The ideal air conditioning system for

small offices and shops

Extending the core 5S conceptSpace saving, Sufficient capacity, Slim design, Soundreduced operation and Single phase power supplyDaikins VRVIII-S offers added value
with the 1E conceptEasy installation. With all these features and more, we proudly
present the ideal air conditioning system designed for small-sized buildings.

S
5S
concept

Slim, compact and sufficient capacity

Approx.

765 mm

The

5S+1E concepts of

50%

reduction

The VRVIII-S is highly space saving, featuring slim and compact


outdoor units. It is suitable for small offices and shops with capacities
of 4, 5 and 6 HP.

320 mm

Footprint
635 mm

VRVIII
(5 HP)

Approx.

40%

reduction

900 mm

(4, 5, 6 HP)

VRVIII
(5 HP)
(4, 5, 6 HP)

Space saving
Sufficient capacity
Slim design

Sound-reduced operation
Single phase power supply

Volume

Easy installation

Outdoor unit can be installed


on a balcony

1E

The compact, trunk-shaped outdoor unit can easily


be installed on a balcony, realising complete system
installation within each floor. This enables more
useful utilisation of the space on the building rooftop.

concept

Contents
Introduction.......... page 1 Indoor unit lineup..... page 15 Option list............ page 33
Main features........ page 3 Specifications........... page 25
Control systems... page 9

Indoor units............... page 25


Outdoor units............ page 32

Indoor units......... page 33


Outdoor units.......page 35
Control systems...page 35
2

MAIN FEATURES
Wide range of choices

Indoor units

To suit the variety of rooms found in small offices


and shops, the VRVIII-S system offers wide range of
indoor and outdoor units.
VRVIII-S indoor and outdoor units are almost as easy
to install as residential air conditioning systems,
making them ideal for small offices and shops.

14 types 71 models*

A wide range of indoor units includes


71 models in 14 types. The indoor
units can be selected to match every
room and preference.

Outdoor units
3 models

Outdoor unit can be selected from three


models to provide the power that suits
your needs. The trunk-shaped outdoor unit
can be neatly installed outside the office.

Indoor unit lineup

Outdoor unit lineup


Model Name

RX(Y)MQ4PVE

RX(Y)MQ5PVE

RX(Y)MQ6PVE

Capacity Range

4 HP (11.2 kW)

5 HP (14.0 kW)

6 HP (15.5 kW)

Capacity Index

100

125

140

Type

14 types 71 models*

Model Name

20

25

32

40

50

20

25

31.25

40

50

New

New

New

New

New

Capacity Range 0.8 HP 1 HP 1.25 HP 1.6 HP 2 HP


Capacity Index

63

80

100

62.5

80

100

2.5 HP 3.2 HP 4 HP

125

5 HP
125

140

6 HP
140

FXFQ-LU

Ceiling Mounted
Cassette
(Round Flow)
Ceiling Mounted
Cassette
(Compact Multi Flow)
Ceiling Mounted
Cassette
(Double Flow)

FXZQ-MVE
FXCQ-MVE
FXKQ-MAVE

Ceiling Mounted
Cassette Corner

FXDQ-PBVE
(with drain pump)

Slim Ceiling
Mounted Duct

FXDQ-NBVE
(with drain pump)

FXMQ-PVE

Ceiling Mounted
Duct

FXHQ-MAVE

Ceiling Suspended
Wall Mounted

New

FXAQ-PVE

Floor Standing

FXLQ-MAVE

Concealed
Floor Standing

FXNQ-MAVE

New

Note: R-410A VRV system indoor units are not compatible with the R-22 VRV system.

Connection unit series indoor units (50 Hz only)


Type

Ceiling Suspended
Cassette

Model Name

FXUQ-MAV1

Capacity Range
Capacity Index
Connection Unit

0.8 HP
20

1 HP
25

1.25 HP
31.25

1.6 HP
40

2 HP
50

3 HP
71

BEVQ71MAVE

4 HP
100

5 HP
125

BEVQ100MAVE BEVQ125MAVE

Note: BEV units are necessary for Connection unit series indoor units.

MAIN FEATURES
Energy efficiency and quiet operation
Outdoor units use Daikins unique scroll compressor to realise energy saving
performance and quiet operation.

High COP
achieved
in all ranges!

Cooling

VRVII-S
3.65

4 HP

3.28

5 HP

2.92
3.68

4 HP

3.41

5 HP

3.19

6 HP

Above values are based on the following nominal conditions:


2 Ceiling Mounted Cassette (Round Flow) type units are connected (4 HP:
FXFQ50P x 2; 5 HP: FXFQ63P x 2; and 6 HP: FXFQ63P + FXFQ80P.)
Cooling: Indoor temp. of 27CDB, 19CWB, and outdoor temp. of 35CDB.
Heating: Indoor temp. of 20CDB, and outdoor temp. of 7CDB, 6CWB.

Quiet operation provides


luxurious comfort
Quietness is yet another important feature
of Daikins VRVIII-S system. To reduce
noise and realise comfortable operation,
latest technologies and features are
applied to the outdoor units.

51
52

5 HP

-1dB(A)
-1dB(A)

50
51

Nighttime quiet operation function

Mode 2. Manual mode

Starting time and ending time can be input. (An external


control adaptor for outdoor unit, DTA104A61 or
DTA104A62, and a locally obtained timer are
necessary.)
Mode 3. Combined mode

Combinations of modes 1 and 2 can be used


depending on your needs.
*1. Initial setting. Can be selected from 6, 8 and 10 hours.
*2. Initial setting. Can be selected from 8, 9 and 10 hours.

Capacity %

8 hrs

0
50

Night Mode

47
44
41

Step 1: 47 dB(A)

Step 2 max. - 6 dB(A)


( 4 HP/11.2 kW)

Step 2: 44 dB(A)

Step 3 max. - 9 dB(A)


( 4 HP/11.2 kW)

Step 3: 41 dB(A)

Night mode starts

8:00

12:00

16:00

20:00

Night mode ends


0:00

4:00

AC motor

30

60

90

120

Rotational speed (rps)

Reluctance
DC motor

Large load
High capacity

Sine wave DC inverter

Smooth Air Inlet Bell Mouth and Aero Spiral Fan

With the bent


blade edge

These two features work to reduce sound.


Guides are added to the bell mouth intake to
reduce turbulence in the airflow generated by
fan suction. The Aero Spiral Fan features fan
blades with the bent blade edges, further
reducing turbulence.

(Initial setting)

Step 1 max. - 3 dB(A)


( 4 HP/11.2 kW)

60

RX(Y)MQ4PVE
RX(Y)MQ5PVE
RX(Y)MQ6PVE

Use of an optimised sine wave smoothes motor rotation, further improving


operating efficiency.

10 hrs

(Initial setting)

50

More than 20%

>> Smooth sine wave DC inverter

Peak in outdoor temperature

100

Conventional DC motor
70

*1 A neodymium magnet is approximately 10 times


stronger than a standard ferrite magnet.
*2 The torque created by the change in power
between the iron and magnet parts.

Load %

Mode 1. Automatic mode

Set on the outdoor PCB. Time of maximum


temperature is memorised. The low operating mode
will become active 8 hours*1 after the peak
temperature in the daytime, and operation will return to
normal 10 hours*2 after that. The operation sound
level for the night mode can be selected from 47 dB(A)
(Step 1), 44 dB(A) (Step 2) and 41 dB(A) (Step 3).

Note: Data are based on studies conducted under


controlled conditions at a Daikin laboratory
using Daikin products.

Mode 1. Automatic mode

Operation sound dB(A)

Operation sound level selectable


from 3 steps for the night mode

80

Small load
Low capacity

Previous model
RXYM-MVM

4 HP

Reluctance DC motor

90

50

Lower operation sound is achieved


in cooling operation!
1 dB(A) reduced
in each model!
VRVII-S

Cooling

Compressor equipped with Reluctance DC motor


Daikin DC inverter models are equipped with the Reluctance DC
motor for compressor. The Reluctance DC motor uses 2 different
types of torque, neodymium magnet*1 and reluctance torque*2. This
motor can save energy because it generates more power with a
smaller electric power than an AC or conventional DC motor.

Previous model
RXYM-MVM

6 HP

Heating

Motor efficiency (%)

One of the top features of the VRVIII-S is


its energy efficiency. It achieves high COP
during cooling and heating operations by
employing Daikins unique scroll
compressor.

The high efficiency compressor to achieve a higher COP

8:00

Note: This function is available in setting at site.


The relationship of outdoor temperature (load) and time shown in the
graph is just an example.
The capacity reduction rate differs depending on the operation sound level
step selected.

DC fan motor

Efficiency improved in all areas compared


to conventional AC motors, especially at
low speeds.
DC fan motor structure

Without the bent


blade edge

Escaping eddies are sucked in by


the bent blade edges, reducing
overall turbulence.
DC motor efficiency

100

Efficiency (%)

High COP during both cooling and


heating operations

A collection of cutting-edge technologies


realises efficient and quiet operation.

80
60

(comparison with AC motor)

DC motor

Approx.

20%

increase

40 Approx.

40%

AC motor

Note: Data are based on


studies conducted under
controlled conditions at
0
a Daikin laboratory.
200 300 400 500 600 700 800 900 1000
Motor speed (rpm)

20 increase

MAIN FEATURES
Design flexibility

Easy installation

VRVIII-S systems offer broad design flexibility with long refrigerant piping lengths and
multiple indoor unit combinations, which provides generous freedom for office and shop
design both inside and out.

A variety of functions are provided that make installation easier, such as simple wiring
and piping and automatic test operation.
Previous model
VRVII-S

Easy wiring

As many as 9 indoor units can be


connected to a single outdoor unit

Multiple indoor unit combinations are possible.* As many as 9 indoor units can be connected
to a single outdoor unit, making the VRVIII-S a remarkably versatile system.

A printed circuit board has been


adopted that is easy to see and wire
during installation.

* Total capacity index of connectable indoor units must be 50 - 130 % of the capacity index of the outdoor unit.

For a 6 HP installation

Automatic test operation


1

Max.

units

>> Max. 8 indoor units for a 5 HP

Simply press the test operation button and the unit performs an automatic system check,
including wiring, shutoff valves, and sensors. The results are returned automatically after the
check finishes.

installation

>> Max. 6 indoor units for a 4 HP


installation

Simple wiring and piping connection

Unique piping and wiring systems make it possible to install a VRVIII-S system quickly and easily.

Long piping design possible

>> Super wiring system

The VRVIII-S provides the long piping


length possibility of 150 m, with a total piping
length of 300 m. If the outdoor unit is
installed above indoor units the level
difference can be up to a maximum of 50 m.
These generous allowances facilitate an
extensive variety of system designs.
Actual piping length

Max.

150

*2

Max.

50 m*1

Level
difference

Max.

A super wiring system is used to enable shared use of the


wiring between indoor and outdoor units and the central
control wiring, with a relatively simple wiring operation.
The DIII-NET communication system is employed to
enable the use of advanced control systems.

15 m

Level difference
between indoor
units

Central
remote
controller

Total piping length

Max.

300

Notes: *1. 40 m when the outdoor unit is installed below indoor units.
*2. Maximum piping length between the indoor unit and the first branch is 40 m.

Outdoor unit

Indoor unit

>> REFNET piping system

Wide operation temperature range

Certified operation temperature range

46CDB

40
30
20
10
0
-10

-5CDB
Cooling

Outdoor temperature (CWB)

The versatile operation range of the VRVIII-S system


works to reduce limitations on installation locations. The
operation temperature range for heating goes all the way
down to -20C, while cooling can be performed with
outdoor temperatures as high as 46C. Both these
achievements are due to the adoption of a high-pressure
dome-type compressor.

Outdoor temperature (CDB)

50

20

Daikins advanced REFNET piping system makes


installation easy. Only two main refrigerant lines are
required in any one system. REFNET greatly reduces the
imbalances in refrigerant flow between units, while using
small-diameter piping.

15.5CWB

10
0
-10
-20

20CWB
Heating

CONTROL SYSTEMS
Control systems
The VRVIII-S system uses the same DIII-NET communication system as the
VRV, enabling the use of advanced control systems.

Individual control systems

Navigation remote controller (Wired remote controller) (Option)

Wireless remote controller (Option)


The same operation modes and settings as with wired remote controllers are possible.
A compact signalng is
included.

Large buttons and arrow keys for easy operation.


Guide on display gives an explanation of each setting.
Backlight and dot matrix LCD display for easy viewing.
Weekly schedule timer can be set up easily.
10 display languages are available.
(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch,
Russian and Turkish)

A signallow,
Compact Multi Flow, Double Flow) type, Ceiling Suspended type and Wall Mounted
type is mounted into the indoor unit.
Signal receiver unit can be
installed on the panel

ex. Ceiling Mounted Cassette (Round Flow) type

Signal receiver unit

BRC1E61

(Separate type)

Wired remote controller (Option)

Wired remote controller


with weekly schedule timer (Option)

Displays current airflow, swing, temperature,


operating mode and timer settings.

Adds weekly schedule timer function.

Signal receiver unit

Wireless remote
controller

(Installed type)

*Wireless remote controller ander unit are sold as a set.


*Refer to page 35 for the name of each model.

Simplified(Option)

BRC1D61
Notes: 1. Standard remote controllers (BRC1C62) not required.
2. If the BRC1D61 is connected to the centralised remote controllers
(DCS303A51, DCS302CA61, DCS301BA61, DST301BA61), the
schedule function is not available.

BRC1C62

Concealed type
(For hotel use)
(BRC3A61)

Exposed type

The indoor unit can be connected by the two


remote controller, for example one in the room
and the other one in the control room, which
can control the operation of indoor unit freely.
(The last command has a priority.) Of course,
the group control by two remote controller is
also possible.

Group control

One remote controller can


control the operation of max.16
indoor units at the same time.

Equipment
related to the
central control

Outdoor
unit

Control by two remote controller

The concealed type remote controller smartly fits into a


night table or console panel in a hotel room.

(BRC2C51)

The wired remote controller supports a wide range of control functions


Control of Cool/Heat In all the series of VRV, Cool/Heat changeover in the same refrigerant
circuit can be changed by the remote controller of the indoor unit.
changeover

The remote controller has


centralised its frequently used
operation selectors and switches
(on/off, operation mode,
temperature setting and airflow
volume), making itself suitable
for use in hotel rooms or
conference rooms.
The exposed type remote
controller is fitted with a
thermostat sensor.

Wide variation of remote controllers for indoor units


FXFQ

FXZQ

FXCQ

FXKQ

FXDQ

FXMQ

FXHQ

FXAQ

FXL(N)Q

FXUQ

Navigation remote controller


(Wired remote controller)

(BRC1E61)

Wired remote controller

(BRC1C62)

Remote controller

Indoor unit

Remote controller

Remote
controller

Remote
controller

Remote control

3 Control for the combined operation


Forced OFF
input

Remote controller

The wiring of remote controller can be


extended to max. 500 m and it is possible
to install the remote controllers for the
different indoor units in one place.

Heat Reclaim
Ventilator
Remote controller

Remote controller

Remote controller

The operation of Heat Reclaim Ventilator


be controlled by the remote controller of the
indoor unit. Of course, the remote controller
can display the time to clean the filter.

Wired remote controller with


weekly schedule timer

(BRC1D61)

Wireless remote controller*


(Installed type

Wireless remote controller*


(Separate type signal receiver unit)

Simplifiedremote controller
Expansion of system control

The system can be expanded to add


several controllers, such as BMS, Forced
OFF input and etc.

Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.

(Exposed type)

(BRC2C51)

Simplifiedremote controller
(Concealed type: for Hotel use)

(BRC3A61)

*Refer to page 35 for the name of each model.

10

CONTROL SYSTEMS
Centralised control systems
Up to 64 groups of indoor units (128 units) can be centrally controlled.

Residential central remote controller* (Option)

Optional controllers for centralised control can be combined and optimised in


accordance with building scale and purpose.

Max. 16 groups of indoor units can be easily controlled with


the large LCD panel.

System integration with various air-conditioning peripheral equipment such as


Heat Reclaim Ventilator is easy.
Wiring can be run up to a total length of 2 km, and adapts easily to large-scale
system expansion.

DCS303A51

Max. 16 groups (128 indoor units) controllable


Backlight and large LCD panel for easy readability
ON/OFF, temperature settings and scheduling can be controlled individually for indoor units.
All indoor units can be turned on or off at once with ALL button.
Each group has a dedicated button for convenience.
Outside temperature display
*For residential use only. Cannot be used with other centralised control equipment.

Central remote controller (Option)

Max. 64 groups (zones) of indoor units can be


controlled individually same as LCD Remote controller.

Unified on/off
controller
(DCS301BA61)
Connection of
up to 8 units
possible

Independent
and centralised
control of Heat
Reclaim
Ventilator
possible.

Address setting of central control can be


performed from the remote controller.

DCS302CA61

Connectable number of
centralised control
equipment
Central remote
controller

2 units

Unified on / off
controller

8 units

Schedule timer

1 unit

Group control of up to 16 units is possible 1


(group control via automatic address setting)

Unified ON/OFF controller (Option)


Max. 16 groups of indoor units can be operated
simultaneously/individually.
System without remote control is also available.

Forced
shut-down
input

Central remote
controller
(DCS302CA61)
Up to 2 units
connectable

Central control
adaptor kit
(DTA107A55)

Wiring adaptor
for other airconditioners
(DTA103A51)

Outdoor-air
processing
unit can be
connected.

Interface adaptor for SkyAir


series (built-in indoor unit)
(DTA102A52)

6 cores
Schedule timer (DST301BA61)
1 unit connection possible;
8 weekly schedule control patterns possible

7 cores max.

DCS301BA61

Max. 16 groups (128 indoor units) controllable


2 remote controllers can be used to control from 2 different places.
Operating status indication (Normal operation, Alarm)
Centralised control indication
Max. wiring length 1,000 m (Total: 2,000 m)
Compact size casing (Thickness: 16 mm)
Connectable with Central Remote controller, Schedule timer and BMS system

Schedule timer (Option)

Max. 128 indoor units can be operated as


programmed schedule.

Interlink Building Management System


(host computer monitor panel) also possible

Unification adaptor for computerised


control (DCS302A52)

1. Refer to page 7 for the total number of indoor units that can be connected to the outdoor unit.
Certain indoor units limit the functions of some control systems.

DST301BA61

11

Max. 64 groups (128 indoor units) controllable


Max. 128 groups (128 indoor units) are controllable by using 2 central remote controllers,
which can control from 2 different places.
Zone control
Malfunction code display
Max. wiring length 1,000 m (Total: 2,000 m)
Connectable with Unified ON/OFF controller, schedule timer and BMS system
Airflow volume and direction can be controlled individually for indoor units in each group operation.
Ventilation volume and mode can be controlled for Heat Reclaim Ventilator.
Up to 4 ON/OFF pairs can be set per day by connecting a schedule timer.

Max. 128 indoor units controllable


When used in combination with a central remote controller, a maximum of 8 weekly schedule
patterns can be set, while the central controller can be used to select desired zones. Up to 2
ON/OFF pairs can be set per day.
Max. 48 hours back up power supply
Max. wiring length 1,000 m (Total: 2,000 m)
Compact size casing (Thickness: 16 mm)
Connectable with Central Remote controller, Unified ON/OFF controller and BMS system

12

CONTROL SYSTEMS
Advanced control systems
New

One touch selection to total air comfort

Daikin proudly introduces its new intelligent Touch Manager, a VRV system controller
featuring an array of simple, useful system management functions for added value.

Up to 2,560 groups (5,120 indoor units) can be controlled by one system

Communication functions in the user-friendly icon-based multilingual controller simplify


centralised control of the VRV system.
system overview
Dio Unit
DEC102A51
(Option)

system overview
Internal modem
(option)
Air Conditioning
Network Service System

New

DCS601C51

DCM601A51

Max. 64 groups

line

Phone line

System

iTM plus adaptor line


Max. 50m

LAN

I/O System (Max. 30 modules)


I/O module I/O module I/O module
Fire alarm

RS-232C

System
Components

ACC centre

Air Conditioning Network Service System


(Optional Maintenance Service)

kWh meter

Lighting

Pump

Fan

Central control

Handy area settings simplify detailed management of VRV.


Display of floor plans enables a quick search of desired air conditioning units.
Operation history shows manner of control and origin in past operations of air conditioning units.

Remote access

Remote access with a PC allows total air conditioning management using the same type of screens as those displayed in the
intelligent Touch Manager.
Authorised users can centrally control individual air conditioning units from their own computers.

Automatic control

VRVs are controlled automatically throughout the year by the schedule function.
Interlocking VRVs and other equipment enables easy automation of building facilities operation.
Setback adjusts temperature settings even when rooms are unoccupied.

D -NET Plus Adaptor


DCS601A52 (Option)

Indoor Unit

Heat Reclaim
Ventilator

Number of indoor units expanded from 64 to 128.

Features
Colour LCD touch panel icon display
Small manageable size
Simplified engineering
Multi language (English, French, Italian, German,
Spanish, Dutch, Portuguese, Chinese and Korean)
Yearly schedule

Energy management

Auto heat/cool change-over

Troubleshooting

Enhanced history function

The Energy Navigator feature simplifies energy management by tracking energy consumption data and identifying inefficient
operation.

Temperature limitation

Contact information of maintenance contractors can be registered and displayed.


E-mails are sent automatically to alert of malfunctions and potential trouble.
The intelligent Touch Manager can link to the Air Conditioning Network Service System for 24-hour monitoring of operating
conditions and status.

Simple Interlock Function

Scalability

D -NET

Sensor

Features

A single intelligent Touch Manager can manage a small building or be expanded to handle medium- to large-sized buildings.
Large building properties can also take advantage of the iTM integrator to link up and expand system up to 5 intelligent Touch
Managers for integrated control.

13

Via internet

Di/Pi port

Web Access

Web Access

Air Conditioning Network


Service System modem
for connections

Max. 500m
Di/Pi line
Max. 200m

OFF
command

iTM plus adaptor (Max. 7 adaptors)

I/O expansion line


USB memory

Input (Key signal General purpose ADP)

Set temperature
change command

LAN
Internet
Intranet

Input
(Lights)

Di Unit
DEC101A51
(Option)

Built-in modem for connecting to Air Conditioning Network Service System (Option)
Doubling of number of connectable indoor units by adding a D -NET Plus Adaptor (Option)
Management of facilities/equipment other than A/C units (By adding Dio unit or Di unit)
14

INDOOR UNIT LINEUP


Ceiling Mounted Cassette
(Compact Multi Flow) Type

Ceiling Mounted Cassette


(Round Flow) Type
FXFQ25L/FXFQ32L/FXFQ40L
FXFQ50L/FXFQ63L/FXFQ80L
FXFQ100L/FXFQ125L

FXZQ20M/ FXZQ25M
FXZQ32M/FXZQ40M
FXZQ50M

360 airflow improves temperature distribution


and offers a comfortable living environment.

Dimensions correspond with 600 mm X 600 mm


architectural module ceiling design
specifications.

The industrys first* Round Flow Ceiling Mounted


Cassette type offers 360 airflow with improved
temperature distribution.
Round Flow

4-way flow

Quiet, compact, and designed for user comfort

Low operation sound level

There are areas of


uneven temperature.

There are much fewer


areas of uneven temperature.

(dB(A))

FXZQ-M

20/25

32

40

50

Sound level 230 V


(H/L)
240 V

30/25

32/26

36/28

41/33

32/26

34/28

37/29

42/35

*As of April 2004, the release date for Japan.

All models are lighter than the conventional ones.


Ex: Models FXFQ25L-50L are 4.5 kg lighter
(reduced from 24 kg to 19.5 kg).
Drain pump is equipped as
standard accessory, and the
850 mm
lift height has been improved
from 750 mm to 850 mm.
A modern sophisticated decoration panel has
been applied, with a panel surface that has been
treated with a dirt-repellant coating.
Treated surface

Untreated surface

Dirt and
grime Condition after
exposure to the
smoke of 600
3
cigarettes in 1 m
enclosed space.

Resists
soiling

Control of the airflow rate has been improved


from 2-step to 3-step control.

Low operation sound level


FXFQ-L

25/32

40

50

(dB(A))
63

80

100

125

Sound
level
30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32 44/39/34
(HH/H/L)

Example of airflow patterns:

All-round flow

Comfortable airflow
1

Wide discharge angle: 0 to 60


Fixed angles: 5 levels

Auto swing

An antibacterial treatment that uses silver ions


has been applied to the drain pan, preventing
the growth of slime, mould and bacteria that
cause blockages and odours.
The horizontal louvres prevent dew
condensation. Their non-flocking surfaces, which
repel dirt, are easy to clean.
The air filter has an anti-mould and antibacterial
treatment that prevents the growth of mould
generated from dust or moisture that may
adhere to the filter.
4-way flow

3-way flow

L-shaped 2-way flow

0
60

60

0
60

60

Angles can be also set on site to prevent drafts (0-35)


or soiling of the ceiling (25-60), other than standard setting (0-60).

2-, 3-, and 4-way airflow patterns are available,


enabling installation in the corner of a room.
Drain pump is equipped as standard
accessory with 750 mm lift.

4-way flow

3-way flow

L-shaped
2-way flow

750 mm

For 3-way or 2-way flow installation, the sealing member for air discharge
outlet (option) must be used to close each unused outlet.

360 airflow is available, as well as 2- to


4-way flows, so you can choose the most
suitable airflow pattern depending on
location or room layout.

15

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing member (option) must be used to close each unused outlet.

16

INDOOR UNIT LINEUP


Ceiling Mounted Cassette
(Double Flow) Type

Ceiling Mounted Cassette


Corner Type
FXKQ25MA /FXKQ32MA
FXKQ40MA /FXKQ63MA

FXCQ20M/FXCQ25M/FXCQ32M
FXCQ40M/ FXCQ50M/ FXCQ63M
FXCQ80M/FXCQ125M

Thin, lightweight, and easy to install in


shallow ceiling spaces

Slim design for flexible installation


Slim body needs only 220 mm space above
the ceiling. If you use a panel spacer (option),
the unit can be installed in the minimum space
of 195 mm.

The low profile unit (only 305 mm high) can


be installed in a ceiling space as shallow
as 350 mm. All models feature a compact
design with a depth of only 600 mm.

Min.195 mm
305 mm

Panel spacer
20 mm

(When a high-efficiency filter is attached, the


unit's height is 400 mm.)

Single-flow type allows effective air discharge


from corner or from drop-ceiling.

Low operation sound level

Drain pump is equipped as standard


accessory with 500 mm lift.

FXCQ-M

20

25/32 40/50

(dB(A))
63

80

125

Sound level 220 V 32/27 34/28 34/29 37/32 39/34 44/38


(H/L)
240 V 34/29 36/30 37/32 39/34 41/36 46/40

500 mm

Providing 3 different settings of standard,


draft prevention and ceiling soiling
prevention, the auto swing mechanism
achieves even distribution of airflow and
room temperature.
(m)
3
2

28C
32C 30C

Drain pump is equipped as standard


accessory with 600 mm lift.

600 mm

24C
22C

1
0

20C
1

6 (m)

Front discharge is possible with an air


discharge unit (option), which allows the
installation in the drop-ceiling or sagging wall.
Main body

Designed with higher airflow suitable for


high ceiling application up to 3 metres.
Providing 2 different settings of standard
and ceiling soiling prevention, the auto
swing mechanism achieves even
distribution of airflow and room
temperature.

26C

Downward discharge

Air discharge grille (Option)

Two types of optional high-efficiency filter are


available (65% and 95%, colourimetric method).
A long-life filter (maintenance free up to one
year ) is equipped as standard accessory.
8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Major maintenance work can be performed by


removing the panel. A flat-type suction grille
and a detachable blade make cleaning easy.

Set for front discharge using a suspended ceiling.

Main body

Air discharge grille


(Option)

Downward discharge is shut off and air is blown straight out


(front discharge).

A long-life filter (maintenance free up to one


year ) is equipped as standard accessory.
8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

17

18

INDOOR UNIT LINEUP


Slim Ceiling Mounted
Duct Type

Ceiling Mounted
Duct Type
FXMQ20P/FXMQ25P/ FXMQ32P
FXMQ40P/FXMQ50P/ FXMQ63P
FXMQ80P/FXMQ100P/ FXMQ125P
FXMQ140P

Slim design, quietness and


static pressure switching
Suited to use in drop-ceilings!
FXDQ20PB/FXDQ25PB/FXDQ32PB
Only 700 mm in width and 23 kg in weight, this
model is suitable to install in limited spaces like
drop-ceilings in hotels.

Only 200 mm in height, this model can be


installed in rooms with as little as 240 mm depth
between the drop-ceiling and ceiling slab.

200 mm

900 mm

200 mm

700 mm

1,100 mm in width for the FXDQ63NB model.

Suspension bolt*

Air filter

240 mm

AIR
Discharge grille*
AIR

Suction grille*

*To be obtained locally

External static pressure selectable by remote


controller switching make this indoor unit a very
comfortable and flexible model.
10 Pa-30 Pa/factory set: 10 Pa for FXDQ-PB models.
15 Pa-44 Pa/factory set: 15 Pa for FXDQ-NB models.

FXDQ-PB and FXDQ-NB models are available in


two types to suit different installation conditions.
Control of the airflow rate has been improved
from 2-step to 3-step control.
Low operation sound level

(dB(A))

FXDQ-PB/NB

20/25/32

40

50

63

Sound level
(HH/H/L)

33/31/29

34/32/30

35/33/31

36/34/32

The values of operation sound level represent those for rear-suction operation.
Sound level values for bottom-suction operation can be obtained by adding 5 dB(A).
Values are based on the following conditions:
FXDQ-PB: external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.

19

A DC fan motor increases the external static


pressure capacity range to include middle to high
static pressures, increasing design flexibility.

30 Pa100 Pa for FXMQ20P-32P


30 Pa160 Pa for FXMQ40P
50 Pa200 Pa for FXMQ50P-125P
50 Pa140 Pa for FXMQ140P

Great for
hotel use!

Only

Middle and high static pressure


allows for flexible duct design

FXDQ40NB/FXDQ50NB/FXDQ63NB

FXDQ-PB/NBVE: with a drain pump (750 mm lift)


as a standard accessory

750 mm

Ceiling

All models are only 300 mm in height, an


improvement over the 390 mm height of
conventional models. The weight of the
FXMQ40P has been reduced from 44 kg to
28 kg.

300 mm
Easy installation in buildings
with narrow ceiling spaces

Drain pump is equipped as standard accessory


with 700 mm lift.
700 mm
Ceiling

Control of the airflow rate has been improved


from 2-step to 3-step control.
Low operation sound level

FXMQ-P 20/25

32

40

50

(dB(A))
63

80/100

125

140

Sound
level 33/31/29 34/32/30 39/37/35 41/39/37 42/40/38 43/41/39 44/42/40 46/45/43
(HH/H/L)

Energy-efficient
The adopted DC fan motor is much more
efficient than the conventional AC motor,
yielding an approximate 20% decrease in
energy consumption. (FXMQ125P)

Improved ease of installation


Airflow rate can be controlled using a remote
controller during test operation.
conventional model, the airflow rate was controlled
from the PC board. It is automatically adjusted to
the range between approximately 10% of the rated
HH tap airflow for FXMQ20P-125P.
Improved ease of maintenance
The drain pan can be detached for easy
cleaning. An antibacterial treatment that uses
silver ions has been applied to the drain pan,
preventing the growth of slime, mould and
bacteria that cause blockages and odours.
20

INDOOR UNIT LINEUP


Ceiling Suspended Type

Wall Mounted Type

FXHQ32MA/FXHQ63MA
FXHQ100MA

Stylish flat panel design harmonised


with your interior dcor

Slim body with quiet and wide airflow

Stylish flat panel design creates a graceful


harmony that enhances any interior space.

Adoption of QUIET STREAM FAN


Uses the quiet stream fan and many
advanced technologies.

Turbulent ow
is produced

Flat panel can be cleaned with only the single


pass of a cloth across their smooth surface.
Flat panel can also be easily removed and
washed for more thorough cleaning.

Sound absorption
material

Low operation sound level

Quiet stream fan


Straightening vane

Low operation sound level

FXAQ-P

Sound level
(H/L)

(dB(A))

FXHQ-MA

32

63

Sound level
(H/L)

36/31

39/34

100

Wide air discharge openings produce a


spreading 100 airflow.

Maintenance is easy
Non-dew Flap with no implanted bristles
Bristle-free Flap minimises
contamination and makes
cleaning simpler.

Easy-to-clean at design

Non-dew Flap

Maintenance is easier because servicing can


be performed from below the unit.
A long-life lter (maintenance free up to one
year) is equipped as standard accessory.

21

25

32

40

50

63

35/31

36/31

38/31

39/34

42/37

47/41

Vertical auto-swing realises efficiency of air


distribution. The louvre closes automatically
when the unit stops.

600 mm

Drain pump kit


(built inside main unit)

(dB(A))

20

Drain pan and air filter can be kept clean by


mould-proof polystyrene.

45/37

Installation is easy
Drain pump kit (option) can be easily
incorporated.

100

FXAQ20P/FXAQ25P
FXAQ32P/FXAQ40P
FXAQ50P/FXAQ63P

New

5 steps of discharge angle can be set by


remote controller.
Discharge angle is automatically set at the
same angle as the previous operation when
restarting. (Initial setting: 10 for cooling and
70 for heating)
Flexible installation
Drain pipe can be tted to from either left or
right sides.

Drain pump kit is available as optional accessory,


which lifts the drain 1,000 mm from the bottom of
the unit.
Height of drain-up

1,000 mm

Drain pump kit

Indoor unit

22

INDOOR UNIT LINEUP


Connection unit series indoor units

Ceiling Suspended
Cassette Type (50 Hz only)

Floor Standing Type


FXLQ20MA/ FXLQ25MA
FXLQ32MA/FXLQ40MA
FXLQ50MA/ FXLQ63MA

FXUQ71MA
FXUQ100MA
FXUQ125MA

This thin indoor unit achieves optimum


air distribution, and can be installed
without the need for ceiling cavity

Suitable for perimeter zone air conditioning


Floor Standing types can be hung on the wall for easier floor
cleaning. Running the piping from the back allows the unit to be
hung on walls. Cleaning under the unit, where dust tends to
accumulate, is considerably easier.

Depending on installation site requirements or


room conditions, 2-way, 3-way and 4-way
discharge patterns are available.

The adoption of a fibre-less discharge grille featuring an original


design to prevent condensation also helps prevent staining and
makes cleaning easier.

4-way airflow
from the centre of the store.

A long-life filter (maintenance free up to one year ) is equipped


as standard accessory.
8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

Wall hanging

The 3-way airflow can distribute


comfortable air throughout the room.

Floor installation

Concealed Floor
Standing Type

Only one unit is needed to distribute comfortable air


throughout an L-shaped store.

FXNQ20MA/ FXNQ25MA
FXNQ32MA/ FXNQ40MA
FXNQ50MA/ FXNQ63MA

Designed to be concealed in the perimeter skirting-wall


The unit is concealed in skirting-wall of perimeter, that enables
to create high class interior design.
The connecting port faces
downward, greatly facilitating
on-site piping work.
A long-life filter (maintenance
free up to one year ) is equipped
as standard accessory.
8 hr/day, 25 day/month. For dust concentration of 0.15 mg/m3

23

Connection unit

Connection unit is the device for connecting above indoor unit to VRVIII-S.

BEVQ71MA/BEVQ100MA/BEVQ125MA
Refrigerant piping layout

External wiring layout


Connection unit for indoor unit

Liquid
pipe

Gas pipe

BEVQ-MAVE

Super wiring ( DIII-NET )


Single-phase 220-240 V
power supply
Indoor unit

Refrigerant
piping
Applies also to Floor Standing type (FXLQ-MA).

Piping length*1

Model
FXUQ-MA

VRV -S series
outdoor unit

Connecting
port

*1

Indoor unit
Remote controller

Maximum piping length


between the BEV unit
and the indoor unit.
5m

Notes:
When connecting centralised-control device, it is
necessary to install an interface adaptor for an
indoor unit (DTA102A52).
Connection unit BEVQ-MA is necessary for each
indoor unit.
The refrigerant piping height difference between
the indoor units and the BEV unit must be within
4 m.
The BEV unit must be installed within a
maximum height difference between indoor units
of 15 m.
Branching of the refrigerant piping is not
possible downstream of the BEV unit.

24

SPECIFICATIONS
INDOOR UNITS

Ceiling Mounted Cassette (Double Flow) Type

Power supply

Cooling capacity

Heating capacity

kcal/h(*1)

2,500

3,200

4,000

5,000

6,300

8,000

10,000

12,500

Btu/h(*1)

9,900

12,600

16,000

19,800

24,900

31,700

39,600

49,500

kW (*1)

2.9

3.7

4.7

5.8

7.3

9.3

11.6

14.5

(*2)

2.8

3.6

4.5

5.6

7.1

9.0

11.2

kcal/h

2,800

3,400

4,300

5,400

6,900

8,600

10,800

13,800

Btu/h

10,900

13,600

17,100

21,500

27,300

34,100

42,700

54,600

kW

3.2

4.0

5.0

6.3

8.0

10.0

12.5

16.0

m3/min
cfm

Sound level (HH/H/L)


Dimensions (HXWXD)
Machine weight
Liquid (Flare)
Piping
connections Gas (Flare)
Drain

dB(A)
mm
kg
mm

13/11.5/10 13/11.5/10 15/13/11 16/13.5/11 19/16.5/13.5 21/18/15

459/406/353 459/406/353 530/459/388 565/477/388 671/583/477 742/636/530 1,130/918/706 1,165/989/794


30/28.5/27 30/28.5/27 31/29/27 32/29.5/27 34/31/28 36/33.5/31 43/37.5/32
19.5

19.5

19.5

19.5

22

22

25

25

6.4

6.4

6.4

6.4

9.5

9.5

9.5

9.5

12.7

12.7

12.7

12.7

15.9

15.9

15.9

15.9

VP25 (External Dia, 32/Internal Dia, 25)


BYCP125K-W1

Colour

Fresh white

Weight

44/39/34

246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 246X840X840 288X840X840 288X840X840

Model
Dimensions (HXWXD)

32/26/20 33/28/22.5

mm
kg

5.5

5.5

5.5

5.5

5.5

5.5

5.5

FXZQ20MVE FXZQ25MVE FXZQ32MVE FXZQ40MVE FXZQ50MVE

Power supply

Cooling capacity

Heating capacity

2,000

2,500

3,200

4,000

5,000

Btu/h(*1)

7,800

9,900

12,600

16,000

19,800

kW (*1)

2.3

2.9

3.7

4.7

5.8

(*2)

2.2

2.8

4.5

5.6

kcal/h

2,200

2,800

3,400

4,300

5,400

Btu/h

8,500

10,900

13,600

17,100

21,500

kW

2.5

3.2

4.0

5.0

6.3

Casing

Galvanised steel plate

Airflow rate (H/L)


Sound level
230 V, 50 Hz-240 V,
(H/L)
50 Hz-220 V,
Dimensions (HXWXD)
Machine weight
Liquid (Flare)

Piping
connections Gas (Flare)
Drain
Panel
(Option)

3.6

m3/min

9/7

9/7

9.5/7.5

11/8

14/10

cfm

318/247

318/247

335/265

388/282

493/353

dB(A)

30/25-32/26-32/29 30/25-32/26-32/29 32/26-34/28-33/29 36/28-37/29-36/30 41/33-42/35-41/34

mm
kg
mm

18
6.4

6.4

6.4

6.4

12.7

12.7

12.7

12.7

12.7

VP20 (External Dia, 26/Internal Dia, 20)


BYFQ60B8W1

Colour

White (6.5Y9.5/0.5)

Dimensions (HXWXD)

220 V
240 V

Dimensions (HXWXD)
Machine weight

Liquid (Flare)

Piping
connections Gas (Flare)
Drain

mm

55X700X700

55X700X700

55X700X700

55X700X700

55X700X700

kg

2.7

2.7

2.7

2.7

2.7

3,200

4,000

5,000

6,300

8,000

12,500

9,900

12,600

16,000

19,800

24,900

31,700

49,500

kW (*1)

2.3

2.9

3.7

4.7

5.8

7.3

9.3

14.5

kcal/h

2,200

2,800

3,400

4,300

5,400

6,900

8,600

13,800

Btu/h

8,500

10,900

13,600

17,100

21,500

27,300

34,100

54,600

kW

2.5

3.2

4.0

5.0

6.3

8.0

10.0

16.0

2.2

2.8

3.6

4.5

5.6

7.1

9.0

14.0

m3/min

7/5

9/6.5

9/6.5

12/9

12/9

16.5/13

26/21

33/25

cfm

247/177

318/230

318/230

424/318

424/318

582/459

918/741

1,165/883

dB(A)

32/27

34/28

34/28

34/29

34/29

37/32

39/34

44/38

mm

305X775X600

305X775X600

305X775X600

305X990X600

kg

26

26

26

31

mm

34/29

36/30

36/30

37/32

37/32

39/34

41/36

46/40

305X990X600 305X1,175X600 305X1,665X600 305X1,665X600


32

35

47

48

6.4

6.4

6.4

6.4

6.4

9.5

9.5

9.5

12.7

12.7

12.7

12.7

12.7

15.9

15.9

15.9

VP25 (External Dia, 32/Internal Dia, 25)

Model

BYBC32G-W1

BYBC50G-W1

BYBC63G-W1

BYBC125G-W1

White (10Y9/0.5)

Colour
Dimensions (HXWXD)
Weight

mm
kg

53X1,030X680 53X1,030X680 53X1,030X680 53X1,245X680 53X1,245X680 53X1,430X680 53X1,920X680 53X1,920X680


8.0

8.0

8.0

8.5

8.5

9.5

12.0

12.0

Ceiling Mounted Cassette Corner Type


MODEL

FXKQ25MAVE

Power supply

Cooling capacity

Heating capacity

FXKQ40MAVE

FXKQ63MAVE

kcal/h(*1)

2,500

3,200

4,000

6,300

Btu/h(*1)

9,900

12,600

16,000

24,900

kW (*1)

2.9

3.7

4.7

7.3

(*2)

2.8

3.6

4.5

7.1

kcal/h

2,800

3,400

4,300

6,900

Btu/h

10,900

13,600

17,100

27,300

kW

3.2

4.0

5.0

8.0

Galvanised steel plate

Airflow rate (H/L) 50 Hz


Sound level (H/L) 220 V
240 V

Dimensions (HXWXD)
Machine weight

m3/min

11/9

11/9

13/10

18/15

cfm

388/318

388/318

459/353

635/530

40/35

40/35

42/36

dB(A)

38/33

38/33

42/37
44/39

215X1,110X710

215X1,110X710

215X1,110X710

215X1,310X710

kg

31

31

31

34

mm

6.4

6.4

6.4

9.5

12.7

12.7

12.7

15.9

VP25 (External Dia, 32/Internal Dia, 25)


BYK45FJW1

Colour
Dimensions (HXWXD)

40/34

mm

Model
Panel
(Option)

FXKQ32MAVE

1-phase, 220- 240 V/220 V, 50 Hz

Casing

Weight

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1)27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2)27CDB, 19CWB,
Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent
piping length: 7.5 m, Level difference: 0 m.Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity
index. Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.

25

Sound level (H/L)

Piping
connections Gas (Flare)
Drain

6.4

Model

Weight

Airflow rate (H/L)

Liquid (Flare)

286X575X575

2,500

7,800

Galvanised steel plate

1-phase, 220-240 V/220 V, 50 Hz


kcal/h(*1)

2,000

Btu/h(*1)

Casing

Panel
(Option)

Ceiling Mounted Cassette (Compact Multi Flow) Type


MODEL

Heating capacity

50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950 50X950X950


5.5

kcal/h(*1)

(*2)

14.0

Galvanised steel plate

Airflow rate (HH/H/L)

1-phase, 220 - 240 V/220 V, 50 Hz

Cooling capacity

1-phase, 220 -240 V/220 V, 50 Hz

Casing

Panel
(Option)

Power supply

FXFQ25LU FXFQ32LU FXFQ40LU FXFQ50LU FXFQ63LU FXFQ80LU FXFQ100LU FXFQ125LU

MODEL

FXCQ20MVE FXCQ25MVE FXCQ32MVE FXCQ40MVE FXCQ50MVE FXCQ63MVE FXCQ80MVE FXCQ125MVE

MODEL

Ceiling Mounted Cassette (Round Flow) Type

BYK71FJW1

White (10Y9/0.5)
mm

70X1,240X800

70X1,240X800

70X1,240X800

70X1,440X800

kg

8.5

8.5

8.5

9.5

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1)27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m. (*2)27CDB, 19CWB, Outdoor
temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping
length: 7.5 m, Level difference: 0 m.Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index. Sound
level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre. During actual operation, these values are normally
somewhat higher as a result of ambient conditions.

26

SPECIFICATIONS
Slim Ceiling Mounted Duct Type (700 mm width type)
MODEL
Power supply

with
drain pump

Cooling capacity

FXDQ25PBVE
2,500

3,200

Btu/h(*1)

7,800

9,900

12,600

(*1)

2.3

2.9

3.7

(*2)

2.2

2.8

3.6

kcal/h

2,200

2,800

3,400

Btu/h

8,500

10,900

13,600

kW

2.5

3.2

4.0

m3/min

8.0/7.2/6.4

8.0/7.2/6.4

8.0/7.2/6.4

cfm

282/254/226

282/254/226

282/254/226

Galvanised steel plate

Airflow rate (HH/H/L)


External static pressure
Sound level (HH/H/L) 2 3
Dimensions (HXWXD)
Machine weight

Pa

Piping
connections Gas (Flare)
Drain

30-10 1

dB(A)

33/31/29

33/31/29

33/31/29

mm

200X700X620

200X700X620

200X700X620

kg

23

23

23

Liquid (Flare)
mm

6.4

6.4

6.4

12.7

12.7

12.7

VP20 (External Dia, 26/Internal Dia, 20)

Cooling capacity

with
drain pump

FXDQ40NBVE

Heating capacity

kcal/h(*1)

4,000

5,000

6,300

Btu/h(*1)

16,000

19,800

24,900

(*1)

4.7

5.8

7.3

(*2)

4.5

5.6

7.1

kcal/h

4,300

5,400

6,900

Btu/h

17,100

21,500

27,300

kW

5.0

6.3

8.0

kW

Heating capacity
Casing
Airflow rate (HH/H/L)
External static pressure
Sound level (HH/H/L) 2 3
Dimensions (HXWXD)
Machine weight
Liquid (Flare)
Piping
connections Gas (Flare)
Drain

FXDQ63NBVE

Galvanised steel plate


10.5/9.5/8.5

12.5/11.0/10.0

16.5/14.5/13.0

cfm

371/335/300

441/388/353

583/512/459

Pa

44-15 1

dB(A)

34/32/30

35/33/31

36/34/32

mm

200X900X620

200X900X620

200X1,100X620

kg

27

28

31

6.4
mm

12.7

6.4

9.5

12.7

15.9

VP20 (External Dia, 26/Internal Dia, 20)

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1) 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) 27CDB, 19CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1: External static pressure is changeable to set by the remote controller. This pressure means "High static pressure - Standard". (Factory setting is 10 Pa for
FXDQ-PB models and 15 Pa for FXDQ-NB models.)
2: The values of operation sound level represent those for rear-suction operation. Sound level values for bottom-suction operation can be
obtained by adding 5 dB(A).
3: Values are based on the following conditions: FXDQ-PB external static pressure of 10 Pa; FXDQ-NB: external static pressure of 15 Pa.

27

2,500

3,200

4,000

5,000

Btu/h(*1)

7,800

9,900

12,600

16,000

19,800

(*1)

2.3

2.9

3.7

4.7

5.8

(*2)

2.2

2.8

3.6

4.5

5.6

kcal/h

2,200

2,800

3,400

4,300

5,400

Btu/h

8,500

10,900

13,600

17,100

21,500

kW

2.5

3.2

4.0

5.0

6.3

m3/min

9/7.5/6.5

9/7.5/6.5

9.5/8/7

16/13/11

18/16.5/15

cfm

318/265/230

318/265/230

335/282/247

565/459/388

635/582/530

Pa

30-100

30-100

30-100

30-160

50-200

Galvanised steel plate

Airflow rate (HH/H/L)


External static pressure

Sound level (HH/H/L)

dB(A)

33/31/29

33/31/29

34/32/30

39/37/35

41/39/37

Dimensions (HXWXD)

mm

300X550X700

300X550X700

300X550X700

300X700X700

300X1,000X700

kg

25

25

25

28

36

6.4

6.4

6.4

6.4

6.4

12.7

12.7

12.7

12.7

12.7

Machine weight
Liquid (Flare)

Piping
connections Gas (Flare)
Drain

mm

VP25 (External Dia, 32/Internal Dia, 25)

MODEL

FXMQ63PVE FXMQ80PVE FXMQ100PVE FXMQ125PVE FXMQ140PVE


1-phase, 220-240 V/220 V, 50 Hz

Power supply

Cooling capacity

kcal/h(*1)

6,300

8,000

10,000

12,500

14,300

Btu/h(*1)

24,900

31,700

39,600

49,500

57,000

(*1)

7.3

9.3

11.6

14.5

16.7

(*2)

7.1

9.0

11.2

14.0

16.0

kW

Heating capacity

kcal/h

6,900

8,600

10,800

13,800

15,500

Btu/h

27,300

34,100

42,700

54,600

61,400

kW

8.0

10.0

12.5

16.0

18.0

39/33/28

46/39/32

Casing

Galvanised steel plate

Airflow rate (HH/H/L)

m3/min

2,000

Casing

1-phase, 220-240 V/220 V, 50 Hz

Power supply

Cooling capacity

FXDQ50NBVE

1-phase, 220-240 V/220 V, 50 Hz


kcal/h(*1)

kW

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


MODEL

FXMQ20PVE FXMQ25PVE FXMQ32PVE FXMQ40PVE FXMQ50PVE

Power supply

2,000

Casing

MODEL

FXDQ32PBVE

1-phase, 220-240 V/220 V, 50 Hz

kcal/h(*1)

kW

Heating capacity

FXDQ20PBVE

Ceiling Mounted Duct Type

External static pressure

m3/min

19.5/17.5/16

25/22.5/20

32/27/23

cfm

688/618/565

883/794/706

1,130/953/812

Pa

50-200

50-200

50-200

1,377/1,165/988 1,624/1,377/1,130
50-200

50-140

Sound level (HH/H/L)

dB(A)

42/40/38

43/41/39

43/41/39

44/42/40

46/45/43

Dimensions (HXWXD)

mm

300X1,000X700

300X1,000X700

300X1,400X700

300X1,400X700

300X1,400X700

kg

36

36

46

46

47

9.5

9.5

9.5

9.5

9.5

15.9

15.9

15.9

15.9

15.9

Machine weight
Liquid (Flare)

Piping
connections Gas (Flare)
Drain

mm

VP25 (External Dia, 32/Internal Dia, 25)

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1) 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) 27CDB, 19CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m downward from the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
1: External static pressure can be modified using a remote controller that offers seven (FXMQ20-32P), thirteen (FXMQ40P), fourteen (FXMQ50125P) or ten (FXMQ140P) levels of control. These values indicate the lowest and highest possible static pressures. The standard static
pressure is 50 Pa for FXMQ20-32P and 100 Pa for FXMQ40-140P.

28

SPECIFICATIONS
Ceiling Suspended Type

Floor Standing Type/Concealed Floor Standing Type


FXHQ32MAVE

MODEL

FXHQ63MAVE

Power supply

Cooling capacity

Heating capacity

MODEL

FXHQ100MAVE

FXNQ20MAVE FXNQ25MAVE FXNQ32MAVE FXNQ40MAVE FXNQ50MAVE FXNQ63MAVE

1-phase, 220-240 V/220 V, 50 Hz


kcal/h(*1)

3,200

6,300

10,000

Btu/h(*1)

12,600

24,900

39,600

kW (*1)

3.7

7.3

11.6

(*2)

3.6

7.1

11.2

kcal/h

3,400

6,900

10,800

Btu/h

13,600

27,300

42,700

kW

4.0

8.0

12.5

Casing

Power supply

FXLQ

1-phase, 220 - 240 V/220 V, 50 Hz

Cooling capacity

Heating capacity

White (10Y9/0.5)

Airflow rate (H/L)


Sound level (H/L)
Dimensions (HXWXD)
Machine weight
Liquid (Flare)

Piping
connections Gas (Flare)
Drain

m3/min

12/10

17.5/14

25/19.5

cfm

424/353

618/494

883/688

dB(A)

36/31

39/34

45/37

mm

195X960X680

195X1,160X680

195X1,400X680

kg

24

28

33

mm

FXNQ

6.4

9.5

9.5

12.7

15.9

15.9

Airflow rate (H/L)


Sound level (H/L) 220 V
Dimensions
(HXWXD)
Machine weight

Wall Mounted Type


FXAQ20PVE FXAQ25PVE FXAQ32PVE FXAQ40PVE FXAQ50PVE FXAQ63PVE
1-phase, 220 -240/220V, 50 Hz
kcal/h(*1)

2,000

2,500

3,200

4,000

5,000

6,300

Btu/h(*1)

7,800

9,900

12,600

16,000

19,800

24,900

kW (*1)

2.3

2.9

3.7

4.7

5.8

7.3

2.2

2.8

3.6

4.5

5.6

7.1

kcal/h

2,200

2,800

3,400

4,300

5,400

6,900

Btu/h

8,500

10,900

13,600

17,100

21,500

27,300

kW

2.5

3.2

4.0

5.0

6.3

8.0

(*2)
Heating capacity

Casing

2,500

3,200

4,000

5,000

6,300

Btu/h(*1)

7,800

9,900

12,600

16,000

19,800

24,900

kW (*1)

2.3

2.9

3.7

4.7

5.8

7.3

(*2)

2.2

2.8

3.6

4.5

5.6

7.1

kcal/h

2,200

2,800

3,400

4,300

5,400

6,900

Btu/h

8,500

10,900

13,600

17,100

21,500

27,300

kW

2.5

3.2

4.0

5.0

6.3

8.0

FXLQ: Ivory white (5Y7.5/1) / FXNQ: Galvanised steel plate

FXLQ

m3/min

7/6

7/6

8/6

11/8.5

14/11

16/12

cfm

247/212

247/212

282/212

388/300

494/388

565/424

dB(A)

35/32

35/32

35/32

38/33

39/34

40/35

37/34

37/34

37/34

40/35

41/36

42/37

600X1,000X222

600X1,000X222

600X1,140X222

600X1,140X222

600X1,420X222

600X1,420X222

610X930X220

610X930X220

610X1,070X220

610X1,070X220

610X1,350X220

610X1,350X220

25

25

30

30

36

36

19

19

23

23

27

27

mm

FXNQ
FXLQ

kg

FXNQ

Piping
connections Gas (Flare)
Drain

Power supply

2,000

240 V

VP20 (External Dia, 26/Internal Dia, 20)

MODEL

kcal/h(*1)

Casing

Liquid (Flare)

Cooling capacity

FXLQ20MAVE FXLQ25MAVE FXLQ32MAVE FXLQ40MAVE FXLQ50MAVE FXLQ63MAVE

mm

6.4

6.4

6.4

6.4

6.4

9.5

12.7

12.7

12.7

12.7

12.7

15.9

21O.D.

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1) 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) 27CDB, 19CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

White (3.0Y8.5/0.5)

Airflow rate (H/L)

m3/min

7.5/4.5

8/5

8.5/5.5

12/9

15/12

19/14

cfm

265/159

282/177

300/194

424/318

530/424

671/494

Sound level (H/L)

dB(A)

35/31

36/31

38/31

39/34

42/37

47/41

mm

290X795X238

290X795X238

290X795X238

290X1,050X238

290X1,050X238

290X1,050X238

kg

11

11

11

14

14

14

mm

6.4

6.4

6.4

6.4

6.4

9.5

12.7

12.7

12.7

12.7

12.7

15.9

Dimensions (HXWXD)
Machine weight
Liquid (Flare)

Piping
connections Gas (Flare)
Drain

VP13 (External Dia, 18/Internal Dia, 13)

Note : Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1) 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) 27CDB, 19CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit and 1 m downward.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

29

30

SPECIFICATIONS
OUTDOOR UNITS

Connection unit series indoor units

* A type of BEV unit is necessary for each Connection unit series indoor unit.
* If indoor units from the Connection unit series are connected within a single refrigerant system to indoor units from any other
series, cooling/heating switchover will not be possible using the remote controller of the Connection unit series indoor units.
However, if the remote controller of an indoor unit from the other series is set as a master remote controller, cooling/heating
switchover will be possible.
* If all indoor units are from the Connection unit series, an outdoor unit Cool/Heat selector will be needed to enable
cooling/heating switchover.
* Group control between Connection Unit series equipment within one system is possible. However, group control with the other
VRV indoor units is not possible.

Cooling Only
MODEL
Power supply

Kcal/h

Cooling capacity
Power consumption
Capacity control

Ceiling Suspended Cassette Type (50 Hz only)


MODEL

Indoor unit

FXUQ71MAV1

Connection unit

BEVQ71MAVE

Power supply

Kcal/h(*1)
Btu/h(*1)

Cooling capacity

Indoor unit

BEVQ125MAVE

7,100

10,000

12,500

28,300

39,600

49,500

8.3

11.6

14.5

(*2)

8.0

11.2

14.0

Kcal/h

7,700

10,800

12,000

Btu/h

30,700

42,700

47,800

kW

9.0

12.5

14.0

230 V

Dimensions (HXWXD)
Machine weight

m /min

19/14

29/21

32/23

cfm

671/494

1,024/741

1,130/812

dB(A)

40/35

43/38

44/39

mm

165X895X895

230X895X895

230X895X895

kg

25

31

31

Liquid
Gas
Drain

9.5 (Flare)
mm

Motor output

Airflow rate

Dimensions (H x W x D)
Sound level

VP 20 (External Dia. 26/Internal Dia. 20)

12,000

Operation range

Type

Refrigerant

Charge
Liquid

Piping
connections

Gas

RXMQ6PVE
13,300

38,200

47,700

52,900

kW

2.95

3.97

4.44

kW

kW

m /min

11.2

14.0

24 to 100

kg

CDB

15.5

Ivory white (5Y7.5/1)

Hermetically sealed scroll type

2.5

3.0

106

mm

dB(A)

3.5

1,345 x 900 x 320


125

50

51

-5 to 46

53

R-410A

kg

4.0

mm

15.9 (Flare)

9.5 (Flare)

19.1 (Brazing)

Heat Pump
MODEL
Power supply

RXYMQ4PVE
Kcal/h

Cooling capacity

Heating capacity
Power
consumption

Heating

Capacity control
Compressor
Airflow rate

Type

Motor output

Machine weight

Kcal/h

10,800

13,800

15,500

kW

12.5

16.0

kW

kW

m /min

Refrigerant
Piping
connections

11.2

14.0

42,700

54,600

2.95
3.27

kg

CDB

Heating

CWB

Charge

kg

Type

Liquid
Gas

mm

15.5

61,400
18.0

3.97

4.44

4.09

4.82

24 to 100

Ivory white (5Y7.5/1)

2.5

mm

Sound level (Cooling/Heating) dB(A)


Cooling

13,300

52,900

Hermetically sealed scroll type


3.0

106

Dimensions (H x W x D)

Operation
range

12,000

47,800

Casing colour

1-phase, 220-230 V, 50 Hz/220 V

RXYMQ6PVE

38,200

Btu/h

Cooling

9,600

RXYMQ5PVE

Btu/h
kW

15.9 (Flare)

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: (*1) 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
(*2) 27CDB, 19CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Capacity of indoor unit is only for reference. Actual capacity of indoor unit is based on the total capacity index.
Sound level: Anechoic chamber conversion value, measured at a point 1.5 m below the unit centre.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.

1-phase, 220-230 V, 50 Hz/220 V

9,600

Machine weight

White(10Y9/0.5)

Airflow rate (H/L)

Piping
connections

BEVQ100MAVE
1-phase, 220-240 V, 50 Hz

Casing

Sound level (H/L)

FXUQ125MAV1

(*1)

kW

Heating capacity (Max.)

FXUQ100MAV1

Type

RXMQ5PVE

Btu/h

Casing colour
Compressor

RXMQ4PVE

3.5

1,345 x 900 x 320


125

50/52

51/53

-5 to 46

53/55

-20 to 15.5
R-410A
4.0

15.9 (Flare)

9.5 (Flare)

19.1 (Brazing)

Note: Specifications are based on the following conditions;


Cooling: Indoor temp.: 27CDB, 19.5CWB, Outdoor temp.: 35CDB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Heating: Indoor temp.: 20CDB, Outdoor temp.: 7CDB, 6CWB, Equivalent piping length: 7.5 m, Level difference: 0 m.
Sound level: Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During
actual operation, these values are normally somewhat higher as a result of ambient conditions.
Refrigerant charge is required.

31

32

OPTION LIST
INDOOR UNITS
Ceiling Mounted Cassette (Round Flow) Type
No.
1
2
3

Type FXFQ25L FXFQ32L FXFQ40L FXFQ50L FXFQ63L FXFQ80L FXFQ100L FXFQ125L

Item

Decoration Panel
Sealing member of air discharge outlet
Panel spacer
High efficiency filter unit 65%
High efficiency filter unit 90%
Replacement high efficiency filter 65%
Replacement high efficiency filter 90%
Filter related
Filter chamber
Long life replacement filter Non-woven type
Ultra long-life filter
Replacement ultra long-life filter
Without T shape and fan
Chamber type
With T shape without fan
Fresh air intake kit
Direct installation type
Branch duct chamber
Chamber connection kit
Insulation kit for high humidity

5
6
7
8

BYCP125K-W1
KDBH55K160F
KDBP55H160FA
KAFP556B80
KAFP557B80
KAFP552B80
KAFP553B80
KDDFP55B160
KAFP551K160
KAFP55B160
KAFP55H160H
KDDP55B160
KDDP55B160K
KDDP55X160
KDJP55B80
KKSJ55KA160
KDTP55K80

KAFP556B160
KAFP557B160
KAFP552B160
KAFP553B160

Type

Item

FXZQ20M

FXZQ25M

Decoration panel
Sealing member of air discharge outlet
Panel spacer
Replacement long-life filter
Fresh air intake kit
Direct installation type

1
2
3
4
5

FXZQ32M

KDJP55B160
KDTP55K160

FXZQ40M

FXZQ50M

Decoration Panel

2
Note:

FXCQ25M
FXCQ32M

Item

Filter related

High efficiency filter 65% 1


High efficiency filter 90% 1
Filter chamber bottom suction
Long life replacement filter

1 Filter chamber is required if installing high efficiency filter.

FXCQ40M

BYBC32G-W1
KAFJ532G36
KAFJ533G36
KDDFJ53G36
KAFJ531G36

FXCQ50M

BYBC50G-W1
KAFJ532G56
KAFJ533G56
KDDFJ53G56
KAFJ531G56

Item

Panel related

Air inlet and air


discharge outlet
related

Type

FXKQ25MA

Decoration Panel
Panel Spacer
Long life replacement filter
Air discharge grille
Air discharge blind panel
Flexible duct (with shutter)

FXKQ32MA

KAF372AA80

KAF373AA56

KAF373AA80

KAF373AA160

Filter chamber

KDDF37AA36

KDDF37AA56

KDDF37AA80

KDDF37AA160

Long life replacement filter

KAF371AA36

KAF371AA56

KAF371AA80

KAF371AA160

Long life filter chamber kit

KAF375AA36

KAF375AA56

KAF375AA80

KAF375AA160

White

KTBJ25K36W

KTB25KA56W

KTB25KA80W

KTB25KA160W

Fresh white

KTBJ25K36F

KTBJ25K56F

KTBJ25K80F

KTBJ25K160F

Brown

KTBJ25K36T

KTBJ25K56T

KTBJ25K80T

KTBJ25K160T

KDAJ25K36A

KDAJ25K56A

KDAJ25K71A

KDAJ25K140A

Service panel
Air discharge adaptor

No.

Item

Type

FXHQ32MA

Drain pump kit

KDU50N60VE

Replacement long-life filter (Resin net)

KAF501DA56

L-type piping kit (for upward direction)

KHFP5MA63

FXCQ80M FXCQ125M

No.

BYBC63G-W1
KAFJ532G80
KAFJ533G80
KDDFJ53G80
KAFJ531G80

BYBC125G-W1
KAFJ532G160
KAFJ533G160
KDDFJ53G160
KAFJ531G160

BYK71FJW1
KPBJ52F80W
KAFJ521F80
K-HV9AW
KDBJ52F80W
KFDJ52FA80

KAF372AA160

Ceiling Suspended Type

FXCQ63M

BYK45FJW1
KPBJ52F56W
KAFJ521F56
K-HV7AW
KDBJ52F56W
KFDJ52FA56

FXMQ100P
FXMQ125P
FXMQ140P

KAF372AA56

Item

Type

FXAQ20P

FXAQ25P

Drain pump kit

Floor Standing Type

FXKQ63MA

FXMQ50P
FXMQ63P
FXMQ80P

KAF373AA36

FXKQ40MA

FXMQ40P

KAF372AA36

Item

FXHQ63MA

FXHQ100MA
KDU50N125VE

KAF501DA80

KAF501DA112
KHFP5MA160

FXAQ32P

FXAQ40P

FXAQ50P

FXAQ63P

K-KDU572EVE

Type FXLQ20MA FXLQ25MA FXLQ32MA FXLQ40MA FXLQ50MA FXLQ63MA

Long life replacement filter

KAFJ361K28

KAFJ361K45

KAFJ361K71

Concealed Floor Standing Type


No.
1

No.

FXMQ20P
FXMQ25P
FXMQ32P

90%

No.

Ceiling Mounted Cassette Corner Type

Type

65%

High efficiency filter

Wall Mounted Type

Ceiling Mounted Cassette (Double Flow) Type


No.

Item

BYFQ60B8W1
KDBH44BA60
KDBQ44BA60A
KAFQ441BA60
KDDQ44XA60

Type FXCQ20M

No.

Ceiling Mounted Cassette (Compact Multi Flow) Type


No.

Ceiling Mounted Duct Type

Item

Type FXNQ20MA FXNQ25MA FXNQ32MA FXNQ40MA FXNQ50MA FXNQ63MA

Long life replacement filter

KAFJ361K28

KAFJ361K45

KAFJ361K71

FXUQ100MA

FXUQ125MA

Ceiling Suspended Cassette Type


No.
1
2
3
4
5

Item
Replacement long-life filter
Sealing member of air discharge outlet (*1)
Decoration panel for air discharge
Vertical flap kit
L-shape piping kit

Type

FXUQ71MA
KDBH49FA80
KDBT49FA80
KDGJ49FA80

KAF495FA140

KHFP49MA140

KDBH49FA140
KDBT49FA140
KDGJ49FA140

Note: (*1): This option is necessary for setting up 2-way (opposing directional) airflow when the air conditioner is installed.

Slim Ceiling Mounted Duct Type (700 mm width type)


No.
1

Item

Type

FXDQ20PB

FXDQ25PB

Insulation kit for high humidity

FXDQ32PB

KDT25N32

Slim Ceiling Mounted Duct Type (900/1,100 mm width type)


No.
1

33

Item

Insulation kit for high humidity

Type

FXDQ40NB

FXDQ50NB
KDT25N50

FXDQ63NB
KDT25N63

34

OPTION LIST
OUTDOOR UNITS

CONTROL SYSTEMS

Cooling only
No.
1
1-1
2

Item

System Configuration
RXMQ4P

Type

RXMQ5P
KRC19-26A

Note 3

KJB111A

Central remote controller

Note 2

KHRP26M22H (Max. 4 branch)

2-1

Fixing Box

REFNET Joint

Central drain plug

KKPJ5F180

Fixture for preventing overturning

KPT-60B160

Wire fixture for preventing overturning

K-KYZP15C

KHRP26A22T

Heat pump
1
1-1
2

Item

RXYMQ4P

Type

RXYMQ5P

Cool/Heat Selector

RXYMQ6P

KRC19-26A

Fixing Box

KJB111A

Cool/Heat Selector

KHRP26M22H (Max. 4 branch)

REFNET Joint

Central drain plug

KKPJ5F180

Fixture for preventing overturning

KPT-60B160

Wire fixture for preventing overturning

K-KYZP15C

No.
1

Item

Remote controller

Wireless

DCS301BA61
KJB212AA

3-2

Noise filter (for electromagnetic interface use only)

KEK26-1A

Schedule timer

Interface adaptor for SkyAir-series For SkyAir, FD(Y)M-FA, FDY-KA

Central control adaptor kit

Wiring adaptor for other air-conditioner

Note 2

DST301BA61
FDYB-KA, FVY(P)J-A, FXUQ-MA
For UAT(Y)-K(A),FD-K

DTA102A52
DTA107A55

-NET

DTA109A51

Mounting plate

KRP4A92

Item
intelligent Touch
Controller

Programmed time weekly schedule can be controlled by unified control for up to 64 groups of indoor units
(128 units). Can turn units ON/OFF twice per day.

Adaptors required to connect products other than those of the VRV System to the high-speed DIII-NET
communication system adopted for the VRV System.
* To use any of the above optional controllers, an appropriate adaptor must be installed on the product unit to be
controlled.

Up to 1024 units can be centrally controlled in 64 different groups.


Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of branches: 16)
apply to each adaptor.
Fixing plate for DTA109A51

1-2

FXMQ-L

FXHQ-MA

FXAQ-L

FXLQ-MA FXUQ-MA
FXNQ-MA

Model No.

Hardware intelligent Touch Controller

DCS601C51

Air-Conditioning management system that can be controlled by a compact all-in-one unit.

Option

Hardware DIII-NET plus adaptor

DCS601A52

Additional 64 groups (10 outside units) is possible.

Electrical box with earth terminal (4 blocks)

intelligent Touch
Manager

2-1

KJB411A

Wall embedded switch box.

Basic

Hardware intelligent Touch Manager

DCM601A51

Air-conditioning management system that can be controlled by touch screen.

Option

Hardware iTM plus adaptor

DCM601A52

Additional 64 groups (10 outdoor units) is possible.


Max. 7 iTM plus adaptors can be connected to intelligent Touch Manager.

iTM integrator

DCM601A53

Max. 5 intelligent Touch Managers can be integrated.

iTM power proportional


distribution

DCM002A51

Power consumption of indoor units are calculated based on operation status of the indoor unit and
outside unit power consumption measured by kWh metre.

iTM energy navigator

DCM008A51

Building energy consumption is visualised.


Wasted air-conditioning energy can be found out.

2-2
2-3

BRC1C62

Function

Basic

C/O BRC7F635F BRC7E531W BRC7C67 BRC4C63 BRC4C66 BRC4C66 BRC7EA66 BRC7EA619 BRC4C64 BRC7CA529W

Wired

Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or simultaneously, and
operation and malfunction can be displayed. Can be used in combination with up to 8 controllers.

DTA103A51

Expander Adaptor

1-1

H/P BRC7F634F BRC7E530W BRC7C62 BRC4C61 BRC4C65 BRC4C65 BRC7EA63W BRC7EA618 BRC4C62 BRC7CA528W

Software

Navigation remote controller (Wired remote controller)

BRC1E61

2-4

Wired remote controller with weekly schedule timer

BRC1D61

2-5

Di unit

DEC101A51

8 pairs based on a pair of On/Off input and abnormality input.

Simplified remote controller (Exposed type)

BRC2C51

BRC2C51

2-6

Dio unit

DEC102A51

4 pairs based on a pair of On/Off input and abnormality input.

Remote controller for hotel use (Concealed type)

BRC3A61

BRC3A61

DMS502B51

Adaptor for wiring

KRP1C63

KRP1BA57

KRP1B61

KRP1B61

KRP1B56

KRP1C64 KRP1BA54

KRP1B61

Interface unit to allow communications between VRV and BMS. Operation and monitoring of
air-conditioning systems through BACnet communication.

7-1

Wiring adaptor for electrical appendices (1)

KRP2A62

KRP2A62

KRP2A61

KRP2A61

KRP2A53

KRP2A61

KRP2A62

KRP2A61 KRP2A61

Optional DIII board

DAM411B51

Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET communication ports. Not usable
independently.

7-2

Wiring adaptor for electrical appendices (2)

KRP4AA53

KRP4AA53

KRP4AA51 KRP4AA51

KRP4A54

KRP4AA51

KRP4AA52

KRP4AA51 KRP4AA51

Optional Di board

DAM412B51

Expansion kit, installed on DMS502B51, to provide 16 more wattmeter pulse input points. Not usable
independently.

DMS504B51

Interface unit to allow communications between VRV and BMS. Operation and monitoring of
air-conditioning systems through LONWORKS communication.

DCS302A52

Interface between the central monitoring board and central control units.

Remote sensor (for indoor temperature)

KRCS01-4B

Installation box for adaptor PCB

Note 2,3

10

External control adaptor for outdoor unit

DTA104A62 DTA104A62 DTA104A61 DTA104A61

11

Adaptor for multi tenant

DTA114A61

Note: 1. Installation box


is necessary for each adaptor marked .
2. Up to 2 adaptors can be fixed for each installation box.

35

Note 2

Electrical box with earth terminal (2 blocks)

No.

Operation Control System Optional Accessories


FXKQ-MA FXDQ-PB
FXDQ-NB

Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature setting and
monitoring can be accomplished individually or simultaneously. Connectable up to 2 controllers in one
system.

Building Management System

CONTROL SYSTEMS
FXCQ-M

KJB311AA

3-1

FXZQ-M

DCS302CA61

Electrical box with earth terminal (3 blocks)

Function
Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD panel. ON/OFF,
temperature settings and scheduling can be controlled individually for indoor units.

Notes: 1. Installation box for adaptor must be obtained locally.


2. For FXUQ-MAV1, an interface adaptor (DTA102A52) for the SkyAir series is necessary.
3. For residential use only. Cannot be used with other centralised control equipment.

KHRP26A22T

FXFQ-L

DCS303A51

Unified ON/OFF controller

8-1

KHRP26M33H (Max. 8 branch)

Type

Model No.

Residential central remote controller

KHRP26M33H (Max. 8 branch)

No.

Item

Cool/Heat Selector

REFNET Header

No.

RXMQ6P

KRP1H98

KRCS01-1B
Note 4.6

Note 2,3

KRP1BA101 KRP1B96

KRCS01-4B
Note 4,6

Note 2,3

KRP1BA101 KRP4A96
DTA104A53

3. Only one installation box can be installed for each indoor unit.
4. Up to 2 installation boxes can be installed for each indoor unit.

DTA104A61
DTA114A61

KRP4AA53

Note 2,3

KRP1CA93 KRP4AA93
DTA104A62

5. Installation box
6. Installation box

KRP1BA97

DTA104A61 DTA104A61
DTA114A61

*1 Interface for use in BACnet

3-1
3-2

Communication
line

KRCS01-1B
Note 3

*2 Interface for use in LONWORKS

Contact/analogue
signal

Unification adaptor for


computerised control

Notes: *1. BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
*2. LONWORKS is a trademark of Echelon Corporation registered in the United States and other countries.
*3. Installation box for adaptor must be obtained locally.

is necessary for second adaptor.


is necessary for each adaptor.

36