Siemens MXL IQ Operation Installation Manual
Siemens MXL IQ Operation Installation Manual
Siemens MXL IQ Operation Installation Manual
com
Cerberus Division
Table of Contents
Version 1.0
Personalize/
Printout Cover
Personalize/
Printout Cover
Navigation
There are three ways to navigate:
1) Use the left hand index column (which appears as you proceed)
2) Use the green buttons above to get to the corresponding manual
3) Use the arrows in the menu bar above
There are 2 ways to enlarge or reduce:
1) Use the magnifying glass in the menu bar above
2) Use the three different page views in the menu bar.
Cerberus Division
CERBERUS PYROTRONICS
CAUTION
ALL WIRING MUST BE DONE AS DESCRIBED BELOW
TO OBTAIN SAFE AND PROPER SYSTEM OPERATION.
1. Earth ground the MXL-IQ enclosure properly; see the latest edition of the National
Electrical Code for approved methods. Conduit ground is NOT adequate.
2. Separate all wiring for initiating devices (i.e., detectors, manual stations, TRI
modules, etc.) from all other wiring in the MXL-IQ enclosure. To wire the System in compliance with UL 864, refer to the Installation and Power Limited
Wiring Instructions for the MSE-3L Enclosure, P/N 315-095445.
3. INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded
electrical box, including those in the MXL-IQ enclosure.
4. Connect shield cable drain wire ONLY inside the MXL-IQ enclosure.
5. No wiring used for any of the following can run outside the building:
an ALD loop
a RS-485 network
an NAC circuit used for audibles
a CZM-1B6 or CZM-4 initiating device loop
For additional wiring information, refer to this manual or call Siemens
Building Technologies, Inc. Technical Support Department at
1-800-248-7976.
Table of Contents
Description ______________________________ 1 - 1
Chapter 1
Introduction ___________________________________________________ 1 - 1
Software ______________________________________________________ 1 - 1
Minimum MXL-IQ Control Panel Configuration ________________________ 1 - 3
Table of Contents
Chapter 2
Installation ______________________________ 2 - 1
General Guidelines For Installing The MXL-IQ ________________________ 2 - 1
ii
Table of Contents
Operation _______________________________ 3 - 1
Chapter 3
Introduction ___________________________________________________ 3 - 1
Addresses ____________________________________________________ 3 - 1
System Modules _______________________________________________ 3 - 2
Remote System Modules ________________________________________ 3 - 2
Alarm ________________________________________________________ 3 - 6
How The System Annunciates Fire Alarms __________________________ 3 - 6
Viewing the List of Alarms ________________________________________ 3 - 7
How to Block Acknowledge A Fire Alarm ____________________________ 3 - 7
How to Individually Acknowledge A Fire Alarm ________________________ 3 - 7
Silencing The System ___________________________________________ 3 - 7
Supervisories __________________________________________________ 3 - 8
How The System Annunciates Supervisories _________________________ 3 - 8
Viewing the List of Supervisories __________________________________ 3 - 8
How to Block Acknowledge a Supervisory ___________________________ 3 - 8
How to Individually Acknowledge a Supervisory _______________________ 3 - 9
Troubles ______________________________________________________ 3 - 9
How The System Annunciates Troubles _____________________________ 3 - 9
Viewing The List of Troubles ______________________________________ 3 - 9
How to Block Acknowledge a Trouble______________________________ 3 - 10
How to Individually Acknowledge a Trouble _________________________ 3 - 10
iii
Table of Contents
Security Conditions_____________________________________________ 3 - 10
How The System Annunciates Security Conditions ___________________ 3 - 10
Viewing the List of Security Conditions _____________________________ 3 - 11
How to Individually Acknowledge a Security Condition _________________ 3 - 11
iv
Table of Contents
Table of Contents
Chapter 4
vi
Table of Contents
Chapter 5
Introduction ___________________________________________________ 5 - 1
System w/AUD ________________________________________________ 5 - 2
System SIL ___________________________________________________ 5 - 2
Loop w/AUD __________________________________________________ 5 - 2
Loop SIL _____________________________________________________ 5 - 2
Zone wAUD ___________________________________________________ 5 - 2
Zone SIL _____________________________________________________ 5 - 2
Cancel _______________________________________________________ 5 - 2
Extend _______________________________________________________ 5 - 2
Chapter 6
vii
Table of Contents
Chapter 7
viii
Table of Contents
Appendix
ix
Table of Contents
+D=FJAH
Description
The CERBERUS PYROTRONICS MXL-IQ
Control Panel is an advanced fire protection
and alarm control panel that provides superior
fire protection and multiplexed alarm reporting.
The MXL-IQ Control Panel can monitor up
to 4 analog loops, each containing up to 60
CERBERUS PYROTRONICS intelligent
devices.
The MXL-IQ Control Panel can control a
wide variety of System outputs, such as:
Conventional Form C relay contacts
Solid State outputs
Supervised outputs to control Alarm
Notification Appliances
Municipal Tie outputs
Leased Line outputs
The MXL-IQ Control Panel can process
logical decisions based on the status of
initiating devices. The System can respond
with customer-specified sequences of
output circuit operation.
The System continuously checks all
software and hardware for proper operation. It continuously checks all System
memory components, control panel electronic hardware, and the System program.
A hardwire watchdog circuit is provided to
ensure that System programs are functioning properly. If a problem develops with the
program or processor, the watchdog circuit
places the System into a trouble condition
and resets it.
INTRODUCTION
The MXL-IQ software was written in a highlevel language for ease of maintenance.
The software incorporates a multitasking
operating system that allows the microprocessor to handle many tasks almost
simultaneously. This enables the MXL-IQ
System to handle communications to all
initiating and output option boards and to
the annunciator. This also enables the
MXL-IQ System to check that everything is
running.
SOFTWARE
1-1
Technical Manuals Online! - http://www.tech-man.com
Description
ALARM
POWER
AUDIBLE
SILENCE
PARTIAL
SYSTEM
DISABLE
SUPERVISORY
DISPLAY
TROUBLE
NEXT
HOLD
SECURITY
CERBERUS PYROTRONICS
MXL-IQ
Exterior View
Interior View
Figure 1
The MXL-IQ Control Panel
1-2
Description
When the MXL-IQ Control Panel receives
power, the System runs a start-up procedure that sets up all initial conditions. The
System then starts the operating system
and the initialization routines for all of the
tasks, most of which concern handling
System modules. When the display task is
finished initializing, it displays the default
time and date at power-up. Initialization of
other modules may take several seconds,
but this takes place in the background and
so does not affect System operation.
Description
72
Local
72
Auxiliary
72
Remote
Station
72
Proprietary
72 Central
Station(a)
UL
1076(b,d)
12A,
13, or 20 01
SMB-2(c)
1*
1*
1*
MPS-6/12
Power Supply
MKB-4
Keyboard/Annunciator Panel
MOM-2
MOM-4
1 or 2**
1(h)
***
***
***
***
***
***
CSM-4
Signal Module
CZM-4
ALD-2I
***
***
***
***
***
****
***
CZM-1B6
***
***
***
***
***
***
-----------
Batteries(e,f)
1(e)
1(e)
1(e)
1(e)
1(d)
1(e)
TSW-2
Tamper Switch
1(d)
PIM-1
PIM-2
PAL-1
Logging Printer
NET-7
Communication Interface
MOI-7
MOD-16
Output Driver
MID-16
Input Module
CRM-4
Relay Module
CMI-30 0
MXL/CXL Interface
X = not required
*
**
NOTES:
a. See pages 7-33 to 7-34 for NFPA 72 Central Station.
b. Refer to the MXL-IQ Wiring Diagram, P/N 575-293638 at the end of the manual.
c. The SMB-2 must be programmed by CSG-M for all System configurations (See CSG-M
Programming Manual, P/N 315-090381).
d. UL 1076 requires a Model TSW-2 tamper switch and a PAL-1 printer.
e. The batteries available are: BP-61, BTX-1, and BTX-2. The BP-61 is a module consisting of four
6V, 15 AH batteries. The BTX-1 batteries are a pair of 12V, 31 AH batteries. The BTX-2 batteries
are a pair of 12V, 55 AH batteries. Actual battery size depends on System configuration.
f. See Appendix C for Battery Calculations.
g. The CMI-300 is not listed for UL 1076 application.
h. Refer to the CSM-4 Installation Instructions (P/N 315-090854) for programming.
TABLE 1
Minimum MXL-IQ Configuration to Meet NFPA 72 Local, Auxiliary, Remote Station, Proprietary, and Central
Station Connections, UL 1076, and NFPA 12A, NFPA 13, and NFPA 2001
Technical Manuals Online! - http://www.tech-man.com
1-3
Description
BATTERY
F2
20A
P14
MPS-6
CB1
NAC1
CB2
NAC2
MPS-12
P2
BATTERY
F3
F4
MOM-4
15 AMP
P3
POWER TO MOM-4
2 AMP MAX.
F1
MPS-6
8 AMP
P8
NAC 2
P13
NAC 1
3
2
1
Watchdog circuitry
Network interface circuitry
DO NOT USE
MNET
TB1
S7
S4
1
D2300CP
PROGRAMMER
P4
PRINTER
P6
1
P5
I
C
1
1
4
I
C
1
1
3
I
C
1
1
2
I
C
1
1
1
I
C
1
1
0
P15
P10
TO ANN-1
GND FAULT
DISCONNECT
12A TO MOM-4
6
4
LOOP 1
7
5
TB2
10
8
4
3
11
9
SMB-2
LOOP 2
CZM-1B6
POWER
TB3
12
4
3
CZM-1B6 POWER
2 AMP
TRBL
4
OFF
1
ON
P17
ALR
24V regulator
2
1
MOM-4
Battery charger
AC transfer relay
CZM-1B6 auxiliary power
Figure 2
SMB-2 Main Board
1-4
Description
Figure 3A
MPS-6 Power Supply
Figure 3B
MPS-12 Power Supply
Figure 4
MKB-4 Keyboard
The MKB-4 has switches for the following functions:
Alarm
Power
Audible Silence
Supervisory
Trouble
Security
In addition the module has display keys (NEXT and HOLD), a numerical keypad, PRINT, HELP, and CLEAR keys, and user-configurable
function keys.
1-5
Description
PAL-1
The PAL-1 Logging Printer provides a
paper record of the activity of the MXL-IQ
System.
Figure 6
PAL-1 Parallel Printer
Figure 7
TSW-2 Tamper Switch
1-6
Description
BP-61 Batteries
The BP-61 is a module consisting of four 6V,
15 AH batteries. The BP-61 is recommended
for the NFPA 72 Local and Proprietary, and
the UL 1076 Systems. Actual battery size
depends on System configuration. See
Appendix C for battery calculations.
Figure 8
BP-61 Batteries
BTX Batteries
The BTX-1 batteries are a pair of 12V, 31
AH batteries. The BTX-2 batteries are a
pair of 12V, 55 AH batteries. Actual battery
size depends on System configuration. See
Appendix C for battery calculations.
Figure 9
BTX Batteries
OPTIONAL
MODULES
1-7
Description
Figure 10
MOM-2 Card Cage
Figure 11
MOM-4 Card Cage
S1
S3
G1
S2
G2
S4
Figure 12
CSM-4 Signal Module
1-8
Description
Figure 13
CMI-300 Interface Module
Figure 14
CRM-4 Relay Module
Figure 15
CZM-4 Conventional Zone Module
1-9
Description
Figure 16
ALD-2I Analog Loop Driver
S1
Figure 17
MOI-7 Voice and Annunciator Driver
Figure 18
MOD-16 Output Driver
1-10
Description
Figure 19
MID-16 Input Driver
Figure 20
NIM-1R Network Interface Module
1-11
Description
The intelligent/analog devices described
below are available for use with the MXL-IQ
Control Panel (SMB-2).
The UL identifiers for compatibility are the
same as the model names specified below.
INTELLIGENT/
ANALOG DEVICES
ID-60P Intelligent/Analog
Photoelectric Detector
The ID-60P is an intelligent/analog photoelectric detector that can be used as an area or
1-12
Description
The ID-60IB is an intelligent/analog ionization detector for use in air duct applications
at altitudes of 0 to 4000 feet. It uses either
the AD-3I housing or the AD-3XRI housing.
The ILI-1BH is an intelligent/analog ionization detector for use in air duct applications
at altitudes of 3000 to 8000 feet. It uses
either the AD-3I housing or the AD-3XRI
housing.
1-13
Description
1-14
Description
The conventional devices described below
are available for use with the MXL-IQ
Control Panel.
The UL identifiers for compatibility are the
same as the model numbers.
CONVENTIONAL
DEVICES
1-15
Description
1-16
+D=FJAH
Installation
Remove all system power
before installation, first
battery and then AC.
NOTE:
INTRODUCTION
WARNING!
Refer to the last page of the
manual for a Warning Note
required by the FCC for all
commercial Class A computing
equipment producing a clock
frequency of 10K Hz or greater.
2-1
Installation
INSTALLATION
INSTRUCTIONS
FOR THE MXL-IQ
CONTROL PANEL
Figure 21
Mounting the MSE-3L Enclosure
Figure 22
TSW-2 Tamper Switch
2-2
Installation
Figure 23
Installing the SMB-2
Figure 24
Installing the MPS-6
2-3
Installation
lockwashers, and finally the nuts over the
two studs. Tighten them securely.
Connect the AC mains to MPS-6/12 as
follows:
Terminal
Black (hot)
White (neutral)
Green (earth ground)
1
2
3
TABLE 2
SWITCH SETTINGS ON THE ANN-1
ADDRESS SETTINGS FOR:
SWITCH
248
249
250
251
S1-SW1
OpenOFF
ClosedON
OpenOFF
ClosedON
S1-SW2
OpenOFF
OpenOFF
ClosedON
ClosedON
S1-SW3
ClosedON
ClosedON
ClosedON
ClosedON
S1-SW4
ClosedON
ClosedON
ClosedON
ClosedON
S1-SW5
Figure 25
Setting S1 on the ANN-1 Board
2-4
Setting Supervision:
Use switch S1-SW5 on the ANN-1 to select
or deselect supervision. If your ANN-1 has
a switch with position 1 indicated on the
left-hand side, ignore the printing on the
switch. SW1 on S1 is at the extreme righthand side of S1, regardless of any other
marking.
Installation
NOTE: When you select non-supervision
for an annunciator, there must also be one
and only one supervised annunciator at
the same address. The supervisory mode
is independent of the network address.
To set for supervision
S1-SW5 = Closed (ON)
To set for non-supervision
S1-SW5 = Open (OFF)
Mounting the MKB-4
(Refer to Figure 26)
1. Install three screws in the first group of
three tapped holes in the right flange.
Leave a 1/8-inch gap between the head
of the screw and the flange. Slide the
slots of the MKB-4 panel hinge under the
head of the screws and tighten.
2. After the MKB-4 is mounted to the
enclosure, connect the cable (P/N 555192238) between P1 on the ANN-1 (on
the back of the MKB-4) and P8 on the
SMB-2.
Figure 26
Installing the MKB-4 Keyboard/Annunciator
MSE-3L
CAUTION:
Be sure the black tracer wire on the edge of
the cable is close to the 1 on position 1 of
connector P1 on the ANN-1 and the 1 on
position 1 of P8 on the SMB-2.
d
Cable supplie
with PIM-1
2)
24
92
(P/N 555-1
1
P1
P1 P2
Back of MKB-
TB1
PIM-1
ANN-1
To P8
o
(Cable n the SMB
-2
suppli
ed wit
h MK
B-4)
PIM-1
1. Install the PIM-1 on the back of the
MKB-4 panel as shown in Figure 27.
Position the PIM-1 so the TB1 is on the
left side of the board.
2. Mount the PIM-1 module on the raised
studs with the hardware provided.
3. Using the cable supplied with the PIM-1,
connect PIM-1, P-1 to ANN-1, P1 (See
Figure 27).
4. Using the cable supplied with the MKB-4,
connect PIM-1, P2 to SMB-2, P8 (See
Figure 27).
Figure 27
Installing a PIM-1 on the Back of an MKB-4
2-5
Installation
PIM-2/PAL-1
The PIM-2 and printer require a standby
power source in the event of a loss of
primary input power (AC mains). Refer to
Figure 28 for the connection of a UPS to
meet this requirement.
TO
80 column color
Supervised PIM-2
Supervised PIM-2
80 column
Supervised PIM-2
132 column (for
PAL-1 and NFPA 72 Proprietary)
NOTES:
1. All wires 14 AWG min,
600V insulation.
2. Wiring to the printer and
PIM-2 must be 14 AWG
min, 600V insulation in
conduit.
3. Use the UPS ICS Lifeline
Model 9300057.
4. Standby Power
requirements: 120 VAC,
0.6A for 24 hours.
5. Standby Power
requirements: 120 VAC,
0.15A for 24 hours.
Figure 28
UPS Wiring Diagram
2-6
MOM-2
MOM-4
3 #10 nut s
4 #10 nut s
3 #10 lockwashers
4 #10 lockwashers
4 #6 x 7/16 screws
2 2-wire cables
4 card guides
2 2-wire cables
2 card guides
Installation
TABLE 4
SERIAL INTERFACE COMMUNICATION PARAMETERS
Dipswitch Position (SW1) -Located at rear of PIM-2
BAUD RATE
960 0
480 0
240 0
120 0
30 0
OFF
ON
OFF
ON
ON
ON
ON
OFF
OFF
ON
OFF
OFF
ON
ON
ON
DATA BITS
8
7
OFF
ON
PARITY
Even
Odd
OFF
ON
PARITY
Disable
Enable
OFF
ON
FLOW CONTROL
Hardware
Software
OFF
ON
PORT TYPE
OFF
NOTE:
When setting Switch S1,
OFF=UP=OPEN
ON=DOWN=CLOSED
ANN-1
MKB-4
PIM-1
SEE INSTL. INSTR.
P/N 315-091462
TB1
120 VAC
60 Hz
CENTRONICS PARALLEL
OUTPUT
Figure 29
PIM-2 to MXL-IQ Wiring Diagram
INPUT
SW1
PWR
XFMR
NOTES:
1. Maximum cable
distance from PIM-1 to
PIM-2 cable is 25 feet.
The two modules must
be in the same room.
2. The maximum distance
from the PIM-2 to the
parallel printer is 6 feet.
The two modules must
be in the same room.
3. PIM-2 power (PWR) is
connected to the 5
VDC, 600mA transformer supplied with the
PIM-2. The transformer
requires 120 VAC, 60
Hz, 0.5A max.
4. For NFPA 72 Local,
Auxiliary, and Remote
Station configurations,
connect the output of
the PIM-2 to any UL
listed EDP Centronics
parallel printer.
5. The parallel printer must
support the EPSON FX
command set.
6. The PIM-2 input and
output connectors are
DB-25 female.
7. Pressing RESET on the
PIM-2 causes the unit
to read the SW1
settings. The status
LED is lit when the unit
is powered. Do not use
the COPY button.
8. For NFPA Proprietary
and UL 1076
configurations, use
parallel printer Model
PAL-1, a UL listed for
fire Centronics parallel
printer.
9. The parallel printer is
supervised for AC, on/
off line, paper out, paper
jam, and connection to
the PIM-2.
10. The PIM-2 is
supervised for power,
connection to the
printer, and connection
to the PIM-1.
11. After loading paper in
the PAL-1 printer, turn
off the power and follow
the steps below:
While pressing the
LOAD PARK button,
turn on the power to
the PAL-1 printer.
Continue pressing
the LOAD PARK
button for 5 seconds.
Release the LOAD
PARK button.
The current setting
will print.
When printing is
completed, the ON
LINE indicator will be
lit. If the ON LINE
indicator is not lit,
press the ON LINE
button.
2-7
Installation
To mount the MOM-2/4 in an MSE-3L
enclosure:
1. Hold the MOM-2/4 so that terminal
blocks TB2 and TB4 are on the left.
2. Place the module vertically on the
mounting studs near the top left of the
enclosure as shown in Figure 23 on
page 2-3.
3. Fasten the MOM-2/4 in position with the
No. 10 flatwashers, lockwashers, and
nuts provided.
To install the card guides
(See Figures 30 and 31):
Install the card guides included in the
package using the #6 x 7/16 screws
provided. (The MOM-4 is shipped with the
MOM-2
Figure 30
Installing the MOM-2 Card Guides
Figure 31
Installing the MOM-4 Card Guides
2-8
Installation
4. Connect the other end of the 2-wire
cable into P5 on the MOM-2/4. The
2-wire cable that attaches P5 on the
MOM-2/4 with P3 on the SMB-2 feeds
24 VDC full-wave unfiltered DC power to
the MOM-2/4. This is the main power
used by the optional modules. The
8-conductor ribbon cable supplies 5 VDC
and communication between the SMB-2
and the MOM-2/4.
TABLE 5
MAXIMUM MODULE LOAD CURRENTS
ALD-2I
CMI-30 0
CRM-4
CSM-4
CZM-4
NIM-1R
The following example assumes that no power is drawn from SMB-2 TB5
(CZM-1B6 power and NAC #1, NAC #2).
Example:
With 1 CZM-4 + 1 CRM-4 + 1 CSM-4, the total load current = 0.72 +
0.075 + 0.034 = 0.83A
The remaining available current = 12.0 (MPS-12) or 6.0 (MPS-6) - 0.83 =
11.83 (MPS-12) or 5.83 (MPS-6).
Mode
2-9
Installation
TABLE 6
WIRING TO THE SMB-2
Screw Terminal
Application
TB5 12-9
TB5 8-5
TB5 4-1
CZM-1B6 Power
Notification Appliance Circuit 2
Notification Appliance Circuit 1
TB4
TB4
6-4
3-1
Trouble Relay
Alarm Relay
TB3
TB2
4-1
4-1
Analog Loop 2
Analog Loop 1
TB1
TB1
TB1
1-2
3
4-5
NOTE: See SMB-2 Connections and Ratings for a more detailed description of the
screw terminals.
Screw Terminal
1-4
9-12
Application
Notification Appliance Circuit 1
Notification Appliance Circuit 2
NOTE: See CSM-4 Connections and Ratings for a more detailed description of the screw
terminals.
CRM-4
1-3
4-6
11-13
14-16
Dry Contact 1
Dry Contact 2
Dry Contact 3
Dry Contact 4
NOTE: See CRM-4 Connections and Ratings for a more detailed description of the screw
terminals.
CZM-4
1-4
5-8
9-12
13-16
Conventional
Conventional
Conventional
Conventional
Zone 1
Zone 2
Zone 3
Zone 4
NOTE: See CZM-4 Connections and Ratings for a more detailed description of the screw
terminals.
CMI-30 0
1-4
NOTE: See CMI-30 0 Connections and Ratings for a more detailed description of the screw
terminals.
NIM-1R
1-2
3-4
12-16
NOTE: See NIM-1R Connections and Ratings for a more detailed description of the screw
terminals.
ALD-2I
1-4
5-8
Initiating Devices
Install all initiating device bases and end-ofline devices where applicable. Install all
initiating devices. Refer to the specific
installation instructions provided with each
device.
Notification Appliances
Install all notification appliances (bells,
strobes, etc.) Refer to the specific installation instructions provided with each device.
Check Resistance Between Wiring Circuits
Start with the wire that goes to TB5-12 on
the SMB-2. Check the resistance between
that wire and all other field wires that will be
connected to the SMB-2. Also, check the
resistance between that wire and all wires
connected to the screw terminals on the
MOM-2/4. Refer to Table 8 for acceptable
resistance readings. If the readings are
good, connect the wire to TB5-12. Repeat
the above procedure for the next wire on
the SMB-2.
When the SMB-2 is complete, continue with
the MOM-2/4 (if it is installed).
Analog Loop 1
Analog Loop 2
NOTE: See ALD-2I Connections and Ratings for a more detailed description of the screw
terminals.
2-10
Installation
1.System Status
When beginning the start-up procedure, the
condition of the system is as follows:
All field wiring is connected to all screw
terminals, except for the analog loops
they should be disconnected. All field
devices are installed.
TABLE 8
FIELD WIRING CHECKOUT
SMB-2 EXTERNAL WIRING AND TROUBLESHOOTING GUIDE
TB-5
Resistance
Between Wires
1.
Chassis to 1-12
2.
Desired Results
>1 Meg
Short in wiring.
11 to 12
<1.5 ohms
3.
9 to 10
<1.5 ohms
4.
7 to 8
<1.5 ohms
5.
5 to 6
<1.5 ohms
6.
3 to 4
<1.5 ohms
7.
1 to 2
<1.5 ohms
8.
9 to 12
>1 Meg
Line shorted.
9.
5 to 8
>1 Meg
Line shorted.
10.
1 to 4
>1 Meg
Line shorted.
11.
9-12 to 1-8
>1 Meg
Line shorted.
12.
5-8 to 1-4
>1 Meg
Line shorted.
8 (+) to 5 (-)
2.2K 10%
14.
4(+) to 1 (-)
2.2K 10%
15.
>1 Meg
>1 Meg
>1 Meg
Line shorted.
12 to 1-8
12 to TB2/3 1-4
12 to all MOM-2/4
16.
>1 Meg
>1 Meg
>1 Meg
Line shorted.
8 to 1-4
8 to TB2/3 1-4
8 to all MOM-2/4
17.
4 to TB2/3 1-4
4 to all MOM-2/4
>1 Meg
>1 Meg
Line shorted.
TB-2
and
TB-3
Resistance
Between Wires
1.
Chassis to all
terminals
2.
CERBERUS PYROTRONICS
MXL
Desired Results
>1 Meg
Short in wiring.
1 to 2
<50 ohms
3.
3 to 4
<50 ohms
4.
1 to 4
<.4F
5.
1 (+) to 4 (-)
>10K ohms
Line shorted.
6.
>1 Meg
Line shorted.
7.
>1 Meg
Line shorted.
8.
>1 Meg
Line shorted.
2-11
Installation
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among
the following (See Appendix J for a
complete list of Trouble Messages):
Device multiple response
Input device not responding
Incorrect device ID
Unspecified device responding
Identify the addresses of the devices
with troubles and eliminate them, reset
the system, and verify that the troubles
have cleared before proceeding.
Modify your test configuration by adding
to it the analog devices that are connected to analog loop 2.
6.ALD-2I Checkout
2-12
Unpack each module just before installation. Inspect the module, looking for such
things as integrated circuits (ICs) not firmly
seated in their sockets, bent IC pins,
connectors not properly installed, dirt, and
packing material on the board.
Install the ALD-2Is one at a time by inserting them in the appropriate card guides on
the MOM-2/4. Make sure that the card is
firmly seated in the card edge connector.
Eliminate all troubles from each module
before installing the next one.
Modify your test configuration by adding to
it any initiating devices that are connected
to the first analog loop on the ALD-2I.
Turn off the power; connect the field wiring
to analog loop 1 on the ALD-2I. Turn on
the power.
Turn off the power and connect the field
wiring to analog loop 1 on the SMB-2.
Turn on the power. Wait for the System
to initialize (approximately 3 minutes).
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among
Installation
Check the trouble list on the MKB for
troubles on the devices that were just
added. The troubles will be from among
the following (See Appendix J for a
complete list of Trouble Messages):
TABLE 9
Panel Number Programming (SW2)
ADDR
87654321
ADDR
000
0 01
0 02
0 03
0 04
0 05
0 06
0 07
0 08
0 09
010
011
012
013
014
015
---
FSI
SOOOOOOX
SOOOOOXO
SOOOOOXX
SOOOOXOO
SOOOOXOX
SOOOOXXO
SOOOOXXX
SOOOXOOO
SOOOXOOX
SOOOXOXO
SOOOXOXX
SOOOXXOO
SOOOXXOX
SOOOXXXO
SOOOXXXX
------------
016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
031
---
87654321
SOOXOOOO
SOOXOOOX
SOOXOOXO
SOOXOOXX
SOOXOXOO
SOOXOXOX
SOOXOXXO
SOOXOXXX
SOOXXOOO
SOOXXOOX
SOOXXOXO
SOOXXOXX
SOOXXXOO
SOOXXXOX
SOOXXXXO
SOOXXXXX
------------
ADDR
87654321
ADDR
87654321
032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047
---
SOXOOOOO
SOXOOOOX
SOXOOOXO
SOXOOOXX
SOXOOXOO
SOXOOXOX
SOXOOXXO
SOXOOXXX
SOXOXOOO
SOXOXOOX
SOXOXOXO
SOXOXOXX
SOXOXXOO
SOXOXXOX
SOXOXXXO
SOXOXXXX
------------
048
049
050
051
052
053
054
055
056
057
058
059
060
061
062
063
064
SOXXOOOO
SOXXOOOX
SOXXOOXO
SOXXOOXX
SOXXOXOO
SOXXOXOX
SOXXOXXO
SOXXOXXX
SOXXXOOO
SOXXXOOX
SOXXXOXO
SOXXXOXX
SOXXXXOO
SOXXXXOX
SOXXXXXO
SOXXXXXX
SXOOOOOO
O = Open or OFF
X = Closed or ON
NOTE:
To open a dipswitch, press down on the side of the dipswitch marked OPEN.
To close a dipswitch, press down on the side of the dipswitch opposite the side marked OPEN.
To open a slide switch, push the slide to the side opposite the side marked ON.
To close a slide switch, push the slide to the side marked ON.
2-13
Installation
2. Set the CMI-300 network address by
using the dipswitch settings on switch
SW1. Use Table 16 at the end of this
chapter to set the network address.
Plug the CMI-300 module in the MOM-2/4
card cage and connect the wiring as shown
in CMI-300 Connections and Ratings.
Eliminate all troubles from each module
prior to installing the next one.
Installing CRM-4 and CZM-4 Modules
Set the address of each module. Refer to
the CSG-M printout of the final configuration for each module address setting. Refer
to the installation instructions for each
module to set the address dipswitch.
Install the optional modules one at a time
by inserting them in the appropriate card
guides on the MOM-2/4. Eliminate all
troubles from each module prior to installing the next one.
Installing the NIM-1R Network Interface
Module
The NIM-1R installs into the MOM-2/4 card
cage where it occupies one full width slot.
The wiring is connected to TB4 of the
MOM-2 or TB3 of the MOM-4.
The NIM-1R has two configuration
dipswitches. Set the dipswitches before
installing the NIM-1R into the MOM-2/4.
Use switch SW1 to set the MXL-IQ network
address. Set this switch according to the
address where the NIM-1R is installed in
the MXL-IQs network map. Refer to the
CSG-M configuration printout for the
address of the module. See Table 16 at the
end of this chapter for settings.
Use switch SW2 to set either the panel
number for networked systems or to select
FSI or AnaLASER operation. Refer to Table
9 for panel settings, Table 10 for FSI
settings, or Table 11 for AnaLASER
settings.
1. When installing the NIM-1R in a
networked system, set the panel number
to agree with the panel number for the
NIM-1R assigned to the MXL-IQ System
in CSG-M.
2. Switch position 8 selects Style 4 or 7
operation for the NIM-1R network.
2-14
87654321
000
OOOOOOOO
O = Open or OFF
87654321
AnaL ASER
XOOOOOOO
O = Open or OF F
X = Closed or ON
Installation
TABLE 12
Modes of Operation
TABLE 13
Setting the Mode of Operation for the CSM-4
(Using S3, S4 and G1, G2)
For Circuit 1
Local (NAC)
Municipal Tie
Leased Li ne
Rel eas i ng Ser v i c e
Illegal (Results in a trouble
on t he CSM - 4)
For Circuit 2
Local (NAC)
Municipal Tie
Leased Li ne
Rel eas i ng Ser v i c e
Illegal (Results in a trouble
on t he CSM - 4)
S3
Position
G1
1
1
2
1
2
No t C u t
Cut
No t C u t
Cut
Cut
S4
Position
G2
1
1
2
1
2
No t C u t
Cut
No t C u t
Cut
Cut
2-15
Installation
d.Degrade Trouble Activation
The degrade trouble bus may ONLY be
used when the circuit is used as a Leased
Line trouble indicating circuit. (See Table
12.) When enabled, this trouble degrade
mode ensures that a trouble will be transmitted to the receiving station even when
the MXL-IQ communication network fails.
TABLE 14
Setting the Degrade Trouble Modes
for the CSM-4 on S2
SW1
G1
For Circuit 1
Leased Line Trouble
No Trouble Activation
On (Closed)
Off (Open)
SW2
G2
For Circuit 2
Leased Line Trouble
No Trouble Activation
On (Closed)
Off (Open)
No t e :
If Circuit 1 or Circuit 2 is not used for Leased Line trouble,
switches SW1 or SW2 must be off (open).
TABLE 15
Setting the Degrade Alarm Modes for the CSM-4 on S2
For Circuit 1
OFF (no degrade activation)
CONTINUOUS (active on degrade alam)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE
For Circuit 2
OFF (no degrade activation)
CONTINUOUS (active on degrade alam)
1 SEC ON, 1 SEC OFF (infinite repeat)
DO NOT USE
SW4
SW3
OFF (Open)
OFF (Open)
ON (Closed)
ON (Closed)
OFF (Open)
ON (Closed)
OFF (Open)
ON (Closed)
SW4
SW3
OFF (Open)
OFF (Open)
ON (Closed)
ON (Closed)
OFF (Open)
ON (Closed)
OFF (Open)
ON (Closed)
NOT E : When circuits are used for leased line supervisory, the alarm degrade modes must
be OFF (Open).
2-16
WARNING!
Prior to activating any initiating device,
take steps to prevent output circuits
from being activated. Failure to do so
may result in building EVAC (bells),
notification of fire department, elevator recall, etc.
Test these operations in accordance
with local codes and follow the direction of the authority having jurisdiction.
Observe all safety precautions.
Installation
Test
1. Observe the display on the MKB-4.
Response
The POWER LED should be on steady.
The TROUBLE LED should be off.
The following message should appear on the alphanumeric
display:
(Time and Date)
(System Custom Message)
SYSTEM
NORMAL
(It may take a few minutes after power-up before the message
System Normal appears.)
2-17
Installation
Test
5. Activate all status devices on the
System.
Response
None of the devices should cause an alarm or trouble condition.
If there is a printer, the System should print the status of reporting devices.
As each device is activated, the custom message recorded on
the printer corresponds to the CSG-M printout for that device.
Check that all appropriate responses are activated.
6. CRM-4 relays:
7. CSM-4 relays:
8. System Functions:
Check all functions that are defined in
the customer specifications.
2-18
Installation
TABLE 16
NETWORK ADDRESS PROGRAMMING
ADDR
000
001
002
003
004
005
006
007
008
009
010
011
012
013
014
015
016
017
018
019
020
021
022
023
024
025
026
027
028
029
030
031
032
033
034
035
036
037
038
039
040
041
042
043
044
045
046
047
048
049
050
051
052
053
054
055
056
057
058
059
060
061
062
063
&%$#"!
ILLEGAL
ILLEGAL
ILLEGAL
OOOOOOXX
OOOOOXOO
OOOOOXOX
OOOOOXXO
OOOOOXXX
OOOOXOOO
OOOOXOOX
OOOOXOXO
OOOOXOXX
OOOOXXOO
OOOOXXOX
OOOOXXXO
OOOOXXXX
OOOXOOOO
OOOXOOOX
OOOXOOXO
OOOXOOXX
OOOXOXOO
OOOXOXOX
OOOXOXXO
OOOXOXXX
OOOXXOOO
OOOXXOOX
OOOXXOXO
OOOXXOXX
OOOXXXOO
OOOXXXOX
OOOXXXXO
OOOXXXXX
OOXOOOOO
OOXOOOOX
OOXOOOXO
OOXOOOXX
OOXOOXOO
OOXOOXOX
OOXOOXXO
OOXOOXXX
OOXOXOOO
OOXOXOOX
OOXOXOXO
OOXOXOXX
OOXOXXOO
OOXOXXOX
OOXOXXXO
OOXOXXXX
OOXXOOOO
OOXXOOOX
OOXXOOXO
OOXXOOXX
OOXXOXOO
OOXXOXOX
OOXXOXXO
OOXXOXXX
OOXXXOOO
OOXXXOOX
OOXXXOXO
OOXXXOXX
OOXXXXOO
OOXXXXOX
OOXXXXXO
OOXXXXXX
&%$#"!
ADDR
OXOOOOOO
064
OXOOOOOX
065
OXOOOOXO
066
OXOOOOXX
067
OXOOOXOO
068
OXOOOXOX
069
OXOOOXXO
070
OXOOOXXX
071
OXOOXOOO
072
OXOOXOOX
073
OXOOXOXO
074
OXOOXOXX
075
OXOOXXOO
076
OXOOXXOX
077
OXOOXXXO
078
OXOOXXXX
079
OXOXOOOO
080
OXOXOOOX
081
OXOXOOXO
082
OXOXOOXX
083
OXOXOXOO
084
OXOXOXOX
085
OXOXOXXO
086
OXOXOXXX
087
OXOXXOOO
088
OXOXXOOX
089
OXOXXOXO
090
OXOXXOXX
091
OXOXXXOO
092
OXOXXXOX
093
OXOXXXXO
094
OXOXXXXX
095
OXXOOOOO
096
OXXOOOOX
097
OXXOOOXO
098
OXXOOOXX
099
OXXOOXOO
100
OXXOOXOX
101
OXXOOXXO
102
OXXOOXXX
103
OXXOXOOO
104
OXXOXOOX
105
OXXOXOXO
106
OXXOXOXX
107
OXXOXXOO
108
OXXOXXOX
109
OXXOXXXO
110
OXXOXXXX
111
OXXXOOOO
112
OXXXOOOX
113
OXXXOOXO
114
OXXXOOXX
115
OXXXOXOO
116
OXXXOXOX
117
OXXXOXXO
118
OXXXOXXX
119
OXXXXOOO
120
OXXXXOOX
121
OXXXXOXO
122
OXXXXOXX
123
OXXXXXOO
124
OXXXXXOX
125
OXXXXXXO
126
OXXXXXXX
127
O = OPEN (or OFF)
&%$#"!
ADDR
XOOOOOOO
128
XOOOOOOX
129
XOOOOOXO
130
XOOOOOXX
131
XOOOOXOO
132
XOOOOXOX
133
XOOOOXXO
134
XOOOOXXX
135
XOOOXOOO
136
XOOOXOOX
137
XOOOXOXO
138
XOOOXOXX
139
XOOOXXOO
140
XOOOXXOX
141
XOOOXXXO
142
XOOOXXXX
143
XOOXOOOO
144
XOOXOOOX
145
XOOXOOXO
146
XOOXOOXX
147
XOOXOXOO
148
XOOXOXOX
149
XOOXOXXO
150
XOOXOXXX
151
XOOXXOOO
152
XOOXXOOX
153
XOOXXOXO
154
XOOXXOXX
155
XOOXXXOO
156
XOOXXXOX
157
XOOXXXXO
158
XOOXXXXX
159
XOXOOOOO
160
XOXOOOOX
161
XOXOOOXO
162
XOXOOOXX
163
XOXOOXOO
164
XOXOOXOX
165
XOXOOXXO
166
XOXOOXXX
167
XOXOXOOO
168
XOXOXOOX
169
XOXOXOXO
170
XOXOXOXX
171
XOXOXXOO
172
XOXOXXOX
173
XOXOXXXO
174
XOXOXXXX
175
XOXXOOOO
176
XOXXOOOX
177
XOXXOOXO
178
XOXXOOXX
179
XOXXOXOO
180
XOXXOXOX
181
XOXXOXXO
182
XOXXOXXX
183
XOXXXOOO
184
XOXXXOOX
185
XOXXXOXO
186
XOXXXOXX
187
XOXXXXOO
188
XOXXXXOX
189
XOXXXXXO
190
XOXXXXXX
191
X = CLOSED (or ON)
ADDR
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
&%$#"!
XXOOOOOO
XXOOOOOX
XXOOOOXO
XXOOOOXX
XXOOOXOO
XXOOOXOX
XXOOOXXO
XXOOOXXX
XXOOXOOO
XXOOXOOX
XXOOXOXO
XXOOXOXX
XXOOXXOO
XXOOXXOX
XXOOXXXO
XXOOXXXX
XXOXOOOO
XXOXOOOX
XXOXOOXO
XXOXOOXX
XXOXOXOO
XXOXOXOX
XXOXOXXO
XXOXOXXX
XXOXXOOO
XXOXXOOX
XXOXXOXO
XXOXXOXX
XXOXXXOO
XXOXXXOX
XXOXXXXO
XXOXXXXX
XXXOOOOO
XXXOOOOX
XXXOOOXO
XXXOOOXX
XXXOOXOO
XXXOOXOX
XXXOOXXO
XXXOOXXX
XXXOXOOO
XXXOXOOX
XXXOXOXO
XXXOXOXX
XXXOXXOO
XXXOXXOX
XXXOXXXO
XXXOXXXX
XXXXOOOO
XXXXOOOX
XXXXOOXO
XXXXOOXX
XXXXOXOO
XXXXOXOX
XXXXOXXO
XXXXOXXX
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
ILLEGAL
2-19
Installation
2-20
+D=FJAH
Operation
This section provides instructions for
operating the MXL-IQ Control Panel.
Please review the introduction to the
MXL-IQ Control Panel at the beginning of
this manual.
INTRODUCTION
Addresses
All modules and devices annunciated on the
MXL-IQ are identified by an address (MMMDDD). Each address is in two partsa
module address (MMM) and a device
address (DDD). The number identifying the
module may be as high as 254, and the
number identifying the device may be as
high as 248. Thus a device on a module
may be identified by any number between
001-001 and 253-250. (See Table 17.)
Fixed Addresses
A module may be assigned to any address
on the System, except for some fixed
addresses that have already been assigned
(See Table 17). The modules communicate
to the MXL-IQ Control Panel through a serial
communications network. The System
continuously supervises all of the modules
for presence and proper operation.
Module
Address
0
1
2
3
*
*
*
248
249
250
251
252
253
254
255
Module
Do not use
Analog loop 1 (SMB-2)
Analog loop 2 (SMB-2)
MKB-4
MKB-4
MKB-4
MKB-4, No. 1
Reserved
SMB-2
Programmer CSG-M
Global (reserved)
Device
Address
(Range)
0 01-060
0 01-060
0 01 to 250
3-1
Operation
System Modules
ALD-2I Analog Loop Module
The ALD-2I takes two adjoining module
addresses. Loop 1 of the ALD-2I is at any
module address and loop 2 at the next
address. The analog loops on the SMB-2
are at module addresses 1 and 2 (See
Table 17, page 3-1) and cannot be moved.
The table below illustrates ALD-2I module
addresses:
ALD at Module
Addresses 3 and 4
Loop 1
Loop 2
Devices
003-001 to 003-060
004-001 to 004-060
ALD at Module
Addresses 15 and 16 Devices
Loop 1
015-001 to 015-060
Loop 2
016-001 to 016-060
CSM-4 Signal Module
The CSM-4 module contains two circuits
and two programmable LEDs.
Their device addresses on the module are
as follows:
Circuit 1
001
Circuit 2
002
LED 1
005
LED 2
006
001
Relay 2
002
Relay 3
003
Relay 4
004
LED 1
005
LED 2
006
3-2
001
Zone 2
002
Zone 3
003
Zone 4
004
LED 1
005
LED 2
006
001
002
004
005
Operation
outputs and MID-16 general purpose
inputs. This gives a maximum of 8 MOD-16
boards and 8 MID-16 boards.
The MOI-7 subaddress map is as follows.
001-016 MOD-16/MID-16
#1
017-032 MOD-16/MID-16
#2
033-048 MOD-16/MID-16
#3
049-064 MOD-16/MID-16
#4
065-080 MOD-16/MID-16
#5
081-096 MOD-16/MID-16
#6
097-112 MOD-16/MID-16
#7
113-128 MOD-16/MID-16
#8
The MOI-7 has two status LEDs:
The TRANSMIT LED indicates that the
MOI-7 is sending information to the SMB-2.
During normal operation this LED flashes
periodically when the SMB-2 requests the
MOI-7s status.
The TROUBLE LED only lights when the
MOI-7 cannot communicate with the
MXL-IQ. This is an indication that the
network connection between the MOI-7 and
SMB-2 is damaged.
MOD-16 (Open Collector Output Module)
The MOD-16 does not occupy a network
address. The MOD-16 is at a subaddress
of the MOI-7 to which it is connected. The
subaddresses of any given MOD-16s are
determined by their position in the string of
MOD-16s.
The output cable from the MOI-7 connects
to the first MOD-16, which has the
subaddress of 001-016 as shown above.
Each additional MOD-16 in the chain has
the next block of 16 addresses.
You may connect a maximum of 8
MOD-16s and MID-16s to an individual
MOI-7 for a total of 128 open collector
outputs and 128 general purpose inputs.
The Display
The display has two lines of 40 characters
each. What is shown on the display depends on the state of the System. The
display contains a back light which turns on
automatically when any key is pressed or
an event is reported. The back light turns
off automatically after 5 minutes of system
inactivity.
The System has several displays. When
the System is Normal, the display shows:
[time/date]
[system message]
SYSTEM
NORMAL
SUPERVISORIES=nnn
SECURITIES=nnn
3-3
Operation
The terms used in the displays described
above are defined as follows:
ACK appears if the event has been
acknowledged; otherwise, the field is
blank.
IN is displayed when a condition occurs.
OUT is displayed when a normal state is
restored.
Q The Display
Figure 32
MKB-4 Keyboard/Annunciator Panel
3-4
S Numeric Keypad
Command Keypad
Left arrow (|) - Press to select the item to
the left of what is flashing on the display
(unless entering a number).
Right arrow (}) - Press to select the item to
the right of what is flashing on the display
(unless entering a number).
Up arrow (~) - Press to go back to the
previous item.
ENTER - Press to select the item on which
the cursor is flashing. When typing in
numbers, press ENTER when finished to
complete the entry.
PRINT - Press to print selected lists and
reports.
FORM FEED - Press to advance the paper
in the printer.
CLEAR - Press to cancel printing begun by
pressing PRINT. The System will print:
This listing prematurely terminated.
V Display Keys
Operation
LEDs
ALARM - This red LED flashes when there
is at least one unacknowledged fire alarm;
it glows steadily when all fire alarms are
acknowledged.
AUDIBLE SILENCE - This red LED flashes
when at least one notification appliance
circuit (NAC) is active; it glows steadily
when all silenceable NACs are silenced.
Under normal conditions, the LED is off.
SUPERVISORY - This yellow LED flashes
when there is at least one unacknowledged
supervisory; it glows steadily when all
supervisories are acknowledged.
TROUBLE - This yellow LED flashes when
there is at least one unacknowledged
trouble; it glows steadily when all troubles
are acknowledged.
SECURITY - This yellow LED flashes when
there is at least one unacknowledged
security condition; it glows steadily when all
security conditions are acknowledged.
POWER - This green LED glows steadily to
indicate that the AC power is on; it flashes
when the System is on battery backup.
PARTIAL SYSTEM DISABLE - This yellow
LED glows steadily when any device is
disabled.
Modes Of Operation
INTRODUCTION
Alarm
Supervisory
Trouble
Security
Normal
3-5
Operation
This order ensures that fire alarms always
take priority over all other conditions. In turn,
supervisories always take priority over
troubles and troubles always take priority over
security conditions. All of the above modes
take priority over Normal mode, which is the
absence of any alarms, supervisories,
troubles, or security conditions.
Alarm
The alphanumeric display shows an alarm
message when a fire alarm is received.
See Alarm.
Supervisory
The alphanumeric display shows a supervisory message when the system receives a
supervisory and no higher priority event is
present. See Supervisories, page 3-8.
Trouble
The alphanumeric display shows a trouble
message when a trouble is present and no
higher priority event is present. See
Troubles, page 3-9.
Security
0
0
0
0
ALARM
SUPERV
TROUBLE
SECURITY
0
0
0
0
ALARM ACK
SUPERV ACK
TROUBLE ACK
SECURITY ACK
Alarm
RESPONDING TO AN ALARM
1. Follow the response plan approved by
the local authority having jurisdiction.
2. When the MXL-IQ is installed, the
ACKnowledge key and Audible Alarm
Silence key (AUD SIL) on the MKB-4
are behind a locked door. The display,
LEDs, and display control keys are
visible and accessible. To acknowledge
an alarm or trouble, or to silence an
audible alarm, first unlock and open the
door.
Message 2:
Normal Mode
3-6
Message 3:
ALARMS=002
SUPERVISORIES=000
TROUBLES=000
SECURITIES=000
Operation
In the messages above, 1-001 represents
the address of the device reporting the
alarm.
NOTE:
3-7
Operation
thus, pressing AUD SIL alternately silences
and unsilences the System.)
If your System has a printer, it prints a
message similar to the following:
AUD SILENCED/UNSIL. 11:01:00 DEC 31, 20XX
AUDIBLES SILENCED
Supervisories
How The System Annunciates
Supervisories
When a supervisory is detected, the
System causes the SUPERVISORY LED
on the MKB-4 to flash, the Systems
internal audible to sound, and the alphanumeric display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two supervisories were received (See the
explanations below).
Message 1:
1-001 [custom message]
002 [device type] IN SUP
Message 2:
1-001 [custom message]
002 [time/date] IN SUP
Message 3:
ALARMS=000
SUPERVISORIES=002
TROUBLES=000
SECURITIES=000
3-8
Operation
Troubles
How The System Annunciates Troubles
When a trouble is detected, the System
causes the TROUBLE LED on the MKB-4
to flash, the Systems internal audible to
sound, and the alphanumeric display on the
MKB-4 to alternate in a sequence among
the three messages shown below. This
example assumes that two troubles were
received (See the explanations below).
Message 2:
1-001 [device type]
002 [time/date] IN TBL
Message 3:
ALARMS=000
SUPERVISORIES=000
TROUBLES=002
SECURITIES=000
Message 1:
1-001 [custom message]
002 [trouble type] IN TBL
3-9
Operation
The TROUBLE LED glows steadily to indicate that all troubles are acknowledged.
If there are no security conditions in the
System, the internal audible goes silent;
if any security conditions still exist, the
internal audible pulses.
Security
How The System Annunciates Security
Conditions
When a security condition is detected, the
System causes the SECURITY LED on the
MKB-4 to flash, the Systems internal
audible to sound, and the alphanumeric
display on the MKB-4 to alternate in a
sequence among the three messages
shown below. This example assumes that
two security conditions were received (See
the explanations below the messages).
Message 1:
1-001 [custom message]
002 [device type] IN SEC
3-10
Message 2:
1-001 [custom message]
002 [time/date] IN SEC
Message 3:
ALARMS=000
TROUBLES=000
SUPERVISORIES=000
SECURITIES=002
Operation
The status information in the third message
reports the total number of alarms, supervisories, troubles, and security conditions.
If your System includes a printer, it prints a
message from two to four lines long similar
to the following:
SECURITY IN 1-1 11:59:59 DEC 31, 20XX
#1 [custom message], [device type]
In the preceding printed message, SECURITY indicates that the type of occurrence
is a security condition; 1-1 is the device
address; #1 is the number of the security
condition in the list of security conditions;
[custom message] is a custom message
entered using the CSG-M Custom Software
Generator (See the CSG-M Programming
Manual, P/N 315-090381); [device type] is
the type of device which reported the
security condition.
Reset Procedures
Hard Reset
Other terms for Hard Reset are Power-up,
Initialization, and Cold Reset.
Applying power to the System performs a
Hard Reset which initializes (starts) the
entire system.
What Is Lost:
Alarms, supervisories, troubles, security
conditions
Any user entries such as time and date
Arm/disarm
Soft Reset
To perform a Soft Reset, press RESET on
the MKB-4 (Refer to Figure 32, page 3-4).
Soft reset does not work until you acknowledge all alarms, supervisories, troubles,
and security conditions and silence the
System.
What Is Lost:
Alarms, supervisories, troubles, security
conditions
Arm/disarm (unless option disabled by
CSG-M)
What Is Not Lost:
Any user entries such as time and date.
Arm/disarm (when enabled by CSG-M)
CSG-M program
Manual sensitivity adjustment
Time-based control
3-11
Operation
If you press RESET before acknowledging
all conditions and silencing the audible
alarms, the display shows a message
similar to the following:
ALARMS NOT ALL ACKNOWLEDGED YET
(or)
SUPERVISORY NOT ALL ACKNOWLEDGED YET
(or)
TROUBLES NOT ALL ACKNOWLEDGED YET
(or)
SECURITY NOT ALL ACKNOWLEDGED YET
(or)
AUDIBLES NOT ALL SILENCED YET
SYSTEM
NORMAL
3-12
Limitations/Restrictions
As in all networked MXL Systems, the
self-restoring trouble option is not
allowed in any MXL.
An MXL still may only contain a maximum of 4 supervised MKBs. This can be
a mix of local and global MKBs.
BLOCK ACK must be enabled in the
CSG-M.
The maximum number of supervised
Global MKBs is 10.
The maximum number of Global Printers
is 2 (not TSP-40s).
SUPERVISORY=0
SECURITY=0
Operation
SUPERVISORY
The 3 event displays are formatted as
follows for a supervisory condition:
NN:MMM-DDD [custom message]
ACK
1 [time/date]
IN SUP
NN:MMM-DDD [custom message]
ACK
1 [device type]
IN SUP
ALARMS=0
TROUBLES=0
SUPERVISORY=1
SECURITY=0
TROUBLE
The 3 event displays are formatted as
follows for a trouble condition:
NN:MMM-DDD [custom message]
ACK
23 [trouble type]
IN TRB
NN:MMM-DDD [custom message]
ACK
23 [time/date]
IN TRB
ALARMS=0
TROUBLES=23
SUPERVISORY=0
SECURITY=0
SECURITY
The 3 event displays are formatted as
follows for a security condition:
AUD SILENCE
This key is NOT a toggle as in a local
mode. If silenceable audibles are active
anywhere in the System, the LED flashes.
SUPERVISORY=0
SECURITY=2
3-13
Operation
nodes as if a local audible unsilence had
been requested. An error code (or success
via a silence event message) allows the
global MKB to keep up to date as to true
System status. If any panel reports an
error, the display status changes since
some audibles have been unsilenced.
RESET
When the global reset key is pressed, each
node is tested. If all nodes meet the
conditions required for reset, the reset
command is sent and executed. Otherwise,
the corresponding error message is displayed.
NEXT
This key operates the same as in the local
mode. However, it moves the user through
the System events globally in the priority
order established earlier.
- Control menu
- Test menu
- Entering your password
- Entering module and device numbers
HOLD
This key operates the same as in the local
mode.
Function Keys
These keys operates the same as in the
local MKB.
Numeric Keypad
These keys operates the same as in the
local MKB.
Numeric Keypad
Use the numeric keypad (keys 0 through 9)
when the System asks for a module
number, device number, password, time,
date, or other information. The display
shows each number as you press the key.
However, when you enter a password, the
System shows asterisks in place of the
digits entered.
3-14
Operation
Acknowledge
Alarm
Supervisory (Supervsry)
Trouble
Security
TABLE 18
COMMAND KEYPAD
Key Purpose
~
ENTER
Status
Alarm
Supervisory (Supervsry)
Trouble
Security
Sensitivity (Senstvty)
Voltages
- Analog
- Threshold
- Sensitivity
Temp
Module type (Mod type)
Device type (Dev type)
Message
Software version
(SW version)
Output States
Device Usages
Node Address
Analaser
- Smoke-lev
- Flow-lev
- Trip-pts
Percent/ft
- Senstvty
- Pre-alarm
- Analog
ASD apps
1
Control
Reset
Sensitivity (Senstvty)
- Hi_3
- Hi_2
- Hi_1
- Norm
- Low_1
- Low_2
- Low_3
Arm/disarm (Arm/dis)
- Arm
- Disarm
Output on/off
- Arm
- Disarm
- Energize
- De-Energize
Loop Arm
Loop Disarm
Netlink Request
Analaser
- Alarm_Trip
- Flow_Trip
Percent/Ft
- Sensitivity
(Senstvty)
- Pre_alarm
Change_Apps
Test
Set time
Ground fault (Gnd_flt)
- Main
Power2
- Main
- Voltage
- Current
Lamp test
- LEDs
- Display
Device LED
MOI_Lamp_Test
X-Network
M-Network
Override
Det_cleaned
Event_log
- Alrm_only
- Trbl_only
- Superv_only
- Security_only
- All_events
- Hist_Ctrl
- Hist_Erase
Pyro_diags
Pre_alarm
ASD_Devices
Summarize
Manual_Activate
2
HELP
FORM
FEED
CLEAR
Walktest
System_wAUD
Loop_wAUD
Zone_wAUD
System_SIL
Loop_SIL
Zone_SIL
Cancel
Extend
3-15
Operation
LIST
CONTROL
LIST
CONTROL
TEST
LIST
CONTROL
TEST
LIST
CONTROL
For help in understanding what the Acknowledge function does, press HELP when the
A in ACKNOWLEDGE is blinking. The
System displays:
TO ACKNOWLEDGE INDIVIDUALLY
LIST
CONTROL
3-16
ACKNOWLEDGE
LIST
CONTROL
TEST
LIST
CONTROL
TEST
LIST
CONTROL
TEST
Operation
TO TEST SYSTEM, LOOP & DEVICE
LIST
CONTROL
TEST
Y
Lowest
Walktest
Test
Control
3-17
Operation
When you type the module number and
the device number, use the Left arrow
key as a backspace key to erase errors.
ACKNOWLEDGE Menu
NOTE:
Acknowledge: Alarm
Use this function to individually acknowledge fire alarms.
Press ENTER when the A in ALARM is
blinking to select ACKNOWLEDGE ALARM:
ACKNOWLEDGE: ALARM SUPERVISRY
If There Is No Alarm:
If there is no current alarm, the System
briefly displays the following message
and then returns you to the Acknowledge
menu:
NO ALARM EXISTS
3-18
Operation
of the unacknowledged alarms, it returns to
the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
Acknowledge: Supervsry
Use this function to individually acknowledge supervisories.
3-19
Operation
The System then displays the next supervisory to acknowledge.
To skip a supervisory, press NEXT. The
System displays the next supervisory in the
series. When the System has displayed all
of the unacknowledged supervisories, the
System returns to the acknowledge menu
on the second line of the display.
(To end a menu session and return to the
Main Menu or to leave the menu at any
time, press the Up arrow key to go backward
one menu each time.)
Acknowledge: Trouble
Use this function to individually acknowledge troubles.
Select ACKNOWLEDGE from the Main
Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
If There Is No Trouble:
If there is no trouble to acknowledge, the
System briefly displays the following
message and returns you to the acknowledge menu:
NO TROUBLE EXISTS
3-20
Operation
In the above message, the time and date
are the time and date that the condition was
acknowledged and 36-050 is the address.
The System then displays the next trouble
to acknowledge.
Acknowledge: Security
Use this function to individually acknowledge security conditions.
Select ACKNOWLEDGE from the Main
Menu by pressing ENTER while the A in
ACKNOWLEDGE is blinking. The System
displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
3-21
Operation
Press ENTER to acknowledge the security
condition shown. The System prints a
message similar to the following message
and removes that security condition from
the unacknowledged security list:
Analaser
Output states
Device usages
Node address
Percent/ft
ASD_apps
LIST Menu
Supervisory (Supervsry)
Trouble
Security
Sensitivity (Senstvty)
Voltages
Temp
Module type (Mod type)
3-22
Operation
Press ENTER to select LIST. The System
displays the first List menu, with the S in
STATUS blinking:
LIST: STATUS ALARM SUPERVSRY
List: Alarm
List: Status
The List Status function shows you the
number of acknowledged and unacknowledged alarms, supervisories, troubles, and
security conditions, in that order.
From the List menu, use the Right or Left
arrow keys to cause the S in STATUS to
blink.
(If you press HELP at this point, the System
explains the List Status function:
2 ALARM ACK
IN ALR
3-23
Operation
When the System has shown all current fire
alarms, it returns to the List menu.
IN SUP
1-001 [custom-message]
002 [time/date]
IN SUP
List: Supervisory
The List Supervisory function shows you all
the supervisories currently in the System in
the order they occurred.
From the List menu, use the Left or Right
arrow key to cause the S in SUPERVSRY
to blink.
(If you press HELP at this point, the System
explains the List Supervisory function:
SHOW INDIVIDUAL SUPERVISORY
In the preceding listing, 32-45 is the address of the device in supervisory, #7 is the
number of the supervisory in the current list,
[custom message] is the custom message
for the device in supervisory, and [device
type] is the type of device in supervisory.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
List: Trouble
If There Is No Supervisory:
If there is no supervisory, the System briefly
displays the following message and then
returns you to the List menu:
3-24
NO SUPERVISORY EXISTS
If There Is a Supervisory:
If there is at least one supervisory, the
System shows the most recent supervisory,
Operation
Press ENTER to select TROUBLE and
display trouble information on the MKB-4
display.
If There Is No Trouble:
If there is no trouble, the System briefly
displays the following message and then
returns to the List menu:
NO TROUBLE EXISTS.
If There Is a Trouble:
If there is at least one trouble, the System
shows the most recent trouble, alternating
between the following two displays:
1-001 [custom message]
002 [trouble type]
IN TBL
IN TBL
IN SEC
IN SEC
3-25
Operation
Listing of all Security at 14:35:20 Oct 09,20XX:
SECURTY IN 29-42 14:34:22 Oct 09,20XX
#7 [custom message], [device type]
1- HI_3
6- ...
11- NORM
3-26
List: Voltages
Use List Voltages to show the voltages of
initiating devices on analog loops.
From the List menu press the Left or Right
arrow key to cause the V in VOLTAGES to
start blinking:
LIST: SECURITY, SENSTVTY, VOLTAGES
Operation
(If you press HELP at this point, the System
displays:
If the device address has no device assigned by CSG-M, the System displays:
No Device Assigned.
3-27
Operation
To print the Sensitivity voltages of all the
smoke detectors for the specified module,
use the arrow keys to cause the S in SENS
to blink and press PRINT. The System
prints those sensitivity voltages in a format
similar to the following (ND = No Device, or
device not a smoke detector):
SENSITIVITY VOLTAGES FOR
1- 2.75 2- 2.62 3- ND
6- ND
7- ND
10- ND
11- ND 12- ND
13- ND
MODULE 1
4- ND 5- ND
8- ND 9- ND
14- ND 15- ND
List: Temp
Use List Temp to display the current
temperature on the LCD display at the
location where the detector is installed.
From the List menu use the left or right
arrow key to cause the T in Temp to start
blinking:
LIST: TEMP
25 DEG C / 77 DEG F
NOTE:
NO MOD ASSIGNED
3-28
Operation
number 255, the highest module number
allowed by the System. It then returns to
the List menu.
Print the Module Type and Network Address of
All Modules
Press PRINT when the M in MOD_ TYPE is
blinking to print a full list of module types
and their Network addresses. The System
prints a list similar to the following:
Listing of Module Types:
1- V7 ALD
2- V7 ALD
3- V4 CZM-4
251- V5 MKB-4
253- V1 MXL-IQ Panel
List: Message
Use List Message to show the CSG-M
assigned custom message of a particular
device.
3-29
Operation
From the List menu use the Left or Right
arrow key to cause the M in MESSAGE to
start blinking:
LIST: MOD TYPE DEV TYPE MESSAGE
3-30
Operation
Press NEXT again to display the version of
CSG-M used to create this System.
3-31
Operation
From the List menu, use the left or right
arrow key to cause the D in DEV_USAGES
to start blinking:
List: Analaser
Use List ANALASER to display operational
characteristics of the AnaLASER devices.
3-32
Flow Lev
Operation
and press ENTER. The system displays the
smoke level for the address specified:
010-004
50%
>>!*
*<<
PRE1
50%
>>!
* <<
NORM
3-33
Operation
The System prompts you to select between
ALARM_TRIP and FLOW_TRIP.
Press ENTER when the A in ALARM_TRIP
is blinking to select LIST TRIP_PTS
ALARM_TRIP.
The System asks you for a module and
device number.
TYPE IN MODULE & DEVICE
P2: 60%
ALM: 90%
010-004
LOW:
20%
HIGH:
80%
List: Percent/ft
3-34
Operation
002-003 SENSTVTY
PRE-ALARM
ANALOG
NORM
NORM
The System prints either the Sensitivity, Prealarm, or Analog of all the devices for the
specified module in a format similar to the
following (NA = ID-60 detector):
%/ft SENSITIVITIES FOR MODULE 2
1-3.00 2-NA
3-1.4 4-3.1 5-1.4
6-1.4 7-ND
8-ND
9-ND
10-ND
11-ND 12-ND 13-ND 14-ND 15-ND
16-ND 17-ND 18-ND 19-ND 20-ND
21-ND 22-ND 23-ND 24-ND 25-ND
26-ND 27-ND 28-ND 29-ND 30-ND
31-ND 32-ND 33-ND 34-ND 35-ND
36-ND 37-ND 38-ND 39-ND 40-ND
41-ND 42-ND 43-ND 44-ND 45-ND
46-ND 47-ND 48-ND 49-ND 50-ND
51-ND 52-ND 53-ND 54-ND 55-ND
56-ND 57-ND 58-ND 59-ND 60-ND
List: ASD_apps
Use List ASD_apps to display operational
characteristics of the ASD devices.
NORM
001-001 SENSTVTY
PRE-ALARM
ANALOG
3-35
Operation
To print the operational characteristics of the ASD
devices assigned to an ALD Loop
Press PRINT when the A in ASD_Apps is
blinking. The System asks you for a module
number:
Arm/Disarm (Arm/dis)
Arm
Disarm
Output_on/off
Arm
Disarm
Type the three-digit module number using
the numeric keypad and press ENTER.
(Enter all leading zeros.) The System prints
a list of all the applications currently assigned to all the ASD devices in that ALD
loop in a format similar to the following (ND
= No Device):
1-NONE
6-ND
11-ND
16-ND
21-ND
26-ND
31-ND
36-ND
41-ND
46-ND
51-ND
56-ND
2-PARK
7-ND
12-ND
17-ND
22-ND
27-ND
32-ND
37-ND
42-ND
47-ND
52-ND
57-ND
3-ND
8-ND
13-ND
18-ND
23-ND
28-ND
33-ND
38-ND
43-ND
48-ND
53-ND
58-ND
4-ND
9-ND
14-ND
19-ND
24-ND
29-ND
34-ND
39-ND
44-ND
49-ND
54-ND
59-ND
5-ND
10-ND
15-ND
20-ND
25-ND
30-ND
35-ND
40-ND
45-ND
50-ND
55-ND
60-ND
Energize
De_energize
Loop arm/disarm
arm
disarm
Net_link_request
Analazer
Alarm-trip
Flow-trip
Percent/ft
Sensitivity(Senstvty)
Pre-alarm
Change-apps
Use the Control menu to perform the
following functions:
Reset the System
Change the sensitivity of a smoke
detector
CONTROL Menu
Reset
Sensitivity (Senstvty)
Hi_3
Hi_2
Hi_1
Norm
Low_1
Low_2
Low_3
3-36
Operation
Control: Sensitivity
Use Control Sensitivity to change the
sensitivity settings of smoke detectors on
analog loops.
From the Control menu, press the Right or
Left arrow key to cause the S in SENSTVTY
to start blinking:
CONTROL: RESET SENSTVTY ARM/DIS
CHANGE SENSITIVITY
Control: Reset
NO DEVICE ASSIGNED
RESET SYSTEM
SYSTEM RESET
3-37
Operation
Type the three-digit module number and
three-digit device number using the numeric keypad and press ENTER. The
System shows the following display:
001-001 Norm Hi 1 Hi 2 Hi 3
Control: Arm/dis
3-38
Operation
Press HELP again to return to the above
menu.)
Press ENTER while the O in OUTPUT is
blinking to select CONTROL_OUTPUT ON/
OFF.
The System asks for a module number and
device number of the device you wish to turn
on or off (energize or de-energize). Type
the three-digit module number and threedigit device number using the numeric
keypad and press ENTER. (Enter all
leading zeros.)
3-39
Operation
Press ENTER while the L in LOOP_DISARM
is blinking to select Control Loop_disarm.
P2: 60%
ALM: 90%
or
Control: Analaser
Use Control ANALASER to display and
change the operational characteristics of
the AnaLASER devices.
3-40
Operation
and press ENTER. The system displays the
current air flow trip point settings for the
address specified:
010-004
LOW: 20%
HIGH: 60%
PHOTO
ION
Pre-alarm adjust
increment
.25% / ft.
.12% / ft.
Pre-alarm range
Pre-alarm default
1.5% / ft.
.75% / ft.
Sensitivity adjust
increment
~.25% / ft.
~.12% / ft.
Sensitivity range
.6 - 1.6% / ft.
Sensitivity default
(Norm)
3.0% / ft.
1.4% / ft.
Control: Percent/ft
Use Control Percent/ft to change sensitivity
and pre-alarm settings in percent/ft obscuration of the ILI and ILP series of detectors.
From the Control menu, press the Left or
Right arrow key to cause the P in Percent/ft
to start blinking. The System asks you for a
module number and device number.
TYPE IN MODULE & DEVICE:
PRE-ALARM
NORM
NORM
3-41
Operation
After you change the pre-alarm setting, the
System prints the information for the
selected device in a format similar to the
following:
CMD CHANGE PRE-ALM 06:38:20 JUN 2, 20XX
002-004 1.4%/FT NORM
NOTE: Because the pre-alarm and sensitivity settings overlap, set the pre-alarm to
at least an increment below the sensitivity
setting.
TEST Menu
X_Network*
Event_log
M_Network*
Override
Det_cleaned
Alrm_only
Trbl_only
Superv_only
Security_only
3-42
[Press ENTER]
Lamp_test
Type the three-digit module number and
three-digit device number using the numeric keypad and press ENTER. (Enter all
leading zeros.)
[Press ENTER]
Operation
All_events
Hist_Ctrl
Hist_Erase
PYRO_Diags
PRE_ALARM
ASD_DEVICES
SUMMARIZE
MANUAL_ACTIVATE
*You can print a report of the information
produced by these functions. See the
discussions for Test Power and Test Network.
3-43
Operation
Press HELP again to return to the above
menu.)
Type the time and date as explained above
and press ENTER. The System prints the
current time and date on the printer and
returns you to the Test menu.
(To end a menu session and return to the
Main Menu or to leave the menu at any time,
press the Up arrow key to go backward one
menu each time.)
Test: Power
Use Test Power to test the Systems
battery voltage, AC voltage, and battery
charge current.
From the Test menu, use the Left or Right
arrow key to cause the P in POWER to
start blinking:
TEST: GND-FLT POWER
DISPLAY POWER
3-44
Operation
Print the AC Voltage, Battery Voltage, and
Charging Current of the Main System
From the Power menu, press PRINT when
the M in MAIN is blinking to select MAIN
POWER. The System will print information
in a format similar to the following:
Power Supply Statistics at 11:23:52
May 01, 20XX:
Battery Voltage = 26.0 volts Charging
CUR = 0.5 AMPS
3-45
Operation
Test: Network
(X-Network, M-Network)
This function is used only by Siemens
Building Technologies, Inc. engineers to
observe network traffic so that they can
evaluate the operation of the module
communication network.
Test: Override
OVERRIDE DISABLED
3-46
Operation
Override the Alarm Confirmation CSG-M
Selection
From the Override menu, press ENTER
when the A in ALR_CONFIRM is blinking to
select Alarm Confirmation.
OVERRIDE: YES NO
Test: Pyro_diags
Use Test Pyro-diags to display a series of
statistics typically used by Siemens Building
Technologies, Inc. to evaluate the operation
of the System. A special password is
required for access to this function.
Test: Pre_alarm
Test: Det_Cleaned
Use Test Det_cleaned to indicate that a
selected detector has been cleaned. This
option is only operational if IEC is enabled in
the CSG-M (See Appendix F).
From the Test menu, use the Left or Right
arrow key to cause the D in DET_CLEANED
to start blinking:
TEST: OVERRIDE DET CLEANED
3-47
Operation
Type the three-digit module number and
the three-digit device number using the
numeric keypad and press ENTER.
The System then sends information to force
this detector into pre-alarm. Once it prealarms, or after a delay, the MXL-IQ then
restores the detector to its proper pre-alarm
setting.
Test: ASD_Devices
Use Test ASD_Devices to disable ASD
parameters and allow timely response to
test gas.
From the Test menu, use the Left or Right
arrow key to cause the A in ASD_Devices
to start blinking.
(If you press HELP at this point, the system
displays:
TEST: ASD DETECTORS
Test: Summarize
Use Test Summarize to ignore known
troubles, and instead view one summarized
trouble for an entire module. This is typically
used during installation and commissioning.
Select Summarize and press ENTER. The
System displays the following menu:
Select Mods
ON
OFF
YES
NO
002
3-48
YES
NO
Operation
One trouble is posted per module
address, regardless of how many
troubles are detected at that module
address.
Test: Manual_Activate
3-49
Operation
3-50
+D=FJAH
Every Year
1. Check that the System operates as
programmed by CSG-M and in
accordance with specifications.
2. Perform any other applicable tests
required by national or local fire codes.
Fuse Replacement
Fuse ratings are as follows:
Fuse
F1
F2
F3
F4
For
Main Power
Battery
CZM-1B6 Power
24V Output
Rating
8A, 3 AG, Normal Blow
15A, 3 AG, Normal Blow
2A, 3 AG, Normal Blow
15A, 3AG, Normal Blow
4-1
TROUBLESHOOTING
Troubleshooting both the external wiring and
the MXL-IQ System wiring follows the steps
in System Function Checkout on page
2-16. If a fault occurs, refer to the Troubleshooting Guide. Locate the type of fault or
any trouble message displayed and follow
the directions in the Corrective Action
column.
TABLE 19
TROUBLESHOOTING GUIDE
This guide assumes that all modules, devices, and wiring are installed.
Note:
Do NOT change modules or wiring unless power is OFF. If available, use your printer during
troubleshooting operations.
SYMPTOM
1. POWER LED is not lit;
display on MKB-4 is
blank.
PROBABLE CAUSE
CORRECTIVE ACTION
No AC Battery
Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuitbreaker
on the MPS-6. Check AC and battery wiring.
If power connections are OK, check the cable between the SMB-2 and MKB-4 for
proper installation.
Adjust contrast control R14 on the ANN-1 board. Remove the MKB-4 and check
cable from ANN-1 to the display. If MKB-4 is defective, replace it.
Correct address setting on the MKB-4 using S1. See the installation instructions for
the MKB-4, page 2-4.
No communication between
SMB-2 and MKB-4.
Defective MKB-4.
Check the cable between the SMB-2 and the MKB-4. Replace the cable if defective.
Replace the MKB-4.
4. Device troubles on
analog loops.
Check loop wiring for shorts, opens, etc. using the Field Wiring Checkout Guide
(page 2-11).
Check that all analog devices are I or IL Series devices, or are CZM-1B6s. See the
list of compatible devices in the appendixes.
Check that all devices are installed.
Check that all devices installed comply with the configuration printout from CSG-M.
Check printed trouble list for ID troubles and correct device IDs as required. Check
devices using the FPI-32 Programmer Tester. Replace devices that fail to respond.
4-2
PROBABLE CAUSE
CORRECTIVE ACTION
Check that the end-of-line resistor is 2.2K, W and is installed according to the
instructions.
Notification appliances
improperly installed.
Check notification appliances for presence of polarizing diodes and correct device
wiring.
Check NACs for proper wiring (shorts, opens, etc.). Use the Field Wiring Checkout
Guide, page 2-11.
6. Output devices
connected to System
relays do not work.
7. CZM-1B6 reports a
trouble.
Incompatible notification
appliance connected.
Check the logic functions using the printout from CSG-M; correct and reload
the System from CSG-M into the SMB-2.
Check that the power source is connected and that power is available.
No power to CZM-1B6.
On the SMB-2, check fuse F3. At the CZM-1B6 check power input; DC power must
be 16-31 VDC. Check polarity.
No power to MOM-2/4.
Check power cable connectors between the SMB-2 (P3) and the MOM-2/4 (P5).
Replace the power cable, if defective.
No communications between
SMB-2 and MOM-2/4.
Check communications cable connections between the SMB-2 (P6) and the
MOM-2/4 (P7). Replace the communications cable, if defective.
Address the modules correctly using the printed configuration from CSG-M (See
CSG-M Programming Manual, P/N 315-090381).
Check wiring for shorts using the Field Wiring Checkout Guide (page 2-11). Replace
fuses.
CSM-4 is improperly
configured.
Check and correct the configuration using the installation instructions for the CSM-4
(P/N 315-090854) and the printed configuration from CSG-M (See CSG-M
Programming Manual, P/N 315-090381).
Incompatible notification
appliances are connected.
Check the logic functions using the printout from CSG-M; correct and reload
the System from CSG-M into the SMB-2 (See CSG-M Programming Manual,
P/N 315-090381).
Defective CSM-4.
Replace CSM-4.
4-3
PROBABLE CAUSE
CORRECTIVE ACTION
Check that the power source to the CRM-4 is connected and that power is available.
Check the logic functions using the printout from CSG-M; correct and reload the
System from CSG-M into the SMB-2 ( See CSG-M Programming Manual, P/N
315-090381. )
Check that the power source and output devices are compatible.
Defective CRM-4.
Replace CRM-4.
Check for wiring errors using the Field Wiring Checkout Guide ( page 2-11) and the
installation instructions for the CZM-4 ( page 2-14) . Check that the end-of-line
capacitor is the proper value and is properly connected. Unused zones must have
end-of-line capacitors installed on MOM-2/4 screw terminals ( 50 MFD, 50 VDC
polarized electrolytic capacitor) . See the installation instructions for the CZM-4 ( page
2-14) .
Defective CZM-4.
Replace the CZM-4.
4-4
+D=FJAH
Walktest Operating
Instructions
INTRODUCTION
The table below shows the selections in the Walktest Menu and
their related help messages.
TABLE 20
Walktest Menu
WALKTEST
HELP MESSAGE
System wAUD
Loop wAUD
LIST
Zone wAUD
CONTROL
Sytem SIL
TEST
Loop SIL
WALKTEST
Zone SIL
Cancel
Extend
5-1
System w/AUD
Cancel
System SIL
Select this option to walktest all CZM-4
zones, CZM-1B6 zones, MID-16 inputs, and
ALD inputs without audible feedback to the
technician. This mode inhibits the
MXL-IQ from annunciating real alarm
conditions.
Extend
Select this option from the menu while in
the Walktest mode to reset the Walktest
timer to the 4 hours remaining mark.
Loop w/AUD
Select this option to walktest input devices
on a specific ALD loop, MOI-7 (MID-16)
group, or on all four zones of a CZM-4 with
audible feedback to the technician. This
mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD
loop or CZM-4 conventional zones in
Walktest.
Loop SIL
Select this option to walktest input devices
on a specific ALD loop, MOI-7 (MID-16)
group, or all four zones of a CZM-4 without
audible feedback to the technician. This
mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD
loop or CZM-4 conventional zones in
Walktest.
Zone wAUD
Select this option to walktest an individual
conventional zone (CZM-1B6 or CZM-4
zone) with audible feedback to the technician. This mode inhibits the MXL-IQ
from annunciating real alarm conditions
for the conventional zone in Walktest.
Zone SIL
Select this option to walktest an individual
conventional zone (CZM-1B6 or CZM-4)
without audible feedback to the technician.
This mode inhibits the MXL-IQ from
annunciating real alarm conditions for
the conventional zone in Walktest.
5-2
Technical Manuals Online! - http://www.tech-man.com
WARNING
A device placed in Walktest is disconnected from its usual functions. Alarm
causing devices in Walktest DO NOT
CAUSE ALARMS until the MXL-IQ is
out of the trouble of Walktest.
Suggested Walktest
Procedure
CODE
ALARM
SUPERVISORY
TROUBLE
SECURITY
STATUS/OTHER
5-3
5-4
Technical Manuals Online! - http://www.tech-man.com
CODE
ALARM
SUPERVISORY
TROUBLE
SECURITY
STATUS/OTHER
5-5
CODE
ALARM
SUPERVISORY
TROUBLE
SECURITY
STATUS/OTHER
5-6
Technical Manuals Online! - http://www.tech-man.com
WARNING:
When performing a partial system
Walktest, DO NOT TEST any devices
that are not in the Walktest as this will
cause an alarm in the system.
+D=FJAH
History Log
The MXL-IQ history system has five major
parts. They are:
1. CSG-M options that control the type and
number of events the MXL-IQ records.
2. Logging lists that record MXL-IQ
hardware events.
3. Event viewing and listing in the MXL-IQ
through the MKB-4 and attached printer.
4. History removal and collation outside the
MXL-IQ.
5. Report generation and analysis on an
external PC.
INTRODUCTION
Screen 1
Options, System Message, Authorizations
6-1
History Log
Small
YES
YES
YES
YES
NO
NO
NO
YES
YES
YES
NO
NO
YES
YES
YES
YES
NO
NO
Screen 2
History Recording Options
Logging Methods
6-2
History Log
the trouble audible sounds
the trouble indicator lights
the message Event Log 90% full shows
on the LCD display
this trouble operates like any other
trouble in the system
Circular Logging
In the circular logging mode, the MXL-IQ
guarantees that the most current 500
Rev. 1.00
2
Rev. 1.00
163840 bytes
114688 bytes
0
0
818 (11) elements (used)
8189 bytes
PROGRAMMING INFO:
Configuration Source Filename -------->
Configuration Size ------------------->
Last Programming Date ---------------->
Configuration Revision Level --------->
Programming Info CHECKSUM ------------>
TEST1
2802 bytes
Wed Mar 22 15:28:16 20XX
215
1085
Screen 3
Display MXL-IQ Panel Info
Technical Manuals Online! - http://www.tech-man.com
6-3
History Log
Logging Item Selection
The system designer can log one or many
event types. The selection is determined by
the system requirements, the amount of
event storage, and the external data base
design. The following list summarizes event
types that can be selected.
* ALARMS
* TROUBLES
* SUPERVISORIES
* SECURITIES
STATUS CHANGES
DEVICE VERIFICATION
OUTPUT ACTIVATIONS
* RESET
* BLOCK ACKNOWLEDGE
* AUDIBLE CONTROL
SET SENSITIVITY
AUTO SET SENSITIVITY
* ARM/DISARM
* ENERGIZE/DE-ENERGIZE
* SET TIME
* PASSWORD
OVERRIDE
*The items marked with an asterisk are set
as default when the logging option is first
selected. At least one event type must be
selected.
6-4
NOTES:
1. The operator should download the
history log for future reference before
erasing the MXL-IQs History, since once
the history is erased it cannot be
undeleted.
2. The history menu options do not alter the
history mode selected in the CSG-M.
History Log
Query Filters
A limited set of event type filters is available
from the MXL-IQ control panel. The mutually exclusive filters are:
ALARMS
The Alrm_Only filter selection displays
or prints incoming alarms, alarm acknowledgments, audible control, and resets.
This set of events gives the operator a
clear picture of the important events that
constitute an alarm condition.
TROUBLES
The Trbl_Only filter displays or prints
troubles and resets.
SUPERVISORIES
The Superv_Only filter displays or prints
supervisories and resets.
SECURITIES
The Security_Only filter displays or prints
securities, device arms, device disarms,
and resets.
ALL
The All_events filter displays or prints all
events.
Query Selection
The MXL-IQ supports one query selection
option when generating listings or printouts
from the MXL-IQ control panel.
HISTORY ON/OFF
The Hist_Ctrl filter turns the History events
on/off.
HISTORY ERASE
The Hist_Erase filter erases the History
events.
6-5
History Log
001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this input.
321
The history log sequence number.
ACK
Optional field indicating that this is an
acknowledgment event. This field is blank
when the initiating event is displayed.
IN
IN
The event direction. The possible event
direction types are:
ON
DEVICE TURNED ON
ALR
The event type. The possible abbreviations
for Device Event types are:
ALR
ALARMS
TBL
TROUBLES
SUP SUPERVISORY
mmm
SAT
STATUS
VFY
VERIFY
BLOCK ACKNOWLEDGE
Device Event
A device event is any alarm, trouble, supervisory, or security input change of state. This
change of state can be into or out of an
active condition. The LCD displays:
001001 1ST FLOOR EAST WING ACK
321 12:24:48 Mar 10,20XX IN ALR
6-6
Where:
SEC SECURITY
Reset Event
A reset event is any cold, warm, manual, or
watchdog reset. The LCD displays:
History Log
253
10100
WATCHDOG RESET
1:22:04 Mar 10,20XX
Where:
253
The module address where the reset
occurred. In this example, the watchdog
reset originated on the SMB-2 at fixed
address 253. The division sign indicates
that this is a history log display.
WATCHDOG RESET
The message describing the type of reset
that occurred. The possible messages for
this field are:
COLD RESET
WARM RESET
MANUAL RESET
WATCHDOG RESET
10100
The history log sequence number.
1:22:04 Mar 10,20XX
The time that the event was logged.
SET TIME
The message describing this display as a
set time event.
10100
The history log sequence number.
2:00:30 Mar 10, 20XX
The date and time in the MXL-IQ before the
SET TIME function was performed.
2:10:45 Mar 10, 20XX
The time when the event was logged. Note
that this is also the new date and time in
the MXL-IQ as a result of this operation.
Where:
Where:
251
The module address where the time
change occurred. In this example, the set
time originated from the MKB-4 at address
251. The division sign indicates that this is
a history log display.
251
The module address where the block
acknowledge occurred. In this example, the
block acknowledge originated from the
MKB-4 at address 251. The division sign
indicates that this is a history log display.
All Alarms Acknowledged
The message that describes this display
as an alarm block acknowledge event. The
text changes to reflect one of the following
four types of block acknowledgments, as
appropriate:
All Alarms Acknowledged
All Troubles Acknowledged
All Supervisories Acknowledged
All Security Acknowledged
4211
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.
6-7
History Log
OVERRIDE
The action that is being applied to the
feature. The selections in this field are:
OVERRIDE
NORMAL
4212
The history log sequence number.
Where:
251
The module address where the audible
silence occurred. In this example, the
audible silence originated on an MKB-4 at
address 251. The division sign indicates
that this is a history log display.
AUDIBLE SILENCED
The message that describes this event.
4212
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.
Override Event
This event occurs when an operator
overrides a verification or confirmation. The
LCD displays:
251
CONFIRMATION OVERRIDE
4212 11:25:14 Mar 11,20XX
Where:
251
The module address where the audible
unsilence occurred. In this example, the
audible unsilence originated on an MKB-4
at address 251. The division sign indicates
that this is a history log display.
AUDIBLE UNSILENCED
The message that describes this event.
4213
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.
Where:
251
The module address where the override
operation occurred. In this example, the
confirmation override originated on an
MKB-4 at address 251. The division sign
indicates that this is a history log display.
CONFIRMATION
The feature that is either being overridden
or returned to normal. This selections in
this field are:
CONFIRMATION
VERIFICATION
6-8
Password Event
This event occurs when an operator enters
a new password at an MKB-4. The LCD
displays:
251
PASSWORD LEVEL : 1
4214 11:25:14 Mar 11,20XX
Where:
251
The module address where the password
event occurred. In this example, the
History Log
password change originated on an MKB-4
at address 251. The division sign indicates
that this is a history log display.
PASSWORD LEVEL : 1
The message that describes this as a
password event and indicates the new
password authorization level that was
entered.
4214
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.
Where:
254
The module addres where the configuration
change occurred. In this example, the
configuration change originated from the
field programmer at address 254. The
division sign indicates that this is a history
log display.
Configuration changed
The message that describes this as a
configuration change event.
10
The old configuration modification sequence number.
11
The new configuration modification sequence number.
Note: These values may not be consecutive. They depend on the number of modifications made to the configuration by the
CSG-M.
4214
The history log sequence number.
11:25:14 Mar 11, 20XX
The time that the event was logged.
NORMAL
Where:
001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this input.
321
The history log sequence number.
12:24:48 Mar 10, 20XX
The time that the event was logged.
NORMAL
The sensitivity value sent to the device. The
selectable values include:
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3
Where:
001001
The module/device address. The division
sign indicates that this is a history log
display.
1ST FLOOR EAST WING
The custom message assigned to this
input.
6-9
History Log
321
The history log sequence number.
2.12
Indicates that this is an IEC (Enviro-Link)
set sensitivity event. The detector sensitivity
has been set to 2.12 volts. (The voltage can
range from 0-5 volts.) This field may
contain the word CLEAN to indicate that
this detector was cleaned and restored to
its base sensitivity.
+
This symbol represents the type of automatic correction that was made. A plus sign
(+) indicates that the sensitivity was increased, a minus sign (-) indicates that the
sensitivity was decreased.
12:24:48 Mar 10, 20XX
The time that the event was logged.
<Listing Date>
Where:
<Listing Conditions>
FN0012
The label of the logical function that generated this sensitivity set. The division sign
indicates that this is a history log display.
<Listing Terminator>
321
The history log sequence number.
12:24:48 Mar 10, 20XX
The time that the event was logged.
NORMAL
The sensitivity value sent to the device.
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3
6-10
Where:
Listing Date
Identifies the report type (in this case the
history log) and the date that the report was
generated.
Listing Conditions
Shows the filter and starting date for this
report.
History Log
History Log Sample Printout
1
Line 1
Line 2
10
20
30
40
50
Listing of History Log at 14:32:22 Apr 04,20XX
This is a FULL list beginning at 09:20:02 Mar 01,20XX:
60
70
80
Line 3
06:00:00
Mar 02,20XX
#1
Line 4
19:00:00
Mar 02,20XX
#2
Line 5
Line 6
TROUBLE IN 1-1
22:10:11
Mar 02,20XX
#3
Response Too Low, TRI-2R Switch Input + Relay
Line 7
22:15:24
Mar 02,20XX
#4
Line 8
22:50:03
Mar 02,20XX
#5
Line 9
06:00:00
Mar 03,20XX
#6
Line 10
19:00:00
Mar 03,20XX
#7
Line 11
Line 12
VERIFY
2-11
21:39:00
Ionization Detector
Mar 03,20XX
#8
Line 13
06:00:00
Mar 04,20XX
#9
Line 14
Line 15
VERIFY
12-23
10:42:20
Ionization Detector
Mar 04,20XX
#10
Line 16
Line 17
ALARM IN 12-23
10:43:12
Ionization Detector
Mar 04,20XX
#11
Line 18
OUTPUT ON FN0103
10:43:13
Mar 04,20XX
#12
Line 19
OUTPUT ON FN0010
10:43:13
Mar 04,20XX
#13
Line 20
10:45:21
Mar 04,20XX
#14
Line 21
SILENCE
10:45:22
Mar 04,20XX
#15
Audibles silenced
Line 22
10:45:25
Mar 04,20XX
#16
Line 23
LOGIN 2
10:50:53
Mar 04,20XX
#17
Line 24
Line 25
DISARM
12-23
10:51:23
Ionization Detector
Mar 04,20XX
#18
Line 26
DISARM
10:52:04
Mar 04,20XX
#19
Line 27
ENERGIZE
10:52:24
Mar 04,20XX
#20
Line 28
19:00:00
Mar 04,20XX
#21
251
251
7-2
7-2
6-11
History Log
Event Type
Identifies the type of history event that is
being reported. The following event types
are arranged in groups. The modifier fields
for each group are different.
Group 1 types:
ACK. ALARM Alarm block acknowledge
SUPERVS
Group 3 types:
SENS
Sensitivity set
ACK. TRBL.
Group 4 types:
LOGIN
Operator login
ACK. SEC.
Group 5 types:
OUTPUT
Output logic event
ACK. SUP.
MAN. RST.
COLD RST.
WARM RST.
WDOG RST.
VERIFY
Alarm verify
ENERGIZE
Energize an output
6-12
SECURTY
ARM
Arm a device
DIS-ARM
Disarm a device
SILENCE
Silence audibles
UNSILENCE
Unsilence audibles
CONFIG.
(CSG-M) Configuration
changed
Modifier
The modifier is an optional field that
extends the meaning of the event type. For
example, ALARM IN, where IN explains the
ALARM type.
Group 1 type:
No modifiers for this group
Group 2 types:
IN
Condition now active
OUT
Condition now inactive
ACK
Condition now acknowledged
Group 3 types:
Hi_3
Hi_2
Hi_1
NORMAL
Low_1
Low_2
Low_3
Group 4 types:
0
Lowest access
1
2
3
Highest access
Group 5 types:
Group 2 types:
ALARM
Alarm causing device
event
ON
OFF
TROUBLE
Event Locator
This field locates the source or destination
History Log
of the event as either a module number,
module-device pair, or function name.
Event Time
The time and date of this event.
Event Sequence #
The sequence number of this event in the
history log list. The maximum value of this
number depends on the type of logging
selected and the length of time since the
last download.
Event Description
The event description is either the custom
message associated with a device, or for
non-devices, it is a descriptive message.
MXL-IQ To CSG-M
Download Formats
ESC=Prev. Menu
Screen 4
Transfer a System to or from an MXL-IQ Panel
6-13
History Log
6-14
+D=FJAH
Alarm
30 VDC peak
66mA max
30 VDC peak
66mA max
(60 devices in alarm)
ALD-2I Wiring
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
100 ohms total.
4. Maximum capacitance:
0.4F between
+ loop and loop.
0.8F between
+ loop and chassis.
0.8F between
loop and chassis.
5. Each detector or group of
detectors, requires a
two-wire circuit of
thermo-plastic fixture
wire enclosed in conduit
or limited energy
shielded cable without
conduit, if permitted by
local building codes.
6. No end of line device
required.
7. Operates in full
conformance with
Style 6.
8. Operates in full
conformance with
Style 4.
9. Either loop may be wired
Class A or B.
10. 60 devices maximum per
loop.
11. T-tapping is NOT
allowed on Class A
loops.
12. Both circuits are
supervised.
7-1
7-2
2-WIRE
18 AWG
CABLE MIN*
TB1
TB2
LLM-1
LLM-1
4
TB2
TB1
MOM-2/4
CXM-1
NOTES
1. All wiring must conform
to local codes and to the
authority having
jurisdiction over the
installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 4.
7-3
TB1
TB1
MOM-2/4
4
LLM-1
TB2
TB2
LLM-1
*USE 2-WIRE
COPPER CABLE,
105 C, 300V, 18 AWG,
SOLID OR STRANDED,
MAX 7 STRANDS.
TB1
NOTES
1. All wiring must
conform to local codes
and to the authority
having jurisdiction
over the installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 7.
TB1
LLM-1
TB2
TB2
LLM-1
CXM-1
CONDITIONED NON-SWITCHED
LEASED TELEPHONE LINE,
600 OHMS IMPEDANCE
TYPICAL CLASS B (STYLE 4)
CONNECTION
R1
560 OHMS,
1/2W, 5%
P/N 140-820366
TB1
LLM-1
4
R2
CXM-1
7-4
LLM-1
TB2
TB1
MOM-2/4
TB2
NOTES
1. All wiring must
conform to local codes
and to the authority
having jurisdiction
over the installation.
2. All circuits are rated
2 volts peak to peak,
1.3mA. All circuits are
supervised.
3. Operates in full
conformance with
Style 4.
MOM-4
(TB-1, TB-2, TB-3, or TB-4)
or
MOM-2
(TB2 or TB4)
NOTES
1. Contact rating: 2A,
30VDC/120 VAC
resistive.
2. Use only with power
limited / Class 2
circuits.
3. Coils are supervised
when de-energized.
4. Contacts are not
supervised.
5. All relay contacts are
shown in normal
(de-energized) state.
7-5
7-6
Supervisory
24V unfiltered,
full wave rectified
12mA max
Alarm
24V unfiltered,
full wave rectified
1.5A max
NOTIFICATION APPLIANCES
(NFPA 72 Local)
All wiring must be in accordance with
Article 760 of NEC and the local building codes.
STYLE Y
(CLASS B)
STYLE Z
(CLASS A)
CIRCUIT 1
CIRCUIT 2
2.2K, 1/2W
NOTIFICATION
APPLIANCES
+
MOM-4 (TB1, TB2, TB3, or TB4)
or
MOM-2 (TB2 or TB4)
2.2K,
1/2W
NO CONNECTION
+
1
NO CONNECTION
10 11 12
13 14 15 16
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
3 ohms total.
4. End of line device:
2.2K, W,
P/N 140-820380.
5. Either circuit may be
wired Class A or B.
6. Both circuits are
supervised.
7. Polarity shown in
supervisory state.
7-7
NOTES
1. Both circuits are not
power limited.
2. The total loop
resistance from the
LLM-1 to the Municipal
Tie, including the 14.5
ohms in the Municipal
Tie, should not exceed
22.5 ohms.
3. Either circuit may be
used.
4. Polarity shown in
supervisory state.
MUNICIPAL TIE
(NFPA 72 Municipal Tie)
All wiring must be in accordance with
Article 760 of NEC and the local building
codes.
Electrical ratings:
Trip Coil
14.5 ohms
Trip Current
220 to 320mA
DC (momentary)
Supervisory
Current
Voltage
12mA DC
24V unfiltered,
full wave rectified
LEASED LINE
(NFPA 72 Remote Station)
All wiring must be in accordance with
Article 760 of NEC and the local building
codes.
Electrical Ratings:
24V unfiltered, full wave rectified
Load must be a compatible polarity
reversal labeled remote station
receiver unit
Rated current
3mA to 9mA, alarm/supervisory
External circuit resistance
2K to 5K ohms
Minimum emergency power
60 hour standby
5 minute alarm
7-8
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. External resistance:
2K-5K ohms.
3. Both circuits are not
supervised.
4. Polarity shown in
supervisory state.
Electrical Ratings:
Solenoids
24 VDC
16.8 watts max
700mA max
Supervisory
12mA max
Alarm
800mA max
Make
Skinner
Model
LV2LBX25, 24V
ASCO
T8210A107, 24V
ASCO
R8210A107, 24V
ASCO
8210A107, 24V
NFPA 12A
Pyro
50 0-982631, 24V
Pyro
50 0-286652, 24V
(Halon)
Pyro
50 0-083377, 24V
Pyro
50 0-086929, 24V
Pyro
ECHS-24 EXP
NFPA 20 01
(FM-20 0)
NOTES
1. Releasing zones are
not power limited.
2. Maximum resistance:
3 ohms total.
3. No end of line device
required.
4. Both circuits are
supervised for opens
only.
5. Polarity show in
supervisory state.
7-9
7-10
NOTES:
1. Use only listed solenoids from the following table:
Application
NFPA 13
(Pre-Action
Deluge)
Make
Skinner
Model
LV2LBX25, 24V
ASCO
T8210A107, 24V
ASCO
R8210A107, 24V
ASCO
8210A107, 24V
NFPA 12A
Pyro
50 0-982631, 24V
Pyro
50 0-286652, 24V
(Halon)
Pyro
50 0-083377, 24V
Pyro
50 0-086929, 24V
Pyro
ECHS-24 EXP
NFPA 20 01
(FM-20 0)
2.
3.
4.
5.
MXL-IQ Releasing Service Wiring Diagram Using MOM-2 (NFPA 12A, 13, and 2001)
VAI-1
24 VAC
+
BATTERY _
1
2
3
4
TRI-60/B6
8 7 6 5 4 3 2 1
N N N
C C C
1 2 3 4
CHASSIS
CHASSIS
120 VAC
INPUT
END OF LINE
RESISTOR
3.6K, 1/4W
P/N 140-820185
CHASSIS
NEUTRAL
HOT
DC OUT
+
_
FAULT
+
_
1
2
3
4
ALARM - SAF
MODEL AS/PS5-BFS-24-UL
UL GUIDE UTRZ
FILE NO. S3584
(Pre-Action
Deluge)
NFPA 12A
(Halon)
2.
3.
4.
5.
6.
Make
Skinner
Model
LV2LBX25, 24V
Maximum #
per MOM-4
5
ASCO
T8210A107, 24V
ASCO
R8210A107, 24V
ASCO
8210A107, 24V
Pyro
50 0-982631, 24V
Pyro
50 0-286652, 24V
Pyro
50 0-083377, 24V
Pyro
50 0-086929, 24V
Pyro
ECHS-24 EXP
SOLENOID
SOLENOID
+
12 VDC LEAD ACID
BTX-1 31 AH
SOLENOID
SOLENOID
TO SMB-1/-2 P6
N N
C C
N N N N
C C C C
N N N N
C C C C
N N
C C
TB1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P1
CSM-4
P2
CSM-4
N
C1
P5
N N
C C
2 1
N N N N
C C C C
N N
C C
TB3
TB6
P7
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P3
CSM-4
P4
DO NOT USE
MOM-4
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
P8
TB2
N N
C C
N N N N
C C C C
N N
C C
N N N N
C C C C
N
C
TB7
2 1
N N
C C
N N N N
C C C C
P10
2
NC
1
NC
TB5
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TB4
DO NOT USE
2.2K, 1/2W
P/N 140-820830
7-11
SOLENOID
MXL -IQ Releasing Service Wiring Using MOM-4 (per NFPA 12A, NFPA 13, and NFPA 2001)
N N N N N N N N N N N N N N N N
C C C C C C C C C C C C C C C C
For FM Approved
Deluge/Pre-Action:
All initiating devices
connected to the
system MUST be
wired Class A.
NFPA 20 01
(FM-20 0)
BATTERY ENCLOSURE
UL LISTED FOR FIRE PROTECTIVE SERVICE
NOTES
1. Use only listed solenoids from the following table:
Application
NFPA 13
_ Power supply
common connection
Connect to:
SMB-1/2 TB5 Terminal 9
7-12
Initiating Devices
Supervisory
18-24.5 VDC
4mA max
Alarm
18-24.5 VDC
45mA max
Zone Resistance
35 ohms total
Max Ripple
500mV
Electrical connections:
There are three basic connections to the
CZM-1B6 as follows:
STYLE B
(CLASS B)
EOL
STYLE D
(CLASS A)
+
POWER
POWER
+
ANALOG LOOP
EARTH
EARTH
ANALOG LOOP
EOL
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
35 ohms total.
4. Each detector or group
of detectors, requires
a two-wire circuit of
thermoplastic fixture
wire enclosed in
conduit or limited
energy shielded cable
without conduit, if
permitted by local
building codes.
5. End of line device:
4.7K, W,
P/N 140-820188.
6. Either circuit may be
wired Class A (Style D)
or Class B (Style B)
7. 15 devices maximum
per circuit.
8. Initiating circuit is
supervised.
7-13
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
100 ohms total.
4. Maximum capacitance:
0.4F between + loop
and loop.
0.8F between + loop
and chassis.
0.8F between loop
and chassis.
5. Each detector or group
of detectors, requires a
two-wire circuit of
thermoplastic fixture
wire enclosed in conduit
or limited energy
shielded cable without
conduit, if permitted by
local building codes.
6. No end of line device
required.
7. Operates in full
conformance with
Style 6.
8. Operates in full
conformance with
Style 4.
9. Either loop may be wired
Class A or B.
10. 60 devices maximum per
loop.
11. T-tapping is NOT
allowed on Class A
loops.
12. Both circuits are
supervised.
7-14
PB-1191 Installation
Analog Loops
The CZM-1B6 communicates with the
MXL-IQ via the MXL-IQs analog loops,
which may be on the SMB-2 or the optional
ALD-2I
MOM-4
TB2
MOM-4
TB1
SMB-2
SMB-2
LOOP
2
TB2
TB3
CLASS A INSTALLATION
See notes 7 and 11.
CZM-1B6
+
+
CZM-1B6
1
7
CLASS B INSTALLATION
See note 8.
CZM-1B6
1
2
CZM-1B6
1
7
CZM-1B6
1
8
CZM-1B6
1 2
CZM-1B6
1
7
CZM-1B6 Power
The CZM-1B6 receives its power from the
CZM-1B6 power output on the SMB-2. This
power is available on TB5 of the SMB-2 on
terminals 9-12. The power may be wired as
SMB-2
TB5
12
11
10
CLASS A INSTALLATION
+
+
See note 6.
CZM-1B6
5
CZM-1B6
5
CZM-1B6
1 2
12
11
10
9
CLASS B INSTALLATION
+
-
4
1
CZM-1B6
5
4
1 2
CZM-1B6
5
CZM-1B6
+
4
CZM-1B6
CZM-1B6
5
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
4 ohms total.
4. No end of line device
required.
5. Circuit is supervised.
6. T-tapping is NOT
allowed on Class A
loops.
7. For loop resistance,
refer to the SMB-2
Installation Instructions,
P/N 315-095097.
7-15
NOTES
1. Intrinsically Safe Output:
Open Circuit Voltage: 28 VDC
Short Circuit Current: 93mA
2. Maximum loop resistance must not exceed 35 ohms.
3. A maximum of ten DI-3IS Ionization Detectors or up to
five S121 or S122 Flame Detectors can be used in
addition to mechanical (non-energy storing) shorting
devices.
4. Maximum safe system voltage is 250 VAC.
5. For mounting and installation of the ISI-1, see the ISI-1
instructions.
6. Only mechanical (non-energy storing) shorting devices
7-16
Supervisory
21.7-22.8 VDC
4mA max
Alarm
21.7-22.8 VDC
180mA per zone max
Max ripple
400mV
STYLE B
(CLASS B)
STYLE D
(CLASS A)
STYLE B
(CLASS B)
ZONE 1
ZONE 2
ZONE 3
ZONE 4
10
11
12
13
14
15
16
50uF
50V *
MOM-4 TERMINALS
TB1 (UPPER SLOT) OR
TB2 (LOWER SLOT) OR
MOM-2 TERMINAL TB2
50uF 50V *
PBA-1191
Linear Beam Detector
- + - + - +
+
50uF, 50V *
DO NOT
USE
CZM-4 Wiring
EOL
4.7K, 1/4W **
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
70 ohms total
(40 ohms if relay bases
are used).
4. Each detector or group
of detectors, requires a
two-wire circuit of
thermoplastic fixture
wire enclosed in
conduit or limited
energy shielded cable
without conduit, if
permitted by local
building codes.
5. Loops may be wired
Class A (Style D) or
Class B (Style B).
6. 30 devices maximum
per loop.
7. All circuits are
supervised.
8. Do not connect more
than one PBA-1191 to
each zone. (Refer to
PBA-1191 instruction,
P/N 315-095424 for
further information.)
9. Do not mix smoke
detectors with the
PBA-1191.
10. The PBA-1191 requires
Rev. 3 or higher of
CZM-4 firmware.
7-17
7-18
5V .5V
140mA
Alarm
5V .5V
180mA
Electrical connections
The MOI-7 is shipped with one cable as
described below.
5V Power
The MOI-7 receives its 5 volt power on
connector P1. This power can be sent to other
modules requiring 5 volts from P2. Pin 1 is the
positive input; pin 2 the return. Use the
supplied cable, P/N 600-291261.
24V Return
TB2 connects to the return side of the
power supply used with the MOD-16s and
MID-16s. There are two positions on the
TB2position 1 connects to the MOD-16/
MID-16 and position 2 to SMB-2, TB5-9, or
to PS-35, terminal 6.
MOD-16 and MID-16 Connection
P4 is the connector for the MOD-16/MID-16
modules. Connect the first MOD-16/MID-16
in the system using a 10-wire cable
P/N 555-190940. Be sure that the locking
tab on the cable engages the rib on P4.
7-19
NETWORK A
TB4
4
N
E 3
T
W
O 2
R
K 1
RCC-1/1F
(PS-5N7)
D D
O O
U
S
E
NOTES:
1. 18 AWG minimum.
2. 80 ohms maximum per
pair.
3. Use twisted pair or
shielded twisted pair.
4. Terminate the shield at
the SMB-2 enclosure
only.
5. Power limited to NFPA
70 per NEC 760.
6. Maximum voltage 8V p-p.
7. Maximum current
150mA.
STYLE 4
N N
O O
T T
+5 VDC IN
P1 P2
SEE
MOI-7
WIRING
U
S
E
4 3 2 1
TB1
TB2
DO NOT USE
P5
MOI-7
7-20
Inputs
The MOI-7 has two inputs. The first input
allows for a local lamp test of all connected
MOD-16 outputs. Screw terminal 1 on TB3
is the lamp test input. To activate the lamp
test, use a normally open switch between
terminals 1 and 2 (common) of TB3.
Each MOD-16 board is lamp tested sequentially. The lamp test sequence stops
automatically after approximately 30
seconds. The second input is for transmission to the MXL-IQ of local trouble. This
input is high going for trouble. Each MOI-7
transmits the state of this input to the
MXL-IQ for annunciation. The MXL-IQ
indicates this trouble as an MOI-7 local
trouble. See the electrical ratings and wiring
diagrams for these two inputs.
MOD-16
MID-16
Electrical ratings:
Electrical ratings:
Supervisory
40V peak
2mA
Alarm
40V peak
850mA
Maximum current
for each output
50mA
Module power
5VDC
2mA max
Input ratings:
Input voltage range
18-31 VDC
Input impedance
8K ohms
Input current
2mA max
MOI-7 Wiring
7-21
NOTES
1. 18 AWG minimum for
LED and 24V lamp
connections.
2. 14 AWG minimum for
supply connections
(TB1-9 and 10, TB2-9
and 10).
3. All wiring must be in
accordance with NEC
760.
4. All wiring must
conform to local codes
and to the authority
having jurisdiction over
the installation.
5. All wiring to MID-16,
MOD-16, or MOI-7
(non-network) modules
is unsupervised. Any
wiring leaving the
enclosure must be
within 20 feet, in rigid
conduit, and must not
leave the room.
6. For additional
information see
MOI-7 Installation
Instructions,
P/N 315-092799.
7. A maximum of 8
MOD-16s can be used
with the MOI-7.
8. Both TB1-9 (or 10) and
TB2-9 (or 10) must be
connected to the
common of the power
supply.
9. When using SR-35,
refer to table on this
page.
TO TB1-9 OF NEXT
MOD-16 OR MID-16
SEE NOTE 8
TB1
1
SW1
1 2 3 4 5 6 7 8
P1
P2
MOD-16
FROM PREVIOUS
MOD-16, MID-16
OR MOI-7 (CABLE
P/N 555-190940)
TO NEXT
MOD-16 OR MID-16
(CABLE P/N 555-190940)
NOTE:
SWITCH S2-8 IS OPEN TO
PROVIDE A 2.7K LIMITING
RESISTOR.
10
SW2
1 2 3 4 5 6 7 8
TB2
1
10
LED
MODULE
TERMINAL
SMB-2
MPS-24
PS-35
TB5-12
TB1-4
TB1-5
TO TB2-9 OF NEXT
MOD-16 OR MID-16
MOD-16 Wiring
Connection To SR-35 Module*
MOD-16
TB1-1
TB1-2
TB1-8
32
SMB-2, TB5-12 or
PS-35, TB1-5
33
SMB-2, TB5-9 or
PS-35, TB1-6
35
7-22
TO TB1-9 OF NEXT
MOD-16 OR MID-16
TB1
1
10
10
P1
DO NOT USE
P3
P4
P5
MID-16
FROM PREVIOUS
MOD-16, MID-16
OR MOI-7 (CABLE
P/N 555-190940)
10
TO NEXT
MOD-16 OR MID-16
(CABLE P/N 555-190940)
10
SWITCH
1
NOTES
1. 18 AWG minimum for
all input connections.
10
P2
TB2
1
10
MODULE
TERMINAL
SMB-2
MPS-24
PS-35
TB5-12
TB1-4
TB1-5
TO TB2-9 OF NEXT
MOD-16 OR MID-16
MID-16 Wiring
7-23
7-24
Max. Current
6*
12 *
7-25
EXAMPLE:
With:
7-26
Max. Current
6*
12 *
7-27
EXAMPLE:
With:
7-28
5 VDC, 160mA
For battery calculations, the
NIM-1R draws 70mA from 24 VDC.
NIM-1R Network
Up to 32 MXL-IQ Systems can be connected in the network with an NIM-1R
installed in each MXL-IQ System. For the
highest level of fault protection, install the
NIM-1R in the enclosure with the SMB-2,
although this is not necessary. When
connecting more than 32 MXL-IQ Systems,
a REP-1/D2300CP repeater is required.
Refer to the REP-1 Installation Instructions,
P/N 315-092686 or the D2300CP Installation Instructions, P/N 315-092882, for the
wiring diagram.
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at MXL-IQ
panel 1.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
8. For Style 4 omit all
Network Pair B
connections.
9. Do not use terminals
12 - 16 if NCC is not
connected.
NETWORK PAIR B *
SUPERVISED (OMIT FOR STYLE 4)
EOLR
120 OHMS, 1/4W
P/N 140-820150
CABLE P/N
555-190506
TO SMB-2
DO NOT USE
TB1, 1-16
DO NOT
USE
P7
CABLE P/N
555-190506
TO SMB-2
SEE
FIGURE 2
10
11
12
13
14
15
16
TB3
NIM-1R
MOM-2/-4
EOLR
120 OHMS, 1/4W
P/N 140-820150
NETWORK PAIR A
SUPERVISED
EOLR
120 OHMS, 1/4W
P/N 140-820150
DO NOT USE
TB1, 1-16
DO NOT
USE
P7
CABLE P/N
555-190506
TO SMB-2
SEE
FIGURE 2
10
11
12
13
14
15
16
TB3
NIM-1R
P3
MOM-2/-4
EOLR
120 OHMS, 1/4W
P/N 140-820150
DO NOT USE
TB1, 1-16
DO NOT
USE
P7
SEE
FIGURE 2
10
11
12
13
14
15
16
TB3
NIM-1R
P3
MOM-2/-4
P3
7-29
The total number of panels in the network must not exceed 64, including the
NCC.
5
DO NOT USE
9
4
DO NOT USE
CONNECT TO COM1
OF NCC/NCC-G
CABLE P/N 555-193085
3
7
2
6
DO NOT USE
1
DO NOT USE
SEE
FIGURE 1
DO NOT USE
1
10
11
12
13
14
15
16
TB1
DO NOT USE
5
10
11
12
13
14
15
16
TB3
NIM-1R
P1
P3
MOM-4
P2
P4
TB2
1
TB4
2
10
11
12
13
14
15
16
7-30
P7
BLACK
SUPERVISED
GREEN
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum cable length
25 feet.
4. Cable must be in rigid
conduit and can not
leave the room.
5. Shielded cable is not
recommended.
6. Maximum voltage:
24V peak to peak.
7. Maximum current:
20mA per circuit.
WHITE
RED
BROWN
DB9 FEMALE
10
11
12
13
14
15
16
DO NOT USE
TERMINALS 12-16
IF NCC IS NOT
CONNECTED
CONNECT ONLY TO
UL EDP OR ETI LISTED
EQUIPMENT
EOLR
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
TRANSMIT
EOLR
120 OHMS, 1/4W
P/N 140-820150
TRANSMIT ENABLE
RECEIVE
EOLR
120 OHMS, 1/4W
P/N 140-820150
10
11
DO NOT USE
12
13
14
15
16
P7
TB1
10
11
12
13
14
15
16
TB3
NIM-1R
P1
P3
MOM-4
P2
P4
TB2
1
TB4
2
10
11
12
13
14
15
16
10
11
12
13
14
15
16
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at NIM-1R
enclosure.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
7-31
AnaLASER Interface
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms per pair.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at NIM-1R
enclosure.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
EOLR
120 OHMS, 1/4W
P/N 140-820150
EOLR
120 OHMS, 1/4W,
P/N 140-820150
SUPERVISED
EOLR
120 OHMS, 1/4W
P/N 140-820150
CABLE P/N
555-190506
TO SMB-2
10
11
12
13
14
15
16
16 15 14 13 12 11 10
TB3
16 15 14 13 12 11 10
2
1
3
2
1
3
2
1
LK1
LK2
SINGLE
ZONE
CON3
AIC-4Z
JUMPER SETTINGS
CON4
TB1
AIC-4Z
P3
DO NOT
USE
TB1
NIM-1R
MOM-4
DO NOT
USE
DO NOT USE
P7
CON2
CON1
LK3
2
1
LK1
3
2
1
LK2
3
2
1
LK3
TO ACC #1, P4
JUMPER SETTINGS
MULTI
ZONE
CON4
CON3
CON2
CON1
TO ACC #28, P4
TO ACC #29, P4
TO ACC #30, P4
TO ACC #31, P4
7-32
18-40 VDC
60mA
Alarm
18-40 VDC
130mA
Electrical connections:
The MXL-IQ Control Panel connects to the
Silent Knight Model 5128/5129 Digital Fire
Communicator using the Alarm, Trouble,
and Supervisory dry contacts on the
MXL-IQ Main Board.
Refer to the Silent Knight 5128/5129 Fire
Slave Communicator Installation Manual,
P/N 150805, provided with Silent Knight
Model 5128/5129 for dialer instructions.
7-33
12
CZM-1B6
POWER
11
10
9
8
7
CHASSIS
6
5
NOT SUPERVISED
SMB-2
3
2
(RED)
(BLK)
(YLW)
(ORN)
(RED)
TROUBLE
5
4
2
1
(GRY)
(VIO)
TO RJ31X
(BLU)
TB4
(GRN)
NOT USED
P2 - CHANNEL INPUTS
NOT USED
(RED)
* UL LISTED
EOL DEVICE
4.7K, 1/2W, 5%
(P/N 140-820388)
NOTES
1. TRI-60R/B6R input
must be programmed
in CSG-M as trouble
causing.
2. TRI-60R/B6R output
must be programmed
in CSG-M to transfer
on loss of AC Mains.
3. All wiring supervised
except as noted.
4. For Remote Station,
provide 60 hour
battery capacity.
SUPERVISED
P4
(BRN)
ALARM
P1 - DC POWER
SUPERVISED
(BRN)
(WHT)
(BLK)
UL LISTED
EOL DEVICE
3.6K, 1/4W
(P/N 140-820185)
6 5
4 3
TRI-B6R
P3 - AC MONITOR
(SEE NOTE 2)
RELAY NC
RELAY C
RELAY NO
SILENT KNIGHT
MODEL NO. 5128/29
TO RJ31X
7-34
TB5
7-35
FIELD WIRING
The screw terminals for the field wiring
circuits are located on the left and right
sides of the SMB-2. They are labeled
TB1 through TB5.
SMB-2
CZM-1B6 power
CZM-1B6
12
11
DO NOT
USE
10
DO NOT
USE
CZM-1B6
T-TAPPING
ALLOWED
9
TB5
CZM-1B6
7-36
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Each detector or group
of detectors requires
the following:
a 2-wire circuit of 18
AWG minimum
thermoplastic fixture
wire enclosed in a
conduit.
or
18 AWG limitedenergy shielded cable
without conduit, if
permitted by local
building codes.
3. Maximum resistance:
100 ohms total.
4. Maximum
capacitance:
0.4F between + loop
and loop.
0.8F between + loop
and chassis.
0.8F between loop
and chassis.
5. Refer to Wiring Guide
for compatible wire
types.
6. Maximum voltage:
Supervisory 30 VDC
peak.
Alarm 30 VDC peak.
7. Maximum current:
Supervisory 66mA
Alarm 66mA
8. No end of line device
required.
9. Operates in full conformance with Style 4.
10. Operates in full conformance with Style 6.
11. Either loop may be
wired Class A or B.
12. 60 devices maximum
per loop.
13. T-tapping is NOT
allowed on Class A
loops.
14. Both circuits are
supervised.
30 VDC peak
66mA max
(60 devices in alarm)
7-37
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
3 ohms total.
4. End of line device:
2.2K, W,
P/N 140-820380.
5. Either circuit may be
wired Class A or B.
6. Both circuits are
supervised.
7. Polarity shown in
supervisory state.
TROUBLE
ALARM
Alarm
24V, unfiltered
full wave rectified
12mA max
24V, unfiltered
full wave rectified
1.5A max
7-38
NOTES
1. Power limited to
NFPA 70 per NEC 760.
2. Minimum wire size:
18 AWG.
3. Maximum resistance:
80 ohms total.
4. Use twisted pair or
shielded twisted pair.
5. Terminate the shield
ONLY at the SMB-2
chassis.
6. Maximum voltage:
8V P-P.
7. Maximum current:
150mA.
SMB-2
SMB-2 Fuses
NOTE: The fuses are located on the upper left and right
corners of the SMB-2 board.
FUSE RATINGS
F1
MPS-6 Input
8A, 3 AG,
Normal Blow
F2
Battery
Reversal
20A, 3 AG,
Normal Blow
F3
CZM-1B6
Power
2A, 3 AG,
Normal Blow
F4
24V Output
15A, 3 AG,
(TB1 - 4 and 5) Normal Blow
7-39
7-40
Appendix A
Compatible Devices
TABLE 2
ANALOG ADDRESSABLE DEVICES
Device
TABLE 1
CONVENTIONAL DEVICES
Detector
Base
Installation
Instructions
CZM-1B6
DB-3S
315-081943-15
CZM-1B6
1,6
DI-B3/B3H
AD-3I/ILP
AD-3RI/3RP
315-093234-4
315-086591-7
CZM-1B6
DT-11
DB-11
315-095429-1
DB-3S + DB-ADPT
CZM-1B6
PBA-1191
PBB-1191
315-095424-2
PE-3/3T
DB-3S
AD-3ILP
AD-3RP
315-090875-6
315-093234-4
315-086591-7
PE-11/PE-11T
DB-11
315-094198-3
DB-3S + DB-ADPT 315-094198-3
AD-11P/11PR
315-095659-2
5,7
FP-11/FPT-11
Compatible With
DI-3/3H
DI-A3/A3H
CZM-1B6
CZM-4
1,6
CZM-4
1,6
CZM-4
1,6
S121/S122 + ISI-1
DB-3S
FP-11 (d) 8, 10
315-095355-2
DB-11, DB-X11RS
DB-3S + DB-ADPT
315-095921-4
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT
315-095659-2
315-095306-3
ID-60I/60IH
ID-60IA/60IAH
DB-3S, DB-X3RS
315-090287-2
CZM-4
ID-60IB/601BH
AD-3I
AD-3XRI
315-093234-4
315-093235-4
CZM-4
ILI-1/1H
ILI-1A/1AH
DB-3S, DB-X3RS
315-095387-1
CZM-4
ILI-1B/1BH
4
AD-3I
AD-3XRI
315-093234-4
315-093235-4
ILP-1/ILPT-1
DB-3S, DB-X3RS
315-092594-5
AD-3ILP
AD-3XRILP
315-093234-4
315-093235-4
DB-3S, DB-X3RS
315-095028-1
AD-3ILP
AD-3XRILP
315-093234-4
315-093235-4
DB-3S
315-093336-1
MSI-10/20
315-090903-3
MSI-10B/20B
315-093329-1
MSI-B6F
315-095302-1
MSI-MB6
315-093613-1
TRI-B6/6D/6R
315-093315-3
TRI-B6M
315-094547-1
TRI-S/D/R
315-096242-2
CZM-1B6
1,6
315-081943-15
CZM-1B6
2,6
315-085258C
CZM-1B6
ICP-B6
ILPT-1(d)
ILP-2
ILP-2(d) 9, 10
1. May use up to 15 detectors of any type.
2. May use up to 10 DI-3IS ionization detectors in addition to mechanical (non-energy storing)
shorting devices.
3. May use up to five S121 or S122 flame detectors in addition to mechanical (non-energy
storing) shorting devices.
4. May use up to 30 detectors of any type, except PB-1191.
5. Do not use with alarm verification.
6. Do not use detector operated accessories with CZM-1B6.
7. Only one PB-1191, and no additional device, can be connected to a CZM-4 initiating zone.
8. The FP-11 is only compatible with MXL-IQ Rev. 6.0 or greater firmware.
9. Must use MXL-IQ Rev 3.0 or greater firmware.
10. When the CSG-M is configured, the DUCT application must be selected when the device is
used in an air duct housing or in a spot duct application.
Installation
Instructions
AD-11P/11XPR
FM Approved Only
DI-3IS + ISI-1
Base
ILT-1
A-1
Appendix A
A-2
Appendix B
Device
Input State
Voltage
Response
CZM-1B6
Normal
Alarm
Trouble
0.50-4.19
4.20-5.0 0
0.0 0-0.47
ID-60T-135
ILT-1
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
MSI-10/20
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
MSI-10B/20B
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
MSI-MB6
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
MSI-B6F
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
MS-MI
Normal
Alarm
Trouble
1.80-3.0 0
3.10-5.0 0
0.0 0-1.79
TRI-60/60D/60R
Not Available
Not Available
TRI-B6/B6D/B6R
Not Available
Not Available
TRI-B6M
Not Available
Not Available
Dust
Supervisory
Trouble
4.25-5.12
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
0.63-4.12
0.63-4.0 0
0.63-3.88
0.63-3.75
0.63-3.63
0.63-3.50
0.63-3.38
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
5.25-10.0 0
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.25-5.12
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
0.63-4.12
0.63-4.0 0
0.63-3.88
0.63-3.75
0.63-3.63
0.63-3.50
0.63-3.38
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
0.0 0-0.50
ID-60P
LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25
0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
ILP-1/ILPT-1
ILPT-1(d)
LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25
0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
ILP-2
(In Default/No
Application
Mode Only)
LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
4.38-10.0 0
4.12-5.0 0
4.0 0-4.88
3.88-4.75
3.75-4.63
3.63-4.50
3.50-4.38
3.88-4.25
0.88-4.0 0
0.88-3.88
0.88-3.75
0.88-3.63
0.88-3.50
0.88-3.38
0.88-3.25
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
0.0 0-0.75
Detector
Sensitivity
Alarm
ID-60I/60IH
ID-60IA/60IAH
ID-60IB/601BH
LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3
5.25-10.0 0
5.12-10.0 0
5.0 0-10.0 0
4.88-10.0 0
4.75-10.0 0
4.63-10.0 0
4.50-10.0 0
ILI-1/1H
ILI-1A/1AH
ILI-1B/1BH
LOW3
LOW2
LOW1
NOR M
HI-1
HI-2
HI-3
Threshold
B-1
Appendix B
B-2
Appendix C
C-1
Appendix C
NOTES
The following modules draw
no 24 VDC current and do
not need to be included in
the battery calculations:
MOM-2
MOM-4
TSW-2
1. Use this column for
battery size calculations.
2. Power is supplied by a
separate UPS.
3. EOL currents included.
C-2
Appendix D
A ct iv e 5 VDC
M odule C ur r ent
SMB -2/MPS -6
6 a mp s
500mA
12 amps
500mA
M odule
D-1
Appendix D
Module
Quantity
SMB-2
(See Note 3)
MKB-4
D-2
Total Active
24 VDC Module
Current
(See Note 1)
Active 5 VDC
Module Current
Total Active
5 VDC Module
Current
(See Note 2)
(See Note 3)
0
15mA
RCC-1/1F
80mA
TSP-40
70mA
CSM-4
34mA + 1.5A
max per circuit
30mA
CRM-4
75mA
30mA
CZM-4
720mA
4 zones in
alarm
24mA
ALD-2I
105mA + 1.1mA
per device
CMI-30 0
96mA
NIM-1R
160mA
MOI-7
Active 24 VDC
Module Current
120mA
175mA
MOD-16
850mA max
2mA
MID-16
32mA max
2mA
50mA
ICP-B6
1.5A
PIM-1
25mA
D230 0CP
20 0mA
CZM-1B6
Silent Knight
130mA
TOTAL
0
TOTAL
Appendix E
Alarm Verification
The Alarm Verification feature provides the
MXL-IQ with a way to verify an alarm from
area type addressable smoke detectors
connected to the analog loops or from
standard smoke detectors connected to
the CZM-4 module. This feature reduces
the incidence of false alarms.
When a detector is supervised with Alarm
Verification, it is turned off immediately
after the System first detects alarm
causing data from it.
The length of time that the detector is
verified is fixed at 50 seconds. In MXL-IQ,
an addressable detector is turned off by
the System ignoring its data; a standard
detector is turned off by the power actually
being removed from the detector. After the
A____________________B________________________C
Time
A
AB
BC
Time at which the System initially recognizes an alarm from a smoke detector.
The 50 seconds during which the System ignores the alarm data
The 60 seconds during which the System alarms if the device is returning alarm data
CAUTION
Use only detectors
which are subjected to air
velocities of less than 100
feet per minute with Alarm
Verification. Under dynamic
air velocity conditions,
smoke may be swept from a
smoke detector after the
initial alarm. That may cause
a long delay before
verification. Do not select
Alarm Verification for such
applications.
E-1
Appendix E
With Device Confirmation, the BC
verification time known as System Justified Alarm time is also adjustable. It is the
same time used by both ionization and
photo detectors. If a device is individually
selected for alarm verification, the alarm
verification feature takes priority over the
device confirmation option. For adjustment
ranges, refer to the CSG-M Programming
Manual, P/N 315-090381.
E-2
Appendix F
Envirolink
SENSITIVITY
VOLTAGE
Analog Voltage
Alarm
Threshold Voltage
0 Volts
F-1
Appendix F
If a detector with Envirolink (IEC) reports an
alarm condition before the detectors alarm
threshold is adjusted, the alarm delays until
the alarm threshold is adjusted. If the device
continues to report an alarm condition once
its alarm threshold is adjusted, the alarm
reports.
If the CSG-M and the device ID do not agree,
the IEC for that device does not activate
until the trouble condition is removed from
the system and the panel is reset.
MXL-IQ Power On
When a system is brought on-line, or when
there is a complete loss of power in an
MXL-IQ enclosure containing detectors with
IEC applied, the operator must perform a
reset sequence for the IEC devices in that
MXL-IQ and also reset the MXL-IQ.
When an MXL-IQ is powered the first time,
and there is no data for IEC devices, MXL-IQ
leaves these devices at the default alarm
threshold. However, if former IEC data is
available, MXL-IQ adjusts the device alarm
threshold accordingly.
Detector Cleaned
IEC must be enabled in the CSG-M in order
to have access to the Det_cleaned option
through the MXL-IQ Annunciator Panel.
At the Test menu, use the Left or Right
arrow key to cause the D in Det_cleaned to
start blinking:
OR
IEC LIMIT REACHED. SERVICE REQ
F-2
Appendix F
The System asks you to type the module
and device numbers.
Type the three-digit module number
and the three-digit device number
(mmm/ddd), including all leading
zeroes.
Press ENTER.
After entering the module-device, MXL-IQ
checks whether the device is subject to
IEC. If the device is not subject to IEC, or if
IEC is not enabled for the system, an error
messages displays:
F-3
Appendix F
F-4
Appendix G
Latching/Non-Latching Troubles
This feature is not available for Networked
MXL-IQ Systems.
G-1
Appendix G
G-2
Appendix H
CAUTION:
When setting the device address using
the FPI-32, select the normally closed
alarm causing input.
1
2
3
4
SWITCH
NC
TRI-60R / TRI-B6R
+ ANALOG
- LOOP
OUT
+ ANALOG
- LOOP IN
1
2
3
EOL *
3.6K
1/4W
+ ANALOG
- LOOP
OUT
+ ANALOG
- LOOP IN
SWITCH
NC
EOL *
3.6K
1/4W
TRI-60D / TRI-B6D
1
2
3
4
NOT USED
GND
GND
+ ANALOG
- LOOP
OUT
+ ANALOG
- LOOP IN
SWITCH A
SWITCH B
NC
EOL *
3.6K
1/4W
NC
EOL *
3.6K
1/4W
NOT USED
GND
H-1
Appendix H
H-2
Appendix I
CSG-M Application
NONE
Disable
OFFC
Office (Retail)
WHSE
Warehouse (Light
Manufacturing)
LOBY
Lobby
COMP
Computer Room
DORM
Dormitory
HLTH
Healthcare
PARK
Parking Garage
UTIL
Utility (Transformer)
Room
PREC
Precious Storage
(Sensitive
Environment)
HOST
Hostile Environment
DUCT
Description
No Applications (Standard Photoelectric
Detector)
Reasonably clean, climate controlled
atmosphere
Airborne dust, equipment, fork truck and
light to medium dock area exhaust fumes
I-1
Appendix I
I-2
Appendix J
Trouble Message
AC Fail or Brownout
Carrier Lost
J-1
Appendix J
J-2
Trouble Message
Communications trouble between the CMI300 and the CXL. Data is attempting to
transmit.
Device is defective.
Detector Trouble
Appendix J
Trouble Message
Incorrect Device ID
Input Disarmed
J-3
Appendix J
J-4
Trouble Message
Defective device.
Appendix J
Trouble Message
Node Disconnected
J-5
Appendix J
J-6
Trouble Message
Output Disarmed
PRE 1 Level
PRE 2 Level
Pre-alarm
Relay Disarmed
The relay at this address has been disarmed from the Control menu.
Appendix J
Trouble Message
Tamper Switch
Troubles Summarized
J-7
Appendix J
Trouble Message
J-8
WALKTEST Activated
Warm Reset
Appendix K
Enclosure
Installation
Instructions
LLM-1
315-093530-2
MSE-3
315-093831-1
MSE-3L
315-095445-1
K-1
Appendix K
K-2
Appendix L
For use in Canada only with MXL-IQ software version 1.0 and higher
NO
YES
NO
NO
NO
NO
NO
L-1
Appendix L
Select NO for the old system flag
driven version of Two Stage
Select YES for the new control function
version of Two Stage
NOTE: When recompiling an older implementation of Two Stage Alarm under
CSG-M 6.07 or higher, make certain that
the New Two Stage Configuration flag is
set to NO before compiling and uploading
to the MXL-IQ.
Stage 1
Input
Stage 2
Input
Coded Audibles in
Ouput List
False
False
Silent
True
False
False
True
True
Example:
Stage 1 audible
Stage 2 audible
L-2
True
Appendix L
ESC=Prev. Menu
5
60/MIN
AUDIBLES ON
1.0
2.0
4.0
3
YES
ESC=Prev. Menu
L-3
Appendix L
When a coded audible appears on the
output list of more than one Two Stage
control function and there is a conflict
(that is, some functions indicate Stage
1 and some functions indicate Stage
2), then Stage 2 has priority over
Stage 1. As a result, the coded
audibles in question will output Stage 2
(either 120 SPM, steady, or temporal,
as selected).
NOTE: When zone coding is selected as the
Stage 1 audible output, Stage 2 always has
priority over the Stage 1 coding. Once the
coded circuit is driven into Stage 2 by logic,
all zone codes will stop for that circuit no
matter what the minimum rounds are.
Keyswitch Type 2
1. If a Type 2 keyswitch is activated when
no alarms are present in the system, it
will result in a trouble condition at the
MXL-IQ.
2. If an alarm is detected while this trouble
condition is present on the trouble
queue, the active Type 2 keyswitch will
be added to the system as an alarm
event (added to alarm queue).
True
False
Inhibited
Not Inhibited
False
True
Inhibited
Not Inhibited
L-4
Keyswitch Devices
Appendix L
Basic Two Stage System
The figure on page L-6 demonstrates a
basic Two Stage system design. Its
operation is summarized below:
RESET_INH
Any Alarm
Trigger (ALL)
30 Sec
True
SS_INH
Any Alarm
Run
Trigger (ALL)
Reset Inhibit
Run
Enable
True
Two Stage
Audible Silence
Enable
Start Timer
Start Timer
Cancel
Cancel
False
Panel Reset
Any_keyswch
Any alarm
Keyswch
List of
Keyswitch
Inputs
OR
(ANY)
AND
(ALL)
L-5
Appendix L
Any Alarm
True
Stg1_timer
Run
Trigger (ALL)
Start Timer
Cancel
Enable
Panel Reset
Set
Stg2_enb
Any Alarm
Reset
Clear
Stg2_can
OR
(ANY)
False
Panel Reset
Panel Reset
Audible Silence
Any Alarm
any_keyswch
Stg1_to
AND
(ALL)
Stg2_timer
Run
Trigger (ANY)
Enable
Start Timer
Cancel
Panel Reset
Audible
Silence
AND
(ALL)
Stg2_sil
OR
(ANY)
Stg2_ran
Set
Reset
Clear
Stg2_sil
AND
(ALL)
Stg_ctl
Stg1
Stg2
Audible
Silence
L-6
xxxx
Stg1_ssz1
To input list of
stg1_ssz1,
stg1_ssz2,
stg1_ssz3
Stg1_timer
Any Alarm
Trigger (ALL)
Run
Enable
Floor 1
alarm pts
Stg1_to
OR
(ANY)
AND
(ALL)
stg2_flr1
AND
(ALL)
Any Alarm
flr1_2stg
Stg1
Audible
Silence
stg1_flr1
stg1_timer
Stg2
Stg2_sils
Floor 1
alarm pts
Start Timer
AND
(ALL)
First Floor
Two Stage
Audible List
Cancel
Stg1_ssz2
Panel Reset
any_keyswch
Stg2_enb
Any Alarm
False
Set
stg1_timer
Floor 2
alarm pts
Stg2_timer
Audible
Silence
Trigger (ANY)
Reset
stg1_flr2
AND
(ALL)
Clear
Stg2_sils
Enable
Panel Reset
Audible Silence
Floor 2
alarm pts
Start Timer
Stg2_can
OR
(ANY)
flr2_2stg
Stg1
Q
stg2_flr2
Run
Panel Reset
OR
(ANY)
Stg2
Second Floor
Two Stage
Audible List
AND
(ALL)
Cancel
Stg1_ssz3
Stg2_sil
stg1_timer
Floor 3
alarm pts
Stg2_ran
Set
L-7
Panel Reset
Clear
Q
Audible
Silence
Audible
Silence
Stg2_sils
OR
(ANY)
stg1_flr3
OR
(ANY)
flr3_2stg
Stg1
Q
stg2_flr3
Use to
indicate
Stage Two
is active
Stg2_sils
Floor 3
alarm pts
Stg2
AND
(ALL)
Third Floor
Two Stage
Audible List
Appendix L
Reset
AND
(ALL)
AND
(ALL)
Appendix L
L-8
Appendix M
CSG-M Software
Pre-alarm
Pre-alarm must be selected to either
annunciate a detectors pre-alarm or use
the detector in a Criteria Selection function.
Pre-alarm can be enabled at each device
when it is installed as a Yes/No (Y/N) option.
The CSG-M provides the following system
options for pre-alarm:
annunciate (Y/N)
automatic adjust (Y/N)
annunciation type trouble
learning period (1 - 30 days)
activate detector LED (Y/N)
M-1
Appendix M
MXL-IQ Pre-alarm
Software
Pre-alarm Learning and Setting
The MXL-IQ automatic pre-alarm learning
feature adjusts smoke detector pre-alarm
levels (during the time period selected in
the CSG-M) until they stabilize. Depending
upon pre-alarm activity, the system starts
with the most sensitive pre-alarm level and
gradually adjusts (de-sensitizes) the
MXL-IQ until pre-alarms no longer occur.
The level reached by each smoke detector
at the end of the learning period is the
learned pre-alarm level. No pre-alarms
annunciate or feed output logic during this
learning period.
The learned pre-alarm level is stored in
flash memory so that on a panel power-on,
watchdog, or nickel reset, the pre-alarm
readings still exist. When a new or modified CSG-M is loaded into flash memory,
the MXL-IQ will NOT assume pre-alarm
existed before and will re-start the
learning mode.
The flash memory used for storing prealarm detector readings shares the intelligent environmental control (IEC) flash
memory area. This requires that a boot
block flash device be used if pre-alarm is
enabled. The flash segment size shared by
M-2
Appendix M
PHOTO
ION
Pre-alarm adjust
increment
.25% / ft.
.12% / ft.
Pre-alarm range
1.5% / ft.
.75% / ft.
Sensitivity adjust
increment
~.25% / ft.
~.12% / ft.
Sensitivity range
.6 - 1.6% / ft.
3.0% / ft.
1.4% / ft.
Pre-alarm
default
Sensitivity
default (Norm)
M-3
Appendix M
M-4
Appendix N
Part Number
SMB-1/-2 to MKB-4
555-192238
60 0-290505
555-190506
SMB-1/-2 to Battery
555-190968
60 0-190704
Fuses
20 Amp MDA Normal Blow
105-292017
105-224090
105-217858
105-210758
N-1
Appendix N
N-2
Appendix O
O-1
Appendix O
the timer if the delay time is other than zero.
No AC failure trouble is reported at this time.
At the end of this delay time, if the AC still
fails, the MXL-IQ posts the AC Failure
trouble; otherwise, it goes back to the
original state.
O-2
Index
A
Acknowledge menu. See Menu: Acknowledge
addresses, 3 - 1
fixed addresses, 3 - 1
CRM-4
connections and ratings, 7 - 5
description, 1 - 9
installation, 2 - 14
module address, 3 - 2
CSM-4
connections and ratings
NFPA 12A, NFPA 1 - 1 and NFPA 2001, 7 - 9
alarm verification, E - 1 to E - 2
NFPA 72 Local, 7 - 7
ALD-2I
connections and ratings, 7 - 1
description, 1 - 10
installation, 2 - 12
module address, 3 - 2
analog loop, 1 - 1
analog voltages. See device analog voltages
initiating devices, 7 - 13
B
battery calculations, C - 1
BP-61 batteries
description, 1 - 7
BTX batteries
description, 1 - 7
power, 7 - 15
description, 1 - 14
CZM-4
connections and ratings, 7 - 17
description, 1 - 9
installation, 2 - 14
module address, 3 - 2
C
Canadian two stage alarm, L - 1 to L - 7
CCU pager interface. See new features - rev.6.0 and
higher
CMI-300
connections and ratings, 7 - 3
description, 1 - 9
installation, 2 - 13
compatible devices, A - 1
Index - 1
Index
IEC. See Envirolink
E
Envirolink, F - 1 to F - 3
F
FP Series of detectors
description, 1 - 12
description, 1 - 13
ILT
description, 1 - 13
History Log
display, 6 - 6 to 6 - 10
audible silenced event, 6 - 8
audible unsilenced event, 6 - 8
auto sensitivity set event, 6 - 9
block acknowledge event, 6 - 7
configuration changed event, 6 - 9
event, 6 - 6
formats, 6 - 6
manual sensitivity set event, 6 - 9
override event, 6 - 8
password event, 6 - 8
reset event, 6 - 6
set time event, 6 - 7
download formats, 6 - 13
sequence, 6 - 14
local log query, 6 - 5
logging methods, 6 - 2 to 6 - 4
options, 6 - 1
enable, disable and erase, 6 - 4
overview, 6 - 1
print formats, 6 - 10 to 6 - 13
latching/non-latching troubles, G - 1
LIM-1
description, 1 - 14
M
Menu. See MKB-4: operation
Acknowledge, 3 - 18
Alarm, 3 - 18 to 3 - 19
Security, 3 - 21 to 3 - 22
Supervisory, 3 - 19 to 3 - 20
Trouble, 3 - 20 to 3 - 21
Control, 3 - 36 to 3 - 42
Analaser, 3 - 40
Arm/dis, 3 - 38
Change Apps, 3 - 42
Loop Arm, 3 - 39
Loop Disarm, 3 - 39 to 3 - 40
Net Link Request, 3 - 40
Output on/off, 3 - 38 to 3 - 39
Percent/ft, 3 - 41 to 3 - 42
Reset, 3 - 37
Sensitivity, 3 - 37
List, 3 - 22 to 3 - 36
I
ICP / ICP-B6
description, 1 - 12
ID Series of detectors
description, 1 - 12 to 1 - 13
Index - 2
Alarm, 3 - 23 to 3 - 24
Analaser, 3 - 32 to 3 - 34
ASD_apps, 3 - 35 to 3 - 36
Device Type, 3 - 29
Device Usages, 3 - 31 to 3 - 32
Index
Message, 3 - 29 to 3 - 30
global operation, 3 - 12 to 3 - 14
Module, 3 - 28 to 3 - 29
display format, 3 - 12
Node Address, 3 - 32
keypad, 3 - 13 to 3 - 14
Output States, 3 - 31
Percent/ft, 3 - 34 to 3 - 35
installation, 2 - 4
Security, 3 - 25 to 3 - 26
local operation, 3 - 3
Sensitivity, 3 - 26
alarm, 3 - 6 to 3 - 8
Software Version, 3 - 30 to 3 - 31
command keypad, 3 - 5
Status, 3 - 23
display, 3 - 3
Supervisory, 3 - 24
display keys, 3 - 5
Temp, 3 - 28
internal audible, 3 - 4
Trouble, 3 - 24 to 3 - 25
LEDs, 3 - 5
Voltages, 3 - 26 to 3 - 28
modes of operation, 3 - 5
Test, 3 - 42 to 3 - 49
numeric keypad, 3 - 4
ASD_Devices, 3 - 48
security, 3 - 10 to 3 - 11
Det_cleaned, 3 - 47
Device LED, 3 - 45
supervisories, 3 - 8 to 3 - 9
Event Log, 3 - 47
troubles, 3 - 9 to 3 - 10
Ground Fault, 3 - 44
Lamp Test, 3 - 45
Manual Activate, 3 - 49
MOI Lamp Test, 3 - 46
module address, 3 - 2
MOD-16
Override, 3 - 46 to 3 - 47
Power, 3 - 44 to 3 - 45
description, 1 - 10
Pre-alarm, 3 - 47 to 3 - 48
installation, 2 - 9
Pyro-diags, 3 - 47
operation, 3 - 3
Set Time, 3 - 43 to 3 - 44
Summarize, 3 - 48 to 3 - 49
MOI-7
Menu overview, 3 - 15
description, 1 - 10
MID-16
installation, 2 - 9
module address, 3 - 2
description, 1 - 11
operation, 3 - 3
installation, 2 - 9
MKB-4
description, 1 - 5
MOM-2
connections and ratings, 7 - 25
description, 1 - 8
installation, 2 - 6 to 2 - 9
Index - 3
Index
MOM-4
connections and ratings, 7 - 27
description, 1 - 8
P
PAL-1
description, 1 - 6
installation, 2 - 6 to 2 - 9
MPS-6/-6W, MPS-12/-12W
description, 1 - 5
installation, 2 - 3 to 2 - 4
MSE-3L
installation, 2 - 2
MSI Series of manual stations
description, 1 - 14
installation, 2 - 6
PBA-1191
description, 1 - 15
PE Series of detectors
description, 1 - 15
percent per foot obscuration, M - 1 to M - 3
PIM-1
description, 1 - 6
N
new features - rev.6.0 and higher, O - 1 to O - 2
installation, 2 - 5
PIM-2/PAL-1
installation, 2 - 6
power limited wiring, K - 1
power supply load calculations, D - 1
pre-alarm, M - 1 to M - 3
R
reset causing zone for MID-16 or CZM-4. See new
features - rev.6.0 and higher: reset causing zone
reset procedures
hard reset, 3 - 11
soft reset, 3 - 11 to 3 - 12
S
security point, installing, H - 1
self restoring troubles. See latching/non-latching
troubles
Silent Knight Model 5128/5129
connections and ratings, 7 - 33
SMB-2
connections and ratings, 7 - 35
network, 7 - 29
field wiring, 7 - 36 to 7 - 38
internal wiring, 7 - 35
description, 1 - 11
description, 1 - 4
installation, 2 - 14
installation, 2 - 3
module address 3 - 2
Index - 4
Index
spare parts list, N - 1
start up procedure, 2 - 10 to 2 - 16
system operation, global, 3 - 12 to 3 - 14
system test, 4 - 1
T
testing procedures, 4 - 1
TRI Series of interface modules
description, 1 - 14
trouble delay time for damper control using TRI. See
new features - rev.6.0 and higher
trouble messages, J - 1 to J - 8
trouble resound / reminder timer. See new features rev.6.0 and higher
Troubleshooting Guide, 4 - 2
TSW-2
description, 1 - 6
installation, 2 - 2
two stage alarm, Canadian, L - 1 to L - 7
W
Walktest, 5 - 1 to 5 - 6
operating instructions, 5 - 4
overview, 5 - 1
suggested procedure, 5 - 2 to 5 - 3
Index - 5
Index
Index - 6
WARNING:
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to radio
communications. It has been tested and found to comply
with the limits for a Class A computing device pursuant to
Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a
commercial environment. Operation of this equipment in a
residential area is likely to cause interference in which case
the user at his own expense will be required to take whatever measures may be required to correct the interference.
NOTES:
1. For Installation Instructions for the MXL-IQ modules refer
to the Table below.
2. Waterflow Alarm must be AccuLINK (CSG-M) configured
to at least one non-silenceable NAC.
3. Refer to the MXL-IQ OPERATION, INSTALLATION,
AND MAINTENANCE MANUAL (P/N 315-093624) for
minimum NFPA configurations and additional information.
4. Use the following batteries: BTX-1, BTX-2, or BP-61.
5. The CSM-4 module is capable of the following functions:
Leased Line Circuit
Supervised Local Energy Auxiliary Trip (Municipal Tie)
Supervised Notification Appliance Circuit
Releasing Service
6. CRM-4 relay coils are supervised when not energized;
contacts are not.
7. For alternate configurations using CZM-1/1B6s, consult
Technical Support.
8. Optional transient suppressors Model CP2341 and
CP2297 may be used in addition to the transient
protection incorporated in the panel and not in lieu of
that protection. Use them for extreme lightning
conditions. For CP2297 refer to instructions P/N 315-092355.
For CP2341 refer to instructions P/N 315- 092390.
9. For the Silent Knight 5128/5129 Central Station, Remote
Station connection (NFPA 72), refer to instructions P/N
315-093294.
10. The modules indicated with an asterisk in the Table below
are rated power limited on all terminals. Refer to the
MXL-IQ Power Limited Wiring Instructions, P/N 315-095445,
for separation of power limited wiring.
11. When the CSM-4 is configured for Municipal Tie or
Releasing Service, terminals 1 and 4 and/or terminals 9
and 12 are non-power limited. In all other applications, the
CSM-4 is power limited on all terminals.
12. For a list of Compatible Notification Appliances, refer
to P/N 315-096363.
:) 0 2 ?
$ . - ( " ? 7 (+ 0- 1(
) OLAE A@?
>&A#@
BI&#GHGAF E,D(2
:$J#@"
BI&#K
#($#0T8 C%+
0A' A@?
,( OLAE A@?
BI&#GHGAF
/9$#0T8 C%+
0A' A@?
)8 OLAE A@?
>&A#@
:-0),3 $,,7
B>&#K
$(0'(+ $.-(
#T86 OLAE
VHRGPSJFE PHRF @RJ PO@JU
#0 C%+
/#A' A@?
#0 C%+
9((A' A@?
) OLAE A@?
B>&#K
4()(0'.-3 >(2=.1(
*See Note 7
&%$#"!
&,+*)('
"-'/0))0/.,"-'/2*1/.,-'
'&%$#"!
+*"$)((!
+.##-,
+.#)0/
+1*$0
+2*$0
+3*$/!
+3*$/54!
+3*$0!
"+.!
"+.$54!
&"*$/!
*"%$/4
*65$0
*7%$/4
)/8$(-/040$8
)/8$(-/#8-$8
)/8$(-#)88$#
)/8$(-#-)($#
)/8$(-(98)+
)/8$(-(980$)/8$(-(,#8$9
)/8$(-8)88$#
)/8$(-(,#4$,
)/8$(-#0,0$4
)/8$(-8)(4$#
)/8$(-#/)8$8
)/8$(-/94($#
)/8$(-)8,8$)
)/8$(-(9)($0
*7"$,!
*7*$#
*7*$0
*.2$4
*.2$/#
:"*$/1
.'&$/
."*$/!
."*$#
.2$8'
.2$8:,!
1++$/</;
2*5$#
>2=$#
)/8$(-#,--$#
)/8$(-#,,,$8
)/8$(-(98#$,
)/8$(-())0$)
)/8$(-#()($)
)/8$(-#-8)$0
)/8$(-#0(9$8
)/8$(-/04#$/(
)/8$(-#0(9$8
)/8$(-#)4,$0
)/8$(-#,#-$4
)/8$(-8)40$#
)/8$(-8-)/$#
)/8$(-#0))$#
See Note 11
Base
Installation
Instructions
CZM-1
315-090725-8
CZM-1B6
315-095355-2
DB-11, DB-X11RS
DB-3S + DB-ADPT
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT
315-095921-4
315-095921-4
315-095921-4
315-095921-4
FP-11*
FP-11*(d)
AD-11P/11XPR
315-095659-2
DB-11, DB-X11RS
DB-3S + DB-ADPT
DB-X3RS + DB-ADPT
ADBI-60 + DB-ADPT
315-095921-4
315-095921-4
315-095921-4
315-095921-4
DB-3S, DB-X3RS
315-090287-2
AD-3I
AD-3XRI
315-093234-4
315-093235-4
ILI-1/1H/1A/1AH
DB-3S, DB-X3RS
315-095387-1
ILP-1
DB-3S, DB-X3RS
315-092594-5
AD-3ILP
AD-3XRILP
315-093234-4
315-093235-4
ILPT-1
DB-3S, DB-X3RS
ILP-2**
FPT-11*
ID-60I/IH/IA/IAH
"-'/0))0/.,"-'/2*1/.,-'
ILP-1 (d)
ILP-2**(d)
ILT-1
Base
Installation Instructions
DI-3/3H*
DB-3S
315-081943-15
315-092594-5
DI-A3/A3H*
DB-3S
315-081943-15
DI-3/3H
DB-3S
315-081943-15
DB-3S, DB-X3RS
315-095028-3
DI-B3/B3H*
DB-3S
315-081943-15
315-093234-4
315-093235-4
315-093234-4
315-086591-7
DI-A3/A3H
AD-3ILP
AD-3XRILP
AD-3I/3ILP
AD-3RI/3RP
DT-11*
DB-11
DB-3S + DB-ADPT
315-095429-1
315-095429-1
DI-B3/B3H
AD-3I/3ILP
AD-3RI/3RP
315-093234-4
315-086591-7
PBA-1191**
PBB-1191
315-095424-2
DB-11
DB-3S + DB-ADPT
315-095429-1
315-095429-1
PE-3/3T*
DB-3S
AD-3ILP
AD-3RP
315-090875-6
315-093234-4
315-086591-7
PE-3/3T
DB-3S
AD-3ILP
AD-3RP
315-090875-6
315-093234-4
315-086591-7
DB-11
DB-3S + DB-ADPT
AD-11P/11PR
315-094198-6
315-094198-6
315-095659-2
PE-11/11T
DB-11
DB-3S + DB-ADPT
AD-11P
315-094198-6
315-094198-6
315-095659-2
DB-3S, DB-X3RS
315-093336-1
MSI-10/-20
315-090903-3
MSI-10B/-20B
315-093329-3
MSI-B6F
315-095302-1
MSI-MB6
315-093613-1
TRI-B6/B6D/B6R
315-093315-3
TRI-B6M
315-094547-1
TRI-S/D/R
315-096242-1
CONNECTION DIAGRAM
) OLAE A@?
#0C SRQHPMFKFJ ;=1B /#A' A@? #0C SRQHPMFKFJ ;=1B /T8A' A@?
B>&#K
&*-.1.70) L.(
ID-60IB/IBH
&%$#"!
&,+*)('
5 ) ( 1 / 2 . 1 0 ) 40 / . - 3 '
;:) ) 20/. -3' 02( 7(2 9,-(8 7(2 ) ,,78 ,2 7(2 1. 21*. /6
PE-11/11T*
Detector
DT-11
Base
Installation Instructions
M a y u s e u p t o 1 5 d e t e c t o rs o f a n y t y p e .
*D o n o t u s e A D - 1 1 P R o r d e t e c t o r - o p e r a t e d a c c e s s o r i e s w i t h t h e
C Z M -1 / -1 B 6 .
P/N 575-293638CD-9