] [ACK


STATUS or BLANK] [event number] [time/date] [IN or 0UT]
ALARMS=nnn
TROUBLES=nnn

SUPERVISORIES=nnn
SECURITIES=nnn

3-3

Operation
The terms used in the displays described
above are defined as follows:
ACK appears if the event has been
acknowledged; otherwise, the field is
blank.
IN is displayed when a condition occurs.
OUT is displayed when a normal state is
restored.

[time/date] shows the time and date the


event occurred.

Internal Audible Alarm


The internal audible alarm (not visible)
sounds steadily when there is an unacknowledged fire alarm. It pulses if all
alarms are acknowledged, but there is at
least one supervisory, trouble, or security
condition.

Q The Display

A 2-line display of 40 characters each that


shows the state of the System. A back light
turns on when any key is pressed or an
event is reported.

Figure 32
MKB-4 Keyboard/Annunciator Panel

3-4

Technical Manuals Online! - http://www.tech-man.com

R System Control Keypad

ALARM ACK - Press to acknowledge a


fire alarm.
AUD SIL - Press to silence or unsilence
a notification appliance circuit.
SUPV ACK - Press to acknowledge a
supervisory.
TRBL ACK - Press to acknowledge a
trouble.
SEC ACK - Press to acknowledge a
security condition.
RESET - Press to reset the System.

S Numeric Keypad

Use the numeric keypad (keys 0 through 9)


when the System asks for a model number,
device number, password, time, date, or
other information. The display shows each
number as you press the key (except when
you enter a password; the System shows
an asterisk for each digit of the password
that you type).

Command Keypad
Left arrow (|) - Press to select the item to
the left of what is flashing on the display
(unless entering a number).
Right arrow (}) - Press to select the item to
the right of what is flashing on the display
(unless entering a number).
Up arrow (~) - Press to go back to the
previous item.
ENTER - Press to select the item on which
the cursor is flashing. When typing in
numbers, press ENTER when finished to
complete the entry.
PRINT - Press to print selected lists and
reports.
FORM FEED - Press to advance the paper
in the printer.
CLEAR - Press to cancel printing begun by
pressing PRINT. The System will print:
This listing prematurely terminated.

HELP - Press to display a one-line help


message.

U The Special (ALT and Function) Keypad

Use the four function keys alone or in


combination with ALT1 or ALT2 to provide
a total of 12 special functions. When using
a combination, hold the ALT key down and
then press the function key.
F1
F2
F3
F4
ALT1-F1
ALT1-F2
ALT1-F3
ALT1-F4
Hold ALT, then press
ALT2-F1
function key.
ALT2-F2
ALT2-F3
ALT2-F4
The special function keys are defined using
the CSG-M Custom Software Generator
(See CSG-M Programming Manual, P/N
315-090381). These definitions can be
recorded in the box on the panel.

Technical Manuals Online! - http://www.tech-man.com

V Display Keys

Operation

The MXL-IQ has two display keys, NEXT


and HOLD, located on the MKB-4.
NEXT - Press NEXT to show the previous
item in a list of Alarms, Supervisories,
Troubles, or Security conditions.
HOLD - Press HOLD at any time to freeze
the present display. The display remains
frozen until HOLD is released.

LEDs
ALARM - This red LED flashes when there
is at least one unacknowledged fire alarm;
it glows steadily when all fire alarms are
acknowledged.
AUDIBLE SILENCE - This red LED flashes
when at least one notification appliance
circuit (NAC) is active; it glows steadily
when all silenceable NACs are silenced.
Under normal conditions, the LED is off.
SUPERVISORY - This yellow LED flashes
when there is at least one unacknowledged
supervisory; it glows steadily when all
supervisories are acknowledged.
TROUBLE - This yellow LED flashes when
there is at least one unacknowledged
trouble; it glows steadily when all troubles
are acknowledged.
SECURITY - This yellow LED flashes when
there is at least one unacknowledged
security condition; it glows steadily when all
security conditions are acknowledged.
POWER - This green LED glows steadily to
indicate that the AC power is on; it flashes
when the System is on battery backup.
PARTIAL SYSTEM DISABLE - This yellow
LED glows steadily when any device is
disabled.

Modes Of Operation

INTRODUCTION

The MXL-IQ alphanumeric display annunciator has five modes of operation:


1.
2.
3.
4.
5.

Alarm
Supervisory
Trouble
Security
Normal

3-5

Operation
This order ensures that fire alarms always
take priority over all other conditions. In turn,
supervisories always take priority over
troubles and troubles always take priority over
security conditions. All of the above modes
take priority over Normal mode, which is the
absence of any alarms, supervisories,
troubles, or security conditions.

Alarm
The alphanumeric display shows an alarm
message when a fire alarm is received.
See Alarm.

Supervisory
The alphanumeric display shows a supervisory message when the system receives a
supervisory and no higher priority event is
present. See Supervisories, page 3-8.

Trouble
The alphanumeric display shows a trouble
message when a trouble is present and no
higher priority event is present. See
Troubles, page 3-9.

Security

0
0
0
0

ALARM
SUPERV
TROUBLE
SECURITY

0
0
0
0

ALARM ACK
SUPERV ACK
TROUBLE ACK
SECURITY ACK

Alarm
RESPONDING TO AN ALARM
1. Follow the response plan approved by
the local authority having jurisdiction.
2. When the MXL-IQ is installed, the
ACKnowledge key and Audible Alarm
Silence key (AUD SIL) on the MKB-4
are behind a locked door. The display,
LEDs, and display control keys are
visible and accessible. To acknowledge
an alarm or trouble, or to silence an
audible alarm, first unlock and open the
door.

How The System Annunciates Fire


Alarms

Normal mode is the absence of any alarms,


supervisories, troubles, or security conditions.

When a fire is detected, the System causes


the ALARM LED on the MKB-4 to flash, the
Systems internal audible to sound, the
AUD SIL LED to flash, and the alphanumeric display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two fire alarms were received (Refer to the
explanations below).
Message 1:

In normal mode the display shows the


following message:

1-001 [custom message]


002 [device type] IN ALR

11:59:59 DEC 31, 20XX


SYSTEM
[custom system message] NORMAL

Message 2:

The alphanumeric display shows a security


message when a security condition is
received and no higher priority event is
present. See Security Conditions, page 3-10.

Normal Mode

The POWER LED glows steadily in normal


mode when the system has AC power. The
ALARM, AUDIBLE SILENCE, SUPERVISORY, TROUBLE, and SECURITY LEDs
are off and the internal audible is off.
If your System has the printer option, the
System prints a message in the following
format every day at midnight, even when
there are alarms or other conditions:

3-6

System Status at 00:00:00 Jul 02, 20XX

Technical Manuals Online! - http://www.tech-man.com

1-001 [custom message]


002 [time/date] IN ALR

Message 3:
ALARMS=002
SUPERVISORIES=000
TROUBLES=000
SECURITIES=000

In addition, the System responds to alarms


with programmed output functions such as
other audible signals.

Operation
In the messages above, 1-001 represents
the address of the device reporting the
alarm.
NOTE:

On the display, not all leading


zeros are shown. If your System
includes a printer, note that the
leading zeros are not shown.

002 in the first message tells you that this is


the second (and the most recent) of two
alarms received.
The status information in the third message
reports the total of alarms, supervisories,
troubles, and security conditions.
If your System includes a printer, it prints a
message from two to four lines long similar
to the following:
ALARM 1-1 11:59:59 DEC 31, 20XX
#1 [custom message], [device type]

In the preceding printed message, ALARM


indicates that the type of occurrence is a
fire alarm; 1-1 is the device address; #1 is
the number of the alarm in the list of fire
alarms; [custom message] is a custom
message entered using the CSG-M Custom Software Generator (See the CSG-M
Programming Manual, P/N 315-090381);
[device type] is the type of device which
reported the alarm.

Viewing the List of Alarms


To see the alarm list when there is more
than one alarm, press NEXT on the MKB-4
(the System displays the most recent alarm
first).

How to Block Acknowledge a Fire


Alarm (NFPA 72 Local, Municipal Tie,
and Remote Station)
1. Note the specific location of the alarm(s)
by using the procedures described
above.
2. Unlock and open the door.
3. Press ALARM ACK to acknowledge all
alarms. The System displays the
following message:
ALL ALARMS ACKNOWLEDGED.

4. If your System includes the printer


option, it prints the following message:
ACK ALARM 11:59:59 DEC 31,20XX
ALL ALARMS ACKNOWLEDGED

Technical Manuals Online! - http://www.tech-man.com

5. If you press ALARM ACK again, the


System displays ALL ALARMS
ACKNOWLEDGED.
The ALARM LED glows steadily to
indicate that all alarms are acknowledged.
If there are no supervisories, troubles, or
security conditions in the System, the
internal audible goes silent; if any of
those conditions still exist, the internal
audible pulses.

How to Individually Acknowledge a Fire


Alarm (NFPA 72 Proprietary, UL 1076)
1. Press ALARM ACK. The System
acknowledges the alarm displayed and
then displays the next unacknowledged
alarm.
If your System has the printer option, it
prints an alarm acknowledgment
message similar to the following:
ACK ALARM 1-5 12:01:28 DEC 31,20XX
#2 [custom message], [device type]

Note that the acknowledgments


message includes the term ACK to
indicate this alarm was acknowledged.
2. Continue acknowledging alarms as
explained above until the System
displays the following message: ALL
ALARMS ACKNOWLEDGED.
The ALARM LED glows steadily to
indicate that all alarms are acknowledged. If there are no supervisories,
troubles, or security conditions still in the
System, the internal audible goes silent;
if any of those conditions still exist, the
internal audible pulses.
3. If your System includes a printer, it prints
a message similar to the following:
ACK ALARM 12:05:44 DEC 31,20XX
ALL ALARMS ACKNOWLEDGED

Silencing The System


Press AUD SIL after all alarms are acknowledged. The System displays the
following message: AUDIBLES SILENCED.
(Pressing AUD SIL a second time causes
the internal audible and the System to
unsilence and the message AUDIBLES
UNSILENCED to appear on the display;

3-7

Operation
thus, pressing AUD SIL alternately silences
and unsilences the System.)
If your System has a printer, it prints a
message similar to the following:
AUD SILENCED/UNSIL. 11:01:00 DEC 31, 20XX
AUDIBLES SILENCED

Supervisories
How The System Annunciates
Supervisories
When a supervisory is detected, the
System causes the SUPERVISORY LED
on the MKB-4 to flash, the Systems
internal audible to sound, and the alphanumeric display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two supervisories were received (See the
explanations below).
Message 1:
1-001 [custom message]
002 [device type] IN SUP

Message 2:
1-001 [custom message]
002 [time/date] IN SUP

Message 3:
ALARMS=000
SUPERVISORIES=002
TROUBLES=000
SECURITIES=000

In addition, the System responds to


supervisories with programmed output
functions such as other audible signals.
In the messages above, 1-001 represents
the address of the device reporting the
supervisory.
002 in the first message tells you that this is
the second (and the most recent) of two
supervisories received.
The status information in the third message
reports the total of alarms, supervisories,
troubles, and security conditions.

3-8

Technical Manuals Online! - http://www.tech-man.com

If your System includes a printer, it prints a


message from two to four lines long similar
to the following:
SUPERV 1-1 11:59:59 DEC 31, 20XX
#1 [custom message], [device type]

In the preceding message, SUPERV


indicates that the type of occurrence is a
supervisory; 1-1 is the device address; #1
is the number of the supervisory in the list
of supervisories; [custom message] is a
custom message entered using the CSG-M
Custom Software Generator (See the CSG-M
Programming Manual, P/N 315-090381);
[device type] is the type of device which
reported the supervisory.

Viewing the List of Supervisories


To see the supervisory list when there is
more than one supervisory, press NEXT on
the MKB-4 (the System displays the most
recent supervisory first).

How to Block Acknowledge a


Supervisory (NFPA 72 Local, Municipal
Tie, and Remote Station)
1. Note the specific location of the
supervisories by using the procedures
described above.
2. Unlock and open the door.
3. Press SUPV ACK to acknowledge all
supervisories. The System displays the
following message:
ALL SUPERVISORIES ACKNOWLEDGED.

4. If your System includes a printer, it prints


the following message:
ACK SUPERVISORY 11:59:59 DEC 31,20XX
ALL SUPERVISORIES ACKNOWLEDGED

5. If you press SUPV ACK again, the


System displays ALL SUPERVISORIES
ACKNOWLEDGED.
The SUPERVISORY LED glows steadily
to indicate that all supervisories are
acknowledged. If there are no troubles or
security conditions in the System, the
internal audible goes silent; if any of
those conditions still exist, the internal
audible pulses.

Operation

How to Individually Acknowledge a


Supervisory (NFPA 72 Proprietary, UL
1076)
1. Press SUPV ACK. The System
acknowledges the supervisory displayed
and then displays the next
unacknowledged supervisory.
If your system has a printer, it prints an
acknowledgment message similar to the
following:
ACK SUPERV 1-5 12:01:28 DEC 3,20XX
#2 [custom message], [device type]

Note that the acknowledgment message


includes the term ACK to indicate this
supervisory was acknowledged.
2. Continue acknowledging supervisories
as explained above until the System
displays the following message: ALL
SUPERVISORIES ACKNOWLEDGED.
The SUPERVISORY LED glows steadily
to indicate that all supervisories are
acknowledged. If there are no troubles or
security conditions still in the System, the
internal audible goes silent; if any of
those conditions still exist, the internal
audible pulses.
3. If your System includes a printer, it prints
the following message:
ACK SUPERVISORY 12:05:44 DEC 3,20XX
ALL SUPERVISORIES ACKNOWLEDGED

Troubles
How The System Annunciates Troubles
When a trouble is detected, the System
causes the TROUBLE LED on the MKB-4
to flash, the Systems internal audible to
sound, and the alphanumeric display on the
MKB-4 to alternate in a sequence among
the three messages shown below. This
example assumes that two troubles were
received (See the explanations below).

Message 2:
1-001 [device type]
002 [time/date] IN TBL

Message 3:
ALARMS=000
SUPERVISORIES=000
TROUBLES=002
SECURITIES=000

In addition, the System responds to


troubles with programmed output functions.
In the messages above, 1-001 represents
the address of the device reporting the
trouble.
002 in the first message tells you that this is
the second (and the most recent) of two
troubles received.
The status information in the third message
reports the total of alarms, supervisories,
troubles, and security conditions.
If your System includes a printer, it prints a
message from two to four lines long similar
to the following:
TROUBLE IN 1-1 11:59:59 DEC 31, 20XX
#1 [custom message] [trouble type], [device type]

In the above printed message, TROUBLE


indicates that the type of occurrence is a
trouble; 1-1 is the device address; and #1 is
the number of troubles in the list of troubles;
[custom message] is a custom message
entered using the CSG-M Custom Software
Generator (See the CSG-M Programming
Manual, P/N 315- 090381); [trouble type]
is the type of trouble which reported;
[device type] is the type of device in
trouble.

Viewing The List of Troubles


To see the trouble list when there is more
than one trouble, press NEXT on the
MKB-4 (the System displays the most
recent trouble first).

Message 1:
1-001 [custom message]
002 [trouble type] IN TBL

Technical Manuals Online! - http://www.tech-man.com

3-9

Operation

How to Block Acknowledge a Trouble


(NFPA 72 Local, Municipal Tie, and
Remote Station)
1. Note the specific location of the
trouble(s) by using the procedures
described above.
2. Unlock and open the door.
3. Press TRBL ACK to acknowledge all
troubles. The System displays the
following message: ALL TROUBLES
ACKNOWLEDGED.
4. If your System includes a printer, it prints
the following message:
ACK TROUBLE 11:59:59 DEC 31, 20XX
ALL TROUBLES ACKNOWLEDGED

5. If you press TRBL ACK again, the


System displays
ALL TROUBLES ACKNOWLEDGED.

The TROUBLE LED glows steadily to indicate that all troubles are acknowledged.
If there are no security conditions in the
System, the internal audible goes silent;
if any security conditions still exist, the
internal audible pulses.

The TROUBLE LED glows steadily to


indicate that all troubles are acknowledged. If there are no security conditions
still in the System, the internal audible
goes silent; if any of those conditions still
exist, the internal audible pulses.
3. If your System includes a printer, it prints
the following message:
ACK TROUBLE 12:05:44 DEC 31, 20XX
ALL TROUBLES ACKNOWLEDGED

Security
How The System Annunciates Security
Conditions
When a security condition is detected, the
System causes the SECURITY LED on the
MKB-4 to flash, the Systems internal
audible to sound, and the alphanumeric
display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two security conditions were received (See
the explanations below the messages).
Message 1:
1-001 [custom message]
002 [device type] IN SEC

How to Individually Acknowledge a


Trouble (NFPA 72 Proprietary, UL 1076)
1. Press TRBL ACK. The System
acknowledges the trouble displayed and
then displays the next unacknowledged
trouble.
If your System has a printer, it prints an
acknowledgment message similar to the
following:
ACK TROUBLE 1-5 12:01:28 DEC 31,20XX
#2 [custom message], [trouble type],
[device type]

Note that the acknowledgment message


includes the term ACK to indicate this
trouble was acknowledged.
2. Continue acknowledging troubles as
explained above until the System
displays the following message:
ALL TROUBLES ACKNOWLEDGED.

3-10

Technical Manuals Online! - http://www.tech-man.com

Message 2:
1-001 [custom message]
002 [time/date] IN SEC

Message 3:
ALARMS=000
TROUBLES=000

SUPERVISORIES=000
SECURITIES=002

In addition, the System responds to security


conditions with programmed output functions.
In the messages above, 1-001 represents
the address of the device reporting the
security condition.
002 in the first message tells you that this is
the second (and the most recent) of two
security conditions received.

Operation
The status information in the third message
reports the total number of alarms, supervisories, troubles, and security conditions.
If your System includes a printer, it prints a
message from two to four lines long similar
to the following:
SECURITY IN 1-1 11:59:59 DEC 31, 20XX
#1 [custom message], [device type]

In the preceding printed message, SECURITY indicates that the type of occurrence
is a security condition; 1-1 is the device
address; #1 is the number of the security
condition in the list of security conditions;
[custom message] is a custom message
entered using the CSG-M Custom Software
Generator (See the CSG-M Programming
Manual, P/N 315-090381); [device type] is
the type of device which reported the
security condition.

3. If your System includes a printer, it prints


the following message:
ACK SECURITY 12:05:44 DEC 31, 20XX
ALL SECURITY CONDITIONS ACKNOWLEDGED

Reset Procedures
Hard Reset
Other terms for Hard Reset are Power-up,
Initialization, and Cold Reset.
Applying power to the System performs a
Hard Reset which initializes (starts) the
entire system.
What Is Lost:
Alarms, supervisories, troubles, security
conditions
Any user entries such as time and date

Viewing the List of Security Conditions

Arm/disarm

To see the security condition list when there


is more than one security condition, press
NEXT on the MKB-4 (the System displays
the most recent security condition first).

Manual sensitivity adjustment

How to Individually Acknowledge a


Security Condition (UL 1076)
1. Press SEC ACK. The System
acknowledges the security condition
displayed and then displays the next
unacknowledged security condition.
If your System has a printer, it prints an
acknowledgment message similar to the
following:
ACK SECURITY 1-5 12:01:28 DEC 3,20XX
#2 [custom message], [device type]

Note that the acknowledgment message


includes the term ACK to indicate this
security condition was acknowledged.
2. Continue acknowledging security
conditions as explained above until the
System displays the following message:
ALL SECURITY CONDITIONS
ACKNOWLEDGED.
The SECURITY LED glows steadily to
indicate that all security conditions are
acknowledged, and the internal audible
goes silent.

Technical Manuals Online! - http://www.tech-man.com

Time-based control until time is reset


What Is Not Lost:
CSG-M program

Soft Reset
To perform a Soft Reset, press RESET on
the MKB-4 (Refer to Figure 32, page 3-4).
Soft reset does not work until you acknowledge all alarms, supervisories, troubles,
and security conditions and silence the
System.
What Is Lost:
Alarms, supervisories, troubles, security
conditions
Arm/disarm (unless option disabled by
CSG-M)
What Is Not Lost:
Any user entries such as time and date.
Arm/disarm (when enabled by CSG-M)
CSG-M program
Manual sensitivity adjustment
Time-based control

3-11

Operation
If you press RESET before acknowledging
all conditions and silencing the audible
alarms, the display shows a message
similar to the following:
ALARMS NOT ALL ACKNOWLEDGED YET

(or)
SUPERVISORY NOT ALL ACKNOWLEDGED YET

(or)
TROUBLES NOT ALL ACKNOWLEDGED YET

(or)
SECURITY NOT ALL ACKNOWLEDGED YET

(or)
AUDIBLES NOT ALL SILENCED YET

If your System has a printer, it prints a


message similar to the following and adds
SYSTEM NOT RESET on the bottom line:
RESET 0:1 1:58 Jul 03,20XX
Not All Acknowledged Yet. System Not
Reset.

When the System performs a Soft Reset,


the display shows the following message:
SYSTEM RESET

The System then returns to Normal mode


and the display shows the following:
11:59:59 DEC 31, 20XX
[custom System message]

SYSTEM
NORMAL

If your System has a printer, it prints the


following message:
SYSTEM RESET

If the System is already in Normal mode


when you press RESET, it displays
SYSTEM ALREADY NORMAL

and does not reset.

3-12

Technical Manuals Online! - http://www.tech-man.com

Using The MKB


Keyboard/Annunciator
Panel in Global Mode
The Global MKB Keyboard/Annunciator
Panel operates the same as described
in Using The MKB Keyboard/Annunciator
Panel Local Mode, except as noted below.

Limitations/Restrictions
As in all networked MXL Systems, the
self-restoring trouble option is not
allowed in any MXL.
An MXL still may only contain a maximum of 4 supervised MKBs. This can be
a mix of local and global MKBs.
BLOCK ACK must be enabled in the
CSG-M.
The maximum number of supervised
Global MKBs is 10.
The maximum number of Global Printers
is 2 (not TSP-40s).

Global MKB Display Format


In order to insert the XNET node information and provide an indication of the number
of events in the System, some of the
characters in the first and second lines
have been lost.
NN = NODE # (1 - 64)
MMM = MODULE # (1 - 253)
DDD = DEVICE # (1 - 254)
ALARM
The 3 event displays are formatted as
follows for an alarm condition:
NN:MMM-DDD [custom message]
ACK
1 [time/date]
IN ALR
NN:MMM-DDD [custom message]
ACK
1 [device type]
IN ALR
ALARMS=1
TROUBLES=0

SUPERVISORY=0
SECURITY=0

Operation
SUPERVISORY
The 3 event displays are formatted as
follows for a supervisory condition:
NN:MMM-DDD [custom message]
ACK
1 [time/date]
IN SUP
NN:MMM-DDD [custom message]
ACK
1 [device type]
IN SUP
ALARMS=0
TROUBLES=0

SUPERVISORY=1
SECURITY=0

TROUBLE
The 3 event displays are formatted as
follows for a trouble condition:
NN:MMM-DDD [custom message]
ACK
23 [trouble type]
IN TRB
NN:MMM-DDD [custom message]
ACK
23 [time/date]
IN TRB
ALARMS=0
TROUBLES=23

SUPERVISORY=0
SECURITY=0

Global Keypad Operation


BLOCK ACK
Global block acknowledgment operates as
in a standalone MXL, but with global scope.
Events for the queue acknowledge System
wide (all nodes).
Pressing a global BLOCK ACK key results
in a broadcast XNET message to all nodes
to acknowledge all events in that queue.
Panels process the event just as if the key
press had occurred at one of its MKBs. A
success code (or error code) is sent to the
NODE that initiated the global acknowledge.
An acknowledgment message is displayed
and printed (and the appropriate LED is
updated) when the MXL determines all
events at that level have been acknowledged (System wide). The time/date stamp
of an event is used to determine the true
state of the System.

SECURITY
The 3 event displays are formatted as
follows for a security condition:

LEDs are not updated unless all nodes


confirm the acknowledgment has been
successfully executed.

NN:MMM-DDD [custom message]


ACK
2 [time/date]
IN SEC

AUD SILENCE
This key is NOT a toggle as in a local
mode. If silenceable audibles are active
anywhere in the System, the LED flashes.

NN:MMM-DDD [custom message]


ACK
2 [device type]
IN SEC
ALARMS=0
TROUBLES=0

SUPERVISORY=0
SECURITY=2

Leading zeros are not included in addresses and counts.


Additional data causes a three character
shift right, resulting in the loss of three
characters from the displayed message.
Additional data also causes a two character
shift to the right, resulting in the loss of two
characters of the device or trouble type.
The System queue totals are over 10,000
events. This expands the event number fields
to 5 digits from 3. The order of these events
is as follows:
Queue priority (Alarm, Supervisory,
Trouble, Security).
Time and date of event (newest first).
If the two previous items are identical,
the lower node number takes priority.

Technical Manuals Online! - http://www.tech-man.com

When the global AUD SILENCE key is


pressed with any/all audibles in the System
unsilenced, a global silence command is
issued. The command is processed in the
nodes as if a local audible silence had been
requested.
Command preprocessing is in place to
prevent silenceable audibles from getting
out of sync (some systems on, some
systems off) on a System basis. No
audibles will be silenced unless all can be
silenced. However, in cases where local
control is enabled, this may be unavoidable.
An error code (or success via a silence
event message) allows the global MKB to
keep up to date as to true System status. If
any panel reports an error, the display
status remains unchanged.
When the global AUD SILENCE key is
pressed with all audibles in the System
silenced, a global unsilence command is
issued. The command is processed in the

3-13

Operation
nodes as if a local audible unsilence had
been requested. An error code (or success
via a silence event message) allows the
global MKB to keep up to date as to true
System status. If any panel reports an
error, the display status changes since
some audibles have been unsilenced.
RESET
When the global reset key is pressed, each
node is tested. If all nodes meet the
conditions required for reset, the reset
command is sent and executed. Otherwise,
the corresponding error message is displayed.

Using The Menu

The menu gives you wide control of the


MXL-IQ System. You may use the menu no
matter what mode the System is in.
The discussion in this section is in the
following order:
Operation of the keys on the MKB-4
Keyboard/Annunciator
Overview of the menus structure
Beginning a menu session
Introduction to each of the four menus:
- Acknowledge menu
- List menu

NEXT
This key operates the same as in the local
mode. However, it moves the user through
the System events globally in the priority
order established earlier.

- Control menu
- Test menu
- Entering your password
- Entering module and device numbers

HOLD
This key operates the same as in the local
mode.

Using the Acknowledge menu

Function Keys
These keys operates the same as in the
local MKB.

Using the Test menu

Numeric Keypad
These keys operates the same as in the
local MKB.

Using the List menu


Using the Control menu

Operation of the Keys on the MXL-IQ


Annunciator Panel
Use the numeric keypad and the directional
and command keypad when working with
the menu.

Numeric Keypad
Use the numeric keypad (keys 0 through 9)
when the System asks for a module
number, device number, password, time,
date, or other information. The display
shows each number as you press the key.
However, when you enter a password, the
System shows asterisks in place of the
digits entered.

The Command Keypad


The Command Keypad has both directional
and command keys that are used to move
through the menu and perform specific
functions. Refer to Table 18 for a description of the Command Keypad.

3-14

Technical Manuals Online! - http://www.tech-man.com

Operation

Overview of the Menus Structure


Press ENTER to enter the menu. The
menu then uses the first 32 spaces of the
second line of the display to communicate
with you. When you use the Acknowledge
or List menu, the menu uses both lines of the
display.

Acknowledge

Alarm
Supervisory (Supervsry)
Trouble
Security

TABLE 18
COMMAND KEYPAD
Key Purpose

| on the display (unless entering a number).

Select the item to the left of what is flashing


Select the item to the right of what is

} flashing on the display (unless entering a


number).

~
ENTER

Go back to the previous item.


Press to select the item on which the cursor
is flashing. After typing in numbers, press

If you are in the menu and do not depress a


numeric or arrow key at any time during a 1
minute period, the System returns to the
previous item.
The five Main Menu items and their subitems
for Revision 6.0 and higher follow; the
shortened terms used in the menu itself are
in parentheses:
List1

Status
Alarm
Supervisory (Supervsry)
Trouble
Security
Sensitivity (Senstvty)
Voltages
- Analog
- Threshold
- Sensitivity
Temp
Module type (Mod type)
Device type (Dev type)
Message
Software version
(SW version)
Output States
Device Usages
Node Address
Analaser
- Smoke-lev
- Flow-lev
- Trip-pts
Percent/ft
- Senstvty
- Pre-alarm
- Analog
ASD apps
1

You can generate a


printed report or listing
for every item in the List
menu except Node
Address; see the
discussion under LIST
Menu.

Control

Reset
Sensitivity (Senstvty)
- Hi_3
- Hi_2
- Hi_1
- Norm
- Low_1
- Low_2
- Low_3
Arm/disarm (Arm/dis)
- Arm
- Disarm
Output on/off
- Arm
- Disarm
- Energize
- De-Energize
Loop Arm
Loop Disarm
Netlink Request
Analaser
- Alarm_Trip
- Flow_Trip
Percent/Ft
- Sensitivity
(Senstvty)
- Pre_alarm
Change_Apps

Test

Set time
Ground fault (Gnd_flt)
- Main
Power2
- Main
- Voltage
- Current
Lamp test
- LEDs
- Display
Device LED
MOI_Lamp_Test
X-Network
M-Network
Override
Det_cleaned
Event_log
- Alrm_only
- Trbl_only
- Superv_only
- Security_only
- All_events
- Hist_Ctrl
- Hist_Erase
Pyro_diags
Pre_alarm
ASD_Devices
Summarize
Manual_Activate
2

You can generate a


printed report for this
item; see the discussion
under TEST Menu.

ENTER to complete the entry.

HELP

Press to display a one-line message.

PRINT

Press to begin printing various lists and


reports.

FORM
FEED

Press to advance the paper in the printer.

CLEAR

Press to cancel printouts begun by pressing


PRINT. The System will print:
This listing prematurely terminated.

Technical Manuals Online! - http://www.tech-man.com

Walktest

System_wAUD
Loop_wAUD
Zone_wAUD
System_SIL
Loop_SIL
Zone_SIL
Cancel
Extend

3-15

Operation

Beginning a Menu Session


When you first press ENTER to begin a
menu session, the second line of the
display shows the four Main Menu items:
ACKNOWLEDGE
TEST

LIST

CONTROL

The A in Acknowledge is blinking. Select


Acknowledge by pressing ENTER while the
A is blinking.
Use the Left and Right arrow keys to move
around in this four-item menu.

LIST

CONTROL

TEST

For help in understanding what the List


function does, press HELP when the L in
LIST is blinking. The System displays:
TO LIST SYSTEM, DEVICE, CSGM INFO

Use this function to list information on the


System and its devices.
To return to the Main Menu display, press
HELP again:
ACKNOWLEDGE

LIST

CONTROL

TEST

To end a menu session and return to the


Main Menu or to leave the menu at any
time, press the Up arrow key to go backward one menu each time.

We discuss the List menu in detail beginning


on page 3-22.

Introduction to the Acknowledge Menu

Introduction to the Control Menu

The Main Menu, displayed when you press


ENTER to begin a menu session, lists the
four main items in the menu:
ACKNOWLEDGE
TEST

LIST

CONTROL

For help in understanding what the Acknowledge function does, press HELP when the
A in ACKNOWLEDGE is blinking. The
System displays:
TO ACKNOWLEDGE INDIVIDUALLY

Use this menu function to acknowledge


alarms, supervisories, troubles, and
security conditions individually.
To return to the Main Menu display, press
HELP again:
ACKNOWLEDGE
TEST

LIST

CONTROL

We discuss the Acknowledge menu in


detail beginning on page 3-18.

Introduction to the List Menu


To move to LIST on the Main Menu, press
the Right arrow key once; the L in LIST
begins blinking:

3-16

ACKNOWLEDGE

Technical Manuals Online! - http://www.tech-man.com

To move to CONTROL on the Main Menu,


press the Right arrow key twice from
ACKNOWLEDGE; the C in CONTROL
begins blinking:
ACKNOWLEDGE

LIST

CONTROL

TEST

For help in understanding what the Control


function does, press HELP while the C in
CONTROL is blinking. The System displays:
TO MODIFY DATA FOR OPERATION

Use the Control function to reset the System


and to change the settings of various devices.
To return to the Main Menu display, press
HELP again:
ACKNOWLEDGE

LIST

CONTROL

TEST

We discuss the Control menu in detail


beginning on page 3-36.

Introduction to the Test Menu


To move to TEST, press the Right arrow
key three times from ACKNOWLEDGE; the
T in TEST begins blinking:
ACKNOWLEDGE

LIST

CONTROL

TEST

For help in understanding what the Test


function does, press HELP while the T in
TEST is blinking. The System displays:

Operation
TO TEST SYSTEM, LOOP & DEVICE

Use this function to test the System, its


loops, and its devices, including ground
fault, battery voltage and current, and the
LEDs.
To return to the Main Menu display, press
HELP again:
ACKNOWLEDGE

LIST

CONTROL

TEST

We discuss the Test menu in detail beginning on page 3-42.

Entering Your Password


If you select CONTROL, TEST, or WALKTEST, the System asks for your password:
ENTER YOUR PASSWORD:

The System gives you three chances to


enter an acceptable password before it
returns you to the Main Menu.
If the System accepts your password, it
displays the Control, Test, or Walktest
menu. We discuss those menus later in this
section.

Entering a Module Number and Device


Number
The System asks you to supply a module
number or device number, or both, during
certain functions described in the pages
that follow. Below is a summary of the
procedures involved.
NOTE:

The terms module number and


module address are used interchangeably in this manual.

Entering a Module Number


The System displays

If you press HELP, the System explains


this function; press HELP again to return to
the previous display.

TYPE IN MODULE NUMBER:

Type your (1-5 digit) password, using the


numeric keypad. The System shows an
asterisk for each digit that you type. (Use
the Left arrow key to erase an error.)

If you press HELP at this point, the System


displays the following explanation:

When you have typed the entire password,


press ENTER. If your password does not
match a password stored in the System,
the System briefly displays the following
message and then returns you to the first
password display:
ACCESS DENIED

If your password level is not high enough to


use the Test functions, the System briefly
displays the following message and then
returns you to the first password display:

3 DIGIT MODULE NO., PRESS <ENTER>

Press HELP again to return to the previous


display. Type all three digits, including
leading zeros, and press ENTER.
When you type the module number, use
the Left arrow key as a backspace key to
erase errors.

Entering a Device Number with the


Module Number
The System displays
TYPE IN THE DEVICE NUMBER:

PASSWORD LEVEL NOT HIGH ENOUGH

(If you press HELP at this point, the System


displays the following explanation:
PASSWORD LEVELS
Rev 5.0 and Above
Highest
Test
Z
Control
Lowest
Walktest
Below Rev 5.0
Highest

Y
Lowest

Walktest
Test
Control

Technical Manuals Online! - http://www.tech-man.com

3 DIGIT MODULE 3 DIGIT DEVICE

Press HELP again to return to the previous


display. Type all of the digits, including
leading zeros, and press ENTER.)

3-17

Operation
When you type the module number and
the device number, use the Left arrow
key as a backspace key to erase errors.

If All Alarms Are Acknowledged:


If all the alarms are acknowledged, the
System displays the following message and
then returns you to the Acknowledge menu.

ACKNOWLEDGE Menu

ALL ALARMS ACKNOWLEDGED

The Acknowledge menu has four items


from which to choose; the shortened
terms used in the menu itself are in
parentheses:
ALARM
SUPERVISORY (SUPERVSRY)
TROUBLE
SECURITY

If There Is an Unacknowledged Alarm:


If there is at least one unacknowledged
alarm, the menu shows the most recent
unacknowledged alarm on both lines of the
display, as in the following display:

Use this menu to individually acknowledge fire alarms, supervisories, troubles,


and security conditions.

29-041 [custom message]


007 [device type] IN ALR

Entering the Acknowledge Menu

In the above display, 29 is the module


number, 041 is the device number, the
message on the first line is the custom
message for the device at that location, 007
indicates that this is the seventh alarm,
[device type] indicates the type of device
in alarm, and IN ALR indicates that this is a
fire alarm.

Select ACKNOWLEDGE from the Main


Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays the first Acknowledge menu (the
A in ALARM is blinking):
ACKNOWLEDGE: ALARM SUPERVISRY

NOTE:

To end a menu session and


return to the Main Menu or to
leave the menu at any time,
press the Up arrow key to go
backward one menu each time.

Acknowledge: Alarm
Use this function to individually acknowledge fire alarms.
Press ENTER when the A in ALARM is
blinking to select ACKNOWLEDGE ALARM:
ACKNOWLEDGE: ALARM SUPERVISRY

If There Is No Alarm:
If there is no current alarm, the System
briefly displays the following message
and then returns you to the Acknowledge
menu:
NO ALARM EXISTS

(If your System has a printer, it prints the


above message as well.)

3-18

(If your System has a printer, it prints the


above message as well.)

Technical Manuals Online! - http://www.tech-man.com

(Press HELP if you want information on


what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT
TO SKIP.

Press HELP again to return to the previous


display.)
Press ENTER to acknowledge the alarm
shown.
The System prints a message similar to the
following and removes that alarm from the
unacknowledged alarm list:
ACK ALARM 29-041 16:11:41 Aug 28,20XX
#7 [custom message], [device type]

In the above message, the time and date


are the time and date that the alarm was
acknowledged and 29-041 is the address.
The System then displays the next alarm to
acknowledge.
To skip an alarm shown, press NEXT. The
System displays the next alarm in the
series. When the System has displayed all

Operation
of the unacknowledged alarms, it returns to
the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY

(To end a menu session and return to the


Main Menu or to leave the menu at any
time, press the Up arrow key to go backward one menu each time.)

If There Is An Unacknowledged Supervisory:


The System does not let you acknowledge
supervisory conditions if there are any
unacknowledged alarms. If there is at least
one unacknowledged alarm, the System
briefly displays the following message and
then returns you to the Acknowledge menu:
ALARM NOT ALL ACKNOWLEDGED YET

Acknowledge: Supervsry
Use this function to individually acknowledge supervisories.

Select ALARM and follow the instructions


in ACKNOWLEDGE ALARM above.

Select ACKNOWLEDGE from the Main


Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays:

(If your System has a printer, it prints the


above message as well.)

ACKNOWLEDGE: ALARM SUPERVISRY

Press the Right arrow key once to cause the


S in SUPERVISRY to blink.
(If you press HELP at this time, the System
explains the Acknowledge Supervisory
function:
TO ACK SUPERVISORY INDIVIDUALLY

Press HELP again to return to the ACKNOWLEDGE: ALARM SUPERVISRY


display.)
Press ENTER while the S is blinking to
select SUPERVISRY.
If There Is No Supervisory:
If there is no supervisory to acknowledge,
the System briefly displays the following
message and then returns you to the Acknowledge menu:
NO SUPERVISORY EXISTS

(If your System has a printer, it prints the


above message as well.)
If All Supervisories Are Acknowledged:
If all supervisories are acknowledged, the
System briefly displays the following
message and then returns you to the
Acknowledge menu:
ALL SUPERVISORIES ACKNOWLEDGED

Technical Manuals Online! - http://www.tech-man.com

After you acknowledge all alarms, the


System allows you to acknowledge
supervisories. If there is at least one
unacknowledged supervisory, the menu
shows the most recent unacknowledged
supervisory on both lines of the display, as
in the following display:
32-045 [custom message]
012 [device type]
IN SUP

In the preceding display, 32 is the module


number, 045 is the device number, the
message on the first line is the custom
message for the device at that location, 012
indicates that this is the twelfth supervisory,
[device type] indicates the type of device
causing the supervisory, and IN SUP identifies the item as an off-normal supervisory.
(Press HELP if you want information on
what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT
TO SKIP

Press HELP again to return to the previous


display.)
Press ENTER to acknowledge the supervisory shown. The System prints a message
similar to the following and removes that
supervisory from the unacknowledged
supervisory list:
ACK SUPERV 32-045 16:11:44 Aug 2,20XX
#12 [custom message], [device type]

In the above message, the time and date


are the time and date the supervisory was
acknowledged and 32-045 is the address.

3-19

Operation
The System then displays the next supervisory to acknowledge.
To skip a supervisory, press NEXT. The
System displays the next supervisory in the
series. When the System has displayed all
of the unacknowledged supervisories, the
System returns to the acknowledge menu
on the second line of the display.
(To end a menu session and return to the
Main Menu or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)

Acknowledge: Trouble
Use this function to individually acknowledge troubles.
Select ACKNOWLEDGE from the Main
Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY

Press the Right arrow key twice. The


System displays the Acknowledge menu
with T in TROUBLE blinking:
ACKNOWLEDGE: SUPERVISRY TROUBLE

(If you press HELP at this time, the System


explains the Acknowledge Trouble function:
TO ACK TROUBLE INDIVIDUALLY

Press HELP again to return to the acknowledge menu.)


Press ENTER while the T is blinking to select
Trouble.

ALL TROUBLES ACKNOWLEDGED

(If your System has a printer, it prints the


above message as well.)
If There Is An Unacknowledged Trouble:
The System does not let you acknowledge
troubles if there are any unacknowledged
fire alarms or supervisories. Follow the
instructions above to acknowledge them.
After you acknowledge all fire alarms and
supervisories, the System allows you to
acknowledge troubles. If there is at least
one unacknowledged trouble, the System
shows the most recent unacknowledged
trouble on both lines of the display, as in
the following display:
36-050 [custom message]
018 [trouble type]
IN TBL

In the above display, 36 is the module


number, 050 is the device number, the
message on the first line is the custom
message for that device, 018 indicates that
this is the eighteenth trouble, [trouble
type] indicates the type of trouble, and IN
TBL identifies the event as the occurrence
of a trouble.
(Press HELP if you want information on
what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT
TO SKIP.

Press HELP again to return to the previous


display.)

If There Is No Trouble:
If there is no trouble to acknowledge, the
System briefly displays the following
message and returns you to the acknowledge menu:

Press ENTER to acknowledge the trouble


shown. The System prints a message
similar to the following message and
removes that trouble from the unacknowledged trouble list:

NO TROUBLE EXISTS

ACK TROUBLE 36-050 16:11:44 Aug 8, 20XX


#18 [custom message], [trouble type]
[device type]

(If your System has a printer, it prints the


above message as well.)

3-20

If All Troubles Are Acknowledged:


If all the troubles are acknowledged, the
System displays the following message and
returns you to the Acknowledge menu:

Technical Manuals Online! - http://www.tech-man.com

Operation
In the above message, the time and date
are the time and date that the condition was
acknowledged and 36-050 is the address.
The System then displays the next trouble
to acknowledge.

If All Security Conditions Are Acknowledged:


If all security conditions are acknowledged,
the System displays the following message
and returns you to the Acknowledge menu:
ALL SECURITIES ARE ACKNOWLEDGED

When the System has displayed all of the


unacknowledged troubles, it returns to the
Acknowledge menu.

(If your System has a printer, it prints the


above message as well.)

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

If There Is An Unacknowledged Security


Condition:
The System does not let you acknowledge
security conditions if there are any unacknowledged alarms, supervisories, or
troubles.

Acknowledge: Security
Use this function to individually acknowledge security conditions.
Select ACKNOWLEDGE from the Main
Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY

Press the Right arrow key three times. The


System displays the second Acknowledge
menu, with the S in SECURITY blinking:
ACKNOWLEDGE: TROUBLE SECURITY

(If you press HELP at this time, the System


explains the Acknowledge Security function:
TO ACK SECURITY INDIVIDUALLY

Press HELP again to return to the Acknowledge menu.)


Press ENTER while the S is blinking to
select Security.
If There Is No Security Condition to Acknowledge:
If there is no Security condition to acknowledge, the System briefly displays the
following message and then returns you to
the Acknowledge menu:
NO SECURITY EXISTS

(If your System has a printer, it prints the


above message as well.)

Technical Manuals Online! - http://www.tech-man.com

If there is at least one unacknowledged


alarm, the System briefly displays the
following message and then returns you to
the Acknowledge menu:
ALARMS NOT ALL ACKNOWLEDGED YET

(If your System has a printer, it prints the


above message as well.)
Follow the instructions above to acknowledge any unacknowledged alarms,
supervisories, and troubles.
After you acknowledge all fire alarms,
supervisories, and troubles, the System
allows you to acknowledge security conditions. If there is at least one unacknowledged
security condition, the System displays the
most recent unacknowledged security
condition:
42-058 [custom message]
005 [device type]
IN SEC

In the above display, 42 is the module


number, 058 is the device number, the
message on the first line is the custom
message for the device at that location, 005
indicates that this is the fifth security
condition, [device type] indicates the type
of device causing the security condition, and
IN SEC identifies this as an off-normal
security condition.
(Press HELP if you want information on
what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT
TO SKIP.

Press HELP again to return to the previous


display.)

3-21

Operation
Press ENTER to acknowledge the security
condition shown. The System prints a
message similar to the following message
and removes that security condition from
the unacknowledged security list:

Software version (SW version)

ACK SECURITY 42-058 16:11:44 Aug 8,20XX


#5 [custom message], [device type]

Analaser

Output states
Device usages
Node address
Percent/ft
ASD_apps

In the above message, the time and date


given are the time and date when the
security condition was acknowledged, and
42-058 is the address.
The System then displays the next security
report to acknowledge.
To skip a security condition, press NEXT.
The System displays the next security
condition in the series. When the System
has displayed all of the unacknowledged
security conditions, it returns to the Acknowledge menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

LIST Menu

The List menu has eighteen items from


which to choose; the shortened terms used
in the menu are in parentheses.
You can generate a printed list or report for
every item on the List menu except Node
Address. See the discussion for each item
that follows.
Status
Alarm

Use the List menu to learn the following


information:
Status of the System
Alarm information
Supervisory information
Trouble information
Security information
Detector sensitivity
Detector voltage
Analog
Threshold (Thresh)
Sensitivity (Sens)
Temperature of FP-11 or FPT-11
Type of module
Type of device
Custom message of the given
address
Version of the System software
Output states
Device usages
Panel's X-Network node address
Percent per foot obscuration
Sensitivity
Pre-alarm
Analog
Device application (ASD setting)

Supervisory (Supervsry)
Trouble
Security
Sensitivity (Senstvty)
Voltages
Temp
Module type (Mod type)

Entering the List Menu


From the Main Menu, use the Left or Right
arrow key to cause the L in List to blink.
If you press HELP at this point, the System
explains the List function:
TO LIST SYSTEM, DEVICE, CSGM INFO

Device type (Dev type)


Message

3-22

Technical Manuals Online! - http://www.tech-man.com

Press HELP again to return to the Main


Menu.

Operation
Press ENTER to select LIST. The System
displays the first List menu, with the S in
STATUS blinking:
LIST: STATUS ALARM SUPERVSRY

(To end a menu session and return to the


Main Menu or to leave the menu at any
time, press the Up arrow key to go backward one menu each time.)

In the above printed message, there are


two alarms, both of them acknowledged, no
supervisory conditions, 30 trouble conditions, all acknowledged, and no security
conditions.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Alarm

List: Status
The List Status function shows you the
number of acknowledged and unacknowledged alarms, supervisories, troubles, and
security conditions, in that order.
From the List menu, use the Right or Left
arrow keys to cause the S in STATUS to
blink.
(If you press HELP at this point, the System
explains the List Status function:

The List Alarm function shows you all the


fire alarms currently in the System in the
order they occurred.
From the List menu, use the Left or Right
arrow key to cause the A in ALARM to
begin blinking.
If you press HELP at this point, the System
explains the List Alarm function:
SHOW INDIVIDUAL ALARM STATUS

SHOW NUMBER OF ACKED & UNACKED

Press HELP again to return to the List


menu.
Press HELP again to return to the List
menu.)
When you press ENTER to select List
Status, the display first shows the total
number of alarms and the number of
acknowledged alarms:
2 ALARM

2 ALARM ACK

Press ENTER to select ALARM and display


alarm information on the MKB-4 display.
If There Is No Fire Alarm:
If there is no fire alarm, the System briefly
displays the following message and then
returns you to the List menu:
NO ALARM EXISTS

To view, in order, the status of


supervisories, troubles, and security
conditions, press NEXT.
After the Security display, the System
returns to the List menu.

If There Is a Fire Alarm:


If there is at least one fire alarm, the System
shows the most recent alarm, alternating
between the following two displays:

To make a printed list of current status,


press PRINT when the S in STATUS is
blinking. The System will print a listing
similar to the following:

1-001 [custom message]


002 [device type]
IN ALR

System Status at 11:02:26 Jul 01, 20XX:


2 ALARM 2 ALARM ACK 0 SUPERV
0 SUPERV ACK
30 TROUBLE 30 TROUBLE ACK
0 SECURITY 0 SECURITY ACK

1-001 [custom message]


002 [time/date]

Technical Manuals Online! - http://www.tech-man.com

IN ALR

Press NEXT to show the two displays for the


previous alarm in the sequence. (Pressing
HOLD freezes a display for as long as you
keep HOLD depressed.)

3-23

Operation
When the System has shown all current fire
alarms, it returns to the List menu.

alternating between the following two


displays:

To obtain a full printed list of alarms in


the following formatone item for each
current alarmpress PRINT when the A in
ALARM is blinking.

1-001 [custom message]


002 [device type]

IN SUP

1-001 [custom-message]
002 [time/date]

IN SUP

Listing of all Alarm at 14:35:20 Oct 09,20XX:


ALARM 1-5 14:34:22 Oct 09,20XX #1
[custom message], [device type]

In the above listing, 1-5 is the address of


the device in alarm, the time is the time the
device went into alarm, #1 is the number of
this alarm in the current list, [custom
message] is the custom message for the
device in alarm, and [device type] is the
type of device in alarm.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Supervisory
The List Supervisory function shows you all
the supervisories currently in the System in
the order they occurred.
From the List menu, use the Left or Right
arrow key to cause the S in SUPERVSRY
to blink.
(If you press HELP at this point, the System
explains the List Supervisory function:
SHOW INDIVIDUAL SUPERVISORY

When the System has shown all current


supervisories, it returns to the List menu.
To obtain a full printed list of
supervisories in the following formatone
item for each current supervisorypress
PRINT when the S in SUPERVISORY is
blinking.
Listing of all Supervsry at 14:35:20 Oct 09,20XX:
SUPERV IN 32-45 14:34:22 Oct 09, 20XX
#7 [custom message], [device type]

In the preceding listing, 32-45 is the address of the device in supervisory, #7 is the
number of the supervisory in the current list,
[custom message] is the custom message
for the device in supervisory, and [device
type] is the type of device in supervisory.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Press HELP again to return to the List


menu.)

List: Trouble

Press ENTER to select SUPERVSRY and


display supervisory information on the
MKB-4 display.

The List Trouble function shows you all the


troubles currently in the System in the order
they occurred.

If There Is No Supervisory:
If there is no supervisory, the System briefly
displays the following message and then
returns you to the List menu:

3-24

Press NEXT to show the two displays for the


previous supervisory in the sequence.
(Pressing HOLD freezes a display for as
long as you keep HOLD depressed.)

From the List menu, use the left or right


arrow key three times to cause the T in
TROUBLE to blink.
(If you press HELP at this point, the System
explains the List Trouble function:

NO SUPERVISORY EXISTS

SHOW INDIVIDUAL TROUBLE STATUS

If There Is a Supervisory:
If there is at least one supervisory, the
System shows the most recent supervisory,

Press HELP again to return to the List


menu.)

Technical Manuals Online! - http://www.tech-man.com

Operation
Press ENTER to select TROUBLE and
display trouble information on the MKB-4
display.

List Security Conditions

If There Is No Trouble:
If there is no trouble, the System briefly
displays the following message and then
returns to the List menu:

From the List menu, use the left or right


arrow key to cause the S in SECURITY to
blink.

NO TROUBLE EXISTS.

The List Security function shows you all the


security conditions currently in the System in
the order they occurred.

(If you press HELP at this point, the System


explains the List Security function:
SHOW INDIVIDUAL SECURITY STATUS

If There Is a Trouble:
If there is at least one trouble, the System
shows the most recent trouble, alternating
between the following two displays:
1-001 [custom message]
002 [trouble type]

IN TBL

1-001 [device type]


002 [time/date]

IN TBL

Press NEXT to show the two displays for the


previous trouble in the sequence. (Pressing
HOLD freezes a display for as long as you
keep HOLD depressed.)
When the System has shown all current
troubles, it returns to the List menu.
To obtain a full printed list of troubles in
the following formatone item for each
current troublepress PRINT when the T
in TROUBLE is blinking.
Listing of all Trouble at 14:35:20 Oct 09, 20XX:
TROUBLE IN 29-41 14:34:22 Oct 09, 20XX
#7 [custom message],[trouble type],
[device type]

Press HELP again to return to the List


menu.)
Press ENTER to select SECURITY and
display security information on the MKB-4
display.
If There Is No Security Condition:
If there is no security condition, the System
briefly displays the following message and
then returns you to the List menu:
NO SECURITY EXISTS

If There Is a Security Condition:


If there is at least one security condition,
the System shows the most recent security
condition, alternating between the following
two displays:
1-001 [custom message]
002 [device type]

IN SEC

1-001 [custom message]


002 [time/date]

IN SEC

In the above listing 29-41 is the address of


the device in trouble, the time tells when the
device went into trouble, #7 is the number
of this trouble in the current list, [custom
message] is the custom message for the
device in trouble, [trouble type] is the type
of trouble, and [device type] is the type of
device in trouble.

Press NEXT to show the two displays for the


previous security condition in the sequence.
(Pressing HOLD freezes a display for as
long as you keep HOLD depressed.)

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

To obtain a full printed list of security


conditions in the following format one
item for each current security condition
press PRINT when the S in SECURITY is
blinking.

Technical Manuals Online! - http://www.tech-man.com

When the System has shown all current


security conditions, it returns to the List
menu.

3-25

Operation
Listing of all Security at 14:35:20 Oct 09,20XX:
SECURTY IN 29-42 14:34:22 Oct 09,20XX
#7 [custom message], [device type]

In the above listing 29-42 is the address of


the device causing the security condition, the
time when the device caused the security
condition, #7 is the number of this security
condition, [custom message] is the custom
message for the device causing the security
condition, and [device type] is the type of
device causing the security condition.

Press NEXT to display the address and


sensitivity setting of each succeeding
smoke detector. When the System has
shown the sensitivity settings of all smoke
detectors on that analog loop, it returns to
the List menu.
To leave the List Sensitivity menu without
going through the entire analog loop, press
the Up arrow key. The System displays the
List menu.

To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.

Print the Sensitivity Setting of All Smoke


Detectors Assigned to a Specified Module
Press PRINT when the S in SENSTVTY is
blinking. The System then asks for a
module number.

List: Sensitivity Settings

TYPE IN MODULE NUMBER: [module number]

Use List Sensitivity to show sensitivity


setting of individual smoke detectors on
analog loops.
From the List menu use the left or right
arrow key to cause the S in SENSTVTY to
start blinking:
LIST: TROUBLE SECURITY SENSTVTY

Type the three-digit module number and


press ENTER. (Enter all leading zeros.)
The System prints the sensitivity settings
(Hi_3, Hi_2, Hi_1, Norm, Low_1, Low_2 or
Low_3, or ... if there is no smoke detector) of
all the devices assigned to the analog loop.
Sensitivities for module 1

(If you press HELP at this point, the System


displays:
SHOW DETECTOR SENSITIVITIES

1- HI_3
6- ...
11- NORM

2- ... 3- NORM 4- ... 5- ...


7- ... 8- ... 9- ... 10- ...
12- ... 13- ... 14- ... 15- LOW1

NOTE: You cannot print the sensitivity


setting of a single smoke detector.
Note that List Sensitivity shows the sensitivity of smoke detectors only. Press HELP
again to return to the List menu.)
Display the Sensitivity Setting of One Device
Press ENTER to select List Sensitivity. The
System asks you for a module and device
number.
TYPE IN MODULE & DEVICE: 001-001

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)
The System displays the sensitivity setting
of the device specified (Hi_3, Hi_2, Hi_1,
Norm, Low_1, Low_2 or Low_3 ).

3-26

Technical Manuals Online! - http://www.tech-man.com

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Voltages
Use List Voltages to show the voltages of
initiating devices on analog loops.
From the List menu press the Left or Right
arrow key to cause the V in VOLTAGES to
start blinking:
LIST: SECURITY, SENSTVTY, VOLTAGES

Operation
(If you press HELP at this point, the System
displays:

If the module number entered is not an


analog loop, the System displays:

SHOW DETECTOR VOLTAGES

Not Analog Loop.

Press HELP again to return to the List menu.)

If the device address has no device assigned by CSG-M, the System displays:

Display the Voltage of One Device


Press ENTER to select List Voltages. The
System asks you for a module number and
device number. Type the three-digit module
number and three-digit device number
using the numeric keypad and press
ENTER. (Enter all leading zeros.) The
System shows the following menu for that
device (the A in ANALOG will be blinking):

No Device Assigned.

001-001 ANALOG THRESH SENS

Press ENTER to show the Analog voltage


for that device. When you ask for any
voltage, the System displays Please wait for
response until it receives a reading from
the device; if you have just reset the
System, it alternates the above message
with the message Device being initialized.
The display for Analog voltage is similar to
the following (readings are dynamic):
001-001 ANALOG2 = 2.75 VOLTS

Press ENTER to return to the previous


display. To view the Threshold or Sensitivity
voltage of any device listed, use the Right
and Left arrow keys to highlight the first
letter of the category desired and press
ENTER.
The display for Threshold voltage is similar
to the following:
001-001 THRESHOLD = 4.75 VOLTS

The display for Sensitivity voltage is similar


to the following (readings are dynamic):
001-001 SENSITIVITY = 2.62 VOLTS

When displaying sensitivities, if the device is


not a smoke detector, the System displays:
Not a Smoke Detector.

Print the Voltage of All Devices Assigned to a


Specified Module
Press PRINT when the V in Voltages is
blinking. The System asks you for a module
number. Type the three-digit module number
and press ENTER. (Enter all leading
zeros.)
002-001 Analog Thresh Sens

Press ENTER to print the Analog voltage


for all devices assigned to the module
(ND = No Device).
ANALOG VOLTAGES FOR MODULE 1
1- 2.00 2- 2.00 3- ND 4- ND 5- ND
6- ND
7- ND
8- ND 9- ND 10- ND
11- ND 12- ND 13- ND 14- ND 15- ND

To print the Threshold voltages of all the


devices for the specified module, use the
arrow keys to cause the T in THRESH to
blink and press PRINT. The System prints
those threshold voltages in a format similar to
the following (ND = No Device):
THRESHOLD VOLTAGES FOR MODULE 1
1- 4.75 2- 4.75 3- ND 4- ND 5- ND
6- ND
7- ND 10- ND 8- ND 9- ND
11- ND 12- ND 13- ND 14- ND 15- ND

Press the Up arrow key to return to the List:


Voltage Mod_type Dev_type menu.

Technical Manuals Online! - http://www.tech-man.com

3-27

Operation
To print the Sensitivity voltages of all the
smoke detectors for the specified module,
use the arrow keys to cause the S in SENS
to blink and press PRINT. The System
prints those sensitivity voltages in a format
similar to the following (ND = No Device, or
device not a smoke detector):
SENSITIVITY VOLTAGES FOR
1- 2.75 2- 2.62 3- ND
6- ND
7- ND
10- ND
11- ND 12- ND
13- ND

MODULE 1
4- ND 5- ND
8- ND 9- ND
14- ND 15- ND

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

To leave the Temp menu without going


through all subaddresses, press the Up
arrow key. The System displays the List
menu.

List: Module Type


Use the List Mod_type to show the type of
a particular module.
From the List menu use the Left or Right
arrow key to cause the M in MOD TYPE to
start blinking:
LIST: VOLTAGES MOD TYPE SENSTVTY

(If you press HELP at this point, the System


explains this function:
SHOW THE TYPE OF MODULE

List: Temp
Use List Temp to display the current
temperature on the LCD display at the
location where the detector is installed.
From the List menu use the left or right
arrow key to cause the T in Temp to start
blinking:
LIST: TEMP

Press ENTER to select List Temp. The


System asks you for a module and device
number:
Type In Module & Device:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER.
If the device is not installed or is not an
FP-11 or FPT-11, the system displays
following message:
Not Applicable or No Device:

Press HELP again to return to the List


menu.)
Display the Module Type of One Module
Press ENTER when the M in MOD_ TYPE
is blinking. The System asks you for a
module number:
TYPE IN MODULE NUMBER:

Type the three-digit module number using


the numeric keypad and press ENTER.
(Enter the leading zeros.) The System
displays the module type for the module
number specified:
MOD 074 TYPE: CZM4

If you press NEXT, the System displays the


module type for the next module number in
the sequence:
MOD 075 TYPE: ALD

If the device is an FP-11 or FPT-11, the


temperature is displayed in the following
format:
001-001

25 DEG C / 77 DEG F

NOTE:

If you enter a module number not


assigned in CSG-M, the System
displays:

NO MOD ASSIGNED

Press NEXT to display the temperature of


the FP-11 or FPT-11 at the next higher
address in the same loop.

3-28

Technical Manuals Online! - http://www.tech-man.com

With each press of NEXT, the System


continues to display module types through

Operation
number 255, the highest module number
allowed by the System. It then returns to
the List menu.
Print the Module Type and Network Address of
All Modules
Press PRINT when the M in MOD_ TYPE is
blinking to print a full list of module types
and their Network addresses. The System
prints a list similar to the following:
Listing of Module Types:
1- V7 ALD
2- V7 ALD
3- V4 CZM-4
251- V5 MKB-4
253- V1 MXL-IQ Panel

In the above display, the number following


the V (for example, V7) is the software
version number of the software installed in
the module.

meric keypad and press ENTER. (Enter all


leading zeros.) The System displays the
device type for the address specified:
004-001 TYPE: [device type]

If you press NEXT, the System displays the


device type for the next device in the
sequence:
004-002 TYPE: [device type]

With each press of NEXT, the System


continues to display device types until there
are no more devices for that module. The
System then returns to the List menu. To
proceed to another module, follow the
preceding instructions.

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Print a List of Devices Assigned to a Specified


Module
Press PRINT when the D is blinking to
select LIST DEVICE. The System asks you
for a module number:

List: Device Type

TYPE IN MODULE NUMBER:

Use List Device Type to show the type of a


particular device.
From the List menu use the Left or Right
arrow key to cause the D in DEV_TYPE to
start blinking:
LIST: VOLTAGES MOD TYPE DEV TYPE

(If you press HELP at this point, the System


displays:
SHOW THE TYPE OF DEVICE

Press HELP again to return to the List menu.)


Display the Device Type of a Specified Device
Press ENTER when the D is blinking to
select LIST DEV_TYPE.
The System asks you for a module and
device number:
TYPE IN MODULE & DEVICE:

Type the three-digit module number and


three-digit device number using the nu-

Technical Manuals Online! - http://www.tech-man.com

Type only the module number and press


PRINT. (Enter all leading zeros.) The
System prints a list of all device types
assigned to the specified module in a
format similar to the following:
Listing of Device Types Module 1 (ALD):
1-TRI-60D Dual Switch Input
2-TRI-60D Dual Switch Input
4-TRI-60D Switch input + Relay
5-TRI-60 Switch Input
7-TRI-60 Switch Input
10-ID-60T-135 Thermal Detector
11-ID-60T-135 Thermal Detector
15-ID-60I Ionization Detector
16-ID-60I Ionization Detector

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Message
Use List Message to show the CSG-M
assigned custom message of a particular
device.

3-29

Operation
From the List menu use the Left or Right
arrow key to cause the M in MESSAGE to
start blinking:
LIST: MOD TYPE DEV TYPE MESSAGE

(If you press HELP at this point, the System


displays:
SHOW MESSAGE FOR A DEVICE

Type only the module number and press


PRINT. (Enter all leading zeros.) The
System prints a list of all the custom device
messages for the specified module in a
format similar to the following:
Listing of Messages in Module 1 (ALD):
4-Conf.Rm
5-Cafeteria
6-Exec. Off. 1
7-Cmptr Rm
8-Exec. Off. 2
9-Camera Rm
10-Exec. Off. 3
11-Conf. Rm

Press HELP again to return to the previous


display.)

(To end a menu session and return to the


Main Menu or to leave the menu at any
time, press the Up arrow key to go backward one menu each time.)

Display the Device Message of a Specified


Device
Press ENTER when the M in MESSAGE is
blinking to select List Message.

List: Software Version

The System asks you for a module and


device number:
TYPE IN MODULE & DEVICE:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. The
System displays the message for the
address specified:

Use List Software Version to show:


1. System Custom Message
2. MXL-IQ Software Version
3. Version of CSG-M used to Create the
System
4. CSG-M File Name Installed
5. Date and Time of Installation
From the List menu use the Left or Right
arrow key to cause the S in S/W_VERSION
to start blinking:
LIST: S/W VERSION STATUS

069-001 [custom message]

(If you press HELP at this point, the System


displays:
If you press NEXT, the System displays the
message for the next device number in the
sequence:

SHOW SOFTWARE VERSION

069-002 [custom message]

Press HELP again to return to the previous


display.)

With each press of NEXT, the System


continues to display device messages until
there are no more devices for that module.

Display the Software Version of Your System


Software
Press ENTER when the S is blinking to
select List S/W_VERSION.

To proceed to another module, follow the


preceding instructions.

Print a List of System Messages for a Specified


Module
Press PRINT when the M in MESSAGE is
blinking to select List Message. The
System asks you for a module number:
TYPE IN MODULE NUMBER:

3-30

Technical Manuals Online! - http://www.tech-man.com

The System displays the CSG-M assigned


System custom message:
MSG [system custom message]

Press NEXT again to display the MXL-IQ


software version:
MXL-IQ VERSION: [version number]

Operation
Press NEXT again to display the version of
CSG-M used to create this System.

Press HELP again to return to the List menu.)

CSG VERSION: [version number]

Display the Output States of One Device


Press ENTER to select List Output States.
The System asks you for a module and
device number.

Press NEXT again to display the CSG-M


file name installed.

TYPE IN MODULE & DEVICE: 001-001

SOURCE: [file name]

Press NEXT again to display the date and


time of CSG-M installation:
LOADED: [time and date]

Print the Software Version of Your System


Software
Press PRINT when the S in SW_ VERSION is blinking to select List S/
W_Version. The System prints the System
Custom Message, MXL-IQ Software
Version, Version of CSG-M Used to Create
the System, CSG-M File Name Installed,
and Date and Time of Installation:
Software Version Information at
11:35:30 Jul 01, 20XX
Installation: [system custom message]
MXL-IQ Version: 1.00
CSG Version: 6.09
Source: 05OCT00
Loaded: 16:09:35 Oct 05, 20XX

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

List: Output States


Use List Output States to show the current
states of individual outputs in the MXL-IQ.
From the List menu use the left or right
arrow key to cause the O in Output States
to start blinking:
LIST: OUTPUT STATES

(If you press HELP at this point, the


System displays:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)
The System displays the output state of the
device specified.
Press NEXT to display the address and
output state of each succeeding device.
When the System has shown the output
states of all devices at that address, it
returns to the List menu.
To leave the List output state menu without
going through all subaddresses, press the
Up arrow key. The System displays the List
menu.
Print the Device Output State of Devices
Assigned to a Specified Module
Press PRINT when the O in Output States
is blinking. The System then asks for a
module number.
TYPE IN MODULE NUMBER: [module number]

Type the three-digit module number and


press ENTER. (Enter all leading zeros.)
The System prints the output state of all of
the devices assigned to that module.
Listing of Output States for Module 1 (ALD):
1-Auxiliary Output: OFF
2-Auxiliary Output: ON
3-Auxiliary Output: ON
4-Auxiliary Output: OFF

List: Device Usages


Use List Device Usages to show the uses
of individual devices as programmed in
CSG-M.

SHOW/PRINT OUTPUT STATES

Technical Manuals Online! - http://www.tech-man.com

3-31

Operation
From the List menu, use the left or right
arrow key to cause the D in DEV_USAGES
to start blinking:

Listing of Device Usages for module 1 (ALD)


1- ALARM
2- TROUBLE
3- STATUS
4- ALARM
5- TROUBLE
6- OUTPUT ONLY

LIST: DEV USAGES

List: Node Address


(If you press HELP at this point, the System
displays:

Use List Node Address to show the panel's


X-Net node address.

SHOW/PRINT DEVICE USAGES

From the List menu, use the left or right


arrow key to cause the N in NODE ADDRESS to start blinking:

Press HELP again to return to the List


menu.)

LIST: NODE ADDRESS

Display the Usage of One Device


Press ENTER to select List Dev_usages.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE: 001-001

Display the Node Address


Press ENTER to select List Node Address.
The System displays the X-Net node
address for that particular MXL-IQ panel.

List: Analaser
Use List ANALASER to display operational
characteristics of the AnaLASER devices.

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)
The System displays the use of the device
specified (i.e., Alarm, Trouble, or Status).
Press NEXT to display the address and use
of each succeeding device. When the
System has shown the uses of all devices
at that address, it returns to the List menu.
To leave the List Dev_usage menu without
going through all subaddresses, press the
Up arrow key. The System displays the List
menu.
Print the Device Usages of Devices Assigned to
a Specified Module
Press PRINT when the D in DEV_USAGES
is blinking. The System then asks for a
module number.
TYPE IN MODULE NUMBER: [module number]

Type the three-digit module number and


press ENTER. (Enter all leading zeros.)
The System prints the uses of all of the
devices assigned to that module.

3-32

Technical Manuals Online! - http://www.tech-man.com

Press ENTER when the A in ANALASER is


blinking to select List ANALASER.
Use the Left or Right arrow to move to the
following selections:
ANALASER: Smoke Lev
Trip Pts

Flow Lev

(If you press HELP at this point, the System


displays:
DISPLAY ANALASER SMOKE LEVEL

Press HELP again to return to the List


menu.)
List Analaser Smoke_Lev
Press ENTER when the S in SMOKE_LEV
is blinking to select List ANALASER
SMOKE_LEV.
The System asks you for a module and
device number:
TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device address number using the numeric keypad

Operation
and press ENTER. The system displays the
smoke level for the address specified:
010-004

50%

>>!*

*<<

PRE1

The bar graph in the example above shows


the following information for the AnaLASER
device at address 010-004:
50% = 50% of full scale smoke level
!
= active trip point at 30%
*
= inactive trip point at 60% and 100%
PRE1 indicates the device is in PreAlarm 1
PRE2 and ALRM indicate the PreAlarm 2
and Alarm states, respectively. The bargraph continuously updates to reflect the
current state of the AnaLASER zone that is
being viewed.
Print the AnaLASER Smoke Level
Press PRINT when the S in SMOKE_LEV
is blinking to print the ANALASER
SMOKE_LEV.

TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device address number using the numeric keypad
and press ENTER. The System displays
the air flow level for the address specified:
010-004

50%

>>!

* <<

NORM

The bar graph in the example above shows


the following information for the AnaLASER
device at address 010-004:
50% = 50% of full scale air flow level
!
= low air flow trip point at 20%
*
= high air flow trip point at 90%
NORM indicates that the current air flow
level is at a normal level, HIGH indicates
airflow is too high, and LOW indicates
airflow is too low. The bar graph continuously updates to reflect the current state of
the AnaLASER zone that is being viewed.

The System asks you for a module number:


TYPE IN MODULE NUMBER:

Type the three-digit NIM-1R (ANA) module


number and press ENTER. The System
sends smoke levels for all devices on the
selected MODULE to the printer.
AnaLASER Smoke Levels at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX
0% Scale >> . . .<< NORM, Cust Msg 1
010-002 13:23:32 Jan 03,20XX
100% Scale >>!!!<< ALRM, Cust Msg
010-010 13:23:31 Jan 03,20XX
42% Scale >>! .
.<< PRE1, Cust Msg 10
010-011 13:23:32 Jan 03,20XX
100% Scale >>!!
.<< PRE2, Cust Msg 11

For printed bar graphs, the characters


shown below indicate the following:
. = an inactive trip point
! = an active trip point
List Analaser Flow_Lev
Press ENTER when the F in FLOW_LEV is
blinking to select LIST ANALASER
FLOW_LEV.
The System asks you for a module and
device number:

Technical Manuals Online! - http://www.tech-man.com

Print the AnaLASER Flow Level


Press PRINT when the F in FLOW_LEV is
blinking to print the ANALASER
FLOW_LEV.
The System asks you for a module number:
TYPE IN MODULE NUMBER:

Type the three-digit NIM-1R (ANA) module


number and press ENTER. The System
sends air flow levels for all devices on the
selected MODULE to the printer.
AnaLASER Air Flow Levels at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX
0% Scale >> .
. << LOW, Cust Msg 1
010-002 13:23:32 Jan 03,20XX
100% Scale >>! !<< HIGH, Cust Msg
010-010 13:23:31 Jan 03,20XX
42% Scale >>!
. << NORM, Cust Msg 10
010-011 13:23:32 Jan 03,20XX
100% Scale >>!
. << NORM, Cust Msg 11

List Analaser Trip_pts


Press ENTER when the T in TRIP_PTS is
blinking to select LIST ANALASER
TRIP_PTS.

3-33

Operation
The System prompts you to select between
ALARM_TRIP and FLOW_TRIP.
Press ENTER when the A in ALARM_TRIP
is blinking to select LIST TRIP_PTS
ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device address number using the numeric keypad
and press ENTER. The System displays
the current alarm trip point settings for the
address specified:
010-004 P1: 20%

P2: 60%

ALM: 90%

Print the AnaLASER Alarm Trip Pts


Press PRINT when the A in ALARM_TRIP
is blinking to print the ANALASER
ALARM_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:

Type the three-digit NIM-1R (ANA) module


number and press ENTER. The System
sends alarm trip point levels for all devices
on the selected MODULE to the printer.

010-004

LOW:

20%

HIGH:

80%

Print the AnaLASER Flow Trip Pts


Press PRINT when the F in FLOW_TRIP
is blinking to print the ANALASER
FLOW_TRIP points.
The System asks you for a module number:
TYPE IN MODULE NUMBER:

Type the three-digit NIM-1R (ANA) module


number and press ENTER.
The System sends air flow trip point levels
for all devices on the selected MODULE to
the printer.
AnaLASER Air Flow Trip Points at 13:23:31 Jan 03, 20XX
010-001 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 90%,
Cust Msg 1
010-002 13:23:31 Jan 03,20XX, LOW: 20% HIGH: 80%,
Cust Msg 1
010-010 13:23:31 Jan 03,20XX, LOW: 30% HIGH: 70%,
Cust Msg 1
010-011 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 80%,
Cust Msg 1

List: Percent/ft

AnaLASER Alarm Trip Points at 13:23:31 Jan 03, 20XX


010-001 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 30%
ALRM: 100%, Cust Msg 1
010-002 13:23:31 Jan 03,20XX, PRE1: 30% PRE2: 50%
ALRM: 90%, Cust Msg 2
010-010 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 50%
ALRM: 100%, Cust Msg 10
010-011 13:23:31 Jan 03,20XX, PRE1: 50% PRE2: 80%
ALRM: 100%, Cust Msg 11

Use List Percent/ft to show settings in


percent/ft obscuration of the ILI and ILP
Series detectors.

Press ENTER when the F in FLOW_TRIP is


blinking to select LIST TRIP_PTS
FLOW_TRIP.

Press ENTER to select List Percent/ft. The


System asks you for a module and device
number.

The System asks you for a module and


device number.

TYPE IN MODULE & DEVICE: 001-001

TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device ad-

3-34

dress number using the numeric keypad


and press ENTER. The System displays
the current air flow trip point settings for the
address specified:

Technical Manuals Online! - http://www.tech-man.com

From the List menu, use the left or right


arrow key to cause the P in PERCENT/FT
to start blinking:
LIST: PERCENT/FT

Type in the three-digit module number and


the three-digit device number using the
numeric keypad and press ENTER. The
System displays the following menu for that
device (the S in Senstvty will be blinking):

Operation
002-003 SENSTVTY

PRE-ALARM

ANALOG

List Percent/ft Senstvty


The display for Sensitivity supplies the
current sensitivity as read back from the
detector and is similar to the following
(readings are dynamic):
002-003 SENS 1.4%/FT

NORM

List Percent/ft Pre-alarm


The display for Pre-alarm supplies the
current Pre-alarm setting read back from
the detector and is similar to the following
(readings are dynamic):
002-003 PRE-ALARM 1.4%/FT

NORM

The System prints either the Sensitivity, Prealarm, or Analog of all the devices for the
specified module in a format similar to the
following (NA = ID-60 detector):
%/ft SENSITIVITIES FOR MODULE 2
1-3.00 2-NA
3-1.4 4-3.1 5-1.4
6-1.4 7-ND
8-ND
9-ND
10-ND
11-ND 12-ND 13-ND 14-ND 15-ND
16-ND 17-ND 18-ND 19-ND 20-ND
21-ND 22-ND 23-ND 24-ND 25-ND
26-ND 27-ND 28-ND 29-ND 30-ND
31-ND 32-ND 33-ND 34-ND 35-ND
36-ND 37-ND 38-ND 39-ND 40-ND
41-ND 42-ND 43-ND 44-ND 45-ND
46-ND 47-ND 48-ND 49-ND 50-ND
51-ND 52-ND 53-ND 54-ND 55-ND
56-ND 57-ND 58-ND 59-ND 60-ND

List: ASD_apps
Use List ASD_apps to display operational
characteristics of the ASD devices.

List Percent/ft Analog


The display for Analog supplies the current
analog2 reading read from the detector and
is similar to the following (readings are
dynamic):
002-003 SENS 1.4%/FT

NORM

To leave the Percent/ft menu without going


through all subaddresses, press the Up
arrow key. The System displays the List
menu.
Print the Analog Loops Current Readings in
Percent/ft Obscuration
Press PRINT when the P in Percent/ft is
blinking. The System asks you for a module
number.

From the List menu use the left or right


arrow key to cause the A in ASD_Apps to
start blinking:
LIST: ASD APPS

Display the Operational Characteristics of One


Device
Press ENTER to select ASD_apps. The
System asks you for a module and device
number:
TYPE IN MODULE & DEVICE:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)

TYPE IN MODULE NUMBER:

The System displays the currently assigned


application for the device specified. (Refer to
the ASD Submenu Abbreviations on page I-1.)

Type the three-digit module number using


the numeric keypad and press ENTER. The
System shows the following menu for that
device (the S in Senstvty will be blinking):

Press NEXT to display the address and


assigned application of each succeeding
device. The System will exit the ASD_Apps
menu if there are no more ASD devices in
that module.

001-001 SENSTVTY

PRE-ALARM

Technical Manuals Online! - http://www.tech-man.com

ANALOG

To leave the List ASD_Apps menu at any


time, press the Up arrow key. The System
displays the List menu.

3-35

Operation
To print the operational characteristics of the ASD
devices assigned to an ALD Loop
Press PRINT when the A in ASD_Apps is
blinking. The System asks you for a module
number:

Arm/Disarm (Arm/dis)
Arm
Disarm
Output_on/off
Arm

TYPE IN MODULE NUMBER:

Disarm
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.) The System prints
a list of all the applications currently assigned to all the ASD devices in that ALD
loop in a format similar to the following (ND
= No Device):
1-NONE
6-ND
11-ND
16-ND
21-ND
26-ND
31-ND
36-ND
41-ND
46-ND
51-ND
56-ND

2-PARK
7-ND
12-ND
17-ND
22-ND
27-ND
32-ND
37-ND
42-ND
47-ND
52-ND
57-ND

3-ND
8-ND
13-ND
18-ND
23-ND
28-ND
33-ND
38-ND
43-ND
48-ND
53-ND
58-ND

4-ND
9-ND
14-ND
19-ND
24-ND
29-ND
34-ND
39-ND
44-ND
49-ND
54-ND
59-ND

5-ND
10-ND
15-ND
20-ND
25-ND
30-ND
35-ND
40-ND
45-ND
50-ND
55-ND
60-ND

Energize
De_energize
Loop arm/disarm
arm
disarm
Net_link_request
Analazer
Alarm-trip
Flow-trip
Percent/ft
Sensitivity(Senstvty)
Pre-alarm
Change-apps
Use the Control menu to perform the
following functions:
Reset the System
Change the sensitivity of a smoke
detector

CONTROL Menu

The Control menu has nine items from


which to choose; six of the items have
submenus, as follows (the shortened terms
used in the menu are in parentheses):

Arm an output device


Disarm and energize an output device
Disarm and de-energize an output
device

Reset

Arm and disarm a loop

Sensitivity (Senstvty)

Send a request to the Network


Command Center (NCC) to disconnect
the MXL from the network

Hi_3
Hi_2
Hi_1
Norm
Low_1
Low_2
Low_3

3-36

Arm or disarm an initiating device

Technical Manuals Online! - http://www.tech-man.com

Change AnaLASER Alarm Trip points


and Flow Trip points
Change sensitivity and pre-alarm
settings in percent/ft obscuration of the
ILI and ILP detectors
Change the application of an ASD device

Operation

Entering the Control Menu


From the Main Menu, use the arrow keys to
cause the C in CONTROL to blink.
(If you press HELP at this point, the System
explains the Control function:
TO MODIFY DATA FOR OPERATION

Press HELP again to return to the Main


Menu.)

If the System is normal, when SYSTEM


RESET is selected, the System displays
the following:
SYSTEM ALREADY NORMAL

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Press ENTER to select CONTROL.


The System asks you for a password
before it allows you to use the Control
functions. Enter your one- to five-digit
password, using the numeric keypad, and
press ENTER (See the discussion under
Entering Your Password on page 3-17).
If the System accepts your password, it
displays the first Control menu, with the R in
RESET blinking:

Control: Sensitivity
Use Control Sensitivity to change the
sensitivity settings of smoke detectors on
analog loops.
From the Control menu, press the Right or
Left arrow key to cause the S in SENSTVTY
to start blinking:
CONTROL: RESET SENSTVTY ARM/DIS

CONTROL: RESET SENSTVTY ARM/DIS

(If you press HELP at this point, the System


displays:
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

CHANGE SENSITIVITY

Control: Reset

Note that Control Sensitivity allows you to


change the sensitivity settings of smoke
detectors only; if you attempt to change the
sensitivity setting of another type of device,
the System displays:

Use Control Reset to initiate a system reset


at any time.
From the Control menu, use the Left or
Right arrow key to cause the R in RESET to
start blinking:

Press HELP again to return to the above


menu.)

[001-001] NOT SMOKE DETECTOR

CONTROL: RESET SENSTVTY ARM/DIS

If you enter any address for which there is


no device assigned, the System displays:
(If you press HELP while the R in RESET is
blinking, the System explains this function:

NO DEVICE ASSIGNED

RESET SYSTEM

Press ENTER while the S in SENSTVTY is


blinking to select CONTROL SENSTVTY.
Press HELP again to return to the above
menu.)
Press ENTER to reset the System and
display the following message:

The System asks you for a module number


and device number:
TYPE IN MODULE & DEVICE:

SYSTEM RESET

Technical Manuals Online! - http://www.tech-man.com

3-37

Operation
Type the three-digit module number and
three-digit device number using the numeric keypad and press ENTER. The
System shows the following display:
001-001 Norm Hi 1 Hi 2 Hi 3

The current sensitivity setting is highlighted.


The System offers you a choice of seven
levels of sensitivity: Hi_3, Hi_2, Hi_1, Norm,
Low_1, Low_2 or Low_3. Use the Right and
Left arrow keys to highlight the level you
wish to set for the smoke detector specified
and press ENTER. The System makes the
change in sensitivity setting.

001-001 ARM DISARM

Press NEXT to move through the devices


until you display the ones you want to
change, and follow the instructions above for
making the changes.

When you disarm an input device, the


System automatically annunciates the
disarming as a Trouble and lights the
PARTIAL SYSTEM DISABLE LED.

When the System has displayed the


highest numbered device for the module
specified, it returns to the Control menu.
You can select another address by selecting SENSTVTY and following the instructions above.

Press NEXT to move through the devices


until you display the ones you want to
change; follow the instructions above for
making the changes.

The System offers you a choice of arming


or disarming the device. Use the Right and
Left arrow keys to highlight your choice and
press ENTER. The System makes the
change.

To leave the Control Sensitivity displays


without going through the entire list, press
the Up arrow key. The System displays the
Control menu.

When the System has displayed the


highest numbered device for the module
specified, it returns to the Control menu. To
arm or disarm another module device,
select ARM/DIS and follow the preceding
instructions.

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Control: Arm/dis

Control: Output on/off

Use Control Arm/dis to enable or disable


the operation of an initiating device.

Use Control Output_On/Off to arm or


disarm an output device. In addition, you can
energize or de-energize disarmed output
devices.

From the Control menu, press the Left or


Right arrow key to cause the A in ARM/DIS
to start blinking.
(If you press HELP at this point, the System
displays:
DISARM OR ARM DEVICES

Press HELP again to return to the Control


menu.)
Press ENTER while the A in ARM/DIS is
blinking to select Control Arm/dis.

3-38

The System asks you for the module


number and device number of the detector
you wish to arm or disarm. Type the threedigit module number and three-digit device
number using the numeric keypad and
press ENTER. (Enter all leading zeros.)
The System displays:

Technical Manuals Online! - http://www.tech-man.com

From the Control menu, press the Left or


Right arrow key to cause the O in OUTPUT
to start blinking:
CONTROL ARM/DIS OUTPUT_ON/OFF

(If you press HELP at this point, the System


displays:
TURN OUTPUTS ON OR OFF

Operation
Press HELP again to return to the above
menu.)
Press ENTER while the O in OUTPUT is
blinking to select CONTROL_OUTPUT ON/
OFF.
The System asks for a module number and
device number of the device you wish to turn
on or off (energize or de-energize). Type
the three-digit module number and threedigit device number using the numeric
keypad and press ENTER. (Enter all
leading zeros.)

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Control: Loop Arm


Use Control Loop Arm to enable the operation of a loop of ALD initiating devices.
From the Control menu, press the Left or
Right arrow key to cause the L in
LOOP_ARM to start blinking.

The System shows the following display:

(If you press HELP at this point, the System


displays:

253-005 ARM DISARM

TO ARM ALL INPUTS ON A LOOP

The System offers you a choice of arming


or disarming the device.

Press HELP again to return to the Control


menu.)

Use the Right and Left arrow keys to


highlight your choice and press ENTER.

Press ENTER while the L in LOOP_ARM is


blinking to select Control Loop_arm.

If you have armed the device, you can


press NEXT to display the number of the
next device in the sequence. You can also
press the Up arrow key to return to the
Control menu.

The System asks you for the module


number of the ALD loop you wish to arm.
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.)

NOTE: You must first disarm a device if


you wish to energize or de-energize it.

When you arm input devices, the System


automatically annunciates the arming as a
Trouble OUT, and lights the PARTIAL
SYSTEM DISABLE LED.

When you disarm an output device, the


System automatically annunciates the
disarming as a Trouble and a Partial
System Disable.
If you choose to disarm an output device,
the System then asks if you wish to energize
it or de-energize it:
253-005 ENERGIZE DE ENERGIZE

Use the Right or Left arrow key to energize


or de-energize the device and press ENTER.
Press NEXT to move through the outputs
until you display the ones you want to
change; follow the instructions above for
making the change.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Control menu. To
arm or disarm and energize or de-energize
a device on a different module, follow the
preceding instructions.

Technical Manuals Online! - http://www.tech-man.com

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Control: Loop Disarm


Use Control Loop Disarm to disable the
operation of a loop of ALD initiating devices.
From the Control menu, press the Left or
Right arrow key to cause the L in
LOOP_DISARM to start blinking.
(If you press HELP at this point, the System
displays:
TO DISARM ALL INPUTS ON A LOOP

Press HELP again to return to the Control


menu.)

3-39

Operation
Press ENTER while the L in LOOP_DISARM
is blinking to select Control Loop_disarm.

Press ENTER when the A in ANALASER is


blinking to select Control ANALASER.

The System asks you for the module


number of the ALD loop you wish to disarm.
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.)

The System prompts you to select between ALARM_TRIP and FLOW_TRIP.

When you disarm input devices, the


System automatically annunciates the
disarming as a Trouble IN, and lights the
PARTIAL SYSTEM DISABLE LED.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Control: Net Link Request


Use Control Net_Link_Request to connect
or disconnect that particular panel from the
X-Network. When the panel is disconnected from the X-Network, the panel
maintains its functions, but it does not
exchange messages with other nodes in the
X-Network.
From the Control menu, press the Left or
Right arrow key to cause the N in
NET_LINK_REQUEST to start blinking.
(If you press HELP at this point, the System
displays:
REQUEST NCC DISCONNECT/RECON NODE

Press HELP again to return to the Control


menu.)

Press ENTER when the A in ALARM_TRIP


is blinking to select CONTROL ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device address number using the numeric keypad
and press ENTER. The system displays the
current alarm trip point settings for the
address specified:
010-004 P1: 20%

P2: 60%

ALM: 90%

Use the numeric keypad and the left and


right arrow keys to modify the value for P1,
P2, and ALM (Alarm). Note that the following provisions apply:
P1 must be less than or equal to P2
which must be less than or equal to
ALM. If these values are different, the
System will reject the settings.
P1, P2, and ALM must be even multiples
of 10% or the System will reject the
settings.
Press ENTER when you are finished
modifying the settings. The display should
then show:

Press ENTER while the N in


NET_LINK_REQUEST is blinking to
disconnect the panel from the X-Network.

TRIP POINTS ACCEPTED

To reconnect the panel to the X-Network,


from the Control menu, press the Left or
Right arrow key to cause the N in
NET_LINK_REQUEST to start blinking and
press ENTER.

TRIP POINTS INVALID.

or

Press ENTER when the F in FLOW_TRIP


is blinking to select Control FLOW_TRIP.
The System asks you for a module and
device number.

Control: Analaser
Use Control ANALASER to display and
change the operational characteristics of
the AnaLASER devices.

3-40

Technical Manuals Online! - http://www.tech-man.com

TYPE IN MODULE & DEVICE

Type the three-digit NIM-1R (ANA) module


number and three-digit ACC device address number using the numeric keypad

Operation
and press ENTER. The system displays the
current air flow trip point settings for the
address specified:
010-004

LOW: 20%

HIGH: 60%

Use the numeric keypad and the left and


right arrow keys to modify the value for
LOW and HIGH. Note that the following
provisions apply:

Use the left and right arrow keys on the


keypad to lower or raise the %/ft reading.
(Refer to the Sensitivity and Pre-Alarm
Settings chart that follows.)

PHOTO

ION

Pre-alarm adjust
increment

.25% / ft.

.12% / ft.

LOW must be less than HIGH, or the


System will reject the settings.

Pre-alarm range

.25 - 2.0% / ft.

.25 - .75% / ft.

The System will reject the settings if they


are not even multiples of 10%.

Pre-alarm default

1.5% / ft.

.75% / ft.

Sensitivity adjust
increment

~.25% / ft.

~.12% / ft.

Sensitivity range

1.25 - 3.4% / ft.

.6 - 1.6% / ft.

Sensitivity default
(Norm)

3.0% / ft.

1.4% / ft.

Press ENTER when you are finished


modifying the settings. The display should
then show TRIP POINTS ACCEPTED.

Control: Percent/ft
Use Control Percent/ft to change sensitivity
and pre-alarm settings in percent/ft obscuration of the ILI and ILP series of detectors.
From the Control menu, press the Left or
Right arrow key to cause the P in Percent/ft
to start blinking. The System asks you for a
module number and device number.
TYPE IN MODULE & DEVICE:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. The
System displays the following:
001-001 SENSTVTY

PRE-ALARM

Control Percent/ft - Senstvty


The display for Sensitivity supplies the
current sensitivity as read back from the
detector and is similar to the following
(readings are dynamic):
002-003 SENS 1.4%/FT

NORM

In the previous message, 002-003 is the


address. Sens is the type of response
(Sensitivity or Pre-alarm). 1.4%/ft is the
smoke detector reading in %/ft obscuration
and Norm is the text sensitivity range
corresponding to the %/ft readings.

Technical Manuals Online! - http://www.tech-man.com

After you change the sensitivity setting, the


System prints the information for the
selected device in a format similar to the
following:
CMD CHANGE SENS
06:38:20 JUN 2, 20XX
002-004 1.4%/FT NORM

Control Percent/ft - Pre-alarm


The display for Pre-alarm supplies the
current pre-alarm setting read back from
the detector and is similar to the following
(readings are dynamic):
002-003 PRE-ALARM .75%/FT

NORM

In the previous message, 002-003 is the


address. Pre-alarm is the type of response
(Sensitivity or Pre-alarm). .75%/ft is the
smoke detector reading in %/ft obscuration
and Norm is the text sensitivity range
corresponding to the %/ft readings.
Use the left and right arrow keys on the
keypad to lower or raise the %/ft reading.
(Refer to the Sensitivity and Pre-Alarm
Settings chart.)

3-41

Operation
After you change the pre-alarm setting, the
System prints the information for the
selected device in a format similar to the
following:
CMD CHANGE PRE-ALM 06:38:20 JUN 2, 20XX
002-004 1.4%/FT NORM

NOTE: Because the pre-alarm and sensitivity settings overlap, set the pre-alarm to
at least an increment below the sensitivity
setting.

Control: Change Apps


Use Control Change_Apps to change the
application of an ASD device.
From the Control menu, press the Left or
Right arrow key to cause the C in
Change_Apps to start blinking.
(If you press HELP at this point, the System
displays:
CHANGE DEVICE'S APPLICATIONS

Press HELP again to return to the Control


menu.)
Press ENTER while the C in Change_Apps
is blinking to select Control Change_Apps.
The System asks you for the module and
device number.
TYPE IN MODULE & DEVICE:

Control: Change_Apps Reset >

Type in Module & Device: 001-001


[Enter
module-device number, including all leading zeros]
001-001 NONE OFFC WHSE LOBY > [Use arrow
keys to select the desired application]
001-001 NONE OFFC WHSE LOBY >

COMMAND +HANGE_APPS 09:41:43 AUG 07,


20XX 001-001 NONE > OFFC

To leave the Change_Apps menu at any


time, press the Up arrow key.
NOTE: If the ASD application is changed
while Test ASD is on, the changes will not
be effective until Test ASD is turned off.

TEST Menu

The Test menu has sixteen items from


which to choose; three of those items have
submenus, as follows (the shortened terms
used in the menu itself are in parentheses):
Set_time
Ground fault (GND_FLT)
Power*
Main
Voltage
Current
LEDs
Display
Device_LED
MOI_Lamp_test

Use the arrow keys to cycle through the 11


supported applications described in the
ASD Submenu Abbreviations on page I-1,
in Appendix I, and press ENTER to select
the desired application.

X_Network*

The transaction and the time that it occurs


will be printed on the printer as a confirmation. The example shown below assumes
that no application is currently assigned to
module 001, device 001:

Event_log

M_Network*
Override
Det_cleaned
Alrm_only
Trbl_only
Superv_only
Security_only

3-42

Technical Manuals Online! - http://www.tech-man.com

[Press ENTER]

A statement will be printed out to confirm


the change:

Lamp_test
Type the three-digit module number and
three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)

[Press ENTER]

Operation
All_events
Hist_Ctrl
Hist_Erase
PYRO_Diags
PRE_ALARM
ASD_DEVICES
SUMMARIZE
MANUAL_ACTIVATE
*You can print a report of the information
produced by these functions. See the
discussions for Test Power and Test Network.

Press ENTER to select TEST. The System


asks you for a password before it allows
you to use the Test functions. Enter your
one- to five-digit password, using the
numeric keypad, and press ENTER (See
the discussion under Entering Your
Password on page 3-17).
If the System accepts your password, it
displays the first Test menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Use the Test menu for the following functions:


Change the time and date in the System

Test: Set Time

Test ground fault state

Use Test Set_Time to set the time and date


for the System.

Display the Systems power condition


Test the LEDs or the display on the
MKB-4
Test the LEDs on an analog device
Perform lamp test on MOD-16 of MOI-7
Display network performance
characteristics

From the Test menu, use the Left or Right


arrow key to cause the S in SET_TIME to
start blinking:
TEST: DETECTOR NETWORK SET-TIME

Alarm verification/confirmation override

(If you press HELP at this point, the System


displays:

IEC detector cleaned function

SET SYSTEM TIME

Event (History) log menu


Test Pre-alarm logic
Test ASD detectors

Press HELP again to return to the above


menu.)

Record one summarized trouble for an


entire module

Press ENTER when the S in SET_ TIME is


blinking to select TEST SET_ TIME.

Perform testing on input points and


simutale alarms

The System shows you the current System


time, using a 24-hour clock, and the date:
SET TIME = 12:34:56 12/23/20XX

Entering the Test Menu


From the Main Menu, use the Left or Right
arrow keys to cause the T in TEST to begin
blinking.
(If you press HELP at this point, the System
explains the Test function:
TO TEST SYSTEM, LOOP & DEVICE

Press HELP again to return to the Main


Menu.)

Technical Manuals Online! - http://www.tech-man.com

(If you press HELP at this point, the System


displays:
TYPE HH:MM:SS MM/DD/YYYY <ENTER>

The Help display tells you to type the time


and date, using the numeric keypad, in the
following format: hour: minute:
seconds_month/day/year, and then to
press ENTER to set the time and date. Use
the Right and Left arrow keys to skip over a
correct digit.

3-43

Operation
Press HELP again to return to the above
menu.)
Type the time and date as explained above
and press ENTER. The System prints the
current time and date on the printer and
returns you to the Test menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Test: Power
Use Test Power to test the Systems
battery voltage, AC voltage, and battery
charge current.
From the Test menu, use the Left or Right
arrow key to cause the P in POWER to
start blinking:
TEST: GND-FLT POWER

(If you press HELP at this point, the System


displays:

Test: Ground Fault


Use Test Gnd_flt to test the present condition of the ground fault detection circuitry.
From the Test menu, use the Left or Right
arrow key to cause the G in GND_FLT to
start blinking:
TEST: NETWORK SET TIME GND FLT

DISPLAY POWER

Press HELP again to return to the above


menu.)
Press ENTER when the P is blinking and
the menu displays:
POWER: MAIN

(If you press HELP at this point, the System


displays:
GROUND FAULT TEST

Press HELP again to return to the Test


menu.)
Press ENTER when the G is blinking and
the menu displays:
GND FLT: MAIN

From the Ground Fault menu, press ENTER


when the M in MAIN is blinking.
The System tests dynamically for ground
fault and reports the results of the test on
the display (OK, PLUS, or MINUS):
GROUND FAULT IS MINUS

If the message is other than OK, locate the


loop and the device responsible. The
display automatically changes to OK when
the ground fault problem is corrected.
(During this test, the System and its
devices remain operational.)

3-44

(To end a menu session and return to the


Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Technical Manuals Online! - http://www.tech-man.com

Display the AC Voltage, Battery Voltage, and


Charging Current of the Main System
From the Power menu, press ENTER when
the M in MAIN is blinking to select Main
Power.
The System shows the following menu:
MAIN: VOLTAGE CURRENT

Press ENTER when the V in VOLTAGE is


blinking to display the battery voltage:
BATTERY VOLTAGE = X.X VOLTS

Press ENTER again to display the AC


voltage:
AC VOLTAGE = X VOLTS

Press the Up arrow key to return to the


Main Power menu. Use the Right arrow key
to cause the C in CURRENT to start
blinking and press ENTER. The System
shows the battery charge current in amps:
BATT CHG CUR = XX.X AMPS

Press the Up arrow key twice to return to


the Power menu.

Operation
Print the AC Voltage, Battery Voltage, and
Charging Current of the Main System
From the Power menu, press PRINT when
the M in MAIN is blinking to select MAIN
POWER. The System will print information
in a format similar to the following:
Power Supply Statistics at 11:23:52
May 01, 20XX:
Battery Voltage = 26.0 volts Charging
CUR = 0.5 AMPS

AC VOLTAGE = 113 VOLTS

Test: Device LED


Use Test Device_LED to test the LEDs on
the Systems analog devices.
From the Test menu, use the Left or Right
arrow key to cause the D in DEVICE to
start blinking:
TEST: LAMP TEST DEVICE LED

(If you press HELP at this point, the System


displays:
TURN ON DEVICE LEDs

Test: Lamp Test


Use Test Lamp_test to test the LEDs on
the alphanumeric display on the MKB-4.
From the Test menu, use the Left or Right
arrow key to cause the L in LAMP to start
blinking:
TEST: GND-FLT POWER LAMP TEST

(If you press HELP at this point, the System


explains this function:
MKB-4 LAMP TEST

Press HELP again to return to the above


menu.)
Press ENTER when the L is blinking to
select TEST LAMP_TEST. The System
displays the following menu:
LAMP TEST: LED'S DISPLAY

Press ENTER to test the LEDs and the


audible on the MKB-4. The LEDs light for 5
seconds and then return to their previous
state.
To test the alphanumeric display, press the
Right arrow key once to cause the D in
DISPLAY to start blinking and then press
ENTER. The System tests the display and
then returns to the Lamp Test menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)

Technical Manuals Online! - http://www.tech-man.com

Press HELP again to return to the above


menu.)
Press ENTER when the D is blinking to
select TEST DEVICE_LED.
The System asks you to type the module
and device numbers. Type the three-digit
module number and the three-digit device
number and press ENTER. (Enter all
leading zeros.)
The System displays the following menu for
the device (the O in ON will be blinking):
001-001 ON OFF

To turn on the LED for that device, press


ENTER. The System turns on the LED for that
device. Turning on a device LED automatically
causes a Trouble to be annunciated.
Use the NEXT key to move through the
devices until you display the ones whose
LEDs you wish to test. Follow the instructions above.
When the System has displayed the
highest numbered device for the module
specified, it returns to the Test menu.
To turn on a device LED for a different
module, select DEVICE_ LED from the
Test menu and follow the preceding
instructions.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)

3-45

Operation

Test: MOI Lamp Test


Use MOI_lamp_test to test the MOD-16
outputs of an MOI-7.
From the Test menu, use the Left or Right
arrow key to cause the M in MOI to start
blinking:
TEST: DEVICE LED MOI Lamp Test

Press HELP again to return to the above


menu.)
Press ENTER when the O in OVERRIDE is
blinking and the menu displays:

OVERRIDE: ALR VERIFY ALR CONFIRM

Use the Left or Right arrow key to switch


between ALR_VERIFY and ALR_CONFIRM.
(If you press HELP at this point, the System
displays:
TO TEST MOI-7 / MOD-16 LAMPS

Press HELP again to return to the above


menu.)
Press ENTER when the M is blinking to
select MOI_LAMP_TEST.
The System asks you to type the module
number. Type the three-digit module
number and press ENTER. (Enter all
leading zeros.)
If the MOI-7 module is present in CSG-M
the MOD-16 outputs will be placed in a 30second lamp test mode. After 30 seconds,
these outputs return to their previous state.
(To end a menu session and return to the
Main Menu, or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)

Test: Network
(X-Network, M-Network)
This function is used only by Siemens
Building Technologies, Inc. engineers to
observe network traffic so that they can
evaluate the operation of the module
communication network.

Test: Override

The System shows the following menu:


OVERRIDE: YES NO

A blinking Y in YES indicates that Alarm


Verification Override is currently enabled. A
blinking N in NO indicates that the Alarm
Verification Override is currently disabled.
To enable Alarm Verification Override, use
the Left or Right arrow key to cause the Y
in YES to start blinking. Pressing ENTER
when the Y in YES is blinking will cause
Alarm Verification Override to be enabled.
The System will display the following
message:
OVERRIDE ENABLED

To disable Alarm Verification Override, use


the Left or Right arrow key to cause the N
in NO to start blinking. Pressing ENTER
when the N in NO is blinking will cause
Alarm Verification Override to be disabled.
The System will display the following
message:

Use Test Override to override the CSG-M


selected options for Alarm Verification and
Alarm Confirmation.

OVERRIDE DISABLED

From the Test menu, use the Left or Right


arrow key to cause the O in OVERRIDE to
start blinking.

In either case, if the Alarm Verification


option was not selected in CSG-M, the
System will display the following message:

(If you press HELP at this point, the System


displays:

FEATURE NOT ENABLED IN CSG

OVERRIDE ALARM VERIFY & CONFIRM

3-46

Override the Alarm Verification CSG-M


Selection
From the Override menu, press ENTER
when the A in ALR_VERIFY is blinking to
select Alarm Verification.

Technical Manuals Online! - http://www.tech-man.com

Operation
Override the Alarm Confirmation CSG-M
Selection
From the Override menu, press ENTER
when the A in ALR_CONFIRM is blinking to
select Alarm Confirmation.

(If you press HELP at this point, the System


displays:

The System shows the following menu:

Press HELP again to return to the above


menu.)

OVERRIDE: YES NO

TO INDICATE DETECTOR CLEANED

Press ENTER when the D is blinking to


select DET_CLEANED.
A blinking Y in YES indicates that Alarm
Confirmation Override is enabled. A blinking
N in NO indicates that the Alarm Confirmation Override is disabled.
To enable Alarm Confirmation Override, use
the Left or Right arrow key to cause the Y
in YES to start blinking. Pressing ENTER
when the Y in YES is blinking enables Alarm
Confirmation Override. The System will
display the following message:
OVERRIDE ENABLED

To disable Alarm Confirmation Override, use


the Left or Right arrow key to cause the N
in NO to start blinking. Pressing ENTER
when the N in NO is blinking disables Alarm
Confirmation Override. The System will
display the following message:
OVERRIDE DISABLED

In either case, if the Alarm Confirmation


option was not selected in CSG-M, the
System will display the following message:
FEATURE NOT ENABLED IN CSG

The System asks you to type the module


and device numbers. Type the three-digit
module number and the three-digit device
number and press ENTER. (Enter all
leading zeros.)
After entering the module-device, the
MXL-IQ determines if the device is subject
to IEC. If the device is not subject to IEC or
if IEC is not enabled for the system, error
messages display (Device not subject to
IEC; IEC not enabled in CSGM).
If the device is an IEC detector, the MXL-IQ
will display and print the time, date, moduledevice and custom message of the cleaned
device.

Test: Event Log


See Section 6, MXL-IQ History Log.

Test: Pyro_diags
Use Test Pyro-diags to display a series of
statistics typically used by Siemens Building
Technologies, Inc. to evaluate the operation
of the System. A special password is
required for access to this function.

Test: Pre_alarm
Test: Det_Cleaned
Use Test Det_cleaned to indicate that a
selected detector has been cleaned. This
option is only operational if IEC is enabled in
the CSG-M (See Appendix F).
From the Test menu, use the Left or Right
arrow key to cause the D in DET_CLEANED
to start blinking:
TEST: OVERRIDE DET CLEANED

Technical Manuals Online! - http://www.tech-man.com

Use Test Pre_alarm to test pre-alarm logic.


From the Test menu, use the left or right
arrow key to cause the P in Pre_alarm to
start blinking:
TEST: PRE ALARM

The System asks you for a module number


and device number.
TYPE IN MODULE & DEVICE:

3-47

Operation
Type the three-digit module number and
the three-digit device number using the
numeric keypad and press ENTER.
The System then sends information to force
this detector into pre-alarm. Once it prealarms, or after a delay, the MXL-IQ then
restores the detector to its proper pre-alarm
setting.

Test: ASD_Devices
Use Test ASD_Devices to disable ASD
parameters and allow timely response to
test gas.
From the Test menu, use the Left or Right
arrow key to cause the A in ASD_Devices
to start blinking.
(If you press HELP at this point, the system
displays:
TEST: ASD DETECTORS

Press HELP again to return to the Test


menu.)
Press ENTER to test the ASD devices
present in the system. The System displays:
TESTING OF ASD DEVICE ENABLED

Press the ENTER key again and the


System displays:

TROUBLE OUT 253 08:25:50 AUG 08, 20XX


#9 CERBERUS PYROTRONICS ,
ASD TESTING DISABLED, MXL PANEL

If Test ASD_Devices is activated and left


alone, the system will automatically disable
the test (time out) after four hours.

Test ASD_Devices is inhibited while the


system is initializing or resetting.

Test: Summarize
Use Test Summarize to ignore known
troubles, and instead view one summarized
trouble for an entire module. This is typically
used during installation and commissioning.
Select Summarize and press ENTER. The
System displays the following menu:
Select Mods

ON

OFF

Test: Summarize - Select_Mods


Use Test Summarize Select_Mods to scroll
through all installed (CSG-M) module
addresses and enable/disable the summarize feature for each module address.
Choose Select_Mods and press ENTER.
The System displays the following:
001

YES

NO

Press NEXT and the System displays:

TESTING OF ASD DEVICE DISABLED

002

Press the ENTER key to toggle between


Testing Enabled (Trouble In) and Testing
Disabled (Trouble Out). When toggling
between Testing Enabled and Testing
Disabled, there is a three minute time
period that separates the two states.

The System flashes the currently active


summarize selection for the module
address. The operator may then press the
right or left arrow keys to highlight either
YES or NO and then press the ENTER key
to accept and program the selection. When
ENTER is pressed, the System scrolls to
the next installed module address. The Up
arrow key terminates the Select_Mods
mode.

Activating the ASD_Devices command will


post a Trouble into the system which will be
printed out as:
TROUBLE IN 253 08:24:53 AUG 08, 20XX
#8 CERBERUS PYROTRONICS ,
ASD TESTING ENABLED, MXL PANEL

3-48

Pressing ENTER a second time will cause


the following message to be printed out:

Technical Manuals Online! - http://www.tech-man.com

YES

NO

All Select_Mods selections remain intact


until the System is turned off, even if
summarize mode is toggled.

Operation
One trouble is posted per module
address, regardless of how many
troubles are detected at that module
address.

and turns on the Partial System Disable


LED. The System displays one summarized
trouble for the total system.

A trouble is not posted unless at least


one trouble is detected at that module
address.

Test: Manual_Activate

The trouble report is consistent with


existing MXL-IQ trouble messages and
the text reads Troubles summarized.
The MXL-IQ only reports TRBL-INs
when summary mode is enabled at an
address.
Alarm, supervisory, security, and status
event reporting are not effected.
Modules which are NOT selected for
summary report their troubles as usual,
even if summary mode is turned on for
other module addresses.
When a module address is summarized,
individually occurring troubles are not
broadcast to XNET; the single Troubles
summarized trouble is broadcast to XNET.
The Troubles summarized trouble is
implemented as any other system trouble,
being logged to history, taking up one of the
300 trouble slots, and appearing in List
Troubles requests. All summarize selections are unaffected through RESET and
default to CSG-M setting at power up.
Test: Summarize - OFF
When Summarize OFF is selected, the
System annunciates the following trouble:
System Commissioning Mode TRBL OUT

and turns off the Partial System Disable


LED. Preexisting Troubles summarized
events remain and the System reverts to
normal trouble reporting and processing for
all new troubles.
Test: Summarize - ON
When Summarize ON is selected, the
System annunciates the following trouble:
System Commissioning Mode TRBL IN

Technical Manuals Online! - http://www.tech-man.com

Use Test Manual_Activate to:


Perform testing on input points and the
associated output logic expected when
the point is activated.
Generate alarms and associated output
activations.
Select Manual_Activate and press ENTER.
The System asks you for a module number
and device number.
Type In Module & Device:

Type the three-digit module number and


three-digit device number using the numeric keypad and press ENTER. Upon
entering the device address, the System
performs as follows based on the point
type:
MANUAL INPUT POINT ACTIVATION
No Input Point Error message.
Analog Smoke System issues command to place
device into the alarm state via
Detectors
sensitivity adjustment. Device then
reports alarm as if an actual alarm
occurred. Associated outputs follow.
All Other
Inputs

System will not issue any command


to device, but will synthesize the
reporting of alarm in by the device.
Associated outputs follow.

Test: Manual_Activate - Test


This provides a remote switch that upon
activation/deactivation of the TRI, the
MXL-IQ reads the module-device address
provided and performs the operations
outlined above. This use is primarily for, but
not limited to, testing intelligent duct
detectors.

3-49

Operation

3-50

Technical Manuals Online! - http://www.tech-man.com

+D=FJAH

Testing and Troubleshooting


SYSTEM TEST
Important:
If the System is connected to the Fire
Department, or activates an external
System (for example, a leased line
connection), disarm the related
outputs before servicing to prevent
activation. Notify persons in the
facility that you are conducting a
System test so that they can ignore
any alarms that sound during testing.
Be sure to reset the System at the
end of the inspection.

To ensure maximum safety, follow the


procedure described below. To ensure
proper and reliable operation, we recommend the following inspection and testing
schedule:

Every Six Months


1. Check the sensitivity of each detector,
using the List Sensitivity menu (See
page 3-26). Refer to Appendix B for a
list of acceptable detector sensitivity
ranges.
2. If the PARTIAL SYSTEM DISABLE
LED is lit, check that all appropriate
detectors are armed, using the Control
Arm/dis menu (See page 3-38).
3. Activate a detector or alarm-initiating
device. To test for GoNo Go operation,

Technical Manuals Online! - http://www.tech-man.com

use CERBERUS PYROTRONICSTM


Test Gas P/N 315-282747, following the
instructions on the label. Check that the
detector LED lights and that the proper
indication is given at the Control Panel.
4. Verify that an alarm can be acknowledged
and that the System can be silenced and
reset (See Acknowledge Alarms on
page 3-18).
5. Verify the time and date setting of the
System clock (See Test Set_Time on
page 3-43).

Every Year
1. Check that the System operates as
programmed by CSG-M and in
accordance with specifications.
2. Perform any other applicable tests
required by national or local fire codes.

Fuse Replacement
Fuse ratings are as follows:

Fuse
F1
F2
F3
F4

For
Main Power
Battery
CZM-1B6 Power
24V Output

Rating
8A, 3 AG, Normal Blow
15A, 3 AG, Normal Blow
2A, 3 AG, Normal Blow
15A, 3AG, Normal Blow

The fuses are located on the upper portion


of the SMB-2 (See Figure 2, page 1-4).

4-1

Testing and Troubleshooting

TROUBLESHOOTING
Troubleshooting both the external wiring and
the MXL-IQ System wiring follows the steps
in System Function Checkout on page
2-16. If a fault occurs, refer to the Troubleshooting Guide. Locate the type of fault or
any trouble message displayed and follow
the directions in the Corrective Action
column.

Sometimes you can locate a fault quickly


using the Troubleshooting Guide. When
this is not possible, continue with the
checkout procedure on page 2-16 and then
the Troubleshooting Guide until all faults
and troubles are corrected. Then repeat the
checkout procedure to ensure that no
additional problems were introduced and
that the original problem was corrected.

TABLE 19
TROUBLESHOOTING GUIDE
This guide assumes that all modules, devices, and wiring are installed.
Note:

Do NOT change modules or wiring unless power is OFF. If available, use your printer during
troubleshooting operations.

SYMPTOM
1. POWER LED is not lit;
display on MKB-4 is
blank.

PROBABLE CAUSE

CORRECTIVE ACTION

No AC Battery

Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuitbreaker
on the MPS-6. Check AC and battery wiring.
If power connections are OK, check the cable between the SMB-2 and MKB-4 for
proper installation.

2. POWER LED is on,


MKB-4 display is blank.

Problem on the MKB-4.

Adjust contrast control R14 on the ANN-1 board. Remove the MKB-4 and check
cable from ANN-1 to the display. If MKB-4 is defective, replace it.

3. MKB-4 display shows


the following default
message:
CERBERUS
PYROTRONICS MXL

Improper address on MKB-4

Correct address setting on the MKB-4 using S1. See the installation instructions for
the MKB-4, page 2-4.

No communication between
SMB-2 and MKB-4.
Defective MKB-4.

Check the cable between the SMB-2 and the MKB-4. Replace the cable if defective.
Replace the MKB-4.

If MOM-2/4 installed, defective


network modules(s).
Defective SMB-2

Disconnect the MOM-2/4 from the SMB-2. If probelm resolved, reconnect


MOM-2/4 and remove all modules from MOM-2/4. Reinstall all modules one
at a time. Replace any that cause the problems to reoccur.
Replace SMB-2

4. Device troubles on
analog loops.

Errors in loop wiring and


installation of devices.

Check loop wiring for shorts, opens, etc. using the Field Wiring Checkout Guide
(page 2-11).
Check that all analog devices are I or IL Series devices, or are CZM-1B6s. See the
list of compatible devices in the appendixes.
Check that all devices are installed.
Check that all devices installed comply with the configuration printout from CSG-M.
Check printed trouble list for ID troubles and correct device IDs as required. Check
devices using the FPI-32 Programmer Tester. Replace devices that fail to respond.

4-2

Technical Manuals Online! - http://www.tech-man.com

Testing and Troubleshooting


TABLE 19
TROUBLESHOOTING GUIDE (Continued)
SYMPTOM
5. Trouble with notification
appliance circuits
(NACs).

PROBABLE CAUSE

CORRECTIVE ACTION

End-of-line resistor improperly


or not installed.

Check that the end-of-line resistor is 2.2K, W and is installed according to the
instructions.

Notification appliances
improperly installed.

Check notification appliances for presence of polarizing diodes and correct device
wiring.
Check NACs for proper wiring (shorts, opens, etc.). Use the Field Wiring Checkout
Guide, page 2-11.

6. Output devices
connected to System
relays do not work.

7. CZM-1B6 reports a
trouble.

Incompatible notification
appliance connected.

Check P/N 315-096363 for a list of compatible notification appliances. Replace


incompatible devices.

Error in control logic functions.

Check the logic functions using the printout from CSG-M; correct and reload
the System from CSG-M into the SMB-2.

Power source for ouput


devices missing or not
connected.

Check that the power source is connected and that power is available.

Improper wiring of connected


devices.

Check that output devices are properly wired.

Connected devices are not


compatible with power source.

Check that power source and ouput devices are compatible.

No power to CZM-1B6.

On the SMB-2, check fuse F3. At the CZM-1B6 check power input; DC power must
be 16-31 VDC. Check polarity.

Wiring error on initiating


device circuit.
8. Modules in MOM-2/4 do
not work.

9. CSM-4 does not respond


to output logic
commands.

Check for opens or incorrect or missing end-of-line resistor (4.7K, W).

No power to MOM-2/4.

Check power cable connectors between the SMB-2 (P3) and the MOM-2/4 (P5).
Replace the power cable, if defective.

No communications between
SMB-2 and MOM-2/4.

Check communications cable connections between the SMB-2 (P6) and the
MOM-2/4 (P7). Replace the communications cable, if defective.

Modules are not properly


seated in edge connectors.

Remove and reseat all modules.

Modules are not properly


addressed.

Address the modules correctly using the printed configuration from CSG-M (See
CSG-M Programming Manual, P/N 315-090381).

Fuses are blown.

Check wiring for shorts using the Field Wiring Checkout Guide (page 2-11). Replace
fuses.

CSM-4 is improperly
configured.

Check and correct the configuration using the installation instructions for the CSM-4
(P/N 315-090854) and the printed configuration from CSG-M (See CSG-M
Programming Manual, P/N 315-090381).

Incompatible notification
appliances are connected.

Check P/N 315-096363 for a list of compatible notification applicances. Replace


incompatible devices.

Error in control logic functions.

Check the logic functions using the printout from CSG-M; correct and reload
the System from CSG-M into the SMB-2 (See CSG-M Programming Manual,
P/N 315-090381).

Defective CSM-4.

Replace CSM-4.

Technical Manuals Online! - http://www.tech-man.com

4-3

Testing and Troubleshooting


TABLE 19
TROUBLESHOOTING GUIDE (Continued)
SYMPTOM

PROBABLE CAUSE

CORRECTIVE ACTION

10. CRM-4 does not


respond to output logic
commands.

Power source for device is


missing or not connected.

Check that the power source to the CRM-4 is connected and that power is available.

Error in control logic functions.

11. Zone troubles from


CZM-4.

Check the logic functions using the printout from CSG-M; correct and reload the
System from CSG-M into the SMB-2 ( See CSG-M Programming Manual, P/N
315-090381. )

Connected devices are


incompatible with power
source.

Check that the power source and output devices are compatible.

Defective CRM-4.

Replace CRM-4.

Errors in initiating device circuit


wiring.

Check for wiring errors using the Field Wiring Checkout Guide ( page 2-11) and the
installation instructions for the CZM-4 ( page 2-14) . Check that the end-of-line
capacitor is the proper value and is properly connected. Unused zones must have
end-of-line capacitors installed on MOM-2/4 screw terminals ( 50 MFD, 50 VDC
polarized electrolytic capacitor) . See the installation instructions for the CZM-4 ( page
2-14) .

Defective CZM-4.
Replace the CZM-4.

4-4

Technical Manuals Online! - http://www.tech-man.com

+D=FJAH

Walktest Operating
Instructions
INTRODUCTION

A Walktest of the MXL-IQ System enables


a qualified technician to test the operation
of input points on the MXL-IQ with or
without disabling the entire fire alarm
system. Testing can be either silent or with
audible feedback in the following ways:
1. Entire system
2. ALD loop (60 subaddresses)
3. CZM-4 module (4 zones)
4. Conventional zone (individual
CZM-1B6 or CZM-4 zone)
5. MOI-7 (MID-16) inputs (128
subaddresses)
If a printer is installed, a printed record of
the test is made.
The Walktest is available with MXL-IQ
Operating Software. You must enter your
1-5 digit password before you can use the
Walktest functions. Enter the Walktest
through the MXL-IQ Main Menu (See
Chapter 3, Operating Instructions).
The MXL-IQ Main Menu structure with
Walktest included is:

The table below shows the selections in the Walktest Menu and
their related help messages.

TABLE 20
Walktest Menu
WALKTEST

HELP MESSAGE

System wAUD

Test Full System with AUDs

Loop wAUD

Test ALD Loop/MOI-7 (MID-16 group)/CZM-4 Module wAUDs

LIST

Zone wAUD

Test CZM-4/CZM-1B6 Zone with AUDs

CONTROL

Sytem SIL

Silent Test Full System

TEST

Loop SIL

Silent Test ALD Loop/MOI-7 (MID-16 group)/CZM-4 Module wAUDs

WALKTEST

Zone SIL

Silent Test CZM-4/CZM-1B6 Zone

Cancel

Cancel Walktest in progress

Extend

Reset test timer to 4 hours left

MXL-IQ Main Menu


ACKNOWLEDGE

Technical Manuals Online! - http://www.tech-man.com

5-1

Walktest Operating Instructions

System w/AUD

Cancel

Select this option to walktest all CZM-4


zones, CZM-1B6 zones, MID-16 inputs, and
ALD inputs with audible feedback to the
technician. This mode inhibits the
MXL-IQ from annunciating real alarm
conditions.

Select this option from the menu while in


the Walktest mode to set the Walktest
timer at the 1 minute left in Walktest mark.
This allows the MXL-IQ to complete
Walktest sequencing on devices placed in
test (alarm) just before cancellation. The
MXL-IQ completes the final 60 seconds of
the Walktest as indicated in Walktest
Ending Sequence (See page 5-4).

System SIL
Select this option to walktest all CZM-4
zones, CZM-1B6 zones, MID-16 inputs, and
ALD inputs without audible feedback to the
technician. This mode inhibits the
MXL-IQ from annunciating real alarm
conditions.

Extend
Select this option from the menu while in
the Walktest mode to reset the Walktest
timer to the 4 hours remaining mark.

Loop w/AUD
Select this option to walktest input devices
on a specific ALD loop, MOI-7 (MID-16)
group, or on all four zones of a CZM-4 with
audible feedback to the technician. This
mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD
loop or CZM-4 conventional zones in
Walktest.

Loop SIL
Select this option to walktest input devices
on a specific ALD loop, MOI-7 (MID-16)
group, or all four zones of a CZM-4 without
audible feedback to the technician. This
mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD
loop or CZM-4 conventional zones in
Walktest.

Zone wAUD
Select this option to walktest an individual
conventional zone (CZM-1B6 or CZM-4
zone) with audible feedback to the technician. This mode inhibits the MXL-IQ
from annunciating real alarm conditions
for the conventional zone in Walktest.

Zone SIL
Select this option to walktest an individual
conventional zone (CZM-1B6 or CZM-4)
without audible feedback to the technician.
This mode inhibits the MXL-IQ from
annunciating real alarm conditions for
the conventional zone in Walktest.

5-2
Technical Manuals Online! - http://www.tech-man.com

WARNING
A device placed in Walktest is disconnected from its usual functions. Alarm
causing devices in Walktest DO NOT
CAUSE ALARMS until the MXL-IQ is
out of the trouble of Walktest.

Suggested Walktest
Procedure

In order to reduce the chance of problems,


the following procedure must be followed
before performing the Walktest.
1. Inform the person in charge of the MXL-IQ
fire alarm system that a Walktest is to be
performed and that part or all of the fire
detection system will be disabled. It is
also advisable (or may be required) to
notify the fire department of the test.
2. Use the MXL-IQs LIST menu to obtain a
printout of the device types and custom
messages for ALL modules to be
walktested.
3. Review the list with the person in charge
of the fire protection equipment to
ensure that the custom messages
provide adequate information for locating
and testing the devices in question.
4. Disable the ASD applications in the
system using ASD_Device in the TEST
menu prior to performing the walktest.

Walktest Operating Instructions


Once the test ASD device option has been
enabled using the test menu, the tester
should wait 3 minutes before attempting
to test the ASD devices. This will ensure
that the ASD R-Algorithm has been
disabled for the test. When the test is
complete, press ASD_Device again to
re-enable ASD R-Algorithm, or it will
automatically re-enable after 4 hours.
The System will not reset if the ASD
devices are still in the disabled state.
5. Initiate Walktest. Test devices in a
predetermined, orderly sequence.
6. When the Walktest is complete (timed
out/canceled), acknowledge the OUT
OF TROUBLE condition and reset the
MXL-IQ. When the system indicates
SYSTEM NORMAL, the test is complete.
WARNING: A device placed in Walktest is
disconnected from its usual functions.
Alarm causing devices in Walktest do NOT
cause alarms until the MXL-IQ is out of the
trouble of Walktest.
In both the silent (SIL) and audible (wAUD)
Walktest modes, information is displayed on
the Control Panel LCD and printed on the
printer (if a printer is installed). The audible
(wAUD) mode also provides audible feedback to the technician with the testing of each
input device. Audible feedback is NOT
included on circuits with zone coded audibles.
A system with only zone coded audibles
ALWAYS results in a silent Walktest.

NOTE: The Walktest Ending Sequence


(See page 5-4) occurs with audible warnings in the audible Walktest modes.
NOTE: The MXL-IQ will not allow a
walktest to be initiated if there are Alarms
or Supervisory events in the event queues.

Walktest the System


To place all CZM-4 zones, MID-16 inputs,
and ALD input devices in Walktest, follow
the procedure below:
Move the cursor to the S in System
wAUD for a Walktest with audible
feedback or to the S in System SIL for
a silent Walktest.
Press ENTER.

Technical Manuals Online! - http://www.tech-man.com

The following events take place:


- the PARTIAL SYSTEM DISABLE
LED lights
- the TROUBLE LED flashes
- the internal audible sounds
- the Walktest activated trouble for the
MXL-IQ records on the trouble list
- if a printer is installed, the trouble is
also printed
The LCD display on the MKB-4 reads:
In Walktest. Normal operation
disabled. ENTER to continue.

Press ENTER or wait 60 seconds and


the display reads:
Walktest expires in 4 hrs unless
canceled. ENTER to continue.

Press ENTER, or wait 60 seconds and


the MXL-IQ returns to the Walktest
menu. (The MXL-IQ is in system
Walktest.) The LCD indicates the time
remaining in Walktest in the last five
positions on the display. The time is
indicated in HH:MM (hours:minutes) until
less than one hour remains, then it is
indicated in MM:SS (minutes:seconds).
Locate the device to be tested and place
that device in alarm (or trouble). When
the event is reported to the MXL-IQ, the
following sequence occurs:
1. When the System is in the audible
Walktest mode, all silenceable and nonsilenceable audibles that are not already
active or disarmed sound the code,
depending on how the device is used in
the CSG-M. The codes are:
EVENT

CODE

ALARM

2 seconds on, then off

SUPERVISORY

2 one-second pulses (on-off)

TROUBLE

4 seconds on, then off

SECURITY

4 one-second pulses (on-off)

STATUS/OTHER

6 seconds on, then off

5-3

Walktest Operating Instructions


2. When a printer is installed, the printer
prints a message similar to the following:
WLK [event type] IN/OUT device
address time/date device type,
custom message, trouble type
(if applicable)

Move the cursor to the L in Loop wAUD


for a Walktest with audible feedback or
to Loop SIL for a silent Walktest.
Press ENTER.
The MXL-IQ prompts the user for the
module number to be tested.

3. The LCD displays the device address,


custom message, WLK IN/OUT [event
type], and device type for 8 seconds.

Enter the desired module network


address, including all leading zeros,
followed by ENTER.

4. If the ALD device has an LED, it turns on


for 30 seconds to provide additional
feedback to the technician.

If the network address entered is not an


ALD, MOI-7, or CZM-4, the message
Invalid type for Walktest is displayed for
2 seconds on the LCD. The display then
returns to the Walktest menu.

If the MXL-IQ detects multiple events, they


are automatically spaced 8-10 seconds
apart to allow for separation of the coding.
Up to five simultaneous events may be
queued for processing.

If the module type is an ALD, MOI-7, or


CZM-4 in the CSG-M, the following
events take place:

Walktest Ending Sequence

- the PARTIAL SYSTEM DISABLE LED


lights

NOTE: This sequence does not occur in


Silent Walktest.

- the TROUBLE LED flashes

When 5 minutes remain in Walktest, all


silenceable and non-silenceable audibles
that are not already active or disarmed cycle
on-off five times (1 second on) to indicate
that the Walktest will time out in 5 minutes.
This occurs in the audible mode only.
When 1 minute remains, event coding and
the processing of devices to the LCD are
suspended. If a device is alarmed, it is cycled
silently through the resetting sequence.
When 45 seconds remain, all silenceable
and non-silenceable audibles that are not
already active or disarmed cycle on-off until
Walktest times out. Do NOT continue to
walktest devices. This 45 second period
of no new Walktest events ensures that all
devices are reset when the Walktest timer
expires and the System returns to normal
operation. Alarming a device during this
period might result in the reporting of
erroneous events when the system
returns to normal operation.

Walktest Entire ALD Loop, MOI-7


(MID-16), or CZM-4 Module
To place an ALD loop of input devices, an
entire set of MID-16 (MOI-7) inputs, or all
four zones of a CZM-4 module in Walktest,
follow the procedure below:

5-4
Technical Manuals Online! - http://www.tech-man.com

- the internal audible sounds


- the Walktest activated trouble for the
module appears on the trouble list
- if a printer is installed, the trouble is also
printed
The LCD display on the MKB-4 reads:
In Walktest. Normal operation
disabled. ENTER to continue.

Press ENTER or wait 60 seconds and


the display reads:
Walktest expires in 4 hrs unless
canceled. ENTER to continue.

Press ENTER or wait 60 seconds and


the MXL-IQ will return to the Walktest
menu. (The MXL-IQ is in system
Walktest.) The LCD indicates the time
remaining in Walktest in the last five
positions on the display. The time is
indicated in HH:MM (hours:minutes) until
less than 1 hour remains; then it is
indicated in MM:SS (minutes:seconds).
Locate the device to be tested and place
that device in alarm (or trouble). When
the event is reported to the MXL-IQ, the
following sequence occurs:

Walktest Operating Instructions


1. When the System is in the audible
Walktest mode, all silenceable and nonsilenceable audibles that are not already
active or disarmed sound the code,
depending on how the device is used in
the CSG-M. The codes are as follows:
EVENT

CODE

ALARM

2 seconds on, then off

SUPERVISORY

2 one-second pulses (on-off)

TROUBLE

4 seconds on, then off

SECURITY

4 one-second pulses (on-off)

STATUS/OTHER

6 seconds on, then off

2. When a printer is installed, the printer


prints a message similar to the following:
WLK [event type] IN/OUT device
address time/date device type,
custom message, trouble type
(if applicable)

3. The LCD displays the device address,


custom message, WLK IN/OUT [event
type], and device type for 8 seconds.
4. If the ALD device has an LED, it turns on
for 30 seconds to provide additional
feedback to the technician.
If the MXL-IQ detects multiple events, they
are automatically spaced 8-10 seconds
apart to allow for separation of the coding.
Up to five simultaneous events may be
queued for processing.

Walktest Ending Sequence


NOTE: This sequence does not occur in
Silent Walktest.
When 5 minutes remain in Walktest, all
silenceable and non-silenceable audibles
that are not already active or disarmed cycle
on-off five times (1 second on) to indicate
that the Walktest will time out in 5 minutes.
This occurs in the audible mode only.
When 1 minute remains, event coding and
the processing of devices to the LCD are
suspended. If a device is alarmed, it is cycled
silently through the resetting sequence.
Technical Manuals Online! - http://www.tech-man.com

When 45 seconds remain, all silenceable


and non-silenceable audibles that are not
already active or disarmed cycle on-off until
Walktest times out. Do NOT continue to
walktest devices. This 45 second period
of no new Walktest events ensures that all
devices are reset when the Walktest timer
expires and the System returns to normal
operation. Alarming a device during this
period might result in the reporting of
erroneous events when the system
returns to normal operation.

NOTE: If an alarm or supervisory is


reported from a device that is NOT in
Walktest, the Walktest is suspended
immediately. No further Walktest events
are annunciated or coded. The Walktest
remains running in the background of the
MXL-IQ until it times out or is canceled.
WARNING:
When performing a partial system
Walktest, DO NOT TEST any devices
that are not in the Walktest as this will
cause an alarm in the system.

Walktest Individual CZM-1B6 or CZM-4


Zone
To place an individual CZM-1B6 or CZM-4
zone in Walktest, follow the procedure
below:
Move the cursor to the Z in Zone wAUD
for a Walktest with audible feedback or
Z SIL for a silent Walktest.
Press ENTER.
The MXL-IQ prompts the user for the
module and device number to be tested.
Enter the desired network address,
including all leading zeros, followed by
ENTER.
If the network address entered is not a
CZM-4 or CZM-1B6 zone, the message
Invalid type for Walktest is displayed for
2 seconds on the LCD. The display then
returns to the Walktest menu.
If the module type is a CZM-1B6 or
CZM-4 zone in the CSG-M, the following
events take place:

5-5

Walktest Operating Instructions


- the PARTIAL SYSTEM DISABLE LED
lights

2. When a printer is installed, the printer


prints a message similar to the following:

- the TROUBLE LED flashes

WLK [event type] IN/OUT device


address time/date device type,
custom message, trouble type
(if applicable)

- the internal audible sounds


- the Walktest activated trouble for the
zone records on the trouble list
- if a printer is installed, the trouble is also
printed
The LCD display on the MKB-4 reads:
In Walktest Normal operation
disabled. ENTER to continue.

Press ENTER or wait 60 seconds and


the display reads:
Walktest expires in 4hrs unless
canceled. ENTER to continue.

Press ENTER or wait 60 seconds and


the MXL-IQ returns to the Walktest
menu. (The MXL-IQ is in system
Walktest.) The LCD indicates the time
remaining in Walktest in the last five
positions on the display. The time is
indicated in HH:MM (hours:minutes) until
less than 1 hour remains, then it is
indicated in MM:SS (minutes:seconds).
Locate the device to be tested and
place that device in alarm (or trouble).
When the event is reported to the
MXL-IQ, the following sequence occurs:
1. When the System is in the audible
Walktest mode, all silenceable and nonsilenceable audibles that are not already
active or disarmed sound the code,
depending on the device usage in the
CSG-M. The codes are as follows:
EVENT

CODE

ALARM

2 seconds on, then off

SUPERVISORY

2 one-second pulses (on-off)

TROUBLE

4 seconds on, then off

SECURITY

4 one-second pulses (on-off)

STATUS/OTHER

6 seconds on, then off

5-6
Technical Manuals Online! - http://www.tech-man.com

3. The LCD displays the device address,


custom message, WLK IN/OUT [event
type], and device type for 8 seconds.
4. If the ALD device has an LED, it turns on
for 30 seconds to provide additional
feedback to the technician.
If the MXL-IQ detects multiple events, they
are automatically spaced 8-10 seconds
apart to allow for separation of the coding.
Up to five simultaneous events may be
queued for processing.
When 5 minutes remain, the system begins the
Walktest Ending Sequence (See page 5-5).
NOTE: If an alarm or supervisory is
reported from a device that is NOT in
Walktest, the Walktest is suspended
immediately. No further Walktest events
are annunciated or coded. The Walktest
remains running in the background of the
MXL-IQ until it times out or is canceled.

WARNING:
When performing a partial system
Walktest, DO NOT TEST any devices
that are not in the Walktest as this will
cause an alarm in the system.

+D=FJAH

History Log
The MXL-IQ history system has five major
parts. They are:
1. CSG-M options that control the type and
number of events the MXL-IQ records.
2. Logging lists that record MXL-IQ
hardware events.
3. Event viewing and listing in the MXL-IQ
through the MKB-4 and attached printer.
4. History removal and collation outside the
MXL-IQ.
5. Report generation and analysis on an
external PC.

CSG-M History Options

INTRODUCTION

The CSG-M gives the designer a set of


options to use for operating the history
system. The designer must first decide
whether or not to use the history option. If
he chooses to use it, he must select the
mode of logging and which event types to
include in the log. The History Recording
Options are selected from the Options,
System Message, Authorizations menu.
(See Screen 1.)
To access the history option, move the
cursor to highlight History Recording
Options and press ENTER. The history
recording option selection screen is then
displayed as shown in Screen 2, page 6-2.

Fire Protection Company Name


CSG-M Memory=2900 used, 316848 free
Options, System Message, Authorizations

CONFIG => TEST1

Options, System Message, Authorizations


Other System Flags
History Recording Options
System Holidays

Press First Letter or Move Cursor to Highlight Selection, then ENTER

Screen 1
Options, System Message, Authorizations

Technical Manuals Online! - http://www.tech-man.com

6-1

History Log

Fire Protection Company Name


CSG-M Memory=2900 used, 316852 free
History Recording Options

History mode ------------------->


Log alarms --------------------->
Log troubles ------------------->
Log supervisories -------------->
Log securities ----------------->
Log status --------------------->
Log verification --------------->
Log output --------------------->
Log resets --------------------->
Log block acks. ---------------->
Log audible changes ------------>
Log manual sens. changes ------->
Log logic sens. changes -------->
Log arm/disarm ----------------->
Log energize/deenergize -------->
Log time changes --------------->
Log passwords ------------------>
Log overrides ------------------>
Enable History Log Via MKB Menu >

CONFIG => TEST1

Small
YES
YES
YES
YES
NO
NO
NO
YES
YES
YES
NO
NO
YES
YES
YES
YES
NO
NO

Move Cursor to Select, ENTER to TOGGLE

ESC = Prev. Menu

Screen 2
History Recording Options

Screen 2 shows the default conditions for


the history option when it is selected for the
first time.
Keep in mind that the external data base
may not contain all events that were ever
detected. The completeness of the data
base depends on whether the system
operator extracts all event log information
before it is lost.

Logging Methods

The MXL-IQ has two mutually exclusive


ways to log events:
1. Small list
2. Circular list

6-2

Technical Manuals Online! - http://www.tech-man.com

Small List Logging


In the small list logging mode, the MXL-IQ
stores up to 818 events (See Screen 3) in
non-volatile memory. Non-volatile memory
is memory that is not lost when the power is
removed.

When the event storage area becomes


80% full, a system trouble begins.
the trouble audible sounds
the trouble indicator lights
the message Event Log 80% full shows
on the LCD display
this trouble operates like any other
trouble in the system

When the event storage area becomes


90% full, a new system trouble begins.

History Log
the trouble audible sounds
the trouble indicator lights
the message Event Log 90% full shows
on the LCD display
this trouble operates like any other
trouble in the system

When the event log is full, an new trouble


condition occurs which causes the trouble
audible to activate.
the message Log FULL, Events will be
lost appears on the display panel
upon reset this trouble reappears,
replacing the 90% trouble message
when the log is full, all new events are
lost
This system encourages removing history
information into an external data base
before the log overflows.

Circular Logging
In the circular logging mode, the MXL-IQ
guarantees that the most current 500

events are stored in non-volatile memory.


Once all available storage is used, the
oldest history entries are replaced by newer
ones. It is assumed that the end user
selects this mode because he does not
wish to maintain an external history data
base. Therefore, only two warning troubles
are issued:
1. When the number of recorded events
reaches 80% of the total.
2. When the number of recorded events
reaches 90% of the total. Once this
trouble is acknowledged, it disappears
until 80% of events is reached in the
next cycle.
Using the circular logging mode does not
prevent the storage of history information
into an external data base. However, there
is a high probability of loosing old events
because of the limited warnings given when
events are about to be overwritten.
Beginning with MXL-IQ Rev. 6.0, the user
can suppress the Circular History Log Full
Trouble. This option must be set in CSG-M
and is only available if the history is in
circular mode.

Fire Protection Company Name


CSG-M Memory=2900 used, 316852 free
DISPLAY MXL-IQ Panel Info

CONFIG => TEST1

MXL-IQ PANEL INFO:


MXL-IQ ROM Version ------------------->
MXL-IQ Main Board Version ------------>
MXL-IQ Minimum Allowable Board Ver.--->
RAM size ----------------------------->
EEROM size --------------------------->
MXL-IQ Dictionary Version ------------>
MXL-IQ Alt. Dictionary Version-------->
History Memory Available ------------->
IEC Storage Memory Available --------->

Rev. 1.00
2
Rev. 1.00
163840 bytes
114688 bytes
0
0
818 (11) elements (used)
8189 bytes

PROGRAMMING INFO:
Configuration Source Filename -------->
Configuration Size ------------------->
Last Programming Date ---------------->
Configuration Revision Level --------->
Programming Info CHECKSUM ------------>

TEST1
2802 bytes
Wed Mar 22 15:28:16 20XX
215
1085

ANY KEY TO CONTINUE

Screen 3
Display MXL-IQ Panel Info
Technical Manuals Online! - http://www.tech-man.com

6-3

History Log
Logging Item Selection
The system designer can log one or many
event types. The selection is determined by
the system requirements, the amount of
event storage, and the external data base
design. The following list summarizes event
types that can be selected.
* ALARMS
* TROUBLES
* SUPERVISORIES
* SECURITIES
STATUS CHANGES
DEVICE VERIFICATION
OUTPUT ACTIVATIONS
* RESET
* BLOCK ACKNOWLEDGE
* AUDIBLE CONTROL
SET SENSITIVITY
AUTO SET SENSITIVITY
* ARM/DISARM
* ENERGIZE/DE-ENERGIZE
* SET TIME

System Message Authorization, then select


History Recording Options. From History
Recording Options, move the cursor down
to the line that reads Enable History Log Via
MKB Menu, and select YES to compile the
CSG-M program and download it to the
MXL-IQ. (Refer to Screen 2.)

From the MKB Menu


Go to the TEST menu, move the cursor to
the right until it highlights the Event-Log
Menu item, and press Enter to bring up the
submenu for MXL History. Move the cursor
within the submenu to either the left or right
to highlight the Hist_Ctrl item to turn on/off
the History, or Hist_Erase to erase History.
Notice that if the CSG-M system option
Enable History Log Via MKB Menu is set
to NO, these submenus are not accessible.
History turned on or off using the MKB
menus is unaffected through PANEL
RESET, and defaults to the setting in
CSG-M upon power-up.
Pressing ENTER while the cursor is on
Hist_Erase displays the following message
on the MKB asking for confirmation:
Enter to proceed, other key to
abort

* PASSWORD
OVERRIDE
*The items marked with an asterisk are set
as default when the logging option is first
selected. At least one event type must be
selected.

MKB Menu Option to


Enable, Disable and Erase
History

Effective with MXL-IQ Revision 6.0, this


option allows the user with the highest level
password to turn on, turn off, or erase the
History, provided that this system option
has been enabled in the CSG-M and the
History mode is other than NONE (that is,
either small or circular).

Enabling the History Option in CSG-M


From the Main Menu, select System
Configuration Edit, then select Options,

6-4

Technical Manuals Online! - http://www.tech-man.com

Pressing ENTER erases the History section


in the flash no matter what state the History
is currently in (manually turned on or off);
pressing any other key aborts the action.
Manual manipulation of History using the
MKB is logged in History as in the following
examples:
History Manually Erased
History Manually Turned off
History Manually Turned on

NOTES:
1. The operator should download the
history log for future reference before
erasing the MXL-IQs History, since once
the history is erased it cannot be
undeleted.
2. The history menu options do not alter the
history mode selected in the CSG-M.

History Log

Local History Log Query

There is a limited set of query selection and


filter options available within the MXL-IQ.
More complex options are only possible
using an IBM PC that is running the
MXL-IQ history support program.
The user can get history log information
from the MKB-4 control panel by choosing
the TEST menu, selecting EVENT_LOG,
and pressing ENTER. A submenu of filter
selections is then displayed. The choices
are as follows:
Alrm_Only
Only display or print
alarm events
Trbl_Only
Only display or print
trouble events
Superv_Only Only display or print
supervisory events
Security_Only Only display or print
supervisory events
All_events
Display or print all
recorded history events
Hist_Ctrl
Use to turn History
on/off
Hist_Erase
Use to Erase History
If the user makes a selection from the
filter menu using the ENTER key of the
MKB-4, the output goes to the LCD
display.
If the filter menu is selected using the
PRINT key of the MKB-4, then the output
goes to the system printer.
If the group of events selected is empty,
then the MXL-IQ displays or prints, as
appropriate, NO HISTORY ITEMS
FOUND.

Cursor left or right until the desired filter


type (See Query Filters, below) is reached
and then press ENTER to display to the
LCD, or PRINT to print on the MXL-IQ
system printer.
The MXL-IQ asks for a starting date and
time. If a time is entered, it suppresses the
display or printing of older events. This
initial display of time and date indicates the
oldest history event recorded in memory. If
the operator presses the ENTER key
without making any numeric input, then all
events in the log are selected.

Query Filters
A limited set of event type filters is available
from the MXL-IQ control panel. The mutually exclusive filters are:
ALARMS
The Alrm_Only filter selection displays
or prints incoming alarms, alarm acknowledgments, audible control, and resets.
This set of events gives the operator a
clear picture of the important events that
constitute an alarm condition.
TROUBLES
The Trbl_Only filter displays or prints
troubles and resets.
SUPERVISORIES
The Superv_Only filter displays or prints
supervisories and resets.
SECURITIES
The Security_Only filter displays or prints
securities, device arms, device disarms,
and resets.
ALL
The All_events filter displays or prints all
events.

Query Selection
The MXL-IQ supports one query selection
option when generating listings or printouts
from the MXL-IQ control panel.

HISTORY ON/OFF
The Hist_Ctrl filter turns the History events
on/off.

From the TEST menu, move the cursor to


the EVENT_LOG item and press the
ENTER key to select history information.
The MXL-IQ responds with a submenu that
allows an event type filter to be selected.

HISTORY ERASE
The Hist_Erase filter erases the History
events.

Technical Manuals Online! - http://www.tech-man.com

6-5

History Log

Navigating The History


Display

When the operator selects the LCD display


mode, the NEXT and HOLD keys are used
to navigate through the log list. When the
history log list first displays, the oldest history
event shows in the display. Use the NEXT
key to select the next newest event in the list
and the HOLD key to select the next oldest
event in the list. When either end of the
history log list is reached, the message End
of History List displays. Continuing to press
either key wraps the list to the oldest or
newest event, as appropriate.

001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this input.
321
The history log sequence number.
ACK
Optional field indicating that this is an
acknowledgment event. This field is blank
when the initiating event is displayed.

The MXL-IQ remains in the history log list


display mode until the up arrow key is
pressed. As with all menu operations, if no
keys are depressed for one minute, the
current activity is canceled.

12:24:48 Mar 10, 20XX


The time that the event was logged.

History Display Formats

IN

History events display one at a time, in


reverse chronological order, with the oldest
event displayed first. History event displays
use both lines of the LCD.

OUT DEVICE REPORTS RETURN TO


NORMAL STATE

A division symbol () in the first line of the


display gives the operator a quick visual
cue that the MXL-IQ is in the history display
mode. If the history event begins with a
module/device (mmm/ddd) code, the
display is formatted as:
mmmddd

IN
The event direction. The possible event
direction types are:

ON

DEVICE REPORTS ACTIVE STATE

DEVICE TURNED ON

OFF DEVICE TURNED OFF


DIS

DEVICE DISARMED (always occurs


with ARM)

ALR
The event type. The possible abbreviations
for Device Event types are:
ALR

ALARMS

TBL

TROUBLES

If the line begins with an event type name,


such as Block Acknowledge, then the first
line of the display reads:

SUP SUPERVISORY

mmm

SAT

STATUS

VFY

VERIFY

BLOCK ACKNOWLEDGE

where mmm is the module number of the


MKB-4 or SMB that caused the event.

Device Event
A device event is any alarm, trouble, supervisory, or security input change of state. This
change of state can be into or out of an
active condition. The LCD displays:
001001 1ST FLOOR EAST WING ACK
321 12:24:48 Mar 10,20XX IN ALR

6-6

Where:

Technical Manuals Online! - http://www.tech-man.com

SEC SECURITY

DEV DEVICE (used for ON and OFF


indications)
ARM DEVICE ARMED (disarmed when
used with DIS)

Reset Event
A reset event is any cold, warm, manual, or
watchdog reset. The LCD displays:

History Log
253
10100

WATCHDOG RESET
1:22:04 Mar 10,20XX

Where:
253
The module address where the reset
occurred. In this example, the watchdog
reset originated on the SMB-2 at fixed
address 253. The division sign indicates
that this is a history log display.
WATCHDOG RESET
The message describing the type of reset
that occurred. The possible messages for
this field are:
COLD RESET
WARM RESET
MANUAL RESET
WATCHDOG RESET
10100
The history log sequence number.
1:22:04 Mar 10,20XX
The time that the event was logged.

SET TIME
The message describing this display as a
set time event.
10100
The history log sequence number.
2:00:30 Mar 10, 20XX
The date and time in the MXL-IQ before the
SET TIME function was performed.
2:10:45 Mar 10, 20XX
The time when the event was logged. Note
that this is also the new date and time in
the MXL-IQ as a result of this operation.

Block Acknowledge Event


A block acknowledge event occurs when
the alarm, trouble, supervisory, or security
acknowledge key is actuated on an MKB-4
in a system that allows block acknowledgments. The LCD displays:
251
All Alarms Acknowledged
4211 11:25:14 Mar 11,20XX

Where:

Set Time Event


A set time event records any change to the
MXL-IQ real time clock. There are two
occasions when a set time event occurs.
They are:
1. When an operator goes into the TEST
menu and manually changes the real
time clock using the SET_TIME function.
2. At the end of a CSG-M configuration
upload.
The LCD displays:
251 SET TIME - 2:00:30 Mar 10,20XX
10100 2:10:45 Mar 10,20XX

Where:
251
The module address where the time
change occurred. In this example, the set
time originated from the MKB-4 at address
251. The division sign indicates that this is
a history log display.

Technical Manuals Online! - http://www.tech-man.com

251
The module address where the block
acknowledge occurred. In this example, the
block acknowledge originated from the
MKB-4 at address 251. The division sign
indicates that this is a history log display.
All Alarms Acknowledged
The message that describes this display
as an alarm block acknowledge event. The
text changes to reflect one of the following
four types of block acknowledgments, as
appropriate:
All Alarms Acknowledged
All Troubles Acknowledged
All Supervisories Acknowledged
All Security Acknowledged
4211
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.

6-7

History Log

Audible Silenced Event


This event occurs when the audible silence
key is actuated on an MKB-4. The LCD
displays:
251
AUDIBLE SILENCED
4212 11:25:14 Mar 11,20XX

OVERRIDE
The action that is being applied to the
feature. The selections in this field are:
OVERRIDE
NORMAL
4212
The history log sequence number.

Where:

11:25:14 Mar 11, 20XX


The time that the event was logged.

251
The module address where the audible
silence occurred. In this example, the
audible silence originated on an MKB-4 at
address 251. The division sign indicates
that this is a history log display.

Audible Unsilenced Event

AUDIBLE SILENCED
The message that describes this event.
4212
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.

Override Event
This event occurs when an operator
overrides a verification or confirmation. The
LCD displays:
251
CONFIRMATION OVERRIDE
4212 11:25:14 Mar 11,20XX

This event occurs when the audible


unsilence key is pressed on an MKB-4. The
LCD displays:
251
AUDIBLE UNSILENCED
4213 11:25:14 Mar 11,20XX

Where:
251
The module address where the audible
unsilence occurred. In this example, the
audible unsilence originated on an MKB-4
at address 251. The division sign indicates
that this is a history log display.
AUDIBLE UNSILENCED
The message that describes this event.
4213
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.

Where:
251
The module address where the override
operation occurred. In this example, the
confirmation override originated on an
MKB-4 at address 251. The division sign
indicates that this is a history log display.
CONFIRMATION
The feature that is either being overridden
or returned to normal. This selections in
this field are:
CONFIRMATION
VERIFICATION

6-8

Technical Manuals Online! - http://www.tech-man.com

Password Event
This event occurs when an operator enters
a new password at an MKB-4. The LCD
displays:
251
PASSWORD LEVEL : 1
4214 11:25:14 Mar 11,20XX

Where:
251
The module address where the password
event occurred. In this example, the

History Log
password change originated on an MKB-4
at address 251. The division sign indicates
that this is a history log display.
PASSWORD LEVEL : 1
The message that describes this as a
password event and indicates the new
password authorization level that was
entered.
4214
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.

Configuration Changed Event


This event occurs when an operator
uploads a new CSG-M configuration to the
MXL-IQ control panel. The LCD displays:
254
Configuration changed 10->11
4214 11:25:14 Mar 11,20XX

Where:
254
The module addres where the configuration
change occurred. In this example, the
configuration change originated from the
field programmer at address 254. The
division sign indicates that this is a history
log display.
Configuration changed
The message that describes this as a
configuration change event.
10
The old configuration modification sequence number.
11
The new configuration modification sequence number.
Note: These values may not be consecutive. They depend on the number of modifications made to the configuration by the
CSG-M.
4214
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.

Technical Manuals Online! - http://www.tech-man.com

Manual Sensitivity Set Event


A sensitivity set event displays any change
of sensitivity to a detector device that was
made manually at a system control panel.
The LCD displays:
001001 1ST FLOOR EAST WING
321 12:24:48 Mar 10,1995

NORMAL

Where:
001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this input.
321
The history log sequence number.
12:24:48 Mar 10, 20XX
The time that the event was logged.
NORMAL
The sensitivity value sent to the device. The
selectable values include:
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3

Auto Sensitivity Set Event


A sensitivity set event displays any change
of sensitivity to a detector device made by
the auto sensitivity adjustment system. The
LCD displays:
001001 1ST FLOOR EAST WING
2.12 +
321 12:24:38 Mar 10, 20XX

Where:
001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this
input.

6-9

History Log
321
The history log sequence number.
2.12
Indicates that this is an IEC (Enviro-Link)
set sensitivity event. The detector sensitivity
has been set to 2.12 volts. (The voltage can
range from 0-5 volts.) This field may
contain the word CLEAN to indicate that
this detector was cleaned and restored to
its base sensitivity.
+
This symbol represents the type of automatic correction that was made. A plus sign
(+) indicates that the sensitivity was increased, a minus sign (-) indicates that the
sensitivity was decreased.
12:24:48 Mar 10, 20XX
The time that the event was logged.

Logic Sensitivity Set Event

History Print Formats At


The MXL-IQ Panel

The history printout format available at the


MXL-IQ control panel appears in the same
format as all other listing type reports. The
listing output is in the higher character
density mode of the output device. The
vertical pitch varies to clearly distinguish
one event from another. If the target printer
has variable point spacing, each event is
separated by a 0.5 line gap. On printers
without variable point spacing, there is one
full blank line between events.
To interrupt the listing operation at any
time, press the CLEAR key. Significant
system activities, such as alarms, troubles,
etc., automatically terminate the listing. The
printout always indicates when the listing
has been prematurely terminated.
(Refer to the History Log Sample Printout on the following page)
The basic format of the history printout is:

A sensitivity set event displays any change


of sensitivity to a device made by output
logic. The LCD displays:

<Listing Date>

FN0012 Sensitivity set by logic


321 12:24:48 Mar 10,20XX
NORMAL

<Event Type [Modifier]>


<Event Locator>
<Event Time>
<Event Sequence #>
<Event Description>

Where:

<Listing Conditions>

FN0012
The label of the logical function that generated this sensitivity set. The division sign
indicates that this is a history log display.

SENSITIVITY SET BY LOGIC


The message describing this as a logic
sensitivity set event.

(repeated for each event having


matching conditions)

<Listing Terminator>

321
The history log sequence number.
12:24:48 Mar 10, 20XX
The time that the event was logged.
NORMAL
The sensitivity value sent to the device.
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3

6-10

Technical Manuals Online! - http://www.tech-man.com

Where:
Listing Date
Identifies the report type (in this case the
history log) and the date that the report was
generated.
Listing Conditions
Shows the filter and starting date for this
report.

History Log
History Log Sample Printout
1
Line 1
Line 2

10
20
30
40
50
Listing of History Log at 14:32:22 Apr 04,20XX
This is a FULL list beginning at 09:20:02 Mar 01,20XX:

60

70

80

Line 3

SENS NORM. FN0012

06:00:00

Mar 02,20XX

#1

Sensitivity set by output logic

Line 4

SENS Hi_1 FN0013

19:00:00

Mar 02,20XX

#2

Sensitivity set by output logic

Line 5
Line 6

TROUBLE IN 1-1
22:10:11
Mar 02,20XX
#3
Response Too Low, TRI-2R Switch Input + Relay

UTILITY CABINET, Input Dev.

Line 7

ACK. TRBL. 251

22:15:24

Mar 02,20XX

#4

Troubles Block Acknowledged

Line 8

MAN. RST. 251

22:50:03

Mar 02,20XX

#5

Manual Panel Reset

Line 9

SENS NORM. FN0012

06:00:00

Mar 03,20XX

#6

Sensitivity set by output logic

Line 10

SENS Hi_1 FN0013

19:00:00

Mar 03,20XX

#7

Sensitivity set by output logic

Line 11
Line 12

VERIFY
2-11
21:39:00
Ionization Detector

Mar 03,20XX

#8

ROOM 101 FIRST FLOOR, ID-60I

Line 13

SENS NORM. FN0012

06:00:00

Mar 04,20XX

#9

Sensitivity set by logic

Line 14
Line 15

VERIFY
12-23
10:42:20
Ionization Detector

Mar 04,20XX

#10

ROOM 221 SECOND FLOOR, ID-60I

Line 16
Line 17

ALARM IN 12-23
10:43:12
Ionization Detector

Mar 04,20XX

#11

ROOM 221 SECOND FLOOR, ID-60I

Line 18

OUTPUT ON FN0103

10:43:13

Mar 04,20XX

#12

Output logic operation

Line 19

OUTPUT ON FN0010

10:43:13

Mar 04,20XX

#13

Output logic operation

Line 20

ACK. ALARM 251

10:45:21

Mar 04,20XX

#14

Alarms Block Acknowledged

Line 21

SILENCE

10:45:22

Mar 04,20XX

#15

Audibles silenced

Line 22

MAN. RST. 251

10:45:25

Mar 04,20XX

#16

Manual Panel Reset

Line 23

LOGIN 2

10:50:53

Mar 04,20XX

#17

Operator Login to Level 2

Line 24
Line 25

DISARM
12-23
10:51:23
Ionization Detector

Mar 04,20XX

#18

ROOM 221 SECOND FLOOR, ID-60I

Line 26

DISARM

10:52:04

Mar 04,20XX

#19

FAN #1, CRM-4 Relay Output

Line 27

ENERGIZE

10:52:24

Mar 04,20XX

#20

FAN #1, CRM-4 Relay Output

Line 28

SENS HIGH FN0013

19:00:00

Mar 04,20XX

#21

Sensitivity set by logic

251

251

7-2
7-2

Technical Manuals Online! - http://www.tech-man.com

6-11

History Log
Event Type
Identifies the type of history event that is
being reported. The following event types
are arranged in groups. The modifier fields
for each group are different.
Group 1 types:
ACK. ALARM Alarm block acknowledge

SUPERVS

Security causing device


event
Supervisory causing device
event

Group 3 types:
SENS
Sensitivity set

ACK. TRBL.

Trouble block acknowledge

Group 4 types:
LOGIN
Operator login

ACK. SEC.

Security block acknowledge

Group 5 types:
OUTPUT
Output logic event

ACK. SUP.

Supervisory block acknowledge

MAN. RST.

Manual reset via MKB-4

COLD RST.

Hard reset from power off

WARM RST.

Hard reset via reset jumper

WDOG RST.

Hard reset via 6805


watchdog

VERIFY

Alarm verify

ENERGIZE

Energize an output

DE-ENERGIZE De-energize an output

6-12

SECURTY

ARM

Arm a device

DIS-ARM

Disarm a device

SILENCE

Silence audibles

UNSILENCE

Unsilence audibles

CONFIG.

(CSG-M) Configuration
changed

Modifier
The modifier is an optional field that
extends the meaning of the event type. For
example, ALARM IN, where IN explains the
ALARM type.
Group 1 type:
No modifiers for this group
Group 2 types:
IN
Condition now active
OUT
Condition now inactive
ACK
Condition now acknowledged
Group 3 types:
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3
Group 4 types:
0
Lowest access
1
2
3
Highest access
Group 5 types:

Group 2 types:
ALARM
Alarm causing device
event

ON

Condition now active

OFF

Condition now inactive

TROUBLE

Event Locator
This field locates the source or destination

Trouble causing device


event

Technical Manuals Online! - http://www.tech-man.com

History Log
of the event as either a module number,
module-device pair, or function name.

Event Time
The time and date of this event.
Event Sequence #
The sequence number of this event in the
history log list. The maximum value of this
number depends on the type of logging
selected and the length of time since the
last download.
Event Description
The event description is either the custom
message associated with a device, or for
non-devices, it is a descriptive message.

MXL-IQ To CSG-M
Download Formats

Download from the MXL-IQ history log to


the CSG-M history support feature occurs
while the MXL-IQ maintains all normal
operations. There are two ways to access
history log events:
1. Non-destructive modeinformation
can be examined only.

2. Destructive modeinformation can be


extracted from the MXL-IQ and
incorporated into a data base (See
Screen 4). If the information is extracted
from the MXL-IQ, the history is erased
from the system, and the system is
reset. Access to the destructive mode is
password and vendor ID protected.
The history contents and organization of
the CSG-M configuration change over the
lifetime of the system. As a result, the
history extraction process must download
both the encoded history log and its configuration in the CSG-M. At the conclusion
of the extraction process, an .IMH file is
created which contains fixed data that is
common to all history extractions from a
given CSG. This technique has the advantage of eliminating the need for a complex
code in the MXL-IQ to reorganize the data,
shifting that burden to programs in the PC
environment which are more easily modified. However, this technique requires time
to perform the download.
Each access of the history, whether in the
examine or extract mode, requires the
transmission of the entire CSG-M configuration from the MXL-IQ to the PC host. For
very large configurations, this could take
many minutes for the first download after a

Fire Protection Company Name


CSG-M Memory=2900 used, 316848 free
CONFIG => TEST1
Transfer a System to or from an MXL-IQ Panel

SEND System Configuration TO MXL-IQ Panel


READ System Configuration FROM MXL-IQ Panel
VERIFY System Configuration in MXL-IQ Panel
DISPLAY MXL-IQ Panel Info
EXTRACT MXL-IQ Panel History

Move Cursor to Highlight Selection, then ENTER

ESC=Prev. Menu

Screen 4
Transfer a System to or from an MXL-IQ Panel

Technical Manuals Online! - http://www.tech-man.com

6-13

History Log

4. The PC creates a raw data file that


contains an identifying header.

History Download Sequence

5. The PC downloads the compressed


history log data and appends it to the file.

The download process uses the existing


capabilities of the CSG-M programming
system. The sequence for extracting history
log events is as follows:
1. PC contacts the MXL-IQ and requests
the configuration header and data area
pointers.
2. If the PC determines that there is history
data present, then the extraction process
begins.
3. The PC computes the required amount
of storage and determines if the media in
the PC has enough room for it. If there is
sufficient room, the process continues; if

6-14

not, the user is prompted to change


disks.

configuration is changed. If the .IMH file is


present after the first download of a configuration, the operation will run more
quickly on subsequent downloads.

Technical Manuals Online! - http://www.tech-man.com

6. The PC downloads the configuration


data and appends it to the file.
7. The resulting file is closed and then
tested for integrity. Any irregularity in this
validation ends the extraction process
and signals the user.
8. If this is a non-destructive download,
then the process is complete.

If this is a destructive download, then


the clearing of the history log in the
MXL-IQ begins. A warm reset occurs in
the MXL-IQ at the end of the extraction
process.

+D=FJAH

Connections and Ratings

ALD-2I Connections and Ratings


Electrical ratings:
Supervisory

Alarm

30 VDC peak
66mA max
30 VDC peak
66mA max
(60 devices in alarm)

All wiring must be in accordance with


Article 760 of NEC and the local building
codes.
Only the devices listed in Appendix A,
Table 2 - Analog Addressable Detectors on page A-1 may be used. The UL
identifiers for compatibility are the same as
the model names specified.

See Notes 7 and 11.


See Note 8.

ALD-2I Wiring

Technical Manuals Online! - http://www.tech-man.com

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
100 ohms total.
4. Maximum capacitance:
0.4F between
+ loop and loop.
0.8F between
+ loop and chassis.
0.8F between
loop and chassis.
5. Each detector or group of
detectors, requires a
two-wire circuit of
thermo-plastic fixture
wire enclosed in conduit
or limited energy
shielded cable without
conduit, if permitted by
local building codes.
6. No end of line device
required.
7. Operates in full
conformance with
Style 6.
8. Operates in full
conformance with
Style 4.
9. Either loop may be wired
Class A or B.
10. 60 devices maximum per
loop.
11. T-tapping is NOT
allowed on Class A
loops.
12. Both circuits are
supervised.

7-1

ALD-2I Connections and Ratings

7-2

Technical Manuals Online! - http://www.tech-man.com

CMI-300 Connections and Ratings


Electrical ratings:
Supervisory or Alarm
5 VDC, 96mA max

TYPICAL CLASS B (STYLE 4)


CONNECTION

2-WIRE
18 AWG

CABLE MIN*

TB1

TB2

LLM-1

LLM-1
4

* USE 2-WIRE COPPER CABLE, 105 C, 300V, 18 AWG,

TB2

TB1

MOM-2/4

CXM-1

NOTES
1. All wiring must conform
to local codes and to the
authority having
jurisdiction over the
installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 4.

SOLID OR STRANDED, MAX 7 STRANDS.

CMI-300 Wiring - Typical Class B (Style 4) Connection

Technical Manuals Online! - http://www.tech-man.com

7-3

CMI-300 Connections and Ratings

TYPICAL CLASS A (STYLE 7)


CONNECTION

TB1

TB1

MOM-2/4
4

LLM-1
TB2

TB2

LLM-1

*USE 2-WIRE

COPPER CABLE,
105 C, 300V, 18 AWG,
SOLID OR STRANDED,
MAX 7 STRANDS.

TB1

NOTES
1. All wiring must
conform to local codes
and to the authority
having jurisdiction
over the installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 7.

TB1

TWO 2-WIRE 18 AWG CABLE MIN*


600 OHM MAX LINE RESISTANCE
TOTAL PER PAIR

LLM-1
TB2

TB2

LLM-1

CXM-1

CMI-300 Wiring - Typical Class A (Style 7) Connection

CONDITIONED NON-SWITCHED
LEASED TELEPHONE LINE,
600 OHMS IMPEDANCE
TYPICAL CLASS B (STYLE 4)
CONNECTION

R1
560 OHMS,
1/2W, 5%
P/N 140-820366

TB1

LLM-1
4

R2

CXM-1

CMI-300 Wiring - Typical Class B (Style 4) Connection


Using Conditioned, Non-Switched Telephone Line

7-4

LLM-1
TB2

TB1

MOM-2/4

TB2

NOTES
1. All wiring must
conform to local codes
and to the authority
having jurisdiction
over the installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 4.

Technical Manuals Online! - http://www.tech-man.com

CRM-4 Connections and Ratings


Electrical ratings:
24 VDC
15mA (no energized relays)
Add: 18.7mA per energized relay
(75mA - all relays energized)

MOM-4
(TB-1, TB-2, TB-3, or TB-4)
or
MOM-2
(TB2 or TB4)

CRM-4 Relay Wiring

Technical Manuals Online! - http://www.tech-man.com

NOTES
1. Contact rating: 2A,
30VDC/120 VAC
resistive.
2. Use only with power
limited / Class 2
circuits.
3. Coils are supervised
when de-energized.
4. Contacts are not
supervised.
5. All relay contacts are
shown in normal
(de-energized) state.

7-5

CRM-4 Connections and Ratings

7-6

Technical Manuals Online! - http://www.tech-man.com

CSM-4 Connections and Ratings


Electrical ratings:

Only the devices listed in Compatible


Notification Appliances, P/N 315096363 may be used. The UL identifiers
for compatibility are the same as the
model names specified.

Supervisory

24V unfiltered,
full wave rectified
12mA max

Alarm

24V unfiltered,
full wave rectified
1.5A max

NOTIFICATION APPLIANCES
(NFPA 72 Local)
All wiring must be in accordance with
Article 760 of NEC and the local building codes.

STYLE Y
(CLASS B)

STYLE Z
(CLASS A)

CIRCUIT 1

CIRCUIT 2

2.2K, 1/2W

NOTIFICATION
APPLIANCES

+
MOM-4 (TB1, TB2, TB3, or TB4)
or
MOM-2 (TB2 or TB4)

2.2K,
1/2W

NO CONNECTION

+
1

NO CONNECTION

10 11 12

13 14 15 16

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
3 ohms total.
4. End of line device:
2.2K, W,
P/N 140-820380.
5. Either circuit may be
wired Class A or B.
6. Both circuits are
supervised.
7. Polarity shown in
supervisory state.

CSM-4 Loop Wiring for Supervised Notification Appliance Circuit

Technical Manuals Online! - http://www.tech-man.com

7-7

CSM-4 Connections and Ratings

NOTES
1. Both circuits are not
power limited.
2. The total loop
resistance from the
LLM-1 to the Municipal
Tie, including the 14.5
ohms in the Municipal
Tie, should not exceed
22.5 ohms.
3. Either circuit may be
used.
4. Polarity shown in
supervisory state.

MUNICIPAL TIE
(NFPA 72 Municipal Tie)
All wiring must be in accordance with
Article 760 of NEC and the local building
codes.

Electrical ratings:
Trip Coil

14.5 ohms

Trip Current

220 to 320mA
DC (momentary)

Supervisory
Current
Voltage

12mA DC
24V unfiltered,
full wave rectified

Minimum emergency power


60 hour standby
5 minute alarm

MOM-4 (TB1, TB2,


TB3,or TB4)
or
MOM-2 (TB2 or TB4)

CSM-4 Loop Wiring for Supervised Municipal Tie

LEASED LINE
(NFPA 72 Remote Station)
All wiring must be in accordance with
Article 760 of NEC and the local building
codes.

When a CSM-4 circuit is used as a Leased


Line trouble output, SW1 and SW2 on
switch S2 must be set. These positions
permit the degrade trouble bus to activate
the trouble line.

Electrical Ratings:
24V unfiltered, full wave rectified
Load must be a compatible polarity
reversal labeled remote station
receiver unit
Rated current
3mA to 9mA, alarm/supervisory
External circuit resistance
2K to 5K ohms
Minimum emergency power
60 hour standby
5 minute alarm

7-8

Technical Manuals Online! - http://www.tech-man.com

CSM-4 Connections and Ratings

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. External resistance:
2K-5K ohms.
3. Both circuits are not
supervised.
4. Polarity shown in
supervisory state.

MOM-4 (TB1, TB2,


TB3,or TB4)
or
MOM-2 (TB2 or TB4)

CSM-4 Leased Line Circuit Wiring

RELEASING SERVICE (Per NFPA 12A,


NFPA 13, and NFPA 2001)

Electrical Ratings:
Solenoids

24 VDC
16.8 watts max
700mA max

Supervisory

12mA max

Alarm

800mA max

All wiring must be in accordance with


Article 760 of NEC and the local building
codes.
Set all positions of switch S2 to OFF
(OPEN).
Application
NFPA 13
(Pre-Action
Deluge)

Make
Skinner

Model
LV2LBX25, 24V

ASCO

T8210A107, 24V

ASCO

R8210A107, 24V

ASCO

8210A107, 24V

NFPA 12A

Pyro

50 0-982631, 24V

Pyro

50 0-286652, 24V

(Halon)

Pyro

50 0-083377, 24V

Pyro

50 0-086929, 24V

Pyro

ECHS-24 EXP

NFPA 20 01
(FM-20 0)

NOTES
1. Releasing zones are
not power limited.
2. Maximum resistance:
3 ohms total.
3. No end of line device
required.
4. Both circuits are
supervised for opens
only.
5. Polarity show in
supervisory state.

MOM-4 (TB1, TB2,


TB3,or TB4)
or
MOM-2 (TB2 or TB4)

CSM-4 Loop Wiring for use as Releasing Service


(per NFPA 12A, NFPA 13, and NFPA 2001)

Technical Manuals Online! - http://www.tech-man.com

7-9

7-10

CSM-4 Connections and Ratings

Technical Manuals Online! - http://www.tech-man.com

NOTES:
1. Use only listed solenoids from the following table:

Application
NFPA 13
(Pre-Action
Deluge)

Make
Skinner

Model
LV2LBX25, 24V

ASCO

T8210A107, 24V

ASCO

R8210A107, 24V

ASCO

8210A107, 24V

NFPA 12A

Pyro

50 0-982631, 24V

Pyro

50 0-286652, 24V

(Halon)

Pyro

50 0-083377, 24V

Pyro

50 0-086929, 24V

Pyro

ECHS-24 EXP

NFPA 20 01
(FM-20 0)

2.
3.
4.
5.

Solenoids supervised for opens only.


Polarity shown in supervisory condition.
Releasing circuits are not power limited.
No end-of-line device used on Pre-Action/Deluge or
releasing circuits.
6. Configure CSM-4 Pre-Action/Deluge circuits as
Municipal Tie.
7. Maximum of 4 zones per MOM-2.
8. Each MOM-2 must be powered from a separate
ALARM-SAF power supply.
9. Set all positions of S2 on the CSM-4 to OFF (OPEN).

MXL-IQ Releasing Service Wiring Diagram Using MOM-2 (NFPA 12A, 13, and 2001)

Technical Manuals Online! - http://www.tech-man.com

MOUNT VAI-1 AND TRI-60/B6 IN ALARM - SAF CABINET

VAI-1

24 VAC
+
BATTERY _

1
2
3
4

TRI-60/B6
8 7 6 5 4 3 2 1
N N N
C C C

1 2 3 4
CHASSIS

CHASSIS
120 VAC
INPUT

END OF LINE
RESISTOR
3.6K, 1/4W
P/N 140-820185

CHASSIS
NEUTRAL
HOT

DC OUT

+
_

FAULT

+
_

1
2
3
4

ALARM - SAF
MODEL AS/PS5-BFS-24-UL
UL GUIDE UTRZ
FILE NO. S3584

(Pre-Action
Deluge)
NFPA 12A
(Halon)

2.
3.
4.
5.
6.

Make
Skinner

Model
LV2LBX25, 24V

Maximum #
per MOM-4
5

ASCO

T8210A107, 24V

ASCO

R8210A107, 24V

ASCO

8210A107, 24V

Pyro

50 0-982631, 24V

Pyro

50 0-286652, 24V

Pyro

50 0-083377, 24V

Pyro

50 0-086929, 24V

Pyro

ECHS-24 EXP

Solenoids supervised for opens only.


Polarity shown in supervisory condition.
Releasing circuits are not power limited.
No end of line device used.
Each MOM-4 must be powered from a separate
ALARM-SAF power supply.
7. Set all positions of S2 on the CSM-4 to OFF (OPEN).

12 VDC LEAD ACID


BTX-1 31 AH

SOLENOID

SOLENOID

+
12 VDC LEAD ACID
BTX-1 31 AH

SOLENOID

SOLENOID

TO SMB-1/-2 P6

N N
C C

N N N N
C C C C

N N N N
C C C C

N N
C C

TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P1

CSM-4

P2

CSM-4

N
C1
P5

N N
C C

2 1

N N N N
C C C C

N N
C C

TB3

TB6

P7

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P3

CSM-4

P4

DO NOT USE

MOM-4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

P8

TB2
N N
C C

N N N N
C C C C

N N
C C

N N N N
C C C C

N
C

TB7
2 1
N N
C C

N N N N
C C C C

P10

2
NC
1
NC
TB5

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TB4

DO NOT USE

2.2K, 1/2W
P/N 140-820830

7-11

SOLENOID

MXL -IQ Releasing Service Wiring Using MOM-4 (per NFPA 12A, NFPA 13, and NFPA 2001)

N N N N N N N N N N N N N N N N
C C C C C C C C C C C C C C C C

For FM Approved
Deluge/Pre-Action:
All initiating devices
connected to the
system MUST be
wired Class A.

CSM-4 Connections and Ratings

NFPA 20 01
(FM-20 0)

To Analog loop on MMB-1/2


or ALD-2I. Program TRI-60/B6
+
_ as trouble causing program
for normally open operation.
Refer to TRI-60 Installation
Instructions, P/N 315-092329
and TRI-B6 Installation
Instructions, P/N 315-093315.

BATTERY ENCLOSURE
UL LISTED FOR FIRE PROTECTIVE SERVICE

NOTES
1. Use only listed solenoids from the following table:

Application
NFPA 13

_ Power supply
common connection
Connect to:
SMB-1/2 TB5 Terminal 9

CSM-4 Connections and Ratings

7-12

Technical Manuals Online! - http://www.tech-man.com

CZM-1B6 Connections and Ratings


Electrical ratings:

Initiating Devices

Supervisory

18-24.5 VDC
4mA max

Alarm

18-24.5 VDC
45mA max

Zone Resistance

35 ohms total

Max Ripple

500mV

The CZM-1B6 supports one zone of


initiating devices in either Class A (Style
D) or Class B (Style B). The initiating
devices are connected to terminals 5-8 on
the CZM-1B6 terminal block.

Electrical connections:
There are three basic connections to the
CZM-1B6 as follows:

Only the devices listed in Appendix A,


Table 1 - Conventional Detectors:
Compatible With CZM-1B6 on page A-1
may be used. Use up to 15 detectors, any
combination of those listed. Only one
PB-1191, and no additional devices, can
be connected to a CZM-1B6. Detector
operated accessories cannot be used with
the CZM-1B6. The model numbers listed
are the UL compatibility identifiers.

STYLE B
(CLASS B)

EOL

STYLE D
(CLASS A)
+

POWER

POWER
+

ANALOG LOOP

EARTH

EARTH

ANALOG LOOP

EOL

CZM-1B6 Class A (Style D) Wiring

Technical Manuals Online! - http://www.tech-man.com

CZM-1B6 Class B (Style B) Wiring

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
35 ohms total.
4. Each detector or group
of detectors, requires
a two-wire circuit of
thermoplastic fixture
wire enclosed in
conduit or limited
energy shielded cable
without conduit, if
permitted by local
building codes.
5. End of line device:
4.7K, W,
P/N 140-820188.
6. Either circuit may be
wired Class A (Style D)
or Class B (Style B)
7. 15 devices maximum
per circuit.
8. Initiating circuit is
supervised.

7-13

CZM-1B6 Connections and Ratings


PB-1191
When the PBA-1191 is used, the
2-position plug from jumper J1
must be removed as follows:
Remove the screw from the center
of the CZM-1B6 plastic cover and
place it to one side.
Remove the circuit board and
locate jumper J1.
Remove the 2-position plug from J1.
Reassemble the circuit board and plastic
cover using the screw that was removed
in the first step.
Be sure to use the correct end of line
device with the CZM-1B6 in this configuration.

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
100 ohms total.
4. Maximum capacitance:
0.4F between + loop
and loop.
0.8F between + loop
and chassis.
0.8F between loop
and chassis.
5. Each detector or group
of detectors, requires a
two-wire circuit of
thermoplastic fixture
wire enclosed in conduit
or limited energy
shielded cable without
conduit, if permitted by
local building codes.
6. No end of line device
required.
7. Operates in full
conformance with
Style 6.
8. Operates in full
conformance with
Style 4.
9. Either loop may be wired
Class A or B.
10. 60 devices maximum per
loop.
11. T-tapping is NOT
allowed on Class A
loops.
12. Both circuits are
supervised.

7-14

PB-1191 Installation

Analog Loops
The CZM-1B6 communicates with the
MXL-IQ via the MXL-IQs analog loops,
which may be on the SMB-2 or the optional

ALD-2I module. The analog loops may be


wired Class A (Style 6) or Class B (Style 4).

ALD-2I
MOM-4
TB2

MOM-4
TB1

SMB-2

SMB-2

LOOP LOOP LOOP LOOP LOOP


1
2
1
2
1

LOOP
2

TB2

TB3

CLASS A INSTALLATION
See notes 7 and 11.

CZM-1B6

+
+

CZM-1B6

1
7

Technical Manuals Online! - http://www.tech-man.com

CLASS B INSTALLATION
See note 8.

CZM-1B6

1
2

CZM-1B6

1
7

CZM-1B6

1
8

CZM-1B6
1 2

Analog Loop Wiring

CZM-1B6

1
7

CZM-1B6 Connections and Ratings

CZM-1B6 Power
The CZM-1B6 receives its power from the
CZM-1B6 power output on the SMB-2. This
power is available on TB5 of the SMB-2 on
terminals 9-12. The power may be wired as

SMB-2
TB5

12
11
10

Class A or Class B. Since the CZM-1B6


monitors the power at its screw terminals, it
is possible to T-tap the power connection; this
can be done only in the Class B configuration.

CLASS A INSTALLATION

+
+

See note 6.

CZM-1B6
5

CZM-1B6
5

CZM-1B6

1 2

12
11
10
9

CLASS B INSTALLATION

+
-

4
1

CZM-1B6
5

4
1 2

CZM-1B6
5

CZM-1B6

+
4

CZM-1B6

CZM-1B6
5

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
4 ohms total.
4. No end of line device
required.
5. Circuit is supervised.
6. T-tapping is NOT
allowed on Class A
loops.
7. For loop resistance,
refer to the SMB-2
Installation Instructions,
P/N 315-095097.

CZM-1B6 Power Wiring

Technical Manuals Online! - http://www.tech-man.com

7-15

CZM-1B6 Connections and Ratings

NOTES
1. Intrinsically Safe Output:
Open Circuit Voltage: 28 VDC
Short Circuit Current: 93mA
2. Maximum loop resistance must not exceed 35 ohms.
3. A maximum of ten DI-3IS Ionization Detectors or up to
five S121 or S122 Flame Detectors can be used in
addition to mechanical (non-energy storing) shorting
devices.
4. Maximum safe system voltage is 250 VAC.
5. For mounting and installation of the ISI-1, see the ISI-1
instructions.
6. Only mechanical (non-energy storing) shorting devices

Intrinsically Safe Zone Wiring


FM Approved Only (Not UL Approved)

7-16

Technical Manuals Online! - http://www.tech-man.com

such as the MS-51 Manual Station may be used.


7. WARNING: Do not make any connection to terminal 6 of
the DB-3S base. Such a connection would void use in an
intrinsically safe application.
8. In addition, S121 and S122 are also approved for use in
Class II and Class III, Groups E, F, and G.
9. For guidance on installation see ANSI/ISA RP 12.6,
Installation of Intrinsically Safe Instrument Systems in
Class I Hazardous Locations.
10. For DI-3IS information, see the DI-3 Series installation
instructions, P/N 315-081943.
11. For S121 and S122 information, see the installation
instructions, P/N 315-085258.

CZM-4 Connections and Ratings


Electrical ratings:

Initiating devices per zone:

Supervisory

21.7-22.8 VDC
4mA max

Alarm

21.7-22.8 VDC
180mA per zone max

Max ripple

400mV

Up to 30 detectors, any combination of


those listed in Appendix A, Table 1 Conventional Detectors (except the
PBA-1191), on page A-1, may be used.
Up to five waterflow switches or 20
tamper switches may be used. Wiring
may be Style D (Class A) or Style B
(Class B).

STYLE B
(CLASS B)

STYLE D
(CLASS A)

STYLE B
(CLASS B)

ZONE 1

ZONE 2

ZONE 3

ZONE 4

10

11

12

13

14

15

16

50uF
50V *

MOM-4 TERMINALS
TB1 (UPPER SLOT) OR
TB2 (LOWER SLOT) OR
MOM-2 TERMINAL TB2

50uF 50V *

PBA-1191
Linear Beam Detector

- + - + - +
+

50uF, 50V *

DO NOT
USE

* EOL CAPACITOR (P/N 100-115588)


** EOL RESISTOR (P/N 140-820188)

CZM-4 Wiring

Technical Manuals Online! - http://www.tech-man.com

EOL
4.7K, 1/4W **

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
70 ohms total
(40 ohms if relay bases
are used).
4. Each detector or group
of detectors, requires a
two-wire circuit of
thermoplastic fixture
wire enclosed in
conduit or limited
energy shielded cable
without conduit, if
permitted by local
building codes.
5. Loops may be wired
Class A (Style D) or
Class B (Style B).
6. 30 devices maximum
per loop.
7. All circuits are
supervised.
8. Do not connect more
than one PBA-1191 to
each zone. (Refer to
PBA-1191 instruction,
P/N 315-095424 for
further information.)
9. Do not mix smoke
detectors with the
PBA-1191.
10. The PBA-1191 requires
Rev. 3 or higher of
CZM-4 firmware.

7-17

CZM-4 Connections and Ratings

7-18

Technical Manuals Online! - http://www.tech-man.com

MOI-7, MOD-16, MID-16


Connections and Ratings
MOI-7
Electrical ratings:
Supervisory

5V .5V
140mA

Alarm

5V .5V
180mA

Electrical connections
The MOI-7 is shipped with one cable as
described below.
5V Power
The MOI-7 receives its 5 volt power on
connector P1. This power can be sent to other
modules requiring 5 volts from P2. Pin 1 is the
positive input; pin 2 the return. Use the
supplied cable, P/N 600-291261.

24V Return
TB2 connects to the return side of the
power supply used with the MOD-16s and
MID-16s. There are two positions on the
TB2position 1 connects to the MOD-16/
MID-16 and position 2 to SMB-2, TB5-9, or
to PS-35, terminal 6.
MOD-16 and MID-16 Connection
P4 is the connector for the MOD-16/MID-16
modules. Connect the first MOD-16/MID-16
in the system using a 10-wire cable
P/N 555-190940. Be sure that the locking
tab on the cable engages the rib on P4.

MXL-IQ Network Connection


For Style 4 wiring use only terminals 1 and
2 of TB1; terminals 3 and 4 of TB1 are not
used. In a Style 4 network, make only
Network A connections and ignore all
Network B connections. Do not use
connector P5 in this configuration.

Technical Manuals Online! - http://www.tech-man.com

7-19

MOI-7, MOD-16, MID-16 Connections and Ratings

NETWORK A
TB4
4

N
E 3
T
W
O 2
R
K 1

RCC-1/1F
(PS-5N7)

CABLE P/N 600-291261


TO PSR-1, P9 OR PS-5, J2

D D
O O

U
S
E

NOTES:
1. 18 AWG minimum.
2. 80 ohms maximum per
pair.
3. Use twisted pair or
shielded twisted pair.
4. Terminate the shield at
the SMB-2 enclosure
only.
5. Power limited to NFPA
70 per NEC 760.
6. Maximum voltage 8V p-p.
7. Maximum current
150mA.

STYLE 4

N N
O O
T T

+5 VDC IN

P1 P2

SEE
MOI-7
WIRING

U
S
E

4 3 2 1

TB1

TB2

DO NOT USE

P5

MOI-7

MXL-IQ Network Connection Wiring Diagram


Local Trouble Input
When terminal 3 of TB3, the local trouble
input, is driven high, it reports a trouble
condition to the MXL-IQ. This input is
protected and has a maximum input rating
of 40V. Terminal 2 of TB3 is the common
for this input.
Local Lamp Test
Terminal 1 of TB3 is used for a local lamp
test. When this input is pulled low, the
MOD-16 outputs do a lamp test. Use a
normally open momentary switch connected between terminal 1 and 2 of TB3.

7-20

Technical Manuals Online! - http://www.tech-man.com

Inputs
The MOI-7 has two inputs. The first input
allows for a local lamp test of all connected
MOD-16 outputs. Screw terminal 1 on TB3
is the lamp test input. To activate the lamp
test, use a normally open switch between
terminals 1 and 2 (common) of TB3.
Each MOD-16 board is lamp tested sequentially. The lamp test sequence stops
automatically after approximately 30
seconds. The second input is for transmission to the MXL-IQ of local trouble. This
input is high going for trouble. Each MOI-7
transmits the state of this input to the
MXL-IQ for annunciation. The MXL-IQ
indicates this trouble as an MOI-7 local
trouble. See the electrical ratings and wiring
diagrams for these two inputs.

MOI-7, MOD-16, MID-16 Connections and Ratings

MOD-16

MID-16

Electrical ratings:

Electrical ratings:

Supervisory

40V peak
2mA

Alarm

40V peak
850mA

Maximum current
for each output

50mA

Module power

5VDC
2mA max

Input ratings:
Input voltage range

18-31 VDC

Input impedance

8K ohms

Input current

2mA max

MOI-7 Wiring

Technical Manuals Online! - http://www.tech-man.com

7-21

MOI-7, MOD-16, MID-16 Connections and Ratings

NOTES
1. 18 AWG minimum for
LED and 24V lamp
connections.
2. 14 AWG minimum for
supply connections
(TB1-9 and 10, TB2-9
and 10).
3. All wiring must be in
accordance with NEC
760.
4. All wiring must
conform to local codes
and to the authority
having jurisdiction over
the installation.
5. All wiring to MID-16,
MOD-16, or MOI-7
(non-network) modules
is unsupervised. Any
wiring leaving the
enclosure must be
within 20 feet, in rigid
conduit, and must not
leave the room.
6. For additional
information see
MOI-7 Installation
Instructions,
P/N 315-092799.
7. A maximum of 8
MOD-16s can be used
with the MOI-7.
8. Both TB1-9 (or 10) and
TB2-9 (or 10) must be
connected to the
common of the power
supply.
9. When using SR-35,
refer to table on this
page.

TO COMMON OF SUPPLY OR TB1-10


OF PREVIOUS MOD-16 OR MID-16

TO TB1-9 OF NEXT
MOD-16 OR MID-16

SEE NOTE 8

TB1, 1-8, PROVIDES


CONTROLLED OUTPUTS

TB1
1

S1, 1-8 CONNECT TO


CORRESPONDING
OUTPUTS TB1, 1-8

SW1

1 2 3 4 5 6 7 8

P1

P2

MOD-16

FROM PREVIOUS
MOD-16, MID-16
OR MOI-7 (CABLE
P/N 555-190940)

NOTE: THE CABLE P/N 555-190940 IS


SUPPLIED. IF THE CONNECTION
IS TO ANOTHER RAIL IN THE
ENCLOSURE, USE OPTIONAL
CABLE P/N 555-190941.

TO NEXT
MOD-16 OR MID-16
(CABLE P/N 555-190940)
NOTE:
SWITCH S2-8 IS OPEN TO
PROVIDE A 2.7K LIMITING
RESISTOR.

S2, 1-8 CONNECT TO


CORRESPONDING
OUTPUTS TB2, 1-8

TB2, 1-8 PROVIDES ADDITIONAL


CONTROLLED OUTPUTS

10

SW2

1 2 3 4 5 6 7 8

CONNECT TO ONE OF THE FOLLOWING:

TB2
1

10

LED

MODULE

TERMINAL

SMB-2
MPS-24
PS-35

TB5-12
TB1-4
TB1-5

OR ANY AUXILIARY POWER SUPPLY


U.L. LISTED FOR FIRE PROTECTION
SIGNALING USE

TO COMMON OF SUPPLY OR TB2-10


OF PREVIOUS MOD-16 OR MID-16

TO TB2-9 OF NEXT
MOD-16 OR MID-16

MOD-16 Wiring
Connection To SR-35 Module*
MOD-16

SR-35 Screw Terminal

TB1-1

TB1-2

TB1-8

32

SMB-2, TB5-12 or
PS-35, TB1-5

33

SMB-2, TB5-9 or
PS-35, TB1-6

35

*For additional information see:


SR-35 Instructions (P/N 315-087691)
PS-35 Instructions (P/N 315-085062)
SMB-2 Instructions (P/N 315-095931)

7-22

Technical Manuals Online! - http://www.tech-man.com

MOI-7, MOD-16, MID-16 Connections and Ratings

TO COMMON OF SUPPLY OR TB1-10


OF PREVIOUS MOD-16 OR MID-16

TB1, 1-8, PROVIDES


THE FIRST 8 INPUTS

TO TB1-9 OF NEXT
MOD-16 OR MID-16

TB1
1

10

10

P1

DO NOT USE

P3

P4

P5

NOTE: THE CABLE P/N 555-190940 IS


SUPPLIED. IF THE CONNECTION
IS TO ANOTHER RAIL IN THE
ENCLOSURE, USE OPTIONAL
CABLE P/N 555-190941.

MID-16

FROM PREVIOUS
MOD-16, MID-16
OR MOI-7 (CABLE
P/N 555-190940)

10

TO NEXT
MOD-16 OR MID-16
(CABLE P/N 555-190940)

10

SWITCH
1

TB2, 1-8 PROVIDES


THE SECOND
8 INPUTS

NOTES
1. 18 AWG minimum for
all input connections.

10

P2

CONNECT TO ONE OF THE FOLLOWING:

TB2
1

INPUT IMPEDANCE: 8K OHMS


MAXIMUM INPUT CURRENT:
4mA / INPUT

10

MODULE

TERMINAL

SMB-2
MPS-24
PS-35

TB5-12
TB1-4
TB1-5

OR ANY AUXILIARY POWER SUPPLY


U.L. LISTED FOR FIRE PROTECTION
SIGNALING USE

TO COMMON OF SUPPLY OR TB2-10


OF PREVIOUS MOD-16 OR MID-16

TO TB2-9 OF NEXT
MOD-16 OR MID-16

2. 14 AWG minimum for


supply connections
(TB1-9 and 10, TB2-9
and 10).
3. All wiring must be
in accordance with
NEC 760.
4. All wiring must
conform to local
codes and to the
authority having
jurisdiction over the
installation.
5. All wiring to MID-16,
MOD-16, or MOI-7
(non-network)
modules is
unsupervised. Any
wiring leaving the
enclosure must be
within 20 feet, in rigid
conduit, and must not
leave the room.
6. For additional
information see
MOI-7 Installation
Instructions,
P/N 315-092799
7. A maximum of 8
MID-16s can be used
with the MOI-7.
8. P1 is connected in
parallel with TB1.
9. P2 is connected in
parallel with TB2.

MID-16 Wiring

Technical Manuals Online! - http://www.tech-man.com

7-23

MOI-7, MOD-16, MID-16 Connections and Ratings

7-24

Technical Manuals Online! - http://www.tech-man.com

MOM-2 Connections and Ratings


Electrical Installation
There are two inputs that connect the
MOM-2 with the SMB-2. These inputs
provide all the necessary power and data
lines to support the optional modules.
The first input is an 8-conductor ribbon
cable. Attach the cable to P6 on the
SMB-2, making sure that the locking rib on
the cable connector engages the locking
tab on P6. Attach the other end of the
cable to P7/P10 on the MOM-2, again
making sure that the locking rib on the
cable engages the locking tab on P7/P10.
This cable supplies 5 VDC and communication between the SMB-2 and the modules installed in the MOM-2.
The second input feeds 24 VDC full wave
unfiltered DC to the MOM-2. This input is
connected to either P5/P8 (SMB-1 only) or
TB6/TB7. A 2-wire cable is provided for
backward compatibility with the SMB-1.
Connect one end of the cable to P3 on the
SMB-1, making sure the cable rib and board
tab lock. Attach the other end of the cable
to P5/P8 on the MOM-2 in the same way.
The SMB-1 limits this power input to 2
amps. Under maximum load conditions the
optional modules must never draw more
than 2 amps from this connection.
When the 24 VDC is provided by the
SMB-2 use TB6/TB7 on the MOM-2 to
connect the power. The wire for this
connection is not supplied (See SMB-2
Installation Instructions, P/N 315-095931
for terminal connections). Use the following chart to determine the available 24
VDC current.

Technical Manuals Online! - http://www.tech-man.com

Depending on the optional modules


installed, additional power may be available at TB5 and for notification appliances.
See the table in Appendix D - MXL
Power Supply Load Calculations on
page D-2 for the maximum current required by each module under full load
conditions.
Determine which optional plug-in modules
are used in your CSG-M configuration.
Depending on the optional modules used,
determine the outstanding power by using
the table in Appendix D - MXL-IQ Power
Supply Load Calculations on page D-2
(See the EXAMPLE). This power can be
used for notification appliances or for the
optional power connector on TB5.
NOTE: When a CSM-4 is used, you may
add notification appliances to it if the
maximum load current to the MOM-2 does
not exceed 2 amps (SMB-1); or with an
SMB-2, 6 amps (MPS-6/6W) or 12 amps
(MPS-12/12W). Include the total alarm
current on each CSM-4 notification appliance
circuit when performing the calculations.

MAXIMUM MODULE LOAD CURRENTS


Source

Max. Current

SMB-2 wit h MPS -6/6W

6*

SMB-2 wit h MPS -12/12W

12 *

* Derat e by t he t ot al of CZM-1B6 power, NAC-1 and NAC-2

7-25

MOM-2 Connections and Ratings

EXAMPLE:
With:

one CZM-4 and


one CRM-4 and
one CSM-4

Total load current =


0.720 + 0.075 + 0.034 = 0.83A
With MPS-6/6W:
Remaining Available Current =
2.0 - 0.83 = 1.17A (SMB-1)
6.0 - 0.83 = 5.17A (SMB-2) with no
CZM-1B6 load
With MPS-12/12W:
Remaining Available Current =
2.0 - 0.83 = 1.17 (SMB-1)
12.0 - 0.83 = 11.17 (SMB-2) with no
CZM-1B6 load

7-26

Technical Manuals Online! - http://www.tech-man.com

MOM-4 Connections and Ratings


Electrical Installation
There are two inputs that connect the
MOM-4 with the SMB-1/-2. These inputs
provide all the necessary power and data
lines to support the optional modules.
The first input is an 8-conductor ribbon
cable. Attach the cable to P6 on the
SMB-1/-2 making sure that the locking rib
on the cable connector engages the
locking tab on P6. Attach the other end of
the cable to P7/P10 on the MOM-4, again
making sure that the locking rib on the
cable engages the locking tab on P7/P10.
This cable supplies 5 VDC and communication between the SMB-2 and the modules installed in the MOM-4.
The second input feeds 24 VDC full wave
unfiltered DC to the MOM-4. This input is
connected to either P5/P8 (SMB-1 only) or
TB6/TB7. A 2-wire cable is provided for
backward compatibility with the SMB-1.
Connect one end of the cable to P3 on the
SMB-1, making sure the cable rib and
board tab lock. Attach the other end of the
cable to P5/P8 on the MOM-4 in the same
way. The SMB-1 limits this power input to 2
amps. Under maximum load conditions the
optional modules must never draw more
than 2 amps from this connection.
When the 24 VDC is provided by the
SMB-2 use TB6/TB7 on the MOM-4 to
connect the power. The wire for this
connection is not supplied (See SMB-2
Installation Instructions, P/N 315-095931
for terminal connections). Use the following chart to determine the available 24
VDC current.

Technical Manuals Online! - http://www.tech-man.com

Depending on the optional modules


installed, additional power may be available at TB5 and for notification appliances.
See the table in Appendix D - MXL
Power Supply Load Calculations on
page D-2 for the maximum current required by each module under full load
conditions.
Determine which optional plug-in modules
are used in your CSG-M configuration.
Depending on the optional modules used,
determine the outstanding power by using
the table in Appendix D - MXL Power
Supply Load Calculations on page D-2.
(See the EXAMPLE). This power can be
used for notification appliances or for the
optional power connector on TB5.

NOTE: When a CSM-4 is used, you may


add notification appliances to it if the
maximum load current to the MOM-4 does
not exceed 2 amps (SMB-1); or with an
SMB-2, 6 amps (MPS-6/6W) or 12 amps
(MPS-12/12W). Include the total alarm
current on each CSM-4 notification appliance
circuit when performing the calculations.

MAXIMUM MODULE LOAD CURRENTS


Source

Max. Current

SMB-2 wit h MPS -6/6W

6*

SMB-2 wit h MPS -12/12W

12 *

* Derat e by t he t ot al of CZM-1B6 power, NAC-1 and NAC-2

7-27

MOM-4 Connections and Ratings

EXAMPLE:
With:

one CZM-4 and


one CRM-4 and
one CSM-4

Total load current =


0.720 + 0.075 + 0.034 = 0.83A
With MPS-6/6W:
Remaining Available Current =
2.0 - 0.83 = 1.17A (SMB-1)
6.0 - 0.83 = 5.17A (SMB-2) with no
CZM-1B6 load
With MPS-12/12W:
Remaining Available Current =
2.0 - 0.83 = 1.17 (SMB-1)
12.0 - 0.83 = 11.17 (SMB-2) with no
CZM-1B6 load

7-28

Technical Manuals Online! - http://www.tech-man.com

NIM-1R Connections and Ratings


Electrical ratings:

The network can be installed as either Style


4 or Style 7. Style 7 is required in Canada.

5 VDC, 160mA
For battery calculations, the
NIM-1R draws 70mA from 24 VDC.

NIM-1R Network
Up to 32 MXL-IQ Systems can be connected in the network with an NIM-1R
installed in each MXL-IQ System. For the
highest level of fault protection, install the
NIM-1R in the enclosure with the SMB-2,
although this is not necessary. When
connecting more than 32 MXL-IQ Systems,
a REP-1/D2300CP repeater is required.
Refer to the REP-1 Installation Instructions,
P/N 315-092686 or the D2300CP Installation Instructions, P/N 315-092882, for the
wiring diagram.

Each NIM-1R is shipped with two 120 ohm


EOLRsonly two are required for each
network pair. Install an EOLR at the ends of
each network pair. Do not install an EOLR at
each NIM-1R. (For a simple rule of thumb,
an EOLR must be installed where only a
single wire lands on a screw terminal.)

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at MXL-IQ
panel 1.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
8. For Style 4 omit all
Network Pair B
connections.
9. Do not use terminals
12 - 16 if NCC is not
connected.

Do not T-tap the network wiring. If T-tapping


is required, use the REP-1/D2300CP
repeater. Refer to the REP-1 Installation
Instructions, P/N 315-092686 or the
D2300CP Installation Instructions, P/N 315092882, for the wiring diagram. For Style 4
wiring, terminate the secondary network
pair (terminals 3 and 4) on each NIM-1R
with an EOLR.

NETWORK PAIR B *
SUPERVISED (OMIT FOR STYLE 4)

EOLR
120 OHMS, 1/4W
P/N 140-820150
CABLE P/N
555-190506
TO SMB-2
DO NOT USE
TB1, 1-16

DO NOT
USE

P7

CABLE P/N
555-190506
TO SMB-2

SEE
FIGURE 2
10

11

12

13

14

15

16

TB3

NIM-1R

MOM-2/-4

EOLR
120 OHMS, 1/4W
P/N 140-820150

NETWORK PAIR A
SUPERVISED

EOLR
120 OHMS, 1/4W
P/N 140-820150

DO NOT USE
TB1, 1-16

DO NOT
USE

P7

CABLE P/N
555-190506
TO SMB-2

SEE
FIGURE 2
10

11

12

13

14

15

16

TB3

NIM-1R
P3

INSTALLED IN MXL-IQ PANEL 1

MOM-2/-4

INSTALLED IN MXL-IQ PANEL 2

EOLR
120 OHMS, 1/4W
P/N 140-820150

DO NOT USE
TB1, 1-16

DO NOT
USE

P7

SEE
FIGURE 2
10

11

12

13

14

15

16

TB3

NIM-1R
P3

MOM-2/-4

P3

INSTALLED IN MXL-IQ PANEL 3

* REQUIRED IN CANADIAN INSTALLATIONS

NIM-1R Network Wiring (Figure 1)

Technical Manuals Online! - http://www.tech-man.com

7-29

NIM-1R Connections and Ratings

Network Command Center (NCC)

The total number of panels in the network must not exceed 64, including the
NCC.

The RS-232 interface connects to the NCC


with a 9-pin female D-SUB connector.

For NIM-1Rs that are not connected to


an NCC, leave terminals 1216 disconnected.

Observe the following restrictions:


Give the NCC a panel number. (This
panel number is in addition to the panel
number for the MXL-IQ system that the
NCC connects to.)

5
DO NOT USE

9
4

DO NOT USE

CONNECT TO COM1
OF NCC/NCC-G
CABLE P/N 555-193085

3
7
2
6

DO NOT USE
1

DO NOT USE

SEE
FIGURE 1

DO NOT USE
1

10

11

12

13

14

15

16

TB1

DO NOT USE
5

10

11

12

13

14

15

16

TB3

NIM-1R
P1

P3

MOM-4

P2

P4

TB2
1

TB4
2

10

11

12

13

14

15

16

NIM-1R and NCC Wiring (Figure 2)

7-30

P7

BLACK

SUPERVISED

CABLE P/N 555-190506 TO SMB-2

GREEN

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum cable length
25 feet.
4. Cable must be in rigid
conduit and can not
leave the room.
5. Shielded cable is not
recommended.
6. Maximum voltage:
24V peak to peak.
7. Maximum current:
20mA per circuit.

WHITE
RED

BROWN

DB9 FEMALE

Technical Manuals Online! - http://www.tech-man.com

10

11

12

13

14

15

16

DO NOT USE
TERMINALS 12-16
IF NCC IS NOT
CONNECTED

NIM-1R Connections and Ratings

Foreign System Interface (FSI)

For networked systems, each FSI port


must be configured as either local or
global in the CSG-M. Local FSI ports
display information only on the MXL-IQ
System to which they are connected.
Global FSI ports display all events in all
MXL-IQ Systems. Refer to the CSG-M
Manual, P/N 315-090381, for further
information.

The FSI installs on TB3 or TB4, terminals


1 and 2, of the MOM-4/-2 depending on
where the NIM-1R is installed. Use one of
the EOLRs provided with the NIM-1R on
terminals 1 and 2. This properly terminates
the FSI. Use the second EOLR on terminals 3 and 4. Never use terminals 3 and
4 to connect to the FSI. Refer to Figure 3
for the polarity of the FSI driver.
If multiple FSI connections are required,
up to four NIM-1Rs may be installed in an
individual MXL-IQ System. In networked
systems each MXL-IQ can support up to
four FSI ports.

CONNECT ONLY TO
UL EDP OR ETI LISTED
EQUIPMENT

EOLR
120 OHMS, 1/4W
P/N 140-820150

SUPERVISED

TRANSMIT

EOLR
120 OHMS, 1/4W
P/N 140-820150

TRANSMIT ENABLE

RECEIVE
EOLR
120 OHMS, 1/4W
P/N 140-820150

CABLE P/N 555-190506 TO SMB-2


DO NOT USE
1

10

11

FOREIGN SYSTEM RS-485 INTERFACE

DO NOT USE
12

13

14

15

16

P7

TB1

10

11

12

13

14

15

16

TB3

NIM-1R
P1

P3

MOM-4

P2

P4

TB2
1

TB4
2

10

11

12

13

14

15

16

NIM-1R and FSI Wiring (Figure 3)

Technical Manuals Online! - http://www.tech-man.com

10

11

12

13

14

15

16

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at NIM-1R
enclosure.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.

7-31

NIM-1R Connections and Ratings

AnaLASER Interface

Complete wiring of the converter before


installing the ACC-1 in the enclosure.

The AnaLASER interface connects to the


MOM-4/-2, TB3 or TB4, terminals 1 and 2,
depending on where the NIM-1R is
installed. Up to 31 AnaLASER detectors
can be connected to a single NIM-1R.

Place the end-of-line resistors in the


locations specified in Figure 4 below.
Install the cable, P/N 500-693801
between the converter and the ACC-1.

The ACC-1 requires an RS-485 to RS-232


converter which mounts in the back of the
ACC-1 enclosure. The converter model
number is AIC-4Z. The AIC-4Z supports
from one to four AnaLASER detectors.
Refer to the AIC-4Z Installation Instructions, P/N 315-093792, for the mounting
and configuration of the converter and the
ACC-1s.

Refer to the AnaLASER Air Sampling


Smoke Detection Manual, P/N 315092893, for connection to the AnaLASER
detector and power supply, as well as
mechanical mounting of the ACC-1.

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at NIM-1R
enclosure.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
EOLR
120 OHMS, 1/4W
P/N 140-820150

EOLR
120 OHMS, 1/4W,
P/N 140-820150

SUPERVISED
EOLR
120 OHMS, 1/4W
P/N 140-820150

CABLE P/N
555-190506
TO SMB-2

TO POWER SUPPLY, TB2 LOAD -

10

11

12

13

14

15

16

16 15 14 13 12 11 10

TB3

TO ACC, TB2, TERMINAL 10

16 15 14 13 12 11 10

2
1
3
2
1
3
2
1

LK1
LK2

SINGLE
ZONE

LK1 1-2 JUMPERED


LK2 2-3 JUMPERED
LK3 2-3 JUMPERED

CON3

AIC-4Z

JUMPER SETTINGS

CON4

TO ACC, TB2, TERMINAL 10

TB1

AIC-4Z
P3

TO POWER SUPPLY, TB2 LOAD +

DO NOT
USE

TB1

NIM-1R

MOM-4

TO ACC, TB2, TERMINAL 9

TO POWER SUPPLY, TB2 LOAD +

DO NOT
USE

DO NOT USE

P7

TO POWER SUPPLY, TB2 LOAD -

TO ACC, TB2, TERMINAL 9

CON2

CON1

LK3

REFER TO THE ANALASER AIR SAMPLING SMOKE DETECTION


MANUAL, P/N 315-092893, FOR CONNECTION OF THE ACC,
THE POWER SUPPLY, AND THE ANALASER DETECTOR AND
AIR SAMPLING NETWORK.

2
1

LK1

3
2
1

LK2

3
2
1

LK3

TO ACC #1, P4

CABLE P/N 500-693801

JUMPER SETTINGS

MULTI
ZONE

LK1 1-2 JUMPERED


LK2 2-3 JUMPERED
LK3 2-3 JUMPERED

CON4

CON3

CON2

CON1

TO ACC #28, P4
TO ACC #29, P4
TO ACC #30, P4
TO ACC #31, P4

NIM-1R and AnaLASER Wiring (Figure 4)

7-32

Technical Manuals Online! - http://www.tech-man.com

Silent Knight Model 5128/5129


Connections and Ratings
Electrical ratings:
Supervisory

18-40 VDC
60mA

Alarm

18-40 VDC
130mA

Electrical connections:
The MXL-IQ Control Panel connects to the
Silent Knight Model 5128/5129 Digital Fire
Communicator using the Alarm, Trouble,
and Supervisory dry contacts on the
MXL-IQ Main Board.
Refer to the Silent Knight 5128/5129 Fire
Slave Communicator Installation Manual,
P/N 150805, provided with Silent Knight
Model 5128/5129 for dialer instructions.

In NFPA 72 Central Station connections,


AC fail reporting is delayed. The delay is 6
hours (25% of 24 hours) for NFPA Local
and Proprietary, and 15 hours (25% of 60
hours) for NFPA Municipal Tie and Remote
Station. Only the reporting of the trouble is
delayed.
AC power must be present for a full minute
before the system switches back to AC
power from the battery.
Using the optional AC monitor input, the
Silent Knight Model 5128/5129 monitors AC
fail trouble. When the MXL-IQ System
reports an AC fail trouble, the Silent Knight
Model 5128/5129 sends a specific code to
the Central Station that identifies the trouble
as AC fail.

The Silent Knight Model 5128/5129


monitors all System troubles through the
MXL-IQ trouble relay. The MXL-IQ delays
the AC fail trouble signal in accordance
with NFPA and UL requirements.
In NFPA 72 Remote Station, install batteries to provide 60 hour standby capacity.
For signalling service DACT wire according to the diagram on the following page.

Technical Manuals Online! - http://www.tech-man.com

7-33

12

CZM-1B6
POWER

11
10
9

8
7

CHASSIS

6
5

NOT SUPERVISED

SMB-2

3
2

(RED)

(BLK)
(YLW)
(ORN)
(RED)

TROUBLE

5
4

2
1

SILENT KNIGHT 5230


(PROGRAMMING)

TELCO 1 TIP (RED)

HOUSE 1 TIP (GRAY)

(GRY)

(VIO)

HOUSE 1 RING (BROWN)

TO RJ31X

(BLU)

TB4

(GRN)
NOT USED

P2 - CHANNEL INPUTS

NOT USED
(RED)

* UL LISTED
EOL DEVICE
4.7K, 1/2W, 5%
(P/N 140-820388)

NOTES
1. TRI-60R/B6R input
must be programmed
in CSG-M as trouble
causing.
2. TRI-60R/B6R output
must be programmed
in CSG-M to transfer
on loss of AC Mains.
3. All wiring supervised
except as noted.
4. For Remote Station,
provide 60 hour
battery capacity.

TELCO 1 RING (GREEN)

SUPERVISED

P4

(BRN)

ALARM

P1 - DC POWER

HOUSE 2 TIP (GRAY)

SUPERVISED

(BRN)
(WHT)
(BLK)

UL LISTED
EOL DEVICE
3.6K, 1/4W
(P/N 140-820185)

6 5

HOUSE 2 RING (BROWN)

4 3

TRI-B6R

MXL-IQ to Silent Knight Model 5128/5129 Wiring Diagram

P3 - AC MONITOR
(SEE NOTE 2)
RELAY NC
RELAY C
RELAY NO

SILENT KNIGHT
MODEL NO. 5128/29

TELCO 2 TIP (RED)

TELCO 2 RING (GREEN)

TO RJ31X

Silent Knight Model 5128/5129 Connections and Ratings

7-34

Technical Manuals Online! - http://www.tech-man.com

TB5

SMB-2 Connections and Ratings


INTERNAL WIRING

To complete the SMB-2 internal wiring


connections, follow the steps below, skipping
those that do not apply to your particular
MXL-IQ System.

Main power connections


Primary power for the SMB-2 is provided by
the MPS-6/6W or MPS-12/12W. Both of
these mount in the lower right-hand corner
of the MXL-IQ enclosure. Follow the instructions below for the appropriate power supply.

MPS-6/6W- Install the MPS-6/6W (See


MPS-6/6W Instructions, P/N 315-090334/W).
With the AC mains disconnected, connect
the MPS-6/6W power cable to P1 of the
SMB-2. Be sure that the jumper assembly is installed in P14 of the SMB-2. If
this jumper is not installed, the SMB-2
will detect a permanent AC fail or
indicate auxiliary power voltage is low.
MPS-12/12W - Install the MPS-12/12W
(See MPS-12/12W Instructions, P/N 315092030/W). Remove and discard the jumper
assembly installed in P14 of the SMB-2.
Disconnect the AC mains. Connect the
MPS-12/12W power cable to P14 of SMB-2.

Technical Manuals Online! - http://www.tech-man.com

Battery power connection


The SMB-2 kit includes a battery cable
(wiring harness). Use the harness to
connect the 24V backup batteries to P2 of
SMB-2.

MOM-4 optional module card cage


There are two connections between the
SMB-2 and the MOM-4 board.
1. 24V power connection.
P3 provides backward compatibility with the
SMB-1 and should only be used when
replacing an SMB-1. P3 is limited to 2
amps. The SMB-2 allows the use of either
an MPS-6/6W or an MPS-12/12W. TB1
terminals 4 and 5 supply 24V to the MOM-4
with a maximum of 6 amps (MPS-6/6W) or
12 amps (MPS-12/12W) available. This
output must be derated by the total current
drawn from NAC1 (1.5A max), NAC2 (1.5A
max) and the CZM-1B6 power (1A max) on
the SMB-2. Connect TB1, 4 and 5 on the
SMB-2 to TB6/TB7, 1 and 2 on the MOM 4.
2. 5V power and the communication
interface. Connect the 8-wire ribbon cable
from P7/P10 on the MOM-4 to P6 on the
SMB-2.

7-35

SMB-2 Connections and Ratings

FIELD WIRING
The screw terminals for the field wiring
circuits are located on the left and right
sides of the SMB-2. They are labeled
TB1 through TB5.

SMB-2

The field wiring circuits available are:


CZM-1B6 power
Analog device loop 1
Analog device loop 2
Notification appliance circuit 1
Notification appliance circuit 2
Common alarm relay
Common trouble relay
Style 4 RS-485 Network (MNET)
The following sections describe each
circuit type and give the related instructions. Refer also to the wiring diagrams.

MOM-4 24V Wiring

CZM-1B6 power
CZM-1B6
12

11

DO NOT
USE

10

DO NOT
USE

CZM-1B6
T-TAPPING
ALLOWED

9
TB5

CZM-1B6

CZM-1B6 Supervised Auxiliary Power


Class B Wiring

7-36

Technical Manuals Online! - http://www.tech-man.com

Auxiliary power is available on TB5,


terminals 9 through 12 of the SMB-2.
The circuit is power limited per NEC
Article 760 and is rated at 1 amp, 18-31
VDC.
This power supply is for use with the
CZM-1B6 Remote Conventional Zone
module.
You may connect a maximum of 20
CZM-1B6s to this power source.
T-tapped wiring can be used to obtain
the maximum of 20 CZM-1B6s. Each tap
can support a maximum of 10 CZM1B6s, 4 ohms max. Multiple power
connections can be used provided you
do not exceed the ratings above (20
CZM-1B6s max and 4 ohms per run
max). For example, you could have four
individual T-tapped power runs, for a
total of 20 devices (6, 4, 3, and 7 CZM1B6s), each of the four runs not
exceeding 4 ohms resistance.

SMB-2 Connections and Ratings

Analog device loops 1 and 2


(TB2 and TB3)
To install a device for Class B, refer to the
wiring diagram below and the electrical
ratings.

Wiring the Analog Loops


Class B Wiring
To install a device for Class A, refer to the
wiring diagram below and the electrical
ratings.

Wiring the Analog Loops


Class A Wiring

Only the devices listed in Appendix A,


Table 2 - Analog Addressable Detectors
on page A-1 may be used. The UL identifiers for compatibility are the same as the
model names specified.

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Each detector or group
of detectors requires
the following:
a 2-wire circuit of 18
AWG minimum
thermoplastic fixture
wire enclosed in a
conduit.
or
18 AWG limitedenergy shielded cable
without conduit, if
permitted by local
building codes.
3. Maximum resistance:
100 ohms total.
4. Maximum
capacitance:
0.4F between + loop
and loop.
0.8F between + loop
and chassis.
0.8F between loop
and chassis.
5. Refer to Wiring Guide
for compatible wire
types.

6. Maximum voltage:
Supervisory 30 VDC
peak.
Alarm 30 VDC peak.
7. Maximum current:
Supervisory 66mA
Alarm 66mA
8. No end of line device
required.
9. Operates in full conformance with Style 4.
10. Operates in full conformance with Style 6.
11. Either loop may be
wired Class A or B.
12. 60 devices maximum
per loop.
13. T-tapping is NOT
allowed on Class A
loops.
14. Both circuits are
supervised.

Analog loop electrical ratings:


Supervisory
30 VDC peak
66mA max
Alarm

30 VDC peak
66mA max
(60 devices in alarm)

All wiring must be in accordance with


Article 760 of NEC and the local building
codes.

Technical Manuals Online! - http://www.tech-man.com

7-37

SMB-2 Connections and Ratings

Notification appliance circuits


(TB5, 1-4 and TB5, 5-8)
These circuits are for notification appliances only, NFPA 72 Local. For NFPA 72
Municipal Tie or NFPA 72 Leased Line,
use the Model CSM-4.
All wiring must be in accordance with
Article 760 of NEC and local building
codes.

Common Alarm Relay


The common alarm relay changes state
whenever a fire alarm is detected.

Common Trouble Relay


The trouble relay changes state whenever
a System trouble is detected.
NOTES
1. Contact rating: 2A,
30 VDC/120 VAC
resistive.
2. Use only with power
limited / Class 2
circuits.
3. Coils are supervised
when de-energized.
4. Contacts are not
supervised.
5. All relay contacts are
shown in normal state.

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
3 ohms total.
4. End of line device:
2.2K, W,
P/N 140-820380.
5. Either circuit may be
wired Class A or B.
6. Both circuits are
supervised.
7. Polarity shown in
supervisory state.

TROUBLE

Notification Appliance Circuits Wiring

ALARM

SMB-2 Relay Wiring


Electrical ratings:
Supervisory

Alarm

24V, unfiltered
full wave rectified
12mA max
24V, unfiltered
full wave rectified
1.5A max

Only the devices listed in Compatible


Notification Appliances, P/N 315-096363
may be used. The UL identifiers for
compatibility are the same as the model
names specified.

7-38

Technical Manuals Online! - http://www.tech-man.com

SMB-2 Connections and Ratings

Style 4 Network (MNET)


The SMB-2 provides a Style 4 MNET
network for connection to remote annunciators (MOI-1/7, RCC-1/1F).

NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms total.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at the SMB-2
chassis.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.

SMB-2

Style 4 Network (MNET) Wiring

SMB-2 Fuses
NOTE: The fuses are located on the upper left and right
corners of the SMB-2 board.

FUSE RATINGS
F1

MPS-6 Input

8A, 3 AG,
Normal Blow

F2

Battery
Reversal

20A, 3 AG,
Normal Blow

F3

CZM-1B6
Power

2A, 3 AG,
Normal Blow

F4

24V Output
15A, 3 AG,
(TB1 - 4 and 5) Normal Blow

Technical Manuals Online! - http://www.tech-man.com

7-39

SMB-2 Connections and Ratings

7-40

Technical Manuals Online! - http://www.tech-man.com

Appendix A

Compatible Devices
TABLE 2
ANALOG ADDRESSABLE DEVICES
Device

TABLE 1
CONVENTIONAL DEVICES
Detector

Base

Installation
Instructions

CZM-1B6

DB-3S

315-081943-15

CZM-1B6

1,6

DI-B3/B3H

AD-3I/ILP
AD-3RI/3RP

315-093234-4
315-086591-7

CZM-1B6

DT-11

DB-11
315-095429-1
DB-3S + DB-ADPT

CZM-1B6

PBA-1191

PBB-1191

315-095424-2

PE-3/3T

DB-3S
AD-3ILP
AD-3RP

315-090875-6
315-093234-4
315-086591-7

PE-11/PE-11T

DB-11
315-094198-3
DB-3S + DB-ADPT 315-094198-3
AD-11P/11PR
315-095659-2

5,7

FP-11/FPT-11

Compatible With

DI-3/3H
DI-A3/A3H

CZM-1B6

CZM-4

1,6

CZM-4

1,6

CZM-4

1,6

S121/S122 + ISI-1

DB-3S

FP-11 (d) 8, 10

315-095355-2

DB-11, DB-X11RS
DB-3S + DB-ADPT
315-095921-4
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT
315-095659-2

315-095306-3

ID-60I/60IH
ID-60IA/60IAH

DB-3S, DB-X3RS

315-090287-2

CZM-4

ID-60IB/601BH

AD-3I
AD-3XRI

315-093234-4
315-093235-4

CZM-4

ILI-1/1H
ILI-1A/1AH

DB-3S, DB-X3RS

315-095387-1

CZM-4

ILI-1B/1BH
4

AD-3I
AD-3XRI

315-093234-4
315-093235-4

ILP-1/ILPT-1

DB-3S, DB-X3RS

315-092594-5

AD-3ILP
AD-3XRILP

315-093234-4
315-093235-4

DB-3S, DB-X3RS

315-095028-1

AD-3ILP
AD-3XRILP

315-093234-4
315-093235-4

DB-3S

315-093336-1

MSI-10/20

315-090903-3

MSI-10B/20B

315-093329-1

MSI-B6F

315-095302-1

MSI-MB6

315-093613-1

TRI-B6/6D/6R

315-093315-3

TRI-B6M

315-094547-1

TRI-S/D/R

315-096242-2

CZM-1B6

1,6

315-081943-15

CZM-1B6

2,6

315-085258C

CZM-1B6

ICP-B6

ILPT-1(d)
ILP-2

ILP-2(d) 9, 10
1. May use up to 15 detectors of any type.
2. May use up to 10 DI-3IS ionization detectors in addition to mechanical (non-energy storing)
shorting devices.
3. May use up to five S121 or S122 flame detectors in addition to mechanical (non-energy
storing) shorting devices.
4. May use up to 30 detectors of any type, except PB-1191.
5. Do not use with alarm verification.
6. Do not use detector operated accessories with CZM-1B6.
7. Only one PB-1191, and no additional device, can be connected to a CZM-4 initiating zone.
8. The FP-11 is only compatible with MXL-IQ Rev. 6.0 or greater firmware.
9. Must use MXL-IQ Rev 3.0 or greater firmware.
10. When the CSG-M is configured, the DUCT application must be selected when the device is
used in an air duct housing or in a spot duct application.

Technical Manuals Online! - http://www.tech-man.com

Installation
Instructions

AD-11P/11XPR

FM Approved Only
DI-3IS + ISI-1

Base

ILT-1

A-1

Appendix A

A-2

Technical Manuals Online! - http://www.tech-man.com

Appendix B

Device Analog Voltages


DETECTOR VOLTAGE RESPONSE

Device

Input State

Voltage
Response

CZM-1B6

Normal
Alarm
Trouble

0.50-4.19
4.20-5.0 0
0.0 0-0.47

ID-60T-135
ILT-1

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

MSI-10/20

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

MSI-10B/20B

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

MSI-MB6

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

MSI-B6F

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

MS-MI

Normal
Alarm
Trouble

1.80-3.0 0
3.10-5.0 0
0.0 0-1.79

TRI-60/60D/60R

Not Available

Not Available

TRI-B6/B6D/B6R

Not Available

Not Available

TRI-B6M

Not Available

Not Available

Technical Manuals Online! - http://www.tech-man.com

Dust

Supervisory

Trouble

4.25-5.12
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38

0.63-4.12
0.63-4.0 0
0.63-3.88
0.63-3.75
0.63-3.63
0.63-3.50
0.63-3.38

0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50

5.25-10.0 0
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0

4.25-5.12
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38

0.63-4.12
0.63-4.0 0
0.63-3.88
0.63-3.75
0.63-3.63
0.63-3.50
0.63-3.38

0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50

ID-60P

LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3

5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0

4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25

0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25

0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75

ILP-1/ILPT-1
ILPT-1(d)

LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3

5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0

4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25

0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25

0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75

ILP-2
(In Default/No
Application
Mode Only)

LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3

5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0

4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25

0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25

0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75

Detector

Sensitivity

Alarm

ID-60I/60IH
ID-60IA/60IAH
ID-60IB/601BH

LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3

5.25-10.0 0
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0

ILI-1/1H
ILI-1A/1AH
ILI-1B/1BH

LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3

Threshold

B-1

Appendix B

B-2

Technical Manuals Online! - http://www.tech-man.com

Appendix C

MXL-IQ Battery Calculations


Battery backup is a requirement for the
MXL-IQ. To determine the size battery you
must use, follow the procedures listed
below. The MXL-IQ can charge a battery
of up to 55 amp hours. A battery size
calculation form is also provided.
1. Record all the modules required in the
form on the following page.
2. Calculate each row across and place
the total in the right column: Total
Standby 24 VDC Module Current
3. Total the right-hand column and record
it at the bottom of the form opposite
Total System Current.

5. Multiply the AH Total by 1.3 to obtain


the final battery amp hour capacity and
record it opposite Battery Size.
Three battery models are UL listed for use
with the MXL-IQ:
BP-6124V, 15 AH
BTX-1a set of 12V, 31 AH
BTX-2a set of 12V, 55 AH
Select the battery that meets or exceeds
the final calculated battery amp hour rating.
Use an external battery box with the BTX-2
model.

4. For NFPA 72 Local, 72 Proprietary,


and UL 1076 systems multiply the total
system current by 24 and record it at
that Total AH location.
or
For NFPA 72 Municipal Tie and 72
Remote Station systems multiply the
total system current by 60 and record it
at that Total AH location.
or
For FM Approved Deluge/PreAction
systems multiply the total system
current by 90 and record it at that Total
AH location.

Technical Manuals Online! - http://www.tech-man.com

C-1

Appendix C

NOTES
The following modules draw
no 24 VDC current and do
not need to be included in
the battery calculations:
MOM-2
MOM-4
TSW-2
1. Use this column for
battery size calculations.
2. Power is supplied by a
separate UPS.
3. EOL currents included.

C-2

Load Current Per Circuit


Standby 24 VDC
Total Standby 24
Module
Quantity Module Current
VDC Module
(See Note 1) End of Line Device Device Current
Current
175mA
SMB-2
12mA per NAC
1.1mA per device
MKB-4
5mA
0
0
RCC-1/1F
75mA
0
0
TSP-40
70mA
0
0
10mA
0
CSM-4
12mA
15mA
CRM-4
15mA per active
relay
55mA
CZM-4
0
3mA
105mA
ALD-2I
0
1.1mA per device
CMI-30 0
30mA
0
0
NIM-1R
70mA
0
NA
MOI-7
120mA
0
0
MOD-16
2mA
0
0
MID-16
2mA
0
0
6mA
CZM-1B6
5mA
NA
ICP-B6
18mA
2.5mA
NA
PIM-1
10mA
0
NA
PIM-2
(See Note 2)
0
NA
PAL-1
(See Note 2)
0
NA
D230 0CP
50mA
0
0
Silent Knight
60 mA
0
0
Total System Current
NFPA Local (72A), Proprietary (72D), UL 1076 (MMB-2 only) - Total AH x 24 =
NFPA Municipal Tie (72B), Remote Station (72C) - Total AH x 60 =
FM Approved Deluge/PreAction - Total AH x 90 =
Battery Size (with Alarm Reserve Correction) x 1.3 =

Technical Manuals Online! - http://www.tech-man.com

Appendix D

MXL-IQ Power Supply Load


Calculations
Each MXL-IQ System enclosure requires
an SMB-2. To ensure that the power supply
is not overloaded, complete the worksheet
on the following page.
Enter the quantity of each module in
the enclosure.
Calculate both the 24V and 5V loads
for each row.
Total the Active 24V and Active 5V
columns.
Ensure that both totals are within the
power supply output ratings in the
table to the right.

Technical Manuals Online! - http://www.tech-man.com

POW ER S U PPLY OU TPU T R ATI NGS


A ct iv e 2 4 VDC
M odule C ur r ent

A ct iv e 5 VDC
M odule C ur r ent

SMB -2/MPS -6

6 a mp s

500mA

SMB -2/MPS -12

12 amps

500mA

M odule

D-1

Appendix D

The following modules


draw no current from
either the 5 VDC or 24 VDC
power supplies and do not
need to be included in
these calculations:
MOM-2
MOM-4
PAL-1
PIM-2
TSW-2

Module

Quantity

SMB-2

(See Note 3)

MKB-4

D-2

Total Active
24 VDC Module
Current
(See Note 1)

Active 5 VDC
Module Current

Total Active
5 VDC Module
Current
(See Note 2)

(See Note 3)
0

15mA

RCC-1/1F

80mA

TSP-40

70mA

CSM-4

34mA + 1.5A
max per circuit

30mA

CRM-4

75mA

30mA

CZM-4

720mA
4 zones in
alarm

24mA

ALD-2I

105mA + 1.1mA
per device

CMI-30 0

96mA

NIM-1R

160mA

MOI-7

1. Use this column to


calculate total current
from 24 VDC supply to
make sure it is not
overloaded.
2. Use this column to
calculate total current
from 5 VDC supply to
make sure it is not
overloaded.
3. SMB-2 supplies 5V at
500mA, 24V at 6A (MPS6), 24V at 12A (MPS-12).

Active 24 VDC
Module Current

120mA

175mA

MOD-16

850mA max

2mA

MID-16

32mA max

2mA

50mA

ICP-B6

1.5A

PIM-1

25mA

D230 0CP

20 0mA

CZM-1B6

Silent Knight

Technical Manuals Online! - http://www.tech-man.com

130mA
TOTAL

0
TOTAL

Appendix E

Alarm Verification
The Alarm Verification feature provides the
MXL-IQ with a way to verify an alarm from
area type addressable smoke detectors
connected to the analog loops or from
standard smoke detectors connected to
the CZM-4 module. This feature reduces
the incidence of false alarms.
When a detector is supervised with Alarm
Verification, it is turned off immediately
after the System first detects alarm
causing data from it.
The length of time that the detector is
verified is fixed at 50 seconds. In MXL-IQ,
an addressable detector is turned off by
the System ignoring its data; a standard
detector is turned off by the power actually
being removed from the detector. After the

turnoff period, the panel puts that detector


into alarm if it has alarm causing data within
60 seconds of being turned back on. See
the figure below for a graphic illustration of
Alarm Verification
You can select Alarm Verification for none,
all, or any combination of addresssable
smoke detectors.
MXL-IQ supports a global verification
feature called Device Confirmation. It
provides adjustable AB verification times
for all addressable:
Ionization detectors
Photo detectors
Ionization and photo detectors

A____________________B________________________C
Time
A
AB
BC

Time at which the System initially recognizes an alarm from a smoke detector.
The 50 seconds during which the System ignores the alarm data
The 60 seconds during which the System alarms if the device is returning alarm data

CAUTION
Use only detectors
which are subjected to air
velocities of less than 100
feet per minute with Alarm
Verification. Under dynamic
air velocity conditions,
smoke may be swept from a
smoke detector after the
initial alarm. That may cause
a long delay before
verification. Do not select
Alarm Verification for such
applications.

Line Graph of Alarm Verification

Technical Manuals Online! - http://www.tech-man.com

E-1

Appendix E
With Device Confirmation, the BC
verification time known as System Justified Alarm time is also adjustable. It is the
same time used by both ionization and
photo detectors. If a device is individually
selected for alarm verification, the alarm
verification feature takes priority over the
device confirmation option. For adjustment
ranges, refer to the CSG-M Programming
Manual, P/N 315-090381.

E-2

Technical Manuals Online! - http://www.tech-man.com

There is an Override menu selection in the


Test menu of MXL-IQ. Select Alr_Verify to
disable all alarm verification or select
Alr_Confirm to disable all alarm confirmation for a period of up to 4 hours or until
manually re-enabled.

Appendix F

Envirolink

INTELLIGENT ENVIRONMENTAL COMPENSATION (IEC)


Envirolink is an optional feature that permits
MXL-IQ to compensate automatically for
environmental changes (such as dirt and dust
buildup) in the analog voltage of an I Series
photo or ion smoke detector. The selection of
Envirolink devices is made in the CSG-M.
Once a detector is chosen to be covered by
Envirolink, MXL-IQ stores and analyzes the
analog readings of the smoke detector and
adjusts the detectors threshold upward or
downward, as necessary, to maintain a
constant sensitivity.

SENSITIVITY
VOLTAGE

Analog Voltage

As the analog voltage increases due to


environmental factors, an equivalent
increase in the detectors alarm threshold
prevents factors other than smoke from
causing an alarm. This method maintains
the selected detectors sensitivity.
Typically, the analog voltage changes
slowly over long periods of time for environmental factors, but changes quickly over
short periods of time for actual smoke.

Initial System Power-Up


When a new or modified CSG-M is loaded
into a system, the MXL-IQ control panel
goes through an initial system power-up.
The MXL-IQ does not keep the Envirolink
option where it was formerly applied when
this new system powers up. The Envirolink
memory re-initializes, and then MXL-IQ
begins adjusting the alarm thresholds
wherever Envirolink is selected in the new
CSG-M.

Technical Manuals Online! - http://www.tech-man.com

Alarm
Threshold Voltage

0 Volts

Adjusting the Alarm Threshold


When a New CSG-M is Uploaded
After MXL-IQ checks that the actual ID of a
device with Envirolink agrees with the
CSG-M, it adjusts the detectors alarm
threshold according to the data stored. The
first adjustment occurs after 100 hours of
data accumulation. In the case of power
cycling or resetting, adjustments begin
within 90 seconds.

F-1

Appendix F
If a detector with Envirolink (IEC) reports an
alarm condition before the detectors alarm
threshold is adjusted, the alarm delays until
the alarm threshold is adjusted. If the device
continues to report an alarm condition once
its alarm threshold is adjusted, the alarm
reports.
If the CSG-M and the device ID do not agree,
the IEC for that device does not activate
until the trouble condition is removed from
the system and the panel is reset.

MXL-IQ Power On
When a system is brought on-line, or when
there is a complete loss of power in an
MXL-IQ enclosure containing detectors with
IEC applied, the operator must perform a
reset sequence for the IEC devices in that
MXL-IQ and also reset the MXL-IQ.
When an MXL-IQ is powered the first time,
and there is no data for IEC devices, MXL-IQ
leaves these devices at the default alarm
threshold. However, if former IEC data is
available, MXL-IQ adjusts the device alarm
threshold accordingly.

Ongoing Adjustments of the


Alarm Threshold
Environmental conditions usually cause a
small change in the analog voltage over a
long period of time. At regular intervals
MXL-IQ collects analog data for each
detector with IEC and adjusts the alarm
threshold accordingly. MXL-IQ adjusts for
both up and down changes in the analog
voltage. In addition, if system power is lost,
MXL-IQ adjusts the alarm thresholds as
needed by using stored data.

Indicating IEC Trouble Conditions


A trouble condition involving the IEC may
be annunciated by the MXL-IQ as:
PRE-DIRTY ANALOG VOLT. REACHED

The trouble conditions shown above are


annunciated on a detector-by-detector
basis as each detector is checked.
MXL-IQ annunciates a trouble condition for
a detector when its alarm threshold
reaches a predetermined limit. The operator should acknowledge the trouble, clean
the detector if possible, and reset the
control panel. If the detector is not cleaned,
the control panel annunciates this trouble
condition after every panel reset until the
detector is cleaned. When it is cleaned, that
is detected by the Auto Clean Detection
feature.

Automatic Cleanliness Detection


MXL-IQ automatically detects when an IEC
detector was cleaned and checks whether
the detector is considered clean by MXL-IQs
standards. If the detector is clean, IEC data
for that device is reset to clean levels, and
the following message prints:
Detector Cleaned

NOTE: Automatic detection and documentation of the cleaning of a detector by


MXL-IQ may take as long as 1 hour. To
avoid this, use the Det cleaned option in
the Test menu to avoid automatic clean
detection. When you enter the address of
the detector that was cleaned, MXL-IQ
adjusts that detectors Norm sensitivity
setting reference.

Detector Cleaned
IEC must be enabled in the CSG-M in order
to have access to the Det_cleaned option
through the MXL-IQ Annunciator Panel.
At the Test menu, use the Left or Right
arrow key to cause the D in Det_cleaned to
start blinking:

TEST: OVERRIDE DET CLEANED

OR
IEC LIMIT REACHED. SERVICE REQ

F-2

Technical Manuals Online! - http://www.tech-man.com

Press ENTER when the D is blinking to


select Det_cleaned.

Appendix F
The System asks you to type the module
and device numbers.
Type the three-digit module number
and the three-digit device number
(mmm/ddd), including all leading
zeroes.
Press ENTER.
After entering the module-device, MXL-IQ
checks whether the device is subject to
IEC. If the device is not subject to IEC, or if
IEC is not enabled for the system, an error
messages displays:

DEVICE NOT SUBJECT TO IEC


IEC NOT ENABLED IN CSG-M

If the device is an IEC detector, MXL-IQ


displays and prints the time, date, device,
and custom message of the cleaned
device.

Technical Manuals Online! - http://www.tech-man.com

F-3

Appendix F

F-4

Technical Manuals Online! - http://www.tech-man.com

Appendix G

Latching/Non-Latching Troubles
This feature is not available for Networked
MXL-IQ Systems.

When the Latching/Non-Latching (self


restoring) trouble option is set to YES in the
CSG-M, MXL-IQ automatically removes
trouble conditions from the trouble queue
when the OUT OF TROUBLE condition is
detected.
For NFPA 72 Local, 72 Municipal Tie, and
72 Remote Station systems, the following
criteria must be met in order for the trouble
to be removed from the trouble queue:
Module and device numbers
must be identical
Trouble type must be identical
Both IN/OUT conditions must be
recorded in the queue
All printers being used must print both
IN/OUT conditions
When all these conditions are met, the MXL-IQ
removes both the in and out occurrence of
this trouble from the queue. If there are no
other events in the system (alarm, supervisory, trouble, or security), MXL-IQ returns
to the SYSTEM NORMAL display (without
a system reset). If there are other events in
the system, MXL-IQ updates the display.

Technical Manuals Online! - http://www.tech-man.com

For NFPA 72 Proprietary systems, the


following criteria must be met if the trouble
is to be removed from the trouble queue:
Module and device numbers
must be identical
Trouble type must be identical
Both IN/OUT conditions must be
recorded in the queue
All printers being used must print both
IN/OUT conditions
Both IN and OUT conditions must be
acknowledged and printed
When all these conditions are met, MXL-IQ
removes both the in and out occurrence of
this trouble from the queue. If there are no
other events in the system (alarm, supervisory, trouble, or security), MXL-IQ returns
to the SYSTEM NORMAL display. If there
are other events in the system, MXL-IQ
updates the display.
Not all troubles can be removed from the
trouble queue. If there is no OUT condition
reported (i.e., Class A loop trouble), MXL-IQ
requires an acknowledgement and reset.

G-1

Appendix G

G-2

Technical Manuals Online! - http://www.tech-man.com

Appendix H

Installing A Security Point


WARNING:

These circuits are


intended for 24 hour
alarm monitoring only.

CAUTION:
When setting the device address using
the FPI-32, select the normally closed
alarm causing input.

UL 1076 requires a TSW-2 tamper switch


as well as a supervised printer (PAL-1/
PAL-2). Other supervised printers that are
selectable in CSG-M are the TI-820 and
the LA-50.
Only Models TRI-60/-60D/-60R or
TRI-B6/-B6D/-B6R may be used as
security points. A COMMUNICATION
FAILURE with a TRI device configured
for SECURITY results in a SECURITY
ALARM as well as a communication
trouble. When installing a TRI device in
the CSG-M, be sure to set the device
usage field to security; otherwise, the
device usage defaults to fire alarm.
TRI-60 / TRI-B6

1
2
3
4

SWITCH

NC

For proprietary burglary application


(UL 1076):
Use a TSW-2 tamper switch to monitor
the main enclosure.
Monitor each TRI-60/-60D/-60R or
TRI-B6/-B6D/-B6R related to this application for 24 hours by using a listed motion
detector (to prevent tampering).

TRI-60R / TRI-B6R

+ ANALOG
- LOOP
OUT

+ ANALOG
- LOOP IN

Connect only one switch per TRI input.

1
2
3

EOL *
3.6K
1/4W

+ ANALOG
- LOOP
OUT

+ ANALOG
- LOOP IN
SWITCH

NC

EOL *
3.6K
1/4W

TRI-60D / TRI-B6D

1
2
3
4

NOT USED

GND

GND

+ ANALOG
- LOOP
OUT

+ ANALOG
- LOOP IN
SWITCH A

SWITCH B

NC

EOL *
3.6K
1/4W

NC

EOL *
3.6K
1/4W

NOT USED
GND

* END OF LINE DEVICE: P/N 140-820185


REFER TO TRI INSTALLATION INSTRUCTIONS,
P/N 315-092329 OR 315-093315, AS APPLICABLE

Installing the Security Point for UL 1076

Technical Manuals Online! - http://www.tech-man.com

H-1

Appendix H

H-2

Technical Manuals Online! - http://www.tech-man.com

Appendix I

Application Specific Detection


(ASD)
Application Specific Detection (ASD)
allows the system designer (and anyone
with Control menu access) to program an
ILP-2 detectors sensitivity, pre-alarm
threshold, and other alarm-related parameters using English descriptions of the
detector's environment (application). This
eliminates the need for detailed knowledge
of smoke detector terminology and
operation. The designer can set all of the
critical detector parameters by simply
selecting an application description that
closely fits the one where the detector is to
be installed.
For example, to use ASD to select the
optimal parameters for a detector in a hotel
lobby, select the LOBBY application in the
CSG-M for that device. The MXL will
automatically transmit the factory determined sensitivity, pre-alarm threshold, and
detection algorithm (R-algorithm) to the
corresponding device. This eliminates the
guesswork of selecting these parameters
for different environments. Changes made
at the control panel using the Control menu
(Change_Apps) override the ASD settings
made in CSG-M for that ILP-2 device until
the next power-on reset.
NOTES:
1. The ILP-2 is only compatible with MXL-IQ Revision 3.0 or
greater firmware.
2. The FP-11/FPT-11 is only compatible with MXL-IQ Revision
6.0 or greater firmware.
3. When the CSG-M is configured, the DUCT application
must be selected when the device is used in an air duct
housing or in a spot duct application.

Technical Manuals Online! - http://www.tech-man.com

ASD SUBMENU ABBREVIATIONS


MXL
Menu

CSG-M Application

NONE

Disable

OFFC

Office (Retail)

WHSE

Warehouse (Light
Manufacturing)

LOBY

Lobby

Relatively clean area, temperature changes,


cellular phones, smoking

COMP

Computer Room

Very controlled environment, clean,


temperature closely regulated, high cost
clean machinery operating, no smoking, high
air velocity

DORM

Dormitory

Airborne dust and temperature changes,


living quarters, cooking fumes, smoking

HLTH

Healthcare

Higher level risk, relatively clean, electronic


equipment

PARK

Parking Garage

UTIL

Utility (Transformer)
Room

PREC

Precious Storage
(Sensitive
Environment)

HOST

Hostile Environment

DUCT

Duct (Open air or


duct housing)

Description
No Applications (Standard Photoelectric
Detector)
Reasonably clean, climate controlled
atmosphere
Airborne dust, equipment, fork truck and
light to medium dock area exhaust fumes

Airborne dust, car and diesel fumes,


temperature swings
Normal to somewhat dirty environment, heat
from running equipment
Sensitive materials or equipment storage,
clean dust-free environment, earliest
warning desired
Dirty, dusty, humid, operating equipment, RF
present, wide temperature swings
Dirty, dusty, humid, wide temperature
swings, high air velocity

I-1

Appendix I

Testing ASD Devices


Since one of the parameters transmitted to
the detector adjusts the detection algorithm (R-algorithm) to reduce false alarms,
it is necessary to defeat ASD (or at least
the R-algorithm) when smoke testing ASD
devices. The Test ASD_Devices menu
option has been supplied for this purpose.
When ASD devices are to be smoke
tested, the Test ASD_Devices option must
be enabled. This disables the application
specific detection R-algorithm so the
detector will alarm using the standard test
gas method. If the Test ASD_Devices
option is not enabled prior to smoking the

I-2

Technical Manuals Online! - http://www.tech-man.com

device, the tester may find it extremely


difficult to alarm the detector since the
algorithms are designed not to be fooled by
a deceptive phenomenon such as test gas.
Once the Test ASD_Devices option has
been enabled using the test menu, the tester
should wait 3 minutes before attempting to
test the ASD devices. This time may vary
slightly with the number of ALDs and ASD
detectors in a system. This will ensure that
the ASD R-algorithm has been defeated for
test purposes. The system will not reset until
the Test ASD_Devices option has been
disabled.

Appendix J

Trouble Message

The Probable Cause Is:

MXL-IQ Trouble Messages


Trouble Message

The Probable Cause Is:

AC Fail or Brownout

Primary AC power is missing or below the


brownout level; the System is running on
battery backup.

Airflow Too Low

AnaLASER airflow is below programmed


threshold.

Airflow Too High

AnaLASER airflow is above programmed


threshold.

AnaLASER Power Trouble

Problem with AnaLASER power supply.

ASD Testing Enabled

Application specific detector testing is


enabled. The applications feature is
disabled during testing.

Aux Pwr Class A Fail Neg

The negative side of the CZM-1B6 power


circuit is open.

Aux Pwr Class A Fail Pos

The positive side of the CZM-1B6 power


circuit is open.

Battery Backup Invalid

A battery is connected, but not selected in


CSG-M.

Battery Fuse/Wiring Open

Either the battery is not connected, or the


battery fuse is blown, or the battery voltage
is too low.

Carrier Lost

CMI-300 to CXL communications problem


where the CMI-300 does not see the CXL's
modem carrier (tone). No data is being
transmitted.

Class A Loop Trouble

If Class A: The initiating circuit at this


module address has an open.
If Class B: Wired zones are missing the
Class A jumpers.

Technical Manuals Online! - http://www.tech-man.com

J-1

Appendix J

J-2

Trouble Message

The Probable Cause Is:

CMI-300 General Trouble

Communications trouble between the CMI300 and the CXL. Data is attempting to
transmit.

CSGM Out Of Date

This MXL-IQ (node) will need to be updated


with the latest CSG-M networked program.
A network CSG-M has been loaded on
another MXL-IQ (node) and has a reference
to this MXL-IQ (node).

Daily Detector Test Abnormal

Device is defective.

Detector Trouble

AnaLASER detector in need of repair.

Device Communication Error

An analog device whose response has


failed error checking.

Device Detected Waveform Error

An analog device reports this trouble if it


receives an unknown polling waveform.

Device LED Turned On

A device LED was turned on from the Test


menu of the MXL-IQ.

Device Multiple Response

Two or more analog devices at the same


address have reported during normal
supervision.

Device Out of Calibration

This message is used with XLD and is the


same as the XL-3 message,
Response out of window at cal.

Device Receive Error

An analog device reports this trouble


if it receives an incorrect analog
transmission.

Event log 80% full

Use extract history in CSG-M to reset the


MXL-IQ history log.

Event log 90% full

Use extract history in CSG-M to reset the


MXL-IQ history log.

Function Recursion Trouble

The number of evaluations of output logic


required until outputs are stable has
exceeded the system maximum. Rewrite
CSG-M to simplify functions.

Ground Fault Minus

Low impedance to the negative side of one


of the field wiring circuits to earth ground.

Technical Manuals Online! - http://www.tech-man.com

Appendix J

Trouble Message

The Probable Cause Is:

Ground Fault Plus

Low impedance to the positive side of one of


the field wiring circuits to earth ground.

High Battery Voltage

Battery voltage is too high because battery


has been overcharged. Battery and/or
charger are possibly defective.

History Manually Turned Off


History Manually Turned On
History Manually Erased

History Log has been manually changed


(Turned Off / Turned On / Erased) using
the MKB.

IEC Limit Reached. Service Req

Detector environmental compensation has


reached UL limit. Detector is very dirty and
requires cleaning.

IEC/Pre-alarm Memory Error

An unsuccessful attempt was made to


access the IEC area of flash memory. Is
IEC-1 module present? Is segmented flash
present?

Incorrect Device ID

An analog device whose type or usage does


not agree with the CSG-M assignment at
that address.

Incorrect Node Address

Address on NIM-1R is incorrect.

Input Device Not Responding

A device assigned in CSG-M is not reporting


at its address.

Input Dev Response Too Low

Input wiring to TRI or CZM-1B6 modules


has an open circuit or no EOL. Loss of
power to CZM-1B6 module. Smoke detector
chamber defective.

Input Device Requires Service

An ion or photo detector has exceeded the


80% dust threshold.

Input Disarmed

An initiating device was disarmed through


the Control menu.

Keyswitch Activated (CANADA)

This is a trouble type for activation of


Canadian manual station keyswitch if no
alarm is present.

Lamp Supervision Trouble

MID-1 input trouble when used for lamp


supervision.

Technical Manuals Online! - http://www.tech-man.com

J-3

Appendix J

J-4

Trouble Message

The Probable Cause Is:

Log FULL, Events Will Be Lost

History Log is full. Use extract history in


CSG-M to reset the MXL-IQ history log

Loss of 24V Input Power

A CZM-4 has lost its 24 VDC input.

Low Battery Voltage

Battery voltage readings low; the battery


requires recharge/replacement.

Low IEC Voltage, Service Req

Defective device.

Memory Error In RAM Test

An error was detected in RAM memory IC


112 or IC 113.

Memory Error in ROM test

An error was detected in the EPROM IC


111 or IC 110

Memory Upgrade Required

Starting with revision 6.00, the MXL-IQ


requires a memory upgrade (RAM) in
socket IC113.

Missing Device ID Response

An ALD module has not returned an ID Poll


response for any of its detectors or devices.
NOTE: This trouble will accompany module
not responding for missing ALD modules.

Module Comm Failure

When network communications are


interrupted, and then restored, all module
addresses affected report this trouble.

Module Not Responding

The module assigned in CSG-M at this


address is not responding.

Module RAM Failure

The CRM-4, CSM-4, or CZM-4 at this


address has determined that its internal
RAM is not operating properly.

Module ROM Failure

The module at this address has a ROM


checksum failure.

MOI-1 Local Trouble

This trouble is reported when the TRBL IN


input of the MOI-7 is driven high.

MOI-1 Voice System Trouble

This condition is caused by driving the


TRBL IN of the MOI-7 high with voice
modules configured in CSG-M for this
module.

Technical Manuals Online! - http://www.tech-man.com

Appendix J

Trouble Message

The Probable Cause Is:

MOI-1 Zone Disarmed

Output of an MOI-7 (MOD-16 or VPM-5)


has been disarmed at the MXL.

More Than 60 Alarms

The System alarm queue is full, and more


alarms have been received.

More Than 60 Securities

The System security condition queue is


full, and more security conditions have
been received.

More Than 60 Supervisory

The System supervisory queue is full, and


mor supervisories have been received.

More Than 60 Troubles

The System trouble queue is full, and


more supervisories have ben received.

Multiple Module Response

Two or more modules respond at the


same address.

Multiple Response Analog Poll

Two or more analog devices at the same


address have reported during an analog
data request.

MXL Network Failure

The MKB/RCC has lost communication


with the MNET.

Network CSGM Upload Needed

A function was added to an XNET node


and had a reference to another node. This
function shall be added to each node it
references.

Network Input Disarmed

A point on another XNET node has been


disarmed.

Network Loop A Failure

The Style 7 primary (A) RS485 MNET


network loop has failed.

Network Loop B Failure

The Style 7 secondary (B) RS485 MNET


network loop has failed.

No CSG - Default In Use

No CSG-M custom programming was


found in FLASH memory so the system is
using the default CSG-M.

Node Disconnected

XNET node was logically disconnected


from the NCC.

Node Multiple Response

Two nodes are programmed at the same


address.

Technical Manuals Online! - http://www.tech-man.com

J-5

Appendix J

J-6

Trouble Message

The Probable Cause Is:

Node Not Responding

XNET wiring and/or NIM-1R module is


defective.

Out of RAM Call Pyrotronics

The configuration upload is too large.

Out of Tasks Call Pyrotronics

Contact the Siemens Building Technologies, Inc. Technical Services Department.

Output Disarmed

Indicates that an output point has been


manually disarmed.

PRE 1 Level
PRE 2 Level

AnaLASER device has reached its


pre-alarm setting.

Pre-alarm

Device has reached its pre-alarm setting.

Pre-dirty Analog Volt. Reached

IEC compensation has reached a level


where the detector should be cleaned.

Printer Off Line/Fault

A supervised printer is not responding.

Printer Out Of Paper

The printer has run out of paper.

Relay Coil Open

The relay coil at this address is open.

Relay Disarmed

The relay at this address has been disarmed from the Control menu.

Relay Driver Inoperative

The relay on the CRM-4 or CSM-4 at this


address does not operate when commanded to energize.

Relay Supervision Failure

The relay at this address has a coil failure.

ROM SW Version Error

Module at the address noted needs an


update to latest available software level.

Signal Circuit Disarmed

The NAC at this address was disarmed


from the Control panel.

Signal Circuit Loop Open

The NAC at this address has a broken wire


or missing EOL device.

Signal Ckt Loop Shorted

The NAC at this address is shorted, or the


EOL device is the wrong value, or the
notification appliances are not polarized or
are connected backwards.

Technical Manuals Online! - http://www.tech-man.com

Appendix J

Trouble Message

The Probable Cause Is:

Signal Mod A/D Convert Fail

The CSM-4 at this address has a failed


analog-to-digital converter.

Signal Module Zone Code

Zone code failure on the CSM-4 module.

Software Key Violation

Incorrect Software Key Installed (NCC


only).

Stack Fault Call Pyrotronics

When the message Call Pyrotronics


appears, a four letter Alpha ID will be
displayed. This number is necessary when
reporting the problem to Siemens Building
Technologies, Inc.

Style 4 Network Mode

The Style 4 jumper on a NET-7 is found on


a Style 7 system. Move the jumper to the
Style 7 position.

Style 7 Network Mode

The Style 7 jumper on a NET-7 is found in


the Style 4 mode. Move the Style 7 jumper
to the Style 4 position.

System Commissioning Mode

The system has been put in the commissioning mode.

System Signal Power Failure

A CSM-4 has lost power to its output


circuits.

Tamper Switch

This is a security-type message for the


tamper switch on the SMB-2 board when
the system is selected for UL 1076 operation.

Too Many ALD-2s

To many ALD-2Is are installed on the system.


This is beyond the maximum allowed.

Trouble Causing Input

A device programmed on the system as


trouble causing has been activated and has
changed state.

Trouble Type Not Defined

Unspecified trouble has been received from


this address.

Troubles Summarized

While the system is in the commissioning


mode, the modules will display this message
in lieu of all the devices on this module.

Unspecified Dev Responding

An analog device has reported at an


address not assigned in CSG-M.

Technical Manuals Online! - http://www.tech-man.com

J-7

Appendix J

Trouble Message

The Probable Cause Is:

Unspecified Mod Responding

A module has reported at an address not


assigned in CSG-M.

Unspecified Node Responding

NIM-1R address on another node is


incorrect.
The network CSG-M is incorrect.

J-8

WALKTEST Activated

The MXL-IQ has been placed in the walk


test mode.

Warm Reset

The hardware reset input to the MXL-IQ


was used.

Watch Dog Circuit Triggered

The watch dog circuit on the


SMB-2 triggered.

Zone Loop Open

Broken wire on CZM-4 circuit.

Zone Loop Shorted

Shorted wire on CZM-4 circuit.

Zone Power Loss

The CZM-4 zone at this address has lost its


24 volt input.

Technical Manuals Online! - http://www.tech-man.com

Appendix K

Power Limited Wiring


For power limited wiring refer to the following Installation Instructions:

Enclosure

Installation
Instructions

LLM-1

315-093530-2

MSE-3

315-093831-1

MSE-3L

315-095445-1

Technical Manuals Online! - http://www.tech-man.com

K-1

Appendix K

K-2

Technical Manuals Online! - http://www.tech-man.com

Appendix L

New Two Stage Alarm

For use in Canada only with MXL-IQ software version 1.0 and higher

Canadian Two Stage Alarm is available


with revision 1.0 of MXL-IQ firmware and
revision 6.07 of CSG-M. All new installations
of Two Stage Alarm should use the new
implementation.
The hardware requirements for the Two
Stage Alarm are as follows:
MXL-IQ firmware revision 1.0 or higher
CSG-M revision 6.07 or higher
CSM-4s must contain revision 4 or
higher
The new Two Stage implementation is
designed for flexibility. It allows the system

designer/programmer to define how Two


Stage alarm should function.

Selecting Two Stage


A new selection in the CSG-M determines
which version of Two Stage Alarm is used
in an MXL-IQ. In the Other System Flags
menu (under the Options, System Message, Authorizations menu), a YES/NO
option has been added for New Two Stage
Configuration. This flag determines which
implementation of Two Stage alarm is used
in the MXL-IQ.

Fire Protection Company Name


CSG-M Memory=2864 used, 243212 free
Other System Flags

CONFIG => TWOSTG

Sensitivity Adjustments Allowed ----------------->


Block Alarm and Trouble Acknowledge Allowed ----->
Multienclosure System --------------------------->
Device disarm through RESET --------------------->
Self restoring troubles ------------------------->
NFPA 71 connection ------------------------------>
NET 7 panel checking ---------------------------->

NO
YES
NO
NO
NO
NO
NO

Network Repeater Used ---------------------------> NO


Independent Function Keys -----------------------> NO
New Two Stage Configuration ---------------------> YES

Move Cursor to Select, ENTER to TOGGLE

ESC = Prev. Menu

CSG-M Other System Flags Menu

Technical Manuals Online! - http://www.tech-man.com

L-1

Appendix L
Select NO for the old system flag
driven version of Two Stage
Select YES for the new control function
version of Two Stage
NOTE: When recompiling an older implementation of Two Stage Alarm under
CSG-M 6.07 or higher, make certain that
the New Two Stage Configuration flag is
set to NO before compiling and uploading
to the MXL-IQ.

Two Stage Signal Circuit Output


Definition
The output for all the coded audibles must
be defined on a system basis. This is done
in CSG-M from the Options, System
Message, Authorizations menu. The Zone
Coded Audible Format menu item determines the systems Two Stage audible
definition. The following nine selections are
provided for Two Stage audibles:

Zone codes must be entered on a point


by point basis.
Zone codes will be output first by
priority, second by queue order.
In order to have the codes sound in the
queue order only, all priorities must be
the same.

Two Stage Control Function (CSG-M)


This function has two inputs and an output
list.
The inputs are labeled Stage 1 and Stage 2.
The inputs may contain the following items:
a device address
function output (logic, timer, etc.)
system flag reference
The output may only be a list of CSM-4 or
main board signal circuits. The signal
circuits referenced must be zone coded
audibles.
The following table describes how the Two
Stage Control Function works.

Two Stage Audible - 30/120 SPM


Two Stage Audible - 30 SPM/Steady
Two Stage Audible - 30 SPM/Temporal
Two Stage Audible - Steady/Steady
Two Stage Audible - Steady/120 SPM
Two Stage Audible - Steady/Temporal
Two Stage Audible - Zone Coded/Steady
Two Stage Audible - Zone Coded/120 SPM
Two Stage Audible - Zone Coded/Temporal

TWO STAGE CONTROL FUNCTIONS

Note that each selection contains a slash (/)


which separates the Stage 1 audible signal
from the Stage 2 audible signal as shown in
the following example.

Stage 1
Input

Stage 2
Input

Coded Audibles in
Ouput List

False

False

Silent

True

False

Stage 1 Audible Signal


For example: 30 SPM,
steady or zone coding

False

True

Stage 2 Audible Signal


For example: 120 SPM,
steady or temporal

True

Stage 2 Audible Signal


For example: 120 SPM,
steady or temporal

Example:
Stage 1 audible

Stage 2 audible

Two Stage Audible - 30 / 120 SPM


slash

When zone coding is selected for Stage 1,


the system displays the Zone Coding
Characteristics menu. (See Figure on the
next page.) This menu allows the system
designer to program the number of rounds,
minimum number of rounds, etc. The final
state will always be STEADY no matter
what is selected in this menu.

L-2

Technical Manuals Online! - http://www.tech-man.com

True

Multiple Two Stage control functions may


be used in a configuration. A single coded
audible may appear on the output list of
more than one Two Stage control function.
Due to the potential conflict between the
functions controlling the same coded
output, the following rule applies to the Two
Stage control function:

Appendix L

Fire Protection Company Name


CSG-M Memory=2900 used, 316874 free
CONFIG => TWOSTG
Options, System Message, Authorizations

System Message ----------------->


Authorization Code-Level 1 ----->
Authorization Code-Level 2 ----->
Authorization Code-Level 3 ----->
COUNTRY where installed -------->
Language Selection ------------->
NFPA System Designation -------->
Backup Power Type -------------->
Zone Coded Audible Format ------>
Function Evaluation Limit ------>
Photo Detector Confirmation ---->
Ion Detector Confirmation ------>
Sys. Justified Alarm Time ------>
Intelligent Env. Compensation -->

----- CERBERUS Pyrotronics ----11111


22222
33333
Canada
ENGLISH and FRENCH
NFPA A System
15 Amp Hour
TWO STAGE AUDIBLE - ZONE CODED/STEADY
32
0
0
60
OFF

VDT Password Time Out (hh:mm) --> 00:05


Zone Coding Characteristics
Move Cursor to Highlight Selection, then ENTER

ESC=Prev. Menu

Fire Protection Company Name


CSG-M Memory=2900 used, 316874 free
Zone Coding Characteristics

# rounds (3-15) ---------------->


Tempo -------------------------->
Final output status ------------>
Inter-digit time (0.5-15 secs) ->
Inter-round time (0.5-15 secs) ->
Inter-group time (0.5-15 secs) ->
Minimum # round (3-15) --------->
Zone Code Alarms After Silence ->

CONFIG => TWOSTG

5
60/MIN
AUDIBLES ON
1.0
2.0
4.0
3
YES

Move Cursor to Highlight Selection, then ENTER

ESC=Prev. Menu

Selecting the Zone Coding Characteristics Menu

Technical Manuals Online! - http://www.tech-man.com

L-3

Appendix L
When a coded audible appears on the
output list of more than one Two Stage
control function and there is a conflict
(that is, some functions indicate Stage
1 and some functions indicate Stage
2), then Stage 2 has priority over
Stage 1. As a result, the coded
audibles in question will output Stage 2
(either 120 SPM, steady, or temporal,
as selected).
NOTE: When zone coding is selected as the
Stage 1 audible output, Stage 2 always has
priority over the Stage 1 coding. Once the
coded circuit is driven into Stage 2 by logic,
all zone codes will stop for that circuit no
matter what the minimum rounds are.

There are two keyswitch types available in


the MXL-IQ. All logic associated with a
keyswitch device is CSG-M programmable.
The only MXL-IQ defined aspects of a
keyswitch are as follows:
Keyswitch Type 1
1. If a Type 1 keyswitch is activated, an
alarm event will result.
2. The event will be recorded on the alarm
queue and all standard MXL-IQ functions
associated with an alarm will occur (that
is, the ANY ALARM flag will be set to
TRUE, the ANY NEW ALARM flag will
pulse, etc.).
3. This is true even if there are no previous
alarms.

Two Stage System Flags


There are two system flags associated with
Two Stage alarm: Reset Inhibit and Two
Stage Audible State. Both of these flags
are writable with user-designed logic. Refer
to the following table for Setting the Two
Stage System Flags.
It is important to note that other Two Stage
writable flags used in the previous Two Stage
implementation are not used in the new Two
Stage implementation.

Keyswitch Type 2
1. If a Type 2 keyswitch is activated when
no alarms are present in the system, it
will result in a trouble condition at the
MXL-IQ.
2. If an alarm is detected while this trouble
condition is present on the trouble
queue, the active Type 2 keyswitch will
be added to the system as an alarm
event (added to alarm queue).

SETTING THE TWO STAGE SYSTEM FLAGS

3. If the keyswitch is activated when an


alarm is present in the system, the
keyswitch will be treated as an alarm.

When the Reset Inhibit Then the Normal Reset


flag is held:*
(Red MMB key) is:

All other system behavior is determined by


output logic design.

True
False

Inhibited
Not Inhibited

*The default value of Reset Inhibit is FALSE if the


system does not require a Reset Inhibit.

Sample Two Stage Systems

If the Two Stage Audible Then the Normal Audible


State flag is held:**
Silence (Red MKB key) is:

Using Reset Inhibit with Timer


The figure on page L-5 shows methods of
implementing Reset Inhibit with a timer,
creating an ANY KEYSWITCH function/flag
and a timer based signal silence inhibit
function.

False
True

Inhibited
Not Inhibited

**The default value of Two Stage Audible State is


TRUE if the system does not require a Two Stage
Audible State Inhibit.

L-4

Keyswitch Devices

Technical Manuals Online! - http://www.tech-man.com

Keep in mind that your implementation of


these features may vary from the examples
shown. If Reset Inhibit or Two Stage
Audible Silence are not required in your
system, then references to these flags are
not required in the logic design.

Appendix L
Basic Two Stage System
The figure on page L-6 demonstrates a
basic Two Stage system design. Its
operation is summarized below:

reset (provided the RESET INHIBIT


logic permits).
If a keyswitch is activated after the
ANY_ALARM flag is TRUE, the
system will output the second stage
audibles.
In either stage, the audible silence
flag/key controls the silencing and
unsilencing of the coded audibles.
The Panel Reset flag is used to assure
timers and latches are reset for the
next event after reset.

This system will output Stage 1


audibles when the first alarm occurs.
If the alarm is not acknowledged prior
to the expiration of stg1_timer, coded
audibles will be forced output Stage 2
audibles.
If the alarm is acknowledged during
Stage 1, only a keyswitch will place
the system in the second stage.
If the system is reset after the alarm
has been acknowledged and coded
audibles silenced, the system may be

RESET_INH
Any Alarm

Trigger (ALL)
30 Sec

True

SS_INH
Any Alarm

Run

Trigger (ALL)

Reset Inhibit

Run

Enable

True

Two Stage
Audible Silence

Enable

Start Timer

Start Timer

Cancel

Cancel

False

Panel Reset

Typical RESET INHIBIT Timer Function

Typical Signal Silence Inhibit Function

Any_keyswch
Any alarm
Keyswch
List of
Keyswitch
Inputs

OR
(ANY)

AND
(ALL)

Typical ANY KEYSWITCH Function

Using Reset Inhibit with Timer

Technical Manuals Online! - http://www.tech-man.com

L-5

Appendix L

Any Alarm

True

Stg1_timer

Run

Trigger (ALL)

Start Timer

Cancel

Enable

Panel Reset

Set

Stg2_enb

Any Alarm

Reset

Clear

Stg2_can

OR
(ANY)

False

Panel Reset

Panel Reset

Audible Silence

In this example, several Two Stage control


functions are used in the system design.
Together with the proper glue logic, a
modified Two Stage system is the result. In
this system, the floors above and below the
alarm signal Stage 1 coded audibles while
the floor of alarm codes Stage 2 audibles.
The general differences between the basic
and complex systems are as follows:

All Alarms Ackd

Any Alarm

any_keyswch

Stg1_to

AND
(ALL)

Stg2_timer

Run

Trigger (ANY)

Enable

Start Timer

Cancel

The first alarm will result in Stage 1


coding on that floor.
An activation of a keyswitch will place
the system in second stage. Therefore, the floors above and below the
alarm will code Stage 1; Stage 2 will
code on the floor of alarm.
If an adjacent floor generates an
alarm, that floor will code Stage 2.
This same principle may be applied to
networked MXL-IQs using external references.

Panel Reset

Audible
Silence

For example: The building in alarm codes


Stage 2 while the adjacent buildings code
Stage 1.
Stg1_ssi

AND
(ALL)

Stg2_sil

OR
(ANY)

Stg2_ran

Set

Reset

Clear

Visual indications are made using MOD-16


outputs. Simply connect the signal in the
logic diagram to the desired LED or other
function to indicate the system stage.

For example: Connect Stage 1 and Stage


2 inputs to an LED function to indicate the
system state.

Stg2_sil

AND
(ALL)

List of Two Stage


Audibles

Technical Manuals Online! - http://www.tech-man.com

Stg_ctl

Stg1

Stg2

Audible
Silence

Basic Two Stage System

L-6

Complex Two Stage System


The figure on the next page demonstrates
a more complex Two Stage system. The
basic principles of operation are the same
as the basic Two Stage system with a slight
variation.

NOTE: Since other audibles may be


present in the system besides coded (Two
Stage) audibles, the AUDIBLE SILENCE
LED on the MKB will indicate the state of
the AUDIBLE SILENCE flag as usual. Its
state will only change with manual intervention (manual silence/unsilence).

xxxx

Complex Two Stage System

Technical Manuals Online! - http://www.tech-man.com

Stg1_ssz1
To input list of
stg1_ssz1,
stg1_ssz2,
stg1_ssz3

Stg1_timer
Any Alarm

Trigger (ALL)
Run
Enable

Floor 1
alarm pts

Stg1_to

OR
(ANY)

AND
(ALL)

stg2_flr1

AND
(ALL)

Any Alarm

flr1_2stg
Stg1

Audible
Silence

All Alarms Ackd


True

stg1_flr1

stg1_timer

Stg2
Stg2_sils
Floor 1
alarm pts

Start Timer

AND
(ALL)

First Floor
Two Stage
Audible List

Cancel

Stg1_ssz2

Panel Reset
any_keyswch

Stg2_enb
Any Alarm
False

Set

stg1_timer
Floor 2
alarm pts

Stg2_timer

Audible
Silence

Trigger (ANY)

Reset

stg1_flr2

AND
(ALL)

Clear

Stg2_sils

Enable

Panel Reset
Audible Silence

Floor 2
alarm pts

Start Timer

Stg2_can
OR
(ANY)

flr2_2stg
Stg1
Q

stg2_flr2

Run
Panel Reset

OR
(ANY)

Stg2

Second Floor
Two Stage
Audible List

AND
(ALL)

Cancel

Stg1_ssz3

Stg2_sil

stg1_timer
Floor 3
alarm pts

Stg2_ran
Set

L-7

Panel Reset

Clear

Q
Audible
Silence

Audible
Silence
Stg2_sils
OR
(ANY)

stg1_flr3
OR
(ANY)

flr3_2stg
Stg1
Q

stg2_flr3
Use to
indicate
Stage Two
is active

Stg2_sils
Floor 3
alarm pts

Stg2
AND
(ALL)

Third Floor
Two Stage
Audible List

Appendix L

Reset

AND
(ALL)

AND
(ALL)

Appendix L

L-8

Technical Manuals Online! - http://www.tech-man.com

Appendix M

Pre-alarm, Dual Criteria Logic


Functions, and Percent Per Foot
Obscuration Features
The pre-alarm feature provides an early
warning of smoke conditions at a more
sensitive reading than alarm level. This
indication can be in the following form:
a displayed and printed pre-alarm
report
output logic control
both
Dual criteria logic allows for the distinction
between the chamber or thermal detector
of the ILPT-1 photo thermal.
The pre-alarm and dual criteria logic
function (ILPT-1 only) features of the ILI or
ILP series of detectors are enabled by the
FPI-32 Field Programmer.
Note:

FPI-32 Rev. 1.3 or higher is


required.

The FPI-32 also gives these detectors new


unique IDs so that they can be identified at
the MXL-IQ as different from the ID-60I and
ID-60P series. The ID-60I and ID60P
detectors still exist in the CSG-M, but the
features described in this appendix do not
apply to them.

Technical Manuals Online! - http://www.tech-man.com

CSG-M Software

ILI ion detectors and ILP photoelectric


detectors are available as I/O device types
for ALD-2s (or ALD-2Is). These device types
tell the CSG-M and the MXL-IQ that they
have the features of pre-alarm, dual criteria
(photo thermal only), and ability to display
readings in percent per foot (%/ft) obscuration.
These detectors appear in the CSG-M with
the existing ID-60I and ID-60P detectors.
The MXL-IQs Custom Software Generator
(CSG-M) allows the installation of the ILI or
ILP detectors at any valid ALD address.

Pre-alarm
Pre-alarm must be selected to either
annunciate a detectors pre-alarm or use
the detector in a Criteria Selection function.
Pre-alarm can be enabled at each device
when it is installed as a Yes/No (Y/N) option.
The CSG-M provides the following system
options for pre-alarm:
annunciate (Y/N)
automatic adjust (Y/N)
annunciation type trouble
learning period (1 - 30 days)
activate detector LED (Y/N)

M-1

Appendix M

Dual Criteria Logic Functions


The CSG-M provides a logic function type
labeled Criteria Selection. The following
inputs to this function are a detectors:
pre-alarm (from IL devices or
Analaser),
verification, or
chamber or thermal for the photo
thermal detector (ILPT-1)
Pre-alarm and chamber or thermal selections cannot be mixed in the same function.
The output can be any that is capable of
being driven by output logic, including
sending the output to another function.
Note:

For networked MXL-IQ systems, no


external panel inputs are allowed in
the Criteria Selection function.

MXL-IQ Pre-alarm
Software
Pre-alarm Learning and Setting
The MXL-IQ automatic pre-alarm learning
feature adjusts smoke detector pre-alarm
levels (during the time period selected in
the CSG-M) until they stabilize. Depending
upon pre-alarm activity, the system starts
with the most sensitive pre-alarm level and
gradually adjusts (de-sensitizes) the
MXL-IQ until pre-alarms no longer occur.
The level reached by each smoke detector
at the end of the learning period is the
learned pre-alarm level. No pre-alarms
annunciate or feed output logic during this
learning period.
The learned pre-alarm level is stored in
flash memory so that on a panel power-on,
watchdog, or nickel reset, the pre-alarm
readings still exist. When a new or modified CSG-M is loaded into flash memory,
the MXL-IQ will NOT assume pre-alarm
existed before and will re-start the
learning mode.
The flash memory used for storing prealarm detector readings shares the intelligent environmental control (IEC) flash
memory area. This requires that a boot
block flash device be used if pre-alarm is
enabled. The flash segment size shared by

M-2

Technical Manuals Online! - http://www.tech-man.com

IEC and pre-alarm is 8K. Each IEC device


uses 2 bytes and each pre-alarm device
uses 1 byte, allowing a maximum of slightly
over 2500 devices with both IEC and prealarm.
Manual pre-alarm settings can be set at the
MXL-IQ by using the CONTROL PERCENT/FT PRE_ALARM command (See
Pre-alarm and Sensitivity Settings below).
Any valid pre-alarm reading within the
range specified in the table on page M-3
can be used. Pre-alarm adjustments are in
%/ft obscuration. Manual settings override
the learning mode settings. However, they
do not take effect until the end of the
learning period.

Pre-alarm Event Annunciation


Annunciation is a global yes/no option and
the type of annunciation is a trouble. The
trouble report contains the type field text of
Pre-alarm and both the INs and OUTs are
recorded. The format of these trouble
reports is identical to the format of all
existing MXL-IQ trouble or supervisory
reports.
Annunciation of a pre-alarm smoke detector is provided even if the device goes
immediately into alarm. The alarm is
reported first because of its higher priority,
but a pre-alarm or trouble is also generated
thereafter with the same time and date.
Output logic control using the criteria
function with ILI/ILP pre-alarm as the
criteria selection follows the INs and OUTs.
If latching is desired, it must be added in
the CSG-M. Using the criteria selection
function to select either the chamber or the
thermal for the ILPT-1 takes the MXL-IQ an
additional 5 seconds (or more) to evaluate
after the device alarms. This occurs
because a special status poll must be done
to determine whether it was the chamber or
the thermal that caused the alarm. A
criteria function with a selection of alarm
verification provides an output for the
duration a smoke detector is being verified
or until reset if the device alarms.

Pre-alarm and Sensitivity Settings


Pre-alarm and sensitivity adjustments are in
%/ft obscuration and have the following
ranges, increments, and default values:

Appendix M
PHOTO

ION

Pre-alarm adjust
increment

.25% / ft.

.12% / ft.

Pre-alarm range

.25 - 2.0% / ft.

.25 - .75% / ft.

1.5% / ft.

.75% / ft.

Sensitivity adjust
increment

~.25% / ft.

~.12% / ft.

Sensitivity range

1.25 - 3.4% / ft.

.6 - 1.6% / ft.

3.0% / ft.

1.4% / ft.

Pre-alarm
default

Sensitivity
default (Norm)

Because the pre-alarm and sensitivity


settings overlap, set the pre-alarm to at
least an increment below the sensitivity
setting.

Field Programmer Use

The FPI-32 (Rev. 1.3 or higher) must be


used to enable the programming of the ILI
and ILP IDs. The IDs tell the smoke
detector it has the advanced features such
as pre-alarm. For more information about
using the FPI-32 with IL series detectors,
refer to the FPI-32 Programmer/Tester
Operations Manual, P/N 315-090077.

Technical Manuals Online! - http://www.tech-man.com

M-3

Appendix M

M-4

Technical Manuals Online! - http://www.tech-man.com

Appendix N

MXL-IQ Spare Parts List


Cables

Part Number

SMB-1/-2 to MKB-4

555-192238

SMB-1/-2 to MOM-2/-4 (24V Power)

60 0-290505

SMB-1/-2 to MOM-2/-4 (5V and Data)

555-190506

SMB-1/-2 to Battery

555-190968

SMB-1/-2 to CSG-M Programming Cable

60 0-190704

Fuses
20 Amp MDA Normal Blow

105-292017

15 Amp 3AG Normal Blow

105-224090

8 Amp 3AG Normal Blow

105-217858

2 Amp 3AG Normal Blow

105-210758

Technical Manuals Online! - http://www.tech-man.com

N-1

Appendix N

N-2

Technical Manuals Online! - http://www.tech-man.com

Appendix O

New Features for MXL-IQ


Revision 6.0 and Higher
Reset Causing Zone for MID-16 or CZM-4
This powerful feature allows the user to
reset the MXL-IQ by changing the state of
the MID-16 or CZM-4 input. In CSG-M
Revision 10.01, select the new Local Reset
Causing usage for MID-16 or CZM-4 in the
Available Device Usage Types screen:
LOC RES CAUSNG

The system designer can connect the


MID-16 or CZM-4 inputs to another system
via a relay or have a remote reset input.
When this input changes state to the offnormal position, the MXL-IQ resets in the
same way as a RED KEY reset. Existing
events do not need to be acknowledged
and audibles do not need to be silenced.
NOTE:
This option is limited to NFPA 72A systems.
In networked systems, the scope of the
reset is local.

ALD Fast Polling


When this option is set in the CSG-M for
the ALD loops, the ALD polls only up to the
last device installed on the loop, thus
speeding up the system response. For
example, if there are only 5 devices installed on the ALD loop, the MXL-IQ polls
only up to address 5 on that loop instead of
polling all 60 addresses.
The ALD Fast Polling option requires
ALD-2I board Revision 14 and SMB ROM
Rev. 6.0. See the CSG-M Appendix for

Technical Manuals Online! - http://www.tech-man.com

Revision 10.01, P/N 315-096220, for setting


this option.
NOTE:
The ALD Fast Polling option can only be
used with Non-Fireprint Detectors.

24 Hour Trouble Resound /


Reminder Timer
If this feature is set in CSG-M, the MXL-IQ
automatically sounds the trouble buzzer
every 24 hours from the time that the
trouble was acknowledged until the trouble is
cleared. The troubles themselves are not
re-annunciated.

Trouble Delay Time for Damper Control


Using TRI
This delay time was fixed at 30 seconds in
the previous MXL-IQ Revisions. In Revision
6.0, the MXL-IQ delays the TRI damper
travel delay time trouble according to the
time that is selected in CSG-M. The delay
time is programmable from 0 to 90 seconds
in 1 second increments.

Delay of AC Failure Report


The delay time is programmable in CSG-M
from 0 to 90 seconds in 1 second increments.
The default value for this option is 0 seconds,
which results in an immediate reporting of
the trouble.
If an AC failure occurs, the MXL-IQ checks
the database for the delay time and starts

O-1

Appendix O
the timer if the delay time is other than zero.
No AC failure trouble is reported at this time.
At the end of this delay time, if the AC still
fails, the MXL-IQ posts the AC Failure
trouble; otherwise, it goes back to the
original state.

CCU Pager Interface


A new selection is added to the list of
printer selections under the Global MKB in
the Network map of the CSG-M: CCU/M
Pager Interface. The new selection
provides a remote interface between the
MXL-IQ panel and the operator.
This selection is available in all situations
where a printer was previously available.
For a 72 Proprietary networked system
(72D system), this selection is available
under a Display Only Global MKB. There
are only two selections in this configuration:
NONE and CCU/M.

O-2

Technical Manuals Online! - http://www.tech-man.com

When programmed into the CSG-M, this


pager interface can be either supervised or
unsupervised. The CCU/M interface is an
application specific output device, and not a
global MKB printer for a 72D system. Therefore, if it is installed on a 72D networked
system, it does not satisfy the compile
check for a supervised printer. To pass this
compile error, add a supervised printer to a
local MKB in every node in a 72D system.
Despite the above limitation, in both 72A
and 72D systems the CCU/M interface
counts as one GMKB printer available in a
networked system.
Only the normal print messages for events
are sent to the CCU/M interface. Information such as acknowledge, reset, time
changes, etc., do not output. The output
formatting is considered as a generic ASCII
printer.

Index
A
Acknowledge menu. See Menu: Acknowledge
addresses, 3 - 1
fixed addresses, 3 - 1

CRM-4
connections and ratings, 7 - 5
description, 1 - 9
installation, 2 - 14
module address, 3 - 2
CSM-4
connections and ratings
NFPA 12A, NFPA 1 - 1 and NFPA 2001, 7 - 9

alarm verification, E - 1 to E - 2

NFPA 72 Local, 7 - 7

ALD fast polling. See new features - rev.6.0 and higher

NFPA 72 Municipal Tie, 7 - 8

ALD-2I
connections and ratings, 7 - 1
description, 1 - 10
installation, 2 - 12
module address, 3 - 2
analog loop, 1 - 1
analog voltages. See device analog voltages

NFPA 72 Remote Station, 7 - 8


description, 1 - 8
installation, 2 - 14
module address, 3 - 2
CZM-1B6
connections and ratings, 7 - 13
analog loops, 7 - 14

application specific detection, I - 1 to I - 2

initiating devices, 7 - 13

ASD. See application specific detection

B
battery calculations, C - 1
BP-61 batteries
description, 1 - 7
BTX batteries
description, 1 - 7

power, 7 - 15
description, 1 - 14
CZM-4
connections and ratings, 7 - 17
description, 1 - 9
installation, 2 - 14
module address, 3 - 2

C
Canadian two stage alarm, L - 1 to L - 7
CCU pager interface. See new features - rev.6.0 and
higher
CMI-300
connections and ratings, 7 - 3
description, 1 - 9
installation, 2 - 13
compatible devices, A - 1

Technical Manuals Online! - http://www.tech-man.com

delay of AC failure report. See new features - rev.6.0


and higher
device analog voltages, B - 1
devices, compatible. See compatible devices
DI Series of detectors
description, 1 - 15
DT-11
description, 1 - 15
dual criteria logic, M - 1 to M - 3

Index - 1

Index
IEC. See Envirolink

E
Envirolink, F - 1 to F - 3

ILI Series of detectors


description, 1 - 13
ILP Series of detectors

F
FP Series of detectors
description, 1 - 12

description, 1 - 13
ILT
description, 1 - 13

History Log
display, 6 - 6 to 6 - 10
audible silenced event, 6 - 8
audible unsilenced event, 6 - 8
auto sensitivity set event, 6 - 9
block acknowledge event, 6 - 7
configuration changed event, 6 - 9
event, 6 - 6
formats, 6 - 6
manual sensitivity set event, 6 - 9
override event, 6 - 8
password event, 6 - 8
reset event, 6 - 6
set time event, 6 - 7
download formats, 6 - 13
sequence, 6 - 14
local log query, 6 - 5
logging methods, 6 - 2 to 6 - 4
options, 6 - 1
enable, disable and erase, 6 - 4
overview, 6 - 1
print formats, 6 - 10 to 6 - 13

latching/non-latching troubles, G - 1
LIM-1
description, 1 - 14

M
Menu. See MKB-4: operation
Acknowledge, 3 - 18
Alarm, 3 - 18 to 3 - 19
Security, 3 - 21 to 3 - 22
Supervisory, 3 - 19 to 3 - 20
Trouble, 3 - 20 to 3 - 21
Control, 3 - 36 to 3 - 42
Analaser, 3 - 40
Arm/dis, 3 - 38
Change Apps, 3 - 42
Loop Arm, 3 - 39
Loop Disarm, 3 - 39 to 3 - 40
Net Link Request, 3 - 40
Output on/off, 3 - 38 to 3 - 39
Percent/ft, 3 - 41 to 3 - 42
Reset, 3 - 37
Sensitivity, 3 - 37
List, 3 - 22 to 3 - 36

I
ICP / ICP-B6
description, 1 - 12
ID Series of detectors
description, 1 - 12 to 1 - 13

Index - 2

Technical Manuals Online! - http://www.tech-man.com

Alarm, 3 - 23 to 3 - 24
Analaser, 3 - 32 to 3 - 34
ASD_apps, 3 - 35 to 3 - 36
Device Type, 3 - 29
Device Usages, 3 - 31 to 3 - 32

Index
Message, 3 - 29 to 3 - 30

global operation, 3 - 12 to 3 - 14

Module, 3 - 28 to 3 - 29

display format, 3 - 12

Node Address, 3 - 32

keypad, 3 - 13 to 3 - 14

Output States, 3 - 31

limitations and restrictions, 3 - 12

Percent/ft, 3 - 34 to 3 - 35

installation, 2 - 4

Security, 3 - 25 to 3 - 26

local operation, 3 - 3

Sensitivity, 3 - 26

alarm, 3 - 6 to 3 - 8

Software Version, 3 - 30 to 3 - 31

command keypad, 3 - 5

Status, 3 - 23

display, 3 - 3

Supervisory, 3 - 24

display keys, 3 - 5

Temp, 3 - 28

internal audible, 3 - 4

Trouble, 3 - 24 to 3 - 25

LEDs, 3 - 5

Voltages, 3 - 26 to 3 - 28

modes of operation, 3 - 5

Test, 3 - 42 to 3 - 49

numeric keypad, 3 - 4

ASD_Devices, 3 - 48

security, 3 - 10 to 3 - 11

Det_cleaned, 3 - 47

special (alt + function) keypad, 3 - 5

Device LED, 3 - 45

supervisories, 3 - 8 to 3 - 9

Event Log, 3 - 47

troubles, 3 - 9 to 3 - 10

Ground Fault, 3 - 44

using the menu, 3-14

Lamp Test, 3 - 45

walktest. See Walktest: operating instructions

Manual Activate, 3 - 49
MOI Lamp Test, 3 - 46

module address, 3 - 2
MOD-16

Override, 3 - 46 to 3 - 47

connections and ratings, 7 - 21

Power, 3 - 44 to 3 - 45

description, 1 - 10

Pre-alarm, 3 - 47 to 3 - 48

installation, 2 - 9

Pyro-diags, 3 - 47

operation, 3 - 3

Set Time, 3 - 43 to 3 - 44

Module Addresses. See Addresses

Summarize, 3 - 48 to 3 - 49

MOI-7

Test Network (X-Net, M-Net), 3 - 46

connections and ratings, 7 - 19

Menu overview, 3 - 15

description, 1 - 10

MID-16

installation, 2 - 9

connections and ratings, 7 - 21

module address, 3 - 2

description, 1 - 11

operation, 3 - 3

installation, 2 - 9
MKB-4
description, 1 - 5

MOM-2
connections and ratings, 7 - 25
description, 1 - 8
installation, 2 - 6 to 2 - 9

Technical Manuals Online! - http://www.tech-man.com

Index - 3

Index
MOM-4
connections and ratings, 7 - 27
description, 1 - 8

P
PAL-1
description, 1 - 6

installation, 2 - 6 to 2 - 9
MPS-6/-6W, MPS-12/-12W
description, 1 - 5
installation, 2 - 3 to 2 - 4
MSE-3L
installation, 2 - 2
MSI Series of manual stations
description, 1 - 14

installation, 2 - 6
PBA-1191
description, 1 - 15
PE Series of detectors
description, 1 - 15
percent per foot obscuration, M - 1 to M - 3
PIM-1
description, 1 - 6

MXL Power Supply Load Calculations, D - 1


MXL-IQ
basic components, 1 - 4
battery calculations, C - 1
description, 1 - 1
minimum configuration, 1 - 3
new features - rev.6.0 and higher, O - 1
power supply load calculations, D - 1
software, 1 - 1

N
new features - rev.6.0 and higher, O - 1 to O - 2

installation, 2 - 5
PIM-2/PAL-1
installation, 2 - 6
power limited wiring, K - 1
power supply load calculations, D - 1
pre-alarm, M - 1 to M - 3

R
reset causing zone for MID-16 or CZM-4. See new
features - rev.6.0 and higher: reset causing zone
reset procedures
hard reset, 3 - 11

24 hour trouble resound /reminder timer, O - 1


ALD fast polling, O - 1
CCU pager interface, O - 2
delay of AC failure report, O - 1 to O - 2
reset causing zone, O - 1
trouble delay time for damper control using TRI, O - 1
NIM-1R
connections and ratings, 7 - 29 to 7 - 32
AnaLaser interface, 7 - 32
foreign system interface (FSI), 7 - 31

soft reset, 3 - 11 to 3 - 12

S
security point, installing, H - 1
self restoring troubles. See latching/non-latching
troubles
Silent Knight Model 5128/5129
connections and ratings, 7 - 33
SMB-2
connections and ratings, 7 - 35

network, 7 - 29

field wiring, 7 - 36 to 7 - 38

network command center (NCC), 7 - 30

internal wiring, 7 - 35

description, 1 - 11

description, 1 - 4

installation, 2 - 14

installation, 2 - 3
module address 3 - 2

Index - 4

Technical Manuals Online! - http://www.tech-man.com

Index
spare parts list, N - 1
start up procedure, 2 - 10 to 2 - 16
system operation, global, 3 - 12 to 3 - 14
system test, 4 - 1

T
testing procedures, 4 - 1
TRI Series of interface modules
description, 1 - 14
trouble delay time for damper control using TRI. See
new features - rev.6.0 and higher
trouble messages, J - 1 to J - 8
trouble resound / reminder timer. See new features rev.6.0 and higher
Troubleshooting Guide, 4 - 2
TSW-2
description, 1 - 6
installation, 2 - 2
two stage alarm, Canadian, L - 1 to L - 7

W
Walktest, 5 - 1 to 5 - 6
operating instructions, 5 - 4
overview, 5 - 1
suggested procedure, 5 - 2 to 5 - 3

Technical Manuals Online! - http://www.tech-man.com

Index - 5

Index

Index - 6

Technical Manuals Online! - http://www.tech-man.com

WARNING:

This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to radio
communications. It has been tested and found to comply
with the limits for a Class A computing device pursuant to
Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a
residential area is likely to cause interference in which case
the user at his own expense will be required to take whatever measures may be required to correct the interference.

Technical Manuals Online! - http://www.tech-man.com

Siemens Building Technologies, Inc.


8 Fernwood Road
Florham Park, New Jersey 07932
P/N 315-093624CD-9
Technical Manuals Online! - http://www.tech-man.com

Siemens Building Technologies, Ltd.


50 East Pearce Street
Richmond Hill, Ontario L4B 1B7 CN

NOTES:
1. For Installation Instructions for the MXL-IQ modules refer
to the Table below.
2. Waterflow Alarm must be AccuLINK (CSG-M) configured
to at least one non-silenceable NAC.
3. Refer to the MXL-IQ OPERATION, INSTALLATION,
AND MAINTENANCE MANUAL (P/N 315-093624) for
minimum NFPA configurations and additional information.
4. Use the following batteries: BTX-1, BTX-2, or BP-61.
5. The CSM-4 module is capable of the following functions:
Leased Line Circuit
Supervised Local Energy Auxiliary Trip (Municipal Tie)
Supervised Notification Appliance Circuit
Releasing Service
6. CRM-4 relay coils are supervised when not energized;
contacts are not.
7. For alternate configurations using CZM-1/1B6s, consult
Technical Support.
8. Optional transient suppressors Model CP2341 and
CP2297 may be used in addition to the transient
protection incorporated in the panel and not in lieu of
that protection. Use them for extreme lightning
conditions. For CP2297 refer to instructions P/N 315-092355.
For CP2341 refer to instructions P/N 315- 092390.
9. For the Silent Knight 5128/5129 Central Station, Remote
Station connection (NFPA 72), refer to instructions P/N
315-093294.
10. The modules indicated with an asterisk in the Table below
are rated power limited on all terminals. Refer to the
MXL-IQ Power Limited Wiring Instructions, P/N 315-095445,
for separation of power limited wiring.
11. When the CSM-4 is configured for Municipal Tie or
Releasing Service, terminals 1 and 4 and/or terminals 9
and 12 are non-power limited. In all other applications, the
CSM-4 is power limited on all terminals.
12. For a list of Compatible Notification Appliances, refer
to P/N 315-096363.

> * 7 (2 =. ', 2 <

:) 0 2 ?

$ . - ( " ? 7 (+ 0- 1(

)( C%+B 44A' A@?

)( C%+B 44A' A@?

/(( OLAE A@? NHML "% 2FKHFE JFIHGFED


8( OLAE A@? NHML "&<;. 2FKHFE JFIHGFED

>&A#@ C:B $,,7

#0C SRQHPMFKFJ ;=1B /#A' A@?

#0C SRQHPMFKFJ ;=1B /T8' A@?

) OLAE A@?

>&A#@
BI&#GHGAF E,D(2

#0C SRQHPMFKFJ ;=1B


/' A@?

#0C SRQHPMFKFJ ;=1B


/' A@?

0 OLAE A@?! V/( +3*$/</54E A@?U

:$J#@"

)( C%+B 4(A' A@?

)( C%+B 4(A' A@?

/(( OLAE A@? NHML "% 2FKHFE JFIHGFED


8( OLAE A@? NHML "&<;. 2FKHFE JFIHGFED

BI&#K

#($#0T8 C%+
0A' A@?

#0T8 C%+ A@?


/9(A' A@?

,( OLAE A@?

BI&#GHGAF

/9$#0T8 C%+
0A' A@?

#0T8 C%+ A@?


08A' A@?

)8 OLAE A@?

>&A#@
:-0),3 $,,7

B>&#K C:B $,,7

#0C SRQHPMFKFJ ;=1B


/#A' A@?

#0C SRQHPMFKFJ ;=1B


##($)#(A' VAOAFRM@KWU

##T8 OLAE A@? VHRGPSJHRX PO@JU

B>&#K
$(0'(+ $.-(

#0C SRQHPMFKFJ ;=1B


)$-A' A@?

#0C SRQHPMFKFJ ;=1B


)$-A' A@?

#T86 OLAE
VHRGPSJFE PHRF @RJ PO@JU

#0 C%+
/#A' A@?

#0 C%+
9((A' A@?

) OLAE A@?

B>&#K
4()(0'.-3 >(2=.1(
*See Note 7

&%$#"!
&,+*)('

"-'/0))0/.,"-'/2*1/.,-'

'&%$#"!
+*"$)((!
+.##-,
+.#)0/
+1*$0
+2*$0
+3*$/!
+3*$/54!
+3*$0!
"+.!
"+.$54!
&"*$/!
*"%$/4
*65$0
*7%$/4

)/8$(-/040$8
)/8$(-/#8-$8
)/8$(-#)88$#
)/8$(-#-)($#
)/8$(-(98)+
)/8$(-(980$)/8$(-(,#8$9
)/8$(-8)88$#
)/8$(-(,#4$,
)/8$(-#0,0$4
)/8$(-8)(4$#
)/8$(-#/)8$8
)/8$(-/94($#
)/8$(-)8,8$)
)/8$(-(9)($0

*7"$,!
*7*$#
*7*$0
*.2$4
*.2$/#
:"*$/1
.'&$/
."*$/!
."*$#
.2$8'
.2$8:,!
1++$/</;
2*5$#
>2=$#

)/8$(-#,--$#
)/8$(-#,,,$8
)/8$(-(98#$,
)/8$(-())0$)
)/8$(-#()($)
)/8$(-#-8)$0
)/8$(-#0(9$8
)/8$(-/04#$/(
)/8$(-#0(9$8
)/8$(-#)4,$0
)/8$(-#,#-$4
)/8$(-8)40$#
)/8$(-8-)/$#
)/8$(-#0))$#

See Note 11

;=1 Y ;SPP =@IF 1FGMHQHFJ

C o mp a tib le In itia tin g D e v ic e s fo r


AL D - 2 I a n d S M B - 2
Compatible
Devices

Base

Installation
Instructions

CZM-1

315-090725-8

CZM-1B6

315-095355-2

DB-11, DB-X11RS
DB-3S + DB-ADPT
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT

315-095921-4
315-095921-4
315-095921-4
315-095921-4

FP-11*

FP-11*(d)

AD-11P/11XPR

315-095659-2

DB-11, DB-X11RS
DB-3S + DB-ADPT
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT

315-095921-4
315-095921-4
315-095921-4
315-095921-4

DB-3S, DB-X3RS

315-090287-2

AD-3I
AD-3XRI

315-093234-4
315-093235-4

ILI-1/1H/1A/1AH

DB-3S, DB-X3RS

315-095387-1

ILP-1

DB-3S, DB-X3RS

315-092594-5

AD-3ILP
AD-3XRILP

315-093234-4
315-093235-4

ILPT-1

DB-3S, DB-X3RS

ILP-2**

FPT-11*

ID-60I/IH/IA/IAH

"-'/0))0/.,"-'/2*1/.,-'

ILP-1 (d)

ILP-2**(d)
ILT-1

For Proprietary Burglary Application (1076) use a


TSW-2 tamper switch to monitor the main enclosure.
Monitor each TRI-60/60R/60D or TRI-B6/B6R/B6D
related to this application (1076) for 24 hours by a
listed motion detector to prevent tampering.

C ompatible D etectors for C ZM -4


Detector

Base

C ompatible D etectors for C ZM -1/ -1B 6*

Installation Instructions

DI-3/3H*

DB-3S

315-081943-15

315-092594-5

DI-A3/A3H*

DB-3S

315-081943-15

DI-3/3H

DB-3S

315-081943-15

DB-3S, DB-X3RS

315-095028-3

DI-B3/B3H*

DB-3S

315-081943-15

315-093234-4
315-093235-4

315-093234-4
315-086591-7

DI-A3/A3H

AD-3ILP
AD-3XRILP

AD-3I/3ILP
AD-3RI/3RP

DT-11*

DB-11
DB-3S + DB-ADPT

315-095429-1
315-095429-1

DI-B3/B3H

AD-3I/3ILP
AD-3RI/3RP

315-093234-4
315-086591-7

PBA-1191**

PBB-1191

315-095424-2

DB-11
DB-3S + DB-ADPT

315-095429-1
315-095429-1

PE-3/3T*

DB-3S
AD-3ILP
AD-3RP

315-090875-6
315-093234-4
315-086591-7

PE-3/3T

DB-3S
AD-3ILP
AD-3RP

315-090875-6
315-093234-4
315-086591-7

DB-11
DB-3S + DB-ADPT
AD-11P/11PR

315-094198-6
315-094198-6
315-095659-2

PE-11/11T

DB-11
DB-3S + DB-ADPT
AD-11P

315-094198-6
315-094198-6
315-095659-2

DB-3S, DB-X3RS

315-093336-1

MSI-10/-20

315-090903-3

MSI-10B/-20B

315-093329-3

MSI-B6F

315-095302-1

MSI-MB6

315-093613-1

TRI-B6/B6D/B6R

315-093315-3

TRI-B6M

315-094547-1

TRI-S/D/R

315-096242-1

*The FP-11 is only com pat ible w it h M XL-I Q R ev. 6. 0 or


great er f irm w are.
**The I LP-2 i s onl y com pat i bl e wi t h M XL-I Q Rev. 3. 0 or
great er f i rm ware.
When t he CSG-M i s conf i gured, t he DUCT appl i cat i on
m ust be sel ect ed when t he devi ce i s used i n an ai r duct
housi ng or i n a spot duct appl i cat i on.

Technical Manuals Online! - http://www.tech-man.com

CONNECTION DIAGRAM

) OLAE A@?

#0C SRQHPMFKFJ ;=1B /#A' A@? #0C SRQHPMFKFJ ;=1B /T8A' A@?

B>&#K
&*-.1.70) L.(

ID-60IB/IBH

&%$#"!
&,+*)('

CERBERUS PYROTRONICS Model MXL-IQ

5 ) ( 1 / 2 . 1 0 ) 40 / . - 3 '
;:) ) 20/. -3' 02( 7(2 9,-(8 7(2 ) ,,78 ,2 7(2 1. 21*. /6

PE-11/11T*

*M ay use up t o 30 det ect ors of any t ype.


**Onl y one PBA-1191, and no addi t i onal devi ces, can be
connect ed t o a CZM -4 i ni t i at i ng zone.

Detector

DT-11

Base

Installation Instructions

M a y u s e u p t o 1 5 d e t e c t o rs o f a n y t y p e .
*D o n o t u s e A D - 1 1 P R o r d e t e c t o r - o p e r a t e d a c c e s s o r i e s w i t h t h e
C Z M -1 / -1 B 6 .

Siemens Building Technologies, Inc.


8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
50 East Pearce Street
Richmond Hill, Ontario L4B 1B7 CN

P/N 575-293638CD-9

You might also like