等蹟裝蹦扴
等蹟裝蹦扴
等蹟裝蹦扴
Application Manual
Page 2 of 60
Contents
Contents ................................................................................................................................3
List of Figures ........................................................................................................................4
List of Tables .........................................................................................................................4
1.
General Description ...................................................................................................5
1.1.
1.2.
1.3.
1.4.
1.4.1.
1.4.2.
1.4.3.
2.
Main Features......................................................................................................................... 5
Construction............................................................................................................................ 5
The Compression Process ..................................................................................................... 6
The Compression Process ..................................................................................................... 8
Suction ............................................................................................................................... 8
Compression...................................................................................................................... 9
Discharge ........................................................................................................................... 9
3.
Economiser Facility..................................................................................................17
3.1.
3.2.
4.
5.
6.
7.
Lubricating Oils........................................................................................................33
Page 3 of 60
8.
List of Figures
Fig 1 Compression Process...................................................................................................................... 8
Fig 2 Capacity Control Slide Valve in Operation .................................................................................... 10
Fig 3 Capacity Control Arrangement Using Separate Pairs of Solenoid Valves ................................... 14
Fig 4 Capacity Control Arrangement Using a 4-Way Solenoid Valve.................................................... 16
Fig 5 Economiser Arrangement.............................................................................................................. 19
Fig 6 Maintaining Discharge Pressure at Start up.................................................................................. 28
Fig 7 Liquid Injection Cooling ................................................................................................................. 30
Fig 8 Typical Methods of Providing Preferential Liquid Supply for Injection.......................................... 31
Fig 9 Oil Cooler Temperature Control .................................................................................................... 32
Fig 10 HBLVDT External Wiring Connections........................................................................................ 36
Fig 11 Key to Schematic Flow Diagrams ............................................................................................... 43
Fig 12 No Oil Pump................................................................................................................................. 44
Fig 13 Start-up Oil Pump: Common Oil Lines for Injection and Lubrication .......................................... 45
Fig 14 Continuously Running or Demand Oil Pump: Common Oil Lines for Injection and Lubrication 46
List of Tables
Table 1 Capacity Control Solenoid Valve Options ................................................................................. 12
Table 2 Pumping Capacities For Continuously Running Oil Pump ....................................................... 25
Table 3 Summary of Differential Pressure Sensing ............................................................................... 26
Table 4 Minimum Specification of Mineral Oils and Polyolester Lubricants .......................................... 33
Table 5 Approved Oils List...................................................................................................................... 58
Page 4 of 60
1.
General Description
1.1.
The J & E Hall International HSO 2000 series of open drive compressors
form part of the HallScrew family of positive displacement, oil injected,
single screw compressors.
These compressors have been specially developed for refrigeration, air
conditioning and heat pump applications, and can be applied to single
stage and multi-stage systems using all normal refrigerants as well as
many other process gases.
Main Features
For use with R717 (ammonia), R404a, R507, R22, R134a
and R407c.
Designed and tested to international standards.
Robust construction.
Improved machine clearance control for maximum efficiency.
Oil injected for maximum reliability.
Balanced loading on main bearings for maximum bearing
life.
Enhanced slide valve geometry for capacity modulation with
minimum loss of efficiency. Infinite adjustment between
maximum (100 %) and minimum load (nominal 10 %).
1.2.
Page 5 of 60
1.3.
Page 6 of 60
The main rotor and star rotors are housed inside a one-piece, cast-iron
main casing. The inside of the casing has a somewhat complex shape,
but essentially consists of a cylindrical annulus which encloses the main
rotor leaving a small clearance. Part of the annulus is cutaway at the
suction end to allow the star teeth to mesh with the main rotor flutes. The
discharge ports (one for each star), are positioned at the other end of the
annulus. These ports convey the compressed gas into the discharge
manifold, formed by a web cast between the annulus and the walls of the
casing; this web separates the casing into two pressure zones. Except
for the discharge manifold, suction pressure prevails elsewhere in the
main casing.
Side covers are provided to allow easy access to the star rotors, star
rotor shafts and bearings, without disturbing working tolerances. The
discharge end cover can also be removed to inspect the capacity control
mechanism. The compressor is provided with the choice of either top or
bottom discharge; the unused connection is sealed off with a blank cover.
It is necessary to fit a suction strainer immediately before the compressor
suction inlet. The strainer is designed to trap any dirt circulating with the
refrigerant which might otherwise enter and damage the compressor.
To prevent reverse rotation of the compressor at shutdown it is necessary
to fit a non-return valve adjacent to the compressor in the suction and/or
discharge lines; refer to 5.4.2.
The Compression Process
In the construction of the HallScrew the helical flutes in the main rotor can
be likened to the cylinders of a reciprocating compressor, the star rotor
teeth taking the place of conventional pistons. Instead of using suction
and discharge valves, gas flow in and out of the flutes (the cylinders) is
controlled by fixed ports.
Gas enters the compressor through the suction connection and fills the
available flutes. Rotation of the main rotor traps the gas in chambers
formed by the flute walls, the cylindrical annular ring housing the main
rotor, and the star teeth. The small clearances around the star teeth are
sealed with oil which is injected into the compressor during operation. As
the main rotor turns, the star teeth act as stationary pistons in the moving
flutes (the cylinders), and the gas is compressed until a discharge port is
uncovered. Each flute is used twice per rotor revolution, i.e. once by one
tooth on each star.
The compression process is illustrated and described in detail in Fig 1.
As the compression process is symmetrical, occurring at the same instant
in each half of the compressor, this results in zero transverse gas
pressure loads on the main rotor bearings. The axial loads are also
minimal because the flutes terminate on the outer surface of the main
rotor. The only bearing loads, apart from the weight of parts, are bending
loads on the star rotor shaft bearings due to high pressure gas acting on
one side of each tooth in mesh. There is also a small axial thrust load on
the main rotor bearings resulting from the main shaft projecting through
the casing, combined with the rotor vent pressure.
Capacity control is effected by slide valves, one for each half of the
compressor. These valves are used to vent part of the gas trapped in the
flutes back to suction, thus effectively shortening the compression length
of the main rotor. Using this method, compressor capacity is infinitely
variable between 100 % and 10 % of full load.
Page 7 of 60
B
a
b
a
b
c
1. SUCTION
B
b
a
a
b
c
2. SUCTION
1.4.
1.4.1.
Page 8 of 60
B
b
a
b
c
A
3. COMPRESSION
B
a
b
a
b
4. DISCHARGE
1.4.2.
1.4.3.
Compression
As the main rotor turns, the volume of gas trapped within the flute is
reduced as the length of the flute shortens and compression occurs.
Discharge
As the star rotor tooth approaches the end of a flute, the pressure of the
trapped vapour reaches a maximum value occurring when the leading
edge of the flute begins to overlap the triangular shaped discharge port.
Compression immediately ceases as the gas is delivered into the
discharge manifold. The star rotor tooth continues to scavenge the flute
until the flute volume is reduced to zero. This compression process is
repeated for each flute/star tooth in turn.
While the compression process described above is occurring in the upper
half of the compressor, there is an identical process taking place
simultaneously in the lower half using star B, thus each main rotor flute is
used twice per rotor revolution (one by one tooth in each star). The
compression process may be likened to an assembly of six double-acting
cylinders (the main rotor flutes) in which the star rotor teeth move as
pistons (always in the same direction).
Page 9 of 60
2.
Main Rotor
Discharge
Suction Gas
Slide valves in fully loaded position
Main Rotor
Discharge
Bypass
Suction Gas
Slide valves in part load position
Page 10 of 60
2.1.
The best part load characteristics are achieved if the design full load VR is
maintained as the compressors capacity is reduced. The HallScrew
2000 series compressor is fitted with a pair of sliding valves, one for each
half of the symmetrical compression process. These valves reduce
pumping capacity by delaying the sealing of the flute volume together
with the opening of the discharge port, altering the effective length of the
main rotor flutes. The valves not only permit stepless capacity control
down to approximately 10 % of full load (actual minimum value varies
with operating conditions), but also maintain the best possible VR over a
wide capacity control range.
Each slide valve is housed in a semicircular slot in the wall of the annular
ring which encloses the main rotor. As the slide valve travels axially from
the full load position it uncovers a port which vents part of the gas
trapped in the main rotor flute back to suction before compression can
begin. When the flute has passed beyond the port, compression
commences with a reduced volume of gas. However, a simple bypass
arrangement without any further refinement would produce an
undesirable fall in the effective volume ratio which in turn causes
undercompression and inefficient part load operation. To overcome this
problem, the slide valve is shaped so that it reduces the discharge port
area at the same time as the bypass slot is created.
Fig 2 shows one of the capacity control slide valves in two positions: fully
loaded and at part load, the arrows on the diagram indicating the flow of
gas. Each half of the compressor is provided with its own slide valve
system, these are operated simultaneously to maintain balanced gas
loads and low bearing loads within the compressor. The position of the
slot at the suction end of the slide and the position of the moving delivery
port can both be chosen to give the desired full load VR, the appropriate
ratio being selected according to the operating conditions. The following
volume ratio slides are available for each compressor size: 2.2, 3.0 and
4.9.
Slide Valve Actuation
The capacity control slides valves are joined together by a yoke which is
connected to a hydraulic piston, housed inside a cylinder and mounted
internally at the discharge end of the compressor.
The motive force required to actuate the piston is derived from a supply
of pressurised oil taken from the lubrication system. The flow of oil to the
cylinder is controlled either by a specially adapted 4-way solenoid valve
or by two pairs of solenoid valves connected in parallel. As the
requirement for duty changes, the plant control system energises or deenergises the solenoid valves, supplying oil pressure to drive the piston
and slide valves in the load or unload direction. The oil on the other side
of the piston is vented to the evaporator side of the suction non-return
valve via a drain line.
The capacity control piston/slide valves speed of travel, and hence how
quickly the compressor loads and unloads, is determined by flow control
valves fitted in the load and unload oil lines to the capacity control
cylinder.
Before the compressor starts, the HBLVDT must provide an at minimum
load permit start signal. If the slide valves are not already at minimum
load, the pressure generated by the system oil pump is used to return
them to the minimum load position.
Page 11 of 60
APPLICATION
No oil pump
2.3.
2.3.1.
2.3.2.
2.3.3.
Page 12 of 60
Page 13 of 60
NO
NC
Load Line
Oil
Drain
Oil
Feed
NO
NC
Unload Line
Load Flow
Control Valve
B
1
Unload Flow
Control Valve
A
COMPRESSOR
LOADING
NO
NC
Load Line
Oil
Drain
Oil
Feed
NO
NC
Unload Line
Load Flow
Control Valve
Unload Flow
Control Valve
COMPRESSOR
UNLOADING
Load compressor
Energise (open)
Energise (close)
Energise (open)
Unload compressor
De-energise (close)
De-energise (open)
De-energise (close)
De-energise (close)
Energise (close)
De-energise (close)
Flow control valves enclosed in boxes incorporate NRV as shown in Fig 11.
Page 14 of 60
2.4.
2.4.1.
2.4.2.
2.4.3.
2.4.4.
Page 15 of 60
SOLENOID B
SOLENOID A
B
1
Unload Flow
Control Valve
A
A
B
P
Oil
Feed
B
U l
Oil
Drain
Unload Line
Load Line
COMPRESSOR
LOADING
SOLENOID B
Unload Flow
Control Valve
SOLENOID A
T
B
A
A
Oil
Feed
Oil
Drain
Unload Line
Load Line
COMPRESSOR
UNLOADING
SOLENOID A
Energise
SOLENOID B
OIL FLOW
De-energise
P A, B T
Unload compressor
De-energise
Energise
P B, A T
De-energise
De-energise
No flow
1
2
Flow control valves enclosed in boxes incorporate NRV as shown in Fig 11.
The solenoids on the 4-way valve are normally closed, energise to open.
Page 16 of 60
3.
Economiser Facility
3.1.
Page 17 of 60
Page 18 of 60
Pressure
Subcooling
Condenser
Compressor
Economiser
Evaporator
Capacity Without Economiser
Capacity With Economiser
Enthalpy
Economiser Cycle on Pressure/Enthalpy (p-h) Diagram
Economiser
TEV
Equalising
Line
Oil
Separator
Evaporator
Condenser
Electrically interlocked to energise (open) when compressor capacity > 50 %, de-energise (close)
when compressor capacity < 50 %.
Page 19 of 60
4.
4.1.1.
4.1.2.
4.1.3.
4.1.4.
Page 20 of 60
Page 21 of 60
5.
5.1.
5.2.
5.2.1.
Page 22 of 60
5.3.1.
5.4.
Oil Separation
All the oil injected into the compressor for lubrication, sealing and
capacity control actuation, ultimately ends up in the discharge gas
stream. During its passage through the compressor the oil is thoroughly
mixed with the refrigerant, eventually ending up in the discharge gas
stream as a fine mist of oil droplets. Before the oil can be recirculated it
must be separated from the discharge gas, filtered, cooled (if compressor
cooling is required and internal cooling by liquid injection is not used),
and then returned to the compressor. An oil separator is therefore
required in the discharge line. This vessel effectively removes the
majority of the oil constituent from the oil/gas mixture, the oil draining into
a reservoir which usually forms the lower portion of the separator vessel.
Oil Separator Design
The method of oil separation utilised by the oil separator is not important
in itself in that velocity, impingement coalescent or other types or
combination of types may be used. However it is important that the
separator operates at sufficient efficiency over the actual operating range,
with the compressor at all load conditions.
Deciding the required level of efficiency is important and is dependant not
only on the compressor but also on the system design. No separator is
100 % efficient and some oil will always be carried over into the system.
On a small direct expansion system this oil will be rapidly recirculated
back to the compressor travelling with the refrigerant through the system
and returning via the suction line. In this case the separator can be sized
such that allowing for the extremes of operation, sufficient oil is
maintained in the oil separator to ensure an adequate head of oil to
match the specified oil flow rate from the separator into the compressor.
Additionally, as the separator efficiency changes with load and operating
conditions, then the amount of oil carried into the system through the
separator will also vary. Therefore the oil remaining in the separator will
vary by an equal amount. Thus either sufficient oil capacity must be
provided in the separator to allow for this change in oil quantity or a more
consistent separator performance must be attained. As high quantities of
oil in the evaporator are detrimental to system performance it is normal to
design the separator with as high an efficiency as is economically
achievable. Even in this case the separator must provide sufficient oil
volume above the normal operating volume to cater for the variation in
efficiency. In addition the separator must have sufficient oil volume to
provide an adequate dwell time to allow oil and refrigerant to reach their
equilibrium condition.
In systems such as those incorporating flooded evaporators where oil
carried over from the separator is not so readily or quickly returned then
greater care is required in oil separator design. The separator must be of
sufficient efficiency that oil carried over into the system can be returned
by the oil rectification system. For miscible oil/refrigerant combinations a
sample of refrigerant is taken from the evaporator the refrigerant boiled
off and the oil returned to the compressor. If this refrigerant is not boiled
off in a useful fashion then this is a direct loss on the system
performance. If conditions change rapidly then it can take considerable
time for equilibrium to be achieved. Under these conditions oil will build
up in the evaporator and be lost from the separator. Thus the separator
must be of a high efficiency type perhaps including coalescent elements
and at the same time must have sufficient oil volume above the minimum
requirement to cope with these variations in operating conditions.
Oil Separator Provisions
In addition to the considerations discussed in 5.3.1, the oil separator
should comply with the following recommendations:
Page 23 of 60
5.4.2.
Oil Return
As already mentioned in 5.2, the separator must be positioned at a
suitable height such that the standing oil level (compressor stopped) is
significantly below the bottom of the compressor. For applications using
a continuously running oil pump a drain line must be installed between
the compressor casing and the oil separator.
The oil separator must have a sufficient free volume to accommodate the
oil drainage from the compressor or oil returned from another part of the
system.
Suction/Discharge Non-return Valve
To prevent excessive reverse rotation of the compressor at shutdown it is
necessary to fit a non-return valve adjacent to the compressor in the
suction and/or discharge lines:
Single compressor application - either a suction or discharge
non-return valve must be fitted. A non-return valve in the
suction line must be located before the suction strainer.
5.4.3.
5.4.4.
5.4.5.
Page 24 of 60
6.
Oil Circulation
An oil circulation pump can be dispensed with for most operating
conditions using HSO 2000 series compressors or if a pump is necessary
it is only required to run at start-up.
For applications without an oil pump, oil circulation is maintained by the
pressure difference generated between the high pressure side of the
system and the pressure in the sealed main rotor flute at the point of oil
injection. When the compressor stops, a special, fail-safe solenoid valve
arrangement (refer to Fig 3) automatically returns the capacity control
slide valves to minimum load.
For applications using an oil pump for starting only, the pump is used to
provide adequate lubrication for the bearings and mainshaft gland seal,
and an oil pressure source to return the compressor capacity control slide
valves to the minimum load position prior to starting. After a short period
the pump is stopped and oil injection maintained by the system pressure
difference. Non-return valves are positioned in the oil lines to ensure that
oil is only delivered to the lubrication and capacity control connections
when the pump is running. When self-injection takes over, oil is fed to
the lubrication, capacity control and oil injection connections.
Exceptions to the above occur when there is only a small system
pressure difference. Typical examples are under low ambient conditions,
low load operation and most low stage (booster) applications. If the
difference between absolute discharge pressure, measured at the outlet
from the oil separator, and twice the absolute suction pressure is less
than 2 bar abs, pumped oil injection/lubrication is necessary using a fullflow oil pump running continuously while the compressor is operating.
For minimum pumping capacities refer to Table 2.
HallScrew
Compressor
Pumping
3
Capacity m /hr
HallScrew
Compressor
Pumping
3
Capacity m /hr
HSO 2024
4 to 6
HSO 2031
7 to 10
HSO 2028
5.5 to 8
HSO 2035
10 to 15
6.1.
Page 25 of 60
CONTINUOUSLY
RUNNING OIL PUMP
ODP1 by differential
pressure switch
Oil-to-suction P
Oil-to-discharge P
Oil-to-suction P
ODP1 by transducers
Oil-to-discharge P
(during start-up only)
ODP2 by differential
pressure switch
Not used
ODP2 by transducers
Not used
Designated ODPS on applications with no oil pump or a continuously running oil pump (only one oil differential pressure
switch fitted).
6.2.
Page 26 of 60
6.2.1.
6.2.2.
6.2.3.
6.2.4.
The demand oil pump starts a few seconds before the compressor.
After the minimum run time interval expires, Fridgewatch checks if
system pressure difference is sufficient to maintain adequate oil
supply without the oil pump running. If Fridgewatch decides that
the oil pump is not required, the pump is stopped, otherwise the
pump continues to run until system pressure difference increases.
Once the pump has stopped, Fridgewatch continues to monitor oil
injection pressure. If as a result of falling system pressure
difference, oil injection pressure approaches the ODP1 trip value,
the pump is restarted.
Oil Flow Switch
For applications without an oil pump or with a continuously running oil
pump, the oil differential pressure switch can be replaced by a flow switch
positioned in the oil line to the compressor bearings.
Contacts close at 0.15 litres/second on flow increase.
Contacts open at 0.095 litres/second on flow decrease.
On starting the compressor, oil flow must rise to a value in excess of the
flow switch contacts close value.
After allowing sufficient time for oil flow to rise, the flow switch is brought
into the trip circuit. If oil flow has not exceeded the contacts close value,
or falls below the contacts open value during operation, the compressor
stops and a trip is displayed.
Oil Differential Pressure 2 (ODP2)
This differential pressure is only applicable when the oil pump runs at
start up only.
Before the compressor starts, the start-up oil pump runs to establish a
discharge/oil pump pressure differential in excess of the ODP2 value.
After allowing sufficient time for the pressure differential to rise, ODP2 is
brought into the trip circuit. If the pressure differential has not exceeded
the ODP2 value, the start sequence is terminated and a trip displayed.
For applications with separate solenoid valves in the oil feed and oil
injection lines, ODP2 continues to be monitored all the time the
compressor is running.
Oil System Differential Pressure Drop
Gauges or pressure transducers must be provided to measure the
pressure differential across the oil system, including the oil filter.
Oil pressure drop = Oil pressure before - Oil pressure
across filter
oil filter
after oil filter
NOTE: do not allow the pressure drop across the filter
to exceed the clean filter pressure drop plus 1.4 bar,
before changing the filter element.
Maintaining Discharge Pressure at Start up
Because oil pressure is generated by discharge pressure, a minimum
discharge pressure must be maintained, this minimum pressure
increases as suction pressure increases in order to maintain the required
pressure differential.
In circumstances where the minimum discharge pressure is difficult to
achieve, even with the help of condenser head pressure control devices,
a differential pressure regulator must be fitted in the discharge line
immediately after the oil separator. Fig 6 ilustrates a typical arrangement
using a Danfoss PM 1 main valve and CVPP pilot valve.
Discharge pressure, inlet pressure to the main valve, is applied to the
space below the pilot valve diaphragm. Suction pressure is applied via a
pilot line to the space above the diaphragm. The main valve, therefore,
controls on the differential between suction and discharge pressure.
Page 27 of 60
Suction
Danfoss PM 1
Main Valve +
CVPP Pilot Valve
Discharge
Line
Discharge
Oil Separator/Reservoir
6.3.
Page 28 of 60
6.4.1.
Compressor Cooling
The heat of compression must be removed either by the evaporation of
liquid refrigerant injected directly into the compression process (liquid
injection), or by using an external heat exchanger to cool the oil injected
to seal the compression process.
Liquid Injection Cooling
Liquid refrigerant is injected into the compressor main rotor flute, partway through the compression process.
The rate of injection is thermostatically controlled by a liquid injection
valve which meters a precise quantity of refrigerant into the compressor
according to changes in discharge gas temperature.
The injection valves sensing bulb is either strapped to the discharge line,
or installed in a bulb pocket in the line. The injection valve is normally set
to limit discharge temperature to 75 C, or 25 C above condensation
temperature if this is above 50 C, whichever is the higher, to ensure
satisfactory oil separator performance.
If liquid injection cooling is adopted and the discharge temperature is
likely to exceed 75 C, a small oil cooler must be provided in the oil line
supplying the bearings, gland seal and capacity control mechanism. This
cooler may be water, air or refrigerant cooled.
Liquid injection line components are illustrated and described in Fig 7.
Page 29 of 60
Suction
PMFH Main
Valve
Liquid
Inlet
LO
To Oil Separator
Main valve
Visual indication that the line is full of liquid and provides early
indication of a choked strainer.
Non-return valve
Solenoid valve
Strainer
Stop valve
Stop valve (locked open)
LO
Page 30 of 60
Liquid Receiver
Sump
Weir
Liquid Receiver
LP or HP System
Condensate From
Condenser
Condensate From
Condenser
Level
Controller
Main Liquid
Supply to
Evaporator
Liquid
Control
Vessel
Transducer
Column Provides
Level Signal
Liquid to
Injection Valve
6.4.2.
Page 31 of 60
3-Way Valve
3-Way Valve,
Thermostatically
Controlled
Oil From
Separator
A
B
Water or
Refrigerant
Oil From
Separator
Oil to Cooler
Oil Cooler
Oil to
Compressor
A
B
Oil to Compressor
Lubrication and Oil Injection
Connection(s)
Warm Oil
From
Separator
Reservoir
A
B
Oil to Cooler
Oil
Warms
up
Cool Oil to
Compressor
C
Thermostat
Oil to Compressor
Lubrication and Oil Injection
Connection(s)
Oil From
Separator
Water or
Refrigerant
Oil Cooler
Oil to
Compressor
Oil From
Separator
Oil to Cooler
Warm Oil
From
Separator
Oil to Cooler
Cool Oil to
Compressor
Oil
Warms
up
Page 32 of 60
7.
Lubricating Oils
Lubricants used in the HallScrew compressor not only provide sealing
and cooling functions. The grade and type of lubricant chosen must
provide these functions at the actual operating environment existing
inside the compressor. In addition, as no oil separation system can be
100 % effective, the refrigeration system must be designed to adequately
return any oil carried over into the system to the compressor. Therefore,
the lubricant must be compatible with the refrigerant and the refrigeration
system as a whole.
The lubrication criteria can be met for standard operating conditions by
using a refrigeration quality oil as specified in Table 4 which is generally
in accordance with BS 2626 : 1992 Lubricating Oils for Refrigeration
Compressors.
Lubricating oils already approved for use with HallScrew 2000 series
compressors are listed in Appendix 5 Approved Oils. Alternative oils from
other suppliers may also be capable of providing adequate lubrication but
approval to use such oils MUST be obtained from J & E Hall International
if guarantees are not to be invalidated. Different types and makes of oils
must not be mixed.
POLYOLESTER
LUBRICANTS
MINERAL OILS
PARAMETER
EXTERNAL
OIL COOLING
Minimum ISO viscosity grade
68
LIQUID
INJECTION
OIL COOLING
4
Acid number
LIQUID INJECTION
AND EXTERNAL
OIL COOLING
100
68
45
33
45
-30 C
-20 C
-25 C
0.88
40 ppm
50 ppm
<0.05
<0.15
Including liquid injection oil cooling where the condensing temperature is below 45 C.
For condensing temperatures above 45 C.
All condensing temperatures.
4
ISO grade 150 or 220 oil is preferred, where available and suitable for the system.
Higher grades enhance compressor performance.
1
2
3
7.1.
7.1.1.
Lubricant Types
Refrigeration compressor lubricants can be divided into three categories:
Mineral Oils
These are the standard choice for use with R22 and R717 (ammonia)
refrigerants. Use of an approved oil from Appendix 5 Approved Oils will
ensure that viscosity and lubricity are maintained at an acceptable level
when diluted with refrigerant at the temperatures and pressures
encountered within the compressor.
Page 33 of 60
7.1.2.
Page 34 of 60
Page 35 of 60
8.
Electrical Connections
The following electrical connections are required to the compressor:
Mains electrical supply to the compressor drive motor and
motor starter. Refer to the motor and starter manufacturers
instructions.
Electrical supply to the capacity control solenoid valves;
refer to Fig 3 and Fig 4.
If a 4-way solenoid valve is used; refer to publication 4-45 available
from J & E Hall International.
Control electrical supply to the LVDT and 4 to 20 mA signal
from the LVDT to the plant controller; refer to 8.1.
HB Linear Variable Displacement Transducer (HBLVDT)
The HBLVDT provides a continuous 4 to 20 mA slide valve position
signal between minimum load (10 %) and maximum load (100 %).
Calibration of the 4 to 20 mA signal for maximum and minimum load is
done at the HBLVDT; refer to the procedure in the HSO 2000 Series
Installation, Operation and Maintenance Manual.
External wiring connections are shown in Fig 10.
An explosion-proof version of the HBLVDT is available, contact J & E Hall
International for details.
8.1.
4 to 20 mA Output Signal
For Remote Indication of
Slide Valve Position
FW
154
3
+
4 to 20 mA Out
24 V dc
Supply
FW
153
FW
152
FW
151
Link
Connections to J & E Hall International
Fridgewatch 2000 and 2100 Controllers
Page 36 of 60
Refrigerants
A = R134a
B = R22
C = R407c
D = Not allocated
E = R507
F = R404a
G = Not allocated
H = R717 (ammonia)
For other refrigerants refer to
J & E Hall International.
Lubricating Oil
E = Ester oil
M = Mineral oil
Capacity Control Slide Valve VR
2 = 2.2 VR
3 = 3.0 VR
4 = 4.9 VR
24, 28, 31 or 35
0 = Twin star
Compressor
2 = Series 2000
Application
O = Open drive
HallScrew
Example: HSO 2028/2/M/B
This describes a HallScrew 2028 twin star open drive compressor fitted with 2.2 VR capacity control slide valves, supplied
with mineral oil. Compressor for operation with R22.
Page 37 of 60
Physical Data
Compressor Type
Compressor Rotation
Anticlockwise looking on the motor (driven) end. Under no circumstances should the
compressor run in the reverse direction.
Method of Drive
Capacity Control
COMPRESSOR
HSO 2024
NORMAL
SPEED
RANGE
SWEPT VOLUME
3
(m /hr)
50 HZ
60 HZ
50 HZ
60 HZ
853
1024
250
300
449
1273
1528
350
420
564
1728
2074
460
550
810
HSO 2035
1000 to
3600
rpm
2486
2983
650
780
1194
COMPRESSOR
TOTAL
dB A
NR
125
250
500
1k
2k
4k
HSO 2024
84
82
71.5
82
80
82
73
69
HSO 2028
86
84
73
84
82
84
75
71
HSO 2031
88
86
75
86
84
86
77
73
HSO 2035
90
88
77
88
85
88
79
75
HSO 2031
Page 38 of 60
WEIGHT
(kg)
1450 to
3600
rpm
HSO 2028
MAX ALLOWABLE
SHAFT POWER (kW)
CENTRE FREQUENCY - Hz
Limits of Operation
Pressure Limits
Detailed below are the test pressures applied to HallScrew compressors during the
course of manufacture. These limits MUST NOT be exceeded during installation,
commissioning or operation of the plant.
Production
43.4 bar g
29.0 bar g
31.7 bar g
29.0 bar g
29.0 bar g
See note
25:1
Temperature Limits
For normal refrigeration and air conditioning applications, the following temperature limits
should be observed.
5,7
100 C maximum
80 C
40C
75 C
100 C maximum
80 C
NOTES
1
Sound pressure level data applies to the compressor only. The sound pressure level for a standard air-cooled compressor
drive motor is usually higher.
The data refers to free-field conditions at a distance of 1 metre from the compressor. It is important to remember that on a
specific installation the actual sound pressure level is considerably affected by the size and type of room, material of
construction and plant design. Adjoining pipework, including suction, can have a very substantial effect on the noise level.
-5
Assembled compressors MUST NOT be subjected to pressures higher than those indicated. This may require isolation of
the compressor during system strength pressure testing.
Oil separator pressure limits may be less than those applicable to the compressor.
Refer to the appropriate limits of operation envelope in the HallScrew 2000 Series Compressor Selection Publication.
An oil cooling system MUST be fitted to all compressors. Part load operation will always require cooling even if full load
operation does not.
Injected oil temperature can be higher than 40 C, allowing a smaller oil cooler to be used, provided the discharge and oil
temperature limits are observed.
If refrigerants other than R22, R717 (ammonia), R134a, R404a, R407c or R507 are used, consult J & E Hall International.
If the controlled discharge temperature is likely to exceed 75 C, a separate oil cooler is required to limit the temperature of
the oil supply to the bearings, mainshaft gland seal and capacity control mechanism. Consult J & E Hall International.
When operating at a condenser gauge above 50 C, it is recommended that the discharge temperature is controlled to 25 C
above the condenser gauge to ensure satisfactory oil separation.
Page 39 of 60
TRIP
DEVICE
SETTING
REMARKS
Discharge pressure
High
HP cut-out
According to the
operating
conditions.
Connected to compressor
discharge, refer to
High
Cut-out or thermistor
100 C
Temperature at the
compressor discharge.
Suction pressure
Low
LP cut-out or pressure
transducer and controller
software programme
According to the
operating
conditions.
Maximum compressor
operating pressure
differential (discharge suction)
High
According to the
operating
conditions.
Low
Refer to Table 3.
High
Cut-out or thermistor
80 C
Oil flow
Low
Contacts close at
0.15 litre/second
on flow increase.
Discharge temperature
Oil temperature
or
3
Bursting disc.
Contacts open at
0.095 litre/second
on flow decrease.
Oil separator oil level
Low
Opto sensor
Trip if oil/liquid
refrigerant
present; refer to
5.2.1 Oil Drain
Sensor.
Page 40 of 60
DIMENSION
Overall
HSO 2024
HSO 2028
HSO 2031
HSO 3035
Length
975
1130
1150
1305
Height
446
500
560
640
Width
714
780
888
1000
420
470
600
660
280
306
415
468
Lifting eyebolts
CONNECTION
4 x M22
1 x M20
1 x M24
4 x M26
2 x M24
2 x M24
2 x M24
HSO 2031
HSO 3035
NO OFF
HSO 2024
HSO 2028
125 mm (5) NB
BS 4504 Table
40/3. 8 x M24
on 220 PCD
150 mm (6) NB
BS 4504 Table
40/3. 8 x M24
on 250 PCD
100 mm (4) NB
BS 4504 Table
40/3. 8 x M20
on 190 PCD
125 mm (5) NB
BS 4504 Table
40/3. 8 x M24
on 220 PCD
Liquid injection
Economiser
Oil injection
1 BSP (plugged)
3/8 BSP (plugged)
Dimensions in mm unless otherwise stated. Data provided as a guide only, refer to J & E Hall International Limited certified
drawing.
Bottom suction and top discharge options must be clearly stated when ordering.
3
Eyebolts screw into opposite tapped holes on main casing suction/discharge flange.
2
Page 41 of 60
Capacity
Control
Unload
Discharge
Pressure
Gauge
Suction
(Top Standard)
Gland Oil Feed
TOP VIEW
Economiser
Connection
(Top)
Capacity
Control
Load
Discharge
(Top Option)
Liquid Injection
L
Suction
Pressure
Gauge
Main Oil
Injection
Main Oil
Injection
Discharge
End Cover
Oil Drain
B
A
W
Rear Main
Bearing
Oil Feed
BOTTOM VIEW
Discharge
(Bottom
Standard)
Page 42 of 60
Economiser
Connection
(Bottom)
Locked Open
Normally Closed
Normally Closed
and Capped
LO
LO
Ball valve
Non-return valve
Control valve
Relief valve
Liquid drainer
Heater
Strainer
FS
Oil filter
Oil pump
B
B
T
P
DPS
PSH
LSL
PSL
TE
PI
Page 43 of 60
Discharge/Suction Bypass
PT
Evacuation
Suction
A
Unload
A
Load
Oil Injection
HS
T
P
4-Way
Solenoid Valve
(Subplate
Shown)
Oil Lubrication
Discharge
TE
Oil Separator/Reservoir
Sight-glass
LSL
Oil Drain
Oil Filling
Connection
HT (Oil)
Purge
TE
Oil
Filter
Circuit Completion
When Using Liquid
Injection Cooling
Second Filter if
Double (Duplex) Oil
Filters Required
Oil Cooler
(Water, Air or Refrigerant Cooled)
Instead of Liquid Injection;
refer to 6.4. Compressor Cooling
HP
PSH
PI
Discharge
ODP
LP
PI
Oil
PI
PSL
Suction
Page 44 of 60
Evacuation
Discharge/Suction Bypass
PT
Suction
A
Unload
A
Load
Oil Injection
HS
4-Way
Solenoid Valve
(Subplate
Shown)
T
P
Oil Lubrication
Discharge
HT (Del)
TE
Oil Separator
Reservoir
Weir
LSL
Oil Drain
Integral
Relief
Valve
Oil Filling
Connection
Purge
Oil Differential
Pressure
Regulator
Oil
Filter
HT (Oil)
TE
Oil Drain
Circuit Completion
When Using Liquid
Injection Cooling
Second Filter if
Double (Duplex) Oil
Filters Required
HP
HP
PSH
PI
Discharge
OD
P2
LP
Oil Cooler
(Water, Air or Refrigerant Cooled)
Instead of Liquid Injection;
refer to 6.4. Compressor Cooling
PI
Oil
OD
P1
LP
PI
PSL
Suction
Fig 13 Start-up Oil Pump: Common Oil Lines for Injection and Lubrication
Page 45 of 60
Evacuation
Discharge/Suction Bypass
Suction
PT
A
Unload
A
Load
Oil Injection
HS
4-Way
Solenoid Valve
(Subplate
Shown)
T
P
Oil Lubrication
HT (Del)
FS
TE
Discharge
Oil Separator
Reservoir
Weir
LSL
Purge
Oil Drain
Second Filter if
Double (Duplex) Oil
Filters Required
Purge
PI
Discharge
LP
PI
Oil
Oil Filling
Connection
Oil
Filter
Oil Cooler
(Water, Air or Refrigerant Cooled)
Instead of Liquid Injection;
refer to 6.4. Compressor Cooling
HP
PSH
TE
Circuit Completion
When Using Liquid
Injection Cooling
Oil Pressure
(After Filter)
OD
P2
HT (Oil)
PI
PI
PSL
Suction
Fig 14 Continuously Running or Demand Oil Pump: Common Oil Lines for Injection and Lubrication
Page 46 of 60
50
VR 4.9
VR 3.0
VR 2.2
40
Discharge Gauge C
30
20
10
-20
-30
-60
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Booster
Page 47 of 60
50
VR 3.0
VR 4.9
40
VR 2.2
Discharge Gauge C
30
20
10
-10
-20
-30
-60
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 48 of 60
Booster
80
70
60
VR 2.2
VR 3.0
50
Discharge Gauge C
VR 4.9
40
30
20
10
0
Consult J & E Hall International when
running at conditions below this line
-10
-20
-50
-40
-30
-20
-10
10
20
30
Suction Gauge C
Booster
Page 49 of 60
60
50
40
VR 2.2
VR 3.0
VR 4.9
Discharge Gauge C
30
20
10
-10
-20
-30
-60
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 50 of 60
Booster
60
50
VR 2.2
40
VR 3.0
VR 4.9
Discharge Gauge C
30
20
10
-10
-20
-30
-60
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Booster
Page 51 of 60
Discharge Gauge C
60 C
20
50 C
Available Injection
Pressure Difference
15
40 C
10
30 C
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 52 of 60
60 C
20
50 C
Available Injection
Pressure Difference
15
40 C
10
30 C
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 53 of 60
60 C
14
12
Available Injection
Pressure Difference
50 C
10
40 C
8
6
30 C
4
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 54 of 60
Discharge Gauge C
60 C
25
50 C
20
Available Injection
Pressure Difference
40 C
15
30 C
10
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 55 of 60
60 C
20
50 C
Available Injection
Pressure Difference
15
40 C
10
30 C
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 56 of 60
Discharge Gauge C
60 C
25
Available Injection
Pressure Difference
50 C
20
40 C
15
30 C
10
20 C
0
-50
-40
-30
-20
-10
10
20
Suction Gauge C
Page 57 of 60
SUPPLIER
BP
PRODUCT
ISO VG
Energol LPT46
Mineral
46
Yes
No
No
Energol LPT68
Mineral
68
Yes
Yes
No
Energol LPT100
Mineral
100
No
Yes
No
Mineral
68
Yes
Yes
No
Icematic 299
Mineral
(55)
Yes
Yes
No
Yes
Limited
No
No
No
Limited
POE
68
No
No
Yes
100
No
No
Yes
POE
220
No
No
Yes
Icematic E100
POE
100
No
No
Yes
CP1009-68
Mineral
68
Yes
No
No
Frima FR68
Mineral
68
No
Yes
No
Frima FR100
Mineral
100
No
Yes
No
Frima NH46
Mineral
46
Yes
No
No
Frima NH68
Mineral
68
Yes
No
No
POE
100
No
No
Yes
Mineral
68
Yes
Planetelf ACD100LT
Zerice 68
Yes
No
Limited
No
Limited
No
AB
100
No
Zerice RS220
PAO
220
No
Purfrigol MP68
Mineral
(55)
Yes
Yes
No
POE
68
No
No
Yes
POE
68
No
No
Yes
Emkarate RL100S
POE
100
No
No
Yes
Emkarate RL150S
POE
150
No
No
Yes
POE
220
No
No
Yes
Zerice S100
Emkarate RL68H
Emkarate RL68HP
ICI
220
POE
Icematic SW220
Fina
PAO
68
Icematic SW100
Esso
PAO
Icematic SW68
Elf
R22
(AMMONIA)
Icematic 99
Icematic 2295
CPI Engineering
R134A,
R404A,
R507 AND
R407C
TYPE
Icematic 2294
Castrol
R717
Emkarate RL220H
Page 58 of 60
SUPPLIER
Mobil
Petro Canada
PRODUCT
R717
TYPE
ISO VG
Mineral
46
Yes
Mineral
(55)
Yes
(AMMONIA)
R22
R134A,
R404A,
R507 AND
R407C
No
No
Yes
No
Limited
No
Limited
No
PAO
68
Yes
PAO
220
No
POE
100
No
No
Yes
Reflo 68A
Mineral
68
Yes
No
No
Clavus 46
Mineral
46
Yes
No
No
Clavus 68
Mineral
68
Yes
Yes
No
Clavus G68
Mineral
68
Yes
Yes
No
Clavus G100
Mineral
100
No
Yes
No
Capella WF 68
Mineral
68
Yes
Yes
No
Suniso 4GS
Mineral
(55)
Yes
Yes
No
Shell
Texaco
Witco
Key
AB
= Alkylbenzene synthetic lubricant.
Mineral = Mineral based oil.
PAO = Polyalphaolefin synthetic lubricant.
POE = Polyolester synthetic lubricant.
1
2
Under certain specific conditions in particular system designs, use of the associated lubricant can be advantageous.
These synthetic oils are the only lubricants approved for use with R134a refrigerant.
Page 59 of 60
Questor House, 191 Hawley Road, Dartford, Kent DA1 1PU England
Telephone: +44 (0) 1322 223 456 Facsimile: +44 (0) 1322 291 458
www.jehall.co.uk
Page 60 of 60